Plan Review Details - Permit 06100099
Plan Review Stops For Permit 06100099
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-10-23 Cont ID  
Sent By alange Date 2006-10-23 Time 08:26 Rev Time 0.00
Received By alange Date 2006-10-23 Time 08:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-01-29 Cont ID  
Sent By btrobaug Date 2007-01-29 Time 08:18 Rev Time 0.50
Received By btrobaug Date 2007-01-29 Time 07:55 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-12-01 Cont ID  
Sent By btrobaug Date 2006-12-01 Time 06:54 Rev Time 0.75
Received By btrobaug Date 2006-12-01 Time 06:36 Sent To P
Notes
2006-12-01 06:54:32 
 DENIED
  
 THERE ARE TWO DIFFERENT RISER DIAGRAMS SUBMITTED.
 CHOOSE THE ONE TO BE INSTALLED AND RESUBMIT TWO COPIES
 FOR REVIEW.
  
 A SIGN SHALL BE PLACED AT THE SERVICE-ENTRANCE
 EQUIPMENT THAT INDICATES THE TYPE AND LOCATION OF
 ON-SITE OPTIONAL STANDBY POWER SOURCES. PLEASE NOTE
 SAME ON RISER.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-19 Cont ID  
Sent By btrobaug Date 2006-10-19 Time 17:58 Rev Time 0.33
Received By btrobaug Date 2006-10-19 Time 17:38 Sent To M
Notes
2006-10-19 17:58:21 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PROVIDE MANUFACTURERS SPECIFICATIONS AND
 RECOMMENDATION, REGARDING CLEARANCES FOR THE
 GENERATOR.
  
 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
 DO THIS ON A SITE PLAN, NOT ON THE SURVEY, 106.1.3FBC.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR THE
 PLAN/DRAWINGS, SHALL PRINT AND SIGN THEIR NAME ON THE
 SHEETS THEY DRAW. PLEASE DO THIS PRIOR TO
 RESUBMITTING.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-12-01 Cont ID  
Sent By mperson Date 2006-12-01 Time 08:50 Rev Time 0.33
Received By mperson Date 2006-12-01 Time 08:50 Sent To M
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-10-20 Cont ID  
Sent By mperson Date 2006-10-20 Time 13:11 Rev Time 0.33
Received By mperson Date 2006-10-20 Time 13:11 Sent To B
Notes
2006-10-20 13:19:57UNSAT
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED FOR GAS PLAN
 REVIEW:
  
 1. PER ZONING COMMENTS PLEASE CORRELATE THE SURVEY
 PLAN.
  
 2. PROVIDE MANUFACTURERS SPECIFICATIONS AND
 RECOMMENDATIONS REGAURDING CLEARENCES FOR GENERATOR.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-01-23 Cont ID  
Sent By adarroug Date 2007-01-23 Time 13:27 Rev Time 0.00
Received By adarroug Date 2007-01-23 Time 13:27 Sent To E
Notes
2007-01-23 13:27:34TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-11-17 Cont ID  
Sent By adarroug Date 2006-11-17 Time 09:59 Rev Time 0.00
Received By adarroug Date 2006-11-17 Time 09:59 Sent To E
Notes
2006-11-17 09:59:25TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-15 Cont ID  
Sent By adarroug Date 2006-11-15 Time 13:12 Rev Time 0.00
Received By adarroug Date 2006-11-15 Time 13:12 Sent To Z
Notes
2006-11-15 13:12:50TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-17 Cont ID  
Sent By adarroug Date 2006-10-17 Time 16:50 Rev Time 0.00
Received By adarroug Date 2006-10-17 Time 16:50 Sent To E
Notes
2006-10-17 16:50:18TO "GEN-RES "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-23 Cont ID  
Sent By alange Date 2006-10-23 Time 08:27 Rev Time 0.00
Received By alange Date 2006-10-06 Time 09:13 Sent To  
Notes
2006-10-06 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-12-01 Cont ID  
Sent By tgordon Date 2006-12-01 Time 10:36 Rev Time 0.20
Received By tgordon Date 2006-12-01 Time 10:36 Sent To  
Notes
2006-12-01 10:38:35*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION
 ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE RESISTANCE
 RATING OF 1 HOUR OR (2) THE WEATHERPROOF ENCLOSURE IS
 CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 FOLLOW MANUFACTURER'S RECOMMENDED
 CLEARANCES AROUND EQUIPMENT FOR
 SERVICING,AND PROVIDE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-20 Cont ID  
Sent By tgordon Date 2006-10-20 Time 08:49 Rev Time 0.20
Received By tgordon Date 2006-10-20 Time 08:49 Sent To P
Notes
2006-10-20 08:51:21*** DENIED ***
 1) SEE ZONING REVIEW NOTES, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-11-16 Cont ID  
Sent By mmclean Date 2006-11-16 Time 15:09 Rev Time 0.00
Received By mmclean Date 2006-11-16 Time 15:09 Sent To I
Notes
2006-11-16 15:10:33NOTE: THE PROPOSED GENERATOR SHALL NOT BE CLOSER THAN
 6FT FROM SIDE PROPERTY LINE. THE PROPOSED GENERATOR
 MUST BE SCREEN WITH A LANDSCAPE BUFFER.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-10-11 Cont ID  
Sent By kdfreema Date 2006-10-11 Time 12:14 Rev Time 0.00
Received By kdfreema Date 2006-10-11 Time 12:09 Sent To  
Notes
2006-10-11 12:10:51PLEASE CLARIFY DISTANCE FROM PROPERTY LINE AS SHOWN ON
 SURVEY. IF THE HOUSE IS 14? FROM THE PROPERTY LINE HOW
 CAN THE GENERATOR BE 15? FROM THE PROPERTY LINE?
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 822-1435 WITH
 ANY QUESTIONS YOU MAY HAVE.