Plan Review Details - Permit 06100658
Plan Review Stops For Permit 06100658
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-11-13 Cont ID  
Sent By rmcdouga Date 2006-11-13 Time 12:29 Rev Time 0.00
Received By rmcdouga Date 2006-11-13 Time 12:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-18 Cont ID  
Sent By rmcdouga Date 2006-10-18 Time 13:47 Rev Time 0.00
Received By rmcdouga Date 2006-10-18 Time 13:47 Sent To  
Notes
2006-10-18 13:57:44DENIED BY BUILDING
  
 1) THE PRODUCT APPROVALS FOR THE TAMKO MODIFIED SYSTEM
 REQUIRES RAS 117 CALCULATIONS FROM AN ARCHITECT,
 ENGINEER OR REGISTERED ROOF CONSULTANT FOR THE REQUIRED
 ENHANCED FASTENING AT THE PERIMETER AND CORNERS. SEE
 PAGE 20 OF THE NOA. SUBMIT CALCULATIONS.
  
 2) SPECIFY THE ROOF PITCH AND MEAN ROOF HEIGHT FOR THE
 SLOPED ROOF.
  
 3) THE ELK SHINGLE NOA DOES NOT ALLOW THEM TO BE
 INSTALLED ON ROOFS WITH A MEAN HEIGHT OF MORE THAN 33
 FEET. SEE LIMITATIONS ON PAGE 2 OF THE NOA.
  
 4) PLEASE INDICATE THE SQUARE FOOTAGE OF FLAT AND
 SLOPED ROOF SEPARATELY ON THE APPLICATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714