Plan Review Details - Permit 06100734
Plan Review Stops For Permit 06100734
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-01-30 Cont ID  
Sent By mjacobs Date 2008-01-30 Time 16:43 Rev Time 0.00
Received By mjacobs Date 2008-01-30 Time 16:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-12-28 Cont ID  
Sent By mjacobs Date 2007-12-28 Time 13:09 Rev Time 0.00
Received By mjacobs Date 2007-12-28 Time 07:50 Sent To  
Notes
2007-12-28 13:09:29 
 BUILDING PLAN REVIEW
 PERMIT: 06100734
 ADD: 3111 S. DIXIE HWY #101
 CONT: LEIGHTON MC GINN CO.
 TEL: (561)863-4455
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: REV. 12/28/07
 ACTION: DENIED
  
 1)) 106.3.3* PRODUCT APPROVALS- 2004 THOSE PRODUCTS
 THAT ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. SUBMIT THE
 PRODUCT APPROVAL FOR THE NEW EXTERIOR DOOR #175 AND THE
 GLAZED AREA WHERE DOOR #167C WAS REMOVED.NOTE: ALL
 GLAZED OPENINGS LOCATED WITHIN 30 FEET OF GRADE SHALL
 MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. SHOW
 COMPLIANCE.
  
 2)SHEET A-3.0 IS MISSING THE DETAIL FOR WALL TYPE
 WT-1. SUBMIT ALL WALL TYPES FOR THE PROJECT ON THE
 DETAIL SHEET.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-03-30 Cont ID  
Sent By mjacobs Date 2007-03-30 Time 16:32 Rev Time 0.00
Received By mjacobs Date 2007-03-30 Time 16:13 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-03-29 Cont ID  
Sent By mjacobs Date 2007-03-29 Time 10:11 Rev Time 0.00
Received By mjacobs Date 2007-03-29 Time 07:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-09 Cont ID  
Sent By mjacobs Date 2007-03-09 Time 11:28 Rev Time 0.00
Received By mjacobs Date 2007-03-09 Time 07:01 Sent To  
Notes
2007-03-09 11:28:44BUILDING PLAN REVIEW
 PERMIT:06100734
 ADD: 3111 S. DIXIE HWY
 CONT: LEIGHTON MCGINN CO.
 TEL: (561)863-4455
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)11-4.13.6MINIMUM MANEUVERING CLEARANCES AT DOORS
 THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS
 SHOWN IN FIGURE 25 (18"MIN). THE FLOOR OR GROUND AREA
 WITHIN THE REQUIRED CLEARANCES SHALL BE LEVEL AND
 CLAEAR. SEE SHEET A-1.0.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-11-02 Cont ID  
Sent By alange Date 2006-11-02 Time 13:14 Rev Time 0.00
Received By alange Date 2006-11-02 Time 13:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-01-29 Cont ID  
Sent By dpalmer Date 2008-01-29 Time 12:34 Rev Time 0.00
Received By dpalmer Date 2008-01-29 Time 12:34 Sent To  
Notes
2008-01-29 12:35:09ELEC OK, STAMPED SHEETS.
 NEED TO RETAIN ONE COPY OF ELECTRICAL SHEETS ONCE FIRE
 REVIEW IS DONE AND OK.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-12-27 Cont ID  
Sent By dpalmer Date 2007-12-27 Time 08:08 Rev Time 0.00
Received By dpalmer Date 2007-12-26 Time 17:02 Sent To  
Notes
2007-12-27 08:11:20*** DENIED REVISION **
  
 1) NOTE: PLEASE SEE NOTES AND PROVISO GIVEN ON 3/4/07
 AND 3/26/07 AS PLANS WERE REDLINED AND NEEDED TO BE
 REVISED TO SHOW MINIMUM CODE COMPLAINCE.
 PLEASE SEE NOTES FROM BOTH OF THOSE REVIEWS ARE
 ATTACHED.
 PLEASE KNOW THAT UNTIL PROVISO NOTES ARE ADDRESSED NO
 FURTHER ELECTRICAL REVISIONS WILL BE
 RED-LINED/PROVISO.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-03-26 Cont ID  
Sent By dpalmer Date 2007-03-26 Time 13:12 Rev Time 0.00
Received By dpalmer Date 2007-03-26 Time 13:12 Sent To  
Notes
2007-03-26 13:13:22PLANS NOT REVISED, PROVISO FROM 3/4/07 IS STILL IN
 EFFECT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-03-04 Cont ID  
Sent By dpalmer Date 2007-03-04 Time 10:33 Rev Time 0.00
Received By dpalmer Date 2007-03-04 Time 09:25 Sent To  
Notes
2007-03-04 10:34:08***PROVISO/REVISON***
  
 1) NOTE: PLEASE SEE THE *EQUIPMENT GROUNDING
 CONDUCTORS* SHOWN ON THE LINE SIDE OF THE METER AND
 MAINS ARE NOT TO BE INSTALLED AS THIS WOULD PARALLEL
 THE NEUTRAL FOR OBJECTIONABLE CURRENTS.
 PLEASE SEE 250.6 AND 250.24B AS *EQUIPMENT GROUNDING
 CONDUCTORS* ARE INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 2) NOTE: PLEASE BE SURE TO UPDATE PANEL SCHEDULES AND
 PLANS TO SHOW ALL NEW CIRCUITING TO THE NEW PANELS AND
 ALL CIRCUITS IN PANELS TO EACH OF THESE
 LOCATIONS/ROOMS.
 PLEASE SEE SECTION OF COMMENTARY WHICH REQUIRES ALL
 CIRCUITS TO BE SPECIFIC TO AREAS AND ROOMS IN WHICH
 THEY FEED. THE FOLLOWING IS TAKEN DIRECTLY FORM THAT
 COMMENTARY.
 ** CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW AND
 STAMPING.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-30 Cont ID  
Sent By dpalmer Date 2006-10-30 Time 07:56 Rev Time 0.00
Received By dpalmer Date 2006-10-30 Time 07:09 Sent To I
Notes
2006-10-30 07:50:52******** UNSAT ************
  
 1) NOTE: PLEASE SEE COVER SHEET WHICH REFLECT ADDRESS
 OF JOB AT 4100 OKEECHOBEE BLVD AS WELL AS 3111 S
 DIXIE.
  
 PLEASE ALSO SEE THE JURISDICTION IS NOT IN PALM BEACH
 COUNTY. JOB-SITE LOCATION IN THE CITY OF WEST PALM
 BEACH.
  
 2) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON
 TITLE BLOCKS FOR ARCHITECTURAL FIRM. PLEASE SEE FAC
 61G1-16.004 AND FS 481.219.
 MISSING CERTIFICATE OF AUTHORIZATION NUMBER/ FIRM
 LICENSE NUMBER.
 THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S).
  
 3) NOTE: PLEASE SEE THE FOLLOWING MINIMUM CODES ARE
 REQUIRED ON PLANS. 2002 NFPA-70, 2002 NFPA-72, 2003
 NFPA-101 .
 **AS STATED ON PLANS, THE "LATEST EDITION " WHICH IS
 AVAIABLE IS NOT YET ADOPTED BY THE STATE> (NEC).
  
 4) NOTE; PLEASE SEE AREAS WHICH ARE SHOWN AS COMMON
 AREA CORRIDORS YET SHOW ELECTRICAL FOR RECEPT AND HVAC
 BEING FED FROM A TENANT SPACE. PLEASE KNOW, NO COMMON
 AREAS MAY BE FED FROM FROM AN TENANT OCCUPANCY. 210.25,
 90.4.
  
 5) NOTE: PLEASE SEE PANEL SCHEDULE FOR "H2" SHOWS OTHER
 ELECTRICAL HOWEVER COULD NOT LOCATE WHAT OR WHERE THESE
 ITEMS ARE??
 PLEASE ALSO SEE LOADS ON THIS PANEL IS SHOWN AS XXXXX
 (BLANK), PLEASE COMPLETE.
 220, 215.5,
 FBC 106.1.2 ADMIN SECT.
  
 6) NOTE: PLEASE SEE RISER AND EXPLAIN HOW FEEDERS FROM
 FPL ARE ROUTED TO THE GUTTER. RISER SEEMS TO SHOW THE
 CT/METER ON THE LOAD SIDE OF THE MDP???
 PLEASE CLARIFY AND REVISE RISER. AS SHOWN DOES NOT
 CORRELATE WITH MIN FPL SERVICE STANDARDS OR NEC. 230.
  
 7) NOTE: PLEASE SEE PANEL INDICATE CIRCUITING FOR NEW
 ROOMS.
 PLEASE SEE PANEL "G" IS BEING SHOWN BEING SHOWN AS 125A
 RATED, YET RISER SHOWS A 150A MAIN DISCONNECT FEEDING
 SAID PANEL.
 PLEASE SEE 240, 230 ETC
  
 8) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR NEW
 DISCONNECTS ARE SHOWN ON RISER. PLEASE SEE 110.9,
 240.12
  
 9) NOTE: PLEASE CLARIFY AND SHOW ALL CONTINUOUS LOADS
 AT 125%. 215.3, 230.42
  
 10) NOTE: PLEASE BE SURE ALL SEALS ARE RAISED, CLEAR
 AND VISABLE WITH ALL INFORMATION AS REQUIRED ON SAID
 SEAL.
 PLEASE SEE SOME ARE NOT VISABLE EVEN WHEN SHADING WITH
 PENCIL.
 FS471.025
 PLEASE BE SURE THEY ARE ALSO SIGNED WITH LEGAL
 SIGNATURE.
  
 11) NOTE: PLEASE SEE FBC 13-101.1.3, METHOD "A" MAY NOT
 BEUSED.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2008-02-04 Cont ID  
Sent By mawillia Date 2008-02-04 Time 11:11 Rev Time 0.00
Received By mawillia Date 2008-02-04 Time 10:28 Sent To  
Notes
2008-02-04 11:11:49*****REVISIONS APPROVED*****
  
  
 REVISED PLAN SHEETS E-2.1, E-2.2, AND FP-1.0 WERE
 STAMPED, INITIALED, AND DATED..
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6622

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-12-31 Cont ID  
Sent By mawillia Date 2007-12-31 Time 11:38 Rev Time 0.00
Received By mawillia Date 2007-12-31 Time 11:30 Sent To  
Notes
2007-12-31 11:38:22*****STAMPING NEEDED*****
  
  
 REVISED PLAN SHEETS E-2.1, E-2.2, AND FP-1.0 TO BE
 FIRE-STAMPED WHEN THE OTHER REVIEWERS HAVE BEEN
 SATISFIED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6622

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-03-30 Cont ID  
Sent By mawillia Date 2007-03-30 Time 14:00 Rev Time 0.00
Received By mawillia Date 2007-03-30 Time 13:22 Sent To  
Notes
2007-03-30 14:00:00*****APPROVED*****
  
  
 ALL COMMENTS FROM PREVIOUS FIRE PLAN REVIEWS HAVE BEEN
 ADDRESSED;PLAN SHEETS A-1.1, E-2.1, E-2.2, AND FP-1.0
 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-03-14 Cont ID  
Sent By mawillia Date 2007-03-14 Time 13:10 Rev Time 0.00
Received By mawillia Date 2007-03-14 Time 12:33 Sent To  
Notes
2007-03-14 13:07:59****UNSAT*****
  
  
 THE FIVE COMMENTS TAKEN FROM THE PREVIOUS FIRE PLAN
 REVIEW HAVE BEEN SATISFIED WITH THE EXCEPTION OF THE
 FOLLOWING WHICH STILL NEED TO BE ADDRESSED:
  
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
 INSERT ON SHEET A-1.0
  
 4.REFERENCE SHALL BE MADE TO WEST PALM BEACH FIRE
 RESCUE (WPBFR) DEPARTMENT ON SHEET A-1.0 GENERAL DEMO
 NOTE #11.ON SHEET A-1.0, DELETE "THE PALM BEACH
 COUNTY FIRE DEPARTMENT (PBFD)";INSERT "WEST PALM
 BEACH FIRE RESCUE (WPBFR)."
  
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCEESS, INCLUDE A
 RESPONSE LETTER INDICATING HOW/WHERE EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-12-05 Cont ID  
Sent By mawillia Date 2006-12-05 Time 11:12 Rev Time 0.00
Received By mawillia Date 2006-12-05 Time 11:12 Sent To  
Notes
2006-12-05 11:32:46*****DENIED*****
  
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.CONSTRUCTION AND (OR) DEMOLITION OPERATIONS IN THE
 WORK SITE AREA SHALL NOT INTERFERE OR HINDER ACCESS OR
 EGRESS FROM OTHER AREA AREAS OF THE BUILDING.
  
 3.IF THE FIRE ALARM SYSTEM IS MODIFIED DUE TO THE
 SCOPE OF THE WORK, SEPARATE PERMIT AND PLANS ARE
 REQUIRED.
  
 4.REFERENCE SHALL BE MADE TO WEST PALM BEACH FIRE
 RESCUE (WPBFR) DEPARTMENT ON SHEET A-1.0 GENERAL DEMO
 NOTE #10.
  
 5.AS PER WPBFR, DUCT DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM.AMEND GENERAL FIRE ALARM NOTE #17,
 SHEET E-2.2.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCEESS, INCLUDE A
 RESPONSE LETTER INDICATING HOW/WHERE EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-01-28 Cont ID  
Sent By adarroug Date 2008-01-28 Time 09:04 Rev Time 0.00
Received By adarroug Date 2008-01-28 Time 09:04 Sent To  
Notes
2008-01-28 09:04:13TO "BOB"#2

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-12-26 Cont ID  
Sent By spalmer Date 2007-12-26 Time 15:41 Rev Time 0.00
Received By spalmer Date 2007-12-26 Time 15:41 Sent To  
Notes
2007-12-26 15:42:08TO "BOB" # 8

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-12-20 Cont ID  
Sent By mmiller Date 2007-12-20 Time 17:47 Rev Time 0.00
Received By mmiller Date 2007-12-20 Time 17:47 Sent To  
Notes
2007-12-20 17:47:22WAITING FOR BOB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-25 Cont ID  
Sent By adarroug Date 2007-03-25 Time 13:44 Rev Time 0.00
Received By adarroug Date 2007-03-25 Time 13:44 Sent To  
Notes
2007-03-25 13:46:02TO "BOB"#14

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-01 Cont ID  
Sent By adarroug Date 2007-03-01 Time 09:16 Rev Time 0.00
Received By adarroug Date 2007-03-01 Time 09:16 Sent To  
Notes
2007-03-01 09:18:47TO "BOB"#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-05 Cont ID  
Sent By mawillia Date 2006-12-05 Time 11:34 Rev Time 0.00
Received By mawillia Date 2006-10-24 Time 13:58 Sent To  
Notes
2006-11-01 10:00:10TO "BOB"#4
2006-10-24 14:03:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-12-27 Cont ID  
Sent By tgordon Date 2007-12-27 Time 09:28 Rev Time 0.35
Received By tgordon Date 2007-12-27 Time 09:28 Sent To  
Notes
2007-12-27 09:30:43REVISION TO MECH. PLANS PAGES AC-1.0, AC-2.0, AND
 AC-2.1.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-03-01 Cont ID  
Sent By tgordon Date 2007-03-01 Time 13:57 Rev Time 0.30
Received By tgordon Date 2007-03-01 Time 13:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-11-01 Cont ID  
Sent By tgordon Date 2006-11-01 Time 11:52 Rev Time 0.45
Received By tgordon Date 2006-11-01 Time 11:52 Sent To  
Notes
2006-11-01 12:20:19*** DENIED ***
 1) SEE PLANS PG. AC-2.1, HP-E4 NEW 10X8 FRESH AIR DUCT
 THROU FIRE WALL AT PORTFOLIO MANAGER ROOM #163 , NEEDS
 A FIRE DAMPER, PER 2004 FBC/M 607.5.1.
  
 2) SEE PLANS PG. AC-2.1, NEW 6" FLEX DUCT THROU FIRE
 WALL FROM CORRIDOR #2 TO CORR. #3A NEEDS A FIRE DAMPER,
 PER 2004 FBC/M 607.5.1.
  
 3) SEE ELECTRICAL REVIEW NOTES 1 AND 2, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-11-09 Cont ID  
Sent By kstevens Date 2006-11-09 Time 13:15 Rev Time 0.00
Received By kstevens Date 2006-11-09 Time 13:15 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved