Plan Review Stops For Permit 06100140 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2006-10-10 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2006-10-10 |
Time |
12:48 |
Rev Time |
0.50 |
Received By |
jgomez |
Date |
2006-10-10 |
Time |
12:47 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-10-05 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2006-10-05 |
Time |
10:38 |
Rev Time |
0.50 |
Received By |
jgomez |
Date |
2006-10-05 |
Time |
10:38 |
Sent To |
|
|
Notes |
2006-10-05 00:00:00 | BUILDING REVIEW CHECKLIST: | | 1- PROPOSED ASSEMBLY TO BE INSTALLED | | PAGE19 OF 20 OF TAMKO DADE COUNTY NOA | | 02-0212.07 IS FOR TILE UNDERLAYMENT | | ONLY. THIS ASSEMBLY DOESN'T WORK FOR | | PROPOSED INSTALLATION. PROVIDE COPY OF | | PROPOSED ASSEMBLY THAT WORKS. | | | | 2- ACCORDING TO GENERAL LIMITATION #7 ON | | PAGE 20 OF 20 OF DADE COUNTY NOA, NEED | | TO PROVIDE CALCULATIONS FOR NAIL | | ENHANCING AT CORNER AND PERIMETER AREAS. | | THESE CALCULATIONS MUST BE DONE BY ANY | | OF THE PROFESSIONALS LISTED IN THE | | LIMITATION #7. PROVIDE SUCH | | CALCULATIONS. | | ***NOTE: KEEP IN MIND THAT IF SELECTED | | ASSEMBLY IS LIMITED BY GENERAL | | LIMITATION #9, THEN IT MAY NOT BE USED | | IN THIS AREA BECAUSE THERE IS NOT NAIL | | ENHANCING ALLOWED. SEE LIMITATION #9. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|
|
|