Plan Review Details - Permit 06100022
Plan Review Stops For Permit 06100022
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-10-20 Cont ID  
Sent By lursu Date 2006-10-20 Time 11:03 Rev Time 0.00
Received By lursu Date 2006-10-20 Time 11:03 Sent To PC
Notes
2006-10-20 11:03:59EXT #0013 WAS CREATED FO ROOM 4900
2006-10-17 18:16:47NEEDS SUITE/UNIT EXTENSION

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-10-24 Cont ID  
Sent By alange Date 2006-10-24 Time 14:33 Rev Time 0.00
Received By alange Date 2006-10-24 Time 14:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-09-07 Cont ID  
Sent By dpalmer Date 2007-09-07 Time 07:53 Rev Time 0.00
Received By dpalmer Date 2007-09-07 Time 07:53 Sent To PC
Notes
2007-09-07 07:53:44REV TO CHANGE 100A FEED/DISC TO 125A FOR X-RAY
 EQUIPMENT.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-08-27 Cont ID  
Sent By dpalmer Date 2007-08-27 Time 12:05 Rev Time 0.00
Received By dpalmer Date 2007-08-27 Time 11:39 Sent To PC
Notes
2007-08-27 12:05:28** REVISED INFORMATION FORLOAD CALCULATIONS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-06-03 Cont ID  
Sent By dpalmer Date 2007-06-03 Time 14:56 Rev Time 0.00
Received By dpalmer Date 2007-06-03 Time 14:38 Sent To  
Notes
2007-06-03 14:59:29** PROVISO/REVISION NEEDED **
  
 1) NOTE: PLEASE SEE PREVIOUS NOTE WHICH REQUESTED THE
 LOAD ON THE EXISTING SERVICE WITH THE NEW LOAD BEING
 ADDED/INCREASED. PLEASE SEE THIS IS THE LOAD ON THE
 EXISTING TENANT WIREWAY.
 215.5, 220.
  
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION ALONG WITH ANY
 OTHER REVISIONS BEFORE ROUGH ELECTRICAL INSPECTION. IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-17 Cont ID  
Sent By dpalmer Date 2006-10-17 Time 18:48 Rev Time 0.00
Received By dpalmer Date 2006-10-17 Time 18:14 Sent To  
Notes
2006-10-17 18:48:07*** UNSAT ****
  
 1) NOTE: PLEASE SHOW AND VERIFY THE GROUNDING ELECTRODE
 ATTACHMENT LOCATION FOR THE SEPARATELY DERIVED
 TRANSFORMER.. 250.66, 250.30, 250.22
  
 2) NOTE: PLEASE VEIRFY THE EXSITING CONDCUCTORS FOR THE
 SECONDARY SIDE OF THE EXISTING TRANSFORMER AS IT SEEMS
 TO BE SHOWN FURTHER THAN CODE PERMITS. PLEASE ALSO
 VERIFY OF THE EXISTING 120/208 VA PANEL CONTAINS A MCB.
 408.16, 240.21
  
 3) NOTE: PLEASE PROVIDE LOAD ON THE EXISTING SERVICE IN
 WHICH WE ARE NOW INCREASING LOAD ON. PLEASE SEE
 EXISTING WAS 100A'S AND ONLY SHOWS THE NEW LOAD ON THE
 NEW 200A PANEL??
 220, 215.3, 230.42
  
 4) NOTE: PLEASE VERIFY THE OCP DEVICES AND CONDUCTOR
 SIZES WHICH WILL BE PLACED INOT THE NEW 200A PANEL.
 240.4, 310.16, 408.4. PLEASE LIST ON SCHEDULE.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-08-27 Cont ID  
Sent By mawillia Date 2007-06-05 Time 12:16 Rev Time 0.00
Received By mawillia Date 2007-06-05 Time 14:56 Sent To  
Notes
2007-06-05 15:12:02*****APPROVED*****
  
  
 PLAN SHEET A-1 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-12-11 Cont ID  
Sent By mawillia Date 2006-12-11 Time 14:18 Rev Time 0.00
Received By mawillia Date 2006-12-11 Time 14:17 Sent To  
Notes
2006-12-11 14:35:24*****PROVISO*****
  
  
  
 1.SINCE THE SCOPE OF WORK IS GREATER THAN $2500.00,
 THE APPLICANT SHALL FILE WITH THE AHJ EITHER A RECORDED
 NOTICE OF COMMENCEMENT OR A NOTORIZED STATEMENT THAT
 THE NOTICE HAS BEEN FILED FOR RECORDING, ALONG WITH A
 COPY THEREOF.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.COMBUSTIBLE WASTE, DUST, AND DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY AS
 NECESSARY FOR SAFE OPERATION.
  
 4.IF THE FIRE ALARMOR FIRE SPRINKLER SYSTEM IS
 MODIFIED DUE TO THE SCOPE WORK, SEPARATE PERMIT AND
 PLAN ARE REQUIRED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-09-06 Cont ID  
Sent By adarroug Date 2007-09-06 Time 11:57 Rev Time 0.00
Received By adarroug Date 2007-09-06 Time 11:57 Sent To E
Notes
2007-09-06 11:57:40TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-27 Cont ID  
Sent By adarroug Date 2007-08-27 Time 09:31 Rev Time 0.00
Received By adarroug Date 2007-08-27 Time 09:31 Sent To E
Notes
2007-08-27 09:32:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-10 Cont ID  
Sent By adarroug Date 2007-05-10 Time 16:31 Rev Time 0.00
Received By adarroug Date 2007-05-10 Time 16:31 Sent To  
Notes
2007-05-30 10:40:27TO "COMM" BD#18
2007-05-10 16:31:29WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-11 Cont ID  
Sent By mawillia Date 2006-12-11 Time 14:17 Rev Time 0.00
Received By mawillia Date 2006-10-04 Time 11:22 Sent To  
Notes
2006-10-17 15:27:12TO "COMM" BD#64
2006-10-04 00:00:00WAITING FOR "COMM" BD