Plan Review Details - Permit 06100667
Plan Review Stops For Permit 06100667
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-11-17 Cont ID  
Sent By lursu Date 2006-11-17 Time 13:02 Rev Time 0.00
Received By lursu Date 2006-11-17 Time 13:02 Sent To  
Notes
2006-11-17 13:03:35TEMPORARY PCN WAS CREATED FOR THIS STRUCTURE .PERMIT
 WAS ASSIGNED TO IT.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-01-04 Cont ID  
Sent By shill Date 2007-01-04 Time 11:14 Rev Time 0.00
Received By shill Date 2007-01-04 Time 11:14 Sent To  
Notes
2007-01-09 15:58:23***PROVISO***FOOTERS ONLY, NO SLAB

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-01-03 Cont ID  
Sent By shill Date 2007-01-03 Time 15:11 Rev Time 0.00
Received By shill Date 2007-01-03 Time 15:10 Sent To  
Notes
2007-01-03 15:11:39****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)PROVIDE THE IMPACT FEE RECEIPT.
  
 2.)PROVIDE A COPY OF THE RECORDED PLAT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-21 Cont ID  
Sent By shill Date 2006-11-21 Time 11:02 Rev Time 0.00
Received By shill Date 2006-11-21 Time 11:02 Sent To  
Notes
2006-11-21 11:03:06****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB
 FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  1
  
 .)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL
 561-233-5025 FOR MORE INFORMATION.
  
 3.) FBC* 109.3.7RESIDENT INSPECTOR. SUBMIT INSPECTOR
 RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA,
 DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.A RESIDENT
 INSPECTOR PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO
 ONE OR MORE OF THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS
 OF CONSTRUCTION
  
 ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION
 SERVICES MANAGER - TEL:
 561 805 6711), A MEETING INVOLVING THE OWNER, RESIDENT
 INSPECTOR, JOB INSPECTOR, CONTRACTOR AND ENGINEER. THIS
 MUST BE DONE PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL
 SETS OF ALL DOCUMENTS ARE REQUIRED FOR PERMITTING.
  
 ****11/29/6OK PER HAROLD PISKURA
  
 4.)SUBMIT A SITE PLAN SHOWING THE EXISTING LOT LINES
 IN RELATION TO THE PROPOSED BUILDING LOCATION.
  
 5.)DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS.THE SOILS REPORTS ARE PHOTOCOPIES; THREE
 ORIGINALS REQUIRED.
  
 6.)INFORMATIONAL ONLY; THIS IS A FOUNDATION PERMT.
 THE PLANS WILL BE REDLINED AND NOTED TO INDICATE THAT
 THE SPECIFICATIONS REGARDING THE SLAB WILL NOT BE A
 PART OF THIS PERMIT.
  
 7.)FBC*105.13, PHASED PERMIT APPROVAL, THE HOLDER OF
 SUCH PERMIT FOR THE FOUNDATIONS OR OTHER PARTS OF A
 BUILDING OR STRUCTURE SHALL PROCEED AT THE HOLDER?S OWN
 RISK WITH THE BUILDING OPERATION AND WITHOUT ASSURANCE
 THAT A PERMIT FOR THE ENTIRE STRUCTURE WILL BE GRANTED.
 CORRECTIONS MAY BE REQUIRED TO MEET THE REQUIREMENTS OF
 THE TECHNICAL CODES.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-01-12 Cont ID  
Sent By dpalmer Date 2007-01-12 Time 10:20 Rev Time 0.00
Received By dpalmer Date 2007-01-12 Time 10:20 Sent To B
Notes
2007-01-12 10:20:59ROUTED TO SAMANTH HILL FOR PROCESSING AND ISSUANCE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-12-23 Cont ID  
Sent By dpalmer Date 2006-12-23 Time 13:46 Rev Time 0.00
Received By dpalmer Date 2006-12-23 Time 13:32 Sent To  
Notes
2006-12-23 13:47:25*** UNSAT 2ND REVIEW **
  
 1) NOTE: PLEASE SUBMIT A DETAIL FOR THE FOOTER AND THE
 STRUCTURAL STEEL AND ANY UNDER GROUND WATER PIPING
 SYSTEMS BEING PART OF THE FOUNDATION PERMIT.
 PLEASE SEE RISER SUBMITTED HAS NOT BEEN REVIEWED FOR
 CODE COMPLIANCE.
 250.50
  
 2) NOTE: PLEASE SEE THAT THE PLANS SHALL BEAR THE
 SIGNATURE FOR THE ENGINEER AS RECOGNIZED AND ON FILE IN
 THE OFFICE.
 FS471.025
  
 ** ** IMPORTANT**
 PLEASE SUBMIT PLANS INTO THREE SETS WITH ALL OTHER
 PLANS FOR PROJECT.
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-03 Cont ID  
Sent By dpalmer Date 2006-11-03 Time 19:41 Rev Time 0.00
Received By dpalmer Date 2006-11-03 Time 19:41 Sent To  
Notes
2006-11-03 19:42:33** UNSAT **
  
  
  
 1) NOTE; PLEASE SEE THE VALUATION FOR SCOPE OF WORK
 APPLIED FOR SHALL BE BASED ON ALL LABOR AND MATERIALS
 EVENS OF OWNER SUPPLIED. PLEASE SEE THE VALUE SEEMS
 VERY LOW FOR THIS FOUNDATION AND AMOUNT OF
 CONCRETE/STEELETC WORK SHOWN. PLEASE SEE BUILDING
 REVIEW NOTES.
 FBC ADMIN SECT 108.3
  
 2) NOTE: PLEASE SEE REVIEW COMMENTS UNDER THE MAIN
 BUILDING PERMITS.
 PLEASE SUPPLY SLAB PLANS FOR ELECTRICAL CONDUIT
 INSTALLATION UNDER SLAB.
 215.5, 230.70, 230.6, 230.70 ETC.
 PLEASE BE SURE TO SEE COMMENTS UNDER BLDG REVIEW AS
 THIS MAY VERY WELL AFFECT THE ELECTRICAL CONDUIT
 LOCATION.
  
 3) NOTE: PLEASEALSO SUBMIT GROUNDING ELECTRODE
 CONNECTION DETAIL AS REQUIRED PER 250.50. (FOOTER
 STEEL, UNDER GROUND COLD WATER PIPES ETC REQUIRED).
 THERE ARE NO EXCEPTIONS TO THE REQUIRED ATTACHMENTS OF
 250.50.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2006-11-13 Cont ID  
Sent By rchokshi Date 2006-11-13 Time 13:59 Rev Time 0.00
Received By rchokshi Date 2006-11-13 Time 13:52 Sent To  
Notes
2006-11-13 13:58:40ACCORDING TO A LETTER (E-MAIL) FROM STEVEN M. PAWLYK OF
 BOWYER-SINGLETON DATED NOV 13, 06,THIS PRMIT IS
 COVERED UNDER PERMIT#06071716.PERMIT # 06071716 IS
 REVIEWED AND PASSED SOMETIME AGO.THEREFORE, THIS IS
 PASSED.
  
 RASIK CHOKSHI805-6723

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-01-10 Cont ID  
Sent By adarroug Date 2007-01-10 Time 11:54 Rev Time 0.00
Received By adarroug Date 2007-01-10 Time 11:54 Sent To  
Notes
2007-01-10 11:54:42TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-05 Cont ID  
Sent By adarroug Date 2006-12-05 Time 13:09 Rev Time 0.00
Received By adarroug Date 2006-12-05 Time 13:09 Sent To  
Notes
2006-12-18 14:48:56TO "COMM" BD#26
2006-12-05 13:09:36WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-01 Cont ID  
Sent By adarroug Date 2006-11-01 Time 09:11 Rev Time 0.00
Received By adarroug Date 2006-11-01 Time 09:09 Sent To ENG
Notes
2006-11-03 16:56:49TO "COMM" BD#45--FOUNDATION ONLY
2006-11-01 09:11:44TO "ENG" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-21 Cont ID  
Sent By shill Date 2006-11-21 Time 16:02 Rev Time 0.00
Received By shill Date 2006-11-21 Time 10:08 Sent To  
Notes
2006-10-20 10:08:57TO "Z" BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2006-12-27 Cont ID  
Sent By eschneid Date 2006-12-27 Time 11:27 Rev Time 0.00
Received By eschneid Date 2006-12-27 Time 11:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-10-31 Cont ID  
Sent By eschneid Date 2006-10-31 Time 16:41 Rev Time 0.00
Received By eschneid Date 2006-10-31 Time 16:40 Sent To I
Notes
2006-10-31 16:42:55FAILED
  
 SITE PLAN SHOWING THE LOCATION OF WORK AND THE APPROVED
 FEDEX FREIGHT BUILDINGS IS REQUIRED.
  
 ERIC SCHNEIDER @ (561) 822-1435.