Plan Review Details - Permit 06091061
Plan Review Stops For Permit 06091061 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2007-10-30 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2007-10-30 |
Time |
15:32 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2007-10-30 |
Time |
15:32 |
Sent To |
|
|
Notes |
2007-10-30 15:33:59 | TWO (2) COPIES OF MANUFACTURER SPECIFICATION SHEETS | | SUBMITTED FOR NEW DEVICE INSTALLATION TO FIRE ALARM | | SYSTEM. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
F |
Date |
2007-10-09 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-10-09 |
Time |
11:45 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-10-09 |
Time |
10:46 |
Sent To |
|
|
Notes |
2007-10-09 11:45:50 | *****UNSAT***** | | | | 1.REVISION #3 (DATED 8/28/07) NOT INDICATED ON PLAN | | SHEETS.A) ALL CHANGES TO THE PLANS ARE TO BE | | IDENTIFIED BY CLOUDS WITH THE REVISION NUMBER/DATEB) | | SUBMIT ONLY THOSE SHEETS WHICH ARE REFLECTIVE OF THE | | REVISION(S) | | | | 2.AMEND NOTE #3 TO INDICATE THAT DUCT SMOKE DETECTORS | | SHALL INITIATE A GENERAL FIRE ALARM. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2006-12-18 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-12-18 |
Time |
14:45 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-12-18 |
Time |
14:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2006-10-13 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-10-13 |
Time |
13:20 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-10-13 |
Time |
13:20 |
Sent To |
|
|
Notes |
2006-10-13 13:33:09 | *****DENIED***** | | | | | | | | | | 1.)ADD VISUAL ALARM DEVICE (STROBE) TO THE FOLLOWING | | CONFERENCE/GATHERING ROOMS: SHEET FA-1, ROOM 139; | | SHEET FA-3, ROOM 321;SHEET FA-4, ROOM 408 . | | | | 2.)FIRE ALARM SYSTEM TO BE FULLY ADDRESSABLE. | | | | 3.)WATERFLOW TO ACTIVATE A GENERAL ALARM WITHIN 45 TO | | 60 SECONDS. | | | | 4.)DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL | | ALARM. | | | | 5.)FIRE ALARM SYSTEM SHALL BE UL CERTIFIED FOR | | CENTRAL STATION SERVICE.INSTALL UL CERTIFICATE AT THE | | FIRE ALARM CONTROL PANEL AND PROVIDE A COPY TO WPBFR BY | | FINAL FIRE ALARM INSPECTION. | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-09-11 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-09-11 |
Time |
12:33 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-09-11 |
Time |
12:33 |
Sent To |
FIRE |
|
Notes |
2007-09-11 12:34:06 | TO "F" BOX/REV |
|
|
|