Plan Review Details - Permit 06100574
Plan Review Stops For Permit 06100574 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
59 |
Status |
P |
Date |
2009-08-21 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2009-08-21 |
Time |
11:33 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2009-08-21 |
Time |
11:33 |
Sent To |
|
|
Notes |
2009-08-21 11:34:01 | STRUCTURAL SUBMITTAL FOR MAILBOX. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
58 |
Status |
P |
Date |
2009-04-08 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2009-04-08 |
Time |
13:29 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2009-04-08 |
Time |
13:29 |
Sent To |
PC |
|
Notes |
2009-04-08 13:31:02 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: THORNTON- TOMASETTI | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | REVISION REVIEW # 27B: | | | | ACTION: REVIEWED | | | | SHEET: | | A9-2.2 | | A9-2.9 | | IDI-1.2 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
57 |
Status |
P |
Date |
2009-04-02 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2009-04-02 |
Time |
10:14 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2009-04-02 |
Time |
10:14 |
Sent To |
PC |
|
Notes |
2009-04-02 10:15:49 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: THORNTON- TOMASETTI | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | REVISION REVIEW:# 28A GARAGE AS-BUILTS | | | | ACTION: REVIEWED |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
56 |
Status |
P |
Date |
2009-04-02 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2009-04-02 |
Time |
09:37 |
Rev Time |
1.77 |
Received By |
jwitmer |
Date |
2009-04-02 |
Time |
09:37 |
Sent To |
|
|
Notes |
2009-04-02 09:39:16 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: THORNTON- TOMASETTI | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | REVISION REVIEW: 27A CAFE REVISIONS | | | | ACTION: REVIEWED |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
55 |
Status |
P |
Date |
2009-03-18 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2009-03-18 |
Time |
11:43 |
Rev Time |
0.33 |
Received By |
jwitmer |
Date |
2009-03-18 |
Time |
11:43 |
Sent To |
|
|
Notes |
2009-03-18 11:44:32 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: THORNTON- TOMASETTI | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | REVIEW: REVISION 24B- SHEET A0-D.2 | | | | ACTION: REVIEWED |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
54 |
Status |
P |
Date |
2009-03-18 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2009-03-18 |
Time |
11:39 |
Rev Time |
2.22 |
Received By |
jwitmer |
Date |
2009-03-18 |
Time |
11:39 |
Sent To |
|
|
Notes |
2009-03-18 11:40:41 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: THORNTON- TOMASETTI | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | REVIEW: REVISION 25A | | | | ACTION: RVIEWED |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
53 |
Status |
P |
Date |
2009-03-13 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2009-03-13 |
Time |
13:58 |
Rev Time |
2.22 |
Received By |
jwitmer |
Date |
2009-03-13 |
Time |
13:58 |
Sent To |
PC |
|
Notes |
2009-03-13 13:59:50 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: THORNTON- TOMASETTI | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | REVIEW: STAIR SHOP DRAWING RAILING | | | | ACTION: REVIEWED |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
52 |
Status |
P |
Date |
2009-01-29 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2009-01-29 |
Time |
16:24 |
Rev Time |
0.33 |
Received By |
jwitmer |
Date |
2009-01-29 |
Time |
16:24 |
Sent To |
PC |
|
Notes |
2009-01-29 16:25:43 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: THORNTON- TOMASETTI | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | REVIEW: ADDENDUM TO REVION 16B FOR 1 LIGHT POLE | | | | ACTION: REVIEWED |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
51 |
Status |
P |
Date |
2009-01-29 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2009-01-29 |
Time |
16:15 |
Rev Time |
0.44 |
Received By |
jwitmer |
Date |
2009-01-29 |
Time |
16:14 |
Sent To |
PC |
|
Notes |
2009-01-29 16:16:35 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: THORNTON- TOMASETTI | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | REVIEW: PLANTER/ SEAT DETAIL | | SSK-205 | | SSK-206 | | SSK-207 | | | | ACTION: REVIEWED |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
50 |
Status |
P |
Date |
2009-01-23 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2009-01-23 |
Time |
15:26 |
Rev Time |
0.88 |
Received By |
jwitmer |
Date |
2009-01-23 |
Time |
15:26 |
Sent To |
|
|
Notes |
2009-01-23 15:30:33 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: THORNTON- TOMASETTI | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | REVISION # 24A REVIEW: | | | | ACTION:OK A0-0, A0-1, A0-3 & A0-D.2 | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
49 |
Status |
F |
Date |
2009-01-14 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2009-01-14 |
Time |
08:40 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2009-01-14 |
Time |
08:40 |
Sent To |
PC |
|
Notes |
2009-01-14 08:45:13 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: THORNTON- TOMASETTI | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | REVIEW: STAIR RAILINGS WITH CALCULATIONS | | | | ACTION: DENIED | | | | 1) FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | SHOP DRAWINGS ETC... | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)805-6731 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
48 |
Status |
P |
Date |
2009-01-14 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2009-01-14 |
Time |
08:34 |
Rev Time |
0.55 |
Received By |
jwitmer |
Date |
2009-01-14 |
Time |
08:34 |
Sent To |
PC |
|
Notes |
2009-01-14 08:37:13 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: THORNTON- TOMASETTI | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | REVIEW: NEW CANOPY FOUNDATION PLAN | | | | ACTION: REVIEWED | | | | SKETCH NUMBER CSA-002/ SSK-001-SSK-004 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
47 |
Status |
P |
Date |
2009-01-13 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2009-01-13 |
Time |
13:54 |
Rev Time |
2.55 |
Received By |
jwitmer |
Date |
2009-01-13 |
Time |
13:54 |
Sent To |
|
|
Notes |
2009-01-13 16:03:18 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: THORNTON- TOMASETTI | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | REVISION REVIEW 23A | | ACTION: BUILDING PROVISO: | | SHEET LS1-2.2 & A1-2.2 | | SITE MEETING HELD 01-13-09 AT CATALFUMO'S SITE OFFICE | | WITH REPRESENTATIVES FROM SONG & ASSOC, | | TED DAVIS ARCHITECTURE, CATALFUMO AND CITY | | REPRESENTATIVES ALL AGREED THESE TWO WALLS ARE | | TENANT SEPERATION WALLS AS PER SECTION 708.1(5). PLANS | | RED LINED TO FACILITATE THE ACCEPTANCE OF REVISION 23A. | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)805-6731 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
46 |
Status |
F |
Date |
2008-12-31 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-12-31 |
Time |
08:24 |
Rev Time |
0.55 |
Received By |
jwitmer |
Date |
2008-12-31 |
Time |
08:24 |
Sent To |
PC |
|
Notes |
2008-12-31 08:27:56 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: THORNTON- TOMASETTI | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | REVIEW: RFI# 0871(1-3) | | | | ACTION: DENIED | | | | 61G15-23.002(2) FL. ADMIN. CODE. PLANS SIGNED & SEALED | | BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE: | | NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR, | | THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE | | NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER | | OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER | | IS PRACTICING (471.025 F.S. AND 471.023 F.S.). | | | | 471.023 F.S. CERTIFICATE OF AUTHORIZATION. THE TITLE | | BLOCK FOR ANY SHEET BEARING THE NAME OF AN ENGINEER | | PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A | | PARTNERSHIP, OFFERING ENGINEERING SERVICES, SHALL | | INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD | | THE NUMBER TO EACH SHEET. THIS MAY BE ADDED BY HAND. | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)805-6731 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
45 |
Status |
P |
Date |
2008-12-24 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-12-24 |
Time |
16:22 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2008-12-24 |
Time |
16:22 |
Sent To |
|
|
Notes |
2008-12-24 16:24:50 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: THORNTON- TOMASETTI | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | BUILDING REVIEW | | ACTION: REVIEWED | | : | | DEC. 24/08 | | REVISION: 20B | | SHEET: A1-GA.1 SECOND FLOOR PARKING LEVEL THE SOUTHWEST | | CORNER OF THE | | PARKING STRUCTURE PLANS INDICATE BOLLARDS LOCATED | | WITHIN THE ACCESS AISLE | | ASSOCIATED WITH DISABLED PARKING SPACE. PLEASE REMOVE | | BOLLARDS, REVIEW | | SECTION 11-4.6.3 MUST BE PART OF THE ACCESSIBLE ROUTE | | TO BUILDING OR FACILITY | | ENTRANCE. | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
44 |
Status |
P |
Date |
2008-11-17 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-11-17 |
Time |
16:15 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2008-11-17 |
Time |
16:15 |
Sent To |
|
|
Notes |
2008-11-17 16:16:19 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: THORNTON- TOMASETTI | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | REVIEW: REVISION# 21A | | | | ACTION: REVIEWED |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
43 |
Status |
P |
Date |
2008-11-12 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-11-12 |
Time |
11:54 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2008-11-12 |
Time |
11:54 |
Sent To |
PC |
|
Notes |
2008-11-12 11:56:44 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: THORNTON- TOMASETTI | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | REVIEW: REVISION 16-C | | | | ACTION: REVIEWED | | REVISED RAILING TO GARAGE RAMP & STAIRS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
42 |
Status |
P |
Date |
2008-11-03 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-11-03 |
Time |
13:54 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2008-11-03 |
Time |
13:54 |
Sent To |
|
|
Notes |
2008-11-03 13:59:32 | | | | | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: THORNTON- TOMASETTI | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | BUILDING PROVISO: | | NOV.03/08 | | REVISION: 20A | | SHEET: A1-GA.1 SECOND FLOOR PARKING LEVEL THE SOUTHWEST | | CORNER OF THE | | PARKING STRUCTURE PLANS INDICATE BOLLARDS LOCATED | | WITHIN THE ACCESS AISLE | | ASSOCIATED WITH DISABLED PARKING SPACE. PLEASE REMOVE | | BOLLARDS, REVIEW | | SECTION 11-4.6.3 MUST BE PART OF THE ACCESSIBLE ROUTE | | TO BUILDING OR FACILITY | | ENTRANCE. | | | | IM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
41 |
Status |
F |
Date |
2008-10-20 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-10-20 |
Time |
08:48 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2008-10-20 |
Time |
08:48 |
Sent To |
|
|
Notes |
2008-10-20 09:08:35 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: THORNTON- TOMASETTI | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | REVIEW: SHEET A0-D.1 REVISION# 16B | | | | ACTION: DENIED | | | | 1) STAIR SECTION THE HANDRAILIS ONLY 1'-6 INCHES LONG | | THIS IS THE DIMENSION TO BE USED FOR EXTENSIONS FOR | | RAMPS. 11-4.9.4(2) IF HANDRAILS ARE NOT CONTINUOUS, | | THEY SHALL EXTEND AT LEAST 12 INCHES (305 MM) BEYOND | | THE TOP RISER AND AT LEAST 12 INCHES (305 MM) PLUS THE | | WIDTH OF ONE TREAD BEYOND THE BOTTOM RISER. AT THE TOP, | | THE EXTENSION SHALL BE PARALLEL WITH THE FLOOR OR | | GROUND SURFACE. AT THE BOTTOM, THE HANDRAIL SHALL | | CONTINUE TO SLOPE FOR A DISTANCE OF THE WIDTH OF ONE | | TREAD FROM THE BOTTOM RISER; THE REMAINDER OF THE | | EXTENSION SHALL BE HORIZONTAL [SEE FIGURE 19 (C) AND | | FIGURE 19 (D)]. HANDRAIL EXTENSIONS SHALL COMPLY WITH | | SECTION 11-4.4 . | | | | 2) THE CONTINIOUS HANDRAIL EXTENSIONS FOR BOTH STAIRS | | AND HANDRAILS STATE IN SECTION 11-4.9.4 (2) WILL NEED | | TO COMPLY WITH SECTION 11-4.4.THE BOTTOM PART OF THE | | EXTENSION MUST BE NO HIGHER THAN27 INCHES. | | | | 3) THE RAMP DOES NOT INDICATE HOW EDGE PROTECTION WILL | | BE MET 11-4.8.7. | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
40 |
Status |
P |
Date |
2008-10-20 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-10-20 |
Time |
08:45 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2008-10-20 |
Time |
08:45 |
Sent To |
|
|
Notes |
2008-10-20 08:48:41 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: THORNTON- TOMASETTI | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | REVIEW: REVISION 16B | | | | ACTION: REVIEWED | | SHEET: A0-0,A0.1, A0-2, A0-3A0-4, A0-5 & A0-D.1 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
39 |
Status |
P |
Date |
2008-08-26 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-08-26 |
Time |
08:39 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2008-08-26 |
Time |
08:39 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
38 |
Status |
P |
Date |
2008-08-26 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-08-26 |
Time |
08:37 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2008-08-26 |
Time |
08:37 |
Sent To |
PC |
|
Notes |
2008-08-26 08:39:11 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: THORNTON- TOMASETTI | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*)MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | REVIEW: TROPICAL DESIGN- ATTACHMENT CALCULATIONS | | | | ACTION: REVIEWED |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
37 |
Status |
P |
Date |
2008-08-26 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-08-26 |
Time |
08:29 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2008-08-26 |
Time |
08:29 |
Sent To |
PC |
|
Notes |
2008-08-26 08:36:10 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: THORNTON- TOMASETTI | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*)MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | REVIEW: CALCULATIONS FOR PRE-CAST | | | | ACTION: REVIEWED |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
36 |
Status |
P |
Date |
2008-08-26 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-08-26 |
Time |
08:21 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2008-08-26 |
Time |
08:21 |
Sent To |
PC |
|
Notes |
2008-08-26 08:22:56 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: THORNTON- TOMASETTI | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*)MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | REVIEW: SHEET S-1 | | | | ACTION: REVIEWED |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
35 |
Status |
F |
Date |
2008-08-01 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-08-01 |
Time |
11:23 |
Rev Time |
1.22 |
Received By |
jwitmer |
Date |
2008-08-01 |
Time |
11:23 |
Sent To |
PC |
|
Notes |
2008-08-01 11:28:45 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: THORNTON- TOMASETTI | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*)MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | REVIEW: CALCULATIONS FOR ARCHITECTURAL PRECAST CONCRETE | | SIGN ATTACHMENT | | | | ACTION: DENIED | | | | 1) THE ENGINEER'S SIGNATURE ARE COPIES NOT ORIGINAL | | SIGNATURES. 61G15-23.002(2)FL. ADMIN. CODE. PLANS | | SIGNED & SEALED BY A PROFESSIONAL ENGINEER SHALL | | INCLUDE EITHER THE: NAME, ADDRESS AND LICENSE NUMBER OF | | THE ENGINEER OR, THE NAME AND LICENSE NUMBER OF THE | | ENGINEER AND THE NAME, ADDRESS AND CERTIFICATE OF | | AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS | | THROUGH WHICH THE ENGINEER IS PRACTICING (471.025 F.S. | | AND 471.023 F.S.). | | | | | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
34 |
Status |
P |
Date |
2008-08-01 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-08-01 |
Time |
10:49 |
Rev Time |
1.22 |
Received By |
jwitmer |
Date |
2008-08-01 |
Time |
10:49 |
Sent To |
PC |
|
Notes |
2008-08-01 10:50:35 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: THORNTON- TOMASETTI | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*)MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | REVIEW: WIND LOAD CALCULATIONS FOR LIGHT POLES | | | | ACTION: REVIEWED | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
33 |
Status |
P |
Date |
2008-06-30 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-06-30 |
Time |
13:46 |
Rev Time |
0.55 |
Received By |
jwitmer |
Date |
2008-06-30 |
Time |
13:46 |
Sent To |
PC |
|
Notes |
2008-06-30 13:48:19 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: THORNTON- TOMASETTI | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*)MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | REVIEW:SUBMITTAL | | | | ACTION:REVIEWED | | CAST STONE ATTACHMENT | | PARAPET WALL LIBRARY BARREL VAULT |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
32 |
Status |
P |
Date |
2008-06-03 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-06-03 |
Time |
11:25 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2008-06-03 |
Time |
11:25 |
Sent To |
PC |
|
Notes |
2008-06-03 11:27:19 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: THORNTON- TOMASETTI | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*)MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | REVIEW: GARAGE A CONNECTOR ROOF NOA & ROOF ENGINEERING | | | | ACTION: REVIEWED |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
31 |
Status |
P |
Date |
2008-06-03 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-06-03 |
Time |
11:24 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2008-06-03 |
Time |
11:24 |
Sent To |
PC |
|
Notes |
2008-06-03 11:25:35 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: THORNTON- TOMASETTI | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*)MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | REVIEW:GARAGE "A" STAIR ROOF NOA & ENGINEERING | | | | ACTION: REVIEWED |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
30 |
Status |
P |
Date |
2008-06-03 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-06-03 |
Time |
11:22 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2008-06-03 |
Time |
11:22 |
Sent To |
PC |
|
Notes |
2008-06-03 11:24:04 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: THORNTON- TOMASETTI | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*)MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | REVIEW: CITY CENTER GARING GARAGE PRECAST PILASTER | | CAPS | | | | ACTION: REVIEWED |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
29 |
Status |
F |
Date |
2008-05-12 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-05-12 |
Time |
11:28 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2008-05-12 |
Time |
11:28 |
Sent To |
PC |
|
Notes |
2008-05-12 11:37:40 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: THORNTON- TOMASETTI | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*)MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | REVISION REVIEW: LIBRARY BARREL VAULT PARAPET WALL | | | | ACTION: DENIED. | | | | 1) 61G15-23.002(2)FL. ADMIN. CODE. PLANS SIGNED & | | SEALED BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER | | THE: NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER | | OR, THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE | | NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER | | OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER | | IS PRACTICING (471.025 F.S. AND 471.023 F.S.). | | | | 61G15-23.002(2)FL. ADMIN. CODE. A COVER SHEET OR | | INDEX SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED | | AND THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF | | THE PRODUCTION & PREPARATION OF EACH SECTION OF THE | | ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION | | ON THE COVER SHEET OR INDEX. | | | | 2) PAGE 1 OF 5 INDICATES THE USE OF 3/4" CDX PLYWOOD TO | | BE USED AS A SUB-SHEATHING, NO WALL FINISH IS PROVIDED. | | PLEASE SEE SECTION 603.1.1.2 NONBEARING EXTERIOR WALLS | | WHERENO FIRE RESISTANCE RATING IS REQUIRED FIRE | | RESISTANCE TREATED PLYWOOD MAY BE INSTALLED. PLEASE | | CORRECT. | | | | | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE.) |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
28 |
Status |
P |
Date |
2008-05-12 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-05-12 |
Time |
11:16 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2008-05-12 |
Time |
11:16 |
Sent To |
|
|
Notes |
2008-05-12 11:28:22 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: THORNTON- TOMASETTI | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*)MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | REVISION REVIEW: | | | | ACTION: REVIEWED | | | | NOTICE OF ACCEPTANCE: 061005746" LOUVER SYSTEM MODEL | | EA 64. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
27 |
Status |
P |
Date |
2008-05-08 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-05-08 |
Time |
12:52 |
Rev Time |
3.33 |
Received By |
jwitmer |
Date |
2008-05-08 |
Time |
12:52 |
Sent To |
FIRE |
|
Notes |
2008-05-08 12:53:41 | CITY HALL/ CITY CENTER REVISION# 14E | | | | BUILDING PLAN REVIEW | | PERMIT: 06100574 | | ADD: 401 CLEMATIS ST. | | CONT: CATALFUMO | | TEL: (561)307-4746 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVISION # 14E | | | | ACTION: REVIEWED-OK |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
26 |
Status |
F |
Date |
2008-04-18 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-04-18 |
Time |
11:47 |
Rev Time |
0.56 |
Received By |
jwitmer |
Date |
2008-04-18 |
Time |
11:47 |
Sent To |
|
|
Notes |
2008-04-18 12:20:17 | CITY HALL/ CITY CENTER REVISION# 14D | | | | BUILDING PLAN REVIEW | | PERMIT: 06100574 | | ADD: 401 CLEMATIS ST. | | CONT: CATALFUMO | | TEL: (561)307-4746 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVISION # 14D | | | | ACTION: DENIED | | | | 1) SHEET A1-1.1 COMMISION CHAMBERS NOW ARE SHOWN AS A 1 | | HRRATED WALL BUT WINDOWS G-10 & G-11ON SHEET A8-2.1 | | INDICATES WINDOWS NOT RATED, SEE TABLE 715.3 OPENING | | PROTECTION. | | | | 2)SEE PLANS THERE ARE (3) AREAS THAT ARE MISSING 1 HR | | RATING IN THE 1 HR RATED WALL AROUND THE CORRIDOR. | | | | 3) A1-1.2 W4-8/ 1 HR WALL RATING IS SHOWN AT THE | | LOADING DOCK WALL BUT THERE IS NO WALL TAGS SHOWN ON | | SHEET A5-D.1. | | | | 4) A1-1.2 W4-8/ 1 HR LOADING DOCK/ CORRIDOR WALL SHOULD | | INDICATE AS A FIRE-SMOKE DESIGNATION. | | | | 5) A1-1.2 TRASH ROOM/ CALL CENTER W4-8 NO WALL TYPE THE | | MECH AND LS BOTH INDICATE AS SUCH. | | | | 6) A1-1.2 COORIDOR D1.006 LS & MECHANICAL INDICATE | | SMOKE RATING WHILE LS INDICATES AN EXIT AT DOOR D1-004A | | WHICH IS A FIRE/ SMOKE RATED CORRIDOR, INACTED BY THE | | MUSEUM BEING A A-3 OCCUPANCY. | | | | 7) A1-1.2 VESTIBULE D1.005 IS TRUELY A EXIT PASSAGEWAY | | NOT A VESTIBULE, THE COMMON WALL BILLING / VESTIBULE | | SHOULD BE A 2 HR RATED WALL, (EXIT PASSAGEWAY). SEE | | MECHANICAL COMMENTS DUCT PENETRATING EXIT. | | | | 8) WALL TYPE P2-4 ON SHEET A5-D.1 DOES NOT INDICATE | | SMOKE RATING. | | | | 9)A1-1.2 LOBBY C1.008 IT APPEARS 3 POSSIBLE BOOK | | RETURNS IN THE 1 HR RATED WALL, PLEASE PROVIDE | | ADDITIONAL DETAILS FOR FIRE RATING OF THIS AREA. | | 106.1.2 ADDITIONAL INFORMATION REQUIRED. | | | | 10)A1-1.2 PLEASE REVIEW STORAGE AREAS ON MECH PLAN | | C1.403 & C1.404 INDICATE THE USE OF TRANSFER OPENINGS | | THERE ARE NO SMOKE DAMPERS PROVIDED 710.7. | | | | 11) A1-2.1 MISSING A REVISION FOR THE ARCHITECTURAL | | SHEET, LS AND MECH PLANS INDICATE SMOKE PARTITIONS AT | | THE STORAGE A2.303 | | | | 12)A1-2.1 MISSING A REVISION FOR THE ARCHITECTURAL | | SHEET, SHAFT WALL COMMON TO THE MONUMENTAL STAIR DOES | | NOT INDICATE A 2HR FIRE RATING WALL TAG. | | | | 13) A1-2.2 (2) ISSUES WITH 707.2 EXCEPTION# 3: | | 13A) STAIR TO MEZZANINE THE DOOR AND WALL NOT RATED, | | SINCE THERE IS NO WALL RATING AT THE MEZZANINE WALL | | LEVEL THIS WILL CREATE THE FLOOR LEVEL FIRE RATING | | BETWEEN FLOORS. | | 13B) THE SAME AREA WHERE THE SHAFT WALL COMES OUT OF | | THE MEZZANINE LEVEL WILL NEED A 1 HR RATED SHAFT WALL. | | | | 14) A1-2.2PLEASE REVIEW THE DOOR LOCATION FOR THE | | ENTRY TO THE MEZZANINE LEVEL , REVIEW ARCHITECTURAL, LS | | BOTH THE OVERALL FLOOR PLAN AND THE MEZZANINE LEVEL | | CORRELATE. | | | | 15) LS1-3.1 REVISIONS SUBMITTED BUT NO ARCHITECTURAL | | SHEETS. | | | | 16) LS 1-3.1 / A1-3.1 & M1-3.1 MISSING ROOM I.D. BY | | CORRIDOR A3.604 & A3.115. | | | | 17) LS1-3.2 THE PLANS DO NOT INDICATE WALL RATING | | BETWEEN THE PRE-FUNCTION AREA AND THE THE LOBBY C3.301 | | ALTHOUGH THE DOORS INDICATE A 20 MINUTE RATING, THIS | | SHOULD BE PART OF THE 1 HOUR RATED DORRIDOR TABLE 1016, | | (A) OCCUPANCY > THAN 30. | | | | 18) RESTROOM EXHAUST 1ST FLOOR THROUGH THE 4 TH FLOOR | | LIBRARY, 5TH FLOOR CITY HALL, ARE NOT INDICATED AS | | BEING IN 2 HR RATED SHAFTS. 716.6. | | | | 19) SHEET LS1.2.2 & A1-2.2 EXIT ACCESS CORRIDOR ON GRID | | LINE COLUMN LINE J & 6 SHOULD HAVE A 1 HR FIRE RATING | | AND DOORS ADDED AGAIN THIS IS AN (A3) OCCUPANCY WITH AN | | OCCUPANT LOAD GREATER THAN 30. TABLE 1016. | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)805-6731 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
25 |
Status |
P |
Date |
2007-11-27 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-11-27 |
Time |
15:56 |
Rev Time |
1.55 |
Received By |
jwitmer |
Date |
2007-11-27 |
Time |
15:56 |
Sent To |
PC |
|
Notes |
2007-11-27 15:57:34 | SHOP DRAWINGS SCAFFOLDING SHOP DRAWINGS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
24 |
Status |
P |
Date |
2007-11-06 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-11-06 |
Time |
09:51 |
Rev Time |
2.22 |
Received By |
jwitmer |
Date |
2007-11-06 |
Time |
09:50 |
Sent To |
|
|
Notes |
2007-11-06 09:53:17 | REVISION# 12A CATCH UP OF REVISIONS 8,9,10,11 & 12. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
23 |
Status |
P |
Date |
2007-09-28 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-09-28 |
Time |
08:45 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2007-09-28 |
Time |
08:45 |
Sent To |
PC |
|
Notes |
2007-09-28 08:46:57 | SHORING CALCULATIONS AND SHOP DRAWINGS FOR MEZZANINE | | STAIRS TO ROOF |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
22 |
Status |
F |
Date |
2007-09-18 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-09-18 |
Time |
14:30 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2007-09-18 |
Time |
15:09 |
Sent To |
|
|
Notes |
2007-09-18 15:09:12 | CITY HALL/ CITY CENTER REVISION# 11 | | | | BUILDING PLAN REVIEW | | PERMIT: 06100574 | | ADD: 401 CLEMATIS ST. | | CONT: CATALFUMO | | TEL: (561)307-4746 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVISION # 11 | | | | ACTION: DENIED | | | | | | NOTES SHEET A8-0.2 FOOTNOTE D DOOR SHALL HAVE | | CLOSER | | FOOTNOTE E SMOKE | | AND DRAFT CONTROL ASSEMBLY W/ ARTIFICIAL BOTTOM SEAL | | | | INSTALLED ACROSS THE FULL WIDTH OFTHE BOTTOM OF THE | | DOOR ALL | | | | IN COMPLIANCE WITHUL 1784. | | | | 1) SHEET A1-1.1: | | 1A) DOOR A1-120A IS MISSING FOOTNOTE "D & E" | | 1B) DOOR A1-201A IS MISSING FOOTNOTE "E" | | 1C) SECURITY DESKA 1 HR RATED WALL IN FRONT OF DESK, | | PLEASE SEE A9.3.1 DETAIL# 4, NOW IS MISSING RATED WALL | | AND DOORWAY | | 1D) RECEPTION DESK A 1 HR RATED WALL PLEASE SEE A9-3.1 | | DETAIL# 3 NOW HAS BY PASS WINDOWS, 1 HR RATED? | | | | 2) SHEET A1-2.1 | | 2A) DOOR A2-008-A 1 HR RATED DOOR MISSING FOOTNOTE | | "D&E" | | 2B) DOOR A2-001-A1 HR RATED DOOR MISSING FOOTNOTE | | "D&E" | | | | 3)SHEET A1-3.2 : | | 3A)DOOR C3-105-A, 1 HR RATED DOOR IS MISSING FOOTNOTE | | "D&E" | | 3B) DOOR C3-106-A , 1 HR RATED DOOR IS MISSING FOOTNOTE | | "D&E" | | 3C) DOOR C3-107-A, 1 HR RATED DOOR ISMISSING FOOTNOTE | | "D&E" | | 3D)DOOR C3-108-A, 1 HR RATED DOOR IS MISSING FOOTNOTE | | "D&E" | | 3E)DOOR C3-109-A, 1 HR RATED DOOR IS MISSING FOOTNOTE | | "D&E" | | | | NOTE MEETING AT CONSTRUCTION SITE 9-18-07 : | | | | 1) DISCUSSED THE NEED FOR CUT SECTIONS OF THE | | STAIRTOWER# 10 THIRD FLOOR INDICATING A 2 HR RATING | | BETWEEN THE A/C DUCT AND | | STAIRWELL AS WELL AS THE MOVING THE FIRE DAMPERS FROM | | WITHIN THE STAIRTOWER WALLS TO ALLOW FOR ACCESS PANELS | | OUTSIDE OF THE STAIR TOWER. | | | | 2) STIAR WAY # 11 DISCUSSED THE NEED OF A CUT SECTION | | THROUGH THE STAIRWAY INDICATING THE PLACEMENT OF THE | | MEZZANINE FLOOR THAT WILL KEEP THE DUCTWORK FROM | | ENTERING STAIRTOWER #7. | | | | 3) THE THIRD ISSUE THAT WAS ALSO BROUGHT UP THAT NO | | SHAFT WALL WILL BE NECESSARY IN THE MEZZANINE STAIRWAY | | SINCE IT IS WITHIN THE STORY. THERE ARE CONCERNS ON THE | | REQUIRED WIDTH OF THE STAIR! | | | | 4) SHEET A8-0.1DOORS MISSING FOOTNOTE :1 HR RATED | | DOOR MISSING FOOTNOTE "D&E" | | A1-120-A | | A1-201-A | | A2-008-A | | A2-001-A | | | | 5) SHEET A8-0.2 DOORS MISSING FOOTNOTE: 1 HR RATED DOOR | | MISSING FOOTNOTE "D&E" | | C3-105-A | | C3-106-A | | C3-107-A | | C3-108-A | | C3-110-A | | | | 6)SHEET A9-3.1 COMMENT 1C & 1D. | | | | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS | | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF | | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST | | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT | | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC | | REQUIREMENT, THE SPECIFIC | | REQUIREMENT SHALL BE APPLICABLE. | | | | BUILDING PLAN REVIEW | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
21 |
Status |
P |
Date |
2007-09-17 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-09-17 |
Time |
08:42 |
Rev Time |
0.55 |
Received By |
jwitmer |
Date |
2007-09-17 |
Time |
08:42 |
Sent To |
PC |
|
Notes |
2007-09-17 08:43:24 | LIBRARY 5TH FLOOR SHORING PLAN |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
20 |
Status |
P |
Date |
2007-09-02 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-09-02 |
Time |
08:51 |
Rev Time |
0.75 |
Received By |
jwitmer |
Date |
2007-09-02 |
Time |
08:51 |
Sent To |
|
|
Notes |
2007-09-02 08:52:59 | REVISIONS # 11& 12 SHEETSA1-GA.2 & A1- GA.3OK |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
19 |
Status |
F |
Date |
2007-09-02 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-09-02 |
Time |
07:44 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2007-09-02 |
Time |
07:11 |
Sent To |
|
|
Notes |
2007-09-02 08:48:58 | BUILDING PLAN REVIEW | | PERMIT: 06100574 | | ADD: 401 CLEMATIS ST | | CONT: CATALFUMO | | TEL: (561)307-4746 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVISION # 11-12REVIEW | | ACTION: DENIED | | | | 1) GARAGE MAIN ELECTRIC ROOM B1.103THE FLOOR IS NOW | | DROPPED DOOR B1-103-AIS INDICATED WITH A PAIR OF 3'-0" | | OUTSWING DOORS AND A LANDING AND STAIR THAT IS ONLY | | 3'-0" WIDE. | | THE PLAN DOESN'T INDICATE THE PRESENCE OF A HANDRAIL | | SYSTEM OR NOTE AS SUCH. THE PLAN ALSO INDICATES THE (2) | | RISERS TO BE 6 7/16" INCHES AND TREAD DEPTH OF 11". | | 1003.5.1 | | WHERE A CHANGE IN LEVEL MEANS OF EGRESS NOT EXCEEDING | | 21 INCHES (533 MM) IS ACHIEVED BY A STAIR, THE MINIMUM | | TREAD DEPTH OF SUCH STAIR SHALL BE 13 INCHES (330 MM) | | AND THE PRESENCE AND LOCATION OF EACH STEP SHALL BE | | READILY APPARENT. | | | | 2)BOTH THE ELECTRIC ROOM AND MECHANICAL ROOM INDICATE | | THE FLOOR SLAB IS NOW RECESSED 6" PLEASE PROVIDE THE | | INFORMATION HOW **READILY APPARENT** WILL BE | | ACCOMPLISHED IN SECTION 1003.5.1. | | | | 3) GARAGE MAIN ELECTRIC ROOM B1.103 DOOR B1-103-B IS AN | | OUTSWING DOOR WITH AUTOMATIC CLOSER WITH LATCHSEE | | A8-0.1 NOTES D & E AND SEE A8-0.2DOOR SCHEDULE. WITH | | THE DOOR | | HAVING A CLOSER AND LATCH THE LANDING ON THE INTERIOR | | OF THE ROOM SHOULD EXTEND A MINIMUM OF 12" SEE | | MANEUVERING CLEARENCE AT DOORS FIGURE 25(A) THE LANDING | | WOULD NEED TO BE A MINIMUM OF 48" DEEP.11-4.13.6 | | MANEUVERING CLEARENCES AT DOORS. MINIMUM MANEUVERING | | CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC OR | | POWER-ASSISTED SHALL BE AS SHOWN IN | | FIG. 25. THE FLOOR OR GROUND AREA WITH IN THE REQUIRED | | CLEARANCES SHALL BE CLEAR & LEVEL. | | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS | | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF | | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST | | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT | | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC | | REQUIREMENT, THE SPECIFIC | | REQUIREMENT SHALL BE APPLICABLE. | | | | 4) SHEET S1-1.0THE EXTERIOR OF THE MAIN ELECTRIC ROOM | | IN THE GARAGE PORTION OF THE PLAN INDICATES A SINGLE | | 3'-0" DOORWAY WHERE AS THE ARCHITECTURAL SHEETS | | INDICATE A PAIR OF DOORS. | | PLEASE CORRELATE PLAN DETAILS.106.1.2*ADDITIONAL | | INFORMATION REQUIRED. | | | | 5) ONE SET OF PLANS IS MISSING SHEET A1-GA.1 THERE ARE | | (2) A1-GA.3 IN SET. | | | | BUILDING PLAN REVIEW | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
18 |
Status |
P |
Date |
2007-08-26 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-08-26 |
Time |
14:27 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2007-08-26 |
Time |
13:50 |
Sent To |
FIRE |
|
Notes |
2007-08-26 14:28:49 | REV # 10 A3-3.0 & A3-3.2 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
17 |
Status |
P |
Date |
2007-08-23 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-08-23 |
Time |
16:31 |
Rev Time |
2.55 |
Received By |
jwitmer |
Date |
2007-08-23 |
Time |
16:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
16 |
Status |
P |
Date |
2007-08-17 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-08-17 |
Time |
15:43 |
Rev Time |
0.33 |
Received By |
jwitmer |
Date |
2007-08-17 |
Time |
15:43 |
Sent To |
PC |
|
Notes |
2007-08-17 15:44:53 | SUBMITTAL: SHOP DRAWINGS 3RD FLOOR LIBRARY SHORING / | | RESHORING PLANS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
15 |
Status |
P |
Date |
2007-08-01 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-08-01 |
Time |
13:27 |
Rev Time |
0.55 |
Received By |
jwitmer |
Date |
2007-08-01 |
Time |
13:23 |
Sent To |
|
|
Notes |
2007-08-01 13:28:44 | LIBRARY 3RD LEVEL SHORING AND RESHORING PLANS AND | | CALCULATIONS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
14 |
Status |
P |
Date |
2007-07-12 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-07-12 |
Time |
14:47 |
Rev Time |
1.33 |
Received By |
jwitmer |
Date |
2007-07-12 |
Time |
14:47 |
Sent To |
PC |
|
Notes |
2007-07-12 14:48:06 | REV# 6 & 9. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
13 |
Status |
P |
Date |
2007-07-06 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-07-06 |
Time |
12:12 |
Rev Time |
0.25 |
Received By |
jwitmer |
Date |
2007-07-06 |
Time |
12:12 |
Sent To |
PC |
|
Notes |
2007-07-06 12:39:55 | CALCULATIONS FROM UNITED FORMING POUR 2& 3 SHORING | | UNITED FORMING CAST-IN-PLACE CONCRETE FRAMING & SHORING | | CALCULATIONS | | UNITED FORMING CAST-IN-PLACE CONCRETE FRAMING & SHORING | | CALCULATIONS LEVEL 6 | | UNITED FORMING CAST-IN-PLACE CONCRETE FRAMING & SHORING | | CALCULATIONS LEVEL 7 & CAPITAL DOME | | 2ND LEVEL GAGARE POUR 1 | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
12 |
Status |
P |
Date |
2007-07-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-06-12 |
Time |
11:10 |
Rev Time |
1.55 |
Received By |
jwitmer |
Date |
2007-07-06 |
Time |
08:03 |
Sent To |
|
|
Notes |
2007-07-06 08:05:04 | ROOF DOME, & BARREL ROOF SHOP DRAWINGS | 2007-06-04 11:24:15 | TO "JWITMER" DESK/SUBMITTAL |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
11 |
Status |
F |
Date |
2007-05-31 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-05-31 |
Time |
15:35 |
Rev Time |
0.55 |
Received By |
jwitmer |
Date |
2007-05-31 |
Time |
15:35 |
Sent To |
PC |
|
Notes |
2007-05-31 15:38:42 | BUILDING PROVISO: TRAINER GLASS HAS NOT SUBMITTED THE | | SITE SPECIFIC NOA FROM MIAMI-DADE FROM HURRICANE TEST | | LAB # 0062-0310-00. | | | | BUILDING PLAN REVIEW | | JIM WITMER C. B. O. | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
10 |
Status |
P |
Date |
2007-05-31 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-05-31 |
Time |
15:33 |
Rev Time |
3.33 |
Received By |
jwitmer |
Date |
2007-05-31 |
Time |
15:33 |
Sent To |
PC |
|
Notes |
2007-05-31 15:35:27 | REVISION NUMBER 8 REVIEWED WITH THE EXCEPTION OF | | REFLECTED CEILING PLANS, SEE ELECTRICAL COMMENT# 7 | | ABOUT LIGHTING PLAN AND PHOTO-METRICS. MAY CHANGE WITH | | THIS REQUIREMENT NOT BEING MET. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
9 |
Status |
F |
Date |
2007-05-07 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-05-07 |
Time |
08:38 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2007-05-07 |
Time |
08:38 |
Sent To |
PC |
|
Notes |
2007-05-07 08:56:54 | BUILDING PLAN REVIEW | | PERMIT: 06100574 | | ADD: 401 CLEMATIS ST | | CONT: CATALFUMO CONSTRUCTION | | TEL: (561)307-4746 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW | | ACTION: DENIED | | | | PLANS, SPECIFICATIONS, REPORTS OR | | OTHER DOCUMENTS PREPARED BY THE | | DESIGN PROFESSIONAL AND BEING FILED FOR PUBLIC | | RECORD SHALL HAVE THE SIGNATURE AND | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | TO THE DOCUMENT. | | FL STATE STAT: 61G15-23.002 ENGINEERS | | FL ATATE STAT: 61G16.003 ARCHITECTS | | | | CALCULATIONS , POUR AND SHORING REPORTS 2 & 3 COPIES OF | | SIGNATURE NOT ORIGINALS, (2) COPIES WILL BE RETAINED TO | | FOWARD TO STATE ENGINEER'S BOARD. | | | | BUILDING PLAN REVIEW | | JIM WITMER C. B. O. | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
8 |
Status |
F |
Date |
2007-04-03 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-04-03 |
Time |
09:54 |
Rev Time |
1.11 |
Received By |
jwitmer |
Date |
2007-04-03 |
Time |
09:54 |
Sent To |
PC |
|
Notes |
2007-04-03 10:20:52 | BUILDING PLAN REVIEW | | PERMIT: 06100574 | | ADD: 401 CLEMATIS ST | | CONT: CATALFUMO | | TEL: (561)307-4776 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVISION# 6REVIEW | | ACTION: DENIED | | | | 1)ONE SET OF PLANS WILL BE RETAINED FOR POSSIBLE | | SUBMITTAL TO THE STATE. PLANS INDICATE REVISION# 6 | | PRINTED ON 2-19-07 BUT THE DESIGNER OF RECORD SIGNED | | AND SEALED THEM ON 2-13-07, SIX DAYS BEFORE THEY WERE | | PRINTED. WHAT IS REALLY PECULIAR THAT BOTH THE | | ARCHITECT AND STRUCTURAL ENGINEER WOULD MAKE THE SAME | | MISTAKE....... | | | | ARCHITECT'S | | 61G1-16.003 USE OF SEAL. | | THE PERSONAL SEAL, SIGNATURE AND DATE OF THE ARCHITECT | | OR INTERIOR DESIGNER SHALL APPEAR ON ALL ARCHITECTURAL | | OR INTERIOR DESIGN DOCUMENTS TO BE FILED FOR PUBLIC | | RECORD AND SHALL BE CONSTRUED TO OBLIGATE HIS PARTNERS | | OR HIS CORPORATION. A CORPORATE SEAL ALONE IS | | INSUFFICIENT. DOCUMENTS SHALL BE SIGNED PERSONALLY AND | | SEALED BY THE RESPONSIBLE ARCHITECT OR INTERIOR | | DESIGNER. FINAL OFFICIAL RECORD DOCUMENTS (NOT | | TRACINGS, ETC.) SHALL BE SO SIGNED. THE SIGNING AND | | SEALING OF THE SPECIFICATION INDEX SHEETS SHALL BE | | CONSIDERED ADEQUATE. ALL DRAWING SHEETS AND PAGES SHALL | | BE SO SIGNED AND SEALED. AN ARCHITECT OR INTERIOR | | DESIGNER SHALL NOT AFFIX, OR PERMIT TO BE AFFIXED, HIS | | SEAL OR NAME TO ANY PLAN, SPECIFICATIONS, DRAWINGS, OR | | OTHER RELATED DOCUMENT WHICH WAS NOT PREPARED BY HIM OR | | UNDER HIS RESPONSIBLE SUPERVISING CONTROL AS PROVIDED | | IN RULE CHAPTER 61G1-23, F.A.C. AN ARCHITECT OR | | INTERIOR DESIGNER SHALL NOT USE HIS SEAL OR DO ANY | | OTHER ACT AS AN ARCHITECT OR INTERIOR DESIGNER UNLESS | | HOLDING AT THE TIME A CERTIFICATE OF REGISTRATION AND | | ALL REQUIRED RENEWALS THEREOF. | | SPECIFIC AUTHORITY 481.2055, 481.221 FS. LAW | | IMPLEMENTED 481.221, 481.225(1)(E), (G), (J), | | 481.2251(1)(G), (H), (I) FS. HISTORY?NEW 12-23-79, | | FORMERLY 21B-16.03, AMENDED 7-27-89, FORMERLY | | 21B-16.003, AMENDED 11-21-94, 4-18-00. | | | | ENGINEER'S | | 61G15-23.002 SEAL, SIGNATURE AND DATE SHALL BE | | AFFIXED. | | (1) A PROFESSIONAL ENGINEER SHALL SIGN HIS NAME AND | | AFFIX HIS SEAL TO ALL PLANS, SPECIFICATIONS, REPORTS, | | FINAL BID DOCUMENTS PROVIDED TO THE OWNER OR THE | | OWNER?S REPRESENTATIVE, OR OTHER DOCUMENTS PREPARED OR | | ISSUED BY SAID REGISTRANT AND BEING FILED FOR PUBLIC | | RECORD. THE DATE THAT THE SIGNATURE AND SEAL IS AFFIXED | | AS PROVIDED HEREIN SHALL BE ENTERED ON SAID PLANS, | | SPECIFICATIONS, REPORTS, OR OTHER DOCUMENTS IMMEDIATELY | | UNDER THE SIGNATURE OF THE PROFESSIONAL ENGINEER. (2) | | EACH SHEET OF PLANS AND PRINTS WHICH MUST BE SEALED | | UNDER THE PROVISIONS OF CHAPTER 471, F.S., SHALL BE | | SEALED, SIGNED AND DATED BY THE PROFESSIONAL ENGINEER | | IN RESPONSIBLE CHARGE. ENGINEERS SHALL LEGIBLY INDICATE | | THEIR NAME, ADDRESS, AND LICENSE NUMBER ON EACH SHEET. | | IF PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING | | BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME | | AND LICENSE NUMBER, AS WELL AS, THE NAME, ADDRESS, AND | | CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGINEERING | | BUSINESS ON EACH SHEET. A TITLE BLOCK ON EACH SHEET | | CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE | | NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND | | LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS | | AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE | | ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT. | | ENGINEERS WORKING FOR LOCAL, STATE OR FEDERAL | | GOVERNMENT AGENCIES SHALL LEGIBLY INDICATE THEIR NAME | | AND LICENSE NUMBER, AND MAY INDICATE THE NAME AND | | ADDRESS OF THE AGENCY. A COVER OR INDEX SHEET FOR | | ENGINEERING SPECIFICATIONS MAY BE USED AND THAT SHEET | | MUST BE SIGNED, SEALED AND DATED BY THOSE PROFESSIONAL | | ENGINEERS IN RESPONSIBLE CHARGE OF THE PRODUCTION AND | | PREPARATION OF EACH SECTION OF THE ENGINEERING | | SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER | | SHEET OR INDEX SO THAT THE USER WILL BE AWARE OF EACH | | PORTION OF THE SPECIFICATIONS FOR WHICH EACH | | PROFESSIONAL ENGINEER IS RESPONSIBLE. ENGINEERING | | REPORTS MUST BE SIGNED, SEALED AND DATED ON A SIGNATURE | | PAGE OR COVER LETTER BY EACH PROFESSIONAL ENGINEER WHO | | IS IN RESPONSIBLE CHARGE OF ANY PORTION OF THE REPORT. | | A PROFESSIONAL ENGINEER MAY ONLY SEAL AN ENGINEERING | | REPORT, PLAN, PRINT OR SPECIFICATION IF THAT | | PROFESSIONAL ENGINEER WAS IN RESPONSIBLE CHARGE OF THE | | PREPARATION AND PRODUCTION OF THE ENGINEERING DOCUMENT | | AND THE PROFESSIONAL ENGINEER HAS THE EXPERTISE IN THE | | ENGINEERING DISCIPLINE USED IN PRODUCING THE | | ENGINEERING DOCUMENT IN QUESTION. | | (3) A PROFESSIONAL ENGINEER SHOULD NOT SEAL ORIGINAL | | DOCUMENTS MADE OF MYLAR, LINEN, SEPIA OR OTHER | | MATERIALS WHICH CAN BE CHANGED BY THE ENTITY WITH WHOM | | SUCH DOCUMENT(S) ARE FILED UNLESS THE PROFESSIONAL | | ENGINEER ACCOMPANIES SUCH DOCUMENT(S) WITH A SIGNED AND | | SEALED LETTER MAKING THE RECEIVER AWARE THAT COPIES OF | | THE ORIGINAL DOCUMENT AS DESIGNED BY THE PROFESSIONAL | | ENGINEER HAVE BEEN RETAINED BY THE PROFESSIONAL | | ENGINEER AND THAT THE PROFESSIONAL ENGINEER WILL NOT BE | | RESPONSIBLE FOR ANY SUBSEQUENT CHANGES TO THE | | REPRODUCIBLE ORIGINAL DOCUMENTS. | | (4) A PROFESSIONAL ENGINEER SHOULD NOT SEAL PRELIMINARY | | PLANS WHICH ARE NOT INTENDED FOR PERMIT, CONSTRUCTION, | | OR BIDDING PURPOSES. IF A PERMITTING AGENCY REQUIRES | | THAT PRELIMINARY PLANS SUBMITTED FOR REVIEW PURPOSES BE | | SIGNED AND SEALED, THEN THE ENGINEER SHOULD CLEARLY | | NOTE SUCH LIMITATIONS ON THE FACE OF THE PLANS, BY | | USING TERMS SUCH AS ?PRELIMINARY,? ?FOR REVIEW ONLY,? | | ?NOT FOR CONSTRUCTION,? OR ANY OTHER SUITABLE STATEMENT | | WHICH DENOTES THAT THE DOCUMENTS ARE FOR DESIGN REVIEW | | ONLY AND ARE NOT INTENDED FOR PERMIT, CONSTRUCTION, OR | | BIDDING PURPOSES. | | (5) ENGINEERS WHO WISH TO SIGN AND SEAL ELECTRONICALLY | | TRANSMITTED PLANS, SPECIFICATIONS, REPORTS, FINAL BID | | DOCUMENTS, OR OTHER DOCUMENTS SHALL FOLLOW THE | | PROCEDURES SET FORTH IN RULE 61G15-23.003, F.A.C. | | SPECIFIC AUTHORITY 471.025 FS. LAW IMPLEMENTED 471.025 | | FS. HISTORY?NEW 1-8-80, AMENDED 1-20-85, FORMERLY | | 21H-23.02, AMENDED 5-14-86, FORMERLY 21H-23.002, | | AMENDED 11-15-94, 8-18-98, 2-3-00, 2-22-01, 2-5-04. | | | | BUILDING PLAN REVIEW | | JIM WITMER C. B. O. | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
7 |
Status |
P |
Date |
2007-03-28 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-03-28 |
Time |
11:18 |
Rev Time |
1.33 |
Received By |
jwitmer |
Date |
2007-03-28 |
Time |
11:17 |
Sent To |
B |
|
Notes |
2007-03-28 11:19:32 | SHORING & RESHORING PLANS REVISED 2/13/07 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
F |
Date |
2007-03-01 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-03-01 |
Time |
08:58 |
Rev Time |
1.11 |
Received By |
jwitmer |
Date |
2007-03-01 |
Time |
08:58 |
Sent To |
FIRE |
|
Notes |
2007-03-01 09:13:56 | BUILDING PLAN REVIEW | | PERMIT: 06100574 | | ADD: 401 CLEMATIS ST | | CONT: CATALFUMO | | TEL: (561)282-8265 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2005 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVISION # 6REVIEW | | ACTION: DENIED | | | | SHEETS: A1-GA.1, | | A1-GA.2 | | A1-GA.3 | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 2) SHEETS A1-GA.1, A1-GA.2 & A1-GA.3, | | ALL SHOW EXHAUST FANS BUT THE HEIGTH ABOVE THE FINISH | | FLOOR SLAB HAS NOT BEEN PROVIDED OR A CUT SECTION | | THAT WOULD PROVIDE AT WHAT ELEVATION THE BOTTOM OF THE | | ENCLOSURE WILL BE ABOVE THE FINISH FLOOR SLAB. | | 11-4.4.1 GENERAL. | | OBJECTS PROJECTING FROM WALLS (FOR EXAMPLE, TELEPHONES) | | WITH THEIR LEADING EDGES BETWEEN 27 INCHES AND 80 | | INCHES (685 MM AND 2030 MM) ABOVE THE FINISHED FLOOR | | SHALL PROTRUDE NO MORE THAN 4 INCHES (102 MM) INTO | | WALKS, HALLS, CORRIDORS, PASSAGEWAYS, OR AISLES [SEE | | FIGURE 11-8 (A)]. OBJECTS MOUNTED WITH THEIR LEADING | | EDGES AT OR BELOW 27 INCHES (685 MM) ABOVE THE FINISHED | | FLOOR MAY PROTRUDE ANY AMOUNT [SEE FIGURE 11-8 (A) AND | | FIGURE 11-8 (B)]. FREE-STANDING OBJECTS MOUNTED ON | | POSTS OR PYLONS MAY OVERHANG 12 INCHES (305 MM) MAXIMUM | | FROM 27 INCHES TO 80 INCHES (685 MM TO 2030 MM) ABOVE | | THE GROUND OR FINISHED FLOOR [SEE FIGURE 11-8 (C) AND | | FIGURE 11-8 (D)]. PROTRUDING OBJECTS SHALL NOT REDUCE | | THE CLEAR WIDTH OF AN ACCESSIBLE ROUTE OR MANEUVERING | | SPACE [SEE FIGURE 11-8 (E)]. | | | | 11-4.4.2 HEADROOM. | | WALKS, HALLS, CORRIDORS, PASSAGEWAYS, AISLES, OR OTHER | | CIRCULATION SPACES SHALL HAVE 80 INCHES (2030 MM) | | MINIMUM CLEAR HEAD ROOM [SEE FIGURE 11-8 (A)]. IF | | VERTICAL CLEARANCE OF AN AREA ADJOINING AN ACCESSIBLE | | ROUTE IS REDUCED TO LESS THAN 80 INCHES (2032 MM) | | (NOMINAL DIMENSION), A BARRIER TO WARN BLIND OR | | VISUALLY-IMPAIRED PERSONS SHALL BE PROVIDED [SEE FIGURE | | 11-8 (C-1)]. | | | | 3)PLEASE SEE ELECTRICAL COMMENTS FOR SHEET A1-GA.3 | | CONCERNING THE LOCATION OF THE FENCE AND THE LOCATION | | OF GENERATOT TO GENERATOR ON THE ROOF TOP OF THE | | PARKING GARAGE. | | | | BUILDING PLAN REVIEW | | JIM WITMER C. B. O. | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2007-03-01 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-03-01 |
Time |
08:53 |
Rev Time |
3.00 |
Received By |
jwitmer |
Date |
2007-03-01 |
Time |
08:53 |
Sent To |
FIRE |
|
Notes |
2007-03-01 08:58:21 | REV. # 6 DATED2/19/07 REVIEWED WITH THE EXCEPTION OF | | SHEETS A1-GA.1 | | DURA-STRESS GARAGE SHOP DRAWINGS | | | | DURA-STRESS GARAGE DESIGN CALCULATIONS | | | | DURA-STRESS CONNECTION DETAILS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2007-02-20 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-02-20 |
Time |
14:54 |
Rev Time |
7.77 |
Received By |
jwitmer |
Date |
2007-02-20 |
Time |
10:17 |
Sent To |
|
|
Notes |
2007-02-20 11:07:00 | | | *** ISSUED PERMIT*** | | -PLAN REVIEW HISTORY- | | | | PERMIT# 06100574 | | ADDRESS: 401 CLEMATIS ST | | CONT: CATALFUMO | | TELL # (561) 694-3000 | | | | THE ATTACHED COMMENTS ARE PART OF THE | | PERMIT AND PLAN REVIEW PACKAGE AND ARE | | NOT TO BE REMOVED FROM THE ISSUED SET OF PLANS. 106.1.1 | | ADMINISTRATIVE CODE/ 06. | | | | | | BUILDING PROVISOS: | | 1 ) 109.3.10* IMPACT OF CONSTRUCTION. | | ALL CONSTRUCTION ACTIVITY REGULATED BY | | THIS CODE SHALL BE PERMORMED IN A MANNER | | SO AS NOT TO ADVERSELY IMPACT THE | | CONDITION OF ADJACENT PROPERTY, UNLESS | | SUCH ACTIVITY IS PERMITTED TO AFFECT | | SAID PROPERTY PURSUANT TO A CONSENT BY | | THE APPLICABLE PROPERTY OWNER, UNDER | | TERMS & CONDITIONS AGREEABLE TO THE | | APPLICABLE PROPERTY OWNER.THIS INCLUDES | | BUT IS NOT LIMITED TO THE CONTROL OF | | DUST, NOISE, WATER OR DRAINAGE RUN-OFF, | | DEBRIS, AND THE STORAGE OF CONSTRUCTION | | MATERIALS. NEW CONSTRUCTION ACTIVITY | | SHALL NOT ADVERSELY IMPACT HISTORIC | | SURFACE WATER DRAINAGE FLOWS SERVING | | ADJACENT PROPERTIES, & MAY REQUIRE | | SPECIAL DRAINAGE DESIGN COMPLYING WITH | | ENGINEERING STANDARDS TO PRESERVE THE | | POSITIVE PATTERNS OF THE AFFECTED SITES. | | ACCORDINGLY, DEVELOPERS, CONTRACTORS, | | AND OWNERS OF ALL NEW RESIDENTIAL | | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, | | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR | | ITEMS, ON EXISTING PROPERTIES RESULTING | | IN A DECREASE IN EXCESS OF 800SQ FT OF | | PERMEABLE LAND AREA ON ANY PARCELL SHALL | | AS A PERMIT CONDITION, PROVIDE A | | PROFESSIONALLY PREPARED DRAINAGE PLAN | | CLEARLY INDICATING COMPLIANCE WITH THIS | | PARAGRAPH. UPON COMPLETION OF THE | | IMPROVEMENT, A CERTIFICATE FROM A | | LICENSED ENGINEER SHALL BE SUBMITTED TO | | THE INSPECTOR IN ORDER TO RECEIVE | | APPROVAL OF THE FINAL INSPECTION. | | | | 2 ) 109.3.10.1 HURICANE PROTECTION. | | IT SHALL BE UNLAWFUL FOR ANY PERSON TO | | ALLOW CONSTRUCTION RELATED MATERIALS | | EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR | | OTHERWISE UNSECURED AT A CONSTRUCTION | | SITE FROM 24 HRS. AFTER A HURRICANE | | WATCH HAS BEEN ISSUED UNTIL THE | | HURRICANE WATCH OR WARNING HAS BEEN | | LIFTED. ALL SUCH CONSTRUCTION MATERIALS, | | EQUIPMENT AND DEBRIS SHALL BE EITHER | | REMOVED FROM THE CONSTRUCTION SITE OR | | SECURED IN SUCH A MANNER AS TO MINIMIZE | | THE DANGER OF SUCH CONSTRUCTION | | MATERIALS, EQUIPMENT AND DEBRIS CAUSING | | DAMAGE TO PERSONS OR PROPERTY FROM HIGH | | WINDS. | | ANY PERSONS WHO FAILS TO COMPLY TO | | REMOVE OR SECURE THE CONSTRUCTION | | MATERIALS EQUIPMENT AND DEBRIS WITHIN | | 24 HRS AFTER A HURRICANE WATCH HAS BEEN | | ISSUED SHALL BE SUBJECT TO A FINE NOT TO | | EXCEED $500.00. | | IN ADDITION TO THE ABOVE, A LICENSED | | CONTRACTOR WHO VIOLATES THIS SECTION | | SHALL BE SUBJECT TO DISCIPLINE PURSUANT | | TO SECTION 113 OF THIS CHAPTER. | | | | 3) SOUTH SIDE OF LIBRARY ROOF REQUIRES STAIR ACCESS AS | | PER | | FBC BUILDING 1009.12 ACCESS TO ROOF. THE PETITIONER | | SONG& ASSOCIATESHAS MADE APPLICATION FOR A VARIANCE | | TO | | THE TECHNICAL CODE, SECTION 1009.12 FBC BUILDING, TO | | EXCLUDE THE USE | | OF STAIRS TO GAINACCESS TO THE ROOF AND ALLOW USE OF | | A SHIPS LADDER | | TO GAIN ACCESS TO THE ROOF LEVEL. | | | | 4) PRE-ENGINEERED ROOF ACCESS HATCHES: RULE 9B-72 / | | 106.3.3 WEST PALM BEACH | | ADMINISTRATIVE CODE, BOTH OF THE MENTIONED ABOVE | | REQUIRE PRODUCT APPROVALS, | | SINCE THERE ARE NO PRODUCTS AVAILABLE THAT HAVE BEEN | | TESTED BY THE STATE THEBUILDING CODEADVISORY BOARD | | OF PALM BEACH COUNTY SENT A LETTER TO DCA ON THIS | | MATTER AND RECEIVED A DECLATORY STATEMENT FROM THE | | STATE (DEC04-DCA-161) THAT REQUIRES THE ENFORCEMENT OF | | THE STATE AND LOCAL PRODUCT APPROVALS. THIS WILL GIVE | | THE MANUFACTURERS TIME TO GET PRODUCTS TESTED AND ON | | THE MARKET. NO CERTIFICATE OF OCCUPANCY WILL BE ISSUED | | UNTIL PRODUCT TESTING FOR WIND LOADS ARE COMPLETED AND | | PRODUCT APPROVALS FOR PRE-ENGINEERED ROOF HATCHES ARE | | REVIEWED. | | | | 5) TRAINER GLASS COMPANY WILL BE GIVEN 90 DAYS TO | | COMPLY WITH GLAZING REQUIREMENTS IN THE END ZONES, THEY | | ARE TO RECEIVE A ONE TIME SITE SPECIFIC NOA FROM | | MIAMI-DADE FOR CITY HALL FROM THE HURRICANE TEST LAB | | REPROT # 0062-0310-00. | | | | 6) ENGINEERED SHOP DRWINGS FOR THE DOME & BARRELBY | | TRIODETICSPACE FRAMES INC. SHALL BE REVIEWED BY THE | | DESIGNER OF RECORD | | BEFORE SUBMITTED TO THE BUILDING DEPARTMENT. | | | | BUILDING PLAN REVIEW | | JIM WITMER C. B. O. | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2007-01-30 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-01-30 |
Time |
07:08 |
Rev Time |
10.25 |
Received By |
jwitmer |
Date |
2007-01-30 |
Time |
07:08 |
Sent To |
|
|
Notes |
2007-01-30 07:12:29 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 06100574 | | 401 CLEMATIS ST. | | SIXTH REVIEW JAN. 27/07 | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: MEINHART CONSULTING ENGINEERS | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*)MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | 1) --- VERY IMPORTANT | | STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | YOUR ANTICIPATED COOPERATION. | | | | 2-13 COMPLIED. | | | | 14) 6TH REQUEST, IN REVIEWING THIS PLAN IT APPEARS THAT | | THERE ARE VARIOUS DOORS THAT DO NOT MEET THE | | REQUIREMENTS OF:11-4.13.6 MANEUVERING CLEARENCES AT | | DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS THAT ARE | | NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN IN | | FIG. 25. THE FLOOR OR GROUND AREA WITH IN THE REQUIRED | | CLEARANCES SHALL BE CLEAR & LEVEL. | | SEE LIST OF DOORS:A1-302A. PLEASE CLOUD OR DELTA THESE | | CHANGES. | | | | THE DESIGN TEAM DID ATTEMPT TO MAKE THE CORRECTION, | | WITH A 1?-2? SIDE CLEARANCE, | | FOR THE LATCH SIDE OF THE DOOR A 1?-6? CLEARANCE IS | | REQUIRED. SEE FIGURE 25(A) PULL SIDE OF DOOR. | | | | 15 ? 31) | | | | 32A) 4TH REQUEST, THE DOOR SCHEDULE NEEDS RATINGS FOR | | SMOKEAND FIRE RATINGS DEPENDING ON FORTH COMING | | DOCUMENTATION FROM SONG & ASSOCIATES. | | RESPONSE WAS SEE 45A & B BELOW. | | 32A)(1)THIS COMMENT HAD TO DO WITH VERTICAL EXIT | | ENCLOSURES ORIGINALLY OR 2 HR RATED ASSEMBLIES. IN | | CHECKING THE STAIRWELLS BEING 2 HR RATED SHAFTSTHE | | ELEVATOR SHAFTS ARE ALSO 2HR RATED ASSEMBLIES. THE | | ELEVATOR MACHINE ROOM DOOR A6102A FOR ELEVATORS | | 1-3 WILL REQUIRE 1 ? HR OPENING PROTECTIVE 707.4, ALSO | | NOTE AUTOMATIC DOOR CLOSER. | | | | 32A)(2)THE SECOND ISSUE IS THE STAIRWELL # 5 IN THE | | GARAGE. DEPENDING ON WHICH SHEET DEPICTED | | STAIRWELL # 5 IS DEPICTED OR NOT: | | SHEET A1-6.0STAIRWELL# 5 IS NOT SHOWN | | SHEET A2-0STAIRWELL# 5 IS SHOWN | | SHEET A3-GA3 STAIRWELL# 5 IS NOT SHOWN | | SEE TABLE 1018.2 | | 1018.1.1 OPEN PARKING STRUCTURES. | | PARKING STRUCTURES SHALL NOT HAVE LESS THAN TWO EXITS | | FROM EACH PARKING TIER, EXCEPT THAT ONLY ONE EXIT IS | | REQUIRED WHERE VEHICLES ARE MECHANICALLY PARKED. | | UNENCLOSED VEHICLE RAMPS SHALL NOT BE CONSIDERED AS | | REQUIRED EXITS UNLESS PEDESTRIAN FACILITIES ARE | | PROVIDED. | | | | 32A)(3) RATED DOORS WITH GLASS,SIDE LIGHTS OR GLASS | | VIEW PANELS IN RATED PARTITIONS. | | | | A1-301A ** SIDE LIGHT | | A1-306A ** SIDE LIGHT | | A1-013A**GLASS | | A1-017A**GLASS | | A1-701A **WOOD/ GLASS | | A2-301-A**SIDE LIGHT | | A2-008A **SIDE LIGHT | | | | ** THESE DOORS ARE PART OF AN EGRESS ENCLOSURE OF AN | | ATRIUM. | | PLEASE INDICATE COMPLIANCE WITH 404.5 | | SHEET FP1.0/ FP2.0 FIRE SPRINKLER SHEETS DO NOT MEET | | THE REQUIREMENTS FOR 404.5 EXCEPTION# 1 AS SHOWN. | | | | GLASS DOORS PROVIDE ADDITIONAL INFORMATION AS TO FIRE | | RATING 715.3, 715.3.4.1& TABLE 715.4.3. | | | | 32A)(4) SHEET A1-1.2DOOR C1-009A, D1-003 & D1-301 ARE | | COMPOSED OF AL/GL WITH SIDE LIGHTS INDICATE COMPLIANCE | | WITH : | | 715.3.3 DOOR ASSEMBLIES IN CORRIDORS AND SMOKE | | BARRIERS. | | FIRE DOOR ASSEMBLIES REQUIRED TO HAVE A MINIMUM FIRE | | PROTECTION RATING OF 20 MINUTES WHERE LOCATED IN | | CORRIDOR WALLS OR SMOKE BARRIER WALLS HAVING A | | FIRE-RESISTANCE RATING IN ACCORDANCE WITH TABLE 715.3 | | SHALL BE TESTED IN ACCORDANCE WITH NFPA 252 OR UL 10C | | WITHOUT THE HOSE STREAM TEST. IF A 20-MINUTE FIRE DOOR | | ASSEMBLY CONTAINS GLAZING MATERIAL, THE GLAZING | | MATERIAL IN THE DOOR ITSELF SHALL HAVE A MINIMUM FIRE | | PROTECTION RATING OF 20 MINUTES AND BE EXEMPT FROM THE | | HOSE STREAM TEST. GLAZING MATERIAL IN ANY OTHER PART OF | | THE DOOR ASSEMBLY, INCLUDING TRANSOM LITES AND | | SIDELITES, SHALL BE TESTED IN ACCORDANCE WITH NFPA 257, | | INCLUDING THE HOSE STREAM TEST, IN ACCORDANCE WITH | | SECTION 715.4 . FIRE DOOR ASSEMBLIES SHALL ALSO MEET | | THE REQUIREMENTS FOR A SMOKE- AND DRAFT-CONTROL DOOR | | ASSEMBLY TESTED IN ACCORDANCE WITH UL 1784 WITH AN | | ARTIFICIAL BOTTOM SEAL INSTALLED ACROSS THE FULL WIDTH | | OF THE BOTTOM OF THE DOOR ASSEMBLY. THE AIR LEAKAGE | | RATE OF THE DOOR ASSEMBLY SHALL NOT EXCEED 3.0 CFM PER | | SQUARE FOOT (0.01524 M 3 /S ? M 2 ) OF DOOR OPENING AT | | 0.10 INCH (24.9 PA) OF WATER FOR BOTH THE AMBIENT | | TEMPERATURE AND ELEVATED TEMPERATURE & ELEVATED | | TEMPERATURE TESTS. LOUVERS ARE PROHIBITED. | | | | | | | | | | 32A)(5) SHEET A1-3.2DOOR C3-401A IS A WOOD & GLASS DOOR | | WITH GLASS SIDE LIGHTS, PLEASE PROVIDE INFORMATION FOR | | OPENING PROTECTIVE FOR A 1 HR RATED WALL TABLE 1016.1., | | TABLE 715.3, 715.3.4.1, 715.3.3 & 715.4 . | | | | 32A)(6)SHEET A1-3.2DOOR C3-201A IS A WOOD & GLASS | | DOOR WITH GLASS SIDE LIGHTS, PLEASE PROVIDE INFORMATION | | FOR OPENING PROTECTIVE FOR A 2 HR RATED WALL. | | TABLE 1016.1, TABLE 715.3, 715.3.3, 715.3.4.1& 715.4. | | | | 32B) ? 38B) COMPLIED. | | | | 38C) THIS COMMENT WAS REDIRECTED UNDER 32A)(5) . | | | | 39- 63) COMPLIED. | | | | 64) TO BE RE-ADDRESSED, HAD COMPLIED: SEE COMMENT | | 32A)(2). | | | | 65) COMPLIED. | | | | 66) TO BE RE-ADDRESSED UNDER COMMENT32A)(5). | | | | 67- 77) COMPLIED. | | | | 78-81) 2ND REQUEST, | | FL BLD CODE 1609.1.4 | | : COMPONENTS & CLADDING, PROVIDE 2 COPIES (3 IF | | THRESHOLD OR RESIDENT INSPECTOR) OF PRODUCT TESTING | | REPORTS. | | | | PLEASE PROVIDE (3) SIGNED & SEALED LETTERS FROM RWDI | | TESTING LABS CONFIRMING THE STRUCTURAL COMPLIANCE OF | | WIND-LOADING CHARACTERISTICS. THE DESIGN TEAMS RESPONSE | | | | INDICATES COMPREHENSIVE WIND-LOADING CALCULATIONS AND | | DIAGRAMS HAVE BEEN PROVIDED. TO DATE ONLY DIAGRAMS | | SUBMITTED ARE SHEETS S0-3.0 & S0.40 AND NO WIND | | CALCULATIONS HAVE BEEN SUBMITTED AS TO DATE. | | | | A) THE TUNNELING EFFECT WIND WILL HAVE BETWEEN THE | | PORTION OF CITY HALL GARAGE AND THE EAST END OF THE | | BUILDING THAT IS 5 STORIES TALL WITH THE DOME.THERE | | IS NO ELEVATIONS INDICATING WHAT POSITIVE AND NEGATIVE | | PRESSURES WILL OCCUR IN THIS AREA. | | THE SECOND CONCERN IS THE INCREASED TUNNELING EFFECT | | WILL OCCUR WITH THE | | THE ENCLOSING OF THE GARAGE, TO BE AN ENCLOSED GARAGE. | | | | | | B) THE SECOND AREA THAT IS NOT SHOWN IS THE PORTION OF | | THE BUILDING THAT JOINS | | THE LIBRARY TO THE 5 STORY SECTION OF THE | | STRUCTURE. THIS AREA HAS A SERIES OF | | STEPPED ROOFS CREATING A SAW TOOTHED EFFECT | | WHICH WILL CREATE A SERIES OF | | VORTEX ZONES AS THE WIND RUSHES OVER THE SERIES | | OF STEPPED PARAPETS, AGAIN | | THE PLANS DO NOT ADDRESS THESE AREAS FOR THE | | PRESSURE ZONES OR THE | | POSITIVE AND NEGATIVE PRESSURES FOR THESE AREAS. | | | | | | SHEET S0-4.0 ROOF PRESSURES INDICATE A -70 FOR | | THESE SAME ROOF TOP AREA, WHY WOULDN?T THE SAME | | NEGATIVE PRESSURES OCCUR WHERE THE WIND WOULD BE | | FLOWING ON A 45 DEGREE ANGLE. THE WIND WILL SWIRL IN A | | VORTEX FASHION IN THESE AREAS. | | | | C) THE THIRD ITEM OF CONCERN IS THE SHOP DRAWING | | CREATED BY TRAINER GLASS INDICATING THE DIFFERENT | | WINDOW TYPES AND THEIR USE IN THE STRUCTURE AND | | ASSOCIATED WIND ZONES. THE DRAWING NEEDS TO REFLECT THE | | SAME END ZONES AS SHEET S0-3.0 & S0-4.0. THIS SHEET | | WILL ALSO BE USED BY THE THRESHOLD INSPECTOR TO | | IDENTIFY WHICH TYPE OF WINDOW (SPECIFY NOA) WILL BE | | USED IN EACH OF THE COLOR CODED AREAS. | | 106.1.2* ADDITIONAL INFORMATION REQUIRED, PLEASE | | PROVIDE THE DESIGNER OF THIS DOCUMENT, PLEASE PRINT | | NAME AND TELEPHONE NUMBER FOR CONTACT INFORMATION. | | THE THIRD ISSUE WITH THIS DOCUMENT IS THAT THE | | STRUCTURAL ENGINEER HAD NEVER REVIEWED THIS DOCUMENT , | | NO SHOP DRAWING STAMP OF APPROVAL OR REVIEW. | | | | D) 78A & B) AS INTERIOR ZONES AND NO MENTION OF | | POSSIBLE HIGHER PRESSURE, NOR HAS THIS DOCUMENT BEEN | | SUBMITTED TO THE STRUCTURAL ENGINEER FOR REVIEW OR | | APPROVAL. | | | | E)IN THE (3) BINDERS FOR THE (BUILDING | | ENVELOPE) SUBMITTED PRODUCT APPROVALS THERE ARE | | MULTIPLE REPORTS FOR THE SAME REPORT, MISMATCHED | | REPORTS, PLEASE CORRECT SO FOR EACH CATEGORY OF WINDOWS | | AND DOORS THERE IS ONLY ONE REPORT SO AS TO NOT CONFUSE | | THE ISSUE AT HAND. | | | | PRODUCT APPROVALS: | | UNITED STATES ALUM CORP EXTERIOR SWING DOOR-PRESSURE- | | OK | | STANLEY ACCESS TECH AUTO SLIDE FL 6249.9 LOW PRESSURE | | U S DOOR 651-37 ROLL UP DOOR,THIS DOOR IS NOT IN THE | | DOOR SCHEDULE SIZE, WHERE IS THE TEST REPORT# USD-05-2. | | IS THIS TO BE USED? ALSO SUBMITTED IS A BEST ROLLING | | DOOR REPORT. | | BEST ROLLING DOOR FL 7760 PRESSURE- OK | | INGERSOL-RAND IR SERIES W/ IR LOCK- IMPACT ONLY FOR | | ZONE 4-OK +/- 75 | | INGERSOL-RANDH-16-4 OUTSWING W/ PANIC LMIR ONLY ZONE | | 4- OK +/- 70 | | **NO** HOLLOW METAL OUTSWING DOOR APPROVALS FOR ZONE 5 | | FIRESTONE OUTSWING LOUVER DOOR LMIR ONLY ZONE 4 OK +/- | | 75 | | AMERICAN WARMING & VENTILATION- WALL LOUVERS LIMITATION | | 96?X180? +/- 150 | | BILCO ROOF HATCH- REQUIRES STATE APPROVAL OR MIAMI-DADE | | APPROVAL. | | AT THIS TIME THERE IS NO SUCH APPROVALS WILL REQUIRE | | SITE SPECIFIC ENGINEERING, BUILDING OFFICIAL TO RULE ON | | IF 3RD PARTY QUALITY INSURANCE PROGRAM TO BE IN | | AFFECT. | | PALM BEACH COUNTY BCAB HAS NOT RULED ON THIS MATTER AS | | OF YET. | | | | TRAINER GLASS CURTAIN WALL TCW250 TS | | FL6198.7/05-0624.07 WEST ELEVATION CAN?T MAKE PRESSURES | | , MULLIONS NOT HIGH LIGHTED NOR IS THE TYPE OF GLASS. | | | | TRAINER GLASS FIXED TCW 250P. L/SMI FL | | 6198.4/05-0624.04 OK FOR ZONE 4 ONLY | | | | TRAINER GLASS FIXED TCW250P SMI FL 6198.5/05-0624.05 | | +/-80 TRAINER PLAN INDICATES THE USE OF THIS WINDOW IN | | ZONE FIVE AREAS- LOW PRESSURES IF USED IN ZONE 5. | | | | TRAINER GLASS CURTAIN WALL/SMI +/-80 TRAINER PLAN | | INDICATES USE IN ZONE 5, ALSO NEEDS MULLIONS AND TYPE | | OF GLAZING TO BE HIGHLIGHTED. | | | | TRAINER GLASS CURTAIN WALL/LMI HIGHLIGHT WHICH MULLIONS | | & GLAZING SHALL BE USED | | | | NO REPORT FROM HURRICANE TEST LABS, TEST | | 0062.0310.00??????????? | | | | JOHN MANSFIELD MODIFIED BITUMEN ROOFING SYSTEM & | | ENHANCED FASTENING SYSTEM-OK | | | | NO REPORT FOR TRIODETIC SPACE FRAMES FOR THE DOME NOR | | BARREL ROOF FRAMING ASSEMBLY. TO DATE NO INFORMATION | | HAS BEEN SUBMITTED FOR REVIEW, NO DESIGN CRITERIA. | | | | 82-84) COMPLIED. | | | | NEW COMMENTS, | | 85) ROOF HATCH COVERS,1009.12 ACCESS TO ROOF. | | BUILDINGS FOUR STORIES OR MORE IN HEIGHT, EXCEPT THOSE | | WITH A ROOF SLOPE GREATER THAN 4:12, SHALL BE PROVIDED | | WITH A STAIRWAY TO THE ROOF. SUCH STAIRWAY SHALL BE | | MARKED AT STREET AND FLOOR LEVELS WITH A SIGN | | INDICATING THAT IT CONTINUES TO THE ROOF. WHERE ROOFS | | ARE USED FOR ROOF GARDENS OR FOR OTHER PURPOSES, | | STAIRWAYS SHALL BE PROVIDED AS REQUIRED FOR SUCH USE OR | | OCCUPANCY. | | | | 86)SHEET A1-5.0 STAIR# 8 IN THE LIBRARY PROVIDES ROOF | | ACCESS TO THE LIBRARY ROOF NORTH OF THE BARREL SECTION, | | PLANS INDICATE THE USE OF A ROOF HATCH TO THE SOUTH | | SIDE OF THE BARREL ROOF PLEASE CORRECT, SEE COMMENT# | | 85. | | | | 87)PLEASE PROVIDE INFORMATION ON THE BARREL ROOF | | PORTION OF THE LIBRARY ROOF, SO THE ENERGY CALCULATIONS | | CAN BE VERIFIED. BUILDING HAS NOT BEGUN TO REVIEW | | ENERGY FORM COMPLIANCE UNTIL ALL OF THE UNKNOWNS ARE | | VERIFIED, THEN WE WILL BE ABLE VERIFY THE INFORMATION | | SUBMITTED. NOTE THE BARREL IS PART OF THE AIR | | CONDITIONED SPACE. | | 13-400.0.ABC COMPLIANCE CRITERIA. | | COMMERCIAL BUILDINGS DEMONSTRATING COMPLIANCE WITH THIS | | CODE BY METHODS A OR B SHALL MEET ALL OF THE CRITERIA | | GIVEN IN THE TEXT AS SPECIFIC TO THE CHOSEN METHOD OF | | COMPLIANCE FOR 1 THROUGH 4 BELOW. COMMERCIAL BUILDINGS | | UTILIZING METHOD C FOR CODE COMPLIANCE SHALL MEET ALL | | CRITERIA SPECIFIED FOR METHOD C FOR 1, 3 AND 4 BELOW. | | 1.PRESCRIPTIVE REQUIREMENTS. | | 2.PERFORMANCE CALCULATION PROCEDURE. | | 3.CERTIFICATION OF COMPLIANCE. | | 4.REPORTING. | | | | 88) A1-6.1 PARTIAL FLOOR PLAN OF THE MECHANICAL | | PENTHOUSE. | | | | 88A) THE FLOOR PLAN INDICATES THE DOORS A6-101 A&B BOTH | | WERE PAIRS OF DOORS, REVISION TO SINGLE OUT SWING | | DOORS. THE ELEVATION NOR THE SECTIONS HAVE BEEN UPDATED | | TO REFLECT THE CHANGE. 106.1.2. ADD INFO REQUIRED. | | | | 88B) SECTION 2/A5.04 IS MISSING STAIR# 13 TO THE DOME. | | DETAIL# 10 INDICATES THE LOCATION OF STAIR# 13 IN | | REGARDS TO THE COLUMN B-5 AND THE 24?X42? BEAM TO | | COLUMN B6. WHEN THIS BEAM IS SUPERIMPOSED ON TO DETAIL# | | 10/ A7.1.6/ S1-8.0 THE STAIR IS NOT ACCESSIBLE. PLEASE | | CORRECT. | | | | 88C) DOME: THE DOME INDICATE AN OPEN STAIRWAY# 13 THAT | | LEADS TO THE 7TH FLOOR, | | 1509.5.1 NONCOMBUSTIBLE CONSTRUCTION REQUIRED. | | ANY TOWER, SPIRE, DOME OR CUPOLA THAT EXCEEDS 60 FEET | | (18 288) IN HEIGHT ABOVE THE HIGHEST POINT AT WHICH IT | | COMES IN CONTACT WITH THE ROOF, OR THAT EXCEEDS 200 | | SQUARE FEET (18.6 M 2 ) IN AREA AT ANY HORIZONTAL | | SECTION, OR WHICH IS INTENDED TO BE USED FOR ANY | | PURPOSE OTHER THAN A BELFRY OR ARCHITECTURAL | | EMBELLISHMENT, SHALL BE ENTIRELY CONSTRUCTED OF AND | | SUPPORTED BY NONCOMBUSTIBLE MATERIALS. SUCH STRUCTURES | | SHALL BE SEPARATED FROM THE BUILDING BELOW BY | | CONSTRUCTION HAVING A FIRE-RESISTANCE RATING OF NOT | | LESS THAN 1.5 HOURS WITH OPENINGS PROTECTED WITH A | | MINIMUM 1.5-HOUR FIRE-PROTECTION RATING. STRUCTURES, | | EXCEPT AERIAL SUPPORTS 12 FEET (3658 MM) HIGH OR LESS, | | FLAGPOLES, WATER TANKS AND COOLING TOWERS, PLACED ABOVE | | THE ROOF OF ANY BUILDING MORE THAN 50 FEET (15 240 MM) | | IN HEIGHT, SHALL BE OF NONCOMBUSTIBLE MATERIAL AND | | SHALL BE SUPPORTED BY CONSTRUCTION OF NONCOMBUSTIBLE | | MATERIAL. | | | | 88D) THE PLANS FOR THE DOME END IN COMPLETENESS AT | | ELEVATION 192?-6? WITH THE 7TH FLOOR SLAB, SHEET S1.8.0 | | INDICATES A BEAM AT ELEVATION 212?-6? AND THE | | SUPPORTING COLUMNS BUT NO INFORMATION ON THE EXTERIOR | | WALL SECTIONS OR THE ATTACHMENT OF THE DOME. IN REGARDS | | TO THE DOME ITSELF NO STRUCTURAL PLANS HAVE BEEN | | SUBMITTED FOR | | REVIEW. | | | | 88E)BARREL S1-8.0 INDICATES IN SECTION # 3 THE EMBEDS | | THAT THE BARREL WILL ATTACH | | TO, THE PLANS LACK INFORMATION AS TO THE FREQUENCY OF | | EMBEDS. 106.1.2* ADD INFO. | | | | WITH NEW INFORMATION SUBMITTED IN THE NEXT REVIEW | | ADDITIONAL COMMENTS MAY OCCUR. | | | | JIM WITMER | | BUILDING PLAN REVIEW | | CONSTRUCTION SERVICES DEPARTMENT | | WEST PALM BEACH, FL | | TEL;(561)805-6715 | | FAX; (561)805-6731 | | E-MAIL; [email protected] | | | | | | CITY HALL CENTER6TH REVIEW.DOC |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2006-12-26 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2006-12-26 |
Time |
09:16 |
Rev Time |
32.00 |
Received By |
jwitmer |
Date |
2006-12-26 |
Time |
09:16 |
Sent To |
|
|
Notes |
2006-12-26 09:17:31 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 06100574 | | 401 CLEMATIS ST. | | FIFTH REVIEW DEC. 23/06 | | | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: MEINHART CONSULTING ENGINEERS | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*)MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | 1) --- VERY IMPORTANT | | STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | YOUR ANTICIPATED COOPERATION. | | | | 2)COMPLIED. | | | | 3A)CIVIL ENGINEERS: CRAVEN THOMPSON & ASSOCIATES, | | INC. IS MISSING THEIR CERTIFICATE OF AUTHORIZATION. | | 471.023 F.S.CERTIFICATE OF AUTHORIZATION.THE TITLE | | BLOCK FOR ANY SHEET BEARING THE NAME OF AN ENGINEER | | PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A | | PARTNERSHIP, OFFERING ENGINEERING SERVICES, SHALL | | INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD | | THE NUMBER TO EACH SHEET.THIS MAY | | BE ADDED BY HAND. | | | | | | 4) COMPLIED. | | | | 5) COMPLIED. | | | | 6) COMPLIED. | | | | 7) COMPLIED. | | PAGE 1 | | | | 8)FIFTH REQUEST, THORNTON TOMASETTI HAS ATTEMPTED TO | | COMPLY WITH THIS REQUIREMENT BY SUPPLYING A COVERSHEET | | WITH THEIR SHOP DRAWING STAMP AND SIGNATURE BUTTHIS | | DOCUMENT DOESN?T INDICATE WHAT PRODUCT APPROVAL | | DOCUMENT IS REVIEWED AND APPROVED. | | WPB ADMIN CODE 106.3* PRODUCT APPROVALS.THOSE | | PRODUCTS WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | 9) COMPLIED. | | | | 10) IN REVIEWING THE THRESHOLD INSPECTION PLAN,THERE | | IS NO COMMENT ON REQUIREMENTS FOR SHORING AND RESHORING | | SHOP DRAWINGS AND INSPECTIONS FORFLOOR SLABS ABOVE | | GRADE. | | | | FL S. S. 553.71(7) ?THRESHOLD BUILDING" MEANING ANY | | BUILDING | | WHICH IS GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, | | OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS | | DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 | | SQ FT IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN | | 500 PERSONS. | | 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL | | INSPECTOR TO PERFORM | | STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING PURSUANT | | TO A STRUCTURAL | | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE | | STRUCTURAL INSPECTION | | PLAN MUST BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO | | THE ISSUANCE OF A | | BUILDINGS PERMIT FOR THE CONSTRUCTION OF A THRESHOLD | | BUILDING. THE PURPOSE OF THE | | STRUCTURAL INSPECTION PLAN IS TO PROVIDE SPECIFIC | | INSPECTION PROCEDURES AND | | SCHEDULES SO THAT THE BUILDING CAN BE ADEQUATELY | | INSPECTED FOR COMPLIANCE WITH | | THE PERMITTED DOCUMENTS. | | | | 11) 3RD REQUEST, RESPONSE SHEET INDICATES THE SPECIAL | | INSPECTOR FORMS TO BE PART OF THE SUBMITTALS, WHERE? | | WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES | | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL | | INSPECTOR AS REQUIRED BY S. 553.79(5) FLORIDA STATUTES | | TO THE MINIMUM INSPECTIONS REQUIRED BY THIS CODE. | | CONTACT HAROLD PISKURA MANAGER OF THE SPECIAL INSPECTOR | | PROGRAM AT (561) 805-6711 FOR FURTHER INFORMATION | | BEFORE THE PERMIT MAY BE ISSUED. | | SEE ATTACHED GUIDELINE. | | | | 12) COMPLIED. | | | | 13) COMPLIED. | | | | 14)5TH REQUEST, IN REVIEWING THIS PLAN IT APPEARS | | THAT THERE ARE VARIOUS DOORS THAT DO NOT MEET THE | | REQUIREMENTS OF:11-4.13.6 MANEUVERING CLEARENCES AT | | DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS THAT ARE | | NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN IN | | FIG. 25. THE FLOOR OR GROUND AREA WITH IN THE REQUIRED | | CLEARANCES SHALL BE CLEAR & LEVEL. | | SEE LIST OF DOORS:A1-302A. PLEASE CLOUD OR DELTA THESE | | CHANGES. | | PAGE2 | | | | 15)COMPLIED. | | | | 16) COMPLIED. | | | | 17) COMPLIED. | | | | 18) COMPLIED. | | | | 19) COMPLIED. | | | | 20) COMPLIED. | | | | 21) COMPLIED. | | | | 22) COMPLIED. | | | | 23) COMPLIED. | | | | 24) COMPLIED. | | | | 25) COMPLIED C-10. | | | | 26) COMPLIED. | | | | 27) COMPLIED. | | | | 28) COMPLIED. | | | | 29) COMPLIED. | | | | 30) COMPLIED. | | | | 32A) 3RD REQUEST, THE DOOR SCHEDULE NEEDS RATINGS FOR | | SMOKEAND FIRE RATINGS DEPENDING ON FORTH COMING | | DOCUMENTATION FROM SONG & ASSOCIATES. | | | | 32B) 2ND REQUEST, THE LIFE SAFETY PLAN AND THE ?A? | | SHEETS DO NOT MATCH UP FOR SMOKE AND FIRE RATINGS OF | | ALL ELECTRICAL ROOMS, STORAGE ROOMS, MECHANICAL ROOMS | | AND ELEVATOR MECHANICAL ROOMS. THE ?A? SHEETS ARE | | MISSING THE WALL DESIGNATIONS FOR EITHER SMOKE ORHR | | RATINGS. | | | | 33) COMPLIED. | | | | 34) COMPLIED. | | | | 35) COMPLIED. | | PAGE 3 | | 36) COMPLIED. | | | | 37) COMPLIED. | | | | 38A) EMPLOYEE LOUNGE, MET WITH TOM KASTNER12-21-06 | | ABOUT THE EMPLOYEE LOUNGE, | | SONG & ASSOCIATES FOR A NET SQ FOOTAGE WERE | | TAKING OUT CABINET SQ FT FOR NET NOT | | WALL TO WALL. SONG & ASSOCIATES WILL CORRECT TO | | REDUCE THE OCCUPANT LOAD TO LESS THAN 50. | | | | 38B) FOURTH FLOOR TRAINING ROOM, I RECEIVED A LETTER | | FROM WILLIAM SWISHER THAT SATES: | | 1) FIXED SEATING NOT TO EXCEED 49 STATIONS. 2) OCCUPANT | | LOAD TO BE POSTED IN THE ROOM 49 PERSONS 3) ROOM IS NOT | | TO BE ALTERED TO ALLOW GREATER THAN 49 PERSONS. | | | | 38C) LS1-3.2 & A1-3.2 BOTH SHEETS ARE MISSING THE 1 HR | | RATED CORRIDOR WALL BETWEEN | | THE ASSEMBLY AND BUSINESS OCCUPANCIES. TABLE 1016.1. | | | | 39) COMPLIED. | | | | 40) COMPLIED. | | | | 41) COMPLIED. | | | | 42) COMPLIED. | | | | 43) COMPLIED. | | | | 44) COMPLIED. | | | | 45A)SHEET LS0.0 CODE SUMMARY- FIRE RESISTANCE RATINGS | | FOR SEPARATIONS, | | THIS SHEET IDENTIFIES NUMEROUS CODE SECTIONS SIGHTING | | NFPA OR FBC BUT IN THE DOOR SCHEDULE THE DOORS ARE NOT | | RATED, ELECTRIC ROOM DOOR B1-111A, | | MECHANICAL ROOM DOOR B1-102A. T-1016/ 708.3/ T-302.1.1 | | & NFPA. | | | | 45B) THE ABOVE LISTED MISSING DOOR RATINGS THE | | CORRELATING MISSING WALL RATINGS ARE THE MECHANICAL | | ROOM B1-102 & THE NEW ELECTRIC ROOM B1-111, NOTE THE | | NEW ELECTRIC ROOM IS MISSING ? OF THE WALL DESIGNATION, | | SHEET | | A1-GA.1. | | | | 46) COMPLIED. | | | | 47) COMPLIED. | | | | 48) COMPLIED. | | | | PAGE 4 | | 49) COMPLIED. | | | | 50) COMPLIED. | | | | 51) COMPLIED. | | | | 52) COMPLIED. | | | | 53) COMPLIED. | | | | 54) COMPLIED. | | | | 55) COMPLIED. | | | | 56) COMPLIED. | | | | 57) COMPLIED. | | | | 58) COMPLIED. | | | | 59) COMPLIED. | | | | 60) COMPLIED. | | | | 61) COMPLIED. | | | | 62) COMPLIED. | | | | 63) COMPLIED. | | | | 64) COMPLIED. | | | | 65) COMPLIED. | | | | 66) (SAME AS 38C), MISSING CORRIDOR RATING BETWEEN | | BUSINESS AND ASSEMBLY OCCUPANCY TABLE 1016. | | | | 67) COMPLIED. | | | | 68)COMPLIED. | | | | 69) COMPLIED. | | | | 70) COMPLIED. | | | | PAGE 5 | | | | 71) COMPLIED. | | | | 72) COMPLIED. | | | | 73) COMPLIED. | | | | 74) COMPLIED. | | | | 75) COMPLIED. | | | | 76) COMPLIED. | | | | 77) COMPLIED. | | | | NOTE ITEMS 78- 81 FIRST REVIEW!!!! | | | | 78)FL BLD CODE 1609.1.4 | | : COMPONENTS & CLADDING, PROVIDE 2 COPIES (3 IF | | THRESHOLD OR RESIDENT INSPECTOR) OF PRODUCT TESTING | | REPORTS. | | | | BEFORE THE SUBMITTED REPORTS CAN BE FULLY REVIEWED | | THERE ARE CONCERNS ABOUT WIND PRESSURES, CONCERNING | | ELEVATIONS NOT SHOWN IN THE STRUCTURAL SHEETS. | | | | A) THE TUNNELING EFFECT WIND WILL HAVE BETWEEN THE | | PORTION OF CITY HALL GARAGE AND THE EAST END OF THE | | BUILDING THAT IS 5 STORIES TALL WITH THE DOME.THERE | | IS NO ELEVATIONS INDICATING WHAT POSITIVE AND NEGATIVE | | PRESSURES WILL OCCUR IN THIS AREA. | | THE SECOND CONCERN IS THE INCREASED TUNNELING EFFECT | | WILL OCCUR WITH THE | | THE ENCLOSING OF THE GARAGE, TO BE AN ENCLOSED GARAGE. | | | | | | B) THE SECOND AREA THAT IS NOT SHOWN IS THE PORTION OF | | THE BUILDING THAT JOINS | | THE LIBRARY TO THE 5 STORY SECTION OF THE | | STRUCTURE. THIS AREA HAS A SERIES OF | | STEPPED ROOFS CREATING A SAW TOOTHED EFFECT | | WHICH WILL CREATE A SERIES OF | | VORTEX ZONES AS THE WIND RUSHES OVER THE SERIES | | OF STEPPED PARAPETS, AGAIN | | THE PLANS DO NOT ADDRESS THESE AREAS FOR THE | | PRESSURE ZONES OR THE | | POSITIVE AND NEGATIVE PRESSURES FOR THESE | | AREAS. | | | | | | C) THE THIRD ITEM OF CONCERN IS THE SHOP DRAWINGS | | CREATED BY TRAINER GLASS INDICATING THE DIFFERENT | | WINDOW TYPES AND THEIR USE IN THE STRUCTURE AND | | ASSOCIATED WIND ZONES. THEY HAVE INDICATED THE AREAS OF | | CONCERN | | (78 A& B). | | D) AS INTERIOR ZONES AND NO MENTION OF POSSIBLE HIGHER | | PRESSURE, NOR HAS THIS DOCUMENT BEEN SUBMITTED TO THE | | STRUCTURAL ENGINEER FOR REVIEW OR APPROVAL. | | | | | | PAGE 6 | | | | | | REPORTS ARE AS FOLLOWS: | | A) FIXED WINDOWS- | | B) OPERABLE WINDOWS | | C) MULLIONS NOT COVERED BY NOA THE REPORTS FOR THE | | CURTAIN WALL SYSTEM HAVE A LIMITATION OF 171? ON THE | | MULLIONS. | | D) GLAZED DOORS, AUTOMATIC SLIDERS, SWING DOORS OR | | PRE-ENGINEERED ROOF ACCESS HATCHES- THIS IS A PRODUCT | | THAT IS REGULATED BY FLORIDA STATUTE RULE 9B-72- AT | | THIS TIME IT APPEARS THERE IS NO PRODUCT THAT IS TESTED | | THROUGH THE STATE OR THROUGH MIAMI-DADE?S NOA. THIS HAS | | BEEN BROUGHT UP BY BUILDING OFFICIAL AT THE PALM BEACH | | COUNTY BCAB BOARD IN NOVEMBER / 06 TO SEE HOW OTHER | | JURISDICTIONS WERE HANDLING THIS ISSUE FURTHER | | DISCUSSION TO BE ON THE JANUARY BOARD AGENDA. | | | | E) EXTERIOR METAL DOORS IF SINGLE OR PAIRS- COVERED | | UNDER COMMENT# 81. | | F) ROLL-UP OR SECTIONAL DOORS- MISSING FLORIDA COVER | | SHEET, PROVIDE WIND | | INFORMATION!!!!!!! | | G) LOUVERS- WALL - OK | | H) PANEL WALLS: SOFFITS, EFIS, STOREFRONTS, CURTAIN | | WALLS- NO REPORT SUBMITTED | | I) SKYLIGHTS- CANOPY ROOF PANELS-SEE A5.02 SECTION | | 1 CHANGE DELTA(2) PROVIDE | | MORE INFORMATION ON THIS SYSTEM | | J)PRE-ENGINEERED A/C STANDS- PROVIDE TECHNICAL | | SHEETS 1-3. PLEASE HIGHLIGHT WHICH FASTENING SYSTEM TO | | THE STRUCTURAL DECK BELOW . | | K) ROOFING PRODUCTS: BUILT UP, MODIFIED, SINGLE PLY | | SYSTEMS, METAL ROOFING | | SPRAY APPLIED POLYURETHANE, ROOF SYSTEM | | FASTENERS, UNDERLAYMENTS AND | | WATERPROOFING | | | | (K1) THE REPORT SUBMITTED BY ATLANTIC & CARIBBEAN ROOF | | CONSULTANTS, IF REPORT IS SUBMITTED BY A REGISTERED | | ROOFING CONSULTANT, THEN TO BE SEALED WITH THE | | APPROPRIATE SEAL. THE WORDING TESTING AND ENGINEERING | | SERVICES INDICATES AN ENGINEERING FIRM, WHICH IS A | | LICENSED ENGINEERING FIRM, MISSING THEIR CERTIFICATE OF | | AUTHORIZATION ON THIS REPORT, AND NOT SEALED BY THE | | ENGINEER. | | 471.023 F.S.CERTIFICATE OF | | AUTHORIZATION.THE TITLE BLOCK FOR ANY | | SHEET BEARING THE NAME OF AN ENGINEER | | PRACTICING UNDER A FICTITIOUS NAME, A | | CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING | | SERVICES, SHALL INCLUDE THE CERTIFICATE OF | | AUTHORIZATION NUMBER. | | | | PLANS, SPECIFICATIONS, REPORTS OR | | OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND | | BEING FILED FOR PUBLIC | | RECORD SHALL HAVE THE SIGNATURE AND | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | TO THE DOCUMENT. | | FL STATE STAT: 61G15-23.002 ENGINEERS | | FL ATATE STAT: 61G16.003 ARCHITECTS | | | | (K2) THE SUBMITTED REPORT INDICATES VARIOUS ROOF DECKS | | BY NUMBER BUT THERE IS NO KEY PLAN PROVIDING THE | | LOCATION OF THE ROOF DECKS. | | PAGE 7 | | | | | | (K3) ROOF DECK NUMBER (2) INDICATES A HEIGHT OF 87? | | WHERE IS THIS DECK LOCATED? | | | | (K4) LIGHTWEIGHT CONCRETE ROOF DECK- MIAMI-DADE NOA, | | THE REPORT SUBMITTED DOES NOT HAVE THE SUB-SYSTEM | | HIGHLIGHTED AS TO WHICH SUB-SYSTEM WILL BE INSTALLED. | | | | (K5) TRIODETIC PREFABRICATED METAL BUILDING SYSTEM- NO | | SUBMITTALS EITHER STATE APPROVAL OR A MIAMI-DADE | | APPROVAL. ADDITIONAL COMMENTS MAY APPEAR ON FURTHER | | REVIEWS. | | | | | | 1609.1.4 PROTECTION OF OPENINGS. | | IN WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING THAT | | RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET (18.3 | | M) IN BUILDINGS SHALL BE ASSUMED TO BE OPENINGS AND THE | | BALANCE OF GLAZED OPENINGS IN THE REST OF THE BUILDING | | SHALL BE ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT | | RECEIVES POSITIVE PRESSURE IS IMPACT RESISTANT OR | | PROTECTED WITH AN IMPACT RESISTANT COVERING MEETING THE | | REQUIREMENTS OF SSTD 12, ASTM E 1886 AND ASTM E 1996, | | OR MIAMI-DADE TAS 201, 202 AND 203 REFERENCED THEREIN | | AS FOLLOWS: 1.GLAZED OPENINGS LOCATED WITHIN 30 | | FEET (9.1 M) OF GRADE SHALL MEET THE REQUIREMENTS OF | | THE LARGE MISSILE TEST. 2.GLAZED OPENINGS LOCATED | | MORE THAN 30 FEET (9.1 M) ABOVE GRADE SHALL MEET THE | | PROVISIONS OF THE SMALL MISSILE TEST. | | | | | | 79) SEE NEXT COMMENT. | | | | | | 80)SAME REQUEST AS COMMENT# 8,W.P.B. ADMIN CODE | | 106.3* PRODUCT APPROVALS. THOSE PRODUCT WHICH ARE | | REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND | | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO | | SUBMITTAL FOR JURISDICTIONAL APPROVAL. THORNTON | | TOMASETTI HAS ATTEMPTED TO COMPLY WITH THIS REQUIREMENT | | BY SUPPLYING A COVERSHEET WITH THEIR SHOP DRAWING STAMP | | AND SIGNATURE BUTTHIS DOCUMENT DOESN?T INDICATE WHAT | | PRODUCT APPROVAL DOCUMENT IS REVIEWED AND APPROVED. | | | | | | 81) 2ND REQUEST, THE SUBMITTAL FOR HOLLOW METAL DOORS | | WILL WORK AT GROUND LEVEL BUT THE DOORS AT THE ROOF TOP | | LEVEL WILL NOT THE REQUIRED HIGHER PRESSURE. 1714.5.3 | | EXTERIOR DOOR ASSEMBLIES. | | EXTERIOR DOOR ASSEMBLIES NOT COVERED BY SECTION | | 1715.4.2 OR SECTION 1714.5.3.1 SHALL BE TESTED FOR | | STRUCTURAL INTEGRITY IN ACCORDANCE WITH ASTM E 330 | | PROCEDURE A, AT A LOAD OF 1.5 TIMES THE REQUIRED DESIGN | | PRESSURE LOAD. THE LOAD SHALL BE SUSTAINED FOR 10 | | SECONDS WITH NO PERMANENT DEFORMATION OF ANY MAIN FRAME | | OR PANEL MEMBER IN EXCESS OF 0.4 PERCENT OF ITS SPAN | | AFTER THE LOAD IS REMOVED. HIGH-VELOCITY HURRICANE | | ZONES SHALL COMPLY WITH TAS 202. AFTER EACH SPECIFIED | | LOADING, THERE SHALL BE NO GLASS BREAKAGE, PERMANENT | | DAMAGE TO FASTENERS, HARDWARE PARTS, OR ANY OTHER | | DAMAGE WHICH CAUSES THE DOOR TO BE INOPERABLE. PAGE 8 | | | | 82) COMPLIED. | | | | 83) COMPLIED. | | | | 84) COMPLIED, EXEMPT A MUNICIPALITY. | | | | JIM WITMER | | BUILDING PLAN REVIEW | | WEST PALM BEACH CONSTRUCTION SERVICES DEPARTMENT WEST | | PALM BEACH, FL 33402 | | TEL (561)805-6715 | | FAX (561)805-6731 | | E-MAIL: [email protected] | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | CITY HALL CENTER 5TH REVIEW .DOC |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-10-24 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2006-10-24 |
Time |
12:57 |
Rev Time |
8.88 |
Received By |
jwitmer |
Date |
2006-10-24 |
Time |
12:57 |
Sent To |
|
|
Notes |
2006-10-24 14:29:21 | WEST PALM BEACH | | CITY CENTER- CITY HALL | | PERMIT# 0610.0574 | | ADDRESS: 401 CLEMATIS ST. | | | | FOURTHREVIEW OCT. 24TH, 2006 | | FIRST UNDER PERMIT | | ARCHITECT: SONG & ASSOCIATES | | ENGINEER: MEINHART CONSULTING ENGINEERS | | | | NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA | | BUILDING CODE, | | (*)MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE | | AMENDMENTS | | | | ***SHEET T-1 APPLICABLE CODEPLEASE CORRECT TO THE | | 2004 FBC.***** | | | | 1) --- VERY IMPORTANT | | STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | YOUR ANTICIPATED COOPERATION. | | | | THIS COMMENT WAS IGNORED UNDER THE FIRST | | REVIEW, THE DESIGN TEAM DIDN?T PROVIDE ANY TRANSMITTAL | | LETTER, NOR WERE ANY OF THE CHANGES MADE HIGHLIGHTED | | WITH A CLOUD OR DELTA AND THE REVISION BOX IN THE | | HEADER STRIP WASN?T FILLED IN MAKING DIFFICULT TO FIND | | THE REVISIONS MADE AND TIME CONSUMING!!!! | | | | | | 2) PLANS INDICATE 100% COMPLETE BUT ARE ONLY A PARTIAL | | ROLL,WHEN PLANS ARE TO BE SUBMITTED FOR PUBLIC RECORD | | :PLANS, SPECIFICATIONS,REPORTS OR OTHER DOCUMENTS | | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR | | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE | | DOCUMENT. | | FL STATE STAT: 61G15-23.002 ENGINEERS | | FL ATATE STAT: 61G16.003 ARCHITECTS | | | | 3) NOTE: PLANS ARE NOT SEALED THIS IS A COURTESY | | REVIEW, WHEN PLANS ARE SUBMITTED FOR PUBLIC RECORD: NEW | | ENGINEERING SEAL DESIGN. "LICENSE" A GRACE PERIOD RAN | | THROUGH DEC. 31, 2005. | | RULE 61G155-23.001(1) F.A.C. | | THE FLORIDA BOARD OF PROFESSIONAL ENGINEERS HAS | | CLEANED UP THE APPEARANCE OF THE SEAL BY ELIMINATING | | OBSOLETE CONTENT AND CHANGING THE WORD "CERTIFICATE" | | TO | | | | COVERSHEET: | | 3A) CIVIL ENGINEERS: CRAVEN THOMPSON & ASSOCIATES, INC. | | IS MISSING THEIR CERTIFICATE OF AUTHORIZATION.) | | 471.023 F.S.CERTIFICATE OF | | AUTHORIZATION.THE TITLE BLOCK FOR ANY | | SHEET BEARING THE NAME OF AN ENGINEER | | PRACTICING UNDER A FICTITIOUS NAME, A | | CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING | | SERVICES, SHALL INCLUDE THE CERTIFICATE OF | | AUTHORIZATION NUMBER. | | ADD THE NUMBER TO EACH SHEET.THIS MAY | | BE ADDED BY HAND. | | | | 4)FOURTH REQUEST, STRUCTURAL SHEET TITLE BLOCK INDICATE | | THAT THORNTON TOMASETTI A CONSULTING ENGINEER, FL DEPT | | OF PROFESSIONAL REGULATION DOESN'T INDICATE LICENSURE | | IN FLORIDA. | | LICENSURE FL S. S. 471.015/471.023 F.S. CERTIFICATE | | OF | | AUTHORIZATION.THE TITLE BLOCK FOR ANY | | SHEET BEARING THE NAME OF AN ENGINEER | | PRACTICING UNDER A FICTITIOUS NAME, A | | CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING | | SERVICES, SHALL INCLUDE THE CERTIFICATE OF | | AUTHORIZATION NUMBER. | | ADD THE NUMBER TO EACH SHEET.THIS MAY | | BE ADDED BY HAND. | | | | 5) COMPLIED. | | | | 6) COMPLIED. | | | | 7) COMPLIED. | | | | 8) FOURTHREQUEST,PRODUCT APPROVAL HAVE BEEN | | SUBMITTED AT THIS TIME. WPB ADMIN CODE 106.3* PRODUCT | | APPROVALS.THOSE PRODUCTS WHICH ARE REGULATED BY DCA | | RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY | | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | JURISDICTIONAL APPROVAL. | | | | 9) COMPLIED. | | | | 10) COMPLIED. SHEET# S0-2.0 STRUCTURAL INSPECTION | | PLAN. | | | | | | 11) THIRDREQUEST,WPB AMENDMENT 105.13.6. W.P.B. | | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD | | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY S. | | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS | | REQUIRED BY THIS CODE. CONTACT HAROLD PISKURA MANAGER | | OF THE SPECIAL INSPECTOR PROGRAM AT (561) 805-6711 FOR | | FURTHER INFORMATION BEFORE THE PERMIT MAY BE ISSUED. | | SEE ATTACHED GUIDELINE. | | | | 12) COMPLIED. | | | | 13) COMPLIED. | | | | 14)THIRD REQUEST, IN REVIEWING THIS PLAN IT APPEARS | | THAT THERE ARE VARIOUS DOORS THAT DO NOT MEET THE | | REQUIREMENTS OF:11-4.13.6 MANEUVERING CLEARENCES AT | | DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS THAT ARE | | NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN IN | | FIG. 25. THE FLOOR OR GROUND AREA WITH IN THE REQUIRED | | CLEARANCES SHALL BE CLEAR & LEVEL. SEE LIST :A1-302A & | | A4-202A. PLEASE CLOUD OR DELTA THESE CHANGES. | | | | 15) COMPLIED. | | | | 16) COMPLIED. | | | | 17) COMPLIED. | | | | 18) COMPLIED. | | | | 19) COMPLIED. | | | | 20) COMPLIED. | | | | 21) COMPLIED. | | | | 22) COMPLIED. | | | | 23)4TH REQUEST,SHEET A1-D DETAILS 1.1 ? 2.2 | | ILLUSTRATE THE USE OF GRANITE VENEER. DETAIL 1.1B | | PROVIDES INFO FOR ATTACHMENT BUT DOES NOT MATCH TO | | SECTION 1405.7 FOR SLAB TYPE <2?THICK (GRANITE).ALSO | | PROVIDE MAXIMUM SQUARE FOOTAGE PER GRANITE. THE MAXIMUM | | AREA PER SLAB STILL ISN'T INDICATED ON THE PLANS. | | | | 24) COMPLIED. | | | | 25) FOURTH REQUEST, PLANS INDICATE FIRST FLOOR FINISH | | FLOOR TO BE 17.35 NGVD, BUT NO SITE PLAN PROVIDES THE | | EXISTING CITY SIDEWALK ELEVATIONS. PROVIDE AT LEAST 1 | | ACCESSIBLE ROUTE TO THE SITE. 11-4.1.2(1-4). IN | | DISCUSSING THE SIDEWALKS AROUND THE PERIMETER WITH THE | | DESIGN TEAM AT THE LAST MEETING THERE WILL BE CONCERNS | | WITH CROSS SLOPE NOT TO EXCEED THE 2%. THE DESIGN TEAM | | INDICATED THAT BETWEEN THE SIDEWALK AND STREET CURBING | | THERE WILL BE PLANTERS FOR TREES, BUT BETWEEN THE TREE | | PLANTERS THERE WILL ALSO BE A WALKING SURFACE ( BRICKS) | | THAT WILL HAVE CROSS SLOPE GREATER THAN 2%. | | IN DISCUSSING THIS ISSUE WITH THE BUILDING | | OFFICIAL IF THE SLOPE OF THE BRICK IS GREATER THAN 2% | | THEN SOME TYPE OF BARRIER NEEDS TO BE IN EFFECT, EITHER | | EDGE PROTECTION OR A GUARD. 11-4.3.7 11-4.3.7 SLOPE. AN | | ACCESSIBLE ROUTE WITH A RUNNING SLOPE GREATER THAN 1:20 | | IS A RAMP AND SHALL COMPLY WITH SECTION 11-4.8 . | | NOWHERE SHALL THE CROSS SLOPE OF AN ACCESSIBLE ROUTE | | EXCEED 1:50. | | | | 26) COMPLIED. | | | | 27) COMPLIED. | | | | 28) COMPLIED. | | | | 29) COMPLIED. | | | | 30) COMPLIED. | | | | 31) COMPLIED. | | | | 32) 2ND REVIEW,DOOR SCHEDULE DOESN?T PROVIDE | | RATING FOR ALL THE VERTICAL EXIT ENCLOSURES (STAIRWELL | | DOORS). FBC 1019. | | 32A) IN CHECKING THE DOOR SCHEDULE FOR EXIT STAIRWAYS | | LS1-1.1 AND A1-1.1 STAIRWELL & VESTIBULE 02 DOESN'T | | MATCH IN CONFIGURATION. | | 32B) MISSING DOOR RATINGS ON ALL ELECTRICAL, | | MECHANICAL, ELEVATOR MECHANICAL ROOMS AND STORAGE | | ROOMS, SEE A-8.01-.02 | | NOTE : TABLE 715.3 FOOTNOTE "B". SEE 715.3.3 | | FIRE DOOR ASSEMBLIES SHALL ALSO MEET THE REQUIREMENTS | | FOR A SMOKE AND DRAFT- CONTROL DOOR ASSEMBLY TESTED IN | | ACCORDANCE WITH UL 1784 WITH AN ARTIFICIAL BOTTOM SEAL | | INSTALLED ACROSS THE FULL WIDTH OF THE BOTTOM OF THE | | DOOR ASSEMBLY. | | | | 33) COMPLIED. | | | | 34) COMPLIED. | | | | 35) COMPLIED. | | | | 36) COMPLIED. | | | | 37) | | | | 38)A) EMPLYEES LOUNGE LS1-3.1& A-1.3.1 THE FLOOR PLAN | | CALCULATES OUT TO BE BETWEEN 844 & 840 SQ FT /15= TO AN | | OCCUPANT LOAD OF 56 REQUIRING 2 EXITS AND THE CORRIDORS | | TO BE FIRE RATED 1 HR. | | TABLE 1016.1. THIS WILL ALSO REQUIRE THE DOORS TO HAVE | | THE FIRE RATING NOT SHOWN ON THE DOOR SCHEDULE. | | | | 38B) TRAINING ROOM LS1-4.1 THE TRAINING ROOM AND | | VESTIBULE TOTAL 1495 SQ FT/20= 75 OCCUPANT LOAD. THE | | DECUSSION AT LAST WEEKS MEETING WAS THAT WILLIAM | | SWICHER HAD INDICATED THIS WAS TO BE FIXED SEATING, WE | | HAVE E-MAILED MR. SWICHER TO VERIFY THIS ROOM WILL HAVE | | FIXED SEATING BOLTED TO THE FLOOR. AT PRESENT NO REPLY | | FROM MR. SWICHER.PLEASE PROVIDE THE1HR RATED | | CORRIDOR AND OPENING PROTECTIVES REQUIRED BY TABLE | | 1016.1. | | | | 38C) LS1-3.2 & A1-3.2 IS STILL MISSING THE 1 HR RATING | | BETWEEN THE CORRIDOR THAT SEPERATES THE BUSINESS AND | | ASSEMBLY OCCUPANCY. TABLE 1016.1. | | | | 39) COMPLIED. | | | | 40) SECOND REQUEST,THE OTHER ISSUE THAT WAS DISCUSSED | | WITH THE DESIGN TEAM IS THE ?MECHANICAL MEZZANINE? , | | SHEET LS1-1.2, THIS SHEET DOESN?T INDICATE THE | | MEZZANINE LEVEL, OR SIZE. | | | | PROVIDE A FLOOR PLAN INDICATING THE SIZE OF ROOM AND | | FLOOR AREA OF THE MEZZANINE. | | INDUSTRIAL EQUIPMENT PLATFORM CAN ONLY BE USED IN | | INDUSTRIAL OCCUPANCIES. 505.5. | | THE SECOND ISSUE IS THE USE OF ALTERNATING STAIRS FOUND | | ON SHEET A6-6.1. SECTION 1009.1 LIMITS THE USE OF | | ALTERNATING TREAD STAIRS TOMEZZANINES OF 250 SQ FT | | AND LESS. | | | | 40A) DOME AREA IS 480 SQ FT. | | 40B) A2M101 IS 930 SQ FT. | | 40C) A2M102 IS 960 SQ FT. | | | | 41) COMPLIED. | | | | 42) SHEET THAT STILL HAVE DETAIL MARKERS MISSING IS | | A1-2.1( MISSING THE SHEET LOCATION) | | | | 43) COMPLIED, STILL NEEDS WALL AND DOOR RATING. | | | | 44) COMPLIED. | | | | 45)3RD REQUEST , PLANS ARE MISSING THE WALL RATING | | TAGS ON SHEET A1-GA.FPL VAULT, MAIN ELECTRIC ROOM, FIRE | | PUMP ROOM, DOORS ARE NOT LABELED ON THE | | DOOR SCHEDULE . ALSO SEE LS).0 FIRE RESISTANCE | | RATINGS. | | | | 46) COMPLIED. | | | | 47) COMPLIED. | | | | 48) COMPLIED. | | | | 49)COMPLIED. | | | | 50) COMPLIED. | | | | 51) COMPLIED. | | | | 52) COMPLIED. | | | | 53) COMPLIED. | | | | 54) COMPLIED. | | | | 55) COMPLIED. | | | | 56) COMPLIED. | | | | 57) COMPLIED. | | | | 58) COMPLIED. | | | | 59) COMPLIED. | | | | 60) COMPLIED. | | | | 61) COMPLIED. | | | | 62) COMPLIED. | | | | 63) COMPLIED. | | | | 64) LS1-GA.1- LS1-GA.3THE PARKING GARAGE EXITS DO NOT | | HAVE THE REQUIRED EGRESS CAPACITY GRAPHICS FILLED IN. | | 106.1.2* ADDITIONAL INFORMATION REQUIRED. | | LIFE SAFETY PLANS NOT SUBMITTED. | | | | 65) 3RDREQUEST, LS1-3.0/ A1-3.2 THERE ARE ISSUES WITH | | 3 AREAS: | | ELEVATOR LOBBY C3.201 | | PREFUNCTION LOBBY C3.301 | | LOBBY C3.303 | | THE BUILDING OFFICIAL WAS MADE AWARE THAT THESE AREAS | | INDICATED ON THE LIFE SAFETY PLAN DO NOT HAVE AN | | OCCUPANT LOAD ASSIGNED TO THEM.NEIL INDICATED HE | | WOULD LIKE | | THESE AREAS TO BE TREATED JUST AS THE MALL AREA ON THE | | FIRST FLOOR, SUBTRACT THE SQUAREFOOTAGE REQUIRED FOR | | EXIT ACCESS CORRIDORS OUT OF THE GROSS AREA FOR EACH | | AREA, THE NET SQUARE FOOTAGE WOULD BE TREATED AS | | ADDITIONAL SQ FOOTAGE TO BE CONSIDERED AT 7 SQUARE FEET | | PER PERSON.TABLE 1004.1.2. | | | | THIS ADDITIONAL OCCUPANT LOAD SHALL BE ADDED TO THE | | LIFE SAFETY SHEETS, STAIRS AND DOORWAY MAY NEED TO BE | | INCREASED IN SIZE DUE TO THE ADDITIONAL LOADING. | | | | 66)2ND REQUEST,THE OTHER ISSUE IN THIS AREA OF THE | | LIBRARY THIRD FLOOR AND THE AMOUNT OF ASSEMBLY | | OCCUPANCY, THE EXIT ACCESS CORRIDORS NOT BEING RATED | | (NORTH SIDE OF ASSEMBLY AREA). STAIR# 8 VESTIBULE | | MISSING FIRE RATING. PLEASE REVISE THE LIFE SAFETY PLAN | | AND DOOR SCHEDULE TO COMPLY WITH THE REQUIREMENTS OF | | TABLE 1016.1 FOR | | ASSEMBLY OCCUPANCY, SPRINKLERED >30= 1 HR FIRE RATED | | CORRIDORS. | | | | 67A) COMPLIED. | | | | 67B) COMPLIED. | | | | 68) SAME AS 38A AND 38 B. 3RD REQUEST,68)2ND REQUEST, | | LS1-3.0 CITY HALL SIDE OF PLAN INDICATES (2) AREAS | | WHERE THERE ARE ASSEMBLY OCCUPANCIES, ROOM A3.108 THE | | EMPLOYEES LOUNGE, OCCUPANT LOAD OF 60 AND ROOM NUMBER | | A3.110THE EXERCISE ROOM WITH AN OCCUPANT LOAD OF 19. | | | | | | THE EMPLOYEE LOUNGE WILL REQUIRE 2 MEANS OF EGRESS, | | PLANS DO INDICATE (2) DOORWAYS ONE TO AN EXIT ACCESS | | CORRIDOR WHICH WILL REQUIRE A 1 HR FIRE RATING. SEE | | TABLE 1016.1 | | ASSEMBLY, OCCUPANT LOAD > THAN 30,SPRINKLERED = 1HR | | RATED CORRIDORS. | | | | 69) 3RD REQUEST,THE OTHER ISSUE WITH THE EMPLOYEE | | LOUNGE REQUIRING (2) MEANS OF EGRESS BEING A OCCUPANT | | LOAD GREATER THAN 50 REQUIRING A SECOND EXIT. TABLE | | 1014.1. | | PAGE 8 | | TO USE THE DOOR FROM THE EMPLOYEE LOUNGE TO THE | | EXERCISE ROOM FBC 1013.2 STATES: | | EGRESS FROM A ROOM OR SPACE SHALL NOT PASS THROUGH | | ADJOINING OR INTERVENING ROOMS OR AREAS, EXCEPT WHERE | | SUCH ADJOINING ROOMS OR AREAS ARE ACCESSORY TO THE AREA | | SERVED. ALSO THE DOORS TO THE GYM MAY END UP BEING | | LOCKED.AN EXIT ACCESS SHALL NOT PASS THROUGH A ROOM | | THAT CAN BE LOCKED TO PREVENT EGRESS.1013.2. | | | | 70) 3RD REQUEST, LS1-3.0 EXIT ACCESS CORRIDOR | | A3.012WILL HAVE TO BE 1 HR FIRE RATED, TO THE (2) | | VERTICAL EXITS ENCLOSURES. TABLE 1014.1/ 1014.1.(1). | | | | 71) COMPLIED. | | | | 72) SAME AS 38B) ,LS1-4.0 / LS1-4.1/ A1-4.0& A1-4.1 | | THESE SHEETS INDICATE TRAINING ROOM# A4.403 IS AN | | ASSEMBLY OCCUPANCY WITH AN OCCUPANT LOAD OF 75@20 SQ FT | | / PERSON, . | | TABLE 1016.1 ASSEMBLY OCCUPANCIES >30 OCCUPANT LOAD | | LOAD REQUIRES 1 HR FIRE SEPARATION IN THE ASSOCIATED | | EXIT ACCESS CORRIDORS. THE 2 CORRIDORS THAT LEAD TO THE | | VERTICAL EXIT ENCLOSURES WILL NEED TO BE FIRE RATED 1HR | | WITH 20 MINUTE OPENING PROTECTIVES. | | | | 73) COMPLIED. | | | | 74) COMPLIED. | | | | 75) COMPLIED. | | | | 76) COMPLIED. | | | | 77) COMPLIED. | | | | 78)78-81 THE CONTRACTOR & DESIGN TEAM REMOVED THESE | | ITEMS FOR FURTHER UPDATING AND REVIEW!!!! | | FL BLD CODE 1609.1.4 | | : COMPONENTS & CLADDING, PROVIDE 2 COPIES(3 IF | | THRESHOLD OR RESIDENT INSPECTOR) OF PRODUCT TESTING | | REPORTS, MISSING REPORTS ARE AS FOLLOWS: (NOTE NOT | | REVIEWED BY THE ENGINEER OF RECORD)PLEASE INDICATE | | WHERE EACH OF THE PRODUCTS WILL BE USED, (EXAMPLE, | | TRAINER, TCW 250P | | ALUMINUM WINDOW WALL SYSTEM W/ UNREINFORCED MULLIONS | | SMUVS. TRAINER TCW250P ALUMINUM WINDOW WALL SYSTEM W/ | | UNREINFORCED MULLIONS LMU, | | ALUMINUM WINDOW WALL) IT APPEARS THAT THESE UNITS WILL | | BE ON THE EAST SIDE OF THE BUILDING SPANING BETWEEN THE | | 2ND & 3RD FLOOR. THERE ARE NO WINDOW OR DOOR SCHEDULES | | IN THIS PLAN, STRUCTURAL ELEVATION SHEET S0-3.0 | | INDICATES NOT TO SCALE!!! | | WITH THE IMPORTANCE FACTORS ON THIS BUILDING THE | | PRESSURES ARE GREATER THAN USUAL, PLEASE HIGHLIGHT | | WHICH UNIT WILL BE USED WHEN THE PRODUCT APPROVAL HAS | | MORE THAN ONE IN THE NOA. ALSO WITH THE WINDOW UNITS | | LISTED ABOVE ARE GOING TO BREAK AT THE | | 30?-0? LINE LARGE MISSILE / SMALL MISSILEBREAK LINE, | | HOW WILL THE MULLIONS AND OR WINDOW UNITS BREAK? | | | | | | | | A) FIXED WINDOWS | | B) OPERABLE WINDOWS | | C) MULLIONS NOT COVERED BY NOA | | D) GLAZED DOORS, AUTOMATIC SLIDERS, SWING DOORS OR | | PRE-ENGINEERED ROOF ACCESS | | HATCHES | | E) EXTERIOR METAL DOORS IF SINGLE OR PAIRS | | F) ROLL-UP OR SECTIONAL DOORS | | G) LOUVERS- WALL | | H) PANEL WALLS: SOFFITS, EFIS, STOREFRONTS, CURTAIN | | WALLS | | I) SKYLIGHTS | | J)PRE-ENGINEERED A/C STANDS | | K) ROOFING PRODUCTS: BUILT UP, MODIFIED, SINGLE PLY | | SYSTEMS, METAL ROOFING | | SPRAY APPLIED POLYURETHANE, ROOF SYSTEM | | FASTENERS, UNDERLAYMENTS AND | | WATERPROOFING ,********** NO ROOFING PRODUCTS | | SUBMITTED AT ALL!!!!!!************* | | L) ACCESS ROOF HATCHES: SINCE THERE IS NO PRODUCTS THAT | | ARE CURRENTLY LISTED WITH EITHER THE STATE WEB SITE OR | | MIAMI-DADE THIS PRODUCT WILL REQUIRE LOCAL APPROVAL | | FORMS WILL BE ATTACHED. | | | | 1609.1.4 PROTECTION OF OPENINGS. | | IN WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING THAT | | RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET (18.3 | | M) IN BUILDINGS SHALL BE ASSUMED TO BE OPENINGS AND THE | | BALANCE OF GLAZED OPENINGS IN THE REST OF THE BUILDING | | SHALL BE ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT | | RECEIVES POSITIVE PRESSURE IS IMPACT RESISTANT OR | | PROTECTED WITH AN IMPACT RESISTANT COVERING MEETING THE | | REQUIREMENTS OF SSTD 12, ASTM E 1886 AND ASTM E 1996, | | OR MIAMI-DADE TAS 201, 202 AND 203 REFERENCED THEREIN | | AS FOLLOWS: 1.GLAZED OPENINGS LOCATED WITHIN 30 | | FEET (9.1 M) OF GRADE SHALL MEET THE REQUIREMENTS OF | | THE LARGE MISSILE TEST. 2.GLAZED OPENINGS LOCATED | | MORE THAN 30 FEET (9.1 M) ABOVE GRADE SHALL MEET THE | | PROVISIONS OF THE SMALL MISSILE TEST. | | | | 79) 2ND REQUEST, W P B ADMINISTRTIVE CODE 106.3.3* | | PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED | | BY DCA RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN | | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL | | FOR JURISDICTIONAL APPROVAL. | | | | 80) SAME REQUEST AS 79. W.P.B. ADMIN CODE 106.3* | | PRODUCT APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY | | DCA RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN | | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL | | FOR JURISDICTIONAL APPROVAL. | | | | 81) 1714.5.3 EXTERIOR DOOR ASSEMBLIES. | | EXTERIOR DOOR ASSEMBLIES NOT COVERED BY SECTION | | 1715.4.2 OR SECTION 1714.5.3.1 SHALL BE TESTED FOR | | STRUCTURAL INTEGRITY IN ACCORDANCE WITH ASTM E 330 | | PROCEDURE A, AT A LOAD OF 1.5 TIMES THE REQUIRED DESIGN | | PRESSURE LOAD. THE LOAD SHALL BE SUSTAINED FOR 10 | | SECONDS WITH NO PERMANENT DEFORMATION OF ANY MAIN FRAME | | OR PANEL MEMBER IN EXCESS OF 0.4 PERCENT OF ITS SPAN | | AFTER THE LOAD IS REMOVED. HIGH-VELOCITY HURRICANE | | ZONES SHALL COMPLY WITH TAS 202. AFTER EACH SPECIFIED | | LOADING, THERE SHALL BE NO GLASS BREAKAGE, PERMANENT | | DAMAGE TO FASTENERS, HARDWARE PARTS, OR ANY OTHER | | DAMAGE WHICH CAUSES THE DOOR TO BE INOPERABLE. | | | | 82) COMPLIED. | | | | 83) COMPLIED. | | | | 84)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, | | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE | | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION. | | | | | | | | JIM WITMER | | BUILDING PLAN REVIEW | | WEST PALM BEACH CONSTRUCTION SERVICES DEPARTMENT WEST | | PALM BEACH, FL 33402 | | TEL (561)805-6715 | | FAX (561)805-6731 | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
44 |
Status |
P |
Date |
2009-09-17 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-09-17 |
Time |
18:14 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-09-17 |
Time |
18:14 |
Sent To |
PC |
|
Notes |
2009-09-17 18:15:12 | | | ** REDLINED PLANS ** | | | | | | 1) NOTE: ELEVATOR LOBBIES ON FIRST AND FORTH FLOORS AT | | LIBRARY ARE REQUIRED TO CONTAIN SOME SORT OF BATTERY | | BACK UP LIGHT FIXTURE. | | NFPA-101 7.8, 7.9 | | FBC 1006.1.2 | | | | 2) NOTE: CLOSET LIGHTS ON FIRST FLOOR CORRIDOR NEED TO | | MEET 410.8. VIF. | | | | 3) NOTE: INFORMATION FOR NEW PANELS 2HDR, 2LDR AND | | 45KVA TRANSFORMERS ADDED FOR SECOND FLOOR OFFICE BUILD | | OUTS ARE SHOWN ON BUILD OUT PLANS. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
43 |
Status |
F |
Date |
2009-06-10 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-06-10 |
Time |
11:26 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-06-10 |
Time |
11:26 |
Sent To |
PC |
|
Notes |
2009-06-10 11:26:23 | ** DENIED REVIEW** | | | | ** PLANS AND FINAL REVISIONS NEED TO BE SUBMITTED WITH | | COORDINATION OF ALL DRAWINGS. THESE ARE THE FINAL | | RECORD PLANS TO BE ON FILE. ALL ITEMS NEED TO BE | | COORDINATED AND CORRECTED. | | | | * THE FOLLOWING WILL BE SOME EXAMPLES ONLY OF AREAS IN | | WHICH THERE ARE DISCREPANCIES ON PLANS. | | | | **** THIS REVIEW IS NOT BASED ON THE COMPARISON OF | | PLANS WITH THE FIELD OR JOBSITE LOCATION. | | | | **** ONE OF THE REDLINED SET OF PLANS WHICH WAS USED IN | | REVIEW WILL REMAIN IN THIS OFFICE. IN NUMEROUS PREVIOUS | | REVIEWS AND MEETINGS IT WAS STATED TO CALL TO GO OVER | | ANY QUESTIONS ON COMMENTS WITH RESPECT TO PLANS OR | | PROPOSED DESIGN. IT IS STRONGLY RECOMMENDED THAT A | | MEETING BE HELD TO GO OVER ANY COMMENTS WHICH MAY NOT | | BE CLEAR OR UNDERSTOOD IN ANY WAY. THIS MEETING SHOULD | | BE HELD WITH REPRESENTATIVES FROM THE GENERAL | | CONTRACTOR, ELECTRICAL CONTRACTOR, ARCHITECTURAL FIRM, | | ENGINEERING FIRM AND THE CITY OF WEST PALM BEACH. | | | | **** THE LIGHTING CONTROL PANEL WILL BE NOTED AS LCP IN | | MANY OF THE COMMENTS BELOW. | | | | **** MANY OF THE COMMENTS BELOW WILL BE GENERAL TO THE | | SECTIONS OF CODES FOR LIGHTING CONTROLS, PANEL SCHEDULE | | AND RECORD PLANS. | | 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4. 408.4, 106.5, | | 106.1.1, 106.1.2 ETC | | MORE SPECIFIC CODES WILL BE NOTED IN OTHER LOCATIONS. | | ** PLEASE BE SURE TO SEE 408.4 WHICH REQUIRE ALL | | LOCATIONS TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH | | THEY FEED. STATING *RECEPTACLES* OR * LIGHTING* IS NOT | | SPECIFIC FOR PANEL SCHEDULES OR PANEL SCHEDULES ON | | RECORD PLANS. | | | | 1) NOTE: PLEASE SUBMIT AN UPDATE LAYOUT OF ALL | | ELECTRICAL ROOMS WHICH EQUIPMENT WAS ADDED. FOR EXAMPLE | | THERE ARE NEW TRANSFORMERS AND PANELS FOR SOME | | LOCATIONS THROUGH OUT THE PLANS. THE TRANSFORMER FOR | | PANEL A FOR EXAMPLE COULD NOT BE LOCATED ON PLAN. | | SEE OTHER NOTES BELOW WITH RESPECT TO OTHER PANELS AND | | COORDINATION OF PLANS.110.26, FBC 106.1.2,106.1.1, | | 106.5 FOR COORDINATION OF RECORD DOCUMENTS. | | THE MAIN ELECTRICAL ROOM IS ONE EXAMPLE OF EQUIPMENT | | BEING ADDED WHICH IS NOT PART OF THE REVISED PLANS. THE | | RECORD PLANS DO NOT INCLUDE OTHER WORK WHICH HAS BEEN | | DONE. | | | | 2) NOTE: PLEASE SUBMIT PANEL SCHEDULE FOR NEW PANEL *A* | | WHICH IS NOW SHOWN ON PLANS. PLEASE BE SURE TO | | COORDINATE. 408.4 | | | | 3) NOTE: PLEASE SHOW LOCATION OF THE TRANSFORMER FOR | | THE SAME PANEL *A*. 450.9, 450.13, 110.26 ETC. AS THIS | | IS NOT SHOWN CODE COMPLIANCE CAN NOT BE DETERMINED. | | | | 4) NOTE: PLEASE REMOVE ALL WORK IN AREAS FOR WHICH THE | | *PHOTO MUSEUM* WILL BE LOCATED. ONE EXAMPLE IS THE 2ND | | FLOOR WHICH STILL INDICATES LIGHTING AND OTHER ITEMS | | WHICH ARE NOW NO LONGER PART OF THE BASE BUILDING. | | PLEASE TAKE A LOOK AT THEIR TENANT SPACE PLANS AND | | REMOVE LIGHTS AS NEEDED. | | PLEASE ALSO COMPLETE LATEST REVISED PLANS FOR COMMON | | AREAS WHICH ARE TO BE FED FROM BASE BUILDING AND ARE | | NOT PART OF THE TENANT SPACE. | | THE RISER STILL INDICATES THE 800A BREAKER FOR THE | | PHOTO-MUSEUM EVEN THOUGH THE SPACE IS FED FROM A | | SEPARATE SERVICE. | | SEE D2.106 | | | | 5) NOTE: RECEPTACLES IN MAIN MECHANICAL ROOM DO NOT | | CONNECT TO ANY CIRCUIT. | | | | 6) NOTE: PLEASE SEE 2-HA-18 WHICH IS SHOWN AS EXTERIOR | | LIGHTS ON PLANS YET THE LCP IS NOT COMPLETE OR LISTS | | THE CIRCUIT. THE PANEL SCHEDULE FOR HA-18 IS SHOWN AS | | SPARE EVEN THOUGH IT IS ON PLANS. | | | | 7) NOTE: PLEASE SEE 2-HC-18 IS NOTED ON PLANS YET NOT | | ON LCP. | | | | 8) NOTE: PLEASE SEE 2-HA-10 WHICH IS NOT ON LCP. | | | | 9) NOTE: PLEASE SEE 2-HB-8 WHICH IS SHOWN AS EXTERIOR | | LIGHTS ON PANEL SCHEDULE HOWEVER THE LCP STATES THIS IS | | FOR LIGHTING INSIDE IN OPEN WORK AREA. | | | | 10) NOTE: PLEASE SEE 2-HA-19 WHICH IS NOT LISTED ON LCP | | HOWEVER ON PLANS AND PANEL SCHEDULE. | | | | 11) NOTE: PLEASE SEE FIRST LEVEL COMMON AREAS WHICH DO | | NOT INDICATE ANY LIGHTING, LIGHTING CONTROLS, AND | | CIRCUITS ETC WHICH ARE NOT PART OF THE PHOTO MUSEUM | | SPACE. | | 13-415.1.ABC.1.1,1.2, .1.3. | | | | 12) NOTE: PLEASE COMPLETE PLANS WITH NEW LIGHTING FOR | | COMMON AREAS OUTSIDE PHOTO MUSEUM SPACE. PLEASE SEE | | NFPA-101 7.8 AND 7.9 FOR COMPLETE LIGHTING IN COMMON | | AREAS FOR LIFE SAFETY. OTHER ITEMS SUCH AS HORNS, | | STROBES, HORN/STROBE FOR COMPLIANCE WITH NFPA-72 AND | | COMPLIANCE WITH FBC 11-4.27.4 SHALL ALSO BE MET. FIRE | | ALARM PLANS HAVE NOT BEEN UPDATED AND COORDINATED TO | | DATE OF THIS REVIEW. | | | | 13) NOTE: PLEASE SEE EE FIXTURE ON C2-2.2 WHICH DOES | | NOT INDICATE ANY CIRCUIT OR CONTROL. THE PREVIOUS PLANS | | DID SHOW CIRCUITING AND CONTROLS. | | | | 14) NOTE: WHERE ARE THE CONTROLS FOR 1-GHA18-20? | | | | 15) NOTE: PLANS SHOW CIRCUIT 1-GLA-30 AS A DEDICATED | | CIRCUIT FOR SODA MACHINE HOWEVER BASED ON THE PLANS | | THIS SAME CIRCUIT IS SHOWN IN MORE THAN ONE LOCATION. | | ONE LOCATION IS THE STORAGE ROOM IN GARAGE WHICH | | INDICATES THE SAME CIRCUIT. | | | | 16) NOTE: PLEASE SEE CIRCUIT 1LB3-21 AND 24 WHICH BOTH | | INDICATE CIRCUITS TO COMMON AREA RECEPTACLES IN SPACE | | A1.115. ARE NOT ONE OF THESE AT LEAST A DEDICATED | | CIRCUIT FOR SODA MACHINE? | | | | 17) NOTE: PLEASE SEE CIRCUIT 1-GLEA-2 WHICH INDICATES | | PLANS A J-BOX YET THIS IS CIRCUITED AS A FA NAC. | | | | 18) NOTE: PLEASE SEE 1-LC2-31 ON PLANS SHOWN AS CIRCUIT | | TO ROOM C1.101 HOWEVER PANEL SCHEDULE INDICATES | | C1.301?? | | | | 19) NOTE: PLEASE SEE POWER PLANS FOR EXAMPLE E1-1.1 | | WHICH DOES NOT SHOW THE NEW PANELS 1TV AND 1LS-1. THESE | | ARE SHOWN ON E7-7.0 YET NOT COORDINATED. | | THE PANEL SCHEDULE FOR EACH OF THESE INDICATED ROOM | | LOCATIONS HOWEVER PANEL NOT AS ON PLANS. ONE OF THESE | | WOULD BE 1TV WHICH STATES THE LOCATION AS A1.406 YET | | SHEET E7-7.0 SHOWS THIS IN ANOTHER LOCATION NEXT TO | | 1LS-1. | | | | 20) NOTE: PLEASE SEE 1TV WHICH IS SHOWN AS 200AMP MLO | | ON SCHEDULE AND ON RISER THIS IS SHOWN AS 150AMP. ?? | | | | 21) NOTE: PLEASE SEE 1LD2-13 ON PANEL SCHEDULE WHICH | | STATES THIS IS FOR AHU-1 PUMP. YET PLANS INDICATE THIS | | FOR GENERAL RECEPTACLE CIRCUIT FEEDING OTHER AREAS | | BESIDES PUMP? | | | | 22) NOTE: PLEASE SEE 2-LA-3-3 ON PANEL WHICH STATES | | THIS FEEDING LOCATION A2.213 YET THE PLANS SHOWS THE | | LOCATION IN FOYER SINGLE LOCATION A2.003. | | | | 23) NOTE: PLEASE SEE 2LD-2-3 WHICH IS NOT SPECIFIC TO | | ROOMS AND LOCATIONS IN WHICH THIS CIRCUIT FEEDS. PANEL | | SCHEDULE DOES NOT LIST LOCATIONS AS FOUND ON PLANS. | | | | 24) NOTE: PLEASE SEE 2LD2-6 WHICH IS SHOWN AS SPARE ON | | PANEL SCHEDULE HOWEVER THE PLANS ON E1-2.2 STILL HAS | | CIRCUIT SHOWN. | | | | 25) NOTE: PLEASE CORRELATE ALL POWER AND RELEVANT | | CHANGES ON POWER PLANS E1-1.1 WITH E7-7.0. | | THERE ARE NUMEROUS ITEMS | | | | 26) NOTE: PLEASE SEE 1LA3-10 WHICH PER PANEL SCHEDULE | | IT STATES COMMISSION OFFICE HOWEVER PLEASE SEE SHEET | | E7-7.0 WHICH INDICATES THIS AS A DEDICATE RECEPTACLE IN | | THE FLAGLER GALLERY. | | | | 27) NOTE: PLEASE SEE 1LA3-18 WHICH DOES LIST THIS AS | | A1-308 ON PLANS HOWEVER PLEASE SEE E7-7.0 | | | | 28) NOTE: PLEASE SEE 3LD2-9 NEEDS TO BE SPECIFIC TO | | ROOMS AND AREAS IN WHICH THEY FEED. THE PLANS INDICATE | | MANY MORE LOCATIONS THAN WHAT IS LISTED ON PANEL | | SCHEDULE. | | | | 29) NOTE: PLEASE SEE 3LC-19 NEED TO BE SPECIFIC TO ALL | | ROOMS AND AREAS IN WHICH THEY FEED. | | | | 30) NOTE: PLEASE SEE 3LD3-21 ON PANEL SCHEDULE WHICH | | INDICATES THIS AS A SPARE CIRCUIT HOWEVER THE PLANS | | STILL SHOW THIS CIRCUIT. | | | | 31) NOTE: PLEASE SEE 3LD3-6 WHICH THE PANEL SCHEDULE | | INDICATES THIS AS A SPARE YET THE PLANS STILL INDICATES | | THIS AS A CIRCUIT BEING USED. | | | | 32) NOTE: PLEASE SEE CIRCUITS 4LA3-5 AND -24 WHICH ARE | | BOTH SHOWN TIED TOGETHER ON PLANS. WHY ARE THESE NOT | | SEPARATED? | | | | 33) NOTE: PLEASE SEE MULTIPLE SETS OF FURNITURE WORK | | STATIONS WHICH SHOW THE SAME CIRCUITING 4LB3-26,28,30. | | PLEASE SEE 220.14(I) FOR LOADS PER YOKE. PLEASE PROVIDE | | INFORMATION ON HOW MANY RECEPTACLES ARE ON THE CIRCUITS | | AS SHOWN FOR KNOWN LOADS. THIS WAS GONE OVER IN | | ORIGINAL REVIEW EVEN BEFORE PERMIT ISSUANCE FOR KNOWN | | LOADS AND LOADS FIGURED AT 180VA. THE REVIEW COMMENTS | | CAN BE PROVIDED ALONG WITH E-MAILS IN WHICH QUESTIONS | | WERE RAISED. | | | | 34) NOTE: PLEASE SEE MULTIPLE SETS OF FURNITURE WORK | | STATIONS WHICH SHOW THE SAME CIRCUITING 4LA3-15,17,19. | | PLEASE SEE 220.14(I) FOR LOADS PER YOKE. PLEASE PROVIDE | | INFORMATION ON HOW MANY RECEPTACLES ARE ON THE CIRCUITS | | AS SHOWN FOR KNOWN LOADS. | | THIS WAS GONE OVER IN ORIGINAL REVIEW EVEN BEFORE | | PERMIT ISSUANCE FOR KNOWN LOADS AND LOADS FIGURED AT | | 180VA. THE REVIEW COMMENTS CAN BE PROVIDED ALONG WITH | | E-MAILS IN WHICH QUESTIONS WERE RAISED. | | | | 35) NOTE: PLANS STILL STATE IT EQUIPMENT TO BE DONE BY | | OTHERS. HOWEVER THE RECORD SET OF PLANS NEED TO NOW | | SHOW ALL OF THIS WORK BEING COMPLETED. PLEASE COMPLETE | | THE IT PANEL SCHEDULE. THE SCHEDULE DOES INDICATE THE | | CIRCUITING FOR AC EQUIPMENT ETC HOWEVER NO OTHER | | EQUIPMENT IS SHOWN BEING FED FROM THIS PANEL. | | WHERE IS ALL OF THE OTHER EQUIPMENT BEING FED FROM? | | CIRCUITS? LOADS? ETC | | 408.4,310.16,240.3,220, ETC | | 645 (ALL) | | | | 36) NOTE: PLEASE PROVIDE INFORMATION ON THE EPO AT THE | | DOOR FOR IT ROOM. | | PLEASE SEE 645.10 FOR THE REQUIRED DISCONNECTING MEANS | | TO ALL EQUIPMENT INCLUDING AC EQUIPMENT. | | THERE IS A CIRCUIT ON 1LED-27 FOR SHUNT TRIP CIRCUIT | | HOWEVER THE IT PANEL OR FEED TO IT PANEL DOES NOT | | INDICATE ANY SHUNT TRIP TYPE MAIN BREAKER OR BRANCH | | BREAKER. THE RISER DOES NOT INDICATE A SHUNT FOR ANY OF | | THE MAIN BREAKERS OR FEEDERS. | | PLEASE PROVIDE INFORMATION AND DETAIL FOR THIS. | | | | 37) NOTE: PLEASE SEE 4LEB-10 WHICH IS SHOWN AS SPARE ON | | PANEL SCHEDULE YET THE PLANS STILL INDICATE THIS | | CIRCUIT. | | | | 38) NOTE: PLEASE SEE 4IT 15,17 ON PANEL SCHEDULE THIS | | IS SHOWN TO RM A4.416 YET THE PLANS DO NOT INDICATE | | THIS. | | | | 39) NOTE: PLEASE SEE 4LD2- 5 STATES RECEPTACLES IN ROOM | | 4-106 HOWEVER THIS IS SHOWN ON PLANS FEEDING OTHER | | AREAS ALSO. | | | | 40) NOTE: PLEASE SEE 4LC2-13 WHICH IS SHOWN ON PANEL TO | | ROOM A4-201 HOWEVER ON PLANS THIS IS LOCATED AT THE | | OTHER END OF THE FLOOR. | | | | 41) NOTE: PLEASE SEE 4LC3-9 AND 25 WHICH IS SHOWN TO | | ROOM/AREA C4.202 YET THE PANEL SCHEDULE INDICATES ONE | | OF THESE FOR THIS LOCATION AND ONE OF THESE FOR A | | DIFFERENT LOCATION. THERE IS ALSO THE FACT THE J-BOX IS | | ALSO FED FROM THE ONE OF THESE CIRCUITS WHICH IS #25. | | IS THIS CORRECT FOR THE J-BOX? | | | | 42) NOTE: PLEASE SEE 4LD3-3, 22 AS BOTH ARE SHOWN ON | | PLANS, HOWEVER PLEASE SEE THAT THE PANEL SCHEDULE FOR | | 22 IS BLANK. | | | | 43) NOTE: PLEASE SEE MULTIPLE SETS OF FURNITURE WORK | | STATIONS WHICH SHOW THE SAME CIRCUITING SUCH AS | | 5LA3-21, 23. PLEASE SEE 220.14(I) FOR LOADS PER YOKE. | | PLEASE PROVIDE INFORMATION ON HOW MANY RECEPTACLES ARE | | ON THE CIRCUITS AS SHOWN FOR KNOWN LOADS. THIS WAS GONE | | OVER IN ORIGINAL REVIEW EVEN BEFORE PERMIT ISSUANCE FOR | | KNOWN LOADS AND LOADS FIGURED AT 180VA. THE REVIEW | | COMMENTS CAN BE PROVIDED ALONG WITH E-MAILS IN WHICH | | QUESTIONS WERE RAISED. | | | | 44) NOTE: PLEASE SEE 5LA2- 34 WHICH ON THE PANEL | | SCHEDULE IT STATES ELECTRICAL ROOM A5.107 RECEPTACLES. | | HOWEVER THE PLANS SHOW A COMPLETELY DIFFERENT CIRCUIT | | WHICH FEEDS MANY OTHER LOCATIONS. THE CIRCUIT ON PLANS | | FOR THIS ROOM IS NOT #34. SEE THE FOLLOWING COMMENT. | | | | 45) NOTE: PLEASE SEE 5LA2-3 ON PANEL SCHEDULE WHICH | | STATES CORRIDOR LIGHTING. HOWEVER ON PLANS THIS FEEDS | | ROOM ABOVE WHICH IS A5.107, 5.103,5.104,203 ETC | | | | 46) NOTE: PLEASE SEE A1.014 ON PLANS SHOWS HA-1 HOWEVER | | THE DESIGNATION ON PANEL SCHEDULE IS NOT THE SAME. | | SHOWS A DIFFERENT ROOM. | | | | 47) NOTE: PLEASE SEE 1HA-12 ON PLANS AND PANEL SCHEDULE | | HOWEVER THIS IS NOT PART OF THE LCP. | | | | 48) NOTE: PLEASE SEE 410.8 A-D FOR MINIMUM LIGHTING | | FIXTURE CLEARANCES FROM COMBUSTIBLES IN CLOSETS WITH | | SHELVING. PLEASE SEE STORAGE CLOSETS A1.612,613.14. | | PLEASE PROVIDE EXACT SHELVING DIMENSION ON PLANS SO | | THAT THE CLEARANCES CAN BE DETERMINED. | | | | 49) NOTE: PLEASE SEE 1HA-2 WHICH THE PLANS , THE PANEL | | SCHEDULE AND THE LCP DO NOT CORRELATE. THE CIRCUITING | | ON PLANS SHOWS ONE LOCATION/ROOM WHICH IS THE GALLERY | | A1.306 YET THE PANEL STATES THIS CIRCUIT IS FOR | | EXTERIOR FIXTURES. THE LCP DOES NOT INDICATE ANY OF | | THESE. | | | | 50) NOTE: PLEASE REVISE FIXTURE SCHEDULE AND SUBMIT. | | FIXTURES FOR EXISTING LOCATION AND REVISED LOCATIONS ON | | PLANS CAN NOT BE DETERMINED AS CODE COMPLIANT WITH THE | | EXISTING REVISED CALCULATIONS PER 13-415.2. | | | | 51) NOTE: PLEASE SHOW LOCATIONS OF REQUIRED OVER RIDES | | ON THE 3RD FLOOR EAST END OF LIBRARY. REVISION 17 | | DELETED THE REQUIRED OVER RIDES BASED ON | | FURNITURE/SHELVING LAYOUT. ALL REVISED PLANS UP TO THIS | | LATEST REVISION STILL INDICATE EACH OF THE CIRCUITS | | WILL GO TO OVER RIDE SWITCHES HOWEVER NEW LOCATIONS | | WERE NOT SHOWN. | | PLEASE SEE 13-415.1.ABC.1.1, .1.2 OF THE FBC. LOCATION | | REQUIRES THE OCCUPANT TO SEE ALL LIGHTING WHICH IS | | BEING OVER RIDDEN OR MEET EXCEPTIONS. | | | | 52) NOTE: PLEASE UPDATE ALL LCP. MANY OF THESE DO NOT | | LIST THE CIRCUITS ON THE PANEL SCHEDULES OR THE | | LOCATIONS LISTED ARE NOT CORRECT. | | | | 53) NOTE: PLEASE SEE 1HC-19 AS THIS IS ON PLAN AND | | SCHEDULE HOWEVER NOT ON LCP. | | | | 54) NOTE: PLEASE SEE LOBBY D1.003 WHERE ARE THE LIGHTS | | WHICH IS NOT PART OF THE PHOTO MUSEUM? FBC CHAPTER 10, | | NFPA- 101 7.8, 7.9. | | NEC CHAPTERS 2,3,4, GIVEN AS GENERAL SECTIONS. | | PLANS ARE BLANK. | | | | 55) NOTE: PLEASE SEE C1.102 AS THERE IS NO CIRCUIT | | LISTED OR SHOWN FOR LIGHTING. WHERE DOES THIS | | INTERCONNECT AND WITH WHICH CIRCUIT? | | | | 56) NOTE: PLEASE SEE 2HA-12 WHICH IS NOT SPECIFIC TO | | ROOMS AND AREAS. | | | | 57) NOTE: PLEASE SEE 2HA-19 WHICH IS ON PLANS, ON PANEL | | SCHEDULE HOWEVER LCP IS BLANK AND DOES NOT INDICATE. | | | | 58) NOTE: PLEASE SEE A2.210 AND .211 ROOMS. WHERE DO | | THE LIGHTS IN THESE TWO ROOMS CONNECT? THE PLANS APPEAR | | TO MAYBE CONNECT TO 2HA-47 HOWEVER BASED ON THE PANEL | | SCHEDULE THESE TWO ROOMS ARE NOT LISTED. | | | | 59) NOTE: PLEASE SEE 3HA-16 WHICH IS SHOWN ON PLANS, | | YET THERE IS NOTHING ON PANEL SCHEDULE OR LCP. | | | | 60) NOTE: PLEASE SEE 3HA-6 STATES ON THE PANEL SCHEDULE | | THIS FEEDS A3.009 AND A3.402 YET THE PLANS INDICATE | | A3.402 BEING FED FROM 3HA-8. PLEASE SEE OTHER LOCATIONS | | NOT SPECIFIC. | | | | 61) NOTE: PLEASE 3HA-8 WHICH IS NOT SPECIFIC. | | | | 62) NOTE: PLEASE COMPLETE PLANS WITH CIRCUITING, LOADS | | AND LIGHTING FOR STAGE AREA LIGHTING. PLANS SHOW *TO BE | | BY OTHERS* HOWEVER THAT WAS WHEN NONE OF THAT | | INFORMATION WAS KNOWN. THIS IS THE END OF THE BUILDING | | ALL OF THE LIGHTING, CIRCUITING, LOADS ETC ARE KNOWN AT | | THIS TIME WHICH NEEDS TO BE COMPLETE ON PLANS. | | 220,13-415.1.ABC.1.1, .1.3 ETC | | | | 63) NOTE: PLEASE SEE AREAS C3.110,.109,0309 ETC. THE | | NORMAL LIGHTING IN THIS AREA DOES NOT HAVE ANY CIRCUIT | | NOTED OR SHOWN. | | | | 64) NOTE: PLEASE SEE E2-4.1, LIGHTS IN CORRIDOR A4.009 | | WHICH DOES NOT INDICATE ANY CIRCUITING FOR NORMAL | | LIGHTING?? | | | | 65) NOTE: PLEASE SEE 4HC-12 WHICH IS LISTED ON THE LCP | | HOWEVER NOT ON PANEL SCHEDULE. | | | | 66) NOTE: PLEASE SEE 4HC-2 WHICH IS ON SCHEDULE FOR | | LIGHTING IN ELEVATOR LOBBY 5 AND 6; HOWEVER THIS SAME | | LOBBY AREA DOES NOT HAVE ANY CIRCUIT FOR THE LIGHTING | | ON PLANS. IN FACT THE LIGHTING ON PLANS IS ALL SHOWN AS | | EMERGENCY CIRCUITED LIGHTING HOWEVER NO CIRCUIT OR | | CONNECTION TO OTHER CIRCUITS IS SHOWN. | | THE CIRCUIT 4HC-2 ON PLANS IS ONLY FEEDING THE C4.105 | | ROOM AND ALSO THE TWO BATHROOMS C4.102,.103 WHICH DOES | | NOT COORDINATE WITH THE PANEL SCHEDULE. | | | | 67) NOTE: PLEASE SEE 4HC-10 WHICH IS ON PANEL SCHEDULE | | HOWEVER ON LCP. | | | | 68) NOTE: PLEASE SEE 5HA-3 WHICH IS LISTED ON THE LCP | | HOWEVER IT IS NOT ON THE PANEL SCHEDULE. ** PLEASE SEE | | THIS SHEET OF PLANS. E2-5.1, GO OVER PLANS. SEE | | COMMENTS BELOW. | | | | 69) NOTE: PLEASE SEE 5HA-17 WHICH STATES * OPEN WORK | | AREA A5.404 HOWEVER ON THE PLANS THIS IS COMPLETELY | | SEPARATE. A5.112,.104,.103. | | | | 70) NOTE: PLEASE SEE AREAS OF NORMAL LIGHTING A5.507, | | .506, .504,.501,.528,.503,.505,.508 ETC WHICH DO NOT | | SHOW ANY CIRCUITING ON PLANS. | | | | 71) NOTE: PLEASE SEE 5HB-5 WHICH IS SHOWN ON PLANS, YET | | THIS IS SHOWN AS A SPARE ON PANEL SCHEDULE. | | | | 72) NOTE: FEE BALANCE OF $1160.00 IS DUE BEFORE PICKING | | UP PLANS AND RESUBMITTING NEW REVISIONS. | | | | | | **** THIS IS NOT AN EXHAUSTED LIST OF ALL POSSIBLE | | ITEMS. THESE HAVE BEEN GIVEN AS EXAMPLES ONLY! THESE | | ARE NOT ALL ITEMS. | | | | | | | | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
42 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-06-02 |
Time |
11:25 |
Sent To |
|
|
Notes |
2009-06-10 11:25:25 | | | | 2009-06-04 17:13:10 | REVIEW IN PROGRESS. | | | | DUE TO FOUR DAY WORK WEEK, REVIEW TO BE COMPLETED ON | | TUESDAY 6/9/09. REVIEW WILL BE GOING INTO FAILED STATUS | | FOR ALL SHEETS. NOTES TO BE POSTED UPON COMPLETION. | 2009-06-01 12:17:13 | REVIEW FEES TO DETERMINED BY THE BUILDING OFFICIAL. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
41 |
Status |
F |
Date |
2009-03-30 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-03-30 |
Time |
16:49 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-03-30 |
Time |
16:49 |
Sent To |
|
|
Notes |
2009-03-30 16:49:56 | ** DENIED REVIEW/PASSED PROVISO ** | | | | REVISION FOR CAF?? | | | | | | | | 1) NOTE: SHEET E1-1.2 STAMPED FOR INSPECTIONS OF LAYOUT | | OF ELECTRICAL ONLY. | | NO OTHER ITEMS ON THIS SHEET REVIEWED FOR CODE | | COMPLIANCE. | | | | 2) NOTE: PLANS SHOW THE LOCATION OF NEW PANEL HOWEVER | | THE NEW TRANSFORMER AND MAIN ON THE LOAD SIDE OF THE | | TRANSFORMER NEEDS TO BE SHOWN. COMPLIANCE WITH 110.26, | | 240.24, 240.21, 450.9, ETC CAN NOT BE REVIEWED AT THIS | | TIME. | | RISER NOTES STATES PANEL TO BE LOCATED IN ROOM C1.402 | | HOWEVER BASED ON SHEET E1-1.2 THE PANEL IS NOT IN THIS | | SAME ROOM/LOCATION. | | PLEASE BE SURE TO COORDINATE ALL SHEETS. | | SHEET REDLINED. | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
40 |
Status |
F |
Date |
2009-03-17 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-03-17 |
Time |
09:40 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-03-17 |
Time |
09:40 |
Sent To |
PC |
|
Notes |
2009-03-17 09:40:55 | ** NOTES REDLINED ** REVISIONS DENIED | | | | | | 1) NOTE: COORDINATION STUDY OVER ALL IS OK AND MEETS | | CODE FOR 700 AND 701 SYSTEMS. | | THERE ARE OVER LAPS SHOWN ON THE TIME CURVE | | COORDINATION STUDY BASED ON ALL TRANSFORMERS WHICH IS | | TYPICAL PER ENGINEER. THERE IS ALSO OVERLAPPING ON TWO | | BREAKERS ON THE OPTIONAL STAND-BY SYSTEM. THESE | | BREAKERS ARE RATED FOR THE AVAILABLE FAULT CURRENT | | HOWEVER THEY ARE NOT SELECTIVELY COORDINATED. THE CODE | | DOES NOT ADDRESS OPTIONAL STAND-BY FOR SELECTIVE | | COORDINATION. THIS IS EQUIPMENT WHICH IS NOT LIFE | | SAFETY/EMERGENCY OR LEGALLY REQUIRED STAND-BY. | | | | 2) NOTE: THE REVISED PLANS ARE BEING SENT BACK AS ALL | | CIRCUITING ON PLANS AND PANEL SCHEDULES NEED TO | | COORDINATE BEFORE THE FINAL CO OF BUILDING. AS THERE | | ARE STILL SEVERAL CIRCUITS ON PANELS AND PLANS WHICH | | HAVE NOT BEEN UPDATED THIS NEEDS TO BE DONE. BASED ON | | THE CIRCUITING OF THE POWER PLANS AND LIGHTING PLANS | | THERE ARE CIRCUITS FOR EXAMPLE SHOWN AS LIGHTING WHICH | | ON THE PANEL SCHEDULE THEY ARE MOTOR CONTROL CENTERS? | | THE REVIEW WILL REMAIN IN FAILED STATUS BASED ON THE | | REVISED PLANS STILL NEEDING TO BE FINALIZED. | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
39 |
Status |
N |
Date |
2009-03-05 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-03-05 |
Time |
11:25 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-03-05 |
Time |
11:24 |
Sent To |
|
|
Notes |
2009-03-05 11:26:35 | | | **REVIEW STATUS *N*. ( NOT NEEDED) | | REVISIONS FOR BASE BUILDING SITE, LANDSCAPE, | | CROSS-WALK, ETC | | | | ALL RIGHT OF WAY ELECTRICAL SHALL BE UNDER SEPARATE | | PERMIT AND MAY NOT BE PART OF THE BASE BUILDING | | PERMITTED SCOPE OF WORK. THIS WORK HAS ALREADY BEEN | | APPLIED FOR BY MISNER ELECTRIC. PERMIT #08120587 | | ALL ELECTRICAL SHOWN ON LANDSCAPE PLANS CONTAINS A NOTE | | WHICH STATES TO SEE ELECTRICAL PLANS FOR ACTUAL SCOPE | | OF WORK UNDER THE BASE BUILDING. | | ALL SITE LIGHTING POLES WHICH IS LOCATED IN THE RIGHT | | OF WAY AREAS ARE ACTUALLY UNDER SEPARATE APPLIED SITE | | RIGHT OF WAY APPLICATION WHICH BY THE WAY IS NOT YET | | ISSUED. PERMIT # 08120587 | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
38 |
Status |
N |
Date |
2009-01-30 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-01-30 |
Time |
12:32 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-01-30 |
Time |
12:32 |
Sent To |
PC |
|
Notes |
2009-01-30 12:32:51 | SITE WORK, IR AND L SHEETS DID NOT CONTAIN ANY | | ELECTRICAL FOR REVIEW. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
37 |
Status |
F |
Date |
2009-01-08 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-01-08 |
Time |
16:13 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-01-08 |
Time |
16:13 |
Sent To |
|
|
Notes |
2009-01-08 16:13:47 | ***** REVISIONS SUBMITTED 12/18/08 | | | | 1) NOTE: LOADS FOR NEW PANELS HAVE NOT BEEN INCREASED | | IN SEVERAL LOCATIONS. | | FOR EXAMPLE: NEW PANELS FOR 1HD, 2HDR, 2LDR ETC ALL THE | | WAY TO MSB1. | | THIS REQUIRES A MINIMUM FOR SPACE WHICH IS NOW KNOWN TO | | BE FUTURE OFFICE SPACE. SEE 220.12,220.14 ETC | | PLEASE SEE OTHER EQUIPMENT FOR EXAMPLE 1-DPHC WHICH HAS | | NOT BEEN REVISED SINCE REVISION 12A. IF IT HAS BEEN | | REVISED IT HAS NOT BEEN SUBMITTED. | | | | | | | | ** IMPORTANT ** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
36 |
Status |
F |
Date |
2009-01-08 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-01-08 |
Time |
16:13 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-01-08 |
Time |
16:13 |
Sent To |
|
|
Notes |
2009-01-08 16:13:30 | ** DENIED REVIEW OF REVISIONS** | | | | ** REVISIONS SUBMITTED 12/11/2008 | | | | | | | | | | | | 1) NOTE: ALTHOUGH NOT REQUIRED IT IS VERY HELPFUL IN | | THE REVIEW PROCESS TO SUBMIT A DETAIL LETTER/LISTING OF | | ITEMS REVISED ON SHEETS. | | SEE NOTES WITH RESPECT TO IDENTIFICATION AND | | COORDINATION OF THE REVISION IN THE TITLE BLOCKS, THE | | REVISIONS ON PLANS. WHEN PLANS DO NOT INDICATE THE | | REVISION OR VISE VERSA THEY ARE NOT NOTED ON TITLE | | BLOCK THE ENTIRE SHEET NEEDS TO BE REVIEWED AND | | COMPARED TO RECORD PLANS. | | | | 2) NOTE: THIS IS NOTED WITH RESPECT TO ORIGINAL PLANS | | SUBMITTED AND ISSUED FOR PERMITTING OF THE PROJECT. A | | PROVISO WAS ISSUED AND GRANTED GIVING THE PROJECT THE | | ABILITY TO MOVE FORWARD TO CONSTRUCTION. THERE ARE | | STILL SHEETS WHICH CONTAINED REDLINED ITEMS WHICH NEED | | CORRECTIONS FROM FEBRUARY OF 2007 WHICH HAVE NOT YET | | BEEN REVISED OR ADDRESSED. | | PLEASE SEE SOME EXAMPLE SHEETS SUCH AS | | 9-1.0,9-1.2,9-3.2,9-4.2 ETC. | | NOW THAT THE PROJECT IS ALMOST COMPLETE IT IS EXPECTED | | THAT THESE SHEETS ALONG WITH THE MANY OTHERS CONTAINING | | REVISIONS ARE REVISED, SUBMITTED FOR REVIEW BEFORE | | FINAL INSPECTIONS. | | | | 3) NOTE: PLEASE SEE SHEET E1-1.2 AS THIS DOES NOT | | CONTAIN REVISION #168. THIS WAS ALSO NOT ON PREVIOUS | | REVISIONS WHICH WERE STAMPED IN ERROR. | | NEC ALL AS THE REVISION IS NOT SHOW SPECIFIC CODE | | SECTION CAN NOT BE GIVEN. | | FBC 106.5 RECORD PLANS AND COORDINATION | | SHEETS STILL SHOWING LIGHTING WHICH IS IN RIGHT OF WAY | | AREA. | | | | 4) NOTE: PLEASE SEE SHEET E 5-1.0 WHICH CONTAINED 23A | | ON PLANS HOWEVER NOT IDENTIFIED BY THE TITLE BLOCK. | | FBC 106.1.1, 106.5 AS NOTED ABOVE. | | | | 5) NOTE: PLEASE SEE 6-1.0 AS NO REVISION #18 IS ON | | PLANS YET SHOWN ON TITLE BLOCKS. | | FBC 106.1.1, 106.5 AS NOTED ABOVE ON PLANS. | | | | 6) NOTE: PLEASE SEE 6-7.0 NO REVISION 168, AND NOT ON | | PREVIOUS PLANS. | | | | | | | | | | ** IMPORTANT ** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
35 |
Status |
P |
Date |
2008-12-22 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-12-22 |
Time |
14:52 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-12-22 |
Time |
14:52 |
Sent To |
|
|
Notes |
2008-12-22 14:54:20 | REV FROM 11/19 STILL IN NEED OF ADDRESSING. | | | | THIS REVISION FOR SITE LIGHTING. RIGHT OF WAY FIXTURES | | SHOWN SHALL BE CIRCUITED FROM CITY STREET ELECTRICAL | | AND NOT BUILDING. SITE LIGHTING FROM CITY CENTER | | PROPERTY IS FED FROM BUILDING. | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
34 |
Status |
F |
Date |
2008-11-19 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-11-19 |
Time |
08:08 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-11-19 |
Time |
08:08 |
Sent To |
|
|
Notes |
2008-11-19 08:08:35 | ** FAILED REVIEW ** | | | | ** REVISION 21A | | | | 1) NOTE: LOADS FOR NEW PANEL 1LF1 NEED TO BE ADDED TO | | ALL PANELS INCLUDING MSBI. | | 220 | | FBC 106.5 | | | | | | | | | | | | **IMPORTANT** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
33 |
Status |
F |
Date |
2008-11-10 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-11-10 |
Time |
14:31 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-11-10 |
Time |
14:31 |
Sent To |
PC |
|
Notes |
2008-11-10 14:31:17 | | | | | | | ** DENIED REVISION ** | | | | 1) NOTE: PLEASE SUBMIT THE RIGHT OF WAY STREET LIGHTING | | UNDER A SEPARATE PERMIT. THESE ARE NOT PART OF THE BASE | | BUILDING LEGAL ADDRESS OR ELECTRICAL SYSTEMS. | | PLEASE BE SURE THE FIXTURE INFORMATION ON PLANS IS | | COMPLETE WITH THE TYPE OF FIXTURE, THE WATTAGE, THE | | VOLTAGE ETC. THE PLANS CONTAIN NOTES WHICH STATE | | RECEPTACLES ON POLE HOWEVER NO DETAIL IS SHOWN ON HOW | | THESE WILL INSTALLED OR WIRED. ARE THESE APART OF THE | | POLE FROM THE MANUFACTURE? | | 215,300,310.16,110.3,240.4, ETC | | FBC 105.1. | | | | 2) NOTE: THE PLANS WERE NOT ROUTED TO THE BUILDING PLAN | | REVIEWER AS NO WIND LOAD INFORMATION/CALCULATIONS WERE | | SUBMITTED FOR REVIEW. IN THE INTEREST OF TIME THIS | | REVIEWER IS ONLY PLACING NOTES FOR INFORMATION WHICH | | WILL BE NEEDED FOR THE STRUCTURAL REVIEW. THE WIND LOAD | | CALCULATIONS NEED TO SHOW THE POLE, STRUCTURAL | | COMPONENTS, THE EPA (EFFECTIVE PROJECTED AREA) OF THE | | FIXTURE OR FIXTURES. THESE WILL NEED TO BE COMPLETE | | WITH TITLE BLOCKS, ORIGINAL SIGNATURE, DATE AND RAISED | | SEAL BY A FLORIDA LICENSED AND REGISTERED ENGINEER. | | FBC TABLE 1609 | | FS 471.025 | | FAC 61G15-23.002 | | | | | | | | | | | | **IMPORTANT** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
32 |
Status |
P |
Date |
2008-11-04 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-11-04 |
Time |
11:13 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-11-04 |
Time |
11:13 |
Sent To |
|
|
Notes |
2008-11-04 11:15:27 | REV 20A FOR E1-1.0, E1-1.1.3. | | | | | | REDLINED SITE AS NO LIGHTING FIXTURES SHALL BE | | INSTALLED IN RIGHT OF WAY FED FROM BUILDING. ALL RIGHT | | OF WAY LIGHTING IS TO BE FED FROM CITY STREET | | ELECTRICAL SYSTEMS UNLESS RIGHT OF WAY CHANGES. RIGHT | | OF WAY FIXTURES ARE NOT PART OF THE BASE BUILDING | | PERMIT SCOPE. THIS WAS REDLINED AND NOTED BACK ON | | ORIGINAL REVIEWS/PLANS/MEETINGS. | | ** IF FIXTURES AS SHOWN ARE WITHIN PROPERTY LINES THEN | | THIS COMMENT IS ONLY NOTED FOR INFORMATION. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
31 |
Status |
P |
Date |
2008-10-29 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-10-29 |
Time |
16:56 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-10-29 |
Time |
16:56 |
Sent To |
PC |
|
Notes |
2008-10-29 16:57:31 | REVISED TO ADD EM FIXTURES IN MEETING ROOM/LIB SIDE. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
30 |
Status |
P |
Date |
2008-10-21 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-10-21 |
Time |
12:21 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-10-21 |
Time |
12:21 |
Sent To |
PC |
|
Notes |
2008-10-21 12:21:16 | REV 18 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
29 |
Status |
P |
Date |
2008-10-21 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-10-21 |
Time |
09:10 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-10-21 |
Time |
09:10 |
Sent To |
PC |
|
Notes |
2008-10-21 09:10:58 | REVISED LIGHTING PLANS, 2ND, 3RD AND 4TH FLOOR. CA | | 225-C |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
28 |
Status |
P |
Date |
2008-10-21 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-10-21 |
Time |
09:09 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-10-21 |
Time |
09:09 |
Sent To |
|
|
Notes |
2008-10-21 09:10:17 | REV FOR 16B OK, REVISED SITE LIGHTING SHEET AND | | PHOTO-METRICS |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
27 |
Status |
P |
Date |
2008-09-30 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-09-30 |
Time |
08:04 |
Rev Time |
3.00 |
Received By |
dpalmer |
Date |
2008-09-30 |
Time |
08:04 |
Sent To |
PC |
|
Notes |
2008-09-30 08:06:08 | REV 17B | | | | | | REDLINED, NO TRIPPING HAZARDS IN MAIN ELECTRICAL ROOM | | AS NOTED ON ORIGINAL REVIEWS. | | | | REDLINED SHEET E-7.7.0 AS THE SCOPE OF WORK SHOWN NEEDS | | TO BE UNDER A SEPARATE PERMIT. THIS SCOPE FOR VIDEO | | SYSTEM IN COMMISSION CHAMBERS WAS NOT PART OF ORIGINAL | | PLANS. | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
26 |
Status |
N |
Date |
2008-09-16 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-09-16 |
Time |
15:50 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-09-16 |
Time |
15:50 |
Sent To |
PC |
|
Notes |
2008-09-16 15:57:25 | | | *** NO REVIEW DONE ON ELECTRICAL PLANS WHICH WERE | | SUBMITTED ON AUGUST 21ST. AT THE REQUEST OF THE | | CONTRACTOR THE PLANS WERE PLACED ON HOLD SO THAT NEW | | SHEETS COULD BE INSERTED. CONTRACTOR?S REP?S CAME IN | | (ROY AND AMADU) AND PLACED NEW RISER SHEETS IN PLANS. | | AT THAT TIME IT WAS DISCOVERED OTHER SHEETS WERE NEEDED | | BASED ON REVISED CIRCUITING FOR SMOKE DETECTORS AND | | PANEL SCHEDULES. ALSO POSSIBLE COMMENTS FROM MECHANICAL | | REVIEWER/INSPECT WHICH MAY HAVE NEEDED PLANS TO CHANGE. | | PLANS WERE ONCE AGAIN PLACED ON HOLD. ON 9/16 I CALLED | | FRANK FROM CATALFUMO AND REMINDED THAT THE PLANS WERE | | STILL ON HOLD AND THAT WOULD NO LONGER KEEP PLANS AT MY | | DESK. PLANS WILL BE OUT FRONT UNDER *C* IN THE LARGE | | BINS WAITING FOR NEW REVISED SHEETS. | | | | IF THERE ARE QUESTIONS PLEASE CALL: | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
25 |
Status |
P |
Date |
2008-09-10 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-09-10 |
Time |
09:57 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-09-10 |
Time |
09:57 |
Sent To |
PC |
|
Notes |
2008-09-10 10:00:03 | REVISED FOURTH FLOOR LIGHTING FOR EMERGENCY BACK UP ON | | THE CITY HALL SIDE OF BUILDING. | | EMERGENCY BATTERY BACK UP FIXTURES ARE REQUIRED HOWEVER | | TYPE OF FIXTURES AND PLACEMENT IS NOT UNDER THE PLAN | | REVIEWERS DIRECTION. | | LIGTHING LEVELS EXCEED MINIMUMS WHICH IS OK. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
24 |
Status |
P |
Date |
2008-09-04 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-09-04 |
Time |
11:10 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-09-04 |
Time |
11:09 |
Sent To |
PC |
|
Notes |
2008-09-04 11:10:29 | REVISION FOR FITH FLOOR LIGHTING. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
23 |
Status |
N |
Date |
2008-07-25 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-07-25 |
Time |
10:07 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-07-25 |
Time |
10:07 |
Sent To |
B |
|
Notes |
2008-07-25 10:08:01 | LT POLE WIND LOAD CALCS SENT TO BUILDING REVIEWER FOR | | REVIEW. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
22 |
Status |
P |
Date |
2008-07-10 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-07-10 |
Time |
17:09 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-07-10 |
Time |
17:09 |
Sent To |
PC |
|
Notes |
2008-07-10 17:10:54 | REV 15C REDLINED |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
21 |
Status |
F |
Date |
2008-07-10 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-07-10 |
Time |
17:08 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-07-10 |
Time |
17:08 |
Sent To |
PC |
|
Notes |
2008-07-10 17:09:13 | ** DENIEDREVIEW OF REVISIONS ** | | | | REV 17A | | | | 1) NOTE: PLEASE PROVIDE REVISED LIGHTING PLANS FOR | | AREAS WHICH WILL BE OCCUPIED UNDER EMERGENCY | | CONDITIONS. ANY LOCATIONS SUCH AS CALL CENTER, IT | | TRAINING, IT ROOM ETC NEEDS TO CONTAIN BATTERY BACK UP | | FIXTURES OF SOME TYPE TO MEET 1FT CANDLE MINIMUM UNDER | | EGRESS CONDITIONS. | | LS 101 7.8, 7.9 | | | | 2) NOTE: PLEASE BE SURE THE LAYERS FOR SITE LIGHTING ON | | ALL SHEETS ARE ON TO SHOW REVISED CIRCUITING. SEVERAL | | FIXTURES WERE RELOCATED WHICH IS OK, HOWEVER COULD NOT | | LOCATE ANY OF THE NEW CIRCUITING ALONG WITH | | COORDINATION OF PANEL SCHEDULES. | | 408.4. | | FBC 106.1.2, 106.1.1 FOR ADDITIONAL INFORMATION AND | | CLARITY OF PLANS. | | | | 3) NOTE: PLEASE SEE E1-1.1 WHICH INDICATES RECEPTACLES | | IN THE FIRE COMMAND ROOM TO A PANEL 1LEG.HOWEVER NO | | PANEL 1LEG WAS SHOWN ON SUBMITTED. THIS MAY BE A | | MISPRINT FOR ANOTHER PANEL. | | NEC 408.4, 310.16 ETC | | FBC 106.1.1 | | | | 4) NOTE: PLEASE COMPLETE THE TRANSFORMER LEGEND FOR THE | | NEW 30KVA UNITS NOW ON PLANS. NO PRIMARY OR SECONDARY | | CONDUCTORS ARE NOTED OR SHOWN. SEE OTHER COMMENTS BELOW | | FOR OTHER NEW PANELS. | | 310.16, 240.4, 240.21 ETC | | FBC 106.1.1 | | | | 5) NOTE: PLEASE SEE THE RISER WHICH INDICATES NEW | | TRANSFORMERS HOWEVER THEY DO NOT INDICATE NAY GROUNDING | | ELECTRODE SYSTEM FOR SEPARATELY DERIVED SYSTEMS AS PART | | OF THE EXISTING GROUNDING RISER. | | PLEASE REVISE AND ALSO INDICATE CONDUCTOR SIZES. | | 250.20,250.30,250.66,250.58 | | FBC 106.1.1, 106.1.2 | | | | 6) NOTE: PLEASE SEE THE RISER SHEET WHICH INDICATES NO | | LOADS ON THE EMERGENCY SYSTEMS. THESE ARE ACTUALLY | | SHOWN BLANK WITH XXX. PLEASE EXPLAIN HOW THE LOADS | | UNDER EMERGENCY ARE DIFFERENT THAN THE LOADS UNDER | | NORMAL AS SHOWN ON PREVIOUS PLANS. WHAT LOAD SHEDDING | | IS PROVIDED TO REDUCE LOADS? | | 220, 700,701,702 | | FBC106.1.2, 106.1.1 | | | | 7) NOTE: PLEASE SEE PANEL 1TV WHICH INDICATES THIS | | BEING FED FROM 1DPHEA, HOWEVER BASED ON REVISED PLANS, | | PANELS ETC THIS SHOULD INDICATE BEING FED FROM | | 1DPHE-OP. PLEASE ADJUST | | FBC 106.1.1, | | NEC 408.4 | | | | 8) NOTE: PLEASE SEE 1TV WHICH INDICATES BRANCH AS | | EMERGENCY/ LIFE SAFETY. PLEASE ADJUST AS THIS IS AN | | OPTIONAL STAND-BY PANEL. | | 702, 408 | | FBC 106.1.1 | | | | 9) NOTE: PLEASE SEE PANEL 1TV WHICH IS SHOWN AS 100AMP | | YET THE CIRCUIT SHOWN ON 1DPHE-OP SHOWS A 150AMPS | | BREAKER FEED. | | THIS OVER CURRENT PROTECTION EXCEEDS THE RATING OF | | PANEL. | | | | 10) NOTE: PLEASE SEE 1TV WHICH AS NOTED ABOVE IS SHOWN | | AS A 100AMP PANEL YET THE RISER SHOWS THIS SAME PANEL | | AS 225AMP. | | PLEASE COORDINATE. | | NEC 408, 215, 240 ETC | | FBC 106.1.1 | | | | 11) NOTE: PLEASE SEE 1DPHE-OP AS THE PANEL SCHEDULE IS | | BLANK FOR CONDUCTORS. PLEASE COMPLETE AS THERE ARE | | SEVERAL ITEMS WHICH NEED TO BE REVIEWED FOR CODE | | COMPLIANCE. PLEASE BE SURE TO SEE OTHER COMMENTS WITH | | RESPECT TO TRANSFORMER CONDUCTORS ON THE PRIMARY SIDE. | | 240.21, 240.4, 310.16, ETC | | FBC 106.1.1 | | | | 12) NOTE: PLEASE SEE PANEL 1DPHE-OP WHICH INDICATES A | | LOAD OF 58AMP/20.9 KVA FOR 1LEDCC. HOW IS THIS AMPERAGE | | THE SAME AS SHOWN ON PANEL 1LEDCC WHEN THE VOLTAGE ON | | 1LEDCC IS ACTUALLY 120/208 AND THE VOLTAGE ON 1DPHE-OP | | IS 277/480V? | | PLEASE COORDINATE AND ADJUST. | | FBC 106.1.1 | | NEC 220, 408.4 ETC | | | | 13) NOTE: PLEASE SEE PANEL SCHEDULE FOR 1LEDCC WHICH | | INDICATES BEING FED FROM 1HEE, YET THE PANEL 1HEE DOES | | NOT FEED THIS PANEL. SEE NOTE #12 ABOVE AS THIS PANEL | | IS FED FROM 1-DPHE-OP. | | 408, 220 ETC | | FBC 106.1.1 | | | | 14) NOTE: PLEASE SEE PANEL 1HEE AS THE OVER CURRENT | | PROTECTION WHICH IS SHOWN ON PANEL TO FEED PANEL 1HED | | IS SHOWN AS 100AMP YET THE FEEDERS ARE ONLY SHOWN AS | | #8. THE #8 CONDUCTORS AS SHOWN ARE ONLY RATED FOR | | 55AMPS BASED ON 310.16, 110.14 | | | | 15) NOTE: PLEASE SEE PANELS 1LETD, 2LETD, 1GHEE, 4IT2, | | 1GLEE ETC WHICH ALL INDICATE THE PANELS BEING LOCATED | | ON THE FIRST FLOOR AND ALL LOCATED IN THE CALL CENTER. | | THE ELECTRICAL POWER PLANS CLEARLY ONLY SHOW ONE | | PANEL. | | PLEASE KNOW AS THE REVISED ELECTRICAL ROOMS HAVE NOT | | YET BEEN SUBMITTED REVIEW FOR CODE COMPLIANCE FOR | | LOCATIONS CAN NOT BE REVISED AT THIS TIME. | | PLEASE COORDINATE PANEL SCHEDULES WITH ACTUAL | | LOCATIONS. | | PLEASE SUBMIT REVISED PLANS TO SHOW THE LOCATIONS OF | | ALL PANELS. | | 110.26, 240.24 ETC | | FBC 106.1.1 | | | | 16) NOTE: PLEASE SEE CALL CENTER A1.111 WHICH INDICATES | | CIRCUIT 1LED-33 YET THE PANEL SCHEDULE IS BLANK FOR | | THIS SAME CIRCUIT. | | REVISION 15A WHICH IS A SINGLE SHEET HAS THIS SAME ITEM | | HOWEVER WILL BE REDLINED. WILL NEED TO BE REVISED. | | 408.4, 310.16, 240.4, 220. | | FBC 106.1.2, 106.1.1 | | | | 17) NOTE: PLEASE SEE 1HED WHICH THE SCHEDULE INDICATES | | THIS PANEL BEING FROM 1DPHEA YET 1DPHEA DOES NOT LIST | | THIS PANEL. | | PLEASE SEE 1HEE!! | | PLEASE COORDINATE. | | FBC 106.1.1 | | NEC 408.4 | | | | 18) NOTE: PLEASE SEE SHEET 6-7.0 WHICH INDICATES A | | PANELLCP1D YET THE PANEL SHOWN IS 1LS1 | | PLEASE COORDINATE PANELS, PLANS. | | NEC 408, | | FBC 106.1.1 | | | | 19) NOTE: PLEASE SEE 1GHEA WHICH IS SHOWN WITH TAPPED | | CONDUCTORS FROM ATS3 YET THE PANEL SCHEDULE FOR THIS | | PANEL 1GHEA INDICATES THIS PANEL AS MLO (MAIN LUG | | ONLY). THIS MAY NOT BE A MLO PANEL. PLEASE SEE 240.21, | | 408.36, 240.4, 310.16 AS TAPPED CONDUCTORS ARE REQUIRED | | TO TERMINATE INTO OVER CURRENT PROTECTION. | | PLEASE REVISE AND ADJUST. | | FBC 106.1.1 | | | | 20) NOTE: PLEASE SEE PANEL SCHEDULE FOR 4IT WHICH | | INDICATES THIS AS AN EMERGENCY/LIFE SAFETY PANEL. | | PLEASE REVISE AND ADJUST. | | 408.4, 700.1,701,702 | | FBC 106.1.1 FOR COORDINATION. | | | | 21) NOTE: PLEASE SEE PANEL 4IT WHICH INDICATES THIS | | PANEL BEING FED FROM 1HEE YET 1HEE DOES NOT LIST THIS | | PANEL. | | APPEARS TO BE A MISPRINT, PLEASE COORDINATE PLANS, | | PANELS ETC | | FBC 106.1.1 | | NEC 408.4 | | | | 22) NOTE: PLEASE SEE CIRCUITING FOR LIGHTING IN TICKET | | BOOTH ROOM IN GARAGE WHICH ISMISSING A CIRCUIT. | | PLEASE SEE ONE CIRCUIT WHICH APPEARS TO BE NOTED TO ONE | | FIGURE IN ROOM IS 1GHA-22 YET THIS CIRCUIT ACTUALLY IS | | SHOWN ON THE PLANS AND PANEL SCHEDULE FOR CANOPY | | LIGHTS. | | PLEASE COORDINATE. | | 408.4 | | FBC 106.1.1 | | | | 23) NOTE: PLEASE VERIFY THE ACTUAL WORDING NOTED IN | | OCTAGONAL NOTE #1 FOR GARAGE ENTRANCE LIGHTS. THE NOTE | | MENTIONS LIGHTS TO BE OFF AT DUSK. SHOULD THIS NOT READ | | *ON* AT DUSK? | | PLEASE PROVIDE INFORMATION FOR INTENT. | | FBC106.1.1 FOR CLARITY AND 106.1.2 FOR ADDITIONAL | | INFORMATION. | | | | 24) NOTE: AS NOTED ABOVE PLEASE INCLUDED LOCATIONS OF | | PANELS AND ALL NEW EQUIPMENT ON PLANS. PANELS SUCH AS | | 1LETD, 2LETD, TAPPED CONDUCTORS ETC NEED TO BE VERIFIED | | FOR CODE COMPLIANCE. | | FBC 106.1.1 FOR CLARITY | | 110.26, 240.24 ETC | | | | 25) NOTE: PLEASE SEE E1-3.1 WHICH INDICATES REVISED | | CIRCUITS TO A PANEL 2LEDT WHICH APPEARS TO BE A | | MISPRINT FOR WHAT SHOULD BE PANEL 2LETD. | | PLEASE SEE ROOMS A3.116, A4.3.14 | | | | 26) NOTE: PLEASE LABEL NEW CU (CONDENSING UNITS) ON | | ROOF. | | CU#1, CU#2 ETC. | | FBC 106.1.1 FOR CLARITY ON PLANS AND 106.1.2 FOR | | ADDITIONAL INFORMATION. | | | | 27) NOTE: PLEASE REVISE AND COMPLETE ALL PANEL | | SCHEDULES FOR CIRCUITS TO SPECIFIC ROOMS AND | | LOCATIONS. | | PLEASE KNOW THAT LISTING *STAIRWELL LIGHTING*IN LIEU | | OF STAIRWELL #1, STAIRWELL #5, #7 ETC WAS PERMITTED AND | | OK ON INITIAL PLANS AS CIRCUITS WOULD BE REVISED ALONG | | THE PROJECT. HOWEVER PLEASE KNOW THAT ALL PANEL | | SCHEDULES NEED TO BE REVISED FOR THESE CIRCUITS AS WELL | | AS OTHERS WHICH LIST ONLY A GENERIC DESIGNATION. THE | | DESIGNATION MAY BE ALPHA OR NUMERIC HOWEVER THIS | | DESIGNATION NEEDS TO BE THE ACTUAL DESIGNATION ON | | PLANS. | | 408.4 **SEE HANDBOOKS WHICH STATES GENERIC *LIGHTS* OR | | *RECEPTACLES* IS NOT ACCEPTABLE. | | FBC 106.1.1, 106.1.2, 106.5 | | | | 28) NOTE: PLEASE VERIFY HOW REVISION 15A IS ACTUALLY A | | REVISION WHICH IS AFTER REVISION 17.REVISION 15 | | SHEETS HAVE BEEN REDLINED AND NEED TO HAVE REVISION | | NUMBERS COORDINATED. | | | | | | ** THE SHEETS FOLLOWING ARE LISTED AT THIS TIME AS OK, | | HOWEVER BASED ON NOTES ABOVE FOR BACK UP LIGHTING NEED | | ETC SOME OF THESE SHEETS MAY NEED TO BE REVISED. | | PLEASE KNOW THAT ANY OF THESE SHEETS WHICH MAY NOT NEED | | TO BE REVISED SHOULD BE TURNED BACK IN WITH OTHER | | REVISED SHEETS WHICH ARE ADDRESSING COMMENTS ABOVE. | | | | ** IF THERE ARE ANY QUESTIONS ON HOW THIS NEEDS TO TAKE | | PLACE, PLEASE DO NOT HESITATE IN CONTACTING THIS | | OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
20 |
Status |
P |
Date |
2008-06-02 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-06-02 |
Time |
14:21 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-06-02 |
Time |
14:21 |
Sent To |
PC |
|
Notes |
2008-06-02 14:22:04 | REV FOR RECEPTS ON FLOORS ONLY. | | PREVIOUS REVIEW COMMENTS STILL IN EFFECT. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
19 |
Status |
F |
Date |
2008-05-05 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-05-05 |
Time |
19:53 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-05-05 |
Time |
19:52 |
Sent To |
|
|
Notes |
2008-05-05 19:53:11 | ** PROVISO ** | | | | ** THE BELOW IS TO HAVE PLANS REVISED AS SOON AS | | POSSIBLE. ANY INSTALLATIONS AND INSPECTIONS ARE AT | | RISK. PLANS ARE CODE COMPLIANT AT THIS TIME ****WITHOUT | | ANY NORMAL OCCUPANCY *** UNDER GENERATOR POWER. | | | | | | 1) NOTE: THIS REVIEWER ALONG WITH THE FIRE MARSHAL IS | | ONCE AGAIN STATING THE FACT THAT ALL LOCATIONS IN | | BUILDING WHICH MAY BE IN USE UNDER EMERGENCY POWER AS A | | NORMAL OCCUPANCY. THERE ARE SEVERAL LOCATIONS WHICH ARE | | ALREADY KNOWN TO THIS OFFICE WHICH WILL REQUIRE BATTERY | | BACK UP FIXTURES TO MEET MINIMUM LIGHTING LEVELS UNDER | | THE LIFE SAFETY CODE 7.8 AND 7.9. | | PLANS STILL NEED TO BE REVISED TO INCLUDE THE NEW | | FIXTURES FOR ALL AREAS. PLANS ARE STAMPED REVIEWED FOR | | INSPECTIONS OF OTHER AREAS OTHER THAN KNOWN LOCATIONS. | | THIS WILL BE AT CONTRACTOR RISK FOR ALL LOCATIONS | | INCLUDING ANY NEW AREAS ADDED. PLANS ARE CODE COMPLIANT | | AT THIS TIME WITHOUT ANY *NORMAL OCCUPANCY* UNDER | | GENERATOR POWER. | | | | ** IF THERE ARE ANY QUESTIONS, PLEASE CONTACT THIS | | OFFICE/REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
18 |
Status |
F |
Date |
2008-03-25 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-03-25 |
Time |
15:54 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-03-25 |
Time |
15:54 |
Sent To |
|
|
Notes |
2008-03-25 15:54:45 | ** DENIEDREVISIONS ** | | CITY CENTER REV 15A ON LIGHTING SHEETS | | | | ** PLEASE SEE REDLINED PLANS AND NOTES BELOW AS THERE | | IS MUCH NEED OF COORDINATION WITH CIRCUITING FOR | | EMERGENCY AND EXIT LIGHTING. | | PLEASE ALSO SEE THAT COORDINATION IS ALSO NEEDED FOR | | OTHER NORMAL LIGHTING CIRCUITS. | | PLEASE SEE NOTES BELOW WITH RESPECT TO OCCUPATION OF | | BUILDING UNDER EMERGENCY POWER. | | | | | | 1) NOTE: PLEASE SEE THAT PER ON-SITE MEETING BATHROOM | | LIGHTING WILL BE REQUIRED TO BE UPDATED. | | | | 2) NOTE: PER ON-SITE AND CONVERSATIONS SEVERAL MONTHS | | AGO, IN AREAS OF BUILDING WHICH ARE GOING TO BE USED OR | | OCCUPIED FOR NORMAL OPERATING/CONDITIONS UNDER | | EMERGENCY POWER SHALL CONTAIN BATTERY BACK UP FIXTURES | | FOR THOSE AREAS FOR EGRESS AND EXISTING FROM BUILDING | | IN THE EVENT OF THE LOSS OF EMERGENCY GENERATOR. | | 7.8, 7.9 LS 101 2003 | | AREAS SUCH AS CALL CENTER AND EXITS, TRAINING ROOMS AND | | EGRESS, SERVER ROOM AND EGRESS, ETC | | PLEASE ALSO SEE STUDIO AND POLICE SUB-STATION ROOMS | | WHICH DO NOT SHOW ANY EMERGENCY LIGHTS ON EM CIRCUITS. | | THESE MAY NOT BE REQUIRED BY CODE, HOWEVER PLEASE | | VERIFY WITH OWNER THE INTENT OF USING THESE ROOMS. | | | | 3) NOTE: PLEASE SEE THERE ARE NUMEROUS LOCATIONS ON | | PLANS IN WHICH CIRCUITING IS NON-EXISTENT, CIRCUITED TO | | OTHER CIRCUITS OR SOME OF THE SAME CIRCUITS IN | | DIFFERENT AREAS WHICH FEED THE SAME ITEMS. | | PLEASE SEE SOME OF THE ITEMS BELOW FOR EXAMPLE; | | THESE ARE IN NO WAY ALL LOCATIONS. PLEASE ALSO SEE SOME | | SHEETS ARE BEING NOTED BELOW AS MANY ROOM AND AREA | | DESIGNATIONS WERE REMOVED FROM PLANS. | | 1HEB-5 AND 1HEB-3 TIED TOGETHER IN A1.804, A1.008. | | SEE 1HEA-2 AT A1.206 AND A1.302 | | SEE 1HEA-6 AND HED-2 TIED TOGETHER | | SEE 1HED-4WHICH IS REPEATED, SEE AREAS D1.104, | | D1.005 | | SEE 1HB-7 IN D1.201 SHOWN ON AS NORMAL CIRCUIT OR | | NOTING TO TIE TO. | | SEE 1HEC-3 AND 1HEC5 TIED TOGETHER. | | SEE CAF?, 1LC2, 8-10 AND 1LEC 6,8 TO SAME LIGHTS. | | SEE 2HEA-3 AND 2HEA-1 TIED TOGETHER ON SHEET E-2.2.1 | | SEE EXIT LIGHT IN AREA A2.302 WHICH SHOWS NO CIRCUIT. | | SEE EXIT LIGHT AT DOOR IN FUTURE SPACE (SHELL AREA) | | WHICH NEEDS TO BE CIRCUITED PER 700.12E | | SEE AREA ON SHEET E2.3.2 *SUPPORT SPACE/FILE PRODUCTION | | AND CORRIDOR AREA IS MISSING CIRCUIT FOR EMERGENCY AND | | EXIT LIGHTS. | | SEE LIGHTING CONTROL IN SOME ROOMS SUCH AS PROGRAM | | MEETING ROOM WHICH SHOWS NORMAL OC DEVICE. THIS IS THE | | SAME IN OTHER LOCATIONS ALSO ONE SHEET E2.3.2/ | | COLLECTION/ PROGRAM ROOM. | | SEE EMERGENCY AND EXIT LIGHTS IN ROOMS SUCH AS A4.420, | | 4.419,4.421 ETC WHICH DOES NOT SHOW ANY CIRCUIT. | | SEE THIS SAME LOCATION AS THERE ARE SWITCHES LOCATED IN | | THE MIDDLE OF THE *AIR* AND NOT LOCATED ON ANY WALL. | | SEE 4HEB-1 IN A4.416 WHICH SHOWS THIS BEING TIED TO | | NORMAL AND EMERGENCY LIGHTS. | | SEE EMERGENCY LIGHTS/EXIT LIGHTS OUTSIDE A4.304 WHICH | | DOES NOT SHOW CIRCUIT. (PUBLIC UTILIZES AREA 03) | | SEE A5.531, EMERGENCY NOT CONNECTED. | | SEE A5.508, 5.505 ETC WHICH DOES NOT SHOW ANY CIRCUITS | | FOR EMERGENCY LIGHT FIXTURES. | | SEE 5HA-17 WHICH IS SHOWN TIED TO EMERGENCY LIGHTS AND | | NOT NORMAL LIGHTING. | | SEE A5.401 AND AREA WHICH INDICATES EMERGENCY AND EXIT | | LIGHTS WITH NO CIRCUITS. | | SEE A5.412 WHICH SHOWS NORMAL CIRCUIT TIED TO EMERGENCY | | LIGHT. | | SEE A5.503,504,505, A5.413 EMERGENCY AND EXIT LIGHTS | | WITH NO CIRCUITING. | | | | ** PLEASE SEE THAT MANY OF THE AREAS ABOVE ARE NOTED | | HOWEVER AS STATED ABOVE ARE IN NO WAY ALL POSSIBLE | | LOCATIONS. | | SEE REDLINED AND HIGHLIGHTED PLANS AS MOST OF THESE | | AREAS INDICATE THE NOTES ABOVE. | | | | | | | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | DELAYS. | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
17 |
Status |
P |
Date |
2008-03-24 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-03-24 |
Time |
13:15 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-03-24 |
Time |
13:15 |
Sent To |
PC |
|
Notes |
2008-03-24 13:15:48 | REV FOR 136 AND 161 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
16 |
Status |
P |
Date |
2008-03-17 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-03-17 |
Time |
12:03 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-03-17 |
Time |
12:03 |
Sent To |
PC |
|
Notes |
2008-03-17 12:05:14 | REV FOR FORTH AND FIFTH FLOOR POWER ALONG WITH REVISED | | PANEL SCHEDULES. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
15 |
Status |
P |
Date |
2008-02-05 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-02-05 |
Time |
18:19 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-02-05 |
Time |
18:19 |
Sent To |
PC |
|
Notes |
2008-02-05 18:20:58 | *** REVISIONS*** | | | | SHEETS E1-3.1, E6-9.0 OK AND STMAPED, | | | | REVISION FOR SHEET E3-3.1 NEEDS TO BE SUBMITTED UNDER | | LV PERMIT WHICH WAS NOT INCLUDED IN BASE BUILDING | | PERMIT #. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
14 |
Status |
P |
Date |
2008-01-30 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-01-30 |
Time |
18:27 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-01-30 |
Time |
18:27 |
Sent To |
PC |
|
Notes |
2008-01-30 18:28:53 | REV FOR E1-2.1, 6-8.0 OK. | | SHEETE3-2.1 NEEDS TO BE SUBMITTED UNDER LOW VOLTAGE | | PERMIT FOR THAT SCOPE OF WORK. NOT AS PART OF ORIGINAL | | BASE BUILDING PLANS FOR ACTUAL WIRING. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
13 |
Status |
P |
Date |
2008-01-23 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-01-23 |
Time |
10:57 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-01-23 |
Time |
10:57 |
Sent To |
PC |
|
Notes |
2008-01-23 10:58:34 | ELEC REV FOR SHEETS E2-2.0, E2-2.2, 8-2.0, 8-2.2 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
12 |
Status |
P |
Date |
2007-12-25 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-12-25 |
Time |
10:27 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-12-25 |
Time |
08:17 |
Sent To |
PC |
|
Notes |
2007-12-25 10:27:47 | 2007-12-25 10:27:47 | | | | ** PROVISO ** | | | | | | 1) NOTE: PLEASE SEE THE RED-LINES FORM THE ORIGINAL | | ISSUED PLANS FOR NORMAL PHOTO-METRICS WILL STILL NEED | | TO BE ADJUSTED. THE NORMAL STAIR LIGHTING LEVELS WERE | | OK; HOWEVER FIXTURES ON NORMAL LIGHTING PLANS AND | | NORMAL PHOTO-METRICS NEEDED COORDINATION.PLEASE SEE | | ORIGINAL RED-LINED PLANS. | | | | 2) NOTE: PLEASE SEE MISPRINT/SHIFT IN PLANS ON SHEETS | | E8-2.0 AND 8-2.2 IN STAIRS. THESE WERE REDLINED ON | | PLANS AS THE LIGHTING PLANS DO NOT SHOW THIS SHIFT. | | | | 3) NOTE: NO REVISED SHEET E2-2.2 WAS SUBMITTED? ( NOT | | PRINTED AND SUBMITTED ) THIS IS ONLY NOTED AS ALL OTHER | | LIGHTING SHEETS WERE REVISED/ADJUSTED AND SUBMITTED. | | | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
11 |
Status |
P |
Date |
2007-12-22 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-12-22 |
Time |
14:50 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-12-22 |
Time |
14:50 |
Sent To |
|
|
Notes |
2007-12-22 14:54:52 | E1-2.2 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
10 |
Status |
P |
Date |
2007-11-06 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-11-06 |
Time |
10:41 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-11-03 |
Time |
15:10 |
Sent To |
|
|
Notes |
2007-11-06 10:41:16 | ** REVISION 12A ** | | | | 1) NOTE: PLEASE SEE MISSING CIRCUIT FOR RECEPTACLE ON | | E1-2.2, THIS WAS REDLINED ON PLANS. | | | | 2) NOTE: THE OUTSTANDING ISSUES WITH THE PROVISO | | PREVIOUSLY ISSUED FOR COMPLETE PHOTO-METRICS FOR | | REVISIONS AND COORDINATION STILL REMAINS. | | IT WAS REQUESTED BY THE ENGINEER OF RECORD FOR AN | | EXTENSION AS WELL AS FROM THE GC. | | | | 3) NOTE: LOW VOLTAGE PERMITS AND PLANS HAVE NOT YET | | BEEN SUBMITTED TO DATE. | | | | 4) NOTE: THE GENERATOR STILL REQUIRES RE-LISTING FOR | | UNIT. THIS WILL BE DONE AT A LATER DATE. | | | | SOME OF THESE ITEMS WERE CARRIED FORTH FROM PREVIOUS | | REVIEWS. | 2007-11-05 16:57:52 | 2007-11-05 16:57:52 | | | | REVIEW COMPLETED, PLANS ARE STILL NEEDED TO BE STAMPED | | AND NOTES NEED TO BE ENTERED AND TYPED INTO SYSTEM. | 2007-11-04 10:28:19 | 2007-11-04 10:28:19 | | | | REVIEW TO CONTINUE ON 11/5 | 2007-11-03 15:34:43 | 2007-11-03 15:10:24 | | | | ONE SET IN ELECTRICAL FOR REVIEW. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
9 |
Status |
F |
Date |
2007-09-09 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-09-09 |
Time |
12:56 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-09-05 |
Time |
19:18 |
Sent To |
|
|
Notes |
2007-09-09 12:56:26 | 2007-09-09 12:56:26 | | REVIEW COMPLETED, NOTES BELOW. | | | | ** DENIED REVISIONS ** | | | | 1) NOTE: PLEASE SEE SHEET E0-2.2 WHICH INDICATES | | CONDUITS FOR LIGHTING IN THE RIGHT OF WAY ON THE PLANS | | FOR THIS BUILDING. THIS IS TO BE INCLUDED ON SEPARATE | | PLANS AND UNDER SEPARATE PERMITS WHICH IS NOT A PART OF | | THIS BUILDING OR LEGAL PROPERTY. | | | | 2) NOTE: PLEASE SEE *PROVISO* AND *DENIAL* COMMENTS | | FROM JULY 27TH, 2007 WHICH HAVE NOT BEEN ADDRESSED. AS | | SOME OF THE REVISED SHEETS SUBMITTED DO HAVE A FEW OF | | THESE ITEMS DONE, MOST HAVE NOT. | | PLEASE SEE THE ATTACHED NOTES FOR THAT DATE. | | THESE NEED TO BE ADDRESSED AND INCORPORATED INTO PLAN | | SETS AS SOON AS POSSIBLE TO ALLEVIATE CONFUSION AND | | REVISIONS BEING MIXED AND/OR MISSED ALONG THE WAY. FBC | | ADMIN SECTION. 106.1.2,106.3.1 ETC | | | | 3) NOTE: PLEASE SEE NUMEROUS SHEETS HAVE BEEN REVISED | | WITH CIRCUITING, LOADS INCREASING, ADDED POWER | | LOCATIONS, ADDED RECEPTACLES ETC HOWEVER NOT REVISED | | PANEL SCHEDULES OR LOAD CALCULATIONS WERE SUBMITTED. | | PLEASE SEE THE PANEL SCHEDULES AND LOADS ON FILE DO NOT | | CONTAIN MANY OF THE NEW CIRCUITS NOW SHOWN. | | PLEASE SEE THE PANEL SCHEDULES DO NOT CONTAIN THE | | INCREASE IN LOADS BY THE ADDED DEVICES ETC. | | PLEASE COORDINATE AND REVISE LOAD CALCULATIONS FOR | | AFFECTED PANELS. PLEASE REVISE PANEL SCHEDULES | | ACCORDINGLY. | | PLEASE SEE SHEET E1-5.1 ROOM A5.406 AS SOME RECEPTACLES | | WERE REVISED AND DO NOT CONTAIN CIRCUITING. | | PLEASE SEE THIS SAME SHEET AS RECEPTACLES ADDED TO | | CIRCUIT(S) 5LA3-5, 5LA3-34 DO NOT CORRELATE WITH LOADS | | AND PANEL SCHEDULES. THIS IS TYPICAL OF NUMEROUS | | CIRCUITS, LOADS, SHEETS AND PANELS. | | FBC 106.3.5.1.2, 106.1.2 | | NEC 408.4, 220 ETC | | | | 4) NOTE: PLEASE SEE THERE ARE SEVERAL LOCATIONS ON | | SHEETS WHERE THE FURNITURE LAYOUTS HAVE NOW BEEN | | REMOVED. ?? | | | | 5) NOTE: AS NOTED AND AGREED BY THE CONTRACTOR, OWNER | | AND AS SHOWN ON ORIGINAL PLANS, THE LOW VOLTAGE SYSTEMS | | ARE TO BE UNDER A SEPARATE PERMIT AND ARE NOT PART OF | | THE BASE BUILDING PLANS AND PERMITTING. | | PLEASE SUBMIT THREE COMPLETE SETS WITH PERMIT | | APPLICATION, APPROPRIATE VALUE AND FEES FOR THE SCOPE | | OF WORK. | | ** PLEASE BE SURE TO SPECIFY THE TYPE OF CABLING, | | CONDUIT INSTALLATION ETC. | | | | 6) NOTE: PLEASE EXPLAIN TITLE BLOCKS WITH | | IDENTIFICATION OF REVISIONS. THE SHEETS ARE LABELED AS | | REV # 11, YET THE DESCRIPTION INDICATES THIS IS | | REVISION #3? | | THIS IS UNCLEAR. | | ALTHOUGH NOT REQUIRED, PLEASE KNOW A SUBMITTAL OF A | | LETTER ON REVISIONS TAKING PLACE ALONG THE PROCESS OF | | THE JOB WOULD HELP TO PERHAPS ALLEVIATE ANY CONFUSION | | AND DELAYS IN PROJECT. | | | | ** AS STATED ON PREVIOUS REVIEWS: IF THERE ARE ANY | | QUESTIONS, PLEASE DO NOT HESITATE IN CONTACTING THIS | | OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | 2007-09-08 21:29:06 | 2007-09-08 21:29:06 | | | | REVIEW COMMENCED. | 2007-09-05 19:19:08 | 2007-09-05 19:19:08 | | 1-ROLL IN ELECTRICAL FOR REVIEW: |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
8 |
Status |
F |
Date |
2007-07-26 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-07-26 |
Time |
11:33 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-07-23 |
Time |
11:13 |
Sent To |
|
|
Notes |
2007-07-26 11:35:29 | | | ** REVIEW FOR REV #8 AND REV #10. | | | | | | *** PROVISO /UNSAT *** | | | | ** PLEASE SEE CONDITIONS ARE STILL GIVEN FOR SOME ITEMS | | NOT SUBMITTED AND FOR SOME ITEMS ON PLANS FOR | | COORDINATION ETC. SOME SHEETS ARE STAMPED AND PROVISO | | NOTES FOLLOW BELOW. | | | | ** PLEASE SEE THE FAILURE COMMENTS AT THE END OF | | *PROVISO* NOTES FOR SHEETS WHICH WERE NOT STAMPED.. | | | | | | | | | | 1) NOTE: PLEASE SEE THE OVER ALL SHEET E1-1.0 DOES NOT | | MATCH WITH NEW LAYOUT FOR MECHANICAL ROOM AT GARAGE AND | | HALLWAY AREA. | | PLEASE SEE NOTES ON REVIEW OF PHOTO-METRIC PLANS | | REVIEW. | | | | 2) NOTE: PLEASE SEE E2-2.2 MEN AND WOMEN RESTROOMS ON | | UPPER LEFT HAND CORNER WHICH STILL SEEM TO INDICATE BY | | HASHED LINES MORE THAN THE TWO EM LTS. | | PLEASE SEE SOME OF THESE ARE SHOWN ON OTHER SHEETS AND | | FOR OTHER BATHROOMS. | | PLEASE SEE COMMENTS WITH RESPECT TO PHOTO-METRICS. | | | | 3) NOTE: PLEASE SEE SHEET E2-4.2 WHICH WILL REMAIN | | REDLINED AS ROOF-TOP ACCESS AND WHETHER OR NOT STAIRS | | WILL BE REQUIRED IS STILL IN QUESTION. | | | | 4) NOTE: PLEASE KNOW THAT UPDATED POWER PLANS FOR | | CHANGES AND CORRECTIONS WILL STILL BE NEEDED. | | | | 5) NOTE: PLEASE SEE THE UPPER PART OF THE ELECTRICAL | | RISER DIAGRAM WAS NOT SUBMITTED. THIS SHEET ALONG WITH | | SOME OTHERS SHOWING THE CHANGES FOR THE GENERATOR ETC | | WILL STILL BE NEEDED. | | PLEASE SEE THAT THE SPECIFICATIONS ON THE GENERATOR AND | | FIELD MODIFICATIONS FOR BI-FUEL ARE STILL NEEDED FOR | | REVIEW. | | 700,701, 110.3, 90.7. | | | | 6) NOTE: PLEASE SEE PANEL 5LEB TOTAL FOR VA HAS NOT | | BEEN CORRECTED AS NOTED ON PREVIOUS REVIEW AND REDLINED | | ON PREVIOUS REVIEWED #8 REVISIONS. | | THE TOTAL LOAD ON PANEL DOES NOT CORRELATE WITH THE | | TOTAL ON LOAD SUMMARY OF PANEL. | | | | 7) NOTE: PLEASE SEE SHEET E6-1.0 WHICH STILL INDICATES | | A 825KW GENERATOR. AS THIS GENERATOR AHS CHANGED SIZE | | SEVERAL TIMES, PLEASE COORDINATE ALL SHEETS WITH | | REFERENCE TO THIS UNIT. PLEASE SEE COMMENTS ON | | PHOTO-METRIC SHEETS AS THESE CONTAIN SEVERAL OTHER | | REFERENCES. | | | | 8) NOTE: PLEASE SEE NOTE #6 ABOVE AS THE LOADS ADJUSTED | | ON 5LEB NEED TO BE CARRIED THROUGH TO ALL OTHER PANELS. | | 5HEB ETC. | | FBC 106.3.5.1.2 NEC 220. | | | | 9) NOTE: PLEASE SEE SHEET E1-6.0 AS THE LAYOUT FOR THE | | GENERATORS AND EQUIPMENT DOES NOT CORRELATE WITH | | PLANS. | | PLEASE SEE ROOF TOP MECH ROOM AND CONTROLS FOR LIGHTING | | WHICH HAVE NOT BEEN CORRECTED TO COORDINATE WITH | | PLANS. | | | | 10) NOTE: PLEASE KNOW THE IT ROOM HAS NOT BEEN | | SUBMITTED FOR PERMITTING TO DATE ALONG WITH ANY LOW | | VOLTAGE SYSTEMS FOR THE BUILDING. | | | | ALL ELECTRICAL SHEETS SUBMITTED WILL BE STAMPED WITH | | THE EXCEPTION OF PHOTO-METRICS. | | | | | | | | ** UNSAT ** | | | | 1) NOTE: PLEASE SEE THE PHOTO-METRIC PLANS SUBMITTED | | STILL NEED SOME COORDINATION. | | PLEASE SEE THERE ARE SEVERAL SHEETS WHERE LIGHTING | | FIXTURES ARE MISSING ALTHOUGH THEY ARE ACTUALLY ON THE | | ELECTRICAL LIGHTING PLANS. | | PLEASE SEE MANY AREAS ARE REDLINED WITH CIRCLES FOR | | MISSING FIXTURES AND OR MULTIPLE FIXTURES WHEN THE | | PLANS SHOW LESS OR MORE. | | PLEASE SEE THAT MANY OF THESE ARE THE EMERGENCY | | PHOTO-METRIC SHEETS.PLEASE SEE SOME OF THESE SHEETS | | IN ONE SET ACTUALLY CONTAINS A *CHECK* AS THESE ARE OK, | | HOWEVER CHANGES ON OTHER SHEETS FOR COORDINATION MAY | | AFFECT THESE. | | PLEASE SEE THE FOLLOWING SHEETS FOR EXAMPLE WHICH ARE | | MISSING FIXTURES, LOCATIONS ARE INCORRECT OR ARE | | SHOWING FIXTURES NOT ON LIGHTING PLANS. | | 8-1.1, | | 8-1.2, | | 8-1.3, | | 8-3.2, | | 8-4.1, | | 8-4.2, | | 8-5.2 MISSING FC AVG. FOR STAIRS. | | 8-6.0 3-GENERATORS SHOWN, 3-400KW GENERATORS. | | 8-6.3 3-GENERATORS SHOWN, 2-FUTURE AND 1-825KW GEN. | | 9-1.0 | | ** PLEASE BE SURE TO COORDINATE THE SHEETS AS THE | | LEVELS OF LIGHTING MAY CERTAINLY CHANGE WHEN FIXTURES | | ARE ADDED OR DELETED. | | PLEASE BE SURE TO SEE ANY ROOMS AND AREAS (MECH | | ELECTRICAL ROOM IN GARAGE). | | PLEASE SEE LS 101 7.8 AND 7.9. | | PLEASE SEE FAC 61G15-33.004 | | | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
7 |
Status |
F |
Date |
2007-04-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-04-14 |
Time |
11:46 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-04-11 |
Time |
11:48 |
Sent To |
|
|
Notes |
2007-04-14 11:48:58 | ** UNSAT ** | | | | ** PLEASE SEE THIS REVIEW IS FOR REVISION #8 AS | | SUBMITTED TO ADDRESS *PROVISO* FROM ISSUANCE OF | | PERMIT** | | | | ** PLEASE SEE THAT MOST OF THE *PROVISO* NOTES HAVE | | BEEN ADDRESSED HOWEVER DUE TO CHANGES IN REVISION #7 | | AND SOME ITEMS WHICH STILL NEED TO BE REVISITED ON | | PROVISO, PLEASE SEE THE COMMENTS BELOW. | | | | 1) NOTE: PLEASE KNOW THAT DUE TO THE CLEARANCE | | REQUIREMENTS FOR THE GENERATOR WHICH WAS COMMENTED ON | | IN REVISION FOR ARCHITECTURAL DATED 3/1/07 THE PLANS AS | | SUBMITTED DO NOT INDICATE THE MINIMUM CLEARANCES FOR | | THE UNIT PER NEC 110.26 AND THAT WHICH IS SET-FORTH | | FROM THE MANUFACTURES SPECIFICATIONS. | | 110.3, 90.7 | | | | 2) NOTE: PLEASE CLARIFY THE CONTROL DEVICE FOR ELEVATOR | | ROOM PER 1-6.1. OCCUPANCY DEVICE REQUIRED. | | 13-415.1.ABC.1.1 | | | | 3) NOTE: PLEASE SEE PANEL 1-HEE WHICH NEEDS TO INDICATE | | AND LABEL THE ROOMS IN WHICH THEY FEED AND THE | | DESIGNATION FOR THE * ELEVATOR MACHINE RM LTS*. | | 408.4, 620.23 | | | | 4) NOTE: PLEASE SEE THE PROVISO WHICH WAS TO REVISE | | CIRCUITS FOR THE ELEVATOR ROOMS, WHICH WAS TO INCLUDE | | THE LIGHTING AND RECEPTACLES, YET ONLY THE REVISED | | LIGHTING PLANS WERE SUBMITTED. PLEASE SEE THE SHEETS | | FOR THESE ROOMS SHOULD HAVE ALSO BEEN SUBMITTED. | | 620.23 | | FBC 106.1.2 | | | | 5) NOTE: PLEASE SEE THE ELECTRICAL RISER DIAGRAM AND | | NOTES FOR REVISION #7 WHICH AHS NOT BEEN CHANGED. | | PLEASE SEE THAT THE ATS SWITCHES WHICH HAVE BEEN | | REVISED ON OTHER DOCUMENTS HAVE NOT BEEN REVISED ON | | RISER DIAGRAM. | | PLEASE SEE NOTES DATED 3/24/07 | | PLEASE BE SURE TO REVISE POWER PLANS, PANEL SCHEDULES, | | LOADS ETC. | | FBC 106.3.5.1.2, 106.1.2 | | | | 6) NOTE: PLEASE CLARIFY STAIR 11 LIGHTS AND LOCATIONS | | FOR THE PHOTO-METRIC LEVELS. PREVIOUS PLANS INDICATE | | LIGHTING IN THE STAIR AREA ABOVE THE STAIRS AND SOME | | SHEETS INDICATE THESE AT THE UPPER LEVEL AND LOWER | | LEVEL WHICH DO NOT SEEM THEY WOULD PROVIDE THE NEEDED. | | PLEASE SEE THE PHOTO-METRIC PLANS WHICH DO INDICATE THE | | LIGHT FIXTURE ABOVE STAIRS AND IF THIS IS HOW THE | | LIGHTING LEVELS ARE DERIVED THEN THE PLACEMENT OF THE | | LIGHTING FIXTURES ON THE LIGHTING PLANS WOULD NOT WORK | | AND PROVIDE THE LIGHTING. | | LS 101 7.8.1.3, 7.9.2.2 | | PLEASE SEE NEXT COMMENT. | | | | 7) NOTE: PLEASE SEE THAT LIGHTING PLANS AND | | PHOTO-METRIC PLANS STILL NEED COORDINATION OG LIGHTING | | FIXTURES. PLEASE SEE THAT THE SAME FIXTURES WHICH ARE | | INDICATED AS EM TYPE FIXTURES ON LIGHTING PLANS ARE NOT | | THE SAME ONES IN ALL LOCATIONS ON PHOTO-METRIC PLANS. | | PLEASE KNOW AS BASED ON COMMENT ABOVE AND THE NEXT | | COMMENT FOR NIGHT LIGHTING AND EMERGENCY LIGHTING, | | THESE WILL ALL NEED TO BE ADJUSTED AND REVISED TO | | CORRELATE. | | FBC 106.1.2 | | LS 101 7.8, 7.9 | | | | 8) NOTE: PLEASE KNOW THAT A MEETING WILL BE REQUIRED TO | | GO OVER PLANS AND PROPOSED *NIGHT-LIGHTS* AS SHOWN ON | | PLANS. PLEASE KNOW THAT EMERGENCY FIXTURES ARE REQUIRED | | FOR EGRESS PATHS UNDER NORMAL AND EMERGENCY HOWEVER THE | | NUMBER OF FIXTURES BEING PROPOSED FOR NIGHT LIGHTS | | WHICH WILL BE LEFT *ON* 24/7/365 DOES NOT TAKE INTO | | CONSIDERATION OF THE REQUIREMENT OF THE FLORIDA ENERGY | | CODE. | | PLEASE SEE THESECTION BELOW WHICH IS TAKEN DIRECTLY | | FROM NFPA-101. *7.8.1.2.2* WHICH IS LOCATED ALONG WITH | | TEXT FOR SECTION OF 7.8. | | PLEASE KNOW THAT DUE TO THE COMPLEXITY OF THE EGRESS | | LIGHTING, THE ACTUAL DESIGNATED EGRESS PATH/PATHS NEEDS | | TO BE DETERMINED AS A STARTING POINT FOR FINDING THE | | MINIMUM REQUIRED. | | PLEASE KNOW THAT THIS OFFICE HAS CONTACTED THE FLORIDA | | BUILDING COMMISSION TO GO OVER THE REQUIREMENTS OF | | CHAPTER 13 AND THE INTENT.CONSIDERATION NEEDS TO BE | | GIVEN FOR THE INTENT AND AT THE SAME TIME MEETING THE | | REQUIRED LIFER SAFETY FOR NORMAL AND EMERGENCY EGRESS | | LIGHTING DURING OCCUPANCY OF BUILDING. | | | | *7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE | | PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY | | BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTER 11 | | THROUGH CHAPTER 42. FOR THE PURPOSES OF THIS | | REQUIREMENT, EXIT ACCESS SHALL INCLUDE ONLY DESIGNATED | | STAIRS, AISLES, CORRIDORS, RAMPS, ESCALATORS, AND | | PASSAGEWAYS LEADING TO AN EXIT. FOR THE PURPOSES OF | | THIS REQUIREMENT, EXIT DISCHARGE SHALL INCLUDE ONLY | | DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS, | | ESCALATORS, WALKWAYS, AND EXIT PASSAGEWAYS LEADING TO A | | PUBLIC WAY. | | 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE | | CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF | | OCCUPANCY REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE | | FOR USE, UNLESS OTHERWISE PROVIDED IN 7.8.1.2.2. | | 7.8.1.2.1 ARTIFICIAL LIGHTING SHALL BE EMPLOYED AT SUCH | | LOCATIONS AND FOR SUCH PERIODS OF TIME AS ARE NECESSARY | | TO MAINTAIN THE ILLUMINATION TO THE MINIMUM CRITERIA | | VALUES HEREIN SPECIFIED. | | 7.8.1.2.2 AUTOMATIC, MOTION SENSOR?TYPE LIGHTING | | SWITCHES SHALL BE PERMITTED WITHIN THE MEANS OF EGRESS, | | PROVIDED THAT THE SWITCH CONTROLLERS ARE EQUIPPED FOR | | FAIL-SAFE OPERATION, THE ILLUMINATION TIMERS ARE SET | | FOR MINIMUM 15-MINUTE DURATION, AND THE MOTION SENSOR | | IS ACTIVATED BY ANY OCCUPANT MOVEMENT IN THE AREA | | SERVED BY THE LIGHTING UNITS. | | | | ** PLEASE SEE ONE SET OF THE PLANS WHICH WAS SUBMITTED | | HAS REDLINED LOCATIONS WHICH ARE ALSO HIGH-LIGHTED FOR | | AREAS WHICH NEED TO BE GONE OVER. | | ** PLEASE CONTACT THIS OFFICE ONCE THE MINIMUM | | LIFE-SAFETY DESIGNATED EGRESS PATHS ARE DONE TO SET UP | | A MEETING TO GO OVER PLANS AND SCENARIOS. | | | | ** PLEASE KNOW THAT DUE TO THE COMPLEXITY OF THE NOTES | | ABOVE AND THE TIME CONSIDERATION WHICH WILL BE GIVEN TO | | ADDRESS THE ABOVE, THE ORIGINAL DATE OF 60DAYS HAS BEEN | | EXTENDED AS DISCUSSED WITH THE ENGINEER OF RECORD. | | | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | 2007-04-14 09:59:47 | REVIEW IN PROGRESS |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
6 |
Status |
F |
Date |
2007-03-24 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-03-24 |
Time |
17:49 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-03-24 |
Time |
16:37 |
Sent To |
|
|
Notes |
2007-03-24 17:49:26 | ** UNSAT ** | | | | | | ** GARAGEREVISION #7** | | | | 1) NOTE: PLEASE SEE THE RISER HAS NOW CHANGED ATS-3 TO | | A 400AMP UNIT, HOWEVER PLEASE SEE THE LEFT SIDE OF | | ATS-3 AS IT IS STILL SHOWN AS A 260AMP UNIT. | | PLEASE ALSO SUBMIT THE REVISED MANUFACTURES SPECS/CUT | | SHEETS FOR THE NEW PROPOSED UNIT.(110.3, 90.7) | | PLEASE COORDINATE ALONG WITH ELECTRICAL SHEET FOR MAIN | | ELECTRICAL ROOM WHICH WAS NOT SUBMITTED YET THE | | DESIGNATION ON SHEET 4-1.0 CONTAINS THE 260AMP UNIT. | | FBC 106.1.2 | | | | 2) NOTE: PLEASE SEE PLANS INDICATE A REVISION TO THE | | LOAD CALCULATIONS ON THE MAIN BUILDING LOAD SUMMARY; | | HOWEVER THE LOADS DID NOT CHANGE FROM THE PERMITTED SET | | OF PLANS. A CLOUD AND A REV #7 IS SHOWN, BUT NOTHING | | WAS REVISED. | | PLEASE SEE THAT THE LOADS OF THESE NEW MOTORS NEED TO | | SHOW *LARGEST* AT 125% AND PLEASE KNOW THAT AS THESE | | MOTOR LOADS MAY BE RUN FOR THREE OR MORE HOURS THE | | LOADS SHALL BE SHOWN AT 125%. | | 215.3, 230.42, 220, 430 ETC. | | PLEASE REVISE CALCULATIONS. | | PLEASE ALSO KEEP IN MIND THE *PROVISO* WHICH WAS GIVEN | | WHICH NEEDED LOAD CALCULATIONS TO BE REVISED AND BASED | | ON THESE SHEETS FOR REVISION #7, LOADS WERE NOT | | REVISED. | | IF REVISION #6 HAS NOT HAD THIS CHANGE BASED ON | | *PROVISO* PLEASE KNOW IT MAY BE THAT REVISED SHEETS ARE | | INSERTED BEFORE REVIEW OF REVISION #6 IS DONE? | | | | 3) NOTE: PLEASE SUBMIT THE REVISED GENERATOR SPECS FOR | | THE INCREASED SIZE INCLUDING FUEL CONSUMPTION FOR ADDED | | SIZE AND INCREASED LOADS. RECORD PLANS NEED TO REVISE | | FUEL CONSUMPTION AND LOADS. | | NFPA-110 | | NFPA 70 110.3, 90.7. | | FBC 106.1.2 | | | | 4) NOTE: THE EXHAUST FANS ARE LABELED EF-1 FOR FIRST | | FLOOR AND THEN EF-2 FOR SECOND FLOOR, EF-3 FOR THIRD | | FLOOR AND THEN FOURTH AND FIFTH LEVELS ARE ALSO LABELED | | EF-3 FOR THESE FANS ON OTHER LEVELS??? | | PLEASE PROVIDE SPECIFIC DESIGNATIONS FOR EACH EXHAUST | | FAN. PLEASE KNOW IF THEY ARE ON LEVEL 2M, THEN LABEL | | EACH ON LEVEL 2 AS THERE ARE MULTIPLE FANS PER FLOOR. | | PLEASE LABEL FANS ON OTHER LEVELS AS THE FANS ON THOSE | | SPECIFIC LEVELS. | | EF-4A NE CORNER?, EF-4B NE CORNER ?ORANY OTHER | | SPECIFIC DESIGNATION OF CHOICE. | | PLEASE SEE 408.4 AS THIS REQUIRES THE SPECIFIC | | DESIGNATIONS AND NOT TO BE GENERIC. PLEAS CALL IF THERE | | ANY QUESTIONS. | | ** PLEASE BE SURE TO ADJUST THE DESIGNATIONS ON THE | | BUILDING/ MECHANICAL PLANS ALSO. | | | | 5) NOTE: PLEASE SEE FBC 132-413.1ABC.1 FOR VOLTAGE | | DROP. THE MCC SHOWS #12AWG FOR THE UPPER FLOORS AND THE | | DISTANCE SEEMS TO EXCEED THE % PERMITTED. | | PLEASE PROVIDE VOLTAGE DROP CALCULATIONS FOR THESE OR | | INCREASE CONDUCTOR SIZES FOR LONGER RUNS. THIS IS NOT | | FOR LOWER LEVELS WITH LESS DISTANCE. | | | | 6) NOTE: PLEASE BE SURE TO ADJUST THE GENERATOR | | SPECIFICATIONS ON ANY OTHER SHEETS WHICH CONTAIN THE | | DESIGNATIONS. | | FBC 106.1.2 | | | | 7) NOTE: PLEASE SUBMIT LV DETAIL FOR WIRING OF THE | | CARBON MONOXIDE DEVICES/SYSTEM. | | CAN BE ON THE SAME GARAGE SHEETS AND A TYPICAL DETAIL. | | FBC 106.3.5.1.2 | | | | ** PLEASE SEE ANY COMMENTS FROM OTHER TRADES( | | BUILD/MECH/FIRE) WHICH MAY CONTAIN COMMENTS THAT MAY | | AFFECT ELECTRICAL SHEETS. | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
F |
Date |
2007-03-01 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-03-01 |
Time |
07:31 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-03-01 |
Time |
07:31 |
Sent To |
|
|
Notes |
2007-03-01 07:32:49 | **** UNSAT **** | | | | 1) NOTE: PLEASE SEE THE ARCHITECTURAL REVISIONS | | SUBMITTED ARE SHOWING NEW FENCING AND CLEARANCES AROUND | | THE CURRENT GENERATOR UNIT AND THE FUTURE GENERATOR | | UNITS WHICH DO NOT MEET EGRESS REQUIREMENTS AND MINIMUM | | CLEARANCE REQUIREMENTS FOR THE NEC 110.26 AND NFPA-110. | | PLEASE OBTAIN INFORMATION ON THE ELECTRICAL BREAKER | | PANEL LOCATIONS, PLEASE SEE ONLY ONE PATH IS BEING | | SHOWN AND THE PATH OF EGRESS DOES NOT MINIMUM WIDTHS. | | PLEASE SEE THAT DEPENDING ON EQUIPMENT AND NUMEROUS | | OTHER FACTORS THE FENCING AND WALLS SHOWN ARE WAY UNDER | | THE MINIMUM AREA REQUIRED ABOUT THE ELECTRICAL | | EQUIPMENT. | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN | | CONTACTING THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2007-02-18 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-02-18 |
Time |
13:29 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-02-15 |
Time |
10:57 |
Sent To |
|
|
Notes |
2007-02-18 13:31:52 | 2007-02-18 13:31:52 | | | | *** PROVISO/REVISION *** | | | | | | ** THE FOLLOWING *PROVISO* WAS SET UP WITH CONDITIONS | | THAT ALL OF THE FOLLOWING BE REVISED, UPDATED AND | | SUBMITTED FOR REVIEW WITHIN 60 DAYS FROM ISSUANCE OF | | PERMIT. | | PLEASE SEE THAT MANY OF THE ITEMS BELOW BESIDES CODE | | RELATED ITEMS ARE MOSTLY BASED ON COORDINATION RELATED | | ISSUES. | | PLEASE SEE SOME OF THE NOTES ARE NEW AS SOME THINGS | | HAVE BEEN ADDED TO THESE PLANS WHICH WERE NOT ON | | PREVIOUS REVIEWED PLANS. | | THE SECTION OF THE FBC 106.1.2 MADE IN NOTES BELOW IS | | FROM THE 2004 FBC ADMINISTRATIVE SECTION AS ADOPTED BY | | THE CITY OF WEST PALM BEACH FOR * ADDITIONAL | | INFORMATION*. | | ** MANY OF THESE WILL NOT ONLY REQUIRE THE PARTIAL FOR | | EACH FLOOR, BUT ALSO THE *OVERALL* FLOOR SHEETS TO BE | | REVISED. | | | | | | 1) NOTE: PLEASE SUBMIT THE WIND LOAD CALCULATIONS FOR | | SITE LIGHT POLES FOR COURTYARD AND ROOF TOP AREAS. | | THESE SHALL CONTAIN THE ORIGINAL SIGNATURE, DATE AND | | SEAL FROM THE ENGINEER OF RECORD. FS 471.025 AND TITLE | | BLOCKS ON EACH SHEET PER 61G15-23.002. | | | | 2) NOTE: PLEASE SEE THAT THERE MAY BE POSSIBLE STAIRS | | TO THE ROOF ON THE SOUTH SIDE OF THE BARREL ROOF FROM | | THE FOURTH LEVEL. THIS IS A BUILDING CODE REQUIREMENT | | AND PENDING ANY DECISION FROM THE CBA, LIGHTING, | | PHOTO-METRICS ETC WILL BE REQUIRED TO BE SUBMITTED AND | | REVISED FOR THOSE SHEETS AFFECTED BY THIS. | | THIS WOULD INVOKE LS 101 7.8 AND 7.9. | | | | 3) NOTE: PLEASE SEE THERE ARE MANY LOCATIONS WHERE | | BATTERY BACK UP TYPE FIXTURES ARE BEING SHOWN WITH OC | | DEVICES OR SWITCHING. | | PLEASE SEE PREVIOUS NOTES WHICH REQUESTED BATTERY BACK | | UP FIXTURES OF SOME SORT IN MANY ROOMS; HOWEVER PLANS | | WERE REVISED IN MANY ROOMS TO INCLUDE A ZE FIXTURES, | | WHICH IF CONTROLLED AS SHOWN (SWITCHED) THEN THE LIGHT | | FIXTURE WHICH IS BATTERY BACK UP WOULD COME ON EACH | | TIME THE SWITCH OR DEVICE TURNS LIGHTING OFF. PLEASE | | SEE MOST ELECTRICAL ROOMS, ELEVATOR EQUIPMENT ROOMS, | | MECHANICAL ROOMS ETC. | | PLEASE SEE THE FOLLOWING LOCATIONS WILL BE REQUIRED TO | | CONTAIN A BATTERY BACK UP FIXTURE, HOWEVER THESE | | LOCATION ARE NOT TO HAVE LIGHTING REMAIN *ON* AS NL | | (NIGHT LIGHTS) 24 HRS A DAY. | | THESE LOCATIONS WHICH WILL REQUIRE A BATTERY BACK UP | | FIXTURE, BUT NOT FOR FIXTURES TO BE SWITCHED OR ON AS | | NL SHALL BE THE *MAIN ELECTRICAL ROOM IN GARAGE, MAIN | | MECHANICAL ROOM IN GARAGE, ALL ELEVATOR EQUIPMENT | | ROOMS, IT ROOM, FIRE PUMP ROOMS, BOTH MEZZANINE | | MECHANICALROOMS, THE MECHANICAL ROOM ON ROOF AND FIRE | | COMMAND ROOM. PLEASE SEE ALL OTHER SMALLER ELECTRICAL | | ROOMS WHICH CONTAIN ZE OR ZE2 FIXTURES ARE NOT REQUIRED | | TO CONTAIN A BATTERY BACK FIXTURE, BUT MAY. IF THEY DO | | CONTAIN A BATTERY BACK UP THESE SHALL NOT BE SWITCHED | | AND SHALL NOT BE ON 24/7. (700.12E). | | PLEASE GO OVER ALL OF THESE LOCATIONS ON PLANS AS MANY | | ROOMS DO SHOW THESE TYPE FIXTURES, HOWEVER NOT ALL. | | (PLEASE SEE REDLINED PLANS AS MANY OF THESE HAVE BEEN | | HIGH-LIGHTED BUT NOT ALL). | | PLEASE SEE DOME ROOM ABOVE THE ROOF TOP MECHANICAL ROOM | | DOES NEED A BATTERY BACK UP FIXTURE FOR EGRESS (STAIRS) | | HOWEVER SHOULD NOT CONTAIN NL FOR 24/7 OPERATION. MANY | | OF THESE WOULD CREATE A DIRECT CONFLICT WITH 700.12E OF | | THE NEC AND CHAPTER 13 OF THE FLORIDA ENERGY CODE. | | ** PLEASE CALL TO GO OVER OR TO COME IN AND GO THROUGH | | PLANS** | | | | 4) NOTE: PLEASE SEE MANY LOCATIONS ON PLANS WHICH | | INDICATE NIGHT LIGHTS (NL). THE AMOUNT OF THESE | | FIXTURES SHOULD BE REVIEWED AS THE AMOUNT IS OVER IN | | MANY LOCATIONS FOR THAT WHICH IS REQUIRED FOR LS 101 | | 7.8 AND 7.9. PLEASE SEE SOME AREAS WHICH CONTAIN NL | | WHICH ARE STILL BEING SHOWN SWITCHED FROM LOCAL | | SWITCHES. | | PLEASE SEE FOR EXAMPLE A.5.06. | | PLEASE SEE MANY LOCATIONS WHICH THESE NIGHT LIGHTS DO | | NOT SHOW ANY CONTROL OR CIRCUITING AND OR ARE IN | | CONFLICT AS THERE ARE OTHER FIXTURES WHICH ARE SHOWN ON | | THE NIGHT LIGHT CIRCUITS WHICH DO NOT CORRELATE WITH | | THE TYPE OF FIXTURES ON LEGENDS. | | FBC 106.1.2 | | | | 5) NOTE: PLEASE SEE STAIRS WHICH ONLY CONTAIN CONTROL | | FOR LIGHT AT ONE LOCATION EITHER AT THE TOP OR AT THE | | BOTTOM OF STAIRS. | | PLEASE SEE STAIR 12, STAIR 13. (PLEASE SEE STAIR 11 FOR | | EXAMPLE WHICH SHOWS BATTERY BACK UP FIXTURES BEING | | SWITCHED. (AS NOTED ABOVE. | | FBC 106.1.2 | | | | 6) NOTE: PLEASE SEE THE ELECTRICAL CIRCUITING WHICH HAS | | NOW BEEN ADDED TO THE ELEVATOR EQUIPMENT ROOM ON ROOF | | TOP. PLEASE SEE THE DEDICATED CIRCUITS AS REQUIRED PER | | 620.23 ARE THE SAME CIRCUITS AS SHOWN FOR THE FIRST | | FLOOR ELEVATOR EQUIPMENT ROOMS WHICH NOW HAVE CIRCUITS | | SHOWN FOR LIGHTING. | | PLEASE ALSO SEE THAT TWO SETS OF THE PLANS WHICH | | INDICATE THESE CIRCUITS TO PANEL 1-HEE DO NOT SHOW | | THESE CIRCUITS OR LOADS ADDED TO PANEL. | | PLEASE SEE ONE OF THE SETS OF PLANS DO SHOW THESE | | CIRCUITS ADDED TO PANEL SCHEDULE; HOWEVER NOT TO | | LOADS. | | PLEASE CORRELATE AND REVISE. PLEASE ALSO SEE NEXT | | NOTE. | | FBC 106.1.2 | | | | 7) NOTE: PLEASE SEE THE NEW ELECTRICAL FOR EQUIPMENT | | ADDED FOR THE ROOF TOP ELEVATOR EQUIPMENT ROOM WHICH | | WAS ADDED TO THESE PLANS AND TO PANEL 5-LEB ARE SHOWN | | ON PANEL SCHEDULE BUT THE LOAD CALCULATIONS WERE NOT | | REVISED OR ADJUSTED FOR THESE NEW LOADS. | | PLEASE ALSO SEE 620.23 AS THE NEW CIRCUIT 16 FOR THIS | | SAME PANEL FOR THE RECEPTACLE CIRCUIT SHOULD BE LABELED | | FOR THIS ELEVATOR EQUIPMENT ROOM AND NOT GENERAL | | RECEPTACLE CIRCUITS. | | FBC 106.1.2. | | | | 8) NOTE: PLEASE SEE THE LIGHTING POWER DENSITIES SHEETS | | 1 OF 14 AND 14 OF 14 WHICH DID NOT CORRELATE FOR 6TH | | AND 7TH LEVELS AND LIGHTING. THESE ITEMS WERE CHANGED | | IN MEETING WITH ENGINEER. | | PLEASE ALSO SEE THE SHEET 4 OF THE FLORIDA ENERGY CODE | | INPUT DATA REPORT WHICH SHOWS *MANUAL CONTROLS FOR TWO | | AREAS. | | PLEASE SE THIS WAS ALSO CHANGED BY THE ENGINEER IN | | MEETING. | | THESE SHEETS SHOULD BE REVISED FOR THESE ITEMS AND FOR | | ANY AND ALL CHANGES MADE FOR FIXTURES IN MANY ROOMS AS | | NOTED ABOVE IN OTHER NOTES. | | FBC 106.1.2 | | FBC 13-415.1.AB.1, 13-415.2 | | | | 9) NOTE: PLEASE SEE FIRST FLOOR CITY HALL SECTION WHICH | | SEEMS TO BE MISSING A 3-WAY SWITCH FOR MAIL/RECEIVING | | ROOM. | | | | 10) NOTE: PLEASE SEE 3-WAY SHOWN ON E 2-2.2 WHICH IS | | NOT SHOWN ON E2-1.4 FOR THE SAME LOCATION. (REDLINED) | | | | 11) NOTE: PLEASE SEE AS NOTED ABOVE A BATTERY BACK UP | | FIXTURE WILL BE REQUIRED IN THE IT ROOM OF SOME SORT. | | LS 101 7.8, 7.9. | | FBC 106.1.2 | | | | 12) NOTE: PLEASE SEE THAT MANY OF THE REVISED LIGHTING | | PLANS DO NOT CORRELATE WITH THE REVISED PHOTO-METRICS | | OR MANY OF PHOTO-METRICS SHEETS WERE NOT REVISED. | | PLEASE SEE STAIR 12, WHICH SHOWS DIFFERENT LIGHTS AND | | LOCATIONS ON LIGHTING PLANS THAN THAT OF THE SAME STAIR | | ON BOTH THE NORMAL AND EMERGENCY PHOTO-METRICS. PLEASE | | SEE THE PHOTO-METRICS SHOULD COORDINATE WITH ALL OTHER | | FIXTURES, TYPES ETC. | | PLEASE SEE PREVIOUSLY NOTED DOUBLE LIGHT FIXTURES IN | | STAIRS. | | FBC 106.1.2 | | | | 13) NOTE:AS PREVIOUSLY NOTED PLEASE CORRELATE AND | | REVISE ALL PHOTO-METRICS FOR STAIR DESIGNATIONS. PLEASE | | SEE THERE ARE MANY SHEETS WHICH STILL INDICATE THE OLD | | DESIGNATIONS. PLEASE SEE SOME SHEETS SHOW THE TABLES | | SHOW ONE DESIGNATION AND THE PLANS SHOW ANOTHER. PLEASE | | SEE SOME TABLES SHOW DESIGNATION, AND THEN THE SHEETS | | FOR THOSE STAIRS ARE BLANK? | | PLEASE SEE MISSING STAIR 6 FOR BOTH NORMAL AND | | EMERGENCY. | | PLEASE SEE TWO OF THE SETS FOR PHOTO-METRICS ARE | | DIFFERENT FROM THE THIRD SET WHERE SOME OTHER | | DESIGNATIONS WERE REVISED, BIT THE OTHER TWO SETS | | CONTAIN SOME SHEETS WHICH WERE REVISED AND SOME WHICH | | WERE NOT. PLEASE SEE THAT EVEN SOME OF THE REVISED | | SHEETS FOR DESIGNATIONS DO NOT CORRELATE. | | PLEASE SEE SHEETS 9-3.0 AND 9-3.2 WHICH BOTH APPEAR TO | | BE THE SAME SHEET. THE SHEET 9-3.2 SHOULD BE THE | | PARTIAL FOR AREA. | | ** PLEASE SEE THAT MANY OF THESE AREAS ARE REDLINED AND | | HIGH-LIGHTED ON PLANS. | | ** PLEASE SEE TWO SETS WHICH THIS IS AN ISSUE FOR | | SHEETS 9-5.0 AND 9-5.2 | | FBC 106.1.2 | | | | 14) NOTE: PLEASE SEE REDLINED DIVISION 16 SPECS FOR | | COLOR CODING FOR 277/480V SYSTEM. | | * BROWN, PURPLE, YELLOW* | | | | 15) NOTE: IF THE FIXTURE DESIGNATIONS ARE GOING TO BE | | SHOWN ON PHOTO-METRICS, THEN PLEASE CORRELATE WITH THE | | LIGHTING PLANS. THERE ARE NUMEROUS FIXTURES WHICH DO | | NOT CORRELATE. | | FBC 106.1.2 | | | | 16) NOTE: LIGHTNING PROTECTION WILL BE UNDER SEPARATE | | PERMIT, HOWEVER MAY USE THESE PLANS TO REFERENCE. | | | | 17) NOTE: PLEASE SEE THE FUTURE BUILD OUT FOR IT WILL | | BE UNDER A SEPARATE PERMIT WHICH WILL REQUIRE | | SUBMITTALS FOR ALL EQUIPMENT BEING INSTALLED IN THIS | | ROOM ALONG WITH PLANS, PERMIT APPLICATIONS AND FEES. | | | | 18) NOTE: PLEASE SEE THE LOW VOLTAGE SYSTEMS ARE UNDER | | A SEPARATE PERMIT, PLANS AND FEES. PLANS ARE TO BE | | SUBMITTED AT A LATER DATE BEFORE INSTALLATION BEGINS. | | THESE PLANS REFLECT CONDUIT LOCATIONS ONLY. | | | | | | ** PLEASE KNOW AS MANY OF THESE ITEMS ARE REDLINED OR | | HIGHLIGHTED ON PLANS, THIS IS IN NO WAY ALL POSSIBLE | | LOCATIONS. PLEASE REVIEW SAID PLANS. | | | | ** PLEASE CALL TO SET UP A TIME TO GO OVER SOME | | POSSIBLE ALTERNATIVES FOR SOME OF THE ITEMS ABOVE. | | | | IF THERE ARE ANY QUESTIONS OR IF THE NOTES TYPED ARE | | NOT CLEAR IN ANY WAY, PLEASE DO NOT HESITATE IN | | CONTACTING THIS REVIEWER. | | | | ** ALL PLANS, ALL SETS, ALL SUBMITTALS, SPEC BOOKS | | STAMPED. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | 2007-02-18 08:14:17 | 2007-02-18 08:14 | | CONTINUING TO PROCESS, NOTES TO FOLLOW. | 2007-02-16 07:01:13 | 2007-02-16 07:01:13 | | IN REVIEW | 2007-02-15 21:14:22 | 2007-02-15 21:14:22 | | ** REVIEW TO CONTINUE ON 2/16, PROVISO NOTES TO FOLLOW. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2007-01-22 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-01-22 |
Time |
10:07 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-01-21 |
Time |
19:08 |
Sent To |
|
|
Notes |
2007-01-22 10:07:22 | 2007-01-22 10:07:22 | | | | ** UNSAT ** | | | | | | ** PLEASE SEE NOTES FROM PREVIOUS REVIEW STILL NEED TO | | BE ADDRESSED. | | | | ** PLEASE SEE THE NOTES BELOW WILL AFFECT NUMEROUS | | SHEETS WHICH WILL BE REQUIRED TO BE REVISED. | | | | ** PLEASE SEE PREVIOUS NOTES WHICH MENTIONED SOME OF | | THE COMMENTS WERE *REDLINED* ON PLANS; HOWEVER WERE IN | | NO WAY ALL LOCATIONS OR ITEMS. PLEASE SEE ONCE AGAIN | | THE PLANS CONTAIN CIRCLES AROUND AREAS IN WHICH | | COMMENTS ARE MADE. | | PLEASE SEE COMMENTS AS MANY OF THE OLD SHEETS WERE | | SUBMITTED BACK IN SETS WITHOUT BEING REVISED. | | | | | | 1) NOTE: PLEASE CORRELATE FP SHEETS WITH THE | | SUBMITTALS. PLEASE SEE THE FP SHEET STILL INDICATES AN | | ELECTRIC FIRE PUMP FOR ONE OF THE PUMPS. THIS IS THE | | 6TH TIME THIS COMMENT HAS BEEN MADE. THIS COMMENT WAS | | MADE ON THE 50%, 90%, 1ST 100%,2ND 100%(FIRST UNDER | | PERMIT) AND 2ND SUBMITTAL UNDER PERMIT AND NOW THIS | | REVIEW. | | PLEASE SEE THE SIZES OF THE FIRE PUMPS ON PLANS DO NOT | | CORRELATE WITH THE SUBMITTALS. | | PLEASE SEE THE SIZE OF ONE OF THE TANKS FOR ONE OF THE | | FIRE PUMPS HAS NOW CHANGED TO A *00*SIZE TANK. PLEASE | | SEE THE HP RATING OF ONE OF THE PUMPS HAS NOW CHANGED | | AND DOES NOT CORRELATE WITH THE SUBMITTALS. PLEASE SEE | | THE TYPE AND MANUFACTURE OF THE FIRE PUMP CONTROLLERS | | STILL DO NOT CORRELATE. | | PLEASE SEE THE SUBMITTAL BOOKS CONTAIN MULTIPLE SPECS | | FOR THE TANKS. PLEASE KNOW IF NEW TANKS AND SIZES ARE | | GOING TO BE USED, DO NOT LEAVE THE OLD SUBMITTALS IN, | | IF THEY ARE INDEED OLD. | | PLEASE CORRELATE ALL OF THE ABOVE AND PLEASE CORRECT | | FP0-1.0. | | 90.7, 110.3, 695 NEC. | | 2003 NFPA-20 CHAPTER 9 AND 10. | | FBC ADMIN SECTION 106.1, 106.1.2, 106.3.5.1.2 | | | | | | 2) NOTE: PLEASE SEE THE PREVIOUS REVIEW COMMENT WHICH | | STATED THE SIGNATURES ON THE FP SHEETS FROM OTHER THAN | | MR. JAMES MINDUR DID NOT CORRELATE. PLEASE SEE ALL THE | | NEW SHEETS SEEM TO CONTAIN THE SAME SIGNATURE AS SHOWN | | ON THE NEW PLUMBING AND MECHANICAL SHEETS. PLEASE SEE | | THE OLD/NOT REVISED FP SHEETS DO NOT CONTAIN THIS NEW | | SIGNATURE. PLEASE SUBMIT A SIGNED, SEALED, DATED AND | | NOTARIZED LETTER FOR LEGAL SIGNATURE VERIFICATION. THIS | | WILL BE PLACED IN OUR SIGNATURE FILE FOR ANY FUTURE | | REFERENCE. | | | | 3) NOTE: PLEASE SEE THE SPEC SUBMITTED FOR THE MTS | | CONTAIN A COVER SHEET FOR AN ATS. | | PLEASE CORRELATE. | | 110.3, 90.7, 702.6 NEC. | | FBC 106.1.2, 106.3.5.1.2 | | | | 4) NOTE: PLEASE SEE THE PLANS IN SOME PLACES STILL | | INDICATE A SMALLER GENERATOR THAN THAT ON OTHER SHEETS | | OF THE PLANS. PLEASE SEE SOME SHEETS AS THEY WERE NOT | | REVISED OR UPDATED FOR OTHER COMMENTS OR FOR THE | | GENERATOR WHICH ARE THE SAME SHEETS FROM THE PREVIOUS | | REVIEWED PLANS. | | PLEASE SEE THE SUBMITTALS FOR THE GENERATOR DO NOT | | CORRELATE. (PLEASE SEE SOME ARE FOR A *KATOLIGHT* UNIT | | WHICH IS A DIFFERENT MANUFACTURE AND DIFFERENT SIZE | | ETC. | | PLEASE CORRELATE ALL OF THE EQUIPMENT. | | 110.3, 90.7, 445 NEC. | | NFPA-110 2002 CHAPTERS 5, 6 AND 7. | | | | 5) NOTE: PLEASE SEE E0-1.0 FOR MAXIMUM TIMES ON DIMMER | | DEVICE. | | FBC 2004 13-415.1.ABC.1.1 AND .1.2. | | | | 6) NOTE: PLEASE SEE LOBBY AREAS/SEPARATE SPACES WHICH | | DO NOT INDICATE OVER RIDE CONTROLS AS GONE OVER IN | | PREVIOUS REVIEW AND IN MEETING. THE RESPONSE LETTER | | MENTIONS THE LOBBIES WERE DONE, HOWEVER NOT ALL. PLEASE | | SEE OTHER AREAS OF BUILDING WHICH DO NOT INDICATE | | CONTROLS FOR SEPARATE SPACES. | | PLEASE KNOW THE REDLINED PLANS WHICH WERE REMOVED FROM | | 13-415.1.ABC.1.1, .1.2, .1.3. | | | | 7) NOTE: PLEASE SEE THE ENERGY CALCULATIONS STILL DO | | NOT SEEM TO CORRELATE FOR EXTERIOR FIXTURES. THE PLANS | | INDICATE A SUBSTANTIAL AMOUNT OF FIXTURES; HOWEVER | | THESE CALCULATIONS DO NOT SEEM TO CORRELATE. PLEASE SEE | | 13-415.1.AB.1.1, 13-415.2.ABC.1.3 ETC | | | | 8) NOTE: PLEASE SEE ALL SHEETS IN SETS WHICH ARE THE | | *OVERALL* SHEETS FOR FLOORS ETC WHICH WERE NOT REVISED. | | PLEASE SEE THEY ARE THE SAME SHEETS FROM THE PREVIOUS | | REVIEW. | | PLEASE CLARIFY HOW THE PLANS CONTAIN TWO SEPARATE | | LAYOUTS. ???? | | FBC 106.1.2, 106.3.5.1.2 | | | | 9) NOTE: PLEASE SEE THE LIGHT POLE SUBMITTALS WHICH DO | | NOT ADDRESS PREVIOUS REVIEW COMMENTS. PLEASE SEE THESE | | DO NOT CONTAIN WIND LOAD INFORMATION AND NO | | CALCULATIONS FOR FIXTURES ON POLES OR POLES AND THE | | EFFECTIVE PROJECTED AREA COULD BE LOCATED. AS | | PREVIOUSLY STATED, THIS COULD BE DONE AS A PROVISO AND | | THIS INFORMATION COULD BE SUBMITTED AT A LATER DATE. | | 106.1.2 | | | | 10) NOTE: PLEASE SEE STAIRS 11 AND 12 ARE NOT COMPLETE | | (SEE LATER NOTES FOR STAIR 13). | | PLEASE SEE MISSING LIGHTING FOR EMERGENCY EGRESS OR | | LIGHTING UNDER NORMAL FOR STAIR 12. PLEASE SEE | | PHOTO-METRICS WHICH ARE ALSO STILL MISSING UNDER NORMAL | | AND UNDER EMERGENCY. | | PLEASE SEE LS 101 7.8.1.3, 7.9.2.2 ETC | | PLEASE SEE THAT ALL SHEETS AND ALL OVER-LAYS NEED TO | | CORRELATE AND PLEASE SEE THAT THESE SECTIONS FOR | | MEZZANINE LEVELS ARE NOT COMPLETE. | | FBC 106.1.2 | | *PLEASE SEE BUILDING REVIEW NOTES FOR POSSIBLE CONFLICT | | FOR DOOR SWINGS (IF APPLICABLE). | | | | 11) NOTE: PLEASE SEE STAIR AREA FOR STAIR (8) ON | | E2-5.0.0. PLEASE SEE THE LIGHTING WAS NOT CHANGED. | | PLEASE SEE THAT ALL SHEETS AND OVER-LAYS NEED TO | | CORRELATE. FBC 106.1 | | | | 12) NOTE: PLEASE SEE LIGHTING ON E1-6.3 WAS NOT UPDATED | | FOR STAIRS 4 AND 5. PLEASE ALSO SEE NOTES FOR | | PHOTO-METRICS. NFPA-101 7.8, 7.9 | | FBC 106.1.2, | | | | 13) NOTE: PLEASE SEE THAT THE LIGHTING POWER DENSITY | | CALCULATIONS STILL DO NOT CORRELATE WITH ALL OF THE | | AREA AND ROOM DESIGNATIONS ON PLANS. | | PLEASE SEE UPPER LEVELS, MISSING ALL OF A-6 | | DESIGNATIONS. | | FBC 13-415.2 | | FBC 106.1.2, 106.3.5.1.2 | | | | 14) NOTE: PLEASE SEE E2-1.2 WHICH CONTAINS MISSING | | CIRCUITING FOR ROOMS FOR MECHANICAL EQUIPMENT. PREVIOUS | | NOTES REQUESTED ALL ROOM DESIGNATIONS TO BE COORDINATED | | ETC. | | PLEASE SEE THESE ARE ROOMS WHICH ARE ELEVATOR EQUIPMENT | | ROOMS WHICH DO NOT CONTAIN THE DEDICATED CIRCUITS AS | | REQUIRED PER 620.23. | | PLEASE SEE DESIGNATIONS FOR ELEVATOR EQUIPMENT ROOMS | | SHOULD BE ON PLANS AS LIGHTING IN THESE ROOMS IS BEING | | SHOWN FEEDING OTHER AREAS. | | ROOMS FOR ELEVATORS 6,7,8, AND 9. | | PLEASE SEE NOTES WITH RESPECT TO UPPER EQUIPMENT | | ROOM(S). | | | | 15) NOTE: PLEASE SEE PLANS FOR UPPER EQUIPMENT ROOMS | | ARE NOT COMPLETE. THIS WAS GONE OVER IN MEETING, | | HOWEVER THE SAME SHEETS WERE SUBMITTED BACK IN FOR | | REVIEW. | | PLEASE CLARIFY THE AREA/ROOM DESIGNATIONS FOR THE | | ELEVATOR EQUIPMENT FOR UNITS 1, 2 AND 3. | | WHERE IS THIS ELEVATOR EQUIPMENT ROOM? PLEASE SEE IF | | THIS IS THE ROOM LOCATED ON UPPER FLOORS POWER PLANS | | E1-6, E1-6.1 WHERE IS THE EQUIPMENT AND THE DEDICATED | | BRANCH CIRCUITS ETC. PLEASE ALSO SEE LIGHTING PLANS. | | PLEASE SEE 620.22, .23, .24, 51 ETC. | | | | 16) NOTE: PLEASE LIGHTING AND POWER PLANS FOR THE SAME | | FLOOR/AREA AS THE LIGHTING AND CONTROLS STILL INDICATE | | SWITCHING OUTSIDE STAIR WALL? PLEASE SEE THE SAME PLANS | | WERE SUBMITTED WITH OUT CHANGES TO THE UPPER DOME AREA | | FOR LIGHTING CONTROL, EGRESS LIGHTING ETC. | | PLEASE SEE THE UPPER AREA PLANS NEED TO BE COORDINATED | | AND COMPLETE. | | NFPA-101 7.8,7.9, FBC 13-415.1.ABC.1.1, ETC, NEC 620, | | 408, 310.16, 240.4 ETC | | FBC 106.1.2, 106.3.5.1.2 ** PLEASE CALL TO GO OVER | | THESE SHEETS. | | | | 17) NOTE: PLEASE SEE STILL MISSING BATTERY BACK LIGHT | | FIXTURES OF SOME KIND ON MECHANICAL EQUIPMENT ROOMS, | | ELEVATOR EQUIPMENT ROOMS.THIS IS FOR MULTIPLE ROOMS | | LS 101 7.8, 7.9, NEC 700.16, 700.12E ETC. | | PLEASE SEE REDLINED SHEETS. | | | | 18) NOTE: PLEASE STILL MISSING THE MANUFACTURES | | SPECS/CUT SHEETS FOR THE TANK LESS WATER HEATERS. | | 110.3, 90.7. THIS COULD BE DONE AS A *PROVISO* ALTHOUGH | | IT WAS ALSO STATED IN PLUMBING REVIEW COMMENTS. | | | | 19) NOTE: PLEASE SEE PHOTO-METRICS. PLEASE CORRELATE | | ALL STAIRS AND AREAS FOR EGRESS. PLEASE SEE PREVIOUS | | NOTE ABOVE WHICH MENTIONS TO COMPLETE STAIRS 11, 12 | | ETC. | | PLEASE SEE THERE ARE SEVERAL SHEETS WHICH THE | | TABLE/INFORMATION IS NOT PRINTED. | | PLEASE SEE SHEETS E8-5.1 THRU 8-6.4 WHICH STILL | | INDICATE LIGHTING PHOTO-METRIC INFORMATION STILL | | PENDING. | | PLEASE SEE SHEETS E9-5.1 THRU 9-5.2 WHICH ALSO INDICATE | | INFORMATION STILL PENDING. | | PLEASE COMPLETE AT THIS TIME AS REQUESTED. | | | | 20) NOTE: PLEASE SEE STAIRS ARE STILL BEING NUMBERED | | WITH NUMERICAL DESIGNATIONS WHICH DO NOT CORRELATE WITH | | THE PLANS. STAIR 1, STAIR 4, STAIR 8, ETC. | | 106.1, 106.1.2, 106.3.5.1.2 | | LS 101 | | PLEASE CLARIFY. | | | | 21) NOTE: PLEASE SEE SOME BATHROOMS STILL MISSING | | BATTERY TYPE BACK UP LIGHT. PLEASE SEE LIBRARY MEN?S | | AND WOMEN?S ON E2-1.2 | | | | 22) NOTE: PLEASE SEE STAIR 1 ON OVER ALL PLANS ON | | E2-5.0 AND 2-5.1 FIXTURE TYPE, WHERE IS THE E2? PLEASE | | ALSO CLARIFY WHERE THIS STAIR CONTINUES UP. | | | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | 2007-01-22 06:31:13 | 2007-01-22 06:31:13 | | IN PROGRESS | 2007-01-21 19:09:40 | 2007-01-21 19:09:40 | | ELECTRICAL REVIEW COMPLETED. | | THE PLANS WILL BE GOING INTO A "F" STATUS AND NOTES ARE | | TO FOLLOW ONCE THEY ARE COMPLETED. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2006-12-25 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-12-25 |
Time |
20:33 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-12-24 |
Time |
18:10 |
Sent To |
|
|
Notes |
2006-12-25 20:33:37 | ** UNSAT 2ND REVIEW ** | | | | | | **** CITY CENTER ******* | | | | FOURTH REVIEW, 2ND UNDER PERMIT APPLICATION. | | | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL | | IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, | | SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING | | REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT | | MADE ON PREVIOUS REVIEWS. | | | | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM | | PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. | | THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE | | PREVIOUS REVIEW NOTES. | | | | A "NO" IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR | | FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS | | ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER | | EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. | | | | AN "OK" WILL BE LABELED AS SUCH ON THE SAME NUMERICAL | | COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. | | | | A "NO/OK" MEANS PART OF THE COMMENT MAY HAVE BEEN | | ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW | | COMMENT MAY HAVE BEEN FULLY ADDRESSED. | | | | ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF | | THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. | | | | | | 1) NOTE: NO, PLEASE SEE THREE SETS OF ALL ARE REQUIRED. | | PLEASE SEE MISSING A THIRD SET OF ELECTRICAL SUBMITTALS | | FOR GENERATOR, ATS, MTS ETC. | | PLEASE ALSO SEE OTHER NOTES FOR MISSING THE LIGHTING | | SPEC BOOKS AND ENGINEERING CALCULATIONS WHICH WERE | | PREVIOUSLY SUBMITTED. | | ENGINEERING FOR SELECTIVE COORDINATION PREVIOUSLY | | SUBMITTED ETC. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE KNOW WHEN SUBMITTING FOR FINAL PERMITTING AND | | STAMPING, A THIRD SET OF SIGNED, DATED AND SEALED PLANS | | WILL BE REQUIRED. | | PLEASE SEE FBC ADMINISTRATIVE SECTION AS ADOPTED BY THE | | CITY OF WEST PALM BEACH, 106.1.2106.1.3, 109.3.6 FOR | | THRESHOLD BUILDINGS. THIS IS WILL BE REQUIRED FOR ALL | | DOCUMENTATION AND PLANS AND FOR ALL TRADES WHETHER OR | | NOT COMMENT IS MADE BY OTHER TRADES. | | | | 2) NOTE: NO, PLEASE SEE SYMBOL LEGEND ONLY HAD CHANGES | | TO TWO OF THE DEVICES. PLEASE SEE ALL SWITCH/OVER RIDE | | TYPE DEVICES INCLUDING THE OC SENSOR SHOULD INDICATE ON | | THE SYMBOL LEGEND ITS DESIGNATION AND TIMES ON OVER | | RIDES. THIS WOULD INCLUDE S3, ST, OC ETC. | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE FBC CHAPTER 13. PLEASE SEE 13-415.1.ABC.1.1, | | .1.2 AND .1.3. | | PLEASE BE SURE ALL DEVICE ON PLANS CORRELATE WITH THE | | DEVICE SYMBOL LEGEND. | | PLEASE BE SURE MAX TIME OF OVER -RIDES ARE SHOWN. IF | | TIMER TYPE, (4HRS MAX), IF OCCUPANCY SENSOR TYPE (30 | | MINS MAX). | | PLEASE SEE ADDITIONAL COMMENTS FOR CONTROLS AND SYSTEM | | BEING PROPOSED. | | | | 3) NOTE: OK. | | | | 4) NOTE: OK/NO, PLEASE SEE THESE WERE NOW SUBMITTED | | HOWEVER PLEASE SEE NEW NOTES AT THE END OF THESE | | COMMENTS AS THESE ARE NOW BEING SUBMITTED AND REVIEWED | | FOR THE FIRST TIME AND THERE ARE COMMENTS ON DOCUMENTS | | SUBMITTED. | | PLEASE ALSO SEE NEW NOTES PERTAINING TO THE SIGNATURE | | OF THE MECHANICAL ENGINEER OF RECORD ON SAID | | DOCUMENTS. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SUBMIT COMPLETED ENERGY CALCULATIONS FOR THE | | ENTIRE BUILDING FOR REVIEW OF ALL TRADES. PLEASE KNOW | | AS NONE WERE SUBMITTED AT THIS TIME THERE ARE MANY | | ITEMS WHICH CAN NOT BE VERIFIED WITH THE PLANS, | | EQUIPMENT AND LIGHTING. | | PLEASE SEE 13-415.1.AB.1. | | | | 5) NOTE: OK/NO, PLEASE SEE THESE WERE SUBMITTED AND | | SEEM TO BE OK, HOWEVER AS NOTED IN NOTE #4 ABOVE THERE | | ARE NEW NOTES BASED ON THE COORDINATION OF THESE | | DOCUMENTS WITH THE ENERGY CALCULATIONS SUBMITTED. | | PLEASE SEE THE TOTALS ON THE WATTAGE DO NOT SEEM TO | | CORRELATE WITH THE ENERGY CALCULATIONS AS SUBMITTED. | | PLEASE ALSO SEE NEW NOTES. | | PLEASE KNOW THE THREE SETS OF LIGHTING POWER DENSITIES | | SHALL CONTAIN TITLE BLOCKS FOR THE ENGINEER AND/OR FIRM | | OF RECORD. THIS MAY BE RE-DONE ON NEW SHEETS WHICH | | CONTAIN THESE TITLE BLOCKS, STAMPED ON EACH SHEET WHICH | | IS SIGNED AND SEALED BY THE ENGINEER OR HANDWRITTEN. | | PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE 13-415.2, 13-415.2ABC.1 FOR MINIMUM AND | | MAXIMUM PERFORMANCE CALCULATIONS. PLEASE SEE THE | | CALCULATIONS SUBMITTED SHOWING THE LIGHTING POWER | | DENSITIES (LPD) ARE NOT COMPLETE AND/OR THERE ARE ITEMS | | WHICH DO NOT CORRELATE WITH SAID PLANS. | | PLEASE SEE THERE ARE MANY ROOMS INDICATED ON PLANS | | WHICH COULD NOT BE LOCATED IN CALCULATIONS OR THERE ARE | | ROOMS ON CALCULATIONS WHICH COULD NOT BE LOCATED ON | | PLANS. | | PLEASE CORRELATE AND PLEASE SEE SOME OF THE LPD'S SEEM | | TO BE VERY HIGH FOR SOME OF THE ROOMS AND AREAS AS | | NOTED AND SHOWN. | | PLEASE SEE OFFICE IN PARKING GARAGE FOR INSTANCE. | | PLEASE SEE SOME OTHERS WHICH BASED ON THE TABLES AS | | SET-FORTH IN THE CODE MAY ALLOW 1.7, THE CALCULATIONS | | MAY SHOW 10.5 ETC. | | PLEASE REVIEW ALL AND RE-ADJUST AS REQUIRED AND | | NEEDED. | | | | 6) NOTE: NO, UNABLE TO VERIFY AT THIS TIME DUE TO THE | | CONFLICTS BETWEEN THE ENERGY CALCULATIONS FOR EXTERIOR | | LIGHTING AND THE ALLOWANCE LEVELS NOT BEING SHOWN. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE 13-415.2.ABC.1.3 FOR ALL EXTERIOR LIGHTING | | ALLOWANCES, INCLUDING THAT WHICH IS DECORATIVE. PLEASE | | SEE THERE ARE EXCEPTIONS FOR SOME AREAS; HOWEVER THESE | | AREAS AS LISTED WOULD BE REQUIRED BY SECTIONS AS | | LISTED. PLEASE SEE 13-415.0(3) (EXCEPTS). | | | | 7) NOTE: OK/NO, PLEASE SEE THE PLANS NOW SEEM TO | | INDICATE THE EQUIPMENT MORE IN DETAIL, HOWEVER AS NOTED | | IN NOTE #1, THE MANUFACTURES SPECS/CUT SHEETS WERE NOT | | SUBMITTED BACK. THIS REVIEWER ONLY HAS THE ONE BOOK | | WHICH WAS RETAINED BY THIS OFFICE. | | WHEN SUBMITTING BOOKS/SPECS, PLEASE BE SURE TO HIGH | | LIGHT AND COORDINATE WITH THE PLANS SUBMITTED FOR THE | | EQUIPMENT AND DEVICES BEING INSTALLED. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE PLANS SHALL INDICATE THE ACTUAL PANEL BEING | | USED FOR LIGHTING CONTROLS. PLEASE SEE THERE ARE | | SEVERAL PANELS INDICATE IN THE MANUFACTURE SPECS/CUT | | SHEETS SUBMITTED AND THE ACTUAL UNIT NEEDS TO BE | | HIGH-LIGHTED IN SPECS. PLANS SHALL ALSO BE REQUIRED TO | | PROVIDE THE TECHNICAL INFORMATION AT EACH LIGHTING | | CONTROL PANEL. (LCP) | | ** PLEASE KNOW AS REFERENCE TO LIGHTING CONTROL PANELS | | IN NOTES HERE ON WILL BE DESIGNATED AS "LCP'S". PLEASE | | SEE RISER INDICATES LCP'S AS 225A RATED, WHICH IS OK, | | HOWEVER PLEASE BE SURE THE INFORMATION AS SHOWN ON | | CUT/SPEC SHEETS IS BROUGHT OVER TO THE PLANS AND LISTED | | ON EACH LCP. | | | | 8) NOTE: OK/NO, PLEASE KNOW MOST OF THE SYSTEM IS | | UNDERSTOOD HOWEVER THERE ARE AREAS IN WHICH A SWITCH | | TYPE DEVICE (SENTRY) IS BEING INSTALLED ALONG WITH AN | | OC (OCCUPANCY SENSOR) TYPE DEVICE. THE DETAIL WAS | | LOCATED ON 7-2.0 HOWEVER THIS WOULD STILL PERMIT THE | | TURNING OFF LIGHTS IN AN UNWANTED FASHION.PLEASE SEE | | EGRESS STAIRS FOR MEZZANINE AREA WHICH COULD BE TURNED | | OFF, YET OF AN OCCUPANT WAS STILL LOCATED ON THE UPPER | | LEVEL THEY WOULD HAVE NO CONTROL OF LIGHTING AS SHOWN. | | | | PLEASE SEE ROOF TOP AREA ON E1-6.1 WHICH LOCATES A | | SWITCH ON WHAT APPEARS TO BE AN OUTSIDE WALL TO CONTROL | | LIGHTING IN ELEVATOR EQUIPMENT ROOM AS WELL AS OTHER | | LIGHTING AS REQUIRED FOR LIFE SAFETY. | | PLEASE SEE OTHER AREAS WHICH CONTAIN BOTH. | | PLEASE ALSO SEE AS NO SPECS WERE SUBMITTED BACK, COULD | | NOT LOCATE A LETTER FROM THE LUTRON MANUFACTURE WHICH | | PERMITS THE USE OF THE SENTRY SWITCH IN THEIR SYSTEM. | | PLEASE SEE AREAS OF MEETINGS ROOMS AND COMMISSION | | CHAMBERS AREA WHICH DO NOT PROVIDE ENOUGH INFORMATION | | FOR HOW THESE WILL BE CONTROLLED. PLEASE SEE THAT THE | | NOTE ON THE PLANS FOR THIS TO BE PROVIDED BY LIGHTING | | TECHNICAL NEEDS TO BE REPLACED WITH ACTUAL DETAILS ON | | HOW THESE WILL BE ADDRESSED TO COMPLY WITH CHAPTER 13 | | AT THIS TIME. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE KNOW THERE IS CONCERN OVER THE TYPE OF SYSTEM | | BEING PROPOSED AND CONTROLS OF SAID SYSTEM. PLANS CALL | | FOR A "SWEEP" EACH HOUR FOR THE SYSTEM OUT OF NORMAL | | BUSINESS HOURS AND THIS WILL TURN OFF ANY AND ALL | | DEVICES. THE DEVICES WILL THEN HAVE THE ABILITY TO OVER | | RIDE THE SYSTEM IN ANY PARTICULAR AREA WHICH THE | | CIRCUIT/SWITCH IS DESIGNATED TO. PLEASE KNOW THIS | | BUILDING IN SEVERAL SECTIONS WILL BE OCCUPIED OUT OF | | THE NORMAL BUSINESS HOURS WHICH ARE SET UP AND WILL | | CAUSE DARKNESS EACH HOUR EVEN WHEN OCCUPIED. PLEASE SEE | | SPECS SHEETS AS SUBMITTED SPEAK OF THE INCLUSION OF AN | | OCCUPANT SENSOR TYPE DEVICE TO ALLEVIATE THIS. | | (UNINTENDED BLACK-OUTS). PLEASE SEE AREAS LIKE THE | | LIBRARY, COMMISSIONS CHAMBERS, OFFICE DESIGNATED FOR | | POLICE, AND OTHER AREAS. | | PLEASE SEE THE CODE ON THE OTHER HAND FOR ALL AREAS | | WHICH DURING NORMAL BUSINESS HOURS WHICH WILL REQUIRE | | ROOMS TO BE OFF. PLEASE SEE 13-415.1.ABC.1.2, FOR ALL | | ROOMS CONTAINING FLOOR TO CEILING HEIGHT PARTITIONS | | WHICH WILL REQUIRED SEPARATE CONTROL. PLEASE SEE AS | | SHOWN ON PLANS, THESE ROOMS WILL COME "ON" AT THE SET | | BUSINESS HOUR TIMES AND WILL REMAIN ON UNTIL AFTER THE | | "ONE HOUR SWEEP" AFTER THE NORMAL OPERATIONAL TIMES | | HAVE PASSED. | | PLEASE SEE CLOSETS, OFFICES, STORAGE AREAS ETC. THERE | | ARE FAR TOO NUMEROUS ROOMS TO LIST. | | PLEASE SEE THERE ARE MANY ROOMS ON PLANS WHICH DO | | INDICATE "OC" TYPE DEVICES; HOWEVER THERE IS NOT DETAIL | | ON THE LIGHTING CONTROL RISER HOW THESE WILL BE | | CONNECTED OR TIED IN. | | PLEASE SEE BATHROOMS ETC. | | PLEASE KNOW THIS TYPE OF DEVICE WILL WORK IN MANY AREAS | | IN THIS BUILDING; HOWEVER THERE ARE AREAS WHICH WILL | | NOT MEET CODE OR THE INTENT IN SEPARATE SPACES. PLEASE | | KNOW AT THIS TIME, AS SHOWN THERE ARE SEVERAL ITEMS | | WHICH WILL BE REQUIRED TO BE ADJUSTED. PLEASE ALSO | | OBTAIN A LETTER FROM THE "SENTRY SWITCH" MANUFACTURE | | WHICH PERMITS THIS TYPE OF DEVICE TO BE USED WITH THE | | LUTRON GRAFIK PANEL. | | 110.3, 90.7 NEC. | | | | 9) NOTE: OK/NO, PLEASE SEE COORDINATION OF NUMERICAL | | IDENTIFICATION SEEMS TO BE BETTER; HOWEVER PLEASE SEE | | SEVERAL AREAS AND ROOM HAVE THEIR DESIGNATION COVERED | | BY A DEVICE, FIXTURE OR SOME OTHER ITEM. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE THERE ARE SEVERAL ROOM NUMERICAL | | DESIGNATIONS ON CALCULATIONS WHICH COULD NOT BE LOCATED | | ON PLANS. PLEASE SEE GARAGE PLANS. | | PLEASE SEE SOME WHERE THE ROOM DESIGNATION IS THERE | | HOWEVER IT SEEMS TO BE VERY LIGHT IN COLOR AND CAN NOT | | BE EASILY READ. PLEASE SEE OTHER AREAS WHICH THE | | FIXTURE DESIGNATION COVERS THE ROOM IDENTIFICATION OR | | VICE VERSA, THE FIXTURE TYPE COULD NOT BE SEEN DUE TO | | THE OVER LAY OF THE NUMERICAL DESIGNATION. | | PLEASE COORDINATE. A1-116-2-1.610 ETC | | FBC ADMIN SECTION 106.1.2, 106.1.3 | | | | 10) NOTE: OK, HOWEVER PLEASE KNOW BASED ON FURTHER | | COMMENTS, ADJUSTMENTS IN FIXTURE TYPES AND DESIGNATIONS | | WILL BE NEEDED. | | | | 11) NOTE:NO, PLEASE SEE THERE ARE SEVERAL ROOMS WHICH | | STILL DO NOT INDICATE A BATTERY BACK UP FIXTURE OF SOME | | SORT WHICH WILL BE REQUIRED. | | FIRE PUMP ROOMS, MAIN ELECTRICAL ROOM, MAIN MECHANICAL | | ROOM, THE MAIN MECHANICAL ROOM ELECTRICAL ROOM, | | ELEVATOR EQUIPMENT ROOM. ETC. | | PLEASE ALSO SEE NEW NOTES FOR ROOF TOP/ELEVATOR | | EQUIPMENT ROOM AND OUTSIDE AREA TO STAIR TWO. PLEASE | | ALSO SEE GARAGE STAIR TOWERS WILL ALSO BE REQUIRED TO | | CONTAIN MINIMUM BATTERY BACK UP FOR FIXTURES AS OTHER | | STAIR TOWERS IN MAIN BUILDING ARE DONE. | | ** PLEASE ALSO SEE FIRE REVIEW COMMENTS. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE THAT BATTERY BACK UP FIXTURES OF SOME TYPE | | WILL BE REQUIRED FOR THE FOLLOWING LOCATIONS. SOME ARE | | SHOWN ALREADY, HOWEVER NOT ALL. THE MAIN ELECTRICAL | | ROOM, THE FIRE COMMAND CENTER, BOTH FIRE PUMP ROOMS, | | ELEVATOR EQUIPMENT ROOM, AND AT THE LOCATION OF THE | | ROOF TOP GENERATOR WILL ALL REQUIRE THIS. PLEASE SEE | | THAT ALL STAIR TOWERS AND EGRESS PATHS SHALL ALSO | | INCLUDE SOME SORT OF BATTERY BACK UP FIXTURE. THERE ARE | | MANY LOCATIONS WHICH INCLUDE THIS; HOWEVER AS SOME OF | | THE FIXTURE INFORMATION IS NOT CLEAR AT THIS TIME THIS | | CAN NOT BE VERIFIED. THIS BUILDING IS EXPECTED TO BE | | OCCUPIED IN THE TIME OF POWER OUTAGES AND IN THE EVENT | | OF THE TRIPPING OF A SINGLE MEANS OF OVER CURRENT | | PROTECTION (EMSB1) OR GEN MAIN, THIS WILL PLACE MANY | | AREAS IN COMPLETE DARKNESS WHICH IS NOT PERMITTED. NEC | | 700.12E, 700.16, LS 101 7.9. | | | | 12) NOTE: OK. | | | | 13) NOTE: OK. | | | | 14) NOTE: NO, PLEASE SEE COMMENTS WITH RESPECT TO STAIR | | TOWERS IN GARAGE AND OTHER ROOMS WITH THESE | | DESIGNATIONS WHICH MAY BE CHANGED OR ADJUSTED. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE FIXTURE "E", PLEASE SEE IT APPEARS TO BE | | BATTERY BACK UP, BUT NOT ENOUGH INFORMATION IS | | PROVIDED. PLEASE SEE FIXTURES, Z,ETC. | | | | 15) NOTE: OK. | | | | 16) NOTE: NO, PLEASE SEE RESPONSE LETTER MENTIONS THIS | | IS TO BE DONE BY THE STRUCTURAL ENGINEER/DESIGNER OF | | RECORD HOWEVER COULD NOT LOCATED ANY DETAIL FOR THIS ON | | THE S SHEETS. PLEASE SEE THE SAME DETAIL FOR GROUND | | LEVEL POLES IS BEING USED FOR ROOF TOP MOUNTING? PLEASE | | SEE NEW NOTES WITH RESPECT TO THE S SHEETS AND TITLE | | BLOCKS MISSING AND OTHER NOT CONTAIN ANY CERTIFICATE OF | | AUTHORIZATION NUMBER AS REQUIRED. SEE NEW ELECTRICAL | | NOTES. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE PROVIDE ALL MINIMUM WIND LOADING FOR SITE | | LIGHTING LIGHT POLES, AND THAT OF THE POLES ON GARAGE | | ROOF STRUCTURE. PLEASE KNOW A DETAIL ON HOW THESE WILL | | BE ATTACHED ON PARKING DECK OF THE GARAGE AND POLE | | DETAIL FOR GROUND MOUNTED/BURIED POLES WILL BE | | REQUIRED. PLEASE KNOW ALL SHOW MEET THE FBC 140MPH | | (3SEC GUST) 120MPH SUSTAINED. | | THE STRUCTURAL CALCULATIONS WILL BE REVIEWED BY THE | | BUILDING PLAN REVIEWER. | | FBC 106.1.2 ADMIN SECT. | | | | 17) NOTE: OK. | | | | 18) NOTE: OK. | | | | 19) NOTE:NO, THIS IS STILL UNCLEAR HOW THE SHORTER | | LENGTHS OF CONDUCTORS OUT TO FIXTURES ACTUALLY CONTAIN | | A HIGHER VOLTAGE DROP. | | PLEASE SEE OTHER COMMENTS ON THE FOLLOWING NOTE #20. | | | | ** PREVIOUS REVIEW NOTE** | | PLEASE PROVIDE THE VOLTAGE DROP ON THIS SAME CIRCUIT AS | | NOTED ABOVE IN NOTE # 18, PLEASE SEE FIXTURE SA | | INDICATE #8'S, AND YET SB WHICH CONTAIN A LONGER RUN | | AND MORE FIXTURES ONLY INCREASE UP TO A #10 AWG. PLEASE | | SEE FBC 13-413.1.ABC.1.2. | | | | 20) NOTE:NO, COULD NOT LOCATE ANY FOR BRANCH | | CIRCUITING. ONLY LOCATED THE FEEDERS ON RISER. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE PROVIDE A WORST CASE FOR BOTH FEEDER AND BRANCH | | CIRCUIT. | | 13-413.1ABC.1. | | IT IS NOTEDTHAT ON MANY OF THE PANEL SCHEDULES A VD % | | IS ALREADY SHOWN, HOWEVER PLEASE BE SURE TO INDICATE | | THE ABOVE. (CAN BE DONE ON A SIMPLE TYPICAL TABLE). FBC | | 106.1.2. | | | | 21) NOTE: NO, SAME NOTE. PLEASE SEE THE FS SHEETS STILL | | INDICATE ELECTRICAL FIRE PUMPS ALONG WITH DIFFERENT | | SIZES OF EQUIPMENT THAN THAT SUBMITTED IN THE | | ELECTRICAL SUBMITTAL BOOKS. PLEASE SEE DIFFERENT | | MANUFACTURE, ETC. | | PLEASE SEE THAT BASED ON THE COMMENTARY PROVIDED FOR | | FUEL USAGE, THE FUEL FOR ONE APPEARS TO BE OK, HOWEVER | | THE OTHER (110HP) DOES NOT MEET THE MINIMUM LEVEL OF | | FUEL REQUIRED. PLEASE SEE AS TWO DIFFERENT SIZE PUMPS | | ARE SUBMITTED, I AM UNABLE TO REVIEW WHICH THE ONE FOR | | INSTALLATION AT THIS TIME. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE THE 100% FIRE SPRINKLER PLANS SUBMITTED DO | | NOT CORRELATE WITH THE FA OR ELECTRICAL PLANS SUBMITTED | | WITH RESPECT TO THE FIRE PUMPS. PLEASE SEE THE FS | | SHEETS WHICH INDICATE ELECTRIC, ELECTRICAL/ DIESEL AND | | DIESEL. PLEASE SEE THE ELECTRICAL PLANS AND THE | | MANUFACTURE SPECS/CUT SHEETS SUBMITTED ONLY INDICATE | | DIESEL. | | PLEASE SEE THE MINIMUM FUEL TANK SIZE SHALL BE | | SUFFICIENT FOR A MINIMUM OF 8HRS AT 100% LOADS. IF | | ELECTRICAL AND BEING DRIVEN BY THE BACK UP POWER OF AN | | EMERGENCY GENERATOR, THE ON-SITE FUEL SUPPLY SHALL BE | | BASED ON THE 100% LOAD OF THE FIRE PUMP AND ALL OTHER | | LEGAL AND EMERGENCY STAND-BY LOADS AT 100% FOR TIMES | | REQUIRED. | | PLEASE SEE 2002 NFPA-110, TEXT EXTRACTED FORM THE | | CODE: | | 9.6.2.2 THE FUEL SUPPLY CAPACITY SHALL BE SUFFICIENT | | TO PROVIDE 8 HOURS OF FIRE PUMP OPERATION AT 100 | | PERCENT OF THE RATED PUMP CAPACITY IN ADDITION TO THE | | SUPPLY REQUIRED FOR OTHER DEMANDS. | | PLEASE SEE NFPA-20 2003 IF DIESEL DRIVEN AND THE SAME | | AMOUNT OF FUEL REQUIRED WHICH EQUALS 1GAL PER HP PER | | HOUR PLUS 5% FOR SUMP AND 5% FOR EXPANSION. PLEASE SEE | | THE FOLLOWING THE CODE. | | 11.4.3.1 FUEL SUPPLY TANK(S) SHALL HAVE A CAPACITY AT | | LEAST EQUAL TO 5.07 L PER KW (1 GAL PER HP), PLUS 5 | | PERCENT VOLUME FOR EXPANSION AND 5 PERCENT VOLUME FOR | | SUMP AND THE COMMENTARY SECTION AS FOLLOWS, A.11.4.3 | | THE QUANTITY 5.07 L PER KW (1 GAL PER HP) IS EQUIVALENT | | TO 0.634 L PER KW (1 PINT PER HP) PER HOUR FOR 8 | | HOURS. WHERE PROMPT REPLENISHMENT OF FUEL SUPPLY IS | | UNLIKELY, A RESERVE SUPPLY SHOULD BE PROVIDED ALONG | | WITH FACILITIES FOR TRANSFER TO THE MAIN TANKS. | | | | 22) NOTE: OK. | | | | 23) NOTE: OK/NO, PLEASE SEE AS SOME AREAS ARE NOT CLEAR | | UNABLE TO VERIFY ANY GFI NOTATION. PLEASE SEE SOME ARE | | SHOWN WITH THE GFI IDENTIFICATION AND IF THE SYMBOLS | | WERE A LITTLE MORE CLEAR THE SYMBOL LEGEND ON E0.10 MAY | | BE IF USE. | | PLEASE ALSO SEE SHEET E1.-1.2 WHICH SHOULD BE A SECTION | | OF THE BUILDING WHICH WOULD BE LARGER IN SIZE. IT SEEMS | | SOMETHING WITH THE PRINTING OF SHEET CAUSED SHEET TO BE | | MUCH SMALLER. PLEASE SEE KITCHEN AREAS WHICH ARE | | LOCATED ON THIS SHEET COULD NOT BE VERIFIED AT THIS | | TIME. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE NEC 210.8B3 FOR ALL RECEPTACLES IN KITCHENS | | IN OTHER THAN DWELLING UNITS. PLEASE SEE THIS WOULD BE | | REQUIRED FOR CAFE/ KITCHENETTE AREAS AS SHOWN ON | | PLANS. | | | | 24) NOTE: OK. | | | | 25) NOTE: NO, PLEASE SEE PHOTO-METRICS ARE CONFUSING. | | PLEASE SEE THE GARAGE STAIRS SEEM TO NOW BE SHOWN, | | HOWEVER THERE IS NO SPECIFIED UNDER NORMAL OR UNDER | | EMERGENCY. PLEASE SEE DESIGNATIONS ON ALL OTHER STAIRS | | AND LABELING OF AREAS DOES NOT CORRELATE WITH ACTUAL | | PLANS AND STAIR TOWERS AS SHOWN. PLEASE KNOW THIS | | COMMENT IS NOT JUST FOR GARAGE STAIRS AS PREVIOUS | | COMMENT WAS TO ADDRESS ALL PHOTO-METRICS. PLEASE SEE | | MISSING STAIR 13, MEZZ STAIRS, PLEASE SEE OTHER STAIR | | DESIGNATIONS NOT LABELED ETC. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE MISSING THE PHOTO-METRICS FOR THE GARAGE | | STAIR TOWERS. PLEASE SEE THE PHOTO-METRICS AS SUBMITTED | | ARE A LITTLE CONFUSING. PLEASE PREVIOUS COMMENTS ONLY | | REQUESTED EGRESS PATHS OF LEVELS SURFACES/ CORRIDORS | | AND EGRESS PATHS THAT OF THE STAIR TOWERS. PLEASE SEE | | THERE MUCH INFORMATION SUBMITTED GIVING FIXTURE | | DESIGNATIONS AND ROOM BY ROOM LEVELS? PLEASE PROVIDE | | THE EGRESS PATHS INFORMATION INDICATING THE CLEAR | | NORMAL AND EMERGENCY LEVELS AS NEEDED AND REQUIRED BY | | CODE. | | PLEASE PROVIDE A BREAKDOWN OF THE NORMAL AND EMERGENCY | | AVERAGE. PLEASE SEE THAT INFORMATION OF WHICH IS | | SUPPLIED ON EACH "OVER-ALL" SHEET DOES NOT SUPPLY THE | | INFORMATION AS NEEDED. | | PLEASE SEE 9-4.1 WHICH INDICATES IN TITLE BLOCK, | | EMERGENCY/ NORMAL? | | | | 26) NOTE: OK. | | | | 27) NOTE: NO, PLEASE SEE SOME ARE STILL SHOWING THIS | | DESIGNATION. | | | | ** PREVIOUS REVIEW NOTE** | | PLEASE CLARIFY GARAGE LIGHTING WHICH SHOWS "ON" NEXT | | TO SOME FIXTURES ON PLANS. (RAMP AREAS) THIS IS UNCLEAR | | AT THIS TIME WHAT IS MEANT BY THIS. | | FBC 106.1.2 ADMIN SECTION | | | | 28) NOTE: OK. | | | | 29) NOTE: OK. | | | | 30) NOTE: OK/NO, PLEASE SEE ROOM LAYOUT DESIGNATION ON | | SHEET E1-1.3 INDICATES SHEET E4-1.0, WHEN IT SHOULD BE | | E- 1.1 | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE MISSING THE ELECTRICAL ROOM FOR 1HMGB AND | | 1HMGA ON THE LAYOUTS FOR THE ELECTRICAL ROOMS. PLEASE | | PROVIDE. 106.1.2, | | NEC 110.26 | | | | 31) NOTE: NO/OK, PLEASE SEE THE DOOR SWINGS SEEM TO BE | | OK, HOWEVER PLEASE SEE NO NOTE FOR PANIC HARDWARE AS | | REQUIRED COULD BE LOCATED ON PLANS. THIS WILL BE | | REQUIRED FOR MAIN ELECTRICAL ROOM AND MAIN ELECTRICAL | | EQUIPMENT FOR MECHANICAL MAIN ELECTRICAL EQUIPMENT | | ROOMS. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE MAIN ELECTRICAL ROOM AND THE MISSING | | ELECTRICAL ROOM FROM NOTE #30 ABOVE WHICH IS STILL | | INDICATING DOORS WITH AN "IN-SWING" WHICH IS NOT | | PERMITTED. PLEASE ALSO BE SURE TO ADD A NOTE WITH | | RESPECT TO PANIC HARDWARE REQUIRED FOR ALL DOORS AS | | REQUIRED PER 110.26. (MAIN ELECTRICAL ROOM/ AND ROOM | | NOTED ON NOTE #30). | | PLEASE SEE THE DOOR SWINGS WERE NOTED ON ALL OF THE | | REVIEWS BASED ON THE 50%, 90% AND THIS REVIEW. PLEASE | | GO OVER ALL PLANS AND DOORS. | | | | 32) NOTE: NO, PLEASE SEE SEVERAL OF THESE UNITS ARE | | BEING SHOWN ON PLANS AT JANITOR CLOSET LOCATIONS, | | HOWEVER NOT ALL OF THESE ROOMS CONTAIN THESE. PLEASE | | ALSO SEE SEVERAL KITENETTE AREA WHICH ALSO INCLUDES | | THESE HOWEVER MANY DO NOT? IN EITHER CASE PLEASE SEE NO | | SPECS WERE SUBMITTED AND NO DISCONNECTING MEANS FOR ALL | | UNITS COULD BE LOCATED ON PLANS. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS FOR AL | | THE TANK-LESS WATER HEATER UNITS. THESE MAY ALSO BE | | LABELED AS INSTA-HOTS. PLEASE SEE MISSING DISCONNECTS | | AS REQUIRED ON THESE UNITS. THESE COULD NOT BE LOCATED | | ON PLANS. | | PLEASE SEE SIZING OF THE OVER CURRENT DEVICES, | | DISCONNECTS AND ETC SHALL BE BASED ON EACH UNIT. PLEASE | | SEE 422.31, 110.3, AND 90.7. | | | | 33) NOTE:NO, SAME NOTE. PLEASE VERIFY ALL. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE SOME TWH UNITS WHICH ARE SHOWN ON PLANS ARE | | MISSING THE REQUIRED CIRCUITING. CAN NOT REVIEW FOR | | COMPLIANCE OF LOAD, CONDUCTOR SIZE, OCP ETC AT THIS | | TIME. | | PLEASE COMPLETE. 240.4, 310.16, 408.4, FBC 106.1.2 | | | | 34) NOTE: OK. | | | | 35) NOTE: OK. | | | | 36) NOTE: OK | | | | 37) NOTE: OK. | | | | 38) NOTE: OK. | | | | 39) NOTE: OK. | | | | 40) NOTE: OK. | | | | 41) NOTE: OK, HOWEVER SEE NOTE FOR CORRELATION OF ROOM | | A5.107 | | | | 42) NOTE: OK. | | | | 43) NOTE: NO? SAME AS SHOWN. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE "SHADED" AREAS ON MEZZANINE LEVEL PLANS | | E-1.1.4, PLEASE CLARIFY | | 106.1.2 FBC ADMIN SECTION. | | | | 44) NOTE: OK. | | | | 45) NOTE: OK. | | | | 45) NOTE: NO/OK, PLEASE SEE WALL AS LOCATED, HOWEVER | | SEPARATE LIGHTING CONTROLS FOR SEPARATE SPACES AS | | REQUIRED COULD NOT BE LOCATED. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE WHAT APPEARS TO BE MISSING WALLS, DOORS | | SEPARATION E-1-1.2, LIBRARY/MUSEUM/ STORE? PLEASE SHOW | | AS THE REQUIREMENTS FOR CHAPTER 13 CAN NOT VERIFIED FOR | | CONTROL OF LIGHTING. LIGHTING OF SOME TYPE INCLUDING | | EXIT/EMERGENCY LIGHTS ARE STILL REQUIRED IN SPACE, EVEN | | IF FOR FUTURE BUILD OUT. PLEASE SEE LS 101 7.8, 7.9 AND | | POSSIBLE COMMENTS FROM FIRE MARSHAL?S OFFICE. | | 13-415.1.ABC.1.ABC.1.1, .1.2, .1.3 | | | | 46) NOTE: OK. | | | | 47) NOTE: NO/OK, SOME OF THESE WERE DONE BY THE CHANGES | | IN THE UNDER GROUND TO OTHER SECTIONS OF BUILDING, | | HOWEVER NOT DETAIL FOR THE ENCASED FEEDERS FROM | | GENERATOR COULD BE LOCATED. PLANS MENTIONS TO SEE | | ARCHITECTURAL PLANS; HOWEVER NO INFORMATION FOR WHICH | | SHEET OR DETAIL THIS IS COULD BE FOUND. PLEASE PROVIDE | | THE DETAIL. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE PROVIDE AN ELEVATION/DETAIL FOR ALL ELECTRICAL | | CONDUITS BEING RUN FROM GARAGE TO THE MAIN BUILDING. | | THIS BUILDING IS BEING CONSIDERED "ATTACHED" AND ONE " | | BUILDING" BY DEFINITION, HOWEVER DUE THE UNDERSTANDING | | OF MANY OF THE CONDUITS ARE NOW BEING INSTALLED IN THE | | SLAB OR UNDER GROUND AND THE AMOUNT OF OTHER CONDUITS, | | PIPING, BEING INSTALLED IN THIS SAME AREA, IT IS OF | | CONCERN FOR THE SPACE REQUIREMENTS FOR BUNDLING OF | | CONDUITS, DE-RATING OF CONDUCTOR AMPACITIES. ETC. (THIS | | CAN BE A DETAIL LIKE A DUCT-BANK DETAIL) | | FBC 106.1.2, 310.16, 300.8, 300.10, 310.10, 310.15, | | 310.16, 300.17 ETC. | | THERE ARE MANY SECTIONS WHICH COULD BE REFERENCED. | | PLEASE ALSO SEE COMMENT WITH RESPECT TO WIRING METHODS | | OF EMERGENCY FEEDERS ETC. | | | | 48) NOTE: OK, HOWEVER SEE NEW NOTES DUE TOP HAND DRAWN | | CHANGES MADE TO PLANS. | | | | 49) NOTE: NO, PLEASE SEE THE RATING OF THIS ROOM IS | | STILL REQUIRED. THIS COMMENT WILL BE IN REVIEWS FROM | | MULTIPLE REVIEWERS AND AS THIS WILL CHANGE THE BACK | | GROUND OF WALL DETAIL PLEASE ADDRESS AT THIS TIME. | | | | ** PREVIOUS REVIEW NOTE** | | PLEASE KNOW AS NO INFORMATION FOR THE IT ROOM EQUIPMENT | | IS BEING SUBMITTED WITH THIS RECORD SET OF PLANS, | | PLEASE PLACE NOTE AND CLOUD ON 4TH FLOOR POWER PLANS | | THAT ALL ELECTRICAL EQUIPMENT, UPS, SERVER EQUIPMENT | | ETC IN THE IT ROOM SHALL BE UNDER A SEPARATE PERMIT, | | PLANS, AND FEES BASED ON THE EQUIPMENT BEING INSTALLED | | IN THIS ROOM. REVIEW FOR CODE COMPLIANCE FOR THIS ROOM | | CAN NOT BE COMPLETED AT THIS TIME. THE REQUIREMENTS FOR | | THE CONSTRUCTION OF THIS ROOM IS REQUIRED AT THIS TIME, | | INCLUDING THE MINIMUM 1HR RATING, THE FIRE DAMPERS ETC | | (IF APPLICABLE) AND THE SHUT DOWN OF AN AND ALL A/C | | EQUIPMENT. | | NEC 645, NFPA-75 | | | | 50) NOTE: OK. | | | | 51) NOTE: OK. | | | | 52) NOTE: OK. | | | | 53) NOTE:OK/NO, THIS NOTE WILL REMAIN AS IT IS THIS | | REVIEWERS UNDERSTANDING THAT THERE WILL BE COMMENTS | | FROM OTHER TRADES WHICH WILL SUBSTANTIALLY AFFECT | | BACKGROUNDS AND LAYOUTS OF SAID PLANS. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE COORDINATE ALL OVER-LAYS AND LAYOUTS FOR | | ELECTRICAL, MECHANICAL, PLUMBING, BUILDING AND ALL | | OTHER TRADE PLANS. PLEASE KNOW THE ELECTRICAL 100% | | PLANS DO NOT SHOW THE SAME ELECTRICAL ROOMS AND | | EQUIPMENT AS THE 100% MECHANICAL PLANS, PLUMBING OR | | BUILDING PLANS ALONG WITH OTHER SHEETS FROM OTHER | | TRADES. | | REVIEW OF ALL APPLICABLE ITEMS WILL STILL NEED TO BE | | DONE AS REQUIREMENTS FOR ELECTRICAL AND OTHER TRADES | | WILL MOST CONTAIN CLEAR CONFLICTS WHICH MAY OR MAY NOT | | BE PERMITTED. | | 110.26, 240.24 NEC. | | FBC 106.3.5.1.1 ADMIN SECTION FOR ALL TRADES FOR | | COMMERCIAL PLANS. | | | | 54) NOTE:NO, SAME NOTE. PLEASE SEE PLANS IN SEVERAL | | LOCATIONS 6-1.0,1-6.3,5-1.1 ETC INDICATE 800KW AND | | SUBMITTALS ARE 900KW. | | PLEASE ALSO SEE SHEET WHICH STILL INDICATES ONLY 5 | | GALLON SPILL CONTAINMENT. THIS MAY BE PART OF THE FIRE | | OR MECHANICAL REVIEW NOTES, IF NOT PLEASE SEE THIS | | NEEDS TO BE VERIFIED. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE CORRELATE THE PLANS WITH THE MANUFACTURE | | SPECS/CUT SHEETS FOR THE GENERATOR WHICH IS BEING | | SUBMITTED AS A LARGER UNIT IN THE SPEC BOOK AS SHOWN ON | | PLANS. THIS WILL AFFECT THE FUEL SUPPLY, AND THE FUEL | | LINE SUPPLY FOR THE PROPOSED NATURAL GAS LINE. 90.7, | | 110.3, | | FBC 106.1.2 | | | | 55) NOTE: OK. | | | | 56) NOTE: OK. | | | | 57) NOTE:OK/NO, PLEASE SEE PREVIOUS COMMENT WITH | | RESPECT TO HOW THIS WILL ACTUALLY BE DESIGNED AND | | INSTALLED. THIS COMMENT WILL REMAIN AT THIS TIME AS A | | REMINDER. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE SOME BATHROOMS CONTAIN OC SENSORS AND MANY | | DO NOT, PLEASE EXPLAIN AND PLEASE SEE OTHER COMMENTS | | FOR TYPE OF DEVICES WHICH WILL BE REQUIRED. | | 13-415.1.ABC.1.2 | | | | 58) NOTE: NO, PLEASE SEE MOST WERE DONE, HOWEVER PLEASE | | SEE 2-2.2, 2-3.1,2-4.2 AND ANY OTHER LARGER BATHROOMS | | OTHER THAN A SINGLE POINT OF USE OCCUPIED ROOM. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE KNOW SOME SORT OF BATTERY BACK UP FIXTURE WILL | | BE REQUIRED IN THE LARGER BATHROOMS (ROOM OTHER THAN | | SINGLE POINT OF USE). | | PLEASE SEE LS 101 7.8., 7.9 | | THIS WAS DISCUSSED WITH THE FIRE MARSHAL CHIEF AND WILL | | BE REQUIRED BOTH BY THIS OFFICE AND THE FIRE MARSHAL'S | | OFFICE IN THE INTEREST OF LIFE SAFETY AND CODE AS | | REFLECT. | | | | 59) NOTE: OK. | | | | 60) NOTE: OK. | | | | 61) NOTE: NO, PLEASE SEE RESPONSE MENTIONS MINIMUM | | LIGHTING REQUIRED FOR EGRESS, HOWEVER PLEASE KNOW THE | | AREA OF THE LOBBY AFTER HOURS WOULD REQUIRE OVER RIDE | | FOR NORMAL LIGHTING. ONLY WOULD THEY NEED THESE | | FIXTURES TO BE BATTERY BACK UP FOR AN EMERGENCY. THIS | | WAS DISCUSSED WITH THE DESIGNER, HOWEVER THE NUMBER OF | | FIXTURES EXCEED ANY REASONABLE AMOUNT PERMITTED TO BE | | LEFT ON FOR THE EXCEPTIONS AS PERMITTED. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE THERE ARE SOME LOCATIONS ON PLANS WHICH ARE | | SHOWING "NL'S" (NIGHT LIGHTS) BEING PART OF A PERMANENT | | ON SCENARIO; HOWEVER THE NUMBERS OF FIXTURES BEING | | PROPOSED TO REMAIN ON AS NIGHT LIGHTS ARE OVER WHAT IS | | BEING CONSIDERED AS NORMAL. PLEASE KNOW THIS CAN BE | | GONE OVER, HOWEVER PLEASE SEE SOME AREAS WHERE THERE | | ARE 10-20PLUS LIGHTS BEING LEFT ON. | | THE INTENT OF CHAPTER 13 AND ALSO THE INTEREST OF LIFE | | SAFETY SHOULD BE CONSIDERED. PLEASE CALL TO OVER. SEE | | SHEET E2-1.2 FOR EXAMPLE IN LOBBY AREA. | | | | 62) NOTE:NO/OK, PROJECT MANUALS ARE TO BE REVIEWED | | FOR ALL OF THESE ITEMS AND DOCUMENTATION WILL BE | | REQUIRED BEFORE FINAL. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE NFPA-20 11.3, 11.3.2, 11.3.2.3 AND FLORIDA | | FIRE PREVENTION CODE , NFPA-1 7-4FOR OTHER REQUIREMENTS | | FOR FIRE PUMPS AND ROOMS IN WHICH THEY ARE LOCATED. | | PLEASE ALSO SEE 11.4.6.2 FUEL PIPING SHALL NOT BE | | GALVANIZED STEEL OR COPPER. | | PLEASE KNOW AS PART OF THE COMPLETED TESTING AND | | ACCEPTANCE AS REQUIRED IN CHAPTER 14, DOCUMENTATION FOR | | TESTING FOR FIRE PUMP ON A WEEKLY BASIS IS REQUIRED TO | | THE OWNER OF RECORD.CODE TEXT FROM NFPA-20: 11.6.1.1 | | ENGINES SHALL BE STARTED NO LESS THAN ONCE A WEEK AND | | RUN FOR NO LESS THAN 30 MINUTES TO ATTAIN NORMAL | | RUNNING TEMPERATURE. | | | | 63) NOTE:NO, RESPONSE MENTIONS INFORMATION GIVEN TO | | ARCHITECT AND STRUCTURAL ENGINNER WHICH IS OK, HOWEVER | | COULD NOT LOCATE ANY INFORMATION OR DETAIL FOR THIS. | | THIS UNIT AND ITS SIZE IS BEING PLACED ON THE ROOF OF | | THE GARAGE AND IT IS OF THE UTMOST IMPORTANCE THAT THE | | INFORMATION IS PROVIDED A THIS TIME AS IT MAY AFFECT | | PLANS. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE NFPA-110 CHAPTER 7 FOR THE INSTALLATION OF | | THE GENERATOR. PLEASE SEE 7.4 AND 7.5, PROVIDE DETAIL | | FOR MOUNTING OF UNIT TO ALLEVIATE ANY INTEGRITY | | INTERFERENCE OF THE STRUCTURE. | | | | 64) NOTE: NO, PLEASE SEE THE SAME SPECS WHICH CONTAIN | | HAND WRITTEN INFORMATION WAS SUBMITTED BACK FOR REVIEW. | | PLEASE KNOW, THIS SYSTEM AS SUBMITTED IS NOT ACCEPTABLE | | TO THIS AHJ WITHOUT THE FAIL SAFE OPERATION TO | | COMPLETELY PREVENT INADVERTENT SIMULTANEOUS OPERATION. | | PLEASE KNOW THERE ARE NUMEROUS OF THE TYPES OF SYSTEMS | | ON THE MARKET WHICH WILL PERMIT BOTH SIDE BEING ON AT | | THE SAME TIME. PLEASE KNOW AS PER KNOWLEDGE OF THIS | | REVIEWER MR. MARK ODE FROM UL WAS IN DISCUSSION WITH | | SAID COMPANY TO START WITH THE PROCEEDINGS TO HAVE | | THEIR EQUIPMENT LISTED AS TRANSFER EQUIPMENT PER UL | | 1081. PLEASE KNOW AT THIS TIME, EITHER PROVIDE THE | | NEEDED INFORMATION OR CHANGE EQUIPMENT TO AN ACCEPT | | UNIT WHICH IS LISTED BY A NRTL. (NATIONALLY RECOGNIZED | | TESTING LABORATORY). | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SUBMIT THE SPEC/CUT SHEET FOR THE PROPOSED MTS. | | THE "KIRK KEY" AS SHOWN AND HAND WRITTEN ON SPECS IS | | NOT ACCEPTED AT THIS TIME. THERE ARE MANY OF THESE | | SYSTEMS ON THE MARKET WHICH WILL PERMIT THE POWER FROM | | TWO SOURCES AT ONCE WHICH IS STRICTLY PROHIBITED. | | PLEASE SEE 700.6, 701.7, 110.3, AND 90.7 CAN NOT VERIFY | | AT THIS TIME. PLEASE ALSO SEE THE FOLLOWING COMMENT. | | | | 65) NOTE: NO/OK, PLEASE SEE SPECS SUBMITTED INDICATE | | 4-POLE UNITS, HOWEVER EACH ATS ON RISER WHEN SUBMITTED | | FOR THE 90% REVIEW CONTAINED DESIGNATION NEXT TO EACH | | UNIT TO BE 4-POLE. PLEASE PLACE THIS MEANS OF | | IDENTIFICATION/DESIGNATION ON RISER AT THIS TIME TO | | AVOID ANY CONFUSION OF WHAT TYPE OF UNITS ARE TO BE | | INSTALLED. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE RISER AND PLANS WERE REVISED FROM THE 50% | | AND 90% PLANS CHANGING ALL ATS UNITS TO 3-POLE UNITS. | | PLEASE SEE ALTHOUGH GF PROTECTION IS NOT REQUIRED ON | | THE EMERGENCY SIDE OF THE EMERGENCY SYSTEM AND LEGALLY | | REQUIRED SYSTEMS, PROPER GROUND FAULT SENSING IS | | REQUIRED. PLEASE KNOW DOCUMENTATION FROM MORE THAN ONE | | MANUFACTURE WAS SENT TO THE ENGINEER PRIOR TO THE | | REVIEW WHEN THE PLANS WERE SUBMITTED ON THE 7TH OF NOV. | | PLEASE SEE NFPA-110 6.2.15** ISOLATION OF NEUTRAL | | CONDUCTORS. PROVISIONS SHALL BE INCLUDED FOR ENSURING | | CONTINUITY, TRANSFER, AND ISOLATION OF THE PRIMARY AND | | THE EPS NEUTRAL CONDUCTORS WHEREVER THEY ARE SEPARATELY | | GROUNDED TO ACHIEVE GROUND-FAULT SENSING. | | PLEASE SEE AN ATTACHED BRIEF EXPLANATION FROM"ASCO" | | WHITE PAPER: WHERE GROUND FAULT PROTECTION IS TRIGGERED | | BY THE CODE AND AN ALTERNATE POWER SUPPLY IS INCLUDED, | | SWITCHING OF THE NEUTRAL BECOMES NECESSARY. THE CIRCUIT | | SHOWN ABOVE ILLUSTRATES SUCH A CIRCUMSTANCE. THE | | SERVICE IS LARGER THAN 1,000 AMPS. CONSEQUENTLY, GROUND | | FAULT PROTECTION IS REQUIRED AT THE MAIN SERVICE | | DISCONNECT AT A MINIMUM. IF IT IS INSTALLED THERE AND | | THE GENERATOR NEUTRAL GROUNDING WAS THROUGH A SOLID | | CONNECTION TO THE MAIN SERVICE NEUTRAL, A GROUND FAULT | | WHEN THE GENERATOR IS FEEDING THE LOAD WILL CAUSE THE | | MAIN SERVICE DISCONNECT TO OPEN. THIS WILL NOT | | DISCONNECT THE ARCING FAULT FROM THE GENERATOR. | | COORDINATION IS THUS LOST." | | PLEASE KNOW BASED ON THE INFORMATION FROM SEVERAL | | MANUFACTURES AND THE CODE PLEASE ADJUST AS REQUIRED. | | PLEASE ALSO SEE GENERATOR GROUNDING DETAIL WILL BE | | REQUIRED TO BE REVISED. | | PLEASE SEE E5-1.1.18 WHICH NOTES A #3 CONDUCTOR, WHICH | | WOULD NOT BE LARGE ENOUGH. | | PLEASE SEE 250.20, 250.30, 250.66, 240.13, 230.95, | | 700.7D, 700.26 | | PLEASE SEE THE MTS. | | | | 66) NOTE: OK, HOWEVER PLEASE SEE SOME OF THESE ARE | | BEING SHOWN ATTACHED DIRECTLY TO CIRCUITS WHICH SEEMED | | TO BE CONTROLLED BY LIGHTING CONTROL SYSTEM OR DEVICES. | | THE NOTES ON PLANS MENTION TO BE SURE TO CONNECT AHEAD | | OF ANY CONTROL OR SWITCHING DEVICES HOWEVER PLEASE | | VERIFY THIS ON THE PLANS AT THIS TIME AS SHOWN. PLEASE | | SEE THERE ARE STILL SOME EXIT LIGHT FIXTURES ON PLANS | | WHICH STILL DO NOT SHOW ANY CONNECTION TO LOCAL | | CIRCUITS E2-3.2,E2-4.2 | | | | PLEASE SEE THERE ARE MANY EXIT/EMERGENCY LIGHTS WHICH | | DO NOT SHOW ANY CONNECTION TO ANY LOCAL CIRCUIT IN | | ANYWAY. PLANS NOTE THIS AND MANY ARE SHOWN THIS WAY, | | HOWEVER NOT ALL. PLEASE GO THROUGH PLANS. PLEASE SEE | | 700.12E WHICH REQUIRES THE BRANCH CIRCUIT FEEDING THE | | UNIT EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS THAT | | SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED | | AHEAD OF ANY LOCAL SWITCHES. | | | | 67) NOTE:NO, SAME NOTE. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE OVER ALL 3RD FLOOR PLANS, WHICH SEEM TO BE | | SHOWING LIGHTING OF SOME KIND ON GARAGE PLANS? PLEASE | | ALSO SEE E2-4.0 | | FBC 106.1.2 ADMIN SECTION. | | | | 68) NOTE: NO, PLEASE SEE THE LOCATION AS SHOWN WOULD | | NOT BE AN ACCEPTABLE LOCATION. PLEASE THE RUNNING OF | | CABLES IN THE EGRESS PATH IS NOT PERMITTED IN FRONT OF | | DOOR WAYS AND ANY OTHER EGRESS PATHS. PERHAPS CONDUITS | | TO A J-BOX OF SOME TYPE TO THE OUTSIDE WALL ON THE | | NORTH SIDE OF BUILDING. PLEASE KNOW TRIPPING HAZARDS | | UNDER THE REQUIREMENTS IN THE CODE FOR TEMPORARY | | INSTALLATIONS IS STILL NOT PERMITTED. PLEASE SECTIONS | | AS PREVIOUSLY GIVEN. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE NOTE #2 ON RISER WITH RESPECT TO THE MTS | | WHICH IS TO PROVIDE FUTURE PROVISIONS FOR POSSIBLE | | PORTABLE GENERATOR TO RUN THE EMERGENCY SYSTEMS, PLEASE | | KNOW A DETAIL TO A LOCATION AND HOW THIS CONNECTION | | WILL BE MADE IS REQUIRED.THE RUNNING OF CORDS, | | CONDUCTORS ETC SHALL BE PERMITTED TO TRAVEL THROUGH THE | | ELECTRICAL ROOM DOORS, ON SIDEWALK AREAS OR ANY | | LOCATIONS PROVIDING A TRIPPING HAZARD OR NOT SECURING | | LIVE PARTS ETC. | | PLEASE PROVIDE A DETAIL AS THIS CONNECTION POINT WILL | | BE SUBSTANTIAL IN NATURE. (J-BOX) ETC ON THE OUTSIDE OF | | BUILDING ETC. | | 110.26, 110.27, NEC 527. | | | | 69) NOTE: OK. | | | | 70) NOTE: OK. | | | | 71) NOTE: OK, PLEASE KNOW ALL LOW VOLTAGE WILL NOT BE | | INCLUDED IN THIS PERMIT. NOTE WILL REMAIN ONLY AS | | INFORMATION AS TO WHAT WILL BE REQUIRED. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE KNOW IF IT IS THE INTENT TO UTILIZE THESE PLANS | | FOR FUTURE LOW VOLTAGE WORK FOR LOCATIONS OF PHONE, | | DATE DROP ETC, PLEASE COMPLETE PLANS AS SUBMITTED | | SHOWING ALL LOCATIONS FOR DROPS.PLEASE SEE MANY AREAS | | WHICH LOW VOLTAGE DATE/PHONE DROPS WILL BE REQUIRED OR | | INSTALLED, HOWEVER THESE LOCATIONS ARE NOT BEING SHOWN | | AT THIS TIME. | | IF THE LV SCOPE IS PART OF THE PERMITTED PLANS AS | | SUBMITTED PLEASE REMOVE AND NOTE AS UNDER SEPARATE | | PERMIT PLANS AND FEES. | | | | 72) NOTE: OK. | | | | 73) NOTE:OK/NO, PLEASE SEE PREVIOUS NOTE #47, WHERE | | THE DETAIL FOR THE FEEDERS IN GARAGE WAS NOT PROVIDED. | | THE DETAIL FOR UNDERGROUND IS OK. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE 700.9D FOR THE FEEDERS FROM THE GENERATOR TO | | THE EMSB1 AND THE FEEDERS OUT TO SYSTEMS WHICH MAY BE | | CONSIDERED INSIDE THE BUILDING. PLEASE SEE THE CODE AS | | THERE ARE WAYS TO MEET THE INSTALLATION OF THESE | | FEEDERS, HOWEVER PLANS SHALL INDICATE WHICH WILL BE | | USED. (TYPE OF CABLE, ENCASED IN 2INCHES OF CONCRETE, | | FULLY SPRINKLED ETC) | | PLEASE KNOW AS THE REQUIREMENT OF FULLY SPRINKLED IS | | OFTEN MISTAKEN AS A BUILDING CONTAINING SPRINKLERS. | | THIS IS NOT THE CASE. PLEASE SEE THE INTENT OF 700.9D | | FOR THIS HAS ALWAYS BEEN THAT ALL AREAS CONTAINING | | THESE FEEDERS BE SPRINKLED IF INSTALLED IN OPEN OR | | ABOVE CEILINGS. PLEASE KNOW A COMMENTARY IN THE 2005 | | NEC MAKES IS CLEAR WHAT THE INTENT OF THE CODE AND THE | | FURTHER EXPLANATION IS PROVIDED. | | | | 74) NOTE: OK. | | | | 75) NOTE: OK.. | | | | 76) NOTE: NO, COULD NOT LOCATE. RESPONSE MENTIONS TO | | SEE SHEETS; HOWEVER THIS WAS REQUESTED FOR RISER TO | | SHOW THIS. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE PROVIDE THE SIZE OF THE CONDUCTOR ON THE | | GROUNDING ELECTRODE RISER AS PROVIDED. PLEASE SEE THE | | GROUNDING ELECTRODE DETAIL SHOWS A 4/0'S, HOWEVER | | PLEASE SEE E5-2.0. | | 250.50, 250.58 | | | | 77) NOTE: NO, PLEASE SEE RESPONSE MENTIONS ALL | | TERMINATE IN OCP. YES, THIS IS TRUE, HOWEVER AS STATED | | IN PREVIOUS REVIEW PER 240.21C THE OCP SHALL LIMIT THE | | LOAD ON CONDUCTORS. | | PLEASE SEE E5-1.0 WHICH SHOWS A 45KVA TRANSFORMER, WHEN | | E6-1.0 SHOWS 1/0'S FOR THE TYPICAL 45 KVA TRANSFORMER | | ON THE SECONDARY SIDE, THIS WOULD MEAN THE OCP WOULD BE | | LIMITED TO 150A?S. PLEASE SEE 6-1.0 FOR 1LD2 WHICH | | INDICATES 225A OCP AS THE SECONDARY MCB. PLEASE SEE | | 6-7.0 1HD WHICH SHOWS 1/0'S ON THE SECONDARY SIDE OF | | THE FEEDERS. | | PLEASE ADJUST. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE THE SIZE OF THE CONDUCTORS ON THE SECONDARY | | SIDE OF ANY TRANSFORMER SHALL BE SIZED AND TERMINATE IN | | OVER-CURRENT PROTECTION WHICH LIMITS THE LOAD ON THE | | CONDUCTORS. PLEASE SEE 240.21C, 310.16. PLEASE SEE | | 1LD2 | | | | 78) NOTE: OK. | | | | 79) NOTE: NO, PLEASE CLARIFY WHERE CONTINUOUS LOADS AND | | LARGEST MOTOR LOADS ARE SHOWN AT 125%. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SUBMIT LOAD CALCULATIONS. PLEASE INDICATE AND | | SHOW ALL CONTINUOUS LOADS AND LARGEST MOTOR LOADS AT | | 125%. | | 220.3, 220.10, 220.11, 220.13, 215.3,230.42 ETC | | | | 80) NOTE: OK. | | | | 81) NOTE:NO, PLEASE KNOW BASED ON THE PREVIOUS NOTES | | ABOVE WITH RESPECT TO PHOTO-METRICS, THIS COMMENT WILL | | REMAIN DUE TO POSSIBLE CHANGES IN PLANS. | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE PREVIOUS NOTES WITH RESPECT TO MINIMUM FOOT | | CANDLES REQUIRED. PLEASE SEE GARAGE SHALL CONTAIN | | EGRESS PATHS WHICH MEET THIS MINIMUM. BASED ON SOME | | AREAS SHOWN ON PHOTO-METRICS, IT DOES NOT APPEAR THIS | | IS MET. | | PLEASE SEE LIFE SAFETY CODE NFPA-101 2003 7.8.1.3, | | 7.9.2.2 | | | | 82) NOTE: OK. | | | | 83) NOTE:NO/OK, PLEASE SEE MOST WERE DONE, HOWEVER | | PLEASE SEE ROOM A1.507 WHICH SHOWS 75K ON RISER AND 45K | | ON ROOM PLANS. | | | | ** PREVIOUS REVIEW NOTE** | | PLEASE CORRELATE THE TRANSFORMERS ON THE ELECTRICAL | | ROOM LAYOUTS AND THE ELECTRICAL RISER. PLEASE SEE THERE | | ARE MANY WHICH ARE SHOWN AS 15KVA ON ONE SHEET AND | | 45KVA ON OTHER SHEETS OR 45KVA ON ONE AND 75KAV ON | | ANOTHER. PLEASE ALSO SEE RISER. | | PLEASE SEE SOME BELOW AS NOTED, THIS IS ONLY SOME AND | | IS IN NO WAY ALL POSSIBLE. | | 1HB, 75KVA ON RISER, 45KVA IN ELECTRICAL ROOM. 2HB, | | 75KVA ON RISER, 45KAV IN ELECTRICAL ROOM. 1GLA-1GHA, | | 45K ON RISER, 15K ON ELECTRICAL ROOM PLANS. ETC | | | | 84) NOTE: OK, | | | | 85) NOTE: NO, PLEASE SEE NOTE NOTES COULD BE LOCATED ON | | FA SHEETS, IN FACT SHEETS STILL ONLY NOTE NFPA72 FOR | | LEVELS. | | PLEASE ADJUST ALL SHEETS AND NOTES ACCORDINGLY AS | | PREVIOUSLY REQUESTED. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE FBC 2004 CHAPTER 11 FOR REQUIREMENTS FOR ADA | | WITH RESPECT TO HORNS, AND STROBES. THE AUDIBLE LEVELS | | SHALL BE PER BOTH FBC CHAPTER 11 AND NFPA-72 AS NOTED, | | HOWEVER THE MORE STRINGENT SHALL APPLY. | | PLEASE SEE 11-4.28.1, 11-4.28.2 AND 11-4.28.3(4). | | PLEASE BE SURE THE LEVELS ARE INDICATED ON PLANS. | | PLEASE KNOW THE LIGHTING CANDELA LEVELS AS REQUIRED IN | | THE FBC ARE FAR GREATER THAN THAT OF NFPA-72. THE | | MINIMUM LEVELS FOR VISUAL SHALL BE 75 CANDELAS. PLEASE | | ADJUST AND PLACE REQUIREMENTS ON PLANS. PLEASE SEE ALL | | FA SHEETS WHICH ONLY INDICATE NFPA-72. | | | | | | 86) NOTE:OK, PLEASE DO THE SAME. NOTE WILL REMAIN. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE KNOW A RESPONSE LETTER/NOTES WERE PROVIDED, | | HOWEVER AS THIS REVIEW WAS MORE OF A REVIEW FOR CODE | | COMPLIANCE, A MORE DETAILED RESPONSE WOULD GREATLY HELP | | IN THE REVIEW PROCESS. THIS RESPONSE COULD INDICATE THE | | SHEETS/LOCATIONS OF CHANGES, CORRECTIONS OR ANY | | COMMENTS RELATED TO AND RESPECT TO THIS REVIEWERS | | NOTES. | | | | ********** NEW NOTES FOR THIS REVIEW************ | | | | 87) NOTE: PLEASE SEE FLORIDA STATUTES WITH RESPECT TO | | THE ENGINEER OF RECORD SIGNING AND SEALING DOCUMENTS IN | | 471.025. PLEASE SEE SHEETS SIGNED OTHER THAN MR. MINDUR | | CONTAINS WHAT APPEARS TO BE MORE THAN ONE SIGNATURE FOR | | THE SAME ENGINEER. PLEASE KNOW AS STATED BY THE | | PLUMBING REVIEWER FOR PLUMBING SHEETS, THE SAME APPLIES | | TO FS SHEETS AND OTHER DOCUMENTS SIGNED AND SEALED. | | PLEASE KNOW UNTIL LEGAL SIGNATURE VERIFICATION CAN BE | | DONE, THE ENERGY CALCULATIONS WHICH ARE SIGNED AND | | SEALED ALSO BY OTHER THAN MR. MINDUR CAN NOT BE | | ACCEPTED AT THIS TIME. | | FAC 61G15-23.002 | | PLEASE BE SURE LETTER FOR LEGAL SIGNATURE VERIFICATION | | FOR MR. WU IS CORRECTLY NOTARIZED PER FLORIDA STATUTES | | 117.05. | | | | 88) NOTE: PLEASE KNOW AS COMMENTS FROM ELECTRICAL | | ENGINEER MENTIONED TO SEE S SHEETS FOR INFORMATION, | | UPON REVIEW OF SAID SHEETS THIS REVIEW NOTICE MANY | | SHEETS WHICH WERE DATED IN DECEMBER NOT CONTAINING ANY | | TITLE BLOCKS FOR THE ENGINEERING FIRM OF RECORD. PLEASE | | SEE SOME SHEETS WHICH WERE DATED FROM OCTOBER WHICH DO | | CONTAIN THE TITLE BLOCKS FOR FIRM DO NOT CONTAIN THE | | CERTIFICATE OF AUTHORIZATION NUMBER AS REQUIRED UNDER | | FS 471.023 AND FAC 61G15-23.002. THIS IS REQUIRED FOR S | | SHEETS WHETHEROR NOT COMMENT IS MADE BY ANY OTHER | | TRADE. | | | | 89) NOTE: PLEASE SEE ENERGY CALCULATIONS WHICH ARE NOW | | SUBMITTED ONLY INDICATE 3 FIXTURES FOR EXTERIOR | | LIGHTING? HOW IS THIS POSSIBLE? PLEASE CORRELATE WITH | | PLANS AND FIXTURES AS SHOWN ON PLANS. | | PLEASE ALSO CORRELATE WITH THE WATTAGES AS SHOWN ON | | LIGHTING POWER DENSITIES AND PLANS. | | PLEASE CLARIFY ZONES IN ENERGY CALCULATIONS AS SHOWN. | | PLEASE SEE FBC 13-415.1.AB.1, 13-415.2 | | | | 90) NOTE: PLEASE SEE NOTES ON LIGHTING SEQUENCE OF | | OPERATION SHEETS. PLEASE SEE NOTE #11 ON E5-3.0 WHICH | | MENTIONS PHOTO-CELL FOR CONTROL OF ROOMS? PLEASE SEE | | THE SAME ROOMS AND NOTE #3 ON 5-3.1 WHICH MENTIONS | | DIFFERENT CONTROLS. | | | | 91) NOTE: PLEASE SEE WATER COOLERS LOCATIONS OF | | RECEPTACLES. PLEASE SEE MANY INDICATE THE RECEPT TO BE | | LOCATED AT THE CEILING LEVEL AND MANY INDICATE AT WC | | LEVEL. PLEASE EXPLAIN THE INDICATION FOR DEVICE AT | | CEILING. PLEASE ALSO SEE AREAS WHERE MORE THAN TWO | | WATER COOLERS ARE BEING SHOWN HOWEVER ONLY ONE DUPLEX | | RECEPT IS BEING SHOWN. PLEASE ADJUST TO QUAD AND PLEASE | | VERIFY LOAD ON THESE UNITS WHICH ARE NOT TO EXCEED | | RATING OF DEVICE AND CIRCUIT. THIS WAS NOT COMMENTED ON | | THE PREVIOUS REVIEW. | | 240.4, 310.16, 210.25, 2210.21B2 ETC. | | | | 92) NOTE: PLEASE PLACE NOTE ON E0-2.1 FOR SECTIONS OF | | 314PART IV , SECTIONS 314.50-314.59 TO BE MET. | | NOT ON PREVIOUS REVIEW. | | | | 93) NOTE: PLEASE SEE UPON REVIEW OF PROJECT MANUAL, | | PLEASE SEE COLOR CODING SHALL BE BROWN, PURPLE, YELLOW | | FOR 277/480V SYSTEMS. PLEASE SEE THE CODE DOES NOT | | PROVIDE COLOR CODING FOR MOST SYSTEMS, HOWEVER ORANGE | | AS BEING NOTED FOR THIS IS FOR A HIGH-LEG SYSTEM WHICH | | IS NOT WHAT IS BEING INSTALLED. PLEASE KNOW AS PER | | LOCAL AMENDMENTS FOR 3 DECADES OR SO UNDER THE 2004 FBC | | THE CITY OF WEST PALM BEACH ALONG WITH PALM BEACH | | COUNTY HAD THIS COLOR SCENARIO FOR 277/480V SYSTEMS AND | | WILL BE REQUIRED TO REMAIN THE SAME FOR ALL OTHER | | BUILDING BEING PROPOSED. PLEASE PLACE A NOTE ON RISER | | FOR COLOR CODING. | | 90.4., FBC ADMIN SECTION 104.6 | | | | 94) NOTE:PLEASE SEE BUILDING REVIEW NOTES AND | | CLARIFY THE TWO PULL BOXES BEING SHOWN ON E0-2.1 WHICH | | SEEM TO BE DIRECTLY LOCATED IN THE WALL OR FOOTER. | | PLEASE CLARIFY THESE AT THE LOCATIONS AS SHOWN AND | | PLEASE ADJUST PLANS AS NEEDED. PLEASE SEE CODE FOR | | ACCESSIBILITY. | | 110.26 | | | | 95) NOTE: PLEASE CLARIFY THE FUEL TANK ROOM AS BEING | | SHOWN ON THE GARAGE PLANS NEXT TO THE FIRE PUMP ROOM. | | PLEASE KNOW IT WAS BEING ASSUMED THIS WAS THE LOCATION | | OF THE TANK FOR THE FIRE PUMP; HOWEVER IT HAS COME TO | | OUR ATTENTION THAT THIS IS NOT THE CASE. PLEASE PROVIDE | | INFORMATION FOR THIS FOR MECHANICAL AND FIRE REVIEW AS | | WELL AS ELECTRICAL REVIEW. PLEASE SEE NEC 500. SPECIFIC | | SECTIONS CAN NOT BE GIVEN AT THIS TIME, AS THE USE AND | | RATING OF ROOM ETC IS NOT KNOWN AT THIS TIME. | | FBC ADMIN SECTION 106.1.2 (MORE INFORMATION). NFPA-70, | | 72, 30? ETC. | | | | 96) NOTE: PLEASE SEE ELEVATOR EQUIPMENT ROOM | | DISCONNECTS ARE BEING SHOWN WITH 3-WAY SWITCH NOTATIONS | | INSTEAD OF DISCONNECTS OR MOTOR RATED SYMBOL. | | NOT ON PREVIOUS REVIEW. | | PLEASE ADJUST. 620.51, 620.61, 620.62 ETC | | FBC 106.1.2, | | | | 97) NOTE: PLEASE SEE ANY HAND DRAWN CHANGES WHICH MAY | | HAVE BEEN DONE BY THE ENGINEER AFTER PLANS WERE SIGNED, | | DATED AND SEALED, SHOULD BE REVISED AT THIS TIME. ONLY | | THE ENGINEER OF RECORD MAY MAKE CHANGES TO SAID PLANS | | WHICH ARE SIGNED AND SEALED. FS 471.025 PLEASE KNOW AS | | PLANS ARE SEALED, MANY OF THE SEALS ARE NOT CLEAR AND | | VISIBLE WITH INFORMATION ON SAID SEAL. PLEASE BE SURE | | PLANS ARE SEALED TO SEE INFORMATION. FS 471.025 | | | | | | IF ANY OF THESE COMMENTS ARE NOT CLEAR IN ANY FASHION | | OR IF ANY ITEMS ARE NOT UNDERSTOOD IN ANY WAY?PLEASE | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | | ** PLEASE KNOW AS THERE IS SOME INFORMATION NOT YET | | SUBMITTED PLEASE BE SURE TO GO OVER ALL. | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. ONCE AGAIN IF THERE | | ARE ANY QUESTIONS , PLEASE DO NOT HESITATE IN | | CONTACTING THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] | 2006-12-25 08:06:40 | 2006-12-25 08:06:40 | | IN PROGRESS | 2006-12-24 20:14:29 | 2006-12-24 20:14:29 | | REVIEW STOPPED. TO CONTINUE ON 12/25 | 2006-12-24 18:11:34 | 2006-12-24 18:11:34 | | ONE ROLL OF MEP'S IN ELECTRIC FOR REVIEW ALONG WITH ONE | | COPY OF RESPONSE LETTERS AND ONE COPY OF SUBMITTIALS | | FOR REVIEW. | | REVIEW IN PROGRESS. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2006-11-25 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-11-25 |
Time |
20:34 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-11-07 |
Time |
10:21 |
Sent To |
|
|
Notes |
2006-11-25 20:22:32 | **** CITY CENTER ******* | | | | | | REVIEW OF 100% ELECTRICAL PLANS SUBMITTED ON NOVEMBER | | 7TH, 2006. | | | | PLEASE SEE THE FOLLOWING COMMENTS ARE BASED ON THESE | | PLANS AS NOTED ABOVE AND NOT THE 100% PLANS SUBMITTED | | ON OCTOBER 17TH, 2006. | | | | 1) NOTE: PLEASE KNOW WHEN SUBMITTING FOR FINAL | | PERMITTING AND STAMPING, A THIRD SET OF SIGNED, DATED | | AND SEALED PLANS WILL BE REQUIRED. | | PLEASE SEE FBC ADMINISTRATIVE SECTION AS ADOPTED BY THE | | CITY OF WEST PALM BEACH, 106.1.2106.1.3, 109.3.6 FOR | | THRESHOLD BUILDINGS. THIS IS WILL BE REQUIRED FOR ALL | | DOCUMENTATION AND PLANS AND FOR ALL TRADES WHETHER OR | | NOT COMMENT IS MADE BY OTHER TRADES. | | | | 2) NOTE: PLEASE SEE FBC CHAPTER 13. PLEASE SEE | | 13-415.1.ABC.1.1, .1.2 AND .1.3. | | PLEASE BE SURE ALL DEVICE ON PLANS CORRELATE WITH THE | | DEVICE SYMBOL LEGEND. | | PLEASE BE SURE MAX TIME OF OVER -RIDES ARE SHOWN. IF | | TIMER TYPE, (4HRS MAX), IF OCCUPANCY SENSOR TYPE (30 | | MINS MAX). | | PLEASE SEE ADDITIONAL COMMENTS FOR CONTROLS AND SYSTEM | | BEING PROPOSED. | | | | 3) NOTE: PLEASE PLACE A NOTE ON PLANS FOR ALL "TASK" | | LIGHTING WHICH MAY NOT BE SHOWN ON PLANS AT THIS TIME. | | 13-415.1.ABC.1.3 | | | | 4) NOTE: PLEASE SUBMIT COMPLETED ENERGY CALCULATIONS | | FOR THE ENTIRE BUILDING FOR REVIEW OF ALL TRADES. | | PLEASE KNOW AS NONE WERE SUBMITTED AT THIS TIME THERE | | ARE MANY ITEMS WHICH CAN NOT BE VERIFIED WITH THE | | PLANS, EQUIPMENT AND LIGHTING. | | PLEASE SEE 13-415.1.AB.1. | | | | 5) NOTE: PLEASE SEE 13-415.2, 13-415.2ABC.1 FOR MINIMUM | | AND MAXIMUM PERFORMANCE CALCULATIONS. PLEASE SEE THE | | CALCULATIONS SUBMITTED SHOWING THE LIGHTING POWER | | DENSITIES (LPD) ARE NOT COMPLETE AND/OR THERE ARE ITEMS | | WHICH DO NOT CORRELATE WITH SAID PLANS. | | PLEASE SEE THERE ARE MANY ROOMS INDICATED ON PLANS | | WHICH COULD NOT BE LOCATED IN CALCULATIONS OR THERE ARE | | ROOMS ON CALCULATIONS WHICH COULD NOT BE LOCATED ON | | PLANS. | | PLEASE CORRELATE AND PLEASE SEE SOME OF THE LPD'S SEEM | | TO BE VERY HIGH FOR SOME OF THE ROOMS AND AREAS AS | | NOTED AND SHOWN. | | PLEASE SEE OFFICE IN PARKING GARAGE FOR INSTANCE. | | PLEASE SEE SOME OTHERS WHICH BASED ON THE TABLES AS | | SET-FORTH IN THE CODE MAY ALLOW 1.7, THE CALCULATIONS | | MAY SHOW 10.5 ETC. | | PLEASE REVIEW ALL AND RE-ADJUST AS REQUIRED AND | | NEEDED. | | | | 6) NOTE: PLEASE SEE 13-415.2.ABC.1.3 FOR ALL EXTERIOR | | LIGHTING ALLOWANCES, INCLUDING THAT WHICH IS | | DECORATIVE. PLEASE SEE THERE ARE EXCEPTIONS FOR SOME | | AREAS; HOWEVER THESE AREAS AS LISTED WOULD BE REQUIRED | | BY SECTIONS AS LISTED. PLEASE SEE 13-415.0(3) | | (EXCEPTS). | | | | 7) NOTE: PLEASE SEE PLANS SHALL INDICATE THE ACTUAL | | PANEL BEING USED FOR LIGHTING CONTROLS. PLEASE SEE | | THERE ARE SEVERAL PANELS INDICATE IN THE MANUFACTURE | | SPECS/CUT SHEETS SUBMITTED AND THE ACTUAL UNIT NEEDS TO | | BE HIGH-LIGHTED IN SPECS. PLANS SHALL ALSO BE REQUIRED | | TO PROVIDE THE TECHNICAL INFORMATION AT EACH LIGHTING | | CONTROL PANEL. (LCP) | | ** PLEASE KNOW AS REFERENCE TO LIGHTING CONTROL PANELS | | IN NOTES HERE ON WILL BE DESIGNATED AS "LCP'S". PLEASE | | SEE RISER INDICATES LCP'S AS 225A RATED, WHICH IS OK, | | HOWEVER PLEASE BE SURE THE INFORMATION AS SHOWN ON | | CUT/SPEC SHEETS IS BROUGHT OVER TO THE PLANS AND LISTED | | ON EACH LCP. | | | | 8) NOTE: PLEASE KNOW THERE IS CONCERN OVER THE TYPE OF | | SYSTEM BEING PROPOSED AND CONTROLS OF SAID SYSTEM. | | PLANS CALL FOR A "SWEEP" EACH HOUR FOR THE SYSTEM OUT | | OF NORMAL BUSINESS HOURS AND THIS WILL TURN OFF ANY AND | | ALL DEVICES. THE DEVICES WILL THEN HAVE THE ABILITY TO | | OVER RIDE THE SYSTEM IN ANY PARTICULAR AREA WHICH THE | | CIRCUIT/SWITCH IS DESIGNATED TO. PLEASE KNOW THIS | | BUILDING IN SEVERAL SECTIONS WILL BE OCCUPIED OUT OF | | THE NORMAL BUSINESS HOURS WHICH ARE SET UP AND WILL | | CAUSE DARKNESS EACH HOUR EVEN WHEN OCCUPIED. PLEASE SEE | | SPECS SHEETS AS SUBMITTED SPEAK OF THE INCLUSION OF AN | | OCCUPANT SENSOR TYPE DEVICE TO ALLEVIATE THIS. | | (UNINTENDED BLACK-OUTS). PLEASE SEE AREAS LIKE THE | | LIBRARY, COMMISSIONS CHAMBERS, OFFICE DESIGNATED FOR | | POLICE, AND OTHER AREAS. | | PLEASE SEE THE CODE ON THE OTHER HAND FOR ALL AREAS | | WHICH DURING NORMAL BUSINESS HOURS WHICH WILL REQUIRE | | ROOMS TO BE OFF. PLEASE SEE 13-415.1.ABC.1.2, FOR ALL | | ROOMS CONTAINING FLOOR TO CEILING HEIGHT PARTITIONS | | WHICH WILL REQUIRED SEPARATE CONTROL. PLEASE SEE AS | | SHOWN ON PLANS, THESE ROOMS WILL COME "ON" AT THE SET | | BUSINESS HOUR TIMES AND WILL REMAIN ON UNTIL AFTER THE | | "ONE HOUR SWEEP" AFTER THE NORMAL OPERATIONAL TIMES | | HAVE PASSED. | | PLEASE SEE CLOSETS, OFFICES, STORAGE AREAS ETC. THERE | | ARE FAR TOO NUMEROUS ROOMS TO LIST. | | PLEASE SEE THERE ARE MANY ROOMS ON PLANS WHICH DO | | INDICATE "OC" TYPE DEVICES; HOWEVER THERE IS NOT DETAIL | | ON THE LIGHTING CONTROL RISER HOW THESE WILL BE | | CONNECTED OR TIED IN. | | PLEASE SEE BATHROOMS ETC. | | PLEASE KNOW THIS TYPE OF DEVICE WILL WORK IN MANY AREAS | | IN THIS BUILDING; HOWEVER THERE ARE AREAS WHICH WILL | | NOT MEET CODE OR THE INTENT IN SEPARATE SPACES. PLEASE | | KNOW AT THIS TIME, AS SHOWN THERE ARE SEVERAL ITEMS | | WHICH WILL BE REQUIRED TO BE ADJUSTED. PLEASE ALSO | | OBTAIN A LETTER FROM THE "SENTRY SWITCH" MANUFACTURE | | WHICH PERMITS THIS TYPE OF DEVICE TO BE USED WITH THE | | LUTRON GRAFIK PANEL. | | 110.3, 90.7 NEC. | | | | 9) NOTE: PLEASE SEE THERE ARE SEVERAL ROOM NUMERICAL | | DESIGNATIONS ON CALCULATIONS WHICH COULD NOT BE LOCATED | | ON PLANS. PLEASE SEE GARAGE PLANS. | | PLEASE SEE SOME WHERE THE ROOM DESIGNATION IS THERE | | HOWEVER IT SEEMS TO BE VERY LIGHT IN COLOR AND CAN NOT | | BE EASILY READ. PLEASE SEE OTHER AREAS WHICH THE | | FIXTURE DESIGNATION COVERS THE ROOM IDENTIFICATION OR | | VICE VERSA, THE FIXTURE TYPE COULD NOT BE SEEN DUE TO | | THE OVER LAY OF THE NUMERICAL DESIGNATION. | | PLEASE COORDINATE. A1-116-2-1.610 ETC | | FBC ADMIN SECTION 106.1.2, 106.1.3 | | | | 10) NOTE: PLEASE BE SURE ALL INFORMATION IS PROVIDED ON | | ALL FIXTURES AS SHOWN ON PLANS ON THE FIXTURE LEGEND. | | PLEASE KNOW THAT THE WATTAGE, TYPE ETC SHALL BE | | SPECIFIED AT THIS TIME. THESE CAN ALWAYS BE REVISED AT | | A LATER DATE. | | FBC 106.1.2,NEC 110.3, ETC | | | | 11) NOTE: PLEASE SEE THAT BATTERY BACK UP FIXTURES OF | | SOME TYPE WILL BE REQUIRED FOR THE FOLLOWING LOCATIONS. | | SOME ARE SHOWN ALREADY, HOWEVER NOT ALL. THE MAIN | | ELECTRICAL ROOM, THE FIRE COMMAND CENTER, BOTH FIRE | | PUMP ROOMS, ELEVATOR EQUIPMENT ROOM, AND AT THE | | LOCATION OF THE ROOF TOP GENERATOR WILL ALL REQUIRE | | THIS. PLEASE SEE THAT ALL STAIR TOWERS AND EGRESS PATHS | | SHALL ALSO INCLUDE SOME SORT OF BATTERY BACK UP | | FIXTURE. THERE ARE MANY LOCATIONS WHICH INCLUDE THIS; | | HOWEVER AS SOME OF THE FIXTURE INFORMATION IS NOT CLEAR | | AT THIS TIME THIS CAN NOT BE VERIFIED. THIS BUILDING IS | | EXPECTED TO BE OCCUPIED IN THE TIME OF POWER OUTAGES | | AND IN THE EVENT OF THE TRIPPING OF A SINGLE MEANS OF | | OVER CURRENT PROTECTION (EMSB1) OR GEN MAIN, THIS WILL | | PLACE MANY AREAS IN COMPLETE DARKNESS WHICH IS NOT | | PERMITTED. NEC 700.12E, 700.16, LS 101 7.9. | | | | 12) NOTE: PLEASE SEE LIGHTING CONTROL RISER WHICH | | INDICATES ALL LCP'S BEING FED FROM THE SAME PANEL? | | 1HA/LCP1A PLEASE ADJUST. | | | | 13) NOTE: PLEASE CORRELATE ALL LCP'S WITH THE HOUSE | | PANELS AND THE CIRCUITS FROM THE HOUSE PANELS WHICH | | FEED THESE LCP'S AND CIRCUITS. PLEASE SEE NUMEROUS | | CIRCUITS WHICH CONTAIN THE DESIGNATION OF "LC" NEXT TO | | THE CIRCUIT HOWEVER MANY WHICH DO GO THROUGH THE PANEL | | DO NOT? PLEASE COORDINATE. | | FBC106.1.2 ADMIN SECT. | | | | 14) NOTE: PLEASE SEE FIXTURE "E", PLEASE SEE IT APPEARS | | TO BE BATTERY BACK UP, BUT NOT ENOUGH INFORMATION IS | | PROVIDED. PLEASE SEE FIXTURES, Z,ETC. | | | | 15) NOTE: PLEASE SEE CIRCUITING FOR ATM ROOM/AREA AND | | THE CIRCUITING FOR THE FIRE COMMAND CENTER. PLEASE SEE | | PANEL SCHEDULE FOR 1LB2, 29 AND 31, ETC. PLEASE PROVIDE | | THE CORRECTED IDENTIFICATION FOR THE CIRCUITS AND | | DESIGNATIONS. | | FBC 106.1.2 ADMIN SECT. | | | | 16) NOTE: PLEASE PROVIDE ALL MINIMUM WIND LOADING FOR | | SITE LIGHTING LIGHT POLES, AND THAT OF THE POLES ON | | GARAGE ROOF STRUCTURE. PLEASE KNOW A DETAIL ON HOW | | THESE WILL BE ATTACHED ON PARKING DECK OF THE GARAGE | | AND POLE DETAIL FOR GROUND MOUNTED/BURIED POLES WILL BE | | REQUIRED. PLEASE KNOW ALL SHOW MEET THE FBC 140MPH | | (3SEC GUST) 120MPH SUSTAINED. | | THE STRUCTURAL CALCULATIONS WILL BE REVIEWED BY THE | | BUILDING PLAN REVIEWER. | | FBC 106.1.2 ADMIN SECT. | | | | 17) NOTE: PLEASE CLARIFY THE LOAD FOR THE LIGHTING IN | | THE COURTYARD AREA FOR FIXTURES SA1. PLEASE SEE 1GHEA | | INDICATES A LOAD OF 7500VA, YET THE 10 FIXTURES AT 400 | | EACH DO NOT CORRELATE TO THIS. PLEASE CLARIFY IN | | RESPONSE OF THE TOTAL LOAD IS BE FIGURED BASED ON THE | | INVERTER AT 7500/ | | FBC 106.1.2 | | | | 18) NOTE: PLEASE SEE OTHER SITE LIGHTING FIXTURES SB, | | WHICH IS 24 FIXTURES AT 70W'S EACH, YET THE LOAD ON THE | | PANEL SCHEDULE IS ACTUALLY HIGHER THAN THIS? PLEASE SEE | | 1GHA-18. | | | | 19) NOTE: PLEASE PROVIDE THE VOLTAGE DROP ON THIS SAME | | CIRCUIT AS NOTED ABOVE IN NOTE # 18, PLEASE SEE FIXTURE | | SA INDICATE #8?S, AND YET SB WHICH CONTAIN A LONGER RUN | | AND MORE FIXTURES ONLY INCREASE UP TO A #10 AWG. PLEASE | | SEE FBC 13-413.1.ABC.1.2. | | | | 20) NOTE: PLEASE PROVIDE A WORST CASE FOR BOTH FEEDER | | AND BRANCH CIRCUIT. | | 13-413.1ABC.1. | | IT IS NOTEDTHAT ON MANY OF THE PANEL SCHEDULES A VD % | | IS ALREADY SHOWN, HOWEVER PLEASE BE SURE TO INDICATE | | THE ABOVE. (CAN BE DONE ON A SIMPLE TYPICAL TABLE). FBC | | 106.1.2. | | | | 21) NOTE: PLEASE SEE THE 100% FIRE SPRINKLER PLANS | | SUBMITTED DO NOT CORRELATE WITH THE FA OR ELECTRICAL | | PLANS SUBMITTED WITH RESPECT TO THE FIRE PUMPS. PLEASE | | SEE THE FS SHEETS WHICH INDICATE ELECTRIC, ELECTRICAL/ | | DIESEL AND DIESEL. PLEASE SEE THE ELECTRICAL PLANS AND | | THE MANUFACTURE SPECS/CUT SHEETS SUBMITTED ONLY | | INDICATE DIESEL. | | PLEASE SEE THE MINIMUM FUEL TANK SIZE SHALL BE | | SUFFICIENT FOR A MINIMUM OF 8HRS AT 100% LOADS. IF | | ELECTRICAL AND BEING DRIVEN BY THE BACK UP POWER OF AN | | EMERGENCY GENERATOR, THE ON-SITE FUEL SUPPLY SHALL BE | | BASED ON THE 100% LOAD OF THE FIRE PUMP AND ALL OTHER | | LEGAL AND EMERGENCY STAND-BY LOADS AT 100% FOR TIMES | | REQUIRED. | | PLEASE SEE 2002 NFPA-110, TEXT EXTRACTED FORM THE | | CODE: | | 9.6.2.2 THE FUEL SUPPLY CAPACITY SHALL BE SUFFICIENT | | TO PROVIDE 8 HOURS OF FIRE PUMP OPERATION AT 100 | | PERCENT OF THE RATED PUMP CAPACITY IN ADDITION TO THE | | SUPPLY REQUIRED FOR OTHER DEMANDS. | | PLEASE SEE NFPA-20 2003 IF DIESEL DRIVEN AND THE SAME | | AMOUNT OF FUEL REQUIRED WHICH EQUALS 1GAL PER HP PER | | HOUR PLUS 5% FOR SUMP AND 5% FOR EXPANSION. PLEASE SEE | | THE FOLLOWING THE CODE. | | 11.4.3.1 FUEL SUPPLY TANK(S) SHALL HAVE A CAPACITY AT | | LEAST EQUAL TO 5.07 L PER KW (1 GAL PER HP), PLUS 5 | | PERCENT VOLUME FOR EXPANSION AND 5 PERCENT VOLUME FOR | | SUMP AND THE COMMENTARY SECTION AS FOLLOWS, A.11.4.3 | | THE QUANTITY 5.07 L PER KW (1 GAL PER HP) IS EQUIVALENT | | TO 0.634 L PER KW (1 PINT PER HP) PER HOUR FOR 8 | | HOURS. WHERE PROMPT REPLENISHMENT OF FUEL SUPPLY IS | | UNLIKELY, A RESERVE SUPPLY SHOULD BE PROVIDED ALONG | | WITH FACILITIES FOR TRANSFER TO THE MAIN TANKS. | | | | 22) NOTE: PLEASE BE SURE THE NFPA-20 2003 EDITION IS | | REFLECT ON ALL PLANS AS THE CURRENT CODE IN EFFECT FOR | | THE SCOPE OF WORK AND DESIGN RELEVANT TO THIS PROJECT. | | | | 23) NOTE: PLEASE SEE NEC 210.8B3 FOR ALL RECEPTACLES IN | | KITCHENS IN OTHER THAN DWELLING UNITS. PLEASE SEE THIS | | WOULD BE REQUIRED FOR CAFE/ KITCHENETTE AREAS AS SHOWN | | ON PLANS. | | | | 24) NOTE: PLEASE SEE MANY AREAS WHERE THE | | FUTURE/PROPOSED FURNITURE LAYOUTS WERE REMOVED FROM THE | | PLANS WHERE THEY WERE ON THE 50% AND THE 90% PLANS? | | PLEASE LOCATE BACK ON PLANS FOR REVIEW OF THE EGRESS | | PATHS AND LIFE SAFETY FOR MINIMUM WIDTHS ETC. THIS MAY | | ALREADY BE IN THE FIRE MARSHAL'S OFFICE REVIEW | | COMMENTS, HOWEVER IF NOT, THIS IS REQUIRED WHETHER OR | | NOT COMMENT IS MADE. | | LS 101 7.8, 7.9, 7.8.1.3, 7.9.2.2. | | | | 25) NOTE: PLEASE SEE MISSING THE PHOTO-METRICS FOR THE | | GARAGE STAIR TOWERS. PLEASE SEE THE PHOTO-METRICS AS | | SUBMITTED ARE A LITTLE CONFUSING. PLEASE PREVIOUS | | COMMENTS ONLY REQUESTED EGRESS PATHS OF LEVELS | | SURFACES/ CORRIDORS AND EGRESS PATHS THAT OF THE STAIR | | TOWERS. PLEASE SEE THERE MUCH INFORMATION SUBMITTED | | GIVING FIXTURE DESIGNATIONS AND ROOM BY ROOM LEVELS? | | PLEASE PROVIDE THE EGRESS PATHS INFORMATION INDICATING | | THE CLEAR NORMAL AND EMERGENCY LEVELS AS NEEDED AND | | REQUIRED BY CODE. | | PLEASE PROVIDE A BREAKDOWN OF THE NORMAL AND EMERGENCY | | AVERAGE. PLEASE SEE THAT INFORMATION OF WHICH IS | | SUPPLIED ON EACH "OVER-ALL" SHEET DOES NOT SUPPLY THE | | INFORMATION AS NEEDED. | | PLEASE SEE 9-4.1 WHICH INDICATES IN TITLE BLOCK, | | EMERGENCY/ NORMAL? | | | | 26) NOTE: PLEASE SEE 9-5.2 WHICH SEEMS TO INDICATE | | "DOUBLE FIXTURES" IN STAIR TOWER AREAS. | | PLEASE CLARIFY FOR EACH SECTION OF THE BUILDING AND ON | | EACH LEVEL. | | FBC 106.1.2 ADMIN SECTION. | | | | 27) NOTE: PLEASE CLARIFY GARAGE LIGHTING WHICH SHOWS | | "ON" NEXT TO SOME FIXTURES ON PLANS. (RAMP AREAS) THIS | | IS UNCLEAR AT THIS TIME WHAT IS MEANT BY THIS. | | FBC 106.1.2 ADMIN SECTION | | | | 28) NOTE: PLEASE PROVIDE A NOTE ON PLANS AND PLEASE BE | | SURE TO CORRELATE WITH THE MECHANICAL PLANS AS THE "XP" | | LCP'S ARE REQUIRED TO BE INSTALLED IN AREAS WITH LESS | | THAN 90% HUMIDITY AS REQUIRED BY THE MANUFACTURE. | | PLEASE BE SURE ALL ROOMS IN WHICH THESE PANELS ARE | | LOCATED SHALL BE CONDITIONED AS REQUIRED. PLEASE | | PROVIDE THE ADDITIONAL NOTE AND ANY CHANGES ON | | MECHANICAL PLANS ALONG WITH NOTE ON 5-3.0. | | 110.3, 90.7. | | | | 29) NOTE: PLEASE SEE MISSING LCPG.COULD NOT LOCATE ON | | PLANS, SCHEDULE, AND RISER OR ON PLANS. | | FBC 106.1.2ADMIN SECTION. | | | | 30) NOTE: PLEASE SEE MISSING THE ELECTRICAL ROOM FOR | | 1HMGB AND 1HMGA ON THE LAYOUTS FOR THE ELECTRICAL | | ROOMS. | | PLEASE PROVIDE. 106.1.2, | | NEC 110.26 | | | | 31) NOTE: PLEASE SEE MAIN ELECTRICAL ROOM AND THE | | MISSING ELECTRICAL ROOM FROM NOTE #30 ABOVE WHICH IS | | STILL INDICATING DOORS WITH AN "IN-SWING" WHICH IS NOT | | PERMITTED. PLEASE ALSO BE SURE TO ADD A NOTE WITH | | RESPECT TO PANIC HARDWARE REQUIRED FOR ALL DOORS AS | | REQUIRED PER 110.26. (MAIN ELECTRICAL ROOM/ AND ROOM | | NOTED ON NOTE #30). | | PLEASE SEE THE DOOR SWINGS WERE NOTED ON ALL OF THE | | REVIEWS BASED ON THE 50%, 90% AND THIS REVIEW. PLEASE | | GO OVER ALL PLANS AND DOORS. | | | | 32) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT | | SHEETS FOR AL THE TANK-LESS WATER HEATER UNITS. THESE | | MAY ALSO LABELED AS INSTA-HOTS. PLEASE SEE MISSING | | DISCONNECTS AS REQUIRED ON THESE UNITS. THESE COULD NOT | | BE LOCATED ON PLANS. | | PLEASE SEE SIZING OF THE OVER CURRENT DEVICES, | | DISCONNECTS AND ETC SHALL BE BASED ON EACH UNIT. PLEASE | | SEE 422.31, 110.3, AND 90.7. | | | | 33) NOTE: PLEASE SEE SOME TWH UNITS WHICH ARE SHOWN ON | | PLANS ARE MISSING THE REQUIRED CIRCUITING. CAN NOT | | REVIEW FOR COMPLIANCE OF LOAD, CONDUCTOR SIZE, OCP ETC | | AT THIS TIME. | | PLEASE COMPLETE. 240.4, 310.16, 408.4, FBC 106.1.2 | | | | 34) NOTE: PLEASE PROVIDE INFORMATION FOR FAIL SAFE | | OPERATION OF THE POWER OPERATED DOORS. THE FAILURE OF | | POWER SHALL NOT IMPEDE THE EGRESS FROM A BUILDING | | DURING A POWER FAILURE AT ANY TIME EVEN IF THESE | | CIRCUITS ARE ON THE BACK-UP GENERATOR. | | LS 101 7.19 | | THIS MAY BE IN THE FIRE MARSHAL'S REVIEW COMMENTS, | | HOWEVER IF NOT THIS ISSTILL REQUIRED. | | | | 35) NOTE: PLEASE ALSO PROVIDE THE FAIL SAFE OPERATION | | OF THE GATES AT THE GARAGE. | | THE SAME NOTE AS ABOVE FOR GATES. | | | | 36) NOTE: PLEASE SEE THERE ARE SEVERAL ELECTRICAL ROOMS | | ON PLANS WHICH THE GROUND BAR IS BEING IN THE DOOR WAY? | | THIS IS APPEARS TO BE A MISPRINT. PLEASE CORRECT AND | | ADJUST PLANS AS NEEDED. | | FBC 106.1.2, NEC 110.26 | | | | 37) NOTE: PLEASE SEE ELECTRICAL ROOM LAYOUT AS THERE | | ARE SOME PANELS WHICH ARE SHOWN IN THE DOOR WAY OR | | PROTRUDING INTO THE DOOR WAY. THIS SEEMS TO BE AN | | OVERLAY/MISPRINT ISSUE AS NOTED ABOVE. | | 110.26. | | | | 38) NOTE: PLEASE SEE ELECTRICAL ROOM'S LAYOUTS WHICH | | ARE MISSING WALLS AND DOORS. PLEASE SEE 2ND, 3RD, AND | | 4TH FLOORS ROOM #4. 4-2.0,4- 3.0,4-4.0 | | CAN NOT VERIFY SOME CODE RELATED ITEMS AT THIS TIME. | | 110.26. | | FBC 106.1.2 ADMIN SECTION. | | | | 39) NOTE: PLEASE SEE ELECTRICAL ROOM LAYOUTS WHICH ARE | | SHOWING PANELS WHICH ARE NOT ON ANY RISER, PANEL | | SCHEDULES ETC. PLEASE ALSO SEE TRANSFORMERS BEING SHOWN | | WHICH ARE NOT LABELED ALSO? | | PLEASE LABEL AS "FUTURE" IF INDEED THE SPACE IS BEING | | ALLOTTED FOR FUTURE EXPANSION WHICH IS REQUIRED BY CODE | | UNDER 90.8, 110.26 | | | | 40) NOTE: PLEASE BE SURE TO LABEL ALL LCP?S ON PLANS, | | ELECTRICAL ROOMS, RISER AND CORRELATE WITH THE LCP'S | | SCHEDULE.9EXAMPLE LCP1D, LCP3B, ETC) | | FBC 106.1.2, 106.3.5.1.2 | | | | 41) NOTE: PLEASE SEE ELECTRICAL ROOM LAYOUTS, SOME SHOW | | TRANSFORMER SIZES AND SOME DO NOT. PLEASE COMPLETE AND | | SHOW. | | 450, FBC 106.1.2, 110.26, 450.9, ETC | | | | 42) NOTE: PLEASE SEE ELECTRICAL ROOM LAYOUTS INDICATE | | WHAT IS BEING SHOWN AS "NAC" PANELS; HOWEVER IT IS | | UNCLEAR WHAT THESE ARE? PLEASE EXPLAIN. | | FBC 106.1.2, 106.3.5.1.2 | | | | 43) NOTE: PLEASE SEE "SHADED" AREAS ON MEZZANINE LEVEL | | PLANS E-1.1.4, PLEASE CLARIFY | | 106.1.2 FBC ADMIN SECTION. | | | | 44) NOTE: PLEASE SEE STAIR TOWERS WHICH ALSO INDICATE | | AN ELECTRICAL ROOM IN THE STAIRWELL. THIS APPEARS TO BE | | SOME SORT OF MISPRINT. THIS IS BEING SHOWN ON MORE THAN | | ONE FLOOR AND LOCATION. PLEASE BE SURE TO CORRELATE | | WITH ALL OTHER PLANS. | | FBC 106.1.2 | | *** ONLY AS NOTED, IT IS KNOWN THAT NO ELECTRICAL | | EQUIPMENT OR OTHER ITEMS ARE PERMITTED IN EXIT | | STAIRWAYS UNLESS PERTAINING TO STAIRWAYS. | | | | 45) NOTE: PLEASE SEE OTHER SHEETS WHICH INDICATE THE | | OPENING FOR THE DOOR LEADING INTO THE STAIRS ACTUALLY | | THROUGH WHAT WOULD BE THE LOW VOLTAGE ELECTRICAL DATA | | ROOM. WHERE THE SANE LOCATION IS SHOWING WHAT APPEARS | | TO BE A DOOR ON THE SHEER/RATED STAIRWAY WALL. PLEASE | | SEE THIS IS SHOWN LIKE THIS AT MANY LOCATIONS AND ON | | MULTIPLE FLOORS. PLEASE BE SURE TO COORDINATE LAYERS, | | LEVELS, AND SHEETS FOR ALL. | | FBC 106.1.2 ADMIN SECTION. | | | | 45) NOTE: PLEASE SEE WHAT APPEARS TO BE MISSING WALLS, | | DOORS SEPARATION E-1-1.2, LIBRARY/MUSEUM/ STORE? PLEASE | | SHOW AS THE REQUIREMENTS FOR CHAPTER 13 CAN NOT | | VERIFIED FOR CONTROL OF LIGHTING. LIGHTING OF SOME TYPE | | INCLUDING EXIT/EMERGENCY LIGHTS ARE STILL REQUIRED IN | | SPACE, EVEN IF FOR FUTURE BUILD OUT. PLEASE SEE LS 101 | | 7.8, 7.9 AND POSSIBLE COMMENTS FROM FIRE MARSHAL?S | | OFFICE. | | 13-415.1.ABC.1.ABC.1.1, .1.2, .1.3 | | | | 46) NOTE: PLEASE VERIFY LIGHTING POWER DENSITIES FOR | | GARAGE. SOME OF WHICH WERE NOTED ABOVE IN COMMENTS FOR | | CHAPTER 13 REQUIREMENTS, HOWEVER THIS IS ALSO BE NOTED | | SEPARATELY. | | PLEASE SEE CONTROL MEANS. | | SEE FBC CHAPTER 13. (ALL) | | | | 47) NOTE: PLEASE PROVIDE AN ELEVATION/DETAIL FOR ALL | | ELECTRICAL CONDUITS BEING RUN FROM GARAGE TO THE MAIN | | BUILDING. THIS BUILDING IS BEING CONSIDERED "ATTACHED" | | AND ONE " BUILDING" BY DEFINITION, HOWEVER DUE THE | | UNDERSTANDING OF MANY OF THE CONDUITS ARE NOW BEING | | INSTALLED IN THE SLAB OR UNDER GROUND AND THE AMOUNT OF | | OTHER CONDUITS, PIPING, BEING INSTALLED IN THIS SAME | | AREA, IT IS OF CONCERN FOR THE SPACE REQUIREMENTS FOR | | BUNDLING OF CONDUITS, DE-RATING OF CONDUCTOR | | AMPACITIES. ETC. (THIS CAN BE A DETAIL LIKE A DUCT-BANK | | DETAIL) | | FBC 106.1.2, 310.16, 300.8, 300.10, 310.10, 310.15, | | 310.16, 300.17 ETC. | | THERE ARE MANY SECTIONS WHICH COULD BE REFERENCED. | | PLEASE ALSO SEE COMMENT WITH RESPECT TO WIRING METHODS | | OF EMERGENCY FEEDERS ETC. | | | | 48) NOTE: PLEASE VERIFY THE SHUNT TRIP FOR THE 4TH | | FLOOR IT PANEL. PLEASE SEE THIS SHUNT TRIP BREAKER | | SHOULD BE LOCATED IN 1HEE. PLEASE ALSO SEE THAT PLANS | | INDICATE WHAT SEEMS TO BE A PUSHBUTTON AT ONE DOOR | | LABELED EPO, AND ONE WHICH APPEARS TO BE THE SAME | | HOWEVER NOT LABELED AS EPO.PLEASE LABEL. AN EPO WILL | | BE REQUIRED AT EACH DOOR. | | PLEASE SEE 645.10, HANDBOOK WHICH EXPLAINS THE | | DISCONNECTING AT THEIR SUPPLY POINT. | | | | 49) NOTE: PLEASE KNOW AS NO INFORMATION FOR THE IT ROOM | | EQUIPMENT IS BEING SUBMITTED WITH THIS RECORD SET OF | | PLANS, PLEASE PLACE NOTE AND CLOUD ON 4TH FLOOR POWER | | PLANS THAT ALL ELECTRICAL EQUIPMENT, UPS, SERVER | | EQUIPMENT ETC IN THE IT ROOM SHALL BE UNDER A SEPARATE | | PERMIT, PLANS, AND FEES BASED ON THE EQUIPMENT BEING | | INSTALLED IN THIS ROOM. REVIEW FOR CODE COMPLIANCE FOR | | THIS ROOM CAN NOT BE COMPLETED AT THIS TIME. THE | | REQUIREMENTS FOR THE CONSTRUCTION OF THIS ROOM IS | | REQUIRED AT THIS TIME, INCLUDING THE MINIMUM 1HRA | | RATING, THE FIRE DAMPERS ETC (IF APPLICABLE) AND THE | | SHUT DOWN OF AN AND ALL A/C EQUIPMENT. | | NEC 645, NFPA-75 | | | | 50) NOTE: PLEASE PLACE NOTE ON THE LIGHTNING PROTECTION | | PLANS, BOTH THE LAYOUT OF THE SYSTEM AND THE SYSTEM | | DETAIL. | | THESE PLANS MAY BE USED FOR REFERENCE OF PERMITTING | | PROJECT; HOWEVER SEPARATE PERMIT AND FEES WILL BE DUE | | UPON APPLICATION. THE LP SYSTEM IS NOT PART OF THE | | VALUE FOR SCOPE OF WORK. | | PLEASE ALSO NOTE THAT SYSTEM MUST BE INSTALLED BY A | | LICENSED LIGHTING PROTECTION CONTRACTOR WHO WILL | | PROVIDE A MASTER UL CERTIFICATION OF THE SYSTEM UPON | | COMPLETION. | | (OR WORDS TO THAT AFFECT) | | | | 51) NOTE: PLEASE SEE LOADS FOR RECEPTACLE CIRCUITS | | SHALL BE BASED ON 180VA MINIMUM FOR CIRCUITS. PLEASE | | SEE CIRCUITS FOR WHAT IS A "J" BOX FOR FUTURE MODULAR | | FURNITURE IS LABELED AS RECEPTACLES? PLEASE LABEL FOR | | THE INTENDED USE. | | 408.4, 220.10 | | | | 52) NOTE: PLEASE SEE PLANS WHICH INDICATE A TRIANGULAR | | SYMBOL WITH A "F" NEXT TO THESE HOWEVER COULD NOT ANY | | INFORMATION ON WHAT THESE ARE ON ANY SYMBOL LEGEND? | | PLEASE REMOVE OR DESIGNATE. | | FBC 106.1.2 | | | | 53) NOTE: PLEASE COORDINATE ALL OVER-LAYS AND LAYOUTS | | FOR ELECTRICAL, MECHANICAL, PLUMBING, BUILDING AND ALL | | OTHER TRADE PLANS. PLEASE KNOW THE ELECTRICAL 100% | | PLANS DO NOT SHOW THE SAME ELECTRICAL ROOMS AND | | EQUIPMENT AS THE 100% MECHANICAL PLANS, PLUMBING OR | | BUILDING PLANS ALONG WITH OTHER SHEETS FROM OTHER | | TRADES. | | REVIEW OF ALL APPLICABLE ITEMS WILL STILL NEED TO BE | | DONE AS REQUIREMENTS FOR ELECTRICAL AND OTHER TRADES | | WILL MOST CONTAIN CLEAR CONFLICTS WHICH MAY OR MAY NOT | | BE PERMITTED. | | 110.26, 240.24 NEC. | | FBC 106.3.5.1.1 ADMIN SECTION FOR ALL TRADES FOR | | COMMERCIAL PLANS. | | | | 54) NOTE: PLEASE CORRELATE THE PLANS WITH THE | | MANUFACTURE SPECS/CUT SHEETS FOR THE GENERATOR WHICH IS | | BEING SUBMITTED AS A LARGER UNIT IN THE SPEC BOOK AS | | SHOWN ON PLANS. THIS WILL AFFECT THE FUEL SUPPLY, AND | | THE FUEL LINE SUPPLY FOR THE PROPOSED NATURAL GAS | | LINE. | | 90.7, 110.3, | | FBC 106.1.2 | | | | 55) NOTE: PLEASE INCLUDE DETAIL AND ATTACHMENT FRO THE | | LIGHTNING PROTECTION SYSTEM AS PART OF THE MAIN | | GROUNDING ELECTRODE SYSTEM AS REQUIRED PER 250.106. IT | | IS NOTED THAT THE DETAIL IN THE LP DETAILS IN THE REAR | | OF PLANS, HOWEVER DOES NOT INCLUDE THE GE SYSTEM, OR | | THE GE RISER, SYSTEM DOES NOT INCLUDE THE LP GROUNDING | | ATTACHMENT. | | | | 56) NOTE: PLEASE INCLUDE ALL OTHER METAL WATER PIPING | | SYSTEMS AS PART OF THE GROUNDING ELECTRODE SYSTEM AS | | REQUIRED PER 250.106. (FIRE SPRINKLER) | | | | 57) NOTE: PLEASE SEE SOME BATHROOMS CONTAIN OC SENSORS | | AND MANY DO NOT, PLEASE EXPLAIN AND PLEASE SEE OTHER | | COMMENTS FOR TYPE OF DEVICES WHICH WILL BE REQUIRED. | | 13-415.1.ABC.1.2 | | | | 58) NOTE: PLEASE KNOW SOME SORT OF BATTERY BACK UP | | FIXTURE WILL BE REQUIRED IN THE LARGER BATHROOMS (ROOM | | OTHER THAN SINGLE POINT OF USE). | | PLEASE SEE LS 101 7.8., 7.9 | | THIS WAS DISCUSSED WITH THE FIRE MARSHAL CHIEF AND WILL | | BE REQUIRED BOTH BY THIS OFFICE AND THE FIRE MARSHAL'S | | OFFICE IN THE INTEREST OF LIFE SAFETY AND CODE AS | | REFLECT. | | | | 59) NOTE: PLEASE SEE NUMEROUS OFFICES ON ONE CIRCUITS | | COMING FROM THE LIGHTING CONTROL PANEL(S). PLEASE SEE | | THE FOLLOWING SCENARIO: IN THE EVENT OF AFTER HOURS, | | THE TIMER ?SWEEPS? THROUGH AND TURNS OFF THAT | | PARTICULAR CIRCUIT, AND EMPLOYEE WILL "RESET" THE | | SENTRY SWITCH WHICH IN-TURN TURN THAT BRANCH CIRCUIT | | BACK ON. WOULD THAT NOT IN-TURN ON OTHER LIGHTS ON THAT | | CIRCUIT. (OTHER ROOMS, OFFICES ETC?) | | PLEASE SEE PREVIOUS NOTE ABOVE #9 WHICH ALSO TOUCHED ON | | THE LIGHTING CONTROL SYSTEM BEING PROPOSED, HOWEVER | | THERE ARE SCENARIOS WHICH ARE STILL IN QUESTION OR NEED | | TO BE WORKED OUT. | | 13-415.1.ABC.1.1 | | | | 60) NOTE: PLEASE SEE MISSING CONTROLS FOR ELEVATOR PIT | | LIGHTS. 13-415.1.ABC.1.2, | | 620.24B. | | | | 61) NOTE: PLEASE SEE THERE ARE SOME LOCATIONS ON PLANS | | WHICH ARE SHOWING "NL'S" (NIGHT LIGHTS) BEING PART OF A | | PERMANENT ON SCENARIO, HOWEVER THE NUMBER OF FIXTURES | | BEING PROPOSED TO REMAIN ON AS NIGHT LIGHTS ARE OVER | | WHAT IS BEING CONSIDERED AS NORMAL. PLEASE KNOW THIS | | CAN BE GONE OVER, HOWEVER PLEASE SEE SOME AREAS WHERE | | THERE ARE 10-20PLUS LIGHTS BEING LEFT ON. | | THE INTENT OF CHAPTER 13 AND ALSO THE INTEREST OF LIFE | | SAFETY SHOULD BE CONSIDERED. PLEASE CALL TO OVER. SEE | | SHEET E2-1.2 FOR EXAMPLE IN LOBBY AREA. | | | | 62) NOTE: PLEASE SEE NFPA-20 11.3, 11.3.2, 11.3.2.3 AND | | FLORIDA FIRE PREVENTION CODE , NFPA-1 7-4FOR OTHER | | REQUIREMENTS FOR FIRE PUMPS AND ROOMS IN WHICH THEY ARE | | LOCATED. | | PLEASE ALSO SEE 11.4.6.2 FUEL PIPING SHALL NOT BE | | GALVANIZED STEEL OR COPPER. | | PLEASE KNOW AS PART OF THE COMPLETED TESTING AND | | ACCEPTANCE AS REQUIRED IN CHAPTER 14, DOCUMENTATION FOR | | TESTING FOR FIRE PUMP ON A WEEKLY BASIS IS REQUIRED TO | | THE OWNER OF RECORD.CODE TEXT FROM NFPA-20: 11.6.1.1 | | ENGINES SHALL BE STARTED NO LESS THAN ONCE A WEEK AND | | RUN FOR NO LESS THAN 30 MINUTES TO ATTAIN NORMAL | | RUNNING TEMPERATURE. | | | | 63) NOTE: PLEASE SEE NFPA-110 CHAPTER 7 FOR THE | | INSTALLATION OF THE GENERATOR. PLEASE SEE 7.4 AND 7.5, | | PROVIDE DETAIL FOR MOUNTING OF UNIT TO ALLEVIATE ANY | | INTEGRITY INTERFERENCE OF THE STRUCTURE. | | | | 64) NOTE: PLEASE SUBMIT THE SPEC/CUT SHEET FOR THE | | PROPOSED MTS. THE "KIRK KEY" AS SHOWN AND HAND WRITTEN | | ON SPECS IS NOT ACCEPTED AT THIS TIME. THERE ARE MANY | | OF THESE SYSTEMS ON THE MARKET WHICH WILL PERMIT THE | | POWER FROM TWO SOURCES AT ONCE WHICH IS STRICTLY | | PROHIBITED. PLEASE SEE 700.6, 701.7, 110.3, AND 90.7 | | CAN NOT VERIFY AT THIS TIME. PLEASE ALSO SEE THE | | FOLLOWING COMMENT. | | | | 65) NOTE: PLEASE SEE RISER AND PLANS WERE REVISED FROM | | THE 50% AND 90% PLANS CHANGING ALL ATS UNITS TO 3-POLE | | UNITS. PLEASE SEE ALTHOUGH GF PROTECTION IS NOT | | REQUIRED ON THE EMERGENCY SIDE OF THE EMERGENCY SYSTEM | | AND LEGALLY REQUIRED SYSTEMS, PROPER GROUND FAULT | | SENSING IS REQUIRED. PLEASE KNOW DOCUMENTATION FROM | | MORE THAN ONE MANUFACTURE WAS SENT TO THE ENGINEER | | PRIOR TO THE REVIEW WHEN THE PLANS WERE SUBMITTED ON | | THE 7TH OF NOV. PLEASE SEE NFPA-110 6.2.15** ISOLATION | | OF NEUTRAL CONDUCTORS. PROVISIONS SHALL BE INCLUDED FOR | | ENSURING CONTINUITY, TRANSFER, AND ISOLATION OF THE | | PRIMARY AND THE EPS NEUTRAL CONDUCTORS WHEREVER THEY | | ARE SEPARATELY GROUNDED TO ACHIEVE GROUND-FAULT | | SENSING. | | PLEASE SEE AN ATTACHED BRIEF EXPLANATION FROM"ASCO" | | WHITE PAPER: WHERE GROUND FAULT PROTECTION IS TRIGGERED | | BY THE CODE AND AN ALTERNATE POWER SUPPLY IS INCLUDED, | | SWITCHING OF THE NEUTRAL BECOMES NECESSARY. THE CIRCUIT | | SHOWN ABOVE ILLUSTRATES SUCH A CIRCUMSTANCE. THE | | SERVICE IS LARGER THAN 1,000 AMPS. CONSEQUENTLY, GROUND | | FAULT PROTECTION IS REQUIRED AT THE MAIN SERVICE | | DISCONNECT AT A MINIMUM. IF IT IS INSTALLED THERE AND | | THE GENERATOR NEUTRAL GROUNDING WAS THROUGH A SOLID | | CONNECTION TO THE MAIN SERVICE NEUTRAL, A GROUND FAULT | | WHEN THE GENERATOR IS FEEDING THE LOAD WILL CAUSE THE | | MAIN SERVICE DISCONNECT TO OPEN. THIS WILL NOT | | DISCONNECT THE ARCING FAULT FROM THE GENERATOR. | | COORDINATION IS THUS LOST." | | PLEASE KNOW BASED ON THE INFORMATION FROM SEVERAL | | MANUFACTURES AND THE CODE PLEASE ADJUST AS REQUIRED. | | PLEASE ALSO SEE GENERATOR GROUNDING DETAIL WILL BE | | REQUIRED TO BE REVISED. | | PLEASE SEE E5-1.1.18 WHICH NOTES A #3 CONDUCTOR, WHICH | | WOULD NOT BE LARGE ENOUGH. | | PLEASE SEE 250.20, 250.30, 250.66, 240.13, 230.95, | | 700.7D, 700.26 | | PLEASE SEE THE MTS. | | | | 66) NOTE: PLEASE SEE THERE ARE MANY EXIT/EMERGENCY | | LIGHTS WHICH DO NOT SHOW ANY CONNECTION TO ANY LOCAL | | CIRCUIT IN ANYWAY. PLANS NOTE THIS AND MANY ARE SHOWN | | THIS WAY, HOWEVER NOT ALL. PLEASE GO THROUGH PLANS. | | PLEASE SEE 700.12E WHICH REQUIRES THE BRANCH CIRCUIT | | FEEDING THE UNIT EQUIPMENT SHALL BE THE SAME BRANCH | | CIRCUIT AS THAT SERVING THE NORMAL LIGHTING IN THE AREA | | AND CONNECTED AHEAD OF ANY LOCAL SWITCHES. | | | | 67) NOTE: PLEASE SEE OVER ALL 3RD FLOOR PLANS, WHICH | | SEEM TO BE SHOWING LIGHTING OF SOME KIND ON GARAGE | | PLANS? | | PLEASE ALSO SEE E2-4.0 | | FBC 106.1.2 ADMIN SECTION. | | | | 68) NOTE: PLEASE SEE NOTE #2 ON RISER WITH RESPECT TO | | THE MTS WHICH IS TO PROVIDE FUTURE PROVISIONS FOR | | POSSIBLE PORTABLE GENERATOR TO RUN THE EMERGENCY | | SYSTEMS, PLEASE KNOW A DETAIL TO A LOCATION AND HOW | | THIS CONNECTION WILL BE MADE IS REQUIRED.THE RUNNING | | OF CORDS, CONDUCTORS ETC SHALL BE PERMITTED TO TRAVEL | | THROUGH THE ELECTRICAL ROOM DOORS, ON SIDEWALK AREAS OR | | ANY LOCATIONS PROVIDING A TRIPPING HAZARD OR NOT | | SECURING LIVE PARTS ETC. | | PLEASE PROVIDE A DETAIL AS THIS CONNECTION POINT WILL | | BE SUBSTANTIAL IN NATURE. (J-BOX) ETC ON THE OUTSIDE OF | | BUILDING ETC. | | 110.26, 110.27, NEC 527. | | | | 69) NOTE: PLEASE PROVIDE CALCULATIONS ON NEUTRAL | | CONDUCTORS FOR ALL NON-LINEAR CIRCUITS. PLEASE SEE ALL | | CIRCUITS WHICH CONTAIN THESE LOADS SHALL MEET THE | | SIZING REQUIREMENTS TO HANDLE AND ALLEVIATE THE OVER | | LOADING OF THE NEUTRAL ON A 3-PHASE 4-WIRE SYSTEM WITH | | PREDOMINATELY OR ACTUALLY IN MANY CASES ALL NON-LINEAR | | LOADS. PLEASE SEE THIS CAN BE DONE BY USING MANY | | METHODS. THE K-RATED TRANSFORMERS WERE REMOVED FROM THE | | DESIGN AS ON PREVIOUS PLANS, SO PLEASE SEE THE REQUEST | | FOR FULL NEUTRAL LOAD CALCULATION OR THE SIZING OF THE | | NEUTRAL AT 200%. | | PLEASE SEE THE RISK OF FIRE AND CAUSE TO PROPERTY | | DAMAGE IS OF CONCERN PLEASE SEE STUDIES IN WHITE PAPERS | | WHICH INDICATE AS MUCH AS 1.7 TIMES THE RATED LOAD OF | | THE CONDUCTOR. | | PLEASE SEE THE FOLLOWING CODES: THIS OFFICE IS AWARE OF | | WHAT A FPN MEANS, HOWEVER SEE SECTIONS GIVEN WHICH DO | | NOT CONTAIN FPN. 210.4A (FPN), 220.22 (FPN(2), 310.10, | | 310.15B4(C), 400.5, 520.44, 408.16, AND FBC 104.6 | | ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF WEST | | PALM BEACH. | | | | 70) NOTE: PLEASE SEE E2-4.2 STAIR TOWER AREA WHICH | | MENTIONS "HOLD FOR ARCHITECT" ? PLEASE SEE PREVIOUS | | NOTE WITH RESPECT TO DOORS INTO STAIRWAYS ETC. | | FBC 106.1.2 ADMIN SECTION. | | | | 71) NOTE: PLEASE KNOW IF IT IS THE INTENT TO UTILIZE | | THESE PLANS FOR FUTURE LOW VOLTAGE WORK FOR LOCATIONS | | OF PHONE, DATE DROP ETC, PLEASE COMPLETE PLANS AS | | SUBMITTED SHOWING ALL LOCATIONS FOR DROPS.PLEASE SEE | | MANY AREAS WHICH LOW VOLTAGE DATE/PHONE DROPS WILL BE | | REQUIRED OR INSTALLED, HOWEVER THESE LOCATIONS ARE NOT | | BEING SHOWN AT THIS TIME. | | IF THE LV SCOPE IS PART OF THE PERMITTED PLANS AS | | SUBMITTED PLEASE REMOVE AND NOTE AS UNDER SEPARATE | | PERMIT PLANS AND FEES. | | | | 72) NOTE: PLEASE PROVIDE VD FOR THE FEEDER FOR THE IT | | PANEL. 13-413.1.ABC.1.1 | | | | 73) NOTE: PLEASE SEE 700.9D FOR THE FEEDERS FROM THE | | GENERATOR TO THE EMSB1 AND THE FEEDERS OUT TO SYSTEMS | | WHICH MAY BE CONSIDERED INSIDE THE BUILDING. PLEASE SEE | | THE CODE AS THERE ARE WAYS TO MEET THE INSTALLATION OF | | THESE FEEDERS, HOWEVER PLANS SHALL INDICATE WHICH WILL | | BE USED. (TYPE OF CABLE, ENCASED IN 2INCHES OF | | CONCRETE, FULLY SPRINKLED ETC) | | PLEASE KNOW AS THE REQUIREMENT OF FULLY SPRINKLED IS | | OFTEN MISTAKEN AS A BUILDING CONTAINING SPRINKLERS. | | THIS IS NOT THE CASE. PLEASE SEE THE INTENT OF 700.9D | | FOR THIS HAS ALWAYS BEEN THAT ALL AREAS CONTAINING | | THESE FEEDERS BE SPRINKLED IF INSTALLED IN OPEN OR | | ABOVE CEILINGS. PLEASE KNOW A COMMENTARY IN THE 2005 | | NEC MAKES IS CLEAR WHAT THE INTENT OF THE CODE AND THE | | FURTHER EXPLANATION IS PROVIDED. | | | | 74) NOTE: PLEASE SEE NOTE WHICH MENTIONS A "LOCK-OFF" | | DEVICE IS REQUIRED FOR THE FIRE ALARM CIRCUIT. THIS IS | | OK; HOWEVER PLEASE ELABORATE ON THE NOTE AS THE DEVICE | | SHALL BE AN INTEGRAL PART OF THE BREAKER. PLEASE KNOW | | THAT SNAP ON/CLIP ON TYPE DEVICES ARE NOT ACCEPTABLE TO | | THIS AHJ. | | 110.3, 90.4 | | | | 75) NOTE: PLEASE SEE TRANSFORMER TYPICAL DETAIL WHICH | | INDICATES #6 FOR 75KVA TRANSFORMERS. PLEASE SEE | | 250.30A2 AND 250.66 FOR THE SIZE ACCORDING TO THE | | 4/0'S. | | PLEASE ADJUST. THIS WILL AFFECT THE SIZE TO THE GROUND | | BAR ONLY IN EACH ROOM FROM THIS TRANSFORMER. | | | | 76) NOTE: PLEASE PROVIDE THE SIZE OF THE CONDUCTOR ON | | THE GROUNDING ELECTRODE RISER AS PROVIDED. PLEASE SEE | | THE GROUNDING ELECTRODE DETAIL SHOWS A 4/0'S, HOWEVER | | PLEASE SEE E5-2.0. | | 250.50, 250.58 | | | | 77) NOTE: PLEASE SEE THE SIZE OF THE CONDUCTORS ON THE | | SECONDARY SIDE OF ANY TRANSFORMER SHALL BE SIZED AND | | TERMINATE IN OVER-CURRENT PROTECTION WHICH LIMITS THE | | LOAD ON THE CONDUCTORS. PLEASE SEE 240.21C, 310.16. | | PLEASE SEE 1LD2 | | | | 78) NOTE: PLEASE SEE 4HA, WHICH INDICATE 114A'S OF LOAD | | ON A BREAKER RATED AT 100A?S. PLEASE ALSO SEE 5HA WHICH | | SHOWS A LOAD OF 99A'S ON A 100A BREAKER. | | PLEASE ADJUST AS REQUIRED AS THE LOADS SHALL NOT EXCEED | | THAT OF THE RATING OF THE BREAKER, FEEDERS ETC. 310.16, | | 240.4, ETC. | | | | 79) NOTE: PLEASE SUBMIT LOAD CALCULATIONS. PLEASE | | INDICATE AND SHOW ALL CONTINUOUS LOADS AND LARGEST | | MOTOR LOADS AT 125%. | | 220.3, 220.10, 220.11, 220.13, 215.3,230.42 ETC | | | | 80) NOTE: PLEASE SEE SOME SHEETS ON THE UPPER LEVELS, | | 1-5.2, 8-5.2 INDICATE A "VAULT", HOWEVER THIS WAS | | COMMENTED ON PREVIOUS REVIEWS AND WAS REMOVED FROM SOME | | SHEETS. PLEASE SEE A SHEET FOR THE SW CORNER OF PROJECT | | AFTER E6-2.1 IF THIS IS INDEED THE SAME AREA. PLEASE | | CLARIFY. | | FBC 106.1.2 ADMIN SECTION. | | | | 81) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO | | MINIMUM FOOT CANDLES REQUIRED. PLEASE SEE GARAGE SHALL | | CONTAIN EGRESS PATHS WHICH MEET THIS MINIMUM. BASED ON | | SOME AREAS SHOWN ON PHOTO-METRICS, IT DOES NOT APPEAR | | THIS IS MET. | | PLEASE SEE LIFE SAFETY CODE NFPA-101 2003 7.8.1.3, | | 7.9.2.2 | | | | 82) NOTE: PLEASE SEE WHAT IS KNOW AS STAIR #9, MORE | | THAN ONE FIXTURE BEING SHOWN ON THE SAME LEVEL ON THE | | SAME WALL. THIS IS OK, HOWEVER ONLY A NOTE FOR | | VERIFICATION. | | E9-2.2 | | | | 83) NOTE: PLEASE CORRELATE THE TRANSFORMERS ON THE | | ELECTRICAL ROOM LAYOUTS AND THE ELECTRICAL RISER. | | PLEASE SEE THERE ARE MANY WHICH ARE SHOWN AS 15KVA ON | | ONE SHEET AND 45KVA ON OTHER SHEETS OR 45KVA ON ONE AND | | 75KAV ON ANOTHER. PLEASE ALSO SEE RISER. | | PLEASE SEE SOME BELOW AS NOTED, THIS IS ONLY SOME AND | | IS IN NO WAY ALL POSSIBLE. | | 1HB, 75KVA ON RISER, 45KVA IN ELECTRICAL ROOM. 2HB, | | 75KVA ON RISER, 45KAV IN ELECTRICAL ROOM. 1GLA-1GHA, | | 45K ON RISER, 15K ON ELECTRICAL ROOM PLANS. ETC | | | | 84) NOTE: PLEASE BE SURE TO GO THROUGH ALL TRANSFORMERS | | AS THE SIZES AS SHOWN MAY AFFECT THE OVER CURRENT | | PROTECTION ON UNITS, THE CONDUCTORS ON THE PRIMARY AND | | SECONDARY SIDE OF THE UNITS. PLEASE SEE COMMENTS WITH | | RESPECT TO SOME. | | PLEASE SEE TRANSFORMER DETAIL ON 6-1.0, THIS SCHEDULE | | IS BEING SHOWN FOR TYPICAL, HOWEVER IT DOES CORRELATE | | WITH SOME UNITS AS NOTED. SOME ARE SHOWN AS 75KVA WHICH | | ON TYPICAL SCHEDULE MENTIONS 225A OVER CURRENT | | PROTECTION ON THE SECONDARY SIDE, YET SOME TERMINATE IN | | 150A OCP ON THE SECONDARY SIDE. | | PLEASE GO THROUGH THESE: 3LC2, EXAMPLE.(NOT ALL) | | | | 85) NOTE: PLEASE SEE FBC 2004 CHAPTER 11 FOR | | REQUIREMENTS FOR ADA WITH RESPECT TO HORNS, AND | | STROBES. THE AUDIBLE LEVELS SHALL BE PER BOTH FBC | | CHAPTER 11 AND NFPA-72 AS NOTED, HOWEVER THE MORE | | STRINGENT SHALL APPLY. | | PLEASE SEE 11-4.28.1, 11-4.28.2 AND 11-4.28.3(4). | | PLEASE BE SURE THE LEVELS ARE INDICATED ON PLANS. | | PLEASE KNOW THE LIGHTING CANDELA LEVELS AS REQUIRED IN | | THE FBC ARE FAR GREATER THAN THAT OF NFPA-72. THE | | MINIMUM LEVELS FOR VISUAL SHALL BE 75 CANDELAS. PLEASE | | ADJUST AND PLACE REQUIREMENTS ON PLANS. PLEASE SEE ALL | | FA SHEETS WHICH ONLY INDICATE NFPA-72. | | | | | | 86) NOTE: PLEASE KNOW A RESPONSE LETTER/NOTES WERE | | PROVIDED, HOWEVER AS THIS REVIEW WAS MORE OF A REVIEW | | FOR CODE COMPLIANCE, A MORE DETAILED RESPONSE WOULD | | GREATLY HELP IN THE REVIEW PROCESS. THIS RESPONSE COULD | | INDICATE THE SHEETS/LOCATIONS OF CHANGES, CORRECTIONS | | OR ANY COMMENTS RELATED TO AND RESPECT TO THIS | | REVIEWERS NOTES. | | IF ANY OF THESE COMMENTS ARE NOT CLEAR IN ANY FASHION | | OR IF ANY ITEMS ARE NOT UNDERSTOOD IN ANY WAY?PLEASE | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | | ** PLEASE KNOW AS THERE IS SOME INFORMATION NOT YET | | SUBMITTED PLEASE BE SURE TO GO OVER ALL. | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. ONCE AGAIN IF THERE | | ARE ANY QUESTIONS , PLEASE DO NOT HESITATE IN CONTATING | | THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] | 2006-11-25 08:33:56 | REVIEW BACK IN PROGRESS 11/25/06 | 2006-11-22 07:38:23 | REVIEW IN PROGRESS | 2006-11-21 20:11:49 | REVIEW STOPPED, WILL CONTINUE ON 11/22 | 2006-11-21 18:54:07 | ELECTRICAL REVIEW HAS NOW RESUMED FROM 11/8 | 2006-11-08 19:53:56 | ELECTRICAL REVIEW STILL IN PROGRESS. | 2006-11-07 16:03:13 | NEW ELECTRICAL PLANS BROUGHT IN BY MR. JAMES MINDUR AT | | 1500HRS ON 11/6/06 | | ELECTRICAL REVIEW IN PROGRESS. |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
11 |
Status |
P |
Date |
2009-02-27 |
|
|
Cont ID |
|
Sent By |
mgonzale |
Date |
2009-02-27 |
Time |
15:36 |
Rev Time |
1.00 |
Received By |
mgonzale |
Date |
2009-02-27 |
Time |
15:36 |
Sent To |
ENG |
|
Notes |
2009-02-27 15:37:41 | **** PASSED ***** | | | | ADA RAMP ACCEPTABLE. | | PLANTERS ACCEPTABLE. | | |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
10 |
Status |
P |
Date |
2009-01-26 |
|
|
Cont ID |
|
Sent By |
mgonzale |
Date |
2009-01-26 |
Time |
09:55 |
Rev Time |
1.00 |
Received By |
mgonzale |
Date |
2009-01-26 |
Time |
09:55 |
Sent To |
ENG |
|
Notes |
2009-01-26 09:57:59 | **** PASSED **** | | | | PLANS APPROVED BY DEAN LAUDERMILK AT 45TH STREET | | ENGINEERING OFFICE. | | PROTECTIVE BOLLARDS DETAILS AND PLANS UNDER REVIEW AT | | 45TH STREET. | | | | MANUEL J GONZALEZ, PROJECT COORDINATOR | | LOCATION ADDRESS: | | CITY OF WEST PALM BEACH | | ENGINEERING SERVICES DEPARTMENT | | 1000 - 45TH STREET, SUITE 15 | | WEST PALM BEACH FL 33407 | | MAILING ADDRESS: | | CITY OF WEST PALM BEACH | | ENGINEERING SERVICES DEPARTMENT | | P.O. BOX 3506 | | WEST PALM BEACH FL 33401 | | TELEPHONE: | | 45TH STREET OFFICE : 561-494-1040 | | 45TH DIRECT: 561-494-1085 | | FAX: 561-494-1117 | | CITY HALL OFFICE: (561) 805-6713 | | CITY HALL DIRECT: (561) 805-6313 | | CITY HALL FAX: (561) 805-6731 OR 805-6676 | | NEXTEL: 561-644-7301 | | NEXTEL DIRECT CONNECT: 159*28165*38 | | EMERGENCIES: | | CENTRAL OPERATIONS CENTER (DISPATCH) 561-822-2210 | | E-MAIL: | | [email protected] | | | | | | | | | | |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
9 |
Status |
P |
Date |
2008-11-17 |
|
|
Cont ID |
|
Sent By |
mgonzale |
Date |
2008-11-17 |
Time |
16:09 |
Rev Time |
1.00 |
Received By |
mgonzale |
Date |
2008-11-17 |
Time |
16:07 |
Sent To |
ENG |
|
Notes |
2008-11-17 16:09:06 | REV 22A | | ADDITION TO CITY HALL PLANTER, COURTYARD GRATES AND | | GARAGE PLANTER. | | APPROVED. | | | | MANUEL J GONZALEZ, PROJECT COORDINATOR | | LOCATION ADDRESS: | | CITY OF WEST PALM BEACH | | ENGINEERING SERVICES DEPARTMENT | | 1000 - 45TH STREET, SUITE 15 | | WEST PALM BEACH FL 33407 | | MAILING ADDRESS: | | CITY OF WEST PALM BEACH | | ENGINEERING SERVICES DEPARTMENT | | P.O. BOX 3506 | | WEST PALM BEACH FL 33401 | | TELEPHONE: | | 45TH STREET OFFICE : 561-494-1040 | | 45TH DIRECT: 561-494-1085 | | FAX: 561-494-1117 | | CITY HALL OFFICE: (561) 805-6723 | | CITY HALL DIRECT: (561) 805-6327 | | CITY HALL FAX: (561) 805-6731 OR 805-6676 | | NEXTEL: 561-644-7301 | | NEXTEL DIRECT CONNECT: 159*28165*38 | | EMERGENCIES: | | CENTRAL OPERATIONS CENTER (DISPATCH) 561-822-2210 | | E-MAIL: | | [email protected] | | |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
8 |
Status |
F |
Date |
2008-11-04 |
|
|
Cont ID |
|
Sent By |
mgonzale |
Date |
2008-11-04 |
Time |
14:32 |
Rev Time |
1.00 |
Received By |
mgonzale |
Date |
2008-11-04 |
Time |
14:24 |
Sent To |
|
|
Notes |
2008-11-04 14:27:24 | REMOVABLE BOLLARDS AND FIXED BOLLARDS MUST MEET CITY OF | | WPB STREETSCAPE STANDARD. | | REMOVABLE BOLLARDS AND FIXED BOLLARDS ARE IN CONFLICT | | WITH WM ON CLEMATIS (SHOW WATERMAIN ON PLANS. | | | | PLEASE SUBMIT PLANS TO ENGINEERING FOR ROW EVALUATION | | AND TO PERFORM A JURISDICTIONAL REVIEW. PLEASE CONTACT | | CITY OF WPB ENGINEERING DEPT. | | 1000 45TH STREET SUITE 15. | | WPB, FL 33407 | | (561) 494-1040 | | ATTENTION: EMERY FABIAN | | | | |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
7 |
Status |
P |
Date |
2008-03-14 |
|
|
Cont ID |
|
Sent By |
rchokshi |
Date |
2008-03-14 |
Time |
15:27 |
Rev Time |
0.00 |
Received By |
rchokshi |
Date |
2008-03-14 |
Time |
15:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
6 |
Status |
P |
Date |
2008-02-08 |
|
|
Cont ID |
|
Sent By |
jbramley |
Date |
2008-02-08 |
Time |
16:40 |
Rev Time |
0.00 |
Received By |
jbramley |
Date |
2008-02-08 |
Time |
16:40 |
Sent To |
|
|
Notes |
2008-02-08 16:42:14 | RE: REVIEW 5 PREVIOUSLY PERFORMED BY RASIK CHOKSHI, | | TOTAL VOLUME EXFILTRATION REMAINS THE SAME.CONSULTANT | | WILL SHOW SAME ON RE SUBMITTED PLANS.FINAL VOLUMES | | ARE UTIMALTY THE CONCERN OF THE SFWMD.THERE WILL BE | | NO RESUB FEE FOR THIS PERMIT REVIEW ITEM.PER JONATHAN | | BRAMLEY AND ROBERT BROWN. |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
5 |
Status |
F |
Date |
2008-01-17 |
|
|
Cont ID |
|
Sent By |
rchokshi |
Date |
2008-01-17 |
Time |
09:17 |
Rev Time |
0.00 |
Received By |
rchokshi |
Date |
2008-01-17 |
Time |
08:54 |
Sent To |
|
|
Notes |
2008-01-17 09:12:58 | ****FAILED**** | | | | I TALKED TO PETER WAYNE AQUART OF CRAVEN THOMPSON & | | ASSOCIATES ON 1/17/08. | | HE SAID HE DID NOT CHANGE 10X8 EX-FILTRATION.HOWEVER, | | HE REDUCED THE LENGTH OF5X4 EX-FILTRATION FROM 180 | | FEETTO 85 FEET.SO, HE REDUCE THE LENGTH BY 95 FEET | | FROM ORIGINAL LENGTH OF 180 FEET OF 5X4 EX-FILTRATION | | TRENCH.HE ALSO INCREASE THE ELEVATION OF WIER BY 6 | | INCHES, SO WATER STAY IN THE GROUND PER PETER AQUART. | | | | MY CONCERNED IS 5X4 EX-FILTRATION TRENCHLENGTH IS | | REDUCED BY APPROXIMATELY 50%.IF IT IS LESS THAN 10 % | | IT ISO.K FOR ME. THEREFORE, ENGINEERING SERVICES & | | SFWMD NEED TO REREVIEW THAT IS WHAT I SUGGESTEDTO | | PETER AQUART. | | | | RASIK CHOKSHI805-6723 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
4 |
Status |
N |
Date |
2007-04-19 |
|
|
Cont ID |
|
Sent By |
rchokshi |
Date |
2007-04-19 |
Time |
11:20 |
Rev Time |
0.00 |
Received By |
rchokshi |
Date |
2007-04-19 |
Time |
11:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
3 |
Status |
P |
Date |
2007-02-09 |
|
|
Cont ID |
|
Sent By |
rchokshi |
Date |
2007-02-09 |
Time |
08:43 |
Rev Time |
0.00 |
Received By |
rchokshi |
Date |
2007-02-09 |
Time |
08:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
P |
Date |
2007-01-04 |
|
|
Cont ID |
|
Sent By |
rchokshi |
Date |
2007-01-04 |
Time |
16:04 |
Rev Time |
0.00 |
Received By |
rchokshi |
Date |
2007-01-04 |
Time |
16:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
F |
Date |
2006-11-03 |
|
|
Cont ID |
|
Sent By |
rchokshi |
Date |
2006-11-03 |
Time |
13:47 |
Rev Time |
0.00 |
Received By |
rchokshi |
Date |
2006-11-03 |
Time |
13:11 |
Sent To |
|
|
Notes |
2006-11-03 13:46:55 | PLEASE PROVIDE FOLLOWING INF: | | 1. CITY OF WPB STANDARD NOTES ON DRAWING FOR PARKING, | | HANDICAP PARIKG PAINTED PER CITY CODES ETC.,, MUST MEET | | PER ADA,,SIDEWALK WIDTH, ITS SLOPE, | | 2. DUMPSTER LOCATION ON DWG, MUST BE ACCESSIBLE FOR | | PICKUP TRUCK. | | 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD , | | SIDEWALK ELEVATION MUST MEET FL BLDG CODE, PLEASE SHOW | | ON THE DRAWINGS. | | 4. PLEASE PROVIDE A COPY OF SFWMD PERMIT | | 5. PLEASE SHOW HOW DID YOU CALCULATE LENGTH OF | | EXFILTRATION TRENCH LENGTH,WHAT IS FACOR OF | | SAFETY?,WHAT CRITERIA YOU ASSUME , LIKE 1" OVER ENTIRE | | SITE OR 2.5"CRITERIA, WHICH CRITERIA YOU USED. | | PLEASE SHOW CALCULATIONS. | | 6. WHAT IS THE SITE AREA, PERVIOUS AREA, IMPERVIOUS | | AREA, PLEASE SHOW RUNOFF CAL & CRITERIA YOU USED. 7. | | STORM WATER FROM CONTROL STRUCTURE GOES TOBANYAN | | BLVD, THERE IS ANOTHER CROSSING STORM WATER PIPE BEFORE | | YOU CONNECT TO THE STORM WATER PIPE., THERE ARE | | COUPLE OF STORM PIPIE RUNNING ON BANYAN NOT SHOW | | CLEARLY.PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR | | SITE SO, WE CAN DETERMINE THE BEST PIPE TO CONNECT WITH | | THE STORM WATER FROM ALL OTHER STORM WATER PIPES. | | PLEASE SHOW DETAIL OF THE CONTROL STRUCTURES WITH | | ELEVATIONS. | | | | RASIK CHOKSHI 805-6723 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
21 |
Status |
P |
Date |
2009-09-22 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2009-09-22 |
Time |
14:16 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2009-09-22 |
Time |
11:40 |
Sent To |
|
|
Notes |
2009-09-22 14:16:08 | *****REVISION #14F, APPROVED***** | | | | THE SUBMITTED MECHANICAL PLAN SHEET (M2-3.0) WAS | | REVIEWED, HOWEVER NO FIRE-STAMPING NECESSARY. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
20 |
Status |
P |
Date |
2009-04-03 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2009-04-03 |
Time |
08:59 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2009-04-03 |
Time |
08:58 |
Sent To |
|
|
Notes |
2009-04-03 08:59:42 | REVISION 24A | | | | 1. NO COMMENT BY THIS OFFICE. | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
19 |
Status |
P |
Date |
2009-03-26 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2009-03-26 |
Time |
16:28 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2009-03-26 |
Time |
15:33 |
Sent To |
B |
|
Notes |
2009-03-26 16:28:29 | *****REVISION #25A, DATED 02/05/09, APPROVED***** | | | | | | REVISED PLAN SHEETS LS0.0, LS1-1.0 THRU LS1-6.1, AND | | A8-0.2 WERE STAMPED, INITIALED, AND DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
18 |
Status |
P |
Date |
2009-01-21 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2009-01-21 |
Time |
09:09 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2009-01-21 |
Time |
09:04 |
Sent To |
|
|
Notes |
2009-01-21 09:09:01 | REVISON 23A | | APPROVED PROVISO | | | | | | 1. PROPER TENANT SEPARATION REQUIRED BETWEEN MUSEUM | | AREA TO BE BUILT UNDER SEPARATE PERMIT AND OTHER AREAS | | OF THE BUILDING. | | | | 2. WHEN PHOT MUSEUM PLANS ARE SUBMITTED THEY ARE TO | | ILLUSTRATE ALL EMERGENCY SYSTEMS AND DEVICES. THESE | | SYSTEMS AND DEVICES INCLUDE FIRE SPRINKLERS, FIRE | | ALARM, ILLUMINATED EXIT SIGNS, EMERGENCY LIGHTS, | | PORTABLE FIRE EXTINGUISHERS AND INTERIOR FINISH | | CLASSIFICATIONS FOR WALLS AND CEILINGS. | | | | 3. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE | | SPRINKLER OR FIRE ALARM SYSTEM REMODEL. | | | | 4. ALL NEW FIRE DAMPERS AND ASSOCIATED EQUIPMENT SHALL | | BE DROP TESTED TO ENSURE PROPER OPERATION. | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF PREVENTION |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
17 |
Status |
P |
Date |
2009-01-21 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2009-01-21 |
Time |
07:36 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2009-01-21 |
Time |
07:36 |
Sent To |
|
|
Notes |
2009-01-21 07:39:29 | REVISION 20 B | | | | 1. THE 500 GALLON DOUBLE WALLED DIESEL FUEL TANK | | ILLUSTRATED ON PAGE M1-1.3 IS TO BE PROPERLY LABELED. | | LABELS SHALL INCLUDE PRODUCT NAME, NO SMOKING, | | COMBUSTIBLE, AND NFPA 704 DIAMOND. | | | | 2. THE INSTALLATION OF THE DIESEL FUEL TANK ON PAGE | | M1-1.3 SHALL COMPLY WITH NFPA 30, THE FLAMMABLE AND | | COMBUSTIBLE LIQUIDS CODE. | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
16 |
Status |
P |
Date |
2008-12-01 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2008-12-01 |
Time |
13:44 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2008-12-01 |
Time |
13:42 |
Sent To |
|
|
Notes |
2008-12-01 13:44:16 | CITY CENTER, 401 CLEMATIS STREET | | REVISION 21-A | | | | 1. NO COMMENT PROVIDED BY THE FIRE RESCUE DEPARTMENT | | REGARDING THIS REVIEW. | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
15 |
Status |
P |
Date |
2008-11-05 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2008-11-05 |
Time |
12:54 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2008-11-05 |
Time |
12:52 |
Sent To |
|
|
Notes |
2008-11-05 12:54:23 | 1. SUBJECT TO FIELD INSPECTION AND APPROVAL. | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | 804-4724 PHONE | | 804-4774 FAX |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
14 |
Status |
P |
Date |
2008-05-05 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2008-05-05 |
Time |
09:07 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2008-05-05 |
Time |
09:06 |
Sent To |
|
|
Notes |
2008-05-05 09:06:55 | 1. SUBJECT TO FIELD INSPECTION AND APPROVAL. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
13 |
Status |
F |
Date |
2008-04-09 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2008-04-09 |
Time |
16:52 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2008-04-09 |
Time |
16:52 |
Sent To |
|
|
Notes |
2008-04-09 17:06:18 | REVISION 15A | | | | 1. THE ELECTRICAL PLAN REVIEWER INDICATES SEVERAL | | PROBLEMS WITH REVISION 15A. THESE PROBLEMS NEED TO BE | | DISCUSSED AND CORRECTED ON THE NEXT REVISION TO ENSURE | | THAT THE REVISIONS DISPLAYED ON 15A CAN BE APPROVED. | | | | 2. THE ENTIRE BUILDING SHALL HAVE SUFFICIENT EMERGENCY | | LIGHTING EQUIPMENT AND ILLUMINATED EXIT SIGNS SO AS TO | | DIRECT PERSONS TO THE EXITS. ALL EQUIPMENT INSTALLED AS | | EMERGENCY LIGHTING AND EXIT SIGNS SHALL BE INSTALLED IN | | ACCORDANCE WITH NFPA 70, THE NATIONAL ELECTRIC CODE AND | | NFPA 101 THE LIFE SAFETY CODE, CHAPTER 7. | | | | 3. PLEASE CORRECT ANY CIRCUITING PROBLEMS SUCH AS | | MISSING OR ABSENT CIRCUITRY. | | | | 4. PLEASE REVIEW REVISION 15A AND MAKE ANY NECESSARY | | CORRECTIONS. COORDINATION OF FIRXTURES AND CIRCUITRY IS | | NECESSARY AS THE PROJECT CONTINUES TO MOVE FORWARD. | | | | 5. ALL EXIT SIGNS AND EMERGENCY LIGHTING EQUIPMENT WILL | | BE TESTED ON NORMAL AND BACK-UP POWER WHEN THE BUILDING | | IS NEARER TO COMPLETION. | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
12 |
Status |
P |
Date |
2008-02-19 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2008-02-19 |
Time |
14:58 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2008-02-19 |
Time |
14:53 |
Sent To |
|
|
Notes |
2008-02-19 14:58:15 | 1. THE WORDING ON NOTE # 26 ON DRAWING FAO-1 HAS BEEN | | REVISED WITH THE CORRECT LANGUAGE. THE WORD DISPLAY HAS | | BEEN SUBSTITUTUED WITH THE WORD TRANSMIT. | | | | 2. NO OTHER DRAWINGS PROVIDED EXCEPT FA0-1. | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | 804-4709 PHONE | | 804-4774 FAX |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
11 |
Status |
P |
Date |
2007-12-24 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2007-12-24 |
Time |
12:23 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2007-12-24 |
Time |
12:06 |
Sent To |
|
|
Notes |
2007-12-24 12:20:54 | 1. THE WORDING ON THE REVISED NOTE # 26 IS INCORRECT. | | THE WORD DISPLAY SHOULD READ TRANSMIT. FOUR DISTINCT | | SIGNALS WATERFLOW, GENERAL ALARM, TROUBLE AND | | SUPERVISORY SHALL BE TRANSMITTED TO THE CENTRAL STATION | | APPROVED FOR CENTRAL STATION SERVICE. | | | | 2. THE REVISED DRAWINGS THAT REFLECT A COMPLETE SMOKE | | DETECTION SYSTEM FOR THE BUILDING SHALL BE SUBMITTED TO | | THE CONSTRUCTION SERVICES DEPARTMENT AS A SEPARATE | | ENTITY AS SHOP DRAWINGS. THESE SHOP DRAWINGS SHALL | | PROVIDE PRODUCT INFORMATION CUT SHEETS, BATTERY | | CALCUALTIONS, RISER DIAGRAMS AND FLOORS PLANS | | ILLUSTRATING DEVICE PLACEMENT FOR THE ENTIRE FIRE ALARM | | SYSTEM. | | | | 3. THERE APPEARS TO BE SOME CONFUSION WITH REGARDS TO | | THE FIRE RATING REQUIRED FOR THE FIRE COMMAND ROOM. THE | | FIRE COMMAND ROOM IS REQUIRED TO BE SEPARATED FROM | | OTHER AREAS OF THE BUILDING BY AT LEAST ONE HOUR FIRE | | RATED CONSTRUCTION. SOME DOCUMENTATION PROVIDED WITH | | DRAWINGS INDICATES THAT NO FIRE DAMPER IS NEEDED FOR | | THE ROOM SINCE IT IS NOT FIRE RATED. THIS IS INCORRECT. | | NFPA 1, SECTION 11.9.2 REQUIRES THAT "THE EMERGENCY | | COMMAND CENTER SHALL BE SEPARATED FROM THE REMAINDER OF | | THE BUILDING BY A FIRE BARRIER HAVING A FIRE RESISTANCE | | RATING OF NOT LESS THAN 1 HOUR". | | | | APPROVED PROVISIO: | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREA OF FIRE PREVENTION | | 804-4709 PHONE | | 804-4774 FAX |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
10 |
Status |
F |
Date |
2007-10-23 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2007-10-23 |
Time |
12:31 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2007-10-23 |
Time |
12:06 |
Sent To |
|
|
Notes |
2007-10-23 12:31:09 | 1. SOME SUGGESTED IMPROVED WORDING IS PROVIDED FOR NOTE | | # 26 ON PAGE FAO.1. "THE FIRE ALARM SYSTEM SHALL BE | | ABLE TO TRANSMIT THE FOLLOWING ALARMS TO THE UL LISTED | | CENTRAL STATION APPROVED FOR CENTRAL STATION SERVICE. | | | | A) WATERFLOW | | B) GENERAL ALARM | | C) SUPERVISORY SIGNAL | | D) TROUBLE SIGNAL | | | | 2. ANY SPECIAL LOCKING ARRANGEMENTS ON EXIT DOORS SHALL | | COMPLY WITH WITH CHAPTER 7 OF THE LIFE SAFETY CODE, | | 101. | | | | 3. THE PLANS SEEM TO SUGGEST "PROVIDE AND INSTALL SMOKE | | DETECTORS PER FLORIDA MECHANICAL CODE (FMC) 607.5.4.1 | | AT EACH SMOKE DAMPER. SINCE NO FIRE ALARM SYSTEM SHOP | | DRAWINGS HAVE BEEN SUBMITTED IT IS UNKNOWN IF A | | COMPLETE SMOKE DETECTION SYSTEM IS TO BE INSTALLED | | WITHIN THE BUILDING. IN FMC 607.3.2.1 PROVIDES | | INFORMATION ON HOW SMOKE DAMPER ACTUATION METHODS CAN | | BE PERFORMED USING 1-5. PLEASE ADVISE THE MECHANICAL | | SECTION OF THE CONSTRUCTION SERVICES DEPARTMENT AND | | THIS OFFICE IF A COMPLETE SMOKE DETECTION SYSTEM IS | | PLANNED FOR THE BUILDING AND IT THIS SYSTEM IS PLANNED | | TO ACTUATE THE SMOKE DAMPERS. PLEASE COORDINATE ALL | | FIRE/ SMOKE DAMPERS AND FIRE DAMPERS WITH THE | | MECHANICAL DIVISION OF THE CONSTRUCTION SERVICES | | DEPARTMENT. | | | | | | MIKE CARSILLO, BATTALION CHIEF | | 804-4709 PHONE | | 804-4774 FAX |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
9 |
Status |
F |
Date |
2007-09-04 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2007-09-04 |
Time |
11:22 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2007-09-04 |
Time |
10:51 |
Sent To |
|
|
Notes |
2007-09-04 11:21:59 | 1. STREET LIGHTS INSTALLATIONS ON PAGE LL.1 SHALL NOT | | INTERFERE WITH ANY FIRE SAFETY EQUIPMENT OR DEVICES. | | | | 2. SOME REVISION CLOUDS ON PAGE A0.3 ARE EMPTY OF | | DETAILS OR DIAGRAMS. | | | | 3. ENSURE THAT BOLLARD THAT IS PLACED AT GROUND LEVEL | | OUTSIDE STAIR # 4 DOES NOT INTERFERE WITH OPENING OF | | THE DOOR OR ANY EXIT DISCHARGE. | | | | 4. HORIZONTAL LINES APPEAR TO TRAVEL THROUGH STAIR # 9 | | ON PAGE E1-1.2. PLEASE PROVIDE DETAILS. | | | | 5. CHAIN LINK FENCE AND PARKING DISPLAYED ON PAGE | | E1-6.3 SHALL NOT INTERFERE WITH ANY EXIT ACCESS, | | EXITING FROM THE UPPER LEVEL OF THE PARKING GARAGE. | | | | 6. ELEVATOR LOBBY WARNING SIGNS "IN CASE OF FIRE, DO | | NOT USE THE ELEVATORS" MUST BE CONSIDERED ALONG WITH | | THE REVISIONS TO THESE AREAS. | | | | 7. ALL STAIRS IDENTIFIED WITH REVISION CLOUDS ON A7.1.4 | | AND A7.16 SHALL COMPLY WITH THE MINIMUM BUILDING AND | | FIRE CODE REQUIREMENTS. | | | | 8. AS EXPRESSED PREVIOUSLY ALL CONSTRUCTION AND SYSTEMS | | AND DEVICES ARE SUBJECT TO FIELD INSPECTION. | | | | 9. PLEASE BE ADVISED THAT REVISONS TO THE SOME FEATURES | | OF THE BUILDING MAY HAVE A NEGATIVE IMPACT ON FIRE | | SPRINKLER, ELECTRICAL, MECHANICAL, AND PLUMBING | | SYSTEMS. REVISIONS WILLBE NECESSARY FOR OTHER SHOP | | DRAWINGS IF NECESSARY. | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | 804-4709 PHONE | | 804-4774 FAX |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
8 |
Status |
P |
Date |
2007-08-01 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2007-08-01 |
Time |
13:22 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2007-08-01 |
Time |
13:03 |
Sent To |
|
|
Notes |
2007-08-01 13:22:22 | 1. THE CARBON MONOXIDE SENSORS DISPLAYED ON THE | | MEHANICAL SHEETS ARE TO BE INSTALLED PER MANUFACTURER'S | | REQUIREMENTS. WHAT SET POINTS ARE THE CARBON MONOXIDE | | DETECTORS GOING TO BE SET AT. THESE DEVICES WILL NEED | | TO BE TESTED WITH CALIBRATION GAS AFTER INSTALLATION. | | PLEASE PROVIDE PRODUCT APPROVALS AND CUT SHEETS FOR | | THESE DEVICES. PLEASE PROVIDE DETAILS ON CARBON | | MONOXIDE SYSTEM. THE INSTALLATION LOCATIONS FOR THESE | | DEVICES SHALL NOT EXCEED MAXIMUM COVERAGE AREAS OR | | SPACING REQURIEMENTS. | | | | 2. ALL ELECTRICAL REVISIONS TO COMPLY WITH NFPA 70, THE | | NATIONAL ELECTRICAL CODE. | | | | 3. THE INSTALLATION OF THE CHAIN LINK FENCE FOR THE | | FUTURE GENERATOR AND ANY PARKING SPACES SHALL NOT | | INTERFERE WITH ANY EXIT ACCESS TO STAIR # 4. | | | | 4. THE OPERATION OF EMERGENCY LIGHTING EQUIPMENT EVEN | | IF THEY ARE EQUIPPED WITH OCCUPANCY SENSORS SHALL | | COMPLY WITH THE OPERATIONAL REQUIREMENTS OF CHAPTER | | SEVEN OF THE LIFE SAFETY CODE. | | | | 5. NO EMERGENCY PHOTOMETRICS DISPLAYED IN FIRE COMMAND | | CENTER ON PAGE E-8-1.1. | | | | 6. PLEASE BE ADVISED THAT LARGE BATHROOMS MUST BE | | EQUIPPED WITH EMERGENCY LIGHTING. LARGE RESTROOMS CAN | | BE EXTREMELY DARK WHEREBY ACCESS TO THE INGRESS/EGRESS | | DOOR FROM THE ROOM CAN BE IMPOSSIBLE. | | | | | | APPROVED PROVISO | | | | MIKE CARSILLO, BATTALION CHIEF | | 804-4709 PHONE | | 804-4774 FAX |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
7 |
Status |
P |
Date |
2007-06-26 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-06-26 |
Time |
15:52 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-06-26 |
Time |
15:46 |
Sent To |
|
|
Notes |
2007-06-26 15:52:11 | *****REVISION OF 05/08/07 APPROVED***** | | | | | | REVISED FIRE ALARM AND FIRE SPRINKLER STAMPED, | | INITIALED, AND DATED 5/31/07 AS PER ROBERT BROWN. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
6 |
Status |
P |
Date |
2007-04-11 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2007-04-11 |
Time |
09:39 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2007-08-01 |
Time |
13:01 |
Sent To |
|
|
Notes |
2007-04-11 09:38:08 | 1. ON PAGE E5-1.1 GA PLANS MAKE REFERENCE TO A FIVE | | HUNDRED GALLON, DOUBLE WALL SUB-BASE FUEL TANK. PLEASE | | INDICATE WHAT UL LISTING CAN BE EXPECTED FOR THIS FUEL | | TANK. PLEASE PROVIDE PRODUCT APPROVALS AND INFORMATION | | TO THIS OFFICE REGARDING THIS FUEL TANK. | | | | 2. CO SENSORS ARE ILLUSTRATED ON THE DRAWINGS. PLEASE | | PROVIDE DETAILS ON THESE DEVICES. THESE DEVICES ARE TO | | BE UL LISTED AND PLEASE INDICATE IF THESE DEVICES WILL | | BE FACTORY OR FIELD SET. MOUNTING HEIGHTS, AREA OF | | COVERAGE, AND TESTING PROCEDURES SHALL BE DOCUMENTED TO | | THIS OFFICE. WHAT POWERS THESE DEVICES AND ARE THEY | | EQUIPPED WITH PROVISIONS SHOULD LOSS OF POWER OCCURS. | | IF BATTERY POWER EXISTS, HOW LONG CAN THEY BE EXPECTED | | TO OPERATE. ALSO PLEASE INDICATE WHAT SET POINTS THESE | | DETECTORS WILL BE SET AT. WHAT PARTS PER MILLION WILL | | ACTIVATE THESE SENSORS. | | | | 3. A VISUAL REPRESENTATION OF THE FIREFIGHTERS SMOKE | | CONTROL PANEL NEEDS TO BE ILLUSTRATED AT TIME OF SHOP | | DRAWING SUBMITTAL. THE SMOKE CONTROL PANEL SHALL | | DISPLAY A GRAPHIC REPRESENTATION OF THE BUILDING AND | | THE SYSTEM TO INCLUDE HAND, ON, AND AUTO CONTROLS. | | | | 4. PLEASE PROVIDE THIS OFFICE IN WRITING WHEN THE | | TEMPORARY STANDPIPE SYSTEM WILL BE INSTALLED AT THE | | PARKING GARAGE AND THE FUTURE BUILDING. CERTAIN CODE | | REQUIREMENTS MANDATE THIER INSTALLATION WHEN THEY REACH | | CERTAIN HEIGHT OR FLOOR ARRANGEMENTS. | | | | | | MIKE CARSILLO, BATTALION CHIEF OF FIRE PREVENTION | | 804-4709 PHONE | | 804-4774 FAX |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
5 |
Status |
P |
Date |
2007-03-01 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-03-01 |
Time |
12:46 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-03-01 |
Time |
12:46 |
Sent To |
B |
|
Notes |
2007-03-01 12:53:38 | *****APPROVED***** | | | | | | REVISIONS (02/19/07) TO PLAN SHEETS A1-1.0, LS1.0. | | LS1.GA.1, LS1.GA.2, AND LS1.GA.3 WERE STAMPED, | | INITIALED, AND DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2007-02-21 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-02-21 |
Time |
16:21 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-02-21 |
Time |
16:21 |
Sent To |
|
|
Notes |
2007-02-21 16:24:12 | *****APPROVED***** | | | | | | LIFE SAFETY, FIRE ALARM, AND FIRE SPRINKLER SHEETS WERE | | STAMPED, INITIALED, AND DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2007-01-26 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2007-01-26 |
Time |
13:17 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2007-01-26 |
Time |
13:17 |
Sent To |
|
|
Notes |
2007-01-26 13:36:28 | 1. SIAMESE CONNECTION DISPLAYED ON PAGE FP1-1.2 IS NOT | | NEEDED AND SHOULD BE STRICKEN FROM THE PLANS. THE PLAN | | REVIEW PERMIT RESPONSES INCLUDE NOW THREE SIAMSE | | CONNECTIONS INSTEAD OF THE FIVE PREVIOUSLY SHOWN. 2. NO | | FIRE ALARM EQUIPMENT SHOWN IN MACHINE ROOM A6.102 ON | | PAGE FA1-6.0. THIS IS AN EXISTING COMMENT. | | 3. ONLY TWO FIRE ALARM STROBES ARE PRESENT IN THE | | GARAGE ON PAGE FA1-6.0. THIS IS ALSO AN EXISTING | | COMMENT. | | 4. SMOKE DETECTOR STILL MISISNG IN VOICE DATA CLOSET | | C3.104 ON PAGE FA1-3.0. THIS IS AN EXISTING COMMENT. 5. | | A VISUAL REPRESENTATION OF THE SMOKE CONTROL PANEL | | SHALL BE SUBMITTED AT TIME OF SHOP DRAWING SUBMITTAL. | | THIS SMOKE CONTROL PANEL SHALL DISPLAY A GRAPHIC | | REPRESENTATION OF THE BUILDING SYSTEM TO INCLUDE HAND, | | ON, AND AUTO CONTROLS. | | 6. ITEMS # 9, 11, 12, 20, 23, COULD NOT BE CLEARED FRON | | LIST. SOME ITEMS CAN BE PICKED UP AT SHOP DRAWING | | SUBMITAL TIME SO LONG AS THEY ARE PROPERLY IDENTIFIED. | | 7. ALL ELECTRICAL PLAN REVIEW COMMENTS ARE TO BE | | PROPERLY SATISFIED WITH THE ELECTRICAL PLAN REVIEWER. | | 8. PLEASE REMEMBER THAT THE ELVATION OF FLOOR LEVELS ON | | BOTH SIDES OF AN EXIT DOOR CANNOT EXCEED 1/2 ". | | | | PLANS WILL BE APPROVED PROVISO AND ALL WORK AT THE SITE | | IS SUBJECT TO FIELD INSPECTION AND APPROVAL. THIS | | APPROVAL DOES NOT RELLIEVE RESPONSIBLE PERSONS OR FIRMS | | FROM OBTAINING ANY OTHER GOVERNMENTAL REVIEWS OR | | APPROVALS. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2006-12-22 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2006-12-22 |
Time |
11:22 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2006-12-22 |
Time |
08:45 |
Sent To |
|
|
Notes |
2006-12-22 11:22:46 | 1. ON PAGE C-16 AT LEAST FIVE FIRE DEPARTMENT | | CONNECTIONS ARE SHOWN. AS STATED PREVIOUSLY, THAT MANY | | FIRE DEPARTMENT CONNECTIONS ARE NOT NEEDED. | | 2. SEVERAL AREAS ON PAGE FP1-1.1 ARE ABSENT OF FIRE | | SPRINKLER PROTECTION. | | 3. SEVERAL AREAS ON PAGE FP1-1.2 ARE ABSENT OF FIRE | | SPRINKLER PROTECTION. | | 4. STAIR # 2 ON PAGE FP1-2.1 IS MISSING THE FIRE | | VALVE. | | 5. FIRE SPRINKLER HEADS MISSING IN VOICE DATA A2.105 | | AND UTILITY ROOM A2105.1 ON PAGE FP1-2.1. | | 6. CLOSETS A3.110.1 AND A3.118.1 ARE ABSENT OF FIRE | | SPRINKLER HEADS ON PAGE FP1-3.1. | | 7. SERVER ROOM A4.416 SHOWN ON PAGE FP1-4.1 IS EQUIPPED | | WITH AN FM 200 SYSTEM. THIS ROOM IS LOCATED IN A | | SPRINKLERED BUILDING AND SHALL CONTAIN FIRE SPRINKLER | | PROTECTION SERVED BY A SEPARATE VALVE PER THE | | REQUIREMENTS OF NFPA 75, THE STANDARD FOR THE | | PROTECTION OF INFORMATION TECHNOLOGY EQUIPMENT. SECTION | | 8-1.1 AND 8.1.3 PROVIDES GUIDANCE ON THESE | | REQUIREMENTS. | | 8. FIRE SPRINKLER HEADS NOT SHOWN IN CAFE C1.401 ON | | PAGE FP1-1.0. | | 9. EXIT DOOR NEAR VOICE DATA C4.108 SWINGS IN THE WRONG | | DIRECTION ON PAGE ID2-4.2. | | 10. "NO EXIT" SIGNS SHALL BE INSTALLED ON THE DOUBLE | | DOORS TO SERVER ROOM NEAR STAIR # ON PAGE LS1-4.1. | | THESE DOORS ARE IN CLOSE PROXIMITY TO THE EXIT DOOR. | | 11. ONLY TWO FIRE ALARM STROBES EXIST IN THE PARKING | | AREA SHOWN ON PAGE FA1-6. | | 12. NO FIRE ALARM DEVICES EXIT IN MACHINE ROOM A6.102 | | ON PAGE FA1-6. PLEASE EXPLAIN. | | 13. MANUAL PULL STATION LOCATED IN VOICE DATA CLOSET | | C4.108 ON PAGE FA1-4.0. THE MANUAL PULL STATION SHOULD | | BE LOCATED NEXT TO STAIR. | | 14. VOICE DATA C3.104 ON PAGE FA1-3 IS MISSING SMOKE | | DETECTOR LIKE OTHER SIMILAR SPACES. PLEASE ADVISE. | | 15. MANUAL PULL STATION MISSING FROM STAIR # 2 ON PAGE | | FA1-2. | | 16. NO SMOKE DETECTOR PRESENT IN VOICE DATA C1.102 BUT | | EXIST IN SIMILAR SPACES ON PAGE FA1-1. | | 17. NO EXIT SIGNS APPEAR TO EXIST IN PROGRAM MEETING | | ROOM C3.306 WHICH CONTAINS FIFTY SEATS ON PAGE E2-3.2. | | 18. AN EXIT SIGN IN THE PROGRAM/MEETING ROOM ON PAGE | | E2-3.2 IS CONFUSING. IF THE SIGN IS LOCATED INSIDE THE | | ROOM, THE EXIT SIGN IS SWINGING IN THE WRONG DIRECTION. | | IF THE SIGN IS OUTSIDE THE ROOM OTHER EXIT SIGNS ARE | | VAILABLE TO DIRECT PERSONS. PLEASE ADVISE. | | 19. THE EXIT SIGN FROM PLANNING INTO THE ENTRY/WAITING | | AREA STILL APPEARS CONFUSING. ONCE IN THE ENTRY/WAITING | | AREA WHAT IS THE PREFERRED EXIT TRAVEL DIRECTION | | ANTICIPATED ON PAGE E2-2.1. PLEASE PROVIDE MORE | | DETAILS. | | 20. EXIT SIGNS STILL APPEAR TO BE MISSING FROM BACK OF | | HOUSE OF THE COMMISSION CHAMBERS ON PAGE E2-2.1. | | 21. NO ILLUMINATED EXIT SIGNS DISPLAYED IN LARGE | | MECHANICAL ROOM DISPLAYED ON PAGE ON PAGE E1-1.3 | | 22. SOME ISSUES REMAIN WITH THE LIFE SAFETY SHEETS AND | | THE ARCHITECTURAL DRAWINGS AS THEY RELATE TO WALL | | RATINGS. PLEASE ENSURE THAT THEY MIRROR ONE ANOTHER. | | 23. COULD NOT LOCATE FLOOR LEVEL INFORMATION AS IT | | RELATES TO EXIT DOORS. PLEASE SEE NFPA 101, THE LIFE | | SAFETY CODE, SECTION 7.2.1.3. | | 24. COULD NOT LOCATE A VISUAL ON THE FIREFIGHTERS SMOKE | | CONTROL PANEL ONLY A DESCRIPTION OF WHAT IT WILL LOOK | | LIKE. | | 25. THE TEMPORARY STANDPIPE SYSTEM REQUIREMENT COULD | | NOT BE LOCATED ON THE LIFE SAFETY OR FIRE SPRINKLER | | SYSTEM DRAWINGS. | | 26. ALL BUILDING, MECHANICAL, ELECTRICAL, PLUMBING | | COMMENTS ARE TO BE SATISFIED. | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION OFFICER | | 804-4709 PHONE | | 804-4774 FAX | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2006-10-27 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2006-10-27 |
Time |
11:07 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2006-10-27 |
Time |
09:19 |
Sent To |
|
|
Notes |
2006-10-27 11:07:29 | 1. STAIR SUMMARY CHART NEEDED ON PAGE LS0.0. THIS CHART | | SHALL IDENTIFY ALL STAIRS, WIDTHS, AND EXIT | | CAPACITIES. | | 2. STAIRWELL IDENTIFICATION SIGNS SHALL BE PROVIDED ON | | THE SIGNAGE LEGEND DISPLAYED ON PAGE LS0.0. THESE | | STAIRWELL IDENTIFICATION SIGNS SHALL IDENTIFY THE | | STAIR, TERMINUS, TOP AND BOTTOM, FLOOR NUMBER, ETC. | | 3. STAIR # 5 ON PAGE LS1-1.0 HAS STILL NOT BEEN | | CORRECTED. PLEASE MOVE OR REMOVE WALL SECTION DIRECTLY | | IN FRONT OF EXIT STAIR DOOR TO ALLOW FOR PROPER EXIT | | DISCHARGE. | | 4. EXIT SIGNS APPEAR TO BE MISSING FROM SHEET LS1-1.1. | | PLEASE SEE BACK OF HOUSE AREA IN COMMISSION CHAMBERS. | | OTHER AREAS ALSO ABSENT OF SIGNS. CONFLICTS APPEAR TO | | EXIST BETWEEN LS1-1.1 AND E2-1.1. | | 5. EXIT SIGN NOTED DIRECTLY INFRONT OF ELECTRICAL ROOM | | DOOR ON PAGE E2-1.2. | | 6. EXIT SIGN IN CENTER OF STAIR # 9 ON PAGE E2-1.2. | | 7. EXIT SIGN WITH DIRECTIONAL ARROWS DIRECTS PERSONS TO | | GRAND STAIR ON PAGE E2-2.1. | | 8. EXIT SIGN MISSING IN FRONT OF STAIR DOOR # 7 ON PAGE | | E2-2.2. | | 9. EXIT SIGN CONTAINED WITHIN STAIR # 9 NOT INFRONT OF | | STAIR DOOR ON PAGE E2-2.2. | | 10. EXIT SIGN CONTAINED WITHIN STAIR # 9 NOT INFRONT OF | | STAIR DOOR ON PAGE E2-3.2. | | 11. EXIT SIGN INSTALLED NEAR WALL OF STAIR # 9 NOT NEAR | | DOUBLE DOORS ON PAGE E2-3.2. | | 12. NO EXIT MARKINGS COULD NOT BE LOCATED ON PAGES | | E2-4.0 AND E2-4.1. | | 13. EXIT SIGN MARKINGS MISSING FROM PAGE E2-4.2. | | 14. SAME CONDITION EXISTS ON PAGE E2-5.1. | | 15. PLEASE EXPLAIN FACP CALL OUT IN VOICE DATA ROOM ON | | PAGE E3-1.0. | | 16. SEPARATE PLANS AND PERMITS REQUIRED FOR THE | | INSTALLATION OF THE FIRE ALARM SYSTEM. FIRE ALARM | | SYSTEM SHALL BE UL LISTED FOR CENTRAL STATION SERVICE. | | PLEASE EXPLAIN "PROVIDE ZONED EMERGENCY VOICE | | EVACUATION"ON PAGE FA1-1. SYSTEM TO COMPLY WITH NFPA | | 72, THE NATIONAL FIRE ALARM CODE, 2002 EDITION. | | 17. EXIT SIGN MISSING NEAR STAIR # 2 ON PAGE E1-6.1. | | 18. TRAINING ROOM AT A 4 AND 5 MISSING FIRE ALARM | | NOTIFICATION APPLIANCES ON PAGE FA1-4. | | 19. PLEASE EXPLAIN NOTE # 3 FIRE PROTECTION DESIGN | | CRITERIA INFORMATION BOX ON PAGE FP0-1.0. | | 20. ON PAGE FP1-1.0 AT LEAST FIVE FIRE DEPARTMENT | | CONNECTIONS ARE SHOWN. AGAIN ALL OF THESE ARE NOT | | NECESSARY. | | 21. SOME FIRE SPRINKLER DRAWINGS ARE ABSENT OF FIRE | | SPRINKLER HEADS. IT IS DIFFICULT TO DETERMINE IF 100 % | | COVERAGE IS PROVIDED DUE TO INSUFFICIENT INFORMATION. | | 22. ON PAGE FP1-2.1 KEY NOTE # 5 "PROVIDE WATER CURTAIN | | FOR GLASS AREAS LOCATE SPRINKLERS 6'-0 ON CENTER". | | PLEASE ILLUSTRATE WATER CURTAIN ARRANGEMENT. | | 23. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FM 200 | | FIRE SUPPRESSION SYSTEM PLANNED FOR THE SERVER ROOM ON | | PAGE FP1-4.0. | | 24. DOUBLE DETECTOR CHECK VALVE ASSEMBLY DETAIL SHOWN | | ON PAGE FP2-1.0 DOES NOT INDICATE TAMPER SWITCHES, | | CHAIN AND LOCK. | | 25. FLOOR CONTROL VALVE ASSEMBLY DETAIL SHOWN ON PAGE | | FP3-1.0 SHALL BE EQUIPPED WITH 2 1/2 TO 1 1/2 | | REDUCERS. | | 26. PLEASE DISPLAY HEIGHT DIMENSIONS FROM ROOF TO | | EXHAUST FAN ON PAGE M502.0. | | 27. COULD NOT LOCATE WHAT THE FIREFIGHTERS SMOKE | | CONTROL PANEL FOR THE ATRIUM SYSTEM LOOKS LIKE WITH THE | | MECHANICAL DRAWINGS. | | 28. ALSO COULD NOT LOCATE A SEQUENCE OF OPERATIONS | | MATRIX FOR THE ATRIUM MECHANICAL SYSTEM IN THE | | MECHANICAL DRAWINGS. | | 29. NO EXIT SIGN NOTED AT THE BACK LOADING DOCK DOUBLE | | DOORS ON PAGE LS1-1.2. | | 30. ALL MECHANICAL, ELECTRICAL, AND STORAGE ROOM DOORS | | ARE TO BE SMOKE RESISTANT. PLEASE ESNURE THAT THE PLANS | | ARE REVISED TO REFLECT THIS CHANGE. | | 31. OCCUPANT LOAD TAG FOR GROUP B BUSINESS ON PAGE | | LS1-2.0 SHOULD READ 25 OCCUPANTS INSTEAD OF 40 | | OCCUPANTS. | | 32. PROGRAM MEETING ROOM ON PAGE LS1-3.2 THAT CONTAINS | | 50 SEATS DOES NOT CONTAIN ANY EXIT SIGNS. | | 33. OCCUPANT LOAD TAG FOR GROUP B BUSINESS OCCUPANCY ON | | PAGE LS1-4.0 SHOULD READ 270 PERSONS NOT 278 | | OCCUPANTS. | | 34. ILLUMINATED EXIT SIGN IN SERVER ROOM LOCATED ON | | PAGE LS1-4.1 IS NOT LOCATED INFRONT OF ANY EXIT DOOR. | | 35. EXIT SEPARATION LINE IN TRAINING ROOM ON PAGE | | LS1-4.1 IS DRAWN TO A DOOR ABSENT OF AN EXIT SIGN. | | 36. A FIRE EXTINGUISHER CABINET IS LOCATED ON PAGE | | LS1-4.1 NEAR MEN'S ROOM BUT DOES NOT APPEAR TO BE | | AFFIXED TO ANYTHING. | | 37. IT APPEAR THAT A FIRE EXTINGUISHER CABINET IS | | MOUNTED ON A DOOR TO THE SERVER ROOM ON PAGE LS1-4.1. | | 38. EXIT SIGN ON PAGE LS1.6.1 IS NOT LOCATED NEAR STAIR | | DOOR. | | 39. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS | | FOR ALL HANDRAILS, GUARDRAILS, TEMPERED GLASS WALLS | | CABLE RAILINGS, AND PRE-ENGINEERED RAILINGS. | | 40. ON PAGE ID2-4.2 A SOLID WALL EXISTS WHERE A DOOR | | EXISTS FOR THE STAIRWELL. | | 41. SEVERAL BUILDING ADDRESSES NOTED ON TWO DIFFFERENT | | ELEVATIONS ON PAGE A4-1.0. THE ADDRESSES SHALL ONLY BE | | LISTED ON THE PROPER ELEVATION. | | 42.ALL PROPOSED WORK STATIONS IN OPEN WORK AREAS | | SHALL PROVIDE FOR A MINIMUM OF AT LEAST 44" INCHES. | | 43. ALL FIRE DAMPERS WILL BE REQUIRED TO BE DROP TESTED | | AFTER INSTALLATION TO ENSURE PROPER OPERATION. | | 44. CHAIRS LOCATED IN ENTRY/WAITING A2.009 MAY | | INTERFERE WITH DOORS ON PAGE ID2-2.0. | | 45. PLEASE EXPLAIN EXIT ACCESS FOR MEETING ROOM ON PAGE | | ID2-3.2 ESPECIALLY NEAR THE FOUR COLUMNS. | | 46. PLEASE PROVIDE A STAIR SECTION FOR THE PROPOSED | | ALTERNATING TREAD STAIRS SHOWN ON THE DRAWINGS. | | 47. PLEASE DISPLAY THE REQUIRED 1/2 MAXIMUM AT ALL EXIT | | DOOR LOCATIONS. | | 48. THE SERVER ROOM SHALL COMPLY WITH NFPA 75, THE | | STANDARD FOR THE PROTECTION OF INFORMATION TECHNOLOGY | | EQUIPMENT. | | 49. SOME OF THE ITEMS IDENTIFIED AT THE PREVIOUS | | REVIEWS STILL SEEM TO EXIST AT THIS PERMIT REVIEW. | | PLEASE REVIEW ALL PREVIOUS COMMENTS PROVIDED BY CITY | | STAFF AND ESNURE THAT PREVIOUS ITEMS IDENTIFIED HAVE | | BEEN CORRECTED AND PROPERLY COORDINATED ON THE | | APPROPRIATE SHEETS. | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION OFFICER | | 804-4709 PHONE | | 804-4774 FAX |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
6 |
Status |
P |
Date |
2007-04-09 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-04-09 |
Time |
14:47 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-04-09 |
Time |
14:46 |
Sent To |
|
|
Notes |
2007-04-09 14:50:50 | REVISION OK - SHT P3-3.0 |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
5 |
Status |
P |
Date |
2007-04-09 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-04-09 |
Time |
12:51 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-04-09 |
Time |
12:51 |
Sent To |
|
|
Notes |
2007-04-09 12:53:06 | GAS REVISION OK-SHT P3-4.0 GAS RISER DIAGRAM. |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
4 |
Status |
P |
Date |
2007-02-17 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-02-17 |
Time |
17:10 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-02-17 |
Time |
17:10 |
Sent To |
|
|
Notes |
2007-02-17 17:14:28 | PASSED/PROVISO | | | | GAS RISER DIAGRAM SHOWS 128' FROM GENERATOR TO LAST | | FUTURE GENERATOR. THIS SCALES OUT TO ABOUT 30' ON THE | | PLANS. THE PIPING SHALL BE SIZED FOR 200' MAXIMUM. A | | REVISION WILL BE REQUIRED SHOWING THE CORRECT DISTANCE | | FROM THE FIRST GENERATOR TO THE LAST.--THE MANUF. | | SPECIFICATIONS SHALL BE REQUIRED SHOWING THE MAXIMUM | | BTU LOAD AT 100% CAPACITY WHEN APPLYING FOR THE | | REQUIRED GAS PERMIT. |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
F |
Date |
2007-01-31 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-01-31 |
Time |
06:36 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-01-31 |
Time |
06:36 |
Sent To |
|
|
Notes |
2007-01-31 11:04:09 | DENIED | | REFERENCE: FBC-2004 FUEL GAS | | | | FROM PREVIOUS REVIEWS: | | | | 39B. SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING | | INFORMATION IS REQUIRED FOR THE GAS PERMIT: | | | | A. OK | | B. OK | | C. OK | | D. OK | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | ****RESPONSE NOTED, BUT NOT ADDRESSED. ******RESPONSE | | NOTED, BUT THE SIZING OF THE PIPE SHALL BE TO THE MOST | | REMOTE APPLIANCE/GENERATOR. PLEASE INDICATE THE TOTAL | | DEVELOPED LENGTH TO THE MOST REMOTE FUTURE GENERATOR. | | | | F. OK | | | | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | ****RESPONSE NOTED, BUT NO MANUF. SHEETS FOR THE | | GENERATOR HAS BEEN SUBMITTED. - ALSO SUBMIT THE MANUF. | | SPECIFICATION SHEETS FOR THE GAS REGULATORS. INDICATE | | MODEL NUMBER. LISTING INFORMATION REQUIRED. | | ******RESPONSE NOTED, BUT THE BTU LOAD FOR THE NATURAL | | GAS @ 100% LOAD IS NOT INDICATED ON THE MANUF. | | SPECIFICATION SHEETS. THIS SHALL BE SHOWN TO VERIFY | | PIPE SIZING. | | | | H. NA | | I. NA | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2007-01-30 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2006-12-16 |
Time |
17:53 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2006-12-16 |
Time |
17:54 |
Sent To |
|
|
Notes |
2007-01-30 17:59:07 | DENIED | | REFERENCE: FBC-2004 FUEL GAS | | | | | | FROM PREVIOUS REVIEW: | | FROM PREVIOUS REVIEW: | | | | 39B. SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING | | INFORMATION IS REQUIRED FOR THE GAS PERMIT: | | | | A. OK - "NEW"SHOW THE LOCATION OF THE 2PSI TO 1/2PSI | | REGULATOR. SHUT OFF VALVE REQUIRED UPSTREAM OF | | REGULATOR. | | B. OK | | C. OK | | D. OK | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | ****RESPONSE NOTED, BUT NOT ADDRESSED | | | | F. OK - INFORMATIONAL - 2PSI AT MAXIMUM 200 FT | | DEVELOPED LENGTH ALLOWS 39,656,000 BTU'S. ONLY 10,000 | | BTU'S ARE INDICATED ON PLANS. THE 10,000 BTU'S IS | | QUESTIONABLE AS MOST RESIDENTIAL DRYERS ARE RATED AT | | 22,000 BTU'S. FOR COMPARISON, A .5 PSI SYSTEM WITH 2" | | PIPE WILL DELIVER 800,000 BTU'S. WITH THE EXTRA | | DEVELOPED LENGTH TO THE FARTHEST FUTURE GENERATOR,ITS | | APPROXAMATLY 180'. | | | | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | ****RESPONSE NOTED, BUT NO MANUF. SHEETS FOR THE | | GENERATOR HAS BEEN SUBMITTED. - ALSO SUBMIT THE MANUF. | | SPECIFICATION SHEETS FOR THE GAS REGULATORS. INDICATE | | MODEL NUMBER. LISTING INFORMATION REQUIRED. | | | | H. NA | | I.NA | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6721 | | E-MAIL [email protected] | | | | | | | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2006-11-14 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2006-11-14 |
Time |
17:51 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2006-11-14 |
Time |
17:51 |
Sent To |
|
|
Notes |
2006-12-16 17:53:18 | DENIED | | REFERENCE: FBC-2004 FUEL GAS | | | | 1. SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING | | INFORMATION IS REQUIRED FOR THE GAS PERMIT: | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. - RISER DOES NOT REFLECT | | THE FLOOR PLAN. OFFSETS BETWEEN THE | | METER AND THE RISER ARE NOT SHOWN. - | | INDICATE WHAT THE RISERS ABOVE THE TEE | | AT THE TOP OF THE RISER AND AT THE | | GENERATOR ARE FOR. FUTURE BTU LOAD AND | | DISTANCE MAY REQUIRE CHANGES IN THE | | GAS SYSTEM WHEN ADDED. | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | C. TYPE OF GAS, (LP OR NATURAL). | | | | D. BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | 402.4(33). | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | | | F. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | H. CLEARLY SHOW THE LOCATION AND CAP- | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | OR ASME), THE DISTANCE OF THE TANK FROM | | THE BUILDING AND ADJACENT PROPERTY LINES | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | CES OF IGNITION, OTHER CONTAINERS, BUILD- | | INGS, AND THE LOCATION OF ANY BUILDING | | OPENINGS BELOW THE RELIEF VALVE OF THE | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | I. CLEARLY INDICATE ON THE PLAN IF THE | | LP TANK IS ABOVE OR BELOW GROUND, AND | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | PER NFPA 58. IF THE TANK | | IS BELOW GROUND THE CONTAINER SHALL BE | | SECURILY ANCHORED PER NFPA 58 SECTION | | 3-2.2.7(H). | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
97 |
Status |
N |
Date |
2009-09-08 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2009-09-08 |
Time |
11:28 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2009-09-08 |
Time |
11:28 |
Sent To |
|
|
Notes |
2009-09-09 07:53:06 | ELECTRICAL REVISION FORWARDED TO D. PALMER |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
96 |
Status |
N |
Date |
2009-09-01 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-09-01 |
Time |
13:44 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-09-01 |
Time |
13:44 |
Sent To |
|
|
Notes |
2009-09-01 13:49:24 | SENT TO C- |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
95 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2009-05-20 |
Time |
11:18 |
Sent To |
|
|
Notes |
2009-05-20 11:19:31 | FINAL DRAWINGS SENT TO DEWEY |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
94 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
2009-05-15 15:34:45 | FIRE ALARM AS-BUILTS SENT TO M. CARISSILLO |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
93 |
Status |
N |
Date |
2009-04-03 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2009-04-03 |
Time |
14:41 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2009-04-03 |
Time |
14:41 |
Sent To |
B |
|
Notes |
2009-04-03 14:41:46 | TO "JWITMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
92 |
Status |
N |
Date |
2009-04-02 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2009-04-02 |
Time |
16:19 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2009-04-02 |
Time |
16:19 |
Sent To |
P |
|
Notes |
2009-04-02 16:19:29 | TO "P" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
91 |
Status |
N |
Date |
2009-03-30 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2009-03-30 |
Time |
11:16 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2009-03-30 |
Time |
11:16 |
Sent To |
|
|
Notes |
2009-03-30 11:16:24 | TO IN-BOX "C29" |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
90 |
Status |
N |
Date |
2009-03-18 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2009-03-18 |
Time |
09:15 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2009-03-18 |
Time |
09:15 |
Sent To |
B |
|
Notes |
2009-03-18 09:16:46 | TO "JWITMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
89 |
Status |
N |
Date |
2009-02-20 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2009-02-20 |
Time |
11:12 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2009-02-20 |
Time |
11:12 |
Sent To |
B |
|
Notes |
2009-02-20 11:13:21 | TO "JWITMER" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
88 |
Status |
N |
Date |
2009-02-20 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2009-02-20 |
Time |
10:04 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2009-02-20 |
Time |
10:04 |
Sent To |
|
|
Notes |
2009-02-20 10:07:49 | TO "COMM" BD#7 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
87 |
Status |
N |
Date |
2009-02-20 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2009-02-20 |
Time |
09:50 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2009-02-20 |
Time |
09:50 |
Sent To |
|
|
Notes |
2009-02-20 09:53:45 | TO "COMM" BD#14 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
86 |
Status |
N |
Date |
2009-02-09 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2009-02-09 |
Time |
10:47 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2009-02-09 |
Time |
10:47 |
Sent To |
B |
|
Notes |
2009-02-09 10:47:49 | TO "JWITMER" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
85 |
Status |
N |
Date |
2009-01-22 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2009-01-22 |
Time |
11:59 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2009-01-22 |
Time |
11:59 |
Sent To |
B |
|
Notes |
2009-01-22 11:59:57 | TO "JWITMER" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
84 |
Status |
N |
Date |
2009-01-20 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2009-01-20 |
Time |
16:03 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2009-01-20 |
Time |
16:03 |
Sent To |
B |
|
Notes |
2009-01-20 16:03:51 | TO "JWITMER" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
83 |
Status |
N |
Date |
2009-01-15 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2009-01-15 |
Time |
10:02 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2009-01-15 |
Time |
10:02 |
Sent To |
|
|
Notes |
2009-01-15 10:05:27 | TO "COMM" BD#18 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
82 |
Status |
N |
Date |
2009-01-08 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2009-01-08 |
Time |
08:29 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2009-01-08 |
Time |
08:29 |
Sent To |
B |
|
Notes |
2009-01-08 08:30:15 | TO "JWITMER" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
81 |
Status |
N |
Date |
2009-01-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2009-01-06 |
Time |
16:39 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2009-01-06 |
Time |
16:39 |
Sent To |
B |
|
Notes |
2009-01-06 16:41:05 | TO "JWITMER" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
80 |
Status |
N |
Date |
2008-12-22 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-12-22 |
Time |
09:18 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-12-22 |
Time |
09:18 |
Sent To |
|
|
Notes |
2008-12-22 09:18:36 | TO "COMM" BD#33 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
79 |
Status |
N |
Date |
2008-12-12 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-12-12 |
Time |
10:12 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-12-12 |
Time |
10:12 |
Sent To |
E |
|
Notes |
2008-12-12 10:13:01 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
78 |
Status |
N |
Date |
2008-12-12 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-12-12 |
Time |
09:51 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-12-12 |
Time |
09:51 |
Sent To |
|
|
Notes |
2008-12-12 10:06:24 | TO "COMM" BD#19 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
77 |
Status |
N |
Date |
2008-12-10 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-12-10 |
Time |
11:26 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-12-10 |
Time |
11:26 |
Sent To |
|
|
Notes |
2008-12-10 11:29:30 | TO "COMM" BD#22/ REV #52 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
76 |
Status |
N |
Date |
2008-12-10 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-12-10 |
Time |
10:30 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-12-10 |
Time |
10:30 |
Sent To |
B |
|
Notes |
2008-12-10 10:30:46 | TO "JWITMER" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
75 |
Status |
N |
Date |
2008-12-05 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-12-05 |
Time |
15:17 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-12-05 |
Time |
15:16 |
Sent To |
P |
|
Notes |
2008-12-05 15:18:09 | TO "P" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
74 |
Status |
N |
Date |
2008-11-13 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-11-13 |
Time |
14:43 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-11-13 |
Time |
14:43 |
Sent To |
B |
|
Notes |
2008-11-13 14:43:56 | TO "JWITMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
73 |
Status |
N |
Date |
2008-11-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-11-06 |
Time |
14:19 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-11-06 |
Time |
14:19 |
Sent To |
|
|
Notes |
2008-11-06 14:21:47 | TO "COMM" BD#61--EXPEDITED-- |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
72 |
Status |
N |
Date |
2008-11-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-11-06 |
Time |
13:59 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-11-06 |
Time |
13:59 |
Sent To |
P |
|
Notes |
2008-11-06 14:00:06 | TO "P" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
71 |
Status |
N |
Date |
2008-11-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-11-06 |
Time |
13:38 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-11-06 |
Time |
13:38 |
Sent To |
ENG |
|
Notes |
2008-11-06 13:39:09 | TO "ENG" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
70 |
Status |
N |
Date |
2008-11-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-11-06 |
Time |
13:30 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-11-06 |
Time |
13:30 |
Sent To |
B |
|
Notes |
2008-11-06 13:31:29 | TO "JWITMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
69 |
Status |
N |
Date |
2008-11-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-11-06 |
Time |
13:17 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-11-06 |
Time |
13:17 |
Sent To |
E |
|
Notes |
2008-11-06 13:18:12 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
68 |
Status |
N |
Date |
2008-10-28 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-10-28 |
Time |
14:21 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-10-28 |
Time |
14:21 |
Sent To |
B |
|
Notes |
2008-10-28 14:21:28 | TO "JWITMER" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
67 |
Status |
N |
Date |
2008-10-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-10-24 |
Time |
16:34 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-10-24 |
Time |
16:34 |
Sent To |
|
|
Notes |
2008-10-24 16:38:13 | TO "COMM" BD#18--EXPEDITED-- |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
66 |
Status |
N |
Date |
2008-10-22 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-10-22 |
Time |
15:20 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-10-22 |
Time |
15:20 |
Sent To |
E |
|
Notes |
2008-10-22 15:21:14 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
65 |
Status |
N |
Date |
2008-10-22 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-10-22 |
Time |
09:04 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-10-22 |
Time |
09:04 |
Sent To |
M |
|
Notes |
2008-10-22 09:05:03 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
64 |
Status |
N |
Date |
2008-10-14 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-10-14 |
Time |
14:51 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-10-14 |
Time |
14:51 |
Sent To |
E |
|
Notes |
2008-10-14 14:51:38 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
63 |
Status |
N |
Date |
2008-10-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-10-06 |
Time |
11:30 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-10-06 |
Time |
11:30 |
Sent To |
E |
|
Notes |
2008-10-06 11:30:22 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
62 |
Status |
N |
Date |
2008-10-03 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-10-03 |
Time |
15:03 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-10-03 |
Time |
15:03 |
Sent To |
|
|
Notes |
2008-10-03 15:03:34 | TO"COMM" BD#25 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
61 |
Status |
N |
Date |
2008-09-23 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-09-23 |
Time |
12:37 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-09-23 |
Time |
12:37 |
Sent To |
P |
|
Notes |
2008-09-23 12:37:41 | TO "P" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
60 |
Status |
N |
Date |
2008-09-03 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-09-03 |
Time |
14:16 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-09-03 |
Time |
14:16 |
Sent To |
E |
|
Notes |
2008-09-03 14:16:28 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
59 |
Status |
N |
Date |
2008-08-21 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-08-21 |
Time |
14:43 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-08-21 |
Time |
14:43 |
Sent To |
P |
|
Notes |
2008-08-21 14:44:04 | TO "P" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
58 |
Status |
N |
Date |
2008-08-21 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-08-21 |
Time |
14:29 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-08-21 |
Time |
14:29 |
Sent To |
E |
|
Notes |
2008-08-21 14:30:33 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
57 |
Status |
N |
Date |
2008-08-21 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-08-21 |
Time |
11:30 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-08-21 |
Time |
11:30 |
Sent To |
B |
|
Notes |
2008-08-21 11:30:52 | TO "JWITMER" DESK/2 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
56 |
Status |
N |
Date |
2008-08-21 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-08-21 |
Time |
11:13 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-08-21 |
Time |
11:13 |
Sent To |
E |
|
Notes |
2008-08-21 11:13:45 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
55 |
Status |
N |
Date |
2008-08-14 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-08-14 |
Time |
13:37 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-08-14 |
Time |
13:37 |
Sent To |
B |
|
Notes |
2008-08-14 13:38:50 | TO "JWITMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
54 |
Status |
N |
Date |
2008-07-30 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-07-30 |
Time |
08:43 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-07-30 |
Time |
08:43 |
Sent To |
B |
|
Notes |
2008-07-30 08:44:13 | TO "JWITMER" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
53 |
Status |
N |
Date |
2008-07-11 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-07-11 |
Time |
11:14 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-07-11 |
Time |
11:14 |
Sent To |
E |
|
Notes |
2008-07-11 11:15:06 | TO "DPALMER" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
52 |
Status |
N |
Date |
2008-07-01 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-07-01 |
Time |
11:10 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-07-01 |
Time |
11:10 |
Sent To |
E |
|
Notes |
2008-07-01 11:10:39 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
51 |
Status |
N |
Date |
2008-06-20 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-06-20 |
Time |
15:16 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-06-20 |
Time |
15:16 |
Sent To |
E |
|
Notes |
2008-06-20 15:16:57 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
50 |
Status |
N |
Date |
2008-06-17 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-06-17 |
Time |
09:13 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-06-17 |
Time |
09:13 |
Sent To |
P |
|
Notes |
2008-06-17 09:13:33 | TO "P" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
49 |
Status |
N |
Date |
2008-06-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-06-16 |
Time |
16:38 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-06-16 |
Time |
16:38 |
Sent To |
B |
|
Notes |
2008-06-16 16:39:13 | TO "JWITMER" DESK/2 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
48 |
Status |
N |
Date |
2008-06-10 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-06-10 |
Time |
15:47 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-06-10 |
Time |
15:47 |
Sent To |
|
|
Notes |
2008-06-10 15:47:28 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
47 |
Status |
N |
Date |
2008-05-30 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-05-30 |
Time |
09:39 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-05-30 |
Time |
09:39 |
Sent To |
B |
|
Notes |
2008-05-30 09:40:49 | TO "JWITMER" DESK/ 3 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
46 |
Status |
N |
Date |
2008-05-14 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-05-14 |
Time |
14:14 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-05-14 |
Time |
14:14 |
Sent To |
P |
|
Notes |
2008-05-14 14:15:02 | TO "P" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
45 |
Status |
N |
Date |
2008-05-14 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-05-14 |
Time |
14:12 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-05-14 |
Time |
14:12 |
Sent To |
E |
|
Notes |
2008-05-14 14:12:32 | TO "JWITMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
44 |
Status |
N |
Date |
2008-05-05 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-05-05 |
Time |
14:15 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-05-05 |
Time |
14:15 |
Sent To |
B |
|
Notes |
2008-05-05 14:16:16 | TO "JWITMER" DESK/2 REV'S |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
43 |
Status |
N |
Date |
2008-05-01 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-05-01 |
Time |
17:00 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-05-01 |
Time |
17:00 |
Sent To |
|
|
Notes |
2008-05-01 17:01:02 | TO "COMM" BD#58/PLANS ON RACK/5 SMALL ROLLS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
42 |
Status |
N |
Date |
2008-04-10 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-04-10 |
Time |
11:31 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-04-10 |
Time |
11:31 |
Sent To |
|
|
Notes |
2008-04-10 11:40:47 | TO "COMM" BD#32 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
41 |
Status |
N |
Date |
2008-03-17 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-03-17 |
Time |
13:50 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-03-17 |
Time |
13:50 |
Sent To |
E |
|
Notes |
2008-03-17 13:51:02 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
40 |
Status |
N |
Date |
2008-03-14 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-03-14 |
Time |
16:54 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-03-14 |
Time |
16:54 |
Sent To |
|
|
Notes |
2008-03-17 14:25:18 | TO "COMM" BD#7--PLANS ON RACK--3 ROLLS---EXPEDITED--- | 2008-03-14 16:55:16 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
39 |
Status |
N |
Date |
2008-03-13 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-03-13 |
Time |
15:51 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-03-13 |
Time |
15:50 |
Sent To |
M |
|
Notes |
2008-03-13 15:51:27 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
38 |
Status |
N |
Date |
2008-03-13 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-03-13 |
Time |
15:37 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-03-13 |
Time |
15:37 |
Sent To |
ENG |
|
Notes |
2008-03-13 15:38:32 | TO "ENG" BOX/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
37 |
Status |
N |
Date |
2008-02-21 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-02-21 |
Time |
12:03 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-02-21 |
Time |
12:03 |
Sent To |
Z |
|
Notes |
2008-02-21 12:04:08 | TO "Z" BOX/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
36 |
Status |
N |
Date |
2008-02-21 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-02-21 |
Time |
11:57 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-02-21 |
Time |
11:57 |
Sent To |
E |
|
Notes |
2008-02-21 11:58:58 | TO "E" BOX/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
35 |
Status |
N |
Date |
2008-02-11 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-02-11 |
Time |
13:56 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-02-11 |
Time |
13:56 |
Sent To |
M |
|
Notes |
2008-02-11 13:57:10 | TO "M" BOX/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
34 |
Status |
N |
Date |
2008-01-31 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-01-31 |
Time |
12:50 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-01-31 |
Time |
12:50 |
Sent To |
E |
|
Notes |
2008-01-31 12:51:01 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
33 |
Status |
N |
Date |
2008-01-28 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-01-28 |
Time |
12:33 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-01-28 |
Time |
12:33 |
Sent To |
E |
|
Notes |
2008-01-28 12:33:37 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
32 |
Status |
N |
Date |
2008-01-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-01-16 |
Time |
14:52 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-01-16 |
Time |
14:52 |
Sent To |
M |
|
Notes |
2008-01-16 14:53:54 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
31 |
Status |
N |
Date |
2008-01-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-01-16 |
Time |
14:46 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-01-16 |
Time |
14:46 |
Sent To |
ENG |
|
Notes |
2008-01-16 14:46:57 | TO "ENG' BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
30 |
Status |
N |
Date |
2008-01-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-01-16 |
Time |
14:34 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-01-16 |
Time |
14:34 |
Sent To |
E |
|
Notes |
2008-01-16 14:34:38 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
29 |
Status |
N |
Date |
2007-12-21 |
|
|
Cont ID |
|
Sent By |
mmiller |
Date |
2007-12-21 |
Time |
09:20 |
Rev Time |
0.00 |
Received By |
mmiller |
Date |
2007-12-21 |
Time |
09:19 |
Sent To |
M |
|
Notes |
2007-12-21 09:20:23 | SENT TO "RR" 'S DESK MMILLER |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
28 |
Status |
N |
Date |
2007-12-14 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-12-14 |
Time |
16:25 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-12-14 |
Time |
16:25 |
Sent To |
|
|
Notes |
2007-12-14 16:28:16 | TO "COMM" BD#37--EXPEDITED-- |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
27 |
Status |
N |
Date |
2007-12-14 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-12-14 |
Time |
16:13 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-12-14 |
Time |
16:13 |
Sent To |
E |
|
Notes |
2007-12-14 16:14:04 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
26 |
Status |
N |
Date |
2007-12-13 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-12-13 |
Time |
16:59 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-12-13 |
Time |
16:59 |
Sent To |
M |
|
Notes |
2007-12-13 17:01:20 | TO "RREGUIERO" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
25 |
Status |
N |
Date |
2007-11-26 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-11-26 |
Time |
12:03 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-11-26 |
Time |
12:03 |
Sent To |
B |
|
Notes |
2007-11-26 12:04:00 | TO "JWITMER" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
24 |
Status |
N |
Date |
2007-11-01 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-11-01 |
Time |
18:21 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-11-01 |
Time |
18:21 |
Sent To |
|
|
Notes |
2007-11-01 18:21:35 | TO COMM BD # 39 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
23 |
Status |
N |
Date |
2007-09-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-09-24 |
Time |
10:45 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-09-24 |
Time |
10:45 |
Sent To |
B |
|
Notes |
2007-09-24 10:45:51 | TO "JWITMER" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
22 |
Status |
N |
Date |
2007-08-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-20 |
Time |
09:56 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-20 |
Time |
09:56 |
Sent To |
|
|
Notes |
2007-08-30 08:14:17 | TO "COMM" BD#56--EXPEDITED--PLANS ON RACK/3 ROLLS | 2007-08-24 09:56:36 | WAITING FOR "COMM" BD-REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
21 |
Status |
N |
Date |
2007-08-09 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-08-09 |
Time |
13:22 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-08-09 |
Time |
13:22 |
Sent To |
B |
|
Notes |
2007-08-09 13:23:25 | TO JW'S DESK. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
20 |
Status |
N |
Date |
2007-08-09 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-08-09 |
Time |
13:22 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-08-09 |
Time |
13:22 |
Sent To |
B |
|
Notes |
2007-08-09 13:22:52 | TO JW'S DESK. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
19 |
Status |
N |
Date |
2007-08-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-08-07 |
Time |
20:37 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-08-07 |
Time |
20:37 |
Sent To |
|
|
Notes |
2007-08-07 20:38:15 | BLDG/PLUMB REVS WAITING FOR COMM BOARD. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
18 |
Status |
N |
Date |
2007-07-28 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-07-28 |
Time |
13:32 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-07-28 |
Time |
13:32 |
Sent To |
B |
|
Notes |
2007-07-28 13:32:24 | TO "JWITMER" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
17 |
Status |
N |
Date |
2007-07-17 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-07-17 |
Time |
16:02 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-07-17 |
Time |
16:02 |
Sent To |
B |
|
Notes |
2007-07-17 16:02:35 | TO "JWITMER" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
16 |
Status |
N |
Date |
2007-07-17 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-07-02 |
Time |
15:06 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-07-02 |
Time |
15:06 |
Sent To |
|
|
Notes |
2007-07-17 15:07:03 | TO "COMM" BD#21/PLANS ON RACK--7 ROLLS AND 3 BINDERS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
15 |
Status |
N |
Date |
2007-06-12 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-06-12 |
Time |
16:08 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-06-12 |
Time |
16:08 |
Sent To |
B |
|
Notes |
2007-06-12 16:08:49 | TO "JWITMER" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
14 |
Status |
N |
Date |
2007-06-12 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-06-12 |
Time |
11:11 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-06-12 |
Time |
11:11 |
Sent To |
B |
|
Notes |
2007-06-12 11:12:16 | TO "JWITMER" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
13 |
Status |
N |
Date |
2007-06-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-06-06 |
Time |
16:53 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-06-06 |
Time |
16:53 |
Sent To |
P |
|
Notes |
2007-06-06 16:53:54 | TO "P" BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
12 |
Status |
N |
Date |
2007-05-23 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-05-23 |
Time |
14:44 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-05-23 |
Time |
14:44 |
Sent To |
B |
|
Notes |
2007-05-23 14:44:35 | TO "JWITMER" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
11 |
Status |
N |
Date |
2007-05-14 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-05-14 |
Time |
15:19 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-05-14 |
Time |
15:19 |
Sent To |
B |
|
Notes |
2007-05-14 15:20:03 | TO "JWITMER" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
10 |
Status |
N |
Date |
2007-04-06 |
|
|
Cont ID |
|
Sent By |
spalmer |
Date |
2007-04-06 |
Time |
17:39 |
Rev Time |
0.00 |
Received By |
spalmer |
Date |
2007-04-06 |
Time |
17:39 |
Sent To |
B |
|
Notes |
2007-04-06 17:39:23 | TO JIM WITMER |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
9 |
Status |
N |
Date |
2007-03-27 |
|
|
Cont ID |
|
Sent By |
spalmer |
Date |
2007-03-27 |
Time |
17:46 |
Rev Time |
0.00 |
Received By |
spalmer |
Date |
2007-03-27 |
Time |
17:46 |
Sent To |
B |
|
Notes |
2007-03-27 17:47:11 | SUBMITTAL TO JIM WITMER |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
8 |
Status |
N |
Date |
2007-03-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-03-24 |
Time |
14:13 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-03-24 |
Time |
14:13 |
Sent To |
|
|
Notes |
2007-03-24 14:15:59 | TO "COMM" BD#6/PLANS ON RACK--3 ROLLS AND 3 BINDERS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
7 |
Status |
N |
Date |
2007-03-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-03-24 |
Time |
13:58 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-03-24 |
Time |
13:58 |
Sent To |
B |
|
Notes |
2007-03-24 13:59:10 | TO "JWITMER' DESK/PARKING GARAGE REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2007-03-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-03-16 |
Time |
14:34 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-03-16 |
Time |
14:34 |
Sent To |
|
|
Notes |
2007-03-19 14:18:00 | TO "COMM" BD#22 | 2007-03-16 14:34:38 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2007-02-22 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-02-22 |
Time |
17:46 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-02-22 |
Time |
17:46 |
Sent To |
B |
|
Notes |
2007-02-22 17:46:44 | TO "JWITMER" DESK/REV--PER "RBROWN" |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2007-02-12 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-02-12 |
Time |
16:21 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-02-12 |
Time |
16:21 |
Sent To |
|
|
Notes |
2007-02-12 16:21:47 | TO "COMM" BD#30/PLANS ON RACK/6 ROLLS AND 4 BOXES |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-01-19 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-01-19 |
Time |
16:00 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-01-19 |
Time |
16:00 |
Sent To |
|
|
Notes |
2007-01-19 16:04:59 | TO "COMM" BD#10/PLANS ON RACK6 ROLLS, 2 BOXES AND 2 | | ROLLS OLD PLANS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2006-12-15 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-12-15 |
Time |
16:39 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-12-15 |
Time |
16:39 |
Sent To |
|
|
Notes |
2006-12-15 16:40:49 | TO "COMM" BD#3/PLANS ON RACK/7 ROLLS, 1 BOX, AND | | BINDERS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-11-25 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-11-25 |
Time |
|
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-10-19 |
Time |
11:13 |
Sent To |
|
|
Notes |
2006-10-24 17:06:20 | TO "COMM" BD#47/PLANS ON RACK--6 ROLLS AND 1 BOX | 2006-10-20 11:14:14 | WAITING FOR "COMM" BD |
|
|
Review Stop |
L |
LANDSCAPING |
Rev No |
1 |
Status |
P |
Date |
2008-10-16 |
|
|
Cont ID |
|
Sent By |
mflis |
Date |
2008-10-16 |
Time |
08:39 |
Rev Time |
0.00 |
Received By |
mflis |
Date |
2008-10-16 |
Time |
08:39 |
Sent To |
|
|
Notes |
2008-10-16 08:43:04 | ZONING REVIEW: PASSED WITH COMMENTS: | | | | 1) STRUCTURAL SOIL SHOULD BE USED AROUND ALL SIDEWALKS | | FOR STREET TREES | | | | 2) AT SE CORNER OF SITE, FDOT DATE PALMS WILL NEED TO | | BE REINSTALLED TO MATCH OTHER STREET CORNERS (NORTH | | SIDE OF CLEMATIS, WEST OF DIXIE). NOTE IS INDICATED ON | | PLANS THAT THESE ARE STORED OFF-SITE, BUT PLANT | | MATERIALS ARE NOT SHOWN. | | | | 3) REVISIONS TO BUILDING ENTRIES AT CLEMATIS STREET AND | | BANYAN STREET ARE NOT INDICATED WITH THIS SET AND WILL | | NEED TO BE SUBMITTED FOR APPROVAL. (ADJUSTMENTS TO TAKE | | INTO ACCOUNT ELEVATION CHANGES). | | | | 4) PITCH APPLE LOCATED IN MIDDLE COURTYARD MAY BE TOO | | SMALL TO PROVIDE ANY MEANINGFUL SHADE OR ACCENT FOR THE | | SPACE. PLEASE CONTACT ROBERT KUSSNER, LANDSCAPE | | PLANNER, AT 822-1435 FOR RECOMMENDATIONS TO SWITCH OUT | | SMALLER MATERIAL FOR SOMETHING TALLER WHICH WILL BE | | PROPORTIONAL TO SCALE OF SPACE AND BUILDING | | | | MATT FLIS - 822-1445 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
24 |
Status |
P |
Date |
2009-09-09 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2009-09-09 |
Time |
12:14 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2009-09-09 |
Time |
11:30 |
Sent To |
|
|
Notes |
2009-09-09 12:14:21 | REVISED M2-3.0 DELTA 14F/G |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
23 |
Status |
P |
Date |
2009-01-20 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2009-01-20 |
Time |
08:40 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2009-01-20 |
Time |
08:39 |
Sent To |
|
|
Notes |
2009-01-20 08:40:25 | PAGE M1-2.2 REVISION 23A |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
22 |
Status |
P |
Date |
2009-01-20 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2009-01-20 |
Time |
08:20 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2009-01-20 |
Time |
08:13 |
Sent To |
|
|
Notes |
2009-01-20 08:17:53 | REVISION 20B, PAGE M1-1.3. THIS PAGE ALSO NEEDS FIRE | | REVIEW. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
21 |
Status |
P |
Date |
2008-11-22 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-11-22 |
Time |
12:44 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-11-22 |
Time |
12:32 |
Sent To |
|
|
Notes |
2008-11-22 12:32:44 | REVISED M1-1.2, M3,1.0 REV 21A |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
20 |
Status |
P |
Date |
2008-11-15 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-11-15 |
Time |
13:10 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-11-15 |
Time |
12:09 |
Sent To |
PC |
|
Notes |
2008-11-15 13:10:17 | REVISED M1-1.3 FUEL PUMP ROOM. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
19 |
Status |
P |
Date |
2008-11-08 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-11-08 |
Time |
15:20 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-11-08 |
Time |
15:18 |
Sent To |
PC |
|
Notes |
2008-11-08 15:19:47 | REV.19, PAGES: M1-1.1, M1-1.2, M1-2.1, M1-2.2, M1-3.1, | | M1-3.2, M1-4.1, M1-4.2, M1-5.1 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
18 |
Status |
P |
Date |
2008-07-02 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-07-02 |
Time |
14:44 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-07-02 |
Time |
13:03 |
Sent To |
PC |
|
Notes |
2008-07-02 14:44:00 | REVISION CA-201 PAGES M1-1.1, M1-2.1, M1-2.2, M1-3.1, | | M1-4.1, M1-4.2, M1-5.1 | | ADDED TRANSFER AIR OPENING SIZES. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
17 |
Status |
|
Date |
2008-05-12 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-05-07 |
Time |
08:50 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-05-07 |
Time |
16:28 |
Sent To |
PC |
|
Notes |
2008-05-12 08:50:46 | REV.14E |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
16 |
Status |
F |
Date |
2008-04-20 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-04-20 |
Time |
13:37 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-04-19 |
Time |
17:30 |
Sent To |
PC |
|
Notes |
2008-04-20 13:37:13 | REVIEW #: REV.14D | | ACTION: DENIED | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | 1. PG M1-1.1: 6 INCH ROUND SUPPLY DUCT FEEDING FILE | | ROOM A1.207 IS PENETRATING A RATED CORRIDOR WALL AND IS | | ONLY PROTECTED WITH A FIRE DAMPER. THIS PENETRATION | | REQUIRES A FIRE AND SMOKE DAMPER IN ACCORDANCE WITH | | FBCM 607.5.4(3) BECAUSE THE DUCT HAS OPENINGS IN THE | | CORRIDOR. | | | | 2. PG M1-1.1: 10 INCH ROUND SUPPLY DUCT FEEDING | | VESTIBULE A1.011 IS PROTECTED WITH A FIRE/SMOKE DAMPER. | | HOWEVER, THIS VESTIBULE IS SERVING AS AN EXIT | | PASSAGEWAY FROM STAIR 02 AS DEFINED IN FBCB SECTION | | 1002. THIS PENETRATION IS PROHIBITED IN ACCORDANCE WITH | | FBCB 1020.5. | | | | 3. PG M1-1.1 AND MOST REV.14D PAGES: KEY NOTES WHICH | | ARE LISTED ON THE BOTTOM RIGHT OF PAGE ARE NOW MISSING | | FROM FLOOR PLANS. SOME KEY NOTES ARE NO LONGER VALID | | AND SHOULD BE REMOVED FROM PLANS. EXAMPLE: PG M1-1.2 | | KEY NOTE #1 STILL CALLS FOR DUCT SMOKE DETECTORS AT | | SHAFTS FOR SMOKE DAMPERS. PLEASE SHOW RELEVANT KEY | | NOTES WHERE NEEDED ON FLOOR PLANS AND REMOVE THOSE | | WHICH ARE NO LONGER APPLICABLE. | | | | 4. PG M1-1.2: IN VESTIBULE D1.005 THERE ARE TWO DUCT | | PENETRATIONS. THIS IS AN EXIT PASSAGEWAY AS DEFINED IN | | FBCB SECTION 1002. THESE PENETRATIONS ARE PROHIBITED IN | | ACCORDANCE WITH FBCB 1020.5. | | | | 5. PG M1-1.2: AT VOICE/DATA ROOM D1.107 THERE IS A | | 36X56 DUCT PENETRATING THE FLOOR ABOVE AND IS SHOWN IN | | THE MIDDLE OF A SMOKE PARTITION. ARCHITECTURAL PLANS | | CALL FOR THIS WALL TO BE BUILT TO THE UNDERSIDE OF THE | | FLOOR ABOVE. PLEASE SHOW HOW THIS WILL BE ACCOMPLISHED | | WITHOUT COMPROMISING THE FIRE/SMOKE DAMPER INSTALLATION | | OR THE SMOKE RATING OF THE PARTITION. FBCM 607.2, FBCB | | 710.4. | | | | 6. PG M1-1.2: A 14 INCH ROUND DUCT PENETRATING THE WALL | | BETWEEN VOICE/DATA ROOM C1.102 AND LOBBY C1.008 IS | | SHOWN PROTECTED WITH A FIRE DAMPER. THIS PENETRATION | | REQUIRES FIRE AND SMOKE DAMPER IN ACCORDANCE WITH FBCM | | 607.5.4(3). | | | | 7. PG M1-1.2: STORAGE ROOMS C1.403 AND C1.404 ARE | | ENCLOSED IN SMOKE PARTITIONS AS SHOWN ON LS1-1.2. | | MECHANICAL FLOOR PLAN SHOWS AIR TRANSFER OPENINGS IN | | EACH ROOM. THESE OPENINGS SHALL BE PROTECTED BY SMOKE | | DAMPER IN ACCORDANCE WITH FBCB 710.7. | | | | 8. PG M1-1.2 THROUGH M1-5.2: STARTING IN MEN?S ROOM | | C1.104 THERE IS AN EXHAUST DUCT ENTERING WHAT APPEARS | | TO BE AN ENCLOSURE AND TRAVELS THROUGH THE 4TH FLOOR TO | | EF-4 ON THE ROOF. THIS ENCLOSURE IS NOT SHOWN TO BE | | FIRE RESISTANCE RATED AS A SHAFT ON THE ARCHITECTURAL | | OR LIFE SAFETY PLANS.A SHAFT ENCLOSURE IS REQUIRED | | WHERE DUCTS PENETRATE HORIZONTAL ASSEMBLIES IN | | ACCORDANCE WITH FBCM 607.6. SHAFT ENCLOSURES SHALL HAVE | | A FIRE-RESISTANCE RATING OF NOT LESS THAN 2 HOURS WHERE | | CONNECTING FOUR STORIES OR MORE IN ACCORDANCE WITH FBCB | | 707.4. | | | | 9. PG M1-2.1: KEY NOTE #6 NEEDS TO BE ASSOCIATED WITH | | THE FIRE/SMOKE DAMPERS LOCATED WHERE THE SMOKE EXHAUST | | DUCTS PENETRATE THE SHAFT ENCLOSURE. THESE DAMPERS NEED | | TO BE UNDER THE CONTROL OF THE SMOKE CONTROL SYSTEM TO | | ENSURE THEY ARE OPEN WHEN THE ATRIUM IS IN SMOKE | | CONTROL MODE IN ACCORDANCE WITH FBCB 909.22.1. | | | | 10. PG M1-3.2: AT VOICE/DATA ROOM C3.110 THE 10X8 DUCT | | PENETRATION OF THE RATED CORRIDOR WALL REQUIRES FIRE | | AND SMOKE DAMPER IN ACCORDANCE WITH FBCM 607.5.4(3). | | | | 11. PG M1-3.2: AT CORRIDOR C3.010 THE 55X18 DUCT | | PENETRATION OF THE RATED CORRIDOR WALL REQUIRES FIRE | | AND SMOKE DAMPER IN ACCORDANCE WITH FBCM 607.5.4(3). | | | | 12. PG M1-3.2: AT PROGRAM/MEETING ROOM C3.306 THE 48X18 | | DUCT PENETRATION OF THE RATED CORRIDOR WALL REQUIRES | | FIRE AND SMOKE DAMPER IN ACCORDANCE WITH FBCM | | 607.5.4(3). | | | | 13. PG M1-3.2: AT CORRIDOR C3.015 THERE IS VAV 3-1R-5. | | THE DUCTS ON BOTH SIDES OF THE VAV ARE SHOWN AS | | PROTECTED WITH FIRE DAMPERS. IF THE DUCT CONNECTION TO | | THIS VAV IS MADE BY FLEXIBLE NON-METALLIC DUCT, THESE | | DUCT PENETRATIONS WILL NOT MEET THE EXCEPTION FOR SMOKE | | DAMPER REQUIREMENT IN ACCORDANCE WITH FBCM 607.5.4(3). | | PLEASE VERIFY THAT THIS DUCT AND VAV CONNECTION ARE | | CONTINUOUS STEEL NOT LESS THAN 0.019 INCH THICKNESS (26 | | GAGE) OR PROVIDE FIRE AND SMOKE DAMPER AT CORRIDOR | | PENETRATIONS IN ACCORDANCE WITH FBCM 607.5.4. | | | | 14. PG M1-3.2, A1-3.2 AND LS1-3.2: THERE IS A PORTION | | OF THE WALL BETWEEN LOBBY C3.303 AND PREFUNCTION LOBBY | | C3.301 WHICH IS NOT SHOWN TO CARRY THE 1-HOUR FIRE | | RESISTANCE RATING AS REQUIRED FOR EXIT ACCESS CORRIDORS | | IN THIS AREA IN ACCORDANCE WITH FBCB TABLE 1016.1. | | | | 15. PG M2-3.0 AND M1-6.0: ELEVATOR MACHINE ROOM A6.103 | | REQUIRES INDEPENDENT VENTILATION IN ACCORDANCE WITH | | FBCB 3006.2. THE DUCT PENETRATION INTO THIS ROOM SHALL | | BE PROTECTED WITH FIRE/SMOKE DAMPER IN ACCORDANCE WITH | | FBCB 3006.4 AND FBCM 607.5.5.1. | | | | 16. PG M2-3.0 AND M1-6.0: ELEVATOR MACHINE ROOM A6.102, | | THE 44X30 DUCT OPENING IN TO ELEVATOR 03 HOISTWAY SHALL | | BE PROTECTED WITH COMBINATION FIRE/SMOKE DAMPER IN | | ACCORDANCE WITH FBCB 3002.1.1 AND FBCM 607.5.5.1. | | | | 17. PG M2-3.0 AND M1-6.0: ELEVATOR MACHINE ROOM A6.102, | | THE 18X14 DUCT PENETRATION FROM FCU-6 SHALL BE | | PROTECTED WITH COMBINATION FIRE/SMOKE DAMPER IN | | ACCORDANCE WITH FBCB 3006.4 AND FBCM 607.5.5.1. | | | | 18. PG M2-3.0 AND M1-6.0: ELEVATOR MACHINE ROOM A6.102, | | THE 44X30 HOISTWAY VENT REQUIRES A MOTORIZED DAMPER IN | | ACCORDANCE WITH FBCB 13-409.1.ABC.3.1. | | | | 19. PG M6-1.0: PLEASE REMOVE KEY NOTE #1 FROM PLAN AS | | IT IS NO LONGER APPLICABLE. | | FBCB 106.1.1. SEE ALSO COMMENT #3 ABOVE. | | | | NOTE: MECHANICAL REVIEW HAS BEEN COMPLETED. HOWEVER, | | BUILDING REVIEW IS PARTIALLY COMPLETE AT THIS TIME AND | | STILL PENDING. PLEASE COORDINATE ALL MECHANICAL, | | ARCHITECTURAL AND LIFE SAFETY PLANS TO ENSURE CODE | | COMPLIANCE PRIOR TO RESUBMITTAL OF PLANS. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
15 |
Status |
F |
Date |
2008-04-08 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-04-08 |
Time |
16:00 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-03-22 |
Time |
15:38 |
Sent To |
PC |
|
Notes |
2008-04-08 16:00:16 | REVIEW #: REV.14B AND 14C | | ACTION: DENIED | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | 1. PG M1-1.1: THIS SHEET CONTAINS CHANGES WHICH ARE NOT | | MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS. PLEASE | | MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED SINCE | | REV. 12C. ONE EXAMPLE OF SUCH CHANGES IS CIRCLED ON | | PLAN. | | ALSO, REVISIONS 12B AND 12C WHICH WERE PART OF THE | | REVISION HISTORY ARE NOW MISSING FROM PLANS. THIS | | INDICATES IT IS LIKELY THAT THE PLANS HAVE REVERTED TO | | A PREVIOUS STATE BEFORE BEING REVISED AS PART OF REV | | 14B. | | | | 2. PG M1-1.2: THIS SHEET CONTAINS CHANGES WHICH ARE NOT | | MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS. PLEASE | | MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED SINCE | | REV. 12B. ONE EXAMPLE OF SUCH CHANGES IS CIRCLED ON | | PLAN. | | ALSO, REVISION WHICH WAS PART OF THE REVISION HISTORY | | IS NOW MISSING FROM PLANS. THIS INDICATES IT IS LIKELY | | THAT THE PLANS HAVE REVERTED TO A PREVIOUS STATE BEFORE | | BEING REVISED AS PART OF REV 14B AND 14C. | | | | 3. PG M1-1.2: THERE IS A 10 INCH ROUND DUCT PENETRATING | | A 2-HOUR RATED WALL BETWEEN LOADING D1.106 AND CORRIDOR | | D1.006. SHOW HOW THIS PENETRATION IS TO BE PROTECTED IN | | ACCORDANCE WITH FBCM 607.5. | | | | 4. PG M1-2.1: THIS SHEET CONTAINS CHANGES WHICH ARE NOT | | MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS. PLEASE | | MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED SINCE | | REV. 12C. ONE EXAMPLE OF SUCH CHANGES IS CIRCLED ON | | PLAN. | | ALSO, REVISIONS 12B AND 12C WHICH WERE PART OF THE | | REVISION HISTORY ARE NOW MISSING FROM PLANS. THIS | | INDICATES IT IS LIKELY THAT THE PLANS HAVE REVERTED TO | | A PREVIOUS STATE BEFORE BEING REVISED AS PART OF REV | | 14B. | | | | 5. PG M1-2.2: THIS PAGE IS NOT ABLE TO BE REVIEWED. | | THERE ARE MULTIPLE LAYERS IN MULTIPLE SCALES ON THE | | SAME PAGE. PLEASE CORRECT THE PAGE AND RESUBMIT. | | | | 6. PG M1-3.1: THIS SHEET CONTAINS CHANGES WHICH ARE NOT | | MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS. PLEASE | | MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED SINCE | | REV. 12C. ONE EXAMPLE OF SUCH CHANGES IS CIRCLED ON | | PLAN. | | | | 7. PG M1-3.1: THIS PAGE HAS BEEN MODIFIED BY HAND WITH | | A PEN. THERE IS NO INDICATION ON PLANS THAT THESE | | MODIFICATIONS WERE MADE BY THE DESIGN PROFESSIONAL OF | | RECORD. SIGNED AND SEALED DRAWINGS SHALL NOT BE | | MODIFIED ONCE SIGNED AND SEALED UNLESS THE | | MODIFICATIONS ARE SIGNED AND DATED BY THE DESIGNER OF | | RECORD. OTHERWISE, IT SHALL BE ASSUMED THAT THE | | DRAWINGS WERE MODIFIED BY SOMEONE NOT AUTHORIZED TO DO | | SO. | | | | 8. PG M1-3.1: PLAN SHOWS TWO FIRE DAMPERS IN THE WALL | | AT VOICE/DATA A3.116. THIS WALL IS NOT SHOWN AS HAVING | | A FIRE RESISTANCE RATING ON ARCHITECTURAL OR LIFE | | SAFETY PLANS. THERE IS ALSO A 60X26 UNPROTECTED DUCT | | PENETRATION SHOWN IN THE SAME ROOM. PLEASE COORDINATE | | MECH. PLANS WITH ARCH. PLANS AND LS PLANS, SHOWING | | PROTECTION OF PENETRATIONS WHERE NEEDED IN ACCORDANCE | | WIT FBCM 607.5. | | | | 9. PG M1-3.2: THERE ARE AT LEAST FIVE DUCT PENETRATIONS | | OF FIRE RATED WALL ASSEMBLIES WITHOUT PROTECTION AT | | CORRIDORS C3.011 AND C3.012. SHOW HOW THESE | | PENETRATIONS ARE TO BE PROTECTED IN ACCORDANCE WITH | | FBCM 607.5 AND 607.5.4. | | | | 10. PG M1-3.2: THIS SHEET CONTAINS CHANGES WHICH ARE | | NOT MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS. | | PLEASE MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED | | SINCE REV. 12B. ONE EXAMPLE OF SUCH CHANGES IS CIRCLED | | ON PLAN. | | ALSO, REVISION 12B WHICH WAS PART OF THE REVISION | | HISTORY IS NOW MISSING FROM PLANS. THIS INDICATES IT IS | | LIKELY THAT THE PLANS HAVE REVERTED TO A PREVIOUS STATE | | BEFORE BEING REVISED AS PART OF REV 14B AND 14C. | | | | 11. PG M1-3.2: PLEASE SHOW SIZE OF DUCT FOR EF-3 ABOVE | | STAIR 10 RISER BETWEEN TRANSITIONS. ALSO, SHOW SIZE OF | | TAP AT 40X44 RETURN DUCT FOR RTU-2 NEAR STAIR 7. | | | | 12. THIS SHEET CONTAINS CHANGES WHICH ARE NOT MARKED OR | | CLOUDED FROM PREVIOUS PASSED PLANS. PLEASE MARK OR | | CLOUD ALL CHANGES WHICH HAVE OCCURRED SINCE REV. 12A. | | ONE EXAMPLE OF SUCH CHANGES IS CIRCLED ON PLAN. | | | | 13. PG M1-4.1: THE DUCT FEEDING A VAV FROM SOUTH END OF | | SERVER ROOM IS PENETRATING A 2-HOUR RATED WALL ASSEMBLY | | AS SHOWN ON ARCHITECTURAL AND LIFE SAFETY PLANS. PLEASE | | COORDINATE PLANS AND SHOW PENETRATIONS TO BE PROTECTED | | IN ACCORDANCE WITH FBCM 607.5. | | | | 14. PG M1-4.1: THERE IS A DELTA-13 REVISION MARK IN THE | | RISER FOR CAHU-1. THERE IS NO REVISION 13 SHOWN ON THE | | REVISION HISTORY FOR THIS PAGE. PLEASE CLARIFY. | | | | 15. PG M1-4.2: RETURN DUCT SIZE FOR AHU-3 HAS BEEN | | REVISED ON THIS PAGE BUT THE CORRESPONDING DUCT HAS NOT | | BEEN REVISED ON PAGE M2-2.0. PLEASE COORDINATE PLANS | | AND RESUBMIT. | | | | 16. SUPPLY AND RETURN DUCT RISER SIZES FOR RTU-1 AND | | RTU-2 HAVE BEEN REVISED ON THIS PAGE BUT HAVE NOT BEEN | | REVISED ON PAGE M1-5.2. PLEASE COORDINATE PLANS AND | | RESUBMIT. | | | | 17. PG M1-5.1: THIS SHEET CONTAINS CHANGES WHICH ARE | | NOT MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS. | | PLEASE MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED | | SINCE REV. 12A. ONE EXAMPLE OF SUCH CHANGES IS CIRCLED | | ON PLAN. | | | | 18. PG M2-1.0, M3-1.0, M6-1.0: THESE PAGES ARE OK BUT | | ARE BEING RETURNED TO CONTRACTOR PER THEIR REQUEST. | | | | 19. PG M2-3.0: THIS SHEET CONTAINS CHANGES WHICH ARE | | NOT MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS. | | PLEASE MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED | | SINCE REV. 12A. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
14 |
Status |
P |
Date |
2008-02-16 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-02-16 |
Time |
16:30 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-02-16 |
Time |
15:53 |
Sent To |
PC |
|
Notes |
2008-02-16 16:30:22 | REV 12C M1-1.1, M1-2,1, M4-4.0 AND SMOKE CONTROL | | RATIONAL ANALYSIS. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
13 |
Status |
F |
Date |
2008-01-02 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-01-02 |
Time |
16:21 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-01-02 |
Time |
16:08 |
Sent To |
PC |
|
Notes |
2008-01-02 16:21:34 | DUCT PARTIAL SHOP DRAWINGS DENIED. THE FOLLOWING ARE | | EXAMPLES OF CONDITIONS WHICH MAY EXIST THROUGHOUT THE | | DRAWINGS. THESE SHOP DRAWINGS WERE COMPARED TO HVAC | | REVISION #14. | | | | 1. PG SM-1-4: 36X24 SUPPLY DUCT IS PENETRATING A RATED | | WALL AT ALCOVE A1.104 WITHOUT REQUIRED OPENING | | PROTECTIVES IN ACCORDANCE WITH FBC, M 607.5. THE SAME | | OPENING PROTECTIVES ARE MISSING IN REV. 14 ON PR | | M1-1.1. PLEASE CHECK ALL PENETRATIONS OF RATED | | ASSEMBLIES FOR PROPER OPENING PROTECTIVES AS REQUIRED | | BY THIS SECTION. | | | | 2. PG SM-3-2: DUCTWORK IN CONFERENCE ROOMS A3.306 AND | | A3.307 DOES NOT CORRESPOND WITH WHAT IS SHOWN IN REV.14 | | ON PG M1-3.1. PLEASE CHECK ALL DUCTS SHOWN CORRESPOND | | BETWEEN SHOP DRAWINGS AND SIGNED AND SEALED PLANS. WORK | | SHALL BE INSTALLED IN ACCORDANCE WITH THE REVIEWED | | CONSTRUCTION DOCUMENTS, AND ANY CHANGES MADE DURING | | CONSTRUCTION THAT ARE NOT IN COMPLIANCE WITH THE | | REVIEWED CONSTRUCTION DOCUMENTS SHALL BE RESUBMITTED | | FOR REVIEW AS AN AMENDED SET OF CONSTRUCTION DOCUMENTS | | IN ACCORDANCE WITH FBC 106.4. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
12 |
Status |
P |
Date |
2008-01-02 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-01-02 |
Time |
15:44 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-12-22 |
Time |
14:22 |
Sent To |
PC |
|
Notes |
2008-01-02 15:47:18 | REV.14 PAGES: | | M1-1.0 | | M1-2.0 | | M1-3.0 | | M1-4.0 | | M1-5.0 | | M1-6.0 | | M2-1.0 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
11 |
Status |
F |
Date |
2008-01-02 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-01-02 |
Time |
15:42 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-12-22 |
Time |
14:41 |
Sent To |
PC |
|
Notes |
2007-12-22 14:42:09 | REVIEW #: REV.14 | | ACTION: DENIED | | | | FBC 2004 CODE FAMILY W/ 2005 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | 1. M1-1.1: THE 36/24 SUPPLY DUCT FROM CAHU-1 HAS AT | | LEAST ONE UNPROTECTED OPENING IN THE WALL AT ALCOVE | | A1.104. SHOW OPENING PROTECTIVES (FIRE/SMOKE DAMPER) AS | | REQUIRED BY FBC, M 607.5. | | | | 2. M1-1.1: THE 16/14 EXHAUST DUCT CROSSING CORRIDOR | | A1.013 HAS 2 FIRE DAMPERS WHICH HAVE BEEN CHANGED TO | | FIRE/SMOKE DAMPERS. WHY HAVE THESE CHANGED? SMOKE | | DAMPERS ARE NOT REQUIRED IN THIS DUCT AS IT MEETS | | EXCEPTION #3 UNDER FBC, M 607.5.4. | | | | 3. M1-2.1: EF 17 EXHAUST DUCT HAS NO SIZE SHOWN ON | | PLANS AND THE CORRESPONDING KEY NOTE #1 IS INCORRECTLY | | IDENTIFYING THE RETURN DUCT AS EXHAUST DUCT. ALSO, ADD | | KEY NOTE #6 TO FIRE/SMOKE DAMPERS WHERE SMOKE EXHAUST | | DUCTS EXIT THE SHAFT ENCLOSURE, AS STATED IN PREVIOUS | | REVIEW OF THIS PAGE. KEY NOTE #2 IS ALSO IN THE | | INCORRECT LOCATION TO BE ASSOCIATED WITH THE SMOKE | | EXHAUST DUCT. | | | | 4. M1-3.1 KEY NOTE #3, M1-4.1 KEY NOTE #5, M1-5.1 KEY | | NOTE #3, M2-3.0 KEY NOTE #6 AND M6-1.0 KEY NOTE #1 CALL | | FOR SMOKE DETECTORS AT SHAFT PENETRATIONS, PRESUMABLY | | FOR CONTROL OF FIRE/SMOKE DAMPERS. AS OF REV 12B, THESE | | DAMPERS ARE TO BE ACTUATED BY AREA SMOKE DETECTORS IN | | ACCORDANCE WITH FBC, M 607.3.2.1(5). THESE KEY NOTES | | ARE IN CONFLICT WITH REVISION 12B. | | | | 5. M5-2.0: DETAIL 09, DUCT WRAP INSULATION IS SHOWN | | STOPPING AT BOTH SIDES OF THE WALL WITH AN INTERRUPTION | | OF THE VAPOR RETARDER. WHERE DUCTS USED FOR COOLING ARE | | EXTERNALLY INSULATED (WRAPPED RATHER THAN INTERNALLY | | LINED), THE INSULATION SHALL BE COVERED WITH A VAPOR | | RETARDER AND ALL JOINTS AND SEAMS SHALL BE SEALED TO | | MAINTAIN THE CONTINUITY OF THE VAPOR RETARDER IN | | ACCORDANCE WITH FBC, M 604.11 AND 304.1. | | NOTE: THE INSTALLATION OF AN AIR DISTRIBUTION SYSTEM | | SHALL NOT AFFECT THE FIRE PROTECTION REQUIREMENTS | | SPECIFIED IN THE BUILDING CODE IN ACCORDANCE WITH FBC, | | M 603.1. THEREFORE THESE REQUIREMENTS DO NOT APPLY WHEN | | THE DUCT PENETRATION OF A RATED WALL ASSEMBLY IS | | PROTECTED BY OPENING PROTECTIVES SUCH AS FIRE DAMPERS, | | SMOKE DAMPERS OR COMBINATION FIRE/SMOKE DAMPERS. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
10 |
Status |
P |
Date |
2007-12-19 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-12-19 |
Time |
16:54 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-12-19 |
Time |
16:46 |
Sent To |
|
|
Notes |
2007-12-19 16:54:15 | REV 12B PAGES: | | M1-1.2 | | M1-1.3 | | M1-2.3 | | M1-3.2 | | M1-3.3 | | M1-4.3 | | M1-5.3 | | M4-1.0 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
9 |
Status |
F |
Date |
2007-12-19 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-12-19 |
Time |
16:46 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-12-18 |
Time |
15:06 |
Sent To |
|
|
Notes |
2007-12-19 16:46:00 | REVIEW #: 12B | | ACTION: DENIED | | | | FBC 2004 CODE FAMILY W/ 2005 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN | | RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | | REV 11 COMMENTS: | | | | 2. M1-1.1WRITTEN RESPONSE INDICATES A FIRE DAMPER IS | | NOT REQUIRED IN THE 6X6 TRANSFER DUCT AT THE FIRE | | COMMAND CENTER (ROOM A1.120) BECAUSE THE SECTION OF | | WALL WHERE THE TRANSFER DUCT IS LOCATED IS NOT SHOWN TO | | BE FIRE RESISTANCE RATED ON THE LIFE SAFETY PLAN. | | WHETHER OR NOT IT IS SHOWN AS RATED, THE FIRE COMMAND | | CENTER IS REQUIRED TO BE SEPARATED FROM THE REMAINDER | | OF THE BUILDING BY NOT LESS THAN A 1-HOUR FIRE | | RESISTANCE RATED FIRE BARRIER IN ACCORDANCE WITH FBC | | 911.1. AS SUCH THIS WALL IS REQUIRED TO BE RATED. | | THEREFORE A FIRE DAMPER IS REQUIRED PER FBC, M 607.5. | | | | 5. OK | | | | 6. M1-2.1: PLEASE INCLUDE KEY NOTE #6 AT THE FIRE/SMOKE | | DAMPERS WHERE THE SMOKE EXHAUST DUCTS PENETRATE THE | | SHAFT ENCLOSURE. THEY ARE REQUIRED FOR THE OPERATION OF | | THE SMOKE CONTROL SYSTEM. THEREFORE THEY SHOULD BE | | CONTROLLED IN ACCORDANCE WITH FBC, M 513.5.2. | | | | 13. OK | | | | 14. OK | | | | REV 10 COMMENTS: | | | | 3. OK | | | | 5. OK | | | | REV 12A COMMENTS: | | | | 1. M4-4.0: SMOKE CONTROL SEQUENCE NOTE #4, SMOKE | | CONTROL SYSTEM SHALL ACTIVATE FROM ATRIUM SMOKE | | DETECTORS OR DETECTION OF FLOW IN THE FIRST OR SECOND | | FLOOR FIRE SPRINKLER PIPING SERVING THE ATRIUM. | | | | 2. OK | | | | 3. A RATIONAL ANALYSIS SUPPORTING THE TYPES OF SMOKE | | CONTROL SYSTEMS TO BE EMPLOYED, THEIR METHODS OF | | OPERATION, THE SYSTEMS SUPPORTING THEM AND THE METHODS | | OF CONSTRUCTION TO BE UTILIZED SHALL ACCOMPANY THE | | SUBMITTED CONSTRUCTION DOCUMENTS AND SHALL INCLUDE, BUT | | NOT BE LIMITED TO, THE ITEMS INDICATED IN SECTIONS | | 909.4.1 THROUGH 909.4.6 IN ACCORDANCE WITH FBC 909.4. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
8 |
Status |
P |
Date |
2007-11-09 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-11-09 |
Time |
11:12 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-11-06 |
Time |
14:12 |
Sent To |
P |
|
Notes |
2007-11-06 15:30:42 | REVIEW #: 8TH | | ACTION: PASSED/DENIED | | | | FBC 2004 CODE FAMILY W/ 2005 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | THE FOLLOWING PAGES WERE REVIEWED FOR COMPLIANCE, | | STAMPED AND INCORPORATED INTO THE PERMIT SET OF PLANS | | AS REV 12A: | | | | M1-1.0, M1-2.0, M1-2.2, M1-3.0, M1-3.1, M1-4.0, M1-4.1, | | M1-4.2, M1-5.0, M1-5.1, M1-5.2, M1-6.0, M2-3.0, M3-1.0 | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN | | RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | | REV. 11 COMMENTS: | | | | 1. REVISION 12A WILL BE REVIEWED FOR CODE COMPLIANCE AS | | WELL AS RESPONSES TO PREVIOUS REVIEW COMMENTS FROM | | REVISIONS 10 AND 11. | | | | 2. M1-1.1: AT THE FIRE COMMAND CENTER, A 6X6 TRANSFER | | DUCT HAS BEEN RELOCATED. IF THIS ROOM IS STILL ENCLOSED | | BY FIRE-RESISTANCE RATED CONSTRUCTION, THIS OPENING IS | | REQUIRED TO BE PROTECTED BY A FIRE DAMPER IN ACCORDANCE | | WITH FBC,M 607.5. ALSO, THE 50X26 SUPPLY DUCT FROM | | CAHU-1 SHOWS A TEE FITTING OVER ALCOVE A1.104. AT THIS | | LOCATION THERE ARE TWO DUCTS PENETRATING THE RATED WALL | | BUT ONLY ONE DUCT SHOWS OPENING PROTECTIVE FSD | | | | 3. OK | | | | 4. OK | | | | 5. OK | | | | 5A. M1-1.2: EF-3 DUCT PENETRATING FLOOR/CEILING | | ASSEMBLY ABOVE ROOM D1.107, IS THIS DUCT ENTERING A | | SHAFT? IF SO, PROVIDE FIRE AND SMOKE DAMPER AS REQUIRED | | BY FBC,M 607.5.5.1. | | | | 6. OK, EXCEPT: KEY NOTE #6 INDICATES ONLY THE TWO | | FIRE/SMOKE DAMPERS ON THE SMOKE EXHAUST DUCT AT THE | | ?ATRIUM? ARE TO BE CONTROLLED BY THE SMOKE CONTROL | | SYSTEM. HAS THERE BEEN A RATIONAL ANALYSIS DONE TO | | DETERMINE WHICH DAMPERS SHOULD BE OPENED AND CLOSED | | DURING SMOKE CONTROL MODE? OPENINGS IN SMOKE BARRIERS | | SHALL BE PROTECTED BY AUTOMATIC-CLOSING DEVICES | | ACTUATED BY THE REQUIRED CONTROLS FOR THE MECHANICAL | | SMOKE CONTROL SYSTEM IN ACCORDANCE WITH FBC,M 513.5.2. | | THIS MAY ALSO APPLY TO THE FIRE/SMOKE DAMPERS IN THE | | SMOKE EXHAUST DUCT PENETRATIONS OF THE SHAFT | | ENCLOSURES. | | | | 7. OK | | | | 8. OK | | | | 9. OK | | | | 10. OK | | | | 11. M1-2.3 WILL BE REVIEWED IN RESPONSE TOPART OF REV | | 10 COMMENTS. | | | | 12. OK | | | | 13. M1-3.2: HOW WILL THE FIRE/SMOKE DAMPERS BE ACCESSED | | FOR SERVICE, MAINTENANCE AND TESTING ABOVE THIS STAIR | | CAP? EVEN WITH 4?9? BETWEEN THE CAP AND THE DECK ABOVE, | | AT LEAST 2 OF THE DAMPERS MAY BE RENDERED INACCESSIBLE | | BY THE ROUTING OF THE DUCTS. ALSO, IF THE STAIR CAP IS | | TO BE USED AS A SERVICE PLATFORM, IT SHALL BE REQUIRED | | TO MEET THE REQUIREMENTS FOR A SERVICE PLATFORM IN | | ACCORDANCE WITH THE FBC. | | | | 14. M1-3.2: THERE IS ONE DUCT SHOWN PENETRATING | | PROGRAM/MEETING ROOM C3.306 TO FEED TWO VAV BOXES. | | WHILE THE SIZE OF THE DUCTS FEEDING THE VAV?S IS | | DETEMINED BY THE INLET SIZE ON THE VAV, A SIZE NEEDS TO | | BE PROVIDED FOR THE DUCT PENETRATING THE WALL BEFORE IT | | BRANCHES TO FEED THE TWO VAV?S. PLEASE CLARIFY. FBC,M | | 603.1 | | | | 15. OK | | | | 16. OK | | | | 17. OK | | | | 18. OK | | | | REV. 10 COMMENTS: | | | | 1. OK | | | | 2. OK | | | | 3. M1-1.3 THROUGH M1-5.3: ACCORDING TO MANUFACTURER?S | | INSTALLATION INSTRUCTIONS, THE CO SENSORS ARE GOOD FOR | | APPROXIMATELY 5000 SQ FT OR A 40 FT RADIUS. BASED ON | | THE LAYOUT SHOWN ON PLANS, THERE ARE AREAS NOT | | ADEQUATELY COVERED BY THE SENSORS. SHOW DETECTORS | | LOCATED TO PROVIDE FULL COVERAGE OF THE PARKING GARAGE. | | FBC,M 304.1 | | | | 4. OK | | | | 5. OK PENDING VERIFICATION OF INTAKE LOCATION. | | | | 6. OK | | | | 7. OK | | | | 8. OK | | | | 9. OK | | | | 10. OK | | | | NEW COMMENTS RELATED TO REV. 12A: | | | | 1. M4-4.0: SEQUENCE OF OPERATION NOTE #1, ACTIVATION OF | | THE SMOKE CONTROL SYSTEM SHALL BE IN COMPLIANCE WITH | | FBC 909.12.3. | | | | 2. M4-4.0: SEQUENCE OF OPERATION NOTE #2, THIS NOTE IS | | IN CONFLICT WITH THE NOTE ON FLOOR PLANS WHICH | | INDICATES SMOKE DAMPERS ARE TO BE CONTROLLED BY DUCT | | SMOKE DETECTORS. ALSO, ALL SMOKE DAMPERS WHICH ARE | | RELATED TO THE SMOKE CONTROL SYSTEM AND REQUIRED BY THE | | SMOKE CONTROL SYSTEM FOR THE ATRIUM AREA SHALL BE | | CONTROLLED BY THE SMOKE CONTROL SYSTEM. FBC,M 513.5.2 | | | | 3. M4-4.0: SEQUENCE OF OPERATION NOTES 2 THROUGH 7: A | | RATIONAL ANALYSIS FOR THE DESIGN OF THE SMOKE CONTROL | | SYSTEM SHALL BE PROVIDED TO DETERMINE THE ACTUAL | | REQUIRED SEQUENCE OF OPERATIONS, INCLUDING SMOKE DAMPER | | ACTUATION, RELATED TO THE PROPER OPERATION OF THE SMOKE | | CONTROL SYSTEM IN ACCORDANCE WITH FBC,M 513.4. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
7 |
Status |
F |
Date |
2007-09-15 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-09-15 |
Time |
15:28 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-09-11 |
Time |
17:55 |
Sent To |
|
|
Notes |
2007-09-15 14:22:11 | REVISION 11 1ST REVIEW | | ACTION: DENIED | | | | FBC 2004 W/ 2005 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | NOTE: A WRITTEN DESCRIPTION OR NARRATIVE OF CHANGES | | BEING MADE AS PART OF A REVISION, WHILE NOT REQUIRED, | | WOULD BE HELPFUL IN DETERMINING THE NATURE AND EXTENT | | OF CHANGES AND WOULD HELP EXPEDITE THE REVIEW PROCESS. | | THIS IS ESPECIALLY WHEN THERE ARE SEVERAL AREAS ON | | PLANS WHICH ARE CLOUDED, YET CONTAIN NO DISCERNABLE | | DIFFERENCES FROM THE PREVIOUS PERMIT SET OF PLANS | | (REV.8). | | | | 1. THERE ARE SOME MECHANICAL PAGES INCLUDED IN THIS | | REVISION WHICH WERE INCLUDED IN REV.10. COMMENTS FROM | | THE REVIEW OF REV.10 MECHANICAL PLANS HAVE NOT BEEN | | ADDRESSED. THEREFORE, ANY PAGES WHICH HAVE OUTSTANDING | | COMMENTS FROM REV.10 WILL NOT BE REVIEWED AT THIS | | TIME: | | M1-1.3, M1-2.3, M1-3.3, M1-4.3, M1-5.3 | | | | THE FOLLOWING COMMENTS ARE BASED ON A SET OF REV.11 | | PLANS THAT HAVE BEEN MARKED-UP TO DEMONSTRATE THE | | EXTENT AND LOCATION OF CODE DEFICIENCIES. PER A | | CONVERSATION WITH WPB FIRE MARSHAL MIKE CARSILLO AND | | GEORGE WANDOVER OF MEINHART ENGINEERS, A MEETING MAY BE | | NECESSARY TO GO OVER THE COMMENTS AND DETERMINE THE | | BEST COURSE OF ACTION IN ADDRESSING THE COMMENTS. | | | | 2. M1-1.1: THERE ARE NUMEROUS DUCT PENETRATIONS AND | | TRANSFER OPENINGS WHICH ARE CURRENTLY PROTECTED BY FIRE | | DAMPERS BUT ALSO REQUIRE PROTECTION BY SMOKE DAMPERS. | | BASED ON THE LOCATION OF FIRE RATED CORRIDORS AS SHOWN | | ON LS1-1.1, SMOKE DAMPERS ARE REQUIRED AT ALL DUCT | | PENETRATIONS AND AIR TRANSFER OPENINGS IN SMOKE | | BARRIERS OR CORRIDORS WHICH REQUIRE SMOKE AND DRAFT | | CONTROL DOORS IN ACORDANCE WITH FBC, BUILDING. SEE | | FBC,M 607.5.4 AND FBC 715.3.3. AT LEAST ONE DUCT (AT | | ROOM A1.207 IS MISSING BOTH FIRE AND SMOKE DAMPERS. SEE | | MARKED-UP PLAN FOR LOCATIONS. | | | | 3. M1-1.1: EXHAUST DUCTS FOR EF-1 AND EF-5 ARE | | PENETRATING A SHAFT ENCLOSURE AT THE 2ND FLOOR/CEILING | | ASSEMBLY ABOVE ROOM A1.207. THESE PENETRATIONS SHALL BE | | PROTECTED BY BOTH FIRE AND SMOKE DAMPERS IN ACCORDANCE | | WITH FBC,M 607.5.5.1. NO OPENING PROTECTIVES ARE SHOWN | | ON PLAN. | | | | 4. M1-1.2: SEE COMMENT #2 REGARDING DUCT PENETRATIONS | | AND AIR TRANSFER OPENINGS PENETRATING LOBBY C1.008. SEE | | MARKED-UP PLANS FOR LOCATION. | | | | 5. M1-1.2: EF-4 RISER DUCT IS REQUIRED TO BE ENCLOSED | | IN SHAFT CONSTRUCTION PER FBC 707.2. DUCTS PENETRATING | | THIS ENCLOSURE REQUIRE FIRE AND SMOKE DAMPERS AS | | OPENING PROTECTIVES PER FBC,M 607.5.5.1. | | | | 6. M1-2.1: SEE COMMENT #2 REGARDING DUCT PENETRATIONS | | AND AIR TRANSFER OPENINGS PENETRATING CORRIDOR A2.007 | | AND STAIR A2.003. SEE MARKED-UP PLAN FOR LOCATIONS. | | | | 7. M1-2.1: THERE ARE AT LEAST 5 SMOKE DAMPERS SHOWN ON | | PLANS WHICH ARE NOT REQUIRED BY CODE AS THEY ARE NOT | | LOCATED IN EITHER A SMOKE BARRIER OR A FIRE-RATED | | CORRIDOR. SEE MARKED-UP PLANS FOR LOCATIONS. THEY MAY | | STILL BE INSTALLED IF DEEMED NECESSARY BY DESIGN. | | HOWEVER, A DETERMINATION IS NEEDED DUE TO THE | | OUTSTANDING ISSUE OF HOW SMOKE DAMPERS IN THIS BUILDING | | ARE TO BE CONTROLLED IN ACCORDANCE WITH FBC,M 607.5.4.1 | | ABSENT FULL-COVERAGE SMOKE DETECTION IN THE BUILDING. | | | | 8. M1-2.1: OFFICE A2.404 HAS NO SUPPLY AIR. THE SUPPLY | | DROP FOR THIS ROOM APPEARS TO HAVE BEEN MISTAKENLY | | SHOWN IN CONFERENCE A2.405. PLEASE CORRECT. | | | | 9.M1-2.1: SMOKE EXHAUST DUCTS AT THE ATRIUM SHOW FIRE | | DAMPERS AT WALL PENETRATIONS. WHERE THE INSTALLATION OF | | A FIRE DAMPER WILL INTERFERE WITH THE OPERATION OF A | | REQUIRED SMOKE CONTROL SYSTEM IN ACCORDANCE WITH FBC,M | | SECTION 513, APPROVED ALTERNATIVE PROTECTION SHALL BE | | UTILIZED PER FBC,M 607.2.1. COMBINATION FIRE/SMOKE | | DAMPERS WHICH ARE CONTROLLED BY THE SMOKE CONTROL | | SYSTEM ARE CALLED FOR ON THE SMOKE CONTROL RISER | | DIAGRAM ON M4-1.0 AND WILL MEET THE REQUIREMENT FOR | | APPROVED ALTERNATIVE PROTECTION. | | | | 10. M1-2.2: EF-4 RISER, EXHAUST DUCT PENETRATION OF | | SHAFT REQUIRES FIRE AND SMOKE DAMPERS AS OPENING | | PROTECTIVE PER FBC,M 607.5.5.1 | | | | 11. M1-2.3 WAS NOT REVIEWED. HOWEVER, SEE MARKED-UP | | PLANS FOR CONCERNS PRIOR TO RESUBMITTAL. | | | | 12. M1-3.1: SEE COMMENT #7 REGARDING SMOKE DAMPERS. SEE | | MARKED-UP PLAN FOR LOCATIONS. | | | | 13. M1-3.2: STAIR 10 C3.001 HAS DUCTS FROM RTU-1 ABOVE | | WITHIN THE STAIR ENCLOSURE. PENETRATIONS OF STAIR | | ENCLOSURES BY DUCTS OTHER THAN THOSE REQUIRED FOR | | INDEPENDENT PRESSURIZATIONAND VENTILATION OF THE | | STAIR ARE PROHIBITED BY FBC 1019.1.2 AND 1019.1.2. | | | | 14. M1-3.2: SEE COMMENT #2 REGARDING DUCT PENETRATIONS | | AND AIR TRANSFER OPENINGS PENETRATING MULTIPLE | | CORRIDORS AND LOBBY C3.303. SEE MARKED-UP PLANS FOR | | LOCATION. | | | | 15. M1-3.2: SEE COMMENT #7 REGARDING SMOKE DAMPERS. SEE | | MARKED-UP PLAN FOR LOCATIONS. | | | | 16. M1-4.1: SERVER ROOM A4.416, ALL DUCT PENETRATIONS | | OF THIS ROOM EXCEPT ONE ARE PROTECTED WITH BOTH FIRE | | AND SMOKE DAMPERS. ONE TRANSFER DUCT COMMUNICATING WITH | | OPEN WORK A4.311 HAS A FIRE DAMPER BUT NO SMOKE DAMPER. | | WHAT IS THE PURPOSE OF THIS TRANSFER AND WHY DOES IT | | NOT REQUIRE THE SAME PROTECTION AS THE OTHER DUCTS? | | | | 17. M1-4.1: SEE COMMENT #7 REGARDING SMOKE DAMPERS. SEE | | MARKED-UP PLAN FOR LOCATIONS. | | | | 18. M1-5.1: SEE COMMENT #7 REGARDING SMOKE DAMPERS. SEE | | MARKED-UP PLAN FOR LOCATIONS. | | | | THE FOLLOWING PAGES HAVE BEEN REVIEWED FOR CODE | | COMPLIANCE AND STAMPED: | | | | M2-1.0, M2-2.0, M2-3.0, M3-1.0, M3-2.0 | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
6 |
Status |
P |
Date |
2007-08-01 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-08-01 |
Time |
15:04 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-07-31 |
Time |
14:23 |
Sent To |
|
|
Notes |
2007-08-01 15:03:54 | REVISION 10 - 1 PAGE PASSED. | | | | PG M3-1.0 REVIEWED AND STAMPED. ALL OTHER SUBMITTED | | MECHANICAL PAGES: | | ---------------DENIED----------------- | | | | FBC 2004 CODE FAMILY W/ 2005 REVISIONS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | 1. WHAT IS THE HEIGHT OF FCU 1-6? SHOW COMPLIANCE WITH | | FBC,M 304.5. | | | | 2. M1-1.3 THROUGH M1-5.3: GARAGE EXHAUST FANS ARE TO | | RUN INTERMITTANTLY, CONTROLLED BY C.O SENSORS. HOWEVER, | | AUTOMATIC OPERATION OF THE SYSTEM SHALL NOT REDUCE THE | | VENTILATION RATE BELOW0.05 CFM PER SQUARE FOOT OF THE | | FLOOR AREA AND THE SYSTEM SHALL BE CAPABLE OF PRODUCING | | A VENTILATION RATE OF 1.5 CFM PER SQUARE FOOT OF FLOOR | | AREA. FBC,M 404.2. THE 0.05 CFM/SQ.FT IS TO BE | | CONTINUOUS. | | | | 3. M1-1.3 THROUGH M1-5.3: IN PREVIOUS REVIEW COMMENT #3 | | (DATED 4/5/07), THE SPECS AND INSTALL INSTRUCTIONS FOR | | THE C.O. DETECTION SYSTEM WERE REQUESTED. THAT | | INFORMATION WAS NOT PROVIDED WITH THE SUBMITTED PLANS. | | A COMPLETE REVIEW OF THE GARAGE VENTILATION SYSTEM CAN | | NOT BE DONE AT THIS TIME. | | | | 4. M1-1.3: PLEASE IDENTIFY THE LARGE PIPES RUNNING FROM | | THE MECHANICAL ROOM TO THE FIRE PUMP ROOM. PIPES ON | | RISER ARE SHOWN GOING UP BUT THEY DO NOT APPEAR ON | | UPPER FLOORS. PLEASE CORRECT. FBC 106.1.1 | | | | 5. M1-1.3: PLEASE SHOW HOW VENTILATION (OUTDOOR AIR) IS | | TO BE PROVIDED IN OFFICE B1-104 AND TICKET BOOTH | | B1-109. | | NOTE: TICKET BOOTHS AND SIMILAR USES THAT ARE ACCESSORY | | TO A PUBLIC GARAGE SHALL BE MAINTAINED AT A POSITIVE | | PRESSURE AND SHALL BE PROVIDED WITH VENTILATION IN | | ACCORDANCE WITH SECTION 403.3 PER FBC,M 404.3. | | | | 6. M1-1.3: WHAT IS THE SOURCE OF MAKE-UP AIR FOR THE | | 960 CFM OF EXHAUST IN FIRE PUMP ROOM B1-106 AND THE 875 | | CFM OF EXHAUST IN FUEL TANK STORAGE B1-107? SEE FBC,M | | 403.1. | | | | 7. M1-1.3: ACCORDING TO PG LS1-1.0, FUEL TANK ROOM | | B1-107 IS 3-HOUR RATED. PLEASE SPECIFY A 3-HOUR | | FIRE/SMOKE DAMPER BETWEEN FUEL TANK ROOM AND FIRE PUMP | | ROOM. ALSO, A 3-HOUR FIRE DAMPER IS REQUIRED AT THE | | 22X14 EXHAUST DUCT PENETRATION OF THE FLOOR/CEILING | | ASSEMBLY ABOVE THE FUEL TANK ROOM TO MAINTAIN THE | | 3-HOUR RATING OF THE ROOM. FBC,M TABLE 607.3.1 | | | | 8. M1-2.3: PLEASE SHOW CU 1-3, 1-6, 1-7 AND ANY OTHER | | POTENTIALLY EXPOSED MECHANICAL EQUIPMENT TO BE | | PROTECTED FROM VEHICLE DAMAGE PER FBC,M 304.5. | | | | 9. M1-2.3 THROUGH M1-5.3: THE 22X14 EXHAUST DUCT RISER | | SHALL BE PROTECTED FROM MECHANICAL DAMAGE BY APPROVED | | BARRIERS. FBC,M 603.13 | | | | 10. M3-2.0: GARAGE FAN SCHEDULE, WHAT TYPE OF WALL | | TERMINATION WILL BE USED AT EF20-23? THE SCHEDULE DOES | | NOT CALL FOR LOUVERS. SCREENS ALONE WILL NOT PROTECT | | AGAINST WEATHER CONDITIONS. FBC,M 401.6 | | | | 11. M4-3.0: UNABLE TO REVIEW GARAGE VENTILATION SYSTEM | | AT THIS TIME. SEE CURRENT AND PREVIOUS COMMENT #3. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
P |
Date |
2007-04-05 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-04-05 |
Time |
16:45 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-04-05 |
Time |
10:42 |
Sent To |
|
|
Notes |
2007-04-05 14:21:13 | ALL MECH PROVISOS DATED 1/27/07 HAVE BEEN ADEQUATELY | | ADDRESSED BY REVISION (8) SUBMITTED ON 3/21/07 | | THE FOLLOWING PAGES ARE REVISED: | | | | M1-1.0 | | M1-1.1 | | M1-1.2 | | M1-2.0 | | M1-2.1 | | M1-2.2 | | M1-3.0 | | M1-3.1 | | M1-3.2 | | M1-4.0 | | M1-4.1 | | M1-4.2 | | M1-5.0 | | M1-5.1 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
F |
Date |
2007-04-05 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-04-05 |
Time |
10:12 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-04-04 |
Time |
15:10 |
Sent To |
|
|
Notes |
2007-04-05 10:12:41 | ---------------DENIED------------------ | | | | GARAGE REVISIONS (7) SUBMITTED 3/16/07 | | | | 1. NEW MECHANICAL SHEETS SUBMITTED ARE MODIFYING | | EXISTING SHEETS WHICH ALREADY COVER THE SCOPE OF | | MECHANICAL WORK IN THE PERMIT SET OF PLANS. PLEASE | | REVISE EXISTING SHEETS TO INCLUDE THE ADDED WORK OR | | SHOW THE FULL SCOPE OF WORK TO BE PERFORMED IN THESE | | AREAS ON NEW SHEETS WHICH WOULD REPLACE/SUPERCEDE | | EXISTING SHEETS. | | | | 2. EQUIPMENT LOCATED IN PUBLIC GARAGES SHALL BE | | INSTALLED A MINIMUM OF 8 FEET ABOVE THE FLOOR, OR A | | MINIMUM OF 2 FEET HIGHER THAN THE HEIGHT OF THE TALLEST | | VEHICLE, OR PROTECTED FROM MOTOR VEHICLE IMPACT. FBC,M | | 304.5 | | | | 3. PLEASE PROVIDE MANUFACTURER'S SUBMITTAL AND | | INSTALLATION INSTRUCTIONS FOR C.O. SYSTEM. FBC,M 304.1 | | | | NOTE: A COMPLETE REVIEW OF THIS WORK CAN NOT BE | | PERFORMED PRIOR TO THE INCORPORATION OF ALL MECHANICAL | | WORK TO BE PERFORMED IN THESE AREAS AS STATED IN | | COMMENT #1. | | | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2007-01-27 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2007-01-27 |
Time |
10:12 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2007-01-27 |
Time |
10:12 |
Sent To |
|
|
Notes |
2007-01-27 11:01:42 | PROVISO: | | | | 1.NON-HABITABLE ROOMS (I.E., STORAGE, ELECTRICAL, | | ETC.)ARE NOT REQUIRED TO COMPLY WITH 2004 FMC 601.4 | | EXCEPTION #3.PLEASE ALSO NOTE, RETURN AIR GRILLES ARE | | INDICATED IN THESE ROOMS AND THE ARCHITECTURAL PLANS | | INDICATE NO CEILING.PLEASE REMOVE R/A GRILLES FROM | | THESE AREAS. | | | | 2.PUMP ROOM A1.112 INDICATES A TRANSFER FROM THE PUMP | | ROOM INTO THE FILE ROOM.PER 2004 FMC 502.1.3, | | EQUIPMENT ROOMS THAT HOUSE SOURCES OF FUMES, ODERS OR | | NOXIOUS GASES SHALL BE DESIGNED TO AND CONSTRUCTED SO | | AS TO PREVENT SPREADING OF SUCH CONTAMINANTS TO OTHER | | OCCUPIED PARTS OF THE BUILDING. | | | | 3.PLEASE PROVIDE DUCT SIZES TO VAV'S. | | | | 4.MANY OF THE NON-HABITABLE ROOMS INDICATE RETURN AIR | | GRILLES TO THE PLENUM.ACCORDING TO THE ARCHITECTURAL | | DRAWINGS THESE ROOMS HAVE NO CEILING.PLEASE REMOVE | | RETURN AIR GRILLES FROM THESE AREAS IF IN FACT THEY DO | | NOT GO INTO THE RETURN AIR PLENUM. | | | | 5.ADDITIONAL PERMITS REQUIRED FOR FUEL PIPING. | | | | PLEASE SEE ELECTRICAL COMMENTS FOR SIZING OF THE DIESEL | | FUEL TANKS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT HAROLD MOSER | | AT (561)805-6732 OR E-MAIL [email protected]. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2006-12-26 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2006-12-26 |
Time |
13:11 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2006-12-26 |
Time |
11:47 |
Sent To |
|
|
Notes |
2006-12-26 13:25:55 | DENIED: | | RESPONSE TO COMMENTS DATED 11-07-06: | | | | COMMENT 1:OK | | COMMENT 2A & 2B:OK | | | | COMMENT 2C:RESPONSE INDICATES THE CAPACITY OF THE | | FUEL STORAGE TANK LOCATED ON THE FIRST FLOOR IS 500 | | GALLONS. THE SUBMITTAL BOOK REFLECTS (2) DAY TANKS ONE | | WITH THE CAPAPCITY OF 100 GALLONS AND THE SECOND ONE | | WITH A CAPACITY OF 150 GALLONS.PLEASE SUBMIT THE | | CORRECT SUBMITTAL FOR THE DAY TANK. | | | | COMMENT 3:OK | | | | COMMENT 9:OK | | | | COMMENT 10:OK | | | | COMMENT 11:OK | | | | COMMENT 12:OK | | | | COMMENT 13:OK | | | | COMMENT 14:OK | | | | COMMENT 15:OK | | | | COMMENT 16:RESPONSE INDICATES FIRE RATINGS ARE NOT | | REQUIRED FOR ELECTRICAL RM.SMOKE RATING IS INDICATED | | FOR THE MECHANICAL ROOM AND A 1 HR RATING FOR THE | | ELEVATOR EQUIPMENT RM.PER 2004 FMC 607.8,SMOKE | | DAMPERS, FIRE DAMPERS AND COMBINATION DAMPERS ARE TO BE | | IDENTIFIEDON THE BUILDING PLANS.PLEASE NOTE, LIFE | | SAFETY PLANS IDENTIFY CERTIAN WALLS/PARTITIONS AS | | HAVING A FIRE, SMOKE OR FIRE/SMOKE RATING THAT ARE NOT | | REFLECTED ON THE ARCHITECTURAL PLANS.PLEASE CORRELATE | | LIFE SAFETY, ARCHITECTURAL AND MECHANICAL PLANS. PLEASE | | SEE ?ADDITIONAL COMMENT #21?. | | | | COMMENT 17:OK | | | | COMMENT 18:OK | | | | COMMENT 19:OK | | | | COMMENT 20:OK | | ADDITIONAL COMMENTS: | | | | 21.THE FOLLOWING PLAN SHEET & ROOM NUMBERS ARE | | MISSING DAMPERS AS REQUIRED PER 2004 FMC 607.5.4 & | | 607.5.4.1: | | | | DWG M1-1.1; RM# - A1.014, A1.118, A1.110 | | DWG M1-2.1; RM# - C1.101, D1.108, A1.110, D1.111. | | | | PLEASE ALSO NOTE ON DWG #M1-1.2, THE OUTSIDE AIR INTAKE | | TO THE WEST EXTERIOR WALL.PER 2004 FMC 401.5.1, | | INTAKE OPENINGS SHALL BE LOCATED A MINIMUM OF 10 FT | | FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS | | STREETS, ALLEYS, PARKING LOTS OR LOADING DOCKS. | | | | DWG M1-2.1 CORRIDOR A2.010, 38/18 & 12/10 DUCT,RM # | | A2.104, A2.108, A2.407, A2.08, A2.409 | | DWG M1-2.2 RM# C2.101, C2.219, D2.108 | | DWG M1-3.1 CORRIDOR A3.008, A3.012, A3.406, A3.308, | | A3.706, C3.414 RM# A3.107, A3.106, A3.421, A3.420, | | A3.105, A3.104, A3.304, A3.205, C3.314, C3.413, A3.705, | | A3.603, A3.115, A3.514, A3.513 | | DWG M1-3.2 CORRIDOR C3.417, C3.407, C3.426, RM# C3.418, | | C3.310, C3.309, C3.402, C3.107,C3.101 | | DWG M1-4.1 CORRIDOR A4.009, A4.008, A4.007 RM#A4.415, | | A4.101 & F/D FROM RM# A4.416. | | DWG M1-4.2 RM# C4.106, C4.104.PLEASE NOTE, MECHANICAL | | FLOOR PLAN DOES NOT MATCH THE LIFE SAFETY PLAN FOR THIS | | PARTICULAR FLOOR.THE VOICE DATA RM & ELECTRICAL RM | | ARE NOT INDICATED ON THE MECHANICAL SHEET. | | | | DWG M1-5.1 CORRIDOR A5.009, A5.008, A5.007 RM# A5.303, | | A5.203, A5.101, A5.507, A5.107, A5.416 | | | | 22.PLAN SHEET M1-1.0 KEY NOTE 1 SPECIFIES THE | | CONDENSATE TO MOP SINK IN THE GARAGE AREA.PER CITY | | CODE SEC. 90-125(5) CONDENSATE SHALL NOT TERMINATE INTO | | THE SANITARY.PLAN SHEET P1-10U INDICATES THE | | CONDENSATE TO A DRYWELL WHICH IS CODE COMPLIANT. PLEASE | | CORRELATE MECHANICAL PLAN WITH PLUMBING PLAN. | | | | ADDITIONAL PERMIT REQUIRED FOR FUEL PIPING. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | AT (561)805-6719 OR E-MAIL [email protected]. | | | | | | | | | | | | | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2006-11-07 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2006-11-07 |
Time |
15:32 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2006-11-07 |
Time |
15:32 |
Sent To |
|
|
Notes |
2006-11-07 16:00:24 | DENIED: | | RESPONSE TO COMMENTS FROM PREVIOUS REVIEW THAT WERE NOT | | ADDRESSED: | | | | PLEASE NOTE, RESPONSE TO COMMENTS 1, 2 & 3 STATES | | INFORMATION WILL BE PROVIDED WITH 100% DOCUMENTATION. | | ****************************************************** | | * | | COMMENT 1:REQUEST FOR ENERGY & SIZING CALCULATIONS IN | | ACCORDANCE WITH 2004 FBC CHAPTER 13 SUB-CHAPTER 13-4. | | | | RESPONSE INDICATES CALCS WILL BE PROVIDED WITH 100% | | DOCUMENTS. | | | | COMMENT 2:REQUEST FOR INFORMATION IN RELATION TO THE | | FUEL TANK & DIESEL FIRE PUMPS | | A) VENTILATION FOR THE ROOM (EXHAUST FANS WERE | | INDICATED WITH NO VENTILATION CALCS).PLEASE REFERENCE | | 2004 FMC 502.1.2 THROUGH 502.1.4 & NFPA 37-6.3.5.4 | | THROUGH 6.3.5.4.3. | | | | B) DISTANCE TO PROPERTY LINES WITH RELATION TO THE | | TERMINATION OF EXHAUST. | | | | C) CAPACITY OF THE FUEL TANKS.THE SUBMITTAL BOOK | | INDICATES (1) 100 GAL, (1) 150 GAL, & (1) 500 GAL | | SUB-BASE FUEL TANK.PLANS DO NOT CORRELATE WITH | | SUBMITTAL BOOK. SUBMITTAL BOOK INDICATES 500 GAL | | SUB-BASE FUEL TANK, PLAN SHEET P3-4.0 DETAIL 03 SHOWS | | THE 500 GAL TANK AT THE GROUND LEVEL WITH A DAY TANK ON | | THE ROOF.PLAN SHEET P1-6.0 INDICATES THE GENERATOR | | AS "NATURAL GAS". PLEASE CLARIFY.PLEASE ALSO NOTE, | | PLAN SHEET P-3.40 PROVIDES A SCHEMATIC FOR THE DIESEL | | FUEL PIPING, SUPPLY, RETURN, & VENT PIPING SHOWN ON | | SHEETS P1-1.0, P1-2.0, P1-3.0, P1-4.0, P1-5.0 & P1-6.0. | | DIESEL FUEL SUPPLY AND RETURN PIPING ARE NOT DEPICTED | | ON PLAN SHEET P1-6.0 ONLY THE VENT PIPING.PLAN SHEE | | P1-6.0 SHOWS THE NATURAL GAS SUPPLYING FUEL TO THE | | GENERATOR.THIS DOES NOT CORRELATE WITH THE SUBMITTAL | | BOOK.PLEASE NOTE, PER NFPA 37-6.3.5.3 ROOMS HOUSING | | FUEL TANKS WITH AN AGGREGATE CAPACITY LESS THAN 1320 | | GAL, EACH TANK ROOM SHALL BE PROVIDED WITH SPILL | | CONTAINMENT CONSISTING OF EITHER A WALL, CURB, OR DIKE | | HAVING A CAPACITY AT LEAST EQUAL TO THAT OF THE LARGEST | | TANK.FUEL TANKS LOCATED ON THE ROOF SHALL COMPLY | | WITH NFPA 37-6.3.4 THROUGH 6.3.4.2. | | | | COMMENTS 10 & 11 NO RESPONSE WAS GIVEN. | | | | COMMENT 3 & 15:FIRE & FIRE/SMOKE DAMERS AT SHAFT | | PENETRATIONS.PLEASE INDICATE DAMPERS ON THE RISERS AS | | REQUESTED IN PREVIOUS REVIEW. | | | | COMMENT 9:PLAN SHEET M1-1.3 PROVIDE ELEVATION OF THE | | MAKE -UP AIR AND EXHAUST FROM MECHANICAL ROOM B1.102 | | THE REPONSE SENTENCE WAS NOT COMPLETE AND DID NOT | | PROVIDE ELEVATION. | | | | COMMENTS 10 & 11 NO RESPONSE WAS GIVEN. | | | | COMMENT 12:THE EQUIPMENT SCHEDULE WAS PROVIDED BUT | | THE CHILLER SCHEDULE ON SHEET M3-2.0 ANNOTATES ALL | | CHILLERS AS CH-1 NOT CH-1, CH-2, CH-3 | | | | | | NEW COMMENTS: | | 13.PLEASE PROVIDE SEQUENCE OF OPERATION FOR THE SMOKE | | CONTROL OR EVAC IN ACCORDANCE WITH 2004 FMC 513 OR | | CHAPTER 909 OF THE FBC. | | | | 14.PLEASE PROVIDE VENTILATION CALCS FOR THE GARAGE | | PER 2004 FMC 404. | | | | 15.PLEASE INDICATE THE VOLUME OF THE ATRIUM. | | | | 16.PLAN SHEET M1-1.1, FIRE DAMPERS ARE MISSING FROM | | ELECTRICAL ROOM A1.102.PLEASE VERIFY FIRE DAMPERS, | | FOR ALL ELECTRICAL, MECHANICAL AND STORAGE ROOMS. | | | | 17.PLAN SHEET M1-2.2, SUPPLY/RETURN TO AHU-2 & | | EXHAUST DUCT (EF-4), SHAFT IS NOT LARGE ENOUGH TO | | ENCLOSE THESE DUCTS.PLEASE NOTE, DUCTS SHALL HAVE | | SUFFICIENT CLEARANCE FOR INSTALLATION & INSPECTION PER | | 2004 FMC 603.1.3. | | | | 18.PLEASE PROVIDE ANCHORING DETAIL FOR INSTALLATION | | OF THE COOLING TOWERS PER 2004 FBC 106.1.1.2 , 1509.4 & | | 1509.7. | | | | 19.PROVIDE DETAIL FOR ANCHORING & VIBRATION ISOLATION | | ON ALL MOUNTED EQUIPMENT. | | | | 20.PLAN SHEET M5-3.0 DETAIL 6 SHOWS 1" INSULATION ON | | THE 4"CHILLED WATER PIPING.WILL THE INSULATION | | INCREASE TO 2" ON THE LARGER PIPING? | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | AT (561)805-6719 OR E-MAIL [email protected]. | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
35 |
Status |
P |
Date |
2009-05-01 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-05-01 |
Time |
16:12 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-05-01 |
Time |
16:12 |
Sent To |
|
|
Notes |
2009-05-01 16:12:53 | REVISIONS OK -- SHTS P2-1.0U & P3-1.0 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
34 |
Status |
P |
Date |
2009-04-02 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-03-31 |
Time |
09:34 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-03-31 |
Time |
09:34 |
Sent To |
|
|
Notes |
2009-03-31 09:34:19 | REVISION PASSED/PROVISO: | | | | ***REVISION REQUIRED*** | | | | | | 1. SHTS P2-1.0U P3-1.0 THE MOP SINK SHALL CONNECT TO | | THE GREASE SYSTEM, NOT THE SANITARY SYSTEM. SECTION | | 1003.3.1. -- ALSO THE MOP SINK SHALL NOT DRAIN THRU THE | | WET VENT FOR THE BATHROOM FIXTURES PER SECTION 909.1. | | -- PLANS RED LINED WITH REVISION TO FOLLOW. | | | | | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
33 |
Status |
P |
Date |
2009-03-31 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-03-31 |
Time |
08:48 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-03-31 |
Time |
08:48 |
Sent To |
|
|
Notes |
2009-03-31 09:35:33 | REVISIONS OK -- SHTS P2-1.0 & P3-5.0 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
32 |
Status |
P |
Date |
2009-01-21 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-01-21 |
Time |
10:02 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-01-20 |
Time |
16:58 |
Sent To |
|
|
Notes |
2009-01-21 10:02:52 | REVISION OK -- SHT IR-1 -- REVISIONS 11 & 16B NOT FOUND | | OR APPROVED. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
31 |
Status |
F |
Date |
2009-01-20 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-01-20 |
Time |
16:35 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-01-20 |
Time |
16:35 |
Sent To |
|
|
Notes |
2009-01-20 16:38:12 | DENIED | | REFERENCE: | | FBC-2004 CHAPTER 1 | | FBC-2004 PLUMBING | | | | 1. SHT P1-2.2 REVISION INDICATED ABOVE THE MATCH LINE | | IS NOT APPROVED FOR THIS SHEET. SUBMIT REVISIONS FOR | | SHEET P1-2.1 & P1-2.2 WITH THE REVISION FOR EACH SHEET | | AS REQUIRED. SECTION 106.1.3. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
30 |
Status |
P |
Date |
2009-01-20 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-01-20 |
Time |
16:34 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-01-20 |
Time |
16:34 |
Sent To |
|
|
Notes |
2009-01-20 16:35:40 | REVISIONS OK -- SHTS P2-2.0, P3-2.0 & P3-6.0. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
29 |
Status |
P |
Date |
2009-01-20 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-01-20 |
Time |
15:57 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-01-20 |
Time |
15:56 |
Sent To |
|
|
Notes |
2009-01-20 16:02:39 | REVISIONS OK -- SHTS P1-1.0U, P1-1.0, P1-1.2U, P1-1.2, | | P2-1.0, P2-1.0U & P3-1.0 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
28 |
Status |
P |
Date |
2009-01-20 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-01-20 |
Time |
13:52 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-01-20 |
Time |
13:52 |
Sent To |
|
|
Notes |
2009-01-20 13:53:04 | REVISION OK -- SHT P1-1.3 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
27 |
Status |
P |
Date |
2009-01-20 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-01-20 |
Time |
13:37 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-01-20 |
Time |
13:37 |
Sent To |
|
|
Notes |
2009-01-20 13:39:29 | REVISION OK -- SHTS P1-1.0 & P1-1.0U |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
26 |
Status |
F |
Date |
2008-11-25 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-11-25 |
Time |
16:29 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-11-25 |
Time |
16:29 |
Sent To |
|
|
Notes |
2008-11-25 16:32:06 | REVISION DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | | | 1. SHT P1-1.0U REVISION INDEX & FLOOR PLAN FROM | | PREVIOUS SHEET SIGNED, SEALED & DATED ON 9-17-08 | | INDICATES REVISION 193R3 DATED 9-16-08. NEW REVISIED | | SHEET SUBMITTED DELETED REVISION 193R3 AND NOW SHOWS | | REVISION 193R4 DATED 10-30-08 BUT NO CLOUD FOR NEW | | REVISION. PER SECTION 106.1.3 COMPLETE REVISION RECORD | | IS REQUIRED AND ALL NEW REVISIONS SHALL BE INDIDCATED | | WITH A CLOUD AND REVISION NUMBER SHOWING WHERE THE NEW | | REVISION CAN BE LOCATED. -- THIS HAS BEEN INDICATED IN | | A PREVIOUS REVISION REVIEW. | | | | 2. SHT P1-1.0 REVISION INDEX & FLOOR PLAN FROM PREVIOUS | | SHEET SIGNED, SEALED & DATED ON 9-17-08 INDICATES | | REVISION 193R3 DATED 9-16-08. NEW REVISIED SHEET | | SUBMITTED DELETED REVISION 193R3 AND NOW SHOWS REVISION | | 193R4 DATED 10-30-08 BUT NO CLOUD FOR NEW REVISION. PER | | SECTION 106.1.3 COMPLETE REVISION RECORD IS REQUIRED | | AND ALL NEW REVISIONS SHALL BE INDIDCATED WITH A CLOUD | | AND REVISION NUMBER SHOWING WHERE THE NEW REVISION CAN | | BE LOCATED. -- THIS HAS BEEN INDICATED IN A PREVIOUS | | REVISION REVIEW. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
25 |
Status |
P |
Date |
2008-11-25 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-11-25 |
Time |
16:29 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-11-25 |
Time |
16:29 |
Sent To |
|
|
Notes |
2008-11-25 16:29:33 | REVISION OK -- SHT P1-1.2 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
24 |
Status |
F |
Date |
2008-11-17 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-11-17 |
Time |
09:50 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-11-17 |
Time |
09:50 |
Sent To |
|
|
Notes |
2008-11-17 10:57:12 | REVISION DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | | | 1. SHT P1-1.0U REVISION INDEX & FLOOR PLAN FROM | | PREVIOUS SHEET SIGNED, SEALED & DATED ON 9-17-08 | | INDICATES REVISION 193R3 DATED 9-16-08. NEW REVISIED | | SHEET SUBMITTED DELETED REVISION 193R3 AND NOW SHOWS | | REVISION 193R4 DATED 10-30-08 BUT NO CLOUD FOR NEW | | REVISION. PER SECTION 106.1.3 COMPLETE REVISION RECORD | | IS REQUIRED AND ALL NEW REVISIONS SHALL BE INDIDCATED | | WITH A CLOUD AND REVISION NUMBER SHOWING WHERE THE NEW | | REVISION CAN BE LOCATED. | | | | 2. SHT P1-1.0U 2-WAY CLEANOUTS ARE REQUIRED AS THE | | GREASE LINE EXITS THE BUILDING AND BEFORE THE INLET OF | | THE GREASE INTERCEPTOR AND ON THE OUTLET OF THE GREASE | | INTERCEPTOR. THE GREASE INTERCEPTOR PRIOR TO THE GREASE | | INTERCEPTOR OUTLET CAN BE USED FOR BOTH THE INLET | | REQUIREMENT AND THE REQUIREMENT AS THE GREASE LINE | | EXITS THE BUILDING. SECTION 708.3.5 & UTILITY DEPT | | GREASE INTERCEPTOR STANDARD. | | | | 3. SHT 1-1.0U 2-WAY CLEANOUTS ARE REQUIRED ON THE INLET | | AND OUTLET OF THE GREASE INTERCEPTOR. UTILITY DEPT | | GREASE INTERCEPTOR STANDARD. | | | | 4. SHT P1-1.0 REVISION INDEX & FLOOR PLAN FROM PREVIOUS | | SHEET SIGNED, SEALED & DATED ON 9-17-08 INDICATES | | REVISION 193R3 DATED 9-16-08. NEW REVISIED SHEET | | SUBMITTED DELETED REVISION 193R3 AND NOW SHOWS REVISION | | 193R4 DATED 10-30-08 BUT NO CLOUD FOR NEW REVISION. PER | | SECTION 106.1.3 COMPLETE REVISION RECORD IS REQUIRED | | AND ALL NEW REVISIONS SHALL BE INDIDCATED WITH A CLOUD | | AND REVISION NUMBER SHOWING WHERE THE NEW REVISION CAN | | BE LOCATED. | | | | 5. SHT P1-1.0 CHANGES TO THE CONDENSATE HAVE BEEN FOUND | | WITHOUT CLOUDS OR INDICATED BY REVISION NUMBERS. SHOW | | ALL CHANGES WITH CLOUDS AND REVISION NUMBERS. SECTION | | 106.1.3. PLEASE INDICATE ALL CHANGES/REVISIONS ON THE | | SHEET WITH A CLOUD AND A REVISION NUMBER. | | | | 6. SHT P1-1.2U 2-WAY CLEANOUTS ARE REQUIRED ON THE | | INLET AND OUTLET OF THE GREASE INTERCEPTOR. UTILITY | | DEPT GREASE INTERCEPTOR STANDARD. | | | | 7. SHT P1-1.2 THE 2" GOOSENECK VENT FOR THE GREASE | | INTERCEPTOR IS NOT REQUIRED AS THE INLET LINE TO THE | | INTERCEPTOR IS A VENTED LINE. IF THE VENT IS INSTALLED | | IT SHALL BE TERMINATED PER SECTIONS 904.5 & 904.6. | | | | 8. SHT P2-1.0 DETAIL 5 SHOWS CHANGES WITH NO CLOUDS OR | | REVISION NUMBERS INDICATING THE LOCATION OF THE | | REVISIONS. REVISIONS 1 & 2 WERE DELETED AND A REVISION | | DATED 12-06-07 IS INDICATED WITHOUT A REVISION NUMBER. | | PLEASE CLARIFY. SECTION 106.1.3. PLEASE INDICATE ALL | | CHANGES/REVISIONS ON THE SHEET WITH A CLOUD AND A | | REVISION NUMBER. | | | | 9. SHT P2-1.0U DETAIL 5 SHOWS CHANGES WITH NO CLOUDS OR | | REVISION NUMBERS INDICATING THE LOCATION OF THE | | REVISIONS. REVISIONS 1 & 2 WERE DELETED PLEASE CLARIFY. | | SECTION 106.1.3. PLEASE INDICATE ALL CHANGES/REVISIONS | | ON THE SHEET WITH A CLOUD AND A REVISION NUMBER. | | | | 10. SHT P3-1.0 A CLEANOUT IS REQUIRED NEAR THE JUNCTION | | OF THE BUILDING GREASE DRAIN AND THE BUILDING SEWER | | GREASE PER SECTION 708.3.5. PLEASE SHOW ON THE RISER | | DIAGRAM. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
23 |
Status |
P |
Date |
2008-11-17 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-11-17 |
Time |
09:49 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-11-14 |
Time |
16:53 |
Sent To |
|
|
Notes |
2008-11-17 09:50:16 | REVISION OK -- SHT P3-5.0 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
22 |
Status |
F |
Date |
2008-10-28 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-10-28 |
Time |
07:31 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-10-28 |
Time |
07:30 |
Sent To |
|
|
Notes |
2008-10-28 07:45:35 | REVISION DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 MECHANICAL | | | | 1. SHT P1-1.3 INDICATES REVISION TO THE DIESEL FUEL | | SYSTEM FOR THE GENERATORS. THE DIESEL FUEL SYSTEM IS A | | MECHANICAL PERMIT AND ALL CHANGES TO THE DIESEL SYSTEM | | SHALL BE SUBMITTED ON THE MECHANICAL SHEETS. THE DIESEL | | SYSTEM IS INSPECTED FROM THE MECHANICAL SHEETS BY THE | | MECHANICAL INSPECTOR. SECTION 915. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
21 |
Status |
F |
Date |
2008-09-29 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-09-29 |
Time |
08:24 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-09-29 |
Time |
08:24 |
Sent To |
|
|
Notes |
2008-09-29 08:27:58 | | | SUBMITTAL FOR PLANTER WALL DETAIL -2 DENIED. THE | | WATERPROOFING & PROTECTION BOARD IS NOT SHOWN TO THE | | BASE OF THE FOOTER OR UP TO THE SAME HEIGHT AS | | INDICATED IN THE MEETING WITH DAVID MORRIS IN THE LOBBY | | OF CONSTRUCTION SERVICES ON 9-16-8. THIS REQUIRED FOR | | THE APPROVAL OF THE CONDENSATE TO DRAIN INTO THE | | PLANTER. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
20 |
Status |
P |
Date |
2008-09-26 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-09-26 |
Time |
16:54 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-09-26 |
Time |
16:54 |
Sent To |
|
|
Notes |
2008-09-26 16:56:48 | REVISIONS OK -- SHTS P1-1.0U, P1-1.0 & P1-5.1 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
19 |
Status |
F |
Date |
2008-08-29 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-08-29 |
Time |
11:09 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-08-28 |
Time |
14:12 |
Sent To |
|
|
Notes |
2008-08-29 13:57:45 | REVISIONS DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | NFPA-101 | | | | 1. SHTS P1-1.0 & P1-1.0U. REVISION 12A NOT FOUND, NOT | | CLOUDED. REVISION NUMBER SHALL BE LEGIBLE ON FLOOR | | PLAN. ALL REVISIONS SHALL BE CLOUDED. SEE COMMENT 3 | | FROM PREVIOUS REVIEW. SECTION 106.1.3. | | | | 2. SHTS P1-1.0U, P1-1.0 & P1-1.2. SUBMIT A DETAIL FOR | | THE PLANTER ON THE WEST SIDE OF THE COURTYARD. INDICATE | | HOW THE STORM WATER AND THE CONDENSATE WILL NOT DRAIN | | TO THE FOOTER AREA OF THE OUTSIDE WALL TO COMPLY WITH | | SECTION 1503.6. BY HAVING THE PLANTER OPEN AT THE | | BOTTOM, THE INTENT OF THE CODE IS NOT BEING MET. | | | | 3. SHTS P1-4.0, P1-4.2 & P3-7.0. PIPING FROM THE ROOF | | DRAIN, (6" RD 1865SF), NOT APPROVED IN THE EXIT | | STAIRWELL. NFPA 101 SECTION 7.1.3.2.1(6). | | | | 4. SHT P1-5.1. REVISION 193 SUBMITTED AND PLANS SIGNED, | | SEALED & DATED ON 05-09-08 NOT SHOWN ON REVISION | | SUBMITTED ON 08-21-08. ALSO CHANGES TO LATEST REVISION | | ARE NOT CLOUDED NOR NUMBERED WITH A REVISION NUMBER. | | (HUB DRAINS DELETED). SECTION 106.1.3. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
18 |
Status |
P |
Date |
2008-08-29 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-08-29 |
Time |
11:08 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-08-28 |
Time |
14:12 |
Sent To |
|
|
Notes |
2008-08-29 11:09:04 | REVISIONS OK -- SHTS P1-1.1, P1-1.1U, P1-1.2U, P1-4.1, | | P1-5.0 & P1-6.0. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
17 |
Status |
F |
Date |
2008-07-18 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-07-18 |
Time |
08:10 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-07-18 |
Time |
08:10 |
Sent To |
|
|
Notes |
2008-07-18 08:54:08 | REVISIONS DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | | | 1. SHT P1-1.0 REVISION 193R SHOWS A 2" CONDENSATE FROM | | AHU-1 CONNECTING TO A 1" CONDENSATE LINE THAT SNAKES | | OVER TO A PLANTER & DISCHARGES MINIMUM 12" AWAY FROM | | THE BUILDING WALL. FITTINGS SHOULD BE USED WHEN | | CHANGING DIRECTION ON DRAINAGE PIPE. SECTION 706.1.-- | | THE SIZE OF THE DRAINAGE PIPING SHALL NOT BE REDUCED IN | | SIZE IN THE DIRECTION OF FLOW. SECTION 704.2.--MORE | | INFORMATION IS REQUIRED. IF THE CONDENSATE WILL BE | | DRAINING 24 HOURS, 365 DAYS A YEAR, WHERE WILL THE | | CONDENSATE WATER DRAINING INTO THE PLANTER GO? IS THE | | PLANTER SEALED OFF FROM THE BUILDING WALL WITH A | | FLASHING OR SOME OTHER FORM OF WATER PROOFING?--IF | | THE EXCESS WATER REMAINS IN THE PLANTER, WILL THIS | | CAUSE ROOT ROT ON THE REQUIRED PLANTS?--ALSO ALL | | CHANGES TO THE CONDENSATE SYSTEM SHALL BE REFLECTED ON | | THE CONDENSATE RISER DIAGRAM. SECTIONS 106.1.1, 106.1.2 | | & 1503.6. | | | | 2. SHT P1-1.0 REVISIONS 193 & 193RSHOWS THE | | CONDENSATE LINE SNAKING TO 1" DC DOWN.FITTINGS SHOULD | | BE USED WHEN CHANGING DIRECTION ON DRAINAGE PIPE. | | SECTION 706.1. | | | | 3. SHT P1-1.01 PLANS STAMPED AND ISSUED 2-21-05 SHOW | | REVISIONS 1, 2, 4 & 5 IN THE REVISION INDEX. THE NEW | | REVISED SHEET SUBMITTED DOES NOT INDICATE REVISION 1 | | AND SHOWS REVISIONS 12A & 193R. REVISION 12A IS NOT | | CLOUDED AND THE NUMBER IS NOT LEGIBLE IN THE TRIANGLE | | WHICH MAY OR MAY NOT BE REVISION 12A. PLEASE CLOUD ALL | | REVISIONS TO BE SUBMITTED AND MAKE SURE THE REVISION | | NUMBERS IN THE TRIANGLES ARE LEGIBLE. ALSO MAKE SURE | | THE REVISION INDEX SHOWS ALL REVISIONS RELATED TO THE | | SHEET. SECTIONS 106.1.1, 106.1.2 & 106.1.3. | | | | 4. SHT P1-1.1 REVISIONS 193 & 193R FITTINGS SHOULD BE | | USED WHEN CHANGING DIRECTION ON DRAINAGE PIPE. SECTION | | 706.1. | | | | 5. SHT P1-1.1U REVISIONS 1 & 2 ARE NOT SHOWN ON THE | | REVISION INDEX AND REVISION 193R SHOWN ON THE FLOOR | | PLAN IS NOT SHOWN ON THE REVISION INDEX. PLEASE | | CORRELATE ALL REVISIONS AND THE REVISION INDEX. ALSO | | ALL REVISIONS ON PREVIOUSLY REVIEWED SHEETS SHALL | | REMAIN ON THE REVISION INDEX THRU THE LIFE OF THE PLANS | | TO TRACK ALL REVISIONS AND FOR PUBLIC RECORD. SECTION | | 1106.1.3. | | | | 6. SHT P1-1.2U REVISION 1 MISSING FROM THE REVISION | | INDEX. ALL REVISIONS ON PREVIOUSLY REVIEWED SHEETS | | SHALL REMAIN ON THE REVISION INDEX THRU THE LIFE OF THE | | PLANS TO TRACK ALL REVISIONS AND FOR PUBLIC RECORD. | | SECTION 1106.1.3. | | | | 7. SHT P1-1.2 REVISIONS 11, 12 & 193 SHOWN IN THE | | REVISION INDEX ARE NOT SHOWN ON THE FLOOR PLAN. PLEASE | | CORRELATE. ALSO CLOUD AND NUMBER ALL REVISIONS | | SUBMITTED AFTER THE PREVIOUSLY REVIEWED SHEET. | | | | 8. SHT P1-3.1 NO REVISION SHOWN. NO CHANGE FROM | | PREVIOUSLY REVIEWED SHEET. SECTION 106.1.3. | | | | 9. SHT P1-4.0 REVISIONS NOT CLOUDED AT THE NEW ROOF | | DRAIN LOCATIONS.--ALSO THE RWL SIZE IS NOT LEGIBLE | | AT COLUUM LINES 8/L & 8/H. PLEASE CLARIFY. SECTION | | 106.1.1 & TABLE 1106.3. | | | | 10. SHT P1-4.1 REVISION 190 NOT FOUND ON THE FLOOR PLAN | | & REVISIONS 1 & 2 HAVE BEEN DELETED FROM THE REVISION | | INDEX. PLEASE CORRELATE AND ALL REVISIONS ON PREVIOUSLY | | REVIEWED SHEETS SHALL REMAIN ON THE REVISION INDEX THRU | | THE LIFE OF THE PLANS TO TRACK ALL REVISIONS AND FOR | | PUBLIC RECORD. SECTION 1106.1.3. | | | | 11. SHT P1-4.2 REVISIONS NOT CLOUDED IN MANY AREAS. BE | | SURE TO CLOUD ALL REVISIONS SUBMITTED AFTER THE LAST | | REVIEWED/STAMPED SET OF REVISIONS. SECTION 106.1.3. | | | | 12. SHT P1-5.0 NO REVISION NUMBER INDICATED FOR CLOUDED | | REVISIONS BETWEEN COLUUM LINES 1/H-L & 10/H-L. PLEASE | | NUMBER ALL REVISIONS. ALSO NO CHANGE NOTED FOR CLOUDED | | REVISION AT COLUUM LINES 6/C-D1 & B/6-8. PLEASE | | CORRELATE. SECTION 106.1.3.--PIPING FOR THE | | CONDENSATE SNAKING FROM RISER TO UNIT.FITTINGS SHOULD | | BE USED WHEN CHANGING DIRECTION ON DRAINAGE PIPE. | | SECTION 706.1. | | | | 13. SHTP3-7.0 REVISIONS SHOWN ON RWL'S 5, 6 & 7 WITH | | CLOUDS OR REVISIONS NUMBERS. PLEASE SHOW CLOUDS AND | | REVISION NUMBERS FOR EACH REVISIONS. SECTION 106.1.3. | | --REVISION NUMBER 11 DOES NOT INDICATE WHAT IS | | REVISED. PLEASE CLARIFY. SECTION 106.1.1.--THE | | ADDITION OF RWL'S 11& 14 ADD UP TO 10,420SF. 10" PIPE | | IS REQUIRED PER TABLE 1106.3. 8" IS SHOWN. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | | | | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
16 |
Status |
P |
Date |
2008-07-18 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-07-18 |
Time |
08:07 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-07-17 |
Time |
15:57 |
Sent To |
|
|
Notes |
2008-07-18 08:10:32 | REVISIONS OK -- SHTS P1-2.0, P1-2.1, P1-2.2. P1-3.0, | | P1-3.2 P1-6.0 (REVISIONS 11 & 12 NOT FOUND OR | | APPROVED), P3-1.0 (REVISION 193 NOT FOUND OR APPROVED). |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
15 |
Status |
F |
Date |
2008-05-29 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-05-29 |
Time |
14:46 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-05-29 |
Time |
14:46 |
Sent To |
|
|
Notes |
2008-05-29 15:05:51 | REVISION DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | | | 1. SHTS P1-1.0 & P1-1.1 REVISION 193. SHOW THE 2" | | CONDENSATE RISER INDICATED ON THE REVISION. PLANS SHOW | | CONDENSATE CONNECTION TO THE 4" SANITARY LINE. PLEASE | | CLARIFY. SECTION 106.1.1. | | | | 2. SHTS P1-3.0 & P1-3.1 CONDENSATE SHALL NOT CONNECT TO | | THE RAIN WATER LEADER OTHER THAN AT THE ROOF DRAINS. | | THE CONDENSATE SHALL DRAIN SEPARATELY FROM THE BUILDING | | BY A DEDICATED CONDENSATE RISER AND CONNECT TO A | | DRYWELL, A CATCH BASIN, A STORM LINE OR INTO A PLANTED | | AREA. IF CONNECTING TO THE STORM DRAIN OUTSIDE THE | | BUILDING, A RELIEF VENT OR GOOSENECK IS REQUIRED AS THE | | CONDENSATE EXITS THE BUILDING. SECTION 314.2.1. | | | | 3. SHT P1-4.0 RISER RWL/12 TOTAL SQUARE FOOTAGE DOES | | NOT REFLECT THE TOTAL OF BOTH ROOF DRAINS. TABLE | | 1106.3.--SHOW THE LOCATION OF RWL/9. PIPING APPEARS | | TO BE CONNECTING TO THE SANITARY RISER P/2. PLEASE | | CLARIFY. SECTION 106.1.1. | | | | 4. SHT P1-4.2 RISER RWL/12 TOTAL SQUARE FOOTAGE DOES | | NOT REFLECT THE TOTAL OF BOTH ROOF DRAINS. TABLE | | 1106.3.--SHOW THE LOCATION OF RWL/9. PIPING APPEARS | | TO BE CONNECTING TO THE SANITARY RISER P/2. PLEASE | | CLARIFY.--ALSO REVISION NUMBER 5 IS NOT INDICATED | | ON THE REVISION INDEX. PLEASE SHOW ALL REVISIONS ON THE | | INDEX. SECTIONS 106.1.2 & 106.1.3. | | | | 5. SHT P1-5.0 CHANGES TO THE ROOF DRAINS & OVERFLOW | | DRAIN ARE NOT INDICATED AS CHANGES. PLEASE CLOUD AND | | NUMBER ALL REVISIONS SUBMITTED. SECTION 106.1.3. | | | | 6. SHT P3-1.0 RISER DIAGRAM DOES NOT REFLECT THE FLOOR | | PLAN FOR THE NEW SINK AT THE CONNECTION AND ROUTING OF | | THE PIPING. PLEASE CORRELATE. SECTION 106.1.1. | | | | 7. SHT P3-7.0 RISER DOES NOT REFLECT THE FLOOR PLAN AT | | RWL'S 11 THRU 14. ALSO RECHECK THE SQUARE FOOTAGE AT | | EACH ROOF DRAIN AND THE TOTAL SQUARE FOOTAGE FOR EACH | | RWL. THIS INFORMATION SHALL REFLECT THE FLOOR PLAN. | | SECTION 106.1.1 & TABLE 1106.3.--ALSO CONDENSATE | | SHALL NOT CONNECT TO THE RAIN WATER LEADER OTHER THAN | | AT THE ROOF DRAINS. THE CONDENSATE SHALL DRAIN | | SEPARATELY FROM THE BUILDING BY A DEDICATED CONDENSATE | | RISER AND CONNECT TO A DRYWELL, A CATCH BASIN, A STORM | | LINE OR INTO A PLANTED AREA. IF CONNECTING TO THE STORM | | DRAIN OUTSIDE THE BUILDING, A RELIEF VENT OR GOOSENECK | | IS REQUIRED AS THE CONDENSATE EXITS THE BUILDING. | | SECTION 313.2.1. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
14 |
Status |
P |
Date |
2008-05-29 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-05-29 |
Time |
14:38 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-05-29 |
Time |
14:38 |
Sent To |
|
|
Notes |
2008-05-29 14:46:08 | | | REVISIONS APPROVED | | | | | | | | SHTS P1-2.0 & P1-2.1 REVISIONS ARE REQUIRED FOR THE | | SANITARY AND WATER RISERS THAT REFLECT THE CHANGES TO | | THE SINK AT COL. LINE 5.2 BETWEEN COL'S B & C. | | | | | | | | | | SHT P1-2.2A REVISION IS REQUIRED FOR SHT P2-1.0 TO | | REFLECT CHANGES TO THE SANITARY AND WATER PIPING THAT | | SHOW THE CONNECTIONS FOR THE SINK. | | | | | | | | | | SHT P1-3.2A REVISION IS REQUIRED FOR SHT P2.3.0 TO | | REFLECT CHANGES TO THE SANITARY AND WATER PIPING THAT | | SHOW THE CONNECTIONS FOR THE SINK. | | | | | | | | | | SHT P1-5.1OK | | SHT P3-5.0OK | | | | | | | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
13 |
Status |
P |
Date |
2007-12-20 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-12-20 |
Time |
18:16 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-12-20 |
Time |
18:16 |
Sent To |
|
|
Notes |
2007-12-20 18:18:33 | REVISION OK SHT P3-2.0 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
12 |
Status |
P |
Date |
2007-11-03 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-11-03 |
Time |
14:39 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-11-03 |
Time |
14:39 |
Sent To |
|
|
Notes |
2007-11-03 14:40:58 | REVISIONS OK--SHTS P1-1.3U, P1-1.0, P1-2.0, P1-2.1, | | P1-5.0 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
11 |
Status |
F |
Date |
2007-11-03 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-11-03 |
Time |
14:25 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-11-03 |
Time |
14:25 |
Sent To |
|
|
Notes |
2007-11-03 14:29:12 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | | | 1. SHT P3-2.0SANT. RISER P-7 TOILET ROOM A2.705 THE | | PIPING, TRAP AND FLOOR DRAIN ARE INDICATED ABOVE THE | | FLOOR. PLEASE CLARIFY. SECTIONS 106.1.1 & 106.1.2. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
10 |
Status |
F |
Date |
2007-09-19 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-09-19 |
Time |
10:40 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-09-17 |
Time |
10:40 |
Sent To |
|
|
Notes |
2007-09-19 11:17:05 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | | | 1. SHT P1-1.3U MANY REVISIONS #11 SHOWN. THE PREVIOUS | | REVISION NUMBER REVIEWED WAS REVISION #4. NO REVISIONS | | SUBMITTED OR APPROVED AFTER THAT. CLOUD AND NUMBER ALL | | REVISIONS AFTER REVISION #4. REVISIONS #10 & #11 ARE | | NOT INDICATED ON THE REVISION INDEX, BUT ARE INDICATED | | ON THE PLANS. THESE REVISIONS ARE NOT CLOUDED.FOR | | EXAMPLE SEE CHANGES IN THE TOILET ROOM B1.108 NOT | | INDICATED AS A REVISION AS WELL AS CHANGES IN THE | | SANITARY AND CHANGES IN THE STORM AND CHANGES IN THE | | LOCATION OF THE FLOOR DRAINS IN THE PUMP ROOMS. THE | | COLUMN LINES HAVE BEEN CHANGED ALSO, (DELETED SOME). | | THESE HAVE NOT BEEN INDICATED AS REVISIONS.--ALL | | CHANGES IN THE SYSTEMS SHALL BE REFLECTED ON THE RISER | | DIAGRAMS TO REFLECT THESE CHANGES. SECTION 106.1.1. | | | | 2. SHT P1-5.0 MANY CHANGES ARE NOT INDICATED BY CLOUDS | | OR REVISION NUMBERS. THE LAST REVISION #5, SIGNED, | | SEALED & DATED 2-5-7. ALL CHANGES FROM THE STAMPED | | PLANS SHALL BE CLOUDED AND INDICATED WITH A REVISION | | NUMBER. (PLEASE TURN OFF ALL PREVIOUS CLOUDS AND | | REVISION NUMBERS FROM SHEETS THAT HAVE BEEN APPROVED | | PRIOR TO SUBMITTING NEW REVISIONS. -- LEAVING ON | | PREAPPROVED REVISION CLOUDS AND REVISION NUMBERS ADDS | | TIME TO EACH REVIEW). | | | | 3. SHT P1-5.1 REVISION #12 HAS NOT BEEN FOUND. PLEASE | | INDICATE WITH A CLOUD AND A REVISION NUMBER AND PLEASE | | TURN OFF THE CLOUDS AND REVISION NUMBERS FROM | | PREVIOUSLY APPROVED REVISIONS. | | | | 4. SHT P3-7.0 ISOMETRIC RISER DIAGRAM FOR RWL-7 DOES | | NOT REFLECT THE FLOOR PLAN. CLEANOUT NOT SHOWN ON THE | | FLOOR PLAN. CLEANOUTS TO BE INSTALLED PER SECTION | | 1101.8. SECTION 106.1.1. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
9 |
Status |
P |
Date |
2007-09-19 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-09-19 |
Time |
10:36 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-09-17 |
Time |
19:30 |
Sent To |
|
|
Notes |
2007-09-19 10:40:38 | REVISIONS OK - SHTS P1-2.3, P1-3.3, P1-4.3, P1-6.0, & | | P3-4.0. REVISION 12. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
8 |
Status |
P |
Date |
2007-09-10 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-09-10 |
Time |
17:21 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-09-10 |
Time |
17:21 |
Sent To |
|
|
Notes |
2007-09-10 17:25:03 | REVISIONS OK--SHTS P1-1.1, P1-3.0, P1-3.1, P1-4.0, | | P1-4.1, P2-1.0U, P2-1.0, P2-3.0 & P3-5.0. APPROVAL ONLY | | FOR REVISION #11 CLOUDED AND NUMBERED ON EACH SHEET. | | ANY OTHER REVISION NOT INDICATED WITH CLOUDS AND | | NUMBERS NOT APPROVED. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
7 |
Status |
F |
Date |
2007-09-10 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-09-10 |
Time |
16:55 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-09-10 |
Time |
16:55 |
Sent To |
|
|
Notes |
2007-09-10 17:14:48 | REVISIONS DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | | | 1. SHT P1-1.0 CLOUD AND NUMBER ALL REVISIONS. REVISIONS | | SEEN WITH NO CLOUDS OR REVISION NUMBERS. SECTION | | 106.1.3. | | | | 2. SHTS P1-2.0 & P1-2.1 ROOM A2.316 SINK SHALL BE | | ACCESSIBLE. PLEASE SHOW CLEAR FLOOR SPACE AND TURNING | | AREA REQUIRED BY SECTIONS 11-4.24.5 & 11-4.2.3.-- | | CLOUD AND NUMBER ALL REVISIONS. SECTION 106.1.3. | | | | 3. SHT P3-20 RISERS DO NOT REFLECT THE FLOOR PLAN.-- | | RISER P/2, SEE PROVISO FOR CLEANOUT DOWNSTREAM OF | | JANITOR SINK 3RD FLOOR. SEE PREVIOUS APPROVED SHEETS | | WITH COMMENT ABOUT REVISIONS.--SINK S-1 BY THE BASE | | OF RISER P/4, (RM A1.709), DOES NOT REFLECT REVISION | | #11 CHANGE.--SINK S-1 BY THE TOILET ROOM A2.705 | | CONNECTS TO BOTH RISERS P/7 & P/4. PLEASE CLARIFY.-- | | SINK SK-1 DOWNSTREAM OF TOILET ROOM A2.107 DOES NOT | | REFLECT THE FLOOR PLAN. PLEASE CORRELATE THE RISER WITH | | THE FLOOR PLANS. SECTION 106.1.1. | | | | 4. SHT P3-3.0 RISER DOES NOT REFLECT THE FLOOR PLAN FOR | | THE OFFSET OF THE SINK IN THE JANITOR ROOM, NOR FOR THE | | CLEANOUT PRIOR TO THE SINK UPSTREAM OF THE EWC-1 BY THE | | JANITOR ROOM A4.105. PLEASE CORRELATE RISER AND FLOOR | | PLAN. SECTION 106.1.1. | | | | 5. SHT P3-6.0 THE WATER LINES FOR THE SINK BY THE | | ELECTRIC W/H IN THE JANITOR ROOM A4.105 DO NOT REFLECT | | THE SINK LOCATION ON THE FLOOR PLAN. THE RISER SHOWS | | THEM TURNING INTO THE JANITOR ROOM, BUT THE FLOOR PLAN | | SHOWS THE SINK IN THE HALLWAY OUTSIDE THE JANITOR ROOM. | | THE WATER RISER FOR THE TOILET ROOM A2.105 DOES NOT | | REFLECT THE PIPING SHOWN ON SHT P2.30 FOR THE SINK IN | | ROOM A2.730. PLEASE CORRELATE RISER AND FLOOR PLANS. | | SECTION 106.1.1. | | | | EVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
6 |
Status |
F |
Date |
2007-06-15 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-06-15 |
Time |
09:14 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-06-15 |
Time |
09:14 |
Sent To |
|
|
Notes |
2007-06-15 10:31:31 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | | | 1. SHT P1.1.3U THE STORAGE ROOM B1.101 SHOWS SANITARY | | PIPING. PLEASE INDICATE THE TYPE OF FIXTURE AND THE | | TYPE OF DRAINAGE FITTING FOR THE FIXTURE.A REVISION | | IS REQUIRED FOR THE SANITARY RISER DIAGRAM TO REFLECT | | THE CHANGES TO THE SANITARY SYSTEM. SECTION 106.1.1. | | | | 2. SHT P1-6.0 THE TRENCH DRAIN AT THE BOTTOM OF THE | | LOWER RAMP HAS BEEN DELETED, BUT IS STILL SHOWN ON THE | | STORM RISER DIAGRAM ON SHT P3.7.0. PLEASE CORRELATE | | RISER AND FLOOR PLAN LAYOUT. | | | | 2. SHT P1-6.0SHOWS 6" AREA DRAINS, BUT THE RISER | | DIAGRAM ON SHT P3-7.0 SHOWS 8" AREA DRAINS. PLEASE | | CORRELATE RISER AND FLOOR PLAN. | | | | 3. SHT P1-6.0 AREA DRAINS HAVE BEEN DELETED ON THE FLAT | | LEVELS OF THE ROOF AND LOWER ROOF SECTION. PLEASE | | INDICATE IF THE SLAB WILL BE SLOPED TO THE AREA DRAINS | | NOW SHOW AT THE BOTTOM OF THE RAMPS. | | | | 4. SHT P1-6.0 THE AREA DRAIN IS SHOWN AT THE BOTTOM OF | | THE SECOND RAMP, (NORTH END), ON THE FLOOR PLAN, BUT | | THE RISER DIAGRAM SHOWS THE AREA DRAIN ON THE ROOF | | ABOVE THE RAMP. PLEASE CLARIFY & CORRELATE RISER AND | | FLOOR PLAN. SECTION 106.1.1. | | | | 5. REVISIONS ARE REQUIRED FOR SHTS P1-2.3, P1.3.3, | | P1-4.3, & P1-6.0SHOWING THE NEW AREA DRAINS AND | | SHOWING THE CHANGED LOCATION OF THE RWL RISER #6. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
5 |
Status |
P |
Date |
2007-04-09 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-04-09 |
Time |
12:19 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-04-09 |
Time |
12:19 |
Sent To |
|
|
Notes |
2007-04-09 12:51:01 | REVISIONS OK - SHTS LSO.0, A9-0.2, P-6.0, P3-2.0, | | P2-3.0, P3-1.0, P3-4.0, LS-0.0, IR-1, A9-0.2.- | | REVISION 8 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2007-02-20 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-02-20 |
Time |
11:22 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-02-17 |
Time |
17:15 |
Sent To |
|
|
Notes |
2007-02-20 12:09:22 | PASSED/PROVISO | | | | SHT P3.2.0 RISER P/2 SHOWS 3 DRINKING FOUNTAINS AT | | TOILET ROOMS C3.107 & C3.108. THE FLOOR PLAN ONLY SHOWS | | 2. REVISION REQUIRED TO CORRELATE RISER WITH FLOOR | | PLAN. | | | | SHT P1.60 REVISION REQUIRED. VENT NOT ALLOWED IN THE | | STAIRWELL, AND DOES NOT REFLECT THE RISER DIAGRAM. | | | | SHT P1.60 REVISION REQUIRED. SHOW THE TRENCH DRAINS AT | | THE BOTTOM OF THE RAMPS. | | | | SHT LSO.0 PLUMBING FIXTURE COUNT TO BE CORRECTED FOR | | DRINKING FOUNTAINS. 2 REQUIRED, READS 1 REQUIRED, | | REVISION REQUIRED. | | | | SHT LSO.0 PLUMBING FIXTURE COUNT TO BE CORRECTED FOR | | DRINKING FOUNTAINS. 4 REQUIRED, READS 2 REQUIRED. | | REVISION REQUIRED. | | | | SHT A9-0.2 TOILET ROOMS C1.05 & C1.106 FINISH OF EPOXY | | PAINT NOT APPROVED. SECTION 1210.2. REVISION REQUIRED. | | | | PLEASE SUBMIT ALL REVISIONS REQUESTED WITHIN 60 DAYS | | AFTER ISSUANCE OF PERMIT. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2007-01-30 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-01-30 |
Time |
17:53 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-01-30 |
Time |
17:53 |
Sent To |
|
|
Notes |
2007-01-30 17:59:39 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 BUILDING | | FBC-2004 FUEL GAS | | FBC-2001 CHAPTER 1 | | FBC-2001 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | FROM PREVIOUS REVIEW: | | FROM PREVIOUS REVIEW: | | | | 1. OK | | 2. OK | | | | 3. SHT P1-1.1 PUMP ROOM A1-112. RPZV BACKFLOW SHALL BE | | INSTALLED A MAXIMUM OF 4' ABOVE THE FLOOR FOR | | CERTIFICATION AND SERVICE. | | ****RESPONSE NOTED, HEIGHT TO BE INDICATED FOR THE | | BACKFLOWS TO BE A MAXIMUM OF 4' ABOVE THE FLOOR. | | ****RESPONSE NOTED, BUT PLANS INDICATE MINIMUM 4' ABOVE | | THE FLOOR. THE REQUIREMENT IS FOR MAXIMUM 4' ABOVE THE | | FLOOR. | | ******RESPONSE NOTED, BUT THE MINIMUM IS STILL | | INDICATED. | | | | 4. OK | | 5. OK | | 6.OK | | 7.OK | | 8.OK | | 9.OK | | 10. OK | | 11. OK | | 12. OK | | 13. OK | | 14. OK | | 15. OK | | 16. OK (SHOWN ON SHT P2-1.0U) | | 17. OK | | 18. OK | | 19. OK | | 20. OK | | 21. OK | | 22. OK | | 23. OK | | 24. OK | | 25. OK | | 26. OK | | 27. OK | | 28. OK | | 29. OK | | 30. OK | | 31. OK | | 32. OK | | 33. OK | | 34. OK | | 35. OK | | | | 36. SUBMIT A SANITARY HORIZONTAL RISER ISOMETRIC AND | | VERTICAL RISER DIAGRAMS. SHOW ALL PIPE SIZES, TRAPS, | | VENTS, CLEANOUTS, OFFSETS, RISER NUMBERS AND DFU'S AS | | THEY ACCUMULATE IN THE SYSTEM. SECTION 106.3.5.1.3. | | ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN, | | ALL REQUIRED CLEANOUTS ARE NOT SHOWN, AND DFU'S ARE NOT | | SHOWN AS THEY ACCUMULATE IN THE SYSTEM. ALSO INDICATE | | ON THE FIRST FLOOR WHERE ALL RISERS BEGIN IN THE | | SYSTEM. | | ****RESPONSE NOTED, BUT SHT P3-1.0 RISER 1, LAVS DO NOT | | REFLECT THE FLOOR PLAN 2ND FLOOR C2-1.03. - DOES NOT | | REFLECT THE FLOOR PLAN C4.103/C4.104 DRINKING FOUNTAINS | | SHOW 3, FLOOR PLAN SHOWS 2. - CLEANOUT NOT SHOWN AT THE | | BASE OF P/1. - NOT ALL PIPE SIZES SHOWN.-SHT P3-2.0 | | RISER P/2 CLEANOUT DOWNSTREAM OF JANITOR SINK IN ROOM | | C4.101 NOT INSTALLED PER SECTION 706.3. SECOND CLEANOUT | | AT THE BASE OF P/2 NOT REQUIRED AS IT DOES NOT CLEANOUT | | THE BASE OF THE STACK, NOR DOES IT REFLECT THE FLOOR | | PLAN. - FLOOR DRAIN PIPING IN ROOM D1.101 AS INDICATED | | IS BEING INSTALLED ABOVE THE FLOOR. - EACH DRINKING | | FOUNTAIN SHALL HAVE ITS OWN TRAP. SAFE WASTE FOR THE | | FIXTURES IS NOT APPROVED.(SEE ROOMS D1.101, D1.108, | | AND A3.111). -CLEANOUTS ARE REQUIRED AT THE BASE OF | | STACKS P/4 & P/10. - CLEANOUT FOR P/7 NOT INSTALLED AT | | THE BASE OF P/7. -THE NEW SANT. PIPING TO TOILET ROOM | | D2.105 NOT SHOWN ON THE FLOOR PLAN. -SHOW ALL TOILET | | ROOM NUMBERS ON THE RISER DIAGRAM. - SHOW ALL PIPE | | SIZES. THE PIPE SIZES ARE NOT SHOWN ON MANY PIPES.- | | SHT P3-3.0A TWO WAY CLEANOUT IS REQUIRED NEAR THE | | JUNCTION OF THE BUILDING DRAIN AND THE BUILDING SEWER. | | (DETAIL 1).-THE RISER DIAGRAM DOES NOT REFLECT THE | | FLOOR PLAN FOR A1.05 & A1.106. AN EXTRA FLOOR DRAIN IS | | INDICATED THAT IS NOT SHOWN ON THE FLOOR PLAN.- | | A3.102 & A3.103 ONLY SHOWS 2 LAVS ON THE RISER AND THE | | FLOOR PLAN SHOWS 4.-A4.103 & A4.104TWO W/C'S ARE | | MISSING FROM THE RISER THAT ARE SHOWN ON THE FLOOR | | PLAN.-A4.105NO FLOOR DRAIN AND A SECOND SINK ARE | | SHOWN ON THE FLOOR PLAN THAT ARE NOT SHOWN ON THE RISER | | DIAGRAM. (JANITOR ROOM).-A5.105 SHOWS THE BRANCH | | LINE CONNECTING NEAR THE DRINKING FOUNTAINS ON THE | | FLOOR PLAN, BUT CONNECTING DOWNSTREAM OF THE NEXT | | FIXTURES ON THE RISER DIAGRAM.-A CLEANOUT IS | | REQUIRED AT THE BASE OF RISER P/8-ALL RISER | | DIAGRAMS,CHECK ALL PIPE SIZES, MAKE SURE THE RISER | | DIAGRAMS REFLECT THE FLOOR PLAN FOR BOTH THE SANITARY | | AND THE VENTING.SECTIONS106.1.1, 106..1.2, 706.3, | | 708.3.4, 708.3.5, 100.2.1. | | ******RESPONSE NOTED, BUT NOW THE FLOOR PLAN SHOWS 3 | | DRINKING FOUNTAINS & THE SANT. RISER SHOW 2. PLEASE | | CORRELATE.--D1.108 STILL SHOWS A SAFE WASTE AT THE | | CENTER DRINKING FOUNTAIN. | | | | 37. OK | | 38. OK | | 39. OK | | | | 40. ALL PME & FIRE PROTECTION SHEETS. PLANS SHALL BE | | SIGNED, SEALED, AND DATED. SECTION 106.1. ALL TITLE | | BLOCK INFORMATION REQUIRED BY FAC 61G1-23.002 AND FS | | 471.025 SHALL BE SUBMITTED ON EACH SHEET. ****RESPONSE | | NOTED, BUT THE SEAL USED IS NOT APPROVED. NEW SEALS | | SHALL INDICATE THE WORD "LICENSE" IN THE SEAL. (SEE | | ATTACHED SHEET FROM THE FLORIDA BOARD OF PROFESSIONAL | | ENGINEERS). | | ****RESPONSE NOTED, BUT THE SEALS OF SOME MECH. AND | | PLUMBING SHEETS ARE STILL THE OLD SEAL. - ALSO THERE | | SEEMS TO BE TWO SETS OF SIGNATURES FOR THE ENGINEER OF | | RECORD. PLEASE SUBMIT A SIGNED, SEALED, DATED, | | NOTORIZED LETTER INDICATING THE LEGAL SIGNATURE OF THE | | ENGINEER OF RECORD FOR OUR FILES. ONE SET OF PLANS | | SHALL BE RETAINED FOR POSSIBLE REVIEW BY THE FLORIDA | | BOARD OF PROFESSIONAL ENGINEERS. | | ******RESPONSE NOTED, BUT THERE ARE STILL SOME SEALS | | WITH "CERTIFICATE" ON THE MECHANICAL SHEETS. | | | | **************NEW COMMENTS************** | | | | 1B. SHTS P1-1.0U, P1-1.1U, P1-1.1 & P1-2.1. RWL-4 DOES | | NOT REFLECT THE SQUARE FOOTAGE SHOWN ON RISER DIAGRAM | | OR ROOF PLAN. PLEASE CORRELATE RISER, FLOOR PLAN, & | | ROOF PLAN. SECTION 106.1.1. | | ****RESPONSE NOTED. WILL RECHECK AFTER THE CALCULATIONS | | FOR THE ROOF DRAINS HAS BEEN RESUBMITTED WITH | | CORRECTIONS. | | ******RESPONSE NOTED, BUT SOME SHEETS SHOW A DIFFERENT | | SQUARE FOOTAGE THAN SHOWN ON THE ROOF PLAN & RISER. | | PLEASE CORRELATE ALL SHEETS. | | | | 2B. OK | | 3B. OK | | 4B. OK | | 5B. OK | | | | 6B. SHTS P1-1.2U, ASSOCIATED RISER DIAGRAMS, AND | | ENLARGED FLOOR PLANS. INDICATE HOW THE STACKS P/1 & | | P/10 CAN DRAIN INTO THE TOILET GROUP FIXTURE BRANCH. | | SUBMIT A DETAIL SHOWING THE 4" CLEANOUT TEE, THE 4" | | CROSS FOR THE FIXTURE BRANCH, AND THE 4" DOUBLE | | Y/EIGHTH BEND FITTINGS STACKED ON TOP OF EACH OTHER. | | WILL THEY BE AT THE RIGHT HEIGHT FOR THE W/C'S?SEE | | SECTION 908.3 ALSO. SECTION 106.1.1. (STACKS SHOULD | | CONNECT TO THE BUILDING DRAIN AND FIXTURE GROUPS SHOULD | | CONNECT TO THE STACK SO THAT THE STACK DOES NOT RUN | | THRU THE MIDDLE OF THE FIXTURE GROUP). ****RESPONSE | | NOTED, BUT C/O'S ARE REQUIRED AT THE BASE OF EACH | | STACK. COMMENT HAS NOT BEEN ADDRESSED. ******RESPONSE | | NOTED, BUT NOW THE VENTING TO THE W/C'S IS NOT SHOWN ON | | THE 1ST FLOOR STACK P-10. | | | | 7B. SHTS P1-1.3U, P1-2.0, P1-2.3, P1-3.3, & P1-4.3 | | RWL-6 DOES NOT REFLECT THE SQUARE FOOTAGE SHOWN ON THE | | RISER DIAGRAM, NOR ON THE ROOF PLAN. PLEASE CORRELATE | | INFORMATION. SECTION 106.1.1 & TABLE 1106.3. | | ****RESPONSE NOTED, BUT THE COMMENT WAS NOT ADDRESSED | | ON SHTS P1-3.3, & P1-4.3. | | ******RESPONSE NOTED, BUT THE SQUARE FOOTAGE ON SHTS | | P1-2.0 & P1-2.3 IS INDICATED AS 5,584SF. PLEASE | | CORRELATE ALL SHEETS. | | | | 8B. OK | | 9B. OK | | 10B. OK | | 11B. OK | | 12B. OK | | 13B. OK | | 14B. OK | | | | 15B. SHT P1-6.0 SHOW THE LOCATIONS FOR ALL VTR'S. - | | INDICATE THE RWL EACH ROOF DRAIN IS CONNECTED TO. | | SECTION 106.1.1. | | ****RESPONSE NOTED, BUT VTR'S 1, 3, 9 & 10 ARE NOT | | SHOWN. | | ******RESPONSE NOTED, BUT THE VTR FOR THE TOILET ROOM | | IN THE GARAGE IS NOT INDICATED PAST THE 1ST FLOOR. | | PLEASE SHOW THE VENT ON THE 2ND, 3RD, 4TH, 5TH & AT THE | | ROOF LEVEL OF THE GARAGE. | | | | 16B. OK | | 17B. OK | | 18B. OK | | 19B. OK | | 20B. OK | | 21B. OK | | 22B. OK | | 23B. OK | | 24B. OK | | 25B. OK. | | 26B. OK | | 27B. OK | | 28B. OK | | 29B. OK | | 30B. OK | | 31B. OK | | 32B. OK | | 33B. OK | | | | 34B. SHT P3.1.0 SANT RISER DIAGRAM, TRAPS ARE REQUIRED | | ON ALL DRINKING FOUNTAINS. SECTION 1002.1. - 1ST FLOOR | | LAVS PIPING DOES NOT REFLECT THE FLOOR PLAN. - FLOOR | | DRAINS DOWNSTREAM OF RISER P/1 ARE NOT VENTED. SECTION | | 901.2.1. - A C/O IS REQUIRED AT THE BASE OF STACK P/1 | | SECTION 708.3.4 - SHOW THE CONNECTION DETAIL AT THE | | BASE OF STACK P/1 WITH A 4" CLEANOUT, A 4" CROSS, AND | | 4" WYE FITTINGS INDICATING THE HEIGHT OF THE W/C | | STUBOUT. - W/C-1 AT THE BASE OF STACK IS NOT VENTED. | | SECTION 901.2.1. -W/C ON 2ND FLOOR IS NOT VENTED. | | SECTION 901.2.1. - LAV ON 3RD FLOOR NOT VENTED. SECTION | | 901.2.1. - INDICATE HOW/WHERE PIPING FOR LAVS & FLOOR | | DRAINS CONNECT TO THE RISER/BRANCH ON THE 2ND, 3RD, & | | 4TH FLOORS. THE FITTINGS INDICATE THAT THE PIPING IS | | SLOPED TO THE LAVS. PLEASE CLARIFY. - MEN C4.104 DOES | | NOT REFLECT ROOM NUMBER ON THE FLOOR PLAN. - PIPING FOR | | FLOOR DRAINS & LAVS 4TH FLOOR DOES NOT REFLECT THE | | FLOOR PLAN. SECTION 106.1.1. | | ****RESPONSE NOTED, BUT 1ST FLOOR LAVS PIPING DOES NOT | | REFLECT THE FLOOR PLAN. -A C/O IS REQUIRED AT THE | | BASE OF STACK P/1 SECTION 708.3.4 - SHOW THE CONNECTION | | DETAIL AT THE BASE OF STACK P/1 WITH A 4" CLEANOUT, A | | 4" CROSS, AND 4" WYE FITTINGS INDICATING THE HEIGHT OF | | THE W/C HOW THE CONNECTION DETAIL AT THE BASE OF STACK | | P/1 WITH A 4" CLEANOUT, A 4" CROSS, AND 4" WYE FITTINGS | | INDICATING THE HEIGHT OF THE W/C STUBOUT. - MEN C4.104 | | DOES NOT REFLECT ROOM NUMBER ON THE FLOOR PLAN. - | | PIPING FOR FLOOR DRAINS & LAVS 4TH FLOOR DOES NOT | | REFLECT THE FLOOR PLAN. SECTION 106.1.1. THESE ITEMS | | HAVE NOT BEEN ADDRESSED. | | ******RESPONSE NOTED, BUT MEN'S C4.104 STILL DOES NOT | | REFLECT THE ROOM NUMBER ON THE FLOOR PLAN.--NOW NO | | SANITARY PIPING OR HOT WATER PIPING IS SHOWN ON THE | | FLOOR PLAN OF THE ENLARGED FLOOR PLAN. PLEASE CLARIFY. | | | | 35B. ALL RISER DIAGRAMS, ALL FLOOR PLANS FOR ALL | | SYSTEMS. INDICATE THE PIPE SIZE. SECTION 106.1.1. | | ****RESPONSE NOTED, BUT MANY PIPE SIZES ARE NOT SHOWN | | ON THE RISER DIAGRAMS. | | ******RESPONSE NOTED, BUT THERE ARE MANY SECTIONS OF | | SANITARY PIPING THAT HAVE NO PIPE SIZES. TABLES | | 710.1(1) & 710.1(2). | | | | 36B. SHT P3-2.0 JANITOR ROOM PIPING DOES NOT REFLECT | | THE FLOOR PLAN. - TRAPS REQUIRED ON ALL DRINKING | | FOUNTAINS. SECTION 1002.1. - CLEANOUTS REQUIRED AT THE | | BASE OF ALL STACKS. 708.3.4. - PIPING TO FLOOR DRAIN | | SHOWN ABOVE THE FLOOR IN ROOM D1.101. PLEASE CLARIFY. - | | PIPING AT THE BASE OF RISER P/2 DOES NOT REFLECT THE | | FLOOR PLAN. - PIPING TO FD-2 AT THE LOADING D1.106 DOES | | NOT REFLECT THE FLOOR PLAN. - PIPING FOR A1.108/A1.109 | | DOES NOT REFLECT THE FLOOR PLAN. - ROOM D2.103 IS | | INDICATED AS D2.104 ON THE FLOOR PLAN. CORRELATE | | INFORMATION. - ALL VENTING AT RISER P/10 STOPS AT LEVEL | | 2. SECTION 903.3 VTR REQUIRED. - TOILET ROOM A2.708 IS | | INDICATED AS A2.706 ON THE FLOOR PLAN. CORRELATE | | INFORMATION. - BATHROOM RISER DOES NOT REFLECT THE | | FLOOR PLAN. (NO FD). - PIPING TO ROOM A4.414 DOES NOT | | REFLECT THE FLOOR PLAN. - CLEANOUT PIPING DOWNSTREAM OF | | C4.101 IS NOT APPROVED AS PIPED. SECTION 706.3. - | | PIPING ON RISER DOES NOT REFLECT THE FLOOR PLAN | | UPSTREAM OF C3.105. - JANITOR SINK C3.105 IS NOT | | VENTED. SECTION 901.2.1. - FLOOR DRAIN CONNECTION AT | | BRANCH LINE 4TH FLOOR DOES NOT REFLECT THE FLOOR PLAN. | | - PIPING AT A2.107 DOES NOT REFLECT THE FLOOR PLAN. (NO | | F.D. PIPING). - PIPING AT ROOM A3.111 DOES NOT REFLECT | | THE FLOOR PLAN AT THE LAVS. - ROOM A3.111 SUBMIT A | | DETAIL FOR FITTING TO W/C & LAVS. - ROOM D2.105 SHOWN | | AS D2.106/D2.107 ON FLOOR PLANS. CORRELATE INFORMATION. | | - ROOM C3.410/C3.412 FLOOR DRAIN FITTING ARE SHOWN TO | | BE INSTALLED AGAINST THE FLOW. SECTION 706.3. - SECTION | | 106.1.1. | | ****RESPONSE NOTED, BUT SOME COMMENTS WERE NOT | | ADDRESSED. SEE THE FOLLOWING: JANITOR ROOM PIPING DOES | | NOT REFLECT THE FLOOR PLAN. - TRAPS REQUIRED ON ALL | | DRINKING FOUNTAINS. SECTION 1002.1. - CLEANOUTS | | REQUIRED AT THE BASE OF ALL STACKS. 708.3.4. - PIPING | | TO FLOOR DRAIN SHOWN ABOVE THE FLOOR IN ROOM D1.101. | | PLEASE CLARIFY.- PIPING AT THE BASE OF RISER P/2 DOES | | NOT REFLECT THE FLOOR PLAN. - PIPING FOR A1.108/A1.109 | | DOES NOT REFLECT THE FLOOR PLAN. - ROOM D2.103 IS | | INDICATED AS D2.104 ON THE FLOOR PLAN. CORRELATE | | INFORMATION.- TOILET ROOM A2.708 IS INDICATED AS | | A2.706 ON THE FLOOR PLAN. CORRELATE INFORMATION. - | | PIPING TO ROOM A4.414 DOES NOT REFLECT THE FLOOR PLAN. | | - CLEANOUT PIPING DOWNSTREAM OF C4.101 IS NOT APPROVED | | AS PIPED. SECTION 706.3. - PIPING AT ROOM A3.111 DOES | | NOT REFLECT THE FLOOR PLAN AT THE LAVS. - ROOM A3.111 | | SUBMIT A DETAIL FOR FITTING TO W/C & LAVS. - ROOM | | D2.105 SHOWN AS D2.106/D2.107 ON FLOOR PLANS. CORRELATE | | INFORMATION. | | ******RESPONSE NOTED, BUT THE JANITOR ROOM PIPING DOES | | NOT REFLECT THE FLOOR PLAN.--TOILET ROOM A2.708 IS | | STILL INDICATED AS A2.706 ON THE FLOOR PLAN. CORRELATE | | ROOM NUMBERS.--PIPING TO ROOM A4.414 DOES NOT | | REFLECT THE FLOOR PLAN. RISER IS SHOWN AS A TRAVELING | | OFFSET. FLOOR PLAN SHOWS THIS AS A STRAIGHT RISER. | | PLEASE CLARIFY. | | | | 37B. SHT P3-3.0 PIPING TO A3.304 & DOWNSTREAM DOES NOT | | REFLECT THE FLOOR PLAN. - VENT PIPING FROM S-1 SINK | | DOES NOT REFLECT THE FLOOR PLAN. OFFSET NOT SHOWN. - | | TRAPS REQUIRED ON ALL DRINKING FOUNTAINS. SECTION | | 1002.1. - S-1 SINK SHALL NOT DRAIN THRU THE WET VENT OF | | THE TOILET ROOM A1.303. SINK SHALL DISCHARGE DOWNSTREAM | | OF THE W/C & LAV. SECTION 909.1. - INDICATE P/8 WITH | | P/6 AT THE BASE OF THE STACK WHERE IT BEGINS. - PIPING | | TO ROOMS A1.105/A1.106 DOES NOT REFLECT THE FLOOR PLAN. | | FLOOR DRAIN PIPING IS SHOWN AS ABOVE THE FLOOR. - P/5 & | | P/9 BEGIN AT THE BASE OF THE STACK. PLEASE INDICATE ON | | RISER DIAGRAM. - PIPING FOR A3.102/A3.103 DOES NOT | | REFLECT THE FLOOR PLAN. - CLEANOUT REQUIRED AT THE BASE | | OF P/9 STACK. - PIPING TO FLOOR DRAINS IN ROOMS | | A3.102/A3.103 ARE ABOVE THE FLOOR. -W/C AT THE BASE | | OF STACK NOT VENTED. SECTION 901.2.1. - INDICATE WHERE | | LINES TO FLOOR DRAINS IN ROOMS A4.103/A4.104 & | | A5.103/A5.104 ARE CONNECTING TO THE BRANCH/STACK. - | | PIPING FOR A4.103/A4.104 DOES NOT REFLECT THE FLOOR | | PLAN. - W/C AT RISER STACK A4.103 IS NOT VENTED. | | SECTION 901.2.1. - PIPING FOR A4.105 DOES NOT REFLECT | | THE FLOOR PLAN. SECTION 106.1.1. | | ****RESPONSE NOTED, BUT THE FOLLOWING COMMENTS WERE NOT | | ADDRESSED:-PIPING TO A3.304 & DOWNSTREAM DOES NOT | | REFLECT THE FLOOR PLAN. - VENT PIPING FROM S-1 SINK | | DOES NOT REFLECT THE FLOOR PLAN. OFFSET NOT SHOWN. - | | PIPING TO ROOMS A1.105/A1.106 DOES NOT REFLECT THE | | FLOOR PLAN. FLOOR DRAIN PIPING IS SHOWN AS ABOVE THE | | FLOOR. -PIPING FOR A4.103/A4.104 DOES NOT REFLECT THE | | FLOOR PLAN. - W/C AT RISER STACK A4.103 IS NOT VENTED. | | SECTION 901.2.1. - PIPING FOR A4.105 DOES NOT REFLECT | | THE FLOOR PLAN. SECTION 106.1.1. | | ******RESPONSE NOTED, BUT THE PIPING TO A3.304 & | | DOWNSTREAM DOES NOT REFLECT THE FLOOR PLAN. CORRELATE | | RISER & FLOOR PLAN.--VENT PIPING FROM S-1 SINK | | STILL DOES NOT REFLECT THE FLOOR PLAN. CORRELATE RISER | | AND FLOOR PLAN. | | | | 38B. OK | | | | 39B. SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING | | INFORMATION IS REQUIRED FOR THE GAS PERMIT: | | | | A. OK | | B. OK | | C. OK | | D. OK | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | ****RESPONSE NOTED, BUT NOT ADDRESSED. ******RESPONSE | | NOTED, BUT THE SIZING OF THE PIPE SHALL BE TO THE MOST | | REMOTE APPLIANCE/GENERATOR. PLEASE INDICATE THE TOTAL | | DEVELOPED LENGTH TO THE MOST REMOTE FUTURE GENERATOR. | | | | F. OK | | | | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | ****RESPONSE NOTED, BUT NO MANUF. SHEETS FOR THE | | GENERATOR HAS BEEN SUBMITTED. - ALSO SUBMIT THE MANUF. | | SPECIFICATION SHEETS FOR THE GAS REGULATORS. INDICATE | | MODEL NUMBER. LISTING INFORMATION REQUIRED. | | ******RESPONSE NOTED, BUT THE BTU LOAD FOR THE NATURAL | | GAS @ 100% LOAD IS NOT INDICATED ON THE MANUF. | | SPECIFICATION SHEETS. THIS SHALL BE SHOWN TO VERIFY | | PIPE SIZING. | | | | H. NA | | I. NA | | | | 40B. SHT P3-5.0 NO HOT WATER LINE SHOWN IN 1ST THRU 4TH | | FLOOR TOILET ROOMS OFF WATER RISER W/1. - WATER RISER | | DOES NOT REFLECT THE FLOOR PLAN AT THE LAVS. - FULL | | OPEN VALVES ARE REQUIRED ON ALL WATER DOWN-FEED LINES. | | SECTION 606.1(4). - RISER DOES NOT REFLECT THE FLOOR | | PLAN AT ROOMS C2.102/C2.103. (2 LAVS SHOWN EACH TOILET | | ROOM). - PIPE SIZE SUPPLYING ROOMS D1.101/D1.102, | | JANITOR ROOM D1.110, TOILET ROOMS A1.108/A1.109. - | | INDICATE THAT RISERS W/4, W/5, & W/8 RISERS START WITH | | RISER W/2 ON THE 1ST FLOOR. SECTION 106.1.1. | | ****RESPONSE NOTED, BUT THE FOLLOWING COMMENTS WERE NOT | | ADDRESSED: - WATER RISER DOES NOT REFLECT THE FLOOR | | PLAN AT THE LAVS. - FULL OPEN VALVES ARE REQUIRED ON | | ALL WATER DOWN-FEED LINES. SECTION 606.1(4). (MANY | | LAVS, TOILET ROOMS, SINKS ETC MISSING VALVES).- RISER | | DOES NOT REFLECT THE FLOOR PLAN AT ROOMS C2.102/C2.103. | | (2 LAVS SHOWN EACH TOILET ROOM). - PIPE SIZE SUPPLYING | | ROOMS D1.101/D1.102, JANITOR ROOM D1.110, TOILET ROOMS | | A1.108/A1.109. (2" SHOWN ON FLOOR PLAN, 1-1/2" ON | | RISER. 3/4" ON FLOOR PLAN, 1/2" ON RISER.SOME LAVS | | SHOW SEPARATE DROPS TO EACH LAV ON THE FLOOR PLAN, BUT | | SINGLE DROPS ON THE RISER). - INDICATE THAT RISERW/8 | | STARTS WITH RISER W/2 ON THE 1ST FLOOR. SECTION | | 106.1.1. | | ******RESPONSE NOTED, BUT THE SIZE OF THE SUPPLY PIPING | | TO THE JANITOR ROOM D1.110 DOES NOT REFLECT THE FLOOR | | PLAN, AS WELL AS THE PIPE SIZE SUPPLYING TOILET ROOMS | | A1.108/A1.109. PLEASE CORRELATE THE RISER AND FLOOR | | PLAN. | | | | 41B. SHT P3-6.0 RISERS 4, 5 & 8 ARE NOT INDICATED ON | | THE 1ST FLOOR. - RISER DOES NOT REFLECT THE FLOOR PLAN | | ROOMS C3.107/C3.108 AT JAN. SINK, ROOMS C3.410/C3.412, | | AE.111, A4.103/A4.104, A4.105 AND THE TOP OF RISER W/4 | | TO ROOM A5.105, PIPE SIZE AT ROOM A2.209 & SUPPLY TO | | TOILET ROOM ADJACENT, PIPE SIZE SUPPLYING RISER W/8 & | | RISER, SUPPLY LINE TO ROOMS D2.102/D2.103. - W/2 NOT | | FOUND ON 4TH FLOOR AS INDICATED ON RISER. SECTION | | 106.1.1. | | ****RESPONSE NOTED, BUT THE FOLLOWING COMMENTS WERE NOT | | ADDRESSSED: RISER 8 STILL NOT INDICATED ON THE 1ST | | FLOOR. - RISER DOES NOT REFLECT THE FLOOR PLAN ROOMS | | C3.410/C3.412,A4.103/A4.104, (FLOOR PLAN INDICATES | | OVER-HEAD SUPPLY WITH DROPS, BUT RISER INDICATES SUPPLY | | RUN IN THE WALL OFF WATER RISER. TWO W/C'S MISSING ON | | RISER).-PIPE SIZE AT ROOM A2.209, (SHOWS 1" ON THE | | FLOOR PLAN), - PIPE SIZE SUPPLYING RISER W/8 & RISER, ( | | 1" ON FLOOR PLAN, 2" ON RISER - 1-1/2" ON THE FLOOR | | PLAN, BUT 2" ON THE RISER). -W/2 NOT FOUND ON 4TH OR | | 5TH FLOORS AS INDICATED ON RISER. SECTION 106.1.1. | | PLEASE CORRELATE RISER AND FLOOR PLANS. ******RESPONSE | | NOTED, BUT THE RISER STILL DOES NOT REFLECT THE FLOOR | | PLAN, NOR DOES IT REFLECT THE PIPE SIZING FOR THE HOT | | SUPPLY TO TOILET ROOMS C3.410/C3.412.--TOILET ROOMS | | A4.103/A4.104 WATER PIPING STILL DOES NOT REFLECT THE | | FLOOR PLAN.--PIPE SIZE SUPPLYING RISER W/8 STILL | | DOES NOT REFLECT THE FLOOR PLAN. CHECK PIPING | | DOWNSTREAM OF RISER W/8 AND CORRELATE PIPING BETWEEN | | THE RISER AND THE FLOOR PLAN. | | | | 42B. SHT P3-7.0 SIZE ALL PIPE PER SECTION 1106.3, AND | | SHOW ALL PIPE SIZES ON THE RISER. - RISER DOES NOT | | REFLECT THE FLOOR PLAN TOP FLOORS RWL/6 & RWL/7. - | | RISERS INDICATE A 5TH FLOOR, BUT FLOOR PLAN DOES NOT | | SHOW A 5TH FLOOR. - RISER SHOWS TRENCH DRAINS ON TWO | | FLOORS, BUT ONLY SHOW TRENCH DRAINS ON 1 FLOOR, (ROOF | | LEVEL), ON THE FLOOR PLAN. -RWL'S 9 THRU 14 SHOW OFFSET | | PIPING FOR ROOF DRAINS IN THE 4TH FLOOR CEILING, BUT | | INDICATE THE ROOF DRAINS TO BE ON THE 4TH LEVEL. PLEASE | | CLARIFY. - PIPE SIZING IS INCORRECT AT 8"/11,715SF, | | 6"/5077SF, 6"/6657SF. TABLE 1106.3. - RWL/9 INDICATES | | PIPING IN 3RD FLOOR CEILING, BUT ROOF DRAINS ARE TO BE | | ON THE 3RD LEVEL. PLEASE CLARIFY. - RWL/15 DOES NOT | | REFLECT THE FLOOR PLAN TO 4" ROOF DRAINS. - PIPING AT | | THE 1ST FLOOR CEILING CONNECTING TO ROOF DRAINS ON THE | | 1ST LEVEL. PLEASE CLARIFY. SECTION 106.1.1. | | ****RESPONSE NOTED, BUT SOME COMMENTS THE FOLLOWING | | COMMENTS WERE NOT ADDRESSED:- RISER DOES NOT REFLECT | | THE FLOOR PLAN TOP FLOORS RWL/6 & RWL/7. - RISERS | | INDICATE A 5TH FLOOR, BUT FLOOR PLAN DOES NOT SHOW A | | 5TH FLOOR. - RISER SHOWS TRENCH DRAINS ON TWO FLOORS, | | BUT ONLY SHOW TRENCH DRAINS ON 1 FLOOR, (ROOF LEVEL), | | ON THE FLOOR PLAN. - PIPE SIZING IS INCORRECT AT | | 8"/11,715SF, 6"/5077SF, 6"/6657SF. TABLE 1106.3. | | ******RESPONSE NOTED, BUT I STILL HAVE QUESTIONS AS TO | | THE TRENCH DRAINS. IT SEEMS ON THE RISER DIAGRAM THAT | | THE UPPER TRENCH DRAINS ARE SHOWN AT THE WRONG | | ELEVATIONS. THERE IS NO LEVEL ABOVE THE 5TH LEVEL FOR | | RWL 7 & THE AREA DRAINS FOR THE ROOF ON RWL 6COLLECT | | THE ROOF AREA. SHOULDN'T THE TRENCH DRAINS BE AT THE | | BOTTOM OF THE RAMPS BELOW THE ROOF AREAS. PLEASE | | CLARIFY. | | | | 43B. SHTS 1,2,3 OF 3 ARE NOT SIGNED, SEALED, & DATED AS | | REQUIRED PER FS 472.025(1). ALSO SEE SHT 1 WHICH STATES | | "NOT VALID UNLESS SEALED WITH SURVEYOR'S EMBOSSED SEAL | | AND SIGNATURE" | | ****NO RESPONSE, NOT ADDRESSED. | | ******RESPONSE NOTED, BUT SHTS 2 & 3 ARE NOT SIGNED, | | SEALED, DATED. IF THE DESIGN PROFESSIONAL IS AN | | ARCHITECT OR ENGINEER LEGALLY RESISTERED UNDER THE LAWS | | OF THIS STATE REGULATING THE PRACTICE OF ARCHITECTURE | | AS PROVIDED FOR IN CHAPTER 481, FLORIDA STATUTES, PART | | I,OR ENGINEERING AS PROVIDED FOR IN CHAPTER 471, | | FLORIDA STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER | | OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, | | SPECIFICATIONS AND ACCOMPANYING DATA AS REQUIRED BY | | FLORIDA STATUTES. SECTION 106.1. | | | | 44B. SHTS C1, C5 THRU C22 ENGINEERING CERTIFICATE OF | | AUTHORIZTION IS REQUIRED IN THE TITLE BLOCK. | | 61G15-23.002(2) & FS 471.025. - AN EMBOSSED SEAL IS | | REQUIRED TO IMPRESS REQUIRED INFORMATION ON EACH SHEET. | | UNABLE TO GLEAN ALL INFORMATION REQUIRED FROM SEAL. | | PLEASE RESEAL PLANS. | | ****NO RESPONSE, NOT ADDRESSED. | | ******NO RESPONSE, NOT ADDRESSED. | | | | 45B. OK | | 46B. OK | | 47B. OK | | 48B. OK | | | | 49B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 3RD | | FLOOR DRINKING FOUNTAINS SHOW ONLY 3 ARE REQUIRED. PER | | TABLE 403.1, 4 DRINKING FOUNTAINS ARE REQUIRED. PLEASE | | UPDATE FIXTURE COUNT. | | ****NO RESPONSE, NOT ADDRESSED. | | *****RESPONSE NOTED, NO CHANGE NOTED, NOT ADDRESSED | | | | 50B. OK | | | | 51B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 1ST | | FLOOR DRINKING FOUNTAINS 2 REQUIRED PER TABLE 403.1, | | BUT READS 1 REQUIRED. PLEASE CORRECT FIXTURE COUNT | | REQUIRED. | | ****NO RESPONSE, NOT ADDRESSED. | | ******RESPONSE NOTED, NO CHANGE, NOT ADDRESSED. | | | | 52B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 3RD | | FLOOR DRINKING FOUNTAINS 4 REQUIRED PER TABLE 403.1, | | BUT READS 2 REQUIRED. PLEASE CORRECT FIXTURE COUNT | | REQUIRED. - SHOWS 2 PROVIDED, BUT 4 ARE REQUIRED. | | PLEASE CORRECT INFORMATION. | | ****NO RESPONSE, NOT ADDRESSED. | | ******RESPONSE NOTED, NOW SHOWS 3 REQUIRED, 4 DRINKING | | FOUNTAINS ARE REQUIRED. NOT ADDRESSED. | | | | 53B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 4TH | | FLOOR LAVS REQUIRED 2, INDICATED AS 1. PLEASE CORRECT | | THE FIXTURE COUNT. TABLE 403.1. | | ****NO RESPONSE, NOT ADDRESSED. | | ******RESPONSE NOTED, NO CHANGE, NOT ADDRESSED. | | | | 54B. OK | | | | 55B. SHT LSO.0 INDICATES ASSEMBLY OCCUPANCY FOR THE | | CITY HALL AND LIBRARY/MUSEUM. POTTY PARITY IS REQUIRED | | PER SECTION 403.1.1 AND HAS BEEN INDICATED IN THE 50% | | REVIEW BY PAUL SCHMITZ. THIS HAS NOT BEEN ADDRESSED. | | PLEASE SHOW COMPLIANCE WITH THIS REQUIREMENT. ****NO | | RESPONSE, NOT ADDRESSED. | | ******RESPONSE NOTED, BUT POTTY PARITY HAS NOT BEEN | | ADDRESSED, THERE IS NO 3:2 RATIO AS REQUIRED. THERE IS | | A 1:1 RATIO. THE SECTION OF THE CODE REFERENCED DOES | | NOT SAY THAT IF THERE IS A DIFFERENCE OF 2 OR MORE | | WATER CLOSETS FOR WOMEN PARITY IS AUTOMATICALLY | | ACHIEVED.IT STATES "UNLESS THERE ARE 2 OR FEWER | | FIXTURES FOR MEN". THIS MEANS THAT IF THE OCCUPANCY IS | | SMALL ENOUGH TO ONLY REQUIRE 2 FIXTURES FOR THE MEN, | | THEN POTTY PARITY IS NOT REQUIRED. NO MENTION OF POTTY | | PARITY FOR CITY HALL ASSEMBLY HAS BEEN MENTIONED IN THE | | RESPONSE. PLEASE INDICATE HOW POTTY PARITY WILL BE | | COMPLIED WITH. | | | | 56B. OK | | 57B. OK | | 58B. OK | | 59B. OK | | 60B. OK | | 61B. OK | | 62B. OK | | | | 63B. SHT A6-1.1 DETAIL 7, ACCESSIBLE W/C SHALL BE 1'6" | | OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG. | | 11-28. (SHOWS 2'2"). | | ****NO RESPONSE, NOT ADDRESSED. | | ******RESPONSE NOTED, NO CHANGE, NOT ADDRESSED | | | | 64B. OK | | 65B. OK | | 66B. OK | | 67B. OK | | 68B. OK | | 69B. OK | | | | 70B. SHTS A9-0.1 & A9-0.2 FINISH SCHEDULES: ROOMS | | C1.105, C1.106, A2.705, A2.706, A2.210, A2.211, A3.111, | | A3.114, C3.410, AND C3.412 ALL INDICATE THE WALLS TO BE | | PAINTED. PLEASE INDICATE HOW THIS COMPLIES WITH THE | | REQUIREMENT FOR "SMOOTH, HARD, NONABSORBENT WALLS AS | | REQUIRED IN SECTION 1210.2. | | ****NO RESPONSE, NOT ADDRESSED. | | ******RESPONSE NOTED, BUT EPOXY DOES NOT COMPLY WITH | | THE REQUIREMENT FOR THE SURFACE TO BE HARD.--PLEASE | | INDICATE WHAT PNT-5, CT 2-5 MEANS. THE FLOOR AND BASE | | HAVE BEEN INDICATE AS CT. DOES THE CT 2-5 MEAN THAT THE | | CERAMIC TILE WILL START AT 2' AND EXTEND UP TO 5'? IF | | SO, WILL THE BASE BE 2' WIDE? PLEASE CLARIFY AS THERE | | IS NO FINISH LEGNED WITH THE NUMBER DESIGNATIONS AFTER | | THE MATERIAL. (PNT-5 OR CT 2-5). | | | | 71B. OK | | | | 72B. SHT A9-4.1 INDICATE THE ROOM NUMBERS THAT THE | | DETAIL IS REFERENCING. SHOW COMPLIANCE WITH THE | | FOLLOWING: | | A. 11-4.18.4 FLUSH CONTROLS | | B. 11-4.19.2 CLEARANCES | | C. 11-4.19.4 EXPOSED PIPES & CLEARANCES | | ****NO RESPONSE, NOT ADDRESSED. | | ******RESPONSE NOTED, BUT THE CONTROL HEIGHT FOR THE | | URINAL IS NOT INDICATED. | | | | 73B. SHT A9-4.2 INDICATE THE ROOM NUMBERS THAT THE | | DETAIL IS REFERENCING. SHOW COMPLIANCE WITH THE | | FOLLOWING: | | DETAIL #1 | | A. 11-4.18.4 FLUSH CONTROLS | | B. 11-4.19.2 CLEARANCES | | C. 11-4.19.4 EXPOSED PIPES & CLEARANCES | | ****NO RESPONSE, NOT ADDRESSED. | | ******RESPONSE NOTED, BUT THE CONTROL HEIGHT FOR THE | | URINAL IS NOT INDICATED. | | | | DETAIL #2 | | A. 11-4.18.4 FLUSH CONTROLS | | B. 11-4.19.2 CLEARANCES | | C. 11-4.19.4 EXPOSED PIPES & CLEARANCES | | ****NO RESPONSE, NOT ADDRESSED. | | ******RESPONSE NOTED, BUT THE CONTROL HEIGHT FOR THE | | URINAL IS NOT INDICATED. | | | | 74B. OK | | | | 75B. SHT A9-4.5 DETAILS (1) & (2), SHOW THE FOLLOWING | | FOR COMPLIANCE:A. 11-4.19.2 CLEARANCES | | B. 11-4.19.4 EXPOSED PIPES & SURFACES | | C. 11-4.19.5 FAUCETS | | D. 11-4.21.5 CONTROLS | | E. 11-4.21.7 CURBS | | ****NO RESPONSE, NOT ADDRESSED. | | ******RESPONSE NOTED, BUT THE HEIGHT FOR THE CONTROLS | | IN THE SHOWER ARE NOT INDICATED. | | | | 76B. SHTS A1.307, A1.709, A2.209, A2.315, A2.407, | | A3.109, C3.409, C3.310, A5.504 - SHOW COMPLIANCE WITH | | THE FOLLOWING | | A. 11-4.24.4 SINK DEPTH | | B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH | | REQUIRED) | | C. 11-4.24.6 EXPOSED PIPES & SURFACES | | D. 11-4.24.7 FAUCETS | | ****NO RESPONSE, NOT ADDRESSED. | | ******RESPONSE NOTED, BUT THE FAUCETS WERE NOT | | ADDRESSED. | | | | *************NEW COMMENTS************* | | | | 1C. SHTA9-4.6 DETAILS 1 & 2 SHOW COMPLIANCE WITH THE | | FOLLOWING: | | A. 11-4.18.4 FLUSH CONTROLS | | B. 11-4.19.2 CLEARANCES | | C. 11-4.19.4 EXPOSED PIPES & SURFACES ******RESPONSE | | NOTED, BUT THE SHEET NUMBER WAS A TYPO. THIS IS | | REQUIRED ON SHT A9-4.6. | | | | 2C. SHT A9-4.7 DETAILS 1, 2, & 3 SHOW COMPLIANCE WITH | | THE FOLLOWING: | | A. 11-4.18.4 FLUSH CONTROLS | | B. 11-4.19.2 CLEARANCES | | C. 11-4.19.4 EXPOSED PIPES & SURFACES ******RESPONSE | | NOTED, BUT THE SHEET NUMBER WAS A TYPO. THIS IS | | REQUIRED ON SHT A-04.7. | | | | 3C. SHT P1-6.0 THE FOLLOWING VENTS ARE NOT SHOWN ON THE | | ROOF. P1, P2, P3, & P10. PLEASE SHOW ON THIS SHEET OR | | INDICATE WHERE THEY ARE SHOWN. SECTION 106.1.1. | | ******RESPONSE NOTED, BUT VTR P2 IS NOT INDICATED AND | | SHOULD BE LOCATED AT OR NEAR COL. LINE H/2 AS THE RISER | | DIAGRAM INDICATES THE VENT WITH NO OFFSETS. | | | | **************NEW COMMENTS************* | | | | 1D. SHT P3-2.0, 1ST FLOOR VENTING FOR THE WATER CLOSETS | | AT THE BASE OF RISER P10 IS NOT SHOWN. SECTION | | 901.2.1. | | | | 2D. SHT P2-1.0 DETAILS 1 THRU 5. THE SANITARY PIPING IS | | NOT SHOWN ON THE ENLARGED PLANS. ALSO CHECK FOR BOTH | | HOT AND COLD WATER LINES. SECTION 106.1.1. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. SUBMITTING THE RED | | LINED SET OF PLUMBING SHEETS WHEN RESUBMITTING FOR | | REVIEW WILL HELP EXPEDITE THE PERMIT ALSO. THANK YOU | | FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6721 | | E-MAIL [email protected] | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2006-12-23 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2006-12-23 |
Time |
08:37 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2006-12-16 |
Time |
17:48 |
Sent To |
|
|
Notes |
2006-12-23 17:38:49 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 BUILDING | | FBC-2004 FUEL GAS | | FBC-2001 CHAPTER 1 | | FBC-2001 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | FROM PREVIOUS REVIEW: | | FROM PREVIOUS REVIEW: | | | | 1. OK | | 2. OK | | | | 3. SHT P1-1.1 PUMP ROOM A1-112. RPZV BACKFLOW SHALL BE | | INSTALLED A MAXIMUM OF 4' ABOVE THE FLOOR FOR | | CERTIFICATION AND SERVICE. | | ****RESPONSE NOTED, HEIGHT TO BE INDICATED FOR THE | | BACKFLOWS TO BE A MAXIMUM OF 4' ABOVE THE FLOOR. | | ****RESPONSE NOTED, BUT PLANS INDICATE MINIMUM 4' ABOVE | | THE FLOOR. THE REQUIREMENT IS FOR MAXIMUM 4' ABOVE THE | | FLOOR. | | | | 4. OK | | | | 5. SHTS P1-1.1 THRU P1-1.3 CLEANOUTS REQUIRED BY | | SECTIONS 708.3.1, 708.3.2, 708.3.4, 708.3.5 AND 11-8.1 | | (FOR STORM) SHALL BE SHOWN ON THE PLANS. ****RESPONSE | | NOTED, BUT COMMENT NOT ADDRESSED. MANY CLEANOUTS | | REQUIRED ARE NOT INDICATED. MANY CLEANOUTS REQUIRED ARE | | NOT SHOWN. CLEANOUTS AT THE BASE OF STACKS AS SHOWN ARE | | INCORRECT. THEY DO NOT CLEANOUT THE BASE OF THE STACK. | | ALSO SHOW THE CLEANOUTS REQUIRED ON THE RISER | | DIAGRAMS. | | ****RESPONSE NOTED, BUT THE CLEANOUT SHOWN ON P3-3.0 | | DETAIL 1 AS SHOWN IS CORRECT, BUT IT'S NOT SHOWN ON THE | | FLOOR PLAN. PLEASE CORRELATE INFORMATION ON ALL SHEETS. | | ALSO SEE RISERS P/1, P/7 & P/8. | | | | 6.OK | | 7.OK | | 8.OK | | 9.OK | | 10. OK | | 11. OK | | 12. OK | | 13. OK | | | | 14. SHT P1-6.0 SUBMIT CALCULATIONS FOR PRIMARY AND | | SECONDARY ROOF DRAINS. SHOW THE SQUARE FOOTAGE OF EACH | | AREA, AND SHOW 1/2 AREA OF ALL VERTICAL WALLS, | | INCLUDING PARAPETS, AS WELL AS ALL AREAS OF ROOFS | | DRAINING ONTO THE ROOF FROM ABOVE IN THE CALCULATIONS. | | SECTIONS 1106, AND 1107 WITH ALL SUBSECTIONS. SHOW THE | | LOCATION OF ALL SECONDARY ROOF DRAINS AND OR EMERGENCY | | OVERFLOW SCUPPERS. SECTION 106.1.1. | | ****RESPONSE NOTED, BUT NO CALCULATIONS WERE | | SUBMITTED. | | ****RESPONSE NOTED, BUT THE CALCULATIONS ARE NOT | | CORRECT. NO VERTICAL CONTRIBUTION IS SHOWN FOR THE | | LOWER ROOFS. (A1 THRU A4, A7 THRU A9, E1 THRU E4, E7 | | THRU E9, E1 THRU E4, & H1 THRU H4). THE WALL AT COL. | | LINES 4&7 BETWEEN COL. LINES A&D, CALCULATIONS INDICATE | | 7', WHICH IS SUPPOSED TO BE 1/2 THE WALL HEIGHT. BY | | LOOKING AT A SECTION OF THE WALL, THE HEIGHT IS 20' AND | | 1/2 THE WALL HEIGHT SHOULD BE 10'. (SEE A4-2.0WHICH | | SHOW THE WALL TO BE 18', AND IF ITS SIMILAR TO DETAIL 3 | | ON SHT A5-1.1 WILL HAVE A 2' PARAPET WALL ON TOP OF THE | | ROOF LINE. PLEASE RECHECK ALL CALCULATIONS FOR THE ROOF | | AREAS. | | | | 15. OK | | 16. OK (SHOWN ON SHT P2-1.0U) | | 17. OK | | 18. OK | | 19. OK | | 20. OK | | 21. OK | | 22. OK | | 23. OK | | 24. OK | | 25. OK | | 26. OK | | 27. OK | | 28. OK | | 29. OK | | 30. OK | | 31. OK | | 32. OK | | 33. OK | | 34. OK | | 35. OK | | | | 36. SUBMIT A SANITARY HORIZONTAL RISER ISOMETRIC AND | | VERTICAL RISER DIAGRAMS. SHOW ALL PIPE SIZES, TRAPS, | | VENTS, CLEANOUTS, OFFSETS, RISER NUMBERS AND DFU'S AS | | THEY ACCUMULATE IN THE SYSTEM. SECTION 106.3.5.1.3. | | ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN, | | ALL REQUIRED CLEANOUTS ARE NOT SHOWN, AND DFU'S ARE NOT | | SHOWN AS THEY ACCUMULATE IN THE SYSTEM. ALSO INDICATE | | ON THE FIRST FLOOR WHERE ALL RISERS BEGIN IN THE | | SYSTEM. | | ****RESPONSE NOTED, BUT SHT P3-1.0 RISER 1, LAVS DO NOT | | REFLECT THE FLOOR PLAN 2ND FLOOR C2-1.03. - DOES NOT | | REFLECT THE FLOOR PLAN C4.103/C4.104 DRINKING FOUNTAINS | | SHOW 3, FLOOR PLAN SHOWS 2. - CLEANOUT NOT SHOWN AT THE | | BASE OF P/1. - NOT ALL PIPE SIZES SHOWN.-SHT P3-2.0 | | RISER P/2 CLEANOUT DOWNSTREAM OF JANITOR SINK IN ROOM | | C4.101 NOT INSTALLED PER SECTION 706.3. SECOND CLEANOUT | | AT THE BASE OF P/2 NOT REQUIRED AS IT DOES NOT CLEANOUT | | THE BASE OF THE STACK, NOR DOES IT REFLECT THE FLOOR | | PLAN. - FLOOR DRAIN PIPING IN ROOM D1.101 AS INDICATED | | IS BEING INSTALLED ABOVE THE FLOOR. - EACH DRINKING | | FOUNTAIN SHALL HAVE ITS OWN TRAP. SAFE WASTE FOR THE | | FIXTURES IS NOT APPROVED.(SEE ROOMS D1.101, D1.108, | | AND A3.111). -CLEANOUTS ARE REQUIRED AT THE BASE OF | | STACKS P/4 & P/10. - CLEANOUT FOR P/7 NOT INSTALLED AT | | THE BASE OF P/7. -THE NEW SANT. PIPING TO TOILET ROOM | | D2.105 NOT SHOWN ON THE FLOOR PLAN. -SHOW ALL TOILET | | ROOM NUMBERS ON THE RISER DIAGRAM. - SHOW ALL PIPE | | SIZES. THE PIPE SIZES ARE NOT SHOWN ON MANY PIPES.- | | SHT P3-3.0A TWO WAY CLEANOUT IS REQUIRED NEAR THE | | JUNCTION OF THE BUILDING DRAIN AND THE BUILDING SEWER. | | (DETAIL 1).-THE RISER DIAGRAM DOES NOT REFLECT THE | | FLOOR PLAN FOR A1.05 & A1.106. AN EXTRA FLOOR DRAIN IS | | INDICATED THAT IS NOT SHOWN ON THE FLOOR PLAN.- | | A3.102 & A3.103 ONLY SHOWS 2 LAVS ON THE RISER AND THE | | FLOOR PLAN SHOWS 4.-A4.103 & A4.104TWO W/C'S ARE | | MISSING FROM THE RISER THAT ARE SHOWN ON THE FLOOR | | PLAN.-A4.105NO FLOOR DRAIN AND A SECOND SINK ARE | | SHOWN ON THE FLOOR PLAN THAT ARE NOT SHOWN ON THE RISER | | DIAGRAM. (JANITOR ROOM).-A5.105 SHOWS THE BRANCH | | LINE CONNECTING NEAR THE DRINKING FOUNTAINS ON THE | | FLOOR PLAN, BUT CONNECTING DOWNSTREAM OF THE NEXT | | FIXTURES ON THE RISER DIAGRAM.-A CLEANOUT IS | | REQUIRED AT THE BASE OF RISER P/8-ALL RISER | | DIAGRAMS,CHECK ALL PIPE SIZES, MAKE SURE THE RISER | | DIAGRAMS REFLECT THE FLOOR PLAN FOR BOTH THE SANITARY | | AND THE VENTING.SECTIONS106.1.1, 106..1.2, 706.3, | | 708.3.4, 708.3.5, 100.2.1. | | | | 37. SUBMIT A STORM HORIZONTAL RISER ISOMETRIC DIAGRAM & | | VERTICAL RISER DIAGRAMS. SHOW ALL PIPE SIZES, OFFSETS, | | & CLEANOUTS AND INDICATE THE RISER NUMBERS. SHOW THE | | SQUARE FOOTAGE AS IT ACCUMULATES IN THE SYSTEM. SECTION | | 106.3.5.1.3. | | ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN, | | ALL REQUIRED CLEANOUTS ARE NOT SHOWN, AND SQUARE | | FOOTAGE AS IT ACCUMULATES IN THE SYSTEM IS NOT | | INDICATED. | | ****RESPONSE NOTED, BUT THE GARAGE STORM INDICATES A | | TOTAL OF 10,498SF. THE TOTAL AREA WITHOUT ANY VERTICAL | | WALL/PARAPET CONTRIBUTION IS 23,663SF. PLEASE | | RECALCULATE THE SQUARE FOOTAGE DRAINING INTO EACH | | DRAIN. SHOW 1/2 AREA OF ALL VERTICAL WALL INCLUDING | | PARAPETS, AS WELL AS ALL AREAS FROM ROOFS THAT DRAIN | | ONTO THE ROOF FROM ABOVE, (SEE STAIRWELL ROOFS & | | ELEVATOR), IN CALCULATIONS. -THE TRENCH DRAINS SHOW | | NO SF CONTRIBUTING TO THE TOTAL SF. INDICATE THE | | LOCATIONS OF THE DOWNSPOUTS FROM THE ROTUNDA/MECHANICAL | | ROOF. IF THE LOCATION IS THE SAME AS SHOWN ON THE | | ARCHITECTURAL PLANS, PLEASE EXPLAIN THE REASONING FOR | | DIVIDING THE UPPER ROOF CONTRIBUTION TO TWO ROOF DRAINS | | ON EACH SIDE OF THE BUILDING, WHEN ACTUALLY THE TOTAL | | AREA WILL DRAIN TO ONE DRAIN ON EACH SIDE. THIS IS ALSO | | A CONCERN FOR THE LOWER ROOF (FIRST STORY)ROOF DRAINS | | ( 1736SF). PLEASE CLARIFY. | | | | 38. SUBMIT A WATER RISER ISOMETRIC DIAGRAM. SHOW ALL | | PIPE SIZES, VALVES, WATER HAMMER ARRESTORS, BACKFLOW | | PROTECTION ETC. SECTION 106.3.5.1.3. | | ****RESPONSE NOTED, BUT NOT ALL PIPE SIZES ARE SHOWN, | | NOT ALL REQUIRED VALVES ARE SHOWN, AND ALL WATER HAMMER | | ARRESTORS REQUIRED BY SECTION 604.9, (ICE MAKERS, | | DISHWASHERS, & WASH MACHINES IF FIXTURES ARE | | PROVIDED). | | ****RESPONSE NOTED, BUT THE VALVES ON ALL DOWN-FEED | | WATER LINES ARE MISSING FROM MANY LAV SUPPLY LINES, | | SOME TOILET ROOMS, SS, ETC. SECTION 106.1(4). | | | | 39. OK | | | | 40. ALL PME & FIRE PROTECTION SHEETS. PLANS SHALL BE | | SIGNED, SEALED, AND DATED. SECTION 106.1. ALL TITLE | | BLOCK INFORMATION REQUIRED BY FAC 61G1-23.002 AND FS | | 471.025 SHALL BE SUBMITTED ON EACH SHEET. ****RESPONSE | | NOTED, BUT THE SEAL USED IS NOT APPROVED. NEW SEALS | | SHALL INDICATE THE WORD "LICENSE" IN THE SEAL. (SEE | | ATTACHED SHEET FROM THE FLORIDA BOARD OF PROFESSIONAL | | ENGINEERS). | | ****RESPONSE NOTED, BUT THE SEALS OF SOME MECH. AND | | PLUMBING SHEETS ARE STILL THE OLD SEAL. - ALSO THERE | | SEEMS TO BE TWO SETS OF SIGNATURES FOR THE ENGINEER OF | | RECORD. PLEASE SUBMIT A SIGNED, SEALED, DATED, | | NOTORIZED LETTER INDICATING THE LEGAL SIGNATURE OF THE | | ENGINEER OF RECORD FOR OUR FILES. ONE SET OF PLANS | | SHALL BE RETAINED FOR POSSIBLE REVIEW BY THE FLORIDA | | BOARD OF PROFESSIONAL ENGINEERS. | | | | **************NEW COMMENTS************** | | | | 1B. SHTS P1-1.0U, P1-1.1U, P1-1.1 & P1-2.1. RWL-4 DOES | | NOT REFLECT THE SQUARE FOOTAGE SHOWN ON RISER DIAGRAM | | OR ROOF PLAN. PLEASE CORRELATE RISER, FLOOR PLAN, & | | ROOF PLAN. SECTION 106.1.1. | | ****RESPONSE NOTED. WILL RECHECK AFTER THE CALCULATIONS | | FOR THE ROOF DRAINS HAS BEEN RESUBMITTED WITH | | CORRECTIONS. | | | | 2B. SHTS P1-1.OU & P1-1.1U ALL RWL'S THAT CONNECT TO | | RWL-4 TO BE INDICATED ON THE 1ST FLOOR. THIS WILL AID | | IN TRACING THE RWL'S THROUGH THE BUILDING AND TO VERIFY | | PIPE SIZES. SECTION 106.1.1. | | ****RESPONSE NOTED, BUT ISSUE NOT ADDRESSED. | | | | 3B. SHTS P1-1.1U & P2-1.0U DETAIL #6 THE SINK SHALL NOT | | DRAIN THRU THE WET VENT FOR THE TOILET ROOM. THE | | DISCHARGE FOR THE SINK SHALL CONNECT DOWNSTREAM OF THE | | TOILET ROOM FIXTURES. SECTION 909.1. | | ****RESPONSE NOTED, BUT THE PIPING HAS NOT BEEN CHANGED | | ON SHT P1-1.0U | | | | 4B. OK | | | | 5B. SHT P1-1.2U CLEANOUT REQUIRED AT THE BASE OF P/1 & | | P/10 RISERS, NEAR THE JUNCTION OF THE BUILDING DRAIN | | AND THE BUILDING SEWER, AND AT ALL CHANGES OF DIRECTION | | OVER 45 DEGREES. PLEASE INDICATE ON PLANS. SECTIONS. | | 708.3.3, 708.3.4, 708.3.5. | | ****RESPONSE NOTED, BUT C/O'S ARE NOT SHOWN ON SHTS | | P3-1.0 & P3-2.0. | | | | 6B. SHTS P1-1.2U, ASSOCIATED RISER DIAGRAMS, AND | | ENLARGED FLOOR PLANS. INDICATE HOW THE STACKS P/1 & | | P/10 CAN DRAIN INTO THE TOILET GROUP FIXTURE BRANCH. | | SUBMIT A DETAIL SHOWING THE 4" CLEANOUT TEE, THE 4" | | CROSS FOR THE FIXTURE BRANCH, AND THE 4" DOUBLE | | Y/EIGHTH BEND FITTINGS STACKED ON TOP OF EACH OTHER. | | WILL THEY BE AT THE RIGHT HEIGHT FOR THE W/C'S?SEE | | SECTION 908.3 ALSO. SECTION 106.1.1. (STACKS SHOULD | | CONNECT TO THE BUILDING DRAIN AND FIXTURE GROUPS SHOULD | | CONNECT TO THE STACK SO THAT THE STACK DOES NOT RUN | | THRU THE MIDDLE OF THE FIXTURE GROUP). ****RESPONSE | | NOTED, BUT C/O'S ARE REQUIRED AT THE BASE OF EACH | | STACK. COMMENT HAS NOT BEEN ADDRESSED. | | | | 7B. SHTS P1-1.3U, P1-2.0, P1-2.3, P1-3.3, & P1-4.3 | | RWL-6 DOES NOT REFLECT THE SQUARE FOOTAGE SHOWN ON THE | | RISER DIAGRAM, NOR ON THE ROOF PLAN. PLEASE CORRELATE | | INFORMATION. SECTION 106.1.1 & TABLE 1106.3. | | ****RESPONSE NOTED, BUT THE COMMENT WAS NOT ADDRESSED | | ON SHTS P1-3.3, & P1-4.3. | | | | 8B. OK | | 9B. OK | | 10B. OK | | 11B. OK | | | | 12B. SHT P1-4.1 SHOW RISER P/3 VTR. - NOTE STATES "SEE | | 01 ON DRAWING P2-3.0". INFORMATION NOT SHOWN ON DETAIL | | 01. PLEASE CLARIFY. - SHOW THE VENTING TO REFLECT THE | | FLOOR PLAN FOR KINK S-1 CONNECTED TO RISER P/8. - 4" | | SANITARY - 4" VTR AT COL. LINE E/8 IS SHOWN AS AN | | OFFSET ON THE RISER DIAGRAM. PLEASE CORRELATE FLOOR | | PLAN AND SANT. RISER DIAGRAM. SECTION 106.1.1. | | ****RESPONSE NOTED. NOTE DELETED, BUT COMMENT NOT | | ADDRESSED FOR OFFSETS AND VENTING. -VENTING ON ALL | | RISERS SHALL REFLECT THE VENTING ON THE FLOOR PLAN. | | (ALL VENTING NOT SHOWN ON THE FLOOR PLAN), AND ON THE | | ENLARGED PLUMBING PLANS FLOOR PLAN. | | | | 13B. OK | | 14B. OK | | | | 15B. SHT P1-6.0 SHOW THE LOCATIONS FOR ALL VTR'S. - | | INDICATE THE RWL EACH ROOF DRAIN IS CONNECTED TO. | | SECTION 106.1.1. | | ****RESPONSE NOTED, BUT VTR'S 1, 3, 9 & 10 ARE NOT | | SHOWN. | | | | 16B. SHT P2-1.0U DETAIL 1, FLOOR DRAINS IN C1.104 ARE | | NOT VENTED. SECTION 901.2.1. - THE PIPING AT THE LAVS | | IN ROOM C1.103 DOES NOT REFLECT THE RISER DIAGRAM. | | PLEASE CORRELATE. SECTION 106.1.1. | | ****RESPONSE NOTED, BUT THE FLOOR DRAIN IN THE | | ACCESSIBLE STALL HAS NOT CHANGED TO REFLECT THE CHANGE | | IN THE RISER DIAGRAM. | | | | 17B. SHT P2-1.0U DETAIL 2 DOES NOT REFLECT THE PIPING | | LAYOUT SHOWN ON P1-1.2U. - SUBMIT A DETAIL FOR THE | | SANT. PIPING ARRANGEMENT FOR THE DRINKING FOUNTAINS, | | SHOW HOW THE PIPING CONNECTS THROUGH THE SIDE OF THE | | D.F. UNITS. - SUBMIT A DETAIL FOR THE FITTING | | ARRANGEMENT WHERE THE TOILET ROOM FIXTURES CONNECT TO | | THE BLDG. DRAIN. SECTION 106.1.1. | | ****RESPONSE NOTED, BUT A DETAIL HAS NOT BEEN | | SUBMITTED. ALSO EXPLAIN THE 3" SANT. LINE FROM THE | | DRINKING FOUNTAINS TO THE MEN'S ROOM D1/101.-THE | | FLOOR DRAIN PIPING APPEARS TO BE ABOVE THE SLAB. PLEASE | | CLARIFY. | | | | 18B. OK | | | | 19B. SHT P2-1.0U DETAIL 6, SINK SHALL CONNECT | | DOWNSTREAM OF THE WET VENTED FIXTURES IN THE TOILET | | ROOM. SECTION 909.1. | | ****RESPONSE NOTED. CORRECTED, BUT NOT CORRECTED ON SHT | | P1-1.1U. PLEASE CORRECT TO REFLECT RISER AND DETAIL. | | | | 20B. OK | | 21B. OK | | | | 22B. SHT P2-1.0 DETAIL 4 DOES NOT REFLECT THE FLOOR | | PLAN. NO WATER TO WH'S & SHOWS 2" WATER SUPPLY. SECTION | | 106.1.1. | | ****RESPONSE NOTED, BUT STILL NO WATER SUPPLY TO WATER | | HEATERS. | | | | 23B. OK | | 24B. OK | | 25B. OK. | | | | 26B. SHT P2-2.0 DETAIL 3, SUBMIT A DETAIL FOR SANT. | | PIPING TO D.F.'S - INDICATE RISERS FOR COLD WATER | | DOWNSTREAM OF LAST W/C'S. HOT WATER LINE NOT SHOWN THRU | | BATHROOM FIXTURES. SECTION 106.1.1. | | ****RESPONSE NOTED, BUT STILL SHOWS PIPING OUT THE SIDE | | OF 1ST DF. | | | | 27B. OK | | 28B. OK | | 29B. OK | | | | 30B. SHT P2-3.0 DETAIL 1, INDICATE WHERE SANT. BRANCH | | LINE CONNECTS TO THE SANT. RISER. - FLOOR DRAIN SHOWS | | NO PIPING. SECTION 106.1.1. | | ****RESPONSE NOTED, BUT RISER SHOWS P1 RISER BETWEEN | | W/C'S & LAVS, WHEREAS THE FLOOR PLAN SHOW THE RISER | | BETWEEN W/C'S. CORRELATE RISER AND FLOOR PLAN. | | | | 31B. OK | | 32B. OK | | 33B. OK | | | | 34B. SHT P3.1.0 SANT RISER DIAGRAM, TRAPS ARE REQUIRED | | ON ALL DRINKING FOUNTAINS. SECTION 1002.1. - 1ST FLOOR | | LAVS PIPING DOES NOT REFLECT THE FLOOR PLAN. - FLOOR | | DRAINS DOWNSTREAM OF RISER P/1 ARE NOT VENTED. SECTION | | 901.2.1. - A C/O IS REQUIRED AT THE BASE OF STACK P/1 | | SECTION 708.3.4 - SHOW THE CONNECTION DETAIL AT THE | | BASE OF STACK P/1 WITH A 4" CLEANOUT, A 4" CROSS, AND | | 4" WYE FITTINGS INDICATING THE HEIGHT OF THE W/C | | STUBOUT. - W/C-1 AT THE BASE OF STACK IS NOT VENTED. | | SECTION 901.2.1. -W/C ON 2ND FLOOR IS NOT VENTED. | | SECTION 901.2.1. - LAV ON 3RD FLOOR NOT VENTED. SECTION | | 901.2.1. - INDICATE HOW/WHERE PIPING FOR LAVS & FLOOR | | DRAINS CONNECT TO THE RISER/BRANCH ON THE 2ND, 3RD, & | | 4TH FLOORS. THE FITTINGS INDICATE THAT THE PIPING IS | | SLOPED TO THE LAVS. PLEASE CLARIFY. - MEN C4.104 DOES | | NOT REFLECT ROOM NUMBER ON THE FLOOR PLAN. - PIPING FOR | | FLOOR DRAINS & LAVS 4TH FLOOR DOES NOT REFLECT THE | | FLOOR PLAN. SECTION 106.1.1. | | ****RESPONSE NOTED, BUT 1ST FLOOR LAVS PIPING DOES NOT | | REFLECT THE FLOOR PLAN. -A C/O IS REQUIRED AT THE | | BASE OF STACK P/1 SECTION 708.3.4 - SHOW THE CONNECTION | | DETAIL AT THE BASE OF STACK P/1 WITH A 4" CLEANOUT, A | | 4" CROSS, AND 4" WYE FITTINGS INDICATING THE HEIGHT OF | | THE W/C HOW THE CONNECTION DETAIL AT THE BASE OF STACK | | P/1 WITH A 4" CLEANOUT, A 4" CROSS, AND 4" WYE FITTINGS | | INDICATING THE HEIGHT OF THE W/C STUBOUT. - MEN C4.104 | | DOES NOT REFLECT ROOM NUMBER ON THE FLOOR PLAN. - | | PIPING FOR FLOOR DRAINS & LAVS 4TH FLOOR DOES NOT | | REFLECT THE FLOOR PLAN. SECTION 106.1.1. THESE ITEMS | | HAVE NOT BEEN ADDRESSED. | | | | 35B. ALL RISER DIAGRAMS, ALL FLOOR PLANS FOR ALL | | SYSTEMS. INDICATE THE PIPE SIZE. SECTION 106.1.1. | | ****RESPONSE NOTED, BUT MANY PIPE SIZES ARE NOT SHOWN | | ON THE RISER DIAGRAMS. | | | | 36B. SHT P3-2.0 JANITOR ROOM PIPING DOES NOT REFLECT | | THE FLOOR PLAN. - TRAPS REQUIRED ON ALL DRINKING | | FOUNTAINS. SECTION 1002.1. - CLEANOUTS REQUIRED AT THE | | BASE OF ALL STACKS. 708.3.4. - PIPING TO FLOOR DRAIN | | SHOWN ABOVE THE FLOOR IN ROOM D1.101. PLEASE CLARIFY. - | | PIPING AT THE BASE OF RISER P/2 DOES NOT REFLECT THE | | FLOOR PLAN. - PIPING TO FD-2 AT THE LOADING D1.106 DOES | | NOT REFLECT THE FLOOR PLAN. - PIPING FOR A1.108/A1.109 | | DOES NOT REFLECT THE FLOOR PLAN. - ROOM D2.103 IS | | INDICATED AS D2.104 ON THE FLOOR PLAN. CORRELATE | | INFORMATION. - ALL VENTING AT RISER P/10 STOPS AT LEVEL | | 2. SECTION 903.3 VTR REQUIRED. - TOILET ROOM A2.708 IS | | INDICATED AS A2.706 ON THE FLOOR PLAN. CORRELATE | | INFORMATION. - BATHROOM RISER DOES NOT REFLECT THE | | FLOOR PLAN. (NO FD). - PIPING TO ROOM A4.414 DOES NOT | | REFLECT THE FLOOR PLAN. - CLEANOUT PIPING DOWNSTREAM OF | | C4.101 IS NOT APPROVED AS PIPED. SECTION 706.3. - | | PIPING ON RISER DOES NOT REFLECT THE FLOOR PLAN | | UPSTREAM OF C3.105. - JANITOR SINK C3.105 IS NOT | | VENTED. SECTION 901.2.1. - FLOOR DRAIN CONNECTION AT | | BRANCH LINE 4TH FLOOR DOES NOT REFLECT THE FLOOR PLAN. | | - PIPING AT A2.107 DOES NOT REFLECT THE FLOOR PLAN. (NO | | F.D. PIPING). - PIPING AT ROOM A3.111 DOES NOT REFLECT | | THE FLOOR PLAN AT THE LAVS. - ROOM A3.111 SUBMIT A | | DETAIL FOR FITTING TO W/C & LAVS. - ROOM D2.105 SHOWN | | AS D2.106/D2.107 ON FLOOR PLANS. CORRELATE INFORMATION. | | - ROOM C3.410/C3.412 FLOOR DRAIN FITTING ARE SHOWN TO | | BE INSTALLED AGAINST THE FLOW. SECTION 706.3. - SECTION | | 106.1.1. | | ****RESPONSE NOTED, BUT SOME COMMENTS WERE NOT | | ADDRESSED. SEE THE FOLLOWING: JANITOR ROOM PIPING DOES | | NOT REFLECT THE FLOOR PLAN. - TRAPS REQUIRED ON ALL | | DRINKING FOUNTAINS. SECTION 1002.1. - CLEANOUTS | | REQUIRED AT THE BASE OF ALL STACKS. 708.3.4. - PIPING | | TO FLOOR DRAIN SHOWN ABOVE THE FLOOR IN ROOM D1.101. | | PLEASE CLARIFY.- PIPING AT THE BASE OF RISER P/2 DOES | | NOT REFLECT THE FLOOR PLAN. - PIPING FOR A1.108/A1.109 | | DOES NOT REFLECT THE FLOOR PLAN. - ROOM D2.103 IS | | INDICATED AS D2.104 ON THE FLOOR PLAN. CORRELATE | | INFORMATION.- TOILET ROOM A2.708 IS INDICATED AS | | A2.706 ON THE FLOOR PLAN. CORRELATE INFORMATION. - | | PIPING TO ROOM A4.414 DOES NOT REFLECT THE FLOOR PLAN. | | - CLEANOUT PIPING DOWNSTREAM OF C4.101 IS NOT APPROVED | | AS PIPED. SECTION 706.3. - PIPING AT ROOM A3.111 DOES | | NOT REFLECT THE FLOOR PLAN AT THE LAVS. - ROOM A3.111 | | SUBMIT A DETAIL FOR FITTING TO W/C & LAVS. - ROOM | | D2.105 SHOWN AS D2.106/D2.107 ON FLOOR PLANS. CORRELATE | | INFORMATION. | | | | 37B. SHT P3-3.0 PIPING TO A3.304 & DOWNSTREAM DOES NOT | | REFLECT THE FLOOR PLAN. - VENT PIPING FROM S-1 SINK | | DOES NOT REFLECT THE FLOOR PLAN. OFFSET NOT SHOWN. - | | TRAPS REQUIRED ON ALL DRINKING FOUNTAINS. SECTION | | 1002.1. - S-1 SINK SHALL NOT DRAIN THRU THE WET VENT OF | | THE TOILET ROOM A1.303. SINK SHALL DISCHARGE DOWNSTREAM | | OF THE W/C & LAV. SECTION 909.1. - INDICATE P/8 WITH | | P/6 AT THE BASE OF THE STACK WHERE IT BEGINS. - PIPING | | TO ROOMS A1.105/A1.106 DOES NOT REFLECT THE FLOOR PLAN. | | FLOOR DRAIN PIPING IS SHOWN AS ABOVE THE FLOOR. - P/5 & | | P/9 BEGIN AT THE BASE OF THE STACK. PLEASE INDICATE ON | | RISER DIAGRAM. - PIPING FOR A3.102/A3.103 DOES NOT | | REFLECT THE FLOOR PLAN. - CLEANOUT REQUIRED AT THE BASE | | OF P/9 STACK. - PIPING TO FLOOR DRAINS IN ROOMS | | A3.102/A3.103 ARE ABOVE THE FLOOR. -W/C AT THE BASE | | OF STACK NOT VENTED. SECTION 901.2.1. - INDICATE WHERE | | LINES TO FLOOR DRAINS IN ROOMS A4.103/A4.104 & | | A5.103/A5.104 ARE CONNECTING TO THE BRANCH/STACK. - | | PIPING FOR A4.103/A4.104 DOES NOT REFLECT THE FLOOR | | PLAN. - W/C AT RISER STACK A4.103 IS NOT VENTED. | | SECTION 901.2.1. - PIPING FOR A4.105 DOES NOT REFLECT | | THE FLOOR PLAN. SECTION 106.1.1. | | ****RESPONSE NOTED, BUT THE FOLLOWING COMMENTS WERE NOT | | ADDRESSED:-PIPING TO A3.304 & DOWNSTREAM DOES NOT | | REFLECT THE FLOOR PLAN. - VENT PIPING FROM S-1 SINK | | DOES NOT REFLECT THE FLOOR PLAN. OFFSET NOT SHOWN. - | | PIPING TO ROOMS A1.105/A1.106 DOES NOT REFLECT THE | | FLOOR PLAN. FLOOR DRAIN PIPING IS SHOWN AS ABOVE THE | | FLOOR. -PIPING FOR A4.103/A4.104 DOES NOT REFLECT THE | | FLOOR PLAN. - W/C AT RISER STACK A4.103 IS NOT VENTED. | | SECTION 901.2.1. - PIPING FOR A4.105 DOES NOT REFLECT | | THE FLOOR PLAN. SECTION 106.1.1. | | | | 38B. OK | | | | 39B. SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING | | INFORMATION IS REQUIRED FOR THE GAS PERMIT: | | | | A. OK - "NEW"SHOW THE LOCATION OF THE 2PSI TO 1/2PSI | | REGULATOR. SHUT OFF VALVE REQUIRED UPSTREAM OF | | REGULATOR. | | B. OK | | C. OK | | D. OK | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | ****RESPONSE NOTED, BUT NOT ADDRESSED | | | | F. OK - INFORMATIONAL - 2PSI AT MAXIMUM 200 FT | | DEVELOPED LENGTH ALLOWS 39,656,000 BTU'S. ONLY 10,000 | | BTU'S ARE INDICATED ON PLANS. THE 10,000 BTU'S IS | | QUESTIONABLE AS MOST RESIDENTIAL DRYERS ARE RATED AT | | 22,000 BTU'S. FOR COMPARISON, A .5 PSI SYSTEM WITH 2" | | PIPE WILL DELIVER 800,000 BTU'S. WITH THE EXTRA | | DEVELOPED LENGTH TO THE FARTHEST FUTURE GENERATOR,ITS | | APPROXAMATLY 180'. | | | | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | ****RESPONSE NOTED, BUT NO MANUF. SHEETS FOR THE | | GENERATOR HAS BEEN SUBMITTED. - ALSO SUBMIT THE MANUF. | | SPECIFICATION SHEETS FOR THE GAS REGULATORS. INDICATE | | MODEL NUMBER. LISTING INFORMATION REQUIRED. | | | | H. NA | | I. NA | | | | 40B. SHT P3-5.0 NO HOT WATER LINE SHOWN IN 1ST THRU 4TH | | FLOOR TOILET ROOMS OFF WATER RISER W/1. - WATER RISER | | DOES NOT REFLECT THE FLOOR PLAN AT THE LAVS. - FULL | | OPEN VALVES ARE REQUIRED ON ALL WATER DOWN-FEED LINES. | | SECTION 606.1(4). - RISER DOES NOT REFLECT THE FLOOR | | PLAN AT ROOMS C2.102/C2.103. (2 LAVS SHOWN EACH TOILET | | ROOM). - PIPE SIZE SUPPLYING ROOMS D1.101/D1.102, | | JANITOR ROOM D1.110, TOILET ROOMS A1.108/A1.109. - | | INDICATE THAT RISERS W/4, W/5, & W/8 RISERS START WITH | | RISER W/2 ON THE 1ST FLOOR. SECTION 106.1.1. | | ****RESPONSE NOTED, BUT THE FOLLOWING COMMENTS WERE NOT | | ADDRESSED: - WATER RISER DOES NOT REFLECT THE FLOOR | | PLAN AT THE LAVS. - FULL OPEN VALVES ARE REQUIRED ON | | ALL WATER DOWN-FEED LINES. SECTION 606.1(4). (MANY | | LAVS, TOILET ROOMS, SINKS ETC MISSING VALVES).- RISER | | DOES NOT REFLECT THE FLOOR PLAN AT ROOMS C2.102/C2.103. | | (2 LAVS SHOWN EACH TOILET ROOM). - PIPE SIZE SUPPLYING | | ROOMS D1.101/D1.102, JANITOR ROOM D1.110, TOILET ROOMS | | A1.108/A1.109. (2" SHOWN ON FLOOR PLAN, 1-1/2" ON | | RISER. 3/4" ON FLOOR PLAN, 1/2" ON RISER.SOME LAVS | | SHOW SEPARATE DROPS TO EACH LAV ON THE FLOOR PLAN, BUT | | SINGLE DROPS ON THE RISER). - INDICATE THAT RISERW/8 | | STARTS WITH RISER W/2 ON THE 1ST FLOOR. SECTION | | 106.1.1. | | | | 41B. SHT P3-6.0 RISERS 4, 5 & 8 ARE NOT INDICATED ON | | THE 1ST FLOOR. - RISER DOES NOT REFLECT THE FLOOR PLAN | | ROOMS C3.107/C3.108 AT JAN. SINK, ROOMS C3.410/C3.412, | | AE.111, A4.103/A4.104, A4.105 AND THE TOP OF RISER W/4 | | TO ROOM A5.105, PIPE SIZE AT ROOM A2.209 & SUPPLY TO | | TOILET ROOM ADJACENT, PIPE SIZE SUPPLYING RISER W/8 & | | RISER, SUPPLY LINE TO ROOMS D2.102/D2.103. - W/2 NOT | | FOUND ON 4TH FLOOR AS INDICATED ON RISER. SECTION | | 106.1.1. | | ****RESPONSE NOTED, BUT THE FOLLOWING COMMENTS WERE NOT | | ADDRESSSED: RISER 8 STILL NOT INDICATED ON THE 1ST | | FLOOR. - RISER DOES NOT REFLECT THE FLOOR PLAN ROOMS | | C3.410/C3.412,A4.103/A4.104, (FLOOR PLAN INDICATES | | OVER-HEAD SUPPLY WITH DROPS, BUT RISER INDICATES SUPPLY | | RUN IN THE WALL OFF WATER RISER. TWO W/C'S MISSING ON | | RISER).-PIPE SIZE AT ROOM A2.209, (SHOWS 1" ON THE | | FLOOR PLAN), - PIPE SIZE SUPPLYING RISER W/8 & RISER, ( | | 1" ON FLOOR PLAN, 2" ON RISER - 1-1/2" ON THE FLOOR | | PLAN, BUT 2" ON THE RISER). -W/2 NOT FOUND ON 4TH OR | | 5TH FLOORS AS INDICATED ON RISER. SECTION 106.1.1. | | PLEASE CORRELATE RISER AND FLOOR PLANS. | | | | 42B. SHT P3-7.0 SIZE ALL PIPE PER SECTION 1106.3, AND | | SHOW ALL PIPE SIZES ON THE RISER. - RISER DOES NOT | | REFLECT THE FLOOR PLAN TOP FLOORS RWL/6 & RWL/7. - | | RISERS INDICATE A 5TH FLOOR, BUT FLOOR PLAN DOES NOT | | SHOW A 5TH FLOOR. - RISER SHOWS TRENCH DRAINS ON TWO | | FLOORS, BUT ONLY SHOW TRENCH DRAINS ON 1 FLOOR, (ROOF | | LEVEL), ON THE FLOOR PLAN. -RWL'S 9 THRU 14 SHOW OFFSET | | PIPING FOR ROOF DRAINS IN THE 4TH FLOOR CEILING, BUT | | INDICATE THE ROOF DRAINS TO BE ON THE 4TH LEVEL. PLEASE | | CLARIFY. - PIPE SIZING IS INCORRECT AT 8"/11,715SF, | | 6"/5077SF, 6"/6657SF. TABLE 1106.3. - RWL/9 INDICATES | | PIPING IN 3RD FLOOR CEILING, BUT ROOF DRAINS ARE TO BE | | ON THE 3RD LEVEL. PLEASE CLARIFY. - RWL/15 DOES NOT | | REFLECT THE FLOOR PLAN TO 4" ROOF DRAINS. - PIPING AT | | THE 1ST FLOOR CEILING CONNECTING TO ROOF DRAINS ON THE | | 1ST LEVEL. PLEASE CLARIFY. SECTION 106.1.1. | | ****RESPONSE NOTED, BUT SOME COMMENTS THE FOLLOWING | | COMMENTS WERE NOT ADDRESSED:- RISER DOES NOT REFLECT | | THE FLOOR PLAN TOP FLOORS RWL/6 & RWL/7. - RISERS | | INDICATE A 5TH FLOOR, BUT FLOOR PLAN DOES NOT SHOW A | | 5TH FLOOR. - RISER SHOWS TRENCH DRAINS ON TWO FLOORS, | | BUT ONLY SHOW TRENCH DRAINS ON 1 FLOOR, (ROOF LEVEL), | | ON THE FLOOR PLAN. - PIPE SIZING IS INCORRECT AT | | 8"/11,715SF, 6"/5077SF, 6"/6657SF. TABLE 1106.3. | | | | 43B. SHTS 1,2,3 OF 3 ARE NOT SIGNED, SEALED, & DATED AS | | REQUIRED PER FS 472.025(1). ALSO SEE SHT 1 WHICH STATES | | "NOT VALID UNLESS SEALED WITH SURVEYOR'S EMBOSSED SEAL | | AND SIGNATURE" | | ****NO RESPONSE, NOT ADDRESSED. | | | | 44B. SHTS C1, C5 THRU C22 ENGINEERING CERTIFICATE OF | | AUTHORIZTION IS REQUIRED IN THE TITLE BLOCK. | | 61G15-23.002(2) & FS 471.025. - AN EMBOSSED SEAL IS | | REQUIRED TO IMPRESS REQUIRED INFORMATION ON EACH SHEET. | | UNABLE TO GLEAN ALL INFORMATION REQUIRED FROM SEAL. | | PLEASE RESEAL PLANS. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 45B. SHTS LP-0 THRU LP-3 & IR-1 THE CERTIFICATE OF | | AUTHORIZATION IS REQUIRED IN THE TITLE BLOCK. | | 61G1-16.004(1) & FS 481.319. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 46B. SHT LL-1 IS MISSING THE TITLE BLOCK INFORMATION | | REQUIRED IN 61G1-16.004. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 47B. SHT IR-1 THE CONTROLER & RAIN SENSOR LOCATIONS ARE | | REQUIRED ON PLANS. SECTION 106.1.1. | | ****NO RESPONSE. THIS INFORMATION SHALL BE SUBMITTED AS | | A REVISION PRIOR TO APPLICATION, OR WITH THE | | APPLICATION FOR IRRIGATION PERMIT - NEW COMMENT, NO | | CERTIFICATE OF AUTHORIZATION IN THE TITLE BLOCK AS | | REQUIRED BY 61G1-16.004(2) & FS 481.319. | | | | 48B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 2ND | | FLOOR DRINKING FOUNTAINS SHOWS 4 REQUIRED, BUT ONLY 3 | | ARE REQUIRED PER TABLE 403.1. FIXTURE COUNT INDICATES | | ONLY 2 ARE PROVIDED. PLEASE PROVIDE REQUIRED AMOUNT OF | | DRINKING FOUNTAINS. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 49B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 3RD | | FLOOR DRINKING FOUNTAINS SHOW ONLY 3 ARE REQUIRED. PER | | TABLE 403.1, 4 DRINKING FOUNTAINS ARE REQUIRED. PLEASE | | UPDATE FIXTURE COUNT. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 50B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 4TH | | FLOOR DRINKING FOUNTAINS INDICATE 4 REQUIRED, BUT ONLY | | 3 ARE PROVIDED. PLEASE PROVIDE 4 DRINKING FOUNTAINS. | | TABLE 403.1. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 51B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 1ST | | FLOOR DRINKING FOUNTAINS 2 REQUIRED PER TABLE 403.1, | | BUT READS 1 REQUIRED. PLEASE CORRECT FIXTURE COUNT | | REQUIRED. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 52B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 3RD | | FLOOR DRINKING FOUNTAINS 4 REQUIRED PER TABLE 403.1, | | BUT READS 2 REQUIRED. PLEASE CORRECT FIXTURE COUNT | | REQUIRED. - SHOWS 2 PROVIDED, BUT 4 ARE REQUIRED. | | PLEASE CORRECT INFORMATION. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 53B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 4TH | | FLOOR LAVS REQUIRED 2, INDICATED AS 1. PLEASE CORRECT | | THE FIXTURE COUNT. TABLE 403.1. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 54B. SHT LSO.0 LIBRARY/MUSEUM INDICATES A RESTURANT IN | | OCCUPANT LOAD 1ST FLOOR.PLEASE CONTACT LYNN MASSON, | | ENVIRONMENTAL COMPLIANCE MANAGER CONCERNING THE | | POSSIBLE REQUIREMENT FOR A GREASE INTERCEPTOR. CONTACT | | LYNN BY PHONE (561) 822-2271, OR FAX (561) 822-2279, OR | | E-MAIL [email protected]. | | ****PER ARCHITECT, NO RESTURANT WILL BE IN THE LIBRARY. | | THIS WAS INDICATED AS A RESTURANT FOR OCCUPANCY | | CALCULATIONS ONLY. THERE WILL BE A CAFE IN THE LIBRARY | | WITH NO FOOD PREPARATION. | | | | 55B. SHT LSO.0 INDICATES ASSEMBLY OCCUPANCY FOR THE | | CITY HALL AND LIBRARY/MUSEUM. POTTY PARITY IS REQUIRED | | PER SECTION 403.1.1 AND HAS BEEN INDICATED IN THE 50% | | REVIEW BY PAUL SCHMITZ. THIS HAS NOT BEEN ADDRESSED. | | PLEASE SHOW COMPLIANCE WITH THIS REQUIREMENT. ****NO | | RESPONSE, NOT ADDRESSED. | | | | 56B. SHT A2-0 3 AREAS SHOW STORM WATER FROM ROOF AREAS | | ABOVE THAT CONTRIBUTE TO THE MAIN ROOF AREAS BELOW. THE | | SLOPE OF THE MAIN ROOF AND THE LOCTION OF THE DOWNSPOUT | | IS SHOWING THE TOTAL AREA DRAINING TO ONE ROOF DRAIN, | | BUT THE AREA IS DIVIDED EQUALLY BETWEEN TWO ROOF | | DRAINS. THE SIZING FOR THE ROOF DRAINS WILL HAVE TO BE | | RECHECKED TO ACCOUNT FOR THE AMOUNT OF AREA DRAINING TO | | ONE DRAIN, NOT TWO. TABLE 1106.3. (SEE ROOF AREAS AT | | COL. LINES 1THRU 4/A THRU D, 7 THRU 9.1/A THRU D, AND 4 | | - 5/E THRU H). | | ****NO RESPONSE, NOT ADDRESSED. | | | | 57D. SHTS A2-0, A2-1, A2-2, A2-3 SUBMIT CALCULATIONS | | FOR PRIMARY AND SECONDARY ROOF DRAINS. INDICATE THE | | CONTRUBUTION ADD FROM 1/2 AREA OF ALL VERTICAL WALLS, | | INCLUDING PARAPETS, AND ROOF AREAS FROM ABOVE ADDED TO | | THE ROOF SECTIONS. THIS IS REQUIRED FOR ALL ROOF | | LEVELS. SQUARE FOOTAGE IS SHOWN, BUT NO CALCULATIONS | | WERE SUBMITTED. CONTRIBUTING VERTICAL AREAS FOR WALLS | | IS UNCLEAR. IS THE AREA SHOWN INDICATED PER WALL, OR | | TOTAL FOR ALL WALLS SHOWN. PLEASE CLARIFY. SECTIONS | | 1106.1, 1106.2, 1106.3, 1106.4. | | ****NO RESPONSE NOTED. PRIMARY AND SECONDARY ROOF DRAIN | | CALCULATIONS WERE NOT FOUND. | | | | 58B. SHT A2-0 UPPER ROOF BY DOME SHOWS A DETAIL | | INDICATOR 20/A2-D.1. DETAIL 20 NOT FOUND ON SHT A2-D.1. | | PLEASE CLARIFY. SECTION 106.1.1. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 59B. SHT A2-D.1 DETAIL 04 SHOW HEIGHT AND WIDTH AND | | INDICATE THE MEASUREMENT FROM THE ROOF TO THE FLOW LINE | | OF THE SCUPPER. SECTIONS 106.1.1 AND 1503.4.3. ****NO | | RESPONSE, NOT ADDRESSED. | | | | 60B. SHT A6-1.1 DETAILS 1 THRU 6. SHOW THE TURNING AREA | | IN THE TOILET ROOMS. NOT IN THE ACCESSIBLE STALLS. | | SECTION 11-4.22.3. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 61B. SHT A6-1.1 DETAIL 2, SHOW THE CLEAR FLOOR SPACE | | FOR THE URINAL. SECTION 11-4.18.3. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 62B. SHT A6-1.1 DETAIL 4, ACCESSIBLE W/C SHALL BE 1'6" | | OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG. | | 11-28. LAV TO BE MIN. 15" (C/L OF CLEAR FLOOR SPACE). | | ****NO RESPONSE, NOT ADDRESSED. | | | | 63B. SHT A6-1.1 DETAIL 7, ACCESSIBLE W/C SHALL BE 1'6" | | OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG. | | 11-28. (SHOWS 2'2"). | | ****NO RESPONSE, NOT ADDRESSED. | | | | 64B. SHT A6-2.1 DETAILS 2, 6 & 7 SHOWTHE TURNING AREA | | IN THE TOILET ROOMS. NOT IN THE ACCESSIBLE STALLS. | | SECTION 11-4.22.3. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 65B. SHT A6-2.1 DETAIL 4, ACCESSIBLE W/C SHALL BE 1'6" | | OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG. | | 11-28. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 66B. SHT A6-3.1 DETAIL 2, SHOW A TURNING AREA IN THE | | LOCKER ROOM AREA. SECTION 11-4.2.3. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 67B. SHT A6-3.1 DETAILS 1, 3, 4 & 5, SHOW THE TURNING | | AREA IN THE TOILET ROOMS, NOT IN THE ACCESSIBLE STALLS. | | SECTION 11-4.22.3. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 68B. SHT A6-4.1 DETAILS 1 & 2, SHOW THE TURINING AREA | | IN THE TOILET ROOMS, NOT IN THE ACCESSIBLE STALLS. | | SECTION 11-4.22.3. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 69B. SHT A6-5.1 DETAIL 1, SHOW THE TURNING AREA IN THE | | TOILET ROOM, AND SHOW THE CLEAR FLOOR SPACE FOR THE | | URINAL. SECTIONS 11-4.22.3 AND 11-4.18.3. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 70B. SHTS A9-0.1 & A9-0.2 FINISH SCHEDULES: ROOMS | | C1.105, C1.106, A2.705, A2.706, A2.210, A2.211, A3.111, | | A3.114, C3.410, AND C3.412 ALL INDICATE THE WALLS TO BE | | PAINTED. PLEASE INDICATE HOW THIS COMPLIES WITH THE | | REQUIREMENT FOR "SMOOTH, HARD, NONABSORBENT WALLS AS | | REQUIRED IN SECTION 1210.2. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 71B. SHTS A9-0.1 & A9-0.2 FINISH SCHEDULES: ROOMS D2.10 | | & D2.104 SHOW NO WALL FINISH AND THE FLOORING/BASE | | INDICATE RUBBERIZED FLOORING. INDICATE HOW THIS | | COMPLIES WITH "SMOOTH, HARD, NONABSORBENT FLOORS AS | | REQUIRED IN SECTION 1210.1. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 72B. SHT A9-4.1 INDICATE THE ROOM NUMBERS THAT THE | | DETAIL IS REFERENCING. SHOW COMPLIANCE WITH THE | | FOLLOWING: | | A. 11-4.18.4 FLUSH CONTROLS | | B. 11-4.19.2 CLEARANCES | | C. 11-4.19.4 EXPOSED PIPES & CLEARANCES | | ****NO RESPONSE, NOT ADDRESSED. | | | | 73B. SHT A9-4.2 INDICATE THE ROOM NUMBERS THAT THE | | DETAIL IS REFERENCING. SHOW COMPLIANCE WITH THE | | FOLLOWING: | | DETAIL #1 | | A. 11-4.18.4 FLUSH CONTROLS | | B. 11-4.19.2 CLEARANCES | | C. 11-4.19.4 EXPOSED PIPES & CLEARANCES | | ****NO RESPONSE, NOT ADDRESSED. | | | | DETAIL #2 | | A. 11-4.18.4 FLUSH CONTROLS | | B. 11-4.19.2 CLEARANCES | | C. 11-4.19.4 EXPOSED PIPES & CLEARANCES | | ****NO RESPONSE, NOT ADDRESSED. | | | | 74B. SHT A9-4.4 INDICATE THE ROOM NUMBERS THAT THE | | DETAILS ARE REFERENCING.SHOW COMPLIANCE WITH THE | | FOLLOWING: | | DETAILS #1 - #2 - #3 | | A. 11-4.19.2 CLEARANCES | | B. 11-4.19.4 EXPOSED PIPES & SURFACES | | ****NO RESPONSE, NOT ADDRESSED. | | | | 75B. SHT A9-4.5 DETAILS (1) & (2), SHOW THE FOLLOWING | | FOR COMPLIANCE:A. 11-4.19.2 CLEARANCES | | B. 11-4.19.4 EXPOSED PIPES & SURFACES | | C. 11-4.19.5 FAUCETS | | D. 11-4.21.5 CONTROLS | | E. 11-4.21.7 CURBS | | ****NO RESPONSE, NOT ADDRESSED. | | | | 76B. SHTS A1.307, A1.709, A2.209, A2.315, A2.407, | | A3.109, C3.409, C3.310, A5.504 - SHOW COMPLIANCE WITH | | THE FOLLOWING | | A. 11-4.24.4 SINK DEPTH | | B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH | | REQUIRED) | | C. 11-4.24.6 EXPOSED PIPES & SURFACES | | D. 11-4.24.7 FAUCETS | | ****NO RESPONSE, NOT ADDRESSED. | | | | *************NEW COMMENTS************* | | | | 1C. SHT P9-4.6 DETAILS 1 & 2 SHOW COMPLIANCE WITH THE | | FOLLOWING: | | A. 11-4.18.4 FLUSH CONTROLS | | B. 11-4.19.2 CLEARANCES | | C. 11-4.19.4 EXPOSED PIPES & SURFACES | | | | 2C. SHT P9-4.7 DETAILS 1, 2, & 3 SHOW COMPLIANCE WITH | | THE FOLLOWING: | | A. 11-4.18.4 FLUSH CONTROLS | | B. 11-4.19.2 CLEARANCES | | C. 11-4.19.4 EXPOSED PIPES & SURFACES | | | | 3C. SHT P1-6.0 THE FOLLOWING VENTS ARE NOT SHOWN ON THE | | ROOF. P1, P2, P3, & P10. PLEASE SHOW ON THIS SHEET OR | | INDICATE WHERE THEY ARE SHOWN. SECTION 106.1.1. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. SUBMITTING THE RED | | LINED SET OF PLUMBING SHEETS WHEN RESUBMITTING FOR | | REVIEW WILL HELP EXPEDITE THE PERMIT ALSO. THANK YOU | | FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6721 | | E-MAIL [email protected] | | | | | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2006-11-14 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2006-11-14 |
Time |
07:42 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2006-11-14 |
Time |
07:42 |
Sent To |
|
|
Notes |
2006-11-14 17:40:40 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 BUILDING | | FBC-2004 FUEL GAS | | FBC-2001 CHAPTER 1 | | FBC-2001 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | FROM PREVIOUS REVIEW: | | | | 1. SHT P0-1.0 WATER HEATER SCHEDULE. TWH-1, TWH-2, | | TWH-3, SUBMIT MANUF. SPECIFICATION SHEETS THAT SHOW | | LISTING. SECTION 303.4. | | ****RESPONSE NOTED, WILL BE IN THE SUBMITTAL PACKAGE. | | | | 2. SHT P0-1.0 PUMP SCHEDULE. SUBMIT MANUF. | | SPECIFICATION SHEETS THAT SHOW LISTING. SECTION 303.4. | | ****RESPONSE NOTED, WILL BE IN THE SUBMITTAL PACKAGE. | | | | 3. SHT P1-1.1 PUMP ROOM A1-112. RPZV BACKFLOW SHALL BE | | INSTALLED A MAXIMUM OF 4' ABOVE THE FLOOR FOR | | CERTIFICATION AND SERVICE. | | ****RESPONSE NOTED, HEIGHT TO BE INDICATED FOR THE | | BACKFLOWS TO BE A MAXIMUM OF 4' ABOVE THE FLOOR. | | | | 4. SHTS P1-1.1 THRU P1-5.1 INDICATE RISER NUMBER FOR | | THE SANITARY, STORM, AND WATER RISERS TO TRACK RISERS | | THRU THE BUILDING. SECTION 106.1.1. | | ****RESPONSE NOTED, BUT SOME RISERS INDICATED ON THE | | UPPER FLOORS ARE NOT INDICATED ON THE FIRST FLOOR. | | EXAMPLE P/6 STARTS ON THE FIRST FLOOR, BUT P/8 ALSO | | DRAINS THRU P/6. LABEL P/8 WITH P/6 ON THE FIRST FLOOR. | | ALSO WHY DOES P5 TURN INTO P9? | | | | 5. SHTS P1-1.1 THRU P1-1.3 CLEANOUTS REQUIRED BY | | SECTIONS 708.3.1, 708.3.2, 708.3.4, 708.3.5 AND 11-8.1 | | (FOR STORM) SHALL BE SHOWN ON THE PLANS. ****RESPONSE | | NOTED, BUT COMMENT NOT ADDRESSED. MANY CLEANOUTS | | REQUIRED ARE NOT INDICATED. MANY CLEANOUTS REQUIRED ARE | | NOT SHOWN. CLEANOUTS AT THE BASE OF STACKS AS SHOWN ARE | | INCORRECT. THEY DO NOT CLEANOUT THE BASE OF THE STACK. | | ALSO SHOW THE CLEANOUTS REQUIRED ON THE RISER | | DIAGRAMS. | | | | 6.OK | | 7.OK | | 8.OK | | 9.OK | | 10. OK | | 11. OK | | 12. OK | | 13. OK | | | | 14. SHT P1-6.0 SUBMIT CALCULATIONS FOR PRIMARY AND | | SECONDARY ROOF DRAINS. SHOW THE SQUARE FOOTAGE OF EACH | | AREA, AND SHOW 1/2 AREA OF ALL VERTICAL WALLS, | | INCLUDING PARAPETS, AS WELL AS ALL AREAS OF ROOFS | | DRAINING ONTO THE ROOF FROM ABOVE IN THE CALCULATIONS. | | SECTIONS 1106, AND 1107 WITH ALL SUBSECTIONS. SHOW THE | | LOCATION OF ALL SECONDARY ROOF DRAINS AND OR EMERGENCY | | OVERFLOW SCUPPERS. SECTION 106.1.1. | | ****RESPONSE NOTED, BUT NO CALCULATIONS WERE | | SUBMITTED. | | | | 15. OK | | 16. OK (SHOWN ON SHT P2-1.0U) | | 17. OK | | 18. OK | | 19. OK | | 20. OK | | | | 21. SHT P2-2.0 ALL DETAILS, SHOW ALL PIPE SIZES FOR ALL | | SYSTEMS. SECTION 106.1.1. | | ****RESPONSE NOTED, BUT PIPE SIZES ARE NOT SHOWN FOR | | MANY SECTIONS OF PIPES. ALSO SEE TABLES 710.1(1) & | | 710.1(2). | | | | 22. OK | | 23. OK | | 24. OK | | 25. OK | | 26. OK | | 27. OK | | 28. OK | | 29. OK | | 30. OK | | 31. OK | | 32. OK | | | | 33. SHT P2-3.0 ALL DETAILS, SHOW ALL PIPE SIZES IN ALL | | SYSTEMS. SECTION 106.1.1. | | ****RESPONSE NOTED, BUT PIPE SIZES ARE NOT SHOWN FOR | | MANY SECTIONS OF PIPES. ALSO SEE TABLES 710.1(1) & | | 710.1(2). | | | | 34. SHT P4-1.0 DETAIL #12 CONDENSATE DRAIN, DETAIL NOT | | APPROVED AS SHOWN. CLARIFY OPEN NIPPLE. CLARIFY GAP | | BETWEEN PIPE AND FLOOR. WHY USE A TEE AT THE BOTTOM OF | | THE TRAP? SECTION 106.1.1. | | ****RESPONSE NOTED, BUT DETAIL NOT EXPLAINED OR REVISED | | AS NOTED. COMMENT NOT ADDRESSED. | | | | 35. SHT P4-1.0 DETAIL #13 WATER HEATER DETAIL. PLEASE | | SHOW COMPLIANCE WITH SECTION 607.3.2, THERMAL EXPANSION | | CONTROL. - A SHUT OFF VALVE IS REQUIRED ON EACH SIDE OF | | THE CIRCULATING PUMP. - SUBMIT PUMP MANUF. | | SPECIFICATIONS SHEETS. PUMP SHALL BE LISTED. SECTION | | 303.4. | | ****RESPONSE NOTED, BUT THERMAL EXPANSION CONTROL HAS | | NOT BEEN ADDRESSED. CIRCULATION PUMP SPECIFICATIONS | | SHALL BE SUBMITTED WITH SUBMITTAL PACKAGE. | | | | 36. SUBMIT A SANITARY HORIZONTAL RISER ISOMETRIC AND | | VERTICAL RISER DIAGRAMS. SHOW ALL PIPE SIZES, TRAPS, | | VENTS, CLEANOUTS, OFFSETS, RISER NUMBERS AND DFU'S AS | | THEY ACCUMULATE IN THE SYSTEM. SECTION 106.3.5.1.3. | | ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN, | | ALL REQUIRED CLEANOUTS ARE NOT SHOWN, AND DFU'S ARE NOT | | SHOWN AS THEY ACCUMULATE IN THE SYSTEM. ALSO INDICATE | | ON THE FIRST FLOOR WHERE ALL RISERS BEGIN IN THE | | SYSTEM. | | | | 37. SUBMIT A STORM HORIZONTAL RISER ISOMETRIC DIAGRAM & | | VERTICAL RISER DIAGRAMS. SHOW ALL PIPE SIZES, OFFSETS, | | & CLEANOUTS AND INDICATE THE RISER NUMBERS. SHOW THE | | SQUARE FOOTAGE AS IT ACCUMULATES IN THE SYSTEM. SECTION | | 106.3.5.1.3. | | ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN, | | ALL REQUIRED CLEANOUTS ARE NOT SHOWN, AND SQUARE | | FOOTAGE AS IT ACCUMULATES IN THE SYSTEM IS NOT | | INDICATED. | | | | 38. SUBMIT A WATER RISER ISOMETRIC DIAGRAM. SHOW ALL | | PIPE SIZES, VALVES, WATER HAMMER ARRESTORS, BACKFLOW | | PROTECTION ETC. SECTION 106.3.5.1.3. | | ****RESPONSE NOTED, BUT NOT ALL PIPE SIZES ARE SHOWN, | | NOT ALL REQUIRED VALVES ARE SHOWN, AND ALL WATER HAMMER | | ARRESTORS REQUIRED BY SECTION 604.9, (ICE MAKERS, | | DISHWASHERS, & WASH MACHINES IF FIXTURES ARE | | PROVIDED). | | | | 39. SUBMIT A CONDENSATE RISER ISOMETRIC DIAGRAM. SHOW | | ALL PIPE SIZES, VENTS, TERMINATION POINTS ETC. SECTION | | 106.3.5.1.3. | | ****RESPONSE NOTED, BUT NO CONDENSATE RISER DIAGRAM | | SUBMITTED AS REQUESTED. | | | | 40. ALL PME & FIRE PROTECTION SHEETS. PLANS SHALL BE | | SIGNED, SEALED, AND DATED. SECTION 106.1. ALL TITLE | | BLOCK INFORMATION REQUIRED BY FAC 61G1-23.002 AND FS | | 471.025 SHALL BE SUBMITTED ON EACH SHEET. ****RESPONSE | | NOTED, BUT THE SEAL USED IS NOT APPROVED. NEW SEALS | | SHALL INDICATE THE WORD "LICENSE" IN THE SEAL. (SEE | | ATTACHED SHEET FROM THE FLORIDA BOARD OF PROFESSIONAL | | ENGINEERS). | | | | **************NEW COMMENTS************** | | | | 1B. SHTS P1-1.0U, P1-1.1U, P1-1.1 & P1-2.1. RWL-4 DOES | | NOT REFLECT THE SQUARE FOOTAGE SHOWN ON RISER DIAGRAM | | OR ROOF PLAN. PLEASE CORRELATE RISER, FLOOR PLAN, & | | ROOF PLAN. SECTION 106.1.1. | | | | 2B. SHTS P1-1.OU & P1-1.1U ALL RWL'S THAT CONNECT TO | | RWL-4 TO BE INDICATED ON THE 1ST FLOOR. THIS WILL AID | | IN TRACING THE RWL'S THROUGH THE BUILDING AND TO VERIFY | | PIPE SIZES. SECTION 106.1.1. | | | | 3B. SHTS P1-1.1U & P2-1.01 DETAIL #6 THE SINK SHALL NOT | | DRAIN THRU THE WET VENT FOR THE TOILET ROOM. THE | | DISCHARGE FOR THE SINK SHALL CONNECT DOWNSTREAM OF THE | | TOILET ROOM FIXTURES. SECTION 909.1. | | | | 4B. SHT P1-1.2U FD-2 IN D1.106 LOADING REQUIRES A VENT. | | THIS DOES NOT REFLECT THE RISER DIAGRAM PIPING. THE | | FLOOR IS SLOPING AWAY FROM THE TRENCH DRAIN. PLEASE | | CLARIFY. SECTIONS 901.2.1, 106.1.1. | | | | 5B. SHT P1-1.2U CLEANOUT REQUIRED AT THE BASE OF P/1 & | | P/10 RISERS, NEAR THE JUNCTION OF THE BUILDING DRAIN | | AND THE BUILDING SEWER, AND AT ALL CHANGES OF DIRECTION | | OVER 45 DEGREES. PLEASE INDICATE ON PLANS. SECTIONS. | | 708.3.3, 708.3.4, 708.3.5. | | | | 6B. SHTS P1-1.2U, ASSOCIATED RISER DIAGRAMS, AND | | ENLARGED FLOOR PLANS. INDICATE HOW THE STACKS P/1 & | | P/10 CAN DRAIN INTO THE TOILET GROUP FIXTURE BRANCH. | | SUBMIT A DETAIL SHOWING THE 4" CLEANOUT TEE, THE 4" | | CROSS FOR THE FIXTURE BRANCH, AND THE 4" DOUBLE | | Y/EIGHTH BEND FITTINGS STACKED ON TOP OF EACH OTHER. | | WILL THEY BE AT THE RIGHT HEIGHT FOR THE W/C'S?SEE | | SECTION 908.3 ALSO. SECTION 106.1.1. (STACKS SHOULD | | CONNECT TO THE BUILDING DRAIN AND FIXTURE GROUPS SHOULD | | CONNECT TO THE STACK SO THAT THE STACK DOES NOT RUN | | THRU THE MIDDLE OF THE FIXTURE GROUP). | | | | 7B. SHTS P1-1.3U, P1-2.0, P1-2.3, P1-3.3, & P1-4.3 | | RWL-6 DOES NOT REFLECT THE SQUARE FOOTAGE SHOWN ON THE | | RISER DIAGRAM, NOR ON THE ROOF PLAN. PLEASE CORRELATE | | INFORMATION. SECTION 106.1.1 & TABLE 1106.3. | | | | 8B. SHT P1-1.3 THE WATER SUPPLY TO THE ICE MAKER SHALL | | CONNECT UPSTREAM OF THE MAKE-UP WATER FOR THE COOLING | | TOWERS. - SHOW THE LOCATIONS FOR RWL-6 & RWL-7. SECTION | | 106.1.1 & 608.1. | | | | 9B. SHT P1-2.1 RISER P/8 NOT INDICATED ON THE 1ST | | FLOOR. PLEASE SHOW WHERE RISERS START ON THE FIRST | | FLOOR. SECTION 106.1.1. | | | | 10B. SHT P1-3.2 RISER P/4 SHOWN AT COL. LINE H/2 WAS | | RISER P/2 ON THE FLOOR BELOW. PLEASE CLARIFY. SECTION | | 106.1.1. | | | | 11B. SHT P1-4.1 C/O FOR S-1 SINK PIPING CONNECTING TO | | RISER P/7 IS NOT APPROVED AS INDICATED. SECTION 706.3. | | - RISER P/9 IS NOT INDICATED ON PREVIOUS LEVELS. PLEASE | | CLARIFY. - RISER P/5 SHOWN ON PREVIOUS LEVEL IS NOT | | INDICATED. PLEASE CLARIFY. | | | | 12B. SHT P1-4.1 SHOW RISER P/3 VTR. - NOTE STATES "SEE | | 01 ON DRAWING P2-3.0". INFORMATION NOT SHOWN ON DETAIL | | 01. PLEASE CLARIFY. - SHOW THE VENTING TO REFLECT THE | | FLOOR PLAN FOR KINK S-1 CONNECTED TO RISER P/8. - 4" | | SANITARY - 4" VTR AT COL. LINE E/8 IS SHOWN AS AN | | OFFSET ON THE RISER DIAGRAM. PLEASE CORRELATE FLOOR | | PLAN AND SANT. RISER DIAGRAM. SECTION 106.1.1. | | | | 13B. SHT P1-4.2 SANT. RISER P/2 VTR NOT SHOWN. SECTION | | 106.1.1. | | | | 14B. SHOW ALL PIPE SIZES PER TABLE 1106.3. | | | | 15B. SHT P1-6.0 SHOW THE LOCATIONS FOR ALL VTR'S. - | | INDICATE THE RWL EACH ROOF DRAIN IS CONNECTED TO. | | SECTION 106.1.1. | | | | 16B. SHT P2-1.0U DETAIL 1, FLOOR DRAINS IN C1.104 ARE | | NOT VENTED. SECTION 901.2.1. - THE PIPING AT THE LAVS | | IN ROOM C1.103 DOES NOT REFLECT THE RISER DIAGRAM. | | PLEASE CORRELATE. SECTION 106.1.1. | | | | 17B. SHT P2-1.0U DETAIL 2 DOES NOT REFLECT THE PIPING | | LAYOUT SHOWN ON P1-1.2U. - SUBMIT A DETAIL FOR THE | | SANT. PIPING ARRANGEMENT FOR THE DRINKING FOUNTAINS, | | SHOW HOW THE PIPING CONNECTS THROUGH THE SIDE OF THE | | D.F. UNITS. - SUBMIT A DETAIL FOR THE FITTING | | ARRANGEMENT WHERE THE TOILET ROOM FIXTURES CONNECT TO | | THE BLDG. DRAIN. SECTION 106.1.1. | | | | 18B. SHT P2-1.0U DETAILS 3 & 4, SUBMIT A DETAIL FOR THE | | PIPING ARRANGEMENT FOR THE D.F.'S. SECTION 106.1.1. | | | | 19B. SHT P2-1.0U DETAIL 6, SINK SHALL CONNECT | | DOWNSTREAM OF THE WET VENTED FIXTURES IN THE TOILET | | ROOM. SECTION 909.1. | | | | 20B. SHT P2-1.0 DETAIL 1 DOES NOT REFLECT THE FLOOR | | PLAN OR RISER DIAGRAM. NO WATER PIPING TO WH'S SHOWN. | | SECTION 106.1.1. | | | | 21B. SHT P2-1.0 DETAIL 2 DOES NOT REFLECT THE FLOOR | | PLAN. SHOWS 2" WATER SUPPLY. SECTION 106.1.1. | | | | 22B. SHT P2-1.0 DETAIL 4 DOES NOT REFLECT THE FLOOR | | PLAN. NO WATER TO WH'S & SHOWS 2" WATER SUPPLY. SECTION | | 106.1.1. | | | | 23B. SHT P2-1.0 DETAIL 6 DOES NOT REFLECT THE FLOOR | | PLAN FOR SANT. TO LAVS. FLOOR DRAINS NOT VENTED. | | SECTIONS 106.1.1 & 901.2.1. | | | | 24B. SHT P2-2.0 DETAIL 1, INDICATE RISER NUMBERS. | | SECTION 106.1.1. | | | | 25B. SHT P2-2.0 DETAIL 2, SUBMIT A DETAIL FOR SANT. | | PIPING TO D.F'S. - DOES NOT REFLECT THE RISER DIAGRAM. | | SECTION 106.1.1. | | | | 26B. SHT P2-2.0 DETAIL 3, SUBMIT A DETAIL FOR SANT. | | PIPING TO D.F.'S - INDICATE RISERS FOR COLD WATER | | DOWNSTREAM OF LAST W/C'S. HOT WATER LINE NOT SHOWN THRU | | BATHROOM FIXTURES. SECTION 106.1.1. | | | | 27B. SHT P2-2.0 DETAIL 4, NO PIPING TO FLOOR DRAINS | | SHOWN. SECTION 106.1.1. | | | | 28B. SHT P2-2.0 DETAIL 5, SUBMIT A DETAIL FOR SANT. | | PIPING TO D.F.'S. SECTION 106.1.1. | | | | 29B. SHT P2-2.0 DETAIL 6, SUBMIT A DETAIL FOR SANT. | | PIPING TO D.F.'S. SECTION 106.1.1. - SANT. RISER | | UPSTREAM OF JANITOR SINK NOT SHOWN. (SEE RISER | | DIAGRAM). SECTION 106.1.1. | | | | 30B. SHT P2-3.0 DETAIL 1, INDICATE WHERE SANT. BRANCH | | LINE CONNECTS TO THE SANT. RISER. - FLOOR DRAIN SHOWS | | NO PIPING. SECTION 106.1.1. | | | | 31B. SHT P2-3.0 DETAIL 2, NO PIPING SHOWN TO FLOOR | | DRAINS. - SUBMIT A DETAIL FOR D.F. SANT. PIPING. | | SECTION 106.1.1. | | | | 32B. SHT P2-3.0 DETAIL 3, NO PIPING SHOWN TO FLOOR | | DRAINS. - SUBMIT A DETAIL FOR D.F. SANT. PIPING. | | SECTION 106.1.1. | | | | 33B. SHT P2-3.0 DETAIL 4, NO PIPING SHOWN TO FLOOR | | DRAINS. - SUBMIT A DETAIL FOR D.F. SANT. PIPING. | | SECTION 106.1.1. | | | | 34B. SHT P3.1.0 SANT RISER DIAGRAM, TRAPS ARE REQUIRED | | ON ALL DRINKING FOUNTAINS. SECTION 1002.1. - 1ST FLOOR | | LAVS PIPING DOES NOT REFLECT THE FLOOR PLAN. - FLOOR | | DRAINS DOWNSTREAM OF RISER P/1 ARE NOT VENTED. SECTION | | 901.2.1. - A C/O IS REQUIRED AT THE BASE OF STACK P/1 | | SECTION 708.3.4 - SHOW THE CONNECTION DETAIL AT THE | | BASE OF STACK P/1 WITH A 4" CLEANOUT, A 4" CROSS, AND | | 4" WYE FITTINGS INDICATING THE HEIGHT OF THE W/C | | STUBOUT. - W/C-1 AT THE BASE OF STACK IS NOT VENTED. | | SECTION 901.2.1. -W/C ON 2ND FLOOR IS NOT VENTED. | | SECTION 901.2.1. - LAV ON 3RD FLOOR NOT VENTED. SECTION | | 901.2.1. - INDICATE HOW/WHERE PIPING FOR LAVS & FLOOR | | DRAINS CONNECT TO THE RISER/BRANCH ON THE 2ND, 3RD, & | | 4TH FLOORS. THE FITTINGS INDICATE THAT THE PIPING IS | | SLOPED TO THE LAVS. PLEASE CLARIFY. - MEN C4.104 DOES | | NOT REFLECT ROOM NUMBER ON THE FLOOR PLAN. - PIPING FOR | | FLOOR DRAINS & LAVS 4TH FLOOR DOES NOT REFLECT THE | | FLOOR PLAN. SECTION 106.1.1. | | | | 35B. ALL RISER DIAGRAMS, ALL FLOOR PLANS FOR ALL | | SYSTEMS. INDICATE THE PIPE SIZE. SECTION 106.1.1. | | | | 36B. SHT P3-2.0 JANITOR ROOM PIPING DOES NOT REFLECT | | THE FLOOR PLAN. - TRAPS REQUIRED ON ALL DRINKING | | FOUNTAINS. SECTION 1002.1. - CLEANOUTS REQUIRED AT THE | | BASE OF ALL STACKS. 708.3.4. - PIPING TO FLOOR DRAIN | | SHOWN ABOVE THE FLOOR IN ROOM D1.101. PLEASE CLARIFY. - | | PIPING AT THE BASE OF RISER P/2 DOES NOT REFLECT THE | | FLOOR PLAN. - PIPING TO FD-2 AT THE LOADING D1.106 DOES | | NOT REFLECT THE FLOOR PLAN. - PIPING FOR A1.108/A1.109 | | DOES NOT REFLECT THE FLOOR PLAN. - ROOM D2.103 IS | | INDICATED AS D2.104 ON THE FLOOR PLAN. CORRELATE | | INFORMATION. - ALL VENTING AT RISER P/10 STOPS AT LEVEL | | 2. SECTION 903.3 VTR REQUIRED. - TOILET ROOM A2.708 IS | | INDICATED AS A2.706 ON THE FLOOR PLAN. CORRELATE | | INFORMATION. - BATHROOM RISER DOES NOT REFLECT THE | | FLOOR PLAN. (NO FD). - PIPING TO ROOM A4.414 DOES NOT | | REFLECT THE FLOOR PLAN. - CLEANOUT PIPING DOWNSTREAM OF | | C4.101 IS NOT APPROVED AS PIPED. SECTION 706.3. - | | PIPING ON RISER DOES NOT REFLECT THE FLOOR PLAN | | UPSTREAM OF C3.105. - JANITOR SINK C3.105 IS NOT | | VENTED. SECTION 901.2.1. - FLOOR DRAIN CONNECTION AT | | BRANCH LINE 4TH FLOOR DOES NOT REFLECT THE FLOOR PLAN. | | - PIPING AT A2.107 DOES NOT REFLECT THE FLOOR PLAN. (NO | | F.D. PIPING). - PIPING AT ROOM A3.111 DOES NOT REFLECT | | THE FLOOR PLAN AT THE LAVS. - ROOM A3.111 SUBMIT A | | DETAIL FOR FITTING TO W/C & LAVS. - ROOM D2.105 SHOWN | | AS D2.106/D2.107 ON FLOOR PLANS. CORRELATE INFORMATION. | | - ROOM C3.410/C3.412 FLOOR DRAIN FITTING ARE SHOWN TO | | BE INSTALLED AGAINST THE FLOW. SECTION 706.3. - SECTION | | 106.1.1. | | | | 37B. SHT P3-3.0 PIPING TO A3.304 & DOWNSTREAM DOES NOT | | REFLECT THE FLOOR PLAN. - VENT PIPING FROM S-1 SINK | | DOES NOT REFLECT THE FLOOR PLAN. OFFSET NOT SHOWN. - | | TRAPS REQUIRED ON ALL DRINKING FOUNTAINS. SECTION | | 1002.1. - S-1 SINK SHALL NOT DRAIN THRU THE WET VENT OF | | THE TOILET ROOM A1.303. SINK SHALL DISCHARGE DOWNSTREAM | | OF THE W/C & LAV. SECTION 909.1. - INDICATE P/8 WITH | | P/6 AT THE BASE OF THE STACK WHERE IT BEGINS. - PIPING | | TO ROOMS A1.105/A1.106 DOES NOT REFLECT THE FLOOR PLAN. | | FLOOR DRAIN PIPING IS SHOWN AS ABOVE THE FLOOR. - P/5 & | | P/9 BEGIN AT THE BASE OF THE STACK. PLEASE INDICATE ON | | RISER DIAGRAM. - PIPING FOR A3.102/A3.103 DOES NOT | | REFLECT THE FLOOR PLAN. - CLEANOUT REQUIRED AT THE BASE | | OF P/9 STACK. - PIPING TO FLOOR DRAINS IN ROOMS | | A3.102/A3.103 ARE ABOVE THE FLOOR. -W/C AT THE BASE | | OF STACK NOT VENTED. SECTION 901.2.1. - INDICATE WHERE | | LINES TO FLOOR DRAINS IN ROOMS A4.103/A4.104 & | | A5.103/A5.104 ARE CONNECTING TO THE BRANCH/STACK. - | | PIPING FOR A4.103/A4.104 DOES NOT REFLECT THE FLOOR | | PLAN. - W/C AT RISER STACK A4.103 IS NOT VENTED. | | SECTION 901.2.1. - PIPING FOR A4.105 DOES NOT REFLECT | | THE FLOOR PLAN. SECTION 106.1.1. | | | | 38B. SHT P3-4.0 GARAGE WATER RISER DIAGRAM SHOWS WH'S | | BELOW GRADE. PLEASE CLARIFY. - SHUT OFF VALVE REQUIRED | | ON WH SHOWN BELOW GRADE. SECTION 606.2(2). - A WATER | | HAMMER ARRESTOR IS REQUIRED AT THE ICE MACHINE. SECTION | | 604.9. - SHUT OFF VALVES ARE REQUIRED FOR THE HOSE | | BIBBS ON THE ROOF. SECTION 606.2(2). - SANITARY RISER | | DIAGRAM, FLOOR DRAINS ARE NOT APPROVED FOR INDIRECT | | WASTE. A FLOOR SINK OR HUB DRAIN IS REQUIRED FOR THE | | ICE MACHINE. SECTIONS 802.3 & 802.3.2. - SECTION | | 106.1.1. | | | | 39B. SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING | | INFORMATION IS REQUIRED FOR THE GAS PERMIT: | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. - RISER DOES NOT REFLECT | | THE FLOOR PLAN. OFFSETS BETWEEN THE | | METER AND THE RISER ARE NOT SHOWN. - | | INDICATE WHAT THE RISERS ABOVE THE TEE | | AT THE TOP OF THE RISER AND AT THE | | GENERATOR ARE FOR. FUTURE BTU LOAD AND | | DISTANCE MAY REQUIRE CHANGES IN THE | | GAS SYSTEM WHEN ADDED. | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | C. TYPE OF GAS, (LP OR NATURAL). | | | | D. BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | 402.4(33). | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | | | F. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | H. CLEARLY SHOW THE LOCATION AND CAP- | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | OR ASME), THE DISTANCE OF THE TANK FROM | | THE BUILDING AND ADJACENT PROPERTY LINES | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | CES OF IGNITION, OTHER CONTAINERS, BUILD- | | INGS, AND THE LOCATION OF ANY BUILDING | | OPENINGS BELOW THE RELIEF VALVE OF THE | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | I. CLEARLY INDICATE ON THE PLAN IF THE | | LP TANK IS ABOVE OR BELOW GROUND, AND | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | PER NFPA 58. IF THE TANK | | IS BELOW GROUND THE CONTAINER SHALL BE | | SECURILY ANCHORED PER NFPA 58 SECTION | | 3-2.2.7(H). | | | | 40B. SHT P3-5.0 NO HOT WATER LINE SHOWN IN 1ST THRU 4TH | | FLOOR TOILET ROOMS OFF WATER RISER W/1. - WATER RISER | | DOES NOT REFLECT THE FLOOR PLAN AT THE LAVS. - FULL | | OPEN VALVES ARE REQUIRED ON ALL WATER DOWN-FEED LINES. | | SECTION 606.1(4). - RISER DOES NOT REFLECT THE FLOOR | | PLAN AT ROOMS C2.104/C2.103. (2 LAVS SHOWN EACH TOILET | | ROOM). - PIPE SIZE SUPPLYING ROOMS D1.101/D1.102, | | JANITOR ROOM D1.110, TOILET ROOMS A1.108/A1.109. - | | INDICATE THAT RISERS W/4, W/5, & W/8 RISERS START WITH | | RISER W/2 ON THE 1ST FLOOR. SECTION 106.1.1. | | | | 41B. SHT P3-6.0 RISERS 4, 5 & 8 ARE NOT INDICATED ON | | THE 1ST FLOOR. - RISER DOES NOT REFLECT THE FLOOR PLAN | | ROOMS C3.107/C3.108 AT JAN. SINK, ROOMS C3.410/C3.412, | | AE.111, A4.103/A4.104, A4.105 AND THE TOP OF RISER W/4 | | TO ROOM A5.105, PIPE SIZE AT ROOM A2.209 & SUPPLY TO | | TOILET ROOM ADJACENT, PIPE SIZE SUPPLYING RISER W/8 & | | RISER, SUPPLY LINE TO ROOMS D2.102/D2.103. - W/2 NOT | | FOUND ON 4TH FLOOR AS INDICATED ON RISER. SECTION | | 106.1.1. | | | | 42B. SHT P3-7.0 SIZE ALL PIPE PER SECTION 1106.3, AND | | SHOW ALL PIPE SIZES ON THE RISER. - RISER DOES NOT | | REFLECT THE FLOOR PLAN TOP FLOORS RWL/6 & RWL/7. - | | RISERS INDICATE A 5TH FLOOR, BUT FLOOR PLAN DOES NOT | | SHOW A 5TH FLOOR. - RISER SHOWS TRENCH DRAINS ON TWO | | FLOORS, BUT ONLY SHOW TRENCH DRAINS ON 1 FLOOR, (ROOF | | LEVEL), ON THE FLOOR PLAN. -RWL'S 9 THRU 14 SHOW OFFSET | | PIPING FOR ROOF DRAINS IN THE 4TH FLOOR CEILING, BUT | | INDICATE THE ROOF DRAINS TO BE ON THE 4TH LEVEL. PLEASE | | CLARIFY. - PIPE SIZING IS INCORRECT AT 8"/11,715SF, | | 6"/5077SF, 6"/6657SF. TABLE 1106.3. - RWL/9 INDICATES | | PIPING IN 3RD FLOOR CEILING, BUT ROOF DRAINS ARE TO BE | | ON THE 3RD LEVEL. PLEASE CLARIFY. - RWL/15 DOES NOT | | REFLECT THE FLOOR PLAN TO 4" ROOF DRAINS. - PIPING AT | | THE 1ST FLOOR CEILING CONNECTING TO ROOF DRAINS ON THE | | 1ST LEVEL. PLEASE CLARIFY. SECTION 106.1.1. | | | | 43B. SHTS 1,2,3 OF 3 ARE NOT SIGNED, SEALED, & DATED AS | | REQUIRED PER FS 472.025(1). ALSO SEE SHT 1 WHICH STATES | | "NOT VALID UNLESS SEALED WITH SURVEYOR'S EMBOSSED SEAL | | AND SIGNATURE" | | | | 44B. SHTS C1, C5 THRU C22 ENGINEERING CERTIFICATE OF | | AUTHORIZTION IS REQUIRED IN THE TITLE BLOCK. | | 61G15-23.002(2) & FS 471.025. - AN EMBOSSED SEAL IS | | REQUIRED TO IMPRESS REQUIRED INFORMATION ON EACH SHEET. | | UNABLE TO GLEAN ALL INFORMATION REQUIRED FROM SEAL. | | PLEASE RESEAL PLANS. | | | | 45B. SHTS LP-0 THRU LP-3 & IR-1 THE CERTIFICATE OF | | AUTHORIZATION IS REQUIRED IN THE TITLE BLOCK. | | 61G1-16.004(1) & FS 481.319. | | | | 46B. SHT LL-1 IS MISSING THE TITLE BLOCK INFORMATION | | REQUIRED IN 61G1-16.004. | | | | 47B. SHT IR-1 THE CONTROLER & RAIN SENSOR LOCATIONS ARE | | REQUIRED ON PLANS. SECTION 106.1.1. | | | | 48B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 2ND | | FLOOR DRINKING FOUNTAINS SHOWS 4 REQUIRED, BUT ONLY 3 | | ARE REQUIRED PER TABLE 403.1. FIXTURE COUNT INDICATES | | ONLY 2 ARE PROVIDED. PLEASE PROVIDE REQUIRED AMOUNT OF | | DRINKING FOUNTAINS. | | | | 49B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 3RD | | FLOOR DRINKING FOUNTAINS SHOW ONLY 3 ARE REQUIRED. PER | | TABLE 403.1, 4 DRINKING FOUNTAINS ARE REQUIRED. PLEASE | | UPDATE FIXTURE COUNT. | | | | 50B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 4TH | | FLOOR DRINKING FOUNTAINS INDICATE 4 REQUIRED, BUT ONLY | | 3 ARE PROVIDED. PLEASE PROVIDE 4 DRINKING FOUNTAINS. | | TABLE 403.1. | | | | 51B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 1ST | | FLOOR DRINKING FOUNTAINS 2 REQUIRED PER TABLE 403.1, | | BUT READS 1 REQUIRED. PLEASE CORRECT FIXTURE COUNT | | REQUIRED. | | | | 52B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 3RD | | FLOOR DRINKING FOUNTAINS 4 REQUIRED PER TABLE 403.1, | | BUT READS 2 REQUIRED. PLEASE CORRECT FIXTURE COUNT | | REQUIRED. - SHOWS 2 PROVIDED, BUT 4 ARE REQUIRED. | | PLEASE CORRECT INFORMATION. | | | | 53B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 4TH | | FLOOR LAVS REQUIRED 2, INDICATED AS 1. PLEASE CORRECT | | THE FIXTURE COUNT. TABLE 403.1. | | | | 54B. SHT LSO.0 LIBRARY/MUSEUM INDICATES A RESTURANT IN | | OCCUPANT LOAD 1ST FLOOR.PLEASE CONTACT LYNN MASSON, | | ENVIRONMENTAL COMPLIANCE MANAGER CONCERNING THE | | POSSIBLE REQUIREMENT FOR A GREASE INTERCEPTOR. CONTACT | | LYNN BY PHONE (561) 822-2271, OR FAX (561) 822-2279, OR | | E-MAIL [email protected]. | | | | 55B. SHT LSO.0 INDICATES ASSEMBLY OCCUPANCY FOR THE | | CITY HALL AND LIBRARY/MUSEUM. POTTY PARITY IS REQUIRED | | PER SECTION 403.1.1 AND HAS BEEN INDICATED IN THE 50% | | REVIEW BY PAUL SCHMITZ. THIS HAS NOT BEEN ADDRESSED. | | PLEASE SHOW COMPLIANCE WITH THIS REQUIREMENT. | | | | 56B. SHT A2-0 3 AREAS SHOW STORM WATER FROM ROOF AREAS | | ABOVE THAT CONTRIBUTE TO THE MAIN ROOF AREAS BELOW. THE | | SLOPE OF THE MAIN ROOF AND THE LOCTION OF THE DOWNSPOUT | | IS SHOWING THE TOTAL AREA DRAINING TO ONE ROOF DRAIN, | | BUT THE AREA IS DIVIDED EQUALLY BETWEEN TWO ROOF | | DRAINS. THE SIZING FOR THE ROOF DRAINS WILL HAVE TO BE | | RECHECKED TO ACCOUNT FOR THE AMOUNT OF AREA DRAINING TO | | ONE DRAIN, NOT TWO. TABLE 1106.3. (SEE ROOF AREAS AT | | COL. LINES 1THRU 4/A THRU D, 7 THRU 9.1/A THRU D, AND 4 | | - 5/E THRU H). | | | | 57D. SHTS A2-0, A2-1, A2-2, A2-3 SUBMIT CALCULATIONS | | FOR PRIMARY AND SECONDARY ROOF DRAINS. INDICATE THE | | CONTRUBUTION ADD FROM 1/2 AREA OF ALL VERTICAL WALLS, | | INCLUDING PARAPETS, AND ROOF AREAS FROM ABOVE ADDED TO | | THE ROOF SECTIONS. THIS IS REQUIRED FOR ALL ROOF | | LEVELS. SQUARE FOOTAGE IS SHOWN, BUT NO CALCULATIONS | | WERE SUBMITTED. CONTRIBUTING VERTICAL AREAS FOR WALLS | | IS UNCLEAR. IS THE AREA SHOWN INDICATED PER WALL, OR | | TOTAL FOR ALL WALLS SHOWN. PLEASE CLARIFY. SECTIONS | | 1106.1, 1106.2, 1106.3, 1106.4. | | | | 58B. SHT A2-0 UPPER ROOF BY DOME SHOWS A DETAIL | | INDICATOR 20/A2-D.1. DETAIL 20 NOT FOUND ON SHT A2-D.1. | | PLEASE CLARIFY. SECTION 106.1.1. | | | | 59B. SHT A2-D.1 DETAIL 04 SHOW HEIGHT AND WIDTH AND | | INDICATE THE MEASUREMENT FROM THE ROOF TO THE FLOW LINE | | OF THE SCUPPER. SECTIONS 106.1.1 AND 1503.4.3. | | | | 60B. SHT A6-1.1 DETAILS 1 THRU 6. SHOW THE TURNING AREA | | IN THE TOILET ROOMS. NOT IN THE ACCESSIBLE STALLS. | | SECTION 11-4.22.3. | | | | 61B. SHT A6-1.1 DETAIL 2, SHOW THE CLEAR FLOOR SPACE | | FOR THE URINAL. SECTION 11-4.18.3. | | | | 62B. SHT A6-1.1 DETAIL 4, ACCESSIBLE W/C SHALL BE 1'6" | | OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG. | | 11-28. LAV TO BE MIN. 15" (C/L OF CLEAR FLOOR SPACE). | | | | 63B. SHT A6-1.1 DETAIL 7, ACCESSIBLE W/C SHALL BE 1'6" | | OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG. | | 11-28. (SHOWS 2'2"). | | | | 64B. SHT A6-2.1 DETAILS 2, 6 & 7 SHOWTHE TURNING AREA | | IN THE TOILET ROOMS. NOT IN THE ACCESSIBLE STALLS. | | SECTION 11-4.22.3. | | | | 65B. SHT A6-2.1 DETAIL 4, ACCESSIBLE W/C SHALL BE 1'6" | | OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG. | | 11-28. | | | | 66B. SHT A6-3.1 DETAIL 1, SHOW THE TURNING AREA IN THE | | LOCKER ROOM AREA. SECTION 11-4.2.3. | | | | 67B. SHT A6-3.1 DETAILS 2, 3, 4 & 6, SHOW THE TURNING | | AREA IN THE TOILET ROOMS, NOT IN THE ACCESSIBLE STALLS. | | SECTION 11-4.22.3. | | | | 68B. SHT A6-4.1 DETAILS 1 & 2, SHOW THE TURINING AREA | | IN THE TOILET ROOMS, NOT IN THE ACCESSIBLE STALLS. | | SECTION 11-4.22.3. | | | | 69B. SHT A6-5.1 DETAIL 1, SHOW THE TURNING AREA IN THE | | TOILET ROOM, AND SHOW THE CLEAR FLOOR SPACE FOR THE | | URINAL. SECTIONS 11-4.22.3 AND 11-4.18.3. | | | | 70B. SHTS A9-0.1 & A9-0.2 FINISH SCHEDULES: ROOMS | | C1.105, C1.106, A2.705, A2.706, A2.210, A2.211, A3.111, | | A3.114, C3.410, AND C3.412 ALL INDICATE THE WALLS TO BE | | PAINTED. PLEASE INDICATE HOW THIS COMPLIES WITH THE | | REQUIREMENT FOR "SMOOTH, HARD, NONABSORBENT WALLS AS | | REQUIRED IN SECTION 1210.2. | | | | 71B. SHTS A9-0.1 & A9-0.2 FINISH SCHEDULES: ROOMS D2.10 | | & D2.104 SHOW NO WALL FINISH AND THE FLOORING/BASE | | INDICATE RUBBERIZED FLOORING. INDICATE HOW THIS | | COMPLIES WITH "SMOOTH, HARD, NONABSORBENT FLOORS AS | | REQUIRED IN SECTION 1210.1. | | | | 72B. SHT A9-4.1 INDICATE THE ROOM NUMBERS THAT THE | | DETAIL IS REFERENCING. SHOW COMPLIANCE WITH THE | | FOLLOWING: | | A. 11-4.18.4 FLUSH CONTROLS | | B. 11-4.19.2 CLEARANCES | | C. 11-4.19.4 EXPOSED PIPES & CLEARANCES | | | | 73B. SHT A9-4.2 INDICATE THE ROOM NUMBERS THAT THE | | DETAIL IS REFERENCING. SHOW COMPLIANCE WITH THE | | FOLLOWING: | | DETAIL #1 | | A. 11-4.18.4 FLUSH CONTROLS | | B. 11-4.19.2 CLEARANCES | | C. 11-4.19.4 EXPOSED PIPES & CLEARANCES | | | | DETAIL #2 | | A. 11-4.18.4 FLUSH CONTROLS | | B. 11-4.19.2 CLEARANCES | | C. 11-4.19.4 EXPOSED PIPES & CLEARANCES | | | | 74B. SHT A9-4.4 INDICATE THE ROOM NUMBERS THAT THE | | DETAILS ARE REFERENCING.SHOW COMPLIANCE WITH THE | | FOLLOWING: | | DETAILS #1 - #2 - #3 | | A. 11-4.19.2 CLEARANCES | | B. 11-4.19.4 EXPOSED PIPES & SURFACES | | | | 75B. SHT A9-4.4 SHOW THE FOLLOWING FOR COMPLIANCE:A. | | 11-4.19.2 CLEARANCES | | B. 11-4.19.4 EXPOSED PIPES & SURFACES | | C. 11-4.19.5 FAUCETS | | D. 11-4.21.5 CONTROLS | | E. 11-4.21.7 CURBS | | | | 76B. SHTS A1.307, A1.709, A2.209, A2.315, A2.407, | | A3.109, C3.409, C3.310, A5.504 - SHOW COMPLIANCE WITH | | THE FOLLOWING | | A. 11-4.24.4 SINK DEPTH | | B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH | | REQUIRED) | | C. 11-4.24.6 EXPOSED PIPES & SURFACES | | D. 11-4.24.7 FAUCETS | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. SUBMITTING THE RED | | LINED SET OF PLUMBING SHEETS WHEN RESUBMITTING FOR | | REVIEW WILL HELP EXPEDITE THE PERMIT ALSO. THANK YOU | | FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6721 | | E-MAIL [email protected] | | | | | | | | | | | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
12 |
Status |
P |
Date |
2009-02-26 |
|
|
Cont ID |
|
Sent By |
mflis |
Date |
2009-02-26 |
Time |
08:54 |
Rev Time |
0.00 |
Received By |
mflis |
Date |
2009-02-26 |
Time |
08:54 |
Sent To |
|
|
Notes |
2009-02-26 08:54:27 | ZONING REVIEW: PASSED | | | | ** MID-BLOCK CROSSING REVISIONS | | | | MATT FLIS - 822-1445 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
11 |
Status |
F |
Date |
2009-01-16 |
|
|
Cont ID |
|
Sent By |
mflis |
Date |
2009-01-16 |
Time |
16:51 |
Rev Time |
0.00 |
Received By |
mflis |
Date |
2009-01-16 |
Time |
16:51 |
Sent To |
|
|
Notes |
2009-01-16 16:55:26 | ZONING REVIEW: FAILED | | | | 1) C-9 - SECTION "F" IS NOT INCLUDED FOR REVIEW. PLEASE | | PROVIDE SO THAT STAFF MAY REVIEW SLOPES. | | | | 2) AMENDED CROSS-BLOCK WILL IMPACT EXISTING LIGHT POLES | | ON CLEMATIS STREET. PLEASE INDICATE LOCATION AND | | WHETHER RELOCATION WILL BE NECESSARY. | | | | 3) SEATING AT CROSSBLOCK IS INDICATED AT 16" HIGH. THIS | | IS TOO LOW FOR MOST PEOPLE. PLEASE ADJUST SEAT HEIGHT | | TO 18"-20". | | | | MATT FLIS - 822-1445 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
10 |
Status |
N |
Date |
2009-01-06 |
|
|
Cont ID |
|
Sent By |
mflis |
Date |
2009-01-06 |
Time |
09:33 |
Rev Time |
0.00 |
Received By |
mflis |
Date |
2009-01-06 |
Time |
09:33 |
Sent To |
|
|
Notes |
2009-01-06 09:33:51 | ZONING REVIEW: NOT REQUIRED | | | | ** INTERIOR REVISIONS 2ND FLOOR | | | | MATT FLIS - 822-1445 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
9 |
Status |
N |
Date |
2009-01-06 |
|
|
Cont ID |
|
Sent By |
mflis |
Date |
2009-01-06 |
Time |
08:34 |
Rev Time |
0.00 |
Received By |
mflis |
Date |
2009-01-06 |
Time |
08:34 |
Sent To |
|
|
Notes |
2009-01-06 08:34:53 | ZONING REVIEW: NOT REQUIRED | | | | E & P REVISIONS | | | | MATT FLIS - 822-1445 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
8 |
Status |
P |
Date |
2008-10-27 |
|
|
Cont ID |
|
Sent By |
mflis |
Date |
2008-10-27 |
Time |
11:21 |
Rev Time |
0.00 |
Received By |
mflis |
Date |
2008-10-27 |
Time |
11:21 |
Sent To |
|
|
Notes |
2008-10-27 11:23:16 | ZONING REVIEW: PASSED WITH PROVISO | | | | ** REVISION OF GARAGE | | | | ** NOTE: BOLLARDS WITHIN PARKING GARAGE MAY NOT IMPINGE | | UPON 5'-0" CLEAR SIDE AISLE FOR ADA SPACES. THIS AREA | | MUST BE FREE OF OBSTRUCTION. (SEE ADA SPACE, SW CORNER | | OF GARAGE ON A1-GA.1). THIS WAS AN ISSUE WITH CLEMATIS | | STREET GARAGE. | | | | MATT FLIS - 822-1445 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
7 |
Status |
P |
Date |
2008-02-27 |
|
|
Cont ID |
|
Sent By |
mflis |
Date |
2008-02-27 |
Time |
15:20 |
Rev Time |
0.00 |
Received By |
mflis |
Date |
2008-02-27 |
Time |
15:20 |
Sent To |
|
|
Notes |
2008-02-27 15:31:25 | ZONING REVIEW: PASSED WITH PROVISO | | | | *REVISION TO LANDSCAPE PLANS* | | | | NOTE: SYLVESTER PALM SPECIES IS NOT INIDCATED ON PLANS | | THROUGH ANNOTATION. THIS INCLUDES THE PALMS LOCATED IN | | THE COURTYARD/PLAZA AREA. PLEASE ADD LABEL TO PLAN TO | | CORRECTLY IDENTIFY AND LOCATE THIS SPECIES. | | | | MATT FLIS - 822-1445 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
6 |
Status |
P |
Date |
2007-04-02 |
|
|
Cont ID |
|
Sent By |
mflis |
Date |
2007-04-02 |
Time |
13:41 |
Rev Time |
0.00 |
Received By |
mflis |
Date |
2007-04-02 |
Time |
13:41 |
Sent To |
|
|
Notes |
2007-04-02 13:44:02 | ZONING REVIEW: REVISION 8 - PASSED | | | | * NOTES: | | | | - PLAN OF SIDEWALK/RAMP/PLANTER AT CLEMATIS STREET | | CROSSING REMAINS UNCLEAR; PLEASE CONFIRM THE GRADE | | CHANGES AND THAT NO HANDRAIL WILL BE REQUIRED (AS | | PREVIOUSLY STATED) | | - PLAN SEEMS TO SHOW SOME KIND OF RAILING PROJECTING | | INTO CROSSWALK AREA ADJACENT TO THE RAMP. IS THIS | | CORRECT? | | | | MATT FLIS - 822-1445 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
5 |
Status |
N |
Date |
2007-03-26 |
|
|
Cont ID |
|
Sent By |
mflis |
Date |
2007-03-26 |
Time |
14:00 |
Rev Time |
0.00 |
Received By |
mflis |
Date |
2007-03-26 |
Time |
14:00 |
Sent To |
|
|
Notes |
2007-03-26 14:01:35 | ZONING REVIEW: REVISION 7: NOT REQUIRED | | | | - REVIEW OF MECH AND ELEC REVISIONS IN GARAGE | | - NO CHANGES TO PARKING LAYOUT OR BUILDING ELEVATIONS | | INDICATED | | | | MATT FLIS 822-1445 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
P |
Date |
2007-02-21 |
|
|
Cont ID |
|
Sent By |
mflis |
Date |
2007-02-21 |
Time |
11:22 |
Rev Time |
0.00 |
Received By |
mflis |
Date |
2007-02-21 |
Time |
11:22 |
Sent To |
|
|
Notes |
2007-02-21 11:26:00 | ZONING REVIEW: PASSED WITH PROVISO: | | | | 1) CLEMATIS STREET SHALL BE RETAINED AS EXISTING EXCEPT | | FOR MODIFICATIONS NEAR CROSS-BLOCK CONNECTION. PER | | PREVIOUS PERMIT COMMENTS, LANDSCAPE AND SITE PLAN STILL | | INDICATE ADDITIONAL PLANTERS AND LANDSCAPING. CLEMATIS | | SHOULD BE REMAIN AS PRESENTLY CONFIGURED IN REGARDS TO | | LANDSCAPING. | | 2) ANY UPDATE OF GARAGE ELEVATIONS WILL REQUIRE URBAN | | DESIGN REVIEW AND APPROVAL. | | 3) PLEASE INDICATE SITE VISIBILITY TRIANGLES AT ALL | | CORNERS - 25'-0" LEG PROJECTED FROM CURB LINE. | | | | MATT FLIS 822-1445 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2007-01-30 |
|
|
Cont ID |
|
Sent By |
mflis |
Date |
2007-01-30 |
Time |
16:45 |
Rev Time |
0.00 |
Received By |
mflis |
Date |
2007-01-30 |
Time |
11:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2006-12-27 |
|
|
Cont ID |
|
Sent By |
mflis |
Date |
2006-12-27 |
Time |
14:21 |
Rev Time |
0.00 |
Received By |
mflis |
Date |
2006-12-27 |
Time |
13:42 |
Sent To |
|
|
Notes |
2006-12-27 14:20:54 | ZONING REVIEW: DENIED | | | | OLD ITEMS: | | | | 1. OK - BOLLARDS CAN MATCH THOSE PRESENTLY INSTALLED AT | | INTERSECTION OF CLEMATIS & DIXIE BY FDOT. THESE ARE | | CRASH-RESISTANT. VERIFY THAT BOLLARDS ARE ONLY | | NECESSARY WITH FLUSH CURB. | | 2. OK - DISCUSSED WITH ARCHITECT AND ARE THEY ARE AWARE | | THAT EASEMENTS WILL BE NECESSARY PRIOR TO INSTALLATION | | OF CANOPIES. | | 3. REVIEWED - ON CIVIL SECTION THROUGH SIDEWALK, PLEASE | | PROVIDE DIMENSIONS INDICATING WIDTH OF PLANTER AREA, | | PAVING ADJACENT TO PARKING ETC. | | 4. NOT ADDRESSED - INDICATE 25'-0" SITE VISIBILITY | | TRIANGLES (BACK OF CURB) ON OVERALL SITE PLAN. | | 5. NOT ADDRESSED - EXCEPT FOR ITEM (3) ABOVE, | | STREETSCAPE PLANTINGS ALONG CLEMATIS SHOULD NOT CHANGE. | | THERE ARE APPROXIMATELY 7-8 PLANTERS WITH PALMS | | PRESENTLY. NO ADDITIONAL TREES AND PLANTERS NEED BE | | ADDED. | | 6.OK | | 7. NOT ADDRESSED - LP.1 - PLEASE REPLACE WASHINGTONIA | | PALMS AT INTERSECTION OF BANYAN AND QUADRILLE WITH LIVE | | OAKS (SPACE APPROPRIATELY). | | 8. OK - LANDSCAPE ARCHITECT IS AWARE THAT PLANNING | | SHOULD BE APPRISED OF ANY COORDINATION THAT IMPACTS | | TREE COUNTS, PLACEMENT. | | 9. OK | | 10. OK | | 11. PARTIALLY ADDRESSED - OPENINGS, BUILDING PLAN AND | | SECTION DO NOT SEEM TO MATCH. PLEASE CONFIRM. | | 12. OK | | 13. OK | | 14. OK | | 15. PARTIALLY ADDRESSED - STILL DOES NOT APPEAR TO BE A | | BUILDING SECTION MARKED WHICH PICKS UP THIS STRUCTURE | | AND ASSOCIATED DETAILS. | | | | NEW ITEMS: | | | | 16. ELEVATION KEYS ON A4-XX SERIES DO NOT ALWAYS MATCH | | ELEVATION VIEW. PLEASE MODIFY TO ACCURATELY REFLECT | | WHAT IS SHOWN (BUILDING ONLY OR GARAGE ONLY ETC) 17. | | ELEVATIONS OF GARAGE WERE DISCUSSED WITH ARCHITECT. | | PLANNING STAFF WILL REVIEW MODIFICATIONS PER THAT | | MEETING. | | | | MATT FLIS - 822-1445 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2006-11-07 |
|
|
Cont ID |
|
Sent By |
mflis |
Date |
2006-11-07 |
Time |
09:10 |
Rev Time |
0.00 |
Received By |
mflis |
Date |
2006-11-06 |
Time |
11:37 |
Sent To |
ENG |
|
Notes |
2006-11-06 13:54:17 | ZONING REVIEW: DENIED | | | | 1. A1-1.0 - BOLLARDS LOCATED ALONG PLAZA SHALL MATCH | | THOSE PROVIDED CURRENTLY ALONG CLEMATIS STREET, AND | | SHALL BE APPROPRIATELY SPACED. | | 2. A1-1.0 - ANY CANOPIES OR OVERHANGS MAY REQUIRE | | AIR-RIGHTS EASEMENTS - PLEASE COORDINATE WITH PLANNING | | AND LAW DEPTS. | | 3. A1-1.0, LP.1, C-10 - CLEMATIS STREET | | PAVING/LANDSCAPING, AND GRADING SHALL BE MODIFIED TO | | MATCH RESOLUTION AS DISCUSSED IN NOV. 6, 2006 MEETING. | | PLANNING AND OTHER CITY STAFF SHALL REVIEWSIDEWALK | | AND PLANTER TRANSITION ALONG CLEMATIS PRIOR TO FINAL | | APPROVAL. VERFIY NO RAILING WILL BE REQURIRED ALONG OR | | IN SIDEWALK. | | 4. A1-1.0 - SITE VISIBILITY TRIANGLES MUST BE SHOWN ON | | SITE PLAN - A1-1.0. GARAGE LOOKS VERY CLOSE TO | | IMPINGING. | | 5. LP.1 - ALONG CLEMATIS STREET, PLEASE REMOVE ANY NEW | | PLANTERS OR TREE GRATES WHICH ARE IN ADDITION TO | | EXISTING CONDITIONS. STREET TREE LAYOUT SHALL NOT BE | | MODIFIED FROM EXISTING, EXCEPT PER ITEM #3 ABOVE. (SITE | | AND LANDSCAPE PLANS SHOW INCREASED NUMBER OF TREE | | GRATES AND PLANTINGS). | | 6.LP.1 - CLEMATIS STREET PAVERS MUST MATCH COLOR AND | | STYLE OF EXISTING. | | 7. LP.1 - PLEASE REPLACE WASHINGTONIA PALM AT | | INTERSECTION OF BANYAN AND QUADRILLE WITH LIVE OAKS. 8. | | LP.1 -LANDSCAPING PLANTINGS SHALL BE COORDINATED WITH | | ENGINEERING AND UTILITIES; PLANNING STAFF SHALL REVIEW | | ANY RELOCATED TREES ETC. AS A RESULT OF THIS | | COORDINATION. | | 9. 2/A4-4.0 - NOTE AT T.O. COOLING TOWERS IS MARKED "?" | | - PLEASE CONFIRM SIZE OF EQUIPMENT AND VERIFY THAT IT | | WILL BE SCREENED BY THE PANELS. | | 10. PLEASE PROVIDE STANDARD CITY PARKING DETAILS. 11. | | 1/A4-4.0 - NORTH ELEVATION OF GARAGE IS INCORRECT: | | PLEASE MATCH CORRECT OPENING LOCATIONS. CONTINUE | | KICKPLATE ACROSS ENTIRE ELEVATION. | | 12. 4/A4-4.0 - PLEASE CONTINUE HORIZONTAL REVEAL | | (12"X3/4") FOUND ON EAST ELEVATION OF GARAGE TO SOUTH | | ELEVATION. | | 13. 4/A4-4.0 - NOTE INDICATED WATER FEATURE NIC. | | CONFIRM THAT THIS NOTE SHOULD REMAIN. | | 14. LP.1 - PHOENIX SYLVESTRIS PALMS LOCATED AT CLEMATIS | | STREET PLAZA - NOT SURE EXACTLY WHAT DESIGN STRATEGY IS | | HERE. SHOULD THESE SPECIMEN TREES HIGHLIGHT THE CIRCLE | | FEATURE OR STAND AS A SEPARATE GRID? LAYOUT OF TREES | | SEEMS TO BE A HYBRID OF BOTH IDEAS, AND IS SOMEWHAT | | UNCLEAR. | | 15. 1/A5-0.2/ 2/A4-3.0 - COVERED STRUCTURE WHICH | | EXTENDS BETWEEN CITY HALL AND LIBRARY IN COURTYARD | | APPEARS IN ELEVATION, DOES NOT SHOW IN BUILDING | | SECTIONS. PLEASE PROVIDE DETAILS REGARDING THIS | | ELEMENT. | | | | | | MATT FLIS - 822-1445 |
|
|
|
Account Summary | Usage Policy | Privacy Policy