Plan Review Details - Permit 06100680
Plan Review Stops For Permit 06100680
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-11-13 Cont ID  
Sent By jgomez Date 2006-11-13 Time 12:47 Rev Time 0.50
Received By jgomez Date 2006-11-13 Time 12:37 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-07 Cont ID  
Sent By jgomez Date 2006-11-07 Time 18:50 Rev Time 0.50
Received By jgomez Date 2006-11-07 Time 18:43 Sent To  
Notes
2006-11-07 18:59:33BUILDING REVIEW CHECKLIST:
  
 1-A) NEED TO PROVIDE EMERGENCY EGRESS AS REQUIRED BY
 SEC. R310.4 2004 FLORIDA RESIDENTIAL CODE.
 B) IDENTIFY IN WHICH ROOM IS THE MEANS OF ESCAPE
 LOCATED. IT CAN'T BE LOCATED WITHIN A GARAGE OR ANY
 ROOM THAT CAN BE LOCKED.
  
 2-ANCHOR SPACING TABLE ON SHEET 8 OF 16 CALLS FOR
 ANCHOR SPACING AT 6" O.C.. SPECIFY ON INSTALLATION
 SCHEDULE WHICH OPENING IS THE ONE HAVING THE ANCHOR
 SPACING AT 6" O.C. . REVISE INSTALLATION SCHEDULE AS
 REQUIRED TO MATCH ANCHOR SPACING ON SHEET 8 OF 16.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-07 Cont ID  
Sent By jgomez Date 2006-11-07 Time 18:59 Rev Time 0.00
Received By jgomez Date 2006-10-20 Time 14:04 Sent To  
Notes
2006-10-20 14:04:36TO "MISC" BOX#1