2007-03-24 08:17:04 | ****** UNSAT 2ND REVIEW****** |
| |
| ** PLEASE KNOW THAT AS SOME INFORMATION HAS NOT YET |
| BEEN SUBMITTED FOR REVIEW YET THERE MAY VERY WELL BE |
| NEW COMMENTS ON THE NEXT REVIEW. |
| |
| ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1 |
| IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE |
| ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY |
| THE CITY OF WEST PALM BEACH. |
| |
| |
| 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| ARE SUBMITTED BEFORE DECEMBER 8TH, 2006 PLACES PROJECTS |
| UNDER THE OLD CODES ADOPTED BY THE STATE. |
| PLEASE SEE THAT THIS SHALL INCLUDE THE 2004 FBC FOR ALL |
| TRADES AND THE 2002 NFPA-70. |
| PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| AFFECT DESIGNS FOR ALL TRADES. |
| PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| REVIEWER AT A MINIMUM. |
| 2004 FBC |
| 2002 NFPA-70 |
| 2002 NFPA-72 |
| 2003 NFPA-101 |
| ** SOME OF THESE CODES MAY BE PRESENT ON PLANS HOWEVER |
| PLEASE VERIFY THE CODES AND SEE COMMENTS FROM OTHER |
| TRADES WHICH MAY AFFECT THIS NOTE. |
| |
| ** PLEASE SEE SOME AREAS OF PLANS WHICH REFLECT THE |
| 2001 FBC AND THE 2005 NFPA-70. |
| |
| 2) NOTE:PLEASE SUBMIT A COMPLETE FIXTURE LEGEND OF |
| ALL FIXTURES AND CORRELATE WITH PLANS. |
| PLEASE ALSO SEE THE 2004 FBC CHAPTER 13 FOR THE POWER |
| ALLOWANCES PERMITTED AND PERFORMANCE CALCULATIONS PER |
| 13-415.2. |
| PLEASE PROVIDE WORST CASE VOLTAGE DROP PER |
| 13-413.1ABC.1 FOR BRANCH CIRCUITS INSTALLED AS NEW. |
| PLEASE SEE ALL OF CHAPTER 13 FOR LIGHTING AND CONTROLS |
| WHERE APPLICABLE. THE SECTION OF 13-415.1.ABC.1.1 DOES |
| NOT SEEM TO APPLY AS THE SQ FT IS LESS THAN 5K SQ FT. |
| PLEASE KNOW HOWEVER ENERGY CALCULATIONS PER 13-415.AB.1 |
| ARE REQUIRED TO VERIFY FOR NEW ELECTRICAL AND |
| MECHANICAL BEING INSTALLED. |
| FBC 106.1.2 |
| |
| 3) NOTE: PLEASE INCLUDE NEW LIGHTING FOR STAIR AREAS TO |
| MEET NFPA-101 7.8 AND 7.9. |
| PLEASE INCLUDE ANY EGRESS STAIR AREAS TO THE PUBLIC |
| RIGHT OF WAY AND EGRESS PATHS. |
| PLEASE KNOW THE STAIR AREAS ARE REQUIRED TO HAVE A |
| MINIMUM OF 10FT CANDLES UNDER NORMAL AND ARE PERMITTED |
| TO GO TO 1FT CANDLE UNDER EMERGENCY CONDITIONS. PLEASE |
| SUBMIT PHOTO-METRICS FOR REVIEW. |
| NFPA-101 7.8.1.3, 7.9.2.2. |
| FBC 106.1.2 |
| |
| 4) NOTE: PLEASE LABEL ALL PANELS AND SERVICE EQUIPMENT |
| ON PLANS. |
| THERE ARE SEVERAL NOTES ON PLANS WHICH MENTIONS |
| EXISTING, HOWEVER THIS WORK WAS NOT DONE UNDER THE |
| PRIOR PERMIT AS THE ELECTRICAL PERMIT FOR THIS SCOPE |
| WAS NEVER ISSUED AND NO RECORD OF ANY INSPECTIONS WAS |
| DONE. |
| PLEASE INDICATE THIS ELECTRICAL WORK AS NEW UNLESS THIS |
| WAS DONE BEFORE 02.? |
| PLEASE SHOW AND LABEL ALL EQUIPMENT. PLEASE SEE SOME |
| PANELS ARE SHOWN IN AREAS WHICH ARE CONSIDERED CLOSETS/ |
| STORAGE ROOM AREAS. |
| PLEASE SEE 110.26, 408.7, 240.24 ETC |
| PLEASE SEE SHOW WHERE THE *WIRE-WAY* IS LOCATED.? |
| PLEASE SEE THE AREA OF STAIRS OUTSIDE APPEAR TO BE |
| LOCATED IN FRONT OF THE METER AS NOTED ON PLANS. PLEASE |
| COMPLETE THE RISER AS THE RISER DOES NOT INCLUDE THE |
| METER. |
| PLEASE SHOW THE LOCATION OF THE SERVICE MAIN. PLEASE |
| SEE THERE IS A NOTE ON PLANS *NOTE A* WHICH MENTIONS TO |
| SEE SHEET C-1 FOR THESE ITEMS YET THERE WAS NO SHEETS |
| C-1 IN SET? |
| PLEASE INCLUDE ALL TAPPED CONDUCTORS TO EQUIPMENT. |
| PLEASE SHOW ALL EQUIPMENT FOR A/C UNITS. (NOTED AS |
| EXISTING) HOWEVER AS PLANS SEEM TO INDICATE THE LEVEL |
| OF REWIRED AND ALTERATION WHICH IS INCLUDING COMPLETE |
| REWIRE FOR MOST, PLEASE INCLUDE WHAT IS EXISTING OF |
| THIS SERVICE WHICH MEETS THE CURRENT CODE. |
| 240.4, 310.16, 110.26, 240.21, 440.11,ETC. |
| FBC 106.3.5.1.2 |
| |
| 5) NOTE: PLEASE VERIFY THE LOAD CALCULATIONS AS SHOWN |
| AS THE NEW LOADS BEING ADDED ARE NOT SHOWN PER NEC FOR |
| THE LOADS REQUIRED. CONTINUOUS LOADS AT 125%. PLEASE |
| SEE LOADS ARE ONLY SHOWN AS CONNECTED LOADS ON PANEL |
| SCHEDULE. |
| PLEASE CLARIFY HOW LOADS ARE DERIVED. |
| PLEASE SEE 220.10,220.11,220.3,220.13, ETC. |
| 215.3, 230.42. |
| PLEASE SEE AS THE SERVICE SHOWN HAS LOAD AT 196+ AMPS, |
| THERE IS NOT ROOM FOR FUTURE |
| WIRING/EXPANSION/LOAD/PLANNING. |
| PLEASE KNOW THAT AS THE LOAD IS BEING SHOWN SO CLOSE TO |
| THE MAXIMUM LOAD ON SERVICE THE SERVICE WILL BE |
| REQUIRED TO BE INCREASED TO A MINIMUM OF 225AMPS. |
| PLEASE KNOW ONCE ALL LOADS ARE SHOWN AND DECLARED THE |
| FINAL REVIEW OF THIS WILL BE DONE AT THAT TIME. 90.8, |
| 90.4. |
| |
| 6) NOTE: PLEASE INCLUDE ALL CIRCUITING ON PLANS AND |
| CORRELATE WITH THE SUBMITTED PANEL SCHEDULE. PLEASE SEE |
| THERE ARE SEVERAL ITEMS ON PLANS WHICH DO NOT INDICATE |
| ANY CIRCUITING. PLEASE EXPLAIN THE LOWER CASE *A*,*C* |
| WHICH IS BEING SHOWN BEHIND SOME OF THE CIRCUITS? |
| PLEASE SEE 408.4, 310.16, AND 240.4 AS MANY ITEMS NEED |
| TO BE VERIFIED. |
| PLEASE SEE 700.12E FOR CIRCUITING OF EMERGENCY AND EXIT |
| LIGHTS. |
| FBC 106.1.2 |
| |
| 7) NOTE: PLEASE ALSO INCLUDE HOW AND WHERE LIGHTING FOR |
| SANCTUARY IS AND HOW MANY OF THE OTHER LIGHTS ARE GOING |
| TO BE CONTROLLED. PLEASE SEE SOME AREAS WHICH DO NOT |
| SHOW LIGHTS OR CONTROLS? |
| PLEASE CLARIFY THE NUMERICAL DESIGNATIONS AND LETTERS |
| AT SWITCH LOCATIONS? |
| FBC 106.3.5.1.2 |
| |
| 8) NOTE: PLEASE BE SURE ALL BRANCH CIRCUIT CONDUCTORS |
| ARE SHOWN AND MEET 310.16, 240.4 |
| FBC 106.3.5.1.2. |
| |
| 9) NOTE: PLEASE SEE THE NOTICE OF COMMENCEMENT HAS |
| EXPIRED PER FS713.13(2). WILL ONLY NEED TO BE SUBMITTED |
| ONCE PERMIT IS ISSUED. |
| |
| ** AS ELECTRICAL SCOPE OF WORK WAS NEVER COMPLETED, |
| PERMITTED, OR INSPECTED UNDER PREVIOUS PLANS, CAN NOT |
| REFERENCE BACK TO WORK NOT DONE. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
2007-03-24 07:02:19 | REVIEW IN PROGRESS |