Plan Review Details - Permit 06100032
Plan Review Stops For Permit 06100032
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-10-16 Cont ID  
Sent By lursu Date 2006-10-16 Time 10:47 Rev Time 0.00
Received By lursu Date 2006-10-16 Time 10:47 Sent To PC
Notes
2006-10-16 10:47:44EXT#0009 IS OK TO USE FOR 2ND FLOOR , JUST MAKE A NOTE
 ON THE PERMIT
2006-10-13 07:57:47NEEDS FLR/SUIT UNIT #

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-08-20 Cont ID  
Sent By rmcdouga Date 2008-08-20 Time 10:46 Rev Time 0.00
Received By rmcdouga Date 2008-08-20 Time 10:46 Sent To  
Notes
2008-08-20 10:51:44REVISED SHEETS A1.2,A1.5, A4.6 AND A6.2.1 ARE OK WITH
 PROVISO FOR KNEE SPACE AT BREAK ROOM SINK TO COMPLY
 WITH FBC 11-4.24.3. SEE NOTE ON SHEET A6.2.1.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-10-12 Cont ID  
Sent By rmcdouga Date 2006-10-12 Time 12:48 Rev Time 0.00
Received By rmcdouga Date 2006-10-12 Time 12:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2007-09-13 Cont ID  
Sent By dpalmer Date 2007-09-13 Time 14:13 Rev Time 0.00
Received By dpalmer Date 2007-09-13 Time 14:13 Sent To  
Notes
2007-09-13 14:14:01RE-STAMP FOR INSPECTIONS

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2007-09-07 Cont ID  
Sent By dpalmer Date 2007-09-07 Time 19:41 Rev Time 0.00
Received By dpalmer Date 2007-09-07 Time 19:27 Sent To PC
Notes
2007-09-07 19:45:08** DENIED REVISIONS **
  
 1) NOTE: PLEASE SEE THE REVISIONS SUBMITTED ARE
 ACTUALLY ALREADYON FILE.
 PLEASE SUBMIT REVISED PLANS IF INDEED THAT IS THE
 INTENT.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-07-23 Cont ID  
Sent By dpalmer Date 2007-07-23 Time 10:56 Rev Time 0.00
Received By dpalmer Date 2007-07-23 Time 10:51 Sent To PC
Notes
2007-07-23 10:57:02REV FOR 2FLR LIGHTING CONTROLS

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-03-13 Cont ID  
Sent By dpalmer Date 2007-03-13 Time 11:11 Rev Time 0.00
Received By dpalmer Date 2007-03-13 Time 11:11 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-02-15 Cont ID  
Sent By dpalmer Date 2007-02-15 Time 09:36 Rev Time 0.00
Received By dpalmer Date 2007-02-15 Time 09:36 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-02-07 Cont ID  
Sent By dpalmer Date 2007-02-07 Time 15:36 Rev Time 0.00
Received By dpalmer Date 2007-02-07 Time 15:36 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-01-10 Cont ID  
Sent By dpalmer Date 2007-01-10 Time 08:39 Rev Time 0.00
Received By dpalmer Date 2007-01-10 Time 07:50 Sent To  
Notes
2007-01-10 08:40:48SEQUENCE OF OPERATION FOR SENTRY DEVICES, ON E-4.2 OK,
 STAMPED ELEC.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-13 Cont ID  
Sent By dpalmer Date 2006-10-13 Time 07:19 Rev Time 0.00
Received By dpalmer Date 2006-10-13 Time 07:02 Sent To  
Notes
2006-10-13 07:19:21**** UNSAT ***
  
  
 1) NOTE: PLEASE SEE FBC CHAPTER 13 13-415.1.ABC.1.1,
 .1.2 AND .1.3.
 PLEASE ALSO SEE 13-415.2.ABC.1. PLEASE SEE THIS SPACE
 WAS A "SHELL" SPACE AND IS NOW BEING BUILT OUT UNDER
 THE 2004 FBC. PLEASE ADJUST AS NEEDED.
  
 2) NOTE: PLEASE VERIFY THE EXISTING EXIT LT BEING SHOWN
 FROM SPACE LEADING TO STAIR TOWER. PLEASE KNOW, THE
 CIRCUITING SHALL MEET 700.12E. PLEASE SHOW.
  
 3) NOTE: PLEASE CLARIFY THE PANEL SCHEDULE MENTIONS A
 "RECEPT" FOR THE INSTA-HOT. PLEASE SEE 430.30, 430.31
 ETC AS LOAD OF THIS SIZE WHEN UNIT IS REQUIRED TO
 CONTAIN A DISCONNECT , A PLUG MAY NOT BE USED. PLEASE
 ALSO VERIFY IF THE DISCONNECTING MEANS CONTAINS OCP, IF
 SO ,PLEASE SEE 110.26.
  
 4) NOTE: PLEASE SEE PLANS ARE CALLING THE ROOM WHERE
 THE ELECTRICAL PANELS ARE LOCATED AS "IT" ROOM?? PLEASE
 VERIFY AS IF THIS IS INDEED GOING TO BE AN "IT" ROOM,
 PLEASE SEE NFPA-75, AND NFPA-70 645 FOR REQUIREMENTS.
 PLEASE SEE CHAPTER TWO OF 75 AS TO DEFINITION AND
 CHARACTERISTICS OF SUCH A ROOM.
  
 5) NOTE: PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK
 SHALL BE BASED ON ALL LABOUR AND MATERIALS EVEN IF
 OWNER SUPPLIED.
 FBC 108.3
 PLEASE SEE $25K IS WAY LOW. PLEASE KNOW, USING TABLES
 BASED ON THE FBCONE WILL BE ASSESSED. FEES WILL BE
 OWED.
  
 6) NOTE: PLEASE KNOW, THIS INTERIOR BUILD OUT WILL
 REQUIRE A NEW NOTICE OF COMMENCEMENT AS THE ONE UDNER
 THE BUILDING AHS EXPIRED AND IS NOT PARTOF THIS SCOPE
 OF WORK. FS 713.13
  
 7) NOTE: PLEASE INDICATE AND SHOW LOAD SUMMARY AND
 CALCULATIONS INCLUDING ALL CONTINUOUS LOADS AT 125%.
 220.3,220.10,220.11,220.13, ETC 215.3, 230.42
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-10-26 Cont ID  
Sent By mcarsill Date 2006-10-26 Time 14:45 Rev Time 0.00
Received By mcarsill Date 2006-10-26 Time 14:45 Sent To  
Notes
2006-10-26 14:46:541. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM
 AND FIRE SPRINKLER SYSTEM REMODEL.
 2. CONSTRUCTION, RENOVATION, AND DEMOLITION ACTIVITIES
 TO COMPLY WITH NFPA 241.
 3. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-08-14 Cont ID  
Sent By adarroug Date 2008-08-14 Time 13:14 Rev Time 0.00
Received By adarroug Date 2008-08-14 Time 13:14 Sent To B
Notes
2008-08-14 13:14:48TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-01-30 Cont ID  
Sent By adarroug Date 2008-01-30 Time 16:36 Rev Time 0.00
Received By adarroug Date 2008-01-30 Time 16:36 Sent To M
Notes
2008-01-30 16:36:45TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-11-15 Cont ID  
Sent By adarroug Date 2007-11-15 Time 13:54 Rev Time 0.00
Received By adarroug Date 2007-11-15 Time 13:54 Sent To M
Notes
2007-11-15 13:55:09TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-09-07 Cont ID  
Sent By adarroug Date 2007-09-07 Time 10:14 Rev Time 0.00
Received By adarroug Date 2007-09-07 Time 10:14 Sent To E
Notes
2007-09-07 10:15:12TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-07-19 Cont ID  
Sent By adarroug Date 2007-07-19 Time 08:53 Rev Time 0.00
Received By adarroug Date 2007-07-19 Time 08:53 Sent To E
Notes
2007-07-19 08:53:32TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-26 Cont ID  
Sent By spalmer Date 2007-03-26 Time 18:06 Rev Time 0.00
Received By spalmer Date 2007-03-26 Time 18:06 Sent To M
Notes
2007-03-26 18:07:48TO RON REGUEIRO

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-03-10 Cont ID  
Sent By adarroug Date 2007-03-10 Time 14:12 Rev Time 0.00
Received By adarroug Date 2007-03-10 Time 14:12 Sent To E
Notes
2007-03-10 14:12:19TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-02-13 Cont ID  
Sent By adarroug Date 2007-02-13 Time 09:19 Rev Time 0.00
Received By adarroug Date 2007-02-13 Time 09:19 Sent To E
Notes
2007-02-13 09:19:44TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-27 Cont ID  
Sent By adarroug Date 2006-12-27 Time 10:45 Rev Time 0.00
Received By adarroug Date 2006-12-27 Time 10:45 Sent To  
Notes
2007-01-09 14:23:41TO "BOB"#17
2006-12-27 10:46:23WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-27 Cont ID  
Sent By lmartine Date 2006-10-27 Time 10:57 Rev Time 0.00
Received By lmartine Date 2006-10-04 Time 13:57 Sent To  
Notes
2006-10-04 00:00:00TO "BOB"#15

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-02-04 Cont ID  
Sent By rregueir Date 2008-02-04 Time 10:40 Rev Time 0.00
Received By rregueir Date 2008-02-04 Time 10:38 Sent To PC
Notes
2008-02-04 10:40:22REVISED PG M1 ALONG WITH LETTERS TO CHANGE ENGINEER OF
 RECORD FROM JEFF WU OF MEINHARDT CONSULTING ENGINEERS
 TO ROBERT PETERSON OF DYANKI, INC.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2007-11-28 Cont ID  
Sent By rregueir Date 2007-11-28 Time 19:45 Rev Time 0.00
Received By rregueir Date 2007-11-28 Time 17:59 Sent To PC
Notes
2007-11-28 19:45:55PG M-1 SUBMITTED AS AN "AS-BUILT" PLAN. THIS PLAN IS
 ACTUALLY A REVISION AND WAS SIGNED AND SEALED BY
 SOMEONE OTHER THAN THE DESIGNER OF RECORD FOR THIS
 PERMIT. RESUBMIT PLANS WHICH ARE SIGNED AND SEALED BY
 THE DESIGNER OF RECORD IN ACCORDANCE WTH F.S. 471.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-03-27 Cont ID  
Sent By rregueir Date 2007-03-27 Time 19:11 Rev Time 0.00
Received By rregueir Date 2007-03-27 Time 18:57 Sent To  
Notes
2007-03-27 19:00:04REVISED PAGE M2.1
  
 -----------------PROVISO-------------------
  
 EXHAUST DUCTS UNDER POSITIVE PRESSURE (WHETHER EXISTING
 OR NEW) SHALL NOT EXTEND INTO OR PASS THROUGH A PLENUM
 PER FBC,M 601.3
  
 RONALD J REGUEIRO
 561-805-6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-02-02 Cont ID  
Sent By tgordon Date 2007-02-02 Time 12:03 Rev Time 0.45
Received By tgordon Date 2007-02-02 Time 12:03 Sent To  
Notes
2007-02-02 12:05:09REVISION TO PAGES M0.1 AND M2.1.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-10-10 Cont ID  
Sent By tgordon Date 2006-10-10 Time 16:25 Rev Time 0.30
Received By tgordon Date 2006-10-10 Time 16:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-01-10 Cont ID  
Sent By jleech Date 2007-01-10 Time 13:46 Rev Time 0.00
Received By jleech Date 2007-01-10 Time 13:46 Sent To  
Notes
2007-01-10 13:53:53PROVISO;
  
 DELETE CABINET DOORS AT BREAK SINK. DOORS CANNOT SWING
 INTO THE CLEAR FLOOR SPACE. SEE SECTION 11-4.24.2.4.
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-10-24 Cont ID  
Sent By jleech Date 2006-10-24 Time 08:22 Rev Time 0.00
Received By jleech Date 2006-10-24 Time 08:22 Sent To  
Notes
2006-10-24 08:39:01DENIED;
 PLEASE SHOW A DETAIL OF BREAK SINK WITH ALLDIMENSIONS
 AND REQUIREMENTS TO MEET FBC-2004 CHAPTER 11
 ACCESSIBILITY CODE.
 11-4.24.2 HEIGHT
 11-4.24.3KNEE CLEARANCE
 11-4.24.4 DEPTH OF SINK
 11-4.24.5 CLEAR FLOOR SPACE
 11-4.24.6 EXPOSED PIPES
 11-4.24.7 FAUCET
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2006-10-23 Cont ID  
Sent By astelly Date 2006-10-23 Time 10:48 Rev Time 0.00
Received By astelly Date 2006-10-23 Time 10:48 Sent To  
Notes
2006-10-13 08:27:32NEEDS FOR DMP.