Plan Review Details - Permit 06090950
Plan Review Stops For Permit 06090950
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-01-11 Cont ID  
Sent By jgomez Date 2007-01-11 Time 10:24 Rev Time 0.50
Received By jgomez Date 2007-01-11 Time 10:24 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-12-08 Cont ID  
Sent By jgomez Date 2006-12-08 Time 12:41 Rev Time 0.50
Received By jgomez Date 2006-12-08 Time 12:41 Sent To  
Notes
2006-12-08 13:11:44BUILDING REVIEW 4TH CHECKLIST:
 1- NOW, PROPOSED INSTALLATION IS "GROMMET TWO SIDE
 ATTACHMENT INSTALLATION".PRODUCT IS STILL LIMITED TO
 154" MAX. SPAN. IT CAN'T BE USED FOR OPENING #12 WHICH
 HAS AN SPAN OF 180". PRODUCT DOESN'T WORK FOR PROPOSED
 INSTALLATION.
  
 ***NOTE: THIS IS THE 4TH TIME THE PERMIT APPLICATION IS
 DENIED FOR THE SAME ITEM.THIS PRODUCT DOESN'T WORK
 FOR THE PROPOSED INSTALLATION.
  
 2- OPENING #19 CALLS FOR AND EDGE DISTANCE OF 3".
 ANCHOR SPACING IS 12"O.C.. NEED TO REDUCE ANCHOR
 SPACING AS REQUIRED BY ANCHOR SPACING CHART ON PAGE 7
 OF 8 OF DRAWING SC 02-06.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-11-17 Cont ID  
Sent By jgomez Date 2006-11-17 Time 09:12 Rev Time 0.50
Received By jgomez Date 2006-11-17 Time 07:59 Sent To  
Notes
2006-11-17 09:22:57BUILDING REVIEW 3RD CHECKLIST:
  
 1- ACCORDING TO INSTALLATION SCHEDULE SUBMITTED,
 PROPOSED INSTALLATION IS A GROMMET THREE SIDE
 ATTACHMENT OF THE STORM CATCHER. PAGE 7 OF 8 OF DRAWING
 NO SC 02-06SUBMITTEDINDICATES ANCHOR SPACING OF
 1/4" TAPCON TO BE AT 12"O.C. AT CONDITION 1 AND 4"O.C.
 AT CONDITION 2 WHEN EDGE DISTANCE IS 3-1/2".EDGE
 DISTANCE INDICATED ON PROPOSED INSTALLATION SCHEDULE IS
 3". THEREFORE, NEED TO REDUCE ANCHOR SPACING ACCORDING
 TO TABLE ON SHEET 7 OF 8. REVISE INSTALLATION SCHEDULE
 AS REQUIRED.
  
 2- MAXIMUM PANEL SPAN IS 154". SPAN FOR OPENING #12 IS
 180". REVISE AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-11-06 Cont ID  
Sent By jgomez Date 2006-11-06 Time 17:19 Rev Time 0.50
Received By jgomez Date 2006-11-06 Time 17:19 Sent To  
Notes
2006-11-06 17:28:21BUILDING REVIEW 2ND CHECKLIST:
  
 1- ACCORDING TO INSTALLATION SCHEDULE SUBMITTED THE
 EDGE DISTANCE IS 3".THEREFORE,NEED TO REVISE THE
 ANCHOR SPACING AS REQUIRED ON PAGE 7 OF 8 OF DRAWINGS
 SUBMITTED.
  
 2- ACCORDING TO THE INSTALLATION SCHEDULE SUBMITTED THE
 CALCULATED DESIGN PRESSURES ARE -60PSF.NEED TO REVISE
 ANCHOR SPACING ACCORDING TO THE DESIGN PRESSURES AND IF
 STRUCTURE TO BE ATTACHED IS HOLLOW CONCRETE BLOCK OR
 CONCRETE BLOCK WITH FILLED CELLS. SEE DRAWING 6 OF 8 OF
 DRAWINGS SUBMITTED. CLEARLY INDICATE IF CONCRETE BLOCK
 HAS FILLED CELLS OR NOT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-18 Cont ID  
Sent By jgomez Date 2006-10-18 Time 17:10 Rev Time 0.50
Received By jgomez Date 2006-10-18 Time 17:10 Sent To  
Notes
2006-10-18 17:26:34BUILDING REVIEW CHECKLIST:
 1-PROVIDE COMPLETE INSTALLATION SCHEDULE TO VERIFY
 COMPLIANCE WITH PRODUCT APPROVAL AND PROPOSED
 INSTALLATION. SEE ATTACHED COPY OF INSTALLATION
 SCHEDULE SAMPLE FROM THE CITY IMPLEMENTATION STANDARD
 FOR WIND-BORNE DEBRIS IMPACT PROTECTION. COMPLETE ALL
 INFORMATION AS APPLICABLE.
  
 2-ACCORDING TO LIMITATIONS OF PRODUCT APPROVAL ON
 DRAWING 1 OF 8, THE MAXIMUM SPAN IS 154". THEREFORE, IT
 DOESN'T WORK FOR OPENING #12. REVISE AS REQUIRED.
  
 3-NEED RECORDED NOTICE OF COMMENCEMENT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561) 805-6712

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-01-10 Cont ID  
Sent By adarroug Date 2007-01-10 Time 11:09 Rev Time 0.00
Received By adarroug Date 2007-01-10 Time 11:09 Sent To B
Notes
2007-01-10 11:10:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-12-07 Cont ID  
Sent By adarroug Date 2006-12-07 Time 15:06 Rev Time 0.00
Received By adarroug Date 2006-12-07 Time 15:06 Sent To B
Notes
2006-12-07 15:07:08TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-16 Cont ID  
Sent By adarroug Date 2006-11-16 Time 11:28 Rev Time 0.00
Received By adarroug Date 2006-11-16 Time 11:28 Sent To B
Notes
2006-11-16 11:28:56TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-27 Cont ID  
Sent By adarroug Date 2006-10-27 Time 10:00 Rev Time 0.00
Received By adarroug Date 2006-10-27 Time 10:00 Sent To B
Notes
2006-10-27 10:01:09TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-18 Cont ID  
Sent By jgomez Date 2006-10-18 Time 17:28 Rev Time 0.00
Received By jgomez Date 2006-09-29 Time 09:26 Sent To  
Notes
2006-09-29 00:00:00TO "MISC' BOX#1