Plan Review Details - Permit 06100522
Plan Review Stops For Permit 06100522
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-04-18 Cont ID  
Sent By shill Date 2007-04-18 Time 10:13 Rev Time 0.00
Received By shill Date 2007-04-11 Time 17:40 Sent To  
Notes
2007-04-18 10:34:48****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)SEE ELECTRIC COMMENTS REGARDING "EXISTING"
 CONDITIONS.THE PERMIT 03052313 HAS A VOID STATUS DUE
 TO INACTIVITY.THIS PERMIT HAD ONLY ONE INSPECTION.
 THIS ISSUE MUST BE ADDRESSED PRIOR TO ISSUANCE OF THIS
 PERMIT.EITHER INCORPORATE THE WORK WHICH WAS
 COMPLETED INTO THIS PERMIT, OR APPLY FOR A SEPARATE
 PERMIT INCLUDING WORK THAT WAS COMPLETED BUT NOT
 FINALED.
  
 2.)GOVERNING CODE IS FBC2004.SEVERAL SHEETS REFER
 TO FBC2001.
  
 3.)SEE PREVIOUS LIST, ITEM 5, PEWS BLOCK THE EXIT.
 THE RESPONSE LETTER STATES THE PEWS ARE BEING REMOVED,
 BUT THEY STILL APPEAR ON S1.1.
  
 4.)ACCESSIBILITY HAS NOT BEEN ADDRESSED IN THIS
 REVIEW AS DESIGNER HAS STATED THAT THIS BUILDING IS
 EXEMPT (CHURCH).NOTE THAT IF THE USE CHANGES, AND THE
 BUILDING IS OPEN TO THE PUBLIC, ALL ACCESSIBILITY
 REQUIREMENTS OF FBC11 APPLY.
  
 5.)SEE DEFINITION OF AREA, BUILDING, FBC502.1.IT
 APPEARS THAT THE NORTH CHAPEL, SOUTH CHAPEL, AND
 KITCHEN ARE ONE BUILDING AS THEY ARE CONNECTED BY A
 COVERED PATIO.REVISE THE CODE ANALYSIS AS NECESSARY.
 ALSO NOTE THAT LEVEL 3 ALTERATION WAS DECLARED; THIS
 MAY CHANGE IF THE DECLARED BUILDING AREA INCREASES.
  
 6.)S1.1, SEE FBC TABLE 1607.1.1(4), LIVE LOAD
 REQUIRED FOR THE FLOOR.50 IS SPECIFIED, 100 REQUIRED
 FOR MOVEABLE SEATS AND 125 REQUIRED FOR THE STAGE.
  
 7.)A1.1 WALL TYPE 2 STATES "UNDERSIDE OF RATED
 FLOOR/CEILING ASSEMBLY".SHOW ALL REQUIRED FIRE
 RESISTANCE.
  
 8.)SHOW THE RAMP RUN AND SLOPE.IT APPEARS TO HAVE A
 LANDING, BUT AS THE SLOPE IS NOT SHOWN IT IS NOT CLEAR
 THAT THIS IS A LANDING.ALSO SHOW WIDTH, EDGE
 PROTECTION. FBC1010.SHOW MANEUVERING CLEARANCE AT THE
 DOOR, FBC1010.6, SEE ALSO FBC11-4.8.4.
  
 9.)WHEN RESUBMITTING, PLEASE SUBMIT OLD SHEETS.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-21 Cont ID  
Sent By shill Date 2006-11-21 Time 16:48 Rev Time 0.00
Received By shill Date 2006-11-21 Time 16:48 Sent To  
Notes
2006-11-21 16:59:41****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)PLEASE REMOVE THE REFERENCE TO THE SECOND FLOOR
 FROM THE PERMIT APPLICATION.THE APPLICATION SHOULD
 REPRESENT WORK TO BE DONE, NO SECOND FLOOR WORK SHOWN.
  
 2.)GOVERNING CODE IS FBC2004.THERE IS A REFERENCE
 TO FBC2001, CVR, CODE ANALYSIS.THE REFERENCE TO TABLE
 500 SHOULD BE TABLE 503.
  
 3.)PLYWOOD SHEATHING NOTES ARE NOT COMPLIANT WITH FBC
 TABLE 2304.9.1, ITEM 31.THERE IS NO EXTERIOR WORK ON
 THE PLAN; IT IS NOT CLEAR AS TO THE PURPOSE OF THE
 NOTE.
  
 4.)FOR THE PLATFORM AREA, OCCUPANT LOAD HAS BEEN
 CALCULATED BASED ON UNCONCENTRATED SEATING, FBC TABLE
 1004.1.2.IT APPEARS THAT THE CORRECT NUMBER SHOULD BE
 5 NET, STANDING.
  
 5.)THE EXISTING PEWS BLOCK THE EXIT 102.
  
 6.)ALTERATIONS TO EXISTING BUILDINGS SHALL COMPLY
 WITH THE FOLLOWING; IF EXISTING ELEMENTS, SPACES, OR
 COMMON AREAS ARE ALTERED, THEN EACH SUCH ALTERED
 ELEMENT, SPACE, FEATURE, OR AREA SHALL COMPLY WITH THE
 APPLICABLE PROVISIONS OF SECTION 11-4.1.1 TO SECTION
 11-4.1.3, MINIMUM REQUIREMENTS FOR NEW CONSTRUCTION,
 FBC11-4.1.6.PLEASE PROVIDE INFORMATION IN REGARDS TO
 THE IMPROVEMENT AREA; WILL THIS AREA BE RENTED OUT AT
 ANY TIME?CODE COMPLIANCE (VERTICAL ACCESSIBILITY)
 CANNOT BE DETERMINED BASED ON THE INFORMATION PROVIDED.
 SEE THE ATTACHED MEMORANDUM AND FEEL FREE TO CONTACT ME
 TO DISCUSS.
  
 7.)SEE ABOVE COMMENT.IF ACCESSIBILITY IS REQUIRED,
 SHOW MANEUVERING CLEARANCE, PUSH SIDE, FOR DOOR 106 AND
 PULL SIDE, DOOR 114.
  
 8.)PROVIDE THE HEIGHT OF THE HANDRAIL AND GUARDRAIL,
 FBC1009.11.1, FBC1012.2.
  
 9.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-03-24 Cont ID  
Sent By dpalmer Date 2007-03-24 Time 08:18 Rev Time 0.00
Received By dpalmer Date 2007-03-23 Time 19:20 Sent To  
Notes
2007-03-24 08:17:04****** UNSAT 2ND REVIEW******
  
 ** PLEASE KNOW THAT AS SOME INFORMATION HAS NOT YET
 BEEN SUBMITTED FOR REVIEW YET THERE MAY VERY WELL BE
 NEW COMMENTS ON THE NEXT REVIEW.
  
 ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE
 ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
  
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED BEFORE DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE OLD CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE THE 2004 FBC FOR ALL
 TRADES AND THE 2002 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC
 2002 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 ** SOME OF THESE CODES MAY BE PRESENT ON PLANS HOWEVER
 PLEASE VERIFY THE CODES AND SEE COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT THIS NOTE.
  
 ** PLEASE SEE SOME AREAS OF PLANS WHICH REFLECT THE
 2001 FBC AND THE 2005 NFPA-70.
  
 2) NOTE:PLEASE SUBMIT A COMPLETE FIXTURE LEGEND OF
 ALL FIXTURES AND CORRELATE WITH PLANS.
 PLEASE ALSO SEE THE 2004 FBC CHAPTER 13 FOR THE POWER
 ALLOWANCES PERMITTED AND PERFORMANCE CALCULATIONS PER
 13-415.2.
 PLEASE PROVIDE WORST CASE VOLTAGE DROP PER
 13-413.1ABC.1 FOR BRANCH CIRCUITS INSTALLED AS NEW.
 PLEASE SEE ALL OF CHAPTER 13 FOR LIGHTING AND CONTROLS
 WHERE APPLICABLE. THE SECTION OF 13-415.1.ABC.1.1 DOES
 NOT SEEM TO APPLY AS THE SQ FT IS LESS THAN 5K SQ FT.
 PLEASE KNOW HOWEVER ENERGY CALCULATIONS PER 13-415.AB.1
 ARE REQUIRED TO VERIFY FOR NEW ELECTRICAL AND
 MECHANICAL BEING INSTALLED.
 FBC 106.1.2
  
 3) NOTE: PLEASE INCLUDE NEW LIGHTING FOR STAIR AREAS TO
 MEET NFPA-101 7.8 AND 7.9.
 PLEASE INCLUDE ANY EGRESS STAIR AREAS TO THE PUBLIC
 RIGHT OF WAY AND EGRESS PATHS.
 PLEASE KNOW THE STAIR AREAS ARE REQUIRED TO HAVE A
 MINIMUM OF 10FT CANDLES UNDER NORMAL AND ARE PERMITTED
 TO GO TO 1FT CANDLE UNDER EMERGENCY CONDITIONS. PLEASE
 SUBMIT PHOTO-METRICS FOR REVIEW.
 NFPA-101 7.8.1.3, 7.9.2.2.
 FBC 106.1.2
  
 4) NOTE: PLEASE LABEL ALL PANELS AND SERVICE EQUIPMENT
 ON PLANS.
 THERE ARE SEVERAL NOTES ON PLANS WHICH MENTIONS
 EXISTING, HOWEVER THIS WORK WAS NOT DONE UNDER THE
 PRIOR PERMIT AS THE ELECTRICAL PERMIT FOR THIS SCOPE
 WAS NEVER ISSUED AND NO RECORD OF ANY INSPECTIONS WAS
 DONE.
 PLEASE INDICATE THIS ELECTRICAL WORK AS NEW UNLESS THIS
 WAS DONE BEFORE 02.?
 PLEASE SHOW AND LABEL ALL EQUIPMENT. PLEASE SEE SOME
 PANELS ARE SHOWN IN AREAS WHICH ARE CONSIDERED CLOSETS/
 STORAGE ROOM AREAS.
 PLEASE SEE 110.26, 408.7, 240.24 ETC
 PLEASE SEE SHOW WHERE THE *WIRE-WAY* IS LOCATED.?
 PLEASE SEE THE AREA OF STAIRS OUTSIDE APPEAR TO BE
 LOCATED IN FRONT OF THE METER AS NOTED ON PLANS. PLEASE
 COMPLETE THE RISER AS THE RISER DOES NOT INCLUDE THE
 METER.
 PLEASE SHOW THE LOCATION OF THE SERVICE MAIN. PLEASE
 SEE THERE IS A NOTE ON PLANS *NOTE A* WHICH MENTIONS TO
 SEE SHEET C-1 FOR THESE ITEMS YET THERE WAS NO SHEETS
 C-1 IN SET?
 PLEASE INCLUDE ALL TAPPED CONDUCTORS TO EQUIPMENT.
 PLEASE SHOW ALL EQUIPMENT FOR A/C UNITS. (NOTED AS
 EXISTING) HOWEVER AS PLANS SEEM TO INDICATE THE LEVEL
 OF REWIRED AND ALTERATION WHICH IS INCLUDING COMPLETE
 REWIRE FOR MOST, PLEASE INCLUDE WHAT IS EXISTING OF
 THIS SERVICE WHICH MEETS THE CURRENT CODE.
 240.4, 310.16, 110.26, 240.21, 440.11,ETC.
 FBC 106.3.5.1.2
  
 5) NOTE: PLEASE VERIFY THE LOAD CALCULATIONS AS SHOWN
 AS THE NEW LOADS BEING ADDED ARE NOT SHOWN PER NEC FOR
 THE LOADS REQUIRED. CONTINUOUS LOADS AT 125%. PLEASE
 SEE LOADS ARE ONLY SHOWN AS CONNECTED LOADS ON PANEL
 SCHEDULE.
 PLEASE CLARIFY HOW LOADS ARE DERIVED.
 PLEASE SEE 220.10,220.11,220.3,220.13, ETC.
 215.3, 230.42.
 PLEASE SEE AS THE SERVICE SHOWN HAS LOAD AT 196+ AMPS,
 THERE IS NOT ROOM FOR FUTURE
 WIRING/EXPANSION/LOAD/PLANNING.
 PLEASE KNOW THAT AS THE LOAD IS BEING SHOWN SO CLOSE TO
 THE MAXIMUM LOAD ON SERVICE THE SERVICE WILL BE
 REQUIRED TO BE INCREASED TO A MINIMUM OF 225AMPS.
 PLEASE KNOW ONCE ALL LOADS ARE SHOWN AND DECLARED THE
 FINAL REVIEW OF THIS WILL BE DONE AT THAT TIME. 90.8,
 90.4.
  
 6) NOTE: PLEASE INCLUDE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL SCHEDULE. PLEASE SEE
 THERE ARE SEVERAL ITEMS ON PLANS WHICH DO NOT INDICATE
 ANY CIRCUITING. PLEASE EXPLAIN THE LOWER CASE *A*,*C*
 WHICH IS BEING SHOWN BEHIND SOME OF THE CIRCUITS?
 PLEASE SEE 408.4, 310.16, AND 240.4 AS MANY ITEMS NEED
 TO BE VERIFIED.
 PLEASE SEE 700.12E FOR CIRCUITING OF EMERGENCY AND EXIT
 LIGHTS.
 FBC 106.1.2
  
 7) NOTE: PLEASE ALSO INCLUDE HOW AND WHERE LIGHTING FOR
 SANCTUARY IS AND HOW MANY OF THE OTHER LIGHTS ARE GOING
 TO BE CONTROLLED. PLEASE SEE SOME AREAS WHICH DO NOT
 SHOW LIGHTS OR CONTROLS?
 PLEASE CLARIFY THE NUMERICAL DESIGNATIONS AND LETTERS
 AT SWITCH LOCATIONS?
 FBC 106.3.5.1.2
  
 8) NOTE: PLEASE BE SURE ALL BRANCH CIRCUIT CONDUCTORS
 ARE SHOWN AND MEET 310.16, 240.4
 FBC 106.3.5.1.2.
  
 9) NOTE: PLEASE SEE THE NOTICE OF COMMENCEMENT HAS
 EXPIRED PER FS713.13(2). WILL ONLY NEED TO BE SUBMITTED
 ONCE PERMIT IS ISSUED.
  
 ** AS ELECTRICAL SCOPE OF WORK WAS NEVER COMPLETED,
 PERMITTED, OR INSPECTED UNDER PREVIOUS PLANS, CAN NOT
 REFERENCE BACK TO WORK NOT DONE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-03-24 07:02:19REVIEW IN PROGRESS

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-27 Cont ID  
Sent By dpalmer Date 2006-10-27 Time 19:50 Rev Time 0.00
Received By dpalmer Date 2006-10-27 Time 19:42 Sent To  
Notes
2006-10-27 19:50:33*** UNSAT ****
  
 1) NOTE: PLEASE SEE SCOPE OF WORK IS UNCLEAR AT THIS
 POINT IN TIME. PLEASE SEE PERMIT APPLICATION HAS BEEN
 SUBMITTED,, " "NOT" TO BUILD SECOND FLOOR"? . IF THIS
 IS PART OF A PREVIOUS PERMIT, PLEASE SUBMIT A REVISION
 WHICH MAY REDUCE A CERTAIN SCOPE OF WORK ORIGINALLY
 APPLIED FOR. IF WORK IS TO DONE FOR A REMODEL AS PLANS
 SEEM TO INDICATE BUT NOT CLEAR, THEN PLEASE ADJUST
 PERMIT APPLICATION. NOT CLEAR WHAT TO REVIEW FOR.???
 FBC ADMIN SECTION 106.1.2
  
  
 PLEASE SUBMIT FOR REVIEW EITHER BY ADJUSTING SCOPE ON
 APPLICATION OR SUBMIT PLANS AS A REVSION UNDER AN
 EXISTING PERMIT.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-04-06 Cont ID  
Sent By mwennerg Date 2007-04-06 Time 14:23 Rev Time 0.00
Received By mwennerg Date 2007-04-06 Time 14:23 Sent To  
Notes
2007-04-06 14:43:57***DENIED***
  
 1) BASED ON OCCUPANT LOAD CALCULATIONS FOR SOUTH
 CHAPEL, PLEASE CLARIFY IF ALL AREAS INCLUDING THE NORTH
 CHAPEL UNDER ROOF ARE DEFINED AS (1) BUILDING.
  
 2) PLEASE ADD NOTE TO PLANS THAT OCCUPANT LOAD WILL
 REMAIN AS DOCUMENTED, THEREBY NOT INITIATING ANY
 REQUIREMENTS FOR FIRE ALARM AND FIRE SPRINKLER SYSTEMS,
 AS WELL AS INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILING.
  
 3) PLEASE SHOW REQUIRED LOCATION OF 2A-10B,C RATED FIRE
 EXTINGUISHERS THAT SHALL BE MOUNTED SO AS NOT TO EXCEED
 75' TRAVEL DISTANCE.
  
 4) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE
 SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 5) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-11-20 Cont ID  
Sent By mwennerg Date 2006-11-20 Time 11:08 Rev Time 0.00
Received By mwennerg Date 2006-11-20 Time 11:08 Sent To  
Notes
2006-11-20 11:12:37***DENIED***
  
 1) PLEASE NOTE THAT A COMPLETE FIRE PLAN REVIEW CAN'T
 BE PERFORMED AT THIS TIME. PLEASE SEE OTHER REVIEW
 COMMENTS REGARDING THE UNCLEAR SCOPE OF WORK.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 (561) 805-6722 OR 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-15 Cont ID  
Sent By adarroug Date 2007-03-15 Time 16:55 Rev Time 0.00
Received By adarroug Date 2007-03-15 Time 16:55 Sent To  
Notes
2007-03-19 14:12:36TO "COMM" BD#4
2007-03-15 16:56:10WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-02 Cont ID  
Sent By shill Date 2006-12-15 Time 09:05 Rev Time 0.00
Received By shill Date 2006-10-14 Time 17:35 Sent To  
Notes
2006-10-24 16:07:04TO "COMM" BD#42
2006-10-14 17:38:58WIATING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-04-05 Cont ID  
Sent By rregueir Date 2007-04-05 Time 17:28 Rev Time 0.00
Received By rregueir Date 2007-04-05 Time 16:58 Sent To  
Notes
2007-04-05 17:24:14-----------------DENIED---------------------
  
 1. HVAC NOTE 1: PLEASE REFERENCE FBC,M 2004, NOT 2001.
  
 2. HVAC NOTE 12: PLEASE SHOW ON PLAN THE LOCATION OF
 FIRE DAMPERS IN RATED FLOOR/CEILING ASSEMBLIES PER
 FBC,M 607.8
  
 3. PLAN INDICATES 15X10 DUCT UP TO 2ND FLOOR BUT SHEET
 CVR STATES THAT THE 2ND FLOOR HAS BEEN DELETED. PLEASE
 CLARIFY PER FBC,M 106.1.1.
  
 4. BATHROOM WITH 3 STALLS: PLAN SHOWS 150 CFM EXHAUST
 AND 175 CFM SUPPLY. ALL AIR SUPPLIED TO SUCH SPACES
 SHALL BE EXHAUSTED, INCLUDING ANY AIR IN EXCESS OF THAT
 REQUIRED BY TABLE 403.3 PER FBC,M 403.2.1.
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-30 Cont ID  
Sent By rregueir Date 2006-10-30 Time 19:14 Rev Time 0.00
Received By rregueir Date 2006-10-30 Time 19:06 Sent To  
Notes
2006-10-30 19:15:36UNABLE TO PERFORM REVIEW AT THIS TIME. PLEASE SEE
 ELECTRICAL PLAN REVIEW COMMENTS.
  
 RONALD J REGUEIRO
 561.805.6734
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-04-24 Cont ID  
Sent By pschmitz Date 2007-03-31 Time 10:17 Rev Time 0.00
Received By pschmitz Date 2007-03-31 Time 10:36 Sent To  
Notes
2007-03-31 11:45:35PROVISO SEE SHTS A1.2ANDM1.1

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-12-02 Cont ID  
Sent By pschmitz Date 2006-12-02 Time   Rev Time  
Received By pschmitz Date 2006-12-02 Time   Sent To  
Notes
2006-12-02 08:57:27PAUL SCHMITZ
  
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
  
 DENIED
  
 (1) SHT A1.1 AND A1.2
 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL (SEE ALSO SECTION 106.3.5).
  
 (2) SEC 401 WATER SUPPLY. WATER RISER DIAGRAM
 REQUIRED.
 THIS CHAPTER SHALL GOVERN THE MATERIALS, DESIGN AND
 INSTALLATION OF PLUMBING FIXTURES, FAUCETS AND FIXTURE
 FITTINGS IN ACCORDANCE WITH THE TYPE OF OCCUPANCY, AND
 SHALL PROVIDE FOR THE MINIMUM NUMBER OF FIXTURES FOR
 VARIOUS TYPES OF OCCUPANCIES.
  
  
 (3) TAB 403.1 SECTION
 MINIMUM PLUMBING FACILITIES PROVIDE PLUMBING FIXTURE
 SCHEDULE.
 403.1 MINIMUM NUMBER OF FIXTURES.
 PLUMBING FIXTURES SHALL BE PROVIDED FOR THE TYPE OF
 OCCUPANCY AND IN THE MINIMUM NUMBER SHOWN IN TABLE
 403.1. TYPES OF OCCUPANCIES NOT SHOWN IN TABLE 403.1
 SHALL BE CONSIDERED INDIVIDUALLY BY THE CODE OFFICIAL.
 THE NUMBER OF OCCUPANTS SHALL BE DETERMINED BY THE
 FLORIDA BUILDING CODE, BUILDING. OCCUPANCY
 CLASSIFICATION SHALL BE DETERMINED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING.
  
 403.1.1 POTTY PARITY.
 IN ASSEMBLY OCCUPANCIES, RESTROOMS WHICH ARE OPEN TO
 THE PUBLIC MUST HAVE A RATIO OF 3:2 WATER CLOSETS
 PROVIDED FOR WOMEN AS THE COMBINED TOTAL OF WATER
 CLOSETS AND URINALS PROVIDED FOR MEN, UNLESS THESE ARE
 TWO OR FEWER SUCH FIXTURES FOR MEN, IN ACCORDANCE WITH
 ?553.86, FLORIDA STATUTES.
 SHT A1.2 ELVATION DO NOT REFLECT THE FLOOR PLAN.
  
 (4) DRINKING FOUNTAIN AND SERVICE SINK REQUIRED. SHOW
 LOCATION OF FIXTURES AND LABEL AS SUCH.
  
 (5) SHT A1.2SEC 905.3 DRY VENTS PROBHIBITED, DWV
 RISER DIAGRAM.
  
 (6) SEE COMMENTS FROM OTHER PLAN REVIEWERS, AS IT MAY
 EFFECT PLUMBING PLAN REVIEW
  
 END OF COMMENTS. QUESTIONS 561-805-6692

Review Stop Z ZONING
Rev No 2 Status N Date 2007-03-22 Cont ID  
Sent By kdfreema Date 2007-03-22 Time 17:38 Rev Time 0.00
Received By kdfreema Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-11-03 Cont ID  
Sent By kdfreema Date 2006-11-03 Time 15:00 Rev Time 0.00
Received By kdfreema Date 2006-11-03 Time 15:00 Sent To  
Notes
2006-11-03 15:01:05PLEASE PROVIDE A SURVEY OF THE PROPERTY. ENSURE THAT
 THE SURVEY INCLUDES THE LOCATIONS OF ALL STRUCTURES ON
 THE PROPERTY AS WELL AS THE SETBACKS FROM THE PROPERTY
 LINES.
  
 PLEASE SHOW PROPERTY LINES ON THE SITE PLAN.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT (561)
 822-1435 WITH ANY QUESTIONS.