Plan Review Stops For Permit 06100087 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2007-06-26 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2007-06-26 |
Time |
09:28 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2007-06-26 |
Time |
09:28 |
Sent To |
|
|
Notes |
2007-06-26 14:08:33 | PROVISO | | | | SUBMIT REVISED TRUSS ENGINEERING , REFERENCING EXPOSURE | | 'C' . | | STRUCTURE IS DESIGNED TO EXPOSURE 'C' . | | | | | | | | | | | | L.MARTINEZ | | 805-6710 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2007-03-28 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2007-03-28 |
Time |
15:10 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2007-03-28 |
Time |
15:10 |
Sent To |
|
|
Notes |
2007-03-28 15:47:00 | | | BUILDING REVIEW COMMENTS | | -------------------------------------------- | | | | | | 1.NOTICE OF COMMENCEMENT WILL EXPIRE ON MARCH 3RD. | | 2007. | | | | 2.SUBMIT PRODUCT APPROVALS FOR THE LINTELS. | | | | 3.HAVE DESIGNER OF RECORD REVIEW AND APPROVE TRUSS | | LAYOUT. | | | | 4.VERIFY BATHROOM WINDOW SH22 IS SAFETY GLAZING | | RATED. | | | | | | | | | | | | L.MARTINEZ | | 805-6710 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-10-20 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2006-10-20 |
Time |
08:15 |
Rev Time |
0.00 |
Received By |
alange |
Date |
2006-10-20 |
Time |
08:14 |
Sent To |
|
|
Notes |
2006-10-20 08:25:19 | DENIED | | | | | | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT SHALL BE | | RECORDED AT PALM BEACH COUNTY COURTHOUSE AND A COPY | | SUBMITTED TO THIS OFFICE BEFORE A PERMIT CAN BE ISSUED. | | BLANK FORMS ARE AVAILABLE FROM THIS OFFICE. | | NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF | | THE DESCRIBED IMPROVEMENT OR CONSTRUCTION IS NOT | | COMMENCED WITHIN 90 DAYS OF RECORDING. | | | | 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION. | | | | 3.BASED ON ICC BUILDING VALUATION DATA THE PERMIT | | VALUE HAS BEEN REVISED TO $144,527.ADDITIONAL PERMIT | | FEES ARE DUE. | | | | 4.SUBMIT TWO COPIES OF ENERGY CALCS PER 2004 FBC ON | | FORM 600A-04.COMPLETE TOP SECTION OF FORM.FBC | | 13-600.3.A | | | | 5.PRODUCT APPROVALS REQUIRED FOR IMPACT PROTECTION | | AND LINTELS.. | | | | 6.ALL PRODUCT APPROVALS SUBMITTED WITH QUALITY | | ASSURANCE SHALL HAVE THE FOLLOWING STATE APPROVAL | | ATTACHED. | | | | PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION | | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE | | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE | | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. | | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE | | SUBMITTED WITH A STATE PRODUCT APPROVAL SHEETS THAT | | LISTS THE PRODUCT IDENTITY NUMBER FROM THE STATE. IF | | THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT AN | | APPLICATION FOR LOCAL PRODUCT APPROVAL OR SITE SPECIFIC | | FORM PER RULE 9B-72. SEE ATTACHMENT. | | WWW.FLORIDABUILDING.ORG | | | | 7.PRODUCT APPROVAL FOR THE OVERHEAD DOOR IS FOR THE | | WRONG SIZE DOOR. | | | | 8.SUBMIT TWO SETS OF TRUSS DRAWINGS FOR REVIEW PER | | 2004 FBC R-802.10.1TRUSS DRAWING REQUIRED TO BE | | APPROVED PRIOR TO INSTALLATION. | | | | 9.SAFTEY GLAZING REQUIRED FOR WINDOW AT TUB | | LOCATIONS.R-308.4 | | | | 10.R401.3 DRAINAGE. | | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER | | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS | | TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO | | DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE | | GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM | | OF 6 INCHESWITHIN THE FIRST 10 FEET. | | | | 11.SUBMIT TWO ORIGINAL SIGNED AND SEALED SURVEYS.FS | | 472.025 | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. SUBMIT ONE | | COPY OF OLD PAGES FOR REFERENCE . A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A | | DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET | | OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | ANTICIPATED COOPERATION. | | | | | | | | ART LANGE | | BUILDING PLANS EXAMINER | | CONSTRUCTION SERVICES DEPARTMENT | | 561-805-6672 | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2007-08-06 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-08-06 |
Time |
09:22 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-08-06 |
Time |
09:00 |
Sent To |
P |
|
Notes |
2007-08-06 09:23:21 | REDLINED PLANS FOR 424.3B. THE MIN OVER CURRENT | | PROTECTION FOR AHU IS SHOWN TOO SMALL PER MINIMUM PER | | NEC. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2007-04-25 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-04-25 |
Time |
18:01 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-04-25 |
Time |
17:02 |
Sent To |
P |
|
Notes |
2007-04-25 18:01:04 | ** UNSAT 3RD REVIEW ** | | | | | | ***** PLEASE SEE THE PLANS HAVE NOW BEEN REVISED | | REMOVING MANY CODE COMPLIANT ITEMS WHICH WERE OK ON | | PREVIOUS PLANS???? | | PLEASE SEE THERE ARE SEVERAL ITEMS WHICH WERE ON PLANS | | WHICH HAVE NOW BEEN REMOVED. | | IT IS UNCLEAR WHY SO MANY OF THESE ITEMS WERE REMOVED | | OR CHANGED FROM PREVIOUS PLANS WHICH WERE SUBMITTED ON | | THE FIRST REVIEW. | | | | ** ONE COPY OF EACH WAS RETAINED BY THIS OFFICE. | | | | 1) NOTE: PLEASE INDICATE THE AIC RATINGS ON PLANS AS | | PREVIOUSLY SHOWN. | | 110.9 | | FBC 106.1.2 | | | | 2) NOTE: PLEASE SEE MISSING RECEPTACLE FOR MASTER | | BEDROOM 2FT OR MORE OF WALL PER 210.52 | | | | 3) NOTE: PLEASE SEE MISSING DESIGNATIONS ON PANEL | | SCHEDULE AS PREVIOUSLY DONE ON PANEL SCHEDULE. PLEASE | | SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY FROM THE | | NEC> | | * CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY | | CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE | | LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR | | WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME | | PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR | | EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY | | OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN | | COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL | | APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, | | THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL | | RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR | | ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' | | CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH | | ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE | | SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* | | 408.4, 310.16, 240.4 ETC | | FBC 106.3.5.4 | | | | 4) NOTE: PLEASE SEE THE KW RATING WHICH IS 7KW ON | | MECHANICAL PLANS IS NOW SHOWN AS 6.5KW ON ELECTRICAL | | PLANS.?? | | PLEASE COORDINATE. | | 424.3, 310.16, 240.4 ETC. | | | | 5) NOTE: PLEASE SEE MISSING AFCI NOTE WHICH MENTIONS | | ALL REQUIRED PROTECTED OUTLETS IN BEDROOMS PER 210.12. | | (PREVIOUS PLANS NOTES WERE OK) | | | | 6) NOTE: PLEASE SEE MISSING REQUIRED CODES TO BE STATED | | ON ELECTRICAL PLANS AS PREVIOUSLY DONE. | | NFPA-70 2002 | | NFPA-72 2002 | | THE 2004 FBC. | | | | 7) NOTE: PLEASE SEE MISSING GFI FOR CU OUTSIDE PER | | 210.8, 210.63 | | | | 8) NOTE: PLEASE SEE MISSING DISCONNECT FOR WATER HEATER | | PER 422.31. | | THIS MENTIONS *HARD-WIRED* WHICH IS REQUIRED PER THE | | NEC ALSO, HOWEVER THE SYMBOL USED FOR THIS IS A | | RECEPTACLE?? | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2007-01-19 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-01-19 |
Time |
07:21 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-01-19 |
Time |
07:07 |
Sent To |
M |
|
Notes |
2007-01-19 07:23:42 | | | | | | | *** UNSAT 2ND REVIEW *** | | | | 1) NOTE: PLEASE SEE THE EXACT SAME PLANS WHICH WERE | | PREVIOUSLY SUBMITTED ARE SUBMITTED BACK WITH OUT | | CORRECTIONS MADE. | | PLEASE SEE ONE SET HAS SOME HAND DRAWN CHANGES WHICH | | ARE NOT PERMITTED TO PLANS WHICH ARE SIGNED, DATED AND | | SEALED BY AN ARCHITECT OR ENGINEER. PLEASE GIVE PLANS | | BACK TO THE DESIGN PROFESSIONAL, SHEETS WILL BE | | REQUIRED TO BE RE-PRINTED AND SIGNED DATED AND SEALED | | AS PREVIOUSLY DONE. | | PLEASE SEE THE COMMENTS FROM THE PREVIOUS REVIEW ARE | | STILL ATTACHED TO PACKAGE. | | | | 2) NOTE: PLEASE KNOW THAT A MEETING WAS HELD AT THE | | SOUTHERN SECTION MEETING IN OCT 06WHERE WE WERE | | DIRECTLY INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE | | DETECTORS ON PLANS FOR RESIDENTIAL HOMES IS NOT | | ACCEPTABLE WHEN THESE DEVICES ANY ACTUALLY FALL UNDER | | THE DEFINITIONS OF SMOKE ALARMS WHICH WOULD BE SHOWN AS | | SA/SMOKE ALARMS. | | THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE | | OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED. | | BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE | | DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL | | NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY | | HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF | | SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS | | SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS | | SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS | | FOR OTHER NEW HOMES. | | ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC | | RESIDENTIAL CODE/ FBC AND IN NFPA-72. | | PLANS ARE BEING CORRECTED FOR OTHER ITEMS, PLEASE MAKE | | THIS ADJUSTMENT. | | IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE. | | | | ** TAKEN FROM THE NFPA-72** | | 11.5.1.1 SMOKE DETECTION.WHERE REQUIRED BY APPLICABLE | | LAWS, CODES, OR STANDARDS FOR THE SPECIFIED OCCUPANCY, | | APPROVED SINGLE- AND MULTIPLE-STATION SMOKE ALARMS | | SHALL BE INSTALLED AS FOLLOWS: | | (1)IN ALL SLEEPING ROOMS | | EXCEPTION:SMOKE ALARMS SHALL NOT BE REQUIRED IN | | SLEEPING ROOMS IN EXISTING ONE- AND TWO-FAMILY DWELLING | | UNITS. | | (2)OUTSIDE OF EACH SEPARATE SLEEPING AREA, IN THE | | IMMEDIATE VICINITY OF THE SLEEPING ROOMS | | (3)ON EACH LEVEL OF THE DWELLING UNIT, INCLUDING | | BASEMENTS | | EXCEPTION:IN EXISTING ONE- AND TWO-FAMILY DWELLING | | UNITS, APPROVED SMOKE ALARMS POWERED BY BATTERIES SHALL | | BE PERMITTED. | | 11.5.1.2 NOTIFICATION. | | (A) FIRE-WARNING EQUIPMENT FOR DWELLING UNITS SHALL | | PROVIDE A SOUND THAT IS AUDIBLE IN ALL OCCUPIABLE | | DWELLING AREAS. | | (B) WHERE MORE THAN ONE SMOKE OR HEAT ALARM IS | | INSTALLED FOR NEW CONSTRUCTION, THEY SHALL BE ARRANGED | | SO THAT THE OPERATION OF ANY SMOKE OR HEAT ALARM CAUSES | | THE ALARM IN ALL SMOKE AND HEAT ALARMS WITHIN THE | | DWELLING UNIT TO SOUND | | | | 11.8.3* SMOKE DETECTORS AND SMOKE ALARMS. SMOKE ALARMS, | | SMOKE DETECTORS, DEVICES, COMBINATION OF DEVICES, AND | | EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE | | MANUFACTURER'S LISTING AND INSTRUCTIONS, AND UNLESS | | SPECIFICALLY LISTED FOR THE APPLICATION, SHALL COMPLY | | WITH REQUIREMENTS IN11.8.3.1 THROUGH11.8.3.5. | | | | 3) NOTE: PLEASE SEE COPY OF FLORIDA STATUTES | | 553.80(2)(B) WITH RESPECT TO REPEAT NOTES FOR CODE | | COMPLIANCE. THIS IS BEING GIVEN ONLY AS NOTICE AT THIS | | TIME. | | | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2006-10-06 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-10-06 |
Time |
16:44 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-10-06 |
Time |
16:36 |
Sent To |
Z |
|
Notes |
2006-10-06 00:00:00 | **** UNSAT **** | | | | 1) NOTE: PLEASE SEE FAC 61G17 AND FS | | 472.025 AS THE SURVEY'S ARE REQUIRED TO | | BE SEALED WHEN SIGNED TO BE VALID. | | | | 2) NOTE: PLEASE SEE ALL SEALS ON PLANS | | SHALL BE CLEAR AND VISABLE WITH ALL | | INFORMATION ON SAID SEAL AS REQUIRED PER | | FAC 61G1-16.003, FS 481.221 | | | | 3) NOTE: PLEASE SEE MISSING DINING | | AREA/BREAKFEST AREAS AND THE LIKE FOR | | CIRCUTING AND MIN 20A #12 CIRCUITS | | REQUIRED TO MEET 210.52B1, 220.16, | | 210.11C1 | | | | 4) NOTE: PLEASE OCP ON 50A RANGE RECEPT | | SHALL NOT EXCEED RATINGS AS PERMITTED IN | | TABLES 220.21B3 | | | | 5) NOTE: PLEASE SEE OCP FOR AHU, SHALL | | MEET 424.3B FOR MIN 125%. | | PLEASE ADJUST. | | | | 2) NOTE: PLEASE LIST THE OCP FOR THE | | BRANCH CIRCUIT TO THE CU. | | | | | | PLEASE SEE NOTES ONE AND TWO ARE | | REQUIRED FOR ALL. | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2007-08-02 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-02 |
Time |
15:47 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-02 |
Time |
15:47 |
Sent To |
E |
|
Notes |
2007-08-02 15:47:38 | TO "DPALMER" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2007-04-23 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-04-23 |
Time |
14:53 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-04-23 |
Time |
14:53 |
Sent To |
E |
|
Notes |
2007-04-23 14:53:45 | TO "DPALMER" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-01-17 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-01-17 |
Time |
09:44 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-01-17 |
Time |
09:44 |
Sent To |
E |
|
Notes |
2007-01-17 09:44:54 | TO "DPALMER" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-01-04 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-01-04 |
Time |
12:25 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-01-04 |
Time |
12:25 |
Sent To |
Z |
|
Notes |
2007-01-04 12:25:27 | TO "Z" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-10-20 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2006-10-20 |
Time |
08:15 |
Rev Time |
0.00 |
Received By |
alange |
Date |
2006-10-05 |
Time |
09:37 |
Sent To |
|
|
Notes |
2006-10-05 00:00:00 | TO "SFR" "Z" |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2007-01-19 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-01-19 |
Time |
08:13 |
Rev Time |
0.25 |
Received By |
tgordon |
Date |
2007-01-19 |
Time |
08:13 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2006-10-17 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-10-17 |
Time |
14:42 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2006-10-17 |
Time |
14:42 |
Sent To |
Z |
|
Notes |
2006-10-17 14:49:51 | *** DENIED *** | | 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04 | | (2004) PER FBC 13-600.3.A . | | | | 2) 10" RETURN AIR TRANSFER DUCT TO MASTER SUITE IS TO | | SMALL, SEE NOTE #3. | | | | 3) BALANCED RETURN AIR. | | THIS MAY BE ACHIEVED BY. | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY | | INCREASING THE RETURN TRANSFER ONE AND | | ONE HALF TIMES THE CROSS SECTIONAL AREA | | (SQUARE INCHES) OF THE SUPPLY DUCT | | ENTERING THE ROOM OR SPACE IT'S SERVING | | AND THE DOOR HAVING AT LEAST AN | | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE | | PROPER RETURN AIR BALANCE. | | (B)TRANSFER GRILLES SHALL USE 50 | | SQUARE INCHES (OF GRILLE AREA) TO 100 | | CFM (OF SUPPLY AIR) FOR SIZING | | THROUGH-THE-WALL TRANSFER GRILLES AND | | USING AN UNRESTRICTED 1-INCH | | UNDERCUTTING OF DOORS TO ACHIEVE PROPER | | RETURN AIR BALANCE | | (C)HABITABLE ROOMS ONLY SHALL BE | | REQUIRED TO MEET THESE REQUIREMENTS FOR | | PROPER BALANCED RETURN AIR EXCLUDING | | BATHROOMS, CLOSETS, STORAGE ROOMS AND | | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY | | AIR INTO THE MASTER SUITE SHALL BE | | INCLUDED. PER 2004 FBC/R M1602.4 . | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2007-08-14 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-08-14 |
Time |
10:52 |
Rev Time |
0.33 |
Received By |
mperson |
Date |
2007-08-14 |
Time |
10:52 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2007-05-10 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-05-10 |
Time |
10:13 |
Rev Time |
0.33 |
Received By |
mperson |
Date |
2007-05-10 |
Time |
10:13 |
Sent To |
B |
|
Notes |
2007-05-10 10:25:21 | DENIED 3RD TIME | | REFERENCE: | | ** FBC-2004 PLUMBING. | | ** FBC-2004 CHAPTER 1, THE CITY OF | | WEST PALM BEACH AMENDMENTS. | | | | THE RESUBMITTED DRAWINGS ARE INCOMPLETE THE FOLLOWING | | IS REQUIRED FOR PLUMBING PLAN REVIEW TO MEET CODE | | COMPLIANCE: | | | | 1. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4 | | RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A | | PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING | | ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT | | LOCATIONS. | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561) 805-6721 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2007-02-05 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2007-02-05 |
Time |
07:25 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2007-02-05 |
Time |
07:25 |
Sent To |
B |
|
Notes |
2007-02-05 07:27:23 | DENIED; | | SEE ELECTRICAL PLAN REVIEW NOTE # 1. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2006-10-14 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2006-10-14 |
Time |
14:06 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2006-10-14 |
Time |
14:06 |
Sent To |
Z |
|
Notes |
2006-10-14 14:08:32 | SEE ELECTRICAL PLAN REVIEW NOTES 1 AND 2. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2007-01-12 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2007-01-12 |
Time |
11:23 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2007-01-12 |
Time |
11:23 |
Sent To |
|
|
Notes |
2007-01-12 11:29:38 | PROVISO: SHALL APPLY FOR A SEPARATE PERMIT FOR THE CBS | | WALLS.HEIGHT ALLOWED WITHIN THE 25FT SETBACK IS 4FT | | ONLY. SHALL PROVIDE EASEMENT APPROVAL FROM THE CITY OF | | WEST PALM BEACH UTILITY DEPT. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2006-10-18 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2006-10-18 |
Time |
11:16 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2006-10-18 |
Time |
11:16 |
Sent To |
B |
|
Notes |
2006-10-18 11:17:24 | DENIED, | | 1. SEE ELECTRICAL NOTES 1 & 2. | | 2. PLEASE PROVIDE THE DIMENSION OF THE PROPOSED | | DRIVEWAY (LENGTH & WIDTH). | | | | NOTE: MUST MAINTAIN 1000SQ FT OR 75% OF | | LANDSCAPE, WHICHEVER IS LESS WITHIN THE | | FIRST 25FT FRONT SETBACK. | | | | | | | | MICHELLE MCLEAN | | ZONING TECHNICIAN | | 805-6720 |
|
|