2006-10-22 19:39:28 | ***** UNSAT ****** |
| |
| 1) NOTE: PLEASE SEE FLORIDA STATUTES 471.025 AND |
| FLORIDA ADMINISTRATIVE CODE 61G15-23.001,.002 WHICH |
| REQUIRES ALL SEALS ON SAID PLANS TO BE RAISED AND CLEAR |
| AND VISABLE WITH ALL SAID INFORMATION REQUIRED ON SAID |
| SEAL. |
| PLEASE SEE M, P, FS SHEETS ARE NOT CLEAR. |
| PLEASE ALSO SEE THE SAME STATUTES AND ADMINISTRATIVE |
| SECTIONS ABOVE AS THE SIGNATURE OF THE ENGINEER OF |
| RECORD SHALL BE THAT WHICH RECOGNIZED BY THIS OFFICE |
| AND IS CURRENTLY ON FILE. PLEASE SEE PLANS ARE "NOT" |
| SIGNED WITH SIGNATURE CURRENTLY ON FILE. |
| |
| 2) NOTE: PLEASE SEEFS 471.023, FS 481.229(1)(C) AS A |
| "DRAFTING/DESIGN" FIRM MAY NOT PRODUCE PLANS FOR SCOPE |
| OF WORK AS SHOWN. PLEASE PROVIDE LICENSE INFORMATION |
| FOR "TRONIX INC". PLEASE SEE SCOPE OF WORK SHOWN AND |
| SUBMITTED IS REQUIRED TO BE DONE BY A LICENSED PE PER |
| FS 471.003 (H)(2A). |
| PLEASE SEE FAC 61G15-23.002 |
| IT IS CLEAR TO THIS OFFICE THAT PLANS ARE SIGNED DATED |
| AND SEALED BY AN ENGINEER FOR THE ELECTRICAL SHEETS, |
| HOWEVER THEY ARE PRODUCED BY WHAT APPEARS TO BE A |
| DRAFTING FIRM AND THIS IS STATED ON SAID TITLE BLOCKS. |
| NO CERTIFICATE OF AUTHORIZATION NUMBER COULD BE LOCATED |
| FOR SAID FIRM NOR COULD WE LOCATE THE NAME ON A SEARCH |
| WITH THE DEPARTMENT OF BUSINESS AND PROFESSIONAL |
| REGULATION FOR THE FLORIDA BOARD OF PROFESSIONAL |
| ENGINEERS. PLEASE KNOW THIS HAS BEEN VERIFIED WITH THE |
| STATE INVESTIGATOR AND STATE PROSECUTING ATTORNEY. |
| PLEASE ALSO SEE 471.025 (3). |
| |
| ** PLEASE KNOW AS THIS OFFICE HAS HAD SIMILAR COMMENTS |
| AND INSTANCES FOR ABOVE ON PREVIOUS PROJECTS ON ONE OR |
| MORE OF THE DESIGNERS ON PLANS,ONE COMPLETE SET OF |
| PLANS WILL BE RETAINED BY THIS OFFICE AT THIS TIME FOR |
| FILE. |
| **** IMPORTANT**** |
| THE ABOVE COMMENTS 1&2 ARE REQUIRED FOR ALL SHEETS AND |
| FOR ALL TRADES WHETHER OR NOT COMMENTS ARE MADE BY |
| OTHER REVIEWER(S). |
| |
| 3) NOTE: PLEASE BE SURE TO INCLUDE ALL RELEVANT CODES |
| ON PLANS FOR DESIGN AT HAND. PLEASE SEE THE FOLLOWING |
| AT A MINIMUM WILL BE REQUIRED: 2002 NFPA-70, 2002 |
| NFPA-110, NFPA-72, 2003 NFPA-101, 2004 FBC. |
| |
| 4) NOTE: PLEASE SUBMIT AND PROVIDE ALL MANUFACTURES |
| SPECS/CUT SHEETS FOR THE GENERATOR/SUB-BASE FUEL TANK/ |
| AND ATS DEVICE FOR REVIEW. |
| PLEASE SEE 90.7, 110.3, ETC |
| THERE ARE CODE COMPLIANCE ITEMS WHICH CAN NOT BE |
| VERIFIED AT THIS TIME AS THESE ITEMS HAVE NOT BEEN |
| SUBMITTED. PLEASE ALSO SEE OTHER NOTES WHICH WILL |
| DIRECTLY AFFECT THIS. |
| |
| 5) NOTE: PLEASE INDICATE IF GENERATOR WILL BE A |
| SEPARATELY DERIVED SYSTEMM? PLEASE KNOW, IT IS KNOWN |
| FROM THIS OFFICE THAT ALL KOHLER GEN'S SHIPPED FROM THE |
| MANUFACTURE COME WIRED FOR "SD" SYSTEMS. IF INDEED THIS |
| IS HOW SYSTEM WILL BE INSTALLED PLEASE BE SURE TO SHOW |
| AND INDICATE GROUNDING ELECTRODE SYSTEM AT THE GEN FOR |
| A SD SYSTE, 250.50, 250.56 ETC. |
| 250.20, 250.30, ETC. |
| PLEASE ALSO BE SURE TO UPDATE THE ATS AS THIS WILL BE |
| REQUIRED TO BE A 4POLE UNIT. PLEASE BE SURE TO ADJUST |
| PLANS AND SPECS ACCORDINGLY. |
| PLEASE SEE RISER AS SHOWN DOES NOT INDICATE A SD |
| SYSTEM.? PLEASE SEE MANUFACTURES SPECS/CUT SHEETS. |
| |
| 6) NOTE: PLEASE SEE PLANS, BY NOTES WHICH IS STATED ON |
| PLANS AND HOW SYSTEM IS SHOWN, THIS IS A "LEGALLY |
| REQUIRED" STANDBY SYSTEM. PLEASE SEE ALL REQUIREMENTS |
| IN 701. PLEASE BE SURE TO PROVIDE ALL MIN ON-SITE FUEL |
| REQUIREMENTS. |
| IF NOT A LSS. PLEASE ADJUST LIGHTING ETC. PLEASE SEE |
| NEXT COMMENT. |
| |
| 7) NOTE: PLEASE PROVIDE MINIMUM REQUIRED BATTERY BACK |
| UP FIXTURES FOR ALL MEANS OF EGRESSS AREAS WHICH IS |
| REQUIRED TO PROVIDE A MIN OF 1FT CANDLE UNDER EMERGENCY |
| POWER. PLEASE SEE NFPA-101 7.8, 7.9.2.2. |
| PLEASE UPDATE FIXTURE SCHEDULE AS SOME SORT OF BATTERY |
| BACK UP FIXTURES WILL BE REQUIRED FOR EM LTS. PLEASE |
| SEE 700.12E FOR CIRCUITING OF FIXTURES TO THE NORMAL |
| LIGHTING CIRCUITS IN ANY ONE AREA. NO SINGLE MEANS OF |
| THE TRIPPINGOF A SWITCH/BREAKER OR OVER-CURRENT |
| PROTECTIVE DEVICE CAN LEAVE ANY ONE AREA IN TOTAL |
| DARKNESS. |
| |
| 8) NOTE: PLEASE SEE FBC 11-4.28.1, 11-4.28.3(4) AS MIN |
| LIGHTING LEVELS IN ALL AREAS REQUIRED AT A MIN OF 75 |
| CANDELA. PLEASE ADJUST AS SOME AREAS DO NOT MEET THIS. |
| |
| 9) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1, |
| .1.2 AND .1.3 FOR MINLIGHTING CONTROLS FOR NEW BUILD |
| OUT. |
| PLEASE PROVIDE/SHOW SYSTEM. |
| PLEASE PROVIDE SCHEDULING. |
| PLEASE INDICATE ALL DEVICES REQUIRED IN SEPARATE |
| SPACES. |
| PLEASE SEE REQUIRMENTS FOR DEVICES LOCATED AT THE |
| LOCATION OF INGRESS/EGRES FOR THE OCCUPANT TO OVER RIDE |
| ANY TIME OF DAY SCHEDULED SYSTEM. |
| PLEASE PROVIDE MAX OVER RIDE DEVICE TIMES AND LIST |
| DEVICES WHICH WILL BE USED ON SYMBOL LEGEND. PLEASE |
| KNOW A MAX OF 30MINS FOR OCCUPANT TYPE DEVICES AND A |
| MAX OF 4HRS FOR TIMER TYPE DEVICES. |
| PLEASE PROVIDE MIN PERFORMANCE CALCULATIONS FOR |
| LIGHTING LEVELS. PLEASE SEE 13-415.2, 13-415.2.ABC.1, |
| PLEASE SEE SPACE BY SPACE METHODS AS SOME AREAS CAN NOT |
| BE FIGURED INTO ALL OFFICE AREA. PLEASE SEE THERE ARE |
| SOME EXCEPTIONS FOR MEANS OF EGRESS ETC. |
| PLEASE SEE TABLES 415.2.B ETC |
| |
| 10) NOTE: PLEASE SEE MISSING DISCONNECTING MEANS |
| REQUIRED FOR FEEDERS FROM GENERATOR. PLEASE SEE THIS |
| SHALL BE LOCATED IN CLOSE PROXIMITY OF THE EXISTING NEW |
| MAIN FOR SPACE. PLEASE SEE 225.31-225.39. |
| PLEASE SEE 701 OR 702 AS SYSTEM AS SHOWN IS NOT YET |
| CLEAR WHICH IT WILL BE. |
| |
| 11) NOTE: PLEASE701.6 OR 702.5 AS THE SYSTEM |
| INCLUDING THE ATS SHALL ALL BE RATED FOR THE AVAILABLE |
| FAULT CURRENT FROM NORMAL AND EM SIDE. |
| PLEASE SEE SPECS AND FAULT CURRENT CALCULATIONS WILL BE |
| REQUIRED TO BE NOTED. 110.9, 240.12 |
| PLEASE ALSO SEE NFPA-110 2002 "6.5.2 SHORT CIRCUIT |
| CURRENT. THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT |
| FROM BOTH THE UTILITY SOURCE AND THE EMERGENCY ENERGY |
| SOURCE SHALL BE EVALUATED FOR ABILITY TO SATISFY THIS |
| COORDINATION CAPABILITY." |
| |
| 12) NOTE: PLEASE PROVIDE AIC RATINGS FOR ALL NEW |
| SERVICE EQUIPMENT. PANELS INDICATE 10K, HOWEVER NOTHING |
| SHOWN FOR MAIN? PLEASE SEE 240.12 FOR COORDINATION OF |
| SYSTEMS. 110.9 |
| |
| 13) NOTE: PLEASE PROVIDE INFORMATION ON RISER AS RISER |
| DOES NOT INDICATE OF THERE IS A MAIN DISCONNECT LOCATED |
| AHEAD OF THE NEW METER AND MAIN DISCONNECT. PLEASE SEE |
| 250.6, 250.24, AS AN "EQUIPMENT GROUNDING CONDUCTOR" IS |
| BEING SHOWN AHEAD OF METER WHICHIS NOT PERMITTED. |
| PLEASE KNOW HOWEVER IF INDEED THERE IS A MAIN LOCATED |
| AHEAD OF THIS METER AND MAIN, PLEASE NOTE AND INDICATE |
| A "FLOATING NEUTRAL KIT REQUIRED" AT METER TO |
| ALLEAVIATE OBJECTIONABLE CURRENTS.250.6 |
| |
| 14) NOTE: PLEASE SEE THAT PANEL SCHEDULE SHALL BE |
| SPECIFIC TO ALL AREAS AND ROOMS FOR BRANCH CIRCUITING |
| AS SHOWN. PLEASE SEE "GEN LTS" AND GEN RECEPTS' ARE NOT |
| SPECIFIC TO ROOMS AND AREAS. PLEASE SEE 408.4. IT IS |
| KNOWN TO THE OFFICE THAT DURING CONSTRUCTION CIRCUITING |
| MAY CHANGE, HOWEVER THIS CAN BE REVISED AT A LATER DATE |
| ALONG WITH ANY OTHER REVISIONS WHICH MAY TAKE PLACE. |
| THIS IS REQUIRED AT THIS TIME> IE: ACCOUNTING RECEPTS, |
| GEN MGR LTS, BATH RECEPTS ETC. |
| |
| 15) NOTE: PLEASE SEE RISER IS SHOWING THE SAME FEEDERS |
| FORM THE HV PANEL "A" TO TRANSFORMER AS THE FEEDERS |
| FROM THE TRANSFORMER TO THE PANEL "A1 ". PLEASE SEE |
| THIS IS A SD SYSTEM STEP DOWN UNIT. 250.30, 250.20 ETC |
| |
| NEUTRAL IS NOT INSTALLED TO TRANSFORMER). |
| |
| 16) NOTE: PLEASE SEE BUILDING REVIEW NOTES AS THE |
| SPECIFICATIONS FOR THE GENERATOR SLAB SHALL BE PROVIDED |
| AT THIS TIME WITH ALL INFORMATION REQUIRED FOR |
| STRUCTURAL INTEGRITYOF SYSTEM'S REQUIRED PER NFPA-110 |
| CHAPTER 7. |
| |
| 17) NOTE: PLEASE KNOW AS THERE IS MISSING INFORMATION |
| REQUIRED AT THIS TIME FOR REVIEW, THERE MAY BE COMMENTS |
| ON NEXT REVIEW. |
| |
| ** PLEASE BE SURE TO SEE COMMENTS FROM OTHER TRADES |
| WHICH MAY AFFECT THE ELECTRICLA PLANS. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
| |
| |
| |
2006-10-22 18:18:52 | IN ELEC FOR REVIEW. |