Plan Review Details - Permit 06100656
Plan Review Stops For Permit 06100656
Review Stop G GAS REVIEW
Rev No 4 Status P Date 2007-04-09 Cont ID  
Sent By mperson Date 2007-04-09 Time 11:04 Rev Time 0.33
Received By mperson Date 2007-04-09 Time 11:04 Sent To PC
Notes
2007-04-09 11:06:06REFERENCE: GEN/RES PERMIT #06080671

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2007-04-03 Cont ID  
Sent By spalmer Date 2007-04-03 Time 18:12 Rev Time 0.00
Received By spalmer Date 2007-04-03 Time 18:12 Sent To G
Notes
2007-04-03 18:13:09TO MIKE PERSON

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-03-19 Cont ID  
Sent By mperson Date 2007-03-19 Time 11:41 Rev Time 0.45
Received By mperson Date 2007-03-19 Time 11:41 Sent To PC
Notes
2007-03-19 12:56:57DENIED 2ND TIME
 REFERENCE: FBC-2004 FUEL GAS
  
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1.**OK**
  
 2.**NO/OK** PLEASE INDICATE THE MAKE AND MODEL NUMBER
 OF THE 2LB MP REGULATOR FOR THE GENERATOR ON THE
 RESUBMITTAL.
 NOTE: IS IT YOUR INTENT TO USE A MAXITROL 325-5A MP
 REGULATOR FOR THE GENERATOR. PLEASE CLEARIFY ON THE
 RESUBMITTAL.
  
 THE FOLLOWING ARE NEW COMMENTS:
  
 3. THE SUBMITTED GAS ISOMETRIC DOES NOT REFLECT THE
 FLOOR PLAN. FLOOR PLAN INDICATES GAS PIPE TO GENERATOR
 BEING PIPED FROM RANGE LOCATION, AND THE ISOMETRIC
 INDICATES GAS BEING PIPED FROM THE METER LOCATION TO
 THE GENERATOR. PLEASE CORRELATE AND CORRECT ON THE
 RESUBMITTAL.
  
 4.SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE SUBMITTED ISOMETRIC DOES NOT HAVE ALL
 CORRESPONDING LENGTHS INDICATED ON THE DRAWING. PLEASE
 CORRECT AND RESUBMIT.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-10-24 Cont ID  
Sent By mperson Date 2006-10-24 Time 15:54 Rev Time 0.33
Received By mperson Date 2006-10-24 Time 15:54 Sent To PC
Notes
2006-10-24 16:26:42UNSAT
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED FOR GAS PLAN
 REVIEW:
  
 1. A GAS PERMIT CAN NOT BE ISSUED UNTIL
 A GEN/RES PERMIT APPLICATION HAS BEEN
 APPLIED FOR AND APPROVED BY ZONING, ELECTRICAL, AND GAS
 FOR
 THE GENERATOR LOCATION. NOTE: GEN/RES PERMIT
 APPLICATION HAS FAILED ZONING ON TWO SEPERATE
 SUBMITTALS. THE FIRST DATED 08/18/06 AND THE SECOND
 DATED 10/13/06.
  
 2. PLEASE INDICATE THE MAKE AND MODEL NUMBER OF THE
 2LB REGULATOR FOR THE GENERATOR ON THE RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-07 Cont ID  
Sent By adarroug Date 2007-03-07 Time 13:48 Rev Time 0.00
Received By adarroug Date 2007-03-07 Time 13:48 Sent To G
Notes
2007-03-07 13:49:18TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-24 Cont ID  
Sent By mperson Date 2006-10-24 Time 15:54 Rev Time 0.00
Received By mperson Date 2006-10-20 Time 13:57 Sent To  
Notes
2006-10-24 16:12:31 
2006-10-20 13:57:50TO "G" BOX