2006-11-02 08:20:40 | ***** UNSAT ********* |
| |
| |
| ** PLEASE KNOW, PLANS HAVE ONLY BEEN SUBMITTED FOR |
| "PLAN REVIEW" ONLY AND HAVE NOT BEEN SUBMITTED FOR |
| PERMIT AT THIS TIME. |
| |
| 1) NOTE: PLEASE KNOW WHEN FINAL APPLICATION IS MADE FOR |
| INSTALLATION AND WIRING FOR FPC, THIS CAN NOT BE DONE |
| BY A GC, CGC ETC. THIS MUST BE AN ELECTRICAL CONTRACTOR |
| WHO APPLIES. |
| |
| 2) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS |
| FOR THE NEW METER CENTERS. |
| 110.3,90.7 |
| PLEASE SEE OTHER COMMENTSBELOW FOR METER CENTERS. |
| |
| 3) NOTE: PLEASE CORRELATE METER CENTER DESIGNATIONS. |
| PLEASE SEE METER BANK BOX #4 IS FOR METER CENTER #3, |
| AND MC #3 SHOWS # 4 BOX. |
| THIS WAS REDLINED ON PLANS. |
| |
| 4) NOTE: PLEASE PROVIDE ACTUAL MC DESIGNATION AND |
| LABELING IN THE MAIN SWITCH GEAR EQUIPMENT. PLEASE ALSO |
| CLARIFY THE OCP AS SHOWN. SOME ARE SHOWN DIFFERENTLY AS |
| 500A, RATED WITH 600A FUSES, AND OTHERS 600A RATED WITH |
| THE 450A OCP. PLEASE CORRELATE AND COORDINATE THESE. |
| |
| 5) NOTE: PLEASE CLARIFY WHERE MAIN 1 IS? 2OF 6 THROUGH |
| 6OF 6 IS SHOWN , HOWEVER COULD NOT LOCATED 1? |
| 230.70,230.72 |
| |
| 6) NOTE: PLEASE SEE RISER SHOWS BUS-DUCT UNDERGROUND TO |
| FPL? PLEASE VERIFY THIS. IT IS BEING SHOWN AS EXISTING |
| , HOWEVER THIS IS IN QUESTION AT THIS TIME. |
| 110.3, 90.7. |
| IS THIS PERHAPS EITHER A BUS STAB OR DUCT BANK |
| EXISTING? |
| |
| 7) NOTE: PLEASE REMOVED FIRE PUMP AND ASSOCIATED |
| EQUIPMENT FROM RISER WHICH IS NOT IN THIS SCOPE OF |
| WORK. |
| |
| 8) NOTE: PLEASE SEE THE " EQUIPMENT GROUNDING |
| CONDUCTORS" FROM THEN METER CENTER MAINS TO THE UNITS |
| ARE NOT LARGE ENOUGH PER 250.122. PLEASE SEE MIN SIZE |
| SHALL BE #6. |
| |
| 9) NOTE: PLEASE SPECIFY THE CONDUIT TYPE ON ALL RUNS. |
| PLEASE SEE SOME CONDUIT FILLS ON NEW PULLS SEEM VERIFY |
| CLOSE, PLEASE VERIFY. |
| PLEASE SEE TABLES IN CHAPTER 9. |
| |
| 10) NOTE: PLEASE PROVIDE VOLTAGE DROP FOR FEEDERS TO |
| THE METER CENTERS, AS THE DISTANCES AS SHOWN FOR 4/0'S |
| ETC ARE OVER 200FT. |
| |
| 11) NOTE: PLEASE ALSO PROVIDE A WORST CASE VD ON |
| APT/CONDO FEEDER(S). |
| |
| 12) NOTE: PLEASE KNOW THAT EACH PANEL IN EACH UNIT WILL |
| BE REQUIRED TO BE UNDER A SEPARATE PERMIT FOR EACH |
| UNIT, AS EACH UNIT IS INDIVIDUALLY OWNED. THIS TYPICAL |
| PANEL DETAIL CAN BE ON 8/12 BY 11'S, HOWEVER TWO |
| SIGNED, DATED AND SEALED COPIES FOR EACH APPLICATION |
| WILL BE REQUIRED FOR PANEL CHANGE OUTS. |
| 106.1.2, 106.1.3 ETC |
| |
| 13) NOTE: PLEASE CLARIFY LOAD CALCULATIONS ON MC WHICH |
| INDICATE 450A OCP AND LOAD IS SHOWN AS 448A'S. PLEASE |
| ONLY VERIFY. |
| 215.5, 220. |
| |
| 14) NOTE: PLEASE BE SURE THE 2002 NFPA-70( NEC ) IS |
| STATED ON PLANS. |
| 106.1.2 FBC ADMIN SECT. |
| |
| 15) NOTE: PLEASE SEE VALUE ON SCOPE OF WORK WHEN |
| APPLICATION IS MADE MAY BE ADJUSTED. PLEASE VERIFY AS |
| THE VALUE SEEMS LOW. PLEASE KNOW VALUE PANEL FOR EACH |
| UNIT CANE BE SUBTRACTED AS THESE WILL BE SEPARATE, |
| HOWEVER ALL NEW FEEDERS FOR UNITS, FEEDERS FOR METER |
| CENTERS AND NEW METER CENTERS SHALL BE INCLUDED. VALUE |
| SHALL INCLUDE ALL LABOR AND MATERIALS EVEN IF ANY |
| EQUIPMENT IS OWNER SUPPLIED. |
| FBC 108.3. |
| |
| 16) NOTE: PLEASE INDICATE AIC RATINGS FOR ALL MAINS , |
| EQUIPMENT AND PANELS. PLEASE BE SURE TO INDICATE THE |
| SELECTIVE COORDINATION AS REQUIRED. |
| 110.9, 240.12 |
| FBC106.1.2 ADMIN SECT. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |