Plan Review Details - Permit 06090795
Plan Review Stops For Permit 06090795
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-11-07 Cont ID  
Sent By jgomez Date 2006-11-07 Time 10:03 Rev Time 0.50
Received By jgomez Date 2006-11-07 Time 09:41 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-10-17 Cont ID  
Sent By jgomez Date 2006-10-17 Time 12:54 Rev Time 0.50
Received By jgomez Date 2006-10-17 Time 12:43 Sent To  
Notes
2006-10-17 13:00:34BUILDING REVIEW 2ND CHECKLIST:
 1- ACCORDION SHUTTERS:ANCHOR SPECIFIED ON
 INSTALLATION SCHEDULE DOESN'T MATCH ANCHOR SHOWN ON
 ACCORDION SHUTTERS DRAWINGS.SEE PAGE 16 OF 26 AND
 REVISE AS REQUIRED.
  
 2- SINGLE HUNG WINDOWS DADE COUNTY NOA 05-0112.01
 EXPIRED ON 10/08/06. NEED TO PROVIDE CURRENT DADE
 COUNTY NOA.
  
 3- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-05 Cont ID  
Sent By jgomez Date 2006-10-05 Time 17:59 Rev Time 0.50
Received By jgomez Date 2006-10-05 Time 17:53 Sent To  
Notes
2006-10-05 00:00:00BUILDING REVIEW CHECKLIST:
 1- ACCORDION SHUTTERS INSTALLATION
 SCHEDULE CALLS FOR METAL FRAME AS THE
 SUBSTRUCTURE. NEED PRODUCT APPROVAL FOR
 PROPOSED INSTALLATION. PRODUCT APPROVAL
 SUBMITTED IS FOR ATTACHMENT TO CONCRETE,
 CONCRETE BLOCK OR WOOD ONLY. THEREFORE,
 IT DOESN'T APPLY TO PROPOSED
 INSTALLATION.
  
 2- ENGINEERED WIND LOAD SCHEDULE NEED TO
 HAVE ENGINEER'S ORIGINAL SEAL, SIGNATURE
 AND DATE AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTES. BOTH COPIES.
  
 3- SPECIFY SIZE OF WINDOWS AND LOCATION.
 SPECIFY WINDOW SIZE IN BEDROOMS TO
 VERIFY COMPLIANCE WITH THE EGRESS
 REQUIREMENTS.
  
 4- WHEN RE-SUBMITTING CHECK THE
 FOLLOWING:
 A) CLEAR AND LEGIBLE DRAWINGS.
 B) ANCHOR SPECIFIED MATCHES ONE IN THE
 PRODUCT APPROVAL.
 C) EDGE DISTANCE AND SPACING REDUCTION
 IF REQUIRED.
  
 5- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-04 Cont ID  
Sent By adarroug Date 2006-11-04 Time 15:36 Rev Time 0.00
Received By adarroug Date 2006-11-04 Time 15:36 Sent To B
Notes
2006-11-04 15:37:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-14 Cont ID  
Sent By adarroug Date 2006-10-14 Time 18:11 Rev Time 0.00
Received By adarroug Date 2006-10-14 Time 18:11 Sent To B
Notes
2006-10-14 18:11:36TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-05 Cont ID  
Sent By jgomez Date 2006-10-05 Time 18:00 Rev Time 0.00
Received By jgomez Date 2006-09-23 Time 19:43 Sent To  
Notes
2006-09-23 00:00:00TO "MISC" BOX#1


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved