Plan Review Details - Permit 06091006
Plan Review Stops For Permit 06091006
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-03-19 Cont ID  
Sent By jwitmer Date 2007-03-19 Time 10:05 Rev Time 0.77
Received By jwitmer Date 2007-03-19 Time 10:05 Sent To PC
Notes
2007-03-19 10:07:47JUDICIAL CENTER PARKING GARAGE EXPANSION/
 GEOTECHNICAL ENGINEERING SERVICES
 TIERRA FILE # 6611-05-504
 1-30-2006

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-01-30 Cont ID  
Sent By jwitmer Date 2007-01-17 Time 14:21 Rev Time 1.55
Received By jwitmer Date 2007-01-17 Time 14:21 Sent To  
Notes
2007-01-17 14:35:02BUILDING PLAN REVIEW
 PERMIT: 06091006
 ADD: 505 BANYAN BLVD
 CONT: THE WEITZ CO.
 TEL: (561)309-7386
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: BUILDING PROVISO
  
 JANUARY 30/2007
 2 WEEKS TO PROVIDE ORIGINAL SIGNATURES.
  
 2E) THE THREE SOILS REPORTS SUBMITTED BY TIERRA (FILE#
 6611-05-504) ARE SEALED WITH PHOTO-COPIED SIGNATURES.
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-17 Cont ID  
Sent By jwitmer Date 2006-11-17 Time 10:25 Rev Time 5.77
Received By jwitmer Date 2006-11-17 Time 10:25 Sent To  
Notes
2006-11-17 13:24:08BUILDING PLAN REVIEW
 PERMIT: 06091006
 ADD: 505 BANYAN BLVD
 CONT: THE WEITZ CO.
 TEL: (561)309-7386
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)SHEET S1.0.0:
  
 2A) THE WIND LOAD DESIGN CRITERIA INDICATES THE
 DESIGNER IS USING ASCE 7-98.
 THE REFRENCE STANDARD REFRENCED TO IN CHAPTER 35
 REFRENCES ASCE 7-02.
  
 2B) WIND IMPORTANCE FACTOR, THE PLANS INDICATE AN
 IMPORTANCE FACTOR (1)=1.00.
 IF THE (1) IS REPRESENTATIVE OF THE IMPORTANCE FACTOR,
 THIS IS TO BE USED FOR
 AGRICULTURAL FACILITIES, TEMPORARY FACILITIES AND MINOR
 STORAGE FACILITIES, PLEASE
 REVISIT TABLE 1-1 FOR THE CORRECT IMPORTANCE FACTOR.
  
 2C) WIND LOAD INFORMATION AS STATED IN (E) (1) (D) THE
 INTERNAL
 PRESSURE COEFFICIENT = + / -.55OR PARTIALLY ENCLOSED.
 INTHE BODY OF THE TEXT
 DIRECTLY BELOWTHE WIND DESIGN CRITERIA IT IS STATED
 AS BEING DESIGNED AS AN
 ENCLOSED STRUCTURE?PLEASE PROVIDE ADDITIONAL
 INFORMATION?
  
 2D) (I) FUTURE EXPANSION THE ORIGINAL DESIGN DRAWINGS
 INDICATE
 THAT THE STRUCTURE WAS DESIGNED FOR
 TWO LEVELS OF FUTURE EXPANSION.ARE THE TWO NEW LEVELS
 OF FUTURE
 EXPANSION TO BE INCORPORATED INTO THE SCOPE OF WORK
 COVERED BY
 THISPERMIT APPLICATION?
  
 2E) PLEASE PROVIDE (3) ORIGINAL SIGNED & SEALEDSOILS
 REPORTS DATED JULY 14,2006
 (TIERRA FILE 6611- 05504. 1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING
 VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS
 CLAIMED, THE BUILDING OFFICIAL SHALL
 REQUIRE THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY
 WITH THE PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6
 .
  
  
 2F) CONTRACTOR SUBSTITUTIONS: THE TERM ICBO IS NO
 LONGER IN EXISTANCE, THE ICC CODE HAVE REPLACED ALL OF
 THE LEGACY REPORTS .
  
 3) PLANS DO NOT PROVIDE THE FOLLOWING INFORMATION:
 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 -------------------------------------
 G ) NUMBER OF FLOORS
 H ) SQ. FT. FOOTPRINT
 I ) SQ. FT. UNDER ROOF (TOTAL)
  
 4)FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 STRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE
 ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT FOR THE
 CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURL INSPECTION
 PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE
 BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 5)WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 6)W.P.B. AMENDMENT 105.13.4.4 ALL
 PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CON-
 TAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH
 THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-01-13 Cont ID  
Sent By dpalmer Date 2007-01-13 Time 15:34 Rev Time 0.00
Received By dpalmer Date 2007-01-13 Time 15:27 Sent To  
Notes
2007-01-13 15:36:07*** REDLINED PLANS.
  
  
 ALL EMERGENCY LIGHTING AND EXIT LIGHTING SHALL MAINTAIN
 ALL MINIMUM LEVELS AS REQUIRED PER LS 101 7.8, 7.9.
  
 THIS IS NOT FOR CONSTRUCTION OF THE ADDTIONAL FLOORS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-23 Cont ID  
Sent By dpalmer Date 2006-10-23 Time 20:37 Rev Time 0.00
Received By dpalmer Date 2006-10-23 Time 20:26 Sent To  
Notes
2006-10-23 20:37:31***UNSAT *****
  
 1) NOTE: PLEASE SEE THERE ARE NOTES PLACED ON
 ELECTRICLA PLANS AT AREAS, HOWEVER THESE ARE NOT NOTED
 UNDER THE "CODED NOTES"?
 PLEASE VERIFY AND CLARIFY THE SCOPE OF ELECTRICAL
 WORK.
 PLEASE STATE AND NOTE ANY ELECTRICAL SYSTEMS/ LIGHTING
 ETC REQUIRED FOR EGRESS ETC WHICH MAY BE AFFECTED BY
 THIS WORK.
 PLEASE KNOW ALL LIFE SAFETY WILL BE REQUIRED TO BE
 MAINTAINED AT ALL TIMES IF THE STRUCTURE IS GOING TO BE
 IN A CONTINUED USE STATE.
 2003 LS101 7.8, 7.9. ETC
 NEC 2002 .
 NFPA-70, 70E ETC.
  
 PLEASE SEE OTHER COMMENS FROM OTHER TRADES WHICH MAY
 AFFECT THE ELECTRICAL PLANS.
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
2006-10-23 20:26:21IN ELEC FOR REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-01-18 Cont ID  
Sent By mawillia Date 2007-01-18 Time 15:16 Rev Time 0.00
Received By mawillia Date 2007-01-18 Time 15:16 Sent To  
Notes
2007-01-18 15:20:43*****APPROVED*****
  
  
 COMMENTS FROM PREVIOUS FIRE PLAN REVIEW (12/11/2006)
 HAVE BEEN ADDRESSED.PLAN SHEETS A0.0.4 AND E2.10 WERE
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-12-11 Cont ID  
Sent By mawillia Date 2006-12-11 Time 09:48 Rev Time 0.00
Received By mawillia Date 2006-12-11 Time 09:48 Sent To  
Notes
2006-12-11 10:46:47*****DENIED*****
  
  
  
 1.THE PERSONS LISTED UNDER THE BOARD OF COUNTY
 COMMISSIONERS ARE CITY OF WEST PALM BEACH
 COMMISSIONERS.
  
 2.NFPA 101-2003 EDITION AND THE FLORIDA FIRE
 PREVENTION CODE -2004 EDITION SHALL BE REFERENCED.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD
 TO GENERAL NOTES SHEET NUMBER A0.0.4
  
 4.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF.
  
 5.FIRE HYDRANTS AND CONNECTIONS TO OTHER OTHER
 APPROVED WATER SUPPLIES SHALL BE ACCESSIBLE TO THE FIRE
 DEPARTMENT.
  
 6.IT IS INDICATED THAT THE EXISTING FIRE LINE IS
 GOING TO BE RELOCATED.HOW WILL THIS SCOPE OF WORK
 AFFECT THE FIRE PROTECTION SYSTEM IN THE BUILDING?
 ALSO, WHAT IS THE ANTICIPATED TIME NEEDED FOR THE
 RELOCATED FIRE LINE TO BE OPERATIONAL.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-03-05 Cont ID  
Sent By adarroug Date 2007-03-05 Time 14:59 Rev Time 0.00
Received By adarroug Date 2007-03-05 Time 14:59 Sent To B
Notes
2007-03-05 14:59:58TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-02-05 Cont ID  
Sent By rbrown Date 2007-02-05 Time 16:31 Rev Time 0.00
Received By rbrown Date 2007-02-05 Time 16:31 Sent To  
Notes
2007-02-05 16:32:42RE-SUB SENT TO JIM WITMER'S DESK FOR PROCESSING.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-27 Cont ID  
Sent By adarroug Date 2006-12-27 Time 16:24 Rev Time 0.00
Received By adarroug Date 2006-12-27 Time 16:24 Sent To  
Notes
2007-01-13 12:50:24TO "COMM" BD#18
2006-12-27 16:25:16WAITING FOR "COMM" BD/NEW SHEETS SUBMITTED FOR "PLUMB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-07 Cont ID  
Sent By mawillia Date 2006-12-07 Time 22:53 Rev Time 0.00
Received By mawillia Date 2006-10-02 Time 11:01 Sent To  
Notes
2006-10-17 15:23:14TO "COMM" BD#48
2006-10-02 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-10-26 Cont ID  
Sent By rregueir Date 2006-10-26 Time 19:30 Rev Time 0.00
Received By rregueir Date 2006-10-26 Time 18:32 Sent To  
Notes
2006-10-23 19:33:26EXISTING GARAGE. NO CHANGES TO MECHANICAL.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-01-13 Cont ID  
Sent By pschmitz Date 2007-01-13 Time 13:44 Rev Time 0.00
Received By pschmitz Date 2007-01-13 Time 13:44 Sent To  
Notes
2007-01-13 13:45:36PREVIIOUS NOTE
 STAMP PLUMBING SHEETS
 UP GRADE STORM DRAINS FOR STRUCTAL FOUNDATIONS AND
 SHEAR WALLS.

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-11-04 Cont ID  
Sent By pschmitz Date 2006-11-04 Time 13:46 Rev Time 0.00
Received By pschmitz Date 2006-11-04 Time 13:45 Sent To  
Notes
2006-11-04 13:55:52UP GRADE STORM DRAINS FOR STRUCTAL FOUNDATIONS AND
 SHEAR WALLS

Review Stop Z ZONING
Rev No 1 Status N Date 2006-10-31 Cont ID  
Sent By astelly Date 2006-10-31 Time 13:53 Rev Time 0.00
Received By astelly Date 2006-10-31 Time 13:53 Sent To  
Notes
***NONE***