Plan Review Details - Permit 06100638
Plan Review Stops For Permit 06100638
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-01-16 Cont ID  
Sent By lmartine Date 2007-01-16 Time 13:05 Rev Time 0.00
Received By lmartine Date 2007-01-16 Time 13:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-01-31 Cont ID  
Sent By btrobaug Date 2007-01-31 Time 13:09 Rev Time 0.50
Received By btrobaug Date 2007-01-31 Time 12:44 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-03 Cont ID  
Sent By btrobaug Date 2006-11-03 Time 13:45 Rev Time 0.50
Received By btrobaug Date 2006-11-03 Time 12:40 Sent To M
Notes
2006-11-03 13:45:08 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
 DO THIS ON A SITE PLAN, NOT ON THE SURVEY, 106.1.3FBC.
  
 2} PROVIDE MANUFACTURERS SPECIFICATIONS AND
 RECOMMENDATION, REGARDING CLEARANCES FROM STRUCTURES
 FOR THE GENERATOR.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2.
  
 4} SUBMIT TWO COPIES OF ALL DOCUMENTS FOR REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-03-02 Cont ID  
Sent By mperson Date 2007-03-02 Time 14:20 Rev Time 0.45
Received By mperson Date 2007-03-02 Time 14:20 Sent To B
Notes
2007-03-02 14:28:03NOTE: GAS PERMIT #07020632 SUBMITTED 2/22/07 TO REPLACE
 EXPIRED GAS PERMIT #06031322 AND ATTACHED TO GEN/RES
 PERMIT #06100638

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-02-12 Cont ID  
Sent By mperson Date 2007-02-12 Time 14:21 Rev Time 0.33
Received By mperson Date 2007-02-12 Time 14:21 Sent To B
Notes
2007-02-12 14:35:44DENIED 2ND TIME
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS STILL REQUIRED FOR GAS
 PLAN REVIEW:
  
 ******IMPORTANT INFORMATION******
 AS OF 8/25/06 GENERATOR (GEN/RES AND
 GEN/COM) PERMIT APPLICATIONS SHALL NOT
 BE ACCEPTED UNLESS THE ELECTRICAL INFOR-
 MATION AND GAS (OR DIESEL) INFORMATION
 IS ALL SUBMITTED AT THE SAME TIME. THE
 GENERATOR, ELECTRICAL AND GAS/DIESEL IN-
 FORMATION WILL BE ROUTED TOGETHER. THIS
 WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY
 THE MANUFACTURER'S SPECI-
 FICATIONS AND INSTALLATION INSTRUCTIONS)
 ARE AVAILABLE TO ALL PLAN REVIEWERS.
  
 CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/RES INSPECTION.
  
 NOTE: GAS PERMIT #06031322 IS EXPIRED (PLEASE REFERENCE
 THE ATTACHED PERMIT INFORMATION SHEET) AND A NEW GAS
 PERMIT APPLICATION WITH TWO SETS OF DRAWINGS NEEDS TO
 BE ATTACHED TO THE RESUBMITTED GEN/RES PERMIT
 APPLICATION IN ORDER TO ATTAIN A GENERATOR PERMIT.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-11-15 Cont ID  
Sent By mperson Date 2006-11-15 Time 16:48 Rev Time 0.33
Received By mperson Date 2006-11-15 Time 16:48 Sent To PC
Notes
2006-11-15 16:51:05UNSAT: SENT TO FRONT COUNTER PER LUIS MARTINEZ REQUEST
 CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/RES INSPECTION.
  
 ******IMPORTANT INFORMATION******
 AS OF 8/25/06 GENERATOR (GEN/RES AND
 GEN/COM) PERMIT APPLICATIONS SHALL NOT
 BE ACCEPTED UNLESS THE ELECTRICAL INFOR-
 MATION AND GAS (OR DIESEL) INFORMATION
 IS ALL SUBMITTED AT THE SAME TIME. THE
 GENERATOR, ELECTRICAL AND GAS/DIESEL IN-
 FORMATION WILL BE ROUTED TOGETHER. THIS
 WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY
 THE MANUFACTURER'S SPECI-
 FICATIONS AND INSTALLATION INSTRUCTIONS)
 ARE AVAILABLE TO ALL PLAN REVIEWERS.
  
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-02-27 Cont ID  
Sent By adarroug Date 2007-02-27 Time 09:53 Rev Time 0.00
Received By adarroug Date 2007-02-27 Time 09:53 Sent To G
Notes
2007-02-27 09:53:26TO "G" BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-31 Cont ID  
Sent By btrobaug Date 2007-01-31 Time 12:48 Rev Time 0.00
Received By btrobaug Date 2007-01-31 Time 12:48 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-31 Cont ID  
Sent By adarroug Date 2006-10-31 Time 09:09 Rev Time 0.00
Received By adarroug Date 2006-10-31 Time 09:08 Sent To E
Notes
2006-10-31 09:09:20TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-16 Cont ID  
Sent By mmclean Date 2006-10-28 Time 11:50 Rev Time 0.00
Received By lmartine Date 2006-10-19 Time 14:06 Sent To  
Notes
2006-10-19 14:08:45TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-11-03 Cont ID  
Sent By tgordon Date 2006-11-03 Time 15:40 Rev Time 0.20
Received By tgordon Date 2006-11-03 Time 15:40 Sent To P
Notes
2006-11-03 15:43:51*** PROVISO ***
 PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION
 ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE RESISTANCE
 RATING OF 1 HOUR OR (2) THE WEATHERPROOF ENCLOSURE IS
 CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 FOLLOW MANUFACTURE'S RECOMMENDED
 CLEARANCES AROUND EQUIPMENT FOR
 SERVICING,AND PROVIDE MANUFACTURE'S
 INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 1 Status P Date 2006-10-28 Cont ID  
Sent By mmclean Date 2006-10-28 Time 11:48 Rev Time 0.00
Received By mmclean Date 2006-10-28 Time 11:48 Sent To I
Notes
2006-10-28 11:49:58NOTE: THE PROPOSED GENERATOR SHALL NOT BE CLOSER THAN
 3.5FT OR 4FT FROM SIDE PROPERTY LINE. GENERATOR MUST BE
 SCREENED.