Plan Review Details - Permit 06091061
Plan Review Stops For Permit 06091061
Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-10-30 Cont ID  
Sent By mwennerg Date 2007-10-30 Time 15:32 Rev Time 0.00
Received By mwennerg Date 2007-10-30 Time 15:32 Sent To  
Notes
2007-10-30 15:33:59TWO (2) COPIES OF MANUFACTURER SPECIFICATION SHEETS
 SUBMITTED FOR NEW DEVICE INSTALLATION TO FIRE ALARM
 SYSTEM.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-10-09 Cont ID  
Sent By mawillia Date 2007-10-09 Time 11:45 Rev Time 0.00
Received By mawillia Date 2007-10-09 Time 10:46 Sent To  
Notes
2007-10-09 11:45:50*****UNSAT*****
  
 1.REVISION #3 (DATED 8/28/07) NOT INDICATED ON PLAN
 SHEETS.A) ALL CHANGES TO THE PLANS ARE TO BE
 IDENTIFIED BY CLOUDS WITH THE REVISION NUMBER/DATEB)
 SUBMIT ONLY THOSE SHEETS WHICH ARE REFLECTIVE OF THE
 REVISION(S)
  
 2.AMEND NOTE #3 TO INDICATE THAT DUCT SMOKE DETECTORS
 SHALL INITIATE A GENERAL FIRE ALARM.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-12-18 Cont ID  
Sent By mawillia Date 2006-12-18 Time 14:45 Rev Time 0.00
Received By mawillia Date 2006-12-18 Time 14:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-13 Cont ID  
Sent By mawillia Date 2006-10-13 Time 13:20 Rev Time 0.00
Received By mawillia Date 2006-10-13 Time 13:20 Sent To  
Notes
2006-10-13 13:33:09*****DENIED*****
  
  
  
  
 1.)ADD VISUAL ALARM DEVICE (STROBE) TO THE FOLLOWING
 CONFERENCE/GATHERING ROOMS: SHEET FA-1, ROOM 139;
 SHEET FA-3, ROOM 321;SHEET FA-4, ROOM 408 .
  
 2.)FIRE ALARM SYSTEM TO BE FULLY ADDRESSABLE.
  
 3.)WATERFLOW TO ACTIVATE A GENERAL ALARM WITHIN 45 TO
 60 SECONDS.
  
 4.)DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL
 ALARM.
  
 5.)FIRE ALARM SYSTEM SHALL BE UL CERTIFIED FOR
 CENTRAL STATION SERVICE.INSTALL UL CERTIFICATE AT THE
 FIRE ALARM CONTROL PANEL AND PROVIDE A COPY TO WPBFR BY
 FINAL FIRE ALARM INSPECTION.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-11 Cont ID  
Sent By adarroug Date 2007-09-11 Time 12:33 Rev Time 0.00
Received By adarroug Date 2007-09-11 Time 12:33 Sent To FIRE
Notes
2007-09-11 12:34:06TO "F" BOX/REV