Plan Review Details - Permit 06100821
Plan Review Stops For Permit 06100821
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-10-26 Cont ID  
Sent By lursu Date 2006-10-26 Time 10:55 Rev Time 0.00
Received By lursu Date 2006-10-26 Time 10:55 Sent To  
Notes
2006-10-26 10:56:16ATTACH PERMIT TO EXT # 0002 FOR THE PARKING LOT

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-06-07 Cont ID  
Sent By jgomez Date 2007-06-07 Time 15:38 Rev Time 0.00
Received By jgomez Date 2007-06-07 Time 15:38 Sent To PC
Notes
2007-06-07 15:40:48BUILDING REVIEW 4TH CHECKLIST:
  
 1- INFORMATION SUBMITTED NOW IS MISSING THE
 MANUFACTURER'S COMPLETE SPECS FOR LIGHT POST TO BE
 INSTALLED.DESIGNER OF RECORD TO REVIEW AND APPROVE IN
 WRITING SPECS (NOT SIGNING AND SEALING) AS REQUIRED BY
 SEC. 106.3.3CITY AMENDMENTS TO FBC 2004 AND MAKE SURE
 THE POST IS DESIGNED TO MEET CORRESPONDING WIND LOADS
 TO AVOID FUTURE DENIALS.
  
 2- THERE IS NEWENGINEER ON BOARD AND THE FOLLOWING
 COMMENTS NEED TO BE ADDRESSED:
 A) DESIGN CRITERIA USED FOR WIND LOAD ANALYSIS WAS
 BASED ON ASCE 7-04.ASCE EDITION ADOPTED BY FBC 2004
 IS ASCE 7-02. NEED TO REVISE AS REQUIRED.
 B)DRAWING FOR NEW FOOTING ARE NOT LEGIBLE.
 *** THE FOLLOWING INFORMATION IS REQUIRED BY CHAPTER
 471 FLORIDA STATUTE AND SEC. 61G15-23.002 OF FLOIRDA
 ADMINISTRATIVE CODE.
 C) ALL SHEETS NEED TO BE SIGNED, SEALED AND DATED BY
 THE ENGINEER. ALL SHEETS MUST HAVE ORIGINAL SEAL AND
 SIGNATURE.
 D) ALL SHEETS NEED TO HAVE THE ENGINEER' LICENSE
 NUMBER.
  
 ***NOTE:
 ONE SET OF DRAWINGS WAS RETAINED IN THIS OFFICE FOR
 REFERENCE ON FUTURE SUBMITTALS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-01-29 Cont ID  
Sent By jgomez Date 2007-01-29 Time 11:45 Rev Time 0.50
Received By jgomez Date 2007-01-29 Time 11:45 Sent To  
Notes
2007-01-29 12:43:16BUILDING REVIEW THIRD CHECKLIST:
  
 1-CLARIFY WHAT 'S THE RELATIONSHIP BETWEEN VALMONT
 STRUCTURES SPECIFICATIONS (PAGE 7 OF ENGINEERED PACKAGE
 SUBMITTED) AND ENGINEERED DRAWING E-1.SEE SIZE OF
 ANCHORS ETC.CLARIFY/REVISE AS REQUIRED.
  
 2-VALMONT STRUCTURES SPECIFICATIONS PAGE 7:
 EFFECTIVE PROJECTED AREA (EPA)DOESN'T WORK FOR
 140MPH.SEE DIMENSIONAL AND LOAD DATA.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-12-15 Cont ID  
Sent By jgomez Date 2006-12-15 Time 10:57 Rev Time 0.50
Received By jgomez Date 2006-12-15 Time 07:44 Sent To  
Notes
2006-12-15 11:09:40BUILDING REVIEW 2ND CHECKLIST:
  
 1- ENGINEER NEEDS TO USE THE NEW SEAL THAT READS
 "LICENSE" INSTEAD OF "CERTIFICATE".ENGINEER USED
 CORRECT SEAL ON FIRST SUBMITTALBUT, IS USING THE OLD
 SEAL IN THIS RE-SUBMITTAL. RULE 61G15-23.001 OF FLORIDA
 ADMINISTRATIVE CODE.
  
 2- PROVIDE MANUFACTURER'S COMPLETE SPECS FOR LIGHT POST
 TO BE INSTALLAED. DESIGNER OF RECORD TO REVIEW AND
 APPROVE SPECS PRIOR TO SUBMITTAL TO THIS OFFICE TO
 VERIFY COMPLIANCE WITH HIS DESIGN. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-06 Cont ID  
Sent By jgomez Date 2006-11-06 Time 16:45 Rev Time 0.50
Received By jgomez Date 2006-11-06 Time 16:37 Sent To  
Notes
2006-11-06 16:44:57BUILDING REVIEW CHECKLIST:
  
 1- ENGINEER CALCULATIONS TO SPECIFY DESIGN CRITERIA,
 CODE IS USED ANDWHAT ARE THE WIND LOADS?. WE ARE IN
 A 140MPH ZONE.
 SECTION 1609 FBC 2004.
  
 2- ENGINEER TO PROVIDE ALL HIS INFORMATION IN ALL
 SHEETS AS REQUIRED BY SEC. 61G15-23.002 OF FLORIDA
 ADMINISTRATIVE CODE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-06-01 Cont ID  
Sent By btrobaug Date 2007-06-01 Time 14:14 Rev Time 0.33
Received By btrobaug Date 2007-06-01 Time 14:14 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-01-29 Cont ID  
Sent By btrobaug Date 2007-01-29 Time 07:53 Rev Time 0.33
Received By btrobaug Date 2007-01-29 Time 07:45 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-10-31 Cont ID  
Sent By btrobaug Date 2006-10-31 Time 14:26 Rev Time 0.50
Received By btrobaug Date 2006-10-31 Time 14:01 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-05-22 Cont ID  
Sent By adarroug Date 2007-05-22 Time 13:17 Rev Time 0.00
Received By adarroug Date 2007-05-22 Time 13:17 Sent To E
Notes
2007-05-22 13:17:56TO "BTROBAUG" DESK/RESUB--NEW SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-23 Cont ID  
Sent By adarroug Date 2007-01-23 Time 10:15 Rev Time 0.00
Received By adarroug Date 2007-01-23 Time 10:15 Sent To E
Notes
2007-01-23 10:16:18TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-14 Cont ID  
Sent By adarroug Date 2006-12-14 Time 14:44 Rev Time 0.00
Received By adarroug Date 2006-12-14 Time 14:44 Sent To B
Notes
2006-12-14 14:45:19TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-06 Cont ID  
Sent By jgomez Date 2006-11-06 Time 16:47 Rev Time 0.00
Received By jgomez Date 2006-10-25 Time 13:27 Sent To  
Notes
2006-10-25 13:27:51TO "E" BOX