Plan Review Details - Permit 06100668
Plan Review Stops For Permit 06100668
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-11-17 Cont ID  
Sent By lursu Date 2006-11-17 Time 13:04 Rev Time 0.00
Received By lursu Date 2006-11-17 Time 13:04 Sent To  
Notes
2006-11-17 13:05:06TEMPORARY PCN WAS CREATED FOR THIS STRUCTURE .PERMIT
 WAS ASSIGNED TO IT.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-01-04 Cont ID  
Sent By shill Date 2007-01-04 Time 10:37 Rev Time 0.00
Received By shill Date 2007-01-04 Time 10:37 Sent To  
Notes
2007-01-04 10:37:30RECEIVED PLAT & IMPACT FEE RECEIPT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-01-03 Cont ID  
Sent By shill Date 2007-01-03 Time 13:15 Rev Time 0.00
Received By shill Date 2007-01-03 Time 13:15 Sent To  
Notes
2007-01-03 13:18:22****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
  
 FROM PREVIOUS LIST:
  
 1.)ADDRESSED.
  
 2.)PLEASE PROVIDE THE IMPACT FEE RECEIPT.
  
 3.-4.)ADDRESSED.
  
 5.)PLEASE PROVIDE A COPY OF THE RECORDED PLAT.
  
 6-7.)ADDRESSED.
  
 8.)FBC*105.13, PHASED PERMIT APPROVAL, THE HOLDER OF
 SUCH PERMIT FOR THE FOUNDATIONS OR OTHER PARTS OF A
 BUILDING OR STRUCTURE SHALL PROCEED AT THE HOLDER'S OWN
 RISK WITH THE BUILDING OPERATION AND WITHOUT ASSURANCE
 THAT A PERMIT FOR THE ENTIRE STRUCTURE WILL BE GRANTED.
 CORRECTIONS MAY BE REQUIRED TO MEET THE REQUIREMENTS OF
 THE TECHNICAL CODES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-21 Cont ID  
Sent By shill Date 2006-11-21 Time 09:21 Rev Time 0.00
Received By shill Date 2006-11-21 Time 09:21 Sent To  
Notes
2006-11-21 09:41:33****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB
 FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL
 561-233-5025 FOR MORE INFORMATION.
  
 3.) FBC* 109.3.7RESIDENT INSPECTOR. SUBMIT INSPECTOR
 RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA,
 DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.A RESIDENT
 INSPECTOR PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO
 ONE OR MORE OF THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS
 OF CONSTRUCTION
  
 ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION
 SERVICES MANAGER - TEL:
 561 805 6711), A MEETING INVOLVING THE OWNER, RESIDENT
 INSPECTOR, JOB INSPECTOR, CONTRACTOR AND ENGINEER. THIS
 MUST BE DONE PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL
 SETS OF ALL DOCUMENTS ARE REQUIRED FOR PERMITTING.
  
 ****11/28/6OK PER HAROLD PISKURA****
  
 4.)NOTE THAT ONLY TWO SURVEYS WERE SUBMITTED.PLEASE
 SUBMIT THREE ORIGINAL SETS.
  
 5.)SUBMIT A SITE PLAN SHOWING THE EXISTING LOT LINES
 IN RELATION TO THE PROPOSED BUILDING LOCATION.
  
 6.)DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS.THE SOILS REPORTS ARE PHOTOCOPIES; THREE
 ORIGINALS REQUIRED.
  
 7.)INFORMATIONAL ONLY; THIS IS A FOUNDATION PERMT.
 THE PLANS WILL BE REDLINED AND NOTED TO INDICATE THAT
 THE SPECIFICATIONS REGARDING THE SLAB WILL NOT BE A
 PART OF THIS PERMIT.
  
 8.)FBC*105.13, PHASED PERMIT APPROVAL, THE HOLDER OF
 SUCH PERMIT FOR THE FOUNDATIONS OR OTHER PARTS OF A
 BUILDING OR STRUCTURE SHALL PROCEED AT THE HOLDER?S OWN
 RISK WITH THE BUILDING OPERATION AND WITHOUT ASSURANCE
 THAT A PERMIT FOR THE ENTIRE STRUCTURE WILL BE GRANTED.
 CORRECTIONS MAY BE REQUIRED TO MEET THE REQUIREMENTS OF
 THE TECHNICAL CODES.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-01-12 Cont ID  
Sent By dpalmer Date 2007-01-12 Time 10:10 Rev Time 0.00
Received By dpalmer Date 2007-01-12 Time 09:25 Sent To B
Notes
2007-01-12 10:11:03SENT TO SAMANTHA HILL FOR PROCESSING AND ISSUANCE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-12-23 Cont ID  
Sent By dpalmer Date 2006-12-23 Time 14:27 Rev Time 0.00
Received By dpalmer Date 2006-12-23 Time 13:58 Sent To  
Notes
2006-12-23 14:28:16*** UNSAT 2ND REVIEW ***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW AND SOME
 NEW NOTES DUE TO PLANS SUBMITTED.
  
 1) NOTE:NO, SAME COMMENT BASED ON PLANS SUBMITTED
 SCOPE OF WORK FAR EXCEEDS THAT OF THE VALUE ON PERMIT
 APPLICATION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE VALUATION FOR SCOPE OF WORK APPLIED FOR
 SHALL BE BASED ON ALL LABOR AND MATERIALS EVENS OF
 OWNER SUPPLIED. PLEASE SEE THE VALUE SEEMS VERY LOW FOR
 THIS FOUNDATION AND AMOUNT OF CONCRETE/STEEL ETC WORK
 SHOWN. PLEASE SEE BUILDING REVIEW NOTES.
 FBC ADMIN SECT 108.3
  
 2) NOTE:NO, PLEASE SEE MISSING INFORMATION AS
 PREVIOUSLY STATED IS STILL NOT SHOWN.
 PLEASE SEE MISSING PRINTED NAME FOR ENGINEER.
 PLEASE SEE MISSING PRINTED LICENSE NUMBER
 PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION
 NUMBER.
 PLEASE ALSO SEE NEW NOTE BELOW.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING INFORMATION FOR TITLE BLOCKS AS
 REQUIRED UNDER FLORIDA STATUTES 481.219/471.023 FAC
 61G1-16.004, 61G15-23.002
  
 3) NOTE: OK/NO, IT IS UNCLEAR AS THE PLANS SHOW MORE
 THAN ONLY FOOTINGS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE REVIEW COMMENTS UNDER THE MAIN BUILDING
 PERMITS.
 PLEASE SUPPLY SLAB PLANS FOR ELECTRICAL CONDUIT
 INSTALLATION UNDER SLAB.
 215.5, 230.70, 230.6, 230.70 ETC.
 PLEASE BE SURE TO SEE COMMENTS UNDER BLDG REVIEW AS
 THIS MAY VERY WELL AFFECT THE ELECTRICAL CONDUIT
 LOCATION.
  
 4) NOTE: OK, HOWEVER NEED ONLY SHOW DETAIL AS THE
 SERVICE INFORMATION IS NOT BEING REVIEWED. THIS IS OK,
 HOWEVER DUE TO OTHER COMMENTS, PLANS WILL BE REVISED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE ALSO SUBMIT GROUNDING ELECTRODE CONNECTION
 DETAIL AS REQUIRED PER 250.50. (FOOTER STEEL, UNDER
 GROUND COLD WATER PIPES ETC REQUIRED). THERE ARE NO
 EXCEPTIONS TO THE REQUIRED ATTACHMENTS OF 250.50.
  
 ** NEW NOTES **
  
 1) NOTE: PLEASE SEE THE SEAL ON SAID PLANS IS NOT
 LONGER VALID FOR USE IN THE STATE OF FLORIDA. PLEASE
 SEE RULING 61G15-23.001 WHICH WAS PASSED BY THE FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS IN FEB 04, IN WHICH THE
 WORDING O IN THE SEAL "CERTIFICATE" COULD NOT LONGER BE
 USED AND MUST BE CHANGED TO THE WORDING OF"LICENSE".
 PLEASE KNOW AN EXTENSION WAS GIVEN ONLY TO THE DATE OF
 DECEMBER 31ST, 2005. PLEASE OBTAIN NEW SEAL.
 PLEASE ALSO SEE PLANS APPEAR TO BE SIGNED WITH
 INITIALS, IF THIS IS INDEED THE LEGAL SIGNATURE OF SAID
 ENGINEER, PLEASE SUBMIT A SIGNED, DATED, SEALED AND
 NOTARIZED LETTER FOR VERIFICATION OF LEGAL SIGNATURE.
 THIS WILL BE PLACED IN OUR SIGNATURE FILE FOR FUTURE
 REFERENCE.
 FS 471.025, FAC 61G15-23.002
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-03 Cont ID  
Sent By dpalmer Date 2006-11-03 Time 19:30 Rev Time 0.00
Received By dpalmer Date 2006-11-03 Time 19:22 Sent To  
Notes
2006-11-03 19:30:09*** UNSAT ***
  
 1) NOTE; PLEASE SEE THE VALUATION FOR SCOPE OF WORK
 APPLIED FOR SHALL BE BASED ON ALL LABOR AND MATERIALS
 EVENS OF OWNER SUPPLIED. PLEASE SEE THE VALUE SEEMS
 VERY LOW FOR THIS FOUNDATION AND AMOUNT OF
 CONCRETE/STEELETC WORK SHOWN. PLEASE SEE BUILDING
 REVIEW NOTES.
 FBC ADMIN SECT 108.3
  
 2) NOTE:PLEASE SEE MISSING INFORMATION FOR TITLE BLOCKS
 AS REQUIRED UNDER FLORIDA STATUTES 481.219/471.023 FAC
 61G1-16.004, 61G15-23.002
  
 3) NOTE: PLEASE SEE REVIEW COMMENTS UNDER THE MAIN
 BUILDING PERMITS.
 PLEASE SUPPLY SLAB PLANS FOR ELECTRICAL CONDUIT
 INSTALLATION UNDER SLAB.
 215.5, 230.70, 230.6, 230.70 ETC.
 PLEASE BE SURE TO SEE COMMENTS UNDER BLDG REVIEW AS
 THIS MAY VERY WELL AFFECT THE ELECTRICAL CONDUIT
 LOCATION.
  
 4) NOTE: PLEASEALSO SUBMIT GROUNDING ELECTRODE
 CONNECTION DETAIL AS REQUIRED PER 250.50. (FOOTER
 STEEL, UNDER GROUND COLD WATER PIPES ETC REQUIRED).
 THERE ARE NO EXCEPTIONS TO THE REQUIRED ATTACHMENTS OF
 250.50.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2006-11-13 Cont ID  
Sent By rchokshi Date 2006-11-13 Time 14:03 Rev Time 0.00
Received By rchokshi Date 2006-11-13 Time 14:02 Sent To  
Notes
2006-11-13 14:03:11ACCORDING TO A LETTER (E-MAIL) FROM STEVEN M. PAWLYK OF
 BOWYER-SINGLETON DATED NOV 13, 06,THIS PRMIT IS
 COVERED UNDER PERMIT#06071716.PERMIT # 06071716 IS
 REVIEWED AND PASSED SOMETIME AGO.THEREFORE, THIS IS
 PASSED.
  
 RASIK CHOKSHI805-6723

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-10 Cont ID  
Sent By adarroug Date 2007-01-10 Time 15:11 Rev Time 0.00
Received By adarroug Date 2007-01-10 Time 15:11 Sent To E
Notes
2007-01-10 15:12:04TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-05 Cont ID  
Sent By adarroug Date 2006-12-05 Time 13:04 Rev Time 0.00
Received By adarroug Date 2006-12-05 Time 13:04 Sent To  
Notes
2006-12-18 14:55:47TO "COMM" BD#64
2006-12-05 13:05:08WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By eschneid Date 2006-11-06 Time 08:24 Rev Time 0.00
Received By adarroug Date 2006-11-01 Time 08:52 Sent To  
Notes
2006-11-03 16:55:59TO "COMM" BD#45--FOUNDATION ONLY
2006-11-01 08:56:57TO "ENG" BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2006-12-27 Cont ID  
Sent By eschneid Date 2006-12-27 Time 13:01 Rev Time 0.00
Received By eschneid Date 2006-12-27 Time 13:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-11-06 Cont ID  
Sent By eschneid Date 2006-11-06 Time 08:24 Rev Time 0.00
Received By eschneid Date 2006-10-31 Time 16:44 Sent To I
Notes
2006-10-31 16:44:22FAILED
  
 SITE PLAN SHOWING THE LOCATION OF WORK AND THE APPROVED
 FEDEX GROUND BUILDING IS REQUIRED.
  
 ERIC SCHNEIDER @ (561) 822-1435.