Plan Review Details - Permit 06100524
Plan Review Stops For Permit 06100524
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2007-10-30 Cont ID  
Sent By rmcdouga Date 2007-10-30 Time 10:20 Rev Time 0.00
Received By rmcdouga Date 2007-10-30 Time 10:20 Sent To  
Notes
2007-10-30 10:27:32REVISED SHEET SP-1 HAS BEEN REVIEWED FOR CODE
 COMPLIANCE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-08-01 Cont ID  
Sent By rmcdouga Date 2007-08-01 Time 10:28 Rev Time 0.00
Received By rmcdouga Date 2007-08-01 Time 09:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-07-10 Cont ID  
Sent By rmcdouga Date 2007-07-10 Time 15:57 Rev Time 0.00
Received By rmcdouga Date 2007-07-10 Time 15:57 Sent To  
Notes
2007-07-10 16:35:25REVISION OF SHEETS S1 - S6 IS DENIED
  
 1) THIS REVISION INCREASES THE VALUE OF THE JOB.
 INDICATE THE AMOUNT OF THE INCREASE ON THE REVISION
 FORM AND HAVE THE INTAKE CLERK ADD THIS TO THE ORIGINAL
 VALUE.
  
 2) ON SHEET S3 ONE OF THE PORCH DIMENSIONS IS MISSING.
 SEE RED MARKS ON THE DRAWING.
  
 3) PROVIDE A SECTION THROUGH THE STAIRS SHOWN AT THE
 MASTER BEDROOM PORCH ON SHEET S3.
  
 4) ON SHEET S4 THERE IS A SECTION TAG FOR 13/S6 AND
 THERE IS NO SUCH SECTION ON SHEET S6. PLEASE CORRECT.
  
 5) ON SHEET S4, (2) 1-3/4"X 11-1/4" 1.95 MICROLAMS
 ARE SPECIFIED AND IN SECTION 9/S6 (2) 1-3/4" X 11-3/4"
 1.9E MICROLAM BEAMS ARE SPECIFIED. PLEASE CORRECT.
  
 6) SPECIFY THE TRUSS CONNECTORS FOR THE MASTER BEDROOM
 PORCH.
  
 7) SECTION 5/S6 ON S4 IS IN THE WRONG LOCATION. IT
 NEEDS TO BE REVISED TO SHOW THE NEW MASTER BEDROOM
 PORCH.
  
 8) IN DETAIL 3 ON S6 SPECIFY WHAT THE 5/8" DIA
 FASTENERS @ 24"OC ARE. ALSO CHECK THE SIMPSON
 CONNECTORS THAT ARE SPECIFIED ( LUZ10 AND HSTC 78).
 THESE COULD NOT BE FOUND IN THE SIMPSON CATALOG. SHOULD
 THESE BE LU210 AND MSTC 78 ?
  
 9) ADDRESS ZONING COMMENTS.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-02-27 Cont ID  
Sent By rmcdouga Date 2007-02-27 Time 17:43 Rev Time 0.00
Received By rmcdouga Date 2007-02-27 Time 17:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-02-26 Cont ID  
Sent By tgordon Date 2007-02-27 Time 14:58 Rev Time 0.00
Received By rmcdouga Date 2007-02-26 Time 12:29 Sent To  
Notes
2007-02-26 16:53:49DENIED BY BUILDING
  
 1) THE NOA SUBMITTED FOR THE SOUTHEASTERN METALS MFG.
 CO. METAL ROOF IS EXPIRED. THE NOA NUMBER 06-1012.08
 HAS NOT BEEN APPROVED BY MIAMI-DADE PRODUCT CONTROL
 DIVISION AT THIS TIME. STATUS STATES THAT ADDITIONAL
 INFORMATION HAS BEEN REQUESTED.
  
 2) SPECIFY WHICH ONE OF THE APPROVED SYSTEMS LISTED IN
 THE FIRESTONE MODIFIED SYSTEM PRODUCT APPROVAL WILL BE
 INSTALLED. SPECIFY THE FASTENING OPTION AND DESIGN
 PRESSURE FOR THE SELECTED SYSTEM. CIRCLE THE
 APPROPRIATE ITEMS ON THE PRODUCT APPROVALS. IF ENHANCED
 FASTENING IS REQUIRED TO MEET THE HIGHER UPLIFT
 PRESSURES IN THE PERIMETER OR CORNER AREAS, SUBMIT RAS
 117 CALCULATIONS PER LIMITATION #7 ON PAGE 34 OF THE
 NOA.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-02-05 Cont ID  
Sent By rmcdouga Date 2007-02-05 Time 10:27 Rev Time 0.00
Received By rmcdouga Date 2007-02-05 Time 06:36 Sent To  
Notes
2007-02-05 10:27:02DENIED BY BUILDING
  
 1)ON SHEET S2 THE TYPE AND NUMBER OF FASTENERS IS
 REQUIRED IN THE TRUSS CONNECTOR SCHEDULE FOR EACH OF
 THE UPLIFT VALUES LISTED.
  
 2)SHOW COMPLIANCE WITH R320.1 FOR TERMITE
 PROTECTION.
  
 TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED
 TERMITICIDES, INCLUDING SOIL APPLIED PESTICIDES,
 BAITING SYSTEMS, AND PESTICIDES APPLIED TO WOOD, OR
 OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED
 FOR USE AS A PREVENTATIVE TREATMENT TO NEW CONSTRUCTION
 (SEE SECTION 202 , REGISTERED TERMITICIDE). UPON
 COMPLETION OF THE APPLICATION OF THE TERMITE PROTECTIVE
 TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL BE ISSUED
 TO THE BUILDING DEPARTMENT BY THE LICENSED PEST CONTROL
 COMPANY THAT CONTAINS THE FOLLOWING STATEMENT: ?THE
 BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE
 PREVENTION OF SUBTERRANEAN TERMITES. TREATMENT IS IN
 ACCORDANCE WITH RULES AND LAWS ESTABLISHED BY THE
 FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER
 SERVICES.?
  
 3) SHOW COMPLIANCE WITH R319.1 WHERE FLOOR JOISTS ARE
 INSTALLED OVER EXISTING SLAB.
 IN AREAS SUBJECT TO DECAY DAMAGE AS ESTABLISHED BY
 TABLE R301.2(1) , THE FOLLOWING LOCATIONS SHALL REQUIRE
 THE USE OF AN APPROVED SPECIES AND GRADE OF LUMBER,
 PRESSURE TREATED IN ACCORDANCE WITH AWPA C1, C2, C3,
 C4, C9, C15, C18, C22, C23, C24, C28, C31, C33, P1, P2
 AND P3, OR DECAY-RESISTANT HEARTWOOD OF REDWOOD, BLACK
 LOCUST, OR CEDARS
 3.SILLS AND SLEEPERS ON A CONCRETE OR MASONRY
 SLAB THAT IS IN DIRECT CONTACT WITH THE GROUND UNLESS
 SEPARATED FROM SUCH SLAB BY AN IMPERVIOUS MOISTURE
 BARRIER.
  
 4) SHOW COMPLIANCE WITH R506.2.3 VAPOR RETARDER.
 A 6 MIL (0.006 INCH; 152 ?M) POLYETHYLENE OR APPROVED
 VAPOR RETARDER WITH JOINTS LAPPED NOT LESS THAN 6
 INCHES (152 MM) SHALL BE PLACED BETWEEN THE CONCRETE
 FLOOR SLAB AND THE BASE COURSE OR THE PREPARED SUBGRADE
 WHERE NO BASE COURSE EXISTS.
 EXCEPTION: THE VAPOR RETARDER MAY BE OMITTED:
 1.FROM GARAGES, UTILITY BUILDINGS AND OTHER
 UNHEATED ACCESSORY STRUCTURES.
 2.FROM DRIVEWAYS, WALKS, PATIOS AND OTHER FLATWORK
 NOT LIKELY TO BE ENCLOSED AND HEATED AT A LATER DATE.
 3.WHERE APPROVED BY THE BUILDING OFFICIAL, BASED
 ON LOCAL SITE CONDITIONS.
 NOTE: EXISTING SCREEN PORCH SLAB THAT IS BEING LEFT IN
 PLACE MAY NOT HAVE VAPOR RETARDER.
  
 5) IN THE SECTION THROUGH THE GARAGE SLAB, SECTION 6 ON
 S5,THE SLAB IS SHOWN AT THE SAME ELEVATION AS THE
 EXTERIOR GRADE. THE SLAB IS REQUIRED TO BE A MINIMUM OF
 4' ABOVE GRADE. SEE R404.1.6.
  
 6)SHOW COMPLIANCE WITH WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 7)SUBMIT PRODUCT APPROVALS FOR THE LARGE MISSLE
 IMPACT RATED DOUBLE AND SINGLE OUTSWING GLAZED FRENCH
 DOORS WITHOUT SIDELITES. THE ONES THAT WERE SUBMITTED
 ARE FOR DOORS WITH SIDELITES.
  
 8)SUBMIT PRODUCT APPROVALS FOR THE NEW BAHAMA
 HURRICANE SHUTTERS.
  
 9)SUBMIT PRODUCT APPROVALS FOR THE METAL ROOF. THE
 NOA SUBMITTED FOR THE SOUTHEASTERN METALS MFG. CO.
 METAL ROOF IS EXPIRED.
  
 10) SUBMIT PRODUCT APPROVALS FOR THE ROOFING THAT WILL
 BE INSTALLED ON THE FLAT DECK.
  
 11) SUBMIT TWO SETS OF TRUSS DRAWINGS THAT HAVE BEEN
 SIGNED AND SEALED BY THE TRUSS ENGINEER AND HAVE BEEN
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD FOR THE PROJECT PRIOR TO INSTALLATION. SEE
 R802.1.6.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-06 Cont ID  
Sent By alange Date 2006-11-06 Time 08:19 Rev Time 0.00
Received By alange Date 2006-11-06 Time 08:19 Sent To  
Notes
2006-11-06 08:23:53DENIED
  
 1.SHOW METHOD OD SLAB ATTACHMENT FROM EXISTING SLAB
 TO NEW.
  
 2.PRODUCT APPROVALS REQUIRED FOR LINTELS.
  
 3.ALL PRODUCT APPROVALS SUBMITTED WITH QUALITY
 ASSURANCE SHALL HAVE THE FOLLOWING STATE APPROVAL
 ATTACHED.
 NOTE:INCORRECT STATE PRODUCT APPROVAL PAGES SUBMITTED
 FOR WINGARD DOOR AND PGT SH 701.PGT SH 701 MIAMI-DADE
 IS EXPIRED.
  
 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL SHEETS THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM THE STATE. IF
 THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT AN
 APPLICATION FOR LOCAL PRODUCT APPROVAL OR SITE SPECIFIC
 FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 4.THOSE PRODUCT APPROVALS WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.WPB AMENDMENT TO FBC 106.3.3.
  
  
 5.SUBMIT TWO SETS OF TRUSS DRAWINGS FOR REVIEW PER
 2004 FBC R-802.10.1TRUSS DRAWING REQUIRED TO BE
 APPROVED PRIOR TO INSTALLATION.
  
 6.A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR
 A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.SHOW HOW PLANS
 WILL COMPLY WITH THE SECTION(S) SELECTED.2004 FBC
 EXISTING BUILDING 301.5
  
 7.R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS
 TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE
 GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM
 OF 6 INCHESWITHIN THE FIRST 10 FEET.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. SUBMIT ONE
 COPY OF OLD PAGES FOR REFERENCE . A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DEPARTMENT
 561-805-6672
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-07-26 Cont ID  
Sent By dpalmer Date 2007-07-26 Time 14:37 Rev Time 0.00
Received By dpalmer Date 2007-07-26 Time 12:16 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-07-13 Cont ID  
Sent By dpalmer Date 2007-07-13 Time 11:55 Rev Time 0.00
Received By dpalmer Date 2007-07-13 Time 11:13 Sent To PC
Notes
2007-07-13 11:55:28**** PROVISO **** ** I
  
  
 1) NOTE: PLEASE REVISE LOAD CALCULATIONS TO COORIDNATE
 WITH THE CIRCUITING ON PLANS AND MINIMUM REQUIRED PER
 NEC 220.31B.
  
 2) NOTE: PLEASE SUBMIT REVISED UPDATE PANEL SCHEDULE(S)
 WITH ALL CIRCUITING AS SHOWN ON PLAN WITH COMPLETE
 SPECIFIC ROOMS AND AREAS PER 408.4
  
  
 ** THE ABOVE MUST BE COMPLETED AND ON-SITE FOR
 INSPECTION BEFORE FINAL.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-07-03 Cont ID  
Sent By dpalmer Date 2007-07-03 Time 16:52 Rev Time 0.00
Received By dpalmer Date 2007-07-03 Time 16:52 Sent To PC
Notes
2007-07-03 17:00:39**** UNSAT **
  
 1) NOTE: PLEASE SEE PLANS MAY NOT BE SUBMITTED DONE
 WIHT INK AND WHITE OUT IN ANY CASE.FBC 106.1
 PLEASE ALSO SEE THAT ALL OF THESE CHANGES WERE MADE TO
 PLANS WHICH WERE SIGNED, DATED AND SEALED BY AN
 ARCHITECT. FS 481.221
  
 ** PLEASE GIVE CHANGES TO TO THE ARCHITECT OF RECORD.
 PLEASE ALSO SEE THE *PROVISO* NOTES WHICH WERE ATTACHED
 AND WRITTEN ON PLANS WHEN PERMIT WAS ISSUED. PLEASE SEE
 THESE NOTES ARE BELOW WHICH STILL NEED TO BE
 ADDRESSED.
  
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
  
  
  
  
  
 ** PROVISO/REVISON NEEDED **
  
  
 1) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.16 AS
 1500VA SHALL BE FIGURED INTO THE LOAD CALCULATIONS FOR
 ONE, TWO OR *MORE* OF THE SMALL APPLIANCE CIRCUITS.
  
 2) NOTE: PLEASE CORRELATE VA FOR GDO.
  
 ** PLEASE REVISE THE ABOVE ALONG WITH ANY OTHER
 ELECTRICAL REVISIONS BEFORE ROUGH ELECTRICAL
 INSPECTION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-02-25 Cont ID  
Sent By dpalmer Date 2007-02-25 Time 14:39 Rev Time 0.00
Received By dpalmer Date 2007-02-25 Time 14:19 Sent To M
Notes
2007-02-25 14:39:21 
 ** PROVISO/REVISON NEEDED **
  
  
 1) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.16 AS
 1500VA SHALL BE FIGURED INTO THE LOAD CALCULATIONS FOR
 ONE, TWO OR *MORE* OF THE SMALL APPLIANCE CIRCUITS.
  
 2) NOTE: PLEASE CORRELATE VA FOR GDO.
  
 ** PLEASE REVISE THE ABOVE ALONG WITH ANY OTHER
 ELECTRICAL REVISIONS BEFORE ROUGH ELECTRICAL
 INSPECTION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-12-27 Cont ID  
Sent By dpalmer Date 2006-12-27 Time 08:07 Rev Time 0.00
Received By dpalmer Date 2006-12-26 Time 17:42 Sent To P
Notes
2006-12-27 08:08:23***** UNSAT2ND REVIEW ****
  
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
  
 1) NOTE: NO, PLEASE SEE THIS IS THE SAME NOTE. PLEASE
 SEE THERE ARE STILL CODES ON ELECTRICAL PLANS WHICH ARE
 FROM THE 1996 NEC. (NOTE #37)
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE PLANS REFLECT THE FOLLOWING CODES AT A
 MINIMUM.
 2002 NFPA-70 (NEC.
 2002 NFPA-72 FAC.
  
 2) NOTE: OK/NO, SYMBOL WAS CHANGED; HOWEVER PLEASE SEE
 THAT THE NOTE ON E-2 STILL INDICATES SMOKE DETECTORS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NFPA-72 DEFINITIONS, THE SYMBOL FOR SMOKE
 DETECTION DEVICES SHOULD BE SA IF INDEED A DEVICE WHICH
 WILL BE INSTALLED TO DETECT AND SOUND. IF THERE IS A
 FIRE ALARM SYSTEM, THEN ONLY THEN WOULD THEY BE SD.
  
 3) NOTE: NO/OK, PLEASE SEE NOTES ON PLANS ON E-2 WHICH
 ARE LABELED AS KEYNOTES STILL ARE IN QUESTION. PLEASE
 SEE MISSING #6. PLEASE ACTUALLY SHOW THE EQUIPMENT AND
 LOCATIONS ON PLANS. COMPLIANCE FOR SOME CODE REVIEW
 ITEMS CAN NOT BE DONE.
 PLEASE SEE MANY OF THE PREVIOUS ITEMS FROM THIS COMMENT
 WAS ADDRESSED, HOWEVER NOT ALL.
  
  
 **PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE RISER AND PLANS, AS PLANS CALL FOR A
 NEW METER/MAIN COMBO, YET RISER SHOWS AND MAIN AND A
 NEW PANEL??
 PLEASE SEE RISER SHOWS THE IDENTIFICATION OF THE
 CONDUCTORS FROM THE METER TO THE MAIN AS "FEEDERS".
 PLEASE KNOW, THESE ARE INDEED SERVICE ENTRANCE
 CONDUCTORS TO THE MAIN. PLEASE KNOW FEEDERS ARE ONLY
 AFTER THE FIRST MEANS OF DISCONNECT.
 PLEASE SEE IN EITHER CASE THE CONDUCTOR SIZES ARE
 MISSING FOR THE SEC'S AND THE FEEDERS FROM THE MAIN TO
 PANELS?
 PLEASE SEE 240.4, 310.16, 100, 215.5, 230.7 ETC
 NO REVIEW FOR COMPLIANCE OF THESE CAN BE DONE AT THIS
 TIME.
  
 4) NOTE: OK/NO, PLEASE SEE NOTE #10 COMMENTS WITH
 RESPECT TO CORRELATION OF OVER CURRENT PROTECTION,
 CONDUCTOR SIZES AND SIZE OF LOADS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE ALL PANEL AND EQUIPMENT SIZE AND
 CORRELATE WITH CONDUCTORS AND OCP.
 240., 230.310 ETC.
  
 5) NOTE: OK.
  
 6) NOTE: OK/NO, PLEASE SEE THE PANEL SCHEDULE WAS
 SUBMITTED, HOWEVER THERE ARE ITEMS WHICH DO NO MEET
 MINIMUM CODE FOR OCP, CONDUCTORS SIZES ETC.
 PLEASE SEE COMMENTS ON THESE NOTES AND REDLINED PLANS.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SUBMIT A PANEL SCHEDULE INDICATING ALL MINIMUM
 REQUIRED CIRCUITS FOR ALL NEW AND INDICATE EXISTING.
 PLEASE BE SURE PANEL SCHEDULE SHOWS ALL OCP DEVICES AND
 CONDUCTOR SIZES AS REQUIRED FOR MIN CIRCUITS. PLEASE
 KNOW WE ARE UNABLE TO REVIEW FOR CODE COMPLIANCE AT
 THIS TIME.
 240.4,310.16, 424.3B, 210.52, ETC.
 FBC ADMIN SECTION 106.3.5.4(8).
  
 7) NOTE: NO, PLEASE SEE 220.31B FOR MINIMUM LOAD
 CALCULATIONS, THIS MAY ACTUALLY AFFECT THE SERVICE AND
 SIZE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE PANEL SCHEDULE AND CORRELATE LOAD
 CALCULATIONS FOR ALL DEDICATED ELECTRICAL CIRCUITS ON
 PLANS. PLEASE SEE THERE ARE SEVERAL DEDICATED CIRCUITS
 WHICH ARE NOT FIGURED INTO THE LOAD CALCS. FRIG, GDO,
 OTHERS SHOWN ETC.
 220.31B, 220.16, 210.11
  
 8) NOTE: NO, PLEASE SEE CIRCUIT(S) SHOWN; HOWEVER
 PLEASE SEE THESE CAN NOT BE #14 OR 15A OCP.
 PLEASE SEE MASTER BATH RECEPTS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING DEDICATED BATH(S) CIRCUIT(S) PER
 210.52D, 210.11C3
  
 9) NOTE:NO, COULD NOT LOCATE ANY INDICATION OF THIS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING DINING AREA/BREAKFAST AREA PER
 210.52B1, 210.11C1, 220.16
  
 10) NOTE: NO, PLEASE SEE THE OCP AND CONDUCTOR SIZES
 FOR THE EACH OF THE CIRCUITS DO NOT MEET CODE. PLEASE
 SEE PANEL SCHEDULE SHOWS 50A OCP AND #6 AND EACH
 APPLIANCE CIRCUIT AS 240V?
 PLEASE ADJUST AND CORRELATE.
  
  
 **PREVIOUS REVIEW NOTE **
 PLEASE SEE DISPOSAL IS BEING SHOWN WITH 2KW LOAD.
 PLEASE KNOW THIS UNIT IS MOST LIKELY A 120V UNIT AND
 2KW EXCEEDS THE RATING OF A 20A CIRCUIT. PLEASE KNOW AS
 NO PANEL SCHEDULE WAS NOT SUBMITTED, IT IS UNCLEAR OF
 THE OCP AND THE SIZE OF THE CONDUCTORS INTENDED. 240.4,
 310.16, ETC
  
 11) NOTE: OK.
  
 12) NOTE: OK.
  
 13) NOTE:OK.
  
 14) NOTE: OK.
  
 15) NOTE:NO, PLEASE CLARIFY THE EXISTING AREAS AND
 NEW, AND MUCH IF THE EXISTING DWELLING IS BEING
 REMODELED AND CODE COMPLIANCE FOR RECEPT SPACING NEEDS
 TO BE VERIFIED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THERE ARE SOME AREAS WHICH APPEAR TO CONTAIN
 NEW WALLS, YET DO NOT MEET 210.52 FOR RECEPT SPACING.
 PLEASE INDICATED ALL NEW AND EXISTING (E) WHICH WILL OR
 DO MEET ABOVE.
  
 16) NOTE: OK.
  
 17) NOTE:OK/NO, PLEASE SEE A/C UNITS AS NOW SHOWN,
 HOWEVER PLEASE SEE MISSING DISCONNECTS FOR THE AHU?S
 WHICH SHOWS A RECEPT FOR UNIT. PLEASE SEE 440.11,
 440.12 AS RECEPTS ARE NOT PERMITTED FOR THE CONNECTION
 OF THESE UNITS AND TO USE AS DISCONNECT EITHER.
 PLEASE ALSO SEE NEW NOTES WITH RESPECT TO CU?S.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INCLUDE ANY NEW A/C EQUIPMENT AND DISCONNECTS
 IF APPLICABLE.
  
 18) NOTE:NO, PLEASE SEE THE WASHER AND DRYER WAS
 IDENTIFIED, HOWEVER THERE ARE STILL TWO OTHER LOCATION
 WHICH APPEARS TO BE EQUIPMENT OF SOME KIND.PLEASE SEE
 PANEL SCHEDULE MENTIONS A WATER HEATER AND ELECTRIC FOR
 THIS UNIT, HOWEVER THIS IS NOT SHOWN ON PLANS. PLEASE
 SEE REDLINED SET.
  
 **PREVIOUS REVIEW NOTE **
 PLEASE SEE NEW EQUIPMENT WHICH SEEMS TO BE SHOWN IN
 GARAGE BUT NOT IDENTIFIED?
 WASHER/ DRYER?
  
 **** NEW NOTES***
  
 1) NOTE: PLEASE SEE MISSING GFI RECEPTS PER 210.63 ,
 210.8A3.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH CONTAIN A
 NOTE IN ASTERISK ** WHICH SAID ** IMPORTANT**, WHICH
 REQUESTED FOR ALL OLD/VOIDED SHEETS TO BE COMPLETELY
 REMOVED FROM SETS AND ONLY INSERT NEW SHEETS INTO THE
 TWO COMPLETE SETS FOR REVIEW. PLEASE KNOW THIS WILL
 HELP IN THE REVIEW PROCESS TO EXPEDITE PLANS IN THE
 REVIEW AND PROCESSING. IF THESE ARE NOT REMOVED, THE
 CONTRACTOR WILL BE CONTACTED TO COME IN AND DO THIS
 BEFORE PLANS CAN BE PROCESSED FOR ISSUANCE.
 PLEASE SEE THAT ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE ONLY.
  
 3) NOTE: PLEASE SEE ATTACHED NOTICE TO FLORIDA STATUTES
 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS FOR CODE
 COMPLIANCE. THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-12-26 16:38:042006-12-26 18:07:32
 NOTES TO FOLLOW, REVIEW STOPPED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-31 Cont ID  
Sent By dpalmer Date 2006-10-31 Time 19:59 Rev Time 0.00
Received By dpalmer Date 2006-10-31 Time 19:20 Sent To M
Notes
2006-10-31 19:59:19***** UNSAT ****
  
 1) NOTE: PLEASE BE SURE PLANS REFLECT THE FOLLOWING
 CODES AT A MINIMUM.
 2002 NFPA-70 (NEC.
 2002 NFPA-72 FAC.
  
 2) NOTE: PLEASE SEE NFPA-72 DEFINITIONS, THE SYMBOL FOR
 SMOKE DETECTION DEVICES SHOULD BE SA IF INDEED A DEVICE
 WHICH WILL BE INSTALLED TO DETECT AND SOUND. IF THERE
 IS A FIRE ALARM SYSTEM, THEN ONLY THENWOULD THEY BE
 SD.
  
 3) NOTE: PLEASE CORRELATE RISER AND PLANS, AS PLANS
 CALL FOR A NEW METER/MAIN COMBO, YET RISER SHOWS AND
 MAIN AND A NEW PANEL??
 PLEASE SEE RISER SHOWS THE IDENTIFICATION OF THE
 CONDUCTORS FROM THE METER TO THE MAIN AS "FEEDERS".
 PLEASE KNOW, THESE ARE INDEED SERVICE ENTRANCE
 CONDUCTORS TO THE MAIN. PLEASE KNOW FEEDERS ARE ONLY
 AFTER THE FIRST MEANS OF DISCONNECT.
 PLEASE SEE IN EITHER CASE THE CONDUCTOR SIZES ARE
 MISSING FOR THE SEC'S AND THE FEEDERS FROM THE MAIN TO
 PANELS?
 PLEASE SEE 240.4, 310.16, 100, 215.5, 230.7 ETC
 NO REVIEW FOR COMPLIANCE OF THESE CAN BE DONE AT THIS
 TIME.
  
 4) NOTE: PLEASE INDICATE ALL PANEL AND EQUIPMENT SIZE
 AND CORRELATE WITH CONDUCTORS AND OCP.
 240., 230.310 ETC.
  
 5) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR NEW SERVICE
 EQUIPMENT ALONG WITH SELECTIVE COORDINATION WHICH IS TO
 BE DONE.
 110.9, 240.12
  
 6) NOTE: PLEASE SUBMIT A PANEL SCHEDULE INDICATING ALL
 MINIMUM REQUIRED CIRCUITS FOR ALL NEW AND INDICATE
 EXISTING.
 PLEASE BE SURE PANEL SCHEDULE SHOWS ALL OCP DEVICES AND
 CONDUCTOR SIZES AS REQUIRED FOR MIN CIRCUITS. PLEASE
 KNOW WE ARE UNABLE TO REVIEW FOR CODE COMPLIANCE AT
 THIS TIME.
 240.4,310.16, 424.3B, 210.52, ETC.
 FBC ADMIN SECTION 106.3.5.4(8).
  
 7) NOTE: PLEASE COMPLETE PANEL SCHEDULE AND CORRELATE
 LOAD CALCULATIONS FOR ALL DEDICATED ELECTRICAL CIRCUITS
 ON PLANS. PLEASE SEE THERE ARE SEVERAL DEDICATED
 CIRCUITS WHICH ARE NOT FIGURED INTO THE LOAD CALCS.
 FRIG, GDO, OTHERS SHOWN ETC.
 220.31B, 220.16, 210.11
  
 8) NOTE: PLEASE SEE MISSING DEDICATED BATH(S)
 CIRCUIT(S) PER 210.52D, 210.11C3
  
 9) NOTE: PLEASE SEE MISSING DINING AREA/BREAKFAST AREA
 PER 210.52B1, 210.11C1, 220.16
  
 10) NOTE: PLEASE SEE DISPOSAL IS BEING SHOWN WITH 2KW
 LOAD. PLEASE KNOW THIS UNIT IS MOST LIKELY A 120V UNIT
 AND 2KW EXCEEDS THE RATING OF A 20A CIRCUIT. PLEASE
 KNOW AS NO PANEL SCHEDULE WAS SUBMITTED, IT IS UNCLEAR
 OF THE OCP AND THE SIZE OF THE CONDUCTORS INTENDED.
 240.4, 310.16, ETC
  
 11) NOTE: PLEASE SEE NOTE ON PLANS CALLS FOR AFCI
 PROTECTION FOR RECEPTS, WHEREAS THIS IS UNDER THE 1999
 NEC REQUIREMENTS. PLEASE SEE WE ARE UNDER THE 2002 NEC
 AND REQUIRES AFCI PROTECTIONS FOR ALL "OUTLETS" IN
 BEDRM/SLEEPING AREAS.
 PLEASE ALSO SEE THIS IS REQUIRED OF NEW SMOKE ALARMS,
 FANS, LTS, RECEPTS ETC.
  
 12) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTOR PER 250.6, 250.24B, 250.110, 250.122
  
 13) NOTE: PLEASE NOTE AND VERIFY THE EXISTING GROUNDING
 ELECTRODE SYSTEM FOR THE NEW SERVICE.
 250.50
  
 14) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTS SERVING
 KITCHEN COUNTER SPACE ARE REQUIRED TO GFI/ GFI
 PROTECTED.
  
 15) NOTE: PLEASE SEE THERE ARE SOME AREAS WHICH APPEAR
 TO CONTAIN NEW WALLS, YET DO NOT MEET 210.52 FOR RECEPT
 SPACING.
 PLEASE INDICATED ALL NEW AND EXISTING (E) WHICH WILL OR
 DO MEET ABOVE.
  
 16) NOTE: PLEASE INDICATE ALL ROOM AND AREA
 DESIGNATIONS ON ELECTRICAL PLANS.
 106.1.2
  
 17) NOTE: PLEASE INCLUDE ANY NEW A/C EQUIPMENT AND
 DISCONNECTS IF APPLICABLE.
  
 18) NOTE: PLEASE SEE NEW EQUIPMENT WHICH SEEMS TO BE
 SHOWN IN GARAGE BUT NOT IDENTIFIED?
 WASHER/ DRYER?
  
 ** PLEASE KNOW AT THIS TIME AS THERE ARE MANY ITEMS NOT
 YET SUBMITTED, THERE MAY BE NEW COMMENTS ON NEW PLANS
 SUBMITTED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  
  
2006-10-31 19:21:11IN ELEC ON 10/31

Review Stop G GAS REVIEW
Rev No 6 Status P Date 2008-01-30 Cont ID  
Sent By mperson Date 2008-01-30 Time 10:04 Rev Time 0.00
Received By mperson Date 2008-01-30 Time 10:04 Sent To PC
Notes
2008-01-30 10:05:21REVISION: "OK" SHEETS P1 AND P2.

Review Stop G GAS REVIEW
Rev No 5 Status F Date 2007-12-06 Cont ID  
Sent By mperson Date 2007-12-06 Time 08:51 Rev Time 0.00
Received By mperson Date 2007-12-06 Time 08:51 Sent To PC
Notes
2007-12-06 09:13:34PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 REVISION DENIED:
  
 1. SHEET P1 AND P2: WITH THE GAS PIPING MATERIAL BEING
 CHANGED TO CSST AND LONGEST LONGEST LENGTH BEING
 INCREASED TO 123' THE GAS PIPING SYSTEM IS SIZED
 INCORRECTLY IN THE INTERIOR PER TABLE *402.4(14).
 PLEASE REFERENCE THE RED LINE CORRECTIONS TO THESE
 SHEETS AND ATTACHED TABLES TO THESE COMMENTS REFLECTING
 THE NEEDED CHANGES ON THE RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2007-10-29 Cont ID  
Sent By mperson Date 2007-10-29 Time 15:34 Rev Time 0.00
Received By mperson Date 2007-10-29 Time 15:34 Sent To B
Notes
2007-10-29 16:06:47REVISION DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE ON THE REVISED
 PLANS:
  
 1. SHEET P1 THE 1/2" GAS AND BTU LOAD FOR THE ADDED
 DRYER IS MISSING AND NEEDS TO BE INDICATED IN THE
 CLOUDED REVISION ON THE RESUBMITTED REVISION. PER
 *106.1.1, INFORMATION ON CONSTRUCTION DOCUMENTS AND
 *401.1, SCOPE.
  
 2. SHEET P2 GAS ISOMETRIC RISER DIAGRAM: THE DRYER AND
 ITS BUT LOAD ARE MISSING FROM THE REVISION CLOUD. PER
 *106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS AND
 *401.1, SCOPE.
  
 3. SHEET P2 GAS ISOMETRIC RISER DIAGRAM: THE GAS METER
 IS MISSING FROM THE GAS ISOMETRIC. PER *401.1, SCPOE.
  
 4. SHEET P2 GAS ISOMETRIC RISER DIAGRAM: THE TOTAL BTU
 LOAD NEEDS TO REVISED WITH THE ADDITION OF THE DRYER.
 PER *401.1, SCOPE.
  
 5. SHEET P2 GAS ISOMETRIC RISER DIAGRAM: PLEASE
 CLARIFY WHAT "PIPING MATERIALIS WARFLEX" IS. SHOULD IT
 READ AS "PIPING MATERIAL IS WARDFLEX"? AND PLEASE
 CLARIFY IF ALL PIPING MATERIAL IS BEING CHANGED TO
 WARDFLEX C.S.S.T. ON THE REVISION RESUBMITTAL. PLEASE
 CLEARLY IDENTIFY ALL PIPING MATERIALS BEING USED FOR
 EACH CUT SECTION OF PIPE. PER *106.1.1, INFORMATION ON
 COSTRUCTION DOCUMENTS AND *401.1, SCOPE.
  
 6. SHEET P2 GAS ISOMETRIC RISER DIAGRAM: PLEASE
 CORRELATE THE GAS ISOMETRIC, WHICH HAS THE ADDED SUM OF
 THE INDICATED CUT SECTIONS OF PIPE OF FIFTY EIGHT FEET
 (58') AND HAS THE REMOTE OUTLET BEING INDICATED AS
 SIXTYFIVE FEET (65'). PER *106.1.1, INFORMATION ON
 CONSTRUCTION DOCUMENTS AND *401.1, SCOPE.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2007-07-12 Cont ID  
Sent By mperson Date 2007-07-12 Time 13:19 Rev Time 0.45
Received By mperson Date 2007-07-12 Time 13:19 Sent To PC
Notes
2007-07-12 13:44:53DENIED REVISION
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PER PHONE CONVERSATION WITH DAVID BISHOP PLUMBING
 INSPECTOR THERE HAVE BEEN MANY CHANGES TO THIS GAS
 SYSTEM INCLUDING ADDING APPLIANCES, RELOCATING
 APPLIANCES, CHANGING PIPE SIZES AND MATERIALS.THE
 SUBMITTED SHEET P1 DOES NOT INDICATE ALL OF THESE
 CHANGES.
 NOTE: PLEASE SUBMIT SHEET P2, WITH THE NATURAL GAS
 ISOMETRIC RISER INDICATING ALL CHANGES FROM THE GAS
 METER LOCATION TO ANY CHANGES TO THE INTERIOR PIPING
 THAT IS DIFFERENT FROM THE APPROVED SET OF PLANS. THIS
 INCLUDES PIPE SIZES, PIPE MATERIAL, RELOCATED
 APPLIANCES AND THE ADDITION OF ANY APPLIANCES.
  
 2. NOTE: PLEASE RESUBMIT SHEET P1 AND INDICATE ON THE
 FLOOR PLAN THE RELOCATION AND ADDITION OF GAS
 APPLIANCES AND PLEASE MAKE SURE THAT PLAN KEY NOTE #4
 CORRELATES WITH SHEET P2.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-12-29 Cont ID  
Sent By mperson Date 2006-12-29 Time 08:39 Rev Time 0.33
Received By mperson Date 2006-12-29 Time 08:39 Sent To B
Notes
2006-12-29 08:45:11****************PROVISO****************
 PER FBC-2004 FUEL GAS, TABLES 402.4(2) AND 402.4(14)
 THE LONGEST LENGTH METER LOCATION FROM MOST REMOTE
 OUTLET IN THE BUILDING IS 100'. ANYTHING LONGER THAN
 THAT DISTANCE A REVISION WILL BE REQUIRED.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-11-02 Cont ID  
Sent By mperson Date 2006-11-02 Time 10:09 Rev Time 0.33
Received By mperson Date 2006-11-02 Time 10:09 Sent To B
Notes
2006-11-02 10:16:09UNSAT
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW ON THE RESUBMITTAL TO MEET CODE COMPLIANCE:
  
 1. NOTE THE SUBMITTED PLANS REFERENCE FBC-2001 FUEL
 GAS, TABLE 402(2), THIS IS WRONG THEY SHOULD REFERENCE
 FBC-2004 FUEL GAS TABLE 402.4 (2).
  
 2. THEGAS PIPING INDICATED ON SHEET P1 FLOOR PLAN AND
 P2 GAS RISER MATERIAL IS INDICATED AS BEING 3/4"
 SCHEDULE 40 BLACK STEEL BEING INSTALLED IN A SLEEVE
 WITH THREE (3) 90 DEGREE TURNS.IT IS RECOMMENDED THAT
 THE GAS PIPE MATERIAL IN THE SLEEVE BE CHANGED TO 3/4"
 CSST {FBC-2004 FUEL GAS TABLE 404.4(14)} AND THAT THE
 SLEEVE BE INSTALLED WITH TWO (2) 90 DEGREE TURNS.
 PLEASE REFERENCE SHEETS P1 AND P2 INDICATING THESE
 CHANGES.
  
 3. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 4. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2007-07-26 Cont ID  
Sent By choops Date 2007-07-26 Time 17:40 Rev Time 0.00
Received By choops Date 2007-07-26 Time 17:40 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2007-07-05 Cont ID  
Sent By choops Date 2007-07-05 Time 13:30 Rev Time 0.00
Received By choops Date 2007-07-05 Time 13:30 Sent To Z
Notes
2007-07-05 13:31:38REVISION ***FAILED***
  
  
 1)NO SITE PLAN OR ELEVATION PROVIDED.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2006-10-13 Cont ID  
Sent By swurafti Date 2006-10-13 Time 16:27 Rev Time 0.00
Received By swurafti Date 2006-10-13 Time 16:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2008-01-25 Cont ID  
Sent By shill Date 2008-01-25 Time 16:33 Rev Time 0.00
Received By shill Date 2008-01-25 Time 16:33 Sent To P
Notes
2008-01-25 16:33:57TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2007-11-26 Cont ID  
Sent By adarroug Date 2007-11-26 Time 15:58 Rev Time 0.00
Received By adarroug Date 2007-11-26 Time 15:58 Sent To P
Notes
2007-11-26 15:58:26TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2007-10-12 Cont ID  
Sent By shill Date 2007-10-12 Time 16:03 Rev Time 0.00
Received By shill Date 2007-10-12 Time 16:03 Sent To Z
Notes
2007-10-12 16:03:20TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-07-26 Cont ID  
Sent By adarroug Date 2007-07-26 Time 09:36 Rev Time 0.00
Received By adarroug Date 2007-07-26 Time 09:36 Sent To E
Notes
2007-07-26 09:36:26TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-07-26 Cont ID  
Sent By adarroug Date 2007-07-26 Time 09:32 Rev Time 0.00
Received By adarroug Date 2007-07-26 Time 09:32 Sent To Z
Notes
2007-07-26 09:32:32TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-07-11 Cont ID  
Sent By adarroug Date 2007-07-11 Time 13:50 Rev Time 0.00
Received By adarroug Date 2007-07-11 Time 13:50 Sent To E
Notes
2007-07-11 13:50:34TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-07-03 Cont ID  
Sent By adarroug Date 2007-07-03 Time 14:55 Rev Time 0.00
Received By adarroug Date 2007-07-03 Time 14:55 Sent To HIST
Notes
2007-07-03 14:55:32TO HISTORIC

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-07-03 Cont ID  
Sent By adarroug Date 2007-07-03 Time 11:20 Rev Time 0.00
Received By adarroug Date 2007-07-03 Time 11:20 Sent To E
Notes
2007-07-03 11:20:36TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-07-02 Cont ID  
Sent By adarroug Date 2007-07-02 Time 15:55 Rev Time 0.00
Received By adarroug Date 2007-07-02 Time 15:55 Sent To P
Notes
2007-07-02 15:55:42TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-02-22 Cont ID  
Sent By adarroug Date 2007-02-22 Time 17:39 Rev Time 0.00
Received By adarroug Date 2007-02-22 Time 17:39 Sent To E
Notes
2007-02-22 17:39:43TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-12-26 Cont ID  
Sent By adarroug Date 2006-12-26 Time 16:33 Rev Time 0.00
Received By adarroug Date 2006-12-26 Time 16:33 Sent To E
Notes
2007-02-01 16:43:27 
 ROUTED TO ROBBIE MCDOUGAL FOR BUILDING/STRUCTURAL
 REVIEW.
2006-12-26 16:33:45TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-16 Cont ID  
Sent By adarroug Date 2006-12-16 Time 15:46 Rev Time 0.00
Received By adarroug Date 2006-12-16 Time 15:46 Sent To Z
Notes
2006-12-16 15:47:02TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-31 Cont ID  
Sent By adarroug Date 2006-10-31 Time 11:13 Rev Time 0.00
Received By adarroug Date 2006-10-31 Time 11:13 Sent To E
Notes
2006-10-31 11:13:40TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-06 Cont ID  
Sent By alange Date 2006-11-06 Time 08:20 Rev Time 0.00
Received By alange Date 2006-10-16 Time 09:49 Sent To  
Notes
2006-10-16 09:52:15TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2007-02-27 Cont ID  
Sent By tgordon Date 2007-02-26 Time 08:21 Rev Time 0.30
Received By tgordon Date 2007-02-27 Time 14:57 Sent To B
Notes
2007-02-26 08:34:17NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME. A/C CONTRACTOR WILL SUBMIT MECH. PLANS WHEN
 SUBMITTING APP.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-02-26 Cont ID  
Sent By tgordon Date 2006-11-01 Time 08:23 Rev Time 0.30
Received By tgordon Date 2006-11-01 Time 08:23 Sent To P
Notes
2006-11-01 08:32:51*** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC
 13-101.2.2.
  
 2) PLEASE SUBMIT MANUAL J CALCULATIONS FOR WHOLE HOUSE,
 PER 2004 FBC/R M1401.3.
  
 3)NO MECHANICAL PLANS SUBMITTED, AND NO MECHANICAL
 PERMIT NUMBER APPLIED FOR AT THIS TIME.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-01-30 Cont ID  
Sent By mperson Date 2008-01-30 Time 10:02 Rev Time 0.00
Received By mperson Date 2008-01-30 Time 10:02 Sent To G
Notes
2008-01-30 10:03:56REVISION: "OK" SHEETS P1 AND P2.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-12-06 Cont ID  
Sent By mperson Date 2007-12-06 Time 07:37 Rev Time 0.00
Received By mperson Date 2007-12-06 Time 07:36 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-10-29 Cont ID  
Sent By mperson Date 2007-10-29 Time 15:18 Rev Time 0.00
Received By mperson Date 2007-10-29 Time 15:18 Sent To G
Notes
2007-10-29 15:33:58REVISION DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE ON THE
 REVISED PLANS:
  
 1. SHEET P1 SANITARY FLOOR PLAN DOES NOT REFLECT THE
 SANITARY ISOMETRIC ON SHEET P2: THE TRAP FOR THE MOP
 SINK IS MISSING. PER *701.1, SCOPE.
  
 2. SHEET P2 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN ON SHEET P1: THE WYE FITTING IS
 NOT INDICATED FOR THE WASHING MACHINE. PER *701.1,
 SCOPE.
  
 3. SHEET P2 SANITARY ISOMETRIC RISER DIAGRAM: THE
 FOLLOWING NEEDS TO BE INDICATED FOR THE WASHING
 MACHINE.
  
 (A) PER *708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 **NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE THREE
 INCH (3").
  
 (B) PER *708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 **NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE
 LOCATED AT FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.).
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-12-29 Cont ID  
Sent By tgordon Date 2007-02-26 Time 08:06 Rev Time 0.45
Received By mperson Date 2006-12-29 Time 08:34 Sent To G
Notes
2006-12-29 08:39:12****************PROVISO****************
 PER FBC-2004 PLUMBING, SEC. 708.9 ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS. CLEANOUT FOR WASHING MACHINE
 TO BE LOCATED FOUR FEET ABOVE FINNISH FLOOR.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-11-02 Cont ID  
Sent By tgordon Date 2006-12-12 Time 09:43 Rev Time 1.25
Received By mperson Date 2006-11-02 Time 09:33 Sent To G
Notes
2006-11-02 10:08:52UNSAT
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW ON THE RESUBMITTAL TO MEET CODE
 COMPLIANCE:
  
 1. NOTE: THE SUBMITTED PLANS REFERENCE FBC-2001
 PLUMBING, THIS IS WRONG THEY SHOULD REFERENCE FBC-2004
 PLUMBING.
  
 2.THE SANITARY RISER DIAGRAM ON SHEET P2 DOES NOT
 REFLECT THE FLOOR PLAN ON SHEETS A-1 AND P1. NOT ALL OF
 THE PLUMBING FIXTURES ARE INDICATED ON THE SANTARY
 RISER DIAGRAM. PLEASE REFERNCE SHEET A-1 IN THE
 GARAGE-6 WHERE THE 24" MOP SINK IS INDICATED.
  
 3. 1. PER FBC-2004, PLUMBING, SECTION 909.1
 WET VENT PERMITTED: ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT. (NOTE: PLEASE
 REFERENCE THE CORRECTED SHEETS P1 AND P2 WHERE THE MOP
 SINK ON SHEET A-1 IS ADDED TO SHEET P1 FLOOR PLAN AND
 SHEET P2 SANITARY RISER FOR THE RESUBMITTAL.)
  
 4. THE BRANCH DRAIN PIPING TO THE WASHING MACHINE IS
 SIZED WRONG PER FBC-2004 PLUMBING SEC. 406.3.
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER. (NOTE: PLEASE REFERENCE THE CORRECTED SHEETS
 P1 AND P2 FOR THE RESUBMITTAL.)
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  

Review Stop Z ZONING
Rev No 5 Status P Date 2007-10-16 Cont ID  
Sent By choops Date 2007-10-16 Time 10:30 Rev Time 0.00
Received By choops Date 2007-10-16 Time 10:30 Sent To P
Notes
2007-10-16 10:31:28***APPROVED - REVISION***
  
 SENT TO "P" - MP

Review Stop Z ZONING
Rev No 4 Status F Date 2007-07-26 Cont ID  
Sent By choops Date 2007-07-26 Time 17:52 Rev Time 0.00
Received By choops Date 2007-07-26 Time 17:52 Sent To B
Notes
2007-07-26 17:55:31***FAILED - REVISION***
  
  
 1)SETBACK DIMENSIONS SHALL BE INDICATED FROM ALL
 PROPOSED WORK TO THE PROPERTY LINES.
  
 2)SHOW ANY PROPOSED MECHANICAL / A/C EQUIPMENT WITH
 SETBACK DIMENSIONS TO THE PROPERTY LINES.
  
 3)PROVIDE OVERHANG DIMENSIONS FROM WALL TO THE
 OUTERMOST POINT OF THE ROOF'S EDGE.
  
 4)PROVIDE ELEVATION PLANS OF ALL PROPOSED WORK
 (PREVIOUS COMMENT).
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 3 Status F Date 2007-07-05 Cont ID  
Sent By choops Date 2007-07-05 Time 13:33 Rev Time 0.00
Received By choops Date 2007-07-05 Time 13:33 Sent To B
Notes
2007-07-05 13:36:51***FAILED - REVISION***
  
  
 1)PLEASE PROVIDE TWO (2) COPIES OF EACH:CURRENT
 SURVEY SHOWING SCOPE OF WORK WITH ALL DIMENSIONS AND
 SETBACK DIMENSIONS TO PROPERTY LINES.SITE PLANS OF
 PROPOSED WORK.ELEVATIONS OF PROPOSED WORK.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 2 Status P Date 2006-12-22 Cont ID  
Sent By mmclean Date 2006-12-22 Time 11:57 Rev Time 0.00
Received By mmclean Date 2006-12-22 Time 10:41 Sent To I
Notes
2006-12-22 11:06:03NOTE: MUST HAVE HISTORIC SIGN-OFF FOR ANY REVISION.
  
 NOTE: SHALL PULL A SEPARATE PERMIT FOR NEW FENCE/GATE
 WITH EASEMENT APPROVAL FROM THE CITY OF WEST PALM BEACH
 UTILITY DEPT.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-10-28 Cont ID  
Sent By mmclean Date 2006-10-28 Time 07:18 Rev Time 0.00
Received By mmclean Date 2006-10-28 Time 10:41 Sent To I
Notes
2006-10-28 07:31:52DENIED,
 1.PLEASE PROVIDE A COPY OF CURRENT SURVEY OF THE
 PROPERTY.
  
  
 NOTE: MUST PULL A SEPARATE PERMIT FOR FENCE/GATE WITH
 UTILITY EASEMENT APPROVAL FROM CITY OF WEST PALM BEACH
 UTILITY DEPT.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720