Plan Review Details - Permit 06090692
Plan Review Stops For Permit 06090692
Review Stop AD ADDRESSING
Rev No 4 Status P Date 2007-09-25 Cont ID  
Sent By lursu Date 2007-09-25 Time 16:18 Rev Time 0.00
Received By lursu Date 2007-09-25 Time 16:18 Sent To  
Notes
2007-09-25 16:19:08SITE ADDRESS AND PCN ARE CORRECT.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 3 Status P Date 2006-11-17 Cont ID  
Sent By lursu Date 2006-11-17 Time 13:04 Rev Time 0.00
Received By lursu Date 2006-11-17 Time 13:04 Sent To  
Notes
2006-11-17 13:04:17TEMPORARY PCN WAS CREATED FOR THIS STRUCTURE .PERMIT
 WAS ASSIGNED TO IT.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 2 Status P Date 2006-10-18 Cont ID  
Sent By lursu Date 2006-10-18 Time 15:17 Rev Time 0.00
Received By lursu Date 2006-10-18 Time 15:17 Sent To  
Notes
2006-10-18 15:18:05NEW ADDRESS ASSIGNED TO BLDG 4 ON PARCEL D IS 5850
 PREMIER PARK DR

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2006-09-22 Cont ID  
Sent By lursu Date 2006-09-22 Time 11:23 Rev Time 0.00
Received By lursu Date 2006-09-21 Time 14:52 Sent To  
Notes
2006-09-22 00:00:00THIS BLDG IS ON ANINDIVIDUAL PARCEL ,
 OWNERSHIP DOCUMENTATION IS NEEDED .

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2007-12-21 Cont ID  
Sent By shill Date 2007-12-21 Time 18:39 Rev Time 0.00
Received By shill Date 2007-12-21 Time 18:39 Sent To  
Notes
2007-12-21 18:39:35ROOF HATCH PRODUCT APPROVAL OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status F Date 2007-12-13 Cont ID  
Sent By shill Date 2007-12-13 Time 08:54 Rev Time 0.00
Received By shill Date 2007-12-13 Time 08:54 Sent To  
Notes
2007-12-13 09:02:19****CORRECTIONS****
 ****LOCAL PRODUCT APPROVAL FOR NYSTROM ROOF HATCH****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SEE FAC9B72.010(6), DEFINITIONS,APPROVED QUALITY
 ASSURANCE ENTITY MEANS AN ENTITY APPROVED BY THE
 COMMISSION PURSUANT TO SUBSECTION 9B-72.100(5), F.A.C.,
 TO PROVIDE OVERSIGHT AND DETERMINE THAT THE PRODUCT OR
 SYSTEM IS BEING MANUFACTURED OR ASSEMBLED, PER THE
 SUBMITTED DESCRIPTION, TEST RESULTS, OR CALCULATIONS TO
 ESTABLISH CONTINUAL PRODUCT PERFORMANCE. I WAS UNABLE
 TO LOCATE ACRC IN THE FLORIDA DATABASE.SEE
 WWW.FLORIDABUILDING.ORG, PRODUCT APPROVAL, ORGANIZATION
 SEARCH.
  
 2.THE SHEET TITLED "WIND UPLIFT FOR ROOF HATCH
 PRODUCTS" IS NOT LEGIBLE.PLESE PROVIDE A LEGIBLE COPY
 OF THIS DOCUMENT AS WELL AS THE TITLE AND
 CONTENTS/INDEX PAGES OF THE DOCUMENT WHERE THIS SHEET
 CAME FROM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2007-10-19 Cont ID  
Sent By shill Date 2007-10-19 Time 08:02 Rev Time 0.00
Received By shill Date 2007-10-19 Time 08:01 Sent To  
Notes
2007-10-19 08:03:05REVISED A0.1, LULA LIFT DETAIL

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2007-10-01 Cont ID  
Sent By shill Date 2007-10-01 Time 11:04 Rev Time 0.00
Received By shill Date 2007-10-01 Time 11:04 Sent To  
Notes
2007-10-01 11:05:16REVISION - OVERHEAD DOORS
 SUBMITTAL - DOCK EQUIPMENT
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2007-10-01 Cont ID  
Sent By shill Date 2007-10-01 Time 09:48 Rev Time 0.00
Received By shill Date 2007-10-01 Time 09:48 Sent To  
Notes
2007-10-01 11:04:00***SUBMITTAL/REVISION***
  
 ****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 ROOFING SUBMITTAL:
  
 1.)TAS105 IS TO BE PERFORMED BY AN APPROVED TESTING
 LAB.PLEASE PROVIDE EVIDENCE OF NUTTING ENGINEERS AS
 AN APPROVED TESTING LAB AS I WAS UNABLE TO LOCATE A
 LIST ON THE INTERNET.
  
 **OK - REVISED 10/2 - CONTRACTOR SHOWED TO J SMITH,
 INSPECTOR**
  
 2.)FASTENER DESIGN IN ACCORDANCE WITH RAS117 IS TO BE
 SUBMITTED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT AS PER GENERAL LIMITATION #7 OF THE
 MIAMIDADE NOA 06-0626.05.PLEASE SUBMIT.**OK -
 SUBMITTED W/ROOF PERMIT 07070582**
  
 ROOF HATCH:
  
 3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 FOR THE ROOF HATCH, FAC9B72. IF A FLORIDA STATE PRODUCT
 APPROVAL IS NOT AVAILABLE, SUBMIT APPLICATION FOR LOCAL
 PRODUCT APPROVAL; SEE ATTACHED.ALL INFORMATION ON THE
 APPLICATION MUST BE COMPLETED AND ALL ENGINEERING MUST
 BE ORIGINAL.IF A MIAMIDADE NOA HAS BEEN ISSUED FOR
 THE PRODUCT YOU ARE USING, AN APPLICATION (AND ORIGINAL
 ENGINEERING) IS NOT REQUIRED.OTHERWISE, SUBMIT ALL
 INFORMATION REQUIRED INCLUDING PROOF OF A QUALITY
 ASSURANCE PROGRAM.
  
 ACCESSIBLE LIFT, SCUTTLE LADDER:
  
 4.)HAVE THE SHOP DRAWINGS REVIEWED BY DESIGNER OF
 RECORD.
  
 MISCELLANEOUS:
  
 5.)AS A COURTESY, I HAVE PRINTED THE INSTALLATION
 INSTRUCTIONS AND SUPPLEMENTARY DRAWINGS FOR THE
 EVALUATION REPORT FOR THE OVERHEAD DOOR PRODUCT
 APPROVAL AS THE DRAWINGS WERE ILLEGIBLE.IN THE
 FUTURE, PLEASE SUBMIT ONLY LEGIBLE DOCUMENTS.THEY ARE
 AVAILABLE ON THE INTERNET AT WWW.FLORIDABUILDING.ORG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2007-09-26 Cont ID  
Sent By shill Date 2007-09-26 Time 11:40 Rev Time 0.00
Received By shill Date 2007-09-26 Time 11:40 Sent To  
Notes
2007-09-26 11:58:44REVISION DATED 9/19, SHEET A-0.1, DETAIL SD-3.0
  
  
2007-09-26 11:40:34REVISION DATED 9/10/07, SHEET 5

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2007-09-24 Cont ID  
Sent By shill Date 2007-09-24 Time 09:36 Rev Time 0.00
Received By shill Date 2007-09-24 Time 09:35 Sent To  
Notes
2007-09-24 09:39:18****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)REGARDING THE UL DETAILS SUBMITTED; IF THEY ARE
 ALREADY A PART OF THE APPROVED PLAN, THE SHOP DRAWINGS
 (UL W-L DETAILS) SUBMITTED ARE UNNECESSARY.IF THEY
 ARE NOT A PART OF THE APPROVED PLAN, PLEASE INCORPORATE
 THESE DETAILS INTO THE PLAN AND SUBMIT AS A REVISION.
  
 2.)FIRESTOPPING SUBMITTAL OK.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-09-24 Cont ID  
Sent By shill Date 2007-09-24 Time 07:51 Rev Time 0.00
Received By shill Date 2007-09-24 Time 07:51 Sent To  
Notes
2007-09-24 07:52:35****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 PROVISO ITEMS
 REVISION DATED 8/21/07
  
  
 1.)SUBMIT PRODUCT APPROVALS COMPLIANT WITH THE DESIGN
 PRESSURE REQUIREMENT OF +-33 (S2.1) FOR THE GARAGE
 DOORS OR REVISE S2.1.THE PRODUCT APPROVAL SUBMITTED
 HAS DP LIMITATION OF +28/-32.
  
 A FLORIDA STATE PRODUCT APPROVAL WAS SUBMITTED WITH
 SHOP DRAWINGS WHICH DO NOT SHOW ANY DESIGN PRESSURES.
 PRINT THE DOCUMENTS FROM THE WEBSITE; EVALUATION REPORT
 (WHICH SHOULD HAVE THE DESIGN PRESSURES FOR THIS
 PRODUCT) AND INSTALLATION INSTRUCTIONS.HAVE THE
 PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD PRIOR
 TO SUBMITTAL, FBC*106.3.3.
  
 2.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 FOR THE ROOF HATCH FAC9B72.
  
 SHOP DRAWINGS WERE SUBMITTED.PROVIDE FLORIDA STATE
 PRODUCT APPROVAL OR APPLY FOR LOCAL PRODUCT APPROVAL AS
 REQUIRED BY FAC9B72.
  
 3.)THE ROOFING PRODUCT APPROVALS WERE ALREADY
 SUBMITTED.HOWEVER, SEE GENERAL LIMITATION #7.
 ENHANCED FASTENING CALCULATIONS PREPARED BY AN
 ARCHITECT, ENGINEER, OR REGISTERED ROOF CONSULTANT
 REQUIRED.(OK -SUBMITTED W/ROOF PERMIT 07070582)
  
 (NOA06-0626.05, ASSEMBLY PAGE 27)

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-05-01 Cont ID  
Sent By shill Date 2007-05-01 Time 08:03 Rev Time 0.00
Received By shill Date 2007-05-01 Time 08:03 Sent To  
Notes
2007-05-01 08:08:56*** PROVISO ***
  
 1.)SUBMIT PRODUCT APPROVALS COMPLIANT WITH THE DESIGN
 PRESSURE REQUIREMENT OF +-33 (S2.1) FOR THE GARAGE
 DOORS OR REVISE S2.1.THE PRODUCT APPROVAL SUBMITTED
 HAS DP LIMITATION OF +28/-32.
  
 2.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 FOR THE ROOF HATCH FAC9B72.
  
 INFORMATIONAL NOTE - NOA06-0626.05, ASSEMBLY PAGE 27
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-04-09 Cont ID  
Sent By shill Date 2007-04-09 Time 08:50 Rev Time 16.00
Received By shill Date 2007-04-04 Time 07:44 Sent To  
Notes
2007-04-04 07:45:09****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 ***NOTE - PLAN REVIEW COMMENTS WERE CHANGED 4/12/07 TO
 DOCUMENT ITEMS DISCUSSED/NEGOTIATED WITH ARCHITECT AND
 CONTRACTOR IN A MEETING 4/11/07**
 ***NOTE THAT A LIFE SAFETY PLAN WAS ACCEPTED DURING THE
 PLAN REVIEW PROCESS DURING REVIEW #3.THIS IS THE 4TH
 COURTESY REVIEW REFERRED TO IN THE PLAN REVIEW
 NOTES.***
  
 1-8.) ADDRESSED.
  
 9.)A SEPARATE PERMIT WILL BE REQUIRED FOR THE SIGN
 SHOWN ON A-0.1.SEPARATE PLANS AND PERMIT APPLICATION
 WILL BE REQUIRED.INFORMATIONAL ONLY; THIS IS NOT
 REQUIRED TO BE ADDRESSED AT THIS TIME.
  
 10-12.)ADDRESSED.
  
 13.)EXTRA FP1 SHEETS WERE SUBMITTED.PLEASE PROVIDE
 THREE ORIGINALS, ONE PUT INTO EACH ROLLED PERMIT SET.
  
 THREE SETS SUBMITTED.PLEASE KEEP THE THREE SETS IN
 THE PACKAGE.THEY ARE NOT CURRENTLY A PART OF THE
 BOUND SET.THIS IS ACCEPTABLE; HOWEVER, PLEASE ENSURE
 THAT THEY ARE NOT INADVERTENTLY REMOVED FROM THE
 PACKAGE AS THIS IS A STATUTORY REQUIREMENT AND THE
 PERMIT CANNOT BE ISSUED WITHOUT SPRINKLER PLANS.
  
 14-15.) ADDRESSED.
  
 16.)A NEW LIFE SAFETY PLAN WAS ACCEPTED DURING THE
 PLAN REVIEW PROCESS.NOTE THAT THE ORIGINAL LS PLAN
 SUBMITTED DID NOT PROPERLY ADDRESS THE COMMENTS AND A
 NEW LS PLAN WAS SUBMITTED AFTER DISCUSSION WITH THE
 ARCHITECT.
  
 3RD REVIEW:ONLY ONE ACCESSIBLE EXIT SHOWN FOR EACH
 AREA.BASED ON OCCUPANT LOAD, TWO EXITS ARE REQUIRED
 FOR THE DISTRIBUTION AREA, TWO EXITS ARE REQUIRED FOR
 THE OFFICE AREA.PROVIDE ALL INFORMATION FOR EXITING
 ON THE LIFE SAFETY PLAN FOR THE ACCESSIBLE EXITS.
 REVIEW WAS STOPPED AND I AGREED TO ACCEPT A NEW LIFE
 SAFETY PLAN IN ATTEMPT TO ISSUE THE PERMIT IF ALL OTHER
 ITEMS WERE ADDRESSED FROM ALL PLAN REVIEWERS, INCLUDING
 MY LIST.HOWEVER, THE LIFE SAFETY PLAN SUBMITTED WAS
 NOT COMPLIANT.
  
 FOURTH (COURTESY) REVIEW.THE NEW LIFE SAFETY PLAN
 SHOULD BE REVISED TO SHOW THE FOLLOWING FOR THE SECOND
 ACCESSIBLE MEANS OF EGRESS FROM THE DISTRIBUTION AREA:
  
 EXIT LIGHTS, FBC1006.3
 EXIT CAPACITY, FBC1004.1.3
 DOOR SWING, FBC1008.1.2
 TRAVEL DISTANCE, FBC1015
 EGRESS CAPACITY, FBC1005
  
 NOTE THAT TRAVEL DISTANCE IS SHOWN THROUGH THE MIDDLE
 OF SOME ROOMS; THIS IS USUALLY DONE AROUND THE
 PERIMETER OF THE ROOM, FBC1015.1.
  
 ALL OF THE ABOVE INFORMATION WAS PROVIDED ON THE LIFE
 SAFETY PLAN BUT DID NOT ADDRESS ACCESSIBLE MEANS OF
 EGRESS.SEE COMMENT 17, ACCESSIBLE MEANS OF EGRESS
 SHALL BE PROVIDED IN THE SAME NUMBER AS REQUIRED FOR
 EXITS BY LOCAL BUILDING/LIFE SAFETY REGULATIONS,
 FBC11-4.1.3(9).A LIFT WAS ADDED, EXITING THROUGH THE
 OFFICE AREA WAS DISCUSSED BUT NOTHING IS SHOWN ON THE
 PLAN; OTHER INFORMATION ABOVE NOT PROVIDED.
  
 17.)FBC11-4.1.3(9), ACCESSIBLE MEANS OF EGRESS SHALL
 BE PROVIDED IN THE SAME NUMBER AS REQUIRED FOR EXITS BY
 LOCAL BUILDING/LIFE SAFETY REGULATIONS. A RAMP IS SHOWN
 AT THE BUILDING ENTRANCE, NO OTHER ACCESSIBLE EXITS
 SHOWN.
  
 2ND REVIEW, THE RESPONSE LETTER STATES THAT ALL EXITS
 ARE ACCESSIBLE.SEE FBC11-3, DEFINITION OF EGRESS,
 MEANS OF; DOES NOT INCLUDE STAIRS, STEPS, OR
 ESCALATORS.
  
 (REVISED 4/12) 3RD COURTESY REVIEW, TWO EXITS ARE
 REQUIRED FROM THE DISTRIBUTION AREA AND TWO EXITS
 REQUIRED FROM THE OFFICE AREA.ONLY ONE ACCESSIBLE
 EXIT FOR EACH AREA IS SHOWN.
  
 (REVISED 4/12) 4TH REVIEW, REVISED LIFE SAFETY PLAN
 SUBMITTED DURING REVIEW; THERE IS STILL ONLY ONE
 ACCESSIBLE EXIT FROM THE DISTRIBUTION AREA, TWO
 REQUIRED BASED ON OCCUPANT LOAD.
  
 18.)1ST/2ND REVIEW: THIS BUILDING REQUIRES MORE THAN
 ONE EXIT, SEE FBC1018.2.THIS WAS NOT ADDRESSED FOR
 ACCESSIBLE EXITS; ONLY ONE SHOWN.
  
 (REVISED 4/12) 3RD REVIEW:SEE COMMENT 17.
  
 (REVISED 4/12) 4TH COURTESY REVIEW:THERE IS NOW ONE
 ACCESSIBLE EXIT SHOWN FOR THE DISTRIBUTION AREA
 (REQUIRES TWO BASED ON OCCUPANT LOAD) AND ONE FOR THE
 OFFICE AREA.OFFICE AREA IS COMPLIANT AS IT REQUIRES
 ONE EXIT BASED ON OCCUPANT LOAD, BUT TWO ACCESSIBLE
 EXITS ARE REQUIRED FOR THE DISTRIBUTION AREA.
  
 19-22.)ADDRESSED.
  
 23.)1ST/2ND REVIEWS: EXIT OR EXIT ACCESS DOORWAY
 ARRANGEMENT SHALL COMPLY WITH FBC1014.2 OR
 FBC1014.2.2., SHOW DISTANCE APART, SEE EXCEPTION 2.
 THERE ARE TO BE TWO ACCESSIBLE EXITS WHICH ARE REMOTELY
 LOCATED.ONLY ONE SHOWN ON THE PLAN (ALL OTHERS HAVE
 STAIRS).
  
 3RD REVIEW (REVISED 4/12):THE TWO DOORS SHOWN SERVE
 TWO DIFFERENT AREAS.SHOW THE TWO ACCESSIBLE EXITS,
 REMOTELY LOCATED, AS REQUESTED.
  
 4TH (COURTESY) REVIEW: THE DISTANCE IS SHOWN BETWEEN
 THE TWO ACCESSIBLE EXITS BUT THE EXIT WITH THE RAMP
 DOES NOT SERVE THE DISTRIBUTION AREA (NO EXIT SIGNS
 FROM DISTRIBUTION AREA THROUGH OFFICE, NOTHING ON THE
 PLAN TO SHOW THAT THIS IS TO BE AN EXIT TO SERVE THE
 DISTRIBUTION AREA).IT IS CLEAR THAT NON ACCESSIBLE
 EXITS ARE COMPLIANT.SHOW COMPLIANCE FOR ACCESSIBLE
 EXITS AS REQUESTED ON PREVIOUS REVIEWS.
  
 24.) ADDRESSED.
  
 25.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC.
  
 26.)THE COMMENT REGARDING REMOVABLE SHUTTERS WAS, I
 BELIEVE, ADDRESSED WITH SUBMITTAL OF IMPACT DOOR
 PRODUCT APPROVALS.IT APPEARS THAT IMPACT RATED
 PRODUCTS WILL BE USED.PLEASE NOTE THAT IF NON IMPACT
 PRODUCT APPROVALS ARE SUBMITTED ON THIRD REVIEW, A
 SHUTTER INSTALLATION PLAN WILL BE REQUIRED PRIOR TO
 PERMIT ISSUANCE.PLEASE CONTACT ME IF YOU WOULD LIKE
 TO PROPOSE THE USE OF REMOVABLE SHUTTERS TO DISCUSS
 THAT APPROVAL PROCESS.IF ALL PRODUCTS WILL BE IMPACT
 RATED, DISREGARD THE COMMENT.
  
 THIRD REVIEW - PLEASE SUBMIT ALL REQUIRED PRODUCT
 APPROVALS AT THIS TIME.
  
 27.)PLEASE NOTE THAT PRODUCT APPROVALS FOR IMPACT
 DOORS WERE SUBMITTED.PRODUCT APPROVALS ARE TO BE
 REVIEWED BY DESIGNER OF RECORD, FBC*106.3.3.NO OTHER
 PRODUCT APPROVALS WERE SUBMITTED.FLORIDA STATE OR
 LOCAL PRODUCT APPROVAL REQUIRED IN ADDITION TO THE
 EVALUATION REPORT (MIAMIDADE NOA IN THIS CASE)
 PROVIDED, FAC9B72; WWW.FLORIDABUILDING.ORG.IF FLORIDA
 STATE PRODUCT APPROVAL IS NOT AVAILABLE, PLEASE CONTACT
 ME TO DISCUSS.
  
 NO ROOFING PR-DUCT APPROVALS WERE SUBMITTED. CONTRACTOR
 OR DOR IS TO SELECT THE APPROVED ASSEMBLY.
  
 FOR ALL OTHER PRODUCTS, INCLUDING THE STANDING SEAM
 ROOF PANELS, IF THERE ARE DIFFERENT OPTIONS FOR
 INSTALLATION AND NOT ALL OF THEM ARE COMPLIANT FOR
 DESIGN PRESSURES FOR THIS BUILDING, CIRCLE THE
 INSTALLATION OR PARTICULAR OPTION YOU ARE USING SO THAT
 CODE COMPLIANCE CAN BE DETERMINED.
  
 THIRD REVIEW ? THE PRODUCT APPROVALS WHICH ARE IN THE
 PACKAGE STILL HAVE NO EVIDENCE THAT THEY HAVE BEEN
 REVIEWED BY DESIGNER OF RECORD.THIS MAY BE DONE WITH
 A SHOP DRAWING REVIEW STAMP, A LETTER, OR INCORPORATED
 INTO THE PLAN BY REFERENCE.
  
 ALL PRODUCT APPROVALS REQUIRED BY FAC9B72 ARE REQUIRED
 AT THIS TIME DUE TO A POLICY CHANGE.STATEMENTS IN THE
 PREVIOUS COMMENTS THAT THEY COULD BE SUBMITTED IN THE
 FUTURE UNDER SEPARATE PERMIT HAVE BEEN REMOVED FROM
 THIS REVIEW TO AVOID CONFUSION.
  
 AS THE DOR DID NOT PROVIDE A SCHEDULE, ALL WALL
 PRODUCTS ARE TO COMPLY WITH WORST CASE WALL PRESSURE OF
 -48PSF.PRODUCT APPROVALS REQUIRED INCLUDE STOREFRONT,
 SKYLIGHT, OVERHEAD DOOR, FULL LOUVER METAL DOOR,
 LOUVERS, ROOF HATCH, 24 GA GALVALUME STANDING SEAM
 METAL ROOF, 4 PLY BUR OVER INSULATED LW CONCRETE.THIS
 MAY NOT BE A COMPLETE LIST; CONTRACTOR OR DOR IS
 RESPONSIBLE FOR THE COMPLETENESS OF THE SUBMITTED
 PACKAGE.
  
 **4/12/07** DURING THE MEETING WITH THE ARCHITECT I
 BECAME AWARE THAT THE THREE BOUND SETS OF DOCUMENTS
 SUBMITTED WERE NOT IDENTICAL SETS.THERE WERE SOME
 PRODUCT APPROVALS REVIEWED BY DOR IN THE OTHER PACKAGE.
 THE ROOF PRODUCT APPROVAL WAS REVIEWED BY ANOTHER
 ARCHITECT FROM A DIFFERENT PRODUCT.
  
 WHEN RESUBMITTING, PLEASE PROVIDE THREE IDENTICAL BOUND
 SETS FOR PERMIT ISSUANCE.FAILURE TO DO SO WILL RESULT
 IN PERMIT DELAYS.
  
 ALL OTHER COMMENTS IN REGARDS TO PRODUCT APPROVALS
 STILL APPLY.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED FOR ALL PRODUCTS, FAC9B72,
 WWW.FLORIDABUILDING.ORG.FLORIDA STATE PRODUCT
 APPROVAL IS TO BE FOR THE 2004 CODE (NOT 2001 AS IS THE
 CASE WITH THE OVERHEAD DOOR PRODUCT APPROVAL).ONLY
 ONE SHEET OF THE NOA FOR THE INGERSOLL RAND DOOR WAS
 SUBMITTED; ALL SHEETS REQUIRED.IF A FLORIDA STATE
 PRODUCT APPROVAL IS NOT AVAILABLE FOR ANY OF THE
 PRODUCTS YOU HAVE SELECTED, PLEASE CONTACT ME IN
 REGARDS TO THE PROCEDURE FOR APPLICATION FOR LOCAL
 PRODUCT APPROVAL.
  
 28.)SQUARE FOOT AREAS ON THE ENERGY CALCS DO NOT
 MATCH THE PLAN.
  
 THIRD REVIEW - THE ARCHITECT RESPONSE LETTER STATES
 THAT INSIDE DIMENSIONS WERE USED FOR THE ENERGY CALCS.
 SEE FBC 13, CHAPTER 2, DEFINITION OF FLOOR AREA, GROSS.
 AS NEW ENERGY CALCS ARE REQUIRED, ELECTRIC REVIEW WILL
 ALSO BE REQUIRED ON RESUBMITTAL.NOTE THAT ENERGY
 CALCS ARE A STATUTORY REQUIREMENT AND STATUTORY
 REQUIREMENTS CAN NEVER BE WAIVED OR PROVISO?D (PER
 BUILDING OFFICIAL).
  
 29.)FROM FIRST REVIEW - THE ENGINEER'S TITLE BLOCK IS
 TO COMPLY WITH FAC61G15-23.002, VP BUILDINGS.
  
 4/12/07MR. JOHN RYAN, ATTORNEY FOR FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS, CONFIRMED THE CERTIFICATE OF
 AUTHORIZATION REQUIREMENT, FS471.023.THE ENGINEER'S
 LETTER STATING THAT ENGINEERING IS NOT THE PRODUCT
 OFFERED TO THE PUBLIC IS ACKNOWLEDGED.HOWEVER, WHEN
 PRACTICING ENGINEERING THROUGH A COMPANY, A CERTIFICATE
 OF AUTHORIZATION IS REQUIRED REGARDLESS OF PRODUCT
 OFFERED.PLEASE CONTACT FBPE IF YOU NEED FURTHER
 CLARIFICATION, 850-521-0500.AS THIS IS A STATUTORY
 REQUIREMENT, THIS CANNOT BE WAIVED OR PROVISO'D; PLANS
 MUST BE IN COMPLIANCE FOR PERMITTING.
  
 30.)ADDRESSED.
  
 31.)THE ENGINEER'S SIGNATURE IS A PHOTOCOPY, ORIGINAL
 WET SIGNATURE REQUIRED.SEE PANEL SHEETS AND VP
 SHEETS.
  
 THIRD REVIEW - PANEL ENGINEERING STILL HAS A PHOTOCOPY
 SIGNATURE.ALSO ALL INFORMATION REQUIRED BY
 FAC61G15-23.002 IS REQUIRED TO BE ON EACH SHEET
 (CERTIFICATE OF AUTHORIZATION).
  
 THE FOOTERS, SITEWORK, AND STRUCTURE (PANELS, STEEL
 STRUCTURE) WERE ISSUED UNDER SEPARATE PERMITS.HAVE
 THE CHANGES SHOWN ON THE CIVIL DRAWINGS BEEN MADE TO
 THE ISSUED SITEWORK PERMIT?PLEASE PROVIDE A PERMIT
 NUMBER FOR THE SITEWORK.
  
 THE PANEL PLANS AND STEEL STRUCTURAL PLANS ARE NOT
 REQUIRED FOR THIS PERMIT AS THEY ARE INCLUDED IN THE
 SCOPE OF WORK OF ANOTHER PERMIT.IF EITHER PLAN IS
 CHANGED AS A RESULT OF THESE COMMENTS, THE CHANGES
 SHOULD BE SUBMITTED AS REVISIONS TO THE ISSUED PERMIT.
 ALSO HAVING A SET INCLUDED FOR REFERENCE (AS LONG AS IT
 MATCHES THE PERMIT SET) WILL ASSIST IN PLAN REVIEW.
  
 32-36.) ADDRESSED.
  
 37.)SEE ATTACHED FS553.80(2)(B).NOTE THAT THIS IS A
 MANDATORY FINE AND CANNOT BE WAIVED.NOTE THAT SOME
 COMMENTS HAVE ALREADY BEEN MADE THREE TIMES (ENERGY
 CALCS, LIFE SAFETY).A 4X PLAN REVIEW FEE HAS BEEN
 CHARGED.
  
 NEW COMMENTS:
  
 38.)SEE CIVIL SHEET 17 OF 29 PREPARED BY BOYER
 SINGLETON.THIS SHEET HAS A DATE OF FEBRUARY 12, 2007,
 NO CHANGES CLOUDED.THE SECOND BUILDING REVIEW WAS
 JANUARY 30, 2007.THIS IS EITHER A NEW SHEET OR
 CHANGES WERE MADE TO THE SHEET AND NOT INDICATED.ALL
 CHANGES TO THE PLAN ARE TO BE CLEARLY INDICATED WITH
 CLOUDS AND REVISION NUMBERS.WHEN CHANGES ARE
 SUBMITTED A COMPLETE NEW PLAN REVIEW IS REQUIRED AS I
 CANNOT DETERMINE SPECIFICALLY WHAT HAS CHANGED.NOTE
 THAT THE ARCHITECT (CORRECTLY) CLOUDED THE PAGE NUMBER
 TO SHOW NEW SHEETS.
  
 THE "TURNSTILE & HANDICAPPED SECURITY GATE" DETAIL ON
 SHEET 17 IS ILLEGIBLE.AS THIS DETAIL IS REQUIRED TO
 SHOW CODE COMPLIANCE (ACCESSIBILITY, EGRESS) PLEASE
 PROVIDE LEGIBLE DETAILS.
  
 4/12/07 ** IN THE MEETING WITH ARCHITECT ON 4/11/7, IT
 WAS DISCUSSED THAT THIS DETAIL IS ALSO IN THE ELECTRIC
 DRAWINGS.TO AVOID FURTHER PERMITTING DELAYS, DO NOT
 ADDRESS THIS COMMENT AT THIS TIME.FOR THE FUTURE,
 PLEASE NOTE THAT ALL DETAILS ARE REQUIRED TO BE
 LEGIBLE!!!WHEN ISSUING THE PERMIT I WILL MAKE A NOTE
 ON THE PLAN REFERRING TO THE APPROPRIATE ELECTRIC
 SHEET.
  
 39.)SHEET 18 OF 24 OF THE CIVIL DRAWINGS CONTAINS
 INFORMATION IN REGARDS TO THE FUEL TANK.THIS IS
 CURRENTLY IN THE PLAN REVIEW PROCESS UNDER SEPARATE
 PERMIT.AS THIS SHEET HAS NOT BEEN REVIEWED BY ALL
 TRADES FOR CODE COMPLIANCE, AND TO AVOID HAVING
 INFORMATION IN THIS PERMIT WHICH CONFLICTS WITH OTHER
 PERMITS, PLEASE REMOVE THIS SHEET.
  
 40.)A3.0, THERE IS A NEW NOTE STATING THAT A
 SATELLITE DISH IS TO BE INSTALLED AND A SLEEVE PROVIDED
 IN THE TILT WALL PANEL.PROVIDE A DETAIL FOR THE
 SATELLITE DISH AND A SPECIFICATION FOR THE SLEEVE.THE
 WALL PANEL ENGINEER IS TO INCLUDE THIS INFORMATION IN
 HIS STRUCTURAL DRAWINGS.SEE SHEET PN10; THERE IS A
 NOTE ADDRESSING CORE DRILLING AFTER ERECTION.IT IS
 NOT CLEAR IF THIS SLEEVE IS TO BE PROVIDED IN THE PANEL
 WHEN IT IS CONSTRUCTED OR IF IT IS DRILLED AFTER
 ERECTION.IN EITHER CASE, IT REQUIRES THE APPROVAL OF
 THE WALL PANEL ENGINEER AND SHOULD ALSO BE ADDRESSED ON
 HIS DRAWINGS SO THAT THE STRUCTURAL DRAWINGS ARE
 CONSISTENT WITH THE ARCHITECTURAL DRAWINGS.
  
 **4/12/07** IN THE MEETING WITH THE ARCHITECT, IT WAS
 AGREED THAT THE STRUCTURE/WALL PANEL PERMIT IS TO BE
 REVISED AND THAT THIS PLAN WILL BE REVISED TO SHOW
 METHOD OF ATTACHMENT AND ALSO WILL STATE THAT SHOP
 DRAWINGS WILL BE REQUIRED PRIOR TO ISSUANCE.
  
 41.)A4.0, ELEVATION AND ENTRY DETAIL, SEE
 FBC11-4.13.7.WHEN SCALED, IT APPEARS TO MEET THE
 MINIMUM REQUIREMENT EXACTLY BUT PLEASE NOTE THAT
 REQUIREMENT ON THE PLAN.
  
 42.)SEE THE STRUCTURAL PAGES PREPARED AND SIGNED BY
 BRADLEY B. JOHNSON, PE.FS471, FAC61G15-23, THE SEAL
 IS NOT LEGIBLE.
  
 **4/12/07**IN THE MEETING WITH THE ARCHITECT AND
 CONTRACTOR, IT WAS AGREED THAT THE BEST COURSE OF
 ACTION WOULD BE TO SUBMIT AS SOON AS POSSIBLE.THE
 ENGINEER HAS ORDERED A NEW SEAL.IF NEWLY SEALED
 SHEETS ARE NOT AVAILABLE AT THE TIME OF RESUBMITTAL, I
 WILL ALLOW THE CONTRACTOR OR ARCHITECT TO BRING IN THE
 NEW SHEETS (NEW SEAL ONLY, NO CHANGE TO DRAWING) AFTER
 RESUBMITTAL PROVIDED THAT ALL OTHER COMMENTS FROM ALL
 PLANS EXAMINERS HAVE BEEN SATISFIED.
  
 43.)***NEW COMMENT 4/12/07***THE ARCHITECT'S
 OBJECTION TO SHOWING COMPLIANCE WITH ALL EXITING
 REQUIREMENTS FOR ACCESSIBLE EXITS IS NOTED.AS
 DISCUSSED, THE NEW LIFE SAFETY PLAN WILL SHOW
 COMPLIANCE AS REQUESTED ALTHOUGH THE ARCHITECT DOES NOT
 AGREE WITH THE REQUIREMENT.
  
 HOWEVER, WE ARE IN AGREEMENT REGARDING ITEMS #17 AND
 18.MY UNDERSTANDING IS THAT THE ARCHITECT AGREES THAT
 TWO ARE REQUIRED AND ONLY ACCESSIBLE EXIT SERVING THE
 DISTRIBUTION AREAIS SHOWN ON THE PLAN, FOUR REVIEWS.
  
  
 TO EXPEDITE PLAN REVIEW, INCLUDE A RESPONSE LETTER
 INDICATING HOW EACH ITEM WAS ADDRESSED WHEN
 RESUBMITTING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-01-30 Cont ID  
Sent By shill Date 2007-01-30 Time 11:14 Rev Time 0.00
Received By shill Date 2007-01-23 Time 08:35 Sent To  
Notes
2007-01-30 11:14:52****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1-8.) ADDRESSED.
  
 9.)A SEPARATE PERMIT WILL BE REQUIRED FOR THE SIGN
 SHOWN ON A-0.1.SEPARATE PLANS AND PERMIT APPLICATION
 WILL BE REQUIRED.INFORMATIONAL ONLY; THIS IS NOT
 REQUIRED TO BE ADDRESSED AT THIS TIME.
  
 10.)ADDRESSED.
  
 11.)ADDRESSED.
  
 12.)S1 WAS DECLARED, BUT THE LIFE SAFETY PLAN SHOWS
 S2.PLEASE ADDRESS.
  
 13.)EXTRA FP1 SHEETS WERE SUBMITTED.PLEASE PROVIDE
 THREE ORIGINALS, ONE PUT INTO EACH ROLLED PERMIT SET.
  
  
 14-15.) ADDRESSED.
  
 16.)A LIFE SAFETY PLAN WAS PROVIDED IN RESPONSE TO
 THE PREVIOUS COMMENT.PLEASE ADDRESS THE FOLLOWING
 ITEMS:
  
 A. THE PURPOSE OF THE OVERLAPPING CIRCLES ON THE PLAN
 IS NOT CLEAR, AND NO PATH OF EGRESS TRAVEL WAS SHOWN.
 TYPICALLY THE WORST CASE TRAVEL DISTANCE IS SHOWN FROM
 EACH AREA TO THE REQUIRED EXITS.PLEASE REMOVE THE
 CIRCLES AS THEY MAKE THE PLAN DIFFICULT TO READ, OR
 CLARIFY THE PURPOSE.
  
 B. THE LIFE SAFETY PLAN STATES THAT TRAVEL DISTANCE IS
 UNLIMITED FOR S2 OCCUPANCY, BUT YOU HAVE DECLARED S1 ON
 SHEET A0.0.SEE FBC TABLE 1015.1, S1 HAS A MAXIMUM
 TRAVEL DISTANCE OF 250FEET, FULLY SPRINKLED BUILDING.
 ALSO SEE OTHER NOTES REGARDING ACCESSIBLE EXITS.
  
 C. OCCUPANT LOAD OF 63 HAS BEEN DECLARED FOR THE
 WAREHOUSE AREA.A0.0 DECLARES 32,720 SF.SEE FBC
 TABLE 1004.1.2, FBC 1004.1 STATES THAT OCCUPANT LOAD
 CANNOT BE LESS THAN THE TABLE, SO SHOULD BE A MINIMUM
 OF 65 BASED ON SF AREA.
  
 D. FBC1005.1, THE LOSS OF ANY ONE MEANS OF EGRESS SHALL
 NOT REDUCE THE AVAILABLE CAPACITY TO LESS THAN 50
 PERCENT OF THE REQUIRED CAPACITY.BASED ON DESIGN
 OCCUPANT LOAD FOR THE BUSINESS AREA, THE EXITING DOES
 NOT COMPLY.PLEASE ADDRESS.
  
 E. THE SCALE APPEARS TO BE 1/16.NOTE THE SCALE ON THE
 PLAN.PROVIDE OVERALL DIMENSIONS.
 17.)FBC11-4.1.3(9), ACCESSIBLE MEANS OF EGRESS SHALL
 BE PROVIDED IN THE SAME NUMBER AS REQUIRED FOR EXITS BY
 LOCAL BUILDING/LIFE SAFETY REGULATIONS. A RAMP IS SHOWN
 AT THE BUILDING ENTRANCE, NO OTHER ACCESSIBLE EXITS
 SHOWN.
  
 THE RESPONSE LETTER STATES THAT ALL EXITS ARE
 ACCESSIBLE.SEE FBC11-3, DEFINITION OF EGRESS, MEANS
 OF; DOES NOT INCLUDE STAIRS, STEPS, OR ESCALATORS.
  
 18.)THIS BUILDING REQUIRES MORE THAN ONE EXIT, SEE
 FBC1018.2.THIS WAS NOT ADDRESSED FOR ACCESSIBLE
 EXITS; ONLY ONE SHOWN.
  
 19.)A1.0 SHOWS A CHECK WRITING STAND, PLEASE NOTE ON
 THE PLAN THAT THIS AREA IS NOT OPEN TO THE PUBLIC.
  
 20-21.) ADDRESSED.
  
 22.)FBC11-4.1.3(8)(A)(II), ACCESSIBLE ENTRANCES
 REQUIRED AT LEAST EQUIVALENT TO THE NUMBER OF
 ACCESSIBLE EXITS.SEE OTHER COMMENTS.ENTRANCES WITH
 STAIRS DO NOT MEET THE REQUIREMENTS OF VERTICAL
 ACCESSIBILITY.
  
 23.)EXIT OR EXIT ACCESS DOORWAY ARRANGEMENT SHALL
 COMPLY WITH FBC1014.2 OR FBC1014.2.2., SHOW DISTANCE
 APART, SEE EXCEPTION 2.THERE ARE TO BE TWO ACCESSIBLE
 EXITS WHICH ARE REMOTELY LOCATED.ONLY ONE SHOWN ON
 THE PLAN (ALL OTHERS HAVE STAIRS).
  
 24.)ADDRESSED.
  
 25.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC.
  
 26.)THE COMMENT REGARDING REMOVABLE SHUTTERS WAS, I
 BELIEVE, ADDRESSED WITH SUBMITTAL OF IMPACT DOOR
 PRODUCT APPROVALS.IT APPEARS THAT IMPACT RATED
 PRODUCTS WILL BE USED.PLEASE NOTE THAT IF NONIMPACT
 PRODUCT APPROVALS ARE SUBMITTED ON THIRD REVIEW, A
 SHUTTER INSTALLATION PLAN WILL BE REQUIRED PRIOR TO
 PERMIT ISSUANCE.PLEASE CONTACT ME IF YOU WOULD LIKE
 TO PROPOSE THE USE OF REMOVABLE SHUTTERS TO DISCUSS
 THAT APPROVAL PROCESS.IF ALL PRODUCTS WILL BE IMPACT
 RATED, DISREGARD THE COMMENT.
  
 27.)PLEASE NOTE THAT PRODUCT APPROVALS FOR IMPACT
 DOORS WERE SUBMITTED.PRODUCT APPROVALS ARE TO BE
 REVIEWED BY DESIGNER OF RECORD, FBC*106.3.3.NO OTHER
 PRODUCT APPROVALS WERE SUBMITTED.NOTE THAT ANY
 PRODUCT APPROVALS NOT SUBMITTED AND REVIEWED PRIOR TO
 PERMIT ISSUANCE WILL REQUIRE SEPARATE PERMITS WITH
 SEPARATE FEES.FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED IN ADDITION TO THE EVALUATION REPORT
 (MIAMIDADE NOA IN THIS CASE) PROVIDED, FAC9B72.
 WWW.FLORIDABUILDING.ORGIF FLORIDA STATE PRODUCT
 APPROVAL IS NOT AVAILABLE, PLEASE CONTACT ME TO
 DISCUSS.
  
 NO ROOFING PRODUCT APPROVALS WERE SUBMITTED.THIS MAY
 BE DONE WHEN THE ROOF PERMIT IS APPLIED FOR (WITH
 SEPARATE FEES BASED ON VALUE), OR MAY BE DONE NOW.
 CONTRACTOR OR DOR IS TO SELECT THE APPROVED ASSEMBLY.
  
  
 FOR ALL OTHER PRODUCTS, INCLUDING THE STANDING SEAM
 ROOF PANELS, IF THERE ARE DIFFERENT OPTIONS FOR
 INSTALLATION AND NOT ALL OF THEM ARE COMPLIANT FOR
 DESIGN PRESSURES FOR THIS BUILDING, CIRCLE THE
 INSTALLATION OR PARTICULAR OPTION YOU ARE USING SO THAT
 CODE COMPLIANCE CAN BE DETERMINED.
  
 28.)SQUARE FOOT AREAS ON THE ENERGY CALCS DO NOT
 MATCH THE PLAN.
  
 29.)ADDRESSED.
  
 30.)INCLUDE THE CORRECT JURISDICTION ON THE ENERGY
 CALCS, 604700 FBC13.
  
 31.)THE ENGINEER'S SIGNATURE IS A PHOTOCOPY, ORIGINAL
 WET SIGNATURE REQUIRED.SEE PANEL SHEETS AND VP
 SHEETS.
  
 NEW COMMENTS:
  
 32.)A1.2, SPECIFY DESIGN CRITERIA FOR STAIR AND GUARD
 RAIL RATHER THAN QUOTING A CODE SECTION.PROVIDE A
 DETAIL FOR THE STAIR HANDRAIL, GUARD RAILS, AND RAMP
 HANDRAIL.SEE FBC11-4.8.5, FBC11-4.9.4.WHEN SCALED,
 STAIR HANDRAIL EXTENSIONS ARE NOT LONG ENOUGH.
  
 CLARIFY 5-A4.0 HANDRAIL.IT APPEARS ON THE BOTTOM HALF
 OF THE RAMP BUT NOT THE TOP HALF.
  
 33.)5-A4.0, SHOW THE MINIMUM DIMENSION WHERE THE RAMP
 CHANGES DIRECTION.WHEN SCALED IT IS COMPLIANT AT
 60IN, FBC11-4.8.4(3).
  
 34.)SOILS REPORTS NOT NECESSARY AS THEY WERE PROVIDED
 WITH THE FOUNDATION PERMIT.
  
 35.)THE PANEL CALCS STATES THAT THE PROJECT NAME IS
 SEA HUNTER BOATS ON SOME PAGES.
  
 36.)S2.1, ENGINEER HAS SPECIFIED 69PSF FOR THE FLAT
 DECK ROOF, ZONES 2 AND 3.PROVIDE CALCULATIONS.
  
 37.)SEE ATTACHED FS553.80(2)(B).
  
  
 TO EXPEDITE PLAN REVIEW, INCLUDE A RESPONSE LETTER
 INDICATING HOW EACH ITEM WAS ADDRESSED WHEN
 RESUBMITTING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-23 Cont ID  
Sent By shill Date 2006-10-23 Time 10:51 Rev Time 0.00
Received By shill Date 2006-10-20 Time 09:10 Sent To  
Notes
2006-10-23 10:52:13****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL
 561-233-5025 FOR MORE INFORMATION.
  
 3.)THE COPY OF THE PLAT PROVIDED IS NOT RECORDED.
 PLEASE ADVISE AS TO STATUS.IF THIS IS RECORDED,
 PROVIDE PLAT FILING INFORMATION (BOOK/PAGE).
  
 4.)THE PLAT PROVIDED AND THE PROPOSED PLAT LINES ON
 THE OVERALL SITE PLAN PREPARED BY BOWYER SINGLETON DO
 NOT MATCH.FOR INSTANCE, THE CIRCULAR SECTION AT THE
 END OF THE ROAD (PARCEL G) DOES NOT APPEAR ON THE
 OVERALL SITE PLAN.THE PLAT LINES ARE INCOMPLETE ON
 THE OVERALL SITE PLAN.
  
 5.)THE APPLICATION REFERS TO TWO DIFFERENT PARCEL ID
 NUMBERS.YOU CANNOT CROSS PROPERTY LINES.PROVIDE
 INFORMATION IN REGARDS TO THE LOCATION OF THE TWO
 PARCELS, ENDING IN 3010 AND 3040.OUR GIS RECORDS
 SHOWS 3010 AS A VERY SMALL PARCEL (POSSIBLY A ROAD)
 GOING THROUGH THE MIDDLE OF THE LARGER PARCEL, 3040.
 PLEASE CONTACT ME TO DISCUSS IF YOU ARE UNSURE AS TO
 HOW TO GET THIS MATTERS RESOLVED.
  
 6.) FBC* 109.3.7RESIDENT INSPECTOR. SUBMIT INSPECTOR
 RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA,
 DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.A RESIDENT
 INSPECTOR PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO
 ONE OR MORE OF THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS
 OF CONSTRUCTION
  
 ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION
 SERVICES MANAGER - TEL:
 561 805 6711), A MEETING INVOLVING THE OWNER, RESIDENT
 INSPECTOR, JOB INSPECTOR, CONTRACTOR AND ENGINEER. THIS
 MUST BE DONE PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL
 SETS OF ALL DOCUMENTS ARE REQUIRED FOR PERMITTING.
  
 7.)THERE ARE TWO FULL SETS OF CIVILS WITH DIFFERENT
 DATES.MANY SHEETS APPEAR UNNECESSARY AS THEY ARE FOR
 OTHER BUILDINGS.THERE IS ALREADY A SITEWORK PERMIT
 PENDING.PLEASE COORDINATE WITH ENGINEERING; ANY CIVIL
 SHEETS REQUIRED IN THIS PACKAGE TO SHOW CODE COMPLIANCE
 IS TO MATCH OTHER APPROVED DRAWINGS.ALSO NOTE THAT
 THERE ARE DETAILS FROM THE CITY OF RIVIERA BEACH.
  
 8.)RADON FEES DUE, FS553.721.SEE ATTACHED.
  
 9.)A SEPARATE PERMIT WILL BE REQUIRED FOR THE SIGN
 SHOWN ON A-0.1.SEPARATE PLANS AND PERMIT APPLICATION
 WILL BE REQUIRED.NOTE THAT WIND DESIGN CRITERIA
 FBC1603.1.4 WILL BE REQUIRED.DESIGN CRITERIA SHOWN
 DOES NOT PROVIDE ALL REQUIRED INFORMATION.
  
 10.)THE ACCESSIBLE ROUTE FROM THE PUBLIC WAY IS SHOWN
 ON A-0.1, SHOW SLOPE AND WIDTH FBC11-4.1.2(1).
  
 11.)S2 DECLARED, SEE FBC302; IT APPEARS THAT THIS IS
 A MIXED USE DUE TO THE 5000 SF OF BUSINESS AREA,
 FBC302.3.
  
 12.)S2 DECLARED, SEE FBC311.3, DEFINITION IS FOR
 NON-COMBUSTIBLE STORAGE.PROVIDE INFORMATION IN
 REGARDS TO WHAT WILL BE STORED AND WHAT ACTIVITY WILL
 TAKE PLACE IN THIS BUILDING.NOTE THAT PACKAGING MUST
 BE ADDRESSED AS WELL AS THE ITEMS STORED.
  
 13.)THE FEDEX FREIGHT SITE PLAN (CIVIL) SHOWS A 10FT
 CANOPY.SEE FBC502, DEFINITION OF AREA, BUILDING.
 PLEASE CLARIFY WHAT THIS IS, AND SHOULD THIS BE
 INCLUDED IN BUILDING AREA?
  
 14.)EXTRA FP1 SHEETS WERE SUBMITTED; NOT CLEAR AS TO
 WHY.PLEASE PROVIDE ONLY THREE COMPLETE ORIGINAL SETS
 FOR PERMITTING, COLLATED.
  
 15.)ELECTRIC SHEETS SHOW EXIT LIGHTS LEADING TO THE
 WAREHOUSE AREA, NONE AT DOORS TO THE OUTSIDE.SEE
 FBC1006.3.
  
 16.)PROVIDE A LIFE SAFETY PLAN, FBC*106.3.5.1.1(6)
 AND (7).INCLUDE THE FOLLOWING:
 OCCUPANT LOAD FOR EACH AREA, FBC302.
 EGRESS CAPACITIES, FBC1005.
 EXIT LIGHTS, FBC1006.3.
 EXITING INFORMATION, FBC10.
 ANY OTHER INFORMATION REQUIRED TO DETERMINE CODE
 COMPLIANCE
  
 17.)FBC11-4.1.3(9), ACCESSIBLE MEANS OF EGRESS SHALL
 BE PROVIDED IN THE SAME NUMBER AS REQUIRED FOR EXITS BY
 LOCAL BUILDING/LIFE SAFETY REGULATIONS. A RAMP IS SHOWN
 AT THE BUILDING ENTRANCE, NO OTHER ACCESSIBLE EXITS
 SHOWN.
  
 18.)THIS BUILDING REQUIRES MORE THAN ONE EXIT, SEE
 FBC1018.2.
  
 19.)A1.0 SHOWS A CHECK WRITING STAND, REFERS TO DTL
 4/A2.01.I COULD NOT LOCATE THAT SHEET.PROVIDE A
 DETAIL, OR CHANGE REFERENCE, AND SHOW ACCESSIBILITY
 FBC11-7.2.
  
 20.)BREAK ROOM IS SHOWN AS POD AREA, WHAT DOES THIS
 MEAN?
  
 21.)A1.0 SHOWS AN AREA OF RESCUE.DO YOU MEAN AREA
 OF RESCUE ASSISTANCE?IT IS ACCEPTABLE TO EXCEED CODE,
 BUT NOTE THAT THIS IS NOT REQUIRED FBC11-4.1.3(9)
 EXCEPTION.ALSO THIS IS FOR EXITS FROM OCCUPIABLE
 LEVELS ABOVE OR BELOW THE LEVEL OF THE MEANS OF
 ACCESSIBLE EXIT DISCHARGE.THIS IS THE LEVEL OF
 ACCESSIBLE EXIT DISCHARGE, SO AN ACCESSIBLE EXIT IS
 REQUIRED.
  
 22.)FBC11-4.1.3(8)(A)(II), ACCESSIBLE ENTRANCES
 REQUIRED AT LEAST EQUIVALENT TO THE NUMBER OF
 ACCESSIBLE EXITS.
  
 23.)EXIT OR EXIT ACCESS DOORWAY ARRANGEMENT SHALL
 COMPLY WITH FBC1014.2 OR FBC1014.2.2., SHOW DISTANCE
 APART, SEE EXCEPTION 2.
  
 24.)S2.1, CONCRETE NOTE 1, REFERS TO ACI318-95,
 PLEASE USE CURRENT STANDARD.CHECK ALL REFERENCES.
  
 25.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC.
  
 26.)IMPACT PROTECTION REQUIRED.NONIMPACT STOREFRONT
 PRODUCT APPROVALS WERE SUBMITTED.SEE ATTACHED POLICY,
 ITEM 13, IN REGARDS TO IMPACT PROTECTION ON COMMERCIAL
 BUILDINGS.USE IF REMOVABLE SHUTTERS ON COMMERCIAL
 BUILDINGS MUST BE APPROVED BY THE BUILDING OFFICIAL.
  
  
 27.)IF YOU ARE USING HURRICANE SHUTTERS, SEE ATTACHED
 SCHEDULE FOR INSTALLATION.PROVIDE PRODUCT APPROVALS
 AND ALL REQUIRED INFORMATION TO DETERMINE CODE
 COMPLIANCE.
  
 28.)SQUARE FOOT AREAS ON THE ENERGY CALCS DO NOT
 MATCH THE PLAN.
  
 29.)THE ENGINEER'S TITLE BLOCK IS TO COMPLY WITH
 FAC61G15-23.002, VP BUILDINGS.
  
 30.)INCLUDE THE CORRECT JURISDICTION ON THE ENERGY
 CALCS, 604700 FBC13.
  
 31.)THE ENGINEER'S SIGNATURE IS A TITLE BLOCK,
 ORIGINAL WET SIGNATURE REQUIRED.
  
 32.)PROVIDE ROOF DRAINAGE CALCULATIONS FBC1503.4.
 PROVIDE DETAILS, SHOW OVERFLOW.
  
  
 TO EXPEDITE PLAN REVIEW, INCLUDE A RESPONSE LETTER
 INDICATING HOW EACH ITEM WAS ADDRESSED WHEN
 RESUBMITTING.

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2007-11-01 Cont ID  
Sent By dpalmer Date 2007-11-01 Time 08:15 Rev Time 0.00
Received By dpalmer Date 2007-11-01 Time 08:15 Sent To PC
Notes
2007-11-01 08:17:09*** PROVISO ****
  
  
 1) NOTE: PLEASE SUBMIT REVISED ENERGY CALCULATIONS
 BEFORE FINAL AS LIGHTING FIXTURES HAVE CHANGED. FBC
 CHAPTER 13

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2007-09-15 Cont ID  
Sent By dpalmer Date 2007-09-15 Time 09:38 Rev Time 0.00
Received By dpalmer Date 2007-09-15 Time 09:28 Sent To PC
Notes
2007-09-15 09:39:34REV 4A ND 5 FOR 2.1, 2.2 2.3 ONLY.
 NOTES FROM PREVIOUS REVIEW STILL APPLY

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2007-09-13 Cont ID  
Sent By dpalmer Date 2007-09-13 Time 13:40 Rev Time 0.00
Received By dpalmer Date 2007-09-13 Time 13:15 Sent To  
Notes
2007-09-13 13:41:09 
 ** DENIED **
  
 1) NOTE: PLEASE SEE THE NEW SEPARATE ELECTRICAL SERVICE
 AND METER LOCATION WOULD BE UNDER A SEPARATE PERMIT FOR
 THE SERVICE. THIS IS NOT ACTUALLY COMING FROM THE
 BUILDING ELECTRICAL SERVICE OR ANY PART OF THE
 BUILDING.
 PLEASE SEE THIS LOCATION WILL ALSO REQUIRE AN ADDRESS
 EXTENSION TO PCN FOR NEW METER/SERVICE LOCATION. PLEASE
 BE SURE TO GET WITH THE FPL REPRESENTATIVE AND THE CITY
 ADDRESSING REVIEWER LILI LACRAMIOARA @ 561-822-1239.
  
 2) NOTE: PLEASE CLARIFY RISER AS THIS SHOWS A *GROUND*
 ON THE LINE SIDE OF THE FIRST MEANS OF DISCONNECT. IS
 THIS THE NEUTRAL/GROUNDED CONDUCTOR?
 NO *EQUIPMENT GROUNDING CONDUCTORS* ARE ALLOWED ON THE
 LINE SIDE OF SERVICE MAINS.
 250.6, 250.24
  
 3) NOTE: TWO GROUND RODS MINIMUM WILL BE REQUIRED PER
 250.50 AND 250.56
  
 4) NOTE: PLEASE PROVIDE INFORMATION FOR PUMP SIZE AND
 OVER CURRENT PROTECTION INFORMATION.
 REVIEW OF SOME ITEMS FOR CONDUCTOR SIZES, SERVICE ETC
 CAN NOT BE REVIEWED AT THIS TIME.
  
 ** PLEASE KNOW THE ABOVE ELECTRICAL WILL NEED TO BE
 SUBMITTED UNDER AN ELECTRICAL PERMIT FOR THE NEW
 SEPARATE SERVICE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-05-01 Cont ID  
Sent By dpalmer Date 2007-05-01 Time 08:44 Rev Time 0.00
Received By dpalmer Date 2007-05-01 Time 08:44 Sent To  
Notes
2007-05-01 08:45:11REVISED SHEET E2.1 TO MEET BLDG CODE REQUIRED EXIT.
 THE REDLINED NOTES ON PLANS AS OF 3/20/07 REVIEW IS
 STILL NOTED.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-03-20 Cont ID  
Sent By dpalmer Date 2007-03-20 Time 15:50 Rev Time 0.00
Received By dpalmer Date 2007-03-20 Time 15:44 Sent To  
Notes
2007-03-20 15:52:17***REDLINED 8.1 AND 8.2 FOR FUEL WHICH IS UNDER A
 SEPARATE PERMIT

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-03-18 Cont ID  
Sent By dpalmer Date 2007-03-18 Time 16:21 Rev Time 0.00
Received By dpalmer Date 2007-03-18 Time 14:55 Sent To  
Notes
2007-03-18 16:24:30** UNSAT **
  
 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS
 SUBMITTED DOES NOT CONTAIN ANY INTERIOR LIGHTING ON THE
 COMPLIANCE SUMMARY SHEET #2. THIS LIGHTING IS IN THE
 INPUT DATA REPORT WHICH IS ATTACHED TO ENERGY
 CALCULATIONS.
 PLEASE BE SURE TO HAVE THE PRINTED NAME AND LICENSE
 NUMBER OF THE DESIGNER OF RECORD ON SHEET 3.
 PLEASE SEE SHEET 7 WHICH IS NOT FILLED OUT.
 REVIEW FOR CODE COMPLIANCE AND COORDIANTION WITH PLANS
 TO BE DONE UPON FINAL DOCUMENTS.
 ** THIS WILL NOT BE THE ONLY OUTSTANDING COMMENT FROM
 TRADES.
 PLEASE KNOW *IF* WAS TO REMAIN THE ONLY COMMENT FOR
 ISSUANCE, THEN CALL TO GO OVER.
  
 2) PLEASE SEE BUILDING REVIEW COMMENTS. ** ONLY NOTED,
 SEE THE *PN* SHEETS SUBMITTED CONTAIN A RAISED SEAL OF
 OVER A PHOTO-COPIED SIGNATURE FROM THE ENGINEER OF
 RECORD WHICH IS REQUIRED TO BE ORIGINAL ALONG WITH THE
 DATE WHEN SIGNED. FAC 61G15-23.002, FS 471.025
  
 ** REDLINED SHEET 8.1 AND 8.2, FUEL SYSTEM IS UNDER A
 SEPARATE PERMIT. PLANS ARE FOR MAIN POWER AND REFERENCE
 ONLY.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-01-09 Cont ID  
Sent By dpalmer Date 2007-01-09 Time 13:20 Rev Time 0.00
Received By dpalmer Date 2007-01-07 Time 19:53 Sent To  
Notes
2007-01-09 13:22:47** UNSAT **
  
 2ND REVIEW
 FED EX FREIGHT
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL
 ARE IN NEED OF PROVIDING MORE INFORMATION AND/OR
 ADDRESSING.
  
 ** PLEASE SEE SOME NEW COMMENTS BASED ON SUBMITTALS AND
 PLANS SUBMITTED.
  
 1) NOTE: ** THIS IS NOT A COMMENT FOR KAMM CONSULTING,
 HOWEVER IS BEING NOTED BY THIS REVIEWER.
 PLEASE SEE THE VP SHEETS AND THE PN SHEETS CONTAIN
 RAISED SEALS OVER PHOTO-COPIED SIGNATURES FOR THE
 ENGINEERS ON EACH OF THESE WHICH IS NOT PERMITTED UNDER
 FLORIDA STATUTES 471.025 AND FLORIDA ADMINISTRATIVE
 CODE 61G15-23.002
 PLEASE SEE BUILDING REVIEW COMMENTS FOR THIS ALSO.
 **THIS WAS COMMENT #2 FROM THE PREVIOUS REVIEW.
 PLEASE KNOW ONE SET OF PLANS MAY BE RETAINED BY THIS
 OFFICE.
  
 2) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3
 WHICH SPEAKS OF MAXIMUM TIMES PERMITTED ON THE TYPE OF
 DEVICES INSTALLED.
 PLEASE SEE NOTES ON E0.1 AND 2.1 IN SEVERAL PLACES
 INDICATE OCCUPANCY TYPE DEVICES WITH 3HRS AND 4HRS FOR
 MAXIMUM TIMES. PLEASE SEE THE SECTIONS AS NOTED ABOVE
 AS THE MAXIMUM PERMITTED TIMES ON THESE TYPES OF
 DEVICES IS 30MINS FROM THE LAST SENSING OF THE
 OCCUPANT.
 PLEASE ADJUST NOTES AND ALSO PLEASE BE SURE TO ADJUST
 ALL DEVICES TO CONTAIN NOTES FOR THIS.
 **PREVIOUS REVIEW NOTE #3
  
 3) NOTE: PLEASE SEE THE PERFORMANCE/ENERGY CALCULATIONS
 SUBMITTED WHICH DO NOT PROVIDE THE INFORMATION NEEDED
 FOR REVIEW.
 PLEASE SEE RESPONSE LETTER SPEAKS OF EXTERIOR LIGHTING
 CONTACTOR AND PHOTO-METRICS PLANS BY OTHERS?
 PLEASE SEE ENERGY CALCULATIONS SUBMITTED INDICATE ALL
 CONTROLS AS MANUAL ON/OFF WHEN PLANS INDICATE
 OTHERWISE?
 PLEASE PROVIDE INFORMATION FOR THE PERFORMANCE OF
 LIGHTING DENSITIES.
 **PREVIOUS REVIEW NOTE #4
  
 4) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR
 FEEDER(S) AND BRANCH CIRCUIT(S) PER 13-413.1.ABC.1.1.
 RESPONSE LETTER MENTIONS TO SEE 4.1 AND 5.1, HOWEVER
 4.1 IS AIC CALCULATIONS, AND 5.1 WAS THE RISER DIAGRAM
 SHEETS WHICH THIS REVIEWER COULD NOT LOCATED ANY
 VOLTAGE DROP CALCULATIONS/ OR WORST CASE INFORMATION.
 **PREVIOUS REVIEW #6
  
 5) NOTE: PLEASE SEE INFORMATION ON ACCESS CONTROL
 SYSTEM DOES NOT YET PROVIDE ENOUGH INFORMATION. PLEASE
 SEE NFPA-101 2003
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOORS SHALL BE ARRANGED TO BE OPENED READILY
 FROM THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
  
 7.2.1.5.2 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
 7.2.1.6 SPECIAL LOCKING ARRANGEMENTS.
 PLEASE SEE FIRE REVIEW COMMENTS AS WELL AS THE RESPONSE
 AND NOTE ON PLANS MENTIONS IN THE EVENT OF POWER
 FAILURE UNDER EMERGENCY OR NORMAL POWER THE FIRE ALARM
 AND SECURITY WILL NOT BE AFFECTED.
 PLEASE SEE THIS IS BEING CONSIDERED AN EGRESS CONCERN
 AND NOT THAT OF THE NOTE AS STATED.
 ** PREVIOUS NOTE #9
  
 6) NOTE: PLEASE SUBMIT ALL MANUFACTURES SPEC/CUT SHEETS
 FOR THE GENERATOR, ATS, WP ENCLOSURE AND FUEL TANKS.
 PLEASE CORRELATE THESE WITH THE SUBMITTED PLANS.
 SOME OF THESE WERE SUBMITTED, HOWEVER NOT FOR BOTH
 TANKS AND PLEASE SEE SOME OF THESE DO NOT MATCH WITH
 THE SUBMITTED PLANS.
 PLEASE SEE THE RESPONSE LETTER DOES NOT CONTAIN A
 RESPONSE FOR NOTE #11 FROM PREVIOUS REVIEW.
 90.7, 110.3 NEC
 FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION.
 ** PREVIOUS NOTE #11
  
 7) NOTE: PLEASE SEE 225.31-225.39, 702, 110.27 FOR
 DISCONNECTING MEANS REQUIRED FOR FEEDERS FROM THE
 GENERATOR. THE RESPONSE LETTER MENTIONS TO BE BY
 OTHERS; HOWEVER THIS INFORMATION IS REQUIRED AT THIS
 TIME. PLEASE KNOW THIS IS A DISCONNECTING MEANS AND IS
 NOT REQUIRED TO CONTAIN OVER CURRENT PROTECTION. THERE
 ARE SEVERAL WAYS OF DOING THIS, HOWEVER THE USE OF THE
 BREAKER INSIDE THE GEN UNIT WHICH MAY NOT MEET 110.27
 OR 702.
 PLEASE PROVIDE MORE INFORMATION ON DISCONNECT, THIS MAY
 BE LOCATED OUTSIDE MAIN ELECTRICAL ROOM ON BUILDING OR
 IN MAIN ELECTRICAL ROOM. SIGNAGE WILL BE REQUIRED.
 702.8, 230.2E
 ** PREVIOUS REVIEW NOTE #19
  
 8) NOTE: PLEASE SEE NOTE #20 FROM THE PREVIOUS REVIEW
 WITH RESPECT TO SLAB DETAIL, HEIGHT MOUNTING ETC FOR
 THE GENERATOR PER NFPA-110 CHAPTER 7.
 PLEASE SEE THE RESPONSE LETTER DOES NOT CONTAIN A
 RESPONSE FOR NOTE #20.
  
 9) NOTE: PLEASE SHOW MORE INFORMATION FOR NEC 514.
 PLEASE SEE 514.11(A) AND (C). PLEASE SEE COMMENTARY
 WHICH SPEAKS OF THE LOCATION AND SIGNAGE REQUIREMENTS.
 PLANS DO CONTAIN SOME NOTES FOR THESE HOWEVER PLEASE
 PROVIDE MORE DETAILS. PLEASE SEE THAT THE PUSHBUTTON EM
 CUT-OFF DEVICE SHOULD BE LOCATED AWAY FROM ANY HAZARD
 BUT NOT MORE THAN 100FT.PLEASE SEE THE DISTANCE AND
 THE LOCATION AS THIS IS BEING SHOWN BEHIND THE ADJACENT
 BUILDING WHICH IS PER SCALE PERHAPS LESS THAN 20FT FROM
 THE TANK GIVES CONCERN. PLEASE SEE FIRE MARSHAL'S
 COMMENTS ALSO.
 ** PREVIOUS REVIEW NOTE #22
  
 10) NOTE: PLEASE SEE PROVIDE MORE INFORMATION ON THE
 CLASS AND DIVISION LOCATIONS SURROUNDING THE FUEL
 DISPENSING. PLEASE SEE THE RESPONSE MENTIONED TO SEE
 THE TWO SHEETS, HOWEVER THOSE SHEET 1.1 AND 1.4 ONLY
 INDICATE THE DOTTED LINES FOR THE AREA.
 PLEASE SEE NEC 500, 514
 FBC ADMIN SECTION 106.1.2
 ** PREVIOUS REVIEW NOTE #23.
  
 11) NOTE: PLEASE CLARIFY THE LIGHTING FOR LIGHTS TO THE
 PUBLIC RIGHT OF WAY. PLEASE SEE THE STAIRS LOCATED
 OUTSIDE OF THE EGRESS DOORS WHICH WILL REQUIRE
 EMERGENCY LIGHTING OF SOME SORT.
 PLEASE ALSO SEE RESPONSE MENTIONS FOR SITE
 PHOTO-METRICS TO BE PROVIDED BY OTHERS, HOWEVER PLEASE
 SEE THE SITE LIGHTING IS BEING PERMITTED UNDER THIS
 BASE BUILDING.
 LS 101 7.8, 7.9
 ** PREVIOUS REVIEW NOTE #26.
  
 12) NOTE: PLEASE SEE THE MISSING STRUCTURAL BUILDING
 STEEL AND FIRE SPRINKLER LINE ATTACHMENT AS PART OF THE
 GROUNDING ELECTRODE SYSTEM.
 250.50, 250.104.
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-01-07 19:53:192007-01-07 19:53:19
 IN ELEC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-24 Cont ID  
Sent By dpalmer Date 2006-10-24 Time 10:31 Rev Time 0.00
Received By dpalmer Date 2006-10-22 Time 19:47 Sent To  
Notes
2006-10-24 10:36:28*** PLEASE SEE NOW THAT AN ADDRESS HAS BEEN CREATED,
 PLEASE PLACE ON TITLE BLOCKS FOR PLANS.
2006-10-24 10:31:25********* UNSAT **********
  
  
 1) NOTE: PLEASE LIST ALL OF THE FOLLOWING CODES
 RELEVANT TO PLANS AND DESIGNS ON THEOR RESPECTIVE
 SHEETS.
 PLEASE SEE THE FOLLOWING ARE REQUIRED AT A MINIMUM:
 2002NFPA-70, 2002 NFPA-72, 2003 NFPA-101, 2003 NFPA-20,
 2002 NFPA-110, 2000 NPPA-30A,2004 FBC .
 PLEASE BE AWARE OF ANY OTHER APPLICABLE CODES FROM
 OTHER REVIEWERS WHICH MAY BE REQUIRED.
  
 2) NOTE: PLEASE SEE "VP" BUILDING SHEETS AND SETS WHICH
 CONTAINEDRAISED SEALS OVER "PHOTO-COPIED" SIGNATURES.
 PLEASE SEE THIS COMMENT IS MADE WETHER OR NOT COMMENT
 IS MADE BY ANY OTHER REVIEWER.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002,
 FLORIDA STATUTES 471.025, PLEASE ALSO SEE MISSING
 REQUIRED TITLE BLOCK INFORMATION.
  
 3) NOTE: PLEASE SEE FBC 2004 CHAPTER 13.
 13-415.1.ABC.1.1, .1.2 AND .1.3. PLEASE SEE NO MORE
 THAN 4HRS IS PERMITTED ON OVER-RIDE DEVICES. (SOME
 SHOWN AS 12HRS). PLEASE SEE OTHER AREAS WHERE A TIMED
 OR OCCUPANT TYPE DEVICE IS NOT INDICATED. PLEASE
 CLARIFY THE USE OF THE MOMNETARY CONTACTS, FOR AREAS OF
 INGRESS/EGRESS.THE OCCUPANT MUST BE ABLE TO OVER RIDE
 ANY TIME OF DAY SCHEDULEING DEVICE AND SEE THE LIGHTING
 BEING CONTROLLED. (TIMES OR SENSOR TYPE). PLEASE SEE
 SYSMBOL LEGEND NEEDS TO INDICATE THE MAX AMOUNT OF
 TIMES ON DEVICE WHICH ARE SHOWN ON THIS LEGEND, HOWEVER
 NOT ON PLANS.
 (30MINS MAX OS, 4HRS MAX TIMER TYPE)
  
 4) NOTE: PLEASE PROVIDE ALL LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2, 13-415.2.ABC.1, TBALES
 415.2.C.1, 415.2.B1, AS SPACE BY SPACE WILL BE REQUIRED
 FOR SOME AREAS.
 PLEASE SEE METHOD "A" AS SUBMITTED DOES NOT SHOW
 THESE.
  
 5) NOTE: PLEASE SEE NO PLANS, DOCUMENTS ETC MAY CONTAIN
 "WHITE-OUT" OF ANY KIND ON SAID DOCUMENTS WITH
 HANDWRITTEN ITEMS OVER SUCH SHEETS. PLEASE SEE ENERGY
 CALCULATIONS.
 FS471
  
 6) NOTE: PLEASE PROVIDE VOLTAGE DROP CALCULATIONS FOR
 WORST CASE FOR EACH FOR FEEDERS AND BRANCH CIRCUITS.
 PLEASE SEE FBC 13-413.1.ABC.1.1 &.1.2.
  
 7) NOTE: PLEASE SEE SYMBOLSHOWN IN STORAGE/SPRINKLER
 ROOM ON 3.1, AND 2.1 APPEARS TO BE THAT OF A
 TRANSFORMER, YET THIS IS UNCLEAR AT THIS TIME.??
 FBC ADMIN SECT 106.1.2
  
 8) NOTE: PLEASE SEE IT WILL NOT BE PERMITTED THAT THE
 ONLY ACCESS TO THE MAIN ELECTRICAL ROOM IS THROUGH A
 STORAGE ROOM AND AREA. THESE TYPES OF ROOMS DO NOT
 TYPICALLY PROVIDE THE READY ACCESS TO THE ELECTRICAL
 EQUIPMENT IN THE QUICK TIME WHICH MAY BE NEED IN THE
 CASE OF AN EMERGENCY FOR FIRE DEPARTMENT OR ANY OTHER
 PERSONNEL TRYING TO SHUT OFF THE POWER. PLEASE SEE THAT
 RELOCATION OR ACCESS SEPARATELY FOR ROOM WILL BE
 REQUIRED AT THIS TIME.
 230.70,110.26, 408.7,90.4
  
 9) NOTE: PLEASE SEE POSSIBLE FIRE REVIEW COMMENTS WIHT
 RESPECT TO ACCESS CONTROL SYSTEM WHICH WILL REQUIRE
 ADDITIONAL INFORMATION. PLEASE INDICATE THAT IN THE
 EVENT OF AN EMERGENCY OR FAILURE OF NORMAL POWER EGRESS
 FROM THE BUILDING WILL NOT BE AFFECTED. PLEASE SEE LS
 101. SEE FIRE REVIEW COMMENTS.
  
 10) NOTE: PLEASE SEE FBC 11-4.28, 11-4.28.3. PLEASE
 INDICATE THE MIN LEVELS FOR DB RATINGS OF HORNS/ OR
 COMBO DEVICES.PLEASE SEE SCHEDULE INDICATES A
 POSSIBLE OF 15CD MIN, HOWEVER AS INDICATE ON PLANS AND
 ADA REQUIREMENTS, A MIN OF 75 CD IS REQUIRED. PLEASE
 PROVIDE AND COMPLETE THE LAYOUT OF THE FA DEVICES ON
 PLANS. THE 2ND AND THIRD SECTIONS DO NOT APPEAR ON FA
 SHEETS.
 11-4.28.3(4).
  
 11) NOTE: PLEASE SUBMIT COMPLETE MANUFACTURE SPECS/CUT
 SHEETS FOR ALL OF THE FOLLOWING. GENERATOR, FUEL
 TANK(REVIEW BY OTHERS), ATS, FIRE PUMP AND FIRE PUMP
 CONTROLLER. PLEASE SEE AS NONE OF THESE ARE SUBMITTED
 AT THIS TIME NOT REVIEW FOR SOME CODE REQUIRED ITMES
 CAN EB DONE.
 110.3, 90.7.
  
 12) NOTE: PLEASE INDICATE ALL OCP DEVICE SIZES AT THE
 GEN. PLEASE SEE SHEET7.3 INDICATES A BREAKER FOR FIRE
 PUMP AT GEN AS G-1 , YET THE RISER DOES NOT INDICATE
 THIS BREAKER AT ALL ON GEN.
 PLEASE SEE 445.13 AS THE SIZING OF THE FEEDERS CAN NOT
 BE VERIFIED AT THIS TIME.
  
 13) NOTE: PLEASE SEE THE GEN SEEMS IT WILL FEED A FIRE
 PUMP, THE STAND-BY FOR THIS BUILDING AND THE POSSIBLE
 STAND-BY FOR AN ADDITIONAL LOCATION, HOWEVER A COMPLETE
 LOAD SUMMARY AND LOAD SHEDDDING DETAILS HAVE NOT BEEN
 PROVIDED AT THIS TIME. PLEASE SEE THE LOAD ON THE MD IS
 THE ONLY LOAD SHOWN AT THIS TIME. PLEASE PROVIDE A LOAD
 SUMMARY FOR THE GEN AS THIS IS A LEGALLY REQUIRED
 STAND-BY UNIT.
 701.6,6.3 OF NFPA-110, NFPA-20 9.6.1.1 ETC.,THESE
 ITEMS CAN NOT BE REVIEWED AT THIS TIME.
  
 14) NOTE: PLEASE PROVIDE ALL MINIMUM FUEL CONSUMPTION
 FOR THEGENERATOR AS THIS FEED THE FIRE PUMP AND
 SYSTEM AS SHOWN NEEDS TO MEET THE MINIMUM OF HRS FOR
 100% LOAD INCLUDING ALL OTHER LOADS 9.6.2.2.
 CAN NOT REVIEW AT THIS TIME.
  
 15) NOTE: PLEASE SUBMIT ALL THE INFORMATION FOR FIRE
 PUMP SERVICE, LOCATION, LOCKED ROTOR OCP SIZE ETC.
 PLEASE SEE PLANS AND RISER DO NOT SEEM TO INDICATE ANY
 INFORMATION FOR THE FIRE PUMP. PLEASE SEE FP SHEETS
 ALSO DO NOT INDICATE ANY FP?PLEASE SEE 2003 NFPA-20
 CHAPTER 9 FOR DISCONNECTING MEANS, ISOLATION SWITCH
 REQUIREDETC ETC.
  
 16) NOTE: PLEASE PROVIDE ALL AIC RATINGS FOR ALL
 SERVICE EQUIPMENT. PLEASE PROVIDE A DETAIL FOR
 SELECTIVE COORDINATION. 110.9/240.12.
 PLEASE SEE NEC 701.6, 700.5 AND NFPA-110, 6.5.2 ETC FOR
 ATS AND ALL OTHER EQUIPMENT ASSOCIATED WITH ELECTRICAL
 SYSTEM.
  
 17) NOTE: PLEASE VERFIY WITH MANUFACTURE THE GENERATOR
 GROUNDING SCENARIO, AS IT IS KNOWN TO THIS OFFICE SOME
 OF THESE DEPENDING ON THE MANUFACTURE ARE SHIPPED AND
 WIRED FOR SEPARATELY DERIVED SYSTEM, PLEASE MAKE ANY
 ADJUSTMENTS AS NEED.
 90.7., 250.20, 250.50, ETC
  
 18) NOTE: PLEASE CORRELATE CIRCUITING FOR PANEL FD,
 PANEL "LB" DOES NOT SHOW FEEDING OF THIS PANEL .
 PLEASE SEE CIRCUITS FOR OTHER ITEMS SHOWN ON SCHEDULE.
 240.4,310.16,408.4,
 FBC 106.3.5.1.2. ADMIN SECT.
  
 19) NOTE: PLEASE SEE MISSIGN A DISONNECTING MEANS FOR
 FEEDERS FROM GENERATOR INTO BLDG LOCATED IN CLOSE
 PROXIMITY OF OTHER MAINS OR MEETINGEXCEPTIONS UNDER
 CODE, HOWEVER SYSTEM IS NOT KNOWN AT THIS TIME
 CLASSIFICATION OF BACK UP POWER IS NOT CLEAR. PLEASE
 ALSO KNOW AS INFORMATION FOR THE GEN AND W/P ENCLOSURE
 AND ACCESS IS ALSO NOT KNOW AT THIS TIME.
 225.31-225.39
 700, 701, 702 ?
  
 20) NOTE: PLEASE SEE NOT INFORMATION FOR LOCATION,
 ELEVATION, MOUNTING , SLAB DETAIL ETC COULD BE LOCATED
 ON PLANS. PLEASE SEE NFPA-110 2002 CHAPTER 7, AS MANY
 OF THESE SCETIONS APPLY, HOWEVER AS NOTHING COULD BE
 LOCATED FOR THIS, A REVIEW FOR COMPLIANCE COULD NOT BE
 DONE AT THIS TIME.
  
 21) NOTE: PLEASE SEE MD AS THIS SHOWS A NEUTRAL
 CONDUCTOR BEING SHOWN FEEDING THE TRANSFORMER WHICH IS
 A SD SYSTEM. PLEASE SEE 250.30, 250.20 ETC
  
 22) NOTE: PLEASE SEE ANY COMMENTS WITH RESPECT THE EM
 SHUT OFF OF POWER FOR THEFD PANEL. PLEASE SEE 514
  
 23) NOTE: PLEASE PROVIDE A LAYOUT AND SHOW ALL
 HAZARDOUS LOCATIONSON PLANS.
 500. CLASS AND DIVISIONS.
  
 24) NOTE: PLEASE SEE MECH REVIEW NOTES FOR SEPARATE
 FUEL PERMIT REQUIRED.
  
 25: ) NOTE: PLEASE SEE THE GEN SPECIFICATIONS ON 7.3 DO
 NOT LIST THE OTHER OCP/ BREAKERS ON GEN AS SHOWN ON
 RISER.
  
 26) ) NOTE: PLEASE PROVIDE EM BATTERY BACK UP
 FIXTURE(S) OF SOME TYPE LEADING TO THE PUBLIC RIGHT OF
 WAY. PLEASE PROVIDE PHOTO-METRICS FOR EGRESS PATHS
 UNDER NORMAL AND UNDER EMERGENCY POWER. PLEASSE SEE
 NFPA-101 7.8.1.3, 7.9.2.2, PLEASE SEE STAIR AREAS
 LEADING TO THE OUTSIDE.
  
 27) NOTE: PLEASE SEE SOME SHEETS IN SETS ARE PLACED IN
 SETS BACKWARDS. PLEASE SEE THE FOLLOWING NOTE.
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE KNOW AS THERE IS INFORMATION NOT YET
 SUBMITTED FOR REVIEW , PLEASE KNOW THERE MAY BE FURTHER
 COMMENTS UPON NEXT REVIEW.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
2006-10-22 19:47:55ONE SET IN ELEC FOR REVIEW

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2007-10-16 Cont ID  
Sent By rchokshi Date 2007-10-16 Time 11:46 Rev Time 0.00
Received By rchokshi Date 2007-10-16 Time 11:46 Sent To P
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2006-11-13 Cont ID  
Sent By rchokshi Date 2006-11-13 Time 13:23 Rev Time 0.00
Received By rchokshi Date 2006-11-13 Time 13:17 Sent To  
Notes
2006-11-13 13:22:54ACCORDING TO A LETTER (E-MAIL) FROM STEVEN M. PAWLYK OF
 BOWYER-SINGLETON DATED NOV 13, 06,THIS PRMIT IS
 COVERED UNDER PERMIT#06071716.PERMIT # 06071716 IS
 REVIEWED AND PASSED SOMETIME AGO.THEREFORE, THIS IS
 PASSED.
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-05-01 Cont ID  
Sent By mawillia Date 2007-05-01 Time 15:46 Rev Time 0.00
Received By mawillia Date 2007-05-01 Time 14:25 Sent To  
Notes
2007-05-01 15:46:36*****APPROVED*****
  
  
 PLAN SHEETS A1.2, A4.0, E2.1, E2.2, E2.3, FA0.1, FA2.1,
 FA2.2, FA2.3, FP-1, FP-2, AND FP-3 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-04-19 Cont ID  
Sent By mawillia Date 2007-04-19 Time 14:35 Rev Time 0.00
Received By mawillia Date 2007-05-01 Time 14:25 Sent To  
Notes
2007-04-19 13:57:47*****PROVISO*****
  
  
 THE COMMENTS FROM PREVIOUS FIRE PLAN REVIEWS HAVE BEEN
 ADDRESSED, HOWEVER, THE PLANS WILL BE FIRE STAMPED WHEN
 OTHER PLAN REVIEW COMMENTS HAVE BEEN SATISFIED.ONLY
 ONE SET OF FIRE PROTECTION SHEETS WERE REVIEWED DUE TO
 FP SHEETS NOT BEING ATTACHED TO THE REST OF THE
 SUBMITTED PLAN SHEETS.PLEASE
 VERIFY/COORDINATE/ARRANGE THAT ALL PLAN SHEETS BE
 SUBMITTED AS A SET.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-01-29 Cont ID  
Sent By mawillia Date 2007-02-01 Time 14:15 Rev Time 0.00
Received By mawillia Date 2007-01-29 Time 14:15 Sent To  
Notes
2007-01-29 14:19:10*****DENIED*****
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE SHEET INDICATING HOW/WHERE EACH ITEM
 FROM 10/31/2006 WAS ADDRESSED (ON/IN THE PLANS).
  
  
  
 05.LANDSCAPING SHALL NOT OBSTRUCT OR INTERFERE WITH
 FIRE PROTECTION EQUIPMENT.PROPER CLEARANCES SHALL BE
 MAINTAINED AT ALL TIMES.PLEASE NOTE IN LANDSCAPING
 PLANS
  
 07.FIRE DEPARTMENT CONNECTIONS (FDC'S) SHALL BE
 POSITIONED SO THAT THEY CANNOT BE BLOCKED BY STORAGE,
 VESSELS, EQUIPMENT, ETC.PLEASE NOTE ON FIRE SPRINKLER
 DRAWINGS
  
 08.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE
 DEPARTMENT CONNECTIONS.NOTE ON FIRE SPRINKLER
 DRAWINGS
  
 09.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK
 IS REQUIRED FOR DOUBLECHECK DETECTOR ASSEMBLY.NOTE
 ON FIRE SPRINKLER DRAWINGS
  
 19.LIFE SAFETY PLAN SHALL INCLUDE ALL COMMON PATHS OF
 TRAVEL TO EXITS.INCLUDE TRAVEL DISTANCE TO EXITS AS
 PER 2003 NFPA 101: 7.6.1
  
 22.FIRE SPRINKLER SYSTEM IS TO BE MONITORED.NOTE ON
 FIRE SPRINKLER DRAWINGS
  
 23.FIRE ALARM SHALL BE UL CERTIFIED FOR CENTRAL
 STATION SERVICE.NOTE IN FIRE ALARM DRAWING
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-31 Cont ID  
Sent By mawillia Date 2006-10-31 Time 10:55 Rev Time 0.00
Received By mawillia Date 2006-10-31 Time 10:55 Sent To  
Notes
2006-10-31 12:10:40*****DENIED*****
  
  
  
 01.NFPA 101 - 2003 EDITION AND FLORIDA FIRE
 PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED.
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION SHALL COMPLY WITH NFPA241.
  
 03.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF.
  
 04.ALL PAVEMENT ROAD SYSTEMS SHALL BE CAPABLE OF
 SUPPORTING 32 TONS FOR FIRE EQUIPMENT.
  
 05.LANDSCAPING SHALL NOT OBSTRUCT OR INTERFERE WITH
 FIRE PROTECTION EQUIPMENT.PROPER CLEARANCES SHALL BE
 MAINTAINED AT ALL TIMES.
  
 06.SHOW/DISPLAY THE NUMERICAL ADDRESS OF THE BUILDING
 ON THE PROPER ELEVATION.AS PER WEST PALM BEACH CODE,
 THOSE NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND 1"
 IN WIDTH.IF A MONUMENT SIGN OR MARKEE IS REQUIRED, A
 NUMERICAL ADDRESS WILL ALSO BE POSTED.IF THERE ARE
 GOING TO BE SEVERAL ADDRESSED BUILDINGS WITHIN THE FED
 EX COMPLEX, A RANGE OF ADDRESSES FROM THE LOWEST TO THE
 HIGHEST WILL BE REQUIRED ON THE MONUMENT SIGN OR
 MARKEE.
  
 07.FIRE DEPARTMENT CONNECTIONS (FDC'S) SHALL BE
 POSITIONED SO THAT THEY CANNOT BE BLOCKED BY STORAGE,
 VESSELS, EQUIPMENT, ETC.
  
 08.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE
 DEPARTMENT CONNECTIONS.
  
 09.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK
 IS REQUIRED FOR DOUBLECHECK DETECTOR ASSEMBLY.
  
 10.KNOX BOX FOR THE BUILDING WILL BE REQUIRED. PLEASE
 CONTACT THE FIRE PREVENTION BUREAU AT (561) 804-4724
 FOR APPLICATIONS.
  
 11.WILL THERE BE SECURITY GATES TO THE PREMISES AND
 IF SO, HOW WILL THE MEANS OF EGRESS BE IMPACTED?
  
 12.PROVIDE MORECANOPY DETAILS IN REGARDS TO SMOKE
 FLAME RETARDANT CAPABILITIES.
  
 13.PROVIDE MORE DETAILS FOR GENERATOR INCLUDING
 MANUFACTURER SPEC SHEETS.
  
 14.PLEASE INDICATE WHERE AND IN WHAT QUANTITY WILL
 FUEL OR ANY OTHER COMBUSTIBLE/FLAMMABLE LIQUIDS BE
 STORED AT THE NEW FACILITY.
  
 15.PLEASE PROVIDE PRESCIPTIVE STRENGHT FOR ALL
 HANDRAILS / GUARDRAILS.
  
 16.ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA
 80.
  
 17.PLEASE ILLUSTRATE ALL EXIT DISCHARGE LOCATIONS
 FROM THE BUILDING.EXIT DISCHARGE LOCATIONS SHALL
 COMPLY WITH APPLICABLE FIRE CODE REQUIREMENTS.
  
 18.INTERIOR FINISH FOR WALLS AND CEILING IN EXITS AND
 EXIT ACCESS CORRIDORS SHALL BE CLASS "A" OR CLASS "B".
  
 19.LIFE SAFETY PLAN SHALL INCLUDE ALL COMMON PATHS OF
 TRAVEL TO EXITS.
  
 20.INDICATE LOCATION OF 2A-10BC RATED FIRE
 EXTINGUISHERS AT DISTANCES TO SATISFY THE 75' TRAVEL
 DISTANCE REQUIREMENT.
  
 21.SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED
 FOR FIRE SPRINKLER AND FIRE ALARM SYSTEMS.
  
 22.FIRE SPRINKLER SYSTEM IS TO BE MONITORED.
  
 23.WILL THE STRUCTURE HAVE A FIRE ALARM SYSTEM?IF
 SO, FIRE ALARM SHALL BE UL CERTIFIED FOR CENTRAL
 STATION SERVICE.
  
 24.FIRE ALARM SYSTEM IS TO BE CLASS A OR FULLY
 ADDRESSABLE.
  
 25.DELAYED-EGRESS LOCKS AND/ORACCESS-CONTROLLED
 EGRESS DOORS SHALL COMPLY WITH NFPA 101, CH. 7.2.1.6,
 SPECIAL LOCKING ARRANGEMENTS.
  
 26.PLEASE PROVIDE SPEC SHEETS FOR FIRE PUMP AND
 ASSOCIATED EQUIPMENT.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2007-12-10 Cont ID  
Sent By adarroug Date 2007-12-10 Time 14:22 Rev Time 0.00
Received By adarroug Date 2007-12-10 Time 14:21 Sent To B
Notes
2007-12-10 14:22:51TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2007-12-03 Cont ID  
Sent By adarroug Date 2007-12-03 Time 15:46 Rev Time 0.00
Received By adarroug Date 2007-12-03 Time 15:46 Sent To P
Notes
2007-12-03 15:46:47TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-10-29 Cont ID  
Sent By adarroug Date 2007-10-29 Time 16:49 Rev Time 0.00
Received By adarroug Date 2007-10-29 Time 16:49 Sent To E
Notes
2007-10-29 16:49:34TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-10-24 Cont ID  
Sent By adarroug Date 2007-10-24 Time 14:16 Rev Time 0.00
Received By adarroug Date 2007-10-24 Time 14:16 Sent To P
Notes
2007-10-24 14:16:19TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-09-28 Cont ID  
Sent By adarroug Date 2007-09-28 Time 11:12 Rev Time 0.00
Received By adarroug Date 2007-09-28 Time 11:12 Sent To B
Notes
2007-09-28 11:12:52TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-09-20 Cont ID  
Sent By adarroug Date 2007-09-20 Time 16:59 Rev Time 0.00
Received By adarroug Date 2007-09-20 Time 16:59 Sent To B
Notes
2007-10-12 16:43:1710/12/07--TO "Z" BOX/REV
2007-09-20 17:00:17TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-09-20 Cont ID  
Sent By adarroug Date 2007-09-20 Time 15:46 Rev Time 0.00
Received By adarroug Date 2007-09-20 Time 15:46 Sent To  
Notes
2007-10-10 12:06:32TO "COMM" BD#12
2007-09-20 15:46:34WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-09-18 Cont ID  
Sent By adarroug Date 2007-09-18 Time 11:48 Rev Time 0.00
Received By adarroug Date 2007-09-18 Time 11:48 Sent To  
Notes
2007-09-18 11:48:32WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-09-13 Cont ID  
Sent By adarroug Date 2007-09-13 Time 15:58 Rev Time 0.00
Received By adarroug Date 2007-09-13 Time 15:58 Sent To  
Notes
2007-09-13 15:59:08TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-21 Cont ID  
Sent By adarroug Date 2007-08-21 Time 11:32 Rev Time 0.00
Received By adarroug Date 2007-08-21 Time 11:32 Sent To  
Notes
2007-09-13 11:33:13TO "COMM" BD#59

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-09 Cont ID  
Sent By adarroug Date 2007-03-09 Time 09:57 Rev Time 0.00
Received By kstevens Date 2007-03-09 Time 15:20 Sent To  
Notes
2007-03-09 15:22:32TO "COMM" BD#44/PLANS ON RACK-4 ROLLS/PAPERWORK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-09 Cont ID  
Sent By adarroug Date 2006-12-05 Time 13:23 Rev Time 0.00
Received By adarroug Date 2006-12-05 Time 15:10 Sent To  
Notes
2007-01-05 10:54:33TO "COMM" BD#15/PLANS ON RACK
2006-12-05 15:10:44WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-15 Cont ID  
Sent By adarroug Date 2006-11-13 Time 09:02 Rev Time 0.00
Received By adarroug Date 2006-09-20 Time 13:49 Sent To  
Notes
2006-10-17 13:25:22TO "COMM" BD#38
2006-10-13 13:50:57WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-03-30 Cont ID  
Sent By rregueir Date 2007-03-30 Time 10:59 Rev Time 0.00
Received By rregueir Date 2007-03-30 Time 10:43 Sent To  
Notes
2007-03-30 10:59:48NEW SHEETS WERE ADDED, REVIEWED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-02-06 Cont ID  
Sent By rregueir Date 2007-02-06 Time 09:32 Rev Time 0.00
Received By rregueir Date 2007-02-05 Time 15:24 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-24 Cont ID  
Sent By rregueir Date 2006-10-24 Time 19:40 Rev Time 0.00
Received By rregueir Date 2006-10-24 Time 16:44 Sent To  
Notes
2006-10-24 19:55:53----------------DENIED----------------
 1. M0.1 OUTSIDE AIR CALCULATIONS SCHEDULE: NOTE STATES
 "ALL RTU'S ARE EXISTING..." HOW ARE UNITS EXISTING ON
 NEW BUILDING? PLEASE CORRECT OR CLARIFY.
  
 2. M0.1 MECHANICAL NOTES: NOTE 7B STATES "ALL AIR
 CONDITIONING DUCTWORK SHALL BE OF 1 1/2"...
 FIBERGLASS..."THIS IS IN CONFLICT WITH NOTE 7C.
 PLEASE CLARIFY.
  
 3. M2.1 ROOMS 117 AND 119 SHOW TRANSFER JUMPERS FOR
 RETURN AIR. PROVIDE SIZES FOR FLEX DUCTS TO SHOW
 COMPLIANCE WITH FBC,M 601.4 EXCEPTION 1. DUCT SIZES ON
 FLEX SCHEDULE DO NOT MEET THE EXCEPTION REQUIREMENTS.
  
 4. M2.1 ROOM 120 THE DESIGN CFM OF THE DUCTED RETURN
 (500CFM) IS LESS THAN THAT OF THE SUPPLY (600CFM) PLUS
 THE TRANSFER RETURN AIR FROM ROOM 119 (80CFM) FOR A
 TOTAL OF 680CFM TO BE RETURNED. PLEASE SHOW BALANCED
 RETURN I THIS AREA PER FBC,M 601.4
  
 5. M0.1 NOTE #20: NO DETAIL FOR ROOF-TO-CURB OR
 CURB-TO-EQUIPMENT ATTACHMENTS WAS PROVIDED BY
 STRUCTURAL ENGINEER. SHOW COMPLIANCE WITH WIND LOAD
 REQUIREMENTS OF FBC 1509, 1522 AND CHAPTER 16.
  
 6. PLEASE SHOW LOCATIONS FOR CONDENSATE DISPOSAL IN
 COMPLIANCE WITH FBC,M 307.2 AND FBC 1503.6. SECONDARY
 DRAIN PROTECTION IS ALSO REQUIRED PER FBC,M 307.2.3. IS
 THIS WHAT IS MEANT ON EQUIPMENT SCHEDULE NOTE #13?
  
 7. GUARDS SHALL BE PROVIDED WHERE EQUIPMENT REQUIRING
 SERVICE IS LOCATED WITHIN 10 FEET OF ROOF EDGE PER
 FBC,M 304.10
  
 8. M7.1 GRAVITY RELIEF HOOD DETAIL: THIS HOOD APPEARS
 TO BE FOR INKATE PURPOSES BUT IT IS SHOWN ATTACHED TO
 AN EXHAUST DUCT. THE BACKDRAFT DAMPER AS SHOWN WILL NOT
 ALLOW AIR TO ENTER THE BUILDING THROUGH THE HOOD.
 PLEASE CLARIFY.
  
 RONALD J REGUEIRO
 561.805.6734
 [email protected]

Review Stop P PLUMBING
Rev No 6 Status N Date 2007-12-14 Cont ID  
Sent By kstevens Date 2007-12-14 Time 10:09 Rev Time 0.00
Received By kstevens Date 2007-12-14 Time 10:09 Sent To  
Notes
2007-12-14 10:10:25REVISIONS NOT APPROVED, SHEETS WITH THESE REVISIONS
 HAVE BEEN APPROVED PREVIOUSLY.

Review Stop P PLUMBING
Rev No 5 Status P Date 2007-12-14 Cont ID  
Sent By kstevens Date 2007-12-14 Time 10:08 Rev Time 0.00
Received By kstevens Date 2007-12-14 Time 10:08 Sent To  
Notes
2007-12-14 10:09:40REVISIONS OK--SHTS P0.1, P3.1 & P5.1

Review Stop P PLUMBING
Rev No 4 Status F Date 2007-10-17 Cont ID  
Sent By kstevens Date 2007-10-17 Time 10:16 Rev Time 0.00
Received By kstevens Date 2007-10-16 Time 10:42 Sent To  
Notes
2007-10-17 10:21:23REVISIONSDENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHEETS PO.1, P3.1 & P5.1. A PROFESSIONAL ENGINEER
 SHALL SIGN HIS NAME TO ALL PLANS. INITIALS ARE NOT
 ACCEPTABLE. PLEASE SIGN ALL SHEETS AS THEY ARE SEALED
 AND DATED FOR REVIEW. FAC 61G15-23.002(1)(2) & FS
 471.025.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-04-03 Cont ID  
Sent By kstevens Date 2007-04-03 Time 08:09 Rev Time 0.00
Received By kstevens Date 2007-03-23 Time 09:53 Sent To  
Notes
2007-04-03 08:09:38NEW SHEETS - PO.1, P2.2, P3.1, P3.2

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-01-24 Cont ID  
Sent By kstevens Date 2007-01-24 Time 16:01 Rev Time 0.00
Received By kstevens Date 2007-01-23 Time 18:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-10-27 Cont ID  
Sent By kstevens Date 2006-10-27 Time 12:55 Rev Time 0.00
Received By kstevens Date 2006-10-27 Time 12:55 Sent To  
Notes
2006-10-27 13:15:10DENIED
 REFERENCE: FBC-2004 PLUMB
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHTS A-1.0 & A-1.1 INDICATE THE CLEAR FLOOR SPACE
 FOR THE BREAK ROOM SINKS PER SECTION 11-4.24.5. -
 INDICATE THE CLEAR FLOOR SPACE FOR THE URINALS PER
 SECTION 11-4.18.3.
  
 2. SHT A-3.0 DETAIL #5 SHOW THE HEIGHT FOR THE OVERFLOW
 SCUPPER. SEE SECTION 1503.4.3.
  
  
 3. SHT A-7.1 DETAILS #2 & 6 SHOW COMPLIANCE WITH
 SECTION 11-4.19.5 FAUCETS.
  
 4. SHT A-7.1 DETAILS #4 & 5 SHOW COMPLIANCE WITH
 SECTIONS 11-4.24.2 HEIGHT, (DETAIL 5), 11-4.24.3 KNEE
 CLEARANCE, 11-4.24.5 CLEAR FLOOR SPACE, (FORWARD
 APPROACH REQUIRED). GARBAGE DISPOSALS ARE NOT APPROVED
 IN THE CLEAR FLOOR SPACE/KNEE CLEARANCE AREA. PLEASE
 DELETE REFERENCE TO GARBAGE DISPOSALS.
  
 5. SHT A-7.1 DETAILS #1 & 6 SHOW COMPLIANCE WITH
 SECTION 11-4.18.3 CLEAR FLOOR SPACE & SECTION 11-4.18.4
 FLUSH CONTROLS.
  
 6. SHT A-7.1 DETAILS #6 & 7 INDICATE COMPLIANCE WITH
 SECTIONS 11-4.16, 11-4.18, 11-4.19, & 11-4.22 AND ALL
 SUBSECTIONS. SUBMIT THE ELEVATIONS FOR ACCESSIBLE
 STALLS. INDICATE 1'6" OFF THE WALL TO THE CENTERLINE OF
 THE W/C FIXTURE, AND 1'3" MIN. TO THE CENTERLINE OF THE
 LAV OFF THE WALL. SEE FIGS. 28, & 32.
  
 7. SHT A-8.0 ROOM FINISH SECEDULE. ROOM MARKS F-10.
 INDICATE HOW PAINT ON G.B. AND/OR BLOCK MEETS THE
 REQUIREMENT FOR A "SMOOTH, HARD, NONABSORBENT SURFACE",
 REQUIRED IN SECTION 1210.2.
  
 8. SHT P5.1 DOMESTIC WATER ISOMETRIC. WATER HAMMER
 ARRESTOR SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE", NOT IN THE CEILING AS SHOWN. PDI-WH
 201 AND MANUF. INSTALLATION INSTRUCTIONS. - A FULL OPEN
 VALVE IS REQUIRED AT THE ENTRANCE INTO THE STRUCTURE
 PER SECTION 606.1(2). PLEASE INDICATE ON WATER RISER
 ISOMETRIC DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 5 Status P Date 2007-10-18 Cont ID  
Sent By choops Date 2007-10-18 Time 16:13 Rev Time 0.00
Received By choops Date 2007-10-18 Time 16:12 Sent To I
Notes
2007-10-18 16:13:49ADDITION OF LIFT ONLY.PER ERIC SCHNEIDER.

Review Stop Z ZONING
Rev No 4 Status P Date 2007-10-12 Cont ID  
Sent By eschneid Date 2007-10-12 Time 14:51 Rev Time 0.00
Received By eschneid Date 2007-10-12 Time 14:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2007-03-14 Cont ID  
Sent By eschneid Date 2007-03-14 Time 17:26 Rev Time 0.00
Received By eschneid Date 2007-03-14 Time 17:13 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2007-01-22 Cont ID  
Sent By eschneid Date 2007-01-22 Time 13:01 Rev Time 0.00
Received By eschneid Date 2007-01-22 Time 13:01 Sent To  
Notes
2007-01-22 13:14:58FAILED
  
 1) ALL APPLICABLE CONDITIONS OF ORDINANCE NO. 3987-06
 SHALL BE SATISFIED.
  
 A) A TRAFFIC STATEMENT, PREPARED BY A LICENSED TRAFFIC
 ENGINEER, SHALL BE SUBMITTED TO THE PLANNING & ZONING
 AND CONSTRUCTION SERVICES DEPTS. OUTLINING THE NUMBER
 OF DAILY TRIPS, AM TRIPS AND PM TRIPS GENERATED FOR
 EACH USE AND ITS SQUARE FOOTAGE FOR EACH BUILDING.
  
 2) PROVIDE A RECORDED COPY OF THE PLAT.
  
 3) THE BOWYER SINGLETON PLANS (SHEETS 3, 5, 8, 20 AND
 20 OF 29) AND THE LANDSCAPE PLANS SHALL BE UPDATED TO
 REFLECT THE ADA SIDEWALK/ROUTE FROM THE EASTERNMOST
 DISABLED PARKING SPACE SHOWN ON THE ARCHITECT'S SITE
 PLAN.
  
 4) PARKING DETAIL ON BOWYER SINGLETON SHEET 13 OF 29
 SHALL SHOW 2 FEET FROM THE CURB TO THE BACK OF THE
 WHEEL STOP, NOT 2 FEET TO THE MIDDLE OF THE WHEEL
 STOP.
  
 5) 119 PARKING SPACES ARE REQUIRED FOR FULL PROJECT.
 THE STORAGE AREA REQUIRED 1 PARKING SPACE WAS LEFT OUT
 ON THE PARKING TABLE.
  
 6) THE SITE AREA LISTED ON SHEET A-0.0 DIFFERS FROM THE
 SQUARE FOOTAGE LISTED ON THE PLAT FOR PARCEL D.\
  
 7) THE SQUARE FOOTAGE LISTED FOR THE PHASE I BUILDING
 DIFFERS ON ARCHITECTURAL PLANS SHEET A-0.0 (37,904) AND
 SHEET A-0.1 (37,808) AND THE BOWYER SINGLETON PLANS.
  
 8) WHY DO THE ARCHITECTURAL PLANS LIST "BUILDING AREA"
 AS HAVING MORE SQUARE FOOTAGE THEN THE ACTUAL BUILDING
 SQUARE FOOTAGE?
  
 9) PLEASE RESPOND IN WRITING TO THE COMMENTS ABOVE.
  
 ERIC SCHNEIDER (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-10-31 Cont ID  
Sent By eschneid Date 2006-10-31 Time 17:15 Rev Time 0.00
Received By eschneid Date 2006-10-31 Time 17:15 Sent To  
Notes
2006-10-31 17:48:18FAILED
  
 1) ALL APPLICABLE CONDITIONS OF ORDINANCE NO. 3987-06
 SHALL BE SATISFIED.
  
 A) A MINOR AMENDMENT IS REQUIRED TO:
  
 I) SHOW ALL IMPROVEMENTS OUTSIDE OF THE 12 FOOT WIDE
 UTILITY EASEMENT.
  
 II) CORRECT THE FEDERAL EXPRESS FREIGHT ADA PARKING (OR
 A LETTER FROM THE CONSTRUCTION SERVICES DEPT. STATING
 THAT THE PARKING AS SHOWN MEETS ADA REQ.)
  
 III) SHOW THE REQUIRED NOISE BARRIER.
  
 B) A TRAFFIC STATEMENT, PREPARED BY A LICENSED TRAFFIC
 ENGINEER, SHALL BE SUBMITTED TO THE PLANNING & ZONING
 AND CONSTRUCTION SERVICES DEPTS. OUTLINING THE NUMBER
 OF DAILY TRIPS, AM TRIPS AND PM TRIPS GENERATED FOR
 EACH USE AND ITS SQUARE FOOTAGE FOR EACH BUILDING.
  
 2) THE PLAT IS REQUIRED TO BE RECORDED.
  
 3) BOWYER SINGLETON SITE PLANS AND LANDSCAPE PLANS ARE
 NOT THE LATEST VERSIONS APPROVED BY ORD. NO. 3987-06.
  
 4) PLAN LINE IS SHOWN INCORRECTLY ON BOWYER SINGLETON
 SHEET 5 OF 29.
  
 5) 119 PARKING SPACES ARE REQUIRED FOR FULL PROJECT.
 THE STORAGE AREA REQUIRED 1 PARKING SPACE WAS LEFT OUT
 ON THE PARKING TABLE.
  
 ERIC SCHNEIDER (561) 822-1435.
  