Plan Review Stops For Permit 06100482 |
Review Stop |
AD |
ADDRESSING |
Rev No |
3 |
Status |
N |
Date |
2006-12-13 |
|
|
Cont ID |
|
Sent By |
lursu |
Date |
2006-11-15 |
Time |
16:26 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2006-11-15 |
Time |
16:26 |
Sent To |
|
|
Notes |
2006-11-15 16:27:06 | PERMIT ATTACHED TO PCN = 74424302090003440 |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
2 |
Status |
F |
Date |
2006-11-01 |
|
|
Cont ID |
|
Sent By |
lursu |
Date |
2006-11-01 |
Time |
16:53 |
Rev Time |
0.00 |
Received By |
lursu |
Date |
2006-11-01 |
Time |
16:53 |
Sent To |
|
|
Notes |
2006-11-01 16:54:52 | IS THE WORK DONE TO BOTH UNITS :344 & 345, THEN UNITY | | OF TITLE IS REQUIRED PRIOR OF ISSUING THE PERMIT. |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
P |
Date |
2006-10-17 |
|
|
Cont ID |
|
Sent By |
lursu |
Date |
2006-10-17 |
Time |
11:20 |
Rev Time |
0.00 |
Received By |
lursu |
Date |
2006-10-14 |
Time |
18:16 |
Sent To |
PC |
|
Notes |
2006-10-17 11:20:56 | NEW RECORD , PCN = 74 42 43 02 09 000 3440 HAD BEEN | | IMPORTED | 2006-10-14 18:16:37 | COPY OF APPL SENT TO LILI |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2006-12-14 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2006-12-14 |
Time |
08:43 |
Rev Time |
1.66 |
Received By |
jwitmer |
Date |
2006-12-13 |
Time |
16:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-11-01 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2006-11-01 |
Time |
09:20 |
Rev Time |
0.00 |
Received By |
alange |
Date |
2006-11-01 |
Time |
09:14 |
Sent To |
|
|
Notes |
2006-11-01 09:22:21 | DENIED | | | | 1.CONSTRUCTION TYPE VI DOES NOT EXIST UNDER THE 2004 | | FBC PLEASE REVISE. | | | | 2.A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR | | A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO | | SECTIONS 303, 304 AND 305 OF THIS CODE.SHOW HOW PLANS | | WILL COMPLY WITH THE SECTION(S) SELECTED.2004 FBC | | EXISTING BUILDING 301.5 | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. SUBMIT ONE | | COPY OF OLD PAGES FOR REFERENCE . A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A | | DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET | | OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | ANTICIPATED COOPERATION. | | | | | | | | ART LANGE | | BUILDING PLANS EXAMINER | | CONSTRUCTION SERVICES DEPARTMENT | | 561-805-6672 | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2007-02-18 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-02-18 |
Time |
15:32 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-02-18 |
Time |
15:19 |
Sent To |
PC |
|
Notes |
2007-02-18 15:32:47 | REDLINED MAX TIMES FOR OC DEVICES PER 13-415.1.ABC.1.1, | | .1.2 | | 30MINS. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2006-12-08 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-12-08 |
Time |
14:52 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-12-08 |
Time |
14:14 |
Sent To |
I |
|
Notes |
2006-12-08 14:53:56 | REDLINED MAX TIME ON OC DEVICES 30MINS, ALSO REDLINED | | 700.12E FOR EM/EXT LTS. | 2006-12-08 14:15:12 | PLANS REMOVED FROM INCOMING AND WILL BE ROUTED BACK TO | | INCOMING ONCE ELECTRICAL REVIEW IS DONE. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2006-10-26 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-10-26 |
Time |
07:06 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-10-25 |
Time |
20:57 |
Sent To |
|
|
Notes |
2006-10-26 07:15:57 | ** UNSAT ** | | | | 1) NOTE: PLEASE INCLUDE THE FOLLOWING MIN CODES WHICH | | ARE RELEVANT TO DESIGNA DN SCOPE PF WORK ON PLANS. | | 2002 NFPA-70, 2002 NFPA-72, 2003 NFPA-101 | | | | 2) NOTE: PLEASEINDICATE THE "EQUIPMENT GROUNDING | | CONDUCTOR: FOR THE NEW FEEDERS BEING PULLED FROM | | EXISTING MAIN AT SERVICE. | | 250.110,250.24B , 250.122 ETC | | | | 3) NOTE: PLEASE SEE THAT THE ROOMS/OFFICE WHERE NEW | | ELECTRICAL LIGHTING CONTROLS/LAYOUTS WORK IS BEING WILL | | BE REQUIRED TO HAVE OCCUPANT SENSOR TYPE DEVICES TO BE | | INSTALLED. 13-415.1.ABC.1.2 2004 FBC. | | | | 4) NOTE: PLEASE VERIFY THE VOLTAGE COMING INTO SPACES ? | | IT WAS THOUGHT THE VOLTAGE WAS 277/480 COMING INTO | | SPACES ? PLEASE ONLY VERIFY. IF INDEED 120/208V THIS IS | | OK. | | | | 5) NOTE: PLEASE CORRELATE CIRCUITS ON PANEL SCHEDULE | | WIHT ROOMS /AREAS ON PLANS,. IE: OFFICE 102 RECEPT, LT | | RECEPTION AREA ,, ETC. | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | 2006-10-25 20:57:22 | IN ELEC FOR REVIEW |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2006-12-14 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-12-14 |
Time |
11:01 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-12-14 |
Time |
11:01 |
Sent To |
|
|
Notes |
2006-12-14 11:07:40 | *****APPROVED***** W/ ATTENTION | | | | | | | | | | AS STATED BEFORE IN THE PREVIOUS FIRE PLAN REVIEW, THE | | CORRECT ADDRESS SHOULD BE REFLECTED IN THE TITLE BLOCK | | OF EACH SUBMITTED PLAN SHEET.WITH THE EXCEPTION OF | | SHEET A1 AND A2, ALL OTHER SHEETS STILL HAVE THE | | INCORRECT NUMERICAL 5405 INSTEAD OF 5407. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2006-10-27 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-10-27 |
Time |
10:43 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-10-27 |
Time |
10:43 |
Sent To |
|
|
Notes |
2006-10-27 12:31:45 | *****DENIED***** | | | | | | | | 1.THE SUBMITTED PLANS INDICATE THAT THE SCOPE OF WORK | | WILL BE CONDUCTED AT 5405 NO. HAVERHILL ROAD.AS PER | | WEST PALM BEACH ADDRESSING DEPARTMENT, THE CORRECT | | ADDRESS FOR THIS BUILDING IS 5407.THE CORRECT ADDRESS | | SHOULD BE REFLECTED IN THE TITLE BLOCK. | | | | 2.PROVIDE EXISTING FLOOR PLAN TO DETERMINE IF BAY 44 | | & 45 WILL BE ONE UNIT SPACE.IF SO, WHAT WILL THE UNIT | | SPACE NUMBER BE? | | | | 3.NFPA 101 - 2003 EDITION, AND FLORIDA FIRE | | PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED. | | | | 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 5.FIRE EXTINGUISHERS ARE RATED 2A-10BC RATED, | | CERTIFIED AND TAGGED.(SEE SHEET A2) | | | | 6.ONLY TWO OF THE THREE FIRE EXTINGUISHERS COULD BE | | LOCATED. | | | | 7.INTERIOR FINISH FOR WALLS AND CEILING IN EXITS AND | | EXIT ACCESS CORRIDORS SHALL BE CLASS "A" OR CLASS"B". | | (SEE SHEET A2) | | | | 8.SHOW THE LOCATION OF THE FIRE SPRINKLERS.HOW WILL | | THEY BE AFFECTED BY THE SCOPE OF THE WORK? | | | | 9.IF THE SCOPE OF THE INTERIOR BUILDOUT REQUIRES | | MODIFICATION OF THE SPRINKLER SYSTEM, SEPARATE PERMIT | | AND PLANS ARE TO BE SUBMITTED. | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-02-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-02-16 |
Time |
08:52 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-02-16 |
Time |
08:52 |
Sent To |
E |
|
Notes |
2007-02-16 08:53:12 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2006-11-20 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-11-20 |
Time |
16:05 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-11-20 |
Time |
16:05 |
Sent To |
|
|
Notes |
2006-12-12 17:34:48 | TO "BOB"#9 | 2006-11-20 16:05:38 | WAITING FOR "BOB" |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-11-01 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2006-11-01 |
Time |
09:22 |
Rev Time |
0.00 |
Received By |
alange |
Date |
2006-10-14 |
Time |
18:17 |
Sent To |
|
|
Notes |
2006-10-23 10:14:48 | TO "BOB"#16 | 2006-10-14 18:16:56 | WAITING FOR "BOB" |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2006-10-24 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-10-24 |
Time |
14:03 |
Rev Time |
0.00 |
Received By |
tgordon |
Date |
2006-10-24 |
Time |
14:04 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2006-10-30 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2006-10-30 |
Time |
13:50 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2006-10-30 |
Time |
13:50 |
Sent To |
|
|
Notes |
|
|