Plan Review Details - Permit 06090752
Plan Review Stops For Permit 06090752
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-09-29 Cont ID  
Sent By lmartine Date 2006-09-29 Time 13:32 Rev Time 0.00
Received By lmartine Date 2006-09-29 Time 13:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-09-29 Cont ID  
Sent By shill Date 2006-09-29 Time 09:49 Rev Time 0.00
Received By shill Date 2006-09-29 Time 09:49 Sent To  
Notes
2006-09-29 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)THE APPLICATION HAS BEEN REVISED TO
 CONCRETE DECK, BUT THE PRODUCT APPROVAL
 IS FOR A LIGHTWEIGHT CONCRETE DECK.
 ADDRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-09-26 Cont ID  
Sent By shill Date 2006-09-26 Time 08:52 Rev Time 0.00
Received By shill Date 2006-09-26 Time 08:52 Sent To  
Notes
2006-09-26 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)THE ASSEMBLY SELECTED IS FOR TILE
 UNDERLAYMENT; ACCORDING TO THE
 APPLICATION, THIS IS A FLAT DECK.
 ADDRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-21 Cont ID  
Sent By shill Date 2006-09-21 Time 10:27 Rev Time 0.00
Received By shill Date 2006-09-21 Time 10:27 Sent To  
Notes
2006-09-21 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
 _XX_1.)A NOTICE OF COMMENCEMENT
 MUST BE FILED WITH THE CLERK OF COURTS
 BEFORE A PERMIT CAN BE ISSUED.
  
 _XX_2.)CONTRACTOR IS TO PROVIDE THE
 FOLLOWING INFORMATION ON THE
 APPLICATION:
  
 MEAN ROOF HEIGHT
  ROOF PITCH
  ROOF DECK TYPE
  AREA OF EACH ROOF TYPE
  
 ____3.)FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL REQUIRED IN ADDITION TO
 THE EVALUATION REPORT SUBMITTED,
 FAC9B72.WWW.FLORIDABUILDING.ORG
  
 _XX_4.)FOR THE FLAT DECK, SELECT THE
 APPROVED ASSEMBLY YOU ARE USING.
  
 ____ 5.)ON THE TILE PRODUCT APPROVAL,
 INDICATE WHICH METHOD OF ATTACHMENT YOU
 ARE USING.
  
 ____ 6.)SEE PRODUCT LIMITATION #7.
 CALCULATIONS PREPARED BY AN ARCHITECT,
 ENGINEER, OR REGISTERED ROOF CONSULTANT
 REQUIRED FOR ENHANCED FASTENING.
  
 _XX_ 7.)PROVIDE A REASONABLE VALUE FOR
 THIS JOB.
  