Plan Review Details - Permit 06090720
Plan Review Stops For Permit 06090720 |
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
P |
Date |
2006-10-16 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2006-10-16 |
Time |
09:53 |
Rev Time |
0.33 |
Received By |
mperson |
Date |
2006-10-16 |
Time |
09:53 |
Sent To |
PC |
|
Notes |
2006-10-16 09:55:42 | | | | | IF DRYER ROOM IS A CONFINED SPACE, OPEN- | | INGS REQUIRED PER SECTION 304.5 OR | | SECTION 304.6 SHALL BE INSTALLED. | | MINIMUM 1,000 CUBIC FEET REQUIRED. | | | | IF WATER HEATER ROOM IS A CONFINED | | SPACE, OPENINGS REQUIRED PER SECTION | | 304.5 OR SECTION 304.6 SHALL BE | | INSTALLED. | | MINIMUM 2,000 CUBIC FEET REQUIRED. |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2006-09-27 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2006-09-27 |
Time |
11:47 |
Rev Time |
0.33 |
Received By |
mperson |
Date |
2006-09-27 |
Time |
11:47 |
Sent To |
PC |
|
Notes |
2006-09-27 00:00:00 | ******DENIED****** | | REFERENCE: FBC-2004 FUEL GAS | | | | THE FOLLOWING INFORMATION IS REQUIRED | | FOR GAS PLAN REVIEW: | | | | 1. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT (MP REGULATORS) TO VERIFY | | COMPLIANCE WITH STANDARDS NFPA 54, NFPA | | 58, AND THE FBC-2004 FUEL GAS CODE SEC | | 402.2, AND CLEARLY INDICATE THE LOCATION | | OF THE MP REGULATORS WITH SHUT OFF | | VALVES ON THE DRAWINGS. | | | | 2. PLEASE CORRELATE THE RANGE BTU'S THE | | ISOMETRIC INDICATES 40,000 BTU'S AND THE | | FLAT PLAN INDICATES 60,000 BTU'S. | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561) 805-6721 | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2006-10-11 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-10-11 |
Time |
09:06 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-10-11 |
Time |
09:06 |
Sent To |
G |
|
Notes |
2006-10-11 09:06:23 | TO "G" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-09-27 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2006-09-27 |
Time |
13:01 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2006-09-22 |
Time |
16:19 |
Sent To |
|
|
Notes |
2006-09-22 00:00:00 | TO "G" BOX |
|
|
|
Account Summary | Usage Policy | Privacy Policy