Plan Review Stops For Permit 06090950 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2007-01-11 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2007-01-11 |
Time |
10:24 |
Rev Time |
0.50 |
Received By |
jgomez |
Date |
2007-01-11 |
Time |
10:24 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2006-12-08 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2006-12-08 |
Time |
12:41 |
Rev Time |
0.50 |
Received By |
jgomez |
Date |
2006-12-08 |
Time |
12:41 |
Sent To |
|
|
Notes |
2006-12-08 13:11:44 | BUILDING REVIEW 4TH CHECKLIST: | | 1- NOW, PROPOSED INSTALLATION IS "GROMMET TWO SIDE | | ATTACHMENT INSTALLATION".PRODUCT IS STILL LIMITED TO | | 154" MAX. SPAN. IT CAN'T BE USED FOR OPENING #12 WHICH | | HAS AN SPAN OF 180". PRODUCT DOESN'T WORK FOR PROPOSED | | INSTALLATION. | | | | ***NOTE: THIS IS THE 4TH TIME THE PERMIT APPLICATION IS | | DENIED FOR THE SAME ITEM.THIS PRODUCT DOESN'T WORK | | FOR THE PROPOSED INSTALLATION. | | | | 2- OPENING #19 CALLS FOR AND EDGE DISTANCE OF 3". | | ANCHOR SPACING IS 12"O.C.. NEED TO REDUCE ANCHOR | | SPACING AS REQUIRED BY ANCHOR SPACING CHART ON PAGE 7 | | OF 8 OF DRAWING SC 02-06. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2006-11-17 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2006-11-17 |
Time |
09:12 |
Rev Time |
0.50 |
Received By |
jgomez |
Date |
2006-11-17 |
Time |
07:59 |
Sent To |
|
|
Notes |
2006-11-17 09:22:57 | BUILDING REVIEW 3RD CHECKLIST: | | | | 1- ACCORDING TO INSTALLATION SCHEDULE SUBMITTED, | | PROPOSED INSTALLATION IS A GROMMET THREE SIDE | | ATTACHMENT OF THE STORM CATCHER. PAGE 7 OF 8 OF DRAWING | | NO SC 02-06SUBMITTEDINDICATES ANCHOR SPACING OF | | 1/4" TAPCON TO BE AT 12"O.C. AT CONDITION 1 AND 4"O.C. | | AT CONDITION 2 WHEN EDGE DISTANCE IS 3-1/2".EDGE | | DISTANCE INDICATED ON PROPOSED INSTALLATION SCHEDULE IS | | 3". THEREFORE, NEED TO REDUCE ANCHOR SPACING ACCORDING | | TO TABLE ON SHEET 7 OF 8. REVISE INSTALLATION SCHEDULE | | AS REQUIRED. | | | | 2- MAXIMUM PANEL SPAN IS 154". SPAN FOR OPENING #12 IS | | 180". REVISE AS REQUIRED. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2006-11-06 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2006-11-06 |
Time |
17:19 |
Rev Time |
0.50 |
Received By |
jgomez |
Date |
2006-11-06 |
Time |
17:19 |
Sent To |
|
|
Notes |
2006-11-06 17:28:21 | BUILDING REVIEW 2ND CHECKLIST: | | | | 1- ACCORDING TO INSTALLATION SCHEDULE SUBMITTED THE | | EDGE DISTANCE IS 3".THEREFORE,NEED TO REVISE THE | | ANCHOR SPACING AS REQUIRED ON PAGE 7 OF 8 OF DRAWINGS | | SUBMITTED. | | | | 2- ACCORDING TO THE INSTALLATION SCHEDULE SUBMITTED THE | | CALCULATED DESIGN PRESSURES ARE -60PSF.NEED TO REVISE | | ANCHOR SPACING ACCORDING TO THE DESIGN PRESSURES AND IF | | STRUCTURE TO BE ATTACHED IS HOLLOW CONCRETE BLOCK OR | | CONCRETE BLOCK WITH FILLED CELLS. SEE DRAWING 6 OF 8 OF | | DRAWINGS SUBMITTED. CLEARLY INDICATE IF CONCRETE BLOCK | | HAS FILLED CELLS OR NOT. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-10-18 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2006-10-18 |
Time |
17:10 |
Rev Time |
0.50 |
Received By |
jgomez |
Date |
2006-10-18 |
Time |
17:10 |
Sent To |
|
|
Notes |
2006-10-18 17:26:34 | BUILDING REVIEW CHECKLIST: | | 1-PROVIDE COMPLETE INSTALLATION SCHEDULE TO VERIFY | | COMPLIANCE WITH PRODUCT APPROVAL AND PROPOSED | | INSTALLATION. SEE ATTACHED COPY OF INSTALLATION | | SCHEDULE SAMPLE FROM THE CITY IMPLEMENTATION STANDARD | | FOR WIND-BORNE DEBRIS IMPACT PROTECTION. COMPLETE ALL | | INFORMATION AS APPLICABLE. | | | | 2-ACCORDING TO LIMITATIONS OF PRODUCT APPROVAL ON | | DRAWING 1 OF 8, THE MAXIMUM SPAN IS 154". THEREFORE, IT | | DOESN'T WORK FOR OPENING #12. REVISE AS REQUIRED. | | | | 3-NEED RECORDED NOTICE OF COMMENCEMENT. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561) 805-6712 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2007-01-10 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-01-10 |
Time |
11:09 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-01-10 |
Time |
11:09 |
Sent To |
B |
|
Notes |
2007-01-10 11:10:00 | TO "JGOMEZ" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2006-12-07 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-12-07 |
Time |
15:06 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-12-07 |
Time |
15:06 |
Sent To |
B |
|
Notes |
2006-12-07 15:07:08 | TO "JGOMEZ" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2006-11-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-11-16 |
Time |
11:28 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-11-16 |
Time |
11:28 |
Sent To |
B |
|
Notes |
2006-11-16 11:28:56 | TO "JGOMEZ" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2006-10-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-10-27 |
Time |
10:00 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-10-27 |
Time |
10:00 |
Sent To |
B |
|
Notes |
2006-10-27 10:01:09 | TO "JGOMEZ" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-10-18 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2006-10-18 |
Time |
17:28 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2006-09-29 |
Time |
09:26 |
Sent To |
|
|
Notes |
2006-09-29 00:00:00 | TO "MISC' BOX#1 |
|
|