Plan Review Details - Permit 06100001
Plan Review Stops For Permit 06100001
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-11-06 Cont ID  
Sent By jgomez Date 2006-11-06 Time 13:22 Rev Time 0.50
Received By jgomez Date 2006-11-06 Time 13:22 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-02 Cont ID  
Sent By jgomez Date 2006-10-02 Time 13:42 Rev Time 0.50
Received By jgomez Date 2006-10-02 Time 13:42 Sent To  
Notes
2006-10-02 00:00:00BUILDING REVIEW CHECKLIST:
 1- NOA 03-0930.07 IS MISSING THE
 SPECIFIC APPROVED ASSEMBLY TO BE
 INSTALLED AS REQUIRED BY CITY POLICY FOR
 ROOFING PERMITS. SEE ATTACHED COPY &
 PROVIDE ALL INFORMATION.
  
 2- NOA 03-0930.07 PAGE 2 OF 31 SHOWS
 THAT THE MAXIMUM DESIGN PRESSURE FOR
 THIS PRODUCT APPROVAL IS -60PSF. NEED TO
 PROVIDE CALCULATIONS FOR ENHANCED
 FASTENING AT CORNER AREAS AS REQUIRED BY
 GENERAL LIMITATION #7. PROVIDE SUCH
 CALCULATIONS.
  
 3- NOTICE OF COMMENCEMENT IS MISSING THE
 CONTRACTOR'S INFORMATION. COMPLETE ALL
 INFORMATION AND RE-RECORD THE NOTICE OF
 COMMENCEMENT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712