2006-10-24 14:30:29 | ******** UNSAT ********** |
| |
| 1) NOTE: PLEASE PROVIDE A PANEL SCHEDULE WHICH |
| INDICATES ALL OF THE REQUIRED MINIMUM CIRCUITS. PLEASE |
| BE SPECIFIC FOR CIRCUITS TO ALL AREAS AND ROOMS. PLEASE |
| SEE FOR INSTANCE ONLY ONE CIRCUIT IS BEING SHOWN IN THE |
| LOAD CALCULATIONS FOR THE BATH(S)RMS). |
| PLEASE INDICATE FOLLOWING : IE: BED RM #2 LTS, MASTER |
| BEDRM RECETPS, KITCHEN LTS, ETC ETC. |
| PLEASE INDICATE ALL CONDUCTOR SIZES AND CORRELATE WITH |
| OCP DEVICES. |
| 240.4,408.4, 310.16 |
| |
| 2) NOTE: PLEASE SEE NOTES ON PLANS STILL MENTIONS AFCI |
| PROTECTION ONLY FOR RECEPTS. WE ARE UNDER THE 2002 NEC. |
| 210.12B |
| PLEASE BE SURE TO LIST ALL AS REQUIRED PER CODE ON THE |
| SAME PANEL SCHEDULE WHICH IS REQUIRED PER NOTE #1. |
| |
| 3) NOTE: PLEASE SEE 210.8A6 FOR ALL RECEPTS SERVING |
| KITCHEN COUNTER SPACE. |
| |
| 4) NOTE: PLEASE SEE 210.52C3/210.8A6 FOR MISSING |
| RECEPT. |
| |
| 5) NOTE: PLEASE SEE NOTES ON PLANS WHICH MENTIONS FUSED |
| DISCONNECT FOR SERVICE, YET SERVICE DOES NOT INDICATE |
| THIS . PLEASE CORRELATE. |
| 230.70, 230.70. |
| PLEASE SEE PLANS ARE MISSING THE LOCATION OF THE |
| SERVICE AND PANEL. 230.70,240.24 |
| CAN NOT BE VERIFIED FOR CODE COMPLIANCE AT THIS TIME. |
| |
| 6) NOTE: PLEASE STATE THE FOLLOWING RELEVANT CODES ON |
| PLANS FOR THE DESIGN AT THIS TIME. 2002 NFPA-70, 2002 |
| NFPA-72. |
| |
| 7) NOTE: PLEASE INDICATE THE REQUIRED DISCONNECT FOR |
| THE WATER HEATER 422.31. |
| |
| 8) NOTE: PLEASE SEE FS 713.13(2) AS THE NOTICE OF |
| COMMENCMENT WHICH WAS SUBMITTED WITH PERMITTED |
| APPLICATION WAS ALREADY EXPIRED WHEN IT WAS SUBMITTED. |
| PLEASE SEE SECTION WHICH STATES WORK SHALL COMMENCE |
| WIHTIN 90DAYS OF RECORDING SUCH NOC OR THE NOC SHALL |
| BECOME VOID AND IS NO LONGER VALID. |
| THE RE-RECORDED NOC IS ONLY REQUIRED AT THE TIME OF |
| PICKING UP PERMIT ONCE ISSUED. |
| |
| |
| |
| *** NOTE: PLEASE SEE FLORIDA STATUTES 481.221(6). |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |