Plan Review Details - Permit 06100831
Plan Review Stops For Permit 06100831
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2006-11-02 Cont ID  
Sent By dpalmer Date 2006-11-02 Time 07:36 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-02-04 Cont ID  
Sent By dpalmer Date 2007-02-04 Time 19:21 Rev Time 0.00
Received By dpalmer Date 2007-02-04 Time 19:11 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-01-09 Cont ID  
Sent By dpalmer Date 2007-01-09 Time 07:32 Rev Time 0.00
Received By dpalmer Date 2007-01-08 Time 07:46 Sent To PC
Notes
2007-01-09 07:34:30** UNSAT **
  
 1) NOTE: PLEASE SEE THE CODES SECTION REFERENCE ON
 RISER FOR 310.15B6 DOES NOT APPLY FOR FEEDERS WHICH ARE
 120/208V SYSTEMS. PLEASE SEE THE SECTION AS GIVEN IS
 FOR 120/240V ONLY.
  
 2) NOTE: PLEASE KNOW THE VOLTAGE DROP INDICATED FOR THE
 4TH FLOOR UNIT SHOWN AT 4% IS STILL IN QUESTION. PLEASE
 KNOW AS PER THE CONVERSATION WITH THE ENGINEER THE VD
 WAS LOWER AND IT WAS THE UNDERSTANDING OF THIS OFFICE
 THE CORRECTED VD WAS GOING TO BE SHOWN FOR THIS?
 PLEASE SEE FBC 13-413.1.ABC.1.1.
  
 3) NOTE: PLEASE KNOW THE VALUE FOR THE COMPLETE SCOPE
 OF WORK WAS ADJUSTED FOR ALL UNITS EVEN THOUGH THE
 CURRENT CONTRACTOR IS COMPLETING WORK. PLEASE KNOW THAT
 THE PREVIOUS CONTRACTOR DID NOT HAVE PERMITS OR PLANS
 TO RE-PULL FEEDERS TO THE UNITS ALREADY DONE NOR DID
 THE CONTRACTOR PULL IN THE RIGHT SIZE EQUIPMENT
 GROUNDING CONDUCTOR.
 PLEASE KNOW BASED ON THE STOP WORK /RED-TAG CORRECTION
 NOTICE GIVEN AND THE ADDITIONAL VALUE ADDED FOR SCOPE
 THE ADDITIONAL FEE IS THAT OF $5081.70.
 *** PLEASE KNOW THIS IS WRITTENNOTICE TO THE NEW
 CONTRACTOR THAT AS THIS CONTRACTOR IS TAKING OVER THE
 PROJECT FOR THE NEW UNITS, THIS NEW CONTRACTOR WILL
 ALSO BE RESPONSIBLE FOR ALL THE OTHER UNITS WHICH
 FEEDERS WERE PULLED IN WITHOUT PERMITS. IT IS THE
 RECOMMENDATION OF THIS OFFICE TO VERIFY ALL PREVIOUS
 WORK BE REVIEWED FOR CODE COMPLIANCE AND INSTALLATION
 OF SAID CONDUCTORS WHICH MAY HAVE BEEN DAMAGED IN THE
 INSTALLATION PROCESS.
  
 4) NOTE: PLEASE VERIFY LOADS SHOWN ON PANELS E, F& G
 SPECIFICALLY TO THE LOADS SHOWN ON THE METER CENTERS,
 THEN PLEASE VERIFY LOAD ON METER CENTERS 3 AND 4.
 PLEASE SEE LOAD AFTER ALL DE-RATING IS BEING SHOWN IS A
 MAXIMUM OF500AMPS WHICH THE RATING OF THE MAIN FUSES
 FEEDING METER CENTER. THE METER CENTER IS RATED AT 600
 AMPS; HOWEVER THE MAIN OVER CURRENT PROTECTION IS THAT
 OF 500AMPS WHICH LEAVES NO ROOM FOR EXPANSION OF FUTURE
 LOADS OF ANY KIND.
 90.8, 220, 240, ETC.
 FBC 106.1.2 ADMIN SECITON FOR ADDITIONAL INFORMATION.
  
 5) NOTE: PLEASE KNOW AS THIS WAS ONLY UNDER PLAN REVIEW
 BEFORE THE DATE OF DECEMBER 8TH, 2006, THE CODE
 SECTIONS ON PLANS ALL NEED TO BE REVISED TO SECTIONS
 OUT OF THE 2005 NEC NFPA-70. PLEASE KNOW AS OF DATE
 GIVEN, THE STATE OF FLORIDA ADOPTED THE NEW 2005
 EDITION AND SINCE THIS SCOPE OF WORK WAS NOT APPLIED
 FOR PERMIT UNTIL AFTER THAT DATE THE ITEMS AS NOTED AND
 ALL DESIGNS ARE REQUIRED TO BE UNDER THE NEW CODE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-11-30 Cont ID  
Sent By dpalmer Date 2006-11-30 Time 19:28 Rev Time 0.00
Received By dpalmer Date 2006-11-30 Time 17:41 Sent To PC
Notes
2006-11-30 19:28:49****** UNSAT2ND REVIEW ******
  
 PLEASE SEE SOME NOTES FROM THE PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
  
  
  
 ** PLEASE KNOW, PLANS HAVE ONLY BEEN SUBMITTED FOR
 "PLAN REVIEW" ONLY AND HAVE NOT BEEN SUBMITTED FOR
 PERMIT AT THIS TIME.
  
 1) NOTE:NO, SAME NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW WHEN FINAL APPLICATION IS MADE FOR
 INSTALLATION AND WIRING FOR FPC, THIS CAN NOT BE DONE
 BY A GC, CGC ETC. THIS MUST BE AN ELECTRICAL CONTRACTOR
 WHO APPLIES.
  
 2) NOTE: NO, SAME NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS FOR THE
 NEW METER CENTERS.
 110.3,90.7
 PLEASE SEE OTHER COMMENTS BELOW FOR METER CENTERS.
  
 3) NOTE: OK.
  
 4) NOTE: OK.
  
 5) NOTE: OK, HOWEVER SEE NEW NOTES.
  
 6) NOTE:NO, NOT CLEAR WHAT THIS IS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE RISER SHOWS BUS-DUCT UNDERGROUND TO FPL?
 PLEASE VERIFY THIS. IT IS BEING SHOWN AS EXISTING;
 HOWEVER THIS IS IN QUESTION AT THIS TIME.
 110.3, 90.7.
 IS THIS PERHAPS EITHER A BUS STAB OR DUCT BANK
 EXISTING?
  
 7) NOTE: NO, STILL SHOWN. AS THIS IS BEING INDICATED
 THE MAIN 1 OF 6, PLEASE INDICATE MAIN, HOWEVER NOT IN
 SCOPE ETC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE REMOVED FIRE PUMP AND ASSOCIATED EQUIPMENT FROM
 RISER WHICH IS NOT IN THIS SCOPE OF WORK.
  
 8) NOTE: OK.
  
 9) NOTE:NO, SAME NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SPECIFY THE CONDUIT TYPE ON ALL RUNS. PLEASE SEE
 SOME CONDUIT FILLS ON NEW PULLS SEEM VERIFY CLOSE,
 PLEASE VERIFY.
 PLEASE SEE TABLES IN CHAPTER 9.
  
 10) NOTE:VOLTAGE DROP PROVIDED, HOWEVER FBC
 13-413.1.ABC.1.1. PLEASE SEE FEEDER WHICH INDICATES 4 %
 ETC AND OTHERS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE VOLTAGE DROP FOR FEEDERS TO THE METER
 CENTERS, AS THE DISTANCES AS SHOWN FOR 4/0'S ETC ARE
 OVER 200FT.
  
 11) NOTE:OK, HOWEVER SEE NOTE ABOVE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE ALSO PROVIDE A WORST CASE VD ON APT/CONDO
 FEEDER(S).
  
 12) NOTE: OK.
  
 13) NOTE: OK.
  
 14) NOTE: OK
  
 15) NOTE:NO? UNCLEAR AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE VALUE ON SCOPE OF WORK WHEN APPLICATION IS
 MADE MAY BE ADJUSTED. PLEASE VERIFY AS THE VALUE SEEMS
 LOW. PLEASE KNOW VALUE PANEL FOR EACH UNIT CANE BE
 SUBTRACTED AS THESE WILL BE SEPARATE, HOWEVER ALL NEW
 FEEDERS FOR UNITS, FEEDERS FOR METER CENTERS AND NEW
 METER CENTERS SHALL BE INCLUDED. VALUE SHALL INCLUDE
 ALL LABOR AND MATERIALS EVEN IF ANY EQUIPMENT IS OWNER
 SUPPLIED.
 FBC 108.3.
  
 16) NOTE: OK.
  
 *** NEW NOTE **
  
 1) NOTE: PLEASE SEE FIRE PUMP MAIN/CONTROLLER
 INFORMATION AS SHOWN ON THIS RISER DOES NOT CORRELATE
 WITH THE PUMP CONTROLLER WHICH HAS YET TO BE APPLIED
 FOR.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-02 Cont ID  
Sent By dpalmer Date 2006-11-02 Time 08:20 Rev Time 0.00
Received By dpalmer Date 2006-11-02 Time 07:36 Sent To PC
Notes
2006-11-02 08:20:40***** UNSAT *********
  
  
 ** PLEASE KNOW, PLANS HAVE ONLY BEEN SUBMITTED FOR
 "PLAN REVIEW" ONLY AND HAVE NOT BEEN SUBMITTED FOR
 PERMIT AT THIS TIME.
  
 1) NOTE: PLEASE KNOW WHEN FINAL APPLICATION IS MADE FOR
 INSTALLATION AND WIRING FOR FPC, THIS CAN NOT BE DONE
 BY A GC, CGC ETC. THIS MUST BE AN ELECTRICAL CONTRACTOR
 WHO APPLIES.
  
 2) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS
 FOR THE NEW METER CENTERS.
 110.3,90.7
 PLEASE SEE OTHER COMMENTSBELOW FOR METER CENTERS.
  
 3) NOTE: PLEASE CORRELATE METER CENTER DESIGNATIONS.
 PLEASE SEE METER BANK BOX #4 IS FOR METER CENTER #3,
 AND MC #3 SHOWS # 4 BOX.
 THIS WAS REDLINED ON PLANS.
  
 4) NOTE: PLEASE PROVIDE ACTUAL MC DESIGNATION AND
 LABELING IN THE MAIN SWITCH GEAR EQUIPMENT. PLEASE ALSO
 CLARIFY THE OCP AS SHOWN. SOME ARE SHOWN DIFFERENTLY AS
 500A, RATED WITH 600A FUSES, AND OTHERS 600A RATED WITH
 THE 450A OCP. PLEASE CORRELATE AND COORDINATE THESE.
  
 5) NOTE: PLEASE CLARIFY WHERE MAIN 1 IS? 2OF 6 THROUGH
 6OF 6 IS SHOWN , HOWEVER COULD NOT LOCATED 1?
 230.70,230.72
  
 6) NOTE: PLEASE SEE RISER SHOWS BUS-DUCT UNDERGROUND TO
 FPL? PLEASE VERIFY THIS. IT IS BEING SHOWN AS EXISTING
 , HOWEVER THIS IS IN QUESTION AT THIS TIME.
 110.3, 90.7.
 IS THIS PERHAPS EITHER A BUS STAB OR DUCT BANK
 EXISTING?
  
 7) NOTE: PLEASE REMOVED FIRE PUMP AND ASSOCIATED
 EQUIPMENT FROM RISER WHICH IS NOT IN THIS SCOPE OF
 WORK.
  
 8) NOTE: PLEASE SEE THE " EQUIPMENT GROUNDING
 CONDUCTORS" FROM THEN METER CENTER MAINS TO THE UNITS
 ARE NOT LARGE ENOUGH PER 250.122. PLEASE SEE MIN SIZE
 SHALL BE #6.
  
 9) NOTE: PLEASE SPECIFY THE CONDUIT TYPE ON ALL RUNS.
 PLEASE SEE SOME CONDUIT FILLS ON NEW PULLS SEEM VERIFY
 CLOSE, PLEASE VERIFY.
 PLEASE SEE TABLES IN CHAPTER 9.
  
 10) NOTE: PLEASE PROVIDE VOLTAGE DROP FOR FEEDERS TO
 THE METER CENTERS, AS THE DISTANCES AS SHOWN FOR 4/0'S
 ETC ARE OVER 200FT.
  
 11) NOTE: PLEASE ALSO PROVIDE A WORST CASE VD ON
 APT/CONDO FEEDER(S).
  
 12) NOTE: PLEASE KNOW THAT EACH PANEL IN EACH UNIT WILL
 BE REQUIRED TO BE UNDER A SEPARATE PERMIT FOR EACH
 UNIT, AS EACH UNIT IS INDIVIDUALLY OWNED. THIS TYPICAL
 PANEL DETAIL CAN BE ON 8/12 BY 11'S, HOWEVER TWO
 SIGNED, DATED AND SEALED COPIES FOR EACH APPLICATION
 WILL BE REQUIRED FOR PANEL CHANGE OUTS.
 106.1.2, 106.1.3 ETC
  
 13) NOTE: PLEASE CLARIFY LOAD CALCULATIONS ON MC WHICH
 INDICATE 450A OCP AND LOAD IS SHOWN AS 448A'S. PLEASE
 ONLY VERIFY.
 215.5, 220.
  
 14) NOTE: PLEASE BE SURE THE 2002 NFPA-70( NEC ) IS
 STATED ON PLANS.
 106.1.2 FBC ADMIN SECT.
  
 15) NOTE: PLEASE SEE VALUE ON SCOPE OF WORK WHEN
 APPLICATION IS MADE MAY BE ADJUSTED. PLEASE VERIFY AS
 THE VALUE SEEMS LOW. PLEASE KNOW VALUE PANEL FOR EACH
 UNIT CANE BE SUBTRACTED AS THESE WILL BE SEPARATE,
 HOWEVER ALL NEW FEEDERS FOR UNITS, FEEDERS FOR METER
 CENTERS AND NEW METER CENTERS SHALL BE INCLUDED. VALUE
 SHALL INCLUDE ALL LABOR AND MATERIALS EVEN IF ANY
 EQUIPMENT IS OWNER SUPPLIED.
 FBC 108.3.
  
 16) NOTE: PLEASE INDICATE AIC RATINGS FOR ALL MAINS ,
 EQUIPMENT AND PANELS. PLEASE BE SURE TO INDICATE THE
 SELECTIVE COORDINATION AS REQUIRED.
 110.9, 240.12
 FBC106.1.2 ADMIN SECT.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2006-11-02 Cont ID  
Sent By dpalmer Date 2006-11-02 Time 07:36 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2006-11-02 Cont ID  
Sent By dpalmer Date 2006-11-02 Time 07:36 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-02-02 Cont ID  
Sent By adarroug Date 2007-02-02 Time 16:45 Rev Time 0.00
Received By adarroug Date 2007-02-02 Time 16:45 Sent To E
Notes
2007-02-02 16:45:28TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-05 Cont ID  
Sent By adarroug Date 2007-01-05 Time 11:00 Rev Time 0.00
Received By adarroug Date 2007-01-05 Time 11:00 Sent To E
Notes
2007-01-05 11:01:05TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-16 Cont ID  
Sent By adarroug Date 2006-11-16 Time 10:36 Rev Time 0.00
Received By adarroug Date 2006-11-16 Time 10:36 Sent To E
Notes
2006-11-16 10:36:32TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-02 Cont ID  
Sent By   Date 2006-11-02 Time   Rev Time 0.00
Received By adarroug Date 2006-10-23 Time 15:06 Sent To  
Notes
2006-10-23 15:06:44TO "DPALMER" DESK/PER "RBROWN"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-11-02 Cont ID  
Sent By dpalmer Date 2006-11-02 Time 07:36 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-11-02 Cont ID  
Sent By dpalmer Date 2006-11-02 Time 07:37 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2006-11-02 Cont ID  
Sent By dpalmer Date 2006-11-02 Time 07:37 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***