Plan Review Details - Permit 06090973
Plan Review Stops For Permit 06090973 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2007-02-22 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-02-22 |
Time |
17:26 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-02-22 |
Time |
17:26 |
Sent To |
M |
|
Notes |
2007-02-22 17:27:20 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-02-08 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-02-08 |
Time |
16:39 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-02-08 |
Time |
16:39 |
Sent To |
M |
|
Notes |
2007-02-08 16:39:50 | TO "M" BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2006-10-13 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-10-13 |
Time |
11:24 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-10-13 |
Time |
11:24 |
Sent To |
M |
|
Notes |
2006-10-13 11:24:37 | TO "M" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-10-04 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-10-04 |
Time |
16:34 |
Rev Time |
0.00 |
Received By |
tgordon |
Date |
2006-09-28 |
Time |
15:23 |
Sent To |
|
|
Notes |
2006-09-28 00:00:00 | TO "M" BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2007-02-23 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-02-23 |
Time |
08:16 |
Rev Time |
0.25 |
Received By |
tgordon |
Date |
2007-02-23 |
Time |
08:16 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2007-02-12 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-02-12 |
Time |
10:47 |
Rev Time |
1.00 |
Received By |
tgordon |
Date |
2007-02-12 |
Time |
10:47 |
Sent To |
|
|
Notes |
2007-02-12 11:04:58 | MECHANICAL REVISION TO PLANS. | | *** DENIED *** | | 1) BY CHANGING THE RETURN AIR DUCTING FROM DIRECT | | RETURN TO TRANSFER RETURN YOU NEED TO COMPLY WITH 2004 | | FBC/R M1602.4. | | | | 2) BALANCED RETURN AIR MAY BE ACHIEVED BY. | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE | | RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS | | SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT | | ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR | | HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO | | ACHIEVE PROPER RETURN AIR BALANCE. | | (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET | | THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR | | EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY | | ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE | | SHALL BE INCLUDED. PER 2004 FBC/R M1602.4 . | | | | 3) FIRST FLOOR 10" RETURN AIR TRANSFER DUCT TO DEN | | NEEDS TO BE 12", SEE NOTE #2 (A). | | | | 4) SECOND FLOOR 10" RETURN AIR TRANSFER DUCT TO MASTER | | SUITE NEEDS TO BE 14", SEE NOTE #2 (A) AND (B) EXCEPT. | | | | 5) 10" RETURN AIR TRANSFER DUCT TO BEDROOM 2 NEEDS TO | | BE 14" , SEE NOTE #2 (A). | | | | 6) 8" RETURN AIR TRANSFER DUCT TO BEDROOM 3 NEEDS TO BE | | 12", SEE NOTE #2 (A). | | | | 7) 8" RETURN AIR TRANSFER DUCT TO GUEST SUITE NEEDS TO | | BE 10", SEE NOTE #2 (A). | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2006-10-17 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-10-17 |
Time |
15:21 |
Rev Time |
0.20 |
Received By |
tgordon |
Date |
2006-10-17 |
Time |
15:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2006-10-04 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-10-04 |
Time |
16:34 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2006-10-04 |
Time |
16:34 |
Sent To |
|
|
Notes |
2006-10-04 00:00:00 | *** DENIED *** | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED | | BY OWNER/AGENT ALSO, PER 2004 FBC | | 13-600.3.ABC.2 . | | | | 2) PLANS NEED THE PRINTED NAME AND | | SIGNATURE OF THE DESIGN PERSON. | | ALL INFORMATION, DRAWINGS, | | SPECIFICATIONS AND ACCOMPANYING DATA | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | PERSON RESPONSIBLE FOR THE DESIGN. PER | | FBC 104.2.1 . | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. | | |
|
|
|
Account Summary | Usage Policy | Privacy Policy