Plan Review Details - Permit 06090734
Plan Review Stops For Permit 06090734
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-10-23 Cont ID  
Sent By mperson Date 2006-10-23 Time 15:21 Rev Time 0.33
Received By mperson Date 2006-10-23 Time 15:21 Sent To PC
Notes
2006-10-23 15:22:50 
  
  
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,000 CUBIC FEET REQUIRED.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-09-27 Cont ID  
Sent By mperson Date 2006-09-27 Time 14:06 Rev Time 0.33
Received By mperson Date 2006-09-27 Time 14:06 Sent To PC
Notes
2006-09-27 00:00:00******DENIED******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PLAN REVIEW ON THE ISOMETRIC
 DRAWING.
  
 1. PER FBC-2004 CHAPTER 1, SECTION
 106.1, SUBMITTAL DOCUMENTS: CONSTRUCTION
 DOCUMENTS SHALL BE SUBMITTED IN TWO OR
 MORE SETS.
 NOTE: ONLY ONE SET OF DRAWINGS AND
 APPLIANCE SUBMITTALS WERE SUBMITTED.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: PLEASE CLAIFY WHAT S.S. IS. DO YOU
 MEAN CSST?
  
 3. TYPE OF GAS, (LP OR NATURAL)
  
 4. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 5. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 6. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 NOTE: IF GAS SYSTEM PRESSURE IS 2LB NEED
 SHEETS ON MP REGULATORS.
  
 8. FBC-2004 CHAPTER 1,SECTION
 106.3.4.2: THE PERSON RESPONSIBLE FOR
 THE DESIGN OF THE DRAWING SHALL CLEARLY
 PRINT AND SIGN NAME, AND ALSO DATE
 DRAWING. PLEASE DO THIS PRIOR TO
 RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-18 Cont ID  
Sent By adarroug Date 2006-10-18 Time 15:24 Rev Time 0.00
Received By adarroug Date 2006-10-18 Time 15:24 Sent To P
Notes
2006-10-18 15:25:00TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-27 Cont ID  
Sent By mperson Date 2006-09-27 Time 14:21 Rev Time 0.00
Received By mperson Date 2006-09-22 Time 11:46 Sent To  
Notes
2006-09-22 00:00:00TO "G" BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved