Plan Review Details - Permit 06091004
Plan Review Stops For Permit 06091004
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-06-05 Cont ID  
Sent By jgomez Date 2007-06-05 Time 14:04 Rev Time 0.00
Received By jgomez Date 2007-06-05 Time 14:04 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-12-20 Cont ID  
Sent By jgomez Date 2006-12-20 Time 10:22 Rev Time 0.50
Received By jgomez Date 2006-12-20 Time 07:44 Sent To  
Notes
2006-12-20 11:05:35BUILDING REVIEWSECOND CHECKLIST:
  
 ***NOTE: THE FOLLOWING ITMES FROM FIRST CHECKLIST WERE
 NOT ADDRESSED:
  
 1-STOREFRONT PRODUCT APPROVAL IS FOR STRAIGHT AND
 CONTINUOUS STOREFRONT SYSTEM. PROPOSED STOREFRONT IS
 ANGLED TO 141 DEGREES. PROVIDE PRODUCT APPROVAL THAT
 INCLUDES PROPOSED INSTALLATION ORPROVIDE COMPLETE
 ENGINEERINGANALYSIS FOR STRUCTURAL MULLION TO RECEIVE
 STOREFRONT AT ANGLED SIDES. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004 AND SECTION 1609 FBC 2004.
  
 ***ENGINEER DIDN'T ADDRESSED THIS ISSUE.DRAWINGS
 DON'T SHOW ANY SPECIFICATIONS AND DETAILS FOR
 INSTALLATION OF STRUCTURAL MULLIONS AT ANGLED
 STOREFRONT AND AT LEFT HAND CORNER OF DRAWING 1/P1.
 DETAILS 1/ D3, 2/D3 AND 3/D3 DON'T PROVIDE ANY
 SPECIFICATIONS FOR ANGLED MULLION AND CORNER MULLION.
 PROVIDE ALL INFORMATION AS REQUIRED.SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 2- SPECIFY CALCULATED DESIGN PRESSURES REQUIRED FOR THE
 STOREFRONT. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
 AND SEC. 1609 FBC 2004.
  
 *** ENGINEER DIDN'T ADDRESSED THIS ISSUE. PROVIDE ALL
 DESIGN INFORMATION REQUIRED BY SEC. 1603.1.4 FBC 2004.
 INCLUDING BUILDING CODE USED.
  
 3- DESIGNER OF RECORD TO REVIEW AND APPROVEIN
 WRITTING ALL PRODUCT APPROVALS AS REQUIRED BY SEC.
 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 ***NO DONE. ENGINEER NEEDS TO REVIEW AND APPROVE IN
 WRITING ALL PRODUCT APPROVALS. THIS IS TO BE DONE ON
 THE PRODUCT APPROVALS, NOT ON THE ENGINEERED DRAWINGS
 AS IT WAS DONE. THE ENGINEERED DRAWINGS ARE THE
 ENGINEER'S DESIGN, NOT REVIEWD DRAWINGS.
  
 4- DESIGNER OF RECORD TO SIGN AND PROVIDE ALL HIS
 INFORMATION IN ALL DRAWINGS AS REQUIRED BYSEC. 106.1
 CITY AMENDMENTS TO FBC 2004.
  
 *** ENGINEER NEEDS TO PROVIDE ALL HIS INFORMATIONIN
 ALL DRAWINGS AS REQUIRED BY FLORIDA ADMINISTRATIVE CODE
 SEC. 61G15-23.002 AND CHAPTER 471 FLORIDA STATUTES.
  
 5- NEED PRODUCT APPROVAL FOR SIZE OF DOORS AS SPECIFIED
 ON DRAWINGS. PRODUCT APPROVAL SUBMITTED DOESN'T COVER
 SIZE SPECIFIED ON DRAWINGS E1 AND E2..
  
 ***NO DONE.
  
 6-SIZE OF STOREFRONT PANELSHOWNON DRAWING 2/E2 IS
 BIGGER THAN SIZESCOVERED IN THE STOREFRONT PRODUCT
 APPROVAL. REVISE AS REQUIRED.
  
 ***NO DONE. NEED PRODUCT APPROVAL FOR STOREFRONT PANEL
 SIZE SHOWN ON DETAILS 2/E2, 4/E1,1/E1, AND 4/E1.
  
  
 7-UPDATESTATE AND COUNTY LICENSESWITH PERMIT
 CLERK.
  
 ***NO DONE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-19 Cont ID  
Sent By jgomez Date 2006-10-19 Time 17:08 Rev Time 1.00
Received By jgomez Date 2006-10-19 Time 16:57 Sent To  
Notes
2006-10-19 17:37:48BUILDING REVIEW CHECKLIST:
 1-STOREFRONT PRODUCT APPROVAL IS FOR STRAIGHT AND
 CONTINUOUS STOREFRONT SYSTEM. PROPOSED STOREFRONT IS
 ANGLED TO 141 DEGREES. PROVIDE PRODUCT APPROVAL THAT
 INCLUDES PROPOSED INSTALLATION ORPROVIDE COMPLETE
 ENGINEERINGANALYSIS FOR STRUCTURAL MULLION TO RECEIVE
 STOREFRONT AT ANGLED SIDES. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004 AND SECTION 1609 FBC 2004.
  
 2- SPECIFY CALCULATED DESIGN PRESSURES REQUIRED FOR THE
 STOREFRONT. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
 AND SEC. 1609 FBC 2004.
  
 3- DESIGNER OF RECORD TO REVIEW AND APPROVEIN
 WRITTING ALL PRODUCT APPROVALS AS REQUIRED BY SEC.
 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 4- DESIGNER OF RECORD TO SIGN AND PROVIDE ALL HIS
 INFORMATION IN ALL DRAWINGS AS REQUIRED BYSEC. 106.1
 CITY AMENDMENTS TO FBC 2004.
  
 5- NEED PRODUCT APPROVAL FOR SIZE OF DOORS AS SPECIFIED
 ON DRAWINGS. PRODUCT APPROVAL SUBMITTED DOESN'T COVER
 SIZE SPECIFIED ON DRAWINGS E1 AND E2..
  
 6-SIZE OF STOREFRONT PANELSHOWNON DRAWING 2/E2 IS
 BIGGER THAN SIZESCOVERED IN THE STOREFRONT PRODUCT
 APPROVAL. REVISE AS REQUIRED.
  
 7- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 REVISE VALUATION ACCORDINGLY OR ESTIMATED VALUE WILL BE
 ADJUSTED AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO
 FBC 2004.
  
 8-UPDATESTATE AND COUNTY LICENSESWITH PERMIT
 CLERK.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-17 Cont ID  
Sent By adarroug Date 2007-05-17 Time 09:16 Rev Time 0.00
Received By adarroug Date 2007-05-17 Time 09:16 Sent To B
Notes
2007-05-17 09:17:45TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-19 Cont ID  
Sent By adarroug Date 2006-12-19 Time 14:53 Rev Time 0.00
Received By adarroug Date 2006-12-19 Time 14:52 Sent To B
Notes
2006-12-19 14:53:19TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-19 Cont ID  
Sent By jgomez Date 2006-10-19 Time 17:53 Rev Time 0.00
Received By jgomez Date 2006-09-29 Time 16:48 Sent To  
Notes
2006-09-29 00:00:00TO "MISC" BOX#1