Plan Review Details - Permit 06100172
Plan Review Stops For Permit 06100172
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-10-11 Cont ID  
Sent By jgomez Date 2006-10-10 Time 14:52 Rev Time 1.00
Received By jgomez Date 2006-10-10 Time 14:52 Sent To  
Notes
2006-10-10 15:00:04CALLED CONTRACTOR. LETTER SPECIFYING NAIL SPACING IS
 CONFUSING. NEED CLARIFICATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-05 Cont ID  
Sent By jgomez Date 2006-10-05 Time 16:17 Rev Time 0.50
Received By jgomez Date 2006-10-05 Time 16:16 Sent To  
Notes
2006-10-05 00:00:00BUILDING REVIEW CHECKLIST:
 1- PROVIDE RAS 117 CALCULATIONS FOR NAIL
 ENHANCING AT PERIMETER AND CORNER AREAS
 AS REQUIRED BY GENERAL LIMITATION #7.
 SEE PAGE 34 OF DADE COUNTY NOA
 SUBMITTED. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
 (NOTE: I RAN SOME CALCULATIONS IN THE IN
 HOUSE PROGRAMAND THE NAIL SPACING
 NEEDS TO BE CONSIDERED BECAUSE THERE IS
 A MIN. FASTENER SPACING THAT CAN BE
 USED. SEE RAS 117 STANDARD FOR
 LIMITATIONS ON FASTENER SPACING AND
 REVISE PROPOSED SPACING AS REQUIRED).
  
 2- SPECIFY HOW MUCH AREA IS GOING TO BE
 FLAT AND HOW MUCH IS PITCH TO VERIFY
 BUILDING PERMIT VALUATION. SEE ATTACHED
 COPY OF CITY POLICY FOR ROOFING PERMITS
 REQUIREMENTS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712