Plan Review Details - Permit 06100093
Plan Review Stops For Permit 06100093
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-10-16 Cont ID  
Sent By lursu Date 2006-10-16 Time 10:46 Rev Time 0.00
Received By lursu Date 2006-10-16 Time 10:46 Sent To PC
Notes
2006-10-16 10:46:36EXT #0009 I SOK TO USE FOR 3RD FLOOR
2006-10-13 07:56:56NEEDS FOR SUITE/FLOOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date 2007-02-12 Cont ID  
Sent By rmcdouga Date 2007-02-12 Time 08:21 Rev Time 0.00
Received By rmcdouga Date 2007-02-12 Time 08:21 Sent To  
Notes
2007-02-12 09:05:49DENIED BY BUILDING
  
 1) THE REVISED SHEETS SUBMITTED ARE FOR THE 2ND FLOOR
 (SUITE 200) OF 307 EVERNIA STREET. THE PERMIT NUMBER ON
 THE REVISION SUBMITTAL FORM (06100093) IS FOR THE THIRD
 FLOOR TENANT BUILD OUT.
  
 2) SHOW THAT THE DOOR TO THE LOUNGE COMPLIES WITH FBC
 11-4.13.6 FOR REQUIRED MANEUVERING CLEARANCES AT DOORS.
 A MINIMUM OF 18" IS REQUIRED AT THE LATCH ON THE PULL
 SIDE OF DOORS.
  
 3) THE LOUNGE CABINET DETAILS ON A6.2.1 DO NOT CLEARLY
 SHOW COMPLIANCE WITH FBC 11-4.24. PROVIDE BETTER
 DETAIL.
  
 4) ALL PLAN SHEETS THAT ARE AFFECTED THE CHANGES ARE
 REQUIRED TO BE REVISED. SHEET A5.1 IS MISSING.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-12-08 Cont ID  
Sent By rmcdouga Date 2006-12-08 Time 13:08 Rev Time 0.00
Received By rmcdouga Date 2006-12-08 Time 12:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-17 Cont ID  
Sent By rmcdouga Date 2006-10-17 Time 13:35 Rev Time 0.00
Received By rmcdouga Date 2006-10-17 Time 13:35 Sent To  
Notes
2006-10-17 16:23:38 
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SPECIFY THE NUMBER OF FLOORS AND BUILDING HEIGHT ON
 THE PLANS.
  
 3) THE CONSTRUCTION TYPE SPECIFIED ON THE PLANS IS
 INCORRECT. THIS STRUCTURE IS A TYPE II B SPRINKLERED
 BUILDING, USING 2004 FBC DESIGNATIONS.
  
 4) PROVIDE A DETAIL OF THE BREAK ROOM CABINETS AND AND
 COUNTERS. THE BUILT-IN COUNTERS MUST COMPLY WITH FBC
 11-4.32.4AND THE SINK MUST COMPLY WITH FBC 11-4.24.
 SHOW COMPLIANCE.
  
 5)THE GLASS IN THE SWINGING DOORS IS REQUIRED TO BE
 SAFETY GLAZING PER FBC 2406.3(1).
  
 6) WOOD FLOORING MUST COMPLY WITH FBC 804.4.2.
  
 7) THE FIXED GLASS WINDOWS ADJACENT TO THE DOORS ARE
 REQUIRED TO BE SAFETY GLAZING PER FBC 2406.3(6).
  
 8)DOOR HARDWARE SHALL COMPLY WITH FBC 11-4.13.9.
  
 9) FIRE DOORS SHALL BE SELF CLOSING OR
 AUTOMATIC-CLOSING AS REQUIRE BY FBC 715.3.7.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2007-08-28 Cont ID  
Sent By dpalmer Date 2007-08-28 Time 18:02 Rev Time 0.00
Received By dpalmer Date 2007-08-28 Time 18:02 Sent To PC
Notes
2007-08-28 18:02:59RE-STAMP ONLY OF REV #3

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2007-08-23 Cont ID  
Sent By dpalmer Date 2007-08-23 Time 17:08 Rev Time 0.00
Received By dpalmer Date 2007-08-23 Time 17:08 Sent To PC
Notes
2007-08-23 17:08:38*** DENIED ***
  
 1) NOTE: PLEASE SEE THE PLANS WHICH WERE SUBMITTED FOR
 A RE-STAMP DO NOT CORRELATE WITH THE LATEST REVISED
 SUBMITTED PLANS WHICH ARE ON-FILE AND RECORD WITH THE
 CITY FOR ELECTRICAL.
 PLEASE SUBMIT THE LATEST FOR A RE-STAMP IF NEEDED.
 PLEASE SEE THAT ONLY ONE NEED BE SUBMITTED IF IT IS
 INDEED A *RE-STAMP*.
 IF A REVISION, PLEASE SUBMIT TWO COPIES AND SUBMIT AS A
 REVISION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-08-13 Cont ID  
Sent By dpalmer Date 2007-08-13 Time 08:07 Rev Time 0.00
Received By dpalmer Date 2007-08-13 Time 08:07 Sent To PC
Notes
2007-08-13 08:07:57REV'S SHEETS E1 AND2,
 DELETED VAV'S AND CHANGED FEEDERS.

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2007-02-03 Cont ID  
Sent By dpalmer Date 2007-02-03 Time 15:55 Rev Time 0.00
Received By dpalmer Date 2007-02-03 Time 15:43 Sent To PC
Notes
2007-02-07 15:38:50REV CHNAGED OVER TO 06100032 , PASSED UNDER THAT REVIEW
2007-02-03 15:55:44** UNSAT/NOTES**
  
 PLANS ROUTED TO ADRIANNA TO TRASNFER FEES ETC TO PERMIT
 # 06100032, REVISION ARE FOR 2ND FLOOR AND THIS PERMIT
 WHICH WAS SUBMITTED BY THE CONTRACTOR IS FOR THE THIRD
 FLOOR.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-12-31 Cont ID  
Sent By dpalmer Date 2006-12-31 Time 09:23 Rev Time 0.00
Received By dpalmer Date 2006-12-31 Time 08:59 Sent To  
Notes
2006-12-31 09:25:21REDLINED PLANS ***
  
  
 ** THIRD FLOOR IS ALL ONE TENANT INCLUDING CORRIDOR. AS
 SHOWN ON PLANS THE CORRIDOR IS NOT AN EXIT CORRIDOR OR
 THE FIRE RATED EXIT PASSAGE.
  
 ** MAY ONLY SEPARATE IF CREATING ALL RATED WALLS AND
 REMOVING ELELCTRICAL SYSTEMS FROM CORRIDOR AND MOVING
 OUTSIDEETC ETC.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-12-05 Cont ID  
Sent By dpalmer Date 2006-12-05 Time 18:35 Rev Time 0.00
Received By dpalmer Date 2006-12-05 Time 16:31 Sent To  
Notes
2006-12-05 18:41:12**** UNSAT 2ND REVIEW ***
  
 ** PLEASE SEE SOME NOTES FROM THE PREVIOUS REVIEW ARE
 STILL IN QUESTION. PLEASE ALSO SEE ANY NEW NOTES DUE TO
 PLANS SUBMITTED.
 ** PLEASE SEE A NOTE OF "NO" OR "OK" IS BEING NOTED AT
 EACH NOTE WHICH IS TAKEN DIRECTLY FROM PREVIOUS REVIEW.
 PLEASE SEE IF NO, A FURTHER EXPLANATION IS NOTED TO
 BETTER CLEAR UP COMMENT FROM PREVIOUS REVIEW. PLEASE
 KNOW SOME MAY SHOW NO/OK, THIS MAY BE THAT PART OF THE
 COMMENT WAS ADDRESSED AND PART OF THE COMMENT MAY STILL
 BE OUTSTANDING.
  
  
 1) NOTE:NO, PLEASE SEE BASED ON THE LIGHTING
 DENSITIES SHOWN, PLEASE SEE TABLES IN 13-415.2.ABC.1,
 415.2.B.1.
 PLEASE BE SURE ALL SEPARATE SPACES INDICATE A CONTROL
 DEVICE.
 PLEASE SEE THAT ALL MAXIMUM TIMES ON DEVICES SHOWN BE
 NOTED ON THE LEGEND.
 PLEASE SEE IF THE EXISTING CORRIDOR IS GOING TO BE PART
 OF THE TENANT SPACE, SEE THAT CONTROLS WILL BE
 REQUIRED.
 PLEASE SEE THAT A DETAIL OR NOTE IS PROVIDED TO
 INDICATE THE CIRCUITING OF ALL EM/EXT LTS SHALL BE
 WIRED TO ANY LOCAL BRANCH CIRCUIT AHEAD OF ANY CONTROL
 SWITCHING DEVICES. PLEASE SEE 700.12E.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC CHAPTER 13 13-415.1.ABC.1.1, .1.2 AND
 .1.3.
 PLEASE ALSO SEE 13-415.2.ABC.1. PLEASE SEE THIS SPACE
 WAS A "SHELL" SPACE AND IS NOW BEING BUILT OUT UNDER
 THE 2004 FBC. PLEASE ADJUST AS NEEDED.
  
 2) NOTE: NO, THIS IS NOT CLEAR YET AS TENANT SPACES
 WITH RATE WALL ETC ARE STILL BE SHOWN, PLEASE SEE NOTE
 #3.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE ALL AREAS WHICH ARE BEING SHOWN AS "COMMON
 AREAS" MAY NOT BE FED FROM PANELS WHICH ARE FOR TENANT
 SPACE.210.25
  
 3) NOTE:NO, PLEASE SEE RESPONSE MENTIONS THIS IS ALL
 GOING TO BE ONE TENANT SPACE, HOWEVER PLANS CLEARLY
 STILL INDICATE TWO TENANTS. PLEASE SEE NOTE #1 WHICH
 SPEAKS OF CIRCUITING OF FIXTURES FOR EXISTING CORRIDOR
 AND CIRCUITING TO RECESSED LIGHTS ETC?
 PLEASE SEE TENANT SEPARATION WALLS AND MULTIPLE TENANTS
 ARE STILL BEING SHOWN. IF THIS "IS" ONE TENANT, PLEASE
 ADJUST PLANS ACCORDINGLY.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE ELECTRICAL PANELS MAY NOT BE IN RATED EXIT
 CORRIDOR SEE FBC BUILDING REVIEW COMMENTS. IF INDEED
 THIS IS GOING TO BE TWO TENANT SPACES PLEASE VERIFY AS
 ONLY ONE METER IS BEING SHOWN AND MAY NOT FEED TWO
 TENANTS/SEPARATE OCCUPANCIES FROM ONE METER/MAIN.
 PLEASE SEE COMMENTS FROM OTHER REVIEWS WHICH MAY AFFECT
 THE AMOUNT OF TENANTS ALLOWED PER FLOOR, CORRIDORS
 ETC.
 PLEASE SEE PREVIOUS NOTE WITH RESPECT TO THE COMMON
 AREA NOT BEING FED OR CONTAINING THE ELECTRICAL FROM
 TENANT PANEL.
  
 4) NOTE: NO, MAY NOT USE A "PLUG-IN" FOR THE REQUIRED
 DISCONNECTING MEANS. THIS WAS CHANGED IN THE CODE
 BEFORE THE 93 CODE. PLEASE SEE BASED ON THE LOAD AS
 SHOWN A HARDWIRED DISCONNECT IS REQUIRED. PLEASE KNOW
 IF THE EXISTING INST-HOT IS A PLUG TYPE, THE LOAD MUST
 BE LESS THAN 750VA.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLARIFY THE PANEL SCHEDULE MENTIONS AN
 INSTA-HOT., YET COULD NOT FIND THIS ON PLANS. PLEASE
 SEE 430.30, 430.31 ETC AS LOAD OF THIS SIZE WHEN UNIT
 IS REQUIRED TO CONTAIN A DISCONNECT. A PLUG MAY NOT BE
 USED. PLEASE ALSO VERIFY IF THE DISCONNECTING MEANS
 CONTAINS OCP, IF SO, PLEASE SEE 110.26.
  
 4) NOTE: OK, HOWEVER PLEASE SEE NOTE ABOVE AS IF THE
 SPACE IS ONE, THEN CIRCUITING WILL BE REVISED AND WILL
 RESULT IN SOME CHANGES TO CIRCUITS ON PLANS AS WELL AS
 POSSIBLE PANEL SCHEDULE REVISIONS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE SPECIFIC ROOMS AND AREAS ON PANEL
 SCHEDULE WHICH WILL CORRELATE WITH THE PLANS AND
 LAYOUT. 408.6, PLEASE ALSO BE SURE TO INDICATE ALL
 CONDUCTOR SIZES ON PANEL SCHEDULE.
 310.16, 240.4
 FBC 106.1.2.
  
 5) NOTE: NO/OK, PLEASE SEE THE APPLIED VALUE ON THE
 APPLICATION ALONG WITH THE CORRECT SQ FOOT FOR BUILD
 OUT MUST BE ADJUSTED BY THE CONTRACTOR TO CORRELATE
 WITH PLANS. PLEASE SEE A VALUE HAS BEEN ADJUST TO $50K,
 HOWEVER THIS VALUE MAY STILL BE ADJUSTED BY THE
 BUILDING REVIEWER BASED ON THE TABLES AS SET FORTH IN
 THE FBC. THIS VALUE AMY NOT BE FINAL.
 FEES WERE NOTE PAID FOR ADDITIONAL VALUE AND ALL FEES
 ARE DUE AT THE TIME OF SUBMITIAL UP TO A VALUE OF
 $200K.ONLY THEN CAN A VALUE OF OVER 200K BE ALLLOWED
 TO PAY A % UPFRONT. PLEASE KNOW PLANS WILL NOT BE
 REVIEWED IF ALL FEES ARE NOT PAID BEFORE RESUBMITTING
 PLANS. THIS IS STATE IN 108.3 OF THE ADMINISTRATIVE
 CODE AS ADOPTED INTO CITY ORDINANCEANDADMIN CODE.
  
 **PREVIOUS REVIEW NOTE**
 PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK SHALL BE
 BASED ON ALL LABOR AND MATERIALS EVEN IF OWNER
 SUPPLIED.
 FBC 108.3
 PLEASE SEE $25K IS WAY LOW. PLEASE KNOW, USING TABLES
 BASED ON THE FBC ONE WILL BE ASSESSED. FEES WILL BE
 OWED.
 PLEASE KNOW, ONCE THE SQ FT HAS BEEN VERIFIED FOR
 ACTUAL SCOPE OF WORK, THIS VALUE MAY CHANGE.
  
 6) NOTE: NO, SEE THE MASTER PERMIT # FOR THE BUILDING
 WAS REMOVED FROM BEING REFERENCE IN OUR SYSTEM AND
 NOTES WERE ADDED THAT A NEW RECORD NOC WAS NEEDED.
 PLEASE KNOW THIS IS REQUIRED BEFORE PICKING UP PERMIT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW THIS INTERIOR BUILD OUT WILL REQUIRE A NEW
 NOTICE OF COMMENCEMENT AS THE ONE UNDER THE BUILDING
 HAS EXPIRED AND IS NOT PART OF THIS SCOPE OF WORK. FS
 713.13
  
 7) NOTE:OK, HOWEVER SEE LOAD CALCULATIONS AS
 SUBMITTED DO NOT CORRELATE WITH PANEL SCHEDULE.
 PLEASE ALSO SEE WHEN THE RECEPT LOADS ARE KNOWN, PLEASE
 SEE 220.13.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE AND SHOW ON LOAD SUMMARY AND
 CALCULATIONS ALL CONTINUOUS LOADS AT 125%.
 215.3, 230.42
  
 ** NEW NOTE **
  
 1) NOTE: PLEASE SEE FBC 11-4.28.1,.2 AND .3(4). PLEASE
 DETAIL ALL NEW HORNS AND STROBES AT THE MINIMUM LEVELS
 AS REQUIRED IN CHAPTER 11 OF THE 2004 FBC.
 THIS WAS NOT NOTED IN PREVIOUS REVIEW AS IT HAS NOW
 BECOME AN ELECTRICAL REVIEW ITEM TO BE REVIEWED FOR.
  
 2) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS. PLEASE SEE THIS ONLY BEING GIVEN AS A
 NOTICE AT THIS TIME.
  
 ** PLEASE KNOW, AS PLANS FOR MANY ITEMS WILL CHANGE,
 ALL NOTES MAY NOT BE COMPLETE AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-13 Cont ID  
Sent By dpalmer Date 2006-10-13 Time 09:17 Rev Time 0.00
Received By dpalmer Date 2006-10-13 Time 07:56 Sent To  
Notes
2006-10-13 09:17:08**** UNSAT ***
  
  
 1) NOTE: PLEASE SEE FBC CHAPTER 13 13-415.1.ABC.1.1,
 .1.2 AND .1.3.
 PLEASE ALSO SEE 13-415.2.ABC.1. PLEASE SEE THIS SPACE
 WAS A "SHELL" SPACE AND IS NOW BEING BUILT OUT UNDER
 THE 2004 FBC. PLEASE ADJUST AS NEEDED.
  
 2) NOTE: PLEASE SEE ALL AREAS WHICH ARE BEING SHOWN AS
 "COMMON AREAS" MAY NOT BE FED FROM PANELS WHICH ARE FOR
 TENANT SPACE.210.25
  
 3) NOTE: PLEASE SEE ELECTRICAL PANELS MAY NOT BE IN
 RATED EXIT CORRIDOR SEE FBC BUILDING REVIEW COMMENTS.
 IF INDEED THIS IS GOING TO BE TWO TENANT SPACES PLEASE
 VERIFY AS ONLY ONE METER IS BEING SHOWN AND MAY NOT
 FEED TWO TENANTS/SEPARATE OCCUPANCIES FROM ONE
 METER/MAIN.
 PLEASE SEE COMMENTS FROM OTHER REVIEWS WHICH MAY AFFECT
 THE AMOUNT OF TENANTS ALLOWED PER FLOOR , CORRIDORS
 ETC.
 PLEASE SEE PREVIOUS NOTE WITHE RESPECT TO THE COMMON
 AREA NOT BEING FED OR CONTAINING THE ELECTRICAL FROM
 TENANT PANEL.
  
 4) NOTE: PLEASE CLARIFY THE PANEL SCHEDULE MENTIONS A
 INSTA-HOT., YET COULD NOT FIND THIS ON PLANS.PLEASE SEE
 430.30, 430.31 ETC AS LOAD OF THIS SIZE WHEN UNIT IS
 REQUIRED TO CONTAIN A DISCONNECT , A PLUG MAY NOT BE
 USED. PLEASE ALSO VERIFY IF THE DISCONNECTING MEANS
 CONTAINS OCP, IF SO ,PLEASE SEE 110.26.
  
 4) NOTE:PLEASE PROVIDE SPECIFIC ROOMS AND AREAS ON
 PANEL SCHEDULE WHICH WILL CORRELATE WITH THE PLANS AND
 LAYOUT. 408.6, PLEASE ALSO BE SURE TO INDICATE ALL
 CONDUCTOR SIZES ON PANEL SCHEDULE.
 310.16, 240.4
 FBC 106.1.2.
  
 5) NOTE: PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK
 SHALL BE BASED ON ALL LABOUR AND MATERIALS EVEN IF
 OWNER SUPPLIED.
 FBC 108.3
 PLEASE SEE $25K IS WAY LOW. PLEASE KNOW, USING TABLES
 BASED ON THE FBCONE WILL BE ASSESSED. FEES WILL BE
 OWED.
 PLEASE KNOW, ONCE THE SQ FT HAS BEEN VERIFIED FOR
 ACTUAL SCOPE OF WORK, THIS VALUE MAY CHANGE.
  
 6) NOTE: PLEASE KNOW, THIS INTERIOR BUILD OUT WILL
 REQUIRE A NEW NOTICE OF COMMENCEMENT AS THE ONE UNDER
 THE BUILDING HAS EXPIRED AND IS NOT PARTOF THIS SCOPE
 OF WORK. FS 713.13
  
 7) NOTE: PLEASE INDICATE AND SHOW ON LOAD SUMMARY AND
 CALCULATIONS ALL CONTINUOUS LOADS AT 125%.
 215.3, 230.42
  
 ** PLEASE KNOW, AS PLANS FOR MANY ITEMS WILL CHANGE ,
 ALL NOTES MAY NOT BE COMPLETE AT THIS TIME.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-02-12 Cont ID  
Sent By mawillia Date 2007-02-12 Time 10:09 Rev Time 0.00
Received By mawillia Date 2007-02-12 Time 10:08 Sent To  
Notes
2007-02-12 10:13:32*****DENIED*****
  
  
  
 THE PERMIT NUMBER GIVEN IS FOR THE THIRD FLOOR TENANT
 BUILDOUT, WHEREAS THE SUBMITTED PLAN SHEETS ARE FOR 2ND
 FLOOR PLAN.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-12-12 Cont ID  
Sent By mawillia Date 2006-12-12 Time 13:30 Rev Time 0.00
Received By mawillia Date 2006-12-12 Time 13:30 Sent To  
Notes
2006-12-12 13:32:22*****APPROVED*****
  
  
 TO BE STAMPED WHEN ALL OTHER PLAN REVIEW COMMENTS HAVE
 BEEN SATISFIED

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-10-26 Cont ID  
Sent By mcarsill Date 2006-10-26 Time 14:24 Rev Time 0.00
Received By mcarsill Date 2006-10-26 Time 14:17 Sent To  
Notes
2006-10-26 14:24:251. FIRE DAMPERS ARE REQUIRED TO BE DROP TESTED AFTER
 INSTALLATION.
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE
 ALARM REMODEL.
 3. PLEASE ENSURE THAT THE NOTE ON THE PLANS ARE
 FOLLOWED REGARDING A SEPARATE PERMIT FOR FIRE SPRINKLER
 SYSTEM REMODEL.
 4. ALL RATED FIRE DOORS SHALL BE EQUIPPED WITH
 SELF-CLOSING DEVICES.
 5. INTERIOR FINISH CLASSIFICATIONS SHALL COMPLY WITH
 APPLICABLE BUILDING AND FIRE CODE STANDARDS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2007-08-28 Cont ID  
Sent By adarroug Date 2007-08-28 Time 16:26 Rev Time 0.00
Received By adarroug Date 2007-08-28 Time 16:26 Sent To E
Notes
2007-08-28 16:26:31TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-08-10 Cont ID  
Sent By dpalmer Date 2007-08-10 Time 08:13 Rev Time 0.00
Received By dpalmer Date 2007-08-10 Time 08:13 Sent To E
Notes
2007-08-10 08:13:45TO BT'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-08-07 Cont ID  
Sent By dpalmer Date 2007-08-07 Time 21:05 Rev Time 0.00
Received By dpalmer Date 2007-08-07 Time 21:05 Sent To  
Notes
2007-08-21 11:00:19TO "BOB"#10
2007-08-07 21:06:03WAITING FOR BOB BOARD.

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-04-27 Cont ID  
Sent By adarroug Date 2007-04-27 Time 09:19 Rev Time 0.00
Received By adarroug Date 2007-04-27 Time 09:19 Sent To M
Notes
2007-04-27 09:19:28TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-03-10 Cont ID  
Sent By adarroug Date 2007-03-10 Time 15:53 Rev Time 0.00
Received By adarroug Date 2007-03-10 Time 15:53 Sent To M
Notes
2007-03-10 15:53:19TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-02-01 Cont ID  
Sent By adarroug Date 2007-02-01 Time 15:05 Rev Time 0.00
Received By adarroug Date 2007-02-01 Time 15:05 Sent To E
Notes
2007-02-01 15:05:43TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-02-01 Cont ID  
Sent By adarroug Date 2007-02-01 Time 15:03 Rev Time 0.00
Received By adarroug Date 2007-02-01 Time 15:02 Sent To M
Notes
2007-02-01 15:03:44TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-02-01 Cont ID  
Sent By adarroug Date 2007-02-01 Time 14:52 Rev Time 0.00
Received By adarroug Date 2007-02-01 Time 14:52 Sent To P
Notes
2007-02-01 14:52:37TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-02-01 Cont ID  
Sent By adarroug Date 2007-02-01 Time 14:37 Rev Time 0.00
Received By adarroug Date 2007-02-01 Time 14:37 Sent To  
Notes
2007-02-01 14:38:08WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-27 Cont ID  
Sent By adarroug Date 2006-12-27 Time 14:04 Rev Time 0.00
Received By adarroug Date 2006-12-27 Time 14:04 Sent To E
Notes
2006-12-27 14:04:37TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-13 Cont ID  
Sent By adarroug Date 2006-11-13 Time 13:51 Rev Time 0.00
Received By adarroug Date 2006-11-13 Time 13:50 Sent To  
Notes
2006-12-05 13:29:00TO "BOB"#4
2006-11-13 13:50:56WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-26 Cont ID  
Sent By adarroug Date 2006-10-26 Time 16:51 Rev Time 0.00
Received By adarroug Date 2006-10-05 Time 16:20 Sent To  
Notes
2006-10-12 09:34:08TO "BOB"#5
2006-10-05 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2007-08-23 Cont ID  
Sent By tgordon Date 2007-08-23 Time 14:07 Rev Time 0.25
Received By tgordon Date 2007-08-23 Time 14:07 Sent To  
Notes
2007-08-23 14:08:25RE-STAMP MECHANICAL PLANS PAGES M.1 AND M.2.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-04-27 Cont ID  
Sent By tgordon Date 2007-04-27 Time 15:41 Rev Time 0.25
Received By tgordon Date 2007-04-27 Time 15:41 Sent To  
Notes
2007-04-27 15:42:12REVISION TO MECH. PLANS PAGE M.1.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-03-13 Cont ID  
Sent By tgordon Date 2007-03-13 Time 08:35 Rev Time 0.30
Received By tgordon Date 2007-03-13 Time 08:35 Sent To  
Notes
2007-03-13 08:36:54MECH. REVISION TO PLANS PAGE M.1 AND M.2.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-02-02 Cont ID  
Sent By tgordon Date 2007-02-02 Time 09:27 Rev Time 0.35
Received By tgordon Date 2007-02-02 Time 09:27 Sent To  
Notes
2007-02-02 09:30:12MECHANICAL REVISION
 *** DENIED ***
 1) PLANS SUBMITTED ARE FOR SUITE 200, PERMIT #06100093
 IS FOR SUITE 300, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-12-12 Cont ID  
Sent By tgordon Date 2006-12-12 Time 10:55 Rev Time 0.25
Received By tgordon Date 2006-12-12 Time 10:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-10-16 Cont ID  
Sent By tgordon Date 2006-10-16 Time 14:55 Rev Time 0.30
Received By tgordon Date 2006-10-16 Time 14:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-02-26 Cont ID  
Sent By jleech Date 2007-02-26 Time 09:19 Rev Time 0.00
Received By jleech Date 2007-02-26 Time 09:19 Sent To  
Notes
2007-02-26 09:30:36PLANS SUBMITEDARE FORSUITE 200 PERMIT NUMBER IS FOR
 3RD FLOOR. PLANS FOR 2ND FLOOR DO NOT HAVE A PAGE
 P-2.1. A REVISION IS A CHANGE ON A PREVIOUSLY APPROVED
 PLAN.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-12-19 Cont ID  
Sent By jleech Date 2006-12-19 Time 07:22 Rev Time 0.00
Received By jleech Date 2006-12-19 Time 07:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-10-23 Cont ID  
Sent By jleech Date 2006-10-23 Time 13:01 Rev Time 0.00
Received By jleech Date 2006-10-23 Time 13:01 Sent To  
Notes
2006-10-23 13:34:25DENIED;
 1.PLEASE SHOW PLUMBING RISER FOR BREAK SINK, SIZE OF
 SANITARY DRAIN AND VENT. SHOW ON PLANS WERE THE
 BUILDING
 VENT AND SOIL STACKS ARE LOCATED.
 2. SHOW A DETAIL OF THE BREAK SINK. SINK MUST COMPY
 WITH FBC-2004 CHAPTER 11 SECTIONS;
 11-4.24.2 HEIGHT OF SINK.
 11-4.24.3 KNEE CLEARANCE; 27" HIGH, 30" WIDE, AND
 19" DEEP.
 11-4.24.4 DEPTH OF SINK, A MAXIMUM OF 6 1/2" DEEP.
 11-4.24.5 CLEAR FLOOR SPACE 30" X 48" SHOW ON FLOOR
 PLAN.
 11-4.24.6 EXPOSED PIPES TO BE INSULATED.
 11-4.24.7 FAUCET LEVER HANDLES ETC.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2006-10-23 Cont ID  
Sent By astelly Date 2006-10-23 Time 10:29 Rev Time 0.00
Received By astelly Date 2006-10-23 Time 10:29 Sent To  
Notes
2006-10-13 08:26:30NEEDS DMP.