Plan Review Details - Permit 06100574
Plan Review Stops For Permit 06100574
Review Stop B BUILDING (STRUCTURAL)
Rev No 59 Status P Date 2009-08-21 Cont ID  
Sent By rbrown Date 2009-08-21 Time 11:33 Rev Time 0.00
Received By rbrown Date 2009-08-21 Time 11:33 Sent To  
Notes
2009-08-21 11:34:01STRUCTURAL SUBMITTAL FOR MAILBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 58 Status P Date 2009-04-08 Cont ID  
Sent By jwitmer Date 2009-04-08 Time 13:29 Rev Time 0.77
Received By jwitmer Date 2009-04-08 Time 13:29 Sent To PC
Notes
2009-04-08 13:31:02WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 REVISION REVIEW # 27B:
  
 ACTION: REVIEWED
  
 SHEET:
 A9-2.2
 A9-2.9
 IDI-1.2

Review Stop B BUILDING (STRUCTURAL)
Rev No 57 Status P Date 2009-04-02 Cont ID  
Sent By jwitmer Date 2009-04-02 Time 10:14 Rev Time 0.77
Received By jwitmer Date 2009-04-02 Time 10:14 Sent To PC
Notes
2009-04-02 10:15:49WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 REVISION REVIEW:# 28A GARAGE AS-BUILTS
  
 ACTION: REVIEWED

Review Stop B BUILDING (STRUCTURAL)
Rev No 56 Status P Date 2009-04-02 Cont ID  
Sent By jwitmer Date 2009-04-02 Time 09:37 Rev Time 1.77
Received By jwitmer Date 2009-04-02 Time 09:37 Sent To  
Notes
2009-04-02 09:39:16WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 REVISION REVIEW: 27A CAFE REVISIONS
  
 ACTION: REVIEWED

Review Stop B BUILDING (STRUCTURAL)
Rev No 55 Status P Date 2009-03-18 Cont ID  
Sent By jwitmer Date 2009-03-18 Time 11:43 Rev Time 0.33
Received By jwitmer Date 2009-03-18 Time 11:43 Sent To  
Notes
2009-03-18 11:44:32WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 REVIEW: REVISION 24B- SHEET A0-D.2
  
 ACTION: REVIEWED

Review Stop B BUILDING (STRUCTURAL)
Rev No 54 Status P Date 2009-03-18 Cont ID  
Sent By jwitmer Date 2009-03-18 Time 11:39 Rev Time 2.22
Received By jwitmer Date 2009-03-18 Time 11:39 Sent To  
Notes
2009-03-18 11:40:41WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 REVIEW: REVISION 25A
  
 ACTION: RVIEWED

Review Stop B BUILDING (STRUCTURAL)
Rev No 53 Status P Date 2009-03-13 Cont ID  
Sent By jwitmer Date 2009-03-13 Time 13:58 Rev Time 2.22
Received By jwitmer Date 2009-03-13 Time 13:58 Sent To PC
Notes
2009-03-13 13:59:50WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 REVIEW: STAIR SHOP DRAWING RAILING
  
 ACTION: REVIEWED

Review Stop B BUILDING (STRUCTURAL)
Rev No 52 Status P Date 2009-01-29 Cont ID  
Sent By jwitmer Date 2009-01-29 Time 16:24 Rev Time 0.33
Received By jwitmer Date 2009-01-29 Time 16:24 Sent To PC
Notes
2009-01-29 16:25:43WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 REVIEW: ADDENDUM TO REVION 16B FOR 1 LIGHT POLE
  
 ACTION: REVIEWED

Review Stop B BUILDING (STRUCTURAL)
Rev No 51 Status P Date 2009-01-29 Cont ID  
Sent By jwitmer Date 2009-01-29 Time 16:15 Rev Time 0.44
Received By jwitmer Date 2009-01-29 Time 16:14 Sent To PC
Notes
2009-01-29 16:16:35WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 REVIEW: PLANTER/ SEAT DETAIL
 SSK-205
 SSK-206
 SSK-207
  
 ACTION: REVIEWED

Review Stop B BUILDING (STRUCTURAL)
Rev No 50 Status P Date 2009-01-23 Cont ID  
Sent By jwitmer Date 2009-01-23 Time 15:26 Rev Time 0.88
Received By jwitmer Date 2009-01-23 Time 15:26 Sent To  
Notes
2009-01-23 15:30:33WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 REVISION # 24A REVIEW:
  
 ACTION:OK A0-0, A0-1, A0-3 & A0-D.2
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 49 Status F Date 2009-01-14 Cont ID  
Sent By jwitmer Date 2009-01-14 Time 08:40 Rev Time 0.77
Received By jwitmer Date 2009-01-14 Time 08:40 Sent To PC
Notes
2009-01-14 08:45:13WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 REVIEW: STAIR RAILINGS WITH CALCULATIONS
  
 ACTION: DENIED
  
 1) FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 48 Status P Date 2009-01-14 Cont ID  
Sent By jwitmer Date 2009-01-14 Time 08:34 Rev Time 0.55
Received By jwitmer Date 2009-01-14 Time 08:34 Sent To PC
Notes
2009-01-14 08:37:13WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 REVIEW: NEW CANOPY FOUNDATION PLAN
  
 ACTION: REVIEWED
  
 SKETCH NUMBER CSA-002/ SSK-001-SSK-004

Review Stop B BUILDING (STRUCTURAL)
Rev No 47 Status P Date 2009-01-13 Cont ID  
Sent By jwitmer Date 2009-01-13 Time 13:54 Rev Time 2.55
Received By jwitmer Date 2009-01-13 Time 13:54 Sent To  
Notes
2009-01-13 16:03:18WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 REVISION REVIEW 23A
 ACTION: BUILDING PROVISO:
 SHEET LS1-2.2 & A1-2.2
 SITE MEETING HELD 01-13-09 AT CATALFUMO'S SITE OFFICE
 WITH REPRESENTATIVES FROM SONG & ASSOC,
 TED DAVIS ARCHITECTURE, CATALFUMO AND CITY
 REPRESENTATIVES ALL AGREED THESE TWO WALLS ARE
 TENANT SEPERATION WALLS AS PER SECTION 708.1(5). PLANS
 RED LINED TO FACILITATE THE ACCEPTANCE OF REVISION 23A.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 46 Status F Date 2008-12-31 Cont ID  
Sent By jwitmer Date 2008-12-31 Time 08:24 Rev Time 0.55
Received By jwitmer Date 2008-12-31 Time 08:24 Sent To PC
Notes
2008-12-31 08:27:56WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 REVIEW: RFI# 0871(1-3)
  
 ACTION: DENIED
  
 61G15-23.002(2) FL. ADMIN. CODE. PLANS SIGNED & SEALED
 BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE:
 NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR,
 THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER
 IS PRACTICING (471.025 F.S. AND 471.023 F.S.).
  
 471.023 F.S. CERTIFICATE OF AUTHORIZATION. THE TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD
 THE NUMBER TO EACH SHEET. THIS MAY BE ADDED BY HAND.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 45 Status P Date 2008-12-24 Cont ID  
Sent By jwitmer Date 2008-12-24 Time 16:22 Rev Time 0.77
Received By jwitmer Date 2008-12-24 Time 16:22 Sent To  
Notes
2008-12-24 16:24:50WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 BUILDING REVIEW
 ACTION: REVIEWED
 :
 DEC. 24/08
 REVISION: 20B
 SHEET: A1-GA.1 SECOND FLOOR PARKING LEVEL THE SOUTHWEST
 CORNER OF THE
 PARKING STRUCTURE PLANS INDICATE BOLLARDS LOCATED
 WITHIN THE ACCESS AISLE
 ASSOCIATED WITH DISABLED PARKING SPACE. PLEASE REMOVE
 BOLLARDS, REVIEW
 SECTION 11-4.6.3 MUST BE PART OF THE ACCESSIBLE ROUTE
 TO BUILDING OR FACILITY
 ENTRANCE.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 44 Status P Date 2008-11-17 Cont ID  
Sent By jwitmer Date 2008-11-17 Time 16:15 Rev Time 0.77
Received By jwitmer Date 2008-11-17 Time 16:15 Sent To  
Notes
2008-11-17 16:16:19WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 REVIEW: REVISION# 21A
  
 ACTION: REVIEWED

Review Stop B BUILDING (STRUCTURAL)
Rev No 43 Status P Date 2008-11-12 Cont ID  
Sent By jwitmer Date 2008-11-12 Time 11:54 Rev Time 0.77
Received By jwitmer Date 2008-11-12 Time 11:54 Sent To PC
Notes
2008-11-12 11:56:44WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 REVIEW: REVISION 16-C
  
 ACTION: REVIEWED
 REVISED RAILING TO GARAGE RAMP & STAIRS

Review Stop B BUILDING (STRUCTURAL)
Rev No 42 Status P Date 2008-11-03 Cont ID  
Sent By jwitmer Date 2008-11-03 Time 13:54 Rev Time 0.77
Received By jwitmer Date 2008-11-03 Time 13:54 Sent To  
Notes
2008-11-03 13:59:32 
  
 WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 BUILDING PROVISO:
 NOV.03/08
 REVISION: 20A
 SHEET: A1-GA.1 SECOND FLOOR PARKING LEVEL THE SOUTHWEST
 CORNER OF THE
 PARKING STRUCTURE PLANS INDICATE BOLLARDS LOCATED
 WITHIN THE ACCESS AISLE
 ASSOCIATED WITH DISABLED PARKING SPACE. PLEASE REMOVE
 BOLLARDS, REVIEW
 SECTION 11-4.6.3 MUST BE PART OF THE ACCESSIBLE ROUTE
 TO BUILDING OR FACILITY
 ENTRANCE.
  
 IM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 41 Status F Date 2008-10-20 Cont ID  
Sent By jwitmer Date 2008-10-20 Time 08:48 Rev Time 0.77
Received By jwitmer Date 2008-10-20 Time 08:48 Sent To  
Notes
2008-10-20 09:08:35WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 REVIEW: SHEET A0-D.1 REVISION# 16B
  
 ACTION: DENIED
  
 1) STAIR SECTION THE HANDRAILIS ONLY 1'-6 INCHES LONG
 THIS IS THE DIMENSION TO BE USED FOR EXTENSIONS FOR
 RAMPS. 11-4.9.4(2) IF HANDRAILS ARE NOT CONTINUOUS,
 THEY SHALL EXTEND AT LEAST 12 INCHES (305 MM) BEYOND
 THE TOP RISER AND AT LEAST 12 INCHES (305 MM) PLUS THE
 WIDTH OF ONE TREAD BEYOND THE BOTTOM RISER. AT THE TOP,
 THE EXTENSION SHALL BE PARALLEL WITH THE FLOOR OR
 GROUND SURFACE. AT THE BOTTOM, THE HANDRAIL SHALL
 CONTINUE TO SLOPE FOR A DISTANCE OF THE WIDTH OF ONE
 TREAD FROM THE BOTTOM RISER; THE REMAINDER OF THE
 EXTENSION SHALL BE HORIZONTAL [SEE FIGURE 19 (C) AND
 FIGURE 19 (D)]. HANDRAIL EXTENSIONS SHALL COMPLY WITH
 SECTION 11-4.4 .
  
 2) THE CONTINIOUS HANDRAIL EXTENSIONS FOR BOTH STAIRS
 AND HANDRAILS STATE IN SECTION 11-4.9.4 (2) WILL NEED
 TO COMPLY WITH SECTION 11-4.4.THE BOTTOM PART OF THE
 EXTENSION MUST BE NO HIGHER THAN27 INCHES.
  
 3) THE RAMP DOES NOT INDICATE HOW EDGE PROTECTION WILL
 BE MET 11-4.8.7.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 40 Status P Date 2008-10-20 Cont ID  
Sent By jwitmer Date 2008-10-20 Time 08:45 Rev Time 0.77
Received By jwitmer Date 2008-10-20 Time 08:45 Sent To  
Notes
2008-10-20 08:48:41WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 REVIEW: REVISION 16B
  
 ACTION: REVIEWED
 SHEET: A0-0,A0.1, A0-2, A0-3A0-4, A0-5 & A0-D.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 39 Status P Date 2008-08-26 Cont ID  
Sent By jwitmer Date 2008-08-26 Time 08:39 Rev Time 0.77
Received By jwitmer Date 2008-08-26 Time 08:39 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 38 Status P Date 2008-08-26 Cont ID  
Sent By jwitmer Date 2008-08-26 Time 08:37 Rev Time 0.77
Received By jwitmer Date 2008-08-26 Time 08:37 Sent To PC
Notes
2008-08-26 08:39:11WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*)MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 REVIEW: TROPICAL DESIGN- ATTACHMENT CALCULATIONS
  
 ACTION: REVIEWED

Review Stop B BUILDING (STRUCTURAL)
Rev No 37 Status P Date 2008-08-26 Cont ID  
Sent By jwitmer Date 2008-08-26 Time 08:29 Rev Time 0.77
Received By jwitmer Date 2008-08-26 Time 08:29 Sent To PC
Notes
2008-08-26 08:36:10WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*)MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 REVIEW: CALCULATIONS FOR PRE-CAST
  
 ACTION: REVIEWED

Review Stop B BUILDING (STRUCTURAL)
Rev No 36 Status P Date 2008-08-26 Cont ID  
Sent By jwitmer Date 2008-08-26 Time 08:21 Rev Time 0.77
Received By jwitmer Date 2008-08-26 Time 08:21 Sent To PC
Notes
2008-08-26 08:22:56WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*)MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 REVIEW: SHEET S-1
  
 ACTION: REVIEWED

Review Stop B BUILDING (STRUCTURAL)
Rev No 35 Status F Date 2008-08-01 Cont ID  
Sent By jwitmer Date 2008-08-01 Time 11:23 Rev Time 1.22
Received By jwitmer Date 2008-08-01 Time 11:23 Sent To PC
Notes
2008-08-01 11:28:45WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*)MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 REVIEW: CALCULATIONS FOR ARCHITECTURAL PRECAST CONCRETE
 SIGN ATTACHMENT
  
 ACTION: DENIED
  
 1) THE ENGINEER'S SIGNATURE ARE COPIES NOT ORIGINAL
 SIGNATURES. 61G15-23.002(2)FL. ADMIN. CODE. PLANS
 SIGNED & SEALED BY A PROFESSIONAL ENGINEER SHALL
 INCLUDE EITHER THE: NAME, ADDRESS AND LICENSE NUMBER OF
 THE ENGINEER OR, THE NAME AND LICENSE NUMBER OF THE
 ENGINEER AND THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS
 THROUGH WHICH THE ENGINEER IS PRACTICING (471.025 F.S.
 AND 471.023 F.S.).
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 34 Status P Date 2008-08-01 Cont ID  
Sent By jwitmer Date 2008-08-01 Time 10:49 Rev Time 1.22
Received By jwitmer Date 2008-08-01 Time 10:49 Sent To PC
Notes
2008-08-01 10:50:35WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*)MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 REVIEW: WIND LOAD CALCULATIONS FOR LIGHT POLES
  
 ACTION: REVIEWED
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 33 Status P Date 2008-06-30 Cont ID  
Sent By jwitmer Date 2008-06-30 Time 13:46 Rev Time 0.55
Received By jwitmer Date 2008-06-30 Time 13:46 Sent To PC
Notes
2008-06-30 13:48:19WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*)MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 REVIEW:SUBMITTAL
  
 ACTION:REVIEWED
 CAST STONE ATTACHMENT
 PARAPET WALL LIBRARY BARREL VAULT

Review Stop B BUILDING (STRUCTURAL)
Rev No 32 Status P Date 2008-06-03 Cont ID  
Sent By jwitmer Date 2008-06-03 Time 11:25 Rev Time 0.77
Received By jwitmer Date 2008-06-03 Time 11:25 Sent To PC
Notes
2008-06-03 11:27:19WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*)MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 REVIEW: GARAGE A CONNECTOR ROOF NOA & ROOF ENGINEERING
  
 ACTION: REVIEWED

Review Stop B BUILDING (STRUCTURAL)
Rev No 31 Status P Date 2008-06-03 Cont ID  
Sent By jwitmer Date 2008-06-03 Time 11:24 Rev Time 0.77
Received By jwitmer Date 2008-06-03 Time 11:24 Sent To PC
Notes
2008-06-03 11:25:35WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*)MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 REVIEW:GARAGE "A" STAIR ROOF NOA & ENGINEERING
  
 ACTION: REVIEWED

Review Stop B BUILDING (STRUCTURAL)
Rev No 30 Status P Date 2008-06-03 Cont ID  
Sent By jwitmer Date 2008-06-03 Time 11:22 Rev Time 0.77
Received By jwitmer Date 2008-06-03 Time 11:22 Sent To PC
Notes
2008-06-03 11:24:04WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*)MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 REVIEW: CITY CENTER GARING GARAGE PRECAST PILASTER
 CAPS
  
 ACTION: REVIEWED

Review Stop B BUILDING (STRUCTURAL)
Rev No 29 Status F Date 2008-05-12 Cont ID  
Sent By jwitmer Date 2008-05-12 Time 11:28 Rev Time 0.77
Received By jwitmer Date 2008-05-12 Time 11:28 Sent To PC
Notes
2008-05-12 11:37:40WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*)MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 REVISION REVIEW: LIBRARY BARREL VAULT PARAPET WALL
  
 ACTION: DENIED.
  
 1) 61G15-23.002(2)FL. ADMIN. CODE. PLANS SIGNED &
 SEALED BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER
 THE: NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER
 OR, THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER
 IS PRACTICING (471.025 F.S. AND 471.023 F.S.).
  
 61G15-23.002(2)FL. ADMIN. CODE. A COVER SHEET OR
 INDEX SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED
 AND THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF
 THE PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX.
  
 2) PAGE 1 OF 5 INDICATES THE USE OF 3/4" CDX PLYWOOD TO
 BE USED AS A SUB-SHEATHING, NO WALL FINISH IS PROVIDED.
 PLEASE SEE SECTION 603.1.1.2 NONBEARING EXTERIOR WALLS
 WHERENO FIRE RESISTANCE RATING IS REQUIRED FIRE
 RESISTANCE TREATED PLYWOOD MAY BE INSTALLED. PLEASE
 CORRECT.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.)

Review Stop B BUILDING (STRUCTURAL)
Rev No 28 Status P Date 2008-05-12 Cont ID  
Sent By jwitmer Date 2008-05-12 Time 11:16 Rev Time 0.77
Received By jwitmer Date 2008-05-12 Time 11:16 Sent To  
Notes
2008-05-12 11:28:22WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*)MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 REVISION REVIEW:
  
 ACTION: REVIEWED
  
 NOTICE OF ACCEPTANCE: 061005746" LOUVER SYSTEM MODEL
 EA 64.

Review Stop B BUILDING (STRUCTURAL)
Rev No 27 Status P Date 2008-05-08 Cont ID  
Sent By jwitmer Date 2008-05-08 Time 12:52 Rev Time 3.33
Received By jwitmer Date 2008-05-08 Time 12:52 Sent To FIRE
Notes
2008-05-08 12:53:41CITY HALL/ CITY CENTER REVISION# 14E
  
 BUILDING PLAN REVIEW
 PERMIT: 06100574
 ADD: 401 CLEMATIS ST.
 CONT: CATALFUMO
 TEL: (561)307-4746
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION # 14E
  
 ACTION: REVIEWED-OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 26 Status F Date 2008-04-18 Cont ID  
Sent By jwitmer Date 2008-04-18 Time 11:47 Rev Time 0.56
Received By jwitmer Date 2008-04-18 Time 11:47 Sent To  
Notes
2008-04-18 12:20:17CITY HALL/ CITY CENTER REVISION# 14D
  
 BUILDING PLAN REVIEW
 PERMIT: 06100574
 ADD: 401 CLEMATIS ST.
 CONT: CATALFUMO
 TEL: (561)307-4746
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION # 14D
  
 ACTION: DENIED
  
 1) SHEET A1-1.1 COMMISION CHAMBERS NOW ARE SHOWN AS A 1
 HRRATED WALL BUT WINDOWS G-10 & G-11ON SHEET A8-2.1
 INDICATES WINDOWS NOT RATED, SEE TABLE 715.3 OPENING
 PROTECTION.
  
 2)SEE PLANS THERE ARE (3) AREAS THAT ARE MISSING 1 HR
 RATING IN THE 1 HR RATED WALL AROUND THE CORRIDOR.
  
 3) A1-1.2 W4-8/ 1 HR WALL RATING IS SHOWN AT THE
 LOADING DOCK WALL BUT THERE IS NO WALL TAGS SHOWN ON
 SHEET A5-D.1.
  
 4) A1-1.2 W4-8/ 1 HR LOADING DOCK/ CORRIDOR WALL SHOULD
 INDICATE AS A FIRE-SMOKE DESIGNATION.
  
 5) A1-1.2 TRASH ROOM/ CALL CENTER W4-8 NO WALL TYPE THE
 MECH AND LS BOTH INDICATE AS SUCH.
  
 6) A1-1.2 COORIDOR D1.006 LS & MECHANICAL INDICATE
 SMOKE RATING WHILE LS INDICATES AN EXIT AT DOOR D1-004A
 WHICH IS A FIRE/ SMOKE RATED CORRIDOR, INACTED BY THE
 MUSEUM BEING A A-3 OCCUPANCY.
  
 7) A1-1.2 VESTIBULE D1.005 IS TRUELY A EXIT PASSAGEWAY
 NOT A VESTIBULE, THE COMMON WALL BILLING / VESTIBULE
 SHOULD BE A 2 HR RATED WALL, (EXIT PASSAGEWAY). SEE
 MECHANICAL COMMENTS DUCT PENETRATING EXIT.
  
 8) WALL TYPE P2-4 ON SHEET A5-D.1 DOES NOT INDICATE
 SMOKE RATING.
  
 9)A1-1.2 LOBBY C1.008 IT APPEARS 3 POSSIBLE BOOK
 RETURNS IN THE 1 HR RATED WALL, PLEASE PROVIDE
 ADDITIONAL DETAILS FOR FIRE RATING OF THIS AREA.
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 10)A1-1.2 PLEASE REVIEW STORAGE AREAS ON MECH PLAN
 C1.403 & C1.404 INDICATE THE USE OF TRANSFER OPENINGS
 THERE ARE NO SMOKE DAMPERS PROVIDED 710.7.
  
 11) A1-2.1 MISSING A REVISION FOR THE ARCHITECTURAL
 SHEET, LS AND MECH PLANS INDICATE SMOKE PARTITIONS AT
 THE STORAGE A2.303
  
 12)A1-2.1 MISSING A REVISION FOR THE ARCHITECTURAL
 SHEET, SHAFT WALL COMMON TO THE MONUMENTAL STAIR DOES
 NOT INDICATE A 2HR FIRE RATING WALL TAG.
  
 13) A1-2.2 (2) ISSUES WITH 707.2 EXCEPTION# 3:
 13A) STAIR TO MEZZANINE THE DOOR AND WALL NOT RATED,
 SINCE THERE IS NO WALL RATING AT THE MEZZANINE WALL
 LEVEL THIS WILL CREATE THE FLOOR LEVEL FIRE RATING
 BETWEEN FLOORS.
 13B) THE SAME AREA WHERE THE SHAFT WALL COMES OUT OF
 THE MEZZANINE LEVEL WILL NEED A 1 HR RATED SHAFT WALL.
  
 14) A1-2.2PLEASE REVIEW THE DOOR LOCATION FOR THE
 ENTRY TO THE MEZZANINE LEVEL , REVIEW ARCHITECTURAL, LS
 BOTH THE OVERALL FLOOR PLAN AND THE MEZZANINE LEVEL
 CORRELATE.
  
 15) LS1-3.1 REVISIONS SUBMITTED BUT NO ARCHITECTURAL
 SHEETS.
  
 16) LS 1-3.1 / A1-3.1 & M1-3.1 MISSING ROOM I.D. BY
 CORRIDOR A3.604 & A3.115.
  
 17) LS1-3.2 THE PLANS DO NOT INDICATE WALL RATING
 BETWEEN THE PRE-FUNCTION AREA AND THE THE LOBBY C3.301
 ALTHOUGH THE DOORS INDICATE A 20 MINUTE RATING, THIS
 SHOULD BE PART OF THE 1 HOUR RATED DORRIDOR TABLE 1016,
 (A) OCCUPANCY > THAN 30.
  
 18) RESTROOM EXHAUST 1ST FLOOR THROUGH THE 4 TH FLOOR
 LIBRARY, 5TH FLOOR CITY HALL, ARE NOT INDICATED AS
 BEING IN 2 HR RATED SHAFTS. 716.6.
  
 19) SHEET LS1.2.2 & A1-2.2 EXIT ACCESS CORRIDOR ON GRID
 LINE COLUMN LINE J & 6 SHOULD HAVE A 1 HR FIRE RATING
 AND DOORS ADDED AGAIN THIS IS AN (A3) OCCUPANCY WITH AN
 OCCUPANT LOAD GREATER THAN 30. TABLE 1016.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 25 Status P Date 2007-11-27 Cont ID  
Sent By jwitmer Date 2007-11-27 Time 15:56 Rev Time 1.55
Received By jwitmer Date 2007-11-27 Time 15:56 Sent To PC
Notes
2007-11-27 15:57:34SHOP DRAWINGS SCAFFOLDING SHOP DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 24 Status P Date 2007-11-06 Cont ID  
Sent By jwitmer Date 2007-11-06 Time 09:51 Rev Time 2.22
Received By jwitmer Date 2007-11-06 Time 09:50 Sent To  
Notes
2007-11-06 09:53:17REVISION# 12A CATCH UP OF REVISIONS 8,9,10,11 & 12.

Review Stop B BUILDING (STRUCTURAL)
Rev No 23 Status P Date 2007-09-28 Cont ID  
Sent By jwitmer Date 2007-09-28 Time 08:45 Rev Time 0.77
Received By jwitmer Date 2007-09-28 Time 08:45 Sent To PC
Notes
2007-09-28 08:46:57SHORING CALCULATIONS AND SHOP DRAWINGS FOR MEZZANINE
 STAIRS TO ROOF

Review Stop B BUILDING (STRUCTURAL)
Rev No 22 Status F Date 2007-09-18 Cont ID  
Sent By jwitmer Date 2007-09-18 Time 14:30 Rev Time 0.00
Received By jwitmer Date 2007-09-18 Time 15:09 Sent To  
Notes
2007-09-18 15:09:12CITY HALL/ CITY CENTER REVISION# 11
  
 BUILDING PLAN REVIEW
 PERMIT: 06100574
 ADD: 401 CLEMATIS ST.
 CONT: CATALFUMO
 TEL: (561)307-4746
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION # 11
  
 ACTION: DENIED
  
  
 NOTES SHEET A8-0.2 FOOTNOTE D DOOR SHALL HAVE
 CLOSER
 FOOTNOTE E SMOKE
 AND DRAFT CONTROL ASSEMBLY W/ ARTIFICIAL BOTTOM SEAL
  
 INSTALLED ACROSS THE FULL WIDTH OFTHE BOTTOM OF THE
 DOOR ALL
  
 IN COMPLIANCE WITHUL 1784.
  
 1) SHEET A1-1.1:
 1A) DOOR A1-120A IS MISSING FOOTNOTE "D & E"
 1B) DOOR A1-201A IS MISSING FOOTNOTE "E"
 1C) SECURITY DESKA 1 HR RATED WALL IN FRONT OF DESK,
 PLEASE SEE A9.3.1 DETAIL# 4, NOW IS MISSING RATED WALL
 AND DOORWAY
 1D) RECEPTION DESK A 1 HR RATED WALL PLEASE SEE A9-3.1
 DETAIL# 3 NOW HAS BY PASS WINDOWS, 1 HR RATED?
  
 2) SHEET A1-2.1
 2A) DOOR A2-008-A 1 HR RATED DOOR MISSING FOOTNOTE
 "D&E"
 2B) DOOR A2-001-A1 HR RATED DOOR MISSING FOOTNOTE
 "D&E"
  
 3)SHEET A1-3.2 :
 3A)DOOR C3-105-A, 1 HR RATED DOOR IS MISSING FOOTNOTE
 "D&E"
 3B) DOOR C3-106-A , 1 HR RATED DOOR IS MISSING FOOTNOTE
 "D&E"
 3C) DOOR C3-107-A, 1 HR RATED DOOR ISMISSING FOOTNOTE
 "D&E"
 3D)DOOR C3-108-A, 1 HR RATED DOOR IS MISSING FOOTNOTE
 "D&E"
 3E)DOOR C3-109-A, 1 HR RATED DOOR IS MISSING FOOTNOTE
 "D&E"
  
 NOTE MEETING AT CONSTRUCTION SITE 9-18-07 :
  
 1) DISCUSSED THE NEED FOR CUT SECTIONS OF THE
 STAIRTOWER# 10 THIRD FLOOR INDICATING A 2 HR RATING
 BETWEEN THE A/C DUCT AND
 STAIRWELL AS WELL AS THE MOVING THE FIRE DAMPERS FROM
 WITHIN THE STAIRTOWER WALLS TO ALLOW FOR ACCESS PANELS
 OUTSIDE OF THE STAIR TOWER.
  
 2) STIAR WAY # 11 DISCUSSED THE NEED OF A CUT SECTION
 THROUGH THE STAIRWAY INDICATING THE PLACEMENT OF THE
 MEZZANINE FLOOR THAT WILL KEEP THE DUCTWORK FROM
 ENTERING STAIRTOWER #7.
  
 3) THE THIRD ISSUE THAT WAS ALSO BROUGHT UP THAT NO
 SHAFT WALL WILL BE NECESSARY IN THE MEZZANINE STAIRWAY
 SINCE IT IS WITHIN THE STORY. THERE ARE CONCERNS ON THE
 REQUIRED WIDTH OF THE STAIR!
  
 4) SHEET A8-0.1DOORS MISSING FOOTNOTE :1 HR RATED
 DOOR MISSING FOOTNOTE "D&E"
 A1-120-A
 A1-201-A
 A2-008-A
 A2-001-A
  
 5) SHEET A8-0.2 DOORS MISSING FOOTNOTE: 1 HR RATED DOOR
 MISSING FOOTNOTE "D&E"
 C3-105-A
 C3-106-A
 C3-107-A
 C3-108-A
 C3-110-A
  
 6)SHEET A9-3.1 COMMENT 1C & 1D.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 21 Status P Date 2007-09-17 Cont ID  
Sent By jwitmer Date 2007-09-17 Time 08:42 Rev Time 0.55
Received By jwitmer Date 2007-09-17 Time 08:42 Sent To PC
Notes
2007-09-17 08:43:24LIBRARY 5TH FLOOR SHORING PLAN

Review Stop B BUILDING (STRUCTURAL)
Rev No 20 Status P Date 2007-09-02 Cont ID  
Sent By jwitmer Date 2007-09-02 Time 08:51 Rev Time 0.75
Received By jwitmer Date 2007-09-02 Time 08:51 Sent To  
Notes
2007-09-02 08:52:59REVISIONS # 11& 12 SHEETSA1-GA.2 & A1- GA.3OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 19 Status F Date 2007-09-02 Cont ID  
Sent By jwitmer Date 2007-09-02 Time 07:44 Rev Time 0.77
Received By jwitmer Date 2007-09-02 Time 07:11 Sent To  
Notes
2007-09-02 08:48:58BUILDING PLAN REVIEW
 PERMIT: 06100574
 ADD: 401 CLEMATIS ST
 CONT: CATALFUMO
 TEL: (561)307-4746
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION # 11-12REVIEW
 ACTION: DENIED
  
 1) GARAGE MAIN ELECTRIC ROOM B1.103THE FLOOR IS NOW
 DROPPED DOOR B1-103-AIS INDICATED WITH A PAIR OF 3'-0"
 OUTSWING DOORS AND A LANDING AND STAIR THAT IS ONLY
 3'-0" WIDE.
 THE PLAN DOESN'T INDICATE THE PRESENCE OF A HANDRAIL
 SYSTEM OR NOTE AS SUCH. THE PLAN ALSO INDICATES THE (2)
 RISERS TO BE 6 7/16" INCHES AND TREAD DEPTH OF 11".
 1003.5.1
 WHERE A CHANGE IN LEVEL MEANS OF EGRESS NOT EXCEEDING
 21 INCHES (533 MM) IS ACHIEVED BY A STAIR, THE MINIMUM
 TREAD DEPTH OF SUCH STAIR SHALL BE 13 INCHES (330 MM)
 AND THE PRESENCE AND LOCATION OF EACH STEP SHALL BE
 READILY APPARENT.
  
 2)BOTH THE ELECTRIC ROOM AND MECHANICAL ROOM INDICATE
 THE FLOOR SLAB IS NOW RECESSED 6" PLEASE PROVIDE THE
 INFORMATION HOW **READILY APPARENT** WILL BE
 ACCOMPLISHED IN SECTION 1003.5.1.
  
 3) GARAGE MAIN ELECTRIC ROOM B1.103 DOOR B1-103-B IS AN
 OUTSWING DOOR WITH AUTOMATIC CLOSER WITH LATCHSEE
 A8-0.1 NOTES D & E AND SEE A8-0.2DOOR SCHEDULE. WITH
 THE DOOR
 HAVING A CLOSER AND LATCH THE LANDING ON THE INTERIOR
 OF THE ROOM SHOULD EXTEND A MINIMUM OF 12" SEE
 MANEUVERING CLEARENCE AT DOORS FIGURE 25(A) THE LANDING
 WOULD NEED TO BE A MINIMUM OF 48" DEEP.11-4.13.6
 MANEUVERING CLEARENCES AT DOORS. MINIMUM MANEUVERING
 CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH IN THE REQUIRED
 CLEARANCES SHALL BE CLEAR & LEVEL.
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 4) SHEET S1-1.0THE EXTERIOR OF THE MAIN ELECTRIC ROOM
 IN THE GARAGE PORTION OF THE PLAN INDICATES A SINGLE
 3'-0" DOORWAY WHERE AS THE ARCHITECTURAL SHEETS
 INDICATE A PAIR OF DOORS.
 PLEASE CORRELATE PLAN DETAILS.106.1.2*ADDITIONAL
 INFORMATION REQUIRED.
  
 5) ONE SET OF PLANS IS MISSING SHEET A1-GA.1 THERE ARE
 (2) A1-GA.3 IN SET.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status P Date 2007-08-26 Cont ID  
Sent By jwitmer Date 2007-08-26 Time 14:27 Rev Time 0.00
Received By jwitmer Date 2007-08-26 Time 13:50 Sent To FIRE
Notes
2007-08-26 14:28:49REV # 10 A3-3.0 & A3-3.2

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status P Date 2007-08-23 Cont ID  
Sent By jwitmer Date 2007-08-23 Time 16:31 Rev Time 2.55
Received By jwitmer Date 2007-08-23 Time 16:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status P Date 2007-08-17 Cont ID  
Sent By jwitmer Date 2007-08-17 Time 15:43 Rev Time 0.33
Received By jwitmer Date 2007-08-17 Time 15:43 Sent To PC
Notes
2007-08-17 15:44:53SUBMITTAL: SHOP DRAWINGS 3RD FLOOR LIBRARY SHORING /
 RESHORING PLANS

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status P Date 2007-08-01 Cont ID  
Sent By jwitmer Date 2007-08-01 Time 13:27 Rev Time 0.55
Received By jwitmer Date 2007-08-01 Time 13:23 Sent To  
Notes
2007-08-01 13:28:44LIBRARY 3RD LEVEL SHORING AND RESHORING PLANS AND
 CALCULATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status P Date 2007-07-12 Cont ID  
Sent By jwitmer Date 2007-07-12 Time 14:47 Rev Time 1.33
Received By jwitmer Date 2007-07-12 Time 14:47 Sent To PC
Notes
2007-07-12 14:48:06REV# 6 & 9.

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status P Date 2007-07-06 Cont ID  
Sent By jwitmer Date 2007-07-06 Time 12:12 Rev Time 0.25
Received By jwitmer Date 2007-07-06 Time 12:12 Sent To PC
Notes
2007-07-06 12:39:55CALCULATIONS FROM UNITED FORMING POUR 2& 3 SHORING
 UNITED FORMING CAST-IN-PLACE CONCRETE FRAMING & SHORING
 CALCULATIONS
 UNITED FORMING CAST-IN-PLACE CONCRETE FRAMING & SHORING
 CALCULATIONS LEVEL 6
 UNITED FORMING CAST-IN-PLACE CONCRETE FRAMING & SHORING
 CALCULATIONS LEVEL 7 & CAPITAL DOME
 2ND LEVEL GAGARE POUR 1
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2007-07-06 Cont ID  
Sent By adarroug Date 2007-06-12 Time 11:10 Rev Time 1.55
Received By jwitmer Date 2007-07-06 Time 08:03 Sent To  
Notes
2007-07-06 08:05:04ROOF DOME, & BARREL ROOF SHOP DRAWINGS
2007-06-04 11:24:15TO "JWITMER" DESK/SUBMITTAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status F Date 2007-05-31 Cont ID  
Sent By jwitmer Date 2007-05-31 Time 15:35 Rev Time 0.55
Received By jwitmer Date 2007-05-31 Time 15:35 Sent To PC
Notes
2007-05-31 15:38:42BUILDING PROVISO: TRAINER GLASS HAS NOT SUBMITTED THE
 SITE SPECIFIC NOA FROM MIAMI-DADE FROM HURRICANE TEST
 LAB # 0062-0310-00.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2007-05-31 Cont ID  
Sent By jwitmer Date 2007-05-31 Time 15:33 Rev Time 3.33
Received By jwitmer Date 2007-05-31 Time 15:33 Sent To PC
Notes
2007-05-31 15:35:27REVISION NUMBER 8 REVIEWED WITH THE EXCEPTION OF
 REFLECTED CEILING PLANS, SEE ELECTRICAL COMMENT# 7
 ABOUT LIGHTING PLAN AND PHOTO-METRICS. MAY CHANGE WITH
 THIS REQUIREMENT NOT BEING MET.

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2007-05-07 Cont ID  
Sent By jwitmer Date 2007-05-07 Time 08:38 Rev Time 0.77
Received By jwitmer Date 2007-05-07 Time 08:38 Sent To PC
Notes
2007-05-07 08:56:54BUILDING PLAN REVIEW
 PERMIT: 06100574
 ADD: 401 CLEMATIS ST
 CONT: CATALFUMO CONSTRUCTION
 TEL: (561)307-4746
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE
 DESIGN PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 CALCULATIONS , POUR AND SHORING REPORTS 2 & 3 COPIES OF
 SIGNATURE NOT ORIGINALS, (2) COPIES WILL BE RETAINED TO
 FOWARD TO STATE ENGINEER'S BOARD.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2007-04-03 Cont ID  
Sent By jwitmer Date 2007-04-03 Time 09:54 Rev Time 1.11
Received By jwitmer Date 2007-04-03 Time 09:54 Sent To PC
Notes
2007-04-03 10:20:52BUILDING PLAN REVIEW
 PERMIT: 06100574
 ADD: 401 CLEMATIS ST
 CONT: CATALFUMO
 TEL: (561)307-4776
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION# 6REVIEW
 ACTION: DENIED
  
 1)ONE SET OF PLANS WILL BE RETAINED FOR POSSIBLE
 SUBMITTAL TO THE STATE. PLANS INDICATE REVISION# 6
 PRINTED ON 2-19-07 BUT THE DESIGNER OF RECORD SIGNED
 AND SEALED THEM ON 2-13-07, SIX DAYS BEFORE THEY WERE
 PRINTED. WHAT IS REALLY PECULIAR THAT BOTH THE
 ARCHITECT AND STRUCTURAL ENGINEER WOULD MAKE THE SAME
 MISTAKE.......
  
 ARCHITECT'S
 61G1-16.003 USE OF SEAL.
 THE PERSONAL SEAL, SIGNATURE AND DATE OF THE ARCHITECT
 OR INTERIOR DESIGNER SHALL APPEAR ON ALL ARCHITECTURAL
 OR INTERIOR DESIGN DOCUMENTS TO BE FILED FOR PUBLIC
 RECORD AND SHALL BE CONSTRUED TO OBLIGATE HIS PARTNERS
 OR HIS CORPORATION. A CORPORATE SEAL ALONE IS
 INSUFFICIENT. DOCUMENTS SHALL BE SIGNED PERSONALLY AND
 SEALED BY THE RESPONSIBLE ARCHITECT OR INTERIOR
 DESIGNER. FINAL OFFICIAL RECORD DOCUMENTS (NOT
 TRACINGS, ETC.) SHALL BE SO SIGNED. THE SIGNING AND
 SEALING OF THE SPECIFICATION INDEX SHEETS SHALL BE
 CONSIDERED ADEQUATE. ALL DRAWING SHEETS AND PAGES SHALL
 BE SO SIGNED AND SEALED. AN ARCHITECT OR INTERIOR
 DESIGNER SHALL NOT AFFIX, OR PERMIT TO BE AFFIXED, HIS
 SEAL OR NAME TO ANY PLAN, SPECIFICATIONS, DRAWINGS, OR
 OTHER RELATED DOCUMENT WHICH WAS NOT PREPARED BY HIM OR
 UNDER HIS RESPONSIBLE SUPERVISING CONTROL AS PROVIDED
 IN RULE CHAPTER 61G1-23, F.A.C. AN ARCHITECT OR
 INTERIOR DESIGNER SHALL NOT USE HIS SEAL OR DO ANY
 OTHER ACT AS AN ARCHITECT OR INTERIOR DESIGNER UNLESS
 HOLDING AT THE TIME A CERTIFICATE OF REGISTRATION AND
 ALL REQUIRED RENEWALS THEREOF.
 SPECIFIC AUTHORITY 481.2055, 481.221 FS. LAW
 IMPLEMENTED 481.221, 481.225(1)(E), (G), (J),
 481.2251(1)(G), (H), (I) FS. HISTORY?NEW 12-23-79,
 FORMERLY 21B-16.03, AMENDED 7-27-89, FORMERLY
 21B-16.003, AMENDED 11-21-94, 4-18-00.
  
 ENGINEER'S
 61G15-23.002 SEAL, SIGNATURE AND DATE SHALL BE
 AFFIXED.
 (1) A PROFESSIONAL ENGINEER SHALL SIGN HIS NAME AND
 AFFIX HIS SEAL TO ALL PLANS, SPECIFICATIONS, REPORTS,
 FINAL BID DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER?S REPRESENTATIVE, OR OTHER DOCUMENTS PREPARED OR
 ISSUED BY SAID REGISTRANT AND BEING FILED FOR PUBLIC
 RECORD. THE DATE THAT THE SIGNATURE AND SEAL IS AFFIXED
 AS PROVIDED HEREIN SHALL BE ENTERED ON SAID PLANS,
 SPECIFICATIONS, REPORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL ENGINEER. (2)
 EACH SHEET OF PLANS AND PRINTS WHICH MUST BE SEALED
 UNDER THE PROVISIONS OF CHAPTER 471, F.S., SHALL BE
 SEALED, SIGNED AND DATED BY THE PROFESSIONAL ENGINEER
 IN RESPONSIBLE CHARGE. ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER ON EACH SHEET.
 IF PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING
 BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME
 AND LICENSE NUMBER, AS WELL AS, THE NAME, ADDRESS, AND
 CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
 ENGINEERS WORKING FOR LOCAL, STATE OR FEDERAL
 GOVERNMENT AGENCIES SHALL LEGIBLY INDICATE THEIR NAME
 AND LICENSE NUMBER, AND MAY INDICATE THE NAME AND
 ADDRESS OF THE AGENCY. A COVER OR INDEX SHEET FOR
 ENGINEERING SPECIFICATIONS MAY BE USED AND THAT SHEET
 MUST BE SIGNED, SEALED AND DATED BY THOSE PROFESSIONAL
 ENGINEERS IN RESPONSIBLE CHARGE OF THE PRODUCTION AND
 PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX SO THAT THE USER WILL BE AWARE OF EACH
 PORTION OF THE SPECIFICATIONS FOR WHICH EACH
 PROFESSIONAL ENGINEER IS RESPONSIBLE. ENGINEERING
 REPORTS MUST BE SIGNED, SEALED AND DATED ON A SIGNATURE
 PAGE OR COVER LETTER BY EACH PROFESSIONAL ENGINEER WHO
 IS IN RESPONSIBLE CHARGE OF ANY PORTION OF THE REPORT.
 A PROFESSIONAL ENGINEER MAY ONLY SEAL AN ENGINEERING
 REPORT, PLAN, PRINT OR SPECIFICATION IF THAT
 PROFESSIONAL ENGINEER WAS IN RESPONSIBLE CHARGE OF THE
 PREPARATION AND PRODUCTION OF THE ENGINEERING DOCUMENT
 AND THE PROFESSIONAL ENGINEER HAS THE EXPERTISE IN THE
 ENGINEERING DISCIPLINE USED IN PRODUCING THE
 ENGINEERING DOCUMENT IN QUESTION.
 (3) A PROFESSIONAL ENGINEER SHOULD NOT SEAL ORIGINAL
 DOCUMENTS MADE OF MYLAR, LINEN, SEPIA OR OTHER
 MATERIALS WHICH CAN BE CHANGED BY THE ENTITY WITH WHOM
 SUCH DOCUMENT(S) ARE FILED UNLESS THE PROFESSIONAL
 ENGINEER ACCOMPANIES SUCH DOCUMENT(S) WITH A SIGNED AND
 SEALED LETTER MAKING THE RECEIVER AWARE THAT COPIES OF
 THE ORIGINAL DOCUMENT AS DESIGNED BY THE PROFESSIONAL
 ENGINEER HAVE BEEN RETAINED BY THE PROFESSIONAL
 ENGINEER AND THAT THE PROFESSIONAL ENGINEER WILL NOT BE
 RESPONSIBLE FOR ANY SUBSEQUENT CHANGES TO THE
 REPRODUCIBLE ORIGINAL DOCUMENTS.
 (4) A PROFESSIONAL ENGINEER SHOULD NOT SEAL PRELIMINARY
 PLANS WHICH ARE NOT INTENDED FOR PERMIT, CONSTRUCTION,
 OR BIDDING PURPOSES. IF A PERMITTING AGENCY REQUIRES
 THAT PRELIMINARY PLANS SUBMITTED FOR REVIEW PURPOSES BE
 SIGNED AND SEALED, THEN THE ENGINEER SHOULD CLEARLY
 NOTE SUCH LIMITATIONS ON THE FACE OF THE PLANS, BY
 USING TERMS SUCH AS ?PRELIMINARY,? ?FOR REVIEW ONLY,?
 ?NOT FOR CONSTRUCTION,? OR ANY OTHER SUITABLE STATEMENT
 WHICH DENOTES THAT THE DOCUMENTS ARE FOR DESIGN REVIEW
 ONLY AND ARE NOT INTENDED FOR PERMIT, CONSTRUCTION, OR
 BIDDING PURPOSES.
 (5) ENGINEERS WHO WISH TO SIGN AND SEAL ELECTRONICALLY
 TRANSMITTED PLANS, SPECIFICATIONS, REPORTS, FINAL BID
 DOCUMENTS, OR OTHER DOCUMENTS SHALL FOLLOW THE
 PROCEDURES SET FORTH IN RULE 61G15-23.003, F.A.C.
 SPECIFIC AUTHORITY 471.025 FS. LAW IMPLEMENTED 471.025
 FS. HISTORY?NEW 1-8-80, AMENDED 1-20-85, FORMERLY
 21H-23.02, AMENDED 5-14-86, FORMERLY 21H-23.002,
 AMENDED 11-15-94, 8-18-98, 2-3-00, 2-22-01, 2-5-04.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2007-03-28 Cont ID  
Sent By jwitmer Date 2007-03-28 Time 11:18 Rev Time 1.33
Received By jwitmer Date 2007-03-28 Time 11:17 Sent To B
Notes
2007-03-28 11:19:32SHORING & RESHORING PLANS REVISED 2/13/07

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2007-03-01 Cont ID  
Sent By jwitmer Date 2007-03-01 Time 08:58 Rev Time 1.11
Received By jwitmer Date 2007-03-01 Time 08:58 Sent To FIRE
Notes
2007-03-01 09:13:56BUILDING PLAN REVIEW
 PERMIT: 06100574
 ADD: 401 CLEMATIS ST
 CONT: CATALFUMO
 TEL: (561)282-8265
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2005 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION # 6REVIEW
 ACTION: DENIED
  
 SHEETS: A1-GA.1,
 A1-GA.2
 A1-GA.3
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) SHEETS A1-GA.1, A1-GA.2 & A1-GA.3,
 ALL SHOW EXHAUST FANS BUT THE HEIGTH ABOVE THE FINISH
 FLOOR SLAB HAS NOT BEEN PROVIDED OR A CUT SECTION
 THAT WOULD PROVIDE AT WHAT ELEVATION THE BOTTOM OF THE
 ENCLOSURE WILL BE ABOVE THE FINISH FLOOR SLAB.
 11-4.4.1 GENERAL.
 OBJECTS PROJECTING FROM WALLS (FOR EXAMPLE, TELEPHONES)
 WITH THEIR LEADING EDGES BETWEEN 27 INCHES AND 80
 INCHES (685 MM AND 2030 MM) ABOVE THE FINISHED FLOOR
 SHALL PROTRUDE NO MORE THAN 4 INCHES (102 MM) INTO
 WALKS, HALLS, CORRIDORS, PASSAGEWAYS, OR AISLES [SEE
 FIGURE 11-8 (A)]. OBJECTS MOUNTED WITH THEIR LEADING
 EDGES AT OR BELOW 27 INCHES (685 MM) ABOVE THE FINISHED
 FLOOR MAY PROTRUDE ANY AMOUNT [SEE FIGURE 11-8 (A) AND
 FIGURE 11-8 (B)]. FREE-STANDING OBJECTS MOUNTED ON
 POSTS OR PYLONS MAY OVERHANG 12 INCHES (305 MM) MAXIMUM
 FROM 27 INCHES TO 80 INCHES (685 MM TO 2030 MM) ABOVE
 THE GROUND OR FINISHED FLOOR [SEE FIGURE 11-8 (C) AND
 FIGURE 11-8 (D)]. PROTRUDING OBJECTS SHALL NOT REDUCE
 THE CLEAR WIDTH OF AN ACCESSIBLE ROUTE OR MANEUVERING
 SPACE [SEE FIGURE 11-8 (E)].
  
 11-4.4.2 HEADROOM.
 WALKS, HALLS, CORRIDORS, PASSAGEWAYS, AISLES, OR OTHER
 CIRCULATION SPACES SHALL HAVE 80 INCHES (2030 MM)
 MINIMUM CLEAR HEAD ROOM [SEE FIGURE 11-8 (A)]. IF
 VERTICAL CLEARANCE OF AN AREA ADJOINING AN ACCESSIBLE
 ROUTE IS REDUCED TO LESS THAN 80 INCHES (2032 MM)
 (NOMINAL DIMENSION), A BARRIER TO WARN BLIND OR
 VISUALLY-IMPAIRED PERSONS SHALL BE PROVIDED [SEE FIGURE
 11-8 (C-1)].
  
 3)PLEASE SEE ELECTRICAL COMMENTS FOR SHEET A1-GA.3
 CONCERNING THE LOCATION OF THE FENCE AND THE LOCATION
 OF GENERATOT TO GENERATOR ON THE ROOF TOP OF THE
 PARKING GARAGE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-03-01 Cont ID  
Sent By jwitmer Date 2007-03-01 Time 08:53 Rev Time 3.00
Received By jwitmer Date 2007-03-01 Time 08:53 Sent To FIRE
Notes
2007-03-01 08:58:21REV. # 6 DATED2/19/07 REVIEWED WITH THE EXCEPTION OF
 SHEETS A1-GA.1
 DURA-STRESS GARAGE SHOP DRAWINGS
  
 DURA-STRESS GARAGE DESIGN CALCULATIONS
  
 DURA-STRESS CONNECTION DETAILS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-02-20 Cont ID  
Sent By jwitmer Date 2007-02-20 Time 14:54 Rev Time 7.77
Received By jwitmer Date 2007-02-20 Time 10:17 Sent To  
Notes
2007-02-20 11:07:00 
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT# 06100574
 ADDRESS: 401 CLEMATIS ST
 CONT: CATALFUMO
 TELL # (561) 694-3000
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF PLANS. 106.1.1
 ADMINISTRATIVE CODE/ 06.
  
  
 BUILDING PROVISOS:
 1 ) 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 2 ) 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 3) SOUTH SIDE OF LIBRARY ROOF REQUIRES STAIR ACCESS AS
 PER
 FBC BUILDING 1009.12 ACCESS TO ROOF. THE PETITIONER
 SONG& ASSOCIATESHAS MADE APPLICATION FOR A VARIANCE
 TO
 THE TECHNICAL CODE, SECTION 1009.12 FBC BUILDING, TO
 EXCLUDE THE USE
 OF STAIRS TO GAINACCESS TO THE ROOF AND ALLOW USE OF
 A SHIPS LADDER
 TO GAIN ACCESS TO THE ROOF LEVEL.
  
 4) PRE-ENGINEERED ROOF ACCESS HATCHES: RULE 9B-72 /
 106.3.3 WEST PALM BEACH
 ADMINISTRATIVE CODE, BOTH OF THE MENTIONED ABOVE
 REQUIRE PRODUCT APPROVALS,
 SINCE THERE ARE NO PRODUCTS AVAILABLE THAT HAVE BEEN
 TESTED BY THE STATE THEBUILDING CODEADVISORY BOARD
 OF PALM BEACH COUNTY SENT A LETTER TO DCA ON THIS
 MATTER AND RECEIVED A DECLATORY STATEMENT FROM THE
 STATE (DEC04-DCA-161) THAT REQUIRES THE ENFORCEMENT OF
 THE STATE AND LOCAL PRODUCT APPROVALS. THIS WILL GIVE
 THE MANUFACTURERS TIME TO GET PRODUCTS TESTED AND ON
 THE MARKET. NO CERTIFICATE OF OCCUPANCY WILL BE ISSUED
 UNTIL PRODUCT TESTING FOR WIND LOADS ARE COMPLETED AND
 PRODUCT APPROVALS FOR PRE-ENGINEERED ROOF HATCHES ARE
 REVIEWED.
  
 5) TRAINER GLASS COMPANY WILL BE GIVEN 90 DAYS TO
 COMPLY WITH GLAZING REQUIREMENTS IN THE END ZONES, THEY
 ARE TO RECEIVE A ONE TIME SITE SPECIFIC NOA FROM
 MIAMI-DADE FOR CITY HALL FROM THE HURRICANE TEST LAB
 REPROT # 0062-0310-00.
  
 6) ENGINEERED SHOP DRWINGS FOR THE DOME & BARRELBY
 TRIODETICSPACE FRAMES INC. SHALL BE REVIEWED BY THE
 DESIGNER OF RECORD
 BEFORE SUBMITTED TO THE BUILDING DEPARTMENT.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-01-30 Cont ID  
Sent By jwitmer Date 2007-01-30 Time 07:08 Rev Time 10.25
Received By jwitmer Date 2007-01-30 Time 07:08 Sent To  
Notes
2007-01-30 07:12:29WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 06100574
 401 CLEMATIS ST.
 SIXTH REVIEW JAN. 27/07
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: MEINHART CONSULTING ENGINEERS
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*)MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 1) --- VERY IMPORTANT
 STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2-13 COMPLIED.
  
 14) 6TH REQUEST, IN REVIEWING THIS PLAN IT APPEARS THAT
 THERE ARE VARIOUS DOORS THAT DO NOT MEET THE
 REQUIREMENTS OF:11-4.13.6 MANEUVERING CLEARENCES AT
 DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS THAT ARE
 NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH IN THE REQUIRED
 CLEARANCES SHALL BE CLEAR & LEVEL.
 SEE LIST OF DOORS:A1-302A. PLEASE CLOUD OR DELTA THESE
 CHANGES.
  
 THE DESIGN TEAM DID ATTEMPT TO MAKE THE CORRECTION,
 WITH A 1?-2? SIDE CLEARANCE,
 FOR THE LATCH SIDE OF THE DOOR A 1?-6? CLEARANCE IS
 REQUIRED. SEE FIGURE 25(A) PULL SIDE OF DOOR.
  
 15 ? 31)
  
 32A) 4TH REQUEST, THE DOOR SCHEDULE NEEDS RATINGS FOR
 SMOKEAND FIRE RATINGS DEPENDING ON FORTH COMING
 DOCUMENTATION FROM SONG & ASSOCIATES.
 RESPONSE WAS SEE 45A & B BELOW.
 32A)(1)THIS COMMENT HAD TO DO WITH VERTICAL EXIT
 ENCLOSURES ORIGINALLY OR 2 HR RATED ASSEMBLIES. IN
 CHECKING THE STAIRWELLS BEING 2 HR RATED SHAFTSTHE
 ELEVATOR SHAFTS ARE ALSO 2HR RATED ASSEMBLIES. THE
 ELEVATOR MACHINE ROOM DOOR A6102A FOR ELEVATORS
 1-3 WILL REQUIRE 1 ? HR OPENING PROTECTIVE 707.4, ALSO
 NOTE AUTOMATIC DOOR CLOSER.
  
 32A)(2)THE SECOND ISSUE IS THE STAIRWELL # 5 IN THE
 GARAGE. DEPENDING ON WHICH SHEET DEPICTED
 STAIRWELL # 5 IS DEPICTED OR NOT:
 SHEET A1-6.0STAIRWELL# 5 IS NOT SHOWN
 SHEET A2-0STAIRWELL# 5 IS SHOWN
 SHEET A3-GA3 STAIRWELL# 5 IS NOT SHOWN
 SEE TABLE 1018.2
 1018.1.1 OPEN PARKING STRUCTURES.
 PARKING STRUCTURES SHALL NOT HAVE LESS THAN TWO EXITS
 FROM EACH PARKING TIER, EXCEPT THAT ONLY ONE EXIT IS
 REQUIRED WHERE VEHICLES ARE MECHANICALLY PARKED.
 UNENCLOSED VEHICLE RAMPS SHALL NOT BE CONSIDERED AS
 REQUIRED EXITS UNLESS PEDESTRIAN FACILITIES ARE
 PROVIDED.
  
 32A)(3) RATED DOORS WITH GLASS,SIDE LIGHTS OR GLASS
 VIEW PANELS IN RATED PARTITIONS.
  
 A1-301A ** SIDE LIGHT
 A1-306A ** SIDE LIGHT
 A1-013A**GLASS
 A1-017A**GLASS
 A1-701A **WOOD/ GLASS
 A2-301-A**SIDE LIGHT
 A2-008A **SIDE LIGHT
  
 ** THESE DOORS ARE PART OF AN EGRESS ENCLOSURE OF AN
 ATRIUM.
 PLEASE INDICATE COMPLIANCE WITH 404.5
 SHEET FP1.0/ FP2.0 FIRE SPRINKLER SHEETS DO NOT MEET
 THE REQUIREMENTS FOR 404.5 EXCEPTION# 1 AS SHOWN.
  
 GLASS DOORS PROVIDE ADDITIONAL INFORMATION AS TO FIRE
 RATING 715.3, 715.3.4.1& TABLE 715.4.3.
  
 32A)(4) SHEET A1-1.2DOOR C1-009A, D1-003 & D1-301 ARE
 COMPOSED OF AL/GL WITH SIDE LIGHTS INDICATE COMPLIANCE
 WITH :
 715.3.3 DOOR ASSEMBLIES IN CORRIDORS AND SMOKE
 BARRIERS.
 FIRE DOOR ASSEMBLIES REQUIRED TO HAVE A MINIMUM FIRE
 PROTECTION RATING OF 20 MINUTES WHERE LOCATED IN
 CORRIDOR WALLS OR SMOKE BARRIER WALLS HAVING A
 FIRE-RESISTANCE RATING IN ACCORDANCE WITH TABLE 715.3
 SHALL BE TESTED IN ACCORDANCE WITH NFPA 252 OR UL 10C
 WITHOUT THE HOSE STREAM TEST. IF A 20-MINUTE FIRE DOOR
 ASSEMBLY CONTAINS GLAZING MATERIAL, THE GLAZING
 MATERIAL IN THE DOOR ITSELF SHALL HAVE A MINIMUM FIRE
 PROTECTION RATING OF 20 MINUTES AND BE EXEMPT FROM THE
 HOSE STREAM TEST. GLAZING MATERIAL IN ANY OTHER PART OF
 THE DOOR ASSEMBLY, INCLUDING TRANSOM LITES AND
 SIDELITES, SHALL BE TESTED IN ACCORDANCE WITH NFPA 257,
 INCLUDING THE HOSE STREAM TEST, IN ACCORDANCE WITH
 SECTION 715.4 . FIRE DOOR ASSEMBLIES SHALL ALSO MEET
 THE REQUIREMENTS FOR A SMOKE- AND DRAFT-CONTROL DOOR
 ASSEMBLY TESTED IN ACCORDANCE WITH UL 1784 WITH AN
 ARTIFICIAL BOTTOM SEAL INSTALLED ACROSS THE FULL WIDTH
 OF THE BOTTOM OF THE DOOR ASSEMBLY. THE AIR LEAKAGE
 RATE OF THE DOOR ASSEMBLY SHALL NOT EXCEED 3.0 CFM PER
 SQUARE FOOT (0.01524 M 3 /S ? M 2 ) OF DOOR OPENING AT
 0.10 INCH (24.9 PA) OF WATER FOR BOTH THE AMBIENT
 TEMPERATURE AND ELEVATED TEMPERATURE & ELEVATED
 TEMPERATURE TESTS. LOUVERS ARE PROHIBITED.
  
  
  
  
 32A)(5) SHEET A1-3.2DOOR C3-401A IS A WOOD & GLASS DOOR
 WITH GLASS SIDE LIGHTS, PLEASE PROVIDE INFORMATION FOR
 OPENING PROTECTIVE FOR A 1 HR RATED WALL TABLE 1016.1.,
 TABLE 715.3, 715.3.4.1, 715.3.3 & 715.4 .
  
 32A)(6)SHEET A1-3.2DOOR C3-201A IS A WOOD & GLASS
 DOOR WITH GLASS SIDE LIGHTS, PLEASE PROVIDE INFORMATION
 FOR OPENING PROTECTIVE FOR A 2 HR RATED WALL.
 TABLE 1016.1, TABLE 715.3, 715.3.3, 715.3.4.1& 715.4.
  
 32B) ? 38B) COMPLIED.
  
 38C) THIS COMMENT WAS REDIRECTED UNDER 32A)(5) .
  
 39- 63) COMPLIED.
  
 64) TO BE RE-ADDRESSED, HAD COMPLIED: SEE COMMENT
 32A)(2).
  
 65) COMPLIED.
  
 66) TO BE RE-ADDRESSED UNDER COMMENT32A)(5).
  
 67- 77) COMPLIED.
  
 78-81) 2ND REQUEST,
 FL BLD CODE 1609.1.4
 : COMPONENTS & CLADDING, PROVIDE 2 COPIES (3 IF
 THRESHOLD OR RESIDENT INSPECTOR) OF PRODUCT TESTING
 REPORTS.
  
 PLEASE PROVIDE (3) SIGNED & SEALED LETTERS FROM RWDI
 TESTING LABS CONFIRMING THE STRUCTURAL COMPLIANCE OF
 WIND-LOADING CHARACTERISTICS. THE DESIGN TEAMS RESPONSE
  
 INDICATES COMPREHENSIVE WIND-LOADING CALCULATIONS AND
 DIAGRAMS HAVE BEEN PROVIDED. TO DATE ONLY DIAGRAMS
 SUBMITTED ARE SHEETS S0-3.0 & S0.40 AND NO WIND
 CALCULATIONS HAVE BEEN SUBMITTED AS TO DATE.
  
 A) THE TUNNELING EFFECT WIND WILL HAVE BETWEEN THE
 PORTION OF CITY HALL GARAGE AND THE EAST END OF THE
 BUILDING THAT IS 5 STORIES TALL WITH THE DOME.THERE
 IS NO ELEVATIONS INDICATING WHAT POSITIVE AND NEGATIVE
 PRESSURES WILL OCCUR IN THIS AREA.
 THE SECOND CONCERN IS THE INCREASED TUNNELING EFFECT
 WILL OCCUR WITH THE
 THE ENCLOSING OF THE GARAGE, TO BE AN ENCLOSED GARAGE.
  
  
 B) THE SECOND AREA THAT IS NOT SHOWN IS THE PORTION OF
 THE BUILDING THAT JOINS
 THE LIBRARY TO THE 5 STORY SECTION OF THE
 STRUCTURE. THIS AREA HAS A SERIES OF
 STEPPED ROOFS CREATING A SAW TOOTHED EFFECT
 WHICH WILL CREATE A SERIES OF
 VORTEX ZONES AS THE WIND RUSHES OVER THE SERIES
 OF STEPPED PARAPETS, AGAIN
 THE PLANS DO NOT ADDRESS THESE AREAS FOR THE
 PRESSURE ZONES OR THE
 POSITIVE AND NEGATIVE PRESSURES FOR THESE AREAS.
  
  
 SHEET S0-4.0 ROOF PRESSURES INDICATE A -70 FOR
 THESE SAME ROOF TOP AREA, WHY WOULDN?T THE SAME
 NEGATIVE PRESSURES OCCUR WHERE THE WIND WOULD BE
 FLOWING ON A 45 DEGREE ANGLE. THE WIND WILL SWIRL IN A
 VORTEX FASHION IN THESE AREAS.
  
 C) THE THIRD ITEM OF CONCERN IS THE SHOP DRAWING
 CREATED BY TRAINER GLASS INDICATING THE DIFFERENT
 WINDOW TYPES AND THEIR USE IN THE STRUCTURE AND
 ASSOCIATED WIND ZONES. THE DRAWING NEEDS TO REFLECT THE
 SAME END ZONES AS SHEET S0-3.0 & S0-4.0. THIS SHEET
 WILL ALSO BE USED BY THE THRESHOLD INSPECTOR TO
 IDENTIFY WHICH TYPE OF WINDOW (SPECIFY NOA) WILL BE
 USED IN EACH OF THE COLOR CODED AREAS.
 106.1.2* ADDITIONAL INFORMATION REQUIRED, PLEASE
 PROVIDE THE DESIGNER OF THIS DOCUMENT, PLEASE PRINT
 NAME AND TELEPHONE NUMBER FOR CONTACT INFORMATION.
 THE THIRD ISSUE WITH THIS DOCUMENT IS THAT THE
 STRUCTURAL ENGINEER HAD NEVER REVIEWED THIS DOCUMENT ,
 NO SHOP DRAWING STAMP OF APPROVAL OR REVIEW.
  
 D) 78A & B) AS INTERIOR ZONES AND NO MENTION OF
 POSSIBLE HIGHER PRESSURE, NOR HAS THIS DOCUMENT BEEN
 SUBMITTED TO THE STRUCTURAL ENGINEER FOR REVIEW OR
 APPROVAL.
  
 E)IN THE (3) BINDERS FOR THE (BUILDING
 ENVELOPE) SUBMITTED PRODUCT APPROVALS THERE ARE
 MULTIPLE REPORTS FOR THE SAME REPORT, MISMATCHED
 REPORTS, PLEASE CORRECT SO FOR EACH CATEGORY OF WINDOWS
 AND DOORS THERE IS ONLY ONE REPORT SO AS TO NOT CONFUSE
 THE ISSUE AT HAND.
  
 PRODUCT APPROVALS:
 UNITED STATES ALUM CORP EXTERIOR SWING DOOR-PRESSURE-
 OK
 STANLEY ACCESS TECH AUTO SLIDE FL 6249.9 LOW PRESSURE
 U S DOOR 651-37 ROLL UP DOOR,THIS DOOR IS NOT IN THE
 DOOR SCHEDULE SIZE, WHERE IS THE TEST REPORT# USD-05-2.
 IS THIS TO BE USED? ALSO SUBMITTED IS A BEST ROLLING
 DOOR REPORT.
 BEST ROLLING DOOR FL 7760 PRESSURE- OK
 INGERSOL-RAND IR SERIES W/ IR LOCK- IMPACT ONLY FOR
 ZONE 4-OK +/- 75
 INGERSOL-RANDH-16-4 OUTSWING W/ PANIC LMIR ONLY ZONE
 4- OK +/- 70
 **NO** HOLLOW METAL OUTSWING DOOR APPROVALS FOR ZONE 5
 FIRESTONE OUTSWING LOUVER DOOR LMIR ONLY ZONE 4 OK +/-
 75
 AMERICAN WARMING & VENTILATION- WALL LOUVERS LIMITATION
 96?X180? +/- 150
 BILCO ROOF HATCH- REQUIRES STATE APPROVAL OR MIAMI-DADE
 APPROVAL.
 AT THIS TIME THERE IS NO SUCH APPROVALS WILL REQUIRE
 SITE SPECIFIC ENGINEERING, BUILDING OFFICIAL TO RULE ON
 IF 3RD PARTY QUALITY INSURANCE PROGRAM TO BE IN
 AFFECT.
 PALM BEACH COUNTY BCAB HAS NOT RULED ON THIS MATTER AS
 OF YET.
  
 TRAINER GLASS CURTAIN WALL TCW250 TS
 FL6198.7/05-0624.07 WEST ELEVATION CAN?T MAKE PRESSURES
 , MULLIONS NOT HIGH LIGHTED NOR IS THE TYPE OF GLASS.
  
 TRAINER GLASS FIXED TCW 250P. L/SMI FL
 6198.4/05-0624.04 OK FOR ZONE 4 ONLY
  
 TRAINER GLASS FIXED TCW250P SMI FL 6198.5/05-0624.05
 +/-80 TRAINER PLAN INDICATES THE USE OF THIS WINDOW IN
 ZONE FIVE AREAS- LOW PRESSURES IF USED IN ZONE 5.
  
 TRAINER GLASS CURTAIN WALL/SMI +/-80 TRAINER PLAN
 INDICATES USE IN ZONE 5, ALSO NEEDS MULLIONS AND TYPE
 OF GLAZING TO BE HIGHLIGHTED.
  
 TRAINER GLASS CURTAIN WALL/LMI HIGHLIGHT WHICH MULLIONS
 & GLAZING SHALL BE USED
  
 NO REPORT FROM HURRICANE TEST LABS, TEST
 0062.0310.00???????????
  
 JOHN MANSFIELD MODIFIED BITUMEN ROOFING SYSTEM &
 ENHANCED FASTENING SYSTEM-OK
  
 NO REPORT FOR TRIODETIC SPACE FRAMES FOR THE DOME NOR
 BARREL ROOF FRAMING ASSEMBLY. TO DATE NO INFORMATION
 HAS BEEN SUBMITTED FOR REVIEW, NO DESIGN CRITERIA.
  
 82-84) COMPLIED.
  
 NEW COMMENTS,
 85) ROOF HATCH COVERS,1009.12 ACCESS TO ROOF.
 BUILDINGS FOUR STORIES OR MORE IN HEIGHT, EXCEPT THOSE
 WITH A ROOF SLOPE GREATER THAN 4:12, SHALL BE PROVIDED
 WITH A STAIRWAY TO THE ROOF. SUCH STAIRWAY SHALL BE
 MARKED AT STREET AND FLOOR LEVELS WITH A SIGN
 INDICATING THAT IT CONTINUES TO THE ROOF. WHERE ROOFS
 ARE USED FOR ROOF GARDENS OR FOR OTHER PURPOSES,
 STAIRWAYS SHALL BE PROVIDED AS REQUIRED FOR SUCH USE OR
 OCCUPANCY.
  
 86)SHEET A1-5.0 STAIR# 8 IN THE LIBRARY PROVIDES ROOF
 ACCESS TO THE LIBRARY ROOF NORTH OF THE BARREL SECTION,
 PLANS INDICATE THE USE OF A ROOF HATCH TO THE SOUTH
 SIDE OF THE BARREL ROOF PLEASE CORRECT, SEE COMMENT#
 85.
  
 87)PLEASE PROVIDE INFORMATION ON THE BARREL ROOF
 PORTION OF THE LIBRARY ROOF, SO THE ENERGY CALCULATIONS
 CAN BE VERIFIED. BUILDING HAS NOT BEGUN TO REVIEW
 ENERGY FORM COMPLIANCE UNTIL ALL OF THE UNKNOWNS ARE
 VERIFIED, THEN WE WILL BE ABLE VERIFY THE INFORMATION
 SUBMITTED. NOTE THE BARREL IS PART OF THE AIR
 CONDITIONED SPACE.
 13-400.0.ABC COMPLIANCE CRITERIA.
 COMMERCIAL BUILDINGS DEMONSTRATING COMPLIANCE WITH THIS
 CODE BY METHODS A OR B SHALL MEET ALL OF THE CRITERIA
 GIVEN IN THE TEXT AS SPECIFIC TO THE CHOSEN METHOD OF
 COMPLIANCE FOR 1 THROUGH 4 BELOW. COMMERCIAL BUILDINGS
 UTILIZING METHOD C FOR CODE COMPLIANCE SHALL MEET ALL
 CRITERIA SPECIFIED FOR METHOD C FOR 1, 3 AND 4 BELOW.
 1.PRESCRIPTIVE REQUIREMENTS.
 2.PERFORMANCE CALCULATION PROCEDURE.
 3.CERTIFICATION OF COMPLIANCE.
 4.REPORTING.
  
 88) A1-6.1 PARTIAL FLOOR PLAN OF THE MECHANICAL
 PENTHOUSE.
  
 88A) THE FLOOR PLAN INDICATES THE DOORS A6-101 A&B BOTH
 WERE PAIRS OF DOORS, REVISION TO SINGLE OUT SWING
 DOORS. THE ELEVATION NOR THE SECTIONS HAVE BEEN UPDATED
 TO REFLECT THE CHANGE. 106.1.2. ADD INFO REQUIRED.
  
 88B) SECTION 2/A5.04 IS MISSING STAIR# 13 TO THE DOME.
 DETAIL# 10 INDICATES THE LOCATION OF STAIR# 13 IN
 REGARDS TO THE COLUMN B-5 AND THE 24?X42? BEAM TO
 COLUMN B6. WHEN THIS BEAM IS SUPERIMPOSED ON TO DETAIL#
 10/ A7.1.6/ S1-8.0 THE STAIR IS NOT ACCESSIBLE. PLEASE
 CORRECT.
  
 88C) DOME: THE DOME INDICATE AN OPEN STAIRWAY# 13 THAT
 LEADS TO THE 7TH FLOOR,
 1509.5.1 NONCOMBUSTIBLE CONSTRUCTION REQUIRED.
 ANY TOWER, SPIRE, DOME OR CUPOLA THAT EXCEEDS 60 FEET
 (18 288) IN HEIGHT ABOVE THE HIGHEST POINT AT WHICH IT
 COMES IN CONTACT WITH THE ROOF, OR THAT EXCEEDS 200
 SQUARE FEET (18.6 M 2 ) IN AREA AT ANY HORIZONTAL
 SECTION, OR WHICH IS INTENDED TO BE USED FOR ANY
 PURPOSE OTHER THAN A BELFRY OR ARCHITECTURAL
 EMBELLISHMENT, SHALL BE ENTIRELY CONSTRUCTED OF AND
 SUPPORTED BY NONCOMBUSTIBLE MATERIALS. SUCH STRUCTURES
 SHALL BE SEPARATED FROM THE BUILDING BELOW BY
 CONSTRUCTION HAVING A FIRE-RESISTANCE RATING OF NOT
 LESS THAN 1.5 HOURS WITH OPENINGS PROTECTED WITH A
 MINIMUM 1.5-HOUR FIRE-PROTECTION RATING. STRUCTURES,
 EXCEPT AERIAL SUPPORTS 12 FEET (3658 MM) HIGH OR LESS,
 FLAGPOLES, WATER TANKS AND COOLING TOWERS, PLACED ABOVE
 THE ROOF OF ANY BUILDING MORE THAN 50 FEET (15 240 MM)
 IN HEIGHT, SHALL BE OF NONCOMBUSTIBLE MATERIAL AND
 SHALL BE SUPPORTED BY CONSTRUCTION OF NONCOMBUSTIBLE
 MATERIAL.
  
 88D) THE PLANS FOR THE DOME END IN COMPLETENESS AT
 ELEVATION 192?-6? WITH THE 7TH FLOOR SLAB, SHEET S1.8.0
 INDICATES A BEAM AT ELEVATION 212?-6? AND THE
 SUPPORTING COLUMNS BUT NO INFORMATION ON THE EXTERIOR
 WALL SECTIONS OR THE ATTACHMENT OF THE DOME. IN REGARDS
 TO THE DOME ITSELF NO STRUCTURAL PLANS HAVE BEEN
 SUBMITTED FOR
 REVIEW.
  
 88E)BARREL S1-8.0 INDICATES IN SECTION # 3 THE EMBEDS
 THAT THE BARREL WILL ATTACH
 TO, THE PLANS LACK INFORMATION AS TO THE FREQUENCY OF
 EMBEDS. 106.1.2* ADD INFO.
  
 WITH NEW INFORMATION SUBMITTED IN THE NEXT REVIEW
 ADDITIONAL COMMENTS MAY OCCUR.
  
 JIM WITMER
 BUILDING PLAN REVIEW
 CONSTRUCTION SERVICES DEPARTMENT
 WEST PALM BEACH, FL
 TEL;(561)805-6715
 FAX; (561)805-6731
 E-MAIL; [email protected]
  
  
 CITY HALL CENTER6TH REVIEW.DOC

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-12-26 Cont ID  
Sent By jwitmer Date 2006-12-26 Time 09:16 Rev Time 32.00
Received By jwitmer Date 2006-12-26 Time 09:16 Sent To  
Notes
2006-12-26 09:17:31WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 06100574
 401 CLEMATIS ST.
 FIFTH REVIEW DEC. 23/06
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: MEINHART CONSULTING ENGINEERS
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*)MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 1) --- VERY IMPORTANT
 STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)COMPLIED.
  
 3A)CIVIL ENGINEERS: CRAVEN THOMPSON & ASSOCIATES,
 INC. IS MISSING THEIR CERTIFICATE OF AUTHORIZATION.
 471.023 F.S.CERTIFICATE OF AUTHORIZATION.THE TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD
 THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
  
 4) COMPLIED.
  
 5) COMPLIED.
  
 6) COMPLIED.
  
 7) COMPLIED.
 PAGE 1
  
 8)FIFTH REQUEST, THORNTON TOMASETTI HAS ATTEMPTED TO
 COMPLY WITH THIS REQUIREMENT BY SUPPLYING A COVERSHEET
 WITH THEIR SHOP DRAWING STAMP AND SIGNATURE BUTTHIS
 DOCUMENT DOESN?T INDICATE WHAT PRODUCT APPROVAL
 DOCUMENT IS REVIEWED AND APPROVED.
 WPB ADMIN CODE 106.3* PRODUCT APPROVALS.THOSE
 PRODUCTS WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
  
 9) COMPLIED.
  
 10) IN REVIEWING THE THRESHOLD INSPECTION PLAN,THERE
 IS NO COMMENT ON REQUIREMENTS FOR SHORING AND RESHORING
 SHOP DRAWINGS AND INSPECTIONS FORFLOOR SLABS ABOVE
 GRADE.
  
 FL S. S. 553.71(7) ?THRESHOLD BUILDING" MEANING ANY
 BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000
 SQ FT IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN
 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM
 STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING PURSUANT
 TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION
 PLAN MUST BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO
 THE ISSUANCE OF A
 BUILDINGS PERMIT FOR THE CONSTRUCTION OF A THRESHOLD
 BUILDING. THE PURPOSE OF THE
 STRUCTURAL INSPECTION PLAN IS TO PROVIDE SPECIFIC
 INSPECTION PROCEDURES AND
 SCHEDULES SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH
 THE PERMITTED DOCUMENTS.
  
 11) 3RD REQUEST, RESPONSE SHEET INDICATES THE SPECIAL
 INSPECTOR FORMS TO BE PART OF THE SUBMITTALS, WHERE?
 WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY S. 553.79(5) FLORIDA STATUTES
 TO THE MINIMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561) 805-6711 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
 SEE ATTACHED GUIDELINE.
  
 12) COMPLIED.
  
 13) COMPLIED.
  
 14)5TH REQUEST, IN REVIEWING THIS PLAN IT APPEARS
 THAT THERE ARE VARIOUS DOORS THAT DO NOT MEET THE
 REQUIREMENTS OF:11-4.13.6 MANEUVERING CLEARENCES AT
 DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS THAT ARE
 NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH IN THE REQUIRED
 CLEARANCES SHALL BE CLEAR & LEVEL.
 SEE LIST OF DOORS:A1-302A. PLEASE CLOUD OR DELTA THESE
 CHANGES.
 PAGE2
  
 15)COMPLIED.
  
 16) COMPLIED.
  
 17) COMPLIED.
  
 18) COMPLIED.
  
 19) COMPLIED.
  
 20) COMPLIED.
  
 21) COMPLIED.
  
 22) COMPLIED.
  
 23) COMPLIED.
  
 24) COMPLIED.
  
 25) COMPLIED C-10.
  
 26) COMPLIED.
  
 27) COMPLIED.
  
 28) COMPLIED.
  
 29) COMPLIED.
  
 30) COMPLIED.
  
 32A) 3RD REQUEST, THE DOOR SCHEDULE NEEDS RATINGS FOR
 SMOKEAND FIRE RATINGS DEPENDING ON FORTH COMING
 DOCUMENTATION FROM SONG & ASSOCIATES.
  
 32B) 2ND REQUEST, THE LIFE SAFETY PLAN AND THE ?A?
 SHEETS DO NOT MATCH UP FOR SMOKE AND FIRE RATINGS OF
 ALL ELECTRICAL ROOMS, STORAGE ROOMS, MECHANICAL ROOMS
 AND ELEVATOR MECHANICAL ROOMS. THE ?A? SHEETS ARE
 MISSING THE WALL DESIGNATIONS FOR EITHER SMOKE ORHR
 RATINGS.
  
 33) COMPLIED.
  
 34) COMPLIED.
  
 35) COMPLIED.
 PAGE 3
 36) COMPLIED.
  
 37) COMPLIED.
  
 38A) EMPLOYEE LOUNGE, MET WITH TOM KASTNER12-21-06
 ABOUT THE EMPLOYEE LOUNGE,
 SONG & ASSOCIATES FOR A NET SQ FOOTAGE WERE
 TAKING OUT CABINET SQ FT FOR NET NOT
 WALL TO WALL. SONG & ASSOCIATES WILL CORRECT TO
 REDUCE THE OCCUPANT LOAD TO LESS THAN 50.
  
 38B) FOURTH FLOOR TRAINING ROOM, I RECEIVED A LETTER
 FROM WILLIAM SWISHER THAT SATES:
 1) FIXED SEATING NOT TO EXCEED 49 STATIONS. 2) OCCUPANT
 LOAD TO BE POSTED IN THE ROOM 49 PERSONS 3) ROOM IS NOT
 TO BE ALTERED TO ALLOW GREATER THAN 49 PERSONS.
  
 38C) LS1-3.2 & A1-3.2 BOTH SHEETS ARE MISSING THE 1 HR
 RATED CORRIDOR WALL BETWEEN
 THE ASSEMBLY AND BUSINESS OCCUPANCIES. TABLE 1016.1.
  
 39) COMPLIED.
  
 40) COMPLIED.
  
 41) COMPLIED.
  
 42) COMPLIED.
  
 43) COMPLIED.
  
 44) COMPLIED.
  
 45A)SHEET LS0.0 CODE SUMMARY- FIRE RESISTANCE RATINGS
 FOR SEPARATIONS,
 THIS SHEET IDENTIFIES NUMEROUS CODE SECTIONS SIGHTING
 NFPA OR FBC BUT IN THE DOOR SCHEDULE THE DOORS ARE NOT
 RATED, ELECTRIC ROOM DOOR B1-111A,
 MECHANICAL ROOM DOOR B1-102A. T-1016/ 708.3/ T-302.1.1
 & NFPA.
  
 45B) THE ABOVE LISTED MISSING DOOR RATINGS THE
 CORRELATING MISSING WALL RATINGS ARE THE MECHANICAL
 ROOM B1-102 & THE NEW ELECTRIC ROOM B1-111, NOTE THE
 NEW ELECTRIC ROOM IS MISSING ? OF THE WALL DESIGNATION,
 SHEET
 A1-GA.1.
  
 46) COMPLIED.
  
 47) COMPLIED.
  
 48) COMPLIED.
  
 PAGE 4
 49) COMPLIED.
  
 50) COMPLIED.
  
 51) COMPLIED.
  
 52) COMPLIED.
  
 53) COMPLIED.
  
 54) COMPLIED.
  
 55) COMPLIED.
  
 56) COMPLIED.
  
 57) COMPLIED.
  
 58) COMPLIED.
  
 59) COMPLIED.
  
 60) COMPLIED.
  
 61) COMPLIED.
  
 62) COMPLIED.
  
 63) COMPLIED.
  
 64) COMPLIED.
  
 65) COMPLIED.
  
 66) (SAME AS 38C), MISSING CORRIDOR RATING BETWEEN
 BUSINESS AND ASSEMBLY OCCUPANCY TABLE 1016.
  
 67) COMPLIED.
  
 68)COMPLIED.
  
 69) COMPLIED.
  
 70) COMPLIED.
  
 PAGE 5
  
 71) COMPLIED.
  
 72) COMPLIED.
  
 73) COMPLIED.
  
 74) COMPLIED.
  
 75) COMPLIED.
  
 76) COMPLIED.
  
 77) COMPLIED.
  
 NOTE ITEMS 78- 81 FIRST REVIEW!!!!
  
 78)FL BLD CODE 1609.1.4
 : COMPONENTS & CLADDING, PROVIDE 2 COPIES (3 IF
 THRESHOLD OR RESIDENT INSPECTOR) OF PRODUCT TESTING
 REPORTS.
  
 BEFORE THE SUBMITTED REPORTS CAN BE FULLY REVIEWED
 THERE ARE CONCERNS ABOUT WIND PRESSURES, CONCERNING
 ELEVATIONS NOT SHOWN IN THE STRUCTURAL SHEETS.
  
 A) THE TUNNELING EFFECT WIND WILL HAVE BETWEEN THE
 PORTION OF CITY HALL GARAGE AND THE EAST END OF THE
 BUILDING THAT IS 5 STORIES TALL WITH THE DOME.THERE
 IS NO ELEVATIONS INDICATING WHAT POSITIVE AND NEGATIVE
 PRESSURES WILL OCCUR IN THIS AREA.
 THE SECOND CONCERN IS THE INCREASED TUNNELING EFFECT
 WILL OCCUR WITH THE
 THE ENCLOSING OF THE GARAGE, TO BE AN ENCLOSED GARAGE.
  
  
 B) THE SECOND AREA THAT IS NOT SHOWN IS THE PORTION OF
 THE BUILDING THAT JOINS
 THE LIBRARY TO THE 5 STORY SECTION OF THE
 STRUCTURE. THIS AREA HAS A SERIES OF
 STEPPED ROOFS CREATING A SAW TOOTHED EFFECT
 WHICH WILL CREATE A SERIES OF
 VORTEX ZONES AS THE WIND RUSHES OVER THE SERIES
 OF STEPPED PARAPETS, AGAIN
 THE PLANS DO NOT ADDRESS THESE AREAS FOR THE
 PRESSURE ZONES OR THE
 POSITIVE AND NEGATIVE PRESSURES FOR THESE
 AREAS.
  
  
 C) THE THIRD ITEM OF CONCERN IS THE SHOP DRAWINGS
 CREATED BY TRAINER GLASS INDICATING THE DIFFERENT
 WINDOW TYPES AND THEIR USE IN THE STRUCTURE AND
 ASSOCIATED WIND ZONES. THEY HAVE INDICATED THE AREAS OF
 CONCERN
 (78 A& B).
 D) AS INTERIOR ZONES AND NO MENTION OF POSSIBLE HIGHER
 PRESSURE, NOR HAS THIS DOCUMENT BEEN SUBMITTED TO THE
 STRUCTURAL ENGINEER FOR REVIEW OR APPROVAL.
  
  
 PAGE 6
  
  
 REPORTS ARE AS FOLLOWS:
 A) FIXED WINDOWS-
 B) OPERABLE WINDOWS
 C) MULLIONS NOT COVERED BY NOA THE REPORTS FOR THE
 CURTAIN WALL SYSTEM HAVE A LIMITATION OF 171? ON THE
 MULLIONS.
 D) GLAZED DOORS, AUTOMATIC SLIDERS, SWING DOORS OR
 PRE-ENGINEERED ROOF ACCESS HATCHES- THIS IS A PRODUCT
 THAT IS REGULATED BY FLORIDA STATUTE RULE 9B-72- AT
 THIS TIME IT APPEARS THERE IS NO PRODUCT THAT IS TESTED
 THROUGH THE STATE OR THROUGH MIAMI-DADE?S NOA. THIS HAS
 BEEN BROUGHT UP BY BUILDING OFFICIAL AT THE PALM BEACH
 COUNTY BCAB BOARD IN NOVEMBER / 06 TO SEE HOW OTHER
 JURISDICTIONS WERE HANDLING THIS ISSUE FURTHER
 DISCUSSION TO BE ON THE JANUARY BOARD AGENDA.
  
 E) EXTERIOR METAL DOORS IF SINGLE OR PAIRS- COVERED
 UNDER COMMENT# 81.
 F) ROLL-UP OR SECTIONAL DOORS- MISSING FLORIDA COVER
 SHEET, PROVIDE WIND
 INFORMATION!!!!!!!
 G) LOUVERS- WALL - OK
 H) PANEL WALLS: SOFFITS, EFIS, STOREFRONTS, CURTAIN
 WALLS- NO REPORT SUBMITTED
 I) SKYLIGHTS- CANOPY ROOF PANELS-SEE A5.02 SECTION
 1 CHANGE DELTA(2) PROVIDE
 MORE INFORMATION ON THIS SYSTEM
 J)PRE-ENGINEERED A/C STANDS- PROVIDE TECHNICAL
 SHEETS 1-3. PLEASE HIGHLIGHT WHICH FASTENING SYSTEM TO
 THE STRUCTURAL DECK BELOW .
 K) ROOFING PRODUCTS: BUILT UP, MODIFIED, SINGLE PLY
 SYSTEMS, METAL ROOFING
 SPRAY APPLIED POLYURETHANE, ROOF SYSTEM
 FASTENERS, UNDERLAYMENTS AND
 WATERPROOFING
  
 (K1) THE REPORT SUBMITTED BY ATLANTIC & CARIBBEAN ROOF
 CONSULTANTS, IF REPORT IS SUBMITTED BY A REGISTERED
 ROOFING CONSULTANT, THEN TO BE SEALED WITH THE
 APPROPRIATE SEAL. THE WORDING TESTING AND ENGINEERING
 SERVICES INDICATES AN ENGINEERING FIRM, WHICH IS A
 LICENSED ENGINEERING FIRM, MISSING THEIR CERTIFICATE OF
 AUTHORIZATION ON THIS REPORT, AND NOT SEALED BY THE
 ENGINEER.
 471.023 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER.
  
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 (K2) THE SUBMITTED REPORT INDICATES VARIOUS ROOF DECKS
 BY NUMBER BUT THERE IS NO KEY PLAN PROVIDING THE
 LOCATION OF THE ROOF DECKS.
 PAGE 7
  
  
 (K3) ROOF DECK NUMBER (2) INDICATES A HEIGHT OF 87?
 WHERE IS THIS DECK LOCATED?
  
 (K4) LIGHTWEIGHT CONCRETE ROOF DECK- MIAMI-DADE NOA,
 THE REPORT SUBMITTED DOES NOT HAVE THE SUB-SYSTEM
 HIGHLIGHTED AS TO WHICH SUB-SYSTEM WILL BE INSTALLED.
  
 (K5) TRIODETIC PREFABRICATED METAL BUILDING SYSTEM- NO
 SUBMITTALS EITHER STATE APPROVAL OR A MIAMI-DADE
 APPROVAL. ADDITIONAL COMMENTS MAY APPEAR ON FURTHER
 REVIEWS.
  
  
 1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING THAT
 RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET (18.3
 M) IN BUILDINGS SHALL BE ASSUMED TO BE OPENINGS AND THE
 BALANCE OF GLAZED OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT
 RECEIVES POSITIVE PRESSURE IS IMPACT RESISTANT OR
 PROTECTED WITH AN IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND ASTM E 1996,
 OR MIAMI-DADE TAS 201, 202 AND 203 REFERENCED THEREIN
 AS FOLLOWS: 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE REQUIREMENTS OF
 THE LARGE MISSILE TEST. 2.GLAZED OPENINGS LOCATED
 MORE THAN 30 FEET (9.1 M) ABOVE GRADE SHALL MEET THE
 PROVISIONS OF THE SMALL MISSILE TEST.
  
  
 79) SEE NEXT COMMENT.
  
  
 80)SAME REQUEST AS COMMENT# 8,W.P.B. ADMIN CODE
 106.3* PRODUCT APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL. THORNTON
 TOMASETTI HAS ATTEMPTED TO COMPLY WITH THIS REQUIREMENT
 BY SUPPLYING A COVERSHEET WITH THEIR SHOP DRAWING STAMP
 AND SIGNATURE BUTTHIS DOCUMENT DOESN?T INDICATE WHAT
 PRODUCT APPROVAL DOCUMENT IS REVIEWED AND APPROVED.
  
  
 81) 2ND REQUEST, THE SUBMITTAL FOR HOLLOW METAL DOORS
 WILL WORK AT GROUND LEVEL BUT THE DOORS AT THE ROOF TOP
 LEVEL WILL NOT THE REQUIRED HIGHER PRESSURE. 1714.5.3
 EXTERIOR DOOR ASSEMBLIES.
 EXTERIOR DOOR ASSEMBLIES NOT COVERED BY SECTION
 1715.4.2 OR SECTION 1714.5.3.1 SHALL BE TESTED FOR
 STRUCTURAL INTEGRITY IN ACCORDANCE WITH ASTM E 330
 PROCEDURE A, AT A LOAD OF 1.5 TIMES THE REQUIRED DESIGN
 PRESSURE LOAD. THE LOAD SHALL BE SUSTAINED FOR 10
 SECONDS WITH NO PERMANENT DEFORMATION OF ANY MAIN FRAME
 OR PANEL MEMBER IN EXCESS OF 0.4 PERCENT OF ITS SPAN
 AFTER THE LOAD IS REMOVED. HIGH-VELOCITY HURRICANE
 ZONES SHALL COMPLY WITH TAS 202. AFTER EACH SPECIFIED
 LOADING, THERE SHALL BE NO GLASS BREAKAGE, PERMANENT
 DAMAGE TO FASTENERS, HARDWARE PARTS, OR ANY OTHER
 DAMAGE WHICH CAUSES THE DOOR TO BE INOPERABLE. PAGE 8
  
 82) COMPLIED.
  
 83) COMPLIED.
  
 84) COMPLIED, EXEMPT A MUNICIPALITY.
  
 JIM WITMER
 BUILDING PLAN REVIEW
 WEST PALM BEACH CONSTRUCTION SERVICES DEPARTMENT WEST
 PALM BEACH, FL 33402
 TEL (561)805-6715
 FAX (561)805-6731
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 CITY HALL CENTER 5TH REVIEW .DOC

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-24 Cont ID  
Sent By jwitmer Date 2006-10-24 Time 12:57 Rev Time 8.88
Received By jwitmer Date 2006-10-24 Time 12:57 Sent To  
Notes
2006-10-24 14:29:21WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
 FOURTHREVIEW OCT. 24TH, 2006
 FIRST UNDER PERMIT
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: MEINHART CONSULTING ENGINEERS
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*)MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 ***SHEET T-1 APPLICABLE CODEPLEASE CORRECT TO THE
 2004 FBC.*****
  
 1) --- VERY IMPORTANT
 STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 THIS COMMENT WAS IGNORED UNDER THE FIRST
 REVIEW, THE DESIGN TEAM DIDN?T PROVIDE ANY TRANSMITTAL
 LETTER, NOR WERE ANY OF THE CHANGES MADE HIGHLIGHTED
 WITH A CLOUD OR DELTA AND THE REVISION BOX IN THE
 HEADER STRIP WASN?T FILLED IN MAKING DIFFICULT TO FIND
 THE REVISIONS MADE AND TIME CONSUMING!!!!
  
  
 2) PLANS INDICATE 100% COMPLETE BUT ARE ONLY A PARTIAL
 ROLL,WHEN PLANS ARE TO BE SUBMITTED FOR PUBLIC RECORD
 :PLANS, SPECIFICATIONS,REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 3) NOTE: PLANS ARE NOT SEALED THIS IS A COURTESY
 REVIEW, WHEN PLANS ARE SUBMITTED FOR PUBLIC RECORD: NEW
 ENGINEERING SEAL DESIGN. "LICENSE" A GRACE PERIOD RAN
 THROUGH DEC. 31, 2005.
 RULE 61G155-23.001(1) F.A.C.
 THE FLORIDA BOARD OF PROFESSIONAL ENGINEERS HAS
 CLEANED UP THE APPEARANCE OF THE SEAL BY ELIMINATING
 OBSOLETE CONTENT AND CHANGING THE WORD "CERTIFICATE"
 TO
  
 COVERSHEET:
 3A) CIVIL ENGINEERS: CRAVEN THOMPSON & ASSOCIATES, INC.
 IS MISSING THEIR CERTIFICATE OF AUTHORIZATION.)
 471.023 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER.
 ADD THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 4)FOURTH REQUEST, STRUCTURAL SHEET TITLE BLOCK INDICATE
 THAT THORNTON TOMASETTI A CONSULTING ENGINEER, FL DEPT
 OF PROFESSIONAL REGULATION DOESN'T INDICATE LICENSURE
 IN FLORIDA.
 LICENSURE FL S. S. 471.015/471.023 F.S. CERTIFICATE
 OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER.
 ADD THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 5) COMPLIED.
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8) FOURTHREQUEST,PRODUCT APPROVAL HAVE BEEN
 SUBMITTED AT THIS TIME. WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS.THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 9) COMPLIED.
  
 10) COMPLIED. SHEET# S0-2.0 STRUCTURAL INSPECTION
 PLAN.
  
  
 11) THIRDREQUEST,WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. CONTACT HAROLD PISKURA MANAGER
 OF THE SPECIAL INSPECTOR PROGRAM AT (561) 805-6711 FOR
 FURTHER INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
 SEE ATTACHED GUIDELINE.
  
 12) COMPLIED.
  
 13) COMPLIED.
  
 14)THIRD REQUEST, IN REVIEWING THIS PLAN IT APPEARS
 THAT THERE ARE VARIOUS DOORS THAT DO NOT MEET THE
 REQUIREMENTS OF:11-4.13.6 MANEUVERING CLEARENCES AT
 DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS THAT ARE
 NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH IN THE REQUIRED
 CLEARANCES SHALL BE CLEAR & LEVEL. SEE LIST :A1-302A &
 A4-202A. PLEASE CLOUD OR DELTA THESE CHANGES.
  
 15) COMPLIED.
  
 16) COMPLIED.
  
 17) COMPLIED.
  
 18) COMPLIED.
  
 19) COMPLIED.
  
 20) COMPLIED.
  
 21) COMPLIED.
  
 22) COMPLIED.
  
 23)4TH REQUEST,SHEET A1-D DETAILS 1.1 ? 2.2
 ILLUSTRATE THE USE OF GRANITE VENEER. DETAIL 1.1B
 PROVIDES INFO FOR ATTACHMENT BUT DOES NOT MATCH TO
 SECTION 1405.7 FOR SLAB TYPE <2?THICK (GRANITE).ALSO
 PROVIDE MAXIMUM SQUARE FOOTAGE PER GRANITE. THE MAXIMUM
 AREA PER SLAB STILL ISN'T INDICATED ON THE PLANS.
  
 24) COMPLIED.
  
 25) FOURTH REQUEST, PLANS INDICATE FIRST FLOOR FINISH
 FLOOR TO BE 17.35 NGVD, BUT NO SITE PLAN PROVIDES THE
 EXISTING CITY SIDEWALK ELEVATIONS. PROVIDE AT LEAST 1
 ACCESSIBLE ROUTE TO THE SITE. 11-4.1.2(1-4). IN
 DISCUSSING THE SIDEWALKS AROUND THE PERIMETER WITH THE
 DESIGN TEAM AT THE LAST MEETING THERE WILL BE CONCERNS
 WITH CROSS SLOPE NOT TO EXCEED THE 2%. THE DESIGN TEAM
 INDICATED THAT BETWEEN THE SIDEWALK AND STREET CURBING
 THERE WILL BE PLANTERS FOR TREES, BUT BETWEEN THE TREE
 PLANTERS THERE WILL ALSO BE A WALKING SURFACE ( BRICKS)
 THAT WILL HAVE CROSS SLOPE GREATER THAN 2%.
 IN DISCUSSING THIS ISSUE WITH THE BUILDING
 OFFICIAL IF THE SLOPE OF THE BRICK IS GREATER THAN 2%
 THEN SOME TYPE OF BARRIER NEEDS TO BE IN EFFECT, EITHER
 EDGE PROTECTION OR A GUARD. 11-4.3.7 11-4.3.7 SLOPE. AN
 ACCESSIBLE ROUTE WITH A RUNNING SLOPE GREATER THAN 1:20
 IS A RAMP AND SHALL COMPLY WITH SECTION 11-4.8 .
 NOWHERE SHALL THE CROSS SLOPE OF AN ACCESSIBLE ROUTE
 EXCEED 1:50.
  
 26) COMPLIED.
  
 27) COMPLIED.
  
 28) COMPLIED.
  
 29) COMPLIED.
  
 30) COMPLIED.
  
 31) COMPLIED.
  
 32) 2ND REVIEW,DOOR SCHEDULE DOESN?T PROVIDE
 RATING FOR ALL THE VERTICAL EXIT ENCLOSURES (STAIRWELL
 DOORS). FBC 1019.
 32A) IN CHECKING THE DOOR SCHEDULE FOR EXIT STAIRWAYS
 LS1-1.1 AND A1-1.1 STAIRWELL & VESTIBULE 02 DOESN'T
 MATCH IN CONFIGURATION.
 32B) MISSING DOOR RATINGS ON ALL ELECTRICAL,
 MECHANICAL, ELEVATOR MECHANICAL ROOMS AND STORAGE
 ROOMS, SEE A-8.01-.02
 NOTE : TABLE 715.3 FOOTNOTE "B". SEE 715.3.3
 FIRE DOOR ASSEMBLIES SHALL ALSO MEET THE REQUIREMENTS
 FOR A SMOKE AND DRAFT- CONTROL DOOR ASSEMBLY TESTED IN
 ACCORDANCE WITH UL 1784 WITH AN ARTIFICIAL BOTTOM SEAL
 INSTALLED ACROSS THE FULL WIDTH OF THE BOTTOM OF THE
 DOOR ASSEMBLY.
  
 33) COMPLIED.
  
 34) COMPLIED.
  
 35) COMPLIED.
  
 36) COMPLIED.
  
 37)
  
 38)A) EMPLYEES LOUNGE LS1-3.1& A-1.3.1 THE FLOOR PLAN
 CALCULATES OUT TO BE BETWEEN 844 & 840 SQ FT /15= TO AN
 OCCUPANT LOAD OF 56 REQUIRING 2 EXITS AND THE CORRIDORS
 TO BE FIRE RATED 1 HR.
 TABLE 1016.1. THIS WILL ALSO REQUIRE THE DOORS TO HAVE
 THE FIRE RATING NOT SHOWN ON THE DOOR SCHEDULE.
  
 38B) TRAINING ROOM LS1-4.1 THE TRAINING ROOM AND
 VESTIBULE TOTAL 1495 SQ FT/20= 75 OCCUPANT LOAD. THE
 DECUSSION AT LAST WEEKS MEETING WAS THAT WILLIAM
 SWICHER HAD INDICATED THIS WAS TO BE FIXED SEATING, WE
 HAVE E-MAILED MR. SWICHER TO VERIFY THIS ROOM WILL HAVE
 FIXED SEATING BOLTED TO THE FLOOR. AT PRESENT NO REPLY
 FROM MR. SWICHER.PLEASE PROVIDE THE1HR RATED
 CORRIDOR AND OPENING PROTECTIVES REQUIRED BY TABLE
 1016.1.
  
 38C) LS1-3.2 & A1-3.2 IS STILL MISSING THE 1 HR RATING
 BETWEEN THE CORRIDOR THAT SEPERATES THE BUSINESS AND
 ASSEMBLY OCCUPANCY. TABLE 1016.1.
  
 39) COMPLIED.
  
 40) SECOND REQUEST,THE OTHER ISSUE THAT WAS DISCUSSED
 WITH THE DESIGN TEAM IS THE ?MECHANICAL MEZZANINE? ,
 SHEET LS1-1.2, THIS SHEET DOESN?T INDICATE THE
 MEZZANINE LEVEL, OR SIZE.
  
 PROVIDE A FLOOR PLAN INDICATING THE SIZE OF ROOM AND
 FLOOR AREA OF THE MEZZANINE.
 INDUSTRIAL EQUIPMENT PLATFORM CAN ONLY BE USED IN
 INDUSTRIAL OCCUPANCIES. 505.5.
 THE SECOND ISSUE IS THE USE OF ALTERNATING STAIRS FOUND
 ON SHEET A6-6.1. SECTION 1009.1 LIMITS THE USE OF
 ALTERNATING TREAD STAIRS TOMEZZANINES OF 250 SQ FT
 AND LESS.
  
 40A) DOME AREA IS 480 SQ FT.
 40B) A2M101 IS 930 SQ FT.
 40C) A2M102 IS 960 SQ FT.
  
 41) COMPLIED.
  
 42) SHEET THAT STILL HAVE DETAIL MARKERS MISSING IS
 A1-2.1( MISSING THE SHEET LOCATION)
  
 43) COMPLIED, STILL NEEDS WALL AND DOOR RATING.
  
 44) COMPLIED.
  
 45)3RD REQUEST , PLANS ARE MISSING THE WALL RATING
 TAGS ON SHEET A1-GA.FPL VAULT, MAIN ELECTRIC ROOM, FIRE
 PUMP ROOM, DOORS ARE NOT LABELED ON THE
 DOOR SCHEDULE . ALSO SEE LS).0 FIRE RESISTANCE
 RATINGS.
  
 46) COMPLIED.
  
 47) COMPLIED.
  
 48) COMPLIED.
  
 49)COMPLIED.
  
 50) COMPLIED.
  
 51) COMPLIED.
  
 52) COMPLIED.
  
 53) COMPLIED.
  
 54) COMPLIED.
  
 55) COMPLIED.
  
 56) COMPLIED.
  
 57) COMPLIED.
  
 58) COMPLIED.
  
 59) COMPLIED.
  
 60) COMPLIED.
  
 61) COMPLIED.
  
 62) COMPLIED.
  
 63) COMPLIED.
  
 64) LS1-GA.1- LS1-GA.3THE PARKING GARAGE EXITS DO NOT
 HAVE THE REQUIRED EGRESS CAPACITY GRAPHICS FILLED IN.
 106.1.2* ADDITIONAL INFORMATION REQUIRED.
 LIFE SAFETY PLANS NOT SUBMITTED.
  
 65) 3RDREQUEST, LS1-3.0/ A1-3.2 THERE ARE ISSUES WITH
 3 AREAS:
 ELEVATOR LOBBY C3.201
 PREFUNCTION LOBBY C3.301
 LOBBY C3.303
 THE BUILDING OFFICIAL WAS MADE AWARE THAT THESE AREAS
 INDICATED ON THE LIFE SAFETY PLAN DO NOT HAVE AN
 OCCUPANT LOAD ASSIGNED TO THEM.NEIL INDICATED HE
 WOULD LIKE
 THESE AREAS TO BE TREATED JUST AS THE MALL AREA ON THE
 FIRST FLOOR, SUBTRACT THE SQUAREFOOTAGE REQUIRED FOR
 EXIT ACCESS CORRIDORS OUT OF THE GROSS AREA FOR EACH
 AREA, THE NET SQUARE FOOTAGE WOULD BE TREATED AS
 ADDITIONAL SQ FOOTAGE TO BE CONSIDERED AT 7 SQUARE FEET
 PER PERSON.TABLE 1004.1.2.
  
 THIS ADDITIONAL OCCUPANT LOAD SHALL BE ADDED TO THE
 LIFE SAFETY SHEETS, STAIRS AND DOORWAY MAY NEED TO BE
 INCREASED IN SIZE DUE TO THE ADDITIONAL LOADING.
  
 66)2ND REQUEST,THE OTHER ISSUE IN THIS AREA OF THE
 LIBRARY THIRD FLOOR AND THE AMOUNT OF ASSEMBLY
 OCCUPANCY, THE EXIT ACCESS CORRIDORS NOT BEING RATED
 (NORTH SIDE OF ASSEMBLY AREA). STAIR# 8 VESTIBULE
 MISSING FIRE RATING. PLEASE REVISE THE LIFE SAFETY PLAN
 AND DOOR SCHEDULE TO COMPLY WITH THE REQUIREMENTS OF
 TABLE 1016.1 FOR
 ASSEMBLY OCCUPANCY, SPRINKLERED >30= 1 HR FIRE RATED
 CORRIDORS.
  
 67A) COMPLIED.
  
 67B) COMPLIED.
  
 68) SAME AS 38A AND 38 B. 3RD REQUEST,68)2ND REQUEST,
 LS1-3.0 CITY HALL SIDE OF PLAN INDICATES (2) AREAS
 WHERE THERE ARE ASSEMBLY OCCUPANCIES, ROOM A3.108 THE
 EMPLOYEES LOUNGE, OCCUPANT LOAD OF 60 AND ROOM NUMBER
 A3.110THE EXERCISE ROOM WITH AN OCCUPANT LOAD OF 19.
  
  
 THE EMPLOYEE LOUNGE WILL REQUIRE 2 MEANS OF EGRESS,
 PLANS DO INDICATE (2) DOORWAYS ONE TO AN EXIT ACCESS
 CORRIDOR WHICH WILL REQUIRE A 1 HR FIRE RATING. SEE
 TABLE 1016.1
 ASSEMBLY, OCCUPANT LOAD > THAN 30,SPRINKLERED = 1HR
 RATED CORRIDORS.
  
 69) 3RD REQUEST,THE OTHER ISSUE WITH THE EMPLOYEE
 LOUNGE REQUIRING (2) MEANS OF EGRESS BEING A OCCUPANT
 LOAD GREATER THAN 50 REQUIRING A SECOND EXIT. TABLE
 1014.1.
 PAGE 8
 TO USE THE DOOR FROM THE EMPLOYEE LOUNGE TO THE
 EXERCISE ROOM FBC 1013.2 STATES:
 EGRESS FROM A ROOM OR SPACE SHALL NOT PASS THROUGH
 ADJOINING OR INTERVENING ROOMS OR AREAS, EXCEPT WHERE
 SUCH ADJOINING ROOMS OR AREAS ARE ACCESSORY TO THE AREA
 SERVED. ALSO THE DOORS TO THE GYM MAY END UP BEING
 LOCKED.AN EXIT ACCESS SHALL NOT PASS THROUGH A ROOM
 THAT CAN BE LOCKED TO PREVENT EGRESS.1013.2.
  
 70) 3RD REQUEST, LS1-3.0 EXIT ACCESS CORRIDOR
 A3.012WILL HAVE TO BE 1 HR FIRE RATED, TO THE (2)
 VERTICAL EXITS ENCLOSURES. TABLE 1014.1/ 1014.1.(1).
  
 71) COMPLIED.
  
 72) SAME AS 38B) ,LS1-4.0 / LS1-4.1/ A1-4.0& A1-4.1
 THESE SHEETS INDICATE TRAINING ROOM# A4.403 IS AN
 ASSEMBLY OCCUPANCY WITH AN OCCUPANT LOAD OF 75@20 SQ FT
 / PERSON, .
 TABLE 1016.1 ASSEMBLY OCCUPANCIES >30 OCCUPANT LOAD
 LOAD REQUIRES 1 HR FIRE SEPARATION IN THE ASSOCIATED
 EXIT ACCESS CORRIDORS. THE 2 CORRIDORS THAT LEAD TO THE
 VERTICAL EXIT ENCLOSURES WILL NEED TO BE FIRE RATED 1HR
 WITH 20 MINUTE OPENING PROTECTIVES.
  
 73) COMPLIED.
  
 74) COMPLIED.
  
 75) COMPLIED.
  
 76) COMPLIED.
  
 77) COMPLIED.
  
 78)78-81 THE CONTRACTOR & DESIGN TEAM REMOVED THESE
 ITEMS FOR FURTHER UPDATING AND REVIEW!!!!
 FL BLD CODE 1609.1.4
 : COMPONENTS & CLADDING, PROVIDE 2 COPIES(3 IF
 THRESHOLD OR RESIDENT INSPECTOR) OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS: (NOTE NOT
 REVIEWED BY THE ENGINEER OF RECORD)PLEASE INDICATE
 WHERE EACH OF THE PRODUCTS WILL BE USED, (EXAMPLE,
 TRAINER, TCW 250P
 ALUMINUM WINDOW WALL SYSTEM W/ UNREINFORCED MULLIONS
 SMUVS. TRAINER TCW250P ALUMINUM WINDOW WALL SYSTEM W/
 UNREINFORCED MULLIONS LMU,
 ALUMINUM WINDOW WALL) IT APPEARS THAT THESE UNITS WILL
 BE ON THE EAST SIDE OF THE BUILDING SPANING BETWEEN THE
 2ND & 3RD FLOOR. THERE ARE NO WINDOW OR DOOR SCHEDULES
 IN THIS PLAN, STRUCTURAL ELEVATION SHEET S0-3.0
 INDICATES NOT TO SCALE!!!
 WITH THE IMPORTANCE FACTORS ON THIS BUILDING THE
 PRESSURES ARE GREATER THAN USUAL, PLEASE HIGHLIGHT
 WHICH UNIT WILL BE USED WHEN THE PRODUCT APPROVAL HAS
 MORE THAN ONE IN THE NOA. ALSO WITH THE WINDOW UNITS
 LISTED ABOVE ARE GOING TO BREAK AT THE
 30?-0? LINE LARGE MISSILE / SMALL MISSILEBREAK LINE,
 HOW WILL THE MULLIONS AND OR WINDOW UNITS BREAK?
  
  
  
 A) FIXED WINDOWS
 B) OPERABLE WINDOWS
 C) MULLIONS NOT COVERED BY NOA
 D) GLAZED DOORS, AUTOMATIC SLIDERS, SWING DOORS OR
 PRE-ENGINEERED ROOF ACCESS
 HATCHES
 E) EXTERIOR METAL DOORS IF SINGLE OR PAIRS
 F) ROLL-UP OR SECTIONAL DOORS
 G) LOUVERS- WALL
 H) PANEL WALLS: SOFFITS, EFIS, STOREFRONTS, CURTAIN
 WALLS
 I) SKYLIGHTS
 J)PRE-ENGINEERED A/C STANDS
 K) ROOFING PRODUCTS: BUILT UP, MODIFIED, SINGLE PLY
 SYSTEMS, METAL ROOFING
 SPRAY APPLIED POLYURETHANE, ROOF SYSTEM
 FASTENERS, UNDERLAYMENTS AND
 WATERPROOFING ,********** NO ROOFING PRODUCTS
 SUBMITTED AT ALL!!!!!!*************
 L) ACCESS ROOF HATCHES: SINCE THERE IS NO PRODUCTS THAT
 ARE CURRENTLY LISTED WITH EITHER THE STATE WEB SITE OR
 MIAMI-DADE THIS PRODUCT WILL REQUIRE LOCAL APPROVAL
 FORMS WILL BE ATTACHED.
  
 1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING THAT
 RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET (18.3
 M) IN BUILDINGS SHALL BE ASSUMED TO BE OPENINGS AND THE
 BALANCE OF GLAZED OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT
 RECEIVES POSITIVE PRESSURE IS IMPACT RESISTANT OR
 PROTECTED WITH AN IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND ASTM E 1996,
 OR MIAMI-DADE TAS 201, 202 AND 203 REFERENCED THEREIN
 AS FOLLOWS: 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE REQUIREMENTS OF
 THE LARGE MISSILE TEST. 2.GLAZED OPENINGS LOCATED
 MORE THAN 30 FEET (9.1 M) ABOVE GRADE SHALL MEET THE
 PROVISIONS OF THE SMALL MISSILE TEST.
  
 79) 2ND REQUEST, W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY DCA RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 80) SAME REQUEST AS 79. W.P.B. ADMIN CODE 106.3*
 PRODUCT APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 81) 1714.5.3 EXTERIOR DOOR ASSEMBLIES.
 EXTERIOR DOOR ASSEMBLIES NOT COVERED BY SECTION
 1715.4.2 OR SECTION 1714.5.3.1 SHALL BE TESTED FOR
 STRUCTURAL INTEGRITY IN ACCORDANCE WITH ASTM E 330
 PROCEDURE A, AT A LOAD OF 1.5 TIMES THE REQUIRED DESIGN
 PRESSURE LOAD. THE LOAD SHALL BE SUSTAINED FOR 10
 SECONDS WITH NO PERMANENT DEFORMATION OF ANY MAIN FRAME
 OR PANEL MEMBER IN EXCESS OF 0.4 PERCENT OF ITS SPAN
 AFTER THE LOAD IS REMOVED. HIGH-VELOCITY HURRICANE
 ZONES SHALL COMPLY WITH TAS 202. AFTER EACH SPECIFIED
 LOADING, THERE SHALL BE NO GLASS BREAKAGE, PERMANENT
 DAMAGE TO FASTENERS, HARDWARE PARTS, OR ANY OTHER
 DAMAGE WHICH CAUSES THE DOOR TO BE INOPERABLE.
  
 82) COMPLIED.
  
 83) COMPLIED.
  
 84)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
  
 JIM WITMER
 BUILDING PLAN REVIEW
 WEST PALM BEACH CONSTRUCTION SERVICES DEPARTMENT WEST
 PALM BEACH, FL 33402
 TEL (561)805-6715
 FAX (561)805-6731
  
  

Review Stop E ELECTRICAL
Rev No 44 Status P Date 2009-09-17 Cont ID  
Sent By dpalmer Date 2009-09-17 Time 18:14 Rev Time 0.00
Received By dpalmer Date 2009-09-17 Time 18:14 Sent To PC
Notes
2009-09-17 18:15:12 
 ** REDLINED PLANS **
  
  
 1) NOTE: ELEVATOR LOBBIES ON FIRST AND FORTH FLOORS AT
 LIBRARY ARE REQUIRED TO CONTAIN SOME SORT OF BATTERY
 BACK UP LIGHT FIXTURE.
 NFPA-101 7.8, 7.9
 FBC 1006.1.2
  
 2) NOTE: CLOSET LIGHTS ON FIRST FLOOR CORRIDOR NEED TO
 MEET 410.8. VIF.
  
 3) NOTE: INFORMATION FOR NEW PANELS 2HDR, 2LDR AND
 45KVA TRANSFORMERS ADDED FOR SECOND FLOOR OFFICE BUILD
 OUTS ARE SHOWN ON BUILD OUT PLANS.
  

Review Stop E ELECTRICAL
Rev No 43 Status F Date 2009-06-10 Cont ID  
Sent By dpalmer Date 2009-06-10 Time 11:26 Rev Time 0.00
Received By dpalmer Date 2009-06-10 Time 11:26 Sent To PC
Notes
2009-06-10 11:26:23** DENIED REVIEW**
  
 ** PLANS AND FINAL REVISIONS NEED TO BE SUBMITTED WITH
 COORDINATION OF ALL DRAWINGS. THESE ARE THE FINAL
 RECORD PLANS TO BE ON FILE. ALL ITEMS NEED TO BE
 COORDINATED AND CORRECTED.
  
 * THE FOLLOWING WILL BE SOME EXAMPLES ONLY OF AREAS IN
 WHICH THERE ARE DISCREPANCIES ON PLANS.
  
 **** THIS REVIEW IS NOT BASED ON THE COMPARISON OF
 PLANS WITH THE FIELD OR JOBSITE LOCATION.
  
 **** ONE OF THE REDLINED SET OF PLANS WHICH WAS USED IN
 REVIEW WILL REMAIN IN THIS OFFICE. IN NUMEROUS PREVIOUS
 REVIEWS AND MEETINGS IT WAS STATED TO CALL TO GO OVER
 ANY QUESTIONS ON COMMENTS WITH RESPECT TO PLANS OR
 PROPOSED DESIGN. IT IS STRONGLY RECOMMENDED THAT A
 MEETING BE HELD TO GO OVER ANY COMMENTS WHICH MAY NOT
 BE CLEAR OR UNDERSTOOD IN ANY WAY. THIS MEETING SHOULD
 BE HELD WITH REPRESENTATIVES FROM THE GENERAL
 CONTRACTOR, ELECTRICAL CONTRACTOR, ARCHITECTURAL FIRM,
 ENGINEERING FIRM AND THE CITY OF WEST PALM BEACH.
  
 **** THE LIGHTING CONTROL PANEL WILL BE NOTED AS LCP IN
 MANY OF THE COMMENTS BELOW.
  
 **** MANY OF THE COMMENTS BELOW WILL BE GENERAL TO THE
 SECTIONS OF CODES FOR LIGHTING CONTROLS, PANEL SCHEDULE
 AND RECORD PLANS.
 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4. 408.4, 106.5,
 106.1.1, 106.1.2 ETC
 MORE SPECIFIC CODES WILL BE NOTED IN OTHER LOCATIONS.
 ** PLEASE BE SURE TO SEE 408.4 WHICH REQUIRE ALL
 LOCATIONS TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH
 THEY FEED. STATING *RECEPTACLES* OR * LIGHTING* IS NOT
 SPECIFIC FOR PANEL SCHEDULES OR PANEL SCHEDULES ON
 RECORD PLANS.
  
 1) NOTE: PLEASE SUBMIT AN UPDATE LAYOUT OF ALL
 ELECTRICAL ROOMS WHICH EQUIPMENT WAS ADDED. FOR EXAMPLE
 THERE ARE NEW TRANSFORMERS AND PANELS FOR SOME
 LOCATIONS THROUGH OUT THE PLANS. THE TRANSFORMER FOR
 PANEL A FOR EXAMPLE COULD NOT BE LOCATED ON PLAN.
 SEE OTHER NOTES BELOW WITH RESPECT TO OTHER PANELS AND
 COORDINATION OF PLANS.110.26, FBC 106.1.2,106.1.1,
 106.5 FOR COORDINATION OF RECORD DOCUMENTS.
 THE MAIN ELECTRICAL ROOM IS ONE EXAMPLE OF EQUIPMENT
 BEING ADDED WHICH IS NOT PART OF THE REVISED PLANS. THE
 RECORD PLANS DO NOT INCLUDE OTHER WORK WHICH HAS BEEN
 DONE.
  
 2) NOTE: PLEASE SUBMIT PANEL SCHEDULE FOR NEW PANEL *A*
 WHICH IS NOW SHOWN ON PLANS. PLEASE BE SURE TO
 COORDINATE. 408.4
  
 3) NOTE: PLEASE SHOW LOCATION OF THE TRANSFORMER FOR
 THE SAME PANEL *A*. 450.9, 450.13, 110.26 ETC. AS THIS
 IS NOT SHOWN CODE COMPLIANCE CAN NOT BE DETERMINED.
  
 4) NOTE: PLEASE REMOVE ALL WORK IN AREAS FOR WHICH THE
 *PHOTO MUSEUM* WILL BE LOCATED. ONE EXAMPLE IS THE 2ND
 FLOOR WHICH STILL INDICATES LIGHTING AND OTHER ITEMS
 WHICH ARE NOW NO LONGER PART OF THE BASE BUILDING.
 PLEASE TAKE A LOOK AT THEIR TENANT SPACE PLANS AND
 REMOVE LIGHTS AS NEEDED.
 PLEASE ALSO COMPLETE LATEST REVISED PLANS FOR COMMON
 AREAS WHICH ARE TO BE FED FROM BASE BUILDING AND ARE
 NOT PART OF THE TENANT SPACE.
 THE RISER STILL INDICATES THE 800A BREAKER FOR THE
 PHOTO-MUSEUM EVEN THOUGH THE SPACE IS FED FROM A
 SEPARATE SERVICE.
 SEE D2.106
  
 5) NOTE: RECEPTACLES IN MAIN MECHANICAL ROOM DO NOT
 CONNECT TO ANY CIRCUIT.
  
 6) NOTE: PLEASE SEE 2-HA-18 WHICH IS SHOWN AS EXTERIOR
 LIGHTS ON PLANS YET THE LCP IS NOT COMPLETE OR LISTS
 THE CIRCUIT. THE PANEL SCHEDULE FOR HA-18 IS SHOWN AS
 SPARE EVEN THOUGH IT IS ON PLANS.
  
 7) NOTE: PLEASE SEE 2-HC-18 IS NOTED ON PLANS YET NOT
 ON LCP.
  
 8) NOTE: PLEASE SEE 2-HA-10 WHICH IS NOT ON LCP.
  
 9) NOTE: PLEASE SEE 2-HB-8 WHICH IS SHOWN AS EXTERIOR
 LIGHTS ON PANEL SCHEDULE HOWEVER THE LCP STATES THIS IS
 FOR LIGHTING INSIDE IN OPEN WORK AREA.
  
 10) NOTE: PLEASE SEE 2-HA-19 WHICH IS NOT LISTED ON LCP
 HOWEVER ON PLANS AND PANEL SCHEDULE.
  
 11) NOTE: PLEASE SEE FIRST LEVEL COMMON AREAS WHICH DO
 NOT INDICATE ANY LIGHTING, LIGHTING CONTROLS, AND
 CIRCUITS ETC WHICH ARE NOT PART OF THE PHOTO MUSEUM
 SPACE.
 13-415.1.ABC.1.1,1.2, .1.3.
  
 12) NOTE: PLEASE COMPLETE PLANS WITH NEW LIGHTING FOR
 COMMON AREAS OUTSIDE PHOTO MUSEUM SPACE. PLEASE SEE
 NFPA-101 7.8 AND 7.9 FOR COMPLETE LIGHTING IN COMMON
 AREAS FOR LIFE SAFETY. OTHER ITEMS SUCH AS HORNS,
 STROBES, HORN/STROBE FOR COMPLIANCE WITH NFPA-72 AND
 COMPLIANCE WITH FBC 11-4.27.4 SHALL ALSO BE MET. FIRE
 ALARM PLANS HAVE NOT BEEN UPDATED AND COORDINATED TO
 DATE OF THIS REVIEW.
  
 13) NOTE: PLEASE SEE EE FIXTURE ON C2-2.2 WHICH DOES
 NOT INDICATE ANY CIRCUIT OR CONTROL. THE PREVIOUS PLANS
 DID SHOW CIRCUITING AND CONTROLS.
  
 14) NOTE: WHERE ARE THE CONTROLS FOR 1-GHA18-20?
  
 15) NOTE: PLANS SHOW CIRCUIT 1-GLA-30 AS A DEDICATED
 CIRCUIT FOR SODA MACHINE HOWEVER BASED ON THE PLANS
 THIS SAME CIRCUIT IS SHOWN IN MORE THAN ONE LOCATION.
 ONE LOCATION IS THE STORAGE ROOM IN GARAGE WHICH
 INDICATES THE SAME CIRCUIT.
  
 16) NOTE: PLEASE SEE CIRCUIT 1LB3-21 AND 24 WHICH BOTH
 INDICATE CIRCUITS TO COMMON AREA RECEPTACLES IN SPACE
 A1.115. ARE NOT ONE OF THESE AT LEAST A DEDICATED
 CIRCUIT FOR SODA MACHINE?
  
 17) NOTE: PLEASE SEE CIRCUIT 1-GLEA-2 WHICH INDICATES
 PLANS A J-BOX YET THIS IS CIRCUITED AS A FA NAC.
  
 18) NOTE: PLEASE SEE 1-LC2-31 ON PLANS SHOWN AS CIRCUIT
 TO ROOM C1.101 HOWEVER PANEL SCHEDULE INDICATES
 C1.301??
  
 19) NOTE: PLEASE SEE POWER PLANS FOR EXAMPLE E1-1.1
 WHICH DOES NOT SHOW THE NEW PANELS 1TV AND 1LS-1. THESE
 ARE SHOWN ON E7-7.0 YET NOT COORDINATED.
 THE PANEL SCHEDULE FOR EACH OF THESE INDICATED ROOM
 LOCATIONS HOWEVER PANEL NOT AS ON PLANS. ONE OF THESE
 WOULD BE 1TV WHICH STATES THE LOCATION AS A1.406 YET
 SHEET E7-7.0 SHOWS THIS IN ANOTHER LOCATION NEXT TO
 1LS-1.
  
 20) NOTE: PLEASE SEE 1TV WHICH IS SHOWN AS 200AMP MLO
 ON SCHEDULE AND ON RISER THIS IS SHOWN AS 150AMP. ??
  
 21) NOTE: PLEASE SEE 1LD2-13 ON PANEL SCHEDULE WHICH
 STATES THIS IS FOR AHU-1 PUMP. YET PLANS INDICATE THIS
 FOR GENERAL RECEPTACLE CIRCUIT FEEDING OTHER AREAS
 BESIDES PUMP?
  
 22) NOTE: PLEASE SEE 2-LA-3-3 ON PANEL WHICH STATES
 THIS FEEDING LOCATION A2.213 YET THE PLANS SHOWS THE
 LOCATION IN FOYER SINGLE LOCATION A2.003.
  
 23) NOTE: PLEASE SEE 2LD-2-3 WHICH IS NOT SPECIFIC TO
 ROOMS AND LOCATIONS IN WHICH THIS CIRCUIT FEEDS. PANEL
 SCHEDULE DOES NOT LIST LOCATIONS AS FOUND ON PLANS.
  
 24) NOTE: PLEASE SEE 2LD2-6 WHICH IS SHOWN AS SPARE ON
 PANEL SCHEDULE HOWEVER THE PLANS ON E1-2.2 STILL HAS
 CIRCUIT SHOWN.
  
 25) NOTE: PLEASE CORRELATE ALL POWER AND RELEVANT
 CHANGES ON POWER PLANS E1-1.1 WITH E7-7.0.
 THERE ARE NUMEROUS ITEMS
  
 26) NOTE: PLEASE SEE 1LA3-10 WHICH PER PANEL SCHEDULE
 IT STATES COMMISSION OFFICE HOWEVER PLEASE SEE SHEET
 E7-7.0 WHICH INDICATES THIS AS A DEDICATE RECEPTACLE IN
 THE FLAGLER GALLERY.
  
 27) NOTE: PLEASE SEE 1LA3-18 WHICH DOES LIST THIS AS
 A1-308 ON PLANS HOWEVER PLEASE SEE E7-7.0
  
 28) NOTE: PLEASE SEE 3LD2-9 NEEDS TO BE SPECIFIC TO
 ROOMS AND AREAS IN WHICH THEY FEED. THE PLANS INDICATE
 MANY MORE LOCATIONS THAN WHAT IS LISTED ON PANEL
 SCHEDULE.
  
 29) NOTE: PLEASE SEE 3LC-19 NEED TO BE SPECIFIC TO ALL
 ROOMS AND AREAS IN WHICH THEY FEED.
  
 30) NOTE: PLEASE SEE 3LD3-21 ON PANEL SCHEDULE WHICH
 INDICATES THIS AS A SPARE CIRCUIT HOWEVER THE PLANS
 STILL SHOW THIS CIRCUIT.
  
 31) NOTE: PLEASE SEE 3LD3-6 WHICH THE PANEL SCHEDULE
 INDICATES THIS AS A SPARE YET THE PLANS STILL INDICATES
 THIS AS A CIRCUIT BEING USED.
  
 32) NOTE: PLEASE SEE CIRCUITS 4LA3-5 AND -24 WHICH ARE
 BOTH SHOWN TIED TOGETHER ON PLANS. WHY ARE THESE NOT
 SEPARATED?
  
 33) NOTE: PLEASE SEE MULTIPLE SETS OF FURNITURE WORK
 STATIONS WHICH SHOW THE SAME CIRCUITING 4LB3-26,28,30.
 PLEASE SEE 220.14(I) FOR LOADS PER YOKE. PLEASE PROVIDE
 INFORMATION ON HOW MANY RECEPTACLES ARE ON THE CIRCUITS
 AS SHOWN FOR KNOWN LOADS. THIS WAS GONE OVER IN
 ORIGINAL REVIEW EVEN BEFORE PERMIT ISSUANCE FOR KNOWN
 LOADS AND LOADS FIGURED AT 180VA. THE REVIEW COMMENTS
 CAN BE PROVIDED ALONG WITH E-MAILS IN WHICH QUESTIONS
 WERE RAISED.
  
 34) NOTE: PLEASE SEE MULTIPLE SETS OF FURNITURE WORK
 STATIONS WHICH SHOW THE SAME CIRCUITING 4LA3-15,17,19.
 PLEASE SEE 220.14(I) FOR LOADS PER YOKE. PLEASE PROVIDE
 INFORMATION ON HOW MANY RECEPTACLES ARE ON THE CIRCUITS
 AS SHOWN FOR KNOWN LOADS.
 THIS WAS GONE OVER IN ORIGINAL REVIEW EVEN BEFORE
 PERMIT ISSUANCE FOR KNOWN LOADS AND LOADS FIGURED AT
 180VA. THE REVIEW COMMENTS CAN BE PROVIDED ALONG WITH
 E-MAILS IN WHICH QUESTIONS WERE RAISED.
  
 35) NOTE: PLANS STILL STATE IT EQUIPMENT TO BE DONE BY
 OTHERS. HOWEVER THE RECORD SET OF PLANS NEED TO NOW
 SHOW ALL OF THIS WORK BEING COMPLETED. PLEASE COMPLETE
 THE IT PANEL SCHEDULE. THE SCHEDULE DOES INDICATE THE
 CIRCUITING FOR AC EQUIPMENT ETC HOWEVER NO OTHER
 EQUIPMENT IS SHOWN BEING FED FROM THIS PANEL.
 WHERE IS ALL OF THE OTHER EQUIPMENT BEING FED FROM?
 CIRCUITS? LOADS? ETC
 408.4,310.16,240.3,220, ETC
 645 (ALL)
  
 36) NOTE: PLEASE PROVIDE INFORMATION ON THE EPO AT THE
 DOOR FOR IT ROOM.
 PLEASE SEE 645.10 FOR THE REQUIRED DISCONNECTING MEANS
 TO ALL EQUIPMENT INCLUDING AC EQUIPMENT.
 THERE IS A CIRCUIT ON 1LED-27 FOR SHUNT TRIP CIRCUIT
 HOWEVER THE IT PANEL OR FEED TO IT PANEL DOES NOT
 INDICATE ANY SHUNT TRIP TYPE MAIN BREAKER OR BRANCH
 BREAKER. THE RISER DOES NOT INDICATE A SHUNT FOR ANY OF
 THE MAIN BREAKERS OR FEEDERS.
 PLEASE PROVIDE INFORMATION AND DETAIL FOR THIS.
  
 37) NOTE: PLEASE SEE 4LEB-10 WHICH IS SHOWN AS SPARE ON
 PANEL SCHEDULE YET THE PLANS STILL INDICATE THIS
 CIRCUIT.
  
 38) NOTE: PLEASE SEE 4IT 15,17 ON PANEL SCHEDULE THIS
 IS SHOWN TO RM A4.416 YET THE PLANS DO NOT INDICATE
 THIS.
  
 39) NOTE: PLEASE SEE 4LD2- 5 STATES RECEPTACLES IN ROOM
 4-106 HOWEVER THIS IS SHOWN ON PLANS FEEDING OTHER
 AREAS ALSO.
  
 40) NOTE: PLEASE SEE 4LC2-13 WHICH IS SHOWN ON PANEL TO
 ROOM A4-201 HOWEVER ON PLANS THIS IS LOCATED AT THE
 OTHER END OF THE FLOOR.
  
 41) NOTE: PLEASE SEE 4LC3-9 AND 25 WHICH IS SHOWN TO
 ROOM/AREA C4.202 YET THE PANEL SCHEDULE INDICATES ONE
 OF THESE FOR THIS LOCATION AND ONE OF THESE FOR A
 DIFFERENT LOCATION. THERE IS ALSO THE FACT THE J-BOX IS
 ALSO FED FROM THE ONE OF THESE CIRCUITS WHICH IS #25.
 IS THIS CORRECT FOR THE J-BOX?
  
 42) NOTE: PLEASE SEE 4LD3-3, 22 AS BOTH ARE SHOWN ON
 PLANS, HOWEVER PLEASE SEE THAT THE PANEL SCHEDULE FOR
 22 IS BLANK.
  
 43) NOTE: PLEASE SEE MULTIPLE SETS OF FURNITURE WORK
 STATIONS WHICH SHOW THE SAME CIRCUITING SUCH AS
 5LA3-21, 23. PLEASE SEE 220.14(I) FOR LOADS PER YOKE.
 PLEASE PROVIDE INFORMATION ON HOW MANY RECEPTACLES ARE
 ON THE CIRCUITS AS SHOWN FOR KNOWN LOADS. THIS WAS GONE
 OVER IN ORIGINAL REVIEW EVEN BEFORE PERMIT ISSUANCE FOR
 KNOWN LOADS AND LOADS FIGURED AT 180VA. THE REVIEW
 COMMENTS CAN BE PROVIDED ALONG WITH E-MAILS IN WHICH
 QUESTIONS WERE RAISED.
  
 44) NOTE: PLEASE SEE 5LA2- 34 WHICH ON THE PANEL
 SCHEDULE IT STATES ELECTRICAL ROOM A5.107 RECEPTACLES.
 HOWEVER THE PLANS SHOW A COMPLETELY DIFFERENT CIRCUIT
 WHICH FEEDS MANY OTHER LOCATIONS. THE CIRCUIT ON PLANS
 FOR THIS ROOM IS NOT #34. SEE THE FOLLOWING COMMENT.
  
 45) NOTE: PLEASE SEE 5LA2-3 ON PANEL SCHEDULE WHICH
 STATES CORRIDOR LIGHTING. HOWEVER ON PLANS THIS FEEDS
 ROOM ABOVE WHICH IS A5.107, 5.103,5.104,203 ETC
  
 46) NOTE: PLEASE SEE A1.014 ON PLANS SHOWS HA-1 HOWEVER
 THE DESIGNATION ON PANEL SCHEDULE IS NOT THE SAME.
 SHOWS A DIFFERENT ROOM.
  
 47) NOTE: PLEASE SEE 1HA-12 ON PLANS AND PANEL SCHEDULE
 HOWEVER THIS IS NOT PART OF THE LCP.
  
 48) NOTE: PLEASE SEE 410.8 A-D FOR MINIMUM LIGHTING
 FIXTURE CLEARANCES FROM COMBUSTIBLES IN CLOSETS WITH
 SHELVING. PLEASE SEE STORAGE CLOSETS A1.612,613.14.
 PLEASE PROVIDE EXACT SHELVING DIMENSION ON PLANS SO
 THAT THE CLEARANCES CAN BE DETERMINED.
  
 49) NOTE: PLEASE SEE 1HA-2 WHICH THE PLANS , THE PANEL
 SCHEDULE AND THE LCP DO NOT CORRELATE. THE CIRCUITING
 ON PLANS SHOWS ONE LOCATION/ROOM WHICH IS THE GALLERY
 A1.306 YET THE PANEL STATES THIS CIRCUIT IS FOR
 EXTERIOR FIXTURES. THE LCP DOES NOT INDICATE ANY OF
 THESE.
  
 50) NOTE: PLEASE REVISE FIXTURE SCHEDULE AND SUBMIT.
 FIXTURES FOR EXISTING LOCATION AND REVISED LOCATIONS ON
 PLANS CAN NOT BE DETERMINED AS CODE COMPLIANT WITH THE
 EXISTING REVISED CALCULATIONS PER 13-415.2.
  
 51) NOTE: PLEASE SHOW LOCATIONS OF REQUIRED OVER RIDES
 ON THE 3RD FLOOR EAST END OF LIBRARY. REVISION 17
 DELETED THE REQUIRED OVER RIDES BASED ON
 FURNITURE/SHELVING LAYOUT. ALL REVISED PLANS UP TO THIS
 LATEST REVISION STILL INDICATE EACH OF THE CIRCUITS
 WILL GO TO OVER RIDE SWITCHES HOWEVER NEW LOCATIONS
 WERE NOT SHOWN.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 OF THE FBC. LOCATION
 REQUIRES THE OCCUPANT TO SEE ALL LIGHTING WHICH IS
 BEING OVER RIDDEN OR MEET EXCEPTIONS.
  
 52) NOTE: PLEASE UPDATE ALL LCP. MANY OF THESE DO NOT
 LIST THE CIRCUITS ON THE PANEL SCHEDULES OR THE
 LOCATIONS LISTED ARE NOT CORRECT.
  
 53) NOTE: PLEASE SEE 1HC-19 AS THIS IS ON PLAN AND
 SCHEDULE HOWEVER NOT ON LCP.
  
 54) NOTE: PLEASE SEE LOBBY D1.003 WHERE ARE THE LIGHTS
 WHICH IS NOT PART OF THE PHOTO MUSEUM? FBC CHAPTER 10,
 NFPA- 101 7.8, 7.9.
 NEC CHAPTERS 2,3,4, GIVEN AS GENERAL SECTIONS.
 PLANS ARE BLANK.
  
 55) NOTE: PLEASE SEE C1.102 AS THERE IS NO CIRCUIT
 LISTED OR SHOWN FOR LIGHTING. WHERE DOES THIS
 INTERCONNECT AND WITH WHICH CIRCUIT?
  
 56) NOTE: PLEASE SEE 2HA-12 WHICH IS NOT SPECIFIC TO
 ROOMS AND AREAS.
  
 57) NOTE: PLEASE SEE 2HA-19 WHICH IS ON PLANS, ON PANEL
 SCHEDULE HOWEVER LCP IS BLANK AND DOES NOT INDICATE.
  
 58) NOTE: PLEASE SEE A2.210 AND .211 ROOMS. WHERE DO
 THE LIGHTS IN THESE TWO ROOMS CONNECT? THE PLANS APPEAR
 TO MAYBE CONNECT TO 2HA-47 HOWEVER BASED ON THE PANEL
 SCHEDULE THESE TWO ROOMS ARE NOT LISTED.
  
 59) NOTE: PLEASE SEE 3HA-16 WHICH IS SHOWN ON PLANS,
 YET THERE IS NOTHING ON PANEL SCHEDULE OR LCP.
  
 60) NOTE: PLEASE SEE 3HA-6 STATES ON THE PANEL SCHEDULE
 THIS FEEDS A3.009 AND A3.402 YET THE PLANS INDICATE
 A3.402 BEING FED FROM 3HA-8. PLEASE SEE OTHER LOCATIONS
 NOT SPECIFIC.
  
 61) NOTE: PLEASE 3HA-8 WHICH IS NOT SPECIFIC.
  
 62) NOTE: PLEASE COMPLETE PLANS WITH CIRCUITING, LOADS
 AND LIGHTING FOR STAGE AREA LIGHTING. PLANS SHOW *TO BE
 BY OTHERS* HOWEVER THAT WAS WHEN NONE OF THAT
 INFORMATION WAS KNOWN. THIS IS THE END OF THE BUILDING
 ALL OF THE LIGHTING, CIRCUITING, LOADS ETC ARE KNOWN AT
 THIS TIME WHICH NEEDS TO BE COMPLETE ON PLANS.
 220,13-415.1.ABC.1.1, .1.3 ETC
  
 63) NOTE: PLEASE SEE AREAS C3.110,.109,0309 ETC. THE
 NORMAL LIGHTING IN THIS AREA DOES NOT HAVE ANY CIRCUIT
 NOTED OR SHOWN.
  
 64) NOTE: PLEASE SEE E2-4.1, LIGHTS IN CORRIDOR A4.009
 WHICH DOES NOT INDICATE ANY CIRCUITING FOR NORMAL
 LIGHTING??
  
 65) NOTE: PLEASE SEE 4HC-12 WHICH IS LISTED ON THE LCP
 HOWEVER NOT ON PANEL SCHEDULE.
  
 66) NOTE: PLEASE SEE 4HC-2 WHICH IS ON SCHEDULE FOR
 LIGHTING IN ELEVATOR LOBBY 5 AND 6; HOWEVER THIS SAME
 LOBBY AREA DOES NOT HAVE ANY CIRCUIT FOR THE LIGHTING
 ON PLANS. IN FACT THE LIGHTING ON PLANS IS ALL SHOWN AS
 EMERGENCY CIRCUITED LIGHTING HOWEVER NO CIRCUIT OR
 CONNECTION TO OTHER CIRCUITS IS SHOWN.
 THE CIRCUIT 4HC-2 ON PLANS IS ONLY FEEDING THE C4.105
 ROOM AND ALSO THE TWO BATHROOMS C4.102,.103 WHICH DOES
 NOT COORDINATE WITH THE PANEL SCHEDULE.
  
 67) NOTE: PLEASE SEE 4HC-10 WHICH IS ON PANEL SCHEDULE
 HOWEVER ON LCP.
  
 68) NOTE: PLEASE SEE 5HA-3 WHICH IS LISTED ON THE LCP
 HOWEVER IT IS NOT ON THE PANEL SCHEDULE. ** PLEASE SEE
 THIS SHEET OF PLANS. E2-5.1, GO OVER PLANS. SEE
 COMMENTS BELOW.
  
 69) NOTE: PLEASE SEE 5HA-17 WHICH STATES * OPEN WORK
 AREA A5.404 HOWEVER ON THE PLANS THIS IS COMPLETELY
 SEPARATE. A5.112,.104,.103.
  
 70) NOTE: PLEASE SEE AREAS OF NORMAL LIGHTING A5.507,
 .506, .504,.501,.528,.503,.505,.508 ETC WHICH DO NOT
 SHOW ANY CIRCUITING ON PLANS.
  
 71) NOTE: PLEASE SEE 5HB-5 WHICH IS SHOWN ON PLANS, YET
 THIS IS SHOWN AS A SPARE ON PANEL SCHEDULE.
  
 72) NOTE: FEE BALANCE OF $1160.00 IS DUE BEFORE PICKING
 UP PLANS AND RESUBMITTING NEW REVISIONS.
  
  
 **** THIS IS NOT AN EXHAUSTED LIST OF ALL POSSIBLE
 ITEMS. THESE HAVE BEEN GIVEN AS EXAMPLES ONLY! THESE
 ARE NOT ALL ITEMS.
  
  
  
  
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 42 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By dpalmer Date 2009-06-02 Time 11:25 Sent To  
Notes
2009-06-10 11:25:25 
  
2009-06-04 17:13:10REVIEW IN PROGRESS.
  
 DUE TO FOUR DAY WORK WEEK, REVIEW TO BE COMPLETED ON
 TUESDAY 6/9/09. REVIEW WILL BE GOING INTO FAILED STATUS
 FOR ALL SHEETS. NOTES TO BE POSTED UPON COMPLETION.
2009-06-01 12:17:13REVIEW FEES TO DETERMINED BY THE BUILDING OFFICIAL.

Review Stop E ELECTRICAL
Rev No 41 Status F Date 2009-03-30 Cont ID  
Sent By dpalmer Date 2009-03-30 Time 16:49 Rev Time 0.00
Received By dpalmer Date 2009-03-30 Time 16:49 Sent To  
Notes
2009-03-30 16:49:56** DENIED REVIEW/PASSED PROVISO **
  
 REVISION FOR CAF??
  
  
  
 1) NOTE: SHEET E1-1.2 STAMPED FOR INSPECTIONS OF LAYOUT
 OF ELECTRICAL ONLY.
 NO OTHER ITEMS ON THIS SHEET REVIEWED FOR CODE
 COMPLIANCE.
  
 2) NOTE: PLANS SHOW THE LOCATION OF NEW PANEL HOWEVER
 THE NEW TRANSFORMER AND MAIN ON THE LOAD SIDE OF THE
 TRANSFORMER NEEDS TO BE SHOWN. COMPLIANCE WITH 110.26,
 240.24, 240.21, 450.9, ETC CAN NOT BE REVIEWED AT THIS
 TIME.
 RISER NOTES STATES PANEL TO BE LOCATED IN ROOM C1.402
 HOWEVER BASED ON SHEET E1-1.2 THE PANEL IS NOT IN THIS
 SAME ROOM/LOCATION.
 PLEASE BE SURE TO COORDINATE ALL SHEETS.
 SHEET REDLINED.
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 40 Status F Date 2009-03-17 Cont ID  
Sent By dpalmer Date 2009-03-17 Time 09:40 Rev Time 0.00
Received By dpalmer Date 2009-03-17 Time 09:40 Sent To PC
Notes
2009-03-17 09:40:55** NOTES REDLINED ** REVISIONS DENIED
  
  
 1) NOTE: COORDINATION STUDY OVER ALL IS OK AND MEETS
 CODE FOR 700 AND 701 SYSTEMS.
 THERE ARE OVER LAPS SHOWN ON THE TIME CURVE
 COORDINATION STUDY BASED ON ALL TRANSFORMERS WHICH IS
 TYPICAL PER ENGINEER. THERE IS ALSO OVERLAPPING ON TWO
 BREAKERS ON THE OPTIONAL STAND-BY SYSTEM. THESE
 BREAKERS ARE RATED FOR THE AVAILABLE FAULT CURRENT
 HOWEVER THEY ARE NOT SELECTIVELY COORDINATED. THE CODE
 DOES NOT ADDRESS OPTIONAL STAND-BY FOR SELECTIVE
 COORDINATION. THIS IS EQUIPMENT WHICH IS NOT LIFE
 SAFETY/EMERGENCY OR LEGALLY REQUIRED STAND-BY.
  
 2) NOTE: THE REVISED PLANS ARE BEING SENT BACK AS ALL
 CIRCUITING ON PLANS AND PANEL SCHEDULES NEED TO
 COORDINATE BEFORE THE FINAL CO OF BUILDING. AS THERE
 ARE STILL SEVERAL CIRCUITS ON PANELS AND PLANS WHICH
 HAVE NOT BEEN UPDATED THIS NEEDS TO BE DONE. BASED ON
 THE CIRCUITING OF THE POWER PLANS AND LIGHTING PLANS
 THERE ARE CIRCUITS FOR EXAMPLE SHOWN AS LIGHTING WHICH
 ON THE PANEL SCHEDULE THEY ARE MOTOR CONTROL CENTERS?
 THE REVIEW WILL REMAIN IN FAILED STATUS BASED ON THE
 REVISED PLANS STILL NEEDING TO BE FINALIZED.
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 39 Status N Date 2009-03-05 Cont ID  
Sent By dpalmer Date 2009-03-05 Time 11:25 Rev Time 0.00
Received By dpalmer Date 2009-03-05 Time 11:24 Sent To  
Notes
2009-03-05 11:26:35 
 **REVIEW STATUS *N*. ( NOT NEEDED)
 REVISIONS FOR BASE BUILDING SITE, LANDSCAPE,
 CROSS-WALK, ETC
  
 ALL RIGHT OF WAY ELECTRICAL SHALL BE UNDER SEPARATE
 PERMIT AND MAY NOT BE PART OF THE BASE BUILDING
 PERMITTED SCOPE OF WORK. THIS WORK HAS ALREADY BEEN
 APPLIED FOR BY MISNER ELECTRIC. PERMIT #08120587
 ALL ELECTRICAL SHOWN ON LANDSCAPE PLANS CONTAINS A NOTE
 WHICH STATES TO SEE ELECTRICAL PLANS FOR ACTUAL SCOPE
 OF WORK UNDER THE BASE BUILDING.
 ALL SITE LIGHTING POLES WHICH IS LOCATED IN THE RIGHT
 OF WAY AREAS ARE ACTUALLY UNDER SEPARATE APPLIED SITE
 RIGHT OF WAY APPLICATION WHICH BY THE WAY IS NOT YET
 ISSUED. PERMIT # 08120587
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 38 Status N Date 2009-01-30 Cont ID  
Sent By dpalmer Date 2009-01-30 Time 12:32 Rev Time 0.00
Received By dpalmer Date 2009-01-30 Time 12:32 Sent To PC
Notes
2009-01-30 12:32:51SITE WORK, IR AND L SHEETS DID NOT CONTAIN ANY
 ELECTRICAL FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 37 Status F Date 2009-01-08 Cont ID  
Sent By dpalmer Date 2009-01-08 Time 16:13 Rev Time 0.00
Received By dpalmer Date 2009-01-08 Time 16:13 Sent To  
Notes
2009-01-08 16:13:47***** REVISIONS SUBMITTED 12/18/08
  
 1) NOTE: LOADS FOR NEW PANELS HAVE NOT BEEN INCREASED
 IN SEVERAL LOCATIONS.
 FOR EXAMPLE: NEW PANELS FOR 1HD, 2HDR, 2LDR ETC ALL THE
 WAY TO MSB1.
 THIS REQUIRES A MINIMUM FOR SPACE WHICH IS NOW KNOWN TO
 BE FUTURE OFFICE SPACE. SEE 220.12,220.14 ETC
 PLEASE SEE OTHER EQUIPMENT FOR EXAMPLE 1-DPHC WHICH HAS
 NOT BEEN REVISED SINCE REVISION 12A. IF IT HAS BEEN
 REVISED IT HAS NOT BEEN SUBMITTED.
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 36 Status F Date 2009-01-08 Cont ID  
Sent By dpalmer Date 2009-01-08 Time 16:13 Rev Time 0.00
Received By dpalmer Date 2009-01-08 Time 16:13 Sent To  
Notes
2009-01-08 16:13:30** DENIED REVIEW OF REVISIONS**
  
 ** REVISIONS SUBMITTED 12/11/2008
  
  
  
  
  
 1) NOTE: ALTHOUGH NOT REQUIRED IT IS VERY HELPFUL IN
 THE REVIEW PROCESS TO SUBMIT A DETAIL LETTER/LISTING OF
 ITEMS REVISED ON SHEETS.
 SEE NOTES WITH RESPECT TO IDENTIFICATION AND
 COORDINATION OF THE REVISION IN THE TITLE BLOCKS, THE
 REVISIONS ON PLANS. WHEN PLANS DO NOT INDICATE THE
 REVISION OR VISE VERSA THEY ARE NOT NOTED ON TITLE
 BLOCK THE ENTIRE SHEET NEEDS TO BE REVIEWED AND
 COMPARED TO RECORD PLANS.
  
 2) NOTE: THIS IS NOTED WITH RESPECT TO ORIGINAL PLANS
 SUBMITTED AND ISSUED FOR PERMITTING OF THE PROJECT. A
 PROVISO WAS ISSUED AND GRANTED GIVING THE PROJECT THE
 ABILITY TO MOVE FORWARD TO CONSTRUCTION. THERE ARE
 STILL SHEETS WHICH CONTAINED REDLINED ITEMS WHICH NEED
 CORRECTIONS FROM FEBRUARY OF 2007 WHICH HAVE NOT YET
 BEEN REVISED OR ADDRESSED.
 PLEASE SEE SOME EXAMPLE SHEETS SUCH AS
 9-1.0,9-1.2,9-3.2,9-4.2 ETC.
 NOW THAT THE PROJECT IS ALMOST COMPLETE IT IS EXPECTED
 THAT THESE SHEETS ALONG WITH THE MANY OTHERS CONTAINING
 REVISIONS ARE REVISED, SUBMITTED FOR REVIEW BEFORE
 FINAL INSPECTIONS.
  
 3) NOTE: PLEASE SEE SHEET E1-1.2 AS THIS DOES NOT
 CONTAIN REVISION #168. THIS WAS ALSO NOT ON PREVIOUS
 REVISIONS WHICH WERE STAMPED IN ERROR.
 NEC ALL AS THE REVISION IS NOT SHOW SPECIFIC CODE
 SECTION CAN NOT BE GIVEN.
 FBC 106.5 RECORD PLANS AND COORDINATION
 SHEETS STILL SHOWING LIGHTING WHICH IS IN RIGHT OF WAY
 AREA.
  
 4) NOTE: PLEASE SEE SHEET E 5-1.0 WHICH CONTAINED 23A
 ON PLANS HOWEVER NOT IDENTIFIED BY THE TITLE BLOCK.
 FBC 106.1.1, 106.5 AS NOTED ABOVE.
  
 5) NOTE: PLEASE SEE 6-1.0 AS NO REVISION #18 IS ON
 PLANS YET SHOWN ON TITLE BLOCKS.
 FBC 106.1.1, 106.5 AS NOTED ABOVE ON PLANS.
  
 6) NOTE: PLEASE SEE 6-7.0 NO REVISION 168, AND NOT ON
 PREVIOUS PLANS.
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 35 Status P Date 2008-12-22 Cont ID  
Sent By dpalmer Date 2008-12-22 Time 14:52 Rev Time 0.00
Received By dpalmer Date 2008-12-22 Time 14:52 Sent To  
Notes
2008-12-22 14:54:20REV FROM 11/19 STILL IN NEED OF ADDRESSING.
  
 THIS REVISION FOR SITE LIGHTING. RIGHT OF WAY FIXTURES
 SHOWN SHALL BE CIRCUITED FROM CITY STREET ELECTRICAL
 AND NOT BUILDING. SITE LIGHTING FROM CITY CENTER
 PROPERTY IS FED FROM BUILDING.
  
  

Review Stop E ELECTRICAL
Rev No 34 Status F Date 2008-11-19 Cont ID  
Sent By dpalmer Date 2008-11-19 Time 08:08 Rev Time 0.00
Received By dpalmer Date 2008-11-19 Time 08:08 Sent To  
Notes
2008-11-19 08:08:35** FAILED REVIEW **
  
 ** REVISION 21A
  
 1) NOTE: LOADS FOR NEW PANEL 1LF1 NEED TO BE ADDED TO
 ALL PANELS INCLUDING MSBI.
 220
 FBC 106.5
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 33 Status F Date 2008-11-10 Cont ID  
Sent By dpalmer Date 2008-11-10 Time 14:31 Rev Time 0.00
Received By dpalmer Date 2008-11-10 Time 14:31 Sent To PC
Notes
2008-11-10 14:31:17 
  
  
 ** DENIED REVISION **
  
 1) NOTE: PLEASE SUBMIT THE RIGHT OF WAY STREET LIGHTING
 UNDER A SEPARATE PERMIT. THESE ARE NOT PART OF THE BASE
 BUILDING LEGAL ADDRESS OR ELECTRICAL SYSTEMS.
 PLEASE BE SURE THE FIXTURE INFORMATION ON PLANS IS
 COMPLETE WITH THE TYPE OF FIXTURE, THE WATTAGE, THE
 VOLTAGE ETC. THE PLANS CONTAIN NOTES WHICH STATE
 RECEPTACLES ON POLE HOWEVER NO DETAIL IS SHOWN ON HOW
 THESE WILL INSTALLED OR WIRED. ARE THESE APART OF THE
 POLE FROM THE MANUFACTURE?
 215,300,310.16,110.3,240.4, ETC
 FBC 105.1.
  
 2) NOTE: THE PLANS WERE NOT ROUTED TO THE BUILDING PLAN
 REVIEWER AS NO WIND LOAD INFORMATION/CALCULATIONS WERE
 SUBMITTED FOR REVIEW. IN THE INTEREST OF TIME THIS
 REVIEWER IS ONLY PLACING NOTES FOR INFORMATION WHICH
 WILL BE NEEDED FOR THE STRUCTURAL REVIEW. THE WIND LOAD
 CALCULATIONS NEED TO SHOW THE POLE, STRUCTURAL
 COMPONENTS, THE EPA (EFFECTIVE PROJECTED AREA) OF THE
 FIXTURE OR FIXTURES. THESE WILL NEED TO BE COMPLETE
 WITH TITLE BLOCKS, ORIGINAL SIGNATURE, DATE AND RAISED
 SEAL BY A FLORIDA LICENSED AND REGISTERED ENGINEER.
 FBC TABLE 1609
 FS 471.025
 FAC 61G15-23.002
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 32 Status P Date 2008-11-04 Cont ID  
Sent By dpalmer Date 2008-11-04 Time 11:13 Rev Time 0.00
Received By dpalmer Date 2008-11-04 Time 11:13 Sent To  
Notes
2008-11-04 11:15:27REV 20A FOR E1-1.0, E1-1.1.3.
  
  
 REDLINED SITE AS NO LIGHTING FIXTURES SHALL BE
 INSTALLED IN RIGHT OF WAY FED FROM BUILDING. ALL RIGHT
 OF WAY LIGHTING IS TO BE FED FROM CITY STREET
 ELECTRICAL SYSTEMS UNLESS RIGHT OF WAY CHANGES. RIGHT
 OF WAY FIXTURES ARE NOT PART OF THE BASE BUILDING
 PERMIT SCOPE. THIS WAS REDLINED AND NOTED BACK ON
 ORIGINAL REVIEWS/PLANS/MEETINGS.
 ** IF FIXTURES AS SHOWN ARE WITHIN PROPERTY LINES THEN
 THIS COMMENT IS ONLY NOTED FOR INFORMATION.

Review Stop E ELECTRICAL
Rev No 31 Status P Date 2008-10-29 Cont ID  
Sent By dpalmer Date 2008-10-29 Time 16:56 Rev Time 0.00
Received By dpalmer Date 2008-10-29 Time 16:56 Sent To PC
Notes
2008-10-29 16:57:31REVISED TO ADD EM FIXTURES IN MEETING ROOM/LIB SIDE.

Review Stop E ELECTRICAL
Rev No 30 Status P Date 2008-10-21 Cont ID  
Sent By dpalmer Date 2008-10-21 Time 12:21 Rev Time 0.00
Received By dpalmer Date 2008-10-21 Time 12:21 Sent To PC
Notes
2008-10-21 12:21:16REV 18

Review Stop E ELECTRICAL
Rev No 29 Status P Date 2008-10-21 Cont ID  
Sent By dpalmer Date 2008-10-21 Time 09:10 Rev Time 0.00
Received By dpalmer Date 2008-10-21 Time 09:10 Sent To PC
Notes
2008-10-21 09:10:58REVISED LIGHTING PLANS, 2ND, 3RD AND 4TH FLOOR. CA
 225-C

Review Stop E ELECTRICAL
Rev No 28 Status P Date 2008-10-21 Cont ID  
Sent By dpalmer Date 2008-10-21 Time 09:09 Rev Time 0.00
Received By dpalmer Date 2008-10-21 Time 09:09 Sent To  
Notes
2008-10-21 09:10:17REV FOR 16B OK, REVISED SITE LIGHTING SHEET AND
 PHOTO-METRICS

Review Stop E ELECTRICAL
Rev No 27 Status P Date 2008-09-30 Cont ID  
Sent By dpalmer Date 2008-09-30 Time 08:04 Rev Time 3.00
Received By dpalmer Date 2008-09-30 Time 08:04 Sent To PC
Notes
2008-09-30 08:06:08REV 17B
  
  
 REDLINED, NO TRIPPING HAZARDS IN MAIN ELECTRICAL ROOM
 AS NOTED ON ORIGINAL REVIEWS.
  
 REDLINED SHEET E-7.7.0 AS THE SCOPE OF WORK SHOWN NEEDS
 TO BE UNDER A SEPARATE PERMIT. THIS SCOPE FOR VIDEO
 SYSTEM IN COMMISSION CHAMBERS WAS NOT PART OF ORIGINAL
 PLANS.
  
  

Review Stop E ELECTRICAL
Rev No 26 Status N Date 2008-09-16 Cont ID  
Sent By dpalmer Date 2008-09-16 Time 15:50 Rev Time 0.00
Received By dpalmer Date 2008-09-16 Time 15:50 Sent To PC
Notes
2008-09-16 15:57:25 
 *** NO REVIEW DONE ON ELECTRICAL PLANS WHICH WERE
 SUBMITTED ON AUGUST 21ST. AT THE REQUEST OF THE
 CONTRACTOR THE PLANS WERE PLACED ON HOLD SO THAT NEW
 SHEETS COULD BE INSERTED. CONTRACTOR?S REP?S CAME IN
 (ROY AND AMADU) AND PLACED NEW RISER SHEETS IN PLANS.
 AT THAT TIME IT WAS DISCOVERED OTHER SHEETS WERE NEEDED
 BASED ON REVISED CIRCUITING FOR SMOKE DETECTORS AND
 PANEL SCHEDULES. ALSO POSSIBLE COMMENTS FROM MECHANICAL
 REVIEWER/INSPECT WHICH MAY HAVE NEEDED PLANS TO CHANGE.
 PLANS WERE ONCE AGAIN PLACED ON HOLD. ON 9/16 I CALLED
 FRANK FROM CATALFUMO AND REMINDED THAT THE PLANS WERE
 STILL ON HOLD AND THAT WOULD NO LONGER KEEP PLANS AT MY
 DESK. PLANS WILL BE OUT FRONT UNDER *C* IN THE LARGE
 BINS WAITING FOR NEW REVISED SHEETS.
  
 IF THERE ARE QUESTIONS PLEASE CALL:
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 25 Status P Date 2008-09-10 Cont ID  
Sent By dpalmer Date 2008-09-10 Time 09:57 Rev Time 0.00
Received By dpalmer Date 2008-09-10 Time 09:57 Sent To PC
Notes
2008-09-10 10:00:03REVISED FOURTH FLOOR LIGHTING FOR EMERGENCY BACK UP ON
 THE CITY HALL SIDE OF BUILDING.
 EMERGENCY BATTERY BACK UP FIXTURES ARE REQUIRED HOWEVER
 TYPE OF FIXTURES AND PLACEMENT IS NOT UNDER THE PLAN
 REVIEWERS DIRECTION.
 LIGTHING LEVELS EXCEED MINIMUMS WHICH IS OK.

Review Stop E ELECTRICAL
Rev No 24 Status P Date 2008-09-04 Cont ID  
Sent By dpalmer Date 2008-09-04 Time 11:10 Rev Time 0.00
Received By dpalmer Date 2008-09-04 Time 11:09 Sent To PC
Notes
2008-09-04 11:10:29REVISION FOR FITH FLOOR LIGHTING.

Review Stop E ELECTRICAL
Rev No 23 Status N Date 2008-07-25 Cont ID  
Sent By dpalmer Date 2008-07-25 Time 10:07 Rev Time 0.00
Received By dpalmer Date 2008-07-25 Time 10:07 Sent To B
Notes
2008-07-25 10:08:01LT POLE WIND LOAD CALCS SENT TO BUILDING REVIEWER FOR
 REVIEW.

Review Stop E ELECTRICAL
Rev No 22 Status P Date 2008-07-10 Cont ID  
Sent By dpalmer Date 2008-07-10 Time 17:09 Rev Time 0.00
Received By dpalmer Date 2008-07-10 Time 17:09 Sent To PC
Notes
2008-07-10 17:10:54REV 15C REDLINED

Review Stop E ELECTRICAL
Rev No 21 Status F Date 2008-07-10 Cont ID  
Sent By dpalmer Date 2008-07-10 Time 17:08 Rev Time 0.00
Received By dpalmer Date 2008-07-10 Time 17:08 Sent To PC
Notes
2008-07-10 17:09:13** DENIEDREVIEW OF REVISIONS **
  
 REV 17A
  
 1) NOTE: PLEASE PROVIDE REVISED LIGHTING PLANS FOR
 AREAS WHICH WILL BE OCCUPIED UNDER EMERGENCY
 CONDITIONS. ANY LOCATIONS SUCH AS CALL CENTER, IT
 TRAINING, IT ROOM ETC NEEDS TO CONTAIN BATTERY BACK UP
 FIXTURES OF SOME TYPE TO MEET 1FT CANDLE MINIMUM UNDER
 EGRESS CONDITIONS.
 LS 101 7.8, 7.9
  
 2) NOTE: PLEASE BE SURE THE LAYERS FOR SITE LIGHTING ON
 ALL SHEETS ARE ON TO SHOW REVISED CIRCUITING. SEVERAL
 FIXTURES WERE RELOCATED WHICH IS OK, HOWEVER COULD NOT
 LOCATE ANY OF THE NEW CIRCUITING ALONG WITH
 COORDINATION OF PANEL SCHEDULES.
 408.4.
 FBC 106.1.2, 106.1.1 FOR ADDITIONAL INFORMATION AND
 CLARITY OF PLANS.
  
 3) NOTE: PLEASE SEE E1-1.1 WHICH INDICATES RECEPTACLES
 IN THE FIRE COMMAND ROOM TO A PANEL 1LEG.HOWEVER NO
 PANEL 1LEG WAS SHOWN ON SUBMITTED. THIS MAY BE A
 MISPRINT FOR ANOTHER PANEL.
 NEC 408.4, 310.16 ETC
 FBC 106.1.1
  
 4) NOTE: PLEASE COMPLETE THE TRANSFORMER LEGEND FOR THE
 NEW 30KVA UNITS NOW ON PLANS. NO PRIMARY OR SECONDARY
 CONDUCTORS ARE NOTED OR SHOWN. SEE OTHER COMMENTS BELOW
 FOR OTHER NEW PANELS.
 310.16, 240.4, 240.21 ETC
 FBC 106.1.1
  
 5) NOTE: PLEASE SEE THE RISER WHICH INDICATES NEW
 TRANSFORMERS HOWEVER THEY DO NOT INDICATE NAY GROUNDING
 ELECTRODE SYSTEM FOR SEPARATELY DERIVED SYSTEMS AS PART
 OF THE EXISTING GROUNDING RISER.
 PLEASE REVISE AND ALSO INDICATE CONDUCTOR SIZES.
 250.20,250.30,250.66,250.58
 FBC 106.1.1, 106.1.2
  
 6) NOTE: PLEASE SEE THE RISER SHEET WHICH INDICATES NO
 LOADS ON THE EMERGENCY SYSTEMS. THESE ARE ACTUALLY
 SHOWN BLANK WITH XXX. PLEASE EXPLAIN HOW THE LOADS
 UNDER EMERGENCY ARE DIFFERENT THAN THE LOADS UNDER
 NORMAL AS SHOWN ON PREVIOUS PLANS. WHAT LOAD SHEDDING
 IS PROVIDED TO REDUCE LOADS?
 220, 700,701,702
 FBC106.1.2, 106.1.1
  
 7) NOTE: PLEASE SEE PANEL 1TV WHICH INDICATES THIS
 BEING FED FROM 1DPHEA, HOWEVER BASED ON REVISED PLANS,
 PANELS ETC THIS SHOULD INDICATE BEING FED FROM
 1DPHE-OP. PLEASE ADJUST
 FBC 106.1.1,
 NEC 408.4
  
 8) NOTE: PLEASE SEE 1TV WHICH INDICATES BRANCH AS
 EMERGENCY/ LIFE SAFETY. PLEASE ADJUST AS THIS IS AN
 OPTIONAL STAND-BY PANEL.
 702, 408
 FBC 106.1.1
  
 9) NOTE: PLEASE SEE PANEL 1TV WHICH IS SHOWN AS 100AMP
 YET THE CIRCUIT SHOWN ON 1DPHE-OP SHOWS A 150AMPS
 BREAKER FEED.
 THIS OVER CURRENT PROTECTION EXCEEDS THE RATING OF
 PANEL.
  
 10) NOTE: PLEASE SEE 1TV WHICH AS NOTED ABOVE IS SHOWN
 AS A 100AMP PANEL YET THE RISER SHOWS THIS SAME PANEL
 AS 225AMP.
 PLEASE COORDINATE.
 NEC 408, 215, 240 ETC
 FBC 106.1.1
  
 11) NOTE: PLEASE SEE 1DPHE-OP AS THE PANEL SCHEDULE IS
 BLANK FOR CONDUCTORS. PLEASE COMPLETE AS THERE ARE
 SEVERAL ITEMS WHICH NEED TO BE REVIEWED FOR CODE
 COMPLIANCE. PLEASE BE SURE TO SEE OTHER COMMENTS WITH
 RESPECT TO TRANSFORMER CONDUCTORS ON THE PRIMARY SIDE.
 240.21, 240.4, 310.16, ETC
 FBC 106.1.1
  
 12) NOTE: PLEASE SEE PANEL 1DPHE-OP WHICH INDICATES A
 LOAD OF 58AMP/20.9 KVA FOR 1LEDCC. HOW IS THIS AMPERAGE
 THE SAME AS SHOWN ON PANEL 1LEDCC WHEN THE VOLTAGE ON
 1LEDCC IS ACTUALLY 120/208 AND THE VOLTAGE ON 1DPHE-OP
 IS 277/480V?
 PLEASE COORDINATE AND ADJUST.
 FBC 106.1.1
 NEC 220, 408.4 ETC
  
 13) NOTE: PLEASE SEE PANEL SCHEDULE FOR 1LEDCC WHICH
 INDICATES BEING FED FROM 1HEE, YET THE PANEL 1HEE DOES
 NOT FEED THIS PANEL. SEE NOTE #12 ABOVE AS THIS PANEL
 IS FED FROM 1-DPHE-OP.
 408, 220 ETC
 FBC 106.1.1
  
 14) NOTE: PLEASE SEE PANEL 1HEE AS THE OVER CURRENT
 PROTECTION WHICH IS SHOWN ON PANEL TO FEED PANEL 1HED
 IS SHOWN AS 100AMP YET THE FEEDERS ARE ONLY SHOWN AS
 #8. THE #8 CONDUCTORS AS SHOWN ARE ONLY RATED FOR
 55AMPS BASED ON 310.16, 110.14
  
 15) NOTE: PLEASE SEE PANELS 1LETD, 2LETD, 1GHEE, 4IT2,
 1GLEE ETC WHICH ALL INDICATE THE PANELS BEING LOCATED
 ON THE FIRST FLOOR AND ALL LOCATED IN THE CALL CENTER.
 THE ELECTRICAL POWER PLANS CLEARLY ONLY SHOW ONE
 PANEL.
 PLEASE KNOW AS THE REVISED ELECTRICAL ROOMS HAVE NOT
 YET BEEN SUBMITTED REVIEW FOR CODE COMPLIANCE FOR
 LOCATIONS CAN NOT BE REVISED AT THIS TIME.
 PLEASE COORDINATE PANEL SCHEDULES WITH ACTUAL
 LOCATIONS.
 PLEASE SUBMIT REVISED PLANS TO SHOW THE LOCATIONS OF
 ALL PANELS.
 110.26, 240.24 ETC
 FBC 106.1.1
  
 16) NOTE: PLEASE SEE CALL CENTER A1.111 WHICH INDICATES
 CIRCUIT 1LED-33 YET THE PANEL SCHEDULE IS BLANK FOR
 THIS SAME CIRCUIT.
 REVISION 15A WHICH IS A SINGLE SHEET HAS THIS SAME ITEM
 HOWEVER WILL BE REDLINED. WILL NEED TO BE REVISED.
 408.4, 310.16, 240.4, 220.
 FBC 106.1.2, 106.1.1
  
 17) NOTE: PLEASE SEE 1HED WHICH THE SCHEDULE INDICATES
 THIS PANEL BEING FROM 1DPHEA YET 1DPHEA DOES NOT LIST
 THIS PANEL.
 PLEASE SEE 1HEE!!
 PLEASE COORDINATE.
 FBC 106.1.1
 NEC 408.4
  
 18) NOTE: PLEASE SEE SHEET 6-7.0 WHICH INDICATES A
 PANELLCP1D YET THE PANEL SHOWN IS 1LS1
 PLEASE COORDINATE PANELS, PLANS.
 NEC 408,
 FBC 106.1.1
  
 19) NOTE: PLEASE SEE 1GHEA WHICH IS SHOWN WITH TAPPED
 CONDUCTORS FROM ATS3 YET THE PANEL SCHEDULE FOR THIS
 PANEL 1GHEA INDICATES THIS PANEL AS MLO (MAIN LUG
 ONLY). THIS MAY NOT BE A MLO PANEL. PLEASE SEE 240.21,
 408.36, 240.4, 310.16 AS TAPPED CONDUCTORS ARE REQUIRED
 TO TERMINATE INTO OVER CURRENT PROTECTION.
 PLEASE REVISE AND ADJUST.
 FBC 106.1.1
  
 20) NOTE: PLEASE SEE PANEL SCHEDULE FOR 4IT WHICH
 INDICATES THIS AS AN EMERGENCY/LIFE SAFETY PANEL.
 PLEASE REVISE AND ADJUST.
 408.4, 700.1,701,702
 FBC 106.1.1 FOR COORDINATION.
  
 21) NOTE: PLEASE SEE PANEL 4IT WHICH INDICATES THIS
 PANEL BEING FED FROM 1HEE YET 1HEE DOES NOT LIST THIS
 PANEL.
 APPEARS TO BE A MISPRINT, PLEASE COORDINATE PLANS,
 PANELS ETC
 FBC 106.1.1
 NEC 408.4
  
 22) NOTE: PLEASE SEE CIRCUITING FOR LIGHTING IN TICKET
 BOOTH ROOM IN GARAGE WHICH ISMISSING A CIRCUIT.
 PLEASE SEE ONE CIRCUIT WHICH APPEARS TO BE NOTED TO ONE
 FIGURE IN ROOM IS 1GHA-22 YET THIS CIRCUIT ACTUALLY IS
 SHOWN ON THE PLANS AND PANEL SCHEDULE FOR CANOPY
 LIGHTS.
 PLEASE COORDINATE.
 408.4
 FBC 106.1.1
  
 23) NOTE: PLEASE VERIFY THE ACTUAL WORDING NOTED IN
 OCTAGONAL NOTE #1 FOR GARAGE ENTRANCE LIGHTS. THE NOTE
 MENTIONS LIGHTS TO BE OFF AT DUSK. SHOULD THIS NOT READ
 *ON* AT DUSK?
 PLEASE PROVIDE INFORMATION FOR INTENT.
 FBC106.1.1 FOR CLARITY AND 106.1.2 FOR ADDITIONAL
 INFORMATION.
  
 24) NOTE: AS NOTED ABOVE PLEASE INCLUDED LOCATIONS OF
 PANELS AND ALL NEW EQUIPMENT ON PLANS. PANELS SUCH AS
 1LETD, 2LETD, TAPPED CONDUCTORS ETC NEED TO BE VERIFIED
 FOR CODE COMPLIANCE.
 FBC 106.1.1 FOR CLARITY
 110.26, 240.24 ETC
  
 25) NOTE: PLEASE SEE E1-3.1 WHICH INDICATES REVISED
 CIRCUITS TO A PANEL 2LEDT WHICH APPEARS TO BE A
 MISPRINT FOR WHAT SHOULD BE PANEL 2LETD.
 PLEASE SEE ROOMS A3.116, A4.3.14
  
 26) NOTE: PLEASE LABEL NEW CU (CONDENSING UNITS) ON
 ROOF.
 CU#1, CU#2 ETC.
 FBC 106.1.1 FOR CLARITY ON PLANS AND 106.1.2 FOR
 ADDITIONAL INFORMATION.
  
 27) NOTE: PLEASE REVISE AND COMPLETE ALL PANEL
 SCHEDULES FOR CIRCUITS TO SPECIFIC ROOMS AND
 LOCATIONS.
 PLEASE KNOW THAT LISTING *STAIRWELL LIGHTING*IN LIEU
 OF STAIRWELL #1, STAIRWELL #5, #7 ETC WAS PERMITTED AND
 OK ON INITIAL PLANS AS CIRCUITS WOULD BE REVISED ALONG
 THE PROJECT. HOWEVER PLEASE KNOW THAT ALL PANEL
 SCHEDULES NEED TO BE REVISED FOR THESE CIRCUITS AS WELL
 AS OTHERS WHICH LIST ONLY A GENERIC DESIGNATION. THE
 DESIGNATION MAY BE ALPHA OR NUMERIC HOWEVER THIS
 DESIGNATION NEEDS TO BE THE ACTUAL DESIGNATION ON
 PLANS.
 408.4 **SEE HANDBOOKS WHICH STATES GENERIC *LIGHTS* OR
 *RECEPTACLES* IS NOT ACCEPTABLE.
 FBC 106.1.1, 106.1.2, 106.5
  
 28) NOTE: PLEASE VERIFY HOW REVISION 15A IS ACTUALLY A
 REVISION WHICH IS AFTER REVISION 17.REVISION 15
 SHEETS HAVE BEEN REDLINED AND NEED TO HAVE REVISION
 NUMBERS COORDINATED.
  
  
 ** THE SHEETS FOLLOWING ARE LISTED AT THIS TIME AS OK,
 HOWEVER BASED ON NOTES ABOVE FOR BACK UP LIGHTING NEED
 ETC SOME OF THESE SHEETS MAY NEED TO BE REVISED.
 PLEASE KNOW THAT ANY OF THESE SHEETS WHICH MAY NOT NEED
 TO BE REVISED SHOULD BE TURNED BACK IN WITH OTHER
 REVISED SHEETS WHICH ARE ADDRESSING COMMENTS ABOVE.
  
 ** IF THERE ARE ANY QUESTIONS ON HOW THIS NEEDS TO TAKE
 PLACE, PLEASE DO NOT HESITATE IN CONTACTING THIS
 OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 20 Status P Date 2008-06-02 Cont ID  
Sent By dpalmer Date 2008-06-02 Time 14:21 Rev Time 0.00
Received By dpalmer Date 2008-06-02 Time 14:21 Sent To PC
Notes
2008-06-02 14:22:04REV FOR RECEPTS ON FLOORS ONLY.
 PREVIOUS REVIEW COMMENTS STILL IN EFFECT.

Review Stop E ELECTRICAL
Rev No 19 Status F Date 2008-05-05 Cont ID  
Sent By dpalmer Date 2008-05-05 Time 19:53 Rev Time 0.00
Received By dpalmer Date 2008-05-05 Time 19:52 Sent To  
Notes
2008-05-05 19:53:11** PROVISO **
  
 ** THE BELOW IS TO HAVE PLANS REVISED AS SOON AS
 POSSIBLE. ANY INSTALLATIONS AND INSPECTIONS ARE AT
 RISK. PLANS ARE CODE COMPLIANT AT THIS TIME ****WITHOUT
 ANY NORMAL OCCUPANCY *** UNDER GENERATOR POWER.
  
  
 1) NOTE: THIS REVIEWER ALONG WITH THE FIRE MARSHAL IS
 ONCE AGAIN STATING THE FACT THAT ALL LOCATIONS IN
 BUILDING WHICH MAY BE IN USE UNDER EMERGENCY POWER AS A
 NORMAL OCCUPANCY. THERE ARE SEVERAL LOCATIONS WHICH ARE
 ALREADY KNOWN TO THIS OFFICE WHICH WILL REQUIRE BATTERY
 BACK UP FIXTURES TO MEET MINIMUM LIGHTING LEVELS UNDER
 THE LIFE SAFETY CODE 7.8 AND 7.9.
 PLANS STILL NEED TO BE REVISED TO INCLUDE THE NEW
 FIXTURES FOR ALL AREAS. PLANS ARE STAMPED REVIEWED FOR
 INSPECTIONS OF OTHER AREAS OTHER THAN KNOWN LOCATIONS.
 THIS WILL BE AT CONTRACTOR RISK FOR ALL LOCATIONS
 INCLUDING ANY NEW AREAS ADDED. PLANS ARE CODE COMPLIANT
 AT THIS TIME WITHOUT ANY *NORMAL OCCUPANCY* UNDER
 GENERATOR POWER.
  
 ** IF THERE ARE ANY QUESTIONS, PLEASE CONTACT THIS
 OFFICE/REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 18 Status F Date 2008-03-25 Cont ID  
Sent By dpalmer Date 2008-03-25 Time 15:54 Rev Time 0.00
Received By dpalmer Date 2008-03-25 Time 15:54 Sent To  
Notes
2008-03-25 15:54:45** DENIEDREVISIONS **
 CITY CENTER REV 15A ON LIGHTING SHEETS
  
 ** PLEASE SEE REDLINED PLANS AND NOTES BELOW AS THERE
 IS MUCH NEED OF COORDINATION WITH CIRCUITING FOR
 EMERGENCY AND EXIT LIGHTING.
 PLEASE ALSO SEE THAT COORDINATION IS ALSO NEEDED FOR
 OTHER NORMAL LIGHTING CIRCUITS.
 PLEASE SEE NOTES BELOW WITH RESPECT TO OCCUPATION OF
 BUILDING UNDER EMERGENCY POWER.
  
  
 1) NOTE: PLEASE SEE THAT PER ON-SITE MEETING BATHROOM
 LIGHTING WILL BE REQUIRED TO BE UPDATED.
  
 2) NOTE: PER ON-SITE AND CONVERSATIONS SEVERAL MONTHS
 AGO, IN AREAS OF BUILDING WHICH ARE GOING TO BE USED OR
 OCCUPIED FOR NORMAL OPERATING/CONDITIONS UNDER
 EMERGENCY POWER SHALL CONTAIN BATTERY BACK UP FIXTURES
 FOR THOSE AREAS FOR EGRESS AND EXISTING FROM BUILDING
 IN THE EVENT OF THE LOSS OF EMERGENCY GENERATOR.
 7.8, 7.9 LS 101 2003
 AREAS SUCH AS CALL CENTER AND EXITS, TRAINING ROOMS AND
 EGRESS, SERVER ROOM AND EGRESS, ETC
 PLEASE ALSO SEE STUDIO AND POLICE SUB-STATION ROOMS
 WHICH DO NOT SHOW ANY EMERGENCY LIGHTS ON EM CIRCUITS.
 THESE MAY NOT BE REQUIRED BY CODE, HOWEVER PLEASE
 VERIFY WITH OWNER THE INTENT OF USING THESE ROOMS.
  
 3) NOTE: PLEASE SEE THERE ARE NUMEROUS LOCATIONS ON
 PLANS IN WHICH CIRCUITING IS NON-EXISTENT, CIRCUITED TO
 OTHER CIRCUITS OR SOME OF THE SAME CIRCUITS IN
 DIFFERENT AREAS WHICH FEED THE SAME ITEMS.
 PLEASE SEE SOME OF THE ITEMS BELOW FOR EXAMPLE;
 THESE ARE IN NO WAY ALL LOCATIONS. PLEASE ALSO SEE SOME
 SHEETS ARE BEING NOTED BELOW AS MANY ROOM AND AREA
 DESIGNATIONS WERE REMOVED FROM PLANS.
 1HEB-5 AND 1HEB-3 TIED TOGETHER IN A1.804, A1.008.
 SEE 1HEA-2 AT A1.206 AND A1.302
 SEE 1HEA-6 AND HED-2 TIED TOGETHER
 SEE 1HED-4WHICH IS REPEATED, SEE AREAS D1.104,
 D1.005
 SEE 1HB-7 IN D1.201 SHOWN ON AS NORMAL CIRCUIT OR
 NOTING TO TIE TO.
 SEE 1HEC-3 AND 1HEC5 TIED TOGETHER.
 SEE CAF?, 1LC2, 8-10 AND 1LEC 6,8 TO SAME LIGHTS.
 SEE 2HEA-3 AND 2HEA-1 TIED TOGETHER ON SHEET E-2.2.1
 SEE EXIT LIGHT IN AREA A2.302 WHICH SHOWS NO CIRCUIT.
 SEE EXIT LIGHT AT DOOR IN FUTURE SPACE (SHELL AREA)
 WHICH NEEDS TO BE CIRCUITED PER 700.12E
 SEE AREA ON SHEET E2.3.2 *SUPPORT SPACE/FILE PRODUCTION
 AND CORRIDOR AREA IS MISSING CIRCUIT FOR EMERGENCY AND
 EXIT LIGHTS.
 SEE LIGHTING CONTROL IN SOME ROOMS SUCH AS PROGRAM
 MEETING ROOM WHICH SHOWS NORMAL OC DEVICE. THIS IS THE
 SAME IN OTHER LOCATIONS ALSO ONE SHEET E2.3.2/
 COLLECTION/ PROGRAM ROOM.
 SEE EMERGENCY AND EXIT LIGHTS IN ROOMS SUCH AS A4.420,
 4.419,4.421 ETC WHICH DOES NOT SHOW ANY CIRCUIT.
 SEE THIS SAME LOCATION AS THERE ARE SWITCHES LOCATED IN
 THE MIDDLE OF THE *AIR* AND NOT LOCATED ON ANY WALL.
 SEE 4HEB-1 IN A4.416 WHICH SHOWS THIS BEING TIED TO
 NORMAL AND EMERGENCY LIGHTS.
 SEE EMERGENCY LIGHTS/EXIT LIGHTS OUTSIDE A4.304 WHICH
 DOES NOT SHOW CIRCUIT. (PUBLIC UTILIZES AREA 03)
 SEE A5.531, EMERGENCY NOT CONNECTED.
 SEE A5.508, 5.505 ETC WHICH DOES NOT SHOW ANY CIRCUITS
 FOR EMERGENCY LIGHT FIXTURES.
 SEE 5HA-17 WHICH IS SHOWN TIED TO EMERGENCY LIGHTS AND
 NOT NORMAL LIGHTING.
 SEE A5.401 AND AREA WHICH INDICATES EMERGENCY AND EXIT
 LIGHTS WITH NO CIRCUITS.
 SEE A5.412 WHICH SHOWS NORMAL CIRCUIT TIED TO EMERGENCY
 LIGHT.
 SEE A5.503,504,505, A5.413 EMERGENCY AND EXIT LIGHTS
 WITH NO CIRCUITING.
  
 ** PLEASE SEE THAT MANY OF THE AREAS ABOVE ARE NOTED
 HOWEVER AS STATED ABOVE ARE IN NO WAY ALL POSSIBLE
 LOCATIONS.
 SEE REDLINED AND HIGHLIGHTED PLANS AS MOST OF THESE
 AREAS INDICATE THE NOTES ABOVE.
  
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 17 Status P Date 2008-03-24 Cont ID  
Sent By dpalmer Date 2008-03-24 Time 13:15 Rev Time 0.00
Received By dpalmer Date 2008-03-24 Time 13:15 Sent To PC
Notes
2008-03-24 13:15:48REV FOR 136 AND 161

Review Stop E ELECTRICAL
Rev No 16 Status P Date 2008-03-17 Cont ID  
Sent By dpalmer Date 2008-03-17 Time 12:03 Rev Time 0.00
Received By dpalmer Date 2008-03-17 Time 12:03 Sent To PC
Notes
2008-03-17 12:05:14REV FOR FORTH AND FIFTH FLOOR POWER ALONG WITH REVISED
 PANEL SCHEDULES.

Review Stop E ELECTRICAL
Rev No 15 Status P Date 2008-02-05 Cont ID  
Sent By dpalmer Date 2008-02-05 Time 18:19 Rev Time 0.00
Received By dpalmer Date 2008-02-05 Time 18:19 Sent To PC
Notes
2008-02-05 18:20:58*** REVISIONS***
  
 SHEETS E1-3.1, E6-9.0 OK AND STMAPED,
  
 REVISION FOR SHEET E3-3.1 NEEDS TO BE SUBMITTED UNDER
 LV PERMIT WHICH WAS NOT INCLUDED IN BASE BUILDING
 PERMIT #.

Review Stop E ELECTRICAL
Rev No 14 Status P Date 2008-01-30 Cont ID  
Sent By dpalmer Date 2008-01-30 Time 18:27 Rev Time 0.00
Received By dpalmer Date 2008-01-30 Time 18:27 Sent To PC
Notes
2008-01-30 18:28:53REV FOR E1-2.1, 6-8.0 OK.
 SHEETE3-2.1 NEEDS TO BE SUBMITTED UNDER LOW VOLTAGE
 PERMIT FOR THAT SCOPE OF WORK. NOT AS PART OF ORIGINAL
 BASE BUILDING PLANS FOR ACTUAL WIRING.

Review Stop E ELECTRICAL
Rev No 13 Status P Date 2008-01-23 Cont ID  
Sent By dpalmer Date 2008-01-23 Time 10:57 Rev Time 0.00
Received By dpalmer Date 2008-01-23 Time 10:57 Sent To PC
Notes
2008-01-23 10:58:34ELEC REV FOR SHEETS E2-2.0, E2-2.2, 8-2.0, 8-2.2

Review Stop E ELECTRICAL
Rev No 12 Status P Date 2007-12-25 Cont ID  
Sent By dpalmer Date 2007-12-25 Time 10:27 Rev Time 0.00
Received By dpalmer Date 2007-12-25 Time 08:17 Sent To PC
Notes
2007-12-25 10:27:472007-12-25 10:27:47
  
 ** PROVISO **
  
  
 1) NOTE: PLEASE SEE THE RED-LINES FORM THE ORIGINAL
 ISSUED PLANS FOR NORMAL PHOTO-METRICS WILL STILL NEED
 TO BE ADJUSTED. THE NORMAL STAIR LIGHTING LEVELS WERE
 OK; HOWEVER FIXTURES ON NORMAL LIGHTING PLANS AND
 NORMAL PHOTO-METRICS NEEDED COORDINATION.PLEASE SEE
 ORIGINAL RED-LINED PLANS.
  
 2) NOTE: PLEASE SEE MISPRINT/SHIFT IN PLANS ON SHEETS
 E8-2.0 AND 8-2.2 IN STAIRS. THESE WERE REDLINED ON
 PLANS AS THE LIGHTING PLANS DO NOT SHOW THIS SHIFT.
  
 3) NOTE: NO REVISED SHEET E2-2.2 WAS SUBMITTED? ( NOT
 PRINTED AND SUBMITTED ) THIS IS ONLY NOTED AS ALL OTHER
 LIGHTING SHEETS WERE REVISED/ADJUSTED AND SUBMITTED.
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 11 Status P Date 2007-12-22 Cont ID  
Sent By dpalmer Date 2007-12-22 Time 14:50 Rev Time 0.00
Received By dpalmer Date 2007-12-22 Time 14:50 Sent To  
Notes
2007-12-22 14:54:52E1-2.2

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2007-11-06 Cont ID  
Sent By dpalmer Date 2007-11-06 Time 10:41 Rev Time 0.00
Received By dpalmer Date 2007-11-03 Time 15:10 Sent To  
Notes
2007-11-06 10:41:16** REVISION 12A **
  
 1) NOTE: PLEASE SEE MISSING CIRCUIT FOR RECEPTACLE ON
 E1-2.2, THIS WAS REDLINED ON PLANS.
  
 2) NOTE: THE OUTSTANDING ISSUES WITH THE PROVISO
 PREVIOUSLY ISSUED FOR COMPLETE PHOTO-METRICS FOR
 REVISIONS AND COORDINATION STILL REMAINS.
 IT WAS REQUESTED BY THE ENGINEER OF RECORD FOR AN
 EXTENSION AS WELL AS FROM THE GC.
  
 3) NOTE: LOW VOLTAGE PERMITS AND PLANS HAVE NOT YET
 BEEN SUBMITTED TO DATE.
  
 4) NOTE: THE GENERATOR STILL REQUIRES RE-LISTING FOR
 UNIT. THIS WILL BE DONE AT A LATER DATE.
  
 SOME OF THESE ITEMS WERE CARRIED FORTH FROM PREVIOUS
 REVIEWS.
2007-11-05 16:57:522007-11-05 16:57:52
  
 REVIEW COMPLETED, PLANS ARE STILL NEEDED TO BE STAMPED
 AND NOTES NEED TO BE ENTERED AND TYPED INTO SYSTEM.
2007-11-04 10:28:192007-11-04 10:28:19
  
 REVIEW TO CONTINUE ON 11/5
2007-11-03 15:34:432007-11-03 15:10:24
  
 ONE SET IN ELECTRICAL FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2007-09-09 Cont ID  
Sent By dpalmer Date 2007-09-09 Time 12:56 Rev Time 0.00
Received By dpalmer Date 2007-09-05 Time 19:18 Sent To  
Notes
2007-09-09 12:56:262007-09-09 12:56:26
 REVIEW COMPLETED, NOTES BELOW.
  
 ** DENIED REVISIONS **
  
 1) NOTE: PLEASE SEE SHEET E0-2.2 WHICH INDICATES
 CONDUITS FOR LIGHTING IN THE RIGHT OF WAY ON THE PLANS
 FOR THIS BUILDING. THIS IS TO BE INCLUDED ON SEPARATE
 PLANS AND UNDER SEPARATE PERMITS WHICH IS NOT A PART OF
 THIS BUILDING OR LEGAL PROPERTY.
  
 2) NOTE: PLEASE SEE *PROVISO* AND *DENIAL* COMMENTS
 FROM JULY 27TH, 2007 WHICH HAVE NOT BEEN ADDRESSED. AS
 SOME OF THE REVISED SHEETS SUBMITTED DO HAVE A FEW OF
 THESE ITEMS DONE, MOST HAVE NOT.
 PLEASE SEE THE ATTACHED NOTES FOR THAT DATE.
 THESE NEED TO BE ADDRESSED AND INCORPORATED INTO PLAN
 SETS AS SOON AS POSSIBLE TO ALLEVIATE CONFUSION AND
 REVISIONS BEING MIXED AND/OR MISSED ALONG THE WAY. FBC
 ADMIN SECTION. 106.1.2,106.3.1 ETC
  
 3) NOTE: PLEASE SEE NUMEROUS SHEETS HAVE BEEN REVISED
 WITH CIRCUITING, LOADS INCREASING, ADDED POWER
 LOCATIONS, ADDED RECEPTACLES ETC HOWEVER NOT REVISED
 PANEL SCHEDULES OR LOAD CALCULATIONS WERE SUBMITTED.
 PLEASE SEE THE PANEL SCHEDULES AND LOADS ON FILE DO NOT
 CONTAIN MANY OF THE NEW CIRCUITS NOW SHOWN.
 PLEASE SEE THE PANEL SCHEDULES DO NOT CONTAIN THE
 INCREASE IN LOADS BY THE ADDED DEVICES ETC.
 PLEASE COORDINATE AND REVISE LOAD CALCULATIONS FOR
 AFFECTED PANELS. PLEASE REVISE PANEL SCHEDULES
 ACCORDINGLY.
 PLEASE SEE SHEET E1-5.1 ROOM A5.406 AS SOME RECEPTACLES
 WERE REVISED AND DO NOT CONTAIN CIRCUITING.
 PLEASE SEE THIS SAME SHEET AS RECEPTACLES ADDED TO
 CIRCUIT(S) 5LA3-5, 5LA3-34 DO NOT CORRELATE WITH LOADS
 AND PANEL SCHEDULES. THIS IS TYPICAL OF NUMEROUS
 CIRCUITS, LOADS, SHEETS AND PANELS.
 FBC 106.3.5.1.2, 106.1.2
 NEC 408.4, 220 ETC
  
 4) NOTE: PLEASE SEE THERE ARE SEVERAL LOCATIONS ON
 SHEETS WHERE THE FURNITURE LAYOUTS HAVE NOW BEEN
 REMOVED. ??
  
 5) NOTE: AS NOTED AND AGREED BY THE CONTRACTOR, OWNER
 AND AS SHOWN ON ORIGINAL PLANS, THE LOW VOLTAGE SYSTEMS
 ARE TO BE UNDER A SEPARATE PERMIT AND ARE NOT PART OF
 THE BASE BUILDING PLANS AND PERMITTING.
 PLEASE SUBMIT THREE COMPLETE SETS WITH PERMIT
 APPLICATION, APPROPRIATE VALUE AND FEES FOR THE SCOPE
 OF WORK.
 ** PLEASE BE SURE TO SPECIFY THE TYPE OF CABLING,
 CONDUIT INSTALLATION ETC.
  
 6) NOTE: PLEASE EXPLAIN TITLE BLOCKS WITH
 IDENTIFICATION OF REVISIONS. THE SHEETS ARE LABELED AS
 REV # 11, YET THE DESCRIPTION INDICATES THIS IS
 REVISION #3?
 THIS IS UNCLEAR.
 ALTHOUGH NOT REQUIRED, PLEASE KNOW A SUBMITTAL OF A
 LETTER ON REVISIONS TAKING PLACE ALONG THE PROCESS OF
 THE JOB WOULD HELP TO PERHAPS ALLEVIATE ANY CONFUSION
 AND DELAYS IN PROJECT.
  
 ** AS STATED ON PREVIOUS REVIEWS: IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE IN CONTACTING THIS
 OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-08 21:29:062007-09-08 21:29:06
  
 REVIEW COMMENCED.
2007-09-05 19:19:082007-09-05 19:19:08
 1-ROLL IN ELECTRICAL FOR REVIEW:

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2007-07-26 Cont ID  
Sent By dpalmer Date 2007-07-26 Time 11:33 Rev Time 0.00
Received By dpalmer Date 2007-07-23 Time 11:13 Sent To  
Notes
2007-07-26 11:35:29 
 ** REVIEW FOR REV #8 AND REV #10.
  
  
 *** PROVISO /UNSAT ***
  
 ** PLEASE SEE CONDITIONS ARE STILL GIVEN FOR SOME ITEMS
 NOT SUBMITTED AND FOR SOME ITEMS ON PLANS FOR
 COORDINATION ETC. SOME SHEETS ARE STAMPED AND PROVISO
 NOTES FOLLOW BELOW.
  
 ** PLEASE SEE THE FAILURE COMMENTS AT THE END OF
 *PROVISO* NOTES FOR SHEETS WHICH WERE NOT STAMPED..
  
  
  
  
 1) NOTE: PLEASE SEE THE OVER ALL SHEET E1-1.0 DOES NOT
 MATCH WITH NEW LAYOUT FOR MECHANICAL ROOM AT GARAGE AND
 HALLWAY AREA.
 PLEASE SEE NOTES ON REVIEW OF PHOTO-METRIC PLANS
 REVIEW.
  
 2) NOTE: PLEASE SEE E2-2.2 MEN AND WOMEN RESTROOMS ON
 UPPER LEFT HAND CORNER WHICH STILL SEEM TO INDICATE BY
 HASHED LINES MORE THAN THE TWO EM LTS.
 PLEASE SEE SOME OF THESE ARE SHOWN ON OTHER SHEETS AND
 FOR OTHER BATHROOMS.
 PLEASE SEE COMMENTS WITH RESPECT TO PHOTO-METRICS.
  
 3) NOTE: PLEASE SEE SHEET E2-4.2 WHICH WILL REMAIN
 REDLINED AS ROOF-TOP ACCESS AND WHETHER OR NOT STAIRS
 WILL BE REQUIRED IS STILL IN QUESTION.
  
 4) NOTE: PLEASE KNOW THAT UPDATED POWER PLANS FOR
 CHANGES AND CORRECTIONS WILL STILL BE NEEDED.
  
 5) NOTE: PLEASE SEE THE UPPER PART OF THE ELECTRICAL
 RISER DIAGRAM WAS NOT SUBMITTED. THIS SHEET ALONG WITH
 SOME OTHERS SHOWING THE CHANGES FOR THE GENERATOR ETC
 WILL STILL BE NEEDED.
 PLEASE SEE THAT THE SPECIFICATIONS ON THE GENERATOR AND
 FIELD MODIFICATIONS FOR BI-FUEL ARE STILL NEEDED FOR
 REVIEW.
 700,701, 110.3, 90.7.
  
 6) NOTE: PLEASE SEE PANEL 5LEB TOTAL FOR VA HAS NOT
 BEEN CORRECTED AS NOTED ON PREVIOUS REVIEW AND REDLINED
 ON PREVIOUS REVIEWED #8 REVISIONS.
 THE TOTAL LOAD ON PANEL DOES NOT CORRELATE WITH THE
 TOTAL ON LOAD SUMMARY OF PANEL.
  
 7) NOTE: PLEASE SEE SHEET E6-1.0 WHICH STILL INDICATES
 A 825KW GENERATOR. AS THIS GENERATOR AHS CHANGED SIZE
 SEVERAL TIMES, PLEASE COORDINATE ALL SHEETS WITH
 REFERENCE TO THIS UNIT. PLEASE SEE COMMENTS ON
 PHOTO-METRIC SHEETS AS THESE CONTAIN SEVERAL OTHER
 REFERENCES.
  
 8) NOTE: PLEASE SEE NOTE #6 ABOVE AS THE LOADS ADJUSTED
 ON 5LEB NEED TO BE CARRIED THROUGH TO ALL OTHER PANELS.
 5HEB ETC.
 FBC 106.3.5.1.2 NEC 220.
  
 9) NOTE: PLEASE SEE SHEET E1-6.0 AS THE LAYOUT FOR THE
 GENERATORS AND EQUIPMENT DOES NOT CORRELATE WITH
 PLANS.
 PLEASE SEE ROOF TOP MECH ROOM AND CONTROLS FOR LIGHTING
 WHICH HAVE NOT BEEN CORRECTED TO COORDINATE WITH
 PLANS.
  
 10) NOTE: PLEASE KNOW THE IT ROOM HAS NOT BEEN
 SUBMITTED FOR PERMITTING TO DATE ALONG WITH ANY LOW
 VOLTAGE SYSTEMS FOR THE BUILDING.
  
 ALL ELECTRICAL SHEETS SUBMITTED WILL BE STAMPED WITH
 THE EXCEPTION OF PHOTO-METRICS.
  
  
  
 ** UNSAT **
  
 1) NOTE: PLEASE SEE THE PHOTO-METRIC PLANS SUBMITTED
 STILL NEED SOME COORDINATION.
 PLEASE SEE THERE ARE SEVERAL SHEETS WHERE LIGHTING
 FIXTURES ARE MISSING ALTHOUGH THEY ARE ACTUALLY ON THE
 ELECTRICAL LIGHTING PLANS.
 PLEASE SEE MANY AREAS ARE REDLINED WITH CIRCLES FOR
 MISSING FIXTURES AND OR MULTIPLE FIXTURES WHEN THE
 PLANS SHOW LESS OR MORE.
 PLEASE SEE THAT MANY OF THESE ARE THE EMERGENCY
 PHOTO-METRIC SHEETS.PLEASE SEE SOME OF THESE SHEETS
 IN ONE SET ACTUALLY CONTAINS A *CHECK* AS THESE ARE OK,
 HOWEVER CHANGES ON OTHER SHEETS FOR COORDINATION MAY
 AFFECT THESE.
 PLEASE SEE THE FOLLOWING SHEETS FOR EXAMPLE WHICH ARE
 MISSING FIXTURES, LOCATIONS ARE INCORRECT OR ARE
 SHOWING FIXTURES NOT ON LIGHTING PLANS.
 8-1.1,
 8-1.2,
 8-1.3,
 8-3.2,
 8-4.1,
 8-4.2,
 8-5.2 MISSING FC AVG. FOR STAIRS.
 8-6.0 3-GENERATORS SHOWN, 3-400KW GENERATORS.
 8-6.3 3-GENERATORS SHOWN, 2-FUTURE AND 1-825KW GEN.
 9-1.0
 ** PLEASE BE SURE TO COORDINATE THE SHEETS AS THE
 LEVELS OF LIGHTING MAY CERTAINLY CHANGE WHEN FIXTURES
 ARE ADDED OR DELETED.
 PLEASE BE SURE TO SEE ANY ROOMS AND AREAS (MECH
 ELECTRICAL ROOM IN GARAGE).
 PLEASE SEE LS 101 7.8 AND 7.9.
 PLEASE SEE FAC 61G15-33.004
  
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2007-04-14 Cont ID  
Sent By dpalmer Date 2007-04-14 Time 11:46 Rev Time 0.00
Received By dpalmer Date 2007-04-11 Time 11:48 Sent To  
Notes
2007-04-14 11:48:58** UNSAT **
  
 ** PLEASE SEE THIS REVIEW IS FOR REVISION #8 AS
 SUBMITTED TO ADDRESS *PROVISO* FROM ISSUANCE OF
 PERMIT**
  
 ** PLEASE SEE THAT MOST OF THE *PROVISO* NOTES HAVE
 BEEN ADDRESSED HOWEVER DUE TO CHANGES IN REVISION #7
 AND SOME ITEMS WHICH STILL NEED TO BE REVISITED ON
 PROVISO, PLEASE SEE THE COMMENTS BELOW.
  
 1) NOTE: PLEASE KNOW THAT DUE TO THE CLEARANCE
 REQUIREMENTS FOR THE GENERATOR WHICH WAS COMMENTED ON
 IN REVISION FOR ARCHITECTURAL DATED 3/1/07 THE PLANS AS
 SUBMITTED DO NOT INDICATE THE MINIMUM CLEARANCES FOR
 THE UNIT PER NEC 110.26 AND THAT WHICH IS SET-FORTH
 FROM THE MANUFACTURES SPECIFICATIONS.
 110.3, 90.7
  
 2) NOTE: PLEASE CLARIFY THE CONTROL DEVICE FOR ELEVATOR
 ROOM PER 1-6.1. OCCUPANCY DEVICE REQUIRED.
 13-415.1.ABC.1.1
  
 3) NOTE: PLEASE SEE PANEL 1-HEE WHICH NEEDS TO INDICATE
 AND LABEL THE ROOMS IN WHICH THEY FEED AND THE
 DESIGNATION FOR THE * ELEVATOR MACHINE RM LTS*.
 408.4, 620.23
  
 4) NOTE: PLEASE SEE THE PROVISO WHICH WAS TO REVISE
 CIRCUITS FOR THE ELEVATOR ROOMS, WHICH WAS TO INCLUDE
 THE LIGHTING AND RECEPTACLES, YET ONLY THE REVISED
 LIGHTING PLANS WERE SUBMITTED. PLEASE SEE THE SHEETS
 FOR THESE ROOMS SHOULD HAVE ALSO BEEN SUBMITTED.
 620.23
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE THE ELECTRICAL RISER DIAGRAM AND
 NOTES FOR REVISION #7 WHICH AHS NOT BEEN CHANGED.
 PLEASE SEE THAT THE ATS SWITCHES WHICH HAVE BEEN
 REVISED ON OTHER DOCUMENTS HAVE NOT BEEN REVISED ON
 RISER DIAGRAM.
 PLEASE SEE NOTES DATED 3/24/07
 PLEASE BE SURE TO REVISE POWER PLANS, PANEL SCHEDULES,
 LOADS ETC.
 FBC 106.3.5.1.2, 106.1.2
  
 6) NOTE: PLEASE CLARIFY STAIR 11 LIGHTS AND LOCATIONS
 FOR THE PHOTO-METRIC LEVELS. PREVIOUS PLANS INDICATE
 LIGHTING IN THE STAIR AREA ABOVE THE STAIRS AND SOME
 SHEETS INDICATE THESE AT THE UPPER LEVEL AND LOWER
 LEVEL WHICH DO NOT SEEM THEY WOULD PROVIDE THE NEEDED.
 PLEASE SEE THE PHOTO-METRIC PLANS WHICH DO INDICATE THE
 LIGHT FIXTURE ABOVE STAIRS AND IF THIS IS HOW THE
 LIGHTING LEVELS ARE DERIVED THEN THE PLACEMENT OF THE
 LIGHTING FIXTURES ON THE LIGHTING PLANS WOULD NOT WORK
 AND PROVIDE THE LIGHTING.
 LS 101 7.8.1.3, 7.9.2.2
 PLEASE SEE NEXT COMMENT.
  
 7) NOTE: PLEASE SEE THAT LIGHTING PLANS AND
 PHOTO-METRIC PLANS STILL NEED COORDINATION OG LIGHTING
 FIXTURES. PLEASE SEE THAT THE SAME FIXTURES WHICH ARE
 INDICATED AS EM TYPE FIXTURES ON LIGHTING PLANS ARE NOT
 THE SAME ONES IN ALL LOCATIONS ON PHOTO-METRIC PLANS.
 PLEASE KNOW AS BASED ON COMMENT ABOVE AND THE NEXT
 COMMENT FOR NIGHT LIGHTING AND EMERGENCY LIGHTING,
 THESE WILL ALL NEED TO BE ADJUSTED AND REVISED TO
 CORRELATE.
 FBC 106.1.2
 LS 101 7.8, 7.9
  
 8) NOTE: PLEASE KNOW THAT A MEETING WILL BE REQUIRED TO
 GO OVER PLANS AND PROPOSED *NIGHT-LIGHTS* AS SHOWN ON
 PLANS. PLEASE KNOW THAT EMERGENCY FIXTURES ARE REQUIRED
 FOR EGRESS PATHS UNDER NORMAL AND EMERGENCY HOWEVER THE
 NUMBER OF FIXTURES BEING PROPOSED FOR NIGHT LIGHTS
 WHICH WILL BE LEFT *ON* 24/7/365 DOES NOT TAKE INTO
 CONSIDERATION OF THE REQUIREMENT OF THE FLORIDA ENERGY
 CODE.
 PLEASE SEE THESECTION BELOW WHICH IS TAKEN DIRECTLY
 FROM NFPA-101. *7.8.1.2.2* WHICH IS LOCATED ALONG WITH
 TEXT FOR SECTION OF 7.8.
 PLEASE KNOW THAT DUE TO THE COMPLEXITY OF THE EGRESS
 LIGHTING, THE ACTUAL DESIGNATED EGRESS PATH/PATHS NEEDS
 TO BE DETERMINED AS A STARTING POINT FOR FINDING THE
 MINIMUM REQUIRED.
 PLEASE KNOW THAT THIS OFFICE HAS CONTACTED THE FLORIDA
 BUILDING COMMISSION TO GO OVER THE REQUIREMENTS OF
 CHAPTER 13 AND THE INTENT.CONSIDERATION NEEDS TO BE
 GIVEN FOR THE INTENT AND AT THE SAME TIME MEETING THE
 REQUIRED LIFER SAFETY FOR NORMAL AND EMERGENCY EGRESS
 LIGHTING DURING OCCUPANCY OF BUILDING.
  
 *7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY
 BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTER 11
 THROUGH CHAPTER 42. FOR THE PURPOSES OF THIS
 REQUIREMENT, EXIT ACCESS SHALL INCLUDE ONLY DESIGNATED
 STAIRS, AISLES, CORRIDORS, RAMPS, ESCALATORS, AND
 PASSAGEWAYS LEADING TO AN EXIT. FOR THE PURPOSES OF
 THIS REQUIREMENT, EXIT DISCHARGE SHALL INCLUDE ONLY
 DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS,
 ESCALATORS, WALKWAYS, AND EXIT PASSAGEWAYS LEADING TO A
 PUBLIC WAY.
 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF
 OCCUPANCY REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE
 FOR USE, UNLESS OTHERWISE PROVIDED IN 7.8.1.2.2.
 7.8.1.2.1 ARTIFICIAL LIGHTING SHALL BE EMPLOYED AT SUCH
 LOCATIONS AND FOR SUCH PERIODS OF TIME AS ARE NECESSARY
 TO MAINTAIN THE ILLUMINATION TO THE MINIMUM CRITERIA
 VALUES HEREIN SPECIFIED.
 7.8.1.2.2 AUTOMATIC, MOTION SENSOR?TYPE LIGHTING
 SWITCHES SHALL BE PERMITTED WITHIN THE MEANS OF EGRESS,
 PROVIDED THAT THE SWITCH CONTROLLERS ARE EQUIPPED FOR
 FAIL-SAFE OPERATION, THE ILLUMINATION TIMERS ARE SET
 FOR MINIMUM 15-MINUTE DURATION, AND THE MOTION SENSOR
 IS ACTIVATED BY ANY OCCUPANT MOVEMENT IN THE AREA
 SERVED BY THE LIGHTING UNITS.
  
 ** PLEASE SEE ONE SET OF THE PLANS WHICH WAS SUBMITTED
 HAS REDLINED LOCATIONS WHICH ARE ALSO HIGH-LIGHTED FOR
 AREAS WHICH NEED TO BE GONE OVER.
 ** PLEASE CONTACT THIS OFFICE ONCE THE MINIMUM
 LIFE-SAFETY DESIGNATED EGRESS PATHS ARE DONE TO SET UP
 A MEETING TO GO OVER PLANS AND SCENARIOS.
  
 ** PLEASE KNOW THAT DUE TO THE COMPLEXITY OF THE NOTES
 ABOVE AND THE TIME CONSIDERATION WHICH WILL BE GIVEN TO
 ADDRESS THE ABOVE, THE ORIGINAL DATE OF 60DAYS HAS BEEN
 EXTENDED AS DISCUSSED WITH THE ENGINEER OF RECORD.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-04-14 09:59:47REVIEW IN PROGRESS

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2007-03-24 Cont ID  
Sent By dpalmer Date 2007-03-24 Time 17:49 Rev Time 0.00
Received By dpalmer Date 2007-03-24 Time 16:37 Sent To  
Notes
2007-03-24 17:49:26** UNSAT **
  
  
 ** GARAGEREVISION #7**
  
 1) NOTE: PLEASE SEE THE RISER HAS NOW CHANGED ATS-3 TO
 A 400AMP UNIT, HOWEVER PLEASE SEE THE LEFT SIDE OF
 ATS-3 AS IT IS STILL SHOWN AS A 260AMP UNIT.
 PLEASE ALSO SUBMIT THE REVISED MANUFACTURES SPECS/CUT
 SHEETS FOR THE NEW PROPOSED UNIT.(110.3, 90.7)
 PLEASE COORDINATE ALONG WITH ELECTRICAL SHEET FOR MAIN
 ELECTRICAL ROOM WHICH WAS NOT SUBMITTED YET THE
 DESIGNATION ON SHEET 4-1.0 CONTAINS THE 260AMP UNIT.
 FBC 106.1.2
  
 2) NOTE: PLEASE SEE PLANS INDICATE A REVISION TO THE
 LOAD CALCULATIONS ON THE MAIN BUILDING LOAD SUMMARY;
 HOWEVER THE LOADS DID NOT CHANGE FROM THE PERMITTED SET
 OF PLANS. A CLOUD AND A REV #7 IS SHOWN, BUT NOTHING
 WAS REVISED.
 PLEASE SEE THAT THE LOADS OF THESE NEW MOTORS NEED TO
 SHOW *LARGEST* AT 125% AND PLEASE KNOW THAT AS THESE
 MOTOR LOADS MAY BE RUN FOR THREE OR MORE HOURS THE
 LOADS SHALL BE SHOWN AT 125%.
 215.3, 230.42, 220, 430 ETC.
 PLEASE REVISE CALCULATIONS.
 PLEASE ALSO KEEP IN MIND THE *PROVISO* WHICH WAS GIVEN
 WHICH NEEDED LOAD CALCULATIONS TO BE REVISED AND BASED
 ON THESE SHEETS FOR REVISION #7, LOADS WERE NOT
 REVISED.
 IF REVISION #6 HAS NOT HAD THIS CHANGE BASED ON
 *PROVISO* PLEASE KNOW IT MAY BE THAT REVISED SHEETS ARE
 INSERTED BEFORE REVIEW OF REVISION #6 IS DONE?
  
 3) NOTE: PLEASE SUBMIT THE REVISED GENERATOR SPECS FOR
 THE INCREASED SIZE INCLUDING FUEL CONSUMPTION FOR ADDED
 SIZE AND INCREASED LOADS. RECORD PLANS NEED TO REVISE
 FUEL CONSUMPTION AND LOADS.
 NFPA-110
 NFPA 70 110.3, 90.7.
 FBC 106.1.2
  
 4) NOTE: THE EXHAUST FANS ARE LABELED EF-1 FOR FIRST
 FLOOR AND THEN EF-2 FOR SECOND FLOOR, EF-3 FOR THIRD
 FLOOR AND THEN FOURTH AND FIFTH LEVELS ARE ALSO LABELED
 EF-3 FOR THESE FANS ON OTHER LEVELS???
 PLEASE PROVIDE SPECIFIC DESIGNATIONS FOR EACH EXHAUST
 FAN. PLEASE KNOW IF THEY ARE ON LEVEL 2M, THEN LABEL
 EACH ON LEVEL 2 AS THERE ARE MULTIPLE FANS PER FLOOR.
 PLEASE LABEL FANS ON OTHER LEVELS AS THE FANS ON THOSE
 SPECIFIC LEVELS.
 EF-4A NE CORNER?, EF-4B NE CORNER ?ORANY OTHER
 SPECIFIC DESIGNATION OF CHOICE.
 PLEASE SEE 408.4 AS THIS REQUIRES THE SPECIFIC
 DESIGNATIONS AND NOT TO BE GENERIC. PLEAS CALL IF THERE
 ANY QUESTIONS.
 ** PLEASE BE SURE TO ADJUST THE DESIGNATIONS ON THE
 BUILDING/ MECHANICAL PLANS ALSO.
  
 5) NOTE: PLEASE SEE FBC 132-413.1ABC.1 FOR VOLTAGE
 DROP. THE MCC SHOWS #12AWG FOR THE UPPER FLOORS AND THE
 DISTANCE SEEMS TO EXCEED THE % PERMITTED.
 PLEASE PROVIDE VOLTAGE DROP CALCULATIONS FOR THESE OR
 INCREASE CONDUCTOR SIZES FOR LONGER RUNS. THIS IS NOT
 FOR LOWER LEVELS WITH LESS DISTANCE.
  
 6) NOTE: PLEASE BE SURE TO ADJUST THE GENERATOR
 SPECIFICATIONS ON ANY OTHER SHEETS WHICH CONTAIN THE
 DESIGNATIONS.
 FBC 106.1.2
  
 7) NOTE: PLEASE SUBMIT LV DETAIL FOR WIRING OF THE
 CARBON MONOXIDE DEVICES/SYSTEM.
 CAN BE ON THE SAME GARAGE SHEETS AND A TYPICAL DETAIL.
 FBC 106.3.5.1.2
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER TRADES(
 BUILD/MECH/FIRE) WHICH MAY CONTAIN COMMENTS THAT MAY
 AFFECT ELECTRICAL SHEETS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-03-01 Cont ID  
Sent By dpalmer Date 2007-03-01 Time 07:31 Rev Time 0.00
Received By dpalmer Date 2007-03-01 Time 07:31 Sent To  
Notes
2007-03-01 07:32:49**** UNSAT ****
  
 1) NOTE: PLEASE SEE THE ARCHITECTURAL REVISIONS
 SUBMITTED ARE SHOWING NEW FENCING AND CLEARANCES AROUND
 THE CURRENT GENERATOR UNIT AND THE FUTURE GENERATOR
 UNITS WHICH DO NOT MEET EGRESS REQUIREMENTS AND MINIMUM
 CLEARANCE REQUIREMENTS FOR THE NEC 110.26 AND NFPA-110.
 PLEASE OBTAIN INFORMATION ON THE ELECTRICAL BREAKER
 PANEL LOCATIONS, PLEASE SEE ONLY ONE PATH IS BEING
 SHOWN AND THE PATH OF EGRESS DOES NOT MINIMUM WIDTHS.
 PLEASE SEE THAT DEPENDING ON EQUIPMENT AND NUMEROUS
 OTHER FACTORS THE FENCING AND WALLS SHOWN ARE WAY UNDER
 THE MINIMUM AREA REQUIRED ABOUT THE ELECTRICAL
 EQUIPMENT.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-02-18 Cont ID  
Sent By dpalmer Date 2007-02-18 Time 13:29 Rev Time 0.00
Received By dpalmer Date 2007-02-15 Time 10:57 Sent To  
Notes
2007-02-18 13:31:522007-02-18 13:31:52
  
 *** PROVISO/REVISION ***
  
  
 ** THE FOLLOWING *PROVISO* WAS SET UP WITH CONDITIONS
 THAT ALL OF THE FOLLOWING BE REVISED, UPDATED AND
 SUBMITTED FOR REVIEW WITHIN 60 DAYS FROM ISSUANCE OF
 PERMIT.
 PLEASE SEE THAT MANY OF THE ITEMS BELOW BESIDES CODE
 RELATED ITEMS ARE MOSTLY BASED ON COORDINATION RELATED
 ISSUES.
 PLEASE SEE SOME OF THE NOTES ARE NEW AS SOME THINGS
 HAVE BEEN ADDED TO THESE PLANS WHICH WERE NOT ON
 PREVIOUS REVIEWED PLANS.
 THE SECTION OF THE FBC 106.1.2 MADE IN NOTES BELOW IS
 FROM THE 2004 FBC ADMINISTRATIVE SECTION AS ADOPTED BY
 THE CITY OF WEST PALM BEACH FOR * ADDITIONAL
 INFORMATION*.
 ** MANY OF THESE WILL NOT ONLY REQUIRE THE PARTIAL FOR
 EACH FLOOR, BUT ALSO THE *OVERALL* FLOOR SHEETS TO BE
 REVISED.
  
  
 1) NOTE: PLEASE SUBMIT THE WIND LOAD CALCULATIONS FOR
 SITE LIGHT POLES FOR COURTYARD AND ROOF TOP AREAS.
 THESE SHALL CONTAIN THE ORIGINAL SIGNATURE, DATE AND
 SEAL FROM THE ENGINEER OF RECORD. FS 471.025 AND TITLE
 BLOCKS ON EACH SHEET PER 61G15-23.002.
  
 2) NOTE: PLEASE SEE THAT THERE MAY BE POSSIBLE STAIRS
 TO THE ROOF ON THE SOUTH SIDE OF THE BARREL ROOF FROM
 THE FOURTH LEVEL. THIS IS A BUILDING CODE REQUIREMENT
 AND PENDING ANY DECISION FROM THE CBA, LIGHTING,
 PHOTO-METRICS ETC WILL BE REQUIRED TO BE SUBMITTED AND
 REVISED FOR THOSE SHEETS AFFECTED BY THIS.
 THIS WOULD INVOKE LS 101 7.8 AND 7.9.
  
 3) NOTE: PLEASE SEE THERE ARE MANY LOCATIONS WHERE
 BATTERY BACK UP TYPE FIXTURES ARE BEING SHOWN WITH OC
 DEVICES OR SWITCHING.
 PLEASE SEE PREVIOUS NOTES WHICH REQUESTED BATTERY BACK
 UP FIXTURES OF SOME SORT IN MANY ROOMS; HOWEVER PLANS
 WERE REVISED IN MANY ROOMS TO INCLUDE A ZE FIXTURES,
 WHICH IF CONTROLLED AS SHOWN (SWITCHED) THEN THE LIGHT
 FIXTURE WHICH IS BATTERY BACK UP WOULD COME ON EACH
 TIME THE SWITCH OR DEVICE TURNS LIGHTING OFF. PLEASE
 SEE MOST ELECTRICAL ROOMS, ELEVATOR EQUIPMENT ROOMS,
 MECHANICAL ROOMS ETC.
 PLEASE SEE THE FOLLOWING LOCATIONS WILL BE REQUIRED TO
 CONTAIN A BATTERY BACK UP FIXTURE, HOWEVER THESE
 LOCATION ARE NOT TO HAVE LIGHTING REMAIN *ON* AS NL
 (NIGHT LIGHTS) 24 HRS A DAY.
 THESE LOCATIONS WHICH WILL REQUIRE A BATTERY BACK UP
 FIXTURE, BUT NOT FOR FIXTURES TO BE SWITCHED OR ON AS
 NL SHALL BE THE *MAIN ELECTRICAL ROOM IN GARAGE, MAIN
 MECHANICAL ROOM IN GARAGE, ALL ELEVATOR EQUIPMENT
 ROOMS, IT ROOM, FIRE PUMP ROOMS, BOTH MEZZANINE
 MECHANICALROOMS, THE MECHANICAL ROOM ON ROOF AND FIRE
 COMMAND ROOM. PLEASE SEE ALL OTHER SMALLER ELECTRICAL
 ROOMS WHICH CONTAIN ZE OR ZE2 FIXTURES ARE NOT REQUIRED
 TO CONTAIN A BATTERY BACK FIXTURE, BUT MAY. IF THEY DO
 CONTAIN A BATTERY BACK UP THESE SHALL NOT BE SWITCHED
 AND SHALL NOT BE ON 24/7. (700.12E).
 PLEASE GO OVER ALL OF THESE LOCATIONS ON PLANS AS MANY
 ROOMS DO SHOW THESE TYPE FIXTURES, HOWEVER NOT ALL.
 (PLEASE SEE REDLINED PLANS AS MANY OF THESE HAVE BEEN
 HIGH-LIGHTED BUT NOT ALL).
 PLEASE SEE DOME ROOM ABOVE THE ROOF TOP MECHANICAL ROOM
 DOES NEED A BATTERY BACK UP FIXTURE FOR EGRESS (STAIRS)
 HOWEVER SHOULD NOT CONTAIN NL FOR 24/7 OPERATION. MANY
 OF THESE WOULD CREATE A DIRECT CONFLICT WITH 700.12E OF
 THE NEC AND CHAPTER 13 OF THE FLORIDA ENERGY CODE.
 ** PLEASE CALL TO GO OVER OR TO COME IN AND GO THROUGH
 PLANS**
  
 4) NOTE: PLEASE SEE MANY LOCATIONS ON PLANS WHICH
 INDICATE NIGHT LIGHTS (NL). THE AMOUNT OF THESE
 FIXTURES SHOULD BE REVIEWED AS THE AMOUNT IS OVER IN
 MANY LOCATIONS FOR THAT WHICH IS REQUIRED FOR LS 101
 7.8 AND 7.9. PLEASE SEE SOME AREAS WHICH CONTAIN NL
 WHICH ARE STILL BEING SHOWN SWITCHED FROM LOCAL
 SWITCHES.
 PLEASE SEE FOR EXAMPLE A.5.06.
 PLEASE SEE MANY LOCATIONS WHICH THESE NIGHT LIGHTS DO
 NOT SHOW ANY CONTROL OR CIRCUITING AND OR ARE IN
 CONFLICT AS THERE ARE OTHER FIXTURES WHICH ARE SHOWN ON
 THE NIGHT LIGHT CIRCUITS WHICH DO NOT CORRELATE WITH
 THE TYPE OF FIXTURES ON LEGENDS.
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE STAIRS WHICH ONLY CONTAIN CONTROL
 FOR LIGHT AT ONE LOCATION EITHER AT THE TOP OR AT THE
 BOTTOM OF STAIRS.
 PLEASE SEE STAIR 12, STAIR 13. (PLEASE SEE STAIR 11 FOR
 EXAMPLE WHICH SHOWS BATTERY BACK UP FIXTURES BEING
 SWITCHED. (AS NOTED ABOVE.
 FBC 106.1.2
  
 6) NOTE: PLEASE SEE THE ELECTRICAL CIRCUITING WHICH HAS
 NOW BEEN ADDED TO THE ELEVATOR EQUIPMENT ROOM ON ROOF
 TOP. PLEASE SEE THE DEDICATED CIRCUITS AS REQUIRED PER
 620.23 ARE THE SAME CIRCUITS AS SHOWN FOR THE FIRST
 FLOOR ELEVATOR EQUIPMENT ROOMS WHICH NOW HAVE CIRCUITS
 SHOWN FOR LIGHTING.
 PLEASE ALSO SEE THAT TWO SETS OF THE PLANS WHICH
 INDICATE THESE CIRCUITS TO PANEL 1-HEE DO NOT SHOW
 THESE CIRCUITS OR LOADS ADDED TO PANEL.
 PLEASE SEE ONE OF THE SETS OF PLANS DO SHOW THESE
 CIRCUITS ADDED TO PANEL SCHEDULE; HOWEVER NOT TO
 LOADS.
 PLEASE CORRELATE AND REVISE. PLEASE ALSO SEE NEXT
 NOTE.
 FBC 106.1.2
  
 7) NOTE: PLEASE SEE THE NEW ELECTRICAL FOR EQUIPMENT
 ADDED FOR THE ROOF TOP ELEVATOR EQUIPMENT ROOM WHICH
 WAS ADDED TO THESE PLANS AND TO PANEL 5-LEB ARE SHOWN
 ON PANEL SCHEDULE BUT THE LOAD CALCULATIONS WERE NOT
 REVISED OR ADJUSTED FOR THESE NEW LOADS.
 PLEASE ALSO SEE 620.23 AS THE NEW CIRCUIT 16 FOR THIS
 SAME PANEL FOR THE RECEPTACLE CIRCUIT SHOULD BE LABELED
 FOR THIS ELEVATOR EQUIPMENT ROOM AND NOT GENERAL
 RECEPTACLE CIRCUITS.
 FBC 106.1.2.
  
 8) NOTE: PLEASE SEE THE LIGHTING POWER DENSITIES SHEETS
 1 OF 14 AND 14 OF 14 WHICH DID NOT CORRELATE FOR 6TH
 AND 7TH LEVELS AND LIGHTING. THESE ITEMS WERE CHANGED
 IN MEETING WITH ENGINEER.
 PLEASE ALSO SEE THE SHEET 4 OF THE FLORIDA ENERGY CODE
 INPUT DATA REPORT WHICH SHOWS *MANUAL CONTROLS FOR TWO
 AREAS.
 PLEASE SE THIS WAS ALSO CHANGED BY THE ENGINEER IN
 MEETING.
 THESE SHEETS SHOULD BE REVISED FOR THESE ITEMS AND FOR
 ANY AND ALL CHANGES MADE FOR FIXTURES IN MANY ROOMS AS
 NOTED ABOVE IN OTHER NOTES.
 FBC 106.1.2
 FBC 13-415.1.AB.1, 13-415.2
  
 9) NOTE: PLEASE SEE FIRST FLOOR CITY HALL SECTION WHICH
 SEEMS TO BE MISSING A 3-WAY SWITCH FOR MAIL/RECEIVING
 ROOM.
  
 10) NOTE: PLEASE SEE 3-WAY SHOWN ON E 2-2.2 WHICH IS
 NOT SHOWN ON E2-1.4 FOR THE SAME LOCATION. (REDLINED)
  
 11) NOTE: PLEASE SEE AS NOTED ABOVE A BATTERY BACK UP
 FIXTURE WILL BE REQUIRED IN THE IT ROOM OF SOME SORT.
 LS 101 7.8, 7.9.
 FBC 106.1.2
  
 12) NOTE: PLEASE SEE THAT MANY OF THE REVISED LIGHTING
 PLANS DO NOT CORRELATE WITH THE REVISED PHOTO-METRICS
 OR MANY OF PHOTO-METRICS SHEETS WERE NOT REVISED.
 PLEASE SEE STAIR 12, WHICH SHOWS DIFFERENT LIGHTS AND
 LOCATIONS ON LIGHTING PLANS THAN THAT OF THE SAME STAIR
 ON BOTH THE NORMAL AND EMERGENCY PHOTO-METRICS. PLEASE
 SEE THE PHOTO-METRICS SHOULD COORDINATE WITH ALL OTHER
 FIXTURES, TYPES ETC.
 PLEASE SEE PREVIOUSLY NOTED DOUBLE LIGHT FIXTURES IN
 STAIRS.
 FBC 106.1.2
  
 13) NOTE:AS PREVIOUSLY NOTED PLEASE CORRELATE AND
 REVISE ALL PHOTO-METRICS FOR STAIR DESIGNATIONS. PLEASE
 SEE THERE ARE MANY SHEETS WHICH STILL INDICATE THE OLD
 DESIGNATIONS. PLEASE SEE SOME SHEETS SHOW THE TABLES
 SHOW ONE DESIGNATION AND THE PLANS SHOW ANOTHER. PLEASE
 SEE SOME TABLES SHOW DESIGNATION, AND THEN THE SHEETS
 FOR THOSE STAIRS ARE BLANK?
 PLEASE SEE MISSING STAIR 6 FOR BOTH NORMAL AND
 EMERGENCY.
 PLEASE SEE TWO OF THE SETS FOR PHOTO-METRICS ARE
 DIFFERENT FROM THE THIRD SET WHERE SOME OTHER
 DESIGNATIONS WERE REVISED, BIT THE OTHER TWO SETS
 CONTAIN SOME SHEETS WHICH WERE REVISED AND SOME WHICH
 WERE NOT. PLEASE SEE THAT EVEN SOME OF THE REVISED
 SHEETS FOR DESIGNATIONS DO NOT CORRELATE.
 PLEASE SEE SHEETS 9-3.0 AND 9-3.2 WHICH BOTH APPEAR TO
 BE THE SAME SHEET. THE SHEET 9-3.2 SHOULD BE THE
 PARTIAL FOR AREA.
 ** PLEASE SEE THAT MANY OF THESE AREAS ARE REDLINED AND
 HIGH-LIGHTED ON PLANS.
 ** PLEASE SEE TWO SETS WHICH THIS IS AN ISSUE FOR
 SHEETS 9-5.0 AND 9-5.2
 FBC 106.1.2
  
 14) NOTE: PLEASE SEE REDLINED DIVISION 16 SPECS FOR
 COLOR CODING FOR 277/480V SYSTEM.
 * BROWN, PURPLE, YELLOW*
  
 15) NOTE: IF THE FIXTURE DESIGNATIONS ARE GOING TO BE
 SHOWN ON PHOTO-METRICS, THEN PLEASE CORRELATE WITH THE
 LIGHTING PLANS. THERE ARE NUMEROUS FIXTURES WHICH DO
 NOT CORRELATE.
 FBC 106.1.2
  
 16) NOTE: LIGHTNING PROTECTION WILL BE UNDER SEPARATE
 PERMIT, HOWEVER MAY USE THESE PLANS TO REFERENCE.
  
 17) NOTE: PLEASE SEE THE FUTURE BUILD OUT FOR IT WILL
 BE UNDER A SEPARATE PERMIT WHICH WILL REQUIRE
 SUBMITTALS FOR ALL EQUIPMENT BEING INSTALLED IN THIS
 ROOM ALONG WITH PLANS, PERMIT APPLICATIONS AND FEES.
  
 18) NOTE: PLEASE SEE THE LOW VOLTAGE SYSTEMS ARE UNDER
 A SEPARATE PERMIT, PLANS AND FEES. PLANS ARE TO BE
 SUBMITTED AT A LATER DATE BEFORE INSTALLATION BEGINS.
 THESE PLANS REFLECT CONDUIT LOCATIONS ONLY.
  
  
 ** PLEASE KNOW AS MANY OF THESE ITEMS ARE REDLINED OR
 HIGHLIGHTED ON PLANS, THIS IS IN NO WAY ALL POSSIBLE
 LOCATIONS. PLEASE REVIEW SAID PLANS.
  
 ** PLEASE CALL TO SET UP A TIME TO GO OVER SOME
 POSSIBLE ALTERNATIVES FOR SOME OF THE ITEMS ABOVE.
  
 IF THERE ARE ANY QUESTIONS OR IF THE NOTES TYPED ARE
 NOT CLEAR IN ANY WAY, PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 ** ALL PLANS, ALL SETS, ALL SUBMITTALS, SPEC BOOKS
 STAMPED.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-02-18 08:14:172007-02-18 08:14
 CONTINUING TO PROCESS, NOTES TO FOLLOW.
2007-02-16 07:01:132007-02-16 07:01:13
 IN REVIEW
2007-02-15 21:14:222007-02-15 21:14:22
 ** REVIEW TO CONTINUE ON 2/16, PROVISO NOTES TO FOLLOW.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-01-22 Cont ID  
Sent By dpalmer Date 2007-01-22 Time 10:07 Rev Time 0.00
Received By dpalmer Date 2007-01-21 Time 19:08 Sent To  
Notes
2007-01-22 10:07:222007-01-22 10:07:22
  
 ** UNSAT **
  
  
 ** PLEASE SEE NOTES FROM PREVIOUS REVIEW STILL NEED TO
 BE ADDRESSED.
  
 ** PLEASE SEE THE NOTES BELOW WILL AFFECT NUMEROUS
 SHEETS WHICH WILL BE REQUIRED TO BE REVISED.
  
 ** PLEASE SEE PREVIOUS NOTES WHICH MENTIONED SOME OF
 THE COMMENTS WERE *REDLINED* ON PLANS; HOWEVER WERE IN
 NO WAY ALL LOCATIONS OR ITEMS. PLEASE SEE ONCE AGAIN
 THE PLANS CONTAIN CIRCLES AROUND AREAS IN WHICH
 COMMENTS ARE MADE.
 PLEASE SEE COMMENTS AS MANY OF THE OLD SHEETS WERE
 SUBMITTED BACK IN SETS WITHOUT BEING REVISED.
  
  
 1) NOTE: PLEASE CORRELATE FP SHEETS WITH THE
 SUBMITTALS. PLEASE SEE THE FP SHEET STILL INDICATES AN
 ELECTRIC FIRE PUMP FOR ONE OF THE PUMPS. THIS IS THE
 6TH TIME THIS COMMENT HAS BEEN MADE. THIS COMMENT WAS
 MADE ON THE 50%, 90%, 1ST 100%,2ND 100%(FIRST UNDER
 PERMIT) AND 2ND SUBMITTAL UNDER PERMIT AND NOW THIS
 REVIEW.
 PLEASE SEE THE SIZES OF THE FIRE PUMPS ON PLANS DO NOT
 CORRELATE WITH THE SUBMITTALS.
 PLEASE SEE THE SIZE OF ONE OF THE TANKS FOR ONE OF THE
 FIRE PUMPS HAS NOW CHANGED TO A *00*SIZE TANK. PLEASE
 SEE THE HP RATING OF ONE OF THE PUMPS HAS NOW CHANGED
 AND DOES NOT CORRELATE WITH THE SUBMITTALS. PLEASE SEE
 THE TYPE AND MANUFACTURE OF THE FIRE PUMP CONTROLLERS
 STILL DO NOT CORRELATE.
 PLEASE SEE THE SUBMITTAL BOOKS CONTAIN MULTIPLE SPECS
 FOR THE TANKS. PLEASE KNOW IF NEW TANKS AND SIZES ARE
 GOING TO BE USED, DO NOT LEAVE THE OLD SUBMITTALS IN,
 IF THEY ARE INDEED OLD.
 PLEASE CORRELATE ALL OF THE ABOVE AND PLEASE CORRECT
 FP0-1.0.
 90.7, 110.3, 695 NEC.
 2003 NFPA-20 CHAPTER 9 AND 10.
 FBC ADMIN SECTION 106.1, 106.1.2, 106.3.5.1.2
  
  
 2) NOTE: PLEASE SEE THE PREVIOUS REVIEW COMMENT WHICH
 STATED THE SIGNATURES ON THE FP SHEETS FROM OTHER THAN
 MR. JAMES MINDUR DID NOT CORRELATE. PLEASE SEE ALL THE
 NEW SHEETS SEEM TO CONTAIN THE SAME SIGNATURE AS SHOWN
 ON THE NEW PLUMBING AND MECHANICAL SHEETS. PLEASE SEE
 THE OLD/NOT REVISED FP SHEETS DO NOT CONTAIN THIS NEW
 SIGNATURE. PLEASE SUBMIT A SIGNED, SEALED, DATED AND
 NOTARIZED LETTER FOR LEGAL SIGNATURE VERIFICATION. THIS
 WILL BE PLACED IN OUR SIGNATURE FILE FOR ANY FUTURE
 REFERENCE.
  
 3) NOTE: PLEASE SEE THE SPEC SUBMITTED FOR THE MTS
 CONTAIN A COVER SHEET FOR AN ATS.
 PLEASE CORRELATE.
 110.3, 90.7, 702.6 NEC.
 FBC 106.1.2, 106.3.5.1.2
  
 4) NOTE: PLEASE SEE THE PLANS IN SOME PLACES STILL
 INDICATE A SMALLER GENERATOR THAN THAT ON OTHER SHEETS
 OF THE PLANS. PLEASE SEE SOME SHEETS AS THEY WERE NOT
 REVISED OR UPDATED FOR OTHER COMMENTS OR FOR THE
 GENERATOR WHICH ARE THE SAME SHEETS FROM THE PREVIOUS
 REVIEWED PLANS.
 PLEASE SEE THE SUBMITTALS FOR THE GENERATOR DO NOT
 CORRELATE. (PLEASE SEE SOME ARE FOR A *KATOLIGHT* UNIT
 WHICH IS A DIFFERENT MANUFACTURE AND DIFFERENT SIZE
 ETC.
 PLEASE CORRELATE ALL OF THE EQUIPMENT.
 110.3, 90.7, 445 NEC.
 NFPA-110 2002 CHAPTERS 5, 6 AND 7.
  
 5) NOTE: PLEASE SEE E0-1.0 FOR MAXIMUM TIMES ON DIMMER
 DEVICE.
 FBC 2004 13-415.1.ABC.1.1 AND .1.2.
  
 6) NOTE: PLEASE SEE LOBBY AREAS/SEPARATE SPACES WHICH
 DO NOT INDICATE OVER RIDE CONTROLS AS GONE OVER IN
 PREVIOUS REVIEW AND IN MEETING. THE RESPONSE LETTER
 MENTIONS THE LOBBIES WERE DONE, HOWEVER NOT ALL. PLEASE
 SEE OTHER AREAS OF BUILDING WHICH DO NOT INDICATE
 CONTROLS FOR SEPARATE SPACES.
 PLEASE KNOW THE REDLINED PLANS WHICH WERE REMOVED FROM
 13-415.1.ABC.1.1, .1.2, .1.3.
  
 7) NOTE: PLEASE SEE THE ENERGY CALCULATIONS STILL DO
 NOT SEEM TO CORRELATE FOR EXTERIOR FIXTURES. THE PLANS
 INDICATE A SUBSTANTIAL AMOUNT OF FIXTURES; HOWEVER
 THESE CALCULATIONS DO NOT SEEM TO CORRELATE. PLEASE SEE
 13-415.1.AB.1.1, 13-415.2.ABC.1.3 ETC
  
 8) NOTE: PLEASE SEE ALL SHEETS IN SETS WHICH ARE THE
 *OVERALL* SHEETS FOR FLOORS ETC WHICH WERE NOT REVISED.
 PLEASE SEE THEY ARE THE SAME SHEETS FROM THE PREVIOUS
 REVIEW.
 PLEASE CLARIFY HOW THE PLANS CONTAIN TWO SEPARATE
 LAYOUTS. ????
 FBC 106.1.2, 106.3.5.1.2
  
 9) NOTE: PLEASE SEE THE LIGHT POLE SUBMITTALS WHICH DO
 NOT ADDRESS PREVIOUS REVIEW COMMENTS. PLEASE SEE THESE
 DO NOT CONTAIN WIND LOAD INFORMATION AND NO
 CALCULATIONS FOR FIXTURES ON POLES OR POLES AND THE
 EFFECTIVE PROJECTED AREA COULD BE LOCATED. AS
 PREVIOUSLY STATED, THIS COULD BE DONE AS A PROVISO AND
 THIS INFORMATION COULD BE SUBMITTED AT A LATER DATE.
 106.1.2
  
 10) NOTE: PLEASE SEE STAIRS 11 AND 12 ARE NOT COMPLETE
 (SEE LATER NOTES FOR STAIR 13).
 PLEASE SEE MISSING LIGHTING FOR EMERGENCY EGRESS OR
 LIGHTING UNDER NORMAL FOR STAIR 12. PLEASE SEE
 PHOTO-METRICS WHICH ARE ALSO STILL MISSING UNDER NORMAL
 AND UNDER EMERGENCY.
 PLEASE SEE LS 101 7.8.1.3, 7.9.2.2 ETC
 PLEASE SEE THAT ALL SHEETS AND ALL OVER-LAYS NEED TO
 CORRELATE AND PLEASE SEE THAT THESE SECTIONS FOR
 MEZZANINE LEVELS ARE NOT COMPLETE.
 FBC 106.1.2
 *PLEASE SEE BUILDING REVIEW NOTES FOR POSSIBLE CONFLICT
 FOR DOOR SWINGS (IF APPLICABLE).
  
 11) NOTE: PLEASE SEE STAIR AREA FOR STAIR (8) ON
 E2-5.0.0. PLEASE SEE THE LIGHTING WAS NOT CHANGED.
 PLEASE SEE THAT ALL SHEETS AND OVER-LAYS NEED TO
 CORRELATE. FBC 106.1
  
 12) NOTE: PLEASE SEE LIGHTING ON E1-6.3 WAS NOT UPDATED
 FOR STAIRS 4 AND 5. PLEASE ALSO SEE NOTES FOR
 PHOTO-METRICS. NFPA-101 7.8, 7.9
 FBC 106.1.2,
  
 13) NOTE: PLEASE SEE THAT THE LIGHTING POWER DENSITY
 CALCULATIONS STILL DO NOT CORRELATE WITH ALL OF THE
 AREA AND ROOM DESIGNATIONS ON PLANS.
 PLEASE SEE UPPER LEVELS, MISSING ALL OF A-6
 DESIGNATIONS.
 FBC 13-415.2
 FBC 106.1.2, 106.3.5.1.2
  
 14) NOTE: PLEASE SEE E2-1.2 WHICH CONTAINS MISSING
 CIRCUITING FOR ROOMS FOR MECHANICAL EQUIPMENT. PREVIOUS
 NOTES REQUESTED ALL ROOM DESIGNATIONS TO BE COORDINATED
 ETC.
 PLEASE SEE THESE ARE ROOMS WHICH ARE ELEVATOR EQUIPMENT
 ROOMS WHICH DO NOT CONTAIN THE DEDICATED CIRCUITS AS
 REQUIRED PER 620.23.
 PLEASE SEE DESIGNATIONS FOR ELEVATOR EQUIPMENT ROOMS
 SHOULD BE ON PLANS AS LIGHTING IN THESE ROOMS IS BEING
 SHOWN FEEDING OTHER AREAS.
 ROOMS FOR ELEVATORS 6,7,8, AND 9.
 PLEASE SEE NOTES WITH RESPECT TO UPPER EQUIPMENT
 ROOM(S).
  
 15) NOTE: PLEASE SEE PLANS FOR UPPER EQUIPMENT ROOMS
 ARE NOT COMPLETE. THIS WAS GONE OVER IN MEETING,
 HOWEVER THE SAME SHEETS WERE SUBMITTED BACK IN FOR
 REVIEW.
 PLEASE CLARIFY THE AREA/ROOM DESIGNATIONS FOR THE
 ELEVATOR EQUIPMENT FOR UNITS 1, 2 AND 3.
 WHERE IS THIS ELEVATOR EQUIPMENT ROOM? PLEASE SEE IF
 THIS IS THE ROOM LOCATED ON UPPER FLOORS POWER PLANS
 E1-6, E1-6.1 WHERE IS THE EQUIPMENT AND THE DEDICATED
 BRANCH CIRCUITS ETC. PLEASE ALSO SEE LIGHTING PLANS.
 PLEASE SEE 620.22, .23, .24, 51 ETC.
  
 16) NOTE: PLEASE LIGHTING AND POWER PLANS FOR THE SAME
 FLOOR/AREA AS THE LIGHTING AND CONTROLS STILL INDICATE
 SWITCHING OUTSIDE STAIR WALL? PLEASE SEE THE SAME PLANS
 WERE SUBMITTED WITH OUT CHANGES TO THE UPPER DOME AREA
 FOR LIGHTING CONTROL, EGRESS LIGHTING ETC.
 PLEASE SEE THE UPPER AREA PLANS NEED TO BE COORDINATED
 AND COMPLETE.
 NFPA-101 7.8,7.9, FBC 13-415.1.ABC.1.1, ETC, NEC 620,
 408, 310.16, 240.4 ETC
 FBC 106.1.2, 106.3.5.1.2 ** PLEASE CALL TO GO OVER
 THESE SHEETS.
  
 17) NOTE: PLEASE SEE STILL MISSING BATTERY BACK LIGHT
 FIXTURES OF SOME KIND ON MECHANICAL EQUIPMENT ROOMS,
 ELEVATOR EQUIPMENT ROOMS.THIS IS FOR MULTIPLE ROOMS
 LS 101 7.8, 7.9, NEC 700.16, 700.12E ETC.
 PLEASE SEE REDLINED SHEETS.
  
 18) NOTE: PLEASE STILL MISSING THE MANUFACTURES
 SPECS/CUT SHEETS FOR THE TANK LESS WATER HEATERS.
 110.3, 90.7. THIS COULD BE DONE AS A *PROVISO* ALTHOUGH
 IT WAS ALSO STATED IN PLUMBING REVIEW COMMENTS.
  
 19) NOTE: PLEASE SEE PHOTO-METRICS. PLEASE CORRELATE
 ALL STAIRS AND AREAS FOR EGRESS. PLEASE SEE PREVIOUS
 NOTE ABOVE WHICH MENTIONS TO COMPLETE STAIRS 11, 12
 ETC.
 PLEASE SEE THERE ARE SEVERAL SHEETS WHICH THE
 TABLE/INFORMATION IS NOT PRINTED.
 PLEASE SEE SHEETS E8-5.1 THRU 8-6.4 WHICH STILL
 INDICATE LIGHTING PHOTO-METRIC INFORMATION STILL
 PENDING.
 PLEASE SEE SHEETS E9-5.1 THRU 9-5.2 WHICH ALSO INDICATE
 INFORMATION STILL PENDING.
 PLEASE COMPLETE AT THIS TIME AS REQUESTED.
  
 20) NOTE: PLEASE SEE STAIRS ARE STILL BEING NUMBERED
 WITH NUMERICAL DESIGNATIONS WHICH DO NOT CORRELATE WITH
 THE PLANS. STAIR 1, STAIR 4, STAIR 8, ETC.
 106.1, 106.1.2, 106.3.5.1.2
 LS 101
 PLEASE CLARIFY.
  
 21) NOTE: PLEASE SEE SOME BATHROOMS STILL MISSING
 BATTERY TYPE BACK UP LIGHT. PLEASE SEE LIBRARY MEN?S
 AND WOMEN?S ON E2-1.2
  
 22) NOTE: PLEASE SEE STAIR 1 ON OVER ALL PLANS ON
 E2-5.0 AND 2-5.1 FIXTURE TYPE, WHERE IS THE E2? PLEASE
 ALSO CLARIFY WHERE THIS STAIR CONTINUES UP.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-01-22 06:31:132007-01-22 06:31:13
 IN PROGRESS
2007-01-21 19:09:402007-01-21 19:09:40
 ELECTRICAL REVIEW COMPLETED.
 THE PLANS WILL BE GOING INTO A "F" STATUS AND NOTES ARE
 TO FOLLOW ONCE THEY ARE COMPLETED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-12-25 Cont ID  
Sent By dpalmer Date 2006-12-25 Time 20:33 Rev Time 0.00
Received By dpalmer Date 2006-12-24 Time 18:10 Sent To  
Notes
2006-12-25 20:33:37** UNSAT 2ND REVIEW **
  
  
 **** CITY CENTER *******
  
 FOURTH REVIEW, 2ND UNDER PERMIT APPLICATION.
  
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A "NO" IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN "OK" WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A "NO/OK" MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
  
 1) NOTE: NO, PLEASE SEE THREE SETS OF ALL ARE REQUIRED.
 PLEASE SEE MISSING A THIRD SET OF ELECTRICAL SUBMITTALS
 FOR GENERATOR, ATS, MTS ETC.
 PLEASE ALSO SEE OTHER NOTES FOR MISSING THE LIGHTING
 SPEC BOOKS AND ENGINEERING CALCULATIONS WHICH WERE
 PREVIOUSLY SUBMITTED.
 ENGINEERING FOR SELECTIVE COORDINATION PREVIOUSLY
 SUBMITTED ETC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW WHEN SUBMITTING FOR FINAL PERMITTING AND
 STAMPING, A THIRD SET OF SIGNED, DATED AND SEALED PLANS
 WILL BE REQUIRED.
 PLEASE SEE FBC ADMINISTRATIVE SECTION AS ADOPTED BY THE
 CITY OF WEST PALM BEACH, 106.1.2106.1.3, 109.3.6 FOR
 THRESHOLD BUILDINGS. THIS IS WILL BE REQUIRED FOR ALL
 DOCUMENTATION AND PLANS AND FOR ALL TRADES WHETHER OR
 NOT COMMENT IS MADE BY OTHER TRADES.
  
 2) NOTE: NO, PLEASE SEE SYMBOL LEGEND ONLY HAD CHANGES
 TO TWO OF THE DEVICES. PLEASE SEE ALL SWITCH/OVER RIDE
 TYPE DEVICES INCLUDING THE OC SENSOR SHOULD INDICATE ON
 THE SYMBOL LEGEND ITS DESIGNATION AND TIMES ON OVER
 RIDES. THIS WOULD INCLUDE S3, ST, OC ETC.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC CHAPTER 13. PLEASE SEE 13-415.1.ABC.1.1,
 .1.2 AND .1.3.
 PLEASE BE SURE ALL DEVICE ON PLANS CORRELATE WITH THE
 DEVICE SYMBOL LEGEND.
 PLEASE BE SURE MAX TIME OF OVER -RIDES ARE SHOWN. IF
 TIMER TYPE, (4HRS MAX), IF OCCUPANCY SENSOR TYPE (30
 MINS MAX).
 PLEASE SEE ADDITIONAL COMMENTS FOR CONTROLS AND SYSTEM
 BEING PROPOSED.
  
 3) NOTE: OK.
  
 4) NOTE: OK/NO, PLEASE SEE THESE WERE NOW SUBMITTED
 HOWEVER PLEASE SEE NEW NOTES AT THE END OF THESE
 COMMENTS AS THESE ARE NOW BEING SUBMITTED AND REVIEWED
 FOR THE FIRST TIME AND THERE ARE COMMENTS ON DOCUMENTS
 SUBMITTED.
 PLEASE ALSO SEE NEW NOTES PERTAINING TO THE SIGNATURE
 OF THE MECHANICAL ENGINEER OF RECORD ON SAID
 DOCUMENTS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT COMPLETED ENERGY CALCULATIONS FOR THE
 ENTIRE BUILDING FOR REVIEW OF ALL TRADES. PLEASE KNOW
 AS NONE WERE SUBMITTED AT THIS TIME THERE ARE MANY
 ITEMS WHICH CAN NOT BE VERIFIED WITH THE PLANS,
 EQUIPMENT AND LIGHTING.
 PLEASE SEE 13-415.1.AB.1.
  
 5) NOTE: OK/NO, PLEASE SEE THESE WERE SUBMITTED AND
 SEEM TO BE OK, HOWEVER AS NOTED IN NOTE #4 ABOVE THERE
 ARE NEW NOTES BASED ON THE COORDINATION OF THESE
 DOCUMENTS WITH THE ENERGY CALCULATIONS SUBMITTED.
 PLEASE SEE THE TOTALS ON THE WATTAGE DO NOT SEEM TO
 CORRELATE WITH THE ENERGY CALCULATIONS AS SUBMITTED.
 PLEASE ALSO SEE NEW NOTES.
 PLEASE KNOW THE THREE SETS OF LIGHTING POWER DENSITIES
 SHALL CONTAIN TITLE BLOCKS FOR THE ENGINEER AND/OR FIRM
 OF RECORD. THIS MAY BE RE-DONE ON NEW SHEETS WHICH
 CONTAIN THESE TITLE BLOCKS, STAMPED ON EACH SHEET WHICH
 IS SIGNED AND SEALED BY THE ENGINEER OR HANDWRITTEN.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 13-415.2, 13-415.2ABC.1 FOR MINIMUM AND
 MAXIMUM PERFORMANCE CALCULATIONS. PLEASE SEE THE
 CALCULATIONS SUBMITTED SHOWING THE LIGHTING POWER
 DENSITIES (LPD) ARE NOT COMPLETE AND/OR THERE ARE ITEMS
 WHICH DO NOT CORRELATE WITH SAID PLANS.
 PLEASE SEE THERE ARE MANY ROOMS INDICATED ON PLANS
 WHICH COULD NOT BE LOCATED IN CALCULATIONS OR THERE ARE
 ROOMS ON CALCULATIONS WHICH COULD NOT BE LOCATED ON
 PLANS.
 PLEASE CORRELATE AND PLEASE SEE SOME OF THE LPD'S SEEM
 TO BE VERY HIGH FOR SOME OF THE ROOMS AND AREAS AS
 NOTED AND SHOWN.
 PLEASE SEE OFFICE IN PARKING GARAGE FOR INSTANCE.
 PLEASE SEE SOME OTHERS WHICH BASED ON THE TABLES AS
 SET-FORTH IN THE CODE MAY ALLOW 1.7, THE CALCULATIONS
 MAY SHOW 10.5 ETC.
 PLEASE REVIEW ALL AND RE-ADJUST AS REQUIRED AND
 NEEDED.
  
 6) NOTE: NO, UNABLE TO VERIFY AT THIS TIME DUE TO THE
 CONFLICTS BETWEEN THE ENERGY CALCULATIONS FOR EXTERIOR
 LIGHTING AND THE ALLOWANCE LEVELS NOT BEING SHOWN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 13-415.2.ABC.1.3 FOR ALL EXTERIOR LIGHTING
 ALLOWANCES, INCLUDING THAT WHICH IS DECORATIVE. PLEASE
 SEE THERE ARE EXCEPTIONS FOR SOME AREAS; HOWEVER THESE
 AREAS AS LISTED WOULD BE REQUIRED BY SECTIONS AS
 LISTED. PLEASE SEE 13-415.0(3) (EXCEPTS).
  
 7) NOTE: OK/NO, PLEASE SEE THE PLANS NOW SEEM TO
 INDICATE THE EQUIPMENT MORE IN DETAIL, HOWEVER AS NOTED
 IN NOTE #1, THE MANUFACTURES SPECS/CUT SHEETS WERE NOT
 SUBMITTED BACK. THIS REVIEWER ONLY HAS THE ONE BOOK
 WHICH WAS RETAINED BY THIS OFFICE.
 WHEN SUBMITTING BOOKS/SPECS, PLEASE BE SURE TO HIGH
 LIGHT AND COORDINATE WITH THE PLANS SUBMITTED FOR THE
 EQUIPMENT AND DEVICES BEING INSTALLED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS SHALL INDICATE THE ACTUAL PANEL BEING
 USED FOR LIGHTING CONTROLS. PLEASE SEE THERE ARE
 SEVERAL PANELS INDICATE IN THE MANUFACTURE SPECS/CUT
 SHEETS SUBMITTED AND THE ACTUAL UNIT NEEDS TO BE
 HIGH-LIGHTED IN SPECS. PLANS SHALL ALSO BE REQUIRED TO
 PROVIDE THE TECHNICAL INFORMATION AT EACH LIGHTING
 CONTROL PANEL. (LCP)
 ** PLEASE KNOW AS REFERENCE TO LIGHTING CONTROL PANELS
 IN NOTES HERE ON WILL BE DESIGNATED AS "LCP'S". PLEASE
 SEE RISER INDICATES LCP'S AS 225A RATED, WHICH IS OK,
 HOWEVER PLEASE BE SURE THE INFORMATION AS SHOWN ON
 CUT/SPEC SHEETS IS BROUGHT OVER TO THE PLANS AND LISTED
 ON EACH LCP.
  
 8) NOTE: OK/NO, PLEASE KNOW MOST OF THE SYSTEM IS
 UNDERSTOOD HOWEVER THERE ARE AREAS IN WHICH A SWITCH
 TYPE DEVICE (SENTRY) IS BEING INSTALLED ALONG WITH AN
 OC (OCCUPANCY SENSOR) TYPE DEVICE. THE DETAIL WAS
 LOCATED ON 7-2.0 HOWEVER THIS WOULD STILL PERMIT THE
 TURNING OFF LIGHTS IN AN UNWANTED FASHION.PLEASE SEE
 EGRESS STAIRS FOR MEZZANINE AREA WHICH COULD BE TURNED
 OFF, YET OF AN OCCUPANT WAS STILL LOCATED ON THE UPPER
 LEVEL THEY WOULD HAVE NO CONTROL OF LIGHTING AS SHOWN.
  
 PLEASE SEE ROOF TOP AREA ON E1-6.1 WHICH LOCATES A
 SWITCH ON WHAT APPEARS TO BE AN OUTSIDE WALL TO CONTROL
 LIGHTING IN ELEVATOR EQUIPMENT ROOM AS WELL AS OTHER
 LIGHTING AS REQUIRED FOR LIFE SAFETY.
 PLEASE SEE OTHER AREAS WHICH CONTAIN BOTH.
 PLEASE ALSO SEE AS NO SPECS WERE SUBMITTED BACK, COULD
 NOT LOCATE A LETTER FROM THE LUTRON MANUFACTURE WHICH
 PERMITS THE USE OF THE SENTRY SWITCH IN THEIR SYSTEM.
 PLEASE SEE AREAS OF MEETINGS ROOMS AND COMMISSION
 CHAMBERS AREA WHICH DO NOT PROVIDE ENOUGH INFORMATION
 FOR HOW THESE WILL BE CONTROLLED. PLEASE SEE THAT THE
 NOTE ON THE PLANS FOR THIS TO BE PROVIDED BY LIGHTING
 TECHNICAL NEEDS TO BE REPLACED WITH ACTUAL DETAILS ON
 HOW THESE WILL BE ADDRESSED TO COMPLY WITH CHAPTER 13
 AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW THERE IS CONCERN OVER THE TYPE OF SYSTEM
 BEING PROPOSED AND CONTROLS OF SAID SYSTEM. PLANS CALL
 FOR A "SWEEP" EACH HOUR FOR THE SYSTEM OUT OF NORMAL
 BUSINESS HOURS AND THIS WILL TURN OFF ANY AND ALL
 DEVICES. THE DEVICES WILL THEN HAVE THE ABILITY TO OVER
 RIDE THE SYSTEM IN ANY PARTICULAR AREA WHICH THE
 CIRCUIT/SWITCH IS DESIGNATED TO. PLEASE KNOW THIS
 BUILDING IN SEVERAL SECTIONS WILL BE OCCUPIED OUT OF
 THE NORMAL BUSINESS HOURS WHICH ARE SET UP AND WILL
 CAUSE DARKNESS EACH HOUR EVEN WHEN OCCUPIED. PLEASE SEE
 SPECS SHEETS AS SUBMITTED SPEAK OF THE INCLUSION OF AN
 OCCUPANT SENSOR TYPE DEVICE TO ALLEVIATE THIS.
 (UNINTENDED BLACK-OUTS). PLEASE SEE AREAS LIKE THE
 LIBRARY, COMMISSIONS CHAMBERS, OFFICE DESIGNATED FOR
 POLICE, AND OTHER AREAS.
 PLEASE SEE THE CODE ON THE OTHER HAND FOR ALL AREAS
 WHICH DURING NORMAL BUSINESS HOURS WHICH WILL REQUIRE
 ROOMS TO BE OFF. PLEASE SEE 13-415.1.ABC.1.2, FOR ALL
 ROOMS CONTAINING FLOOR TO CEILING HEIGHT PARTITIONS
 WHICH WILL REQUIRED SEPARATE CONTROL. PLEASE SEE AS
 SHOWN ON PLANS, THESE ROOMS WILL COME "ON" AT THE SET
 BUSINESS HOUR TIMES AND WILL REMAIN ON UNTIL AFTER THE
 "ONE HOUR SWEEP" AFTER THE NORMAL OPERATIONAL TIMES
 HAVE PASSED.
 PLEASE SEE CLOSETS, OFFICES, STORAGE AREAS ETC. THERE
 ARE FAR TOO NUMEROUS ROOMS TO LIST.
 PLEASE SEE THERE ARE MANY ROOMS ON PLANS WHICH DO
 INDICATE "OC" TYPE DEVICES; HOWEVER THERE IS NOT DETAIL
 ON THE LIGHTING CONTROL RISER HOW THESE WILL BE
 CONNECTED OR TIED IN.
 PLEASE SEE BATHROOMS ETC.
 PLEASE KNOW THIS TYPE OF DEVICE WILL WORK IN MANY AREAS
 IN THIS BUILDING; HOWEVER THERE ARE AREAS WHICH WILL
 NOT MEET CODE OR THE INTENT IN SEPARATE SPACES. PLEASE
 KNOW AT THIS TIME, AS SHOWN THERE ARE SEVERAL ITEMS
 WHICH WILL BE REQUIRED TO BE ADJUSTED. PLEASE ALSO
 OBTAIN A LETTER FROM THE "SENTRY SWITCH" MANUFACTURE
 WHICH PERMITS THIS TYPE OF DEVICE TO BE USED WITH THE
 LUTRON GRAFIK PANEL.
 110.3, 90.7 NEC.
  
 9) NOTE: OK/NO, PLEASE SEE COORDINATION OF NUMERICAL
 IDENTIFICATION SEEMS TO BE BETTER; HOWEVER PLEASE SEE
 SEVERAL AREAS AND ROOM HAVE THEIR DESIGNATION COVERED
 BY A DEVICE, FIXTURE OR SOME OTHER ITEM.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THERE ARE SEVERAL ROOM NUMERICAL
 DESIGNATIONS ON CALCULATIONS WHICH COULD NOT BE LOCATED
 ON PLANS. PLEASE SEE GARAGE PLANS.
 PLEASE SEE SOME WHERE THE ROOM DESIGNATION IS THERE
 HOWEVER IT SEEMS TO BE VERY LIGHT IN COLOR AND CAN NOT
 BE EASILY READ. PLEASE SEE OTHER AREAS WHICH THE
 FIXTURE DESIGNATION COVERS THE ROOM IDENTIFICATION OR
 VICE VERSA, THE FIXTURE TYPE COULD NOT BE SEEN DUE TO
 THE OVER LAY OF THE NUMERICAL DESIGNATION.
 PLEASE COORDINATE. A1-116-2-1.610 ETC
 FBC ADMIN SECTION 106.1.2, 106.1.3
  
 10) NOTE: OK, HOWEVER PLEASE KNOW BASED ON FURTHER
 COMMENTS, ADJUSTMENTS IN FIXTURE TYPES AND DESIGNATIONS
 WILL BE NEEDED.
  
 11) NOTE:NO, PLEASE SEE THERE ARE SEVERAL ROOMS WHICH
 STILL DO NOT INDICATE A BATTERY BACK UP FIXTURE OF SOME
 SORT WHICH WILL BE REQUIRED.
 FIRE PUMP ROOMS, MAIN ELECTRICAL ROOM, MAIN MECHANICAL
 ROOM, THE MAIN MECHANICAL ROOM ELECTRICAL ROOM,
 ELEVATOR EQUIPMENT ROOM. ETC.
 PLEASE ALSO SEE NEW NOTES FOR ROOF TOP/ELEVATOR
 EQUIPMENT ROOM AND OUTSIDE AREA TO STAIR TWO. PLEASE
 ALSO SEE GARAGE STAIR TOWERS WILL ALSO BE REQUIRED TO
 CONTAIN MINIMUM BATTERY BACK UP FOR FIXTURES AS OTHER
 STAIR TOWERS IN MAIN BUILDING ARE DONE.
 ** PLEASE ALSO SEE FIRE REVIEW COMMENTS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT BATTERY BACK UP FIXTURES OF SOME TYPE
 WILL BE REQUIRED FOR THE FOLLOWING LOCATIONS. SOME ARE
 SHOWN ALREADY, HOWEVER NOT ALL. THE MAIN ELECTRICAL
 ROOM, THE FIRE COMMAND CENTER, BOTH FIRE PUMP ROOMS,
 ELEVATOR EQUIPMENT ROOM, AND AT THE LOCATION OF THE
 ROOF TOP GENERATOR WILL ALL REQUIRE THIS. PLEASE SEE
 THAT ALL STAIR TOWERS AND EGRESS PATHS SHALL ALSO
 INCLUDE SOME SORT OF BATTERY BACK UP FIXTURE. THERE ARE
 MANY LOCATIONS WHICH INCLUDE THIS; HOWEVER AS SOME OF
 THE FIXTURE INFORMATION IS NOT CLEAR AT THIS TIME THIS
 CAN NOT BE VERIFIED. THIS BUILDING IS EXPECTED TO BE
 OCCUPIED IN THE TIME OF POWER OUTAGES AND IN THE EVENT
 OF THE TRIPPING OF A SINGLE MEANS OF OVER CURRENT
 PROTECTION (EMSB1) OR GEN MAIN, THIS WILL PLACE MANY
 AREAS IN COMPLETE DARKNESS WHICH IS NOT PERMITTED. NEC
 700.12E, 700.16, LS 101 7.9.
  
 12) NOTE: OK.
  
 13) NOTE: OK.
  
 14) NOTE: NO, PLEASE SEE COMMENTS WITH RESPECT TO STAIR
 TOWERS IN GARAGE AND OTHER ROOMS WITH THESE
 DESIGNATIONS WHICH MAY BE CHANGED OR ADJUSTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FIXTURE "E", PLEASE SEE IT APPEARS TO BE
 BATTERY BACK UP, BUT NOT ENOUGH INFORMATION IS
 PROVIDED. PLEASE SEE FIXTURES, Z,ETC.
  
 15) NOTE: OK.
  
 16) NOTE: NO, PLEASE SEE RESPONSE LETTER MENTIONS THIS
 IS TO BE DONE BY THE STRUCTURAL ENGINEER/DESIGNER OF
 RECORD HOWEVER COULD NOT LOCATED ANY DETAIL FOR THIS ON
 THE S SHEETS. PLEASE SEE THE SAME DETAIL FOR GROUND
 LEVEL POLES IS BEING USED FOR ROOF TOP MOUNTING? PLEASE
 SEE NEW NOTES WITH RESPECT TO THE S SHEETS AND TITLE
 BLOCKS MISSING AND OTHER NOT CONTAIN ANY CERTIFICATE OF
 AUTHORIZATION NUMBER AS REQUIRED. SEE NEW ELECTRICAL
 NOTES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE ALL MINIMUM WIND LOADING FOR SITE
 LIGHTING LIGHT POLES, AND THAT OF THE POLES ON GARAGE
 ROOF STRUCTURE. PLEASE KNOW A DETAIL ON HOW THESE WILL
 BE ATTACHED ON PARKING DECK OF THE GARAGE AND POLE
 DETAIL FOR GROUND MOUNTED/BURIED POLES WILL BE
 REQUIRED. PLEASE KNOW ALL SHOW MEET THE FBC 140MPH
 (3SEC GUST) 120MPH SUSTAINED.
 THE STRUCTURAL CALCULATIONS WILL BE REVIEWED BY THE
 BUILDING PLAN REVIEWER.
 FBC 106.1.2 ADMIN SECT.
  
 17) NOTE: OK.
  
 18) NOTE: OK.
  
 19) NOTE:NO, THIS IS STILL UNCLEAR HOW THE SHORTER
 LENGTHS OF CONDUCTORS OUT TO FIXTURES ACTUALLY CONTAIN
 A HIGHER VOLTAGE DROP.
 PLEASE SEE OTHER COMMENTS ON THE FOLLOWING NOTE #20.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE PROVIDE THE VOLTAGE DROP ON THIS SAME CIRCUIT AS
 NOTED ABOVE IN NOTE # 18, PLEASE SEE FIXTURE SA
 INDICATE #8'S, AND YET SB WHICH CONTAIN A LONGER RUN
 AND MORE FIXTURES ONLY INCREASE UP TO A #10 AWG. PLEASE
 SEE FBC 13-413.1.ABC.1.2.
  
 20) NOTE:NO, COULD NOT LOCATE ANY FOR BRANCH
 CIRCUITING. ONLY LOCATED THE FEEDERS ON RISER.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE A WORST CASE FOR BOTH FEEDER AND BRANCH
 CIRCUIT.
 13-413.1ABC.1.
 IT IS NOTEDTHAT ON MANY OF THE PANEL SCHEDULES A VD %
 IS ALREADY SHOWN, HOWEVER PLEASE BE SURE TO INDICATE
 THE ABOVE. (CAN BE DONE ON A SIMPLE TYPICAL TABLE). FBC
 106.1.2.
  
 21) NOTE: NO, SAME NOTE. PLEASE SEE THE FS SHEETS STILL
 INDICATE ELECTRICAL FIRE PUMPS ALONG WITH DIFFERENT
 SIZES OF EQUIPMENT THAN THAT SUBMITTED IN THE
 ELECTRICAL SUBMITTAL BOOKS. PLEASE SEE DIFFERENT
 MANUFACTURE, ETC.
 PLEASE SEE THAT BASED ON THE COMMENTARY PROVIDED FOR
 FUEL USAGE, THE FUEL FOR ONE APPEARS TO BE OK, HOWEVER
 THE OTHER (110HP) DOES NOT MEET THE MINIMUM LEVEL OF
 FUEL REQUIRED. PLEASE SEE AS TWO DIFFERENT SIZE PUMPS
 ARE SUBMITTED, I AM UNABLE TO REVIEW WHICH THE ONE FOR
 INSTALLATION AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE 100% FIRE SPRINKLER PLANS SUBMITTED DO
 NOT CORRELATE WITH THE FA OR ELECTRICAL PLANS SUBMITTED
 WITH RESPECT TO THE FIRE PUMPS. PLEASE SEE THE FS
 SHEETS WHICH INDICATE ELECTRIC, ELECTRICAL/ DIESEL AND
 DIESEL. PLEASE SEE THE ELECTRICAL PLANS AND THE
 MANUFACTURE SPECS/CUT SHEETS SUBMITTED ONLY INDICATE
 DIESEL.
 PLEASE SEE THE MINIMUM FUEL TANK SIZE SHALL BE
 SUFFICIENT FOR A MINIMUM OF 8HRS AT 100% LOADS. IF
 ELECTRICAL AND BEING DRIVEN BY THE BACK UP POWER OF AN
 EMERGENCY GENERATOR, THE ON-SITE FUEL SUPPLY SHALL BE
 BASED ON THE 100% LOAD OF THE FIRE PUMP AND ALL OTHER
 LEGAL AND EMERGENCY STAND-BY LOADS AT 100% FOR TIMES
 REQUIRED.
 PLEASE SEE 2002 NFPA-110, TEXT EXTRACTED FORM THE
 CODE:
 9.6.2.2 THE FUEL SUPPLY CAPACITY SHALL BE SUFFICIENT
 TO PROVIDE 8 HOURS OF FIRE PUMP OPERATION AT 100
 PERCENT OF THE RATED PUMP CAPACITY IN ADDITION TO THE
 SUPPLY REQUIRED FOR OTHER DEMANDS.
 PLEASE SEE NFPA-20 2003 IF DIESEL DRIVEN AND THE SAME
 AMOUNT OF FUEL REQUIRED WHICH EQUALS 1GAL PER HP PER
 HOUR PLUS 5% FOR SUMP AND 5% FOR EXPANSION. PLEASE SEE
 THE FOLLOWING THE CODE.
 11.4.3.1 FUEL SUPPLY TANK(S) SHALL HAVE A CAPACITY AT
 LEAST EQUAL TO 5.07 L PER KW (1 GAL PER HP), PLUS 5
 PERCENT VOLUME FOR EXPANSION AND 5 PERCENT VOLUME FOR
 SUMP AND THE COMMENTARY SECTION AS FOLLOWS, A.11.4.3
 THE QUANTITY 5.07 L PER KW (1 GAL PER HP) IS EQUIVALENT
 TO 0.634 L PER KW (1 PINT PER HP) PER HOUR FOR 8
 HOURS. WHERE PROMPT REPLENISHMENT OF FUEL SUPPLY IS
 UNLIKELY, A RESERVE SUPPLY SHOULD BE PROVIDED ALONG
 WITH FACILITIES FOR TRANSFER TO THE MAIN TANKS.
  
 22) NOTE: OK.
  
 23) NOTE: OK/NO, PLEASE SEE AS SOME AREAS ARE NOT CLEAR
 UNABLE TO VERIFY ANY GFI NOTATION. PLEASE SEE SOME ARE
 SHOWN WITH THE GFI IDENTIFICATION AND IF THE SYMBOLS
 WERE A LITTLE MORE CLEAR THE SYMBOL LEGEND ON E0.10 MAY
 BE IF USE.
 PLEASE ALSO SEE SHEET E1.-1.2 WHICH SHOULD BE A SECTION
 OF THE BUILDING WHICH WOULD BE LARGER IN SIZE. IT SEEMS
 SOMETHING WITH THE PRINTING OF SHEET CAUSED SHEET TO BE
 MUCH SMALLER. PLEASE SEE KITCHEN AREAS WHICH ARE
 LOCATED ON THIS SHEET COULD NOT BE VERIFIED AT THIS
 TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NEC 210.8B3 FOR ALL RECEPTACLES IN KITCHENS
 IN OTHER THAN DWELLING UNITS. PLEASE SEE THIS WOULD BE
 REQUIRED FOR CAFE/ KITCHENETTE AREAS AS SHOWN ON
 PLANS.
  
 24) NOTE: OK.
  
 25) NOTE: NO, PLEASE SEE PHOTO-METRICS ARE CONFUSING.
 PLEASE SEE THE GARAGE STAIRS SEEM TO NOW BE SHOWN,
 HOWEVER THERE IS NO SPECIFIED UNDER NORMAL OR UNDER
 EMERGENCY. PLEASE SEE DESIGNATIONS ON ALL OTHER STAIRS
 AND LABELING OF AREAS DOES NOT CORRELATE WITH ACTUAL
 PLANS AND STAIR TOWERS AS SHOWN. PLEASE KNOW THIS
 COMMENT IS NOT JUST FOR GARAGE STAIRS AS PREVIOUS
 COMMENT WAS TO ADDRESS ALL PHOTO-METRICS. PLEASE SEE
 MISSING STAIR 13, MEZZ STAIRS, PLEASE SEE OTHER STAIR
 DESIGNATIONS NOT LABELED ETC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING THE PHOTO-METRICS FOR THE GARAGE
 STAIR TOWERS. PLEASE SEE THE PHOTO-METRICS AS SUBMITTED
 ARE A LITTLE CONFUSING. PLEASE PREVIOUS COMMENTS ONLY
 REQUESTED EGRESS PATHS OF LEVELS SURFACES/ CORRIDORS
 AND EGRESS PATHS THAT OF THE STAIR TOWERS. PLEASE SEE
 THERE MUCH INFORMATION SUBMITTED GIVING FIXTURE
 DESIGNATIONS AND ROOM BY ROOM LEVELS? PLEASE PROVIDE
 THE EGRESS PATHS INFORMATION INDICATING THE CLEAR
 NORMAL AND EMERGENCY LEVELS AS NEEDED AND REQUIRED BY
 CODE.
 PLEASE PROVIDE A BREAKDOWN OF THE NORMAL AND EMERGENCY
 AVERAGE. PLEASE SEE THAT INFORMATION OF WHICH IS
 SUPPLIED ON EACH "OVER-ALL" SHEET DOES NOT SUPPLY THE
 INFORMATION AS NEEDED.
 PLEASE SEE 9-4.1 WHICH INDICATES IN TITLE BLOCK,
 EMERGENCY/ NORMAL?
  
 26) NOTE: OK.
  
 27) NOTE: NO, PLEASE SEE SOME ARE STILL SHOWING THIS
 DESIGNATION.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE CLARIFY GARAGE LIGHTING WHICH SHOWS "ON" NEXT
 TO SOME FIXTURES ON PLANS. (RAMP AREAS) THIS IS UNCLEAR
 AT THIS TIME WHAT IS MEANT BY THIS.
 FBC 106.1.2 ADMIN SECTION
  
 28) NOTE: OK.
  
 29) NOTE: OK.
  
 30) NOTE: OK/NO, PLEASE SEE ROOM LAYOUT DESIGNATION ON
 SHEET E1-1.3 INDICATES SHEET E4-1.0, WHEN IT SHOULD BE
 E- 1.1
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING THE ELECTRICAL ROOM FOR 1HMGB AND
 1HMGA ON THE LAYOUTS FOR THE ELECTRICAL ROOMS. PLEASE
 PROVIDE. 106.1.2,
 NEC 110.26
  
 31) NOTE: NO/OK, PLEASE SEE THE DOOR SWINGS SEEM TO BE
 OK, HOWEVER PLEASE SEE NO NOTE FOR PANIC HARDWARE AS
 REQUIRED COULD BE LOCATED ON PLANS. THIS WILL BE
 REQUIRED FOR MAIN ELECTRICAL ROOM AND MAIN ELECTRICAL
 EQUIPMENT FOR MECHANICAL MAIN ELECTRICAL EQUIPMENT
 ROOMS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MAIN ELECTRICAL ROOM AND THE MISSING
 ELECTRICAL ROOM FROM NOTE #30 ABOVE WHICH IS STILL
 INDICATING DOORS WITH AN "IN-SWING" WHICH IS NOT
 PERMITTED. PLEASE ALSO BE SURE TO ADD A NOTE WITH
 RESPECT TO PANIC HARDWARE REQUIRED FOR ALL DOORS AS
 REQUIRED PER 110.26. (MAIN ELECTRICAL ROOM/ AND ROOM
 NOTED ON NOTE #30).
 PLEASE SEE THE DOOR SWINGS WERE NOTED ON ALL OF THE
 REVIEWS BASED ON THE 50%, 90% AND THIS REVIEW. PLEASE
 GO OVER ALL PLANS AND DOORS.
  
 32) NOTE: NO, PLEASE SEE SEVERAL OF THESE UNITS ARE
 BEING SHOWN ON PLANS AT JANITOR CLOSET LOCATIONS,
 HOWEVER NOT ALL OF THESE ROOMS CONTAIN THESE. PLEASE
 ALSO SEE SEVERAL KITENETTE AREA WHICH ALSO INCLUDES
 THESE HOWEVER MANY DO NOT? IN EITHER CASE PLEASE SEE NO
 SPECS WERE SUBMITTED AND NO DISCONNECTING MEANS FOR ALL
 UNITS COULD BE LOCATED ON PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS FOR AL
 THE TANK-LESS WATER HEATER UNITS. THESE MAY ALSO BE
 LABELED AS INSTA-HOTS. PLEASE SEE MISSING DISCONNECTS
 AS REQUIRED ON THESE UNITS. THESE COULD NOT BE LOCATED
 ON PLANS.
 PLEASE SEE SIZING OF THE OVER CURRENT DEVICES,
 DISCONNECTS AND ETC SHALL BE BASED ON EACH UNIT. PLEASE
 SEE 422.31, 110.3, AND 90.7.
  
 33) NOTE:NO, SAME NOTE. PLEASE VERIFY ALL.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE SOME TWH UNITS WHICH ARE SHOWN ON PLANS ARE
 MISSING THE REQUIRED CIRCUITING. CAN NOT REVIEW FOR
 COMPLIANCE OF LOAD, CONDUCTOR SIZE, OCP ETC AT THIS
 TIME.
 PLEASE COMPLETE. 240.4, 310.16, 408.4, FBC 106.1.2
  
 34) NOTE: OK.
  
 35) NOTE: OK.
  
 36) NOTE: OK
  
 37) NOTE: OK.
  
 38) NOTE: OK.
  
 39) NOTE: OK.
  
 40) NOTE: OK.
  
 41) NOTE: OK, HOWEVER SEE NOTE FOR CORRELATION OF ROOM
 A5.107
  
 42) NOTE: OK.
  
 43) NOTE: NO? SAME AS SHOWN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE "SHADED" AREAS ON MEZZANINE LEVEL PLANS
 E-1.1.4, PLEASE CLARIFY
 106.1.2 FBC ADMIN SECTION.
  
 44) NOTE: OK.
  
 45) NOTE: OK.
  
 45) NOTE: NO/OK, PLEASE SEE WALL AS LOCATED, HOWEVER
 SEPARATE LIGHTING CONTROLS FOR SEPARATE SPACES AS
 REQUIRED COULD NOT BE LOCATED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE WHAT APPEARS TO BE MISSING WALLS, DOORS
 SEPARATION E-1-1.2, LIBRARY/MUSEUM/ STORE? PLEASE SHOW
 AS THE REQUIREMENTS FOR CHAPTER 13 CAN NOT VERIFIED FOR
 CONTROL OF LIGHTING. LIGHTING OF SOME TYPE INCLUDING
 EXIT/EMERGENCY LIGHTS ARE STILL REQUIRED IN SPACE, EVEN
 IF FOR FUTURE BUILD OUT. PLEASE SEE LS 101 7.8, 7.9 AND
 POSSIBLE COMMENTS FROM FIRE MARSHAL?S OFFICE.
 13-415.1.ABC.1.ABC.1.1, .1.2, .1.3
  
 46) NOTE: OK.
  
 47) NOTE: NO/OK, SOME OF THESE WERE DONE BY THE CHANGES
 IN THE UNDER GROUND TO OTHER SECTIONS OF BUILDING,
 HOWEVER NOT DETAIL FOR THE ENCASED FEEDERS FROM
 GENERATOR COULD BE LOCATED. PLANS MENTIONS TO SEE
 ARCHITECTURAL PLANS; HOWEVER NO INFORMATION FOR WHICH
 SHEET OR DETAIL THIS IS COULD BE FOUND. PLEASE PROVIDE
 THE DETAIL.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE AN ELEVATION/DETAIL FOR ALL ELECTRICAL
 CONDUITS BEING RUN FROM GARAGE TO THE MAIN BUILDING.
 THIS BUILDING IS BEING CONSIDERED "ATTACHED" AND ONE "
 BUILDING" BY DEFINITION, HOWEVER DUE THE UNDERSTANDING
 OF MANY OF THE CONDUITS ARE NOW BEING INSTALLED IN THE
 SLAB OR UNDER GROUND AND THE AMOUNT OF OTHER CONDUITS,
 PIPING, BEING INSTALLED IN THIS SAME AREA, IT IS OF
 CONCERN FOR THE SPACE REQUIREMENTS FOR BUNDLING OF
 CONDUITS, DE-RATING OF CONDUCTOR AMPACITIES. ETC. (THIS
 CAN BE A DETAIL LIKE A DUCT-BANK DETAIL)
 FBC 106.1.2, 310.16, 300.8, 300.10, 310.10, 310.15,
 310.16, 300.17 ETC.
 THERE ARE MANY SECTIONS WHICH COULD BE REFERENCED.
 PLEASE ALSO SEE COMMENT WITH RESPECT TO WIRING METHODS
 OF EMERGENCY FEEDERS ETC.
  
 48) NOTE: OK, HOWEVER SEE NEW NOTES DUE TOP HAND DRAWN
 CHANGES MADE TO PLANS.
  
 49) NOTE: NO, PLEASE SEE THE RATING OF THIS ROOM IS
 STILL REQUIRED. THIS COMMENT WILL BE IN REVIEWS FROM
 MULTIPLE REVIEWERS AND AS THIS WILL CHANGE THE BACK
 GROUND OF WALL DETAIL PLEASE ADDRESS AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE KNOW AS NO INFORMATION FOR THE IT ROOM EQUIPMENT
 IS BEING SUBMITTED WITH THIS RECORD SET OF PLANS,
 PLEASE PLACE NOTE AND CLOUD ON 4TH FLOOR POWER PLANS
 THAT ALL ELECTRICAL EQUIPMENT, UPS, SERVER EQUIPMENT
 ETC IN THE IT ROOM SHALL BE UNDER A SEPARATE PERMIT,
 PLANS, AND FEES BASED ON THE EQUIPMENT BEING INSTALLED
 IN THIS ROOM. REVIEW FOR CODE COMPLIANCE FOR THIS ROOM
 CAN NOT BE COMPLETED AT THIS TIME. THE REQUIREMENTS FOR
 THE CONSTRUCTION OF THIS ROOM IS REQUIRED AT THIS TIME,
 INCLUDING THE MINIMUM 1HR RATING, THE FIRE DAMPERS ETC
 (IF APPLICABLE) AND THE SHUT DOWN OF AN AND ALL A/C
 EQUIPMENT.
 NEC 645, NFPA-75
  
 50) NOTE: OK.
  
 51) NOTE: OK.
  
 52) NOTE: OK.
  
 53) NOTE:OK/NO, THIS NOTE WILL REMAIN AS IT IS THIS
 REVIEWERS UNDERSTANDING THAT THERE WILL BE COMMENTS
 FROM OTHER TRADES WHICH WILL SUBSTANTIALLY AFFECT
 BACKGROUNDS AND LAYOUTS OF SAID PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE COORDINATE ALL OVER-LAYS AND LAYOUTS FOR
 ELECTRICAL, MECHANICAL, PLUMBING, BUILDING AND ALL
 OTHER TRADE PLANS. PLEASE KNOW THE ELECTRICAL 100%
 PLANS DO NOT SHOW THE SAME ELECTRICAL ROOMS AND
 EQUIPMENT AS THE 100% MECHANICAL PLANS, PLUMBING OR
 BUILDING PLANS ALONG WITH OTHER SHEETS FROM OTHER
 TRADES.
 REVIEW OF ALL APPLICABLE ITEMS WILL STILL NEED TO BE
 DONE AS REQUIREMENTS FOR ELECTRICAL AND OTHER TRADES
 WILL MOST CONTAIN CLEAR CONFLICTS WHICH MAY OR MAY NOT
 BE PERMITTED.
 110.26, 240.24 NEC.
 FBC 106.3.5.1.1 ADMIN SECTION FOR ALL TRADES FOR
 COMMERCIAL PLANS.
  
 54) NOTE:NO, SAME NOTE. PLEASE SEE PLANS IN SEVERAL
 LOCATIONS 6-1.0,1-6.3,5-1.1 ETC INDICATE 800KW AND
 SUBMITTALS ARE 900KW.
 PLEASE ALSO SEE SHEET WHICH STILL INDICATES ONLY 5
 GALLON SPILL CONTAINMENT. THIS MAY BE PART OF THE FIRE
 OR MECHANICAL REVIEW NOTES, IF NOT PLEASE SEE THIS
 NEEDS TO BE VERIFIED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE THE PLANS WITH THE MANUFACTURE
 SPECS/CUT SHEETS FOR THE GENERATOR WHICH IS BEING
 SUBMITTED AS A LARGER UNIT IN THE SPEC BOOK AS SHOWN ON
 PLANS. THIS WILL AFFECT THE FUEL SUPPLY, AND THE FUEL
 LINE SUPPLY FOR THE PROPOSED NATURAL GAS LINE. 90.7,
 110.3,
 FBC 106.1.2
  
 55) NOTE: OK.
  
 56) NOTE: OK.
  
 57) NOTE:OK/NO, PLEASE SEE PREVIOUS COMMENT WITH
 RESPECT TO HOW THIS WILL ACTUALLY BE DESIGNED AND
 INSTALLED. THIS COMMENT WILL REMAIN AT THIS TIME AS A
 REMINDER.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE SOME BATHROOMS CONTAIN OC SENSORS AND MANY
 DO NOT, PLEASE EXPLAIN AND PLEASE SEE OTHER COMMENTS
 FOR TYPE OF DEVICES WHICH WILL BE REQUIRED.
 13-415.1.ABC.1.2
  
 58) NOTE: NO, PLEASE SEE MOST WERE DONE, HOWEVER PLEASE
 SEE 2-2.2, 2-3.1,2-4.2 AND ANY OTHER LARGER BATHROOMS
 OTHER THAN A SINGLE POINT OF USE OCCUPIED ROOM.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW SOME SORT OF BATTERY BACK UP FIXTURE WILL
 BE REQUIRED IN THE LARGER BATHROOMS (ROOM OTHER THAN
 SINGLE POINT OF USE).
 PLEASE SEE LS 101 7.8., 7.9
 THIS WAS DISCUSSED WITH THE FIRE MARSHAL CHIEF AND WILL
 BE REQUIRED BOTH BY THIS OFFICE AND THE FIRE MARSHAL'S
 OFFICE IN THE INTEREST OF LIFE SAFETY AND CODE AS
 REFLECT.
  
 59) NOTE: OK.
  
 60) NOTE: OK.
  
 61) NOTE: NO, PLEASE SEE RESPONSE MENTIONS MINIMUM
 LIGHTING REQUIRED FOR EGRESS, HOWEVER PLEASE KNOW THE
 AREA OF THE LOBBY AFTER HOURS WOULD REQUIRE OVER RIDE
 FOR NORMAL LIGHTING. ONLY WOULD THEY NEED THESE
 FIXTURES TO BE BATTERY BACK UP FOR AN EMERGENCY. THIS
 WAS DISCUSSED WITH THE DESIGNER, HOWEVER THE NUMBER OF
 FIXTURES EXCEED ANY REASONABLE AMOUNT PERMITTED TO BE
 LEFT ON FOR THE EXCEPTIONS AS PERMITTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THERE ARE SOME LOCATIONS ON PLANS WHICH ARE
 SHOWING "NL'S" (NIGHT LIGHTS) BEING PART OF A PERMANENT
 ON SCENARIO; HOWEVER THE NUMBERS OF FIXTURES BEING
 PROPOSED TO REMAIN ON AS NIGHT LIGHTS ARE OVER WHAT IS
 BEING CONSIDERED AS NORMAL. PLEASE KNOW THIS CAN BE
 GONE OVER, HOWEVER PLEASE SEE SOME AREAS WHERE THERE
 ARE 10-20PLUS LIGHTS BEING LEFT ON.
 THE INTENT OF CHAPTER 13 AND ALSO THE INTEREST OF LIFE
 SAFETY SHOULD BE CONSIDERED. PLEASE CALL TO OVER. SEE
 SHEET E2-1.2 FOR EXAMPLE IN LOBBY AREA.
  
 62) NOTE:NO/OK, PROJECT MANUALS ARE TO BE REVIEWED
 FOR ALL OF THESE ITEMS AND DOCUMENTATION WILL BE
 REQUIRED BEFORE FINAL.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NFPA-20 11.3, 11.3.2, 11.3.2.3 AND FLORIDA
 FIRE PREVENTION CODE , NFPA-1 7-4FOR OTHER REQUIREMENTS
 FOR FIRE PUMPS AND ROOMS IN WHICH THEY ARE LOCATED.
 PLEASE ALSO SEE 11.4.6.2 FUEL PIPING SHALL NOT BE
 GALVANIZED STEEL OR COPPER.
 PLEASE KNOW AS PART OF THE COMPLETED TESTING AND
 ACCEPTANCE AS REQUIRED IN CHAPTER 14, DOCUMENTATION FOR
 TESTING FOR FIRE PUMP ON A WEEKLY BASIS IS REQUIRED TO
 THE OWNER OF RECORD.CODE TEXT FROM NFPA-20: 11.6.1.1
 ENGINES SHALL BE STARTED NO LESS THAN ONCE A WEEK AND
 RUN FOR NO LESS THAN 30 MINUTES TO ATTAIN NORMAL
 RUNNING TEMPERATURE.
  
 63) NOTE:NO, RESPONSE MENTIONS INFORMATION GIVEN TO
 ARCHITECT AND STRUCTURAL ENGINNER WHICH IS OK, HOWEVER
 COULD NOT LOCATE ANY INFORMATION OR DETAIL FOR THIS.
 THIS UNIT AND ITS SIZE IS BEING PLACED ON THE ROOF OF
 THE GARAGE AND IT IS OF THE UTMOST IMPORTANCE THAT THE
 INFORMATION IS PROVIDED A THIS TIME AS IT MAY AFFECT
 PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NFPA-110 CHAPTER 7 FOR THE INSTALLATION OF
 THE GENERATOR. PLEASE SEE 7.4 AND 7.5, PROVIDE DETAIL
 FOR MOUNTING OF UNIT TO ALLEVIATE ANY INTEGRITY
 INTERFERENCE OF THE STRUCTURE.
  
 64) NOTE: NO, PLEASE SEE THE SAME SPECS WHICH CONTAIN
 HAND WRITTEN INFORMATION WAS SUBMITTED BACK FOR REVIEW.
 PLEASE KNOW, THIS SYSTEM AS SUBMITTED IS NOT ACCEPTABLE
 TO THIS AHJ WITHOUT THE FAIL SAFE OPERATION TO
 COMPLETELY PREVENT INADVERTENT SIMULTANEOUS OPERATION.
 PLEASE KNOW THERE ARE NUMEROUS OF THE TYPES OF SYSTEMS
 ON THE MARKET WHICH WILL PERMIT BOTH SIDE BEING ON AT
 THE SAME TIME. PLEASE KNOW AS PER KNOWLEDGE OF THIS
 REVIEWER MR. MARK ODE FROM UL WAS IN DISCUSSION WITH
 SAID COMPANY TO START WITH THE PROCEEDINGS TO HAVE
 THEIR EQUIPMENT LISTED AS TRANSFER EQUIPMENT PER UL
 1081. PLEASE KNOW AT THIS TIME, EITHER PROVIDE THE
 NEEDED INFORMATION OR CHANGE EQUIPMENT TO AN ACCEPT
 UNIT WHICH IS LISTED BY A NRTL. (NATIONALLY RECOGNIZED
 TESTING LABORATORY).
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT THE SPEC/CUT SHEET FOR THE PROPOSED MTS.
 THE "KIRK KEY" AS SHOWN AND HAND WRITTEN ON SPECS IS
 NOT ACCEPTED AT THIS TIME. THERE ARE MANY OF THESE
 SYSTEMS ON THE MARKET WHICH WILL PERMIT THE POWER FROM
 TWO SOURCES AT ONCE WHICH IS STRICTLY PROHIBITED.
 PLEASE SEE 700.6, 701.7, 110.3, AND 90.7 CAN NOT VERIFY
 AT THIS TIME. PLEASE ALSO SEE THE FOLLOWING COMMENT.
  
 65) NOTE: NO/OK, PLEASE SEE SPECS SUBMITTED INDICATE
 4-POLE UNITS, HOWEVER EACH ATS ON RISER WHEN SUBMITTED
 FOR THE 90% REVIEW CONTAINED DESIGNATION NEXT TO EACH
 UNIT TO BE 4-POLE. PLEASE PLACE THIS MEANS OF
 IDENTIFICATION/DESIGNATION ON RISER AT THIS TIME TO
 AVOID ANY CONFUSION OF WHAT TYPE OF UNITS ARE TO BE
 INSTALLED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE RISER AND PLANS WERE REVISED FROM THE 50%
 AND 90% PLANS CHANGING ALL ATS UNITS TO 3-POLE UNITS.
 PLEASE SEE ALTHOUGH GF PROTECTION IS NOT REQUIRED ON
 THE EMERGENCY SIDE OF THE EMERGENCY SYSTEM AND LEGALLY
 REQUIRED SYSTEMS, PROPER GROUND FAULT SENSING IS
 REQUIRED. PLEASE KNOW DOCUMENTATION FROM MORE THAN ONE
 MANUFACTURE WAS SENT TO THE ENGINEER PRIOR TO THE
 REVIEW WHEN THE PLANS WERE SUBMITTED ON THE 7TH OF NOV.
 PLEASE SEE NFPA-110 6.2.15** ISOLATION OF NEUTRAL
 CONDUCTORS. PROVISIONS SHALL BE INCLUDED FOR ENSURING
 CONTINUITY, TRANSFER, AND ISOLATION OF THE PRIMARY AND
 THE EPS NEUTRAL CONDUCTORS WHEREVER THEY ARE SEPARATELY
 GROUNDED TO ACHIEVE GROUND-FAULT SENSING.
 PLEASE SEE AN ATTACHED BRIEF EXPLANATION FROM"ASCO"
 WHITE PAPER: WHERE GROUND FAULT PROTECTION IS TRIGGERED
 BY THE CODE AND AN ALTERNATE POWER SUPPLY IS INCLUDED,
 SWITCHING OF THE NEUTRAL BECOMES NECESSARY. THE CIRCUIT
 SHOWN ABOVE ILLUSTRATES SUCH A CIRCUMSTANCE. THE
 SERVICE IS LARGER THAN 1,000 AMPS. CONSEQUENTLY, GROUND
 FAULT PROTECTION IS REQUIRED AT THE MAIN SERVICE
 DISCONNECT AT A MINIMUM. IF IT IS INSTALLED THERE AND
 THE GENERATOR NEUTRAL GROUNDING WAS THROUGH A SOLID
 CONNECTION TO THE MAIN SERVICE NEUTRAL, A GROUND FAULT
 WHEN THE GENERATOR IS FEEDING THE LOAD WILL CAUSE THE
 MAIN SERVICE DISCONNECT TO OPEN. THIS WILL NOT
 DISCONNECT THE ARCING FAULT FROM THE GENERATOR.
 COORDINATION IS THUS LOST."
 PLEASE KNOW BASED ON THE INFORMATION FROM SEVERAL
 MANUFACTURES AND THE CODE PLEASE ADJUST AS REQUIRED.
 PLEASE ALSO SEE GENERATOR GROUNDING DETAIL WILL BE
 REQUIRED TO BE REVISED.
 PLEASE SEE E5-1.1.18 WHICH NOTES A #3 CONDUCTOR, WHICH
 WOULD NOT BE LARGE ENOUGH.
 PLEASE SEE 250.20, 250.30, 250.66, 240.13, 230.95,
 700.7D, 700.26
 PLEASE SEE THE MTS.
  
 66) NOTE: OK, HOWEVER PLEASE SEE SOME OF THESE ARE
 BEING SHOWN ATTACHED DIRECTLY TO CIRCUITS WHICH SEEMED
 TO BE CONTROLLED BY LIGHTING CONTROL SYSTEM OR DEVICES.
 THE NOTES ON PLANS MENTION TO BE SURE TO CONNECT AHEAD
 OF ANY CONTROL OR SWITCHING DEVICES HOWEVER PLEASE
 VERIFY THIS ON THE PLANS AT THIS TIME AS SHOWN. PLEASE
 SEE THERE ARE STILL SOME EXIT LIGHT FIXTURES ON PLANS
 WHICH STILL DO NOT SHOW ANY CONNECTION TO LOCAL
 CIRCUITS E2-3.2,E2-4.2
  
 PLEASE SEE THERE ARE MANY EXIT/EMERGENCY LIGHTS WHICH
 DO NOT SHOW ANY CONNECTION TO ANY LOCAL CIRCUIT IN
 ANYWAY. PLANS NOTE THIS AND MANY ARE SHOWN THIS WAY,
 HOWEVER NOT ALL. PLEASE GO THROUGH PLANS. PLEASE SEE
 700.12E WHICH REQUIRES THE BRANCH CIRCUIT FEEDING THE
 UNIT EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED
 AHEAD OF ANY LOCAL SWITCHES.
  
 67) NOTE:NO, SAME NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE OVER ALL 3RD FLOOR PLANS, WHICH SEEM TO BE
 SHOWING LIGHTING OF SOME KIND ON GARAGE PLANS? PLEASE
 ALSO SEE E2-4.0
 FBC 106.1.2 ADMIN SECTION.
  
 68) NOTE: NO, PLEASE SEE THE LOCATION AS SHOWN WOULD
 NOT BE AN ACCEPTABLE LOCATION. PLEASE THE RUNNING OF
 CABLES IN THE EGRESS PATH IS NOT PERMITTED IN FRONT OF
 DOOR WAYS AND ANY OTHER EGRESS PATHS. PERHAPS CONDUITS
 TO A J-BOX OF SOME TYPE TO THE OUTSIDE WALL ON THE
 NORTH SIDE OF BUILDING. PLEASE KNOW TRIPPING HAZARDS
 UNDER THE REQUIREMENTS IN THE CODE FOR TEMPORARY
 INSTALLATIONS IS STILL NOT PERMITTED. PLEASE SECTIONS
 AS PREVIOUSLY GIVEN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NOTE #2 ON RISER WITH RESPECT TO THE MTS
 WHICH IS TO PROVIDE FUTURE PROVISIONS FOR POSSIBLE
 PORTABLE GENERATOR TO RUN THE EMERGENCY SYSTEMS, PLEASE
 KNOW A DETAIL TO A LOCATION AND HOW THIS CONNECTION
 WILL BE MADE IS REQUIRED.THE RUNNING OF CORDS,
 CONDUCTORS ETC SHALL BE PERMITTED TO TRAVEL THROUGH THE
 ELECTRICAL ROOM DOORS, ON SIDEWALK AREAS OR ANY
 LOCATIONS PROVIDING A TRIPPING HAZARD OR NOT SECURING
 LIVE PARTS ETC.
 PLEASE PROVIDE A DETAIL AS THIS CONNECTION POINT WILL
 BE SUBSTANTIAL IN NATURE. (J-BOX) ETC ON THE OUTSIDE OF
 BUILDING ETC.
 110.26, 110.27, NEC 527.
  
 69) NOTE: OK.
  
 70) NOTE: OK.
  
 71) NOTE: OK, PLEASE KNOW ALL LOW VOLTAGE WILL NOT BE
 INCLUDED IN THIS PERMIT. NOTE WILL REMAIN ONLY AS
 INFORMATION AS TO WHAT WILL BE REQUIRED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW IF IT IS THE INTENT TO UTILIZE THESE PLANS
 FOR FUTURE LOW VOLTAGE WORK FOR LOCATIONS OF PHONE,
 DATE DROP ETC, PLEASE COMPLETE PLANS AS SUBMITTED
 SHOWING ALL LOCATIONS FOR DROPS.PLEASE SEE MANY AREAS
 WHICH LOW VOLTAGE DATE/PHONE DROPS WILL BE REQUIRED OR
 INSTALLED, HOWEVER THESE LOCATIONS ARE NOT BEING SHOWN
 AT THIS TIME.
 IF THE LV SCOPE IS PART OF THE PERMITTED PLANS AS
 SUBMITTED PLEASE REMOVE AND NOTE AS UNDER SEPARATE
 PERMIT PLANS AND FEES.
  
 72) NOTE: OK.
  
 73) NOTE:OK/NO, PLEASE SEE PREVIOUS NOTE #47, WHERE
 THE DETAIL FOR THE FEEDERS IN GARAGE WAS NOT PROVIDED.
 THE DETAIL FOR UNDERGROUND IS OK.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 700.9D FOR THE FEEDERS FROM THE GENERATOR TO
 THE EMSB1 AND THE FEEDERS OUT TO SYSTEMS WHICH MAY BE
 CONSIDERED INSIDE THE BUILDING. PLEASE SEE THE CODE AS
 THERE ARE WAYS TO MEET THE INSTALLATION OF THESE
 FEEDERS, HOWEVER PLANS SHALL INDICATE WHICH WILL BE
 USED. (TYPE OF CABLE, ENCASED IN 2INCHES OF CONCRETE,
 FULLY SPRINKLED ETC)
 PLEASE KNOW AS THE REQUIREMENT OF FULLY SPRINKLED IS
 OFTEN MISTAKEN AS A BUILDING CONTAINING SPRINKLERS.
 THIS IS NOT THE CASE. PLEASE SEE THE INTENT OF 700.9D
 FOR THIS HAS ALWAYS BEEN THAT ALL AREAS CONTAINING
 THESE FEEDERS BE SPRINKLED IF INSTALLED IN OPEN OR
 ABOVE CEILINGS. PLEASE KNOW A COMMENTARY IN THE 2005
 NEC MAKES IS CLEAR WHAT THE INTENT OF THE CODE AND THE
 FURTHER EXPLANATION IS PROVIDED.
  
 74) NOTE: OK.
  
 75) NOTE: OK..
  
 76) NOTE: NO, COULD NOT LOCATE. RESPONSE MENTIONS TO
 SEE SHEETS; HOWEVER THIS WAS REQUESTED FOR RISER TO
 SHOW THIS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE THE SIZE OF THE CONDUCTOR ON THE
 GROUNDING ELECTRODE RISER AS PROVIDED. PLEASE SEE THE
 GROUNDING ELECTRODE DETAIL SHOWS A 4/0'S, HOWEVER
 PLEASE SEE E5-2.0.
 250.50, 250.58
  
 77) NOTE: NO, PLEASE SEE RESPONSE MENTIONS ALL
 TERMINATE IN OCP. YES, THIS IS TRUE, HOWEVER AS STATED
 IN PREVIOUS REVIEW PER 240.21C THE OCP SHALL LIMIT THE
 LOAD ON CONDUCTORS.
 PLEASE SEE E5-1.0 WHICH SHOWS A 45KVA TRANSFORMER, WHEN
 E6-1.0 SHOWS 1/0'S FOR THE TYPICAL 45 KVA TRANSFORMER
 ON THE SECONDARY SIDE, THIS WOULD MEAN THE OCP WOULD BE
 LIMITED TO 150A?S. PLEASE SEE 6-1.0 FOR 1LD2 WHICH
 INDICATES 225A OCP AS THE SECONDARY MCB. PLEASE SEE
 6-7.0 1HD WHICH SHOWS 1/0'S ON THE SECONDARY SIDE OF
 THE FEEDERS.
 PLEASE ADJUST.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE SIZE OF THE CONDUCTORS ON THE SECONDARY
 SIDE OF ANY TRANSFORMER SHALL BE SIZED AND TERMINATE IN
 OVER-CURRENT PROTECTION WHICH LIMITS THE LOAD ON THE
 CONDUCTORS. PLEASE SEE 240.21C, 310.16. PLEASE SEE
 1LD2
  
 78) NOTE: OK.
  
 79) NOTE: NO, PLEASE CLARIFY WHERE CONTINUOUS LOADS AND
 LARGEST MOTOR LOADS ARE SHOWN AT 125%.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT LOAD CALCULATIONS. PLEASE INDICATE AND
 SHOW ALL CONTINUOUS LOADS AND LARGEST MOTOR LOADS AT
 125%.
 220.3, 220.10, 220.11, 220.13, 215.3,230.42 ETC
  
 80) NOTE: OK.
  
 81) NOTE:NO, PLEASE KNOW BASED ON THE PREVIOUS NOTES
 ABOVE WITH RESPECT TO PHOTO-METRICS, THIS COMMENT WILL
 REMAIN DUE TO POSSIBLE CHANGES IN PLANS.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PREVIOUS NOTES WITH RESPECT TO MINIMUM FOOT
 CANDLES REQUIRED. PLEASE SEE GARAGE SHALL CONTAIN
 EGRESS PATHS WHICH MEET THIS MINIMUM. BASED ON SOME
 AREAS SHOWN ON PHOTO-METRICS, IT DOES NOT APPEAR THIS
 IS MET.
 PLEASE SEE LIFE SAFETY CODE NFPA-101 2003 7.8.1.3,
 7.9.2.2
  
 82) NOTE: OK.
  
 83) NOTE:NO/OK, PLEASE SEE MOST WERE DONE, HOWEVER
 PLEASE SEE ROOM A1.507 WHICH SHOWS 75K ON RISER AND 45K
 ON ROOM PLANS.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE CORRELATE THE TRANSFORMERS ON THE ELECTRICAL
 ROOM LAYOUTS AND THE ELECTRICAL RISER. PLEASE SEE THERE
 ARE MANY WHICH ARE SHOWN AS 15KVA ON ONE SHEET AND
 45KVA ON OTHER SHEETS OR 45KVA ON ONE AND 75KAV ON
 ANOTHER. PLEASE ALSO SEE RISER.
 PLEASE SEE SOME BELOW AS NOTED, THIS IS ONLY SOME AND
 IS IN NO WAY ALL POSSIBLE.
 1HB, 75KVA ON RISER, 45KVA IN ELECTRICAL ROOM. 2HB,
 75KVA ON RISER, 45KAV IN ELECTRICAL ROOM. 1GLA-1GHA,
 45K ON RISER, 15K ON ELECTRICAL ROOM PLANS. ETC
  
 84) NOTE: OK,
  
 85) NOTE: NO, PLEASE SEE NOTE NOTES COULD BE LOCATED ON
 FA SHEETS, IN FACT SHEETS STILL ONLY NOTE NFPA72 FOR
 LEVELS.
 PLEASE ADJUST ALL SHEETS AND NOTES ACCORDINGLY AS
 PREVIOUSLY REQUESTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC 2004 CHAPTER 11 FOR REQUIREMENTS FOR ADA
 WITH RESPECT TO HORNS, AND STROBES. THE AUDIBLE LEVELS
 SHALL BE PER BOTH FBC CHAPTER 11 AND NFPA-72 AS NOTED,
 HOWEVER THE MORE STRINGENT SHALL APPLY.
 PLEASE SEE 11-4.28.1, 11-4.28.2 AND 11-4.28.3(4).
 PLEASE BE SURE THE LEVELS ARE INDICATED ON PLANS.
 PLEASE KNOW THE LIGHTING CANDELA LEVELS AS REQUIRED IN
 THE FBC ARE FAR GREATER THAN THAT OF NFPA-72. THE
 MINIMUM LEVELS FOR VISUAL SHALL BE 75 CANDELAS. PLEASE
 ADJUST AND PLACE REQUIREMENTS ON PLANS. PLEASE SEE ALL
 FA SHEETS WHICH ONLY INDICATE NFPA-72.
  
  
 86) NOTE:OK, PLEASE DO THE SAME. NOTE WILL REMAIN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW A RESPONSE LETTER/NOTES WERE PROVIDED,
 HOWEVER AS THIS REVIEW WAS MORE OF A REVIEW FOR CODE
 COMPLIANCE, A MORE DETAILED RESPONSE WOULD GREATLY HELP
 IN THE REVIEW PROCESS. THIS RESPONSE COULD INDICATE THE
 SHEETS/LOCATIONS OF CHANGES, CORRECTIONS OR ANY
 COMMENTS RELATED TO AND RESPECT TO THIS REVIEWERS
 NOTES.
  
 ********** NEW NOTES FOR THIS REVIEW************
  
 87) NOTE: PLEASE SEE FLORIDA STATUTES WITH RESPECT TO
 THE ENGINEER OF RECORD SIGNING AND SEALING DOCUMENTS IN
 471.025. PLEASE SEE SHEETS SIGNED OTHER THAN MR. MINDUR
 CONTAINS WHAT APPEARS TO BE MORE THAN ONE SIGNATURE FOR
 THE SAME ENGINEER. PLEASE KNOW AS STATED BY THE
 PLUMBING REVIEWER FOR PLUMBING SHEETS, THE SAME APPLIES
 TO FS SHEETS AND OTHER DOCUMENTS SIGNED AND SEALED.
 PLEASE KNOW UNTIL LEGAL SIGNATURE VERIFICATION CAN BE
 DONE, THE ENERGY CALCULATIONS WHICH ARE SIGNED AND
 SEALED ALSO BY OTHER THAN MR. MINDUR CAN NOT BE
 ACCEPTED AT THIS TIME.
 FAC 61G15-23.002
 PLEASE BE SURE LETTER FOR LEGAL SIGNATURE VERIFICATION
 FOR MR. WU IS CORRECTLY NOTARIZED PER FLORIDA STATUTES
 117.05.
  
 88) NOTE: PLEASE KNOW AS COMMENTS FROM ELECTRICAL
 ENGINEER MENTIONED TO SEE S SHEETS FOR INFORMATION,
 UPON REVIEW OF SAID SHEETS THIS REVIEW NOTICE MANY
 SHEETS WHICH WERE DATED IN DECEMBER NOT CONTAINING ANY
 TITLE BLOCKS FOR THE ENGINEERING FIRM OF RECORD. PLEASE
 SEE SOME SHEETS WHICH WERE DATED FROM OCTOBER WHICH DO
 CONTAIN THE TITLE BLOCKS FOR FIRM DO NOT CONTAIN THE
 CERTIFICATE OF AUTHORIZATION NUMBER AS REQUIRED UNDER
 FS 471.023 AND FAC 61G15-23.002. THIS IS REQUIRED FOR S
 SHEETS WHETHEROR NOT COMMENT IS MADE BY ANY OTHER
 TRADE.
  
 89) NOTE: PLEASE SEE ENERGY CALCULATIONS WHICH ARE NOW
 SUBMITTED ONLY INDICATE 3 FIXTURES FOR EXTERIOR
 LIGHTING? HOW IS THIS POSSIBLE? PLEASE CORRELATE WITH
 PLANS AND FIXTURES AS SHOWN ON PLANS.
 PLEASE ALSO CORRELATE WITH THE WATTAGES AS SHOWN ON
 LIGHTING POWER DENSITIES AND PLANS.
 PLEASE CLARIFY ZONES IN ENERGY CALCULATIONS AS SHOWN.
 PLEASE SEE FBC 13-415.1.AB.1, 13-415.2
  
 90) NOTE: PLEASE SEE NOTES ON LIGHTING SEQUENCE OF
 OPERATION SHEETS. PLEASE SEE NOTE #11 ON E5-3.0 WHICH
 MENTIONS PHOTO-CELL FOR CONTROL OF ROOMS? PLEASE SEE
 THE SAME ROOMS AND NOTE #3 ON 5-3.1 WHICH MENTIONS
 DIFFERENT CONTROLS.
  
 91) NOTE: PLEASE SEE WATER COOLERS LOCATIONS OF
 RECEPTACLES. PLEASE SEE MANY INDICATE THE RECEPT TO BE
 LOCATED AT THE CEILING LEVEL AND MANY INDICATE AT WC
 LEVEL. PLEASE EXPLAIN THE INDICATION FOR DEVICE AT
 CEILING. PLEASE ALSO SEE AREAS WHERE MORE THAN TWO
 WATER COOLERS ARE BEING SHOWN HOWEVER ONLY ONE DUPLEX
 RECEPT IS BEING SHOWN. PLEASE ADJUST TO QUAD AND PLEASE
 VERIFY LOAD ON THESE UNITS WHICH ARE NOT TO EXCEED
 RATING OF DEVICE AND CIRCUIT. THIS WAS NOT COMMENTED ON
 THE PREVIOUS REVIEW.
 240.4, 310.16, 210.25, 2210.21B2 ETC.
  
 92) NOTE: PLEASE PLACE NOTE ON E0-2.1 FOR SECTIONS OF
 314PART IV , SECTIONS 314.50-314.59 TO BE MET.
 NOT ON PREVIOUS REVIEW.
  
 93) NOTE: PLEASE SEE UPON REVIEW OF PROJECT MANUAL,
 PLEASE SEE COLOR CODING SHALL BE BROWN, PURPLE, YELLOW
 FOR 277/480V SYSTEMS. PLEASE SEE THE CODE DOES NOT
 PROVIDE COLOR CODING FOR MOST SYSTEMS, HOWEVER ORANGE
 AS BEING NOTED FOR THIS IS FOR A HIGH-LEG SYSTEM WHICH
 IS NOT WHAT IS BEING INSTALLED. PLEASE KNOW AS PER
 LOCAL AMENDMENTS FOR 3 DECADES OR SO UNDER THE 2004 FBC
 THE CITY OF WEST PALM BEACH ALONG WITH PALM BEACH
 COUNTY HAD THIS COLOR SCENARIO FOR 277/480V SYSTEMS AND
 WILL BE REQUIRED TO REMAIN THE SAME FOR ALL OTHER
 BUILDING BEING PROPOSED. PLEASE PLACE A NOTE ON RISER
 FOR COLOR CODING.
 90.4., FBC ADMIN SECTION 104.6
  
 94) NOTE:PLEASE SEE BUILDING REVIEW NOTES AND
 CLARIFY THE TWO PULL BOXES BEING SHOWN ON E0-2.1 WHICH
 SEEM TO BE DIRECTLY LOCATED IN THE WALL OR FOOTER.
 PLEASE CLARIFY THESE AT THE LOCATIONS AS SHOWN AND
 PLEASE ADJUST PLANS AS NEEDED. PLEASE SEE CODE FOR
 ACCESSIBILITY.
 110.26
  
 95) NOTE: PLEASE CLARIFY THE FUEL TANK ROOM AS BEING
 SHOWN ON THE GARAGE PLANS NEXT TO THE FIRE PUMP ROOM.
 PLEASE KNOW IT WAS BEING ASSUMED THIS WAS THE LOCATION
 OF THE TANK FOR THE FIRE PUMP; HOWEVER IT HAS COME TO
 OUR ATTENTION THAT THIS IS NOT THE CASE. PLEASE PROVIDE
 INFORMATION FOR THIS FOR MECHANICAL AND FIRE REVIEW AS
 WELL AS ELECTRICAL REVIEW. PLEASE SEE NEC 500. SPECIFIC
 SECTIONS CAN NOT BE GIVEN AT THIS TIME, AS THE USE AND
 RATING OF ROOM ETC IS NOT KNOWN AT THIS TIME.
 FBC ADMIN SECTION 106.1.2 (MORE INFORMATION). NFPA-70,
 72, 30? ETC.
  
 96) NOTE: PLEASE SEE ELEVATOR EQUIPMENT ROOM
 DISCONNECTS ARE BEING SHOWN WITH 3-WAY SWITCH NOTATIONS
 INSTEAD OF DISCONNECTS OR MOTOR RATED SYMBOL.
 NOT ON PREVIOUS REVIEW.
 PLEASE ADJUST. 620.51, 620.61, 620.62 ETC
 FBC 106.1.2,
  
 97) NOTE: PLEASE SEE ANY HAND DRAWN CHANGES WHICH MAY
 HAVE BEEN DONE BY THE ENGINEER AFTER PLANS WERE SIGNED,
 DATED AND SEALED, SHOULD BE REVISED AT THIS TIME. ONLY
 THE ENGINEER OF RECORD MAY MAKE CHANGES TO SAID PLANS
 WHICH ARE SIGNED AND SEALED. FS 471.025 PLEASE KNOW AS
 PLANS ARE SEALED, MANY OF THE SEALS ARE NOT CLEAR AND
 VISIBLE WITH INFORMATION ON SAID SEAL. PLEASE BE SURE
 PLANS ARE SEALED TO SEE INFORMATION. FS 471.025
  
  
 IF ANY OF THESE COMMENTS ARE NOT CLEAR IN ANY FASHION
 OR IF ANY ITEMS ARE NOT UNDERSTOOD IN ANY WAY?PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
  
 ** PLEASE KNOW AS THERE IS SOME INFORMATION NOT YET
 SUBMITTED PLEASE BE SURE TO GO OVER ALL.
  
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. ONCE AGAIN IF THERE
 ARE ANY QUESTIONS , PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-12-25 08:06:402006-12-25 08:06:40
 IN PROGRESS
2006-12-24 20:14:292006-12-24 20:14:29
 REVIEW STOPPED. TO CONTINUE ON 12/25
2006-12-24 18:11:342006-12-24 18:11:34
 ONE ROLL OF MEP'S IN ELECTRIC FOR REVIEW ALONG WITH ONE
 COPY OF RESPONSE LETTERS AND ONE COPY OF SUBMITTIALS
 FOR REVIEW.
 REVIEW IN PROGRESS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-25 Cont ID  
Sent By dpalmer Date 2006-11-25 Time 20:34 Rev Time 0.00
Received By dpalmer Date 2006-11-07 Time 10:21 Sent To  
Notes
2006-11-25 20:22:32**** CITY CENTER *******
  
  
 REVIEW OF 100% ELECTRICAL PLANS SUBMITTED ON NOVEMBER
 7TH, 2006.
  
 PLEASE SEE THE FOLLOWING COMMENTS ARE BASED ON THESE
 PLANS AS NOTED ABOVE AND NOT THE 100% PLANS SUBMITTED
 ON OCTOBER 17TH, 2006.
  
 1) NOTE: PLEASE KNOW WHEN SUBMITTING FOR FINAL
 PERMITTING AND STAMPING, A THIRD SET OF SIGNED, DATED
 AND SEALED PLANS WILL BE REQUIRED.
 PLEASE SEE FBC ADMINISTRATIVE SECTION AS ADOPTED BY THE
 CITY OF WEST PALM BEACH, 106.1.2106.1.3, 109.3.6 FOR
 THRESHOLD BUILDINGS. THIS IS WILL BE REQUIRED FOR ALL
 DOCUMENTATION AND PLANS AND FOR ALL TRADES WHETHER OR
 NOT COMMENT IS MADE BY OTHER TRADES.
  
 2) NOTE: PLEASE SEE FBC CHAPTER 13. PLEASE SEE
 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE BE SURE ALL DEVICE ON PLANS CORRELATE WITH THE
 DEVICE SYMBOL LEGEND.
 PLEASE BE SURE MAX TIME OF OVER -RIDES ARE SHOWN. IF
 TIMER TYPE, (4HRS MAX), IF OCCUPANCY SENSOR TYPE (30
 MINS MAX).
 PLEASE SEE ADDITIONAL COMMENTS FOR CONTROLS AND SYSTEM
 BEING PROPOSED.
  
 3) NOTE: PLEASE PLACE A NOTE ON PLANS FOR ALL "TASK"
 LIGHTING WHICH MAY NOT BE SHOWN ON PLANS AT THIS TIME.
 13-415.1.ABC.1.3
  
 4) NOTE: PLEASE SUBMIT COMPLETED ENERGY CALCULATIONS
 FOR THE ENTIRE BUILDING FOR REVIEW OF ALL TRADES.
 PLEASE KNOW AS NONE WERE SUBMITTED AT THIS TIME THERE
 ARE MANY ITEMS WHICH CAN NOT BE VERIFIED WITH THE
 PLANS, EQUIPMENT AND LIGHTING.
 PLEASE SEE 13-415.1.AB.1.
  
 5) NOTE: PLEASE SEE 13-415.2, 13-415.2ABC.1 FOR MINIMUM
 AND MAXIMUM PERFORMANCE CALCULATIONS. PLEASE SEE THE
 CALCULATIONS SUBMITTED SHOWING THE LIGHTING POWER
 DENSITIES (LPD) ARE NOT COMPLETE AND/OR THERE ARE ITEMS
 WHICH DO NOT CORRELATE WITH SAID PLANS.
 PLEASE SEE THERE ARE MANY ROOMS INDICATED ON PLANS
 WHICH COULD NOT BE LOCATED IN CALCULATIONS OR THERE ARE
 ROOMS ON CALCULATIONS WHICH COULD NOT BE LOCATED ON
 PLANS.
 PLEASE CORRELATE AND PLEASE SEE SOME OF THE LPD'S SEEM
 TO BE VERY HIGH FOR SOME OF THE ROOMS AND AREAS AS
 NOTED AND SHOWN.
 PLEASE SEE OFFICE IN PARKING GARAGE FOR INSTANCE.
 PLEASE SEE SOME OTHERS WHICH BASED ON THE TABLES AS
 SET-FORTH IN THE CODE MAY ALLOW 1.7, THE CALCULATIONS
 MAY SHOW 10.5 ETC.
 PLEASE REVIEW ALL AND RE-ADJUST AS REQUIRED AND
 NEEDED.
  
 6) NOTE: PLEASE SEE 13-415.2.ABC.1.3 FOR ALL EXTERIOR
 LIGHTING ALLOWANCES, INCLUDING THAT WHICH IS
 DECORATIVE. PLEASE SEE THERE ARE EXCEPTIONS FOR SOME
 AREAS; HOWEVER THESE AREAS AS LISTED WOULD BE REQUIRED
 BY SECTIONS AS LISTED. PLEASE SEE 13-415.0(3)
 (EXCEPTS).
  
 7) NOTE: PLEASE SEE PLANS SHALL INDICATE THE ACTUAL
 PANEL BEING USED FOR LIGHTING CONTROLS. PLEASE SEE
 THERE ARE SEVERAL PANELS INDICATE IN THE MANUFACTURE
 SPECS/CUT SHEETS SUBMITTED AND THE ACTUAL UNIT NEEDS TO
 BE HIGH-LIGHTED IN SPECS. PLANS SHALL ALSO BE REQUIRED
 TO PROVIDE THE TECHNICAL INFORMATION AT EACH LIGHTING
 CONTROL PANEL. (LCP)
 ** PLEASE KNOW AS REFERENCE TO LIGHTING CONTROL PANELS
 IN NOTES HERE ON WILL BE DESIGNATED AS "LCP'S". PLEASE
 SEE RISER INDICATES LCP'S AS 225A RATED, WHICH IS OK,
 HOWEVER PLEASE BE SURE THE INFORMATION AS SHOWN ON
 CUT/SPEC SHEETS IS BROUGHT OVER TO THE PLANS AND LISTED
 ON EACH LCP.
  
 8) NOTE: PLEASE KNOW THERE IS CONCERN OVER THE TYPE OF
 SYSTEM BEING PROPOSED AND CONTROLS OF SAID SYSTEM.
 PLANS CALL FOR A "SWEEP" EACH HOUR FOR THE SYSTEM OUT
 OF NORMAL BUSINESS HOURS AND THIS WILL TURN OFF ANY AND
 ALL DEVICES. THE DEVICES WILL THEN HAVE THE ABILITY TO
 OVER RIDE THE SYSTEM IN ANY PARTICULAR AREA WHICH THE
 CIRCUIT/SWITCH IS DESIGNATED TO. PLEASE KNOW THIS
 BUILDING IN SEVERAL SECTIONS WILL BE OCCUPIED OUT OF
 THE NORMAL BUSINESS HOURS WHICH ARE SET UP AND WILL
 CAUSE DARKNESS EACH HOUR EVEN WHEN OCCUPIED. PLEASE SEE
 SPECS SHEETS AS SUBMITTED SPEAK OF THE INCLUSION OF AN
 OCCUPANT SENSOR TYPE DEVICE TO ALLEVIATE THIS.
 (UNINTENDED BLACK-OUTS). PLEASE SEE AREAS LIKE THE
 LIBRARY, COMMISSIONS CHAMBERS, OFFICE DESIGNATED FOR
 POLICE, AND OTHER AREAS.
 PLEASE SEE THE CODE ON THE OTHER HAND FOR ALL AREAS
 WHICH DURING NORMAL BUSINESS HOURS WHICH WILL REQUIRE
 ROOMS TO BE OFF. PLEASE SEE 13-415.1.ABC.1.2, FOR ALL
 ROOMS CONTAINING FLOOR TO CEILING HEIGHT PARTITIONS
 WHICH WILL REQUIRED SEPARATE CONTROL. PLEASE SEE AS
 SHOWN ON PLANS, THESE ROOMS WILL COME "ON" AT THE SET
 BUSINESS HOUR TIMES AND WILL REMAIN ON UNTIL AFTER THE
 "ONE HOUR SWEEP" AFTER THE NORMAL OPERATIONAL TIMES
 HAVE PASSED.
 PLEASE SEE CLOSETS, OFFICES, STORAGE AREAS ETC. THERE
 ARE FAR TOO NUMEROUS ROOMS TO LIST.
 PLEASE SEE THERE ARE MANY ROOMS ON PLANS WHICH DO
 INDICATE "OC" TYPE DEVICES; HOWEVER THERE IS NOT DETAIL
 ON THE LIGHTING CONTROL RISER HOW THESE WILL BE
 CONNECTED OR TIED IN.
 PLEASE SEE BATHROOMS ETC.
 PLEASE KNOW THIS TYPE OF DEVICE WILL WORK IN MANY AREAS
 IN THIS BUILDING; HOWEVER THERE ARE AREAS WHICH WILL
 NOT MEET CODE OR THE INTENT IN SEPARATE SPACES. PLEASE
 KNOW AT THIS TIME, AS SHOWN THERE ARE SEVERAL ITEMS
 WHICH WILL BE REQUIRED TO BE ADJUSTED. PLEASE ALSO
 OBTAIN A LETTER FROM THE "SENTRY SWITCH" MANUFACTURE
 WHICH PERMITS THIS TYPE OF DEVICE TO BE USED WITH THE
 LUTRON GRAFIK PANEL.
 110.3, 90.7 NEC.
  
 9) NOTE: PLEASE SEE THERE ARE SEVERAL ROOM NUMERICAL
 DESIGNATIONS ON CALCULATIONS WHICH COULD NOT BE LOCATED
 ON PLANS. PLEASE SEE GARAGE PLANS.
 PLEASE SEE SOME WHERE THE ROOM DESIGNATION IS THERE
 HOWEVER IT SEEMS TO BE VERY LIGHT IN COLOR AND CAN NOT
 BE EASILY READ. PLEASE SEE OTHER AREAS WHICH THE
 FIXTURE DESIGNATION COVERS THE ROOM IDENTIFICATION OR
 VICE VERSA, THE FIXTURE TYPE COULD NOT BE SEEN DUE TO
 THE OVER LAY OF THE NUMERICAL DESIGNATION.
 PLEASE COORDINATE. A1-116-2-1.610 ETC
 FBC ADMIN SECTION 106.1.2, 106.1.3
  
 10) NOTE: PLEASE BE SURE ALL INFORMATION IS PROVIDED ON
 ALL FIXTURES AS SHOWN ON PLANS ON THE FIXTURE LEGEND.
 PLEASE KNOW THAT THE WATTAGE, TYPE ETC SHALL BE
 SPECIFIED AT THIS TIME. THESE CAN ALWAYS BE REVISED AT
 A LATER DATE.
 FBC 106.1.2,NEC 110.3, ETC
  
 11) NOTE: PLEASE SEE THAT BATTERY BACK UP FIXTURES OF
 SOME TYPE WILL BE REQUIRED FOR THE FOLLOWING LOCATIONS.
 SOME ARE SHOWN ALREADY, HOWEVER NOT ALL. THE MAIN
 ELECTRICAL ROOM, THE FIRE COMMAND CENTER, BOTH FIRE
 PUMP ROOMS, ELEVATOR EQUIPMENT ROOM, AND AT THE
 LOCATION OF THE ROOF TOP GENERATOR WILL ALL REQUIRE
 THIS. PLEASE SEE THAT ALL STAIR TOWERS AND EGRESS PATHS
 SHALL ALSO INCLUDE SOME SORT OF BATTERY BACK UP
 FIXTURE. THERE ARE MANY LOCATIONS WHICH INCLUDE THIS;
 HOWEVER AS SOME OF THE FIXTURE INFORMATION IS NOT CLEAR
 AT THIS TIME THIS CAN NOT BE VERIFIED. THIS BUILDING IS
 EXPECTED TO BE OCCUPIED IN THE TIME OF POWER OUTAGES
 AND IN THE EVENT OF THE TRIPPING OF A SINGLE MEANS OF
 OVER CURRENT PROTECTION (EMSB1) OR GEN MAIN, THIS WILL
 PLACE MANY AREAS IN COMPLETE DARKNESS WHICH IS NOT
 PERMITTED. NEC 700.12E, 700.16, LS 101 7.9.
  
 12) NOTE: PLEASE SEE LIGHTING CONTROL RISER WHICH
 INDICATES ALL LCP'S BEING FED FROM THE SAME PANEL?
 1HA/LCP1A PLEASE ADJUST.
  
 13) NOTE: PLEASE CORRELATE ALL LCP'S WITH THE HOUSE
 PANELS AND THE CIRCUITS FROM THE HOUSE PANELS WHICH
 FEED THESE LCP'S AND CIRCUITS. PLEASE SEE NUMEROUS
 CIRCUITS WHICH CONTAIN THE DESIGNATION OF "LC" NEXT TO
 THE CIRCUIT HOWEVER MANY WHICH DO GO THROUGH THE PANEL
 DO NOT? PLEASE COORDINATE.
 FBC106.1.2 ADMIN SECT.
  
 14) NOTE: PLEASE SEE FIXTURE "E", PLEASE SEE IT APPEARS
 TO BE BATTERY BACK UP, BUT NOT ENOUGH INFORMATION IS
 PROVIDED. PLEASE SEE FIXTURES, Z,ETC.
  
 15) NOTE: PLEASE SEE CIRCUITING FOR ATM ROOM/AREA AND
 THE CIRCUITING FOR THE FIRE COMMAND CENTER. PLEASE SEE
 PANEL SCHEDULE FOR 1LB2, 29 AND 31, ETC. PLEASE PROVIDE
 THE CORRECTED IDENTIFICATION FOR THE CIRCUITS AND
 DESIGNATIONS.
 FBC 106.1.2 ADMIN SECT.
  
 16) NOTE: PLEASE PROVIDE ALL MINIMUM WIND LOADING FOR
 SITE LIGHTING LIGHT POLES, AND THAT OF THE POLES ON
 GARAGE ROOF STRUCTURE. PLEASE KNOW A DETAIL ON HOW
 THESE WILL BE ATTACHED ON PARKING DECK OF THE GARAGE
 AND POLE DETAIL FOR GROUND MOUNTED/BURIED POLES WILL BE
 REQUIRED. PLEASE KNOW ALL SHOW MEET THE FBC 140MPH
 (3SEC GUST) 120MPH SUSTAINED.
 THE STRUCTURAL CALCULATIONS WILL BE REVIEWED BY THE
 BUILDING PLAN REVIEWER.
 FBC 106.1.2 ADMIN SECT.
  
 17) NOTE: PLEASE CLARIFY THE LOAD FOR THE LIGHTING IN
 THE COURTYARD AREA FOR FIXTURES SA1. PLEASE SEE 1GHEA
 INDICATES A LOAD OF 7500VA, YET THE 10 FIXTURES AT 400
 EACH DO NOT CORRELATE TO THIS. PLEASE CLARIFY IN
 RESPONSE OF THE TOTAL LOAD IS BE FIGURED BASED ON THE
 INVERTER AT 7500/
 FBC 106.1.2
  
 18) NOTE: PLEASE SEE OTHER SITE LIGHTING FIXTURES SB,
 WHICH IS 24 FIXTURES AT 70W'S EACH, YET THE LOAD ON THE
 PANEL SCHEDULE IS ACTUALLY HIGHER THAN THIS? PLEASE SEE
 1GHA-18.
  
 19) NOTE: PLEASE PROVIDE THE VOLTAGE DROP ON THIS SAME
 CIRCUIT AS NOTED ABOVE IN NOTE # 18, PLEASE SEE FIXTURE
 SA INDICATE #8?S, AND YET SB WHICH CONTAIN A LONGER RUN
 AND MORE FIXTURES ONLY INCREASE UP TO A #10 AWG. PLEASE
 SEE FBC 13-413.1.ABC.1.2.
  
 20) NOTE: PLEASE PROVIDE A WORST CASE FOR BOTH FEEDER
 AND BRANCH CIRCUIT.
 13-413.1ABC.1.
 IT IS NOTEDTHAT ON MANY OF THE PANEL SCHEDULES A VD %
 IS ALREADY SHOWN, HOWEVER PLEASE BE SURE TO INDICATE
 THE ABOVE. (CAN BE DONE ON A SIMPLE TYPICAL TABLE). FBC
 106.1.2.
  
 21) NOTE: PLEASE SEE THE 100% FIRE SPRINKLER PLANS
 SUBMITTED DO NOT CORRELATE WITH THE FA OR ELECTRICAL
 PLANS SUBMITTED WITH RESPECT TO THE FIRE PUMPS. PLEASE
 SEE THE FS SHEETS WHICH INDICATE ELECTRIC, ELECTRICAL/
 DIESEL AND DIESEL. PLEASE SEE THE ELECTRICAL PLANS AND
 THE MANUFACTURE SPECS/CUT SHEETS SUBMITTED ONLY
 INDICATE DIESEL.
 PLEASE SEE THE MINIMUM FUEL TANK SIZE SHALL BE
 SUFFICIENT FOR A MINIMUM OF 8HRS AT 100% LOADS. IF
 ELECTRICAL AND BEING DRIVEN BY THE BACK UP POWER OF AN
 EMERGENCY GENERATOR, THE ON-SITE FUEL SUPPLY SHALL BE
 BASED ON THE 100% LOAD OF THE FIRE PUMP AND ALL OTHER
 LEGAL AND EMERGENCY STAND-BY LOADS AT 100% FOR TIMES
 REQUIRED.
 PLEASE SEE 2002 NFPA-110, TEXT EXTRACTED FORM THE
 CODE:
 9.6.2.2 THE FUEL SUPPLY CAPACITY SHALL BE SUFFICIENT
 TO PROVIDE 8 HOURS OF FIRE PUMP OPERATION AT 100
 PERCENT OF THE RATED PUMP CAPACITY IN ADDITION TO THE
 SUPPLY REQUIRED FOR OTHER DEMANDS.
 PLEASE SEE NFPA-20 2003 IF DIESEL DRIVEN AND THE SAME
 AMOUNT OF FUEL REQUIRED WHICH EQUALS 1GAL PER HP PER
 HOUR PLUS 5% FOR SUMP AND 5% FOR EXPANSION. PLEASE SEE
 THE FOLLOWING THE CODE.
 11.4.3.1 FUEL SUPPLY TANK(S) SHALL HAVE A CAPACITY AT
 LEAST EQUAL TO 5.07 L PER KW (1 GAL PER HP), PLUS 5
 PERCENT VOLUME FOR EXPANSION AND 5 PERCENT VOLUME FOR
 SUMP AND THE COMMENTARY SECTION AS FOLLOWS, A.11.4.3
 THE QUANTITY 5.07 L PER KW (1 GAL PER HP) IS EQUIVALENT
 TO 0.634 L PER KW (1 PINT PER HP) PER HOUR FOR 8
 HOURS. WHERE PROMPT REPLENISHMENT OF FUEL SUPPLY IS
 UNLIKELY, A RESERVE SUPPLY SHOULD BE PROVIDED ALONG
 WITH FACILITIES FOR TRANSFER TO THE MAIN TANKS.
  
 22) NOTE: PLEASE BE SURE THE NFPA-20 2003 EDITION IS
 REFLECT ON ALL PLANS AS THE CURRENT CODE IN EFFECT FOR
 THE SCOPE OF WORK AND DESIGN RELEVANT TO THIS PROJECT.
  
 23) NOTE: PLEASE SEE NEC 210.8B3 FOR ALL RECEPTACLES IN
 KITCHENS IN OTHER THAN DWELLING UNITS. PLEASE SEE THIS
 WOULD BE REQUIRED FOR CAFE/ KITCHENETTE AREAS AS SHOWN
 ON PLANS.
  
 24) NOTE: PLEASE SEE MANY AREAS WHERE THE
 FUTURE/PROPOSED FURNITURE LAYOUTS WERE REMOVED FROM THE
 PLANS WHERE THEY WERE ON THE 50% AND THE 90% PLANS?
 PLEASE LOCATE BACK ON PLANS FOR REVIEW OF THE EGRESS
 PATHS AND LIFE SAFETY FOR MINIMUM WIDTHS ETC. THIS MAY
 ALREADY BE IN THE FIRE MARSHAL'S OFFICE REVIEW
 COMMENTS, HOWEVER IF NOT, THIS IS REQUIRED WHETHER OR
 NOT COMMENT IS MADE.
 LS 101 7.8, 7.9, 7.8.1.3, 7.9.2.2.
  
 25) NOTE: PLEASE SEE MISSING THE PHOTO-METRICS FOR THE
 GARAGE STAIR TOWERS. PLEASE SEE THE PHOTO-METRICS AS
 SUBMITTED ARE A LITTLE CONFUSING. PLEASE PREVIOUS
 COMMENTS ONLY REQUESTED EGRESS PATHS OF LEVELS
 SURFACES/ CORRIDORS AND EGRESS PATHS THAT OF THE STAIR
 TOWERS. PLEASE SEE THERE MUCH INFORMATION SUBMITTED
 GIVING FIXTURE DESIGNATIONS AND ROOM BY ROOM LEVELS?
 PLEASE PROVIDE THE EGRESS PATHS INFORMATION INDICATING
 THE CLEAR NORMAL AND EMERGENCY LEVELS AS NEEDED AND
 REQUIRED BY CODE.
 PLEASE PROVIDE A BREAKDOWN OF THE NORMAL AND EMERGENCY
 AVERAGE. PLEASE SEE THAT INFORMATION OF WHICH IS
 SUPPLIED ON EACH "OVER-ALL" SHEET DOES NOT SUPPLY THE
 INFORMATION AS NEEDED.
 PLEASE SEE 9-4.1 WHICH INDICATES IN TITLE BLOCK,
 EMERGENCY/ NORMAL?
  
 26) NOTE: PLEASE SEE 9-5.2 WHICH SEEMS TO INDICATE
 "DOUBLE FIXTURES" IN STAIR TOWER AREAS.
 PLEASE CLARIFY FOR EACH SECTION OF THE BUILDING AND ON
 EACH LEVEL.
 FBC 106.1.2 ADMIN SECTION.
  
 27) NOTE: PLEASE CLARIFY GARAGE LIGHTING WHICH SHOWS
 "ON" NEXT TO SOME FIXTURES ON PLANS. (RAMP AREAS) THIS
 IS UNCLEAR AT THIS TIME WHAT IS MEANT BY THIS.
 FBC 106.1.2 ADMIN SECTION
  
 28) NOTE: PLEASE PROVIDE A NOTE ON PLANS AND PLEASE BE
 SURE TO CORRELATE WITH THE MECHANICAL PLANS AS THE "XP"
 LCP'S ARE REQUIRED TO BE INSTALLED IN AREAS WITH LESS
 THAN 90% HUMIDITY AS REQUIRED BY THE MANUFACTURE.
 PLEASE BE SURE ALL ROOMS IN WHICH THESE PANELS ARE
 LOCATED SHALL BE CONDITIONED AS REQUIRED. PLEASE
 PROVIDE THE ADDITIONAL NOTE AND ANY CHANGES ON
 MECHANICAL PLANS ALONG WITH NOTE ON 5-3.0.
 110.3, 90.7.
  
 29) NOTE: PLEASE SEE MISSING LCPG.COULD NOT LOCATE ON
 PLANS, SCHEDULE, AND RISER OR ON PLANS.
 FBC 106.1.2ADMIN SECTION.
  
 30) NOTE: PLEASE SEE MISSING THE ELECTRICAL ROOM FOR
 1HMGB AND 1HMGA ON THE LAYOUTS FOR THE ELECTRICAL
 ROOMS.
 PLEASE PROVIDE. 106.1.2,
 NEC 110.26
  
 31) NOTE: PLEASE SEE MAIN ELECTRICAL ROOM AND THE
 MISSING ELECTRICAL ROOM FROM NOTE #30 ABOVE WHICH IS
 STILL INDICATING DOORS WITH AN "IN-SWING" WHICH IS NOT
 PERMITTED. PLEASE ALSO BE SURE TO ADD A NOTE WITH
 RESPECT TO PANIC HARDWARE REQUIRED FOR ALL DOORS AS
 REQUIRED PER 110.26. (MAIN ELECTRICAL ROOM/ AND ROOM
 NOTED ON NOTE #30).
 PLEASE SEE THE DOOR SWINGS WERE NOTED ON ALL OF THE
 REVIEWS BASED ON THE 50%, 90% AND THIS REVIEW. PLEASE
 GO OVER ALL PLANS AND DOORS.
  
 32) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT
 SHEETS FOR AL THE TANK-LESS WATER HEATER UNITS. THESE
 MAY ALSO LABELED AS INSTA-HOTS. PLEASE SEE MISSING
 DISCONNECTS AS REQUIRED ON THESE UNITS. THESE COULD NOT
 BE LOCATED ON PLANS.
 PLEASE SEE SIZING OF THE OVER CURRENT DEVICES,
 DISCONNECTS AND ETC SHALL BE BASED ON EACH UNIT. PLEASE
 SEE 422.31, 110.3, AND 90.7.
  
 33) NOTE: PLEASE SEE SOME TWH UNITS WHICH ARE SHOWN ON
 PLANS ARE MISSING THE REQUIRED CIRCUITING. CAN NOT
 REVIEW FOR COMPLIANCE OF LOAD, CONDUCTOR SIZE, OCP ETC
 AT THIS TIME.
 PLEASE COMPLETE. 240.4, 310.16, 408.4, FBC 106.1.2
  
 34) NOTE: PLEASE PROVIDE INFORMATION FOR FAIL SAFE
 OPERATION OF THE POWER OPERATED DOORS. THE FAILURE OF
 POWER SHALL NOT IMPEDE THE EGRESS FROM A BUILDING
 DURING A POWER FAILURE AT ANY TIME EVEN IF THESE
 CIRCUITS ARE ON THE BACK-UP GENERATOR.
 LS 101 7.19
 THIS MAY BE IN THE FIRE MARSHAL'S REVIEW COMMENTS,
 HOWEVER IF NOT THIS ISSTILL REQUIRED.
  
 35) NOTE: PLEASE ALSO PROVIDE THE FAIL SAFE OPERATION
 OF THE GATES AT THE GARAGE.
 THE SAME NOTE AS ABOVE FOR GATES.
  
 36) NOTE: PLEASE SEE THERE ARE SEVERAL ELECTRICAL ROOMS
 ON PLANS WHICH THE GROUND BAR IS BEING IN THE DOOR WAY?
 THIS IS APPEARS TO BE A MISPRINT. PLEASE CORRECT AND
 ADJUST PLANS AS NEEDED.
 FBC 106.1.2, NEC 110.26
  
 37) NOTE: PLEASE SEE ELECTRICAL ROOM LAYOUT AS THERE
 ARE SOME PANELS WHICH ARE SHOWN IN THE DOOR WAY OR
 PROTRUDING INTO THE DOOR WAY. THIS SEEMS TO BE AN
 OVERLAY/MISPRINT ISSUE AS NOTED ABOVE.
 110.26.
  
 38) NOTE: PLEASE SEE ELECTRICAL ROOM'S LAYOUTS WHICH
 ARE MISSING WALLS AND DOORS. PLEASE SEE 2ND, 3RD, AND
 4TH FLOORS ROOM #4. 4-2.0,4- 3.0,4-4.0
 CAN NOT VERIFY SOME CODE RELATED ITEMS AT THIS TIME.
 110.26.
 FBC 106.1.2 ADMIN SECTION.
  
 39) NOTE: PLEASE SEE ELECTRICAL ROOM LAYOUTS WHICH ARE
 SHOWING PANELS WHICH ARE NOT ON ANY RISER, PANEL
 SCHEDULES ETC. PLEASE ALSO SEE TRANSFORMERS BEING SHOWN
 WHICH ARE NOT LABELED ALSO?
 PLEASE LABEL AS "FUTURE" IF INDEED THE SPACE IS BEING
 ALLOTTED FOR FUTURE EXPANSION WHICH IS REQUIRED BY CODE
 UNDER 90.8, 110.26
  
 40) NOTE: PLEASE BE SURE TO LABEL ALL LCP?S ON PLANS,
 ELECTRICAL ROOMS, RISER AND CORRELATE WITH THE LCP'S
 SCHEDULE.9EXAMPLE LCP1D, LCP3B, ETC)
 FBC 106.1.2, 106.3.5.1.2
  
 41) NOTE: PLEASE SEE ELECTRICAL ROOM LAYOUTS, SOME SHOW
 TRANSFORMER SIZES AND SOME DO NOT. PLEASE COMPLETE AND
 SHOW.
 450, FBC 106.1.2, 110.26, 450.9, ETC
  
 42) NOTE: PLEASE SEE ELECTRICAL ROOM LAYOUTS INDICATE
 WHAT IS BEING SHOWN AS "NAC" PANELS; HOWEVER IT IS
 UNCLEAR WHAT THESE ARE? PLEASE EXPLAIN.
 FBC 106.1.2, 106.3.5.1.2
  
 43) NOTE: PLEASE SEE "SHADED" AREAS ON MEZZANINE LEVEL
 PLANS E-1.1.4, PLEASE CLARIFY
 106.1.2 FBC ADMIN SECTION.
  
 44) NOTE: PLEASE SEE STAIR TOWERS WHICH ALSO INDICATE
 AN ELECTRICAL ROOM IN THE STAIRWELL. THIS APPEARS TO BE
 SOME SORT OF MISPRINT. THIS IS BEING SHOWN ON MORE THAN
 ONE FLOOR AND LOCATION. PLEASE BE SURE TO CORRELATE
 WITH ALL OTHER PLANS.
 FBC 106.1.2
 *** ONLY AS NOTED, IT IS KNOWN THAT NO ELECTRICAL
 EQUIPMENT OR OTHER ITEMS ARE PERMITTED IN EXIT
 STAIRWAYS UNLESS PERTAINING TO STAIRWAYS.
  
 45) NOTE: PLEASE SEE OTHER SHEETS WHICH INDICATE THE
 OPENING FOR THE DOOR LEADING INTO THE STAIRS ACTUALLY
 THROUGH WHAT WOULD BE THE LOW VOLTAGE ELECTRICAL DATA
 ROOM. WHERE THE SANE LOCATION IS SHOWING WHAT APPEARS
 TO BE A DOOR ON THE SHEER/RATED STAIRWAY WALL. PLEASE
 SEE THIS IS SHOWN LIKE THIS AT MANY LOCATIONS AND ON
 MULTIPLE FLOORS. PLEASE BE SURE TO COORDINATE LAYERS,
 LEVELS, AND SHEETS FOR ALL.
 FBC 106.1.2 ADMIN SECTION.
  
 45) NOTE: PLEASE SEE WHAT APPEARS TO BE MISSING WALLS,
 DOORS SEPARATION E-1-1.2, LIBRARY/MUSEUM/ STORE? PLEASE
 SHOW AS THE REQUIREMENTS FOR CHAPTER 13 CAN NOT
 VERIFIED FOR CONTROL OF LIGHTING. LIGHTING OF SOME TYPE
 INCLUDING EXIT/EMERGENCY LIGHTS ARE STILL REQUIRED IN
 SPACE, EVEN IF FOR FUTURE BUILD OUT. PLEASE SEE LS 101
 7.8, 7.9 AND POSSIBLE COMMENTS FROM FIRE MARSHAL?S
 OFFICE.
 13-415.1.ABC.1.ABC.1.1, .1.2, .1.3
  
 46) NOTE: PLEASE VERIFY LIGHTING POWER DENSITIES FOR
 GARAGE. SOME OF WHICH WERE NOTED ABOVE IN COMMENTS FOR
 CHAPTER 13 REQUIREMENTS, HOWEVER THIS IS ALSO BE NOTED
 SEPARATELY.
 PLEASE SEE CONTROL MEANS.
 SEE FBC CHAPTER 13. (ALL)
  
 47) NOTE: PLEASE PROVIDE AN ELEVATION/DETAIL FOR ALL
 ELECTRICAL CONDUITS BEING RUN FROM GARAGE TO THE MAIN
 BUILDING. THIS BUILDING IS BEING CONSIDERED "ATTACHED"
 AND ONE " BUILDING" BY DEFINITION, HOWEVER DUE THE
 UNDERSTANDING OF MANY OF THE CONDUITS ARE NOW BEING
 INSTALLED IN THE SLAB OR UNDER GROUND AND THE AMOUNT OF
 OTHER CONDUITS, PIPING, BEING INSTALLED IN THIS SAME
 AREA, IT IS OF CONCERN FOR THE SPACE REQUIREMENTS FOR
 BUNDLING OF CONDUITS, DE-RATING OF CONDUCTOR
 AMPACITIES. ETC. (THIS CAN BE A DETAIL LIKE A DUCT-BANK
 DETAIL)
 FBC 106.1.2, 310.16, 300.8, 300.10, 310.10, 310.15,
 310.16, 300.17 ETC.
 THERE ARE MANY SECTIONS WHICH COULD BE REFERENCED.
 PLEASE ALSO SEE COMMENT WITH RESPECT TO WIRING METHODS
 OF EMERGENCY FEEDERS ETC.
  
 48) NOTE: PLEASE VERIFY THE SHUNT TRIP FOR THE 4TH
 FLOOR IT PANEL. PLEASE SEE THIS SHUNT TRIP BREAKER
 SHOULD BE LOCATED IN 1HEE. PLEASE ALSO SEE THAT PLANS
 INDICATE WHAT SEEMS TO BE A PUSHBUTTON AT ONE DOOR
 LABELED EPO, AND ONE WHICH APPEARS TO BE THE SAME
 HOWEVER NOT LABELED AS EPO.PLEASE LABEL. AN EPO WILL
 BE REQUIRED AT EACH DOOR.
 PLEASE SEE 645.10, HANDBOOK WHICH EXPLAINS THE
 DISCONNECTING AT THEIR SUPPLY POINT.
  
 49) NOTE: PLEASE KNOW AS NO INFORMATION FOR THE IT ROOM
 EQUIPMENT IS BEING SUBMITTED WITH THIS RECORD SET OF
 PLANS, PLEASE PLACE NOTE AND CLOUD ON 4TH FLOOR POWER
 PLANS THAT ALL ELECTRICAL EQUIPMENT, UPS, SERVER
 EQUIPMENT ETC IN THE IT ROOM SHALL BE UNDER A SEPARATE
 PERMIT, PLANS, AND FEES BASED ON THE EQUIPMENT BEING
 INSTALLED IN THIS ROOM. REVIEW FOR CODE COMPLIANCE FOR
 THIS ROOM CAN NOT BE COMPLETED AT THIS TIME. THE
 REQUIREMENTS FOR THE CONSTRUCTION OF THIS ROOM IS
 REQUIRED AT THIS TIME, INCLUDING THE MINIMUM 1HRA
 RATING, THE FIRE DAMPERS ETC (IF APPLICABLE) AND THE
 SHUT DOWN OF AN AND ALL A/C EQUIPMENT.
 NEC 645, NFPA-75
  
 50) NOTE: PLEASE PLACE NOTE ON THE LIGHTNING PROTECTION
 PLANS, BOTH THE LAYOUT OF THE SYSTEM AND THE SYSTEM
 DETAIL.
 THESE PLANS MAY BE USED FOR REFERENCE OF PERMITTING
 PROJECT; HOWEVER SEPARATE PERMIT AND FEES WILL BE DUE
 UPON APPLICATION. THE LP SYSTEM IS NOT PART OF THE
 VALUE FOR SCOPE OF WORK.
 PLEASE ALSO NOTE THAT SYSTEM MUST BE INSTALLED BY A
 LICENSED LIGHTING PROTECTION CONTRACTOR WHO WILL
 PROVIDE A MASTER UL CERTIFICATION OF THE SYSTEM UPON
 COMPLETION.
 (OR WORDS TO THAT AFFECT)
  
 51) NOTE: PLEASE SEE LOADS FOR RECEPTACLE CIRCUITS
 SHALL BE BASED ON 180VA MINIMUM FOR CIRCUITS. PLEASE
 SEE CIRCUITS FOR WHAT IS A "J" BOX FOR FUTURE MODULAR
 FURNITURE IS LABELED AS RECEPTACLES? PLEASE LABEL FOR
 THE INTENDED USE.
 408.4, 220.10
  
 52) NOTE: PLEASE SEE PLANS WHICH INDICATE A TRIANGULAR
 SYMBOL WITH A "F" NEXT TO THESE HOWEVER COULD NOT ANY
 INFORMATION ON WHAT THESE ARE ON ANY SYMBOL LEGEND?
 PLEASE REMOVE OR DESIGNATE.
 FBC 106.1.2
  
 53) NOTE: PLEASE COORDINATE ALL OVER-LAYS AND LAYOUTS
 FOR ELECTRICAL, MECHANICAL, PLUMBING, BUILDING AND ALL
 OTHER TRADE PLANS. PLEASE KNOW THE ELECTRICAL 100%
 PLANS DO NOT SHOW THE SAME ELECTRICAL ROOMS AND
 EQUIPMENT AS THE 100% MECHANICAL PLANS, PLUMBING OR
 BUILDING PLANS ALONG WITH OTHER SHEETS FROM OTHER
 TRADES.
 REVIEW OF ALL APPLICABLE ITEMS WILL STILL NEED TO BE
 DONE AS REQUIREMENTS FOR ELECTRICAL AND OTHER TRADES
 WILL MOST CONTAIN CLEAR CONFLICTS WHICH MAY OR MAY NOT
 BE PERMITTED.
 110.26, 240.24 NEC.
 FBC 106.3.5.1.1 ADMIN SECTION FOR ALL TRADES FOR
 COMMERCIAL PLANS.
  
 54) NOTE: PLEASE CORRELATE THE PLANS WITH THE
 MANUFACTURE SPECS/CUT SHEETS FOR THE GENERATOR WHICH IS
 BEING SUBMITTED AS A LARGER UNIT IN THE SPEC BOOK AS
 SHOWN ON PLANS. THIS WILL AFFECT THE FUEL SUPPLY, AND
 THE FUEL LINE SUPPLY FOR THE PROPOSED NATURAL GAS
 LINE.
 90.7, 110.3,
 FBC 106.1.2
  
 55) NOTE: PLEASE INCLUDE DETAIL AND ATTACHMENT FRO THE
 LIGHTNING PROTECTION SYSTEM AS PART OF THE MAIN
 GROUNDING ELECTRODE SYSTEM AS REQUIRED PER 250.106. IT
 IS NOTED THAT THE DETAIL IN THE LP DETAILS IN THE REAR
 OF PLANS, HOWEVER DOES NOT INCLUDE THE GE SYSTEM, OR
 THE GE RISER, SYSTEM DOES NOT INCLUDE THE LP GROUNDING
 ATTACHMENT.
  
 56) NOTE: PLEASE INCLUDE ALL OTHER METAL WATER PIPING
 SYSTEMS AS PART OF THE GROUNDING ELECTRODE SYSTEM AS
 REQUIRED PER 250.106. (FIRE SPRINKLER)
  
 57) NOTE: PLEASE SEE SOME BATHROOMS CONTAIN OC SENSORS
 AND MANY DO NOT, PLEASE EXPLAIN AND PLEASE SEE OTHER
 COMMENTS FOR TYPE OF DEVICES WHICH WILL BE REQUIRED.
 13-415.1.ABC.1.2
  
 58) NOTE: PLEASE KNOW SOME SORT OF BATTERY BACK UP
 FIXTURE WILL BE REQUIRED IN THE LARGER BATHROOMS (ROOM
 OTHER THAN SINGLE POINT OF USE).
 PLEASE SEE LS 101 7.8., 7.9
 THIS WAS DISCUSSED WITH THE FIRE MARSHAL CHIEF AND WILL
 BE REQUIRED BOTH BY THIS OFFICE AND THE FIRE MARSHAL'S
 OFFICE IN THE INTEREST OF LIFE SAFETY AND CODE AS
 REFLECT.
  
 59) NOTE: PLEASE SEE NUMEROUS OFFICES ON ONE CIRCUITS
 COMING FROM THE LIGHTING CONTROL PANEL(S). PLEASE SEE
 THE FOLLOWING SCENARIO: IN THE EVENT OF AFTER HOURS,
 THE TIMER ?SWEEPS? THROUGH AND TURNS OFF THAT
 PARTICULAR CIRCUIT, AND EMPLOYEE WILL "RESET" THE
 SENTRY SWITCH WHICH IN-TURN TURN THAT BRANCH CIRCUIT
 BACK ON. WOULD THAT NOT IN-TURN ON OTHER LIGHTS ON THAT
 CIRCUIT. (OTHER ROOMS, OFFICES ETC?)
 PLEASE SEE PREVIOUS NOTE ABOVE #9 WHICH ALSO TOUCHED ON
 THE LIGHTING CONTROL SYSTEM BEING PROPOSED, HOWEVER
 THERE ARE SCENARIOS WHICH ARE STILL IN QUESTION OR NEED
 TO BE WORKED OUT.
 13-415.1.ABC.1.1
  
 60) NOTE: PLEASE SEE MISSING CONTROLS FOR ELEVATOR PIT
 LIGHTS. 13-415.1.ABC.1.2,
 620.24B.
  
 61) NOTE: PLEASE SEE THERE ARE SOME LOCATIONS ON PLANS
 WHICH ARE SHOWING "NL'S" (NIGHT LIGHTS) BEING PART OF A
 PERMANENT ON SCENARIO, HOWEVER THE NUMBER OF FIXTURES
 BEING PROPOSED TO REMAIN ON AS NIGHT LIGHTS ARE OVER
 WHAT IS BEING CONSIDERED AS NORMAL. PLEASE KNOW THIS
 CAN BE GONE OVER, HOWEVER PLEASE SEE SOME AREAS WHERE
 THERE ARE 10-20PLUS LIGHTS BEING LEFT ON.
 THE INTENT OF CHAPTER 13 AND ALSO THE INTEREST OF LIFE
 SAFETY SHOULD BE CONSIDERED. PLEASE CALL TO OVER. SEE
 SHEET E2-1.2 FOR EXAMPLE IN LOBBY AREA.
  
 62) NOTE: PLEASE SEE NFPA-20 11.3, 11.3.2, 11.3.2.3 AND
 FLORIDA FIRE PREVENTION CODE , NFPA-1 7-4FOR OTHER
 REQUIREMENTS FOR FIRE PUMPS AND ROOMS IN WHICH THEY ARE
 LOCATED.
 PLEASE ALSO SEE 11.4.6.2 FUEL PIPING SHALL NOT BE
 GALVANIZED STEEL OR COPPER.
 PLEASE KNOW AS PART OF THE COMPLETED TESTING AND
 ACCEPTANCE AS REQUIRED IN CHAPTER 14, DOCUMENTATION FOR
 TESTING FOR FIRE PUMP ON A WEEKLY BASIS IS REQUIRED TO
 THE OWNER OF RECORD.CODE TEXT FROM NFPA-20: 11.6.1.1
 ENGINES SHALL BE STARTED NO LESS THAN ONCE A WEEK AND
 RUN FOR NO LESS THAN 30 MINUTES TO ATTAIN NORMAL
 RUNNING TEMPERATURE.
  
 63) NOTE: PLEASE SEE NFPA-110 CHAPTER 7 FOR THE
 INSTALLATION OF THE GENERATOR. PLEASE SEE 7.4 AND 7.5,
 PROVIDE DETAIL FOR MOUNTING OF UNIT TO ALLEVIATE ANY
 INTEGRITY INTERFERENCE OF THE STRUCTURE.
  
 64) NOTE: PLEASE SUBMIT THE SPEC/CUT SHEET FOR THE
 PROPOSED MTS. THE "KIRK KEY" AS SHOWN AND HAND WRITTEN
 ON SPECS IS NOT ACCEPTED AT THIS TIME. THERE ARE MANY
 OF THESE SYSTEMS ON THE MARKET WHICH WILL PERMIT THE
 POWER FROM TWO SOURCES AT ONCE WHICH IS STRICTLY
 PROHIBITED. PLEASE SEE 700.6, 701.7, 110.3, AND 90.7
 CAN NOT VERIFY AT THIS TIME. PLEASE ALSO SEE THE
 FOLLOWING COMMENT.
  
 65) NOTE: PLEASE SEE RISER AND PLANS WERE REVISED FROM
 THE 50% AND 90% PLANS CHANGING ALL ATS UNITS TO 3-POLE
 UNITS. PLEASE SEE ALTHOUGH GF PROTECTION IS NOT
 REQUIRED ON THE EMERGENCY SIDE OF THE EMERGENCY SYSTEM
 AND LEGALLY REQUIRED SYSTEMS, PROPER GROUND FAULT
 SENSING IS REQUIRED. PLEASE KNOW DOCUMENTATION FROM
 MORE THAN ONE MANUFACTURE WAS SENT TO THE ENGINEER
 PRIOR TO THE REVIEW WHEN THE PLANS WERE SUBMITTED ON
 THE 7TH OF NOV. PLEASE SEE NFPA-110 6.2.15** ISOLATION
 OF NEUTRAL CONDUCTORS. PROVISIONS SHALL BE INCLUDED FOR
 ENSURING CONTINUITY, TRANSFER, AND ISOLATION OF THE
 PRIMARY AND THE EPS NEUTRAL CONDUCTORS WHEREVER THEY
 ARE SEPARATELY GROUNDED TO ACHIEVE GROUND-FAULT
 SENSING.
 PLEASE SEE AN ATTACHED BRIEF EXPLANATION FROM"ASCO"
 WHITE PAPER: WHERE GROUND FAULT PROTECTION IS TRIGGERED
 BY THE CODE AND AN ALTERNATE POWER SUPPLY IS INCLUDED,
 SWITCHING OF THE NEUTRAL BECOMES NECESSARY. THE CIRCUIT
 SHOWN ABOVE ILLUSTRATES SUCH A CIRCUMSTANCE. THE
 SERVICE IS LARGER THAN 1,000 AMPS. CONSEQUENTLY, GROUND
 FAULT PROTECTION IS REQUIRED AT THE MAIN SERVICE
 DISCONNECT AT A MINIMUM. IF IT IS INSTALLED THERE AND
 THE GENERATOR NEUTRAL GROUNDING WAS THROUGH A SOLID
 CONNECTION TO THE MAIN SERVICE NEUTRAL, A GROUND FAULT
 WHEN THE GENERATOR IS FEEDING THE LOAD WILL CAUSE THE
 MAIN SERVICE DISCONNECT TO OPEN. THIS WILL NOT
 DISCONNECT THE ARCING FAULT FROM THE GENERATOR.
 COORDINATION IS THUS LOST."
 PLEASE KNOW BASED ON THE INFORMATION FROM SEVERAL
 MANUFACTURES AND THE CODE PLEASE ADJUST AS REQUIRED.
 PLEASE ALSO SEE GENERATOR GROUNDING DETAIL WILL BE
 REQUIRED TO BE REVISED.
 PLEASE SEE E5-1.1.18 WHICH NOTES A #3 CONDUCTOR, WHICH
 WOULD NOT BE LARGE ENOUGH.
 PLEASE SEE 250.20, 250.30, 250.66, 240.13, 230.95,
 700.7D, 700.26
 PLEASE SEE THE MTS.
  
 66) NOTE: PLEASE SEE THERE ARE MANY EXIT/EMERGENCY
 LIGHTS WHICH DO NOT SHOW ANY CONNECTION TO ANY LOCAL
 CIRCUIT IN ANYWAY. PLANS NOTE THIS AND MANY ARE SHOWN
 THIS WAY, HOWEVER NOT ALL. PLEASE GO THROUGH PLANS.
 PLEASE SEE 700.12E WHICH REQUIRES THE BRANCH CIRCUIT
 FEEDING THE UNIT EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL LIGHTING IN THE AREA
 AND CONNECTED AHEAD OF ANY LOCAL SWITCHES.
  
 67) NOTE: PLEASE SEE OVER ALL 3RD FLOOR PLANS, WHICH
 SEEM TO BE SHOWING LIGHTING OF SOME KIND ON GARAGE
 PLANS?
 PLEASE ALSO SEE E2-4.0
 FBC 106.1.2 ADMIN SECTION.
  
 68) NOTE: PLEASE SEE NOTE #2 ON RISER WITH RESPECT TO
 THE MTS WHICH IS TO PROVIDE FUTURE PROVISIONS FOR
 POSSIBLE PORTABLE GENERATOR TO RUN THE EMERGENCY
 SYSTEMS, PLEASE KNOW A DETAIL TO A LOCATION AND HOW
 THIS CONNECTION WILL BE MADE IS REQUIRED.THE RUNNING
 OF CORDS, CONDUCTORS ETC SHALL BE PERMITTED TO TRAVEL
 THROUGH THE ELECTRICAL ROOM DOORS, ON SIDEWALK AREAS OR
 ANY LOCATIONS PROVIDING A TRIPPING HAZARD OR NOT
 SECURING LIVE PARTS ETC.
 PLEASE PROVIDE A DETAIL AS THIS CONNECTION POINT WILL
 BE SUBSTANTIAL IN NATURE. (J-BOX) ETC ON THE OUTSIDE OF
 BUILDING ETC.
 110.26, 110.27, NEC 527.
  
 69) NOTE: PLEASE PROVIDE CALCULATIONS ON NEUTRAL
 CONDUCTORS FOR ALL NON-LINEAR CIRCUITS. PLEASE SEE ALL
 CIRCUITS WHICH CONTAIN THESE LOADS SHALL MEET THE
 SIZING REQUIREMENTS TO HANDLE AND ALLEVIATE THE OVER
 LOADING OF THE NEUTRAL ON A 3-PHASE 4-WIRE SYSTEM WITH
 PREDOMINATELY OR ACTUALLY IN MANY CASES ALL NON-LINEAR
 LOADS. PLEASE SEE THIS CAN BE DONE BY USING MANY
 METHODS. THE K-RATED TRANSFORMERS WERE REMOVED FROM THE
 DESIGN AS ON PREVIOUS PLANS, SO PLEASE SEE THE REQUEST
 FOR FULL NEUTRAL LOAD CALCULATION OR THE SIZING OF THE
 NEUTRAL AT 200%.
 PLEASE SEE THE RISK OF FIRE AND CAUSE TO PROPERTY
 DAMAGE IS OF CONCERN PLEASE SEE STUDIES IN WHITE PAPERS
 WHICH INDICATE AS MUCH AS 1.7 TIMES THE RATED LOAD OF
 THE CONDUCTOR.
 PLEASE SEE THE FOLLOWING CODES: THIS OFFICE IS AWARE OF
 WHAT A FPN MEANS, HOWEVER SEE SECTIONS GIVEN WHICH DO
 NOT CONTAIN FPN. 210.4A (FPN), 220.22 (FPN(2), 310.10,
 310.15B4(C), 400.5, 520.44, 408.16, AND FBC 104.6
 ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF WEST
 PALM BEACH.
  
 70) NOTE: PLEASE SEE E2-4.2 STAIR TOWER AREA WHICH
 MENTIONS "HOLD FOR ARCHITECT" ? PLEASE SEE PREVIOUS
 NOTE WITH RESPECT TO DOORS INTO STAIRWAYS ETC.
 FBC 106.1.2 ADMIN SECTION.
  
 71) NOTE: PLEASE KNOW IF IT IS THE INTENT TO UTILIZE
 THESE PLANS FOR FUTURE LOW VOLTAGE WORK FOR LOCATIONS
 OF PHONE, DATE DROP ETC, PLEASE COMPLETE PLANS AS
 SUBMITTED SHOWING ALL LOCATIONS FOR DROPS.PLEASE SEE
 MANY AREAS WHICH LOW VOLTAGE DATE/PHONE DROPS WILL BE
 REQUIRED OR INSTALLED, HOWEVER THESE LOCATIONS ARE NOT
 BEING SHOWN AT THIS TIME.
 IF THE LV SCOPE IS PART OF THE PERMITTED PLANS AS
 SUBMITTED PLEASE REMOVE AND NOTE AS UNDER SEPARATE
 PERMIT PLANS AND FEES.
  
 72) NOTE: PLEASE PROVIDE VD FOR THE FEEDER FOR THE IT
 PANEL. 13-413.1.ABC.1.1
  
 73) NOTE: PLEASE SEE 700.9D FOR THE FEEDERS FROM THE
 GENERATOR TO THE EMSB1 AND THE FEEDERS OUT TO SYSTEMS
 WHICH MAY BE CONSIDERED INSIDE THE BUILDING. PLEASE SEE
 THE CODE AS THERE ARE WAYS TO MEET THE INSTALLATION OF
 THESE FEEDERS, HOWEVER PLANS SHALL INDICATE WHICH WILL
 BE USED. (TYPE OF CABLE, ENCASED IN 2INCHES OF
 CONCRETE, FULLY SPRINKLED ETC)
 PLEASE KNOW AS THE REQUIREMENT OF FULLY SPRINKLED IS
 OFTEN MISTAKEN AS A BUILDING CONTAINING SPRINKLERS.
 THIS IS NOT THE CASE. PLEASE SEE THE INTENT OF 700.9D
 FOR THIS HAS ALWAYS BEEN THAT ALL AREAS CONTAINING
 THESE FEEDERS BE SPRINKLED IF INSTALLED IN OPEN OR
 ABOVE CEILINGS. PLEASE KNOW A COMMENTARY IN THE 2005
 NEC MAKES IS CLEAR WHAT THE INTENT OF THE CODE AND THE
 FURTHER EXPLANATION IS PROVIDED.
  
 74) NOTE: PLEASE SEE NOTE WHICH MENTIONS A "LOCK-OFF"
 DEVICE IS REQUIRED FOR THE FIRE ALARM CIRCUIT. THIS IS
 OK; HOWEVER PLEASE ELABORATE ON THE NOTE AS THE DEVICE
 SHALL BE AN INTEGRAL PART OF THE BREAKER. PLEASE KNOW
 THAT SNAP ON/CLIP ON TYPE DEVICES ARE NOT ACCEPTABLE TO
 THIS AHJ.
 110.3, 90.4
  
 75) NOTE: PLEASE SEE TRANSFORMER TYPICAL DETAIL WHICH
 INDICATES #6 FOR 75KVA TRANSFORMERS. PLEASE SEE
 250.30A2 AND 250.66 FOR THE SIZE ACCORDING TO THE
 4/0'S.
 PLEASE ADJUST. THIS WILL AFFECT THE SIZE TO THE GROUND
 BAR ONLY IN EACH ROOM FROM THIS TRANSFORMER.
  
 76) NOTE: PLEASE PROVIDE THE SIZE OF THE CONDUCTOR ON
 THE GROUNDING ELECTRODE RISER AS PROVIDED. PLEASE SEE
 THE GROUNDING ELECTRODE DETAIL SHOWS A 4/0'S, HOWEVER
 PLEASE SEE E5-2.0.
 250.50, 250.58
  
 77) NOTE: PLEASE SEE THE SIZE OF THE CONDUCTORS ON THE
 SECONDARY SIDE OF ANY TRANSFORMER SHALL BE SIZED AND
 TERMINATE IN OVER-CURRENT PROTECTION WHICH LIMITS THE
 LOAD ON THE CONDUCTORS. PLEASE SEE 240.21C, 310.16.
 PLEASE SEE 1LD2
  
 78) NOTE: PLEASE SEE 4HA, WHICH INDICATE 114A'S OF LOAD
 ON A BREAKER RATED AT 100A?S. PLEASE ALSO SEE 5HA WHICH
 SHOWS A LOAD OF 99A'S ON A 100A BREAKER.
 PLEASE ADJUST AS REQUIRED AS THE LOADS SHALL NOT EXCEED
 THAT OF THE RATING OF THE BREAKER, FEEDERS ETC. 310.16,
 240.4, ETC.
  
 79) NOTE: PLEASE SUBMIT LOAD CALCULATIONS. PLEASE
 INDICATE AND SHOW ALL CONTINUOUS LOADS AND LARGEST
 MOTOR LOADS AT 125%.
 220.3, 220.10, 220.11, 220.13, 215.3,230.42 ETC
  
 80) NOTE: PLEASE SEE SOME SHEETS ON THE UPPER LEVELS,
 1-5.2, 8-5.2 INDICATE A "VAULT", HOWEVER THIS WAS
 COMMENTED ON PREVIOUS REVIEWS AND WAS REMOVED FROM SOME
 SHEETS. PLEASE SEE A SHEET FOR THE SW CORNER OF PROJECT
 AFTER E6-2.1 IF THIS IS INDEED THE SAME AREA. PLEASE
 CLARIFY.
 FBC 106.1.2 ADMIN SECTION.
  
 81) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO
 MINIMUM FOOT CANDLES REQUIRED. PLEASE SEE GARAGE SHALL
 CONTAIN EGRESS PATHS WHICH MEET THIS MINIMUM. BASED ON
 SOME AREAS SHOWN ON PHOTO-METRICS, IT DOES NOT APPEAR
 THIS IS MET.
 PLEASE SEE LIFE SAFETY CODE NFPA-101 2003 7.8.1.3,
 7.9.2.2
  
 82) NOTE: PLEASE SEE WHAT IS KNOW AS STAIR #9, MORE
 THAN ONE FIXTURE BEING SHOWN ON THE SAME LEVEL ON THE
 SAME WALL. THIS IS OK, HOWEVER ONLY A NOTE FOR
 VERIFICATION.
 E9-2.2
  
 83) NOTE: PLEASE CORRELATE THE TRANSFORMERS ON THE
 ELECTRICAL ROOM LAYOUTS AND THE ELECTRICAL RISER.
 PLEASE SEE THERE ARE MANY WHICH ARE SHOWN AS 15KVA ON
 ONE SHEET AND 45KVA ON OTHER SHEETS OR 45KVA ON ONE AND
 75KAV ON ANOTHER. PLEASE ALSO SEE RISER.
 PLEASE SEE SOME BELOW AS NOTED, THIS IS ONLY SOME AND
 IS IN NO WAY ALL POSSIBLE.
 1HB, 75KVA ON RISER, 45KVA IN ELECTRICAL ROOM. 2HB,
 75KVA ON RISER, 45KAV IN ELECTRICAL ROOM. 1GLA-1GHA,
 45K ON RISER, 15K ON ELECTRICAL ROOM PLANS. ETC
  
 84) NOTE: PLEASE BE SURE TO GO THROUGH ALL TRANSFORMERS
 AS THE SIZES AS SHOWN MAY AFFECT THE OVER CURRENT
 PROTECTION ON UNITS, THE CONDUCTORS ON THE PRIMARY AND
 SECONDARY SIDE OF THE UNITS. PLEASE SEE COMMENTS WITH
 RESPECT TO SOME.
 PLEASE SEE TRANSFORMER DETAIL ON 6-1.0, THIS SCHEDULE
 IS BEING SHOWN FOR TYPICAL, HOWEVER IT DOES CORRELATE
 WITH SOME UNITS AS NOTED. SOME ARE SHOWN AS 75KVA WHICH
 ON TYPICAL SCHEDULE MENTIONS 225A OVER CURRENT
 PROTECTION ON THE SECONDARY SIDE, YET SOME TERMINATE IN
 150A OCP ON THE SECONDARY SIDE.
 PLEASE GO THROUGH THESE: 3LC2, EXAMPLE.(NOT ALL)
  
 85) NOTE: PLEASE SEE FBC 2004 CHAPTER 11 FOR
 REQUIREMENTS FOR ADA WITH RESPECT TO HORNS, AND
 STROBES. THE AUDIBLE LEVELS SHALL BE PER BOTH FBC
 CHAPTER 11 AND NFPA-72 AS NOTED, HOWEVER THE MORE
 STRINGENT SHALL APPLY.
 PLEASE SEE 11-4.28.1, 11-4.28.2 AND 11-4.28.3(4).
 PLEASE BE SURE THE LEVELS ARE INDICATED ON PLANS.
 PLEASE KNOW THE LIGHTING CANDELA LEVELS AS REQUIRED IN
 THE FBC ARE FAR GREATER THAN THAT OF NFPA-72. THE
 MINIMUM LEVELS FOR VISUAL SHALL BE 75 CANDELAS. PLEASE
 ADJUST AND PLACE REQUIREMENTS ON PLANS. PLEASE SEE ALL
 FA SHEETS WHICH ONLY INDICATE NFPA-72.
  
  
 86) NOTE: PLEASE KNOW A RESPONSE LETTER/NOTES WERE
 PROVIDED, HOWEVER AS THIS REVIEW WAS MORE OF A REVIEW
 FOR CODE COMPLIANCE, A MORE DETAILED RESPONSE WOULD
 GREATLY HELP IN THE REVIEW PROCESS. THIS RESPONSE COULD
 INDICATE THE SHEETS/LOCATIONS OF CHANGES, CORRECTIONS
 OR ANY COMMENTS RELATED TO AND RESPECT TO THIS
 REVIEWERS NOTES.
 IF ANY OF THESE COMMENTS ARE NOT CLEAR IN ANY FASHION
 OR IF ANY ITEMS ARE NOT UNDERSTOOD IN ANY WAY?PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
  
 ** PLEASE KNOW AS THERE IS SOME INFORMATION NOT YET
 SUBMITTED PLEASE BE SURE TO GO OVER ALL.
  
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. ONCE AGAIN IF THERE
 ARE ANY QUESTIONS , PLEASE DO NOT HESITATE IN CONTATING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-11-25 08:33:56REVIEW BACK IN PROGRESS 11/25/06
2006-11-22 07:38:23REVIEW IN PROGRESS
2006-11-21 20:11:49REVIEW STOPPED, WILL CONTINUE ON 11/22
2006-11-21 18:54:07ELECTRICAL REVIEW HAS NOW RESUMED FROM 11/8
2006-11-08 19:53:56ELECTRICAL REVIEW STILL IN PROGRESS.
2006-11-07 16:03:13NEW ELECTRICAL PLANS BROUGHT IN BY MR. JAMES MINDUR AT
 1500HRS ON 11/6/06
 ELECTRICAL REVIEW IN PROGRESS.

Review Stop ENG ENGINEERING CSD
Rev No 11 Status P Date 2009-02-27 Cont ID  
Sent By mgonzale Date 2009-02-27 Time 15:36 Rev Time 1.00
Received By mgonzale Date 2009-02-27 Time 15:36 Sent To ENG
Notes
2009-02-27 15:37:41**** PASSED *****
  
 ADA RAMP ACCEPTABLE.
 PLANTERS ACCEPTABLE.
  

Review Stop ENG ENGINEERING CSD
Rev No 10 Status P Date 2009-01-26 Cont ID  
Sent By mgonzale Date 2009-01-26 Time 09:55 Rev Time 1.00
Received By mgonzale Date 2009-01-26 Time 09:55 Sent To ENG
Notes
2009-01-26 09:57:59**** PASSED ****
  
 PLANS APPROVED BY DEAN LAUDERMILK AT 45TH STREET
 ENGINEERING OFFICE.
 PROTECTIVE BOLLARDS DETAILS AND PLANS UNDER REVIEW AT
 45TH STREET.
  
 MANUEL J GONZALEZ, PROJECT COORDINATOR
 LOCATION ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 1000 - 45TH STREET, SUITE 15
 WEST PALM BEACH FL 33407
 MAILING ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 P.O. BOX 3506
 WEST PALM BEACH FL 33401
 TELEPHONE:
 45TH STREET OFFICE : 561-494-1040
 45TH DIRECT: 561-494-1085
 FAX: 561-494-1117
 CITY HALL OFFICE: (561) 805-6713
 CITY HALL DIRECT: (561) 805-6313
 CITY HALL FAX: (561) 805-6731 OR 805-6676
 NEXTEL: 561-644-7301
 NEXTEL DIRECT CONNECT: 159*28165*38
 EMERGENCIES:
 CENTRAL OPERATIONS CENTER (DISPATCH) 561-822-2210
 E-MAIL:
 [email protected]
  
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 9 Status P Date 2008-11-17 Cont ID  
Sent By mgonzale Date 2008-11-17 Time 16:09 Rev Time 1.00
Received By mgonzale Date 2008-11-17 Time 16:07 Sent To ENG
Notes
2008-11-17 16:09:06REV 22A
 ADDITION TO CITY HALL PLANTER, COURTYARD GRATES AND
 GARAGE PLANTER.
 APPROVED.
  
 MANUEL J GONZALEZ, PROJECT COORDINATOR
 LOCATION ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 1000 - 45TH STREET, SUITE 15
 WEST PALM BEACH FL 33407
 MAILING ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 P.O. BOX 3506
 WEST PALM BEACH FL 33401
 TELEPHONE:
 45TH STREET OFFICE : 561-494-1040
 45TH DIRECT: 561-494-1085
 FAX: 561-494-1117
 CITY HALL OFFICE: (561) 805-6723
 CITY HALL DIRECT: (561) 805-6327
 CITY HALL FAX: (561) 805-6731 OR 805-6676
 NEXTEL: 561-644-7301
 NEXTEL DIRECT CONNECT: 159*28165*38
 EMERGENCIES:
 CENTRAL OPERATIONS CENTER (DISPATCH) 561-822-2210
 E-MAIL:
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 8 Status F Date 2008-11-04 Cont ID  
Sent By mgonzale Date 2008-11-04 Time 14:32 Rev Time 1.00
Received By mgonzale Date 2008-11-04 Time 14:24 Sent To  
Notes
2008-11-04 14:27:24REMOVABLE BOLLARDS AND FIXED BOLLARDS MUST MEET CITY OF
 WPB STREETSCAPE STANDARD.
 REMOVABLE BOLLARDS AND FIXED BOLLARDS ARE IN CONFLICT
 WITH WM ON CLEMATIS (SHOW WATERMAIN ON PLANS.
  
 PLEASE SUBMIT PLANS TO ENGINEERING FOR ROW EVALUATION
 AND TO PERFORM A JURISDICTIONAL REVIEW. PLEASE CONTACT
 CITY OF WPB ENGINEERING DEPT.
 1000 45TH STREET SUITE 15.
 WPB, FL 33407
 (561) 494-1040
 ATTENTION: EMERY FABIAN
  
  

Review Stop ENG ENGINEERING CSD
Rev No 7 Status P Date 2008-03-14 Cont ID  
Sent By rchokshi Date 2008-03-14 Time 15:27 Rev Time 0.00
Received By rchokshi Date 2008-03-14 Time 15:26 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 6 Status P Date 2008-02-08 Cont ID  
Sent By jbramley Date 2008-02-08 Time 16:40 Rev Time 0.00
Received By jbramley Date 2008-02-08 Time 16:40 Sent To  
Notes
2008-02-08 16:42:14RE: REVIEW 5 PREVIOUSLY PERFORMED BY RASIK CHOKSHI,
 TOTAL VOLUME EXFILTRATION REMAINS THE SAME.CONSULTANT
 WILL SHOW SAME ON RE SUBMITTED PLANS.FINAL VOLUMES
 ARE UTIMALTY THE CONCERN OF THE SFWMD.THERE WILL BE
 NO RESUB FEE FOR THIS PERMIT REVIEW ITEM.PER JONATHAN
 BRAMLEY AND ROBERT BROWN.

Review Stop ENG ENGINEERING CSD
Rev No 5 Status F Date 2008-01-17 Cont ID  
Sent By rchokshi Date 2008-01-17 Time 09:17 Rev Time 0.00
Received By rchokshi Date 2008-01-17 Time 08:54 Sent To  
Notes
2008-01-17 09:12:58****FAILED****
  
 I TALKED TO PETER WAYNE AQUART OF CRAVEN THOMPSON &
 ASSOCIATES ON 1/17/08.
 HE SAID HE DID NOT CHANGE 10X8 EX-FILTRATION.HOWEVER,
 HE REDUCED THE LENGTH OF5X4 EX-FILTRATION FROM 180
 FEETTO 85 FEET.SO, HE REDUCE THE LENGTH BY 95 FEET
 FROM ORIGINAL LENGTH OF 180 FEET OF 5X4 EX-FILTRATION
 TRENCH.HE ALSO INCREASE THE ELEVATION OF WIER BY 6
 INCHES, SO WATER STAY IN THE GROUND PER PETER AQUART.
  
 MY CONCERNED IS 5X4 EX-FILTRATION TRENCHLENGTH IS
 REDUCED BY APPROXIMATELY 50%.IF IT IS LESS THAN 10 %
 IT ISO.K FOR ME. THEREFORE, ENGINEERING SERVICES &
 SFWMD NEED TO REREVIEW THAT IS WHAT I SUGGESTEDTO
 PETER AQUART.
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 4 Status N Date 2007-04-19 Cont ID  
Sent By rchokshi Date 2007-04-19 Time 11:20 Rev Time 0.00
Received By rchokshi Date 2007-04-19 Time 11:20 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2007-02-09 Cont ID  
Sent By rchokshi Date 2007-02-09 Time 08:43 Rev Time 0.00
Received By rchokshi Date 2007-02-09 Time 08:42 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2007-01-04 Cont ID  
Sent By rchokshi Date 2007-01-04 Time 16:04 Rev Time 0.00
Received By rchokshi Date 2007-01-04 Time 16:01 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2006-11-03 Cont ID  
Sent By rchokshi Date 2006-11-03 Time 13:47 Rev Time 0.00
Received By rchokshi Date 2006-11-03 Time 13:11 Sent To  
Notes
2006-11-03 13:46:55PLEASE PROVIDE FOLLOWING INF:
 1. CITY OF WPB STANDARD NOTES ON DRAWING FOR PARKING,
 HANDICAP PARIKG PAINTED PER CITY CODES ETC.,, MUST MEET
 PER ADA,,SIDEWALK WIDTH, ITS SLOPE,
 2. DUMPSTER LOCATION ON DWG, MUST BE ACCESSIBLE FOR
 PICKUP TRUCK.
 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FL BLDG CODE, PLEASE SHOW
 ON THE DRAWINGS.
 4. PLEASE PROVIDE A COPY OF SFWMD PERMIT
 5. PLEASE SHOW HOW DID YOU CALCULATE LENGTH OF
 EXFILTRATION TRENCH LENGTH,WHAT IS FACOR OF
 SAFETY?,WHAT CRITERIA YOU ASSUME , LIKE 1" OVER ENTIRE
 SITE OR 2.5"CRITERIA, WHICH CRITERIA YOU USED.
 PLEASE SHOW CALCULATIONS.
 6. WHAT IS THE SITE AREA, PERVIOUS AREA, IMPERVIOUS
 AREA, PLEASE SHOW RUNOFF CAL & CRITERIA YOU USED. 7.
 STORM WATER FROM CONTROL STRUCTURE GOES TOBANYAN
 BLVD, THERE IS ANOTHER CROSSING STORM WATER PIPE BEFORE
 YOU CONNECT TO THE STORM WATER PIPE., THERE ARE
 COUPLE OF STORM PIPIE RUNNING ON BANYAN NOT SHOW
 CLEARLY.PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR
 SITE SO, WE CAN DETERMINE THE BEST PIPE TO CONNECT WITH
 THE STORM WATER FROM ALL OTHER STORM WATER PIPES.
 PLEASE SHOW DETAIL OF THE CONTROL STRUCTURES WITH
 ELEVATIONS.
  
 RASIK CHOKSHI 805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 21 Status P Date 2009-09-22 Cont ID  
Sent By mawillia Date 2009-09-22 Time 14:16 Rev Time 0.00
Received By mawillia Date 2009-09-22 Time 11:40 Sent To  
Notes
2009-09-22 14:16:08*****REVISION #14F, APPROVED*****
  
 THE SUBMITTED MECHANICAL PLAN SHEET (M2-3.0) WAS
 REVIEWED, HOWEVER NO FIRE-STAMPING NECESSARY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 20 Status P Date 2009-04-03 Cont ID  
Sent By mcarsill Date 2009-04-03 Time 08:59 Rev Time 0.00
Received By mcarsill Date 2009-04-03 Time 08:58 Sent To  
Notes
2009-04-03 08:59:42REVISION 24A
  
 1. NO COMMENT BY THIS OFFICE.
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 19 Status P Date 2009-03-26 Cont ID  
Sent By mawillia Date 2009-03-26 Time 16:28 Rev Time 0.00
Received By mawillia Date 2009-03-26 Time 15:33 Sent To B
Notes
2009-03-26 16:28:29*****REVISION #25A, DATED 02/05/09, APPROVED*****
  
  
 REVISED PLAN SHEETS LS0.0, LS1-1.0 THRU LS1-6.1, AND
 A8-0.2 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 18 Status P Date 2009-01-21 Cont ID  
Sent By mcarsill Date 2009-01-21 Time 09:09 Rev Time 0.00
Received By mcarsill Date 2009-01-21 Time 09:04 Sent To  
Notes
2009-01-21 09:09:01REVISON 23A
 APPROVED PROVISO
  
  
 1. PROPER TENANT SEPARATION REQUIRED BETWEEN MUSEUM
 AREA TO BE BUILT UNDER SEPARATE PERMIT AND OTHER AREAS
 OF THE BUILDING.
  
 2. WHEN PHOT MUSEUM PLANS ARE SUBMITTED THEY ARE TO
 ILLUSTRATE ALL EMERGENCY SYSTEMS AND DEVICES. THESE
 SYSTEMS AND DEVICES INCLUDE FIRE SPRINKLERS, FIRE
 ALARM, ILLUMINATED EXIT SIGNS, EMERGENCY LIGHTS,
 PORTABLE FIRE EXTINGUISHERS AND INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 3. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE
 SPRINKLER OR FIRE ALARM SYSTEM REMODEL.
  
 4. ALL NEW FIRE DAMPERS AND ASSOCIATED EQUIPMENT SHALL
 BE DROP TESTED TO ENSURE PROPER OPERATION.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 17 Status P Date 2009-01-21 Cont ID  
Sent By mcarsill Date 2009-01-21 Time 07:36 Rev Time 0.00
Received By mcarsill Date 2009-01-21 Time 07:36 Sent To  
Notes
2009-01-21 07:39:29REVISION 20 B
  
 1. THE 500 GALLON DOUBLE WALLED DIESEL FUEL TANK
 ILLUSTRATED ON PAGE M1-1.3 IS TO BE PROPERLY LABELED.
 LABELS SHALL INCLUDE PRODUCT NAME, NO SMOKING,
 COMBUSTIBLE, AND NFPA 704 DIAMOND.
  
 2. THE INSTALLATION OF THE DIESEL FUEL TANK ON PAGE
 M1-1.3 SHALL COMPLY WITH NFPA 30, THE FLAMMABLE AND
 COMBUSTIBLE LIQUIDS CODE.
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 16 Status P Date 2008-12-01 Cont ID  
Sent By mcarsill Date 2008-12-01 Time 13:44 Rev Time 0.00
Received By mcarsill Date 2008-12-01 Time 13:42 Sent To  
Notes
2008-12-01 13:44:16CITY CENTER, 401 CLEMATIS STREET
 REVISION 21-A
  
 1. NO COMMENT PROVIDED BY THE FIRE RESCUE DEPARTMENT
 REGARDING THIS REVIEW.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 15 Status P Date 2008-11-05 Cont ID  
Sent By mcarsill Date 2008-11-05 Time 12:54 Rev Time 0.00
Received By mcarsill Date 2008-11-05 Time 12:52 Sent To  
Notes
2008-11-05 12:54:231. SUBJECT TO FIELD INSPECTION AND APPROVAL.
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4724 PHONE
 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 14 Status P Date 2008-05-05 Cont ID  
Sent By mcarsill Date 2008-05-05 Time 09:07 Rev Time 0.00
Received By mcarsill Date 2008-05-05 Time 09:06 Sent To  
Notes
2008-05-05 09:06:551. SUBJECT TO FIELD INSPECTION AND APPROVAL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 13 Status F Date 2008-04-09 Cont ID  
Sent By mcarsill Date 2008-04-09 Time 16:52 Rev Time 0.00
Received By mcarsill Date 2008-04-09 Time 16:52 Sent To  
Notes
2008-04-09 17:06:18REVISION 15A
  
 1. THE ELECTRICAL PLAN REVIEWER INDICATES SEVERAL
 PROBLEMS WITH REVISION 15A. THESE PROBLEMS NEED TO BE
 DISCUSSED AND CORRECTED ON THE NEXT REVISION TO ENSURE
 THAT THE REVISIONS DISPLAYED ON 15A CAN BE APPROVED.
  
 2. THE ENTIRE BUILDING SHALL HAVE SUFFICIENT EMERGENCY
 LIGHTING EQUIPMENT AND ILLUMINATED EXIT SIGNS SO AS TO
 DIRECT PERSONS TO THE EXITS. ALL EQUIPMENT INSTALLED AS
 EMERGENCY LIGHTING AND EXIT SIGNS SHALL BE INSTALLED IN
 ACCORDANCE WITH NFPA 70, THE NATIONAL ELECTRIC CODE AND
 NFPA 101 THE LIFE SAFETY CODE, CHAPTER 7.
  
 3. PLEASE CORRECT ANY CIRCUITING PROBLEMS SUCH AS
 MISSING OR ABSENT CIRCUITRY.
  
 4. PLEASE REVIEW REVISION 15A AND MAKE ANY NECESSARY
 CORRECTIONS. COORDINATION OF FIRXTURES AND CIRCUITRY IS
 NECESSARY AS THE PROJECT CONTINUES TO MOVE FORWARD.
  
 5. ALL EXIT SIGNS AND EMERGENCY LIGHTING EQUIPMENT WILL
 BE TESTED ON NORMAL AND BACK-UP POWER WHEN THE BUILDING
 IS NEARER TO COMPLETION.
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 12 Status P Date 2008-02-19 Cont ID  
Sent By mcarsill Date 2008-02-19 Time 14:58 Rev Time 0.00
Received By mcarsill Date 2008-02-19 Time 14:53 Sent To  
Notes
2008-02-19 14:58:151. THE WORDING ON NOTE # 26 ON DRAWING FAO-1 HAS BEEN
 REVISED WITH THE CORRECT LANGUAGE. THE WORD DISPLAY HAS
 BEEN SUBSTITUTUED WITH THE WORD TRANSMIT.
  
 2. NO OTHER DRAWINGS PROVIDED EXCEPT FA0-1.
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 11 Status P Date 2007-12-24 Cont ID  
Sent By mcarsill Date 2007-12-24 Time 12:23 Rev Time 0.00
Received By mcarsill Date 2007-12-24 Time 12:06 Sent To  
Notes
2007-12-24 12:20:541. THE WORDING ON THE REVISED NOTE # 26 IS INCORRECT.
 THE WORD DISPLAY SHOULD READ TRANSMIT. FOUR DISTINCT
 SIGNALS WATERFLOW, GENERAL ALARM, TROUBLE AND
 SUPERVISORY SHALL BE TRANSMITTED TO THE CENTRAL STATION
 APPROVED FOR CENTRAL STATION SERVICE.
  
 2. THE REVISED DRAWINGS THAT REFLECT A COMPLETE SMOKE
 DETECTION SYSTEM FOR THE BUILDING SHALL BE SUBMITTED TO
 THE CONSTRUCTION SERVICES DEPARTMENT AS A SEPARATE
 ENTITY AS SHOP DRAWINGS. THESE SHOP DRAWINGS SHALL
 PROVIDE PRODUCT INFORMATION CUT SHEETS, BATTERY
 CALCUALTIONS, RISER DIAGRAMS AND FLOORS PLANS
 ILLUSTRATING DEVICE PLACEMENT FOR THE ENTIRE FIRE ALARM
 SYSTEM.
  
 3. THERE APPEARS TO BE SOME CONFUSION WITH REGARDS TO
 THE FIRE RATING REQUIRED FOR THE FIRE COMMAND ROOM. THE
 FIRE COMMAND ROOM IS REQUIRED TO BE SEPARATED FROM
 OTHER AREAS OF THE BUILDING BY AT LEAST ONE HOUR FIRE
 RATED CONSTRUCTION. SOME DOCUMENTATION PROVIDED WITH
 DRAWINGS INDICATES THAT NO FIRE DAMPER IS NEEDED FOR
 THE ROOM SINCE IT IS NOT FIRE RATED. THIS IS INCORRECT.
 NFPA 1, SECTION 11.9.2 REQUIRES THAT "THE EMERGENCY
 COMMAND CENTER SHALL BE SEPARATED FROM THE REMAINDER OF
 THE BUILDING BY A FIRE BARRIER HAVING A FIRE RESISTANCE
 RATING OF NOT LESS THAN 1 HOUR".
  
 APPROVED PROVISIO:
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREA OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 10 Status F Date 2007-10-23 Cont ID  
Sent By mcarsill Date 2007-10-23 Time 12:31 Rev Time 0.00
Received By mcarsill Date 2007-10-23 Time 12:06 Sent To  
Notes
2007-10-23 12:31:091. SOME SUGGESTED IMPROVED WORDING IS PROVIDED FOR NOTE
 # 26 ON PAGE FAO.1. "THE FIRE ALARM SYSTEM SHALL BE
 ABLE TO TRANSMIT THE FOLLOWING ALARMS TO THE UL LISTED
 CENTRAL STATION APPROVED FOR CENTRAL STATION SERVICE.
  
 A) WATERFLOW
 B) GENERAL ALARM
 C) SUPERVISORY SIGNAL
 D) TROUBLE SIGNAL
  
 2. ANY SPECIAL LOCKING ARRANGEMENTS ON EXIT DOORS SHALL
 COMPLY WITH WITH CHAPTER 7 OF THE LIFE SAFETY CODE,
 101.
  
 3. THE PLANS SEEM TO SUGGEST "PROVIDE AND INSTALL SMOKE
 DETECTORS PER FLORIDA MECHANICAL CODE (FMC) 607.5.4.1
 AT EACH SMOKE DAMPER. SINCE NO FIRE ALARM SYSTEM SHOP
 DRAWINGS HAVE BEEN SUBMITTED IT IS UNKNOWN IF A
 COMPLETE SMOKE DETECTION SYSTEM IS TO BE INSTALLED
 WITHIN THE BUILDING. IN FMC 607.3.2.1 PROVIDES
 INFORMATION ON HOW SMOKE DAMPER ACTUATION METHODS CAN
 BE PERFORMED USING 1-5. PLEASE ADVISE THE MECHANICAL
 SECTION OF THE CONSTRUCTION SERVICES DEPARTMENT AND
 THIS OFFICE IF A COMPLETE SMOKE DETECTION SYSTEM IS
 PLANNED FOR THE BUILDING AND IT THIS SYSTEM IS PLANNED
 TO ACTUATE THE SMOKE DAMPERS. PLEASE COORDINATE ALL
 FIRE/ SMOKE DAMPERS AND FIRE DAMPERS WITH THE
 MECHANICAL DIVISION OF THE CONSTRUCTION SERVICES
 DEPARTMENT.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 804-4709 PHONE
 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 9 Status F Date 2007-09-04 Cont ID  
Sent By mcarsill Date 2007-09-04 Time 11:22 Rev Time 0.00
Received By mcarsill Date 2007-09-04 Time 10:51 Sent To  
Notes
2007-09-04 11:21:591. STREET LIGHTS INSTALLATIONS ON PAGE LL.1 SHALL NOT
 INTERFERE WITH ANY FIRE SAFETY EQUIPMENT OR DEVICES.
  
 2. SOME REVISION CLOUDS ON PAGE A0.3 ARE EMPTY OF
 DETAILS OR DIAGRAMS.
  
 3. ENSURE THAT BOLLARD THAT IS PLACED AT GROUND LEVEL
 OUTSIDE STAIR # 4 DOES NOT INTERFERE WITH OPENING OF
 THE DOOR OR ANY EXIT DISCHARGE.
  
 4. HORIZONTAL LINES APPEAR TO TRAVEL THROUGH STAIR # 9
 ON PAGE E1-1.2. PLEASE PROVIDE DETAILS.
  
 5. CHAIN LINK FENCE AND PARKING DISPLAYED ON PAGE
 E1-6.3 SHALL NOT INTERFERE WITH ANY EXIT ACCESS,
 EXITING FROM THE UPPER LEVEL OF THE PARKING GARAGE.
  
 6. ELEVATOR LOBBY WARNING SIGNS "IN CASE OF FIRE, DO
 NOT USE THE ELEVATORS" MUST BE CONSIDERED ALONG WITH
 THE REVISIONS TO THESE AREAS.
  
 7. ALL STAIRS IDENTIFIED WITH REVISION CLOUDS ON A7.1.4
 AND A7.16 SHALL COMPLY WITH THE MINIMUM BUILDING AND
 FIRE CODE REQUIREMENTS.
  
 8. AS EXPRESSED PREVIOUSLY ALL CONSTRUCTION AND SYSTEMS
 AND DEVICES ARE SUBJECT TO FIELD INSPECTION.
  
 9. PLEASE BE ADVISED THAT REVISONS TO THE SOME FEATURES
 OF THE BUILDING MAY HAVE A NEGATIVE IMPACT ON FIRE
 SPRINKLER, ELECTRICAL, MECHANICAL, AND PLUMBING
 SYSTEMS. REVISIONS WILLBE NECESSARY FOR OTHER SHOP
 DRAWINGS IF NECESSARY.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status P Date 2007-08-01 Cont ID  
Sent By mcarsill Date 2007-08-01 Time 13:22 Rev Time 0.00
Received By mcarsill Date 2007-08-01 Time 13:03 Sent To  
Notes
2007-08-01 13:22:221. THE CARBON MONOXIDE SENSORS DISPLAYED ON THE
 MEHANICAL SHEETS ARE TO BE INSTALLED PER MANUFACTURER'S
 REQUIREMENTS. WHAT SET POINTS ARE THE CARBON MONOXIDE
 DETECTORS GOING TO BE SET AT. THESE DEVICES WILL NEED
 TO BE TESTED WITH CALIBRATION GAS AFTER INSTALLATION.
 PLEASE PROVIDE PRODUCT APPROVALS AND CUT SHEETS FOR
 THESE DEVICES. PLEASE PROVIDE DETAILS ON CARBON
 MONOXIDE SYSTEM. THE INSTALLATION LOCATIONS FOR THESE
 DEVICES SHALL NOT EXCEED MAXIMUM COVERAGE AREAS OR
 SPACING REQURIEMENTS.
  
 2. ALL ELECTRICAL REVISIONS TO COMPLY WITH NFPA 70, THE
 NATIONAL ELECTRICAL CODE.
  
 3. THE INSTALLATION OF THE CHAIN LINK FENCE FOR THE
 FUTURE GENERATOR AND ANY PARKING SPACES SHALL NOT
 INTERFERE WITH ANY EXIT ACCESS TO STAIR # 4.
  
 4. THE OPERATION OF EMERGENCY LIGHTING EQUIPMENT EVEN
 IF THEY ARE EQUIPPED WITH OCCUPANCY SENSORS SHALL
 COMPLY WITH THE OPERATIONAL REQUIREMENTS OF CHAPTER
 SEVEN OF THE LIFE SAFETY CODE.
  
 5. NO EMERGENCY PHOTOMETRICS DISPLAYED IN FIRE COMMAND
 CENTER ON PAGE E-8-1.1.
  
 6. PLEASE BE ADVISED THAT LARGE BATHROOMS MUST BE
 EQUIPPED WITH EMERGENCY LIGHTING. LARGE RESTROOMS CAN
 BE EXTREMELY DARK WHEREBY ACCESS TO THE INGRESS/EGRESS
 DOOR FROM THE ROOM CAN BE IMPOSSIBLE.
  
  
 APPROVED PROVISO
  
 MIKE CARSILLO, BATTALION CHIEF
 804-4709 PHONE
 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2007-06-26 Cont ID  
Sent By mawillia Date 2007-06-26 Time 15:52 Rev Time 0.00
Received By mawillia Date 2007-06-26 Time 15:46 Sent To  
Notes
2007-06-26 15:52:11*****REVISION OF 05/08/07 APPROVED*****
  
  
 REVISED FIRE ALARM AND FIRE SPRINKLER STAMPED,
 INITIALED, AND DATED 5/31/07 AS PER ROBERT BROWN.

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2007-04-11 Cont ID  
Sent By mcarsill Date 2007-04-11 Time 09:39 Rev Time 0.00
Received By mcarsill Date 2007-08-01 Time 13:01 Sent To  
Notes
2007-04-11 09:38:081. ON PAGE E5-1.1 GA PLANS MAKE REFERENCE TO A FIVE
 HUNDRED GALLON, DOUBLE WALL SUB-BASE FUEL TANK. PLEASE
 INDICATE WHAT UL LISTING CAN BE EXPECTED FOR THIS FUEL
 TANK. PLEASE PROVIDE PRODUCT APPROVALS AND INFORMATION
 TO THIS OFFICE REGARDING THIS FUEL TANK.
  
 2. CO SENSORS ARE ILLUSTRATED ON THE DRAWINGS. PLEASE
 PROVIDE DETAILS ON THESE DEVICES. THESE DEVICES ARE TO
 BE UL LISTED AND PLEASE INDICATE IF THESE DEVICES WILL
 BE FACTORY OR FIELD SET. MOUNTING HEIGHTS, AREA OF
 COVERAGE, AND TESTING PROCEDURES SHALL BE DOCUMENTED TO
 THIS OFFICE. WHAT POWERS THESE DEVICES AND ARE THEY
 EQUIPPED WITH PROVISIONS SHOULD LOSS OF POWER OCCURS.
 IF BATTERY POWER EXISTS, HOW LONG CAN THEY BE EXPECTED
 TO OPERATE. ALSO PLEASE INDICATE WHAT SET POINTS THESE
 DETECTORS WILL BE SET AT. WHAT PARTS PER MILLION WILL
 ACTIVATE THESE SENSORS.
  
 3. A VISUAL REPRESENTATION OF THE FIREFIGHTERS SMOKE
 CONTROL PANEL NEEDS TO BE ILLUSTRATED AT TIME OF SHOP
 DRAWING SUBMITTAL. THE SMOKE CONTROL PANEL SHALL
 DISPLAY A GRAPHIC REPRESENTATION OF THE BUILDING AND
 THE SYSTEM TO INCLUDE HAND, ON, AND AUTO CONTROLS.
  
 4. PLEASE PROVIDE THIS OFFICE IN WRITING WHEN THE
 TEMPORARY STANDPIPE SYSTEM WILL BE INSTALLED AT THE
 PARKING GARAGE AND THE FUTURE BUILDING. CERTAIN CODE
 REQUIREMENTS MANDATE THIER INSTALLATION WHEN THEY REACH
 CERTAIN HEIGHT OR FLOOR ARRANGEMENTS.
  
  
 MIKE CARSILLO, BATTALION CHIEF OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-03-01 Cont ID  
Sent By mawillia Date 2007-03-01 Time 12:46 Rev Time 0.00
Received By mawillia Date 2007-03-01 Time 12:46 Sent To B
Notes
2007-03-01 12:53:38*****APPROVED*****
  
  
 REVISIONS (02/19/07) TO PLAN SHEETS A1-1.0, LS1.0.
 LS1.GA.1, LS1.GA.2, AND LS1.GA.3 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-02-21 Cont ID  
Sent By mawillia Date 2007-02-21 Time 16:21 Rev Time 0.00
Received By mawillia Date 2007-02-21 Time 16:21 Sent To  
Notes
2007-02-21 16:24:12*****APPROVED*****
  
  
 LIFE SAFETY, FIRE ALARM, AND FIRE SPRINKLER SHEETS WERE
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-01-26 Cont ID  
Sent By mcarsill Date 2007-01-26 Time 13:17 Rev Time 0.00
Received By mcarsill Date 2007-01-26 Time 13:17 Sent To  
Notes
2007-01-26 13:36:281. SIAMESE CONNECTION DISPLAYED ON PAGE FP1-1.2 IS NOT
 NEEDED AND SHOULD BE STRICKEN FROM THE PLANS. THE PLAN
 REVIEW PERMIT RESPONSES INCLUDE NOW THREE SIAMSE
 CONNECTIONS INSTEAD OF THE FIVE PREVIOUSLY SHOWN. 2. NO
 FIRE ALARM EQUIPMENT SHOWN IN MACHINE ROOM A6.102 ON
 PAGE FA1-6.0. THIS IS AN EXISTING COMMENT.
 3. ONLY TWO FIRE ALARM STROBES ARE PRESENT IN THE
 GARAGE ON PAGE FA1-6.0. THIS IS ALSO AN EXISTING
 COMMENT.
 4. SMOKE DETECTOR STILL MISISNG IN VOICE DATA CLOSET
 C3.104 ON PAGE FA1-3.0. THIS IS AN EXISTING COMMENT. 5.
 A VISUAL REPRESENTATION OF THE SMOKE CONTROL PANEL
 SHALL BE SUBMITTED AT TIME OF SHOP DRAWING SUBMITTAL.
 THIS SMOKE CONTROL PANEL SHALL DISPLAY A GRAPHIC
 REPRESENTATION OF THE BUILDING SYSTEM TO INCLUDE HAND,
 ON, AND AUTO CONTROLS.
 6. ITEMS # 9, 11, 12, 20, 23, COULD NOT BE CLEARED FRON
 LIST. SOME ITEMS CAN BE PICKED UP AT SHOP DRAWING
 SUBMITAL TIME SO LONG AS THEY ARE PROPERLY IDENTIFIED.
 7. ALL ELECTRICAL PLAN REVIEW COMMENTS ARE TO BE
 PROPERLY SATISFIED WITH THE ELECTRICAL PLAN REVIEWER.
 8. PLEASE REMEMBER THAT THE ELVATION OF FLOOR LEVELS ON
 BOTH SIDES OF AN EXIT DOOR CANNOT EXCEED 1/2 ".
  
 PLANS WILL BE APPROVED PROVISO AND ALL WORK AT THE SITE
 IS SUBJECT TO FIELD INSPECTION AND APPROVAL. THIS
 APPROVAL DOES NOT RELLIEVE RESPONSIBLE PERSONS OR FIRMS
 FROM OBTAINING ANY OTHER GOVERNMENTAL REVIEWS OR
 APPROVALS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-12-22 Cont ID  
Sent By mcarsill Date 2006-12-22 Time 11:22 Rev Time 0.00
Received By mcarsill Date 2006-12-22 Time 08:45 Sent To  
Notes
2006-12-22 11:22:461. ON PAGE C-16 AT LEAST FIVE FIRE DEPARTMENT
 CONNECTIONS ARE SHOWN. AS STATED PREVIOUSLY, THAT MANY
 FIRE DEPARTMENT CONNECTIONS ARE NOT NEEDED.
 2. SEVERAL AREAS ON PAGE FP1-1.1 ARE ABSENT OF FIRE
 SPRINKLER PROTECTION.
 3. SEVERAL AREAS ON PAGE FP1-1.2 ARE ABSENT OF FIRE
 SPRINKLER PROTECTION.
 4. STAIR # 2 ON PAGE FP1-2.1 IS MISSING THE FIRE
 VALVE.
 5. FIRE SPRINKLER HEADS MISSING IN VOICE DATA A2.105
 AND UTILITY ROOM A2105.1 ON PAGE FP1-2.1.
 6. CLOSETS A3.110.1 AND A3.118.1 ARE ABSENT OF FIRE
 SPRINKLER HEADS ON PAGE FP1-3.1.
 7. SERVER ROOM A4.416 SHOWN ON PAGE FP1-4.1 IS EQUIPPED
 WITH AN FM 200 SYSTEM. THIS ROOM IS LOCATED IN A
 SPRINKLERED BUILDING AND SHALL CONTAIN FIRE SPRINKLER
 PROTECTION SERVED BY A SEPARATE VALVE PER THE
 REQUIREMENTS OF NFPA 75, THE STANDARD FOR THE
 PROTECTION OF INFORMATION TECHNOLOGY EQUIPMENT. SECTION
 8-1.1 AND 8.1.3 PROVIDES GUIDANCE ON THESE
 REQUIREMENTS.
 8. FIRE SPRINKLER HEADS NOT SHOWN IN CAFE C1.401 ON
 PAGE FP1-1.0.
 9. EXIT DOOR NEAR VOICE DATA C4.108 SWINGS IN THE WRONG
 DIRECTION ON PAGE ID2-4.2.
 10. "NO EXIT" SIGNS SHALL BE INSTALLED ON THE DOUBLE
 DOORS TO SERVER ROOM NEAR STAIR # ON PAGE LS1-4.1.
 THESE DOORS ARE IN CLOSE PROXIMITY TO THE EXIT DOOR.
 11. ONLY TWO FIRE ALARM STROBES EXIST IN THE PARKING
 AREA SHOWN ON PAGE FA1-6.
 12. NO FIRE ALARM DEVICES EXIT IN MACHINE ROOM A6.102
 ON PAGE FA1-6. PLEASE EXPLAIN.
 13. MANUAL PULL STATION LOCATED IN VOICE DATA CLOSET
 C4.108 ON PAGE FA1-4.0. THE MANUAL PULL STATION SHOULD
 BE LOCATED NEXT TO STAIR.
 14. VOICE DATA C3.104 ON PAGE FA1-3 IS MISSING SMOKE
 DETECTOR LIKE OTHER SIMILAR SPACES. PLEASE ADVISE.
 15. MANUAL PULL STATION MISSING FROM STAIR # 2 ON PAGE
 FA1-2.
 16. NO SMOKE DETECTOR PRESENT IN VOICE DATA C1.102 BUT
 EXIST IN SIMILAR SPACES ON PAGE FA1-1.
 17. NO EXIT SIGNS APPEAR TO EXIST IN PROGRAM MEETING
 ROOM C3.306 WHICH CONTAINS FIFTY SEATS ON PAGE E2-3.2.
 18. AN EXIT SIGN IN THE PROGRAM/MEETING ROOM ON PAGE
 E2-3.2 IS CONFUSING. IF THE SIGN IS LOCATED INSIDE THE
 ROOM, THE EXIT SIGN IS SWINGING IN THE WRONG DIRECTION.
 IF THE SIGN IS OUTSIDE THE ROOM OTHER EXIT SIGNS ARE
 VAILABLE TO DIRECT PERSONS. PLEASE ADVISE.
 19. THE EXIT SIGN FROM PLANNING INTO THE ENTRY/WAITING
 AREA STILL APPEARS CONFUSING. ONCE IN THE ENTRY/WAITING
 AREA WHAT IS THE PREFERRED EXIT TRAVEL DIRECTION
 ANTICIPATED ON PAGE E2-2.1. PLEASE PROVIDE MORE
 DETAILS.
 20. EXIT SIGNS STILL APPEAR TO BE MISSING FROM BACK OF
 HOUSE OF THE COMMISSION CHAMBERS ON PAGE E2-2.1.
 21. NO ILLUMINATED EXIT SIGNS DISPLAYED IN LARGE
 MECHANICAL ROOM DISPLAYED ON PAGE ON PAGE E1-1.3
 22. SOME ISSUES REMAIN WITH THE LIFE SAFETY SHEETS AND
 THE ARCHITECTURAL DRAWINGS AS THEY RELATE TO WALL
 RATINGS. PLEASE ENSURE THAT THEY MIRROR ONE ANOTHER.
 23. COULD NOT LOCATE FLOOR LEVEL INFORMATION AS IT
 RELATES TO EXIT DOORS. PLEASE SEE NFPA 101, THE LIFE
 SAFETY CODE, SECTION 7.2.1.3.
 24. COULD NOT LOCATE A VISUAL ON THE FIREFIGHTERS SMOKE
 CONTROL PANEL ONLY A DESCRIPTION OF WHAT IT WILL LOOK
 LIKE.
 25. THE TEMPORARY STANDPIPE SYSTEM REQUIREMENT COULD
 NOT BE LOCATED ON THE LIFE SAFETY OR FIRE SPRINKLER
 SYSTEM DRAWINGS.
 26. ALL BUILDING, MECHANICAL, ELECTRICAL, PLUMBING
 COMMENTS ARE TO BE SATISFIED.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION OFFICER
 804-4709 PHONE
 804-4774 FAX
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-27 Cont ID  
Sent By mcarsill Date 2006-10-27 Time 11:07 Rev Time 0.00
Received By mcarsill Date 2006-10-27 Time 09:19 Sent To  
Notes
2006-10-27 11:07:291. STAIR SUMMARY CHART NEEDED ON PAGE LS0.0. THIS CHART
 SHALL IDENTIFY ALL STAIRS, WIDTHS, AND EXIT
 CAPACITIES.
 2. STAIRWELL IDENTIFICATION SIGNS SHALL BE PROVIDED ON
 THE SIGNAGE LEGEND DISPLAYED ON PAGE LS0.0. THESE
 STAIRWELL IDENTIFICATION SIGNS SHALL IDENTIFY THE
 STAIR, TERMINUS, TOP AND BOTTOM, FLOOR NUMBER, ETC.
 3. STAIR # 5 ON PAGE LS1-1.0 HAS STILL NOT BEEN
 CORRECTED. PLEASE MOVE OR REMOVE WALL SECTION DIRECTLY
 IN FRONT OF EXIT STAIR DOOR TO ALLOW FOR PROPER EXIT
 DISCHARGE.
 4. EXIT SIGNS APPEAR TO BE MISSING FROM SHEET LS1-1.1.
 PLEASE SEE BACK OF HOUSE AREA IN COMMISSION CHAMBERS.
 OTHER AREAS ALSO ABSENT OF SIGNS. CONFLICTS APPEAR TO
 EXIST BETWEEN LS1-1.1 AND E2-1.1.
 5. EXIT SIGN NOTED DIRECTLY INFRONT OF ELECTRICAL ROOM
 DOOR ON PAGE E2-1.2.
 6. EXIT SIGN IN CENTER OF STAIR # 9 ON PAGE E2-1.2.
 7. EXIT SIGN WITH DIRECTIONAL ARROWS DIRECTS PERSONS TO
 GRAND STAIR ON PAGE E2-2.1.
 8. EXIT SIGN MISSING IN FRONT OF STAIR DOOR # 7 ON PAGE
 E2-2.2.
 9. EXIT SIGN CONTAINED WITHIN STAIR # 9 NOT INFRONT OF
 STAIR DOOR ON PAGE E2-2.2.
 10. EXIT SIGN CONTAINED WITHIN STAIR # 9 NOT INFRONT OF
 STAIR DOOR ON PAGE E2-3.2.
 11. EXIT SIGN INSTALLED NEAR WALL OF STAIR # 9 NOT NEAR
 DOUBLE DOORS ON PAGE E2-3.2.
 12. NO EXIT MARKINGS COULD NOT BE LOCATED ON PAGES
 E2-4.0 AND E2-4.1.
 13. EXIT SIGN MARKINGS MISSING FROM PAGE E2-4.2.
 14. SAME CONDITION EXISTS ON PAGE E2-5.1.
 15. PLEASE EXPLAIN FACP CALL OUT IN VOICE DATA ROOM ON
 PAGE E3-1.0.
 16. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 INSTALLATION OF THE FIRE ALARM SYSTEM. FIRE ALARM
 SYSTEM SHALL BE UL LISTED FOR CENTRAL STATION SERVICE.
 PLEASE EXPLAIN "PROVIDE ZONED EMERGENCY VOICE
 EVACUATION"ON PAGE FA1-1. SYSTEM TO COMPLY WITH NFPA
 72, THE NATIONAL FIRE ALARM CODE, 2002 EDITION.
 17. EXIT SIGN MISSING NEAR STAIR # 2 ON PAGE E1-6.1.
 18. TRAINING ROOM AT A 4 AND 5 MISSING FIRE ALARM
 NOTIFICATION APPLIANCES ON PAGE FA1-4.
 19. PLEASE EXPLAIN NOTE # 3 FIRE PROTECTION DESIGN
 CRITERIA INFORMATION BOX ON PAGE FP0-1.0.
 20. ON PAGE FP1-1.0 AT LEAST FIVE FIRE DEPARTMENT
 CONNECTIONS ARE SHOWN. AGAIN ALL OF THESE ARE NOT
 NECESSARY.
 21. SOME FIRE SPRINKLER DRAWINGS ARE ABSENT OF FIRE
 SPRINKLER HEADS. IT IS DIFFICULT TO DETERMINE IF 100 %
 COVERAGE IS PROVIDED DUE TO INSUFFICIENT INFORMATION.
 22. ON PAGE FP1-2.1 KEY NOTE # 5 "PROVIDE WATER CURTAIN
 FOR GLASS AREAS LOCATE SPRINKLERS 6'-0 ON CENTER".
 PLEASE ILLUSTRATE WATER CURTAIN ARRANGEMENT.
 23. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FM 200
 FIRE SUPPRESSION SYSTEM PLANNED FOR THE SERVER ROOM ON
 PAGE FP1-4.0.
 24. DOUBLE DETECTOR CHECK VALVE ASSEMBLY DETAIL SHOWN
 ON PAGE FP2-1.0 DOES NOT INDICATE TAMPER SWITCHES,
 CHAIN AND LOCK.
 25. FLOOR CONTROL VALVE ASSEMBLY DETAIL SHOWN ON PAGE
 FP3-1.0 SHALL BE EQUIPPED WITH 2 1/2 TO 1 1/2
 REDUCERS.
 26. PLEASE DISPLAY HEIGHT DIMENSIONS FROM ROOF TO
 EXHAUST FAN ON PAGE M502.0.
 27. COULD NOT LOCATE WHAT THE FIREFIGHTERS SMOKE
 CONTROL PANEL FOR THE ATRIUM SYSTEM LOOKS LIKE WITH THE
 MECHANICAL DRAWINGS.
 28. ALSO COULD NOT LOCATE A SEQUENCE OF OPERATIONS
 MATRIX FOR THE ATRIUM MECHANICAL SYSTEM IN THE
 MECHANICAL DRAWINGS.
 29. NO EXIT SIGN NOTED AT THE BACK LOADING DOCK DOUBLE
 DOORS ON PAGE LS1-1.2.
 30. ALL MECHANICAL, ELECTRICAL, AND STORAGE ROOM DOORS
 ARE TO BE SMOKE RESISTANT. PLEASE ESNURE THAT THE PLANS
 ARE REVISED TO REFLECT THIS CHANGE.
 31. OCCUPANT LOAD TAG FOR GROUP B BUSINESS ON PAGE
 LS1-2.0 SHOULD READ 25 OCCUPANTS INSTEAD OF 40
 OCCUPANTS.
 32. PROGRAM MEETING ROOM ON PAGE LS1-3.2 THAT CONTAINS
 50 SEATS DOES NOT CONTAIN ANY EXIT SIGNS.
 33. OCCUPANT LOAD TAG FOR GROUP B BUSINESS OCCUPANCY ON
 PAGE LS1-4.0 SHOULD READ 270 PERSONS NOT 278
 OCCUPANTS.
 34. ILLUMINATED EXIT SIGN IN SERVER ROOM LOCATED ON
 PAGE LS1-4.1 IS NOT LOCATED INFRONT OF ANY EXIT DOOR.
 35. EXIT SEPARATION LINE IN TRAINING ROOM ON PAGE
 LS1-4.1 IS DRAWN TO A DOOR ABSENT OF AN EXIT SIGN.
 36. A FIRE EXTINGUISHER CABINET IS LOCATED ON PAGE
 LS1-4.1 NEAR MEN'S ROOM BUT DOES NOT APPEAR TO BE
 AFFIXED TO ANYTHING.
 37. IT APPEAR THAT A FIRE EXTINGUISHER CABINET IS
 MOUNTED ON A DOOR TO THE SERVER ROOM ON PAGE LS1-4.1.
 38. EXIT SIGN ON PAGE LS1.6.1 IS NOT LOCATED NEAR STAIR
 DOOR.
 39. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR ALL HANDRAILS, GUARDRAILS, TEMPERED GLASS WALLS
 CABLE RAILINGS, AND PRE-ENGINEERED RAILINGS.
 40. ON PAGE ID2-4.2 A SOLID WALL EXISTS WHERE A DOOR
 EXISTS FOR THE STAIRWELL.
 41. SEVERAL BUILDING ADDRESSES NOTED ON TWO DIFFFERENT
 ELEVATIONS ON PAGE A4-1.0. THE ADDRESSES SHALL ONLY BE
 LISTED ON THE PROPER ELEVATION.
 42.ALL PROPOSED WORK STATIONS IN OPEN WORK AREAS
 SHALL PROVIDE FOR A MINIMUM OF AT LEAST 44" INCHES.
 43. ALL FIRE DAMPERS WILL BE REQUIRED TO BE DROP TESTED
 AFTER INSTALLATION TO ENSURE PROPER OPERATION.
 44. CHAIRS LOCATED IN ENTRY/WAITING A2.009 MAY
 INTERFERE WITH DOORS ON PAGE ID2-2.0.
 45. PLEASE EXPLAIN EXIT ACCESS FOR MEETING ROOM ON PAGE
 ID2-3.2 ESPECIALLY NEAR THE FOUR COLUMNS.
 46. PLEASE PROVIDE A STAIR SECTION FOR THE PROPOSED
 ALTERNATING TREAD STAIRS SHOWN ON THE DRAWINGS.
 47. PLEASE DISPLAY THE REQUIRED 1/2 MAXIMUM AT ALL EXIT
 DOOR LOCATIONS.
 48. THE SERVER ROOM SHALL COMPLY WITH NFPA 75, THE
 STANDARD FOR THE PROTECTION OF INFORMATION TECHNOLOGY
 EQUIPMENT.
 49. SOME OF THE ITEMS IDENTIFIED AT THE PREVIOUS
 REVIEWS STILL SEEM TO EXIST AT THIS PERMIT REVIEW.
 PLEASE REVIEW ALL PREVIOUS COMMENTS PROVIDED BY CITY
 STAFF AND ESNURE THAT PREVIOUS ITEMS IDENTIFIED HAVE
 BEEN CORRECTED AND PROPERLY COORDINATED ON THE
 APPROPRIATE SHEETS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION OFFICER
 804-4709 PHONE
 804-4774 FAX

Review Stop G GAS REVIEW
Rev No 6 Status P Date 2007-04-09 Cont ID  
Sent By kstevens Date 2007-04-09 Time 14:47 Rev Time 0.00
Received By kstevens Date 2007-04-09 Time 14:46 Sent To  
Notes
2007-04-09 14:50:50REVISION OK - SHT P3-3.0

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2007-04-09 Cont ID  
Sent By kstevens Date 2007-04-09 Time 12:51 Rev Time 0.00
Received By kstevens Date 2007-04-09 Time 12:51 Sent To  
Notes
2007-04-09 12:53:06GAS REVISION OK-SHT P3-4.0 GAS RISER DIAGRAM.

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2007-02-17 Cont ID  
Sent By kstevens Date 2007-02-17 Time 17:10 Rev Time 0.00
Received By kstevens Date 2007-02-17 Time 17:10 Sent To  
Notes
2007-02-17 17:14:28PASSED/PROVISO
  
 GAS RISER DIAGRAM SHOWS 128' FROM GENERATOR TO LAST
 FUTURE GENERATOR. THIS SCALES OUT TO ABOUT 30' ON THE
 PLANS. THE PIPING SHALL BE SIZED FOR 200' MAXIMUM. A
 REVISION WILL BE REQUIRED SHOWING THE CORRECT DISTANCE
 FROM THE FIRST GENERATOR TO THE LAST.--THE MANUF.
 SPECIFICATIONS SHALL BE REQUIRED SHOWING THE MAXIMUM
 BTU LOAD AT 100% CAPACITY WHEN APPLYING FOR THE
 REQUIRED GAS PERMIT.

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2007-01-31 Cont ID  
Sent By kstevens Date 2007-01-31 Time 06:36 Rev Time 0.00
Received By kstevens Date 2007-01-31 Time 06:36 Sent To  
Notes
2007-01-31 11:04:09DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 FROM PREVIOUS REVIEWS:
  
 39B. SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE GAS PERMIT:
  
 A. OK
 B. OK
 C. OK
 D. OK
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED, BUT NOT ADDRESSED. ******RESPONSE
 NOTED, BUT THE SIZING OF THE PIPE SHALL BE TO THE MOST
 REMOTE APPLIANCE/GENERATOR. PLEASE INDICATE THE TOTAL
 DEVELOPED LENGTH TO THE MOST REMOTE FUTURE GENERATOR.
  
 F. OK
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT NO MANUF. SHEETS FOR THE
 GENERATOR HAS BEEN SUBMITTED. - ALSO SUBMIT THE MANUF.
 SPECIFICATION SHEETS FOR THE GAS REGULATORS. INDICATE
 MODEL NUMBER. LISTING INFORMATION REQUIRED.
 ******RESPONSE NOTED, BUT THE BTU LOAD FOR THE NATURAL
 GAS @ 100% LOAD IS NOT INDICATED ON THE MANUF.
 SPECIFICATION SHEETS. THIS SHALL BE SHOWN TO VERIFY
 PIPE SIZING.
  
 H. NA
 I. NA
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-01-30 Cont ID  
Sent By kstevens Date 2006-12-16 Time 17:53 Rev Time 0.00
Received By kstevens Date 2006-12-16 Time 17:54 Sent To  
Notes
2007-01-30 17:59:07DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
  
 FROM PREVIOUS REVIEW:
 FROM PREVIOUS REVIEW:
  
 39B. SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE GAS PERMIT:
  
 A. OK - "NEW"SHOW THE LOCATION OF THE 2PSI TO 1/2PSI
 REGULATOR. SHUT OFF VALVE REQUIRED UPSTREAM OF
 REGULATOR.
 B. OK
 C. OK
 D. OK
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED, BUT NOT ADDRESSED
  
 F. OK - INFORMATIONAL - 2PSI AT MAXIMUM 200 FT
 DEVELOPED LENGTH ALLOWS 39,656,000 BTU'S. ONLY 10,000
 BTU'S ARE INDICATED ON PLANS. THE 10,000 BTU'S IS
 QUESTIONABLE AS MOST RESIDENTIAL DRYERS ARE RATED AT
 22,000 BTU'S. FOR COMPARISON, A .5 PSI SYSTEM WITH 2"
 PIPE WILL DELIVER 800,000 BTU'S. WITH THE EXTRA
 DEVELOPED LENGTH TO THE FARTHEST FUTURE GENERATOR,ITS
 APPROXAMATLY 180'.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT NO MANUF. SHEETS FOR THE
 GENERATOR HAS BEEN SUBMITTED. - ALSO SUBMIT THE MANUF.
 SPECIFICATION SHEETS FOR THE GAS REGULATORS. INDICATE
 MODEL NUMBER. LISTING INFORMATION REQUIRED.
  
 H. NA
 I.NA
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6721
 E-MAIL [email protected]
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-11-14 Cont ID  
Sent By kstevens Date 2006-11-14 Time 17:51 Rev Time 0.00
Received By kstevens Date 2006-11-14 Time 17:51 Sent To  
Notes
2006-12-16 17:53:18DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - RISER DOES NOT REFLECT
 THE FLOOR PLAN. OFFSETS BETWEEN THE
 METER AND THE RISER ARE NOT SHOWN. -
 INDICATE WHAT THE RISERS ABOVE THE TEE
 AT THE TOP OF THE RISER AND AT THE
 GENERATOR ARE FOR. FUTURE BTU LOAD AND
 DISTANCE MAY REQUIRE CHANGES IN THE
 GAS SYSTEM WHEN ADDED.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD-
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 97 Status N Date 2009-09-08 Cont ID  
Sent By jwitmer Date 2009-09-08 Time 11:28 Rev Time 0.00
Received By jwitmer Date 2009-09-08 Time 11:28 Sent To  
Notes
2009-09-09 07:53:06ELECTRICAL REVISION FORWARDED TO D. PALMER

Review Stop I INCOMING/PROCESSING
Rev No 96 Status N Date 2009-09-01 Cont ID  
Sent By kstevens Date 2009-09-01 Time 13:44 Rev Time 0.00
Received By kstevens Date 2009-09-01 Time 13:44 Sent To  
Notes
2009-09-01 13:49:24SENT TO C-

Review Stop I INCOMING/PROCESSING
Rev No 95 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmartine Date 2009-05-20 Time 11:18 Sent To  
Notes
2009-05-20 11:19:31FINAL DRAWINGS SENT TO DEWEY

Review Stop I INCOMING/PROCESSING
Rev No 94 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2009-05-15 15:34:45FIRE ALARM AS-BUILTS SENT TO M. CARISSILLO

Review Stop I INCOMING/PROCESSING
Rev No 93 Status N Date 2009-04-03 Cont ID  
Sent By adarroug Date 2009-04-03 Time 14:41 Rev Time 0.00
Received By adarroug Date 2009-04-03 Time 14:41 Sent To B
Notes
2009-04-03 14:41:46TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 92 Status N Date 2009-04-02 Cont ID  
Sent By adarroug Date 2009-04-02 Time 16:19 Rev Time 0.00
Received By adarroug Date 2009-04-02 Time 16:19 Sent To P
Notes
2009-04-02 16:19:29TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 91 Status N Date 2009-03-30 Cont ID  
Sent By adarroug Date 2009-03-30 Time 11:16 Rev Time 0.00
Received By adarroug Date 2009-03-30 Time 11:16 Sent To  
Notes
2009-03-30 11:16:24TO IN-BOX "C29"

Review Stop I INCOMING/PROCESSING
Rev No 90 Status N Date 2009-03-18 Cont ID  
Sent By adarroug Date 2009-03-18 Time 09:15 Rev Time 0.00
Received By adarroug Date 2009-03-18 Time 09:15 Sent To B
Notes
2009-03-18 09:16:46TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 89 Status N Date 2009-02-20 Cont ID  
Sent By adarroug Date 2009-02-20 Time 11:12 Rev Time 0.00
Received By adarroug Date 2009-02-20 Time 11:12 Sent To B
Notes
2009-02-20 11:13:21TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 88 Status N Date 2009-02-20 Cont ID  
Sent By adarroug Date 2009-02-20 Time 10:04 Rev Time 0.00
Received By adarroug Date 2009-02-20 Time 10:04 Sent To  
Notes
2009-02-20 10:07:49TO "COMM" BD#7

Review Stop I INCOMING/PROCESSING
Rev No 87 Status N Date 2009-02-20 Cont ID  
Sent By adarroug Date 2009-02-20 Time 09:50 Rev Time 0.00
Received By adarroug Date 2009-02-20 Time 09:50 Sent To  
Notes
2009-02-20 09:53:45TO "COMM" BD#14

Review Stop I INCOMING/PROCESSING
Rev No 86 Status N Date 2009-02-09 Cont ID  
Sent By adarroug Date 2009-02-09 Time 10:47 Rev Time 0.00
Received By adarroug Date 2009-02-09 Time 10:47 Sent To B
Notes
2009-02-09 10:47:49TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 85 Status N Date 2009-01-22 Cont ID  
Sent By adarroug Date 2009-01-22 Time 11:59 Rev Time 0.00
Received By adarroug Date 2009-01-22 Time 11:59 Sent To B
Notes
2009-01-22 11:59:57TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 84 Status N Date 2009-01-20 Cont ID  
Sent By adarroug Date 2009-01-20 Time 16:03 Rev Time 0.00
Received By adarroug Date 2009-01-20 Time 16:03 Sent To B
Notes
2009-01-20 16:03:51TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 83 Status N Date 2009-01-15 Cont ID  
Sent By adarroug Date 2009-01-15 Time 10:02 Rev Time 0.00
Received By adarroug Date 2009-01-15 Time 10:02 Sent To  
Notes
2009-01-15 10:05:27TO "COMM" BD#18

Review Stop I INCOMING/PROCESSING
Rev No 82 Status N Date 2009-01-08 Cont ID  
Sent By adarroug Date 2009-01-08 Time 08:29 Rev Time 0.00
Received By adarroug Date 2009-01-08 Time 08:29 Sent To B
Notes
2009-01-08 08:30:15TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 81 Status N Date 2009-01-06 Cont ID  
Sent By adarroug Date 2009-01-06 Time 16:39 Rev Time 0.00
Received By adarroug Date 2009-01-06 Time 16:39 Sent To B
Notes
2009-01-06 16:41:05TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 80 Status N Date 2008-12-22 Cont ID  
Sent By adarroug Date 2008-12-22 Time 09:18 Rev Time 0.00
Received By adarroug Date 2008-12-22 Time 09:18 Sent To  
Notes
2008-12-22 09:18:36TO "COMM" BD#33

Review Stop I INCOMING/PROCESSING
Rev No 79 Status N Date 2008-12-12 Cont ID  
Sent By adarroug Date 2008-12-12 Time 10:12 Rev Time 0.00
Received By adarroug Date 2008-12-12 Time 10:12 Sent To E
Notes
2008-12-12 10:13:01TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 78 Status N Date 2008-12-12 Cont ID  
Sent By adarroug Date 2008-12-12 Time 09:51 Rev Time 0.00
Received By adarroug Date 2008-12-12 Time 09:51 Sent To  
Notes
2008-12-12 10:06:24TO "COMM" BD#19

Review Stop I INCOMING/PROCESSING
Rev No 77 Status N Date 2008-12-10 Cont ID  
Sent By adarroug Date 2008-12-10 Time 11:26 Rev Time 0.00
Received By adarroug Date 2008-12-10 Time 11:26 Sent To  
Notes
2008-12-10 11:29:30TO "COMM" BD#22/ REV #52

Review Stop I INCOMING/PROCESSING
Rev No 76 Status N Date 2008-12-10 Cont ID  
Sent By adarroug Date 2008-12-10 Time 10:30 Rev Time 0.00
Received By adarroug Date 2008-12-10 Time 10:30 Sent To B
Notes
2008-12-10 10:30:46TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 75 Status N Date 2008-12-05 Cont ID  
Sent By adarroug Date 2008-12-05 Time 15:17 Rev Time 0.00
Received By adarroug Date 2008-12-05 Time 15:16 Sent To P
Notes
2008-12-05 15:18:09TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 74 Status N Date 2008-11-13 Cont ID  
Sent By adarroug Date 2008-11-13 Time 14:43 Rev Time 0.00
Received By adarroug Date 2008-11-13 Time 14:43 Sent To B
Notes
2008-11-13 14:43:56TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 73 Status N Date 2008-11-06 Cont ID  
Sent By adarroug Date 2008-11-06 Time 14:19 Rev Time 0.00
Received By adarroug Date 2008-11-06 Time 14:19 Sent To  
Notes
2008-11-06 14:21:47TO "COMM" BD#61--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 72 Status N Date 2008-11-06 Cont ID  
Sent By adarroug Date 2008-11-06 Time 13:59 Rev Time 0.00
Received By adarroug Date 2008-11-06 Time 13:59 Sent To P
Notes
2008-11-06 14:00:06TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 71 Status N Date 2008-11-06 Cont ID  
Sent By adarroug Date 2008-11-06 Time 13:38 Rev Time 0.00
Received By adarroug Date 2008-11-06 Time 13:38 Sent To ENG
Notes
2008-11-06 13:39:09TO "ENG" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 70 Status N Date 2008-11-06 Cont ID  
Sent By adarroug Date 2008-11-06 Time 13:30 Rev Time 0.00
Received By adarroug Date 2008-11-06 Time 13:30 Sent To B
Notes
2008-11-06 13:31:29TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 69 Status N Date 2008-11-06 Cont ID  
Sent By adarroug Date 2008-11-06 Time 13:17 Rev Time 0.00
Received By adarroug Date 2008-11-06 Time 13:17 Sent To E
Notes
2008-11-06 13:18:12TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 68 Status N Date 2008-10-28 Cont ID  
Sent By adarroug Date 2008-10-28 Time 14:21 Rev Time 0.00
Received By adarroug Date 2008-10-28 Time 14:21 Sent To B
Notes
2008-10-28 14:21:28TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 67 Status N Date 2008-10-24 Cont ID  
Sent By adarroug Date 2008-10-24 Time 16:34 Rev Time 0.00
Received By adarroug Date 2008-10-24 Time 16:34 Sent To  
Notes
2008-10-24 16:38:13TO "COMM" BD#18--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 66 Status N Date 2008-10-22 Cont ID  
Sent By adarroug Date 2008-10-22 Time 15:20 Rev Time 0.00
Received By adarroug Date 2008-10-22 Time 15:20 Sent To E
Notes
2008-10-22 15:21:14TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 65 Status N Date 2008-10-22 Cont ID  
Sent By adarroug Date 2008-10-22 Time 09:04 Rev Time 0.00
Received By adarroug Date 2008-10-22 Time 09:04 Sent To M
Notes
2008-10-22 09:05:03TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 64 Status N Date 2008-10-14 Cont ID  
Sent By adarroug Date 2008-10-14 Time 14:51 Rev Time 0.00
Received By adarroug Date 2008-10-14 Time 14:51 Sent To E
Notes
2008-10-14 14:51:38TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 63 Status N Date 2008-10-06 Cont ID  
Sent By adarroug Date 2008-10-06 Time 11:30 Rev Time 0.00
Received By adarroug Date 2008-10-06 Time 11:30 Sent To E
Notes
2008-10-06 11:30:22TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 62 Status N Date 2008-10-03 Cont ID  
Sent By adarroug Date 2008-10-03 Time 15:03 Rev Time 0.00
Received By adarroug Date 2008-10-03 Time 15:03 Sent To  
Notes
2008-10-03 15:03:34TO"COMM" BD#25

Review Stop I INCOMING/PROCESSING
Rev No 61 Status N Date 2008-09-23 Cont ID  
Sent By adarroug Date 2008-09-23 Time 12:37 Rev Time 0.00
Received By adarroug Date 2008-09-23 Time 12:37 Sent To P
Notes
2008-09-23 12:37:41TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 60 Status N Date 2008-09-03 Cont ID  
Sent By adarroug Date 2008-09-03 Time 14:16 Rev Time 0.00
Received By adarroug Date 2008-09-03 Time 14:16 Sent To E
Notes
2008-09-03 14:16:28TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 59 Status N Date 2008-08-21 Cont ID  
Sent By adarroug Date 2008-08-21 Time 14:43 Rev Time 0.00
Received By adarroug Date 2008-08-21 Time 14:43 Sent To P
Notes
2008-08-21 14:44:04TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 58 Status N Date 2008-08-21 Cont ID  
Sent By adarroug Date 2008-08-21 Time 14:29 Rev Time 0.00
Received By adarroug Date 2008-08-21 Time 14:29 Sent To E
Notes
2008-08-21 14:30:33TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 57 Status N Date 2008-08-21 Cont ID  
Sent By adarroug Date 2008-08-21 Time 11:30 Rev Time 0.00
Received By adarroug Date 2008-08-21 Time 11:30 Sent To B
Notes
2008-08-21 11:30:52TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 56 Status N Date 2008-08-21 Cont ID  
Sent By adarroug Date 2008-08-21 Time 11:13 Rev Time 0.00
Received By adarroug Date 2008-08-21 Time 11:13 Sent To E
Notes
2008-08-21 11:13:45TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 55 Status N Date 2008-08-14 Cont ID  
Sent By adarroug Date 2008-08-14 Time 13:37 Rev Time 0.00
Received By adarroug Date 2008-08-14 Time 13:37 Sent To B
Notes
2008-08-14 13:38:50TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 54 Status N Date 2008-07-30 Cont ID  
Sent By adarroug Date 2008-07-30 Time 08:43 Rev Time 0.00
Received By adarroug Date 2008-07-30 Time 08:43 Sent To B
Notes
2008-07-30 08:44:13TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 53 Status N Date 2008-07-11 Cont ID  
Sent By adarroug Date 2008-07-11 Time 11:14 Rev Time 0.00
Received By adarroug Date 2008-07-11 Time 11:14 Sent To E
Notes
2008-07-11 11:15:06TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 52 Status N Date 2008-07-01 Cont ID  
Sent By adarroug Date 2008-07-01 Time 11:10 Rev Time 0.00
Received By adarroug Date 2008-07-01 Time 11:10 Sent To E
Notes
2008-07-01 11:10:39TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 51 Status N Date 2008-06-20 Cont ID  
Sent By shill Date 2008-06-20 Time 15:16 Rev Time 0.00
Received By shill Date 2008-06-20 Time 15:16 Sent To E
Notes
2008-06-20 15:16:57TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 50 Status N Date 2008-06-17 Cont ID  
Sent By adarroug Date 2008-06-17 Time 09:13 Rev Time 0.00
Received By adarroug Date 2008-06-17 Time 09:13 Sent To P
Notes
2008-06-17 09:13:33TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 49 Status N Date 2008-06-16 Cont ID  
Sent By adarroug Date 2008-06-16 Time 16:38 Rev Time 0.00
Received By adarroug Date 2008-06-16 Time 16:38 Sent To B
Notes
2008-06-16 16:39:13TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 48 Status N Date 2008-06-10 Cont ID  
Sent By adarroug Date 2008-06-10 Time 15:47 Rev Time 0.00
Received By adarroug Date 2008-06-10 Time 15:47 Sent To  
Notes
2008-06-10 15:47:28TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 47 Status N Date 2008-05-30 Cont ID  
Sent By adarroug Date 2008-05-30 Time 09:39 Rev Time 0.00
Received By adarroug Date 2008-05-30 Time 09:39 Sent To B
Notes
2008-05-30 09:40:49TO "JWITMER" DESK/ 3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 46 Status N Date 2008-05-14 Cont ID  
Sent By adarroug Date 2008-05-14 Time 14:14 Rev Time 0.00
Received By adarroug Date 2008-05-14 Time 14:14 Sent To P
Notes
2008-05-14 14:15:02TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 45 Status N Date 2008-05-14 Cont ID  
Sent By adarroug Date 2008-05-14 Time 14:12 Rev Time 0.00
Received By adarroug Date 2008-05-14 Time 14:12 Sent To E
Notes
2008-05-14 14:12:32TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 44 Status N Date 2008-05-05 Cont ID  
Sent By adarroug Date 2008-05-05 Time 14:15 Rev Time 0.00
Received By adarroug Date 2008-05-05 Time 14:15 Sent To B
Notes
2008-05-05 14:16:16TO "JWITMER" DESK/2 REV'S

Review Stop I INCOMING/PROCESSING
Rev No 43 Status N Date 2008-05-01 Cont ID  
Sent By adarroug Date 2008-05-01 Time 17:00 Rev Time 0.00
Received By adarroug Date 2008-05-01 Time 17:00 Sent To  
Notes
2008-05-01 17:01:02TO "COMM" BD#58/PLANS ON RACK/5 SMALL ROLLS

Review Stop I INCOMING/PROCESSING
Rev No 42 Status N Date 2008-04-10 Cont ID  
Sent By adarroug Date 2008-04-10 Time 11:31 Rev Time 0.00
Received By adarroug Date 2008-04-10 Time 11:31 Sent To  
Notes
2008-04-10 11:40:47TO "COMM" BD#32

Review Stop I INCOMING/PROCESSING
Rev No 41 Status N Date 2008-03-17 Cont ID  
Sent By adarroug Date 2008-03-17 Time 13:50 Rev Time 0.00
Received By adarroug Date 2008-03-17 Time 13:50 Sent To E
Notes
2008-03-17 13:51:02TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 40 Status N Date 2008-03-14 Cont ID  
Sent By adarroug Date 2008-03-14 Time 16:54 Rev Time 0.00
Received By adarroug Date 2008-03-14 Time 16:54 Sent To  
Notes
2008-03-17 14:25:18TO "COMM" BD#7--PLANS ON RACK--3 ROLLS---EXPEDITED---
2008-03-14 16:55:16WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 39 Status N Date 2008-03-13 Cont ID  
Sent By adarroug Date 2008-03-13 Time 15:51 Rev Time 0.00
Received By adarroug Date 2008-03-13 Time 15:50 Sent To M
Notes
2008-03-13 15:51:27TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 38 Status N Date 2008-03-13 Cont ID  
Sent By adarroug Date 2008-03-13 Time 15:37 Rev Time 0.00
Received By adarroug Date 2008-03-13 Time 15:37 Sent To ENG
Notes
2008-03-13 15:38:32TO "ENG" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 37 Status N Date 2008-02-21 Cont ID  
Sent By adarroug Date 2008-02-21 Time 12:03 Rev Time 0.00
Received By adarroug Date 2008-02-21 Time 12:03 Sent To Z
Notes
2008-02-21 12:04:08TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 36 Status N Date 2008-02-21 Cont ID  
Sent By adarroug Date 2008-02-21 Time 11:57 Rev Time 0.00
Received By adarroug Date 2008-02-21 Time 11:57 Sent To E
Notes
2008-02-21 11:58:58TO "E" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 35 Status N Date 2008-02-11 Cont ID  
Sent By adarroug Date 2008-02-11 Time 13:56 Rev Time 0.00
Received By adarroug Date 2008-02-11 Time 13:56 Sent To M
Notes
2008-02-11 13:57:10TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 34 Status N Date 2008-01-31 Cont ID  
Sent By adarroug Date 2008-01-31 Time 12:50 Rev Time 0.00
Received By adarroug Date 2008-01-31 Time 12:50 Sent To E
Notes
2008-01-31 12:51:01TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 33 Status N Date 2008-01-28 Cont ID  
Sent By adarroug Date 2008-01-28 Time 12:33 Rev Time 0.00
Received By adarroug Date 2008-01-28 Time 12:33 Sent To E
Notes
2008-01-28 12:33:37TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 32 Status N Date 2008-01-16 Cont ID  
Sent By adarroug Date 2008-01-16 Time 14:52 Rev Time 0.00
Received By adarroug Date 2008-01-16 Time 14:52 Sent To M
Notes
2008-01-16 14:53:54TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 31 Status N Date 2008-01-16 Cont ID  
Sent By adarroug Date 2008-01-16 Time 14:46 Rev Time 0.00
Received By adarroug Date 2008-01-16 Time 14:46 Sent To ENG
Notes
2008-01-16 14:46:57TO "ENG' BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 30 Status N Date 2008-01-16 Cont ID  
Sent By adarroug Date 2008-01-16 Time 14:34 Rev Time 0.00
Received By adarroug Date 2008-01-16 Time 14:34 Sent To E
Notes
2008-01-16 14:34:38TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 29 Status N Date 2007-12-21 Cont ID  
Sent By mmiller Date 2007-12-21 Time 09:20 Rev Time 0.00
Received By mmiller Date 2007-12-21 Time 09:19 Sent To M
Notes
2007-12-21 09:20:23SENT TO "RR" 'S DESK MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 28 Status N Date 2007-12-14 Cont ID  
Sent By adarroug Date 2007-12-14 Time 16:25 Rev Time 0.00
Received By adarroug Date 2007-12-14 Time 16:25 Sent To  
Notes
2007-12-14 16:28:16TO "COMM" BD#37--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 27 Status N Date 2007-12-14 Cont ID  
Sent By adarroug Date 2007-12-14 Time 16:13 Rev Time 0.00
Received By adarroug Date 2007-12-14 Time 16:13 Sent To E
Notes
2007-12-14 16:14:04TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 26 Status N Date 2007-12-13 Cont ID  
Sent By adarroug Date 2007-12-13 Time 16:59 Rev Time 0.00
Received By adarroug Date 2007-12-13 Time 16:59 Sent To M
Notes
2007-12-13 17:01:20TO "RREGUIERO" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 25 Status N Date 2007-11-26 Cont ID  
Sent By adarroug Date 2007-11-26 Time 12:03 Rev Time 0.00
Received By adarroug Date 2007-11-26 Time 12:03 Sent To B
Notes
2007-11-26 12:04:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2007-11-01 Cont ID  
Sent By rbrown Date 2007-11-01 Time 18:21 Rev Time 0.00
Received By rbrown Date 2007-11-01 Time 18:21 Sent To  
Notes
2007-11-01 18:21:35TO COMM BD # 39

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2007-09-24 Cont ID  
Sent By adarroug Date 2007-09-24 Time 10:45 Rev Time 0.00
Received By adarroug Date 2007-09-24 Time 10:45 Sent To B
Notes
2007-09-24 10:45:51TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2007-08-24 Cont ID  
Sent By adarroug Date 2007-08-20 Time 09:56 Rev Time 0.00
Received By adarroug Date 2007-08-20 Time 09:56 Sent To  
Notes
2007-08-30 08:14:17TO "COMM" BD#56--EXPEDITED--PLANS ON RACK/3 ROLLS
2007-08-24 09:56:36WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2007-08-09 Cont ID  
Sent By dpalmer Date 2007-08-09 Time 13:22 Rev Time 0.00
Received By dpalmer Date 2007-08-09 Time 13:22 Sent To B
Notes
2007-08-09 13:23:25TO JW'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2007-08-09 Cont ID  
Sent By dpalmer Date 2007-08-09 Time 13:22 Rev Time 0.00
Received By dpalmer Date 2007-08-09 Time 13:22 Sent To B
Notes
2007-08-09 13:22:52TO JW'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2007-08-07 Cont ID  
Sent By dpalmer Date 2007-08-07 Time 20:37 Rev Time 0.00
Received By dpalmer Date 2007-08-07 Time 20:37 Sent To  
Notes
2007-08-07 20:38:15BLDG/PLUMB REVS WAITING FOR COMM BOARD.

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2007-07-28 Cont ID  
Sent By adarroug Date 2007-07-28 Time 13:32 Rev Time 0.00
Received By adarroug Date 2007-07-28 Time 13:32 Sent To B
Notes
2007-07-28 13:32:24TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2007-07-17 Cont ID  
Sent By adarroug Date 2007-07-17 Time 16:02 Rev Time 0.00
Received By adarroug Date 2007-07-17 Time 16:02 Sent To B
Notes
2007-07-17 16:02:35TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2007-07-17 Cont ID  
Sent By adarroug Date 2007-07-02 Time 15:06 Rev Time 0.00
Received By adarroug Date 2007-07-02 Time 15:06 Sent To  
Notes
2007-07-17 15:07:03TO "COMM" BD#21/PLANS ON RACK--7 ROLLS AND 3 BINDERS

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2007-06-12 Cont ID  
Sent By adarroug Date 2007-06-12 Time 16:08 Rev Time 0.00
Received By adarroug Date 2007-06-12 Time 16:08 Sent To B
Notes
2007-06-12 16:08:49TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2007-06-12 Cont ID  
Sent By adarroug Date 2007-06-12 Time 11:11 Rev Time 0.00
Received By adarroug Date 2007-06-12 Time 11:11 Sent To B
Notes
2007-06-12 11:12:16TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2007-06-06 Cont ID  
Sent By adarroug Date 2007-06-06 Time 16:53 Rev Time 0.00
Received By adarroug Date 2007-06-06 Time 16:53 Sent To P
Notes
2007-06-06 16:53:54TO "P" BOX

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2007-05-23 Cont ID  
Sent By adarroug Date 2007-05-23 Time 14:44 Rev Time 0.00
Received By adarroug Date 2007-05-23 Time 14:44 Sent To B
Notes
2007-05-23 14:44:35TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-05-14 Cont ID  
Sent By adarroug Date 2007-05-14 Time 15:19 Rev Time 0.00
Received By adarroug Date 2007-05-14 Time 15:19 Sent To B
Notes
2007-05-14 15:20:03TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-04-06 Cont ID  
Sent By spalmer Date 2007-04-06 Time 17:39 Rev Time 0.00
Received By spalmer Date 2007-04-06 Time 17:39 Sent To B
Notes
2007-04-06 17:39:23TO JIM WITMER

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-03-27 Cont ID  
Sent By spalmer Date 2007-03-27 Time 17:46 Rev Time 0.00
Received By spalmer Date 2007-03-27 Time 17:46 Sent To B
Notes
2007-03-27 17:47:11SUBMITTAL TO JIM WITMER

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-03-24 Cont ID  
Sent By adarroug Date 2007-03-24 Time 14:13 Rev Time 0.00
Received By adarroug Date 2007-03-24 Time 14:13 Sent To  
Notes
2007-03-24 14:15:59TO "COMM" BD#6/PLANS ON RACK--3 ROLLS AND 3 BINDERS

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-03-24 Cont ID  
Sent By adarroug Date 2007-03-24 Time 13:58 Rev Time 0.00
Received By adarroug Date 2007-03-24 Time 13:58 Sent To B
Notes
2007-03-24 13:59:10TO "JWITMER' DESK/PARKING GARAGE REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-03-16 Cont ID  
Sent By adarroug Date 2007-03-16 Time 14:34 Rev Time 0.00
Received By adarroug Date 2007-03-16 Time 14:34 Sent To  
Notes
2007-03-19 14:18:00TO "COMM" BD#22
2007-03-16 14:34:38WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-02-22 Cont ID  
Sent By adarroug Date 2007-02-22 Time 17:46 Rev Time 0.00
Received By adarroug Date 2007-02-22 Time 17:46 Sent To B
Notes
2007-02-22 17:46:44TO "JWITMER" DESK/REV--PER "RBROWN"

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-02-12 Cont ID  
Sent By adarroug Date 2007-02-12 Time 16:21 Rev Time 0.00
Received By adarroug Date 2007-02-12 Time 16:21 Sent To  
Notes
2007-02-12 16:21:47TO "COMM" BD#30/PLANS ON RACK/6 ROLLS AND 4 BOXES

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-19 Cont ID  
Sent By adarroug Date 2007-01-19 Time 16:00 Rev Time 0.00
Received By adarroug Date 2007-01-19 Time 16:00 Sent To  
Notes
2007-01-19 16:04:59TO "COMM" BD#10/PLANS ON RACK6 ROLLS, 2 BOXES AND 2
 ROLLS OLD PLANS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-15 Cont ID  
Sent By adarroug Date 2006-12-15 Time 16:39 Rev Time 0.00
Received By adarroug Date 2006-12-15 Time 16:39 Sent To  
Notes
2006-12-15 16:40:49TO "COMM" BD#3/PLANS ON RACK/7 ROLLS, 1 BOX, AND
 BINDERS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-25 Cont ID  
Sent By adarroug Date 2006-11-25 Time   Rev Time 0.00
Received By adarroug Date 2006-10-19 Time 11:13 Sent To  
Notes
2006-10-24 17:06:20TO "COMM" BD#47/PLANS ON RACK--6 ROLLS AND 1 BOX
2006-10-20 11:14:14WAITING FOR "COMM" BD

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2008-10-16 Cont ID  
Sent By mflis Date 2008-10-16 Time 08:39 Rev Time 0.00
Received By mflis Date 2008-10-16 Time 08:39 Sent To  
Notes
2008-10-16 08:43:04ZONING REVIEW: PASSED WITH COMMENTS:
  
 1) STRUCTURAL SOIL SHOULD BE USED AROUND ALL SIDEWALKS
 FOR STREET TREES
  
 2) AT SE CORNER OF SITE, FDOT DATE PALMS WILL NEED TO
 BE REINSTALLED TO MATCH OTHER STREET CORNERS (NORTH
 SIDE OF CLEMATIS, WEST OF DIXIE). NOTE IS INDICATED ON
 PLANS THAT THESE ARE STORED OFF-SITE, BUT PLANT
 MATERIALS ARE NOT SHOWN.
  
 3) REVISIONS TO BUILDING ENTRIES AT CLEMATIS STREET AND
 BANYAN STREET ARE NOT INDICATED WITH THIS SET AND WILL
 NEED TO BE SUBMITTED FOR APPROVAL. (ADJUSTMENTS TO TAKE
 INTO ACCOUNT ELEVATION CHANGES).
  
 4) PITCH APPLE LOCATED IN MIDDLE COURTYARD MAY BE TOO
 SMALL TO PROVIDE ANY MEANINGFUL SHADE OR ACCENT FOR THE
 SPACE. PLEASE CONTACT ROBERT KUSSNER, LANDSCAPE
 PLANNER, AT 822-1435 FOR RECOMMENDATIONS TO SWITCH OUT
 SMALLER MATERIAL FOR SOMETHING TALLER WHICH WILL BE
 PROPORTIONAL TO SCALE OF SPACE AND BUILDING
  
 MATT FLIS - 822-1445

Review Stop M MECHANICAL (A/C)
Rev No 24 Status P Date 2009-09-09 Cont ID  
Sent By rregueir Date 2009-09-09 Time 12:14 Rev Time 0.00
Received By rregueir Date 2009-09-09 Time 11:30 Sent To  
Notes
2009-09-09 12:14:21REVISED M2-3.0 DELTA 14F/G

Review Stop M MECHANICAL (A/C)
Rev No 23 Status P Date 2009-01-20 Cont ID  
Sent By rregueir Date 2009-01-20 Time 08:40 Rev Time 0.00
Received By rregueir Date 2009-01-20 Time 08:39 Sent To  
Notes
2009-01-20 08:40:25PAGE M1-2.2 REVISION 23A

Review Stop M MECHANICAL (A/C)
Rev No 22 Status P Date 2009-01-20 Cont ID  
Sent By rregueir Date 2009-01-20 Time 08:20 Rev Time 0.00
Received By rregueir Date 2009-01-20 Time 08:13 Sent To  
Notes
2009-01-20 08:17:53REVISION 20B, PAGE M1-1.3. THIS PAGE ALSO NEEDS FIRE
 REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 21 Status P Date 2008-11-22 Cont ID  
Sent By rregueir Date 2008-11-22 Time 12:44 Rev Time 0.00
Received By rregueir Date 2008-11-22 Time 12:32 Sent To  
Notes
2008-11-22 12:32:44REVISED M1-1.2, M3,1.0 REV 21A

Review Stop M MECHANICAL (A/C)
Rev No 20 Status P Date 2008-11-15 Cont ID  
Sent By rregueir Date 2008-11-15 Time 13:10 Rev Time 0.00
Received By rregueir Date 2008-11-15 Time 12:09 Sent To PC
Notes
2008-11-15 13:10:17REVISED M1-1.3 FUEL PUMP ROOM.

Review Stop M MECHANICAL (A/C)
Rev No 19 Status P Date 2008-11-08 Cont ID  
Sent By rregueir Date 2008-11-08 Time 15:20 Rev Time 0.00
Received By rregueir Date 2008-11-08 Time 15:18 Sent To PC
Notes
2008-11-08 15:19:47REV.19, PAGES: M1-1.1, M1-1.2, M1-2.1, M1-2.2, M1-3.1,
 M1-3.2, M1-4.1, M1-4.2, M1-5.1

Review Stop M MECHANICAL (A/C)
Rev No 18 Status P Date 2008-07-02 Cont ID  
Sent By rregueir Date 2008-07-02 Time 14:44 Rev Time 0.00
Received By rregueir Date 2008-07-02 Time 13:03 Sent To PC
Notes
2008-07-02 14:44:00REVISION CA-201 PAGES M1-1.1, M1-2.1, M1-2.2, M1-3.1,
 M1-4.1, M1-4.2, M1-5.1
 ADDED TRANSFER AIR OPENING SIZES.

Review Stop M MECHANICAL (A/C)
Rev No 17 Status   Date 2008-05-12 Cont ID  
Sent By rregueir Date 2008-05-07 Time 08:50 Rev Time 0.00
Received By rregueir Date 2008-05-07 Time 16:28 Sent To PC
Notes
2008-05-12 08:50:46REV.14E

Review Stop M MECHANICAL (A/C)
Rev No 16 Status F Date 2008-04-20 Cont ID  
Sent By rregueir Date 2008-04-20 Time 13:37 Rev Time 0.00
Received By rregueir Date 2008-04-19 Time 17:30 Sent To PC
Notes
2008-04-20 13:37:13REVIEW #: REV.14D
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG M1-1.1: 6 INCH ROUND SUPPLY DUCT FEEDING FILE
 ROOM A1.207 IS PENETRATING A RATED CORRIDOR WALL AND IS
 ONLY PROTECTED WITH A FIRE DAMPER. THIS PENETRATION
 REQUIRES A FIRE AND SMOKE DAMPER IN ACCORDANCE WITH
 FBCM 607.5.4(3) BECAUSE THE DUCT HAS OPENINGS IN THE
 CORRIDOR.
  
 2. PG M1-1.1: 10 INCH ROUND SUPPLY DUCT FEEDING
 VESTIBULE A1.011 IS PROTECTED WITH A FIRE/SMOKE DAMPER.
 HOWEVER, THIS VESTIBULE IS SERVING AS AN EXIT
 PASSAGEWAY FROM STAIR 02 AS DEFINED IN FBCB SECTION
 1002. THIS PENETRATION IS PROHIBITED IN ACCORDANCE WITH
 FBCB 1020.5.
  
 3. PG M1-1.1 AND MOST REV.14D PAGES: KEY NOTES WHICH
 ARE LISTED ON THE BOTTOM RIGHT OF PAGE ARE NOW MISSING
 FROM FLOOR PLANS. SOME KEY NOTES ARE NO LONGER VALID
 AND SHOULD BE REMOVED FROM PLANS. EXAMPLE: PG M1-1.2
 KEY NOTE #1 STILL CALLS FOR DUCT SMOKE DETECTORS AT
 SHAFTS FOR SMOKE DAMPERS. PLEASE SHOW RELEVANT KEY
 NOTES WHERE NEEDED ON FLOOR PLANS AND REMOVE THOSE
 WHICH ARE NO LONGER APPLICABLE.
  
 4. PG M1-1.2: IN VESTIBULE D1.005 THERE ARE TWO DUCT
 PENETRATIONS. THIS IS AN EXIT PASSAGEWAY AS DEFINED IN
 FBCB SECTION 1002. THESE PENETRATIONS ARE PROHIBITED IN
 ACCORDANCE WITH FBCB 1020.5.
  
 5. PG M1-1.2: AT VOICE/DATA ROOM D1.107 THERE IS A
 36X56 DUCT PENETRATING THE FLOOR ABOVE AND IS SHOWN IN
 THE MIDDLE OF A SMOKE PARTITION. ARCHITECTURAL PLANS
 CALL FOR THIS WALL TO BE BUILT TO THE UNDERSIDE OF THE
 FLOOR ABOVE. PLEASE SHOW HOW THIS WILL BE ACCOMPLISHED
 WITHOUT COMPROMISING THE FIRE/SMOKE DAMPER INSTALLATION
 OR THE SMOKE RATING OF THE PARTITION. FBCM 607.2, FBCB
 710.4.
  
 6. PG M1-1.2: A 14 INCH ROUND DUCT PENETRATING THE WALL
 BETWEEN VOICE/DATA ROOM C1.102 AND LOBBY C1.008 IS
 SHOWN PROTECTED WITH A FIRE DAMPER. THIS PENETRATION
 REQUIRES FIRE AND SMOKE DAMPER IN ACCORDANCE WITH FBCM
 607.5.4(3).
  
 7. PG M1-1.2: STORAGE ROOMS C1.403 AND C1.404 ARE
 ENCLOSED IN SMOKE PARTITIONS AS SHOWN ON LS1-1.2.
 MECHANICAL FLOOR PLAN SHOWS AIR TRANSFER OPENINGS IN
 EACH ROOM. THESE OPENINGS SHALL BE PROTECTED BY SMOKE
 DAMPER IN ACCORDANCE WITH FBCB 710.7.
  
 8. PG M1-1.2 THROUGH M1-5.2: STARTING IN MEN?S ROOM
 C1.104 THERE IS AN EXHAUST DUCT ENTERING WHAT APPEARS
 TO BE AN ENCLOSURE AND TRAVELS THROUGH THE 4TH FLOOR TO
 EF-4 ON THE ROOF. THIS ENCLOSURE IS NOT SHOWN TO BE
 FIRE RESISTANCE RATED AS A SHAFT ON THE ARCHITECTURAL
 OR LIFE SAFETY PLANS.A SHAFT ENCLOSURE IS REQUIRED
 WHERE DUCTS PENETRATE HORIZONTAL ASSEMBLIES IN
 ACCORDANCE WITH FBCM 607.6. SHAFT ENCLOSURES SHALL HAVE
 A FIRE-RESISTANCE RATING OF NOT LESS THAN 2 HOURS WHERE
 CONNECTING FOUR STORIES OR MORE IN ACCORDANCE WITH FBCB
 707.4.
  
 9. PG M1-2.1: KEY NOTE #6 NEEDS TO BE ASSOCIATED WITH
 THE FIRE/SMOKE DAMPERS LOCATED WHERE THE SMOKE EXHAUST
 DUCTS PENETRATE THE SHAFT ENCLOSURE. THESE DAMPERS NEED
 TO BE UNDER THE CONTROL OF THE SMOKE CONTROL SYSTEM TO
 ENSURE THEY ARE OPEN WHEN THE ATRIUM IS IN SMOKE
 CONTROL MODE IN ACCORDANCE WITH FBCB 909.22.1.
  
 10. PG M1-3.2: AT VOICE/DATA ROOM C3.110 THE 10X8 DUCT
 PENETRATION OF THE RATED CORRIDOR WALL REQUIRES FIRE
 AND SMOKE DAMPER IN ACCORDANCE WITH FBCM 607.5.4(3).
  
 11. PG M1-3.2: AT CORRIDOR C3.010 THE 55X18 DUCT
 PENETRATION OF THE RATED CORRIDOR WALL REQUIRES FIRE
 AND SMOKE DAMPER IN ACCORDANCE WITH FBCM 607.5.4(3).
  
 12. PG M1-3.2: AT PROGRAM/MEETING ROOM C3.306 THE 48X18
 DUCT PENETRATION OF THE RATED CORRIDOR WALL REQUIRES
 FIRE AND SMOKE DAMPER IN ACCORDANCE WITH FBCM
 607.5.4(3).
  
 13. PG M1-3.2: AT CORRIDOR C3.015 THERE IS VAV 3-1R-5.
 THE DUCTS ON BOTH SIDES OF THE VAV ARE SHOWN AS
 PROTECTED WITH FIRE DAMPERS. IF THE DUCT CONNECTION TO
 THIS VAV IS MADE BY FLEXIBLE NON-METALLIC DUCT, THESE
 DUCT PENETRATIONS WILL NOT MEET THE EXCEPTION FOR SMOKE
 DAMPER REQUIREMENT IN ACCORDANCE WITH FBCM 607.5.4(3).
 PLEASE VERIFY THAT THIS DUCT AND VAV CONNECTION ARE
 CONTINUOUS STEEL NOT LESS THAN 0.019 INCH THICKNESS (26
 GAGE) OR PROVIDE FIRE AND SMOKE DAMPER AT CORRIDOR
 PENETRATIONS IN ACCORDANCE WITH FBCM 607.5.4.
  
 14. PG M1-3.2, A1-3.2 AND LS1-3.2: THERE IS A PORTION
 OF THE WALL BETWEEN LOBBY C3.303 AND PREFUNCTION LOBBY
 C3.301 WHICH IS NOT SHOWN TO CARRY THE 1-HOUR FIRE
 RESISTANCE RATING AS REQUIRED FOR EXIT ACCESS CORRIDORS
 IN THIS AREA IN ACCORDANCE WITH FBCB TABLE 1016.1.
  
 15. PG M2-3.0 AND M1-6.0: ELEVATOR MACHINE ROOM A6.103
 REQUIRES INDEPENDENT VENTILATION IN ACCORDANCE WITH
 FBCB 3006.2. THE DUCT PENETRATION INTO THIS ROOM SHALL
 BE PROTECTED WITH FIRE/SMOKE DAMPER IN ACCORDANCE WITH
 FBCB 3006.4 AND FBCM 607.5.5.1.
  
 16. PG M2-3.0 AND M1-6.0: ELEVATOR MACHINE ROOM A6.102,
 THE 44X30 DUCT OPENING IN TO ELEVATOR 03 HOISTWAY SHALL
 BE PROTECTED WITH COMBINATION FIRE/SMOKE DAMPER IN
 ACCORDANCE WITH FBCB 3002.1.1 AND FBCM 607.5.5.1.
  
 17. PG M2-3.0 AND M1-6.0: ELEVATOR MACHINE ROOM A6.102,
 THE 18X14 DUCT PENETRATION FROM FCU-6 SHALL BE
 PROTECTED WITH COMBINATION FIRE/SMOKE DAMPER IN
 ACCORDANCE WITH FBCB 3006.4 AND FBCM 607.5.5.1.
  
 18. PG M2-3.0 AND M1-6.0: ELEVATOR MACHINE ROOM A6.102,
 THE 44X30 HOISTWAY VENT REQUIRES A MOTORIZED DAMPER IN
 ACCORDANCE WITH FBCB 13-409.1.ABC.3.1.
  
 19. PG M6-1.0: PLEASE REMOVE KEY NOTE #1 FROM PLAN AS
 IT IS NO LONGER APPLICABLE.
 FBCB 106.1.1. SEE ALSO COMMENT #3 ABOVE.
  
 NOTE: MECHANICAL REVIEW HAS BEEN COMPLETED. HOWEVER,
 BUILDING REVIEW IS PARTIALLY COMPLETE AT THIS TIME AND
 STILL PENDING. PLEASE COORDINATE ALL MECHANICAL,
 ARCHITECTURAL AND LIFE SAFETY PLANS TO ENSURE CODE
 COMPLIANCE PRIOR TO RESUBMITTAL OF PLANS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 15 Status F Date 2008-04-08 Cont ID  
Sent By rregueir Date 2008-04-08 Time 16:00 Rev Time 0.00
Received By rregueir Date 2008-03-22 Time 15:38 Sent To PC
Notes
2008-04-08 16:00:16REVIEW #: REV.14B AND 14C
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG M1-1.1: THIS SHEET CONTAINS CHANGES WHICH ARE NOT
 MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS. PLEASE
 MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED SINCE
 REV. 12C. ONE EXAMPLE OF SUCH CHANGES IS CIRCLED ON
 PLAN.
 ALSO, REVISIONS 12B AND 12C WHICH WERE PART OF THE
 REVISION HISTORY ARE NOW MISSING FROM PLANS. THIS
 INDICATES IT IS LIKELY THAT THE PLANS HAVE REVERTED TO
 A PREVIOUS STATE BEFORE BEING REVISED AS PART OF REV
 14B.
  
 2. PG M1-1.2: THIS SHEET CONTAINS CHANGES WHICH ARE NOT
 MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS. PLEASE
 MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED SINCE
 REV. 12B. ONE EXAMPLE OF SUCH CHANGES IS CIRCLED ON
 PLAN.
 ALSO, REVISION WHICH WAS PART OF THE REVISION HISTORY
 IS NOW MISSING FROM PLANS. THIS INDICATES IT IS LIKELY
 THAT THE PLANS HAVE REVERTED TO A PREVIOUS STATE BEFORE
 BEING REVISED AS PART OF REV 14B AND 14C.
  
 3. PG M1-1.2: THERE IS A 10 INCH ROUND DUCT PENETRATING
 A 2-HOUR RATED WALL BETWEEN LOADING D1.106 AND CORRIDOR
 D1.006. SHOW HOW THIS PENETRATION IS TO BE PROTECTED IN
 ACCORDANCE WITH FBCM 607.5.
  
 4. PG M1-2.1: THIS SHEET CONTAINS CHANGES WHICH ARE NOT
 MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS. PLEASE
 MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED SINCE
 REV. 12C. ONE EXAMPLE OF SUCH CHANGES IS CIRCLED ON
 PLAN.
 ALSO, REVISIONS 12B AND 12C WHICH WERE PART OF THE
 REVISION HISTORY ARE NOW MISSING FROM PLANS. THIS
 INDICATES IT IS LIKELY THAT THE PLANS HAVE REVERTED TO
 A PREVIOUS STATE BEFORE BEING REVISED AS PART OF REV
 14B.
  
 5. PG M1-2.2: THIS PAGE IS NOT ABLE TO BE REVIEWED.
 THERE ARE MULTIPLE LAYERS IN MULTIPLE SCALES ON THE
 SAME PAGE. PLEASE CORRECT THE PAGE AND RESUBMIT.
  
 6. PG M1-3.1: THIS SHEET CONTAINS CHANGES WHICH ARE NOT
 MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS. PLEASE
 MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED SINCE
 REV. 12C. ONE EXAMPLE OF SUCH CHANGES IS CIRCLED ON
 PLAN.
  
 7. PG M1-3.1: THIS PAGE HAS BEEN MODIFIED BY HAND WITH
 A PEN. THERE IS NO INDICATION ON PLANS THAT THESE
 MODIFICATIONS WERE MADE BY THE DESIGN PROFESSIONAL OF
 RECORD. SIGNED AND SEALED DRAWINGS SHALL NOT BE
 MODIFIED ONCE SIGNED AND SEALED UNLESS THE
 MODIFICATIONS ARE SIGNED AND DATED BY THE DESIGNER OF
 RECORD. OTHERWISE, IT SHALL BE ASSUMED THAT THE
 DRAWINGS WERE MODIFIED BY SOMEONE NOT AUTHORIZED TO DO
 SO.
  
 8. PG M1-3.1: PLAN SHOWS TWO FIRE DAMPERS IN THE WALL
 AT VOICE/DATA A3.116. THIS WALL IS NOT SHOWN AS HAVING
 A FIRE RESISTANCE RATING ON ARCHITECTURAL OR LIFE
 SAFETY PLANS. THERE IS ALSO A 60X26 UNPROTECTED DUCT
 PENETRATION SHOWN IN THE SAME ROOM. PLEASE COORDINATE
 MECH. PLANS WITH ARCH. PLANS AND LS PLANS, SHOWING
 PROTECTION OF PENETRATIONS WHERE NEEDED IN ACCORDANCE
 WIT FBCM 607.5.
  
 9. PG M1-3.2: THERE ARE AT LEAST FIVE DUCT PENETRATIONS
 OF FIRE RATED WALL ASSEMBLIES WITHOUT PROTECTION AT
 CORRIDORS C3.011 AND C3.012. SHOW HOW THESE
 PENETRATIONS ARE TO BE PROTECTED IN ACCORDANCE WITH
 FBCM 607.5 AND 607.5.4.
  
 10. PG M1-3.2: THIS SHEET CONTAINS CHANGES WHICH ARE
 NOT MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS.
 PLEASE MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED
 SINCE REV. 12B. ONE EXAMPLE OF SUCH CHANGES IS CIRCLED
 ON PLAN.
 ALSO, REVISION 12B WHICH WAS PART OF THE REVISION
 HISTORY IS NOW MISSING FROM PLANS. THIS INDICATES IT IS
 LIKELY THAT THE PLANS HAVE REVERTED TO A PREVIOUS STATE
 BEFORE BEING REVISED AS PART OF REV 14B AND 14C.
  
 11. PG M1-3.2: PLEASE SHOW SIZE OF DUCT FOR EF-3 ABOVE
 STAIR 10 RISER BETWEEN TRANSITIONS. ALSO, SHOW SIZE OF
 TAP AT 40X44 RETURN DUCT FOR RTU-2 NEAR STAIR 7.
  
 12. THIS SHEET CONTAINS CHANGES WHICH ARE NOT MARKED OR
 CLOUDED FROM PREVIOUS PASSED PLANS. PLEASE MARK OR
 CLOUD ALL CHANGES WHICH HAVE OCCURRED SINCE REV. 12A.
 ONE EXAMPLE OF SUCH CHANGES IS CIRCLED ON PLAN.
  
 13. PG M1-4.1: THE DUCT FEEDING A VAV FROM SOUTH END OF
 SERVER ROOM IS PENETRATING A 2-HOUR RATED WALL ASSEMBLY
 AS SHOWN ON ARCHITECTURAL AND LIFE SAFETY PLANS. PLEASE
 COORDINATE PLANS AND SHOW PENETRATIONS TO BE PROTECTED
 IN ACCORDANCE WITH FBCM 607.5.
  
 14. PG M1-4.1: THERE IS A DELTA-13 REVISION MARK IN THE
 RISER FOR CAHU-1. THERE IS NO REVISION 13 SHOWN ON THE
 REVISION HISTORY FOR THIS PAGE. PLEASE CLARIFY.
  
 15. PG M1-4.2: RETURN DUCT SIZE FOR AHU-3 HAS BEEN
 REVISED ON THIS PAGE BUT THE CORRESPONDING DUCT HAS NOT
 BEEN REVISED ON PAGE M2-2.0. PLEASE COORDINATE PLANS
 AND RESUBMIT.
  
 16. SUPPLY AND RETURN DUCT RISER SIZES FOR RTU-1 AND
 RTU-2 HAVE BEEN REVISED ON THIS PAGE BUT HAVE NOT BEEN
 REVISED ON PAGE M1-5.2. PLEASE COORDINATE PLANS AND
 RESUBMIT.
  
 17. PG M1-5.1: THIS SHEET CONTAINS CHANGES WHICH ARE
 NOT MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS.
 PLEASE MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED
 SINCE REV. 12A. ONE EXAMPLE OF SUCH CHANGES IS CIRCLED
 ON PLAN.
  
 18. PG M2-1.0, M3-1.0, M6-1.0: THESE PAGES ARE OK BUT
 ARE BEING RETURNED TO CONTRACTOR PER THEIR REQUEST.
  
 19. PG M2-3.0: THIS SHEET CONTAINS CHANGES WHICH ARE
 NOT MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS.
 PLEASE MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED
 SINCE REV. 12A.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 14 Status P Date 2008-02-16 Cont ID  
Sent By rregueir Date 2008-02-16 Time 16:30 Rev Time 0.00
Received By rregueir Date 2008-02-16 Time 15:53 Sent To PC
Notes
2008-02-16 16:30:22REV 12C M1-1.1, M1-2,1, M4-4.0 AND SMOKE CONTROL
 RATIONAL ANALYSIS.

Review Stop M MECHANICAL (A/C)
Rev No 13 Status F Date 2008-01-02 Cont ID  
Sent By rregueir Date 2008-01-02 Time 16:21 Rev Time 0.00
Received By rregueir Date 2008-01-02 Time 16:08 Sent To PC
Notes
2008-01-02 16:21:34DUCT PARTIAL SHOP DRAWINGS DENIED. THE FOLLOWING ARE
 EXAMPLES OF CONDITIONS WHICH MAY EXIST THROUGHOUT THE
 DRAWINGS. THESE SHOP DRAWINGS WERE COMPARED TO HVAC
 REVISION #14.
  
 1. PG SM-1-4: 36X24 SUPPLY DUCT IS PENETRATING A RATED
 WALL AT ALCOVE A1.104 WITHOUT REQUIRED OPENING
 PROTECTIVES IN ACCORDANCE WITH FBC, M 607.5. THE SAME
 OPENING PROTECTIVES ARE MISSING IN REV. 14 ON PR
 M1-1.1. PLEASE CHECK ALL PENETRATIONS OF RATED
 ASSEMBLIES FOR PROPER OPENING PROTECTIVES AS REQUIRED
 BY THIS SECTION.
  
 2. PG SM-3-2: DUCTWORK IN CONFERENCE ROOMS A3.306 AND
 A3.307 DOES NOT CORRESPOND WITH WHAT IS SHOWN IN REV.14
 ON PG M1-3.1. PLEASE CHECK ALL DUCTS SHOWN CORRESPOND
 BETWEEN SHOP DRAWINGS AND SIGNED AND SEALED PLANS. WORK
 SHALL BE INSTALLED IN ACCORDANCE WITH THE REVIEWED
 CONSTRUCTION DOCUMENTS, AND ANY CHANGES MADE DURING
 CONSTRUCTION THAT ARE NOT IN COMPLIANCE WITH THE
 REVIEWED CONSTRUCTION DOCUMENTS SHALL BE RESUBMITTED
 FOR REVIEW AS AN AMENDED SET OF CONSTRUCTION DOCUMENTS
 IN ACCORDANCE WITH FBC 106.4.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 12 Status P Date 2008-01-02 Cont ID  
Sent By rregueir Date 2008-01-02 Time 15:44 Rev Time 0.00
Received By rregueir Date 2007-12-22 Time 14:22 Sent To PC
Notes
2008-01-02 15:47:18REV.14 PAGES:
 M1-1.0
 M1-2.0
 M1-3.0
 M1-4.0
 M1-5.0
 M1-6.0
 M2-1.0

Review Stop M MECHANICAL (A/C)
Rev No 11 Status F Date 2008-01-02 Cont ID  
Sent By rregueir Date 2008-01-02 Time 15:42 Rev Time 0.00
Received By rregueir Date 2007-12-22 Time 14:41 Sent To PC
Notes
2007-12-22 14:42:09REVIEW #: REV.14
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. M1-1.1: THE 36/24 SUPPLY DUCT FROM CAHU-1 HAS AT
 LEAST ONE UNPROTECTED OPENING IN THE WALL AT ALCOVE
 A1.104. SHOW OPENING PROTECTIVES (FIRE/SMOKE DAMPER) AS
 REQUIRED BY FBC, M 607.5.
  
 2. M1-1.1: THE 16/14 EXHAUST DUCT CROSSING CORRIDOR
 A1.013 HAS 2 FIRE DAMPERS WHICH HAVE BEEN CHANGED TO
 FIRE/SMOKE DAMPERS. WHY HAVE THESE CHANGED? SMOKE
 DAMPERS ARE NOT REQUIRED IN THIS DUCT AS IT MEETS
 EXCEPTION #3 UNDER FBC, M 607.5.4.
  
 3. M1-2.1: EF 17 EXHAUST DUCT HAS NO SIZE SHOWN ON
 PLANS AND THE CORRESPONDING KEY NOTE #1 IS INCORRECTLY
 IDENTIFYING THE RETURN DUCT AS EXHAUST DUCT. ALSO, ADD
 KEY NOTE #6 TO FIRE/SMOKE DAMPERS WHERE SMOKE EXHAUST
 DUCTS EXIT THE SHAFT ENCLOSURE, AS STATED IN PREVIOUS
 REVIEW OF THIS PAGE. KEY NOTE #2 IS ALSO IN THE
 INCORRECT LOCATION TO BE ASSOCIATED WITH THE SMOKE
 EXHAUST DUCT.
  
 4. M1-3.1 KEY NOTE #3, M1-4.1 KEY NOTE #5, M1-5.1 KEY
 NOTE #3, M2-3.0 KEY NOTE #6 AND M6-1.0 KEY NOTE #1 CALL
 FOR SMOKE DETECTORS AT SHAFT PENETRATIONS, PRESUMABLY
 FOR CONTROL OF FIRE/SMOKE DAMPERS. AS OF REV 12B, THESE
 DAMPERS ARE TO BE ACTUATED BY AREA SMOKE DETECTORS IN
 ACCORDANCE WITH FBC, M 607.3.2.1(5). THESE KEY NOTES
 ARE IN CONFLICT WITH REVISION 12B.
  
 5. M5-2.0: DETAIL 09, DUCT WRAP INSULATION IS SHOWN
 STOPPING AT BOTH SIDES OF THE WALL WITH AN INTERRUPTION
 OF THE VAPOR RETARDER. WHERE DUCTS USED FOR COOLING ARE
 EXTERNALLY INSULATED (WRAPPED RATHER THAN INTERNALLY
 LINED), THE INSULATION SHALL BE COVERED WITH A VAPOR
 RETARDER AND ALL JOINTS AND SEAMS SHALL BE SEALED TO
 MAINTAIN THE CONTINUITY OF THE VAPOR RETARDER IN
 ACCORDANCE WITH FBC, M 604.11 AND 304.1.
 NOTE: THE INSTALLATION OF AN AIR DISTRIBUTION SYSTEM
 SHALL NOT AFFECT THE FIRE PROTECTION REQUIREMENTS
 SPECIFIED IN THE BUILDING CODE IN ACCORDANCE WITH FBC,
 M 603.1. THEREFORE THESE REQUIREMENTS DO NOT APPLY WHEN
 THE DUCT PENETRATION OF A RATED WALL ASSEMBLY IS
 PROTECTED BY OPENING PROTECTIVES SUCH AS FIRE DAMPERS,
 SMOKE DAMPERS OR COMBINATION FIRE/SMOKE DAMPERS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2007-12-19 Cont ID  
Sent By rregueir Date 2007-12-19 Time 16:54 Rev Time 0.00
Received By rregueir Date 2007-12-19 Time 16:46 Sent To  
Notes
2007-12-19 16:54:15REV 12B PAGES:
 M1-1.2
 M1-1.3
 M1-2.3
 M1-3.2
 M1-3.3
 M1-4.3
 M1-5.3
 M4-1.0

Review Stop M MECHANICAL (A/C)
Rev No 9 Status F Date 2007-12-19 Cont ID  
Sent By rregueir Date 2007-12-19 Time 16:46 Rev Time 0.00
Received By rregueir Date 2007-12-18 Time 15:06 Sent To  
Notes
2007-12-19 16:46:00REVIEW #: 12B
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 REV 11 COMMENTS:
  
 2. M1-1.1WRITTEN RESPONSE INDICATES A FIRE DAMPER IS
 NOT REQUIRED IN THE 6X6 TRANSFER DUCT AT THE FIRE
 COMMAND CENTER (ROOM A1.120) BECAUSE THE SECTION OF
 WALL WHERE THE TRANSFER DUCT IS LOCATED IS NOT SHOWN TO
 BE FIRE RESISTANCE RATED ON THE LIFE SAFETY PLAN.
 WHETHER OR NOT IT IS SHOWN AS RATED, THE FIRE COMMAND
 CENTER IS REQUIRED TO BE SEPARATED FROM THE REMAINDER
 OF THE BUILDING BY NOT LESS THAN A 1-HOUR FIRE
 RESISTANCE RATED FIRE BARRIER IN ACCORDANCE WITH FBC
 911.1. AS SUCH THIS WALL IS REQUIRED TO BE RATED.
 THEREFORE A FIRE DAMPER IS REQUIRED PER FBC, M 607.5.
  
 5. OK
  
 6. M1-2.1: PLEASE INCLUDE KEY NOTE #6 AT THE FIRE/SMOKE
 DAMPERS WHERE THE SMOKE EXHAUST DUCTS PENETRATE THE
 SHAFT ENCLOSURE. THEY ARE REQUIRED FOR THE OPERATION OF
 THE SMOKE CONTROL SYSTEM. THEREFORE THEY SHOULD BE
 CONTROLLED IN ACCORDANCE WITH FBC, M 513.5.2.
  
 13. OK
  
 14. OK
  
 REV 10 COMMENTS:
  
 3. OK
  
 5. OK
  
 REV 12A COMMENTS:
  
 1. M4-4.0: SMOKE CONTROL SEQUENCE NOTE #4, SMOKE
 CONTROL SYSTEM SHALL ACTIVATE FROM ATRIUM SMOKE
 DETECTORS OR DETECTION OF FLOW IN THE FIRST OR SECOND
 FLOOR FIRE SPRINKLER PIPING SERVING THE ATRIUM.
  
 2. OK
  
 3. A RATIONAL ANALYSIS SUPPORTING THE TYPES OF SMOKE
 CONTROL SYSTEMS TO BE EMPLOYED, THEIR METHODS OF
 OPERATION, THE SYSTEMS SUPPORTING THEM AND THE METHODS
 OF CONSTRUCTION TO BE UTILIZED SHALL ACCOMPANY THE
 SUBMITTED CONSTRUCTION DOCUMENTS AND SHALL INCLUDE, BUT
 NOT BE LIMITED TO, THE ITEMS INDICATED IN SECTIONS
 909.4.1 THROUGH 909.4.6 IN ACCORDANCE WITH FBC 909.4.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2007-11-09 Cont ID  
Sent By rregueir Date 2007-11-09 Time 11:12 Rev Time 0.00
Received By rregueir Date 2007-11-06 Time 14:12 Sent To P
Notes
2007-11-06 15:30:42REVIEW #: 8TH
 ACTION: PASSED/DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING PAGES WERE REVIEWED FOR COMPLIANCE,
 STAMPED AND INCORPORATED INTO THE PERMIT SET OF PLANS
 AS REV 12A:
  
 M1-1.0, M1-2.0, M1-2.2, M1-3.0, M1-3.1, M1-4.0, M1-4.1,
 M1-4.2, M1-5.0, M1-5.1, M1-5.2, M1-6.0, M2-3.0, M3-1.0
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 REV. 11 COMMENTS:
  
 1. REVISION 12A WILL BE REVIEWED FOR CODE COMPLIANCE AS
 WELL AS RESPONSES TO PREVIOUS REVIEW COMMENTS FROM
 REVISIONS 10 AND 11.
  
 2. M1-1.1: AT THE FIRE COMMAND CENTER, A 6X6 TRANSFER
 DUCT HAS BEEN RELOCATED. IF THIS ROOM IS STILL ENCLOSED
 BY FIRE-RESISTANCE RATED CONSTRUCTION, THIS OPENING IS
 REQUIRED TO BE PROTECTED BY A FIRE DAMPER IN ACCORDANCE
 WITH FBC,M 607.5. ALSO, THE 50X26 SUPPLY DUCT FROM
 CAHU-1 SHOWS A TEE FITTING OVER ALCOVE A1.104. AT THIS
 LOCATION THERE ARE TWO DUCTS PENETRATING THE RATED WALL
 BUT ONLY ONE DUCT SHOWS OPENING PROTECTIVE FSD
  
 3. OK
  
 4. OK
  
 5. OK
  
 5A. M1-1.2: EF-3 DUCT PENETRATING FLOOR/CEILING
 ASSEMBLY ABOVE ROOM D1.107, IS THIS DUCT ENTERING A
 SHAFT? IF SO, PROVIDE FIRE AND SMOKE DAMPER AS REQUIRED
 BY FBC,M 607.5.5.1.
  
 6. OK, EXCEPT: KEY NOTE #6 INDICATES ONLY THE TWO
 FIRE/SMOKE DAMPERS ON THE SMOKE EXHAUST DUCT AT THE
 ?ATRIUM? ARE TO BE CONTROLLED BY THE SMOKE CONTROL
 SYSTEM. HAS THERE BEEN A RATIONAL ANALYSIS DONE TO
 DETERMINE WHICH DAMPERS SHOULD BE OPENED AND CLOSED
 DURING SMOKE CONTROL MODE? OPENINGS IN SMOKE BARRIERS
 SHALL BE PROTECTED BY AUTOMATIC-CLOSING DEVICES
 ACTUATED BY THE REQUIRED CONTROLS FOR THE MECHANICAL
 SMOKE CONTROL SYSTEM IN ACCORDANCE WITH FBC,M 513.5.2.
 THIS MAY ALSO APPLY TO THE FIRE/SMOKE DAMPERS IN THE
 SMOKE EXHAUST DUCT PENETRATIONS OF THE SHAFT
 ENCLOSURES.
  
 7. OK
  
 8. OK
  
 9. OK
  
 10. OK
  
 11. M1-2.3 WILL BE REVIEWED IN RESPONSE TOPART OF REV
 10 COMMENTS.
  
 12. OK
  
 13. M1-3.2: HOW WILL THE FIRE/SMOKE DAMPERS BE ACCESSED
 FOR SERVICE, MAINTENANCE AND TESTING ABOVE THIS STAIR
 CAP? EVEN WITH 4?9? BETWEEN THE CAP AND THE DECK ABOVE,
 AT LEAST 2 OF THE DAMPERS MAY BE RENDERED INACCESSIBLE
 BY THE ROUTING OF THE DUCTS. ALSO, IF THE STAIR CAP IS
 TO BE USED AS A SERVICE PLATFORM, IT SHALL BE REQUIRED
 TO MEET THE REQUIREMENTS FOR A SERVICE PLATFORM IN
 ACCORDANCE WITH THE FBC.
  
 14. M1-3.2: THERE IS ONE DUCT SHOWN PENETRATING
 PROGRAM/MEETING ROOM C3.306 TO FEED TWO VAV BOXES.
 WHILE THE SIZE OF THE DUCTS FEEDING THE VAV?S IS
 DETEMINED BY THE INLET SIZE ON THE VAV, A SIZE NEEDS TO
 BE PROVIDED FOR THE DUCT PENETRATING THE WALL BEFORE IT
 BRANCHES TO FEED THE TWO VAV?S. PLEASE CLARIFY. FBC,M
 603.1
  
 15. OK
  
 16. OK
  
 17. OK
  
 18. OK
  
 REV. 10 COMMENTS:
  
 1. OK
  
 2. OK
  
 3. M1-1.3 THROUGH M1-5.3: ACCORDING TO MANUFACTURER?S
 INSTALLATION INSTRUCTIONS, THE CO SENSORS ARE GOOD FOR
 APPROXIMATELY 5000 SQ FT OR A 40 FT RADIUS. BASED ON
 THE LAYOUT SHOWN ON PLANS, THERE ARE AREAS NOT
 ADEQUATELY COVERED BY THE SENSORS. SHOW DETECTORS
 LOCATED TO PROVIDE FULL COVERAGE OF THE PARKING GARAGE.
 FBC,M 304.1
  
 4. OK
  
 5. OK PENDING VERIFICATION OF INTAKE LOCATION.
  
 6. OK
  
 7. OK
  
 8. OK
  
 9. OK
  
 10. OK
  
 NEW COMMENTS RELATED TO REV. 12A:
  
 1. M4-4.0: SEQUENCE OF OPERATION NOTE #1, ACTIVATION OF
 THE SMOKE CONTROL SYSTEM SHALL BE IN COMPLIANCE WITH
 FBC 909.12.3.
  
 2. M4-4.0: SEQUENCE OF OPERATION NOTE #2, THIS NOTE IS
 IN CONFLICT WITH THE NOTE ON FLOOR PLANS WHICH
 INDICATES SMOKE DAMPERS ARE TO BE CONTROLLED BY DUCT
 SMOKE DETECTORS. ALSO, ALL SMOKE DAMPERS WHICH ARE
 RELATED TO THE SMOKE CONTROL SYSTEM AND REQUIRED BY THE
 SMOKE CONTROL SYSTEM FOR THE ATRIUM AREA SHALL BE
 CONTROLLED BY THE SMOKE CONTROL SYSTEM. FBC,M 513.5.2
  
 3. M4-4.0: SEQUENCE OF OPERATION NOTES 2 THROUGH 7: A
 RATIONAL ANALYSIS FOR THE DESIGN OF THE SMOKE CONTROL
 SYSTEM SHALL BE PROVIDED TO DETERMINE THE ACTUAL
 REQUIRED SEQUENCE OF OPERATIONS, INCLUDING SMOKE DAMPER
 ACTUATION, RELATED TO THE PROPER OPERATION OF THE SMOKE
 CONTROL SYSTEM IN ACCORDANCE WITH FBC,M 513.4.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 7 Status F Date 2007-09-15 Cont ID  
Sent By rregueir Date 2007-09-15 Time 15:28 Rev Time 0.00
Received By rregueir Date 2007-09-11 Time 17:55 Sent To  
Notes
2007-09-15 14:22:11REVISION 11 1ST REVIEW
 ACTION: DENIED
  
 FBC 2004 W/ 2005 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 NOTE: A WRITTEN DESCRIPTION OR NARRATIVE OF CHANGES
 BEING MADE AS PART OF A REVISION, WHILE NOT REQUIRED,
 WOULD BE HELPFUL IN DETERMINING THE NATURE AND EXTENT
 OF CHANGES AND WOULD HELP EXPEDITE THE REVIEW PROCESS.
 THIS IS ESPECIALLY WHEN THERE ARE SEVERAL AREAS ON
 PLANS WHICH ARE CLOUDED, YET CONTAIN NO DISCERNABLE
 DIFFERENCES FROM THE PREVIOUS PERMIT SET OF PLANS
 (REV.8).
  
 1. THERE ARE SOME MECHANICAL PAGES INCLUDED IN THIS
 REVISION WHICH WERE INCLUDED IN REV.10. COMMENTS FROM
 THE REVIEW OF REV.10 MECHANICAL PLANS HAVE NOT BEEN
 ADDRESSED. THEREFORE, ANY PAGES WHICH HAVE OUTSTANDING
 COMMENTS FROM REV.10 WILL NOT BE REVIEWED AT THIS
 TIME:
 M1-1.3, M1-2.3, M1-3.3, M1-4.3, M1-5.3
  
 THE FOLLOWING COMMENTS ARE BASED ON A SET OF REV.11
 PLANS THAT HAVE BEEN MARKED-UP TO DEMONSTRATE THE
 EXTENT AND LOCATION OF CODE DEFICIENCIES. PER A
 CONVERSATION WITH WPB FIRE MARSHAL MIKE CARSILLO AND
 GEORGE WANDOVER OF MEINHART ENGINEERS, A MEETING MAY BE
 NECESSARY TO GO OVER THE COMMENTS AND DETERMINE THE
 BEST COURSE OF ACTION IN ADDRESSING THE COMMENTS.
  
 2. M1-1.1: THERE ARE NUMEROUS DUCT PENETRATIONS AND
 TRANSFER OPENINGS WHICH ARE CURRENTLY PROTECTED BY FIRE
 DAMPERS BUT ALSO REQUIRE PROTECTION BY SMOKE DAMPERS.
 BASED ON THE LOCATION OF FIRE RATED CORRIDORS AS SHOWN
 ON LS1-1.1, SMOKE DAMPERS ARE REQUIRED AT ALL DUCT
 PENETRATIONS AND AIR TRANSFER OPENINGS IN SMOKE
 BARRIERS OR CORRIDORS WHICH REQUIRE SMOKE AND DRAFT
 CONTROL DOORS IN ACORDANCE WITH FBC, BUILDING. SEE
 FBC,M 607.5.4 AND FBC 715.3.3. AT LEAST ONE DUCT (AT
 ROOM A1.207 IS MISSING BOTH FIRE AND SMOKE DAMPERS. SEE
 MARKED-UP PLAN FOR LOCATIONS.
  
 3. M1-1.1: EXHAUST DUCTS FOR EF-1 AND EF-5 ARE
 PENETRATING A SHAFT ENCLOSURE AT THE 2ND FLOOR/CEILING
 ASSEMBLY ABOVE ROOM A1.207. THESE PENETRATIONS SHALL BE
 PROTECTED BY BOTH FIRE AND SMOKE DAMPERS IN ACCORDANCE
 WITH FBC,M 607.5.5.1. NO OPENING PROTECTIVES ARE SHOWN
 ON PLAN.
  
 4. M1-1.2: SEE COMMENT #2 REGARDING DUCT PENETRATIONS
 AND AIR TRANSFER OPENINGS PENETRATING LOBBY C1.008. SEE
 MARKED-UP PLANS FOR LOCATION.
  
 5. M1-1.2: EF-4 RISER DUCT IS REQUIRED TO BE ENCLOSED
 IN SHAFT CONSTRUCTION PER FBC 707.2. DUCTS PENETRATING
 THIS ENCLOSURE REQUIRE FIRE AND SMOKE DAMPERS AS
 OPENING PROTECTIVES PER FBC,M 607.5.5.1.
  
 6. M1-2.1: SEE COMMENT #2 REGARDING DUCT PENETRATIONS
 AND AIR TRANSFER OPENINGS PENETRATING CORRIDOR A2.007
 AND STAIR A2.003. SEE MARKED-UP PLAN FOR LOCATIONS.
  
 7. M1-2.1: THERE ARE AT LEAST 5 SMOKE DAMPERS SHOWN ON
 PLANS WHICH ARE NOT REQUIRED BY CODE AS THEY ARE NOT
 LOCATED IN EITHER A SMOKE BARRIER OR A FIRE-RATED
 CORRIDOR. SEE MARKED-UP PLANS FOR LOCATIONS. THEY MAY
 STILL BE INSTALLED IF DEEMED NECESSARY BY DESIGN.
 HOWEVER, A DETERMINATION IS NEEDED DUE TO THE
 OUTSTANDING ISSUE OF HOW SMOKE DAMPERS IN THIS BUILDING
 ARE TO BE CONTROLLED IN ACCORDANCE WITH FBC,M 607.5.4.1
 ABSENT FULL-COVERAGE SMOKE DETECTION IN THE BUILDING.
  
 8. M1-2.1: OFFICE A2.404 HAS NO SUPPLY AIR. THE SUPPLY
 DROP FOR THIS ROOM APPEARS TO HAVE BEEN MISTAKENLY
 SHOWN IN CONFERENCE A2.405. PLEASE CORRECT.
  
 9.M1-2.1: SMOKE EXHAUST DUCTS AT THE ATRIUM SHOW FIRE
 DAMPERS AT WALL PENETRATIONS. WHERE THE INSTALLATION OF
 A FIRE DAMPER WILL INTERFERE WITH THE OPERATION OF A
 REQUIRED SMOKE CONTROL SYSTEM IN ACCORDANCE WITH FBC,M
 SECTION 513, APPROVED ALTERNATIVE PROTECTION SHALL BE
 UTILIZED PER FBC,M 607.2.1. COMBINATION FIRE/SMOKE
 DAMPERS WHICH ARE CONTROLLED BY THE SMOKE CONTROL
 SYSTEM ARE CALLED FOR ON THE SMOKE CONTROL RISER
 DIAGRAM ON M4-1.0 AND WILL MEET THE REQUIREMENT FOR
 APPROVED ALTERNATIVE PROTECTION.
  
 10. M1-2.2: EF-4 RISER, EXHAUST DUCT PENETRATION OF
 SHAFT REQUIRES FIRE AND SMOKE DAMPERS AS OPENING
 PROTECTIVE PER FBC,M 607.5.5.1
  
 11. M1-2.3 WAS NOT REVIEWED. HOWEVER, SEE MARKED-UP
 PLANS FOR CONCERNS PRIOR TO RESUBMITTAL.
  
 12. M1-3.1: SEE COMMENT #7 REGARDING SMOKE DAMPERS. SEE
 MARKED-UP PLAN FOR LOCATIONS.
  
 13. M1-3.2: STAIR 10 C3.001 HAS DUCTS FROM RTU-1 ABOVE
 WITHIN THE STAIR ENCLOSURE. PENETRATIONS OF STAIR
 ENCLOSURES BY DUCTS OTHER THAN THOSE REQUIRED FOR
 INDEPENDENT PRESSURIZATIONAND VENTILATION OF THE
 STAIR ARE PROHIBITED BY FBC 1019.1.2 AND 1019.1.2.
  
 14. M1-3.2: SEE COMMENT #2 REGARDING DUCT PENETRATIONS
 AND AIR TRANSFER OPENINGS PENETRATING MULTIPLE
 CORRIDORS AND LOBBY C3.303. SEE MARKED-UP PLANS FOR
 LOCATION.
  
 15. M1-3.2: SEE COMMENT #7 REGARDING SMOKE DAMPERS. SEE
 MARKED-UP PLAN FOR LOCATIONS.
  
 16. M1-4.1: SERVER ROOM A4.416, ALL DUCT PENETRATIONS
 OF THIS ROOM EXCEPT ONE ARE PROTECTED WITH BOTH FIRE
 AND SMOKE DAMPERS. ONE TRANSFER DUCT COMMUNICATING WITH
 OPEN WORK A4.311 HAS A FIRE DAMPER BUT NO SMOKE DAMPER.
 WHAT IS THE PURPOSE OF THIS TRANSFER AND WHY DOES IT
 NOT REQUIRE THE SAME PROTECTION AS THE OTHER DUCTS?
  
 17. M1-4.1: SEE COMMENT #7 REGARDING SMOKE DAMPERS. SEE
 MARKED-UP PLAN FOR LOCATIONS.
  
 18. M1-5.1: SEE COMMENT #7 REGARDING SMOKE DAMPERS. SEE
 MARKED-UP PLAN FOR LOCATIONS.
  
 THE FOLLOWING PAGES HAVE BEEN REVIEWED FOR CODE
 COMPLIANCE AND STAMPED:
  
 M2-1.0, M2-2.0, M2-3.0, M3-1.0, M3-2.0
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2007-08-01 Cont ID  
Sent By rregueir Date 2007-08-01 Time 15:04 Rev Time 0.00
Received By rregueir Date 2007-07-31 Time 14:23 Sent To  
Notes
2007-08-01 15:03:54REVISION 10 - 1 PAGE PASSED.
  
 PG M3-1.0 REVIEWED AND STAMPED. ALL OTHER SUBMITTED
 MECHANICAL PAGES:
 ---------------DENIED-----------------
  
 FBC 2004 CODE FAMILY W/ 2005 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. WHAT IS THE HEIGHT OF FCU 1-6? SHOW COMPLIANCE WITH
 FBC,M 304.5.
  
 2. M1-1.3 THROUGH M1-5.3: GARAGE EXHAUST FANS ARE TO
 RUN INTERMITTANTLY, CONTROLLED BY C.O SENSORS. HOWEVER,
 AUTOMATIC OPERATION OF THE SYSTEM SHALL NOT REDUCE THE
 VENTILATION RATE BELOW0.05 CFM PER SQUARE FOOT OF THE
 FLOOR AREA AND THE SYSTEM SHALL BE CAPABLE OF PRODUCING
 A VENTILATION RATE OF 1.5 CFM PER SQUARE FOOT OF FLOOR
 AREA. FBC,M 404.2. THE 0.05 CFM/SQ.FT IS TO BE
 CONTINUOUS.
  
 3. M1-1.3 THROUGH M1-5.3: IN PREVIOUS REVIEW COMMENT #3
 (DATED 4/5/07), THE SPECS AND INSTALL INSTRUCTIONS FOR
 THE C.O. DETECTION SYSTEM WERE REQUESTED. THAT
 INFORMATION WAS NOT PROVIDED WITH THE SUBMITTED PLANS.
 A COMPLETE REVIEW OF THE GARAGE VENTILATION SYSTEM CAN
 NOT BE DONE AT THIS TIME.
  
 4. M1-1.3: PLEASE IDENTIFY THE LARGE PIPES RUNNING FROM
 THE MECHANICAL ROOM TO THE FIRE PUMP ROOM. PIPES ON
 RISER ARE SHOWN GOING UP BUT THEY DO NOT APPEAR ON
 UPPER FLOORS. PLEASE CORRECT. FBC 106.1.1
  
 5. M1-1.3: PLEASE SHOW HOW VENTILATION (OUTDOOR AIR) IS
 TO BE PROVIDED IN OFFICE B1-104 AND TICKET BOOTH
 B1-109.
 NOTE: TICKET BOOTHS AND SIMILAR USES THAT ARE ACCESSORY
 TO A PUBLIC GARAGE SHALL BE MAINTAINED AT A POSITIVE
 PRESSURE AND SHALL BE PROVIDED WITH VENTILATION IN
 ACCORDANCE WITH SECTION 403.3 PER FBC,M 404.3.
  
 6. M1-1.3: WHAT IS THE SOURCE OF MAKE-UP AIR FOR THE
 960 CFM OF EXHAUST IN FIRE PUMP ROOM B1-106 AND THE 875
 CFM OF EXHAUST IN FUEL TANK STORAGE B1-107? SEE FBC,M
 403.1.
  
 7. M1-1.3: ACCORDING TO PG LS1-1.0, FUEL TANK ROOM
 B1-107 IS 3-HOUR RATED. PLEASE SPECIFY A 3-HOUR
 FIRE/SMOKE DAMPER BETWEEN FUEL TANK ROOM AND FIRE PUMP
 ROOM. ALSO, A 3-HOUR FIRE DAMPER IS REQUIRED AT THE
 22X14 EXHAUST DUCT PENETRATION OF THE FLOOR/CEILING
 ASSEMBLY ABOVE THE FUEL TANK ROOM TO MAINTAIN THE
 3-HOUR RATING OF THE ROOM. FBC,M TABLE 607.3.1
  
 8. M1-2.3: PLEASE SHOW CU 1-3, 1-6, 1-7 AND ANY OTHER
 POTENTIALLY EXPOSED MECHANICAL EQUIPMENT TO BE
 PROTECTED FROM VEHICLE DAMAGE PER FBC,M 304.5.
  
 9. M1-2.3 THROUGH M1-5.3: THE 22X14 EXHAUST DUCT RISER
 SHALL BE PROTECTED FROM MECHANICAL DAMAGE BY APPROVED
 BARRIERS. FBC,M 603.13
  
 10. M3-2.0: GARAGE FAN SCHEDULE, WHAT TYPE OF WALL
 TERMINATION WILL BE USED AT EF20-23? THE SCHEDULE DOES
 NOT CALL FOR LOUVERS. SCREENS ALONE WILL NOT PROTECT
 AGAINST WEATHER CONDITIONS. FBC,M 401.6
  
 11. M4-3.0: UNABLE TO REVIEW GARAGE VENTILATION SYSTEM
 AT THIS TIME. SEE CURRENT AND PREVIOUS COMMENT #3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-04-05 Cont ID  
Sent By rregueir Date 2007-04-05 Time 16:45 Rev Time 0.00
Received By rregueir Date 2007-04-05 Time 10:42 Sent To  
Notes
2007-04-05 14:21:13ALL MECH PROVISOS DATED 1/27/07 HAVE BEEN ADEQUATELY
 ADDRESSED BY REVISION (8) SUBMITTED ON 3/21/07
 THE FOLLOWING PAGES ARE REVISED:
  
 M1-1.0
 M1-1.1
 M1-1.2
 M1-2.0
 M1-2.1
 M1-2.2
 M1-3.0
 M1-3.1
 M1-3.2
 M1-4.0
 M1-4.1
 M1-4.2
 M1-5.0
 M1-5.1

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2007-04-05 Cont ID  
Sent By rregueir Date 2007-04-05 Time 10:12 Rev Time 0.00
Received By rregueir Date 2007-04-04 Time 15:10 Sent To  
Notes
2007-04-05 10:12:41---------------DENIED------------------
  
 GARAGE REVISIONS (7) SUBMITTED 3/16/07
  
 1. NEW MECHANICAL SHEETS SUBMITTED ARE MODIFYING
 EXISTING SHEETS WHICH ALREADY COVER THE SCOPE OF
 MECHANICAL WORK IN THE PERMIT SET OF PLANS. PLEASE
 REVISE EXISTING SHEETS TO INCLUDE THE ADDED WORK OR
 SHOW THE FULL SCOPE OF WORK TO BE PERFORMED IN THESE
 AREAS ON NEW SHEETS WHICH WOULD REPLACE/SUPERCEDE
 EXISTING SHEETS.
  
 2. EQUIPMENT LOCATED IN PUBLIC GARAGES SHALL BE
 INSTALLED A MINIMUM OF 8 FEET ABOVE THE FLOOR, OR A
 MINIMUM OF 2 FEET HIGHER THAN THE HEIGHT OF THE TALLEST
 VEHICLE, OR PROTECTED FROM MOTOR VEHICLE IMPACT. FBC,M
 304.5
  
 3. PLEASE PROVIDE MANUFACTURER'S SUBMITTAL AND
 INSTALLATION INSTRUCTIONS FOR C.O. SYSTEM. FBC,M 304.1
  
 NOTE: A COMPLETE REVIEW OF THIS WORK CAN NOT BE
 PERFORMED PRIOR TO THE INCORPORATION OF ALL MECHANICAL
 WORK TO BE PERFORMED IN THESE AREAS AS STATED IN
 COMMENT #1.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-01-27 Cont ID  
Sent By pkrauss Date 2007-01-27 Time 10:12 Rev Time 0.00
Received By pkrauss Date 2007-01-27 Time 10:12 Sent To  
Notes
2007-01-27 11:01:42PROVISO:
  
 1.NON-HABITABLE ROOMS (I.E., STORAGE, ELECTRICAL,
 ETC.)ARE NOT REQUIRED TO COMPLY WITH 2004 FMC 601.4
 EXCEPTION #3.PLEASE ALSO NOTE, RETURN AIR GRILLES ARE
 INDICATED IN THESE ROOMS AND THE ARCHITECTURAL PLANS
 INDICATE NO CEILING.PLEASE REMOVE R/A GRILLES FROM
 THESE AREAS.
  
 2.PUMP ROOM A1.112 INDICATES A TRANSFER FROM THE PUMP
 ROOM INTO THE FILE ROOM.PER 2004 FMC 502.1.3,
 EQUIPMENT ROOMS THAT HOUSE SOURCES OF FUMES, ODERS OR
 NOXIOUS GASES SHALL BE DESIGNED TO AND CONSTRUCTED SO
 AS TO PREVENT SPREADING OF SUCH CONTAMINANTS TO OTHER
 OCCUPIED PARTS OF THE BUILDING.
  
 3.PLEASE PROVIDE DUCT SIZES TO VAV'S.
  
 4.MANY OF THE NON-HABITABLE ROOMS INDICATE RETURN AIR
 GRILLES TO THE PLENUM.ACCORDING TO THE ARCHITECTURAL
 DRAWINGS THESE ROOMS HAVE NO CEILING.PLEASE REMOVE
 RETURN AIR GRILLES FROM THESE AREAS IF IN FACT THEY DO
 NOT GO INTO THE RETURN AIR PLENUM.
  
 5.ADDITIONAL PERMITS REQUIRED FOR FUEL PIPING.
  
 PLEASE SEE ELECTRICAL COMMENTS FOR SIZING OF THE DIESEL
 FUEL TANKS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT HAROLD MOSER
 AT (561)805-6732 OR E-MAIL [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-12-26 Cont ID  
Sent By pkrauss Date 2006-12-26 Time 13:11 Rev Time 0.00
Received By pkrauss Date 2006-12-26 Time 11:47 Sent To  
Notes
2006-12-26 13:25:55DENIED:
 RESPONSE TO COMMENTS DATED 11-07-06:
  
 COMMENT 1:OK
 COMMENT 2A & 2B:OK
  
 COMMENT 2C:RESPONSE INDICATES THE CAPACITY OF THE
 FUEL STORAGE TANK LOCATED ON THE FIRST FLOOR IS 500
 GALLONS. THE SUBMITTAL BOOK REFLECTS (2) DAY TANKS ONE
 WITH THE CAPAPCITY OF 100 GALLONS AND THE SECOND ONE
 WITH A CAPACITY OF 150 GALLONS.PLEASE SUBMIT THE
 CORRECT SUBMITTAL FOR THE DAY TANK.
  
 COMMENT 3:OK
  
 COMMENT 9:OK
  
 COMMENT 10:OK
  
 COMMENT 11:OK
  
 COMMENT 12:OK
  
 COMMENT 13:OK
  
 COMMENT 14:OK
  
 COMMENT 15:OK
  
 COMMENT 16:RESPONSE INDICATES FIRE RATINGS ARE NOT
 REQUIRED FOR ELECTRICAL RM.SMOKE RATING IS INDICATED
 FOR THE MECHANICAL ROOM AND A 1 HR RATING FOR THE
 ELEVATOR EQUIPMENT RM.PER 2004 FMC 607.8,SMOKE
 DAMPERS, FIRE DAMPERS AND COMBINATION DAMPERS ARE TO BE
 IDENTIFIEDON THE BUILDING PLANS.PLEASE NOTE, LIFE
 SAFETY PLANS IDENTIFY CERTIAN WALLS/PARTITIONS AS
 HAVING A FIRE, SMOKE OR FIRE/SMOKE RATING THAT ARE NOT
 REFLECTED ON THE ARCHITECTURAL PLANS.PLEASE CORRELATE
 LIFE SAFETY, ARCHITECTURAL AND MECHANICAL PLANS. PLEASE
 SEE ?ADDITIONAL COMMENT #21?.
  
 COMMENT 17:OK
  
 COMMENT 18:OK
  
 COMMENT 19:OK
  
 COMMENT 20:OK
 ADDITIONAL COMMENTS:
  
 21.THE FOLLOWING PLAN SHEET & ROOM NUMBERS ARE
 MISSING DAMPERS AS REQUIRED PER 2004 FMC 607.5.4 &
 607.5.4.1:
  
 DWG M1-1.1; RM# - A1.014, A1.118, A1.110
 DWG M1-2.1; RM# - C1.101, D1.108, A1.110, D1.111.
  
 PLEASE ALSO NOTE ON DWG #M1-1.2, THE OUTSIDE AIR INTAKE
 TO THE WEST EXTERIOR WALL.PER 2004 FMC 401.5.1,
 INTAKE OPENINGS SHALL BE LOCATED A MINIMUM OF 10 FT
 FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS
 STREETS, ALLEYS, PARKING LOTS OR LOADING DOCKS.
  
 DWG M1-2.1 CORRIDOR A2.010, 38/18 & 12/10 DUCT,RM #
 A2.104, A2.108, A2.407, A2.08, A2.409
 DWG M1-2.2 RM# C2.101, C2.219, D2.108
 DWG M1-3.1 CORRIDOR A3.008, A3.012, A3.406, A3.308,
 A3.706, C3.414 RM# A3.107, A3.106, A3.421, A3.420,
 A3.105, A3.104, A3.304, A3.205, C3.314, C3.413, A3.705,
 A3.603, A3.115, A3.514, A3.513
 DWG M1-3.2 CORRIDOR C3.417, C3.407, C3.426, RM# C3.418,
 C3.310, C3.309, C3.402, C3.107,C3.101
 DWG M1-4.1 CORRIDOR A4.009, A4.008, A4.007 RM#A4.415,
 A4.101 & F/D FROM RM# A4.416.
 DWG M1-4.2 RM# C4.106, C4.104.PLEASE NOTE, MECHANICAL
 FLOOR PLAN DOES NOT MATCH THE LIFE SAFETY PLAN FOR THIS
 PARTICULAR FLOOR.THE VOICE DATA RM & ELECTRICAL RM
 ARE NOT INDICATED ON THE MECHANICAL SHEET.
  
 DWG M1-5.1 CORRIDOR A5.009, A5.008, A5.007 RM# A5.303,
 A5.203, A5.101, A5.507, A5.107, A5.416
  
 22.PLAN SHEET M1-1.0 KEY NOTE 1 SPECIFIES THE
 CONDENSATE TO MOP SINK IN THE GARAGE AREA.PER CITY
 CODE SEC. 90-125(5) CONDENSATE SHALL NOT TERMINATE INTO
 THE SANITARY.PLAN SHEET P1-10U INDICATES THE
 CONDENSATE TO A DRYWELL WHICH IS CODE COMPLIANT. PLEASE
 CORRELATE MECHANICAL PLAN WITH PLUMBING PLAN.
  
 ADDITIONAL PERMIT REQUIRED FOR FUEL PIPING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].
  
  
  
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-11-07 Cont ID  
Sent By pkrauss Date 2006-11-07 Time 15:32 Rev Time 0.00
Received By pkrauss Date 2006-11-07 Time 15:32 Sent To  
Notes
2006-11-07 16:00:24DENIED:
 RESPONSE TO COMMENTS FROM PREVIOUS REVIEW THAT WERE NOT
 ADDRESSED:
  
 PLEASE NOTE, RESPONSE TO COMMENTS 1, 2 & 3 STATES
 INFORMATION WILL BE PROVIDED WITH 100% DOCUMENTATION.
 ******************************************************
 *
 COMMENT 1:REQUEST FOR ENERGY & SIZING CALCULATIONS IN
 ACCORDANCE WITH 2004 FBC CHAPTER 13 SUB-CHAPTER 13-4.
  
 RESPONSE INDICATES CALCS WILL BE PROVIDED WITH 100%
 DOCUMENTS.
  
 COMMENT 2:REQUEST FOR INFORMATION IN RELATION TO THE
 FUEL TANK & DIESEL FIRE PUMPS
 A) VENTILATION FOR THE ROOM (EXHAUST FANS WERE
 INDICATED WITH NO VENTILATION CALCS).PLEASE REFERENCE
 2004 FMC 502.1.2 THROUGH 502.1.4 & NFPA 37-6.3.5.4
 THROUGH 6.3.5.4.3.
  
 B) DISTANCE TO PROPERTY LINES WITH RELATION TO THE
 TERMINATION OF EXHAUST.
  
 C) CAPACITY OF THE FUEL TANKS.THE SUBMITTAL BOOK
 INDICATES (1) 100 GAL, (1) 150 GAL, & (1) 500 GAL
 SUB-BASE FUEL TANK.PLANS DO NOT CORRELATE WITH
 SUBMITTAL BOOK. SUBMITTAL BOOK INDICATES 500 GAL
 SUB-BASE FUEL TANK, PLAN SHEET P3-4.0 DETAIL 03 SHOWS
 THE 500 GAL TANK AT THE GROUND LEVEL WITH A DAY TANK ON
 THE ROOF.PLAN SHEET P1-6.0 INDICATES THE GENERATOR
 AS "NATURAL GAS". PLEASE CLARIFY.PLEASE ALSO NOTE,
 PLAN SHEET P-3.40 PROVIDES A SCHEMATIC FOR THE DIESEL
 FUEL PIPING, SUPPLY, RETURN, & VENT PIPING SHOWN ON
 SHEETS P1-1.0, P1-2.0, P1-3.0, P1-4.0, P1-5.0 & P1-6.0.
 DIESEL FUEL SUPPLY AND RETURN PIPING ARE NOT DEPICTED
 ON PLAN SHEET P1-6.0 ONLY THE VENT PIPING.PLAN SHEE
 P1-6.0 SHOWS THE NATURAL GAS SUPPLYING FUEL TO THE
 GENERATOR.THIS DOES NOT CORRELATE WITH THE SUBMITTAL
 BOOK.PLEASE NOTE, PER NFPA 37-6.3.5.3 ROOMS HOUSING
 FUEL TANKS WITH AN AGGREGATE CAPACITY LESS THAN 1320
 GAL, EACH TANK ROOM SHALL BE PROVIDED WITH SPILL
 CONTAINMENT CONSISTING OF EITHER A WALL, CURB, OR DIKE
 HAVING A CAPACITY AT LEAST EQUAL TO THAT OF THE LARGEST
 TANK.FUEL TANKS LOCATED ON THE ROOF SHALL COMPLY
 WITH NFPA 37-6.3.4 THROUGH 6.3.4.2.
  
 COMMENTS 10 & 11 NO RESPONSE WAS GIVEN.
  
 COMMENT 3 & 15:FIRE & FIRE/SMOKE DAMERS AT SHAFT
 PENETRATIONS.PLEASE INDICATE DAMPERS ON THE RISERS AS
 REQUESTED IN PREVIOUS REVIEW.
  
 COMMENT 9:PLAN SHEET M1-1.3 PROVIDE ELEVATION OF THE
 MAKE -UP AIR AND EXHAUST FROM MECHANICAL ROOM B1.102
 THE REPONSE SENTENCE WAS NOT COMPLETE AND DID NOT
 PROVIDE ELEVATION.
  
 COMMENTS 10 & 11 NO RESPONSE WAS GIVEN.
  
 COMMENT 12:THE EQUIPMENT SCHEDULE WAS PROVIDED BUT
 THE CHILLER SCHEDULE ON SHEET M3-2.0 ANNOTATES ALL
 CHILLERS AS CH-1 NOT CH-1, CH-2, CH-3
  
  
 NEW COMMENTS:
 13.PLEASE PROVIDE SEQUENCE OF OPERATION FOR THE SMOKE
 CONTROL OR EVAC IN ACCORDANCE WITH 2004 FMC 513 OR
 CHAPTER 909 OF THE FBC.
  
 14.PLEASE PROVIDE VENTILATION CALCS FOR THE GARAGE
 PER 2004 FMC 404.
  
 15.PLEASE INDICATE THE VOLUME OF THE ATRIUM.
  
 16.PLAN SHEET M1-1.1, FIRE DAMPERS ARE MISSING FROM
 ELECTRICAL ROOM A1.102.PLEASE VERIFY FIRE DAMPERS,
 FOR ALL ELECTRICAL, MECHANICAL AND STORAGE ROOMS.
  
 17.PLAN SHEET M1-2.2, SUPPLY/RETURN TO AHU-2 &
 EXHAUST DUCT (EF-4), SHAFT IS NOT LARGE ENOUGH TO
 ENCLOSE THESE DUCTS.PLEASE NOTE, DUCTS SHALL HAVE
 SUFFICIENT CLEARANCE FOR INSTALLATION & INSPECTION PER
 2004 FMC 603.1.3.
  
 18.PLEASE PROVIDE ANCHORING DETAIL FOR INSTALLATION
 OF THE COOLING TOWERS PER 2004 FBC 106.1.1.2 , 1509.4 &
 1509.7.
  
 19.PROVIDE DETAIL FOR ANCHORING & VIBRATION ISOLATION
 ON ALL MOUNTED EQUIPMENT.
  
 20.PLAN SHEET M5-3.0 DETAIL 6 SHOWS 1" INSULATION ON
 THE 4"CHILLED WATER PIPING.WILL THE INSULATION
 INCREASE TO 2" ON THE LARGER PIPING?
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].
  

Review Stop P PLUMBING
Rev No 35 Status P Date 2009-05-01 Cont ID  
Sent By kstevens Date 2009-05-01 Time 16:12 Rev Time 0.00
Received By kstevens Date 2009-05-01 Time 16:12 Sent To  
Notes
2009-05-01 16:12:53REVISIONS OK -- SHTS P2-1.0U & P3-1.0

Review Stop P PLUMBING
Rev No 34 Status P Date 2009-04-02 Cont ID  
Sent By kstevens Date 2009-03-31 Time 09:34 Rev Time 0.00
Received By kstevens Date 2009-03-31 Time 09:34 Sent To  
Notes
2009-03-31 09:34:19REVISION PASSED/PROVISO:
  
 ***REVISION REQUIRED***
  
  
 1. SHTS P2-1.0U P3-1.0 THE MOP SINK SHALL CONNECT TO
 THE GREASE SYSTEM, NOT THE SANITARY SYSTEM. SECTION
 1003.3.1. -- ALSO THE MOP SINK SHALL NOT DRAIN THRU THE
 WET VENT FOR THE BATHROOM FIXTURES PER SECTION 909.1.
 -- PLANS RED LINED WITH REVISION TO FOLLOW.
  
  
  
  

Review Stop P PLUMBING
Rev No 33 Status P Date 2009-03-31 Cont ID  
Sent By kstevens Date 2009-03-31 Time 08:48 Rev Time 0.00
Received By kstevens Date 2009-03-31 Time 08:48 Sent To  
Notes
2009-03-31 09:35:33REVISIONS OK -- SHTS P2-1.0 & P3-5.0

Review Stop P PLUMBING
Rev No 32 Status P Date 2009-01-21 Cont ID  
Sent By kstevens Date 2009-01-21 Time 10:02 Rev Time 0.00
Received By kstevens Date 2009-01-20 Time 16:58 Sent To  
Notes
2009-01-21 10:02:52REVISION OK -- SHT IR-1 -- REVISIONS 11 & 16B NOT FOUND
 OR APPROVED.

Review Stop P PLUMBING
Rev No 31 Status F Date 2009-01-20 Cont ID  
Sent By kstevens Date 2009-01-20 Time 16:35 Rev Time 0.00
Received By kstevens Date 2009-01-20 Time 16:35 Sent To  
Notes
2009-01-20 16:38:12DENIED
 REFERENCE:
 FBC-2004 CHAPTER 1
 FBC-2004 PLUMBING
  
 1. SHT P1-2.2 REVISION INDICATED ABOVE THE MATCH LINE
 IS NOT APPROVED FOR THIS SHEET. SUBMIT REVISIONS FOR
 SHEET P1-2.1 & P1-2.2 WITH THE REVISION FOR EACH SHEET
 AS REQUIRED. SECTION 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 30 Status P Date 2009-01-20 Cont ID  
Sent By kstevens Date 2009-01-20 Time 16:34 Rev Time 0.00
Received By kstevens Date 2009-01-20 Time 16:34 Sent To  
Notes
2009-01-20 16:35:40REVISIONS OK -- SHTS P2-2.0, P3-2.0 & P3-6.0.

Review Stop P PLUMBING
Rev No 29 Status P Date 2009-01-20 Cont ID  
Sent By kstevens Date 2009-01-20 Time 15:57 Rev Time 0.00
Received By kstevens Date 2009-01-20 Time 15:56 Sent To  
Notes
2009-01-20 16:02:39REVISIONS OK -- SHTS P1-1.0U, P1-1.0, P1-1.2U, P1-1.2,
 P2-1.0, P2-1.0U & P3-1.0

Review Stop P PLUMBING
Rev No 28 Status P Date 2009-01-20 Cont ID  
Sent By kstevens Date 2009-01-20 Time 13:52 Rev Time 0.00
Received By kstevens Date 2009-01-20 Time 13:52 Sent To  
Notes
2009-01-20 13:53:04REVISION OK -- SHT P1-1.3

Review Stop P PLUMBING
Rev No 27 Status P Date 2009-01-20 Cont ID  
Sent By kstevens Date 2009-01-20 Time 13:37 Rev Time 0.00
Received By kstevens Date 2009-01-20 Time 13:37 Sent To  
Notes
2009-01-20 13:39:29REVISION OK -- SHTS P1-1.0 & P1-1.0U

Review Stop P PLUMBING
Rev No 26 Status F Date 2008-11-25 Cont ID  
Sent By kstevens Date 2008-11-25 Time 16:29 Rev Time 0.00
Received By kstevens Date 2008-11-25 Time 16:29 Sent To  
Notes
2008-11-25 16:32:06REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P1-1.0U REVISION INDEX & FLOOR PLAN FROM
 PREVIOUS SHEET SIGNED, SEALED & DATED ON 9-17-08
 INDICATES REVISION 193R3 DATED 9-16-08. NEW REVISIED
 SHEET SUBMITTED DELETED REVISION 193R3 AND NOW SHOWS
 REVISION 193R4 DATED 10-30-08 BUT NO CLOUD FOR NEW
 REVISION. PER SECTION 106.1.3 COMPLETE REVISION RECORD
 IS REQUIRED AND ALL NEW REVISIONS SHALL BE INDIDCATED
 WITH A CLOUD AND REVISION NUMBER SHOWING WHERE THE NEW
 REVISION CAN BE LOCATED. -- THIS HAS BEEN INDICATED IN
 A PREVIOUS REVISION REVIEW.
  
 2. SHT P1-1.0 REVISION INDEX & FLOOR PLAN FROM PREVIOUS
 SHEET SIGNED, SEALED & DATED ON 9-17-08 INDICATES
 REVISION 193R3 DATED 9-16-08. NEW REVISIED SHEET
 SUBMITTED DELETED REVISION 193R3 AND NOW SHOWS REVISION
 193R4 DATED 10-30-08 BUT NO CLOUD FOR NEW REVISION. PER
 SECTION 106.1.3 COMPLETE REVISION RECORD IS REQUIRED
 AND ALL NEW REVISIONS SHALL BE INDIDCATED WITH A CLOUD
 AND REVISION NUMBER SHOWING WHERE THE NEW REVISION CAN
 BE LOCATED. -- THIS HAS BEEN INDICATED IN A PREVIOUS
 REVISION REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 25 Status P Date 2008-11-25 Cont ID  
Sent By kstevens Date 2008-11-25 Time 16:29 Rev Time 0.00
Received By kstevens Date 2008-11-25 Time 16:29 Sent To  
Notes
2008-11-25 16:29:33REVISION OK -- SHT P1-1.2

Review Stop P PLUMBING
Rev No 24 Status F Date 2008-11-17 Cont ID  
Sent By kstevens Date 2008-11-17 Time 09:50 Rev Time 0.00
Received By kstevens Date 2008-11-17 Time 09:50 Sent To  
Notes
2008-11-17 10:57:12REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P1-1.0U REVISION INDEX & FLOOR PLAN FROM
 PREVIOUS SHEET SIGNED, SEALED & DATED ON 9-17-08
 INDICATES REVISION 193R3 DATED 9-16-08. NEW REVISIED
 SHEET SUBMITTED DELETED REVISION 193R3 AND NOW SHOWS
 REVISION 193R4 DATED 10-30-08 BUT NO CLOUD FOR NEW
 REVISION. PER SECTION 106.1.3 COMPLETE REVISION RECORD
 IS REQUIRED AND ALL NEW REVISIONS SHALL BE INDIDCATED
 WITH A CLOUD AND REVISION NUMBER SHOWING WHERE THE NEW
 REVISION CAN BE LOCATED.
  
 2. SHT P1-1.0U 2-WAY CLEANOUTS ARE REQUIRED AS THE
 GREASE LINE EXITS THE BUILDING AND BEFORE THE INLET OF
 THE GREASE INTERCEPTOR AND ON THE OUTLET OF THE GREASE
 INTERCEPTOR. THE GREASE INTERCEPTOR PRIOR TO THE GREASE
 INTERCEPTOR OUTLET CAN BE USED FOR BOTH THE INLET
 REQUIREMENT AND THE REQUIREMENT AS THE GREASE LINE
 EXITS THE BUILDING. SECTION 708.3.5 & UTILITY DEPT
 GREASE INTERCEPTOR STANDARD.
  
 3. SHT 1-1.0U 2-WAY CLEANOUTS ARE REQUIRED ON THE INLET
 AND OUTLET OF THE GREASE INTERCEPTOR. UTILITY DEPT
 GREASE INTERCEPTOR STANDARD.
  
 4. SHT P1-1.0 REVISION INDEX & FLOOR PLAN FROM PREVIOUS
 SHEET SIGNED, SEALED & DATED ON 9-17-08 INDICATES
 REVISION 193R3 DATED 9-16-08. NEW REVISIED SHEET
 SUBMITTED DELETED REVISION 193R3 AND NOW SHOWS REVISION
 193R4 DATED 10-30-08 BUT NO CLOUD FOR NEW REVISION. PER
 SECTION 106.1.3 COMPLETE REVISION RECORD IS REQUIRED
 AND ALL NEW REVISIONS SHALL BE INDIDCATED WITH A CLOUD
 AND REVISION NUMBER SHOWING WHERE THE NEW REVISION CAN
 BE LOCATED.
  
 5. SHT P1-1.0 CHANGES TO THE CONDENSATE HAVE BEEN FOUND
 WITHOUT CLOUDS OR INDICATED BY REVISION NUMBERS. SHOW
 ALL CHANGES WITH CLOUDS AND REVISION NUMBERS. SECTION
 106.1.3. PLEASE INDICATE ALL CHANGES/REVISIONS ON THE
 SHEET WITH A CLOUD AND A REVISION NUMBER.
  
 6. SHT P1-1.2U 2-WAY CLEANOUTS ARE REQUIRED ON THE
 INLET AND OUTLET OF THE GREASE INTERCEPTOR. UTILITY
 DEPT GREASE INTERCEPTOR STANDARD.
  
 7. SHT P1-1.2 THE 2" GOOSENECK VENT FOR THE GREASE
 INTERCEPTOR IS NOT REQUIRED AS THE INLET LINE TO THE
 INTERCEPTOR IS A VENTED LINE. IF THE VENT IS INSTALLED
 IT SHALL BE TERMINATED PER SECTIONS 904.5 & 904.6.
  
 8. SHT P2-1.0 DETAIL 5 SHOWS CHANGES WITH NO CLOUDS OR
 REVISION NUMBERS INDICATING THE LOCATION OF THE
 REVISIONS. REVISIONS 1 & 2 WERE DELETED AND A REVISION
 DATED 12-06-07 IS INDICATED WITHOUT A REVISION NUMBER.
 PLEASE CLARIFY. SECTION 106.1.3. PLEASE INDICATE ALL
 CHANGES/REVISIONS ON THE SHEET WITH A CLOUD AND A
 REVISION NUMBER.
  
 9. SHT P2-1.0U DETAIL 5 SHOWS CHANGES WITH NO CLOUDS OR
 REVISION NUMBERS INDICATING THE LOCATION OF THE
 REVISIONS. REVISIONS 1 & 2 WERE DELETED PLEASE CLARIFY.
 SECTION 106.1.3. PLEASE INDICATE ALL CHANGES/REVISIONS
 ON THE SHEET WITH A CLOUD AND A REVISION NUMBER.
  
 10. SHT P3-1.0 A CLEANOUT IS REQUIRED NEAR THE JUNCTION
 OF THE BUILDING GREASE DRAIN AND THE BUILDING SEWER
 GREASE PER SECTION 708.3.5. PLEASE SHOW ON THE RISER
 DIAGRAM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 23 Status P Date 2008-11-17 Cont ID  
Sent By kstevens Date 2008-11-17 Time 09:49 Rev Time 0.00
Received By kstevens Date 2008-11-14 Time 16:53 Sent To  
Notes
2008-11-17 09:50:16REVISION OK -- SHT P3-5.0

Review Stop P PLUMBING
Rev No 22 Status F Date 2008-10-28 Cont ID  
Sent By kstevens Date 2008-10-28 Time 07:31 Rev Time 0.00
Received By kstevens Date 2008-10-28 Time 07:30 Sent To  
Notes
2008-10-28 07:45:35REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 MECHANICAL
  
 1. SHT P1-1.3 INDICATES REVISION TO THE DIESEL FUEL
 SYSTEM FOR THE GENERATORS. THE DIESEL FUEL SYSTEM IS A
 MECHANICAL PERMIT AND ALL CHANGES TO THE DIESEL SYSTEM
 SHALL BE SUBMITTED ON THE MECHANICAL SHEETS. THE DIESEL
 SYSTEM IS INSPECTED FROM THE MECHANICAL SHEETS BY THE
 MECHANICAL INSPECTOR. SECTION 915.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 21 Status F Date 2008-09-29 Cont ID  
Sent By kstevens Date 2008-09-29 Time 08:24 Rev Time 0.00
Received By kstevens Date 2008-09-29 Time 08:24 Sent To  
Notes
2008-09-29 08:27:58 
 SUBMITTAL FOR PLANTER WALL DETAIL -2 DENIED. THE
 WATERPROOFING & PROTECTION BOARD IS NOT SHOWN TO THE
 BASE OF THE FOOTER OR UP TO THE SAME HEIGHT AS
 INDICATED IN THE MEETING WITH DAVID MORRIS IN THE LOBBY
 OF CONSTRUCTION SERVICES ON 9-16-8. THIS REQUIRED FOR
 THE APPROVAL OF THE CONDENSATE TO DRAIN INTO THE
 PLANTER.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 20 Status P Date 2008-09-26 Cont ID  
Sent By kstevens Date 2008-09-26 Time 16:54 Rev Time 0.00
Received By kstevens Date 2008-09-26 Time 16:54 Sent To  
Notes
2008-09-26 16:56:48REVISIONS OK -- SHTS P1-1.0U, P1-1.0 & P1-5.1

Review Stop P PLUMBING
Rev No 19 Status F Date 2008-08-29 Cont ID  
Sent By kstevens Date 2008-08-29 Time 11:09 Rev Time 0.00
Received By kstevens Date 2008-08-28 Time 14:12 Sent To  
Notes
2008-08-29 13:57:45REVISIONS DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 NFPA-101
  
 1. SHTS P1-1.0 & P1-1.0U. REVISION 12A NOT FOUND, NOT
 CLOUDED. REVISION NUMBER SHALL BE LEGIBLE ON FLOOR
 PLAN. ALL REVISIONS SHALL BE CLOUDED. SEE COMMENT 3
 FROM PREVIOUS REVIEW. SECTION 106.1.3.
  
 2. SHTS P1-1.0U, P1-1.0 & P1-1.2. SUBMIT A DETAIL FOR
 THE PLANTER ON THE WEST SIDE OF THE COURTYARD. INDICATE
 HOW THE STORM WATER AND THE CONDENSATE WILL NOT DRAIN
 TO THE FOOTER AREA OF THE OUTSIDE WALL TO COMPLY WITH
 SECTION 1503.6. BY HAVING THE PLANTER OPEN AT THE
 BOTTOM, THE INTENT OF THE CODE IS NOT BEING MET.
  
 3. SHTS P1-4.0, P1-4.2 & P3-7.0. PIPING FROM THE ROOF
 DRAIN, (6" RD 1865SF), NOT APPROVED IN THE EXIT
 STAIRWELL. NFPA 101 SECTION 7.1.3.2.1(6).
  
 4. SHT P1-5.1. REVISION 193 SUBMITTED AND PLANS SIGNED,
 SEALED & DATED ON 05-09-08 NOT SHOWN ON REVISION
 SUBMITTED ON 08-21-08. ALSO CHANGES TO LATEST REVISION
 ARE NOT CLOUDED NOR NUMBERED WITH A REVISION NUMBER.
 (HUB DRAINS DELETED). SECTION 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 18 Status P Date 2008-08-29 Cont ID  
Sent By kstevens Date 2008-08-29 Time 11:08 Rev Time 0.00
Received By kstevens Date 2008-08-28 Time 14:12 Sent To  
Notes
2008-08-29 11:09:04REVISIONS OK -- SHTS P1-1.1, P1-1.1U, P1-1.2U, P1-4.1,
 P1-5.0 & P1-6.0.

Review Stop P PLUMBING
Rev No 17 Status F Date 2008-07-18 Cont ID  
Sent By kstevens Date 2008-07-18 Time 08:10 Rev Time 0.00
Received By kstevens Date 2008-07-18 Time 08:10 Sent To  
Notes
2008-07-18 08:54:08REVISIONS DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P1-1.0 REVISION 193R SHOWS A 2" CONDENSATE FROM
 AHU-1 CONNECTING TO A 1" CONDENSATE LINE THAT SNAKES
 OVER TO A PLANTER & DISCHARGES MINIMUM 12" AWAY FROM
 THE BUILDING WALL. FITTINGS SHOULD BE USED WHEN
 CHANGING DIRECTION ON DRAINAGE PIPE. SECTION 706.1.--
 THE SIZE OF THE DRAINAGE PIPING SHALL NOT BE REDUCED IN
 SIZE IN THE DIRECTION OF FLOW. SECTION 704.2.--MORE
 INFORMATION IS REQUIRED. IF THE CONDENSATE WILL BE
 DRAINING 24 HOURS, 365 DAYS A YEAR, WHERE WILL THE
 CONDENSATE WATER DRAINING INTO THE PLANTER GO? IS THE
 PLANTER SEALED OFF FROM THE BUILDING WALL WITH A
 FLASHING OR SOME OTHER FORM OF WATER PROOFING?--IF
 THE EXCESS WATER REMAINS IN THE PLANTER, WILL THIS
 CAUSE ROOT ROT ON THE REQUIRED PLANTS?--ALSO ALL
 CHANGES TO THE CONDENSATE SYSTEM SHALL BE REFLECTED ON
 THE CONDENSATE RISER DIAGRAM. SECTIONS 106.1.1, 106.1.2
 & 1503.6.
  
 2. SHT P1-1.0 REVISIONS 193 & 193RSHOWS THE
 CONDENSATE LINE SNAKING TO 1" DC DOWN.FITTINGS SHOULD
 BE USED WHEN CHANGING DIRECTION ON DRAINAGE PIPE.
 SECTION 706.1.
  
 3. SHT P1-1.01 PLANS STAMPED AND ISSUED 2-21-05 SHOW
 REVISIONS 1, 2, 4 & 5 IN THE REVISION INDEX. THE NEW
 REVISED SHEET SUBMITTED DOES NOT INDICATE REVISION 1
 AND SHOWS REVISIONS 12A & 193R. REVISION 12A IS NOT
 CLOUDED AND THE NUMBER IS NOT LEGIBLE IN THE TRIANGLE
 WHICH MAY OR MAY NOT BE REVISION 12A. PLEASE CLOUD ALL
 REVISIONS TO BE SUBMITTED AND MAKE SURE THE REVISION
 NUMBERS IN THE TRIANGLES ARE LEGIBLE. ALSO MAKE SURE
 THE REVISION INDEX SHOWS ALL REVISIONS RELATED TO THE
 SHEET. SECTIONS 106.1.1, 106.1.2 & 106.1.3.
  
 4. SHT P1-1.1 REVISIONS 193 & 193R FITTINGS SHOULD BE
 USED WHEN CHANGING DIRECTION ON DRAINAGE PIPE. SECTION
 706.1.
  
 5. SHT P1-1.1U REVISIONS 1 & 2 ARE NOT SHOWN ON THE
 REVISION INDEX AND REVISION 193R SHOWN ON THE FLOOR
 PLAN IS NOT SHOWN ON THE REVISION INDEX. PLEASE
 CORRELATE ALL REVISIONS AND THE REVISION INDEX. ALSO
 ALL REVISIONS ON PREVIOUSLY REVIEWED SHEETS SHALL
 REMAIN ON THE REVISION INDEX THRU THE LIFE OF THE PLANS
 TO TRACK ALL REVISIONS AND FOR PUBLIC RECORD. SECTION
 1106.1.3.
  
 6. SHT P1-1.2U REVISION 1 MISSING FROM THE REVISION
 INDEX. ALL REVISIONS ON PREVIOUSLY REVIEWED SHEETS
 SHALL REMAIN ON THE REVISION INDEX THRU THE LIFE OF THE
 PLANS TO TRACK ALL REVISIONS AND FOR PUBLIC RECORD.
 SECTION 1106.1.3.
  
 7. SHT P1-1.2 REVISIONS 11, 12 & 193 SHOWN IN THE
 REVISION INDEX ARE NOT SHOWN ON THE FLOOR PLAN. PLEASE
 CORRELATE. ALSO CLOUD AND NUMBER ALL REVISIONS
 SUBMITTED AFTER THE PREVIOUSLY REVIEWED SHEET.
  
 8. SHT P1-3.1 NO REVISION SHOWN. NO CHANGE FROM
 PREVIOUSLY REVIEWED SHEET. SECTION 106.1.3.
  
 9. SHT P1-4.0 REVISIONS NOT CLOUDED AT THE NEW ROOF
 DRAIN LOCATIONS.--ALSO THE RWL SIZE IS NOT LEGIBLE
 AT COLUUM LINES 8/L & 8/H. PLEASE CLARIFY. SECTION
 106.1.1 & TABLE 1106.3.
  
 10. SHT P1-4.1 REVISION 190 NOT FOUND ON THE FLOOR PLAN
 & REVISIONS 1 & 2 HAVE BEEN DELETED FROM THE REVISION
 INDEX. PLEASE CORRELATE AND ALL REVISIONS ON PREVIOUSLY
 REVIEWED SHEETS SHALL REMAIN ON THE REVISION INDEX THRU
 THE LIFE OF THE PLANS TO TRACK ALL REVISIONS AND FOR
 PUBLIC RECORD. SECTION 1106.1.3.
  
 11. SHT P1-4.2 REVISIONS NOT CLOUDED IN MANY AREAS. BE
 SURE TO CLOUD ALL REVISIONS SUBMITTED AFTER THE LAST
 REVIEWED/STAMPED SET OF REVISIONS. SECTION 106.1.3.
  
 12. SHT P1-5.0 NO REVISION NUMBER INDICATED FOR CLOUDED
 REVISIONS BETWEEN COLUUM LINES 1/H-L & 10/H-L. PLEASE
 NUMBER ALL REVISIONS. ALSO NO CHANGE NOTED FOR CLOUDED
 REVISION AT COLUUM LINES 6/C-D1 & B/6-8. PLEASE
 CORRELATE. SECTION 106.1.3.--PIPING FOR THE
 CONDENSATE SNAKING FROM RISER TO UNIT.FITTINGS SHOULD
 BE USED WHEN CHANGING DIRECTION ON DRAINAGE PIPE.
 SECTION 706.1.
  
 13. SHTP3-7.0 REVISIONS SHOWN ON RWL'S 5, 6 & 7 WITH
 CLOUDS OR REVISIONS NUMBERS. PLEASE SHOW CLOUDS AND
 REVISION NUMBERS FOR EACH REVISIONS. SECTION 106.1.3.
 --REVISION NUMBER 11 DOES NOT INDICATE WHAT IS
 REVISED. PLEASE CLARIFY. SECTION 106.1.1.--THE
 ADDITION OF RWL'S 11& 14 ADD UP TO 10,420SF. 10" PIPE
 IS REQUIRED PER TABLE 1106.3. 8" IS SHOWN.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 16 Status P Date 2008-07-18 Cont ID  
Sent By kstevens Date 2008-07-18 Time 08:07 Rev Time 0.00
Received By kstevens Date 2008-07-17 Time 15:57 Sent To  
Notes
2008-07-18 08:10:32REVISIONS OK -- SHTS P1-2.0, P1-2.1, P1-2.2. P1-3.0,
 P1-3.2 P1-6.0 (REVISIONS 11 & 12 NOT FOUND OR
 APPROVED), P3-1.0 (REVISION 193 NOT FOUND OR APPROVED).

Review Stop P PLUMBING
Rev No 15 Status F Date 2008-05-29 Cont ID  
Sent By kstevens Date 2008-05-29 Time 14:46 Rev Time 0.00
Received By kstevens Date 2008-05-29 Time 14:46 Sent To  
Notes
2008-05-29 15:05:51REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHTS P1-1.0 & P1-1.1 REVISION 193. SHOW THE 2"
 CONDENSATE RISER INDICATED ON THE REVISION. PLANS SHOW
 CONDENSATE CONNECTION TO THE 4" SANITARY LINE. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 2. SHTS P1-3.0 & P1-3.1 CONDENSATE SHALL NOT CONNECT TO
 THE RAIN WATER LEADER OTHER THAN AT THE ROOF DRAINS.
 THE CONDENSATE SHALL DRAIN SEPARATELY FROM THE BUILDING
 BY A DEDICATED CONDENSATE RISER AND CONNECT TO A
 DRYWELL, A CATCH BASIN, A STORM LINE OR INTO A PLANTED
 AREA. IF CONNECTING TO THE STORM DRAIN OUTSIDE THE
 BUILDING, A RELIEF VENT OR GOOSENECK IS REQUIRED AS THE
 CONDENSATE EXITS THE BUILDING. SECTION 314.2.1.
  
 3. SHT P1-4.0 RISER RWL/12 TOTAL SQUARE FOOTAGE DOES
 NOT REFLECT THE TOTAL OF BOTH ROOF DRAINS. TABLE
 1106.3.--SHOW THE LOCATION OF RWL/9. PIPING APPEARS
 TO BE CONNECTING TO THE SANITARY RISER P/2. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 4. SHT P1-4.2 RISER RWL/12 TOTAL SQUARE FOOTAGE DOES
 NOT REFLECT THE TOTAL OF BOTH ROOF DRAINS. TABLE
 1106.3.--SHOW THE LOCATION OF RWL/9. PIPING APPEARS
 TO BE CONNECTING TO THE SANITARY RISER P/2. PLEASE
 CLARIFY.--ALSO REVISION NUMBER 5 IS NOT INDICATED
 ON THE REVISION INDEX. PLEASE SHOW ALL REVISIONS ON THE
 INDEX. SECTIONS 106.1.2 & 106.1.3.
  
 5. SHT P1-5.0 CHANGES TO THE ROOF DRAINS & OVERFLOW
 DRAIN ARE NOT INDICATED AS CHANGES. PLEASE CLOUD AND
 NUMBER ALL REVISIONS SUBMITTED. SECTION 106.1.3.
  
 6. SHT P3-1.0 RISER DIAGRAM DOES NOT REFLECT THE FLOOR
 PLAN FOR THE NEW SINK AT THE CONNECTION AND ROUTING OF
 THE PIPING. PLEASE CORRELATE. SECTION 106.1.1.
  
 7. SHT P3-7.0 RISER DOES NOT REFLECT THE FLOOR PLAN AT
 RWL'S 11 THRU 14. ALSO RECHECK THE SQUARE FOOTAGE AT
 EACH ROOF DRAIN AND THE TOTAL SQUARE FOOTAGE FOR EACH
 RWL. THIS INFORMATION SHALL REFLECT THE FLOOR PLAN.
 SECTION 106.1.1 & TABLE 1106.3.--ALSO CONDENSATE
 SHALL NOT CONNECT TO THE RAIN WATER LEADER OTHER THAN
 AT THE ROOF DRAINS. THE CONDENSATE SHALL DRAIN
 SEPARATELY FROM THE BUILDING BY A DEDICATED CONDENSATE
 RISER AND CONNECT TO A DRYWELL, A CATCH BASIN, A STORM
 LINE OR INTO A PLANTED AREA. IF CONNECTING TO THE STORM
 DRAIN OUTSIDE THE BUILDING, A RELIEF VENT OR GOOSENECK
 IS REQUIRED AS THE CONDENSATE EXITS THE BUILDING.
 SECTION 313.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop P PLUMBING
Rev No 14 Status P Date 2008-05-29 Cont ID  
Sent By kstevens Date 2008-05-29 Time 14:38 Rev Time 0.00
Received By kstevens Date 2008-05-29 Time 14:38 Sent To  
Notes
2008-05-29 14:46:08 
 REVISIONS APPROVED
  
  
  
 SHTS P1-2.0 & P1-2.1 REVISIONS ARE REQUIRED FOR THE
 SANITARY AND WATER RISERS THAT REFLECT THE CHANGES TO
 THE SINK AT COL. LINE 5.2 BETWEEN COL'S B & C.
  
  
  
  
 SHT P1-2.2A REVISION IS REQUIRED FOR SHT P2-1.0 TO
 REFLECT CHANGES TO THE SANITARY AND WATER PIPING THAT
 SHOW THE CONNECTIONS FOR THE SINK.
  
  
  
  
 SHT P1-3.2A REVISION IS REQUIRED FOR SHT P2.3.0 TO
 REFLECT CHANGES TO THE SANITARY AND WATER PIPING THAT
 SHOW THE CONNECTIONS FOR THE SINK.
  
  
  
  
 SHT P1-5.1OK
 SHT P3-5.0OK
  
  
  
  
  

Review Stop P PLUMBING
Rev No 13 Status P Date 2007-12-20 Cont ID  
Sent By kstevens Date 2007-12-20 Time 18:16 Rev Time 0.00
Received By kstevens Date 2007-12-20 Time 18:16 Sent To  
Notes
2007-12-20 18:18:33REVISION OK SHT P3-2.0

Review Stop P PLUMBING
Rev No 12 Status P Date 2007-11-03 Cont ID  
Sent By kstevens Date 2007-11-03 Time 14:39 Rev Time 0.00
Received By kstevens Date 2007-11-03 Time 14:39 Sent To  
Notes
2007-11-03 14:40:58REVISIONS OK--SHTS P1-1.3U, P1-1.0, P1-2.0, P1-2.1,
 P1-5.0

Review Stop P PLUMBING
Rev No 11 Status F Date 2007-11-03 Cont ID  
Sent By kstevens Date 2007-11-03 Time 14:25 Rev Time 0.00
Received By kstevens Date 2007-11-03 Time 14:25 Sent To  
Notes
2007-11-03 14:29:12DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P3-2.0SANT. RISER P-7 TOILET ROOM A2.705 THE
 PIPING, TRAP AND FLOOR DRAIN ARE INDICATED ABOVE THE
 FLOOR. PLEASE CLARIFY. SECTIONS 106.1.1 & 106.1.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 10 Status F Date 2007-09-19 Cont ID  
Sent By kstevens Date 2007-09-19 Time 10:40 Rev Time 0.00
Received By kstevens Date 2007-09-17 Time 10:40 Sent To  
Notes
2007-09-19 11:17:05DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P1-1.3U MANY REVISIONS #11 SHOWN. THE PREVIOUS
 REVISION NUMBER REVIEWED WAS REVISION #4. NO REVISIONS
 SUBMITTED OR APPROVED AFTER THAT. CLOUD AND NUMBER ALL
 REVISIONS AFTER REVISION #4. REVISIONS #10 & #11 ARE
 NOT INDICATED ON THE REVISION INDEX, BUT ARE INDICATED
 ON THE PLANS. THESE REVISIONS ARE NOT CLOUDED.FOR
 EXAMPLE SEE CHANGES IN THE TOILET ROOM B1.108 NOT
 INDICATED AS A REVISION AS WELL AS CHANGES IN THE
 SANITARY AND CHANGES IN THE STORM AND CHANGES IN THE
 LOCATION OF THE FLOOR DRAINS IN THE PUMP ROOMS. THE
 COLUMN LINES HAVE BEEN CHANGED ALSO, (DELETED SOME).
 THESE HAVE NOT BEEN INDICATED AS REVISIONS.--ALL
 CHANGES IN THE SYSTEMS SHALL BE REFLECTED ON THE RISER
 DIAGRAMS TO REFLECT THESE CHANGES. SECTION 106.1.1.
  
 2. SHT P1-5.0 MANY CHANGES ARE NOT INDICATED BY CLOUDS
 OR REVISION NUMBERS. THE LAST REVISION #5, SIGNED,
 SEALED & DATED 2-5-7. ALL CHANGES FROM THE STAMPED
 PLANS SHALL BE CLOUDED AND INDICATED WITH A REVISION
 NUMBER. (PLEASE TURN OFF ALL PREVIOUS CLOUDS AND
 REVISION NUMBERS FROM SHEETS THAT HAVE BEEN APPROVED
 PRIOR TO SUBMITTING NEW REVISIONS. -- LEAVING ON
 PREAPPROVED REVISION CLOUDS AND REVISION NUMBERS ADDS
 TIME TO EACH REVIEW).
  
 3. SHT P1-5.1 REVISION #12 HAS NOT BEEN FOUND. PLEASE
 INDICATE WITH A CLOUD AND A REVISION NUMBER AND PLEASE
 TURN OFF THE CLOUDS AND REVISION NUMBERS FROM
 PREVIOUSLY APPROVED REVISIONS.
  
 4. SHT P3-7.0 ISOMETRIC RISER DIAGRAM FOR RWL-7 DOES
 NOT REFLECT THE FLOOR PLAN. CLEANOUT NOT SHOWN ON THE
 FLOOR PLAN. CLEANOUTS TO BE INSTALLED PER SECTION
 1101.8. SECTION 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 9 Status P Date 2007-09-19 Cont ID  
Sent By kstevens Date 2007-09-19 Time 10:36 Rev Time 0.00
Received By kstevens Date 2007-09-17 Time 19:30 Sent To  
Notes
2007-09-19 10:40:38REVISIONS OK - SHTS P1-2.3, P1-3.3, P1-4.3, P1-6.0, &
 P3-4.0. REVISION 12.

Review Stop P PLUMBING
Rev No 8 Status P Date 2007-09-10 Cont ID  
Sent By kstevens Date 2007-09-10 Time 17:21 Rev Time 0.00
Received By kstevens Date 2007-09-10 Time 17:21 Sent To  
Notes
2007-09-10 17:25:03REVISIONS OK--SHTS P1-1.1, P1-3.0, P1-3.1, P1-4.0,
 P1-4.1, P2-1.0U, P2-1.0, P2-3.0 & P3-5.0. APPROVAL ONLY
 FOR REVISION #11 CLOUDED AND NUMBERED ON EACH SHEET.
 ANY OTHER REVISION NOT INDICATED WITH CLOUDS AND
 NUMBERS NOT APPROVED.

Review Stop P PLUMBING
Rev No 7 Status F Date 2007-09-10 Cont ID  
Sent By kstevens Date 2007-09-10 Time 16:55 Rev Time 0.00
Received By kstevens Date 2007-09-10 Time 16:55 Sent To  
Notes
2007-09-10 17:14:48REVISIONS DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT P1-1.0 CLOUD AND NUMBER ALL REVISIONS. REVISIONS
 SEEN WITH NO CLOUDS OR REVISION NUMBERS. SECTION
 106.1.3.
  
 2. SHTS P1-2.0 & P1-2.1 ROOM A2.316 SINK SHALL BE
 ACCESSIBLE. PLEASE SHOW CLEAR FLOOR SPACE AND TURNING
 AREA REQUIRED BY SECTIONS 11-4.24.5 & 11-4.2.3.--
 CLOUD AND NUMBER ALL REVISIONS. SECTION 106.1.3.
  
 3. SHT P3-20 RISERS DO NOT REFLECT THE FLOOR PLAN.--
 RISER P/2, SEE PROVISO FOR CLEANOUT DOWNSTREAM OF
 JANITOR SINK 3RD FLOOR. SEE PREVIOUS APPROVED SHEETS
 WITH COMMENT ABOUT REVISIONS.--SINK S-1 BY THE BASE
 OF RISER P/4, (RM A1.709), DOES NOT REFLECT REVISION
 #11 CHANGE.--SINK S-1 BY THE TOILET ROOM A2.705
 CONNECTS TO BOTH RISERS P/7 & P/4. PLEASE CLARIFY.--
 SINK SK-1 DOWNSTREAM OF TOILET ROOM A2.107 DOES NOT
 REFLECT THE FLOOR PLAN. PLEASE CORRELATE THE RISER WITH
 THE FLOOR PLANS. SECTION 106.1.1.
  
 4. SHT P3-3.0 RISER DOES NOT REFLECT THE FLOOR PLAN FOR
 THE OFFSET OF THE SINK IN THE JANITOR ROOM, NOR FOR THE
 CLEANOUT PRIOR TO THE SINK UPSTREAM OF THE EWC-1 BY THE
 JANITOR ROOM A4.105. PLEASE CORRELATE RISER AND FLOOR
 PLAN. SECTION 106.1.1.
  
 5. SHT P3-6.0 THE WATER LINES FOR THE SINK BY THE
 ELECTRIC W/H IN THE JANITOR ROOM A4.105 DO NOT REFLECT
 THE SINK LOCATION ON THE FLOOR PLAN. THE RISER SHOWS
 THEM TURNING INTO THE JANITOR ROOM, BUT THE FLOOR PLAN
 SHOWS THE SINK IN THE HALLWAY OUTSIDE THE JANITOR ROOM.
 THE WATER RISER FOR THE TOILET ROOM A2.105 DOES NOT
 REFLECT THE PIPING SHOWN ON SHT P2.30 FOR THE SINK IN
 ROOM A2.730. PLEASE CORRELATE RISER AND FLOOR PLANS.
 SECTION 106.1.1.
  
 EVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 6 Status F Date 2007-06-15 Cont ID  
Sent By kstevens Date 2007-06-15 Time 09:14 Rev Time 0.00
Received By kstevens Date 2007-06-15 Time 09:14 Sent To  
Notes
2007-06-15 10:31:31DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P1.1.3U THE STORAGE ROOM B1.101 SHOWS SANITARY
 PIPING. PLEASE INDICATE THE TYPE OF FIXTURE AND THE
 TYPE OF DRAINAGE FITTING FOR THE FIXTURE.A REVISION
 IS REQUIRED FOR THE SANITARY RISER DIAGRAM TO REFLECT
 THE CHANGES TO THE SANITARY SYSTEM. SECTION 106.1.1.
  
 2. SHT P1-6.0 THE TRENCH DRAIN AT THE BOTTOM OF THE
 LOWER RAMP HAS BEEN DELETED, BUT IS STILL SHOWN ON THE
 STORM RISER DIAGRAM ON SHT P3.7.0. PLEASE CORRELATE
 RISER AND FLOOR PLAN LAYOUT.
  
 2. SHT P1-6.0SHOWS 6" AREA DRAINS, BUT THE RISER
 DIAGRAM ON SHT P3-7.0 SHOWS 8" AREA DRAINS. PLEASE
 CORRELATE RISER AND FLOOR PLAN.
  
 3. SHT P1-6.0 AREA DRAINS HAVE BEEN DELETED ON THE FLAT
 LEVELS OF THE ROOF AND LOWER ROOF SECTION. PLEASE
 INDICATE IF THE SLAB WILL BE SLOPED TO THE AREA DRAINS
 NOW SHOW AT THE BOTTOM OF THE RAMPS.
  
 4. SHT P1-6.0 THE AREA DRAIN IS SHOWN AT THE BOTTOM OF
 THE SECOND RAMP, (NORTH END), ON THE FLOOR PLAN, BUT
 THE RISER DIAGRAM SHOWS THE AREA DRAIN ON THE ROOF
 ABOVE THE RAMP. PLEASE CLARIFY & CORRELATE RISER AND
 FLOOR PLAN. SECTION 106.1.1.
  
 5. REVISIONS ARE REQUIRED FOR SHTS P1-2.3, P1.3.3,
 P1-4.3, & P1-6.0SHOWING THE NEW AREA DRAINS AND
 SHOWING THE CHANGED LOCATION OF THE RWL RISER #6.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2007-04-09 Cont ID  
Sent By kstevens Date 2007-04-09 Time 12:19 Rev Time 0.00
Received By kstevens Date 2007-04-09 Time 12:19 Sent To  
Notes
2007-04-09 12:51:01REVISIONS OK - SHTS LSO.0, A9-0.2, P-6.0, P3-2.0,
 P2-3.0, P3-1.0, P3-4.0, LS-0.0, IR-1, A9-0.2.-
 REVISION 8

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-02-20 Cont ID  
Sent By kstevens Date 2007-02-20 Time 11:22 Rev Time 0.00
Received By kstevens Date 2007-02-17 Time 17:15 Sent To  
Notes
2007-02-20 12:09:22PASSED/PROVISO
  
 SHT P3.2.0 RISER P/2 SHOWS 3 DRINKING FOUNTAINS AT
 TOILET ROOMS C3.107 & C3.108. THE FLOOR PLAN ONLY SHOWS
 2. REVISION REQUIRED TO CORRELATE RISER WITH FLOOR
 PLAN.
  
 SHT P1.60 REVISION REQUIRED. VENT NOT ALLOWED IN THE
 STAIRWELL, AND DOES NOT REFLECT THE RISER DIAGRAM.
  
 SHT P1.60 REVISION REQUIRED. SHOW THE TRENCH DRAINS AT
 THE BOTTOM OF THE RAMPS.
  
 SHT LSO.0 PLUMBING FIXTURE COUNT TO BE CORRECTED FOR
 DRINKING FOUNTAINS. 2 REQUIRED, READS 1 REQUIRED,
 REVISION REQUIRED.
  
 SHT LSO.0 PLUMBING FIXTURE COUNT TO BE CORRECTED FOR
 DRINKING FOUNTAINS. 4 REQUIRED, READS 2 REQUIRED.
 REVISION REQUIRED.
  
 SHT A9-0.2 TOILET ROOMS C1.05 & C1.106 FINISH OF EPOXY
 PAINT NOT APPROVED. SECTION 1210.2. REVISION REQUIRED.
  
 PLEASE SUBMIT ALL REVISIONS REQUESTED WITHIN 60 DAYS
 AFTER ISSUANCE OF PERMIT.

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-01-30 Cont ID  
Sent By kstevens Date 2007-01-30 Time 17:53 Rev Time 0.00
Received By kstevens Date 2007-01-30 Time 17:53 Sent To  
Notes
2007-01-30 17:59:39DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
  
 3. SHT P1-1.1 PUMP ROOM A1-112. RPZV BACKFLOW SHALL BE
 INSTALLED A MAXIMUM OF 4' ABOVE THE FLOOR FOR
 CERTIFICATION AND SERVICE.
 ****RESPONSE NOTED, HEIGHT TO BE INDICATED FOR THE
 BACKFLOWS TO BE A MAXIMUM OF 4' ABOVE THE FLOOR.
 ****RESPONSE NOTED, BUT PLANS INDICATE MINIMUM 4' ABOVE
 THE FLOOR. THE REQUIREMENT IS FOR MAXIMUM 4' ABOVE THE
 FLOOR.
 ******RESPONSE NOTED, BUT THE MINIMUM IS STILL
 INDICATED.
  
 4. OK
 5. OK
 6.OK
 7.OK
 8.OK
 9.OK
 10. OK
 11. OK
 12. OK
 13. OK
 14. OK
 15. OK
 16. OK (SHOWN ON SHT P2-1.0U)
 17. OK
 18. OK
 19. OK
 20. OK
 21. OK
 22. OK
 23. OK
 24. OK
 25. OK
 26. OK
 27. OK
 28. OK
 29. OK
 30. OK
 31. OK
 32. OK
 33. OK
 34. OK
 35. OK
  
 36. SUBMIT A SANITARY HORIZONTAL RISER ISOMETRIC AND
 VERTICAL RISER DIAGRAMS. SHOW ALL PIPE SIZES, TRAPS,
 VENTS, CLEANOUTS, OFFSETS, RISER NUMBERS AND DFU'S AS
 THEY ACCUMULATE IN THE SYSTEM. SECTION 106.3.5.1.3.
 ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN,
 ALL REQUIRED CLEANOUTS ARE NOT SHOWN, AND DFU'S ARE NOT
 SHOWN AS THEY ACCUMULATE IN THE SYSTEM. ALSO INDICATE
 ON THE FIRST FLOOR WHERE ALL RISERS BEGIN IN THE
 SYSTEM.
 ****RESPONSE NOTED, BUT SHT P3-1.0 RISER 1, LAVS DO NOT
 REFLECT THE FLOOR PLAN 2ND FLOOR C2-1.03. - DOES NOT
 REFLECT THE FLOOR PLAN C4.103/C4.104 DRINKING FOUNTAINS
 SHOW 3, FLOOR PLAN SHOWS 2. - CLEANOUT NOT SHOWN AT THE
 BASE OF P/1. - NOT ALL PIPE SIZES SHOWN.-SHT P3-2.0
 RISER P/2 CLEANOUT DOWNSTREAM OF JANITOR SINK IN ROOM
 C4.101 NOT INSTALLED PER SECTION 706.3. SECOND CLEANOUT
 AT THE BASE OF P/2 NOT REQUIRED AS IT DOES NOT CLEANOUT
 THE BASE OF THE STACK, NOR DOES IT REFLECT THE FLOOR
 PLAN. - FLOOR DRAIN PIPING IN ROOM D1.101 AS INDICATED
 IS BEING INSTALLED ABOVE THE FLOOR. - EACH DRINKING
 FOUNTAIN SHALL HAVE ITS OWN TRAP. SAFE WASTE FOR THE
 FIXTURES IS NOT APPROVED.(SEE ROOMS D1.101, D1.108,
 AND A3.111). -CLEANOUTS ARE REQUIRED AT THE BASE OF
 STACKS P/4 & P/10. - CLEANOUT FOR P/7 NOT INSTALLED AT
 THE BASE OF P/7. -THE NEW SANT. PIPING TO TOILET ROOM
 D2.105 NOT SHOWN ON THE FLOOR PLAN. -SHOW ALL TOILET
 ROOM NUMBERS ON THE RISER DIAGRAM. - SHOW ALL PIPE
 SIZES. THE PIPE SIZES ARE NOT SHOWN ON MANY PIPES.-
 SHT P3-3.0A TWO WAY CLEANOUT IS REQUIRED NEAR THE
 JUNCTION OF THE BUILDING DRAIN AND THE BUILDING SEWER.
 (DETAIL 1).-THE RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN FOR A1.05 & A1.106. AN EXTRA FLOOR DRAIN IS
 INDICATED THAT IS NOT SHOWN ON THE FLOOR PLAN.-
 A3.102 & A3.103 ONLY SHOWS 2 LAVS ON THE RISER AND THE
 FLOOR PLAN SHOWS 4.-A4.103 & A4.104TWO W/C'S ARE
 MISSING FROM THE RISER THAT ARE SHOWN ON THE FLOOR
 PLAN.-A4.105NO FLOOR DRAIN AND A SECOND SINK ARE
 SHOWN ON THE FLOOR PLAN THAT ARE NOT SHOWN ON THE RISER
 DIAGRAM. (JANITOR ROOM).-A5.105 SHOWS THE BRANCH
 LINE CONNECTING NEAR THE DRINKING FOUNTAINS ON THE
 FLOOR PLAN, BUT CONNECTING DOWNSTREAM OF THE NEXT
 FIXTURES ON THE RISER DIAGRAM.-A CLEANOUT IS
 REQUIRED AT THE BASE OF RISER P/8-ALL RISER
 DIAGRAMS,CHECK ALL PIPE SIZES, MAKE SURE THE RISER
 DIAGRAMS REFLECT THE FLOOR PLAN FOR BOTH THE SANITARY
 AND THE VENTING.SECTIONS106.1.1, 106..1.2, 706.3,
 708.3.4, 708.3.5, 100.2.1.
 ******RESPONSE NOTED, BUT NOW THE FLOOR PLAN SHOWS 3
 DRINKING FOUNTAINS & THE SANT. RISER SHOW 2. PLEASE
 CORRELATE.--D1.108 STILL SHOWS A SAFE WASTE AT THE
 CENTER DRINKING FOUNTAIN.
  
 37. OK
 38. OK
 39. OK
  
 40. ALL PME & FIRE PROTECTION SHEETS. PLANS SHALL BE
 SIGNED, SEALED, AND DATED. SECTION 106.1. ALL TITLE
 BLOCK INFORMATION REQUIRED BY FAC 61G1-23.002 AND FS
 471.025 SHALL BE SUBMITTED ON EACH SHEET. ****RESPONSE
 NOTED, BUT THE SEAL USED IS NOT APPROVED. NEW SEALS
 SHALL INDICATE THE WORD "LICENSE" IN THE SEAL. (SEE
 ATTACHED SHEET FROM THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS).
 ****RESPONSE NOTED, BUT THE SEALS OF SOME MECH. AND
 PLUMBING SHEETS ARE STILL THE OLD SEAL. - ALSO THERE
 SEEMS TO BE TWO SETS OF SIGNATURES FOR THE ENGINEER OF
 RECORD. PLEASE SUBMIT A SIGNED, SEALED, DATED,
 NOTORIZED LETTER INDICATING THE LEGAL SIGNATURE OF THE
 ENGINEER OF RECORD FOR OUR FILES. ONE SET OF PLANS
 SHALL BE RETAINED FOR POSSIBLE REVIEW BY THE FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS.
 ******RESPONSE NOTED, BUT THERE ARE STILL SOME SEALS
 WITH "CERTIFICATE" ON THE MECHANICAL SHEETS.
  
 **************NEW COMMENTS**************
  
 1B. SHTS P1-1.0U, P1-1.1U, P1-1.1 & P1-2.1. RWL-4 DOES
 NOT REFLECT THE SQUARE FOOTAGE SHOWN ON RISER DIAGRAM
 OR ROOF PLAN. PLEASE CORRELATE RISER, FLOOR PLAN, &
 ROOF PLAN. SECTION 106.1.1.
 ****RESPONSE NOTED. WILL RECHECK AFTER THE CALCULATIONS
 FOR THE ROOF DRAINS HAS BEEN RESUBMITTED WITH
 CORRECTIONS.
 ******RESPONSE NOTED, BUT SOME SHEETS SHOW A DIFFERENT
 SQUARE FOOTAGE THAN SHOWN ON THE ROOF PLAN & RISER.
 PLEASE CORRELATE ALL SHEETS.
  
 2B. OK
 3B. OK
 4B. OK
 5B. OK
  
 6B. SHTS P1-1.2U, ASSOCIATED RISER DIAGRAMS, AND
 ENLARGED FLOOR PLANS. INDICATE HOW THE STACKS P/1 &
 P/10 CAN DRAIN INTO THE TOILET GROUP FIXTURE BRANCH.
 SUBMIT A DETAIL SHOWING THE 4" CLEANOUT TEE, THE 4"
 CROSS FOR THE FIXTURE BRANCH, AND THE 4" DOUBLE
 Y/EIGHTH BEND FITTINGS STACKED ON TOP OF EACH OTHER.
 WILL THEY BE AT THE RIGHT HEIGHT FOR THE W/C'S?SEE
 SECTION 908.3 ALSO. SECTION 106.1.1. (STACKS SHOULD
 CONNECT TO THE BUILDING DRAIN AND FIXTURE GROUPS SHOULD
 CONNECT TO THE STACK SO THAT THE STACK DOES NOT RUN
 THRU THE MIDDLE OF THE FIXTURE GROUP). ****RESPONSE
 NOTED, BUT C/O'S ARE REQUIRED AT THE BASE OF EACH
 STACK. COMMENT HAS NOT BEEN ADDRESSED. ******RESPONSE
 NOTED, BUT NOW THE VENTING TO THE W/C'S IS NOT SHOWN ON
 THE 1ST FLOOR STACK P-10.
  
 7B. SHTS P1-1.3U, P1-2.0, P1-2.3, P1-3.3, & P1-4.3
 RWL-6 DOES NOT REFLECT THE SQUARE FOOTAGE SHOWN ON THE
 RISER DIAGRAM, NOR ON THE ROOF PLAN. PLEASE CORRELATE
 INFORMATION. SECTION 106.1.1 & TABLE 1106.3.
 ****RESPONSE NOTED, BUT THE COMMENT WAS NOT ADDRESSED
 ON SHTS P1-3.3, & P1-4.3.
 ******RESPONSE NOTED, BUT THE SQUARE FOOTAGE ON SHTS
 P1-2.0 & P1-2.3 IS INDICATED AS 5,584SF. PLEASE
 CORRELATE ALL SHEETS.
  
 8B. OK
 9B. OK
 10B. OK
 11B. OK
 12B. OK
 13B. OK
 14B. OK
  
 15B. SHT P1-6.0 SHOW THE LOCATIONS FOR ALL VTR'S. -
 INDICATE THE RWL EACH ROOF DRAIN IS CONNECTED TO.
 SECTION 106.1.1.
 ****RESPONSE NOTED, BUT VTR'S 1, 3, 9 & 10 ARE NOT
 SHOWN.
 ******RESPONSE NOTED, BUT THE VTR FOR THE TOILET ROOM
 IN THE GARAGE IS NOT INDICATED PAST THE 1ST FLOOR.
 PLEASE SHOW THE VENT ON THE 2ND, 3RD, 4TH, 5TH & AT THE
 ROOF LEVEL OF THE GARAGE.
  
 16B. OK
 17B. OK
 18B. OK
 19B. OK
 20B. OK
 21B. OK
 22B. OK
 23B. OK
 24B. OK
 25B. OK.
 26B. OK
 27B. OK
 28B. OK
 29B. OK
 30B. OK
 31B. OK
 32B. OK
 33B. OK
  
 34B. SHT P3.1.0 SANT RISER DIAGRAM, TRAPS ARE REQUIRED
 ON ALL DRINKING FOUNTAINS. SECTION 1002.1. - 1ST FLOOR
 LAVS PIPING DOES NOT REFLECT THE FLOOR PLAN. - FLOOR
 DRAINS DOWNSTREAM OF RISER P/1 ARE NOT VENTED. SECTION
 901.2.1. - A C/O IS REQUIRED AT THE BASE OF STACK P/1
 SECTION 708.3.4 - SHOW THE CONNECTION DETAIL AT THE
 BASE OF STACK P/1 WITH A 4" CLEANOUT, A 4" CROSS, AND
 4" WYE FITTINGS INDICATING THE HEIGHT OF THE W/C
 STUBOUT. - W/C-1 AT THE BASE OF STACK IS NOT VENTED.
 SECTION 901.2.1. -W/C ON 2ND FLOOR IS NOT VENTED.
 SECTION 901.2.1. - LAV ON 3RD FLOOR NOT VENTED. SECTION
 901.2.1. - INDICATE HOW/WHERE PIPING FOR LAVS & FLOOR
 DRAINS CONNECT TO THE RISER/BRANCH ON THE 2ND, 3RD, &
 4TH FLOORS. THE FITTINGS INDICATE THAT THE PIPING IS
 SLOPED TO THE LAVS. PLEASE CLARIFY. - MEN C4.104 DOES
 NOT REFLECT ROOM NUMBER ON THE FLOOR PLAN. - PIPING FOR
 FLOOR DRAINS & LAVS 4TH FLOOR DOES NOT REFLECT THE
 FLOOR PLAN. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT 1ST FLOOR LAVS PIPING DOES NOT
 REFLECT THE FLOOR PLAN. -A C/O IS REQUIRED AT THE
 BASE OF STACK P/1 SECTION 708.3.4 - SHOW THE CONNECTION
 DETAIL AT THE BASE OF STACK P/1 WITH A 4" CLEANOUT, A
 4" CROSS, AND 4" WYE FITTINGS INDICATING THE HEIGHT OF
 THE W/C HOW THE CONNECTION DETAIL AT THE BASE OF STACK
 P/1 WITH A 4" CLEANOUT, A 4" CROSS, AND 4" WYE FITTINGS
 INDICATING THE HEIGHT OF THE W/C STUBOUT. - MEN C4.104
 DOES NOT REFLECT ROOM NUMBER ON THE FLOOR PLAN. -
 PIPING FOR FLOOR DRAINS & LAVS 4TH FLOOR DOES NOT
 REFLECT THE FLOOR PLAN. SECTION 106.1.1. THESE ITEMS
 HAVE NOT BEEN ADDRESSED.
 ******RESPONSE NOTED, BUT MEN'S C4.104 STILL DOES NOT
 REFLECT THE ROOM NUMBER ON THE FLOOR PLAN.--NOW NO
 SANITARY PIPING OR HOT WATER PIPING IS SHOWN ON THE
 FLOOR PLAN OF THE ENLARGED FLOOR PLAN. PLEASE CLARIFY.
  
 35B. ALL RISER DIAGRAMS, ALL FLOOR PLANS FOR ALL
 SYSTEMS. INDICATE THE PIPE SIZE. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT MANY PIPE SIZES ARE NOT SHOWN
 ON THE RISER DIAGRAMS.
 ******RESPONSE NOTED, BUT THERE ARE MANY SECTIONS OF
 SANITARY PIPING THAT HAVE NO PIPE SIZES. TABLES
 710.1(1) & 710.1(2).
  
 36B. SHT P3-2.0 JANITOR ROOM PIPING DOES NOT REFLECT
 THE FLOOR PLAN. - TRAPS REQUIRED ON ALL DRINKING
 FOUNTAINS. SECTION 1002.1. - CLEANOUTS REQUIRED AT THE
 BASE OF ALL STACKS. 708.3.4. - PIPING TO FLOOR DRAIN
 SHOWN ABOVE THE FLOOR IN ROOM D1.101. PLEASE CLARIFY. -
 PIPING AT THE BASE OF RISER P/2 DOES NOT REFLECT THE
 FLOOR PLAN. - PIPING TO FD-2 AT THE LOADING D1.106 DOES
 NOT REFLECT THE FLOOR PLAN. - PIPING FOR A1.108/A1.109
 DOES NOT REFLECT THE FLOOR PLAN. - ROOM D2.103 IS
 INDICATED AS D2.104 ON THE FLOOR PLAN. CORRELATE
 INFORMATION. - ALL VENTING AT RISER P/10 STOPS AT LEVEL
 2. SECTION 903.3 VTR REQUIRED. - TOILET ROOM A2.708 IS
 INDICATED AS A2.706 ON THE FLOOR PLAN. CORRELATE
 INFORMATION. - BATHROOM RISER DOES NOT REFLECT THE
 FLOOR PLAN. (NO FD). - PIPING TO ROOM A4.414 DOES NOT
 REFLECT THE FLOOR PLAN. - CLEANOUT PIPING DOWNSTREAM OF
 C4.101 IS NOT APPROVED AS PIPED. SECTION 706.3. -
 PIPING ON RISER DOES NOT REFLECT THE FLOOR PLAN
 UPSTREAM OF C3.105. - JANITOR SINK C3.105 IS NOT
 VENTED. SECTION 901.2.1. - FLOOR DRAIN CONNECTION AT
 BRANCH LINE 4TH FLOOR DOES NOT REFLECT THE FLOOR PLAN.
 - PIPING AT A2.107 DOES NOT REFLECT THE FLOOR PLAN. (NO
 F.D. PIPING). - PIPING AT ROOM A3.111 DOES NOT REFLECT
 THE FLOOR PLAN AT THE LAVS. - ROOM A3.111 SUBMIT A
 DETAIL FOR FITTING TO W/C & LAVS. - ROOM D2.105 SHOWN
 AS D2.106/D2.107 ON FLOOR PLANS. CORRELATE INFORMATION.
 - ROOM C3.410/C3.412 FLOOR DRAIN FITTING ARE SHOWN TO
 BE INSTALLED AGAINST THE FLOW. SECTION 706.3. - SECTION
 106.1.1.
 ****RESPONSE NOTED, BUT SOME COMMENTS WERE NOT
 ADDRESSED. SEE THE FOLLOWING: JANITOR ROOM PIPING DOES
 NOT REFLECT THE FLOOR PLAN. - TRAPS REQUIRED ON ALL
 DRINKING FOUNTAINS. SECTION 1002.1. - CLEANOUTS
 REQUIRED AT THE BASE OF ALL STACKS. 708.3.4. - PIPING
 TO FLOOR DRAIN SHOWN ABOVE THE FLOOR IN ROOM D1.101.
 PLEASE CLARIFY.- PIPING AT THE BASE OF RISER P/2 DOES
 NOT REFLECT THE FLOOR PLAN. - PIPING FOR A1.108/A1.109
 DOES NOT REFLECT THE FLOOR PLAN. - ROOM D2.103 IS
 INDICATED AS D2.104 ON THE FLOOR PLAN. CORRELATE
 INFORMATION.- TOILET ROOM A2.708 IS INDICATED AS
 A2.706 ON THE FLOOR PLAN. CORRELATE INFORMATION. -
 PIPING TO ROOM A4.414 DOES NOT REFLECT THE FLOOR PLAN.
 - CLEANOUT PIPING DOWNSTREAM OF C4.101 IS NOT APPROVED
 AS PIPED. SECTION 706.3. - PIPING AT ROOM A3.111 DOES
 NOT REFLECT THE FLOOR PLAN AT THE LAVS. - ROOM A3.111
 SUBMIT A DETAIL FOR FITTING TO W/C & LAVS. - ROOM
 D2.105 SHOWN AS D2.106/D2.107 ON FLOOR PLANS. CORRELATE
 INFORMATION.
 ******RESPONSE NOTED, BUT THE JANITOR ROOM PIPING DOES
 NOT REFLECT THE FLOOR PLAN.--TOILET ROOM A2.708 IS
 STILL INDICATED AS A2.706 ON THE FLOOR PLAN. CORRELATE
 ROOM NUMBERS.--PIPING TO ROOM A4.414 DOES NOT
 REFLECT THE FLOOR PLAN. RISER IS SHOWN AS A TRAVELING
 OFFSET. FLOOR PLAN SHOWS THIS AS A STRAIGHT RISER.
 PLEASE CLARIFY.
  
 37B. SHT P3-3.0 PIPING TO A3.304 & DOWNSTREAM DOES NOT
 REFLECT THE FLOOR PLAN. - VENT PIPING FROM S-1 SINK
 DOES NOT REFLECT THE FLOOR PLAN. OFFSET NOT SHOWN. -
 TRAPS REQUIRED ON ALL DRINKING FOUNTAINS. SECTION
 1002.1. - S-1 SINK SHALL NOT DRAIN THRU THE WET VENT OF
 THE TOILET ROOM A1.303. SINK SHALL DISCHARGE DOWNSTREAM
 OF THE W/C & LAV. SECTION 909.1. - INDICATE P/8 WITH
 P/6 AT THE BASE OF THE STACK WHERE IT BEGINS. - PIPING
 TO ROOMS A1.105/A1.106 DOES NOT REFLECT THE FLOOR PLAN.
 FLOOR DRAIN PIPING IS SHOWN AS ABOVE THE FLOOR. - P/5 &
 P/9 BEGIN AT THE BASE OF THE STACK. PLEASE INDICATE ON
 RISER DIAGRAM. - PIPING FOR A3.102/A3.103 DOES NOT
 REFLECT THE FLOOR PLAN. - CLEANOUT REQUIRED AT THE BASE
 OF P/9 STACK. - PIPING TO FLOOR DRAINS IN ROOMS
 A3.102/A3.103 ARE ABOVE THE FLOOR. -W/C AT THE BASE
 OF STACK NOT VENTED. SECTION 901.2.1. - INDICATE WHERE
 LINES TO FLOOR DRAINS IN ROOMS A4.103/A4.104 &
 A5.103/A5.104 ARE CONNECTING TO THE BRANCH/STACK. -
 PIPING FOR A4.103/A4.104 DOES NOT REFLECT THE FLOOR
 PLAN. - W/C AT RISER STACK A4.103 IS NOT VENTED.
 SECTION 901.2.1. - PIPING FOR A4.105 DOES NOT REFLECT
 THE FLOOR PLAN. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE FOLLOWING COMMENTS WERE NOT
 ADDRESSED:-PIPING TO A3.304 & DOWNSTREAM DOES NOT
 REFLECT THE FLOOR PLAN. - VENT PIPING FROM S-1 SINK
 DOES NOT REFLECT THE FLOOR PLAN. OFFSET NOT SHOWN. -
 PIPING TO ROOMS A1.105/A1.106 DOES NOT REFLECT THE
 FLOOR PLAN. FLOOR DRAIN PIPING IS SHOWN AS ABOVE THE
 FLOOR. -PIPING FOR A4.103/A4.104 DOES NOT REFLECT THE
 FLOOR PLAN. - W/C AT RISER STACK A4.103 IS NOT VENTED.
 SECTION 901.2.1. - PIPING FOR A4.105 DOES NOT REFLECT
 THE FLOOR PLAN. SECTION 106.1.1.
 ******RESPONSE NOTED, BUT THE PIPING TO A3.304 &
 DOWNSTREAM DOES NOT REFLECT THE FLOOR PLAN. CORRELATE
 RISER & FLOOR PLAN.--VENT PIPING FROM S-1 SINK
 STILL DOES NOT REFLECT THE FLOOR PLAN. CORRELATE RISER
 AND FLOOR PLAN.
  
 38B. OK
  
 39B. SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE GAS PERMIT:
  
 A. OK
 B. OK
 C. OK
 D. OK
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED, BUT NOT ADDRESSED. ******RESPONSE
 NOTED, BUT THE SIZING OF THE PIPE SHALL BE TO THE MOST
 REMOTE APPLIANCE/GENERATOR. PLEASE INDICATE THE TOTAL
 DEVELOPED LENGTH TO THE MOST REMOTE FUTURE GENERATOR.
  
 F. OK
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT NO MANUF. SHEETS FOR THE
 GENERATOR HAS BEEN SUBMITTED. - ALSO SUBMIT THE MANUF.
 SPECIFICATION SHEETS FOR THE GAS REGULATORS. INDICATE
 MODEL NUMBER. LISTING INFORMATION REQUIRED.
 ******RESPONSE NOTED, BUT THE BTU LOAD FOR THE NATURAL
 GAS @ 100% LOAD IS NOT INDICATED ON THE MANUF.
 SPECIFICATION SHEETS. THIS SHALL BE SHOWN TO VERIFY
 PIPE SIZING.
  
 H. NA
 I. NA
  
 40B. SHT P3-5.0 NO HOT WATER LINE SHOWN IN 1ST THRU 4TH
 FLOOR TOILET ROOMS OFF WATER RISER W/1. - WATER RISER
 DOES NOT REFLECT THE FLOOR PLAN AT THE LAVS. - FULL
 OPEN VALVES ARE REQUIRED ON ALL WATER DOWN-FEED LINES.
 SECTION 606.1(4). - RISER DOES NOT REFLECT THE FLOOR
 PLAN AT ROOMS C2.102/C2.103. (2 LAVS SHOWN EACH TOILET
 ROOM). - PIPE SIZE SUPPLYING ROOMS D1.101/D1.102,
 JANITOR ROOM D1.110, TOILET ROOMS A1.108/A1.109. -
 INDICATE THAT RISERS W/4, W/5, & W/8 RISERS START WITH
 RISER W/2 ON THE 1ST FLOOR. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE FOLLOWING COMMENTS WERE NOT
 ADDRESSED: - WATER RISER DOES NOT REFLECT THE FLOOR
 PLAN AT THE LAVS. - FULL OPEN VALVES ARE REQUIRED ON
 ALL WATER DOWN-FEED LINES. SECTION 606.1(4). (MANY
 LAVS, TOILET ROOMS, SINKS ETC MISSING VALVES).- RISER
 DOES NOT REFLECT THE FLOOR PLAN AT ROOMS C2.102/C2.103.
 (2 LAVS SHOWN EACH TOILET ROOM). - PIPE SIZE SUPPLYING
 ROOMS D1.101/D1.102, JANITOR ROOM D1.110, TOILET ROOMS
 A1.108/A1.109. (2" SHOWN ON FLOOR PLAN, 1-1/2" ON
 RISER. 3/4" ON FLOOR PLAN, 1/2" ON RISER.SOME LAVS
 SHOW SEPARATE DROPS TO EACH LAV ON THE FLOOR PLAN, BUT
 SINGLE DROPS ON THE RISER). - INDICATE THAT RISERW/8
 STARTS WITH RISER W/2 ON THE 1ST FLOOR. SECTION
 106.1.1.
 ******RESPONSE NOTED, BUT THE SIZE OF THE SUPPLY PIPING
 TO THE JANITOR ROOM D1.110 DOES NOT REFLECT THE FLOOR
 PLAN, AS WELL AS THE PIPE SIZE SUPPLYING TOILET ROOMS
 A1.108/A1.109. PLEASE CORRELATE THE RISER AND FLOOR
 PLAN.
  
 41B. SHT P3-6.0 RISERS 4, 5 & 8 ARE NOT INDICATED ON
 THE 1ST FLOOR. - RISER DOES NOT REFLECT THE FLOOR PLAN
 ROOMS C3.107/C3.108 AT JAN. SINK, ROOMS C3.410/C3.412,
 AE.111, A4.103/A4.104, A4.105 AND THE TOP OF RISER W/4
 TO ROOM A5.105, PIPE SIZE AT ROOM A2.209 & SUPPLY TO
 TOILET ROOM ADJACENT, PIPE SIZE SUPPLYING RISER W/8 &
 RISER, SUPPLY LINE TO ROOMS D2.102/D2.103. - W/2 NOT
 FOUND ON 4TH FLOOR AS INDICATED ON RISER. SECTION
 106.1.1.
 ****RESPONSE NOTED, BUT THE FOLLOWING COMMENTS WERE NOT
 ADDRESSSED: RISER 8 STILL NOT INDICATED ON THE 1ST
 FLOOR. - RISER DOES NOT REFLECT THE FLOOR PLAN ROOMS
 C3.410/C3.412,A4.103/A4.104, (FLOOR PLAN INDICATES
 OVER-HEAD SUPPLY WITH DROPS, BUT RISER INDICATES SUPPLY
 RUN IN THE WALL OFF WATER RISER. TWO W/C'S MISSING ON
 RISER).-PIPE SIZE AT ROOM A2.209, (SHOWS 1" ON THE
 FLOOR PLAN), - PIPE SIZE SUPPLYING RISER W/8 & RISER, (
 1" ON FLOOR PLAN, 2" ON RISER - 1-1/2" ON THE FLOOR
 PLAN, BUT 2" ON THE RISER). -W/2 NOT FOUND ON 4TH OR
 5TH FLOORS AS INDICATED ON RISER. SECTION 106.1.1.
 PLEASE CORRELATE RISER AND FLOOR PLANS. ******RESPONSE
 NOTED, BUT THE RISER STILL DOES NOT REFLECT THE FLOOR
 PLAN, NOR DOES IT REFLECT THE PIPE SIZING FOR THE HOT
 SUPPLY TO TOILET ROOMS C3.410/C3.412.--TOILET ROOMS
 A4.103/A4.104 WATER PIPING STILL DOES NOT REFLECT THE
 FLOOR PLAN.--PIPE SIZE SUPPLYING RISER W/8 STILL
 DOES NOT REFLECT THE FLOOR PLAN. CHECK PIPING
 DOWNSTREAM OF RISER W/8 AND CORRELATE PIPING BETWEEN
 THE RISER AND THE FLOOR PLAN.
  
 42B. SHT P3-7.0 SIZE ALL PIPE PER SECTION 1106.3, AND
 SHOW ALL PIPE SIZES ON THE RISER. - RISER DOES NOT
 REFLECT THE FLOOR PLAN TOP FLOORS RWL/6 & RWL/7. -
 RISERS INDICATE A 5TH FLOOR, BUT FLOOR PLAN DOES NOT
 SHOW A 5TH FLOOR. - RISER SHOWS TRENCH DRAINS ON TWO
 FLOORS, BUT ONLY SHOW TRENCH DRAINS ON 1 FLOOR, (ROOF
 LEVEL), ON THE FLOOR PLAN. -RWL'S 9 THRU 14 SHOW OFFSET
 PIPING FOR ROOF DRAINS IN THE 4TH FLOOR CEILING, BUT
 INDICATE THE ROOF DRAINS TO BE ON THE 4TH LEVEL. PLEASE
 CLARIFY. - PIPE SIZING IS INCORRECT AT 8"/11,715SF,
 6"/5077SF, 6"/6657SF. TABLE 1106.3. - RWL/9 INDICATES
 PIPING IN 3RD FLOOR CEILING, BUT ROOF DRAINS ARE TO BE
 ON THE 3RD LEVEL. PLEASE CLARIFY. - RWL/15 DOES NOT
 REFLECT THE FLOOR PLAN TO 4" ROOF DRAINS. - PIPING AT
 THE 1ST FLOOR CEILING CONNECTING TO ROOF DRAINS ON THE
 1ST LEVEL. PLEASE CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT SOME COMMENTS THE FOLLOWING
 COMMENTS WERE NOT ADDRESSED:- RISER DOES NOT REFLECT
 THE FLOOR PLAN TOP FLOORS RWL/6 & RWL/7. - RISERS
 INDICATE A 5TH FLOOR, BUT FLOOR PLAN DOES NOT SHOW A
 5TH FLOOR. - RISER SHOWS TRENCH DRAINS ON TWO FLOORS,
 BUT ONLY SHOW TRENCH DRAINS ON 1 FLOOR, (ROOF LEVEL),
 ON THE FLOOR PLAN. - PIPE SIZING IS INCORRECT AT
 8"/11,715SF, 6"/5077SF, 6"/6657SF. TABLE 1106.3.
 ******RESPONSE NOTED, BUT I STILL HAVE QUESTIONS AS TO
 THE TRENCH DRAINS. IT SEEMS ON THE RISER DIAGRAM THAT
 THE UPPER TRENCH DRAINS ARE SHOWN AT THE WRONG
 ELEVATIONS. THERE IS NO LEVEL ABOVE THE 5TH LEVEL FOR
 RWL 7 & THE AREA DRAINS FOR THE ROOF ON RWL 6COLLECT
 THE ROOF AREA. SHOULDN'T THE TRENCH DRAINS BE AT THE
 BOTTOM OF THE RAMPS BELOW THE ROOF AREAS. PLEASE
 CLARIFY.
  
 43B. SHTS 1,2,3 OF 3 ARE NOT SIGNED, SEALED, & DATED AS
 REQUIRED PER FS 472.025(1). ALSO SEE SHT 1 WHICH STATES
 "NOT VALID UNLESS SEALED WITH SURVEYOR'S EMBOSSED SEAL
 AND SIGNATURE"
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT SHTS 2 & 3 ARE NOT SIGNED,
 SEALED, DATED. IF THE DESIGN PROFESSIONAL IS AN
 ARCHITECT OR ENGINEER LEGALLY RESISTERED UNDER THE LAWS
 OF THIS STATE REGULATING THE PRACTICE OF ARCHITECTURE
 AS PROVIDED FOR IN CHAPTER 481, FLORIDA STATUTES, PART
 I,OR ENGINEERING AS PROVIDED FOR IN CHAPTER 471,
 FLORIDA STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA AS REQUIRED BY
 FLORIDA STATUTES. SECTION 106.1.
  
 44B. SHTS C1, C5 THRU C22 ENGINEERING CERTIFICATE OF
 AUTHORIZTION IS REQUIRED IN THE TITLE BLOCK.
 61G15-23.002(2) & FS 471.025. - AN EMBOSSED SEAL IS
 REQUIRED TO IMPRESS REQUIRED INFORMATION ON EACH SHEET.
 UNABLE TO GLEAN ALL INFORMATION REQUIRED FROM SEAL.
 PLEASE RESEAL PLANS.
 ****NO RESPONSE, NOT ADDRESSED.
 ******NO RESPONSE, NOT ADDRESSED.
  
 45B. OK
 46B. OK
 47B. OK
 48B. OK
  
 49B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 3RD
 FLOOR DRINKING FOUNTAINS SHOW ONLY 3 ARE REQUIRED. PER
 TABLE 403.1, 4 DRINKING FOUNTAINS ARE REQUIRED. PLEASE
 UPDATE FIXTURE COUNT.
 ****NO RESPONSE, NOT ADDRESSED.
 *****RESPONSE NOTED, NO CHANGE NOTED, NOT ADDRESSED
  
 50B. OK
  
 51B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 1ST
 FLOOR DRINKING FOUNTAINS 2 REQUIRED PER TABLE 403.1,
 BUT READS 1 REQUIRED. PLEASE CORRECT FIXTURE COUNT
 REQUIRED.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, NO CHANGE, NOT ADDRESSED.
  
 52B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 3RD
 FLOOR DRINKING FOUNTAINS 4 REQUIRED PER TABLE 403.1,
 BUT READS 2 REQUIRED. PLEASE CORRECT FIXTURE COUNT
 REQUIRED. - SHOWS 2 PROVIDED, BUT 4 ARE REQUIRED.
 PLEASE CORRECT INFORMATION.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, NOW SHOWS 3 REQUIRED, 4 DRINKING
 FOUNTAINS ARE REQUIRED. NOT ADDRESSED.
  
 53B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 4TH
 FLOOR LAVS REQUIRED 2, INDICATED AS 1. PLEASE CORRECT
 THE FIXTURE COUNT. TABLE 403.1.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, NO CHANGE, NOT ADDRESSED.
  
 54B. OK
  
 55B. SHT LSO.0 INDICATES ASSEMBLY OCCUPANCY FOR THE
 CITY HALL AND LIBRARY/MUSEUM. POTTY PARITY IS REQUIRED
 PER SECTION 403.1.1 AND HAS BEEN INDICATED IN THE 50%
 REVIEW BY PAUL SCHMITZ. THIS HAS NOT BEEN ADDRESSED.
 PLEASE SHOW COMPLIANCE WITH THIS REQUIREMENT. ****NO
 RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT POTTY PARITY HAS NOT BEEN
 ADDRESSED, THERE IS NO 3:2 RATIO AS REQUIRED. THERE IS
 A 1:1 RATIO. THE SECTION OF THE CODE REFERENCED DOES
 NOT SAY THAT IF THERE IS A DIFFERENCE OF 2 OR MORE
 WATER CLOSETS FOR WOMEN PARITY IS AUTOMATICALLY
 ACHIEVED.IT STATES "UNLESS THERE ARE 2 OR FEWER
 FIXTURES FOR MEN". THIS MEANS THAT IF THE OCCUPANCY IS
 SMALL ENOUGH TO ONLY REQUIRE 2 FIXTURES FOR THE MEN,
 THEN POTTY PARITY IS NOT REQUIRED. NO MENTION OF POTTY
 PARITY FOR CITY HALL ASSEMBLY HAS BEEN MENTIONED IN THE
 RESPONSE. PLEASE INDICATE HOW POTTY PARITY WILL BE
 COMPLIED WITH.
  
 56B. OK
 57B. OK
 58B. OK
 59B. OK
 60B. OK
 61B. OK
 62B. OK
  
 63B. SHT A6-1.1 DETAIL 7, ACCESSIBLE W/C SHALL BE 1'6"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG.
 11-28. (SHOWS 2'2").
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, NO CHANGE, NOT ADDRESSED
  
 64B. OK
 65B. OK
 66B. OK
 67B. OK
 68B. OK
 69B. OK
  
 70B. SHTS A9-0.1 & A9-0.2 FINISH SCHEDULES: ROOMS
 C1.105, C1.106, A2.705, A2.706, A2.210, A2.211, A3.111,
 A3.114, C3.410, AND C3.412 ALL INDICATE THE WALLS TO BE
 PAINTED. PLEASE INDICATE HOW THIS COMPLIES WITH THE
 REQUIREMENT FOR "SMOOTH, HARD, NONABSORBENT WALLS AS
 REQUIRED IN SECTION 1210.2.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT EPOXY DOES NOT COMPLY WITH
 THE REQUIREMENT FOR THE SURFACE TO BE HARD.--PLEASE
 INDICATE WHAT PNT-5, CT 2-5 MEANS. THE FLOOR AND BASE
 HAVE BEEN INDICATE AS CT. DOES THE CT 2-5 MEAN THAT THE
 CERAMIC TILE WILL START AT 2' AND EXTEND UP TO 5'? IF
 SO, WILL THE BASE BE 2' WIDE? PLEASE CLARIFY AS THERE
 IS NO FINISH LEGNED WITH THE NUMBER DESIGNATIONS AFTER
 THE MATERIAL. (PNT-5 OR CT 2-5).
  
 71B. OK
  
 72B. SHT A9-4.1 INDICATE THE ROOM NUMBERS THAT THE
 DETAIL IS REFERENCING. SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.18.4 FLUSH CONTROLS
 B. 11-4.19.2 CLEARANCES
 C. 11-4.19.4 EXPOSED PIPES & CLEARANCES
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE CONTROL HEIGHT FOR THE
 URINAL IS NOT INDICATED.
  
 73B. SHT A9-4.2 INDICATE THE ROOM NUMBERS THAT THE
 DETAIL IS REFERENCING. SHOW COMPLIANCE WITH THE
 FOLLOWING:
 DETAIL #1
 A. 11-4.18.4 FLUSH CONTROLS
 B. 11-4.19.2 CLEARANCES
 C. 11-4.19.4 EXPOSED PIPES & CLEARANCES
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE CONTROL HEIGHT FOR THE
 URINAL IS NOT INDICATED.
  
 DETAIL #2
 A. 11-4.18.4 FLUSH CONTROLS
 B. 11-4.19.2 CLEARANCES
 C. 11-4.19.4 EXPOSED PIPES & CLEARANCES
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE CONTROL HEIGHT FOR THE
 URINAL IS NOT INDICATED.
  
 74B. OK
  
 75B. SHT A9-4.5 DETAILS (1) & (2), SHOW THE FOLLOWING
 FOR COMPLIANCE:A. 11-4.19.2 CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 D. 11-4.21.5 CONTROLS
 E. 11-4.21.7 CURBS
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE HEIGHT FOR THE CONTROLS
 IN THE SHOWER ARE NOT INDICATED.
  
 76B. SHTS A1.307, A1.709, A2.209, A2.315, A2.407,
 A3.109, C3.409, C3.310, A5.504 - SHOW COMPLIANCE WITH
 THE FOLLOWING
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH
 REQUIRED)
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
 D. 11-4.24.7 FAUCETS
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE FAUCETS WERE NOT
 ADDRESSED.
  
 *************NEW COMMENTS*************
  
 1C. SHTA9-4.6 DETAILS 1 & 2 SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.18.4 FLUSH CONTROLS
 B. 11-4.19.2 CLEARANCES
 C. 11-4.19.4 EXPOSED PIPES & SURFACES ******RESPONSE
 NOTED, BUT THE SHEET NUMBER WAS A TYPO. THIS IS
 REQUIRED ON SHT A9-4.6.
  
 2C. SHT A9-4.7 DETAILS 1, 2, & 3 SHOW COMPLIANCE WITH
 THE FOLLOWING:
 A. 11-4.18.4 FLUSH CONTROLS
 B. 11-4.19.2 CLEARANCES
 C. 11-4.19.4 EXPOSED PIPES & SURFACES ******RESPONSE
 NOTED, BUT THE SHEET NUMBER WAS A TYPO. THIS IS
 REQUIRED ON SHT A-04.7.
  
 3C. SHT P1-6.0 THE FOLLOWING VENTS ARE NOT SHOWN ON THE
 ROOF. P1, P2, P3, & P10. PLEASE SHOW ON THIS SHEET OR
 INDICATE WHERE THEY ARE SHOWN. SECTION 106.1.1.
 ******RESPONSE NOTED, BUT VTR P2 IS NOT INDICATED AND
 SHOULD BE LOCATED AT OR NEAR COL. LINE H/2 AS THE RISER
 DIAGRAM INDICATES THE VENT WITH NO OFFSETS.
  
 **************NEW COMMENTS*************
  
 1D. SHT P3-2.0, 1ST FLOOR VENTING FOR THE WATER CLOSETS
 AT THE BASE OF RISER P10 IS NOT SHOWN. SECTION
 901.2.1.
  
 2D. SHT P2-1.0 DETAILS 1 THRU 5. THE SANITARY PIPING IS
 NOT SHOWN ON THE ENLARGED PLANS. ALSO CHECK FOR BOTH
 HOT AND COLD WATER LINES. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. SUBMITTING THE RED
 LINED SET OF PLUMBING SHEETS WHEN RESUBMITTING FOR
 REVIEW WILL HELP EXPEDITE THE PERMIT ALSO. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6721
 E-MAIL [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-12-23 Cont ID  
Sent By kstevens Date 2006-12-23 Time 08:37 Rev Time 0.00
Received By kstevens Date 2006-12-16 Time 17:48 Sent To  
Notes
2006-12-23 17:38:49DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
  
 3. SHT P1-1.1 PUMP ROOM A1-112. RPZV BACKFLOW SHALL BE
 INSTALLED A MAXIMUM OF 4' ABOVE THE FLOOR FOR
 CERTIFICATION AND SERVICE.
 ****RESPONSE NOTED, HEIGHT TO BE INDICATED FOR THE
 BACKFLOWS TO BE A MAXIMUM OF 4' ABOVE THE FLOOR.
 ****RESPONSE NOTED, BUT PLANS INDICATE MINIMUM 4' ABOVE
 THE FLOOR. THE REQUIREMENT IS FOR MAXIMUM 4' ABOVE THE
 FLOOR.
  
 4. OK
  
 5. SHTS P1-1.1 THRU P1-1.3 CLEANOUTS REQUIRED BY
 SECTIONS 708.3.1, 708.3.2, 708.3.4, 708.3.5 AND 11-8.1
 (FOR STORM) SHALL BE SHOWN ON THE PLANS. ****RESPONSE
 NOTED, BUT COMMENT NOT ADDRESSED. MANY CLEANOUTS
 REQUIRED ARE NOT INDICATED. MANY CLEANOUTS REQUIRED ARE
 NOT SHOWN. CLEANOUTS AT THE BASE OF STACKS AS SHOWN ARE
 INCORRECT. THEY DO NOT CLEANOUT THE BASE OF THE STACK.
 ALSO SHOW THE CLEANOUTS REQUIRED ON THE RISER
 DIAGRAMS.
 ****RESPONSE NOTED, BUT THE CLEANOUT SHOWN ON P3-3.0
 DETAIL 1 AS SHOWN IS CORRECT, BUT IT'S NOT SHOWN ON THE
 FLOOR PLAN. PLEASE CORRELATE INFORMATION ON ALL SHEETS.
 ALSO SEE RISERS P/1, P/7 & P/8.
  
 6.OK
 7.OK
 8.OK
 9.OK
 10. OK
 11. OK
 12. OK
 13. OK
  
 14. SHT P1-6.0 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW THE SQUARE FOOTAGE OF EACH
 AREA, AND SHOW 1/2 AREA OF ALL VERTICAL WALLS,
 INCLUDING PARAPETS, AS WELL AS ALL AREAS OF ROOFS
 DRAINING ONTO THE ROOF FROM ABOVE IN THE CALCULATIONS.
 SECTIONS 1106, AND 1107 WITH ALL SUBSECTIONS. SHOW THE
 LOCATION OF ALL SECONDARY ROOF DRAINS AND OR EMERGENCY
 OVERFLOW SCUPPERS. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT NO CALCULATIONS WERE
 SUBMITTED.
 ****RESPONSE NOTED, BUT THE CALCULATIONS ARE NOT
 CORRECT. NO VERTICAL CONTRIBUTION IS SHOWN FOR THE
 LOWER ROOFS. (A1 THRU A4, A7 THRU A9, E1 THRU E4, E7
 THRU E9, E1 THRU E4, & H1 THRU H4). THE WALL AT COL.
 LINES 4&7 BETWEEN COL. LINES A&D, CALCULATIONS INDICATE
 7', WHICH IS SUPPOSED TO BE 1/2 THE WALL HEIGHT. BY
 LOOKING AT A SECTION OF THE WALL, THE HEIGHT IS 20' AND
 1/2 THE WALL HEIGHT SHOULD BE 10'. (SEE A4-2.0WHICH
 SHOW THE WALL TO BE 18', AND IF ITS SIMILAR TO DETAIL 3
 ON SHT A5-1.1 WILL HAVE A 2' PARAPET WALL ON TOP OF THE
 ROOF LINE. PLEASE RECHECK ALL CALCULATIONS FOR THE ROOF
 AREAS.
  
 15. OK
 16. OK (SHOWN ON SHT P2-1.0U)
 17. OK
 18. OK
 19. OK
 20. OK
 21. OK
 22. OK
 23. OK
 24. OK
 25. OK
 26. OK
 27. OK
 28. OK
 29. OK
 30. OK
 31. OK
 32. OK
 33. OK
 34. OK
 35. OK
  
 36. SUBMIT A SANITARY HORIZONTAL RISER ISOMETRIC AND
 VERTICAL RISER DIAGRAMS. SHOW ALL PIPE SIZES, TRAPS,
 VENTS, CLEANOUTS, OFFSETS, RISER NUMBERS AND DFU'S AS
 THEY ACCUMULATE IN THE SYSTEM. SECTION 106.3.5.1.3.
 ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN,
 ALL REQUIRED CLEANOUTS ARE NOT SHOWN, AND DFU'S ARE NOT
 SHOWN AS THEY ACCUMULATE IN THE SYSTEM. ALSO INDICATE
 ON THE FIRST FLOOR WHERE ALL RISERS BEGIN IN THE
 SYSTEM.
 ****RESPONSE NOTED, BUT SHT P3-1.0 RISER 1, LAVS DO NOT
 REFLECT THE FLOOR PLAN 2ND FLOOR C2-1.03. - DOES NOT
 REFLECT THE FLOOR PLAN C4.103/C4.104 DRINKING FOUNTAINS
 SHOW 3, FLOOR PLAN SHOWS 2. - CLEANOUT NOT SHOWN AT THE
 BASE OF P/1. - NOT ALL PIPE SIZES SHOWN.-SHT P3-2.0
 RISER P/2 CLEANOUT DOWNSTREAM OF JANITOR SINK IN ROOM
 C4.101 NOT INSTALLED PER SECTION 706.3. SECOND CLEANOUT
 AT THE BASE OF P/2 NOT REQUIRED AS IT DOES NOT CLEANOUT
 THE BASE OF THE STACK, NOR DOES IT REFLECT THE FLOOR
 PLAN. - FLOOR DRAIN PIPING IN ROOM D1.101 AS INDICATED
 IS BEING INSTALLED ABOVE THE FLOOR. - EACH DRINKING
 FOUNTAIN SHALL HAVE ITS OWN TRAP. SAFE WASTE FOR THE
 FIXTURES IS NOT APPROVED.(SEE ROOMS D1.101, D1.108,
 AND A3.111). -CLEANOUTS ARE REQUIRED AT THE BASE OF
 STACKS P/4 & P/10. - CLEANOUT FOR P/7 NOT INSTALLED AT
 THE BASE OF P/7. -THE NEW SANT. PIPING TO TOILET ROOM
 D2.105 NOT SHOWN ON THE FLOOR PLAN. -SHOW ALL TOILET
 ROOM NUMBERS ON THE RISER DIAGRAM. - SHOW ALL PIPE
 SIZES. THE PIPE SIZES ARE NOT SHOWN ON MANY PIPES.-
 SHT P3-3.0A TWO WAY CLEANOUT IS REQUIRED NEAR THE
 JUNCTION OF THE BUILDING DRAIN AND THE BUILDING SEWER.
 (DETAIL 1).-THE RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN FOR A1.05 & A1.106. AN EXTRA FLOOR DRAIN IS
 INDICATED THAT IS NOT SHOWN ON THE FLOOR PLAN.-
 A3.102 & A3.103 ONLY SHOWS 2 LAVS ON THE RISER AND THE
 FLOOR PLAN SHOWS 4.-A4.103 & A4.104TWO W/C'S ARE
 MISSING FROM THE RISER THAT ARE SHOWN ON THE FLOOR
 PLAN.-A4.105NO FLOOR DRAIN AND A SECOND SINK ARE
 SHOWN ON THE FLOOR PLAN THAT ARE NOT SHOWN ON THE RISER
 DIAGRAM. (JANITOR ROOM).-A5.105 SHOWS THE BRANCH
 LINE CONNECTING NEAR THE DRINKING FOUNTAINS ON THE
 FLOOR PLAN, BUT CONNECTING DOWNSTREAM OF THE NEXT
 FIXTURES ON THE RISER DIAGRAM.-A CLEANOUT IS
 REQUIRED AT THE BASE OF RISER P/8-ALL RISER
 DIAGRAMS,CHECK ALL PIPE SIZES, MAKE SURE THE RISER
 DIAGRAMS REFLECT THE FLOOR PLAN FOR BOTH THE SANITARY
 AND THE VENTING.SECTIONS106.1.1, 106..1.2, 706.3,
 708.3.4, 708.3.5, 100.2.1.
  
 37. SUBMIT A STORM HORIZONTAL RISER ISOMETRIC DIAGRAM &
 VERTICAL RISER DIAGRAMS. SHOW ALL PIPE SIZES, OFFSETS,
 & CLEANOUTS AND INDICATE THE RISER NUMBERS. SHOW THE
 SQUARE FOOTAGE AS IT ACCUMULATES IN THE SYSTEM. SECTION
 106.3.5.1.3.
 ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN,
 ALL REQUIRED CLEANOUTS ARE NOT SHOWN, AND SQUARE
 FOOTAGE AS IT ACCUMULATES IN THE SYSTEM IS NOT
 INDICATED.
 ****RESPONSE NOTED, BUT THE GARAGE STORM INDICATES A
 TOTAL OF 10,498SF. THE TOTAL AREA WITHOUT ANY VERTICAL
 WALL/PARAPET CONTRIBUTION IS 23,663SF. PLEASE
 RECALCULATE THE SQUARE FOOTAGE DRAINING INTO EACH
 DRAIN. SHOW 1/2 AREA OF ALL VERTICAL WALL INCLUDING
 PARAPETS, AS WELL AS ALL AREAS FROM ROOFS THAT DRAIN
 ONTO THE ROOF FROM ABOVE, (SEE STAIRWELL ROOFS &
 ELEVATOR), IN CALCULATIONS. -THE TRENCH DRAINS SHOW
 NO SF CONTRIBUTING TO THE TOTAL SF. INDICATE THE
 LOCATIONS OF THE DOWNSPOUTS FROM THE ROTUNDA/MECHANICAL
 ROOF. IF THE LOCATION IS THE SAME AS SHOWN ON THE
 ARCHITECTURAL PLANS, PLEASE EXPLAIN THE REASONING FOR
 DIVIDING THE UPPER ROOF CONTRIBUTION TO TWO ROOF DRAINS
 ON EACH SIDE OF THE BUILDING, WHEN ACTUALLY THE TOTAL
 AREA WILL DRAIN TO ONE DRAIN ON EACH SIDE. THIS IS ALSO
 A CONCERN FOR THE LOWER ROOF (FIRST STORY)ROOF DRAINS
 ( 1736SF). PLEASE CLARIFY.
  
 38. SUBMIT A WATER RISER ISOMETRIC DIAGRAM. SHOW ALL
 PIPE SIZES, VALVES, WATER HAMMER ARRESTORS, BACKFLOW
 PROTECTION ETC. SECTION 106.3.5.1.3.
 ****RESPONSE NOTED, BUT NOT ALL PIPE SIZES ARE SHOWN,
 NOT ALL REQUIRED VALVES ARE SHOWN, AND ALL WATER HAMMER
 ARRESTORS REQUIRED BY SECTION 604.9, (ICE MAKERS,
 DISHWASHERS, & WASH MACHINES IF FIXTURES ARE
 PROVIDED).
 ****RESPONSE NOTED, BUT THE VALVES ON ALL DOWN-FEED
 WATER LINES ARE MISSING FROM MANY LAV SUPPLY LINES,
 SOME TOILET ROOMS, SS, ETC. SECTION 106.1(4).
  
 39. OK
  
 40. ALL PME & FIRE PROTECTION SHEETS. PLANS SHALL BE
 SIGNED, SEALED, AND DATED. SECTION 106.1. ALL TITLE
 BLOCK INFORMATION REQUIRED BY FAC 61G1-23.002 AND FS
 471.025 SHALL BE SUBMITTED ON EACH SHEET. ****RESPONSE
 NOTED, BUT THE SEAL USED IS NOT APPROVED. NEW SEALS
 SHALL INDICATE THE WORD "LICENSE" IN THE SEAL. (SEE
 ATTACHED SHEET FROM THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS).
 ****RESPONSE NOTED, BUT THE SEALS OF SOME MECH. AND
 PLUMBING SHEETS ARE STILL THE OLD SEAL. - ALSO THERE
 SEEMS TO BE TWO SETS OF SIGNATURES FOR THE ENGINEER OF
 RECORD. PLEASE SUBMIT A SIGNED, SEALED, DATED,
 NOTORIZED LETTER INDICATING THE LEGAL SIGNATURE OF THE
 ENGINEER OF RECORD FOR OUR FILES. ONE SET OF PLANS
 SHALL BE RETAINED FOR POSSIBLE REVIEW BY THE FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS.
  
 **************NEW COMMENTS**************
  
 1B. SHTS P1-1.0U, P1-1.1U, P1-1.1 & P1-2.1. RWL-4 DOES
 NOT REFLECT THE SQUARE FOOTAGE SHOWN ON RISER DIAGRAM
 OR ROOF PLAN. PLEASE CORRELATE RISER, FLOOR PLAN, &
 ROOF PLAN. SECTION 106.1.1.
 ****RESPONSE NOTED. WILL RECHECK AFTER THE CALCULATIONS
 FOR THE ROOF DRAINS HAS BEEN RESUBMITTED WITH
 CORRECTIONS.
  
 2B. SHTS P1-1.OU & P1-1.1U ALL RWL'S THAT CONNECT TO
 RWL-4 TO BE INDICATED ON THE 1ST FLOOR. THIS WILL AID
 IN TRACING THE RWL'S THROUGH THE BUILDING AND TO VERIFY
 PIPE SIZES. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT ISSUE NOT ADDRESSED.
  
 3B. SHTS P1-1.1U & P2-1.0U DETAIL #6 THE SINK SHALL NOT
 DRAIN THRU THE WET VENT FOR THE TOILET ROOM. THE
 DISCHARGE FOR THE SINK SHALL CONNECT DOWNSTREAM OF THE
 TOILET ROOM FIXTURES. SECTION 909.1.
 ****RESPONSE NOTED, BUT THE PIPING HAS NOT BEEN CHANGED
 ON SHT P1-1.0U
  
 4B. OK
  
 5B. SHT P1-1.2U CLEANOUT REQUIRED AT THE BASE OF P/1 &
 P/10 RISERS, NEAR THE JUNCTION OF THE BUILDING DRAIN
 AND THE BUILDING SEWER, AND AT ALL CHANGES OF DIRECTION
 OVER 45 DEGREES. PLEASE INDICATE ON PLANS. SECTIONS.
 708.3.3, 708.3.4, 708.3.5.
 ****RESPONSE NOTED, BUT C/O'S ARE NOT SHOWN ON SHTS
 P3-1.0 & P3-2.0.
  
 6B. SHTS P1-1.2U, ASSOCIATED RISER DIAGRAMS, AND
 ENLARGED FLOOR PLANS. INDICATE HOW THE STACKS P/1 &
 P/10 CAN DRAIN INTO THE TOILET GROUP FIXTURE BRANCH.
 SUBMIT A DETAIL SHOWING THE 4" CLEANOUT TEE, THE 4"
 CROSS FOR THE FIXTURE BRANCH, AND THE 4" DOUBLE
 Y/EIGHTH BEND FITTINGS STACKED ON TOP OF EACH OTHER.
 WILL THEY BE AT THE RIGHT HEIGHT FOR THE W/C'S?SEE
 SECTION 908.3 ALSO. SECTION 106.1.1. (STACKS SHOULD
 CONNECT TO THE BUILDING DRAIN AND FIXTURE GROUPS SHOULD
 CONNECT TO THE STACK SO THAT THE STACK DOES NOT RUN
 THRU THE MIDDLE OF THE FIXTURE GROUP). ****RESPONSE
 NOTED, BUT C/O'S ARE REQUIRED AT THE BASE OF EACH
 STACK. COMMENT HAS NOT BEEN ADDRESSED.
  
 7B. SHTS P1-1.3U, P1-2.0, P1-2.3, P1-3.3, & P1-4.3
 RWL-6 DOES NOT REFLECT THE SQUARE FOOTAGE SHOWN ON THE
 RISER DIAGRAM, NOR ON THE ROOF PLAN. PLEASE CORRELATE
 INFORMATION. SECTION 106.1.1 & TABLE 1106.3.
 ****RESPONSE NOTED, BUT THE COMMENT WAS NOT ADDRESSED
 ON SHTS P1-3.3, & P1-4.3.
  
 8B. OK
 9B. OK
 10B. OK
 11B. OK
  
 12B. SHT P1-4.1 SHOW RISER P/3 VTR. - NOTE STATES "SEE
 01 ON DRAWING P2-3.0". INFORMATION NOT SHOWN ON DETAIL
 01. PLEASE CLARIFY. - SHOW THE VENTING TO REFLECT THE
 FLOOR PLAN FOR KINK S-1 CONNECTED TO RISER P/8. - 4"
 SANITARY - 4" VTR AT COL. LINE E/8 IS SHOWN AS AN
 OFFSET ON THE RISER DIAGRAM. PLEASE CORRELATE FLOOR
 PLAN AND SANT. RISER DIAGRAM. SECTION 106.1.1.
 ****RESPONSE NOTED. NOTE DELETED, BUT COMMENT NOT
 ADDRESSED FOR OFFSETS AND VENTING. -VENTING ON ALL
 RISERS SHALL REFLECT THE VENTING ON THE FLOOR PLAN.
 (ALL VENTING NOT SHOWN ON THE FLOOR PLAN), AND ON THE
 ENLARGED PLUMBING PLANS FLOOR PLAN.
  
 13B. OK
 14B. OK
  
 15B. SHT P1-6.0 SHOW THE LOCATIONS FOR ALL VTR'S. -
 INDICATE THE RWL EACH ROOF DRAIN IS CONNECTED TO.
 SECTION 106.1.1.
 ****RESPONSE NOTED, BUT VTR'S 1, 3, 9 & 10 ARE NOT
 SHOWN.
  
 16B. SHT P2-1.0U DETAIL 1, FLOOR DRAINS IN C1.104 ARE
 NOT VENTED. SECTION 901.2.1. - THE PIPING AT THE LAVS
 IN ROOM C1.103 DOES NOT REFLECT THE RISER DIAGRAM.
 PLEASE CORRELATE. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE FLOOR DRAIN IN THE
 ACCESSIBLE STALL HAS NOT CHANGED TO REFLECT THE CHANGE
 IN THE RISER DIAGRAM.
  
 17B. SHT P2-1.0U DETAIL 2 DOES NOT REFLECT THE PIPING
 LAYOUT SHOWN ON P1-1.2U. - SUBMIT A DETAIL FOR THE
 SANT. PIPING ARRANGEMENT FOR THE DRINKING FOUNTAINS,
 SHOW HOW THE PIPING CONNECTS THROUGH THE SIDE OF THE
 D.F. UNITS. - SUBMIT A DETAIL FOR THE FITTING
 ARRANGEMENT WHERE THE TOILET ROOM FIXTURES CONNECT TO
 THE BLDG. DRAIN. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT A DETAIL HAS NOT BEEN
 SUBMITTED. ALSO EXPLAIN THE 3" SANT. LINE FROM THE
 DRINKING FOUNTAINS TO THE MEN'S ROOM D1/101.-THE
 FLOOR DRAIN PIPING APPEARS TO BE ABOVE THE SLAB. PLEASE
 CLARIFY.
  
 18B. OK
  
 19B. SHT P2-1.0U DETAIL 6, SINK SHALL CONNECT
 DOWNSTREAM OF THE WET VENTED FIXTURES IN THE TOILET
 ROOM. SECTION 909.1.
 ****RESPONSE NOTED. CORRECTED, BUT NOT CORRECTED ON SHT
 P1-1.1U. PLEASE CORRECT TO REFLECT RISER AND DETAIL.
  
 20B. OK
 21B. OK
  
 22B. SHT P2-1.0 DETAIL 4 DOES NOT REFLECT THE FLOOR
 PLAN. NO WATER TO WH'S & SHOWS 2" WATER SUPPLY. SECTION
 106.1.1.
 ****RESPONSE NOTED, BUT STILL NO WATER SUPPLY TO WATER
 HEATERS.
  
 23B. OK
 24B. OK
 25B. OK.
  
 26B. SHT P2-2.0 DETAIL 3, SUBMIT A DETAIL FOR SANT.
 PIPING TO D.F.'S - INDICATE RISERS FOR COLD WATER
 DOWNSTREAM OF LAST W/C'S. HOT WATER LINE NOT SHOWN THRU
 BATHROOM FIXTURES. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT STILL SHOWS PIPING OUT THE SIDE
 OF 1ST DF.
  
 27B. OK
 28B. OK
 29B. OK
  
 30B. SHT P2-3.0 DETAIL 1, INDICATE WHERE SANT. BRANCH
 LINE CONNECTS TO THE SANT. RISER. - FLOOR DRAIN SHOWS
 NO PIPING. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT RISER SHOWS P1 RISER BETWEEN
 W/C'S & LAVS, WHEREAS THE FLOOR PLAN SHOW THE RISER
 BETWEEN W/C'S. CORRELATE RISER AND FLOOR PLAN.
  
 31B. OK
 32B. OK
 33B. OK
  
 34B. SHT P3.1.0 SANT RISER DIAGRAM, TRAPS ARE REQUIRED
 ON ALL DRINKING FOUNTAINS. SECTION 1002.1. - 1ST FLOOR
 LAVS PIPING DOES NOT REFLECT THE FLOOR PLAN. - FLOOR
 DRAINS DOWNSTREAM OF RISER P/1 ARE NOT VENTED. SECTION
 901.2.1. - A C/O IS REQUIRED AT THE BASE OF STACK P/1
 SECTION 708.3.4 - SHOW THE CONNECTION DETAIL AT THE
 BASE OF STACK P/1 WITH A 4" CLEANOUT, A 4" CROSS, AND
 4" WYE FITTINGS INDICATING THE HEIGHT OF THE W/C
 STUBOUT. - W/C-1 AT THE BASE OF STACK IS NOT VENTED.
 SECTION 901.2.1. -W/C ON 2ND FLOOR IS NOT VENTED.
 SECTION 901.2.1. - LAV ON 3RD FLOOR NOT VENTED. SECTION
 901.2.1. - INDICATE HOW/WHERE PIPING FOR LAVS & FLOOR
 DRAINS CONNECT TO THE RISER/BRANCH ON THE 2ND, 3RD, &
 4TH FLOORS. THE FITTINGS INDICATE THAT THE PIPING IS
 SLOPED TO THE LAVS. PLEASE CLARIFY. - MEN C4.104 DOES
 NOT REFLECT ROOM NUMBER ON THE FLOOR PLAN. - PIPING FOR
 FLOOR DRAINS & LAVS 4TH FLOOR DOES NOT REFLECT THE
 FLOOR PLAN. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT 1ST FLOOR LAVS PIPING DOES NOT
 REFLECT THE FLOOR PLAN. -A C/O IS REQUIRED AT THE
 BASE OF STACK P/1 SECTION 708.3.4 - SHOW THE CONNECTION
 DETAIL AT THE BASE OF STACK P/1 WITH A 4" CLEANOUT, A
 4" CROSS, AND 4" WYE FITTINGS INDICATING THE HEIGHT OF
 THE W/C HOW THE CONNECTION DETAIL AT THE BASE OF STACK
 P/1 WITH A 4" CLEANOUT, A 4" CROSS, AND 4" WYE FITTINGS
 INDICATING THE HEIGHT OF THE W/C STUBOUT. - MEN C4.104
 DOES NOT REFLECT ROOM NUMBER ON THE FLOOR PLAN. -
 PIPING FOR FLOOR DRAINS & LAVS 4TH FLOOR DOES NOT
 REFLECT THE FLOOR PLAN. SECTION 106.1.1. THESE ITEMS
 HAVE NOT BEEN ADDRESSED.
  
 35B. ALL RISER DIAGRAMS, ALL FLOOR PLANS FOR ALL
 SYSTEMS. INDICATE THE PIPE SIZE. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT MANY PIPE SIZES ARE NOT SHOWN
 ON THE RISER DIAGRAMS.
  
 36B. SHT P3-2.0 JANITOR ROOM PIPING DOES NOT REFLECT
 THE FLOOR PLAN. - TRAPS REQUIRED ON ALL DRINKING
 FOUNTAINS. SECTION 1002.1. - CLEANOUTS REQUIRED AT THE
 BASE OF ALL STACKS. 708.3.4. - PIPING TO FLOOR DRAIN
 SHOWN ABOVE THE FLOOR IN ROOM D1.101. PLEASE CLARIFY. -
 PIPING AT THE BASE OF RISER P/2 DOES NOT REFLECT THE
 FLOOR PLAN. - PIPING TO FD-2 AT THE LOADING D1.106 DOES
 NOT REFLECT THE FLOOR PLAN. - PIPING FOR A1.108/A1.109
 DOES NOT REFLECT THE FLOOR PLAN. - ROOM D2.103 IS
 INDICATED AS D2.104 ON THE FLOOR PLAN. CORRELATE
 INFORMATION. - ALL VENTING AT RISER P/10 STOPS AT LEVEL
 2. SECTION 903.3 VTR REQUIRED. - TOILET ROOM A2.708 IS
 INDICATED AS A2.706 ON THE FLOOR PLAN. CORRELATE
 INFORMATION. - BATHROOM RISER DOES NOT REFLECT THE
 FLOOR PLAN. (NO FD). - PIPING TO ROOM A4.414 DOES NOT
 REFLECT THE FLOOR PLAN. - CLEANOUT PIPING DOWNSTREAM OF
 C4.101 IS NOT APPROVED AS PIPED. SECTION 706.3. -
 PIPING ON RISER DOES NOT REFLECT THE FLOOR PLAN
 UPSTREAM OF C3.105. - JANITOR SINK C3.105 IS NOT
 VENTED. SECTION 901.2.1. - FLOOR DRAIN CONNECTION AT
 BRANCH LINE 4TH FLOOR DOES NOT REFLECT THE FLOOR PLAN.
 - PIPING AT A2.107 DOES NOT REFLECT THE FLOOR PLAN. (NO
 F.D. PIPING). - PIPING AT ROOM A3.111 DOES NOT REFLECT
 THE FLOOR PLAN AT THE LAVS. - ROOM A3.111 SUBMIT A
 DETAIL FOR FITTING TO W/C & LAVS. - ROOM D2.105 SHOWN
 AS D2.106/D2.107 ON FLOOR PLANS. CORRELATE INFORMATION.
 - ROOM C3.410/C3.412 FLOOR DRAIN FITTING ARE SHOWN TO
 BE INSTALLED AGAINST THE FLOW. SECTION 706.3. - SECTION
 106.1.1.
 ****RESPONSE NOTED, BUT SOME COMMENTS WERE NOT
 ADDRESSED. SEE THE FOLLOWING: JANITOR ROOM PIPING DOES
 NOT REFLECT THE FLOOR PLAN. - TRAPS REQUIRED ON ALL
 DRINKING FOUNTAINS. SECTION 1002.1. - CLEANOUTS
 REQUIRED AT THE BASE OF ALL STACKS. 708.3.4. - PIPING
 TO FLOOR DRAIN SHOWN ABOVE THE FLOOR IN ROOM D1.101.
 PLEASE CLARIFY.- PIPING AT THE BASE OF RISER P/2 DOES
 NOT REFLECT THE FLOOR PLAN. - PIPING FOR A1.108/A1.109
 DOES NOT REFLECT THE FLOOR PLAN. - ROOM D2.103 IS
 INDICATED AS D2.104 ON THE FLOOR PLAN. CORRELATE
 INFORMATION.- TOILET ROOM A2.708 IS INDICATED AS
 A2.706 ON THE FLOOR PLAN. CORRELATE INFORMATION. -
 PIPING TO ROOM A4.414 DOES NOT REFLECT THE FLOOR PLAN.
 - CLEANOUT PIPING DOWNSTREAM OF C4.101 IS NOT APPROVED
 AS PIPED. SECTION 706.3. - PIPING AT ROOM A3.111 DOES
 NOT REFLECT THE FLOOR PLAN AT THE LAVS. - ROOM A3.111
 SUBMIT A DETAIL FOR FITTING TO W/C & LAVS. - ROOM
 D2.105 SHOWN AS D2.106/D2.107 ON FLOOR PLANS. CORRELATE
 INFORMATION.
  
 37B. SHT P3-3.0 PIPING TO A3.304 & DOWNSTREAM DOES NOT
 REFLECT THE FLOOR PLAN. - VENT PIPING FROM S-1 SINK
 DOES NOT REFLECT THE FLOOR PLAN. OFFSET NOT SHOWN. -
 TRAPS REQUIRED ON ALL DRINKING FOUNTAINS. SECTION
 1002.1. - S-1 SINK SHALL NOT DRAIN THRU THE WET VENT OF
 THE TOILET ROOM A1.303. SINK SHALL DISCHARGE DOWNSTREAM
 OF THE W/C & LAV. SECTION 909.1. - INDICATE P/8 WITH
 P/6 AT THE BASE OF THE STACK WHERE IT BEGINS. - PIPING
 TO ROOMS A1.105/A1.106 DOES NOT REFLECT THE FLOOR PLAN.
 FLOOR DRAIN PIPING IS SHOWN AS ABOVE THE FLOOR. - P/5 &
 P/9 BEGIN AT THE BASE OF THE STACK. PLEASE INDICATE ON
 RISER DIAGRAM. - PIPING FOR A3.102/A3.103 DOES NOT
 REFLECT THE FLOOR PLAN. - CLEANOUT REQUIRED AT THE BASE
 OF P/9 STACK. - PIPING TO FLOOR DRAINS IN ROOMS
 A3.102/A3.103 ARE ABOVE THE FLOOR. -W/C AT THE BASE
 OF STACK NOT VENTED. SECTION 901.2.1. - INDICATE WHERE
 LINES TO FLOOR DRAINS IN ROOMS A4.103/A4.104 &
 A5.103/A5.104 ARE CONNECTING TO THE BRANCH/STACK. -
 PIPING FOR A4.103/A4.104 DOES NOT REFLECT THE FLOOR
 PLAN. - W/C AT RISER STACK A4.103 IS NOT VENTED.
 SECTION 901.2.1. - PIPING FOR A4.105 DOES NOT REFLECT
 THE FLOOR PLAN. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE FOLLOWING COMMENTS WERE NOT
 ADDRESSED:-PIPING TO A3.304 & DOWNSTREAM DOES NOT
 REFLECT THE FLOOR PLAN. - VENT PIPING FROM S-1 SINK
 DOES NOT REFLECT THE FLOOR PLAN. OFFSET NOT SHOWN. -
 PIPING TO ROOMS A1.105/A1.106 DOES NOT REFLECT THE
 FLOOR PLAN. FLOOR DRAIN PIPING IS SHOWN AS ABOVE THE
 FLOOR. -PIPING FOR A4.103/A4.104 DOES NOT REFLECT THE
 FLOOR PLAN. - W/C AT RISER STACK A4.103 IS NOT VENTED.
 SECTION 901.2.1. - PIPING FOR A4.105 DOES NOT REFLECT
 THE FLOOR PLAN. SECTION 106.1.1.
  
 38B. OK
  
 39B. SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE GAS PERMIT:
  
 A. OK - "NEW"SHOW THE LOCATION OF THE 2PSI TO 1/2PSI
 REGULATOR. SHUT OFF VALVE REQUIRED UPSTREAM OF
 REGULATOR.
 B. OK
 C. OK
 D. OK
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED, BUT NOT ADDRESSED
  
 F. OK - INFORMATIONAL - 2PSI AT MAXIMUM 200 FT
 DEVELOPED LENGTH ALLOWS 39,656,000 BTU'S. ONLY 10,000
 BTU'S ARE INDICATED ON PLANS. THE 10,000 BTU'S IS
 QUESTIONABLE AS MOST RESIDENTIAL DRYERS ARE RATED AT
 22,000 BTU'S. FOR COMPARISON, A .5 PSI SYSTEM WITH 2"
 PIPE WILL DELIVER 800,000 BTU'S. WITH THE EXTRA
 DEVELOPED LENGTH TO THE FARTHEST FUTURE GENERATOR,ITS
 APPROXAMATLY 180'.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT NO MANUF. SHEETS FOR THE
 GENERATOR HAS BEEN SUBMITTED. - ALSO SUBMIT THE MANUF.
 SPECIFICATION SHEETS FOR THE GAS REGULATORS. INDICATE
 MODEL NUMBER. LISTING INFORMATION REQUIRED.
  
 H. NA
 I. NA
  
 40B. SHT P3-5.0 NO HOT WATER LINE SHOWN IN 1ST THRU 4TH
 FLOOR TOILET ROOMS OFF WATER RISER W/1. - WATER RISER
 DOES NOT REFLECT THE FLOOR PLAN AT THE LAVS. - FULL
 OPEN VALVES ARE REQUIRED ON ALL WATER DOWN-FEED LINES.
 SECTION 606.1(4). - RISER DOES NOT REFLECT THE FLOOR
 PLAN AT ROOMS C2.102/C2.103. (2 LAVS SHOWN EACH TOILET
 ROOM). - PIPE SIZE SUPPLYING ROOMS D1.101/D1.102,
 JANITOR ROOM D1.110, TOILET ROOMS A1.108/A1.109. -
 INDICATE THAT RISERS W/4, W/5, & W/8 RISERS START WITH
 RISER W/2 ON THE 1ST FLOOR. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE FOLLOWING COMMENTS WERE NOT
 ADDRESSED: - WATER RISER DOES NOT REFLECT THE FLOOR
 PLAN AT THE LAVS. - FULL OPEN VALVES ARE REQUIRED ON
 ALL WATER DOWN-FEED LINES. SECTION 606.1(4). (MANY
 LAVS, TOILET ROOMS, SINKS ETC MISSING VALVES).- RISER
 DOES NOT REFLECT THE FLOOR PLAN AT ROOMS C2.102/C2.103.
 (2 LAVS SHOWN EACH TOILET ROOM). - PIPE SIZE SUPPLYING
 ROOMS D1.101/D1.102, JANITOR ROOM D1.110, TOILET ROOMS
 A1.108/A1.109. (2" SHOWN ON FLOOR PLAN, 1-1/2" ON
 RISER. 3/4" ON FLOOR PLAN, 1/2" ON RISER.SOME LAVS
 SHOW SEPARATE DROPS TO EACH LAV ON THE FLOOR PLAN, BUT
 SINGLE DROPS ON THE RISER). - INDICATE THAT RISERW/8
 STARTS WITH RISER W/2 ON THE 1ST FLOOR. SECTION
 106.1.1.
  
 41B. SHT P3-6.0 RISERS 4, 5 & 8 ARE NOT INDICATED ON
 THE 1ST FLOOR. - RISER DOES NOT REFLECT THE FLOOR PLAN
 ROOMS C3.107/C3.108 AT JAN. SINK, ROOMS C3.410/C3.412,
 AE.111, A4.103/A4.104, A4.105 AND THE TOP OF RISER W/4
 TO ROOM A5.105, PIPE SIZE AT ROOM A2.209 & SUPPLY TO
 TOILET ROOM ADJACENT, PIPE SIZE SUPPLYING RISER W/8 &
 RISER, SUPPLY LINE TO ROOMS D2.102/D2.103. - W/2 NOT
 FOUND ON 4TH FLOOR AS INDICATED ON RISER. SECTION
 106.1.1.
 ****RESPONSE NOTED, BUT THE FOLLOWING COMMENTS WERE NOT
 ADDRESSSED: RISER 8 STILL NOT INDICATED ON THE 1ST
 FLOOR. - RISER DOES NOT REFLECT THE FLOOR PLAN ROOMS
 C3.410/C3.412,A4.103/A4.104, (FLOOR PLAN INDICATES
 OVER-HEAD SUPPLY WITH DROPS, BUT RISER INDICATES SUPPLY
 RUN IN THE WALL OFF WATER RISER. TWO W/C'S MISSING ON
 RISER).-PIPE SIZE AT ROOM A2.209, (SHOWS 1" ON THE
 FLOOR PLAN), - PIPE SIZE SUPPLYING RISER W/8 & RISER, (
 1" ON FLOOR PLAN, 2" ON RISER - 1-1/2" ON THE FLOOR
 PLAN, BUT 2" ON THE RISER). -W/2 NOT FOUND ON 4TH OR
 5TH FLOORS AS INDICATED ON RISER. SECTION 106.1.1.
 PLEASE CORRELATE RISER AND FLOOR PLANS.
  
 42B. SHT P3-7.0 SIZE ALL PIPE PER SECTION 1106.3, AND
 SHOW ALL PIPE SIZES ON THE RISER. - RISER DOES NOT
 REFLECT THE FLOOR PLAN TOP FLOORS RWL/6 & RWL/7. -
 RISERS INDICATE A 5TH FLOOR, BUT FLOOR PLAN DOES NOT
 SHOW A 5TH FLOOR. - RISER SHOWS TRENCH DRAINS ON TWO
 FLOORS, BUT ONLY SHOW TRENCH DRAINS ON 1 FLOOR, (ROOF
 LEVEL), ON THE FLOOR PLAN. -RWL'S 9 THRU 14 SHOW OFFSET
 PIPING FOR ROOF DRAINS IN THE 4TH FLOOR CEILING, BUT
 INDICATE THE ROOF DRAINS TO BE ON THE 4TH LEVEL. PLEASE
 CLARIFY. - PIPE SIZING IS INCORRECT AT 8"/11,715SF,
 6"/5077SF, 6"/6657SF. TABLE 1106.3. - RWL/9 INDICATES
 PIPING IN 3RD FLOOR CEILING, BUT ROOF DRAINS ARE TO BE
 ON THE 3RD LEVEL. PLEASE CLARIFY. - RWL/15 DOES NOT
 REFLECT THE FLOOR PLAN TO 4" ROOF DRAINS. - PIPING AT
 THE 1ST FLOOR CEILING CONNECTING TO ROOF DRAINS ON THE
 1ST LEVEL. PLEASE CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT SOME COMMENTS THE FOLLOWING
 COMMENTS WERE NOT ADDRESSED:- RISER DOES NOT REFLECT
 THE FLOOR PLAN TOP FLOORS RWL/6 & RWL/7. - RISERS
 INDICATE A 5TH FLOOR, BUT FLOOR PLAN DOES NOT SHOW A
 5TH FLOOR. - RISER SHOWS TRENCH DRAINS ON TWO FLOORS,
 BUT ONLY SHOW TRENCH DRAINS ON 1 FLOOR, (ROOF LEVEL),
 ON THE FLOOR PLAN. - PIPE SIZING IS INCORRECT AT
 8"/11,715SF, 6"/5077SF, 6"/6657SF. TABLE 1106.3.
  
 43B. SHTS 1,2,3 OF 3 ARE NOT SIGNED, SEALED, & DATED AS
 REQUIRED PER FS 472.025(1). ALSO SEE SHT 1 WHICH STATES
 "NOT VALID UNLESS SEALED WITH SURVEYOR'S EMBOSSED SEAL
 AND SIGNATURE"
 ****NO RESPONSE, NOT ADDRESSED.
  
 44B. SHTS C1, C5 THRU C22 ENGINEERING CERTIFICATE OF
 AUTHORIZTION IS REQUIRED IN THE TITLE BLOCK.
 61G15-23.002(2) & FS 471.025. - AN EMBOSSED SEAL IS
 REQUIRED TO IMPRESS REQUIRED INFORMATION ON EACH SHEET.
 UNABLE TO GLEAN ALL INFORMATION REQUIRED FROM SEAL.
 PLEASE RESEAL PLANS.
 ****NO RESPONSE, NOT ADDRESSED.
  
 45B. SHTS LP-0 THRU LP-3 & IR-1 THE CERTIFICATE OF
 AUTHORIZATION IS REQUIRED IN THE TITLE BLOCK.
 61G1-16.004(1) & FS 481.319.
 ****NO RESPONSE, NOT ADDRESSED.
  
 46B. SHT LL-1 IS MISSING THE TITLE BLOCK INFORMATION
 REQUIRED IN 61G1-16.004.
 ****NO RESPONSE, NOT ADDRESSED.
  
 47B. SHT IR-1 THE CONTROLER & RAIN SENSOR LOCATIONS ARE
 REQUIRED ON PLANS. SECTION 106.1.1.
 ****NO RESPONSE. THIS INFORMATION SHALL BE SUBMITTED AS
 A REVISION PRIOR TO APPLICATION, OR WITH THE
 APPLICATION FOR IRRIGATION PERMIT - NEW COMMENT, NO
 CERTIFICATE OF AUTHORIZATION IN THE TITLE BLOCK AS
 REQUIRED BY 61G1-16.004(2) & FS 481.319.
  
 48B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 2ND
 FLOOR DRINKING FOUNTAINS SHOWS 4 REQUIRED, BUT ONLY 3
 ARE REQUIRED PER TABLE 403.1. FIXTURE COUNT INDICATES
 ONLY 2 ARE PROVIDED. PLEASE PROVIDE REQUIRED AMOUNT OF
 DRINKING FOUNTAINS.
 ****NO RESPONSE, NOT ADDRESSED.
  
 49B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 3RD
 FLOOR DRINKING FOUNTAINS SHOW ONLY 3 ARE REQUIRED. PER
 TABLE 403.1, 4 DRINKING FOUNTAINS ARE REQUIRED. PLEASE
 UPDATE FIXTURE COUNT.
 ****NO RESPONSE, NOT ADDRESSED.
  
 50B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 4TH
 FLOOR DRINKING FOUNTAINS INDICATE 4 REQUIRED, BUT ONLY
 3 ARE PROVIDED. PLEASE PROVIDE 4 DRINKING FOUNTAINS.
 TABLE 403.1.
 ****NO RESPONSE, NOT ADDRESSED.
  
 51B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 1ST
 FLOOR DRINKING FOUNTAINS 2 REQUIRED PER TABLE 403.1,
 BUT READS 1 REQUIRED. PLEASE CORRECT FIXTURE COUNT
 REQUIRED.
 ****NO RESPONSE, NOT ADDRESSED.
  
 52B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 3RD
 FLOOR DRINKING FOUNTAINS 4 REQUIRED PER TABLE 403.1,
 BUT READS 2 REQUIRED. PLEASE CORRECT FIXTURE COUNT
 REQUIRED. - SHOWS 2 PROVIDED, BUT 4 ARE REQUIRED.
 PLEASE CORRECT INFORMATION.
 ****NO RESPONSE, NOT ADDRESSED.
  
 53B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 4TH
 FLOOR LAVS REQUIRED 2, INDICATED AS 1. PLEASE CORRECT
 THE FIXTURE COUNT. TABLE 403.1.
 ****NO RESPONSE, NOT ADDRESSED.
  
 54B. SHT LSO.0 LIBRARY/MUSEUM INDICATES A RESTURANT IN
 OCCUPANT LOAD 1ST FLOOR.PLEASE CONTACT LYNN MASSON,
 ENVIRONMENTAL COMPLIANCE MANAGER CONCERNING THE
 POSSIBLE REQUIREMENT FOR A GREASE INTERCEPTOR. CONTACT
 LYNN BY PHONE (561) 822-2271, OR FAX (561) 822-2279, OR
 E-MAIL [email protected].
 ****PER ARCHITECT, NO RESTURANT WILL BE IN THE LIBRARY.
 THIS WAS INDICATED AS A RESTURANT FOR OCCUPANCY
 CALCULATIONS ONLY. THERE WILL BE A CAFE IN THE LIBRARY
 WITH NO FOOD PREPARATION.
  
 55B. SHT LSO.0 INDICATES ASSEMBLY OCCUPANCY FOR THE
 CITY HALL AND LIBRARY/MUSEUM. POTTY PARITY IS REQUIRED
 PER SECTION 403.1.1 AND HAS BEEN INDICATED IN THE 50%
 REVIEW BY PAUL SCHMITZ. THIS HAS NOT BEEN ADDRESSED.
 PLEASE SHOW COMPLIANCE WITH THIS REQUIREMENT. ****NO
 RESPONSE, NOT ADDRESSED.
  
 56B. SHT A2-0 3 AREAS SHOW STORM WATER FROM ROOF AREAS
 ABOVE THAT CONTRIBUTE TO THE MAIN ROOF AREAS BELOW. THE
 SLOPE OF THE MAIN ROOF AND THE LOCTION OF THE DOWNSPOUT
 IS SHOWING THE TOTAL AREA DRAINING TO ONE ROOF DRAIN,
 BUT THE AREA IS DIVIDED EQUALLY BETWEEN TWO ROOF
 DRAINS. THE SIZING FOR THE ROOF DRAINS WILL HAVE TO BE
 RECHECKED TO ACCOUNT FOR THE AMOUNT OF AREA DRAINING TO
 ONE DRAIN, NOT TWO. TABLE 1106.3. (SEE ROOF AREAS AT
 COL. LINES 1THRU 4/A THRU D, 7 THRU 9.1/A THRU D, AND 4
 - 5/E THRU H).
 ****NO RESPONSE, NOT ADDRESSED.
  
 57D. SHTS A2-0, A2-1, A2-2, A2-3 SUBMIT CALCULATIONS
 FOR PRIMARY AND SECONDARY ROOF DRAINS. INDICATE THE
 CONTRUBUTION ADD FROM 1/2 AREA OF ALL VERTICAL WALLS,
 INCLUDING PARAPETS, AND ROOF AREAS FROM ABOVE ADDED TO
 THE ROOF SECTIONS. THIS IS REQUIRED FOR ALL ROOF
 LEVELS. SQUARE FOOTAGE IS SHOWN, BUT NO CALCULATIONS
 WERE SUBMITTED. CONTRIBUTING VERTICAL AREAS FOR WALLS
 IS UNCLEAR. IS THE AREA SHOWN INDICATED PER WALL, OR
 TOTAL FOR ALL WALLS SHOWN. PLEASE CLARIFY. SECTIONS
 1106.1, 1106.2, 1106.3, 1106.4.
 ****NO RESPONSE NOTED. PRIMARY AND SECONDARY ROOF DRAIN
 CALCULATIONS WERE NOT FOUND.
  
 58B. SHT A2-0 UPPER ROOF BY DOME SHOWS A DETAIL
 INDICATOR 20/A2-D.1. DETAIL 20 NOT FOUND ON SHT A2-D.1.
 PLEASE CLARIFY. SECTION 106.1.1.
 ****NO RESPONSE, NOT ADDRESSED.
  
 59B. SHT A2-D.1 DETAIL 04 SHOW HEIGHT AND WIDTH AND
 INDICATE THE MEASUREMENT FROM THE ROOF TO THE FLOW LINE
 OF THE SCUPPER. SECTIONS 106.1.1 AND 1503.4.3. ****NO
 RESPONSE, NOT ADDRESSED.
  
 60B. SHT A6-1.1 DETAILS 1 THRU 6. SHOW THE TURNING AREA
 IN THE TOILET ROOMS. NOT IN THE ACCESSIBLE STALLS.
 SECTION 11-4.22.3.
 ****NO RESPONSE, NOT ADDRESSED.
  
 61B. SHT A6-1.1 DETAIL 2, SHOW THE CLEAR FLOOR SPACE
 FOR THE URINAL. SECTION 11-4.18.3.
 ****NO RESPONSE, NOT ADDRESSED.
  
 62B. SHT A6-1.1 DETAIL 4, ACCESSIBLE W/C SHALL BE 1'6"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG.
 11-28. LAV TO BE MIN. 15" (C/L OF CLEAR FLOOR SPACE).
 ****NO RESPONSE, NOT ADDRESSED.
  
 63B. SHT A6-1.1 DETAIL 7, ACCESSIBLE W/C SHALL BE 1'6"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG.
 11-28. (SHOWS 2'2").
 ****NO RESPONSE, NOT ADDRESSED.
  
 64B. SHT A6-2.1 DETAILS 2, 6 & 7 SHOWTHE TURNING AREA
 IN THE TOILET ROOMS. NOT IN THE ACCESSIBLE STALLS.
 SECTION 11-4.22.3.
 ****NO RESPONSE, NOT ADDRESSED.
  
 65B. SHT A6-2.1 DETAIL 4, ACCESSIBLE W/C SHALL BE 1'6"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG.
 11-28.
 ****NO RESPONSE, NOT ADDRESSED.
  
 66B. SHT A6-3.1 DETAIL 2, SHOW A TURNING AREA IN THE
 LOCKER ROOM AREA. SECTION 11-4.2.3.
 ****NO RESPONSE, NOT ADDRESSED.
  
 67B. SHT A6-3.1 DETAILS 1, 3, 4 & 5, SHOW THE TURNING
 AREA IN THE TOILET ROOMS, NOT IN THE ACCESSIBLE STALLS.
 SECTION 11-4.22.3.
 ****NO RESPONSE, NOT ADDRESSED.
  
 68B. SHT A6-4.1 DETAILS 1 & 2, SHOW THE TURINING AREA
 IN THE TOILET ROOMS, NOT IN THE ACCESSIBLE STALLS.
 SECTION 11-4.22.3.
 ****NO RESPONSE, NOT ADDRESSED.
  
 69B. SHT A6-5.1 DETAIL 1, SHOW THE TURNING AREA IN THE
 TOILET ROOM, AND SHOW THE CLEAR FLOOR SPACE FOR THE
 URINAL. SECTIONS 11-4.22.3 AND 11-4.18.3.
 ****NO RESPONSE, NOT ADDRESSED.
  
 70B. SHTS A9-0.1 & A9-0.2 FINISH SCHEDULES: ROOMS
 C1.105, C1.106, A2.705, A2.706, A2.210, A2.211, A3.111,
 A3.114, C3.410, AND C3.412 ALL INDICATE THE WALLS TO BE
 PAINTED. PLEASE INDICATE HOW THIS COMPLIES WITH THE
 REQUIREMENT FOR "SMOOTH, HARD, NONABSORBENT WALLS AS
 REQUIRED IN SECTION 1210.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 71B. SHTS A9-0.1 & A9-0.2 FINISH SCHEDULES: ROOMS D2.10
 & D2.104 SHOW NO WALL FINISH AND THE FLOORING/BASE
 INDICATE RUBBERIZED FLOORING. INDICATE HOW THIS
 COMPLIES WITH "SMOOTH, HARD, NONABSORBENT FLOORS AS
 REQUIRED IN SECTION 1210.1.
 ****NO RESPONSE, NOT ADDRESSED.
  
 72B. SHT A9-4.1 INDICATE THE ROOM NUMBERS THAT THE
 DETAIL IS REFERENCING. SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.18.4 FLUSH CONTROLS
 B. 11-4.19.2 CLEARANCES
 C. 11-4.19.4 EXPOSED PIPES & CLEARANCES
 ****NO RESPONSE, NOT ADDRESSED.
  
 73B. SHT A9-4.2 INDICATE THE ROOM NUMBERS THAT THE
 DETAIL IS REFERENCING. SHOW COMPLIANCE WITH THE
 FOLLOWING:
 DETAIL #1
 A. 11-4.18.4 FLUSH CONTROLS
 B. 11-4.19.2 CLEARANCES
 C. 11-4.19.4 EXPOSED PIPES & CLEARANCES
 ****NO RESPONSE, NOT ADDRESSED.
  
 DETAIL #2
 A. 11-4.18.4 FLUSH CONTROLS
 B. 11-4.19.2 CLEARANCES
 C. 11-4.19.4 EXPOSED PIPES & CLEARANCES
 ****NO RESPONSE, NOT ADDRESSED.
  
 74B. SHT A9-4.4 INDICATE THE ROOM NUMBERS THAT THE
 DETAILS ARE REFERENCING.SHOW COMPLIANCE WITH THE
 FOLLOWING:
 DETAILS #1 - #2 - #3
 A. 11-4.19.2 CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 ****NO RESPONSE, NOT ADDRESSED.
  
 75B. SHT A9-4.5 DETAILS (1) & (2), SHOW THE FOLLOWING
 FOR COMPLIANCE:A. 11-4.19.2 CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 D. 11-4.21.5 CONTROLS
 E. 11-4.21.7 CURBS
 ****NO RESPONSE, NOT ADDRESSED.
  
 76B. SHTS A1.307, A1.709, A2.209, A2.315, A2.407,
 A3.109, C3.409, C3.310, A5.504 - SHOW COMPLIANCE WITH
 THE FOLLOWING
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH
 REQUIRED)
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
 D. 11-4.24.7 FAUCETS
 ****NO RESPONSE, NOT ADDRESSED.
  
 *************NEW COMMENTS*************
  
 1C. SHT P9-4.6 DETAILS 1 & 2 SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.18.4 FLUSH CONTROLS
 B. 11-4.19.2 CLEARANCES
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
  
 2C. SHT P9-4.7 DETAILS 1, 2, & 3 SHOW COMPLIANCE WITH
 THE FOLLOWING:
 A. 11-4.18.4 FLUSH CONTROLS
 B. 11-4.19.2 CLEARANCES
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
  
 3C. SHT P1-6.0 THE FOLLOWING VENTS ARE NOT SHOWN ON THE
 ROOF. P1, P2, P3, & P10. PLEASE SHOW ON THIS SHEET OR
 INDICATE WHERE THEY ARE SHOWN. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. SUBMITTING THE RED
 LINED SET OF PLUMBING SHEETS WHEN RESUBMITTING FOR
 REVIEW WILL HELP EXPEDITE THE PERMIT ALSO. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6721
 E-MAIL [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-11-14 Cont ID  
Sent By kstevens Date 2006-11-14 Time 07:42 Rev Time 0.00
Received By kstevens Date 2006-11-14 Time 07:42 Sent To  
Notes
2006-11-14 17:40:40DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
  
 1. SHT P0-1.0 WATER HEATER SCHEDULE. TWH-1, TWH-2,
 TWH-3, SUBMIT MANUF. SPECIFICATION SHEETS THAT SHOW
 LISTING. SECTION 303.4.
 ****RESPONSE NOTED, WILL BE IN THE SUBMITTAL PACKAGE.
  
 2. SHT P0-1.0 PUMP SCHEDULE. SUBMIT MANUF.
 SPECIFICATION SHEETS THAT SHOW LISTING. SECTION 303.4.
 ****RESPONSE NOTED, WILL BE IN THE SUBMITTAL PACKAGE.
  
 3. SHT P1-1.1 PUMP ROOM A1-112. RPZV BACKFLOW SHALL BE
 INSTALLED A MAXIMUM OF 4' ABOVE THE FLOOR FOR
 CERTIFICATION AND SERVICE.
 ****RESPONSE NOTED, HEIGHT TO BE INDICATED FOR THE
 BACKFLOWS TO BE A MAXIMUM OF 4' ABOVE THE FLOOR.
  
 4. SHTS P1-1.1 THRU P1-5.1 INDICATE RISER NUMBER FOR
 THE SANITARY, STORM, AND WATER RISERS TO TRACK RISERS
 THRU THE BUILDING. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT SOME RISERS INDICATED ON THE
 UPPER FLOORS ARE NOT INDICATED ON THE FIRST FLOOR.
 EXAMPLE P/6 STARTS ON THE FIRST FLOOR, BUT P/8 ALSO
 DRAINS THRU P/6. LABEL P/8 WITH P/6 ON THE FIRST FLOOR.
 ALSO WHY DOES P5 TURN INTO P9?
  
 5. SHTS P1-1.1 THRU P1-1.3 CLEANOUTS REQUIRED BY
 SECTIONS 708.3.1, 708.3.2, 708.3.4, 708.3.5 AND 11-8.1
 (FOR STORM) SHALL BE SHOWN ON THE PLANS. ****RESPONSE
 NOTED, BUT COMMENT NOT ADDRESSED. MANY CLEANOUTS
 REQUIRED ARE NOT INDICATED. MANY CLEANOUTS REQUIRED ARE
 NOT SHOWN. CLEANOUTS AT THE BASE OF STACKS AS SHOWN ARE
 INCORRECT. THEY DO NOT CLEANOUT THE BASE OF THE STACK.
 ALSO SHOW THE CLEANOUTS REQUIRED ON THE RISER
 DIAGRAMS.
  
 6.OK
 7.OK
 8.OK
 9.OK
 10. OK
 11. OK
 12. OK
 13. OK
  
 14. SHT P1-6.0 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW THE SQUARE FOOTAGE OF EACH
 AREA, AND SHOW 1/2 AREA OF ALL VERTICAL WALLS,
 INCLUDING PARAPETS, AS WELL AS ALL AREAS OF ROOFS
 DRAINING ONTO THE ROOF FROM ABOVE IN THE CALCULATIONS.
 SECTIONS 1106, AND 1107 WITH ALL SUBSECTIONS. SHOW THE
 LOCATION OF ALL SECONDARY ROOF DRAINS AND OR EMERGENCY
 OVERFLOW SCUPPERS. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT NO CALCULATIONS WERE
 SUBMITTED.
  
 15. OK
 16. OK (SHOWN ON SHT P2-1.0U)
 17. OK
 18. OK
 19. OK
 20. OK
  
 21. SHT P2-2.0 ALL DETAILS, SHOW ALL PIPE SIZES FOR ALL
 SYSTEMS. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT PIPE SIZES ARE NOT SHOWN FOR
 MANY SECTIONS OF PIPES. ALSO SEE TABLES 710.1(1) &
 710.1(2).
  
 22. OK
 23. OK
 24. OK
 25. OK
 26. OK
 27. OK
 28. OK
 29. OK
 30. OK
 31. OK
 32. OK
  
 33. SHT P2-3.0 ALL DETAILS, SHOW ALL PIPE SIZES IN ALL
 SYSTEMS. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT PIPE SIZES ARE NOT SHOWN FOR
 MANY SECTIONS OF PIPES. ALSO SEE TABLES 710.1(1) &
 710.1(2).
  
 34. SHT P4-1.0 DETAIL #12 CONDENSATE DRAIN, DETAIL NOT
 APPROVED AS SHOWN. CLARIFY OPEN NIPPLE. CLARIFY GAP
 BETWEEN PIPE AND FLOOR. WHY USE A TEE AT THE BOTTOM OF
 THE TRAP? SECTION 106.1.1.
 ****RESPONSE NOTED, BUT DETAIL NOT EXPLAINED OR REVISED
 AS NOTED. COMMENT NOT ADDRESSED.
  
 35. SHT P4-1.0 DETAIL #13 WATER HEATER DETAIL. PLEASE
 SHOW COMPLIANCE WITH SECTION 607.3.2, THERMAL EXPANSION
 CONTROL. - A SHUT OFF VALVE IS REQUIRED ON EACH SIDE OF
 THE CIRCULATING PUMP. - SUBMIT PUMP MANUF.
 SPECIFICATIONS SHEETS. PUMP SHALL BE LISTED. SECTION
 303.4.
 ****RESPONSE NOTED, BUT THERMAL EXPANSION CONTROL HAS
 NOT BEEN ADDRESSED. CIRCULATION PUMP SPECIFICATIONS
 SHALL BE SUBMITTED WITH SUBMITTAL PACKAGE.
  
 36. SUBMIT A SANITARY HORIZONTAL RISER ISOMETRIC AND
 VERTICAL RISER DIAGRAMS. SHOW ALL PIPE SIZES, TRAPS,
 VENTS, CLEANOUTS, OFFSETS, RISER NUMBERS AND DFU'S AS
 THEY ACCUMULATE IN THE SYSTEM. SECTION 106.3.5.1.3.
 ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN,
 ALL REQUIRED CLEANOUTS ARE NOT SHOWN, AND DFU'S ARE NOT
 SHOWN AS THEY ACCUMULATE IN THE SYSTEM. ALSO INDICATE
 ON THE FIRST FLOOR WHERE ALL RISERS BEGIN IN THE
 SYSTEM.
  
 37. SUBMIT A STORM HORIZONTAL RISER ISOMETRIC DIAGRAM &
 VERTICAL RISER DIAGRAMS. SHOW ALL PIPE SIZES, OFFSETS,
 & CLEANOUTS AND INDICATE THE RISER NUMBERS. SHOW THE
 SQUARE FOOTAGE AS IT ACCUMULATES IN THE SYSTEM. SECTION
 106.3.5.1.3.
 ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN,
 ALL REQUIRED CLEANOUTS ARE NOT SHOWN, AND SQUARE
 FOOTAGE AS IT ACCUMULATES IN THE SYSTEM IS NOT
 INDICATED.
  
 38. SUBMIT A WATER RISER ISOMETRIC DIAGRAM. SHOW ALL
 PIPE SIZES, VALVES, WATER HAMMER ARRESTORS, BACKFLOW
 PROTECTION ETC. SECTION 106.3.5.1.3.
 ****RESPONSE NOTED, BUT NOT ALL PIPE SIZES ARE SHOWN,
 NOT ALL REQUIRED VALVES ARE SHOWN, AND ALL WATER HAMMER
 ARRESTORS REQUIRED BY SECTION 604.9, (ICE MAKERS,
 DISHWASHERS, & WASH MACHINES IF FIXTURES ARE
 PROVIDED).
  
 39. SUBMIT A CONDENSATE RISER ISOMETRIC DIAGRAM. SHOW
 ALL PIPE SIZES, VENTS, TERMINATION POINTS ETC. SECTION
 106.3.5.1.3.
 ****RESPONSE NOTED, BUT NO CONDENSATE RISER DIAGRAM
 SUBMITTED AS REQUESTED.
  
 40. ALL PME & FIRE PROTECTION SHEETS. PLANS SHALL BE
 SIGNED, SEALED, AND DATED. SECTION 106.1. ALL TITLE
 BLOCK INFORMATION REQUIRED BY FAC 61G1-23.002 AND FS
 471.025 SHALL BE SUBMITTED ON EACH SHEET. ****RESPONSE
 NOTED, BUT THE SEAL USED IS NOT APPROVED. NEW SEALS
 SHALL INDICATE THE WORD "LICENSE" IN THE SEAL. (SEE
 ATTACHED SHEET FROM THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS).
  
 **************NEW COMMENTS**************
  
 1B. SHTS P1-1.0U, P1-1.1U, P1-1.1 & P1-2.1. RWL-4 DOES
 NOT REFLECT THE SQUARE FOOTAGE SHOWN ON RISER DIAGRAM
 OR ROOF PLAN. PLEASE CORRELATE RISER, FLOOR PLAN, &
 ROOF PLAN. SECTION 106.1.1.
  
 2B. SHTS P1-1.OU & P1-1.1U ALL RWL'S THAT CONNECT TO
 RWL-4 TO BE INDICATED ON THE 1ST FLOOR. THIS WILL AID
 IN TRACING THE RWL'S THROUGH THE BUILDING AND TO VERIFY
 PIPE SIZES. SECTION 106.1.1.
  
 3B. SHTS P1-1.1U & P2-1.01 DETAIL #6 THE SINK SHALL NOT
 DRAIN THRU THE WET VENT FOR THE TOILET ROOM. THE
 DISCHARGE FOR THE SINK SHALL CONNECT DOWNSTREAM OF THE
 TOILET ROOM FIXTURES. SECTION 909.1.
  
 4B. SHT P1-1.2U FD-2 IN D1.106 LOADING REQUIRES A VENT.
 THIS DOES NOT REFLECT THE RISER DIAGRAM PIPING. THE
 FLOOR IS SLOPING AWAY FROM THE TRENCH DRAIN. PLEASE
 CLARIFY. SECTIONS 901.2.1, 106.1.1.
  
 5B. SHT P1-1.2U CLEANOUT REQUIRED AT THE BASE OF P/1 &
 P/10 RISERS, NEAR THE JUNCTION OF THE BUILDING DRAIN
 AND THE BUILDING SEWER, AND AT ALL CHANGES OF DIRECTION
 OVER 45 DEGREES. PLEASE INDICATE ON PLANS. SECTIONS.
 708.3.3, 708.3.4, 708.3.5.
  
 6B. SHTS P1-1.2U, ASSOCIATED RISER DIAGRAMS, AND
 ENLARGED FLOOR PLANS. INDICATE HOW THE STACKS P/1 &
 P/10 CAN DRAIN INTO THE TOILET GROUP FIXTURE BRANCH.
 SUBMIT A DETAIL SHOWING THE 4" CLEANOUT TEE, THE 4"
 CROSS FOR THE FIXTURE BRANCH, AND THE 4" DOUBLE
 Y/EIGHTH BEND FITTINGS STACKED ON TOP OF EACH OTHER.
 WILL THEY BE AT THE RIGHT HEIGHT FOR THE W/C'S?SEE
 SECTION 908.3 ALSO. SECTION 106.1.1. (STACKS SHOULD
 CONNECT TO THE BUILDING DRAIN AND FIXTURE GROUPS SHOULD
 CONNECT TO THE STACK SO THAT THE STACK DOES NOT RUN
 THRU THE MIDDLE OF THE FIXTURE GROUP).
  
 7B. SHTS P1-1.3U, P1-2.0, P1-2.3, P1-3.3, & P1-4.3
 RWL-6 DOES NOT REFLECT THE SQUARE FOOTAGE SHOWN ON THE
 RISER DIAGRAM, NOR ON THE ROOF PLAN. PLEASE CORRELATE
 INFORMATION. SECTION 106.1.1 & TABLE 1106.3.
  
 8B. SHT P1-1.3 THE WATER SUPPLY TO THE ICE MAKER SHALL
 CONNECT UPSTREAM OF THE MAKE-UP WATER FOR THE COOLING
 TOWERS. - SHOW THE LOCATIONS FOR RWL-6 & RWL-7. SECTION
 106.1.1 & 608.1.
  
 9B. SHT P1-2.1 RISER P/8 NOT INDICATED ON THE 1ST
 FLOOR. PLEASE SHOW WHERE RISERS START ON THE FIRST
 FLOOR. SECTION 106.1.1.
  
 10B. SHT P1-3.2 RISER P/4 SHOWN AT COL. LINE H/2 WAS
 RISER P/2 ON THE FLOOR BELOW. PLEASE CLARIFY. SECTION
 106.1.1.
  
 11B. SHT P1-4.1 C/O FOR S-1 SINK PIPING CONNECTING TO
 RISER P/7 IS NOT APPROVED AS INDICATED. SECTION 706.3.
 - RISER P/9 IS NOT INDICATED ON PREVIOUS LEVELS. PLEASE
 CLARIFY. - RISER P/5 SHOWN ON PREVIOUS LEVEL IS NOT
 INDICATED. PLEASE CLARIFY.
  
 12B. SHT P1-4.1 SHOW RISER P/3 VTR. - NOTE STATES "SEE
 01 ON DRAWING P2-3.0". INFORMATION NOT SHOWN ON DETAIL
 01. PLEASE CLARIFY. - SHOW THE VENTING TO REFLECT THE
 FLOOR PLAN FOR KINK S-1 CONNECTED TO RISER P/8. - 4"
 SANITARY - 4" VTR AT COL. LINE E/8 IS SHOWN AS AN
 OFFSET ON THE RISER DIAGRAM. PLEASE CORRELATE FLOOR
 PLAN AND SANT. RISER DIAGRAM. SECTION 106.1.1.
  
 13B. SHT P1-4.2 SANT. RISER P/2 VTR NOT SHOWN. SECTION
 106.1.1.
  
 14B. SHOW ALL PIPE SIZES PER TABLE 1106.3.
  
 15B. SHT P1-6.0 SHOW THE LOCATIONS FOR ALL VTR'S. -
 INDICATE THE RWL EACH ROOF DRAIN IS CONNECTED TO.
 SECTION 106.1.1.
  
 16B. SHT P2-1.0U DETAIL 1, FLOOR DRAINS IN C1.104 ARE
 NOT VENTED. SECTION 901.2.1. - THE PIPING AT THE LAVS
 IN ROOM C1.103 DOES NOT REFLECT THE RISER DIAGRAM.
 PLEASE CORRELATE. SECTION 106.1.1.
  
 17B. SHT P2-1.0U DETAIL 2 DOES NOT REFLECT THE PIPING
 LAYOUT SHOWN ON P1-1.2U. - SUBMIT A DETAIL FOR THE
 SANT. PIPING ARRANGEMENT FOR THE DRINKING FOUNTAINS,
 SHOW HOW THE PIPING CONNECTS THROUGH THE SIDE OF THE
 D.F. UNITS. - SUBMIT A DETAIL FOR THE FITTING
 ARRANGEMENT WHERE THE TOILET ROOM FIXTURES CONNECT TO
 THE BLDG. DRAIN. SECTION 106.1.1.
  
 18B. SHT P2-1.0U DETAILS 3 & 4, SUBMIT A DETAIL FOR THE
 PIPING ARRANGEMENT FOR THE D.F.'S. SECTION 106.1.1.
  
 19B. SHT P2-1.0U DETAIL 6, SINK SHALL CONNECT
 DOWNSTREAM OF THE WET VENTED FIXTURES IN THE TOILET
 ROOM. SECTION 909.1.
  
 20B. SHT P2-1.0 DETAIL 1 DOES NOT REFLECT THE FLOOR
 PLAN OR RISER DIAGRAM. NO WATER PIPING TO WH'S SHOWN.
 SECTION 106.1.1.
  
 21B. SHT P2-1.0 DETAIL 2 DOES NOT REFLECT THE FLOOR
 PLAN. SHOWS 2" WATER SUPPLY. SECTION 106.1.1.
  
 22B. SHT P2-1.0 DETAIL 4 DOES NOT REFLECT THE FLOOR
 PLAN. NO WATER TO WH'S & SHOWS 2" WATER SUPPLY. SECTION
 106.1.1.
  
 23B. SHT P2-1.0 DETAIL 6 DOES NOT REFLECT THE FLOOR
 PLAN FOR SANT. TO LAVS. FLOOR DRAINS NOT VENTED.
 SECTIONS 106.1.1 & 901.2.1.
  
 24B. SHT P2-2.0 DETAIL 1, INDICATE RISER NUMBERS.
 SECTION 106.1.1.
  
 25B. SHT P2-2.0 DETAIL 2, SUBMIT A DETAIL FOR SANT.
 PIPING TO D.F'S. - DOES NOT REFLECT THE RISER DIAGRAM.
 SECTION 106.1.1.
  
 26B. SHT P2-2.0 DETAIL 3, SUBMIT A DETAIL FOR SANT.
 PIPING TO D.F.'S - INDICATE RISERS FOR COLD WATER
 DOWNSTREAM OF LAST W/C'S. HOT WATER LINE NOT SHOWN THRU
 BATHROOM FIXTURES. SECTION 106.1.1.
  
 27B. SHT P2-2.0 DETAIL 4, NO PIPING TO FLOOR DRAINS
 SHOWN. SECTION 106.1.1.
  
 28B. SHT P2-2.0 DETAIL 5, SUBMIT A DETAIL FOR SANT.
 PIPING TO D.F.'S. SECTION 106.1.1.
  
 29B. SHT P2-2.0 DETAIL 6, SUBMIT A DETAIL FOR SANT.
 PIPING TO D.F.'S. SECTION 106.1.1. - SANT. RISER
 UPSTREAM OF JANITOR SINK NOT SHOWN. (SEE RISER
 DIAGRAM). SECTION 106.1.1.
  
 30B. SHT P2-3.0 DETAIL 1, INDICATE WHERE SANT. BRANCH
 LINE CONNECTS TO THE SANT. RISER. - FLOOR DRAIN SHOWS
 NO PIPING. SECTION 106.1.1.
  
 31B. SHT P2-3.0 DETAIL 2, NO PIPING SHOWN TO FLOOR
 DRAINS. - SUBMIT A DETAIL FOR D.F. SANT. PIPING.
 SECTION 106.1.1.
  
 32B. SHT P2-3.0 DETAIL 3, NO PIPING SHOWN TO FLOOR
 DRAINS. - SUBMIT A DETAIL FOR D.F. SANT. PIPING.
 SECTION 106.1.1.
  
 33B. SHT P2-3.0 DETAIL 4, NO PIPING SHOWN TO FLOOR
 DRAINS. - SUBMIT A DETAIL FOR D.F. SANT. PIPING.
 SECTION 106.1.1.
  
 34B. SHT P3.1.0 SANT RISER DIAGRAM, TRAPS ARE REQUIRED
 ON ALL DRINKING FOUNTAINS. SECTION 1002.1. - 1ST FLOOR
 LAVS PIPING DOES NOT REFLECT THE FLOOR PLAN. - FLOOR
 DRAINS DOWNSTREAM OF RISER P/1 ARE NOT VENTED. SECTION
 901.2.1. - A C/O IS REQUIRED AT THE BASE OF STACK P/1
 SECTION 708.3.4 - SHOW THE CONNECTION DETAIL AT THE
 BASE OF STACK P/1 WITH A 4" CLEANOUT, A 4" CROSS, AND
 4" WYE FITTINGS INDICATING THE HEIGHT OF THE W/C
 STUBOUT. - W/C-1 AT THE BASE OF STACK IS NOT VENTED.
 SECTION 901.2.1. -W/C ON 2ND FLOOR IS NOT VENTED.
 SECTION 901.2.1. - LAV ON 3RD FLOOR NOT VENTED. SECTION
 901.2.1. - INDICATE HOW/WHERE PIPING FOR LAVS & FLOOR
 DRAINS CONNECT TO THE RISER/BRANCH ON THE 2ND, 3RD, &
 4TH FLOORS. THE FITTINGS INDICATE THAT THE PIPING IS
 SLOPED TO THE LAVS. PLEASE CLARIFY. - MEN C4.104 DOES
 NOT REFLECT ROOM NUMBER ON THE FLOOR PLAN. - PIPING FOR
 FLOOR DRAINS & LAVS 4TH FLOOR DOES NOT REFLECT THE
 FLOOR PLAN. SECTION 106.1.1.
  
 35B. ALL RISER DIAGRAMS, ALL FLOOR PLANS FOR ALL
 SYSTEMS. INDICATE THE PIPE SIZE. SECTION 106.1.1.
  
 36B. SHT P3-2.0 JANITOR ROOM PIPING DOES NOT REFLECT
 THE FLOOR PLAN. - TRAPS REQUIRED ON ALL DRINKING
 FOUNTAINS. SECTION 1002.1. - CLEANOUTS REQUIRED AT THE
 BASE OF ALL STACKS. 708.3.4. - PIPING TO FLOOR DRAIN
 SHOWN ABOVE THE FLOOR IN ROOM D1.101. PLEASE CLARIFY. -
 PIPING AT THE BASE OF RISER P/2 DOES NOT REFLECT THE
 FLOOR PLAN. - PIPING TO FD-2 AT THE LOADING D1.106 DOES
 NOT REFLECT THE FLOOR PLAN. - PIPING FOR A1.108/A1.109
 DOES NOT REFLECT THE FLOOR PLAN. - ROOM D2.103 IS
 INDICATED AS D2.104 ON THE FLOOR PLAN. CORRELATE
 INFORMATION. - ALL VENTING AT RISER P/10 STOPS AT LEVEL
 2. SECTION 903.3 VTR REQUIRED. - TOILET ROOM A2.708 IS
 INDICATED AS A2.706 ON THE FLOOR PLAN. CORRELATE
 INFORMATION. - BATHROOM RISER DOES NOT REFLECT THE
 FLOOR PLAN. (NO FD). - PIPING TO ROOM A4.414 DOES NOT
 REFLECT THE FLOOR PLAN. - CLEANOUT PIPING DOWNSTREAM OF
 C4.101 IS NOT APPROVED AS PIPED. SECTION 706.3. -
 PIPING ON RISER DOES NOT REFLECT THE FLOOR PLAN
 UPSTREAM OF C3.105. - JANITOR SINK C3.105 IS NOT
 VENTED. SECTION 901.2.1. - FLOOR DRAIN CONNECTION AT
 BRANCH LINE 4TH FLOOR DOES NOT REFLECT THE FLOOR PLAN.
 - PIPING AT A2.107 DOES NOT REFLECT THE FLOOR PLAN. (NO
 F.D. PIPING). - PIPING AT ROOM A3.111 DOES NOT REFLECT
 THE FLOOR PLAN AT THE LAVS. - ROOM A3.111 SUBMIT A
 DETAIL FOR FITTING TO W/C & LAVS. - ROOM D2.105 SHOWN
 AS D2.106/D2.107 ON FLOOR PLANS. CORRELATE INFORMATION.
 - ROOM C3.410/C3.412 FLOOR DRAIN FITTING ARE SHOWN TO
 BE INSTALLED AGAINST THE FLOW. SECTION 706.3. - SECTION
 106.1.1.
  
 37B. SHT P3-3.0 PIPING TO A3.304 & DOWNSTREAM DOES NOT
 REFLECT THE FLOOR PLAN. - VENT PIPING FROM S-1 SINK
 DOES NOT REFLECT THE FLOOR PLAN. OFFSET NOT SHOWN. -
 TRAPS REQUIRED ON ALL DRINKING FOUNTAINS. SECTION
 1002.1. - S-1 SINK SHALL NOT DRAIN THRU THE WET VENT OF
 THE TOILET ROOM A1.303. SINK SHALL DISCHARGE DOWNSTREAM
 OF THE W/C & LAV. SECTION 909.1. - INDICATE P/8 WITH
 P/6 AT THE BASE OF THE STACK WHERE IT BEGINS. - PIPING
 TO ROOMS A1.105/A1.106 DOES NOT REFLECT THE FLOOR PLAN.
 FLOOR DRAIN PIPING IS SHOWN AS ABOVE THE FLOOR. - P/5 &
 P/9 BEGIN AT THE BASE OF THE STACK. PLEASE INDICATE ON
 RISER DIAGRAM. - PIPING FOR A3.102/A3.103 DOES NOT
 REFLECT THE FLOOR PLAN. - CLEANOUT REQUIRED AT THE BASE
 OF P/9 STACK. - PIPING TO FLOOR DRAINS IN ROOMS
 A3.102/A3.103 ARE ABOVE THE FLOOR. -W/C AT THE BASE
 OF STACK NOT VENTED. SECTION 901.2.1. - INDICATE WHERE
 LINES TO FLOOR DRAINS IN ROOMS A4.103/A4.104 &
 A5.103/A5.104 ARE CONNECTING TO THE BRANCH/STACK. -
 PIPING FOR A4.103/A4.104 DOES NOT REFLECT THE FLOOR
 PLAN. - W/C AT RISER STACK A4.103 IS NOT VENTED.
 SECTION 901.2.1. - PIPING FOR A4.105 DOES NOT REFLECT
 THE FLOOR PLAN. SECTION 106.1.1.
  
 38B. SHT P3-4.0 GARAGE WATER RISER DIAGRAM SHOWS WH'S
 BELOW GRADE. PLEASE CLARIFY. - SHUT OFF VALVE REQUIRED
 ON WH SHOWN BELOW GRADE. SECTION 606.2(2). - A WATER
 HAMMER ARRESTOR IS REQUIRED AT THE ICE MACHINE. SECTION
 604.9. - SHUT OFF VALVES ARE REQUIRED FOR THE HOSE
 BIBBS ON THE ROOF. SECTION 606.2(2). - SANITARY RISER
 DIAGRAM, FLOOR DRAINS ARE NOT APPROVED FOR INDIRECT
 WASTE. A FLOOR SINK OR HUB DRAIN IS REQUIRED FOR THE
 ICE MACHINE. SECTIONS 802.3 & 802.3.2. - SECTION
 106.1.1.
  
 39B. SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - RISER DOES NOT REFLECT
 THE FLOOR PLAN. OFFSETS BETWEEN THE
 METER AND THE RISER ARE NOT SHOWN. -
 INDICATE WHAT THE RISERS ABOVE THE TEE
 AT THE TOP OF THE RISER AND AT THE
 GENERATOR ARE FOR. FUTURE BTU LOAD AND
 DISTANCE MAY REQUIRE CHANGES IN THE
 GAS SYSTEM WHEN ADDED.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD-
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 40B. SHT P3-5.0 NO HOT WATER LINE SHOWN IN 1ST THRU 4TH
 FLOOR TOILET ROOMS OFF WATER RISER W/1. - WATER RISER
 DOES NOT REFLECT THE FLOOR PLAN AT THE LAVS. - FULL
 OPEN VALVES ARE REQUIRED ON ALL WATER DOWN-FEED LINES.
 SECTION 606.1(4). - RISER DOES NOT REFLECT THE FLOOR
 PLAN AT ROOMS C2.104/C2.103. (2 LAVS SHOWN EACH TOILET
 ROOM). - PIPE SIZE SUPPLYING ROOMS D1.101/D1.102,
 JANITOR ROOM D1.110, TOILET ROOMS A1.108/A1.109. -
 INDICATE THAT RISERS W/4, W/5, & W/8 RISERS START WITH
 RISER W/2 ON THE 1ST FLOOR. SECTION 106.1.1.
  
 41B. SHT P3-6.0 RISERS 4, 5 & 8 ARE NOT INDICATED ON
 THE 1ST FLOOR. - RISER DOES NOT REFLECT THE FLOOR PLAN
 ROOMS C3.107/C3.108 AT JAN. SINK, ROOMS C3.410/C3.412,
 AE.111, A4.103/A4.104, A4.105 AND THE TOP OF RISER W/4
 TO ROOM A5.105, PIPE SIZE AT ROOM A2.209 & SUPPLY TO
 TOILET ROOM ADJACENT, PIPE SIZE SUPPLYING RISER W/8 &
 RISER, SUPPLY LINE TO ROOMS D2.102/D2.103. - W/2 NOT
 FOUND ON 4TH FLOOR AS INDICATED ON RISER. SECTION
 106.1.1.
  
 42B. SHT P3-7.0 SIZE ALL PIPE PER SECTION 1106.3, AND
 SHOW ALL PIPE SIZES ON THE RISER. - RISER DOES NOT
 REFLECT THE FLOOR PLAN TOP FLOORS RWL/6 & RWL/7. -
 RISERS INDICATE A 5TH FLOOR, BUT FLOOR PLAN DOES NOT
 SHOW A 5TH FLOOR. - RISER SHOWS TRENCH DRAINS ON TWO
 FLOORS, BUT ONLY SHOW TRENCH DRAINS ON 1 FLOOR, (ROOF
 LEVEL), ON THE FLOOR PLAN. -RWL'S 9 THRU 14 SHOW OFFSET
 PIPING FOR ROOF DRAINS IN THE 4TH FLOOR CEILING, BUT
 INDICATE THE ROOF DRAINS TO BE ON THE 4TH LEVEL. PLEASE
 CLARIFY. - PIPE SIZING IS INCORRECT AT 8"/11,715SF,
 6"/5077SF, 6"/6657SF. TABLE 1106.3. - RWL/9 INDICATES
 PIPING IN 3RD FLOOR CEILING, BUT ROOF DRAINS ARE TO BE
 ON THE 3RD LEVEL. PLEASE CLARIFY. - RWL/15 DOES NOT
 REFLECT THE FLOOR PLAN TO 4" ROOF DRAINS. - PIPING AT
 THE 1ST FLOOR CEILING CONNECTING TO ROOF DRAINS ON THE
 1ST LEVEL. PLEASE CLARIFY. SECTION 106.1.1.
  
 43B. SHTS 1,2,3 OF 3 ARE NOT SIGNED, SEALED, & DATED AS
 REQUIRED PER FS 472.025(1). ALSO SEE SHT 1 WHICH STATES
 "NOT VALID UNLESS SEALED WITH SURVEYOR'S EMBOSSED SEAL
 AND SIGNATURE"
  
 44B. SHTS C1, C5 THRU C22 ENGINEERING CERTIFICATE OF
 AUTHORIZTION IS REQUIRED IN THE TITLE BLOCK.
 61G15-23.002(2) & FS 471.025. - AN EMBOSSED SEAL IS
 REQUIRED TO IMPRESS REQUIRED INFORMATION ON EACH SHEET.
 UNABLE TO GLEAN ALL INFORMATION REQUIRED FROM SEAL.
 PLEASE RESEAL PLANS.
  
 45B. SHTS LP-0 THRU LP-3 & IR-1 THE CERTIFICATE OF
 AUTHORIZATION IS REQUIRED IN THE TITLE BLOCK.
 61G1-16.004(1) & FS 481.319.
  
 46B. SHT LL-1 IS MISSING THE TITLE BLOCK INFORMATION
 REQUIRED IN 61G1-16.004.
  
 47B. SHT IR-1 THE CONTROLER & RAIN SENSOR LOCATIONS ARE
 REQUIRED ON PLANS. SECTION 106.1.1.
  
 48B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 2ND
 FLOOR DRINKING FOUNTAINS SHOWS 4 REQUIRED, BUT ONLY 3
 ARE REQUIRED PER TABLE 403.1. FIXTURE COUNT INDICATES
 ONLY 2 ARE PROVIDED. PLEASE PROVIDE REQUIRED AMOUNT OF
 DRINKING FOUNTAINS.
  
 49B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 3RD
 FLOOR DRINKING FOUNTAINS SHOW ONLY 3 ARE REQUIRED. PER
 TABLE 403.1, 4 DRINKING FOUNTAINS ARE REQUIRED. PLEASE
 UPDATE FIXTURE COUNT.
  
 50B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 4TH
 FLOOR DRINKING FOUNTAINS INDICATE 4 REQUIRED, BUT ONLY
 3 ARE PROVIDED. PLEASE PROVIDE 4 DRINKING FOUNTAINS.
 TABLE 403.1.
  
 51B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 1ST
 FLOOR DRINKING FOUNTAINS 2 REQUIRED PER TABLE 403.1,
 BUT READS 1 REQUIRED. PLEASE CORRECT FIXTURE COUNT
 REQUIRED.
  
 52B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 3RD
 FLOOR DRINKING FOUNTAINS 4 REQUIRED PER TABLE 403.1,
 BUT READS 2 REQUIRED. PLEASE CORRECT FIXTURE COUNT
 REQUIRED. - SHOWS 2 PROVIDED, BUT 4 ARE REQUIRED.
 PLEASE CORRECT INFORMATION.
  
 53B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 4TH
 FLOOR LAVS REQUIRED 2, INDICATED AS 1. PLEASE CORRECT
 THE FIXTURE COUNT. TABLE 403.1.
  
 54B. SHT LSO.0 LIBRARY/MUSEUM INDICATES A RESTURANT IN
 OCCUPANT LOAD 1ST FLOOR.PLEASE CONTACT LYNN MASSON,
 ENVIRONMENTAL COMPLIANCE MANAGER CONCERNING THE
 POSSIBLE REQUIREMENT FOR A GREASE INTERCEPTOR. CONTACT
 LYNN BY PHONE (561) 822-2271, OR FAX (561) 822-2279, OR
 E-MAIL [email protected].
  
 55B. SHT LSO.0 INDICATES ASSEMBLY OCCUPANCY FOR THE
 CITY HALL AND LIBRARY/MUSEUM. POTTY PARITY IS REQUIRED
 PER SECTION 403.1.1 AND HAS BEEN INDICATED IN THE 50%
 REVIEW BY PAUL SCHMITZ. THIS HAS NOT BEEN ADDRESSED.
 PLEASE SHOW COMPLIANCE WITH THIS REQUIREMENT.
  
 56B. SHT A2-0 3 AREAS SHOW STORM WATER FROM ROOF AREAS
 ABOVE THAT CONTRIBUTE TO THE MAIN ROOF AREAS BELOW. THE
 SLOPE OF THE MAIN ROOF AND THE LOCTION OF THE DOWNSPOUT
 IS SHOWING THE TOTAL AREA DRAINING TO ONE ROOF DRAIN,
 BUT THE AREA IS DIVIDED EQUALLY BETWEEN TWO ROOF
 DRAINS. THE SIZING FOR THE ROOF DRAINS WILL HAVE TO BE
 RECHECKED TO ACCOUNT FOR THE AMOUNT OF AREA DRAINING TO
 ONE DRAIN, NOT TWO. TABLE 1106.3. (SEE ROOF AREAS AT
 COL. LINES 1THRU 4/A THRU D, 7 THRU 9.1/A THRU D, AND 4
 - 5/E THRU H).
  
 57D. SHTS A2-0, A2-1, A2-2, A2-3 SUBMIT CALCULATIONS
 FOR PRIMARY AND SECONDARY ROOF DRAINS. INDICATE THE
 CONTRUBUTION ADD FROM 1/2 AREA OF ALL VERTICAL WALLS,
 INCLUDING PARAPETS, AND ROOF AREAS FROM ABOVE ADDED TO
 THE ROOF SECTIONS. THIS IS REQUIRED FOR ALL ROOF
 LEVELS. SQUARE FOOTAGE IS SHOWN, BUT NO CALCULATIONS
 WERE SUBMITTED. CONTRIBUTING VERTICAL AREAS FOR WALLS
 IS UNCLEAR. IS THE AREA SHOWN INDICATED PER WALL, OR
 TOTAL FOR ALL WALLS SHOWN. PLEASE CLARIFY. SECTIONS
 1106.1, 1106.2, 1106.3, 1106.4.
  
 58B. SHT A2-0 UPPER ROOF BY DOME SHOWS A DETAIL
 INDICATOR 20/A2-D.1. DETAIL 20 NOT FOUND ON SHT A2-D.1.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 59B. SHT A2-D.1 DETAIL 04 SHOW HEIGHT AND WIDTH AND
 INDICATE THE MEASUREMENT FROM THE ROOF TO THE FLOW LINE
 OF THE SCUPPER. SECTIONS 106.1.1 AND 1503.4.3.
  
 60B. SHT A6-1.1 DETAILS 1 THRU 6. SHOW THE TURNING AREA
 IN THE TOILET ROOMS. NOT IN THE ACCESSIBLE STALLS.
 SECTION 11-4.22.3.
  
 61B. SHT A6-1.1 DETAIL 2, SHOW THE CLEAR FLOOR SPACE
 FOR THE URINAL. SECTION 11-4.18.3.
  
 62B. SHT A6-1.1 DETAIL 4, ACCESSIBLE W/C SHALL BE 1'6"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG.
 11-28. LAV TO BE MIN. 15" (C/L OF CLEAR FLOOR SPACE).
  
 63B. SHT A6-1.1 DETAIL 7, ACCESSIBLE W/C SHALL BE 1'6"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG.
 11-28. (SHOWS 2'2").
  
 64B. SHT A6-2.1 DETAILS 2, 6 & 7 SHOWTHE TURNING AREA
 IN THE TOILET ROOMS. NOT IN THE ACCESSIBLE STALLS.
 SECTION 11-4.22.3.
  
 65B. SHT A6-2.1 DETAIL 4, ACCESSIBLE W/C SHALL BE 1'6"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG.
 11-28.
  
 66B. SHT A6-3.1 DETAIL 1, SHOW THE TURNING AREA IN THE
 LOCKER ROOM AREA. SECTION 11-4.2.3.
  
 67B. SHT A6-3.1 DETAILS 2, 3, 4 & 6, SHOW THE TURNING
 AREA IN THE TOILET ROOMS, NOT IN THE ACCESSIBLE STALLS.
 SECTION 11-4.22.3.
  
 68B. SHT A6-4.1 DETAILS 1 & 2, SHOW THE TURINING AREA
 IN THE TOILET ROOMS, NOT IN THE ACCESSIBLE STALLS.
 SECTION 11-4.22.3.
  
 69B. SHT A6-5.1 DETAIL 1, SHOW THE TURNING AREA IN THE
 TOILET ROOM, AND SHOW THE CLEAR FLOOR SPACE FOR THE
 URINAL. SECTIONS 11-4.22.3 AND 11-4.18.3.
  
 70B. SHTS A9-0.1 & A9-0.2 FINISH SCHEDULES: ROOMS
 C1.105, C1.106, A2.705, A2.706, A2.210, A2.211, A3.111,
 A3.114, C3.410, AND C3.412 ALL INDICATE THE WALLS TO BE
 PAINTED. PLEASE INDICATE HOW THIS COMPLIES WITH THE
 REQUIREMENT FOR "SMOOTH, HARD, NONABSORBENT WALLS AS
 REQUIRED IN SECTION 1210.2.
  
 71B. SHTS A9-0.1 & A9-0.2 FINISH SCHEDULES: ROOMS D2.10
 & D2.104 SHOW NO WALL FINISH AND THE FLOORING/BASE
 INDICATE RUBBERIZED FLOORING. INDICATE HOW THIS
 COMPLIES WITH "SMOOTH, HARD, NONABSORBENT FLOORS AS
 REQUIRED IN SECTION 1210.1.
  
 72B. SHT A9-4.1 INDICATE THE ROOM NUMBERS THAT THE
 DETAIL IS REFERENCING. SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.18.4 FLUSH CONTROLS
 B. 11-4.19.2 CLEARANCES
 C. 11-4.19.4 EXPOSED PIPES & CLEARANCES
  
 73B. SHT A9-4.2 INDICATE THE ROOM NUMBERS THAT THE
 DETAIL IS REFERENCING. SHOW COMPLIANCE WITH THE
 FOLLOWING:
 DETAIL #1
 A. 11-4.18.4 FLUSH CONTROLS
 B. 11-4.19.2 CLEARANCES
 C. 11-4.19.4 EXPOSED PIPES & CLEARANCES
  
 DETAIL #2
 A. 11-4.18.4 FLUSH CONTROLS
 B. 11-4.19.2 CLEARANCES
 C. 11-4.19.4 EXPOSED PIPES & CLEARANCES
  
 74B. SHT A9-4.4 INDICATE THE ROOM NUMBERS THAT THE
 DETAILS ARE REFERENCING.SHOW COMPLIANCE WITH THE
 FOLLOWING:
 DETAILS #1 - #2 - #3
 A. 11-4.19.2 CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
  
 75B. SHT A9-4.4 SHOW THE FOLLOWING FOR COMPLIANCE:A.
 11-4.19.2 CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 D. 11-4.21.5 CONTROLS
 E. 11-4.21.7 CURBS
  
 76B. SHTS A1.307, A1.709, A2.209, A2.315, A2.407,
 A3.109, C3.409, C3.310, A5.504 - SHOW COMPLIANCE WITH
 THE FOLLOWING
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH
 REQUIRED)
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
 D. 11-4.24.7 FAUCETS
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. SUBMITTING THE RED
 LINED SET OF PLUMBING SHEETS WHEN RESUBMITTING FOR
 REVIEW WILL HELP EXPEDITE THE PERMIT ALSO. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6721
 E-MAIL [email protected]
  
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 12 Status P Date 2009-02-26 Cont ID  
Sent By mflis Date 2009-02-26 Time 08:54 Rev Time 0.00
Received By mflis Date 2009-02-26 Time 08:54 Sent To  
Notes
2009-02-26 08:54:27ZONING REVIEW: PASSED
  
 ** MID-BLOCK CROSSING REVISIONS
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 11 Status F Date 2009-01-16 Cont ID  
Sent By mflis Date 2009-01-16 Time 16:51 Rev Time 0.00
Received By mflis Date 2009-01-16 Time 16:51 Sent To  
Notes
2009-01-16 16:55:26ZONING REVIEW: FAILED
  
 1) C-9 - SECTION "F" IS NOT INCLUDED FOR REVIEW. PLEASE
 PROVIDE SO THAT STAFF MAY REVIEW SLOPES.
  
 2) AMENDED CROSS-BLOCK WILL IMPACT EXISTING LIGHT POLES
 ON CLEMATIS STREET. PLEASE INDICATE LOCATION AND
 WHETHER RELOCATION WILL BE NECESSARY.
  
 3) SEATING AT CROSSBLOCK IS INDICATED AT 16" HIGH. THIS
 IS TOO LOW FOR MOST PEOPLE. PLEASE ADJUST SEAT HEIGHT
 TO 18"-20".
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 10 Status N Date 2009-01-06 Cont ID  
Sent By mflis Date 2009-01-06 Time 09:33 Rev Time 0.00
Received By mflis Date 2009-01-06 Time 09:33 Sent To  
Notes
2009-01-06 09:33:51ZONING REVIEW: NOT REQUIRED
  
 ** INTERIOR REVISIONS 2ND FLOOR
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 9 Status N Date 2009-01-06 Cont ID  
Sent By mflis Date 2009-01-06 Time 08:34 Rev Time 0.00
Received By mflis Date 2009-01-06 Time 08:34 Sent To  
Notes
2009-01-06 08:34:53ZONING REVIEW: NOT REQUIRED
  
 E & P REVISIONS
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 8 Status P Date 2008-10-27 Cont ID  
Sent By mflis Date 2008-10-27 Time 11:21 Rev Time 0.00
Received By mflis Date 2008-10-27 Time 11:21 Sent To  
Notes
2008-10-27 11:23:16ZONING REVIEW: PASSED WITH PROVISO
  
 ** REVISION OF GARAGE
  
 ** NOTE: BOLLARDS WITHIN PARKING GARAGE MAY NOT IMPINGE
 UPON 5'-0" CLEAR SIDE AISLE FOR ADA SPACES. THIS AREA
 MUST BE FREE OF OBSTRUCTION. (SEE ADA SPACE, SW CORNER
 OF GARAGE ON A1-GA.1). THIS WAS AN ISSUE WITH CLEMATIS
 STREET GARAGE.
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 7 Status P Date 2008-02-27 Cont ID  
Sent By mflis Date 2008-02-27 Time 15:20 Rev Time 0.00
Received By mflis Date 2008-02-27 Time 15:20 Sent To  
Notes
2008-02-27 15:31:25ZONING REVIEW: PASSED WITH PROVISO
  
 *REVISION TO LANDSCAPE PLANS*
  
 NOTE: SYLVESTER PALM SPECIES IS NOT INIDCATED ON PLANS
 THROUGH ANNOTATION. THIS INCLUDES THE PALMS LOCATED IN
 THE COURTYARD/PLAZA AREA. PLEASE ADD LABEL TO PLAN TO
 CORRECTLY IDENTIFY AND LOCATE THIS SPECIES.
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 6 Status P Date 2007-04-02 Cont ID  
Sent By mflis Date 2007-04-02 Time 13:41 Rev Time 0.00
Received By mflis Date 2007-04-02 Time 13:41 Sent To  
Notes
2007-04-02 13:44:02ZONING REVIEW: REVISION 8 - PASSED
  
 * NOTES:
  
 - PLAN OF SIDEWALK/RAMP/PLANTER AT CLEMATIS STREET
 CROSSING REMAINS UNCLEAR; PLEASE CONFIRM THE GRADE
 CHANGES AND THAT NO HANDRAIL WILL BE REQUIRED (AS
 PREVIOUSLY STATED)
 - PLAN SEEMS TO SHOW SOME KIND OF RAILING PROJECTING
 INTO CROSSWALK AREA ADJACENT TO THE RAMP. IS THIS
 CORRECT?
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 5 Status N Date 2007-03-26 Cont ID  
Sent By mflis Date 2007-03-26 Time 14:00 Rev Time 0.00
Received By mflis Date 2007-03-26 Time 14:00 Sent To  
Notes
2007-03-26 14:01:35ZONING REVIEW: REVISION 7: NOT REQUIRED
  
 - REVIEW OF MECH AND ELEC REVISIONS IN GARAGE
 - NO CHANGES TO PARKING LAYOUT OR BUILDING ELEVATIONS
 INDICATED
  
 MATT FLIS 822-1445

Review Stop Z ZONING
Rev No 4 Status P Date 2007-02-21 Cont ID  
Sent By mflis Date 2007-02-21 Time 11:22 Rev Time 0.00
Received By mflis Date 2007-02-21 Time 11:22 Sent To  
Notes
2007-02-21 11:26:00ZONING REVIEW: PASSED WITH PROVISO:
  
 1) CLEMATIS STREET SHALL BE RETAINED AS EXISTING EXCEPT
 FOR MODIFICATIONS NEAR CROSS-BLOCK CONNECTION. PER
 PREVIOUS PERMIT COMMENTS, LANDSCAPE AND SITE PLAN STILL
 INDICATE ADDITIONAL PLANTERS AND LANDSCAPING. CLEMATIS
 SHOULD BE REMAIN AS PRESENTLY CONFIGURED IN REGARDS TO
 LANDSCAPING.
 2) ANY UPDATE OF GARAGE ELEVATIONS WILL REQUIRE URBAN
 DESIGN REVIEW AND APPROVAL.
 3) PLEASE INDICATE SITE VISIBILITY TRIANGLES AT ALL
 CORNERS - 25'-0" LEG PROJECTED FROM CURB LINE.
  
 MATT FLIS 822-1445

Review Stop Z ZONING
Rev No 3 Status P Date 2007-01-30 Cont ID  
Sent By mflis Date 2007-01-30 Time 16:45 Rev Time 0.00
Received By mflis Date 2007-01-30 Time 11:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2006-12-27 Cont ID  
Sent By mflis Date 2006-12-27 Time 14:21 Rev Time 0.00
Received By mflis Date 2006-12-27 Time 13:42 Sent To  
Notes
2006-12-27 14:20:54ZONING REVIEW: DENIED
  
 OLD ITEMS:
  
 1. OK - BOLLARDS CAN MATCH THOSE PRESENTLY INSTALLED AT
 INTERSECTION OF CLEMATIS & DIXIE BY FDOT. THESE ARE
 CRASH-RESISTANT. VERIFY THAT BOLLARDS ARE ONLY
 NECESSARY WITH FLUSH CURB.
 2. OK - DISCUSSED WITH ARCHITECT AND ARE THEY ARE AWARE
 THAT EASEMENTS WILL BE NECESSARY PRIOR TO INSTALLATION
 OF CANOPIES.
 3. REVIEWED - ON CIVIL SECTION THROUGH SIDEWALK, PLEASE
 PROVIDE DIMENSIONS INDICATING WIDTH OF PLANTER AREA,
 PAVING ADJACENT TO PARKING ETC.
 4. NOT ADDRESSED - INDICATE 25'-0" SITE VISIBILITY
 TRIANGLES (BACK OF CURB) ON OVERALL SITE PLAN.
 5. NOT ADDRESSED - EXCEPT FOR ITEM (3) ABOVE,
 STREETSCAPE PLANTINGS ALONG CLEMATIS SHOULD NOT CHANGE.
 THERE ARE APPROXIMATELY 7-8 PLANTERS WITH PALMS
 PRESENTLY. NO ADDITIONAL TREES AND PLANTERS NEED BE
 ADDED.
 6.OK
 7. NOT ADDRESSED - LP.1 - PLEASE REPLACE WASHINGTONIA
 PALMS AT INTERSECTION OF BANYAN AND QUADRILLE WITH LIVE
 OAKS (SPACE APPROPRIATELY).
 8. OK - LANDSCAPE ARCHITECT IS AWARE THAT PLANNING
 SHOULD BE APPRISED OF ANY COORDINATION THAT IMPACTS
 TREE COUNTS, PLACEMENT.
 9. OK
 10. OK
 11. PARTIALLY ADDRESSED - OPENINGS, BUILDING PLAN AND
 SECTION DO NOT SEEM TO MATCH. PLEASE CONFIRM.
 12. OK
 13. OK
 14. OK
 15. PARTIALLY ADDRESSED - STILL DOES NOT APPEAR TO BE A
 BUILDING SECTION MARKED WHICH PICKS UP THIS STRUCTURE
 AND ASSOCIATED DETAILS.
  
 NEW ITEMS:
  
 16. ELEVATION KEYS ON A4-XX SERIES DO NOT ALWAYS MATCH
 ELEVATION VIEW. PLEASE MODIFY TO ACCURATELY REFLECT
 WHAT IS SHOWN (BUILDING ONLY OR GARAGE ONLY ETC) 17.
 ELEVATIONS OF GARAGE WERE DISCUSSED WITH ARCHITECT.
 PLANNING STAFF WILL REVIEW MODIFICATIONS PER THAT
 MEETING.
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status F Date 2006-11-07 Cont ID  
Sent By mflis Date 2006-11-07 Time 09:10 Rev Time 0.00
Received By mflis Date 2006-11-06 Time 11:37 Sent To ENG
Notes
2006-11-06 13:54:17ZONING REVIEW: DENIED
  
 1. A1-1.0 - BOLLARDS LOCATED ALONG PLAZA SHALL MATCH
 THOSE PROVIDED CURRENTLY ALONG CLEMATIS STREET, AND
 SHALL BE APPROPRIATELY SPACED.
 2. A1-1.0 - ANY CANOPIES OR OVERHANGS MAY REQUIRE
 AIR-RIGHTS EASEMENTS - PLEASE COORDINATE WITH PLANNING
 AND LAW DEPTS.
 3. A1-1.0, LP.1, C-10 - CLEMATIS STREET
 PAVING/LANDSCAPING, AND GRADING SHALL BE MODIFIED TO
 MATCH RESOLUTION AS DISCUSSED IN NOV. 6, 2006 MEETING.
 PLANNING AND OTHER CITY STAFF SHALL REVIEWSIDEWALK
 AND PLANTER TRANSITION ALONG CLEMATIS PRIOR TO FINAL
 APPROVAL. VERFIY NO RAILING WILL BE REQURIRED ALONG OR
 IN SIDEWALK.
 4. A1-1.0 - SITE VISIBILITY TRIANGLES MUST BE SHOWN ON
 SITE PLAN - A1-1.0. GARAGE LOOKS VERY CLOSE TO
 IMPINGING.
 5. LP.1 - ALONG CLEMATIS STREET, PLEASE REMOVE ANY NEW
 PLANTERS OR TREE GRATES WHICH ARE IN ADDITION TO
 EXISTING CONDITIONS. STREET TREE LAYOUT SHALL NOT BE
 MODIFIED FROM EXISTING, EXCEPT PER ITEM #3 ABOVE. (SITE
 AND LANDSCAPE PLANS SHOW INCREASED NUMBER OF TREE
 GRATES AND PLANTINGS).
 6.LP.1 - CLEMATIS STREET PAVERS MUST MATCH COLOR AND
 STYLE OF EXISTING.
 7. LP.1 - PLEASE REPLACE WASHINGTONIA PALM AT
 INTERSECTION OF BANYAN AND QUADRILLE WITH LIVE OAKS. 8.
 LP.1 -LANDSCAPING PLANTINGS SHALL BE COORDINATED WITH
 ENGINEERING AND UTILITIES; PLANNING STAFF SHALL REVIEW
 ANY RELOCATED TREES ETC. AS A RESULT OF THIS
 COORDINATION.
 9. 2/A4-4.0 - NOTE AT T.O. COOLING TOWERS IS MARKED "?"
 - PLEASE CONFIRM SIZE OF EQUIPMENT AND VERIFY THAT IT
 WILL BE SCREENED BY THE PANELS.
 10. PLEASE PROVIDE STANDARD CITY PARKING DETAILS. 11.
 1/A4-4.0 - NORTH ELEVATION OF GARAGE IS INCORRECT:
 PLEASE MATCH CORRECT OPENING LOCATIONS. CONTINUE
 KICKPLATE ACROSS ENTIRE ELEVATION.
 12. 4/A4-4.0 - PLEASE CONTINUE HORIZONTAL REVEAL
 (12"X3/4") FOUND ON EAST ELEVATION OF GARAGE TO SOUTH
 ELEVATION.
 13. 4/A4-4.0 - NOTE INDICATED WATER FEATURE NIC.
 CONFIRM THAT THIS NOTE SHOULD REMAIN.
 14. LP.1 - PHOENIX SYLVESTRIS PALMS LOCATED AT CLEMATIS
 STREET PLAZA - NOT SURE EXACTLY WHAT DESIGN STRATEGY IS
 HERE. SHOULD THESE SPECIMEN TREES HIGHLIGHT THE CIRCLE
 FEATURE OR STAND AS A SEPARATE GRID? LAYOUT OF TREES
 SEEMS TO BE A HYBRID OF BOTH IDEAS, AND IS SOMEWHAT
 UNCLEAR.
 15. 1/A5-0.2/ 2/A4-3.0 - COVERED STRUCTURE WHICH
 EXTENDS BETWEEN CITY HALL AND LIBRARY IN COURTYARD
 APPEARS IN ELEVATION, DOES NOT SHOW IN BUILDING
 SECTIONS. PLEASE PROVIDE DETAILS REGARDING THIS
 ELEMENT.
  
  
 MATT FLIS - 822-1445