Plan Review Details - Permit 06090973
Plan Review Stops For Permit 06090973
Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-02-22 Cont ID  
Sent By adarroug Date 2007-02-22 Time 17:26 Rev Time 0.00
Received By adarroug Date 2007-02-22 Time 17:26 Sent To M
Notes
2007-02-22 17:27:20TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-02-08 Cont ID  
Sent By adarroug Date 2007-02-08 Time 16:39 Rev Time 0.00
Received By adarroug Date 2007-02-08 Time 16:39 Sent To M
Notes
2007-02-08 16:39:50TO "M" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-13 Cont ID  
Sent By adarroug Date 2006-10-13 Time 11:24 Rev Time 0.00
Received By adarroug Date 2006-10-13 Time 11:24 Sent To M
Notes
2006-10-13 11:24:37TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-04 Cont ID  
Sent By tgordon Date 2006-10-04 Time 16:34 Rev Time 0.00
Received By tgordon Date 2006-09-28 Time 15:23 Sent To  
Notes
2006-09-28 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-02-23 Cont ID  
Sent By tgordon Date 2007-02-23 Time 08:16 Rev Time 0.25
Received By tgordon Date 2007-02-23 Time 08:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-02-12 Cont ID  
Sent By tgordon Date 2007-02-12 Time 10:47 Rev Time 1.00
Received By tgordon Date 2007-02-12 Time 10:47 Sent To  
Notes
2007-02-12 11:04:58MECHANICAL REVISION TO PLANS.
 *** DENIED ***
 1) BY CHANGING THE RETURN AIR DUCTING FROM DIRECT
 RETURN TO TRANSFER RETURN YOU NEED TO COMPLY WITH 2004
 FBC/R M1602.4.
  
 2) BALANCED RETURN AIR MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO
 ACHIEVE PROPER RETURN AIR BALANCE.
 (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED. PER 2004 FBC/R M1602.4 .
  
 3) FIRST FLOOR 10" RETURN AIR TRANSFER DUCT TO DEN
 NEEDS TO BE 12", SEE NOTE #2 (A).
  
 4) SECOND FLOOR 10" RETURN AIR TRANSFER DUCT TO MASTER
 SUITE NEEDS TO BE 14", SEE NOTE #2 (A) AND (B) EXCEPT.
  
 5) 10" RETURN AIR TRANSFER DUCT TO BEDROOM 2 NEEDS TO
 BE 14" , SEE NOTE #2 (A).
  
 6) 8" RETURN AIR TRANSFER DUCT TO BEDROOM 3 NEEDS TO BE
 12", SEE NOTE #2 (A).
  
 7) 8" RETURN AIR TRANSFER DUCT TO GUEST SUITE NEEDS TO
 BE 10", SEE NOTE #2 (A).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-10-17 Cont ID  
Sent By tgordon Date 2006-10-17 Time 15:21 Rev Time 0.20
Received By tgordon Date 2006-10-17 Time 15:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-04 Cont ID  
Sent By tgordon Date 2006-10-04 Time 16:34 Rev Time 0.30
Received By tgordon Date 2006-10-04 Time 16:34 Sent To  
Notes
2006-10-04 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT ALSO, PER 2004 FBC
 13-600.3.ABC.2 .
  
 2) PLANS NEED THE PRINTED NAME AND
 SIGNATURE OF THE DESIGN PERSON.
 ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  