Plan Review Details - Permit 06090921
Plan Review Stops For Permit 06090921
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-10-20 Cont ID  
Sent By amorse Date 2006-10-20 Time 14:01 Rev Time 0.00
Received By amorse Date 2006-10-20 Time 14:01 Sent To PC
Notes
2006-10-20 14:03:04 
  
  
 PASSED PENDING SUBMITAL OF SIGNED AND SEALED WIND LOAD
 CALC'S AND RERECORDED NOC

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-13 Cont ID  
Sent By amorse Date 2006-10-13 Time 13:46 Rev Time 0.00
Received By amorse Date 2006-10-13 Time 13:46 Sent To PC
Notes
2006-10-13 13:47:56 
  
  
 DENIED
  
 1) THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED
 THE FL# FOR THE SH WINDOWS IS FL#6871 AND THE
 VALIDATION DRAWING IS #W06-39, THE NUMBER FOR THE SGD
 IS FL# 5042 AND THE SUBMITTED MIAMI-DADE NOA IS
 CORRECT, AND THE NUMBER FOR THE PGT MULLIONS ISFL# 261
 AND THE VALIDATION IS MIAMI-DADE BUT THE NOA HAS BEEN
 REVISED TO 06-0125.06
  
 2) PER 1609.6.1 FBC THE SIMPLIFIED CALCULATION METHOD
 FOR WIND LOADS SHALL NOT BE USED TO DETERMINE WIND
 PRESSURES FOR BUILDINGS OVER 60 FT IN HEIGHT. PLEASE
 SUBMIT ENGINEERED CALCULATIONS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-20 Cont ID  
Sent By adarroug Date 2006-10-20 Time 11:21 Rev Time 0.00
Received By adarroug Date 2006-10-20 Time 11:21 Sent To B
Notes
2006-10-20 11:21:26TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-10-13 Time   Rev Time 0.00
Received By adarroug Date 2006-09-27 Time 14:13 Sent To  
Notes
2006-09-27 00:00:00TO "MISC" BOX#1


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved