2006-10-17 11:32:48 | ******UNSAT****** |
| REFERENCE: FBC-2004 FUEL GAS AND FBC-2004 CHAPTER 1 |
| |
| THE FOLLOWING INFORMATION IS REQUIRED FOR GAS PLAN |
| REVIEW: |
| |
| 1. PER FBC-2004 CHAPTER 1, SECTION 106.1 SUBMITTAL |
| DOCUMENTS: MINIMUM OF TWO (2) SETS OF DRAWINGS AND |
| OTHER DATA REQUIRED WITH EACH APPLICATION FOR PERMIT. |
| NOTE: ONLY ONE (1) SET WAS SUBMITTED. |
| |
| 2. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. NOTE: PLEASE INDICATE THE CORRESPONDING |
| LENGTHS OF THE NEW GENERATOR PIPING. |
| |
| 3. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. NOTE: PLEASE |
| INDICATE THE MATERIAL TYPE AND PIPE SIZES OF THE NEW |
| GENERATOR PIPING. |
| |
| 4. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). NOTE: PLEASE INDICATE THEEXISTING BTU LOAD |
| TO THE HOUSE |
| |
| 5. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| NAME, AND ALSO DATE DRAWING. PLEASE DO |
| THIS PRIOR TO RESUBMITTING. |
| |
| END OF COMMENTS: |
| |