Plan Review Details - Permit 06100087
Plan Review Stops For Permit 06100087
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-06-26 Cont ID  
Sent By lmartine Date 2007-06-26 Time 09:28 Rev Time 0.00
Received By lmartine Date 2007-06-26 Time 09:28 Sent To  
Notes
2007-06-26 14:08:33PROVISO
  
 SUBMIT REVISED TRUSS ENGINEERING , REFERENCING EXPOSURE
 'C' .
 STRUCTURE IS DESIGNED TO EXPOSURE 'C' .
  
  
  
  
  
 L.MARTINEZ
 805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-28 Cont ID  
Sent By lmartine Date 2007-03-28 Time 15:10 Rev Time 0.00
Received By lmartine Date 2007-03-28 Time 15:10 Sent To  
Notes
2007-03-28 15:47:00 
 BUILDING REVIEW COMMENTS
 --------------------------------------------
  
  
 1.NOTICE OF COMMENCEMENT WILL EXPIRE ON MARCH 3RD.
 2007.
  
 2.SUBMIT PRODUCT APPROVALS FOR THE LINTELS.
  
 3.HAVE DESIGNER OF RECORD REVIEW AND APPROVE TRUSS
 LAYOUT.
  
 4.VERIFY BATHROOM WINDOW SH22 IS SAFETY GLAZING
 RATED.
  
  
  
  
  
 L.MARTINEZ
 805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-20 Cont ID  
Sent By alange Date 2006-10-20 Time 08:15 Rev Time 0.00
Received By alange Date 2006-10-20 Time 08:14 Sent To  
Notes
2006-10-20 08:25:19DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE AND A COPY
 SUBMITTED TO THIS OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT OR CONSTRUCTION IS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.BASED ON ICC BUILDING VALUATION DATA THE PERMIT
 VALUE HAS BEEN REVISED TO $144,527.ADDITIONAL PERMIT
 FEES ARE DUE.
  
 4.SUBMIT TWO COPIES OF ENERGY CALCS PER 2004 FBC ON
 FORM 600A-04.COMPLETE TOP SECTION OF FORM.FBC
 13-600.3.A
  
 5.PRODUCT APPROVALS REQUIRED FOR IMPACT PROTECTION
 AND LINTELS..
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH QUALITY
 ASSURANCE SHALL HAVE THE FOLLOWING STATE APPROVAL
 ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL SHEETS THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM THE STATE. IF
 THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT AN
 APPLICATION FOR LOCAL PRODUCT APPROVAL OR SITE SPECIFIC
 FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.PRODUCT APPROVAL FOR THE OVERHEAD DOOR IS FOR THE
 WRONG SIZE DOOR.
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS FOR REVIEW PER
 2004 FBC R-802.10.1TRUSS DRAWING REQUIRED TO BE
 APPROVED PRIOR TO INSTALLATION.
  
 9.SAFTEY GLAZING REQUIRED FOR WINDOW AT TUB
 LOCATIONS.R-308.4
  
 10.R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS
 TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE
 GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM
 OF 6 INCHESWITHIN THE FIRST 10 FEET.
  
 11.SUBMIT TWO ORIGINAL SIGNED AND SEALED SURVEYS.FS
 472.025
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. SUBMIT ONE
 COPY OF OLD PAGES FOR REFERENCE . A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DEPARTMENT
 561-805-6672
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-08-06 Cont ID  
Sent By dpalmer Date 2007-08-06 Time 09:22 Rev Time 0.00
Received By dpalmer Date 2007-08-06 Time 09:00 Sent To P
Notes
2007-08-06 09:23:21REDLINED PLANS FOR 424.3B. THE MIN OVER CURRENT
 PROTECTION FOR AHU IS SHOWN TOO SMALL PER MINIMUM PER
 NEC.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-04-25 Cont ID  
Sent By dpalmer Date 2007-04-25 Time 18:01 Rev Time 0.00
Received By dpalmer Date 2007-04-25 Time 17:02 Sent To P
Notes
2007-04-25 18:01:04** UNSAT 3RD REVIEW **
  
  
 ***** PLEASE SEE THE PLANS HAVE NOW BEEN REVISED
 REMOVING MANY CODE COMPLIANT ITEMS WHICH WERE OK ON
 PREVIOUS PLANS????
 PLEASE SEE THERE ARE SEVERAL ITEMS WHICH WERE ON PLANS
 WHICH HAVE NOW BEEN REMOVED.
 IT IS UNCLEAR WHY SO MANY OF THESE ITEMS WERE REMOVED
 OR CHANGED FROM PREVIOUS PLANS WHICH WERE SUBMITTED ON
 THE FIRST REVIEW.
  
 ** ONE COPY OF EACH WAS RETAINED BY THIS OFFICE.
  
 1) NOTE: PLEASE INDICATE THE AIC RATINGS ON PLANS AS
 PREVIOUSLY SHOWN.
 110.9
 FBC 106.1.2
  
 2) NOTE: PLEASE SEE MISSING RECEPTACLE FOR MASTER
 BEDROOM 2FT OR MORE OF WALL PER 210.52
  
 3) NOTE: PLEASE SEE MISSING DESIGNATIONS ON PANEL
 SCHEDULE AS PREVIOUSLY DONE ON PANEL SCHEDULE. PLEASE
 SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY FROM THE
 NEC>
 * CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 4) NOTE: PLEASE SEE THE KW RATING WHICH IS 7KW ON
 MECHANICAL PLANS IS NOW SHOWN AS 6.5KW ON ELECTRICAL
 PLANS.??
 PLEASE COORDINATE.
 424.3, 310.16, 240.4 ETC.
  
 5) NOTE: PLEASE SEE MISSING AFCI NOTE WHICH MENTIONS
 ALL REQUIRED PROTECTED OUTLETS IN BEDROOMS PER 210.12.
 (PREVIOUS PLANS NOTES WERE OK)
  
 6) NOTE: PLEASE SEE MISSING REQUIRED CODES TO BE STATED
 ON ELECTRICAL PLANS AS PREVIOUSLY DONE.
 NFPA-70 2002
 NFPA-72 2002
 THE 2004 FBC.
  
 7) NOTE: PLEASE SEE MISSING GFI FOR CU OUTSIDE PER
 210.8, 210.63
  
 8) NOTE: PLEASE SEE MISSING DISCONNECT FOR WATER HEATER
 PER 422.31.
 THIS MENTIONS *HARD-WIRED* WHICH IS REQUIRED PER THE
 NEC ALSO, HOWEVER THE SYMBOL USED FOR THIS IS A
 RECEPTACLE??
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-01-19 Cont ID  
Sent By dpalmer Date 2007-01-19 Time 07:21 Rev Time 0.00
Received By dpalmer Date 2007-01-19 Time 07:07 Sent To M
Notes
2007-01-19 07:23:42 
  
  
 *** UNSAT 2ND REVIEW ***
  
 1) NOTE: PLEASE SEE THE EXACT SAME PLANS WHICH WERE
 PREVIOUSLY SUBMITTED ARE SUBMITTED BACK WITH OUT
 CORRECTIONS MADE.
 PLEASE SEE ONE SET HAS SOME HAND DRAWN CHANGES WHICH
 ARE NOT PERMITTED TO PLANS WHICH ARE SIGNED, DATED AND
 SEALED BY AN ARCHITECT OR ENGINEER. PLEASE GIVE PLANS
 BACK TO THE DESIGN PROFESSIONAL, SHEETS WILL BE
 REQUIRED TO BE RE-PRINTED AND SIGNED DATED AND SEALED
 AS PREVIOUSLY DONE.
 PLEASE SEE THE COMMENTS FROM THE PREVIOUS REVIEW ARE
 STILL ATTACHED TO PACKAGE.
  
 2) NOTE: PLEASE KNOW THAT A MEETING WAS HELD AT THE
 SOUTHERN SECTION MEETING IN OCT 06WHERE WE WERE
 DIRECTLY INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE
 DETECTORS ON PLANS FOR RESIDENTIAL HOMES IS NOT
 ACCEPTABLE WHEN THESE DEVICES ANY ACTUALLY FALL UNDER
 THE DEFINITIONS OF SMOKE ALARMS WHICH WOULD BE SHOWN AS
 SA/SMOKE ALARMS.
 THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE
 OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED.
 BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 PLANS ARE BEING CORRECTED FOR OTHER ITEMS, PLEASE MAKE
 THIS ADJUSTMENT.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 ** TAKEN FROM THE NFPA-72**
 11.5.1.1 SMOKE DETECTION.WHERE REQUIRED BY APPLICABLE
 LAWS, CODES, OR STANDARDS FOR THE SPECIFIED OCCUPANCY,
 APPROVED SINGLE- AND MULTIPLE-STATION SMOKE ALARMS
 SHALL BE INSTALLED AS FOLLOWS:
 (1)IN ALL SLEEPING ROOMS
 EXCEPTION:SMOKE ALARMS SHALL NOT BE REQUIRED IN
 SLEEPING ROOMS IN EXISTING ONE- AND TWO-FAMILY DWELLING
 UNITS.
 (2)OUTSIDE OF EACH SEPARATE SLEEPING AREA, IN THE
 IMMEDIATE VICINITY OF THE SLEEPING ROOMS
 (3)ON EACH LEVEL OF THE DWELLING UNIT, INCLUDING
 BASEMENTS
 EXCEPTION:IN EXISTING ONE- AND TWO-FAMILY DWELLING
 UNITS, APPROVED SMOKE ALARMS POWERED BY BATTERIES SHALL
 BE PERMITTED.
 11.5.1.2 NOTIFICATION.
 (A) FIRE-WARNING EQUIPMENT FOR DWELLING UNITS SHALL
 PROVIDE A SOUND THAT IS AUDIBLE IN ALL OCCUPIABLE
 DWELLING AREAS.
 (B) WHERE MORE THAN ONE SMOKE OR HEAT ALARM IS
 INSTALLED FOR NEW CONSTRUCTION, THEY SHALL BE ARRANGED
 SO THAT THE OPERATION OF ANY SMOKE OR HEAT ALARM CAUSES
 THE ALARM IN ALL SMOKE AND HEAT ALARMS WITHIN THE
 DWELLING UNIT TO SOUND
  
 11.8.3* SMOKE DETECTORS AND SMOKE ALARMS. SMOKE ALARMS,
 SMOKE DETECTORS, DEVICES, COMBINATION OF DEVICES, AND
 EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER'S LISTING AND INSTRUCTIONS, AND UNLESS
 SPECIFICALLY LISTED FOR THE APPLICATION, SHALL COMPLY
 WITH REQUIREMENTS IN11.8.3.1 THROUGH11.8.3.5.
  
 3) NOTE: PLEASE SEE COPY OF FLORIDA STATUTES
 553.80(2)(B) WITH RESPECT TO REPEAT NOTES FOR CODE
 COMPLIANCE. THIS IS BEING GIVEN ONLY AS NOTICE AT THIS
 TIME.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-06 Cont ID  
Sent By dpalmer Date 2006-10-06 Time 16:44 Rev Time 0.00
Received By dpalmer Date 2006-10-06 Time 16:36 Sent To Z
Notes
2006-10-06 00:00:00**** UNSAT ****
  
 1) NOTE: PLEASE SEE FAC 61G17 AND FS
 472.025 AS THE SURVEY'S ARE REQUIRED TO
 BE SEALED WHEN SIGNED TO BE VALID.
  
 2) NOTE: PLEASE SEE ALL SEALS ON PLANS
 SHALL BE CLEAR AND VISABLE WITH ALL
 INFORMATION ON SAID SEAL AS REQUIRED PER
 FAC 61G1-16.003, FS 481.221
  
 3) NOTE: PLEASE SEE MISSING DINING
 AREA/BREAKFEST AREAS AND THE LIKE FOR
 CIRCUTING AND MIN 20A #12 CIRCUITS
 REQUIRED TO MEET 210.52B1, 220.16,
 210.11C1
  
 4) NOTE: PLEASE OCP ON 50A RANGE RECEPT
 SHALL NOT EXCEED RATINGS AS PERMITTED IN
 TABLES 220.21B3
  
 5) NOTE: PLEASE SEE OCP FOR AHU, SHALL
 MEET 424.3B FOR MIN 125%.
 PLEASE ADJUST.
  
 2) NOTE: PLEASE LIST THE OCP FOR THE
 BRANCH CIRCUIT TO THE CU.
  
  
 PLEASE SEE NOTES ONE AND TWO ARE
 REQUIRED FOR ALL.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-08-02 Cont ID  
Sent By adarroug Date 2007-08-02 Time 15:47 Rev Time 0.00
Received By adarroug Date 2007-08-02 Time 15:47 Sent To E
Notes
2007-08-02 15:47:38TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-04-23 Cont ID  
Sent By adarroug Date 2007-04-23 Time 14:53 Rev Time 0.00
Received By adarroug Date 2007-04-23 Time 14:53 Sent To E
Notes
2007-04-23 14:53:45TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-17 Cont ID  
Sent By adarroug Date 2007-01-17 Time 09:44 Rev Time 0.00
Received By adarroug Date 2007-01-17 Time 09:44 Sent To E
Notes
2007-01-17 09:44:54TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-04 Cont ID  
Sent By adarroug Date 2007-01-04 Time 12:25 Rev Time 0.00
Received By adarroug Date 2007-01-04 Time 12:25 Sent To Z
Notes
2007-01-04 12:25:27TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-20 Cont ID  
Sent By alange Date 2006-10-20 Time 08:15 Rev Time 0.00
Received By alange Date 2006-10-05 Time 09:37 Sent To  
Notes
2006-10-05 00:00:00TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-01-19 Cont ID  
Sent By tgordon Date 2007-01-19 Time 08:13 Rev Time 0.25
Received By tgordon Date 2007-01-19 Time 08:13 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-17 Cont ID  
Sent By tgordon Date 2006-10-17 Time 14:42 Rev Time 0.30
Received By tgordon Date 2006-10-17 Time 14:42 Sent To Z
Notes
2006-10-17 14:49:51*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04
 (2004) PER FBC 13-600.3.A .
  
 2) 10" RETURN AIR TRANSFER DUCT TO MASTER SUITE IS TO
 SMALL, SEE NOTE #3.
  
 3) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-08-14 Cont ID  
Sent By mperson Date 2007-08-14 Time 10:52 Rev Time 0.33
Received By mperson Date 2007-08-14 Time 10:52 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-05-10 Cont ID  
Sent By mperson Date 2007-05-10 Time 10:13 Rev Time 0.33
Received By mperson Date 2007-05-10 Time 10:13 Sent To B
Notes
2007-05-10 10:25:21DENIED 3RD TIME
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
  
 THE RESUBMITTED DRAWINGS ARE INCOMPLETE THE FOLLOWING
 IS REQUIRED FOR PLUMBING PLAN REVIEW TO MEET CODE
 COMPLIANCE:
  
 1. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-02-05 Cont ID  
Sent By jleech Date 2007-02-05 Time 07:25 Rev Time 0.00
Received By jleech Date 2007-02-05 Time 07:25 Sent To B
Notes
2007-02-05 07:27:23DENIED;
 SEE ELECTRICAL PLAN REVIEW NOTE # 1.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-10-14 Cont ID  
Sent By jleech Date 2006-10-14 Time 14:06 Rev Time 0.00
Received By jleech Date 2006-10-14 Time 14:06 Sent To Z
Notes
2006-10-14 14:08:32SEE ELECTRICAL PLAN REVIEW NOTES 1 AND 2.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2007-01-12 Cont ID  
Sent By mmclean Date 2007-01-12 Time 11:23 Rev Time 0.00
Received By mmclean Date 2007-01-12 Time 11:23 Sent To  
Notes
2007-01-12 11:29:38PROVISO: SHALL APPLY FOR A SEPARATE PERMIT FOR THE CBS
 WALLS.HEIGHT ALLOWED WITHIN THE 25FT SETBACK IS 4FT
 ONLY. SHALL PROVIDE EASEMENT APPROVAL FROM THE CITY OF
 WEST PALM BEACH UTILITY DEPT.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-10-18 Cont ID  
Sent By mmclean Date 2006-10-18 Time 11:16 Rev Time 0.00
Received By mmclean Date 2006-10-18 Time 11:16 Sent To B
Notes
2006-10-18 11:17:24DENIED,
 1. SEE ELECTRICAL NOTES 1 & 2.
 2. PLEASE PROVIDE THE DIMENSION OF THE PROPOSED
 DRIVEWAY (LENGTH & WIDTH).
  
 NOTE: MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE, WHICHEVER IS LESS WITHIN THE
 FIRST 25FT FRONT SETBACK.
  
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved