Plan Review Details - Permit 06091063
Plan Review Stops For Permit 06091063
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2008-05-20 Cont ID  
Sent By lmartine Date 2008-05-20 Time 12:01 Rev Time 0.00
Received By lmartine Date 2008-05-20 Time 11:06 Sent To  
Notes
2008-05-20 11:57:26REVISION COMMENTS
  
  
 THE WRONG PRODUCT APPROVAL WAS SUBMITTED, PLEASE SEE
 FL6968-R1 PROVIDED.
  
 PLEASE EXPLAIN STRUCTURAL ALUMINUM FRAMING SYSTEM.
  
  
  
 L.MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-12-20 Cont ID  
Sent By rnuquist Date 2006-12-20 Time 05:44 Rev Time 0.00
Received By rnuquist Date 2006-12-20 Time 05:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-12-03 Cont ID  
Sent By rnuquist Date 2006-12-03 Time 17:37 Rev Time 0.00
Received By rnuquist Date 2006-12-03 Time 17:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-10-30 Cont ID  
Sent By jgomez Date 2006-10-30 Time 09:54 Rev Time 0.50
Received By jgomez Date 2006-10-30 Time 07:47 Sent To  
Notes
2006-10-30 10:36:54BUILDING REVIEW 2ND CHECKLIST:
  
 1-PRODUCT APPROVAL FL6968 FOR CLEAR BERTHA STORM
 PANELS DOESN'T WORK FOR OPENING #2.OPENING IS 328" X
 156".SEE TABLE ON SHEET 3 OF 4 OF DRAWINGS NO 05-276
 SUBMITTED FOR MAXIMUM PANEL LENGTH ALLOWED ACCORDING TO
 THE DESIGN PRESSURES.NEED TO PROVIDE PRODUCT APPROVAL
 FOR STORM PANELS THAT WILL WORK FOR OPENING #2.
  
 2- PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE ATTACHED
 CITY SAMPLE.PROVIDE ALL REQUIRED INFORMATION TO
 VERIFY COMPLIANCE WITH PRODUCT APPROVAL PROPOSED
 INSTALLATION. SEE TABLE 1609.6B FBC 2004 TO DETERMINE
 THE OPENING DESIGN PRESSURES. SEE ATTACHED COPY. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-19 Cont ID  
Sent By jgomez Date 2006-10-19 Time 09:54 Rev Time 0.50
Received By jgomez Date 2006-10-19 Time 09:54 Sent To  
Notes
2006-10-19 10:00:32BUILDING REVIEW CHECKLIST:
 1-PRODUCT APPROVAL DRAWING 1 OF 3 STATES THAT MAXIMUM
 PANEL SPAN IS 102".OPENING #2 EXCEEDS THE LIMITATION.
 THEREFORE, IT CAN BE INSTALLED. PROVIDE PRODUCT
 APPROVAL THAT WORKS FOR PROPOSED INSTALLATION.
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561) 805-6712

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-05-12 Cont ID  
Sent By adarroug Date 2008-05-12 Time 10:17 Rev Time 0.00
Received By adarroug Date 2008-05-12 Time 10:16 Sent To B
Notes
2008-05-12 10:17:17TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-12-05 Cont ID  
Sent By adarroug Date 2006-12-05 Time 14:15 Rev Time 0.00
Received By adarroug Date 2006-12-05 Time 14:15 Sent To B
Notes
2006-12-05 14:15:27TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-29 Cont ID  
Sent By spalmer Date 2006-11-29 Time 17:39 Rev Time 0.00
Received By spalmer Date 2006-11-29 Time 17:39 Sent To B
Notes
2006-11-29 17:40:06RESUB/TO LUIS MARTINEZ DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-26 Cont ID  
Sent By adarroug Date 2006-10-26 Time 13:37 Rev Time 0.00
Received By adarroug Date 2006-10-26 Time 13:36 Sent To B
Notes
2006-10-26 13:37:23TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-19 Cont ID  
Sent By jgomez Date 2006-10-19 Time 10:03 Rev Time 0.00
Received By jgomez Date 2006-10-03 Time 17:38 Sent To  
Notes
2006-10-03 00:00:00TO "MISC' BOX#1