Plan Review Details - Permit 06100053
Plan Review Stops For Permit 06100053
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-10-19 Cont ID  
Sent By btrobaug Date 2006-10-19 Time 12:40 Rev Time 0.33
Received By btrobaug Date 2006-10-19 Time 12:35 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-11 Cont ID  
Sent By btrobaug Date 2006-10-11 Time 17:43 Rev Time 0.33
Received By btrobaug Date 2006-10-11 Time 17:31 Sent To PC
Notes
2006-10-11 17:34:58PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5.
  
 2}ALL INFORMATION/DRAWINGS/SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPON-
 SIBLE FOR THE DESIGN. SECTION 106.3.4.3.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
 FAX/:561/805-6676

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-18 Cont ID  
Sent By adarroug Date 2006-10-18 Time 10:10 Rev Time 0.00
Received By adarroug Date 2006-10-18 Time 10:10 Sent To E
Notes
2006-10-18 10:10:45TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-11 Cont ID  
Sent By btrobaug Date 2006-10-11 Time 17:31 Rev Time 0.00
Received By btrobaug Date 2006-10-05 Time 13:08 Sent To E
Notes
2006-10-05 00:00:00TO "E" BOX