Plan Review Details - Permit 06100071
Plan Review Stops For Permit 06100071
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-10-23 Cont ID  
Sent By lursu Date 2006-10-23 Time 10:13 Rev Time 0.00
Received By lursu Date 2006-10-23 Time 10:13 Sent To PC
Notes
2006-10-23 10:18:01EXT # 0004 CAN BE USED FOR THIS UNIT 201
2006-10-22 19:40:56NEEDS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-15 Cont ID  
Sent By shill Date 2006-11-15 Time 10:27 Rev Time 0.00
Received By shill Date 2006-11-14 Time 14:39 Sent To  
Notes
2006-11-15 10:44:59****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB
 FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)INCLUDE FLORIDA BUILDING CODE 2004 EXISTING
 BUILDING CODE AS GOVERNING CODE AND DECLARE LEVEL OF
 ALTERATION.SEE FBC EB CHAPTER 3.
  
 2.)PROVIDE A SITE PLAN.NEW WINDOWS ARE BEING
 INSTALLED; MUST SHOW COMPLIANCE WITH FBC TABLE 704.8.
  
 3.)DECLARE BUILDING TYPE, INCLUDE A OR B, FBC CHAPTER
 6.
  
 4.)SUBMIT PRODUCT APPROVALS FOR THE WINDOWS AND
 STOREFRONT.PRODUCT APPROVALS ARE TO BE REVIEWED BY
 DESIGNER OF RECORD, FBC 106.3.3.
  
 5.)THE SEAL FOR FS1 IS NOT LEGIBLE, PLEASE RE-SEAL.
 CHECK ALL SHEETS; COMMENT MAY APPLY TO OTHER SHEETS AS
 WELL.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-22 Cont ID  
Sent By dpalmer Date 2006-10-22 Time 19:39 Rev Time 0.00
Received By dpalmer Date 2006-10-22 Time 18:03 Sent To  
Notes
2006-10-22 19:39:28***** UNSAT ******
  
 1) NOTE: PLEASE SEE FLORIDA STATUTES 471.025 AND
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001,.002 WHICH
 REQUIRES ALL SEALS ON SAID PLANS TO BE RAISED AND CLEAR
 AND VISABLE WITH ALL SAID INFORMATION REQUIRED ON SAID
 SEAL.
 PLEASE SEE M, P, FS SHEETS ARE NOT CLEAR.
 PLEASE ALSO SEE THE SAME STATUTES AND ADMINISTRATIVE
 SECTIONS ABOVE AS THE SIGNATURE OF THE ENGINEER OF
 RECORD SHALL BE THAT WHICH RECOGNIZED BY THIS OFFICE
 AND IS CURRENTLY ON FILE. PLEASE SEE PLANS ARE "NOT"
 SIGNED WITH SIGNATURE CURRENTLY ON FILE.
  
 2) NOTE: PLEASE SEEFS 471.023, FS 481.229(1)(C) AS A
 "DRAFTING/DESIGN" FIRM MAY NOT PRODUCE PLANS FOR SCOPE
 OF WORK AS SHOWN. PLEASE PROVIDE LICENSE INFORMATION
 FOR "TRONIX INC". PLEASE SEE SCOPE OF WORK SHOWN AND
 SUBMITTED IS REQUIRED TO BE DONE BY A LICENSED PE PER
 FS 471.003 (H)(2A).
 PLEASE SEE FAC 61G15-23.002
 IT IS CLEAR TO THIS OFFICE THAT PLANS ARE SIGNED DATED
 AND SEALED BY AN ENGINEER FOR THE ELECTRICAL SHEETS,
 HOWEVER THEY ARE PRODUCED BY WHAT APPEARS TO BE A
 DRAFTING FIRM AND THIS IS STATED ON SAID TITLE BLOCKS.
 NO CERTIFICATE OF AUTHORIZATION NUMBER COULD BE LOCATED
 FOR SAID FIRM NOR COULD WE LOCATE THE NAME ON A SEARCH
 WITH THE DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION FOR THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS. PLEASE KNOW THIS HAS BEEN VERIFIED WITH THE
 STATE INVESTIGATOR AND STATE PROSECUTING ATTORNEY.
 PLEASE ALSO SEE 471.025 (3).
  
 ** PLEASE KNOW AS THIS OFFICE HAS HAD SIMILAR COMMENTS
 AND INSTANCES FOR ABOVE ON PREVIOUS PROJECTS ON ONE OR
 MORE OF THE DESIGNERS ON PLANS,ONE COMPLETE SET OF
 PLANS WILL BE RETAINED BY THIS OFFICE AT THIS TIME FOR
 FILE.
 **** IMPORTANT****
 THE ABOVE COMMENTS 1&2 ARE REQUIRED FOR ALL SHEETS AND
 FOR ALL TRADES WHETHER OR NOT COMMENTS ARE MADE BY
 OTHER REVIEWER(S).
  
 3) NOTE: PLEASE BE SURE TO INCLUDE ALL RELEVANT CODES
 ON PLANS FOR DESIGN AT HAND. PLEASE SEE THE FOLLOWING
 AT A MINIMUM WILL BE REQUIRED: 2002 NFPA-70, 2002
 NFPA-110, NFPA-72, 2003 NFPA-101, 2004 FBC.
  
 4) NOTE: PLEASE SUBMIT AND PROVIDE ALL MANUFACTURES
 SPECS/CUT SHEETS FOR THE GENERATOR/SUB-BASE FUEL TANK/
 AND ATS DEVICE FOR REVIEW.
 PLEASE SEE 90.7, 110.3, ETC
 THERE ARE CODE COMPLIANCE ITEMS WHICH CAN NOT BE
 VERIFIED AT THIS TIME AS THESE ITEMS HAVE NOT BEEN
 SUBMITTED. PLEASE ALSO SEE OTHER NOTES WHICH WILL
 DIRECTLY AFFECT THIS.
  
 5) NOTE: PLEASE INDICATE IF GENERATOR WILL BE A
 SEPARATELY DERIVED SYSTEMM? PLEASE KNOW, IT IS KNOWN
 FROM THIS OFFICE THAT ALL KOHLER GEN'S SHIPPED FROM THE
 MANUFACTURE COME WIRED FOR "SD" SYSTEMS. IF INDEED THIS
 IS HOW SYSTEM WILL BE INSTALLED PLEASE BE SURE TO SHOW
 AND INDICATE GROUNDING ELECTRODE SYSTEM AT THE GEN FOR
 A SD SYSTE, 250.50, 250.56 ETC.
 250.20, 250.30, ETC.
 PLEASE ALSO BE SURE TO UPDATE THE ATS AS THIS WILL BE
 REQUIRED TO BE A 4POLE UNIT. PLEASE BE SURE TO ADJUST
 PLANS AND SPECS ACCORDINGLY.
 PLEASE SEE RISER AS SHOWN DOES NOT INDICATE A SD
 SYSTEM.? PLEASE SEE MANUFACTURES SPECS/CUT SHEETS.
  
 6) NOTE: PLEASE SEE PLANS, BY NOTES WHICH IS STATED ON
 PLANS AND HOW SYSTEM IS SHOWN, THIS IS A "LEGALLY
 REQUIRED" STANDBY SYSTEM. PLEASE SEE ALL REQUIREMENTS
 IN 701. PLEASE BE SURE TO PROVIDE ALL MIN ON-SITE FUEL
 REQUIREMENTS.
 IF NOT A LSS. PLEASE ADJUST LIGHTING ETC. PLEASE SEE
 NEXT COMMENT.
  
 7) NOTE: PLEASE PROVIDE MINIMUM REQUIRED BATTERY BACK
 UP FIXTURES FOR ALL MEANS OF EGRESSS AREAS WHICH IS
 REQUIRED TO PROVIDE A MIN OF 1FT CANDLE UNDER EMERGENCY
 POWER. PLEASE SEE NFPA-101 7.8, 7.9.2.2.
 PLEASE UPDATE FIXTURE SCHEDULE AS SOME SORT OF BATTERY
 BACK UP FIXTURES WILL BE REQUIRED FOR EM LTS. PLEASE
 SEE 700.12E FOR CIRCUITING OF FIXTURES TO THE NORMAL
 LIGHTING CIRCUITS IN ANY ONE AREA. NO SINGLE MEANS OF
 THE TRIPPINGOF A SWITCH/BREAKER OR OVER-CURRENT
 PROTECTIVE DEVICE CAN LEAVE ANY ONE AREA IN TOTAL
 DARKNESS.
  
 8) NOTE: PLEASE SEE FBC 11-4.28.1, 11-4.28.3(4) AS MIN
 LIGHTING LEVELS IN ALL AREAS REQUIRED AT A MIN OF 75
 CANDELA. PLEASE ADJUST AS SOME AREAS DO NOT MEET THIS.
  
 9) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1,
 .1.2 AND .1.3 FOR MINLIGHTING CONTROLS FOR NEW BUILD
 OUT.
 PLEASE PROVIDE/SHOW SYSTEM.
 PLEASE PROVIDE SCHEDULING.
 PLEASE INDICATE ALL DEVICES REQUIRED IN SEPARATE
 SPACES.
 PLEASE SEE REQUIRMENTS FOR DEVICES LOCATED AT THE
 LOCATION OF INGRESS/EGRES FOR THE OCCUPANT TO OVER RIDE
 ANY TIME OF DAY SCHEDULED SYSTEM.
 PLEASE PROVIDE MAX OVER RIDE DEVICE TIMES AND LIST
 DEVICES WHICH WILL BE USED ON SYMBOL LEGEND. PLEASE
 KNOW A MAX OF 30MINS FOR OCCUPANT TYPE DEVICES AND A
 MAX OF 4HRS FOR TIMER TYPE DEVICES.
 PLEASE PROVIDE MIN PERFORMANCE CALCULATIONS FOR
 LIGHTING LEVELS. PLEASE SEE 13-415.2, 13-415.2.ABC.1,
 PLEASE SEE SPACE BY SPACE METHODS AS SOME AREAS CAN NOT
 BE FIGURED INTO ALL OFFICE AREA. PLEASE SEE THERE ARE
 SOME EXCEPTIONS FOR MEANS OF EGRESS ETC.
 PLEASE SEE TABLES 415.2.B ETC
  
 10) NOTE: PLEASE SEE MISSING DISCONNECTING MEANS
 REQUIRED FOR FEEDERS FROM GENERATOR. PLEASE SEE THIS
 SHALL BE LOCATED IN CLOSE PROXIMITY OF THE EXISTING NEW
 MAIN FOR SPACE. PLEASE SEE 225.31-225.39.
 PLEASE SEE 701 OR 702 AS SYSTEM AS SHOWN IS NOT YET
 CLEAR WHICH IT WILL BE.
  
 11) NOTE: PLEASE701.6 OR 702.5 AS THE SYSTEM
 INCLUDING THE ATS SHALL ALL BE RATED FOR THE AVAILABLE
 FAULT CURRENT FROM NORMAL AND EM SIDE.
 PLEASE SEE SPECS AND FAULT CURRENT CALCULATIONS WILL BE
 REQUIRED TO BE NOTED. 110.9, 240.12
 PLEASE ALSO SEE NFPA-110 2002 "6.5.2 SHORT CIRCUIT
 CURRENT. THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT
 FROM BOTH THE UTILITY SOURCE AND THE EMERGENCY ENERGY
 SOURCE SHALL BE EVALUATED FOR ABILITY TO SATISFY THIS
 COORDINATION CAPABILITY."
  
 12) NOTE: PLEASE PROVIDE AIC RATINGS FOR ALL NEW
 SERVICE EQUIPMENT. PANELS INDICATE 10K, HOWEVER NOTHING
 SHOWN FOR MAIN? PLEASE SEE 240.12 FOR COORDINATION OF
 SYSTEMS. 110.9
  
 13) NOTE: PLEASE PROVIDE INFORMATION ON RISER AS RISER
 DOES NOT INDICATE OF THERE IS A MAIN DISCONNECT LOCATED
 AHEAD OF THE NEW METER AND MAIN DISCONNECT. PLEASE SEE
 250.6, 250.24, AS AN "EQUIPMENT GROUNDING CONDUCTOR" IS
 BEING SHOWN AHEAD OF METER WHICHIS NOT PERMITTED.
 PLEASE KNOW HOWEVER IF INDEED THERE IS A MAIN LOCATED
 AHEAD OF THIS METER AND MAIN, PLEASE NOTE AND INDICATE
 A "FLOATING NEUTRAL KIT REQUIRED" AT METER TO
 ALLEAVIATE OBJECTIONABLE CURRENTS.250.6
  
 14) NOTE: PLEASE SEE THAT PANEL SCHEDULE SHALL BE
 SPECIFIC TO ALL AREAS AND ROOMS FOR BRANCH CIRCUITING
 AS SHOWN. PLEASE SEE "GEN LTS" AND GEN RECEPTS' ARE NOT
 SPECIFIC TO ROOMS AND AREAS. PLEASE SEE 408.4. IT IS
 KNOWN TO THE OFFICE THAT DURING CONSTRUCTION CIRCUITING
 MAY CHANGE, HOWEVER THIS CAN BE REVISED AT A LATER DATE
 ALONG WITH ANY OTHER REVISIONS WHICH MAY TAKE PLACE.
 THIS IS REQUIRED AT THIS TIME> IE: ACCOUNTING RECEPTS,
 GEN MGR LTS, BATH RECEPTS ETC.
  
 15) NOTE: PLEASE SEE RISER IS SHOWING THE SAME FEEDERS
 FORM THE HV PANEL "A" TO TRANSFORMER AS THE FEEDERS
 FROM THE TRANSFORMER TO THE PANEL "A1 ". PLEASE SEE
 THIS IS A SD SYSTEM STEP DOWN UNIT. 250.30, 250.20 ETC
  
 NEUTRAL IS NOT INSTALLED TO TRANSFORMER).
  
 16) NOTE: PLEASE SEE BUILDING REVIEW NOTES AS THE
 SPECIFICATIONS FOR THE GENERATOR SLAB SHALL BE PROVIDED
 AT THIS TIME WITH ALL INFORMATION REQUIRED FOR
 STRUCTURAL INTEGRITYOF SYSTEM'S REQUIRED PER NFPA-110
 CHAPTER 7.
  
 17) NOTE: PLEASE KNOW AS THERE IS MISSING INFORMATION
 REQUIRED AT THIS TIME FOR REVIEW, THERE MAY BE COMMENTS
 ON NEXT REVIEW.
  
 ** PLEASE BE SURE TO SEE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT THE ELECTRICLA PLANS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
2006-10-22 18:18:52IN ELEC FOR REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-11-30 Cont ID  
Sent By mawillia Date 2006-11-30 Time 10:09 Rev Time 0.00
Received By mawillia Date 2006-11-30 Time 09:24 Sent To  
Notes
2006-11-30 10:38:03*****DENIED*****
  
  
  
 1.THE NUMERICAL ADDRESS OF THE JOB SITE SHALL BE IN
 THE TITLE BLOCK OF EACH PLAN SHEET, SPECIFICATION
 PAPERWORK, OR ANY OTHER INFORMATIONAL DOCUMENT WHICH IS
 SUBMITTED FOR PLAN REVIEW.IF ADDITIONAL INFORMATION
 IS NEEDED CONCERNING THE ADDRESS, CONTACT LILI URSA AT
 561-822-1239.
  
 2.ON SHEET LS-1 IN THE FIRE EXTINGUISHER CABINET
 NOTE, CLARIFY THE WORDING (AFETY) WHICH WAS USED.
  
 3.PROVIDE INTERIOR FINISH CLASSIFICATION.INTERIOR
 FINISH CLASSIFICATION IN EXITS AND EXIT ACCESS
 CORRIDORS SHALL BE CLASS "A" OR CLASS "B".
  
 4.SEAL MISSING OR UNRECOGNIZABLE ON SHEETS FS-1 AND
 FS-2.
  
 5.HOW WILL THE SCOPE OF WORK AFFECT THE COMPONENTS OF
 THE FIRE ALARM SYSTEM?IF THE FIRE ALARM SYSTEM IS
 MODIFIED, SEPARATE SHOP DRAWING/PLANS ARE REQUIRED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-30 Cont ID  
Sent By mawillia Date 2006-11-30 Time 10:09 Rev Time 0.00
Received By mawillia Date 2006-10-05 Time 10:51 Sent To  
Notes
2006-10-19 16:28:15TO "COMM" BD#51
2006-10-05 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-25 Cont ID  
Sent By tgordon Date 2006-10-25 Time 15:45 Rev Time 0.30
Received By tgordon Date 2006-10-25 Time 15:45 Sent To  
Notes
2006-10-25 15:47:33*** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTE #1, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-11-27 Cont ID  
Sent By kstevens Date 2006-11-27 Time 09:34 Rev Time 0.00
Received By kstevens Date 2006-11-27 Time 09:34 Sent To  
Notes
2006-11-27 11:25:52DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. COVER SHEET & MECHANICAL SHEETS. LNI CONSULTING
 ENGINEERS ADDRESS DOES NOT REFLECT THE ADDRESS
 INFORMATION ON RECORD ON THE DBPR WEBSITE. PLEASE
 CORRELATE ADDRESS INFORMATION. FAC 61G15-23.002(2) & FS
 471.025 (SEE ATTACHED SHEET FROM DBPR WEBSITE)
  
 2. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 ALL THE REQUIREMENTS OF SECTION 11-4.15 AND ALL
 SUBSECTIONS.
  
 3. SUBMIT A DETAIL FOR THE ACCESSIBLE UNINAL. SHOW THE
 FOLLOWING:
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.18.4 FLUSH CONTROLS
  
 4. SHT A-4 ACCESSIBLE BATHROOM ELEVATIONS. PLEASE SHOW
 COMPLIANCE WITH SECTION 11-4.19.5 FAUCETS.
  
 5. SUBMIT A DETAIL FOR THE CONFERENCE/BREAK ROOM SINK
 SHOWING COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. (FORWARD APPROACH MAXIMUM 19" UNDERNEATH
 THE SINK REQUIRED. CABINET DOORS ARE NOT APPROVED IN
 THE CLEAR FLOOR SPACE.).
  
 6. PLUMBING SHEETS. AN EMBOSSED SEAL SHALL IMPRESS ALL
 INFORMATION REQUIRED ON EACH SHEET PER FAC
 61G15-23.002(1)(2) & FS 471.025. NO INFORMATION CAN BE
 GLEANED FROM THE SEAL TO DETERMINE IF THE SEAL IS
 APPROIATE. PLEASE RESEAL THE PLANS.
  
 7. SHT P-1 IN THE INSTALLATION OR REMOVAL OF ANY PART
 OF A DRAINAGE SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 SECTION 704.5. NOTE STATES TO "CAP& CONCEAL ALL
 PLUMBING STUBS OUT OF THE LINE OF SITE". CHANGE NOTE TO
 ENSURE NOT DEAD ENDS ARE LEFT AT THE DEMO PORTION OF
 THE WORK.
  
 8. SHT P-1 WOMENS TOILET ROOM SHOWS ONE LAV OUTSIDE THE
 ACCESSIBLE STALL, BUT THE SANT SHOW WASTE LINES TO TWO
 LAVS. PLEASE CORRELATE FLOOR PLAN AND SANT PIPING.
 SECTION 106..1.1.
  
 9. SHT P-2 WATER RISER DIAGRAM AND PLUMBING LEGEND
 INDICATE AIR CHAMBERS. AIR CHAMBERS ARE NOT APPROVED.
 SECTION 604.9 & PDI-WH 201. DELETE FROM RISER AND
 LEGEND. WATER HAMMER ARRESTORS ARE REQUIRED TO BE
 INSTALLED NEAR THE FIXTURES WITH QUICK CLOSING VALVES,
 (ICE MAKERS, DISH WASHERS, WASH MACHINES ETC.), PER
 SECTION 604.9.
  
 10. SHT P-2 WATER RISER DIAGRAM IS INDICATING THE
 URINAL (P-3H) BEING PIPED TO THE WOMENS TOILET ROOM.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 11. SHT P-2 SEPARATE GAS PERMIT REQUIRED. SUBMIT THE
 FOLLOWING INFORMATION REQUIRED FOR GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - LENGTHS NOT SHOWN.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. INCLUDING
 INSTALLATION SHEETS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2006-11-01 Cont ID  
Sent By eschneid Date 2006-11-01 Time 16:53 Rev Time 0.00
Received By eschneid Date 2006-11-01 Time 16:53 Sent To  
Notes
2006-11-01 16:58:10FAILED
  
 1) THE GENERATOR AND ENCLOSURE SHALL BE APPROVED BY
 ZONING DIVISION THROUGH A MINOR PD AMENDMENT PRIOR TO
 APPROVAL OF THE BUILDING PERMIT.
  
 2) HOW WILL THE GENERATOR BE NOISE BAFFLED?
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.
2006-10-22 18:03:41NEEDS, NEW OUTDOOR GENERATOR