Plan Review Details - Permit 06090692
Plan Review Stops For Permit 06090692 |
Review Stop |
AD |
ADDRESSING |
Rev No |
4 |
Status |
P |
Date |
2007-09-25 |
|
|
Cont ID |
|
Sent By |
lursu |
Date |
2007-09-25 |
Time |
16:18 |
Rev Time |
0.00 |
Received By |
lursu |
Date |
2007-09-25 |
Time |
16:18 |
Sent To |
|
|
Notes |
2007-09-25 16:19:08 | SITE ADDRESS AND PCN ARE CORRECT. | | | | LACRAMIOARA URSU | | MIS - GIS SUPPORT SPECIALIST | | CITY OF WEST PALM BEACH | | OFFICE:822-1239 | | FAX: 822-1249 | | E-MAIL:[email protected] |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
3 |
Status |
P |
Date |
2006-11-17 |
|
|
Cont ID |
|
Sent By |
lursu |
Date |
2006-11-17 |
Time |
13:04 |
Rev Time |
0.00 |
Received By |
lursu |
Date |
2006-11-17 |
Time |
13:04 |
Sent To |
|
|
Notes |
2006-11-17 13:04:17 | TEMPORARY PCN WAS CREATED FOR THIS STRUCTURE .PERMIT | | WAS ASSIGNED TO IT. | | | | LACRAMIOARA URSU | | MIS - GIS SUPPORT SPECIALIST | | E-MAIL:[email protected] |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
2 |
Status |
P |
Date |
2006-10-18 |
|
|
Cont ID |
|
Sent By |
lursu |
Date |
2006-10-18 |
Time |
15:17 |
Rev Time |
0.00 |
Received By |
lursu |
Date |
2006-10-18 |
Time |
15:17 |
Sent To |
|
|
Notes |
2006-10-18 15:18:05 | NEW ADDRESS ASSIGNED TO BLDG 4 ON PARCEL D IS 5850 | | PREMIER PARK DR |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
F |
Date |
2006-09-22 |
|
|
Cont ID |
|
Sent By |
lursu |
Date |
2006-09-22 |
Time |
11:23 |
Rev Time |
0.00 |
Received By |
lursu |
Date |
2006-09-21 |
Time |
14:52 |
Sent To |
|
|
Notes |
2006-09-22 00:00:00 | THIS BLDG IS ON ANINDIVIDUAL PARCEL , | | OWNERSHIP DOCUMENTATION IS NEEDED . |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
12 |
Status |
P |
Date |
2007-12-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-12-21 |
Time |
18:39 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-12-21 |
Time |
18:39 |
Sent To |
|
|
Notes |
2007-12-21 18:39:35 | ROOF HATCH PRODUCT APPROVAL OK |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
11 |
Status |
F |
Date |
2007-12-13 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-12-13 |
Time |
08:54 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-12-13 |
Time |
08:54 |
Sent To |
|
|
Notes |
2007-12-13 09:02:19 | ****CORRECTIONS**** | | ****LOCAL PRODUCT APPROVAL FOR NYSTROM ROOF HATCH**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | 1.SEE FAC9B72.010(6), DEFINITIONS,APPROVED QUALITY | | ASSURANCE ENTITY MEANS AN ENTITY APPROVED BY THE | | COMMISSION PURSUANT TO SUBSECTION 9B-72.100(5), F.A.C., | | TO PROVIDE OVERSIGHT AND DETERMINE THAT THE PRODUCT OR | | SYSTEM IS BEING MANUFACTURED OR ASSEMBLED, PER THE | | SUBMITTED DESCRIPTION, TEST RESULTS, OR CALCULATIONS TO | | ESTABLISH CONTINUAL PRODUCT PERFORMANCE. I WAS UNABLE | | TO LOCATE ACRC IN THE FLORIDA DATABASE.SEE | | WWW.FLORIDABUILDING.ORG, PRODUCT APPROVAL, ORGANIZATION | | SEARCH. | | | | 2.THE SHEET TITLED "WIND UPLIFT FOR ROOF HATCH | | PRODUCTS" IS NOT LEGIBLE.PLESE PROVIDE A LEGIBLE COPY | | OF THIS DOCUMENT AS WELL AS THE TITLE AND | | CONTENTS/INDEX PAGES OF THE DOCUMENT WHERE THIS SHEET | | CAME FROM. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
10 |
Status |
P |
Date |
2007-10-19 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-10-19 |
Time |
08:02 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-10-19 |
Time |
08:01 |
Sent To |
|
|
Notes |
2007-10-19 08:03:05 | REVISED A0.1, LULA LIFT DETAIL |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
9 |
Status |
P |
Date |
2007-10-01 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-10-01 |
Time |
11:04 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-10-01 |
Time |
11:04 |
Sent To |
|
|
Notes |
2007-10-01 11:05:16 | REVISION - OVERHEAD DOORS | | SUBMITTAL - DOCK EQUIPMENT | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
8 |
Status |
F |
Date |
2007-10-01 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-10-01 |
Time |
09:48 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-10-01 |
Time |
09:48 |
Sent To |
|
|
Notes |
2007-10-01 11:04:00 | ***SUBMITTAL/REVISION*** | | | | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | ROOFING SUBMITTAL: | | | | 1.)TAS105 IS TO BE PERFORMED BY AN APPROVED TESTING | | LAB.PLEASE PROVIDE EVIDENCE OF NUTTING ENGINEERS AS | | AN APPROVED TESTING LAB AS I WAS UNABLE TO LOCATE A | | LIST ON THE INTERNET. | | | | **OK - REVISED 10/2 - CONTRACTOR SHOWED TO J SMITH, | | INSPECTOR** | | | | 2.)FASTENER DESIGN IN ACCORDANCE WITH RAS117 IS TO BE | | SUBMITTED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF | | CONSULTANT AS PER GENERAL LIMITATION #7 OF THE | | MIAMIDADE NOA 06-0626.05.PLEASE SUBMIT.**OK - | | SUBMITTED W/ROOF PERMIT 07070582** | | | | ROOF HATCH: | | | | 3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED | | FOR THE ROOF HATCH, FAC9B72. IF A FLORIDA STATE PRODUCT | | APPROVAL IS NOT AVAILABLE, SUBMIT APPLICATION FOR LOCAL | | PRODUCT APPROVAL; SEE ATTACHED.ALL INFORMATION ON THE | | APPLICATION MUST BE COMPLETED AND ALL ENGINEERING MUST | | BE ORIGINAL.IF A MIAMIDADE NOA HAS BEEN ISSUED FOR | | THE PRODUCT YOU ARE USING, AN APPLICATION (AND ORIGINAL | | ENGINEERING) IS NOT REQUIRED.OTHERWISE, SUBMIT ALL | | INFORMATION REQUIRED INCLUDING PROOF OF A QUALITY | | ASSURANCE PROGRAM. | | | | ACCESSIBLE LIFT, SCUTTLE LADDER: | | | | 4.)HAVE THE SHOP DRAWINGS REVIEWED BY DESIGNER OF | | RECORD. | | | | MISCELLANEOUS: | | | | 5.)AS A COURTESY, I HAVE PRINTED THE INSTALLATION | | INSTRUCTIONS AND SUPPLEMENTARY DRAWINGS FOR THE | | EVALUATION REPORT FOR THE OVERHEAD DOOR PRODUCT | | APPROVAL AS THE DRAWINGS WERE ILLEGIBLE.IN THE | | FUTURE, PLEASE SUBMIT ONLY LEGIBLE DOCUMENTS.THEY ARE | | AVAILABLE ON THE INTERNET AT WWW.FLORIDABUILDING.ORG. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
7 |
Status |
P |
Date |
2007-09-26 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-09-26 |
Time |
11:40 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-09-26 |
Time |
11:40 |
Sent To |
|
|
Notes |
2007-09-26 11:58:44 | REVISION DATED 9/19, SHEET A-0.1, DETAIL SD-3.0 | | | | | 2007-09-26 11:40:34 | REVISION DATED 9/10/07, SHEET 5 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
F |
Date |
2007-09-24 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-09-24 |
Time |
09:36 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-09-24 |
Time |
09:35 |
Sent To |
|
|
Notes |
2007-09-24 09:39:18 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | 1.)REGARDING THE UL DETAILS SUBMITTED; IF THEY ARE | | ALREADY A PART OF THE APPROVED PLAN, THE SHOP DRAWINGS | | (UL W-L DETAILS) SUBMITTED ARE UNNECESSARY.IF THEY | | ARE NOT A PART OF THE APPROVED PLAN, PLEASE INCORPORATE | | THESE DETAILS INTO THE PLAN AND SUBMIT AS A REVISION. | | | | 2.)FIRESTOPPING SUBMITTAL OK. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
F |
Date |
2007-09-24 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-09-24 |
Time |
07:51 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-09-24 |
Time |
07:51 |
Sent To |
|
|
Notes |
2007-09-24 07:52:35 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | PROVISO ITEMS | | REVISION DATED 8/21/07 | | | | | | 1.)SUBMIT PRODUCT APPROVALS COMPLIANT WITH THE DESIGN | | PRESSURE REQUIREMENT OF +-33 (S2.1) FOR THE GARAGE | | DOORS OR REVISE S2.1.THE PRODUCT APPROVAL SUBMITTED | | HAS DP LIMITATION OF +28/-32. | | | | A FLORIDA STATE PRODUCT APPROVAL WAS SUBMITTED WITH | | SHOP DRAWINGS WHICH DO NOT SHOW ANY DESIGN PRESSURES. | | PRINT THE DOCUMENTS FROM THE WEBSITE; EVALUATION REPORT | | (WHICH SHOULD HAVE THE DESIGN PRESSURES FOR THIS | | PRODUCT) AND INSTALLATION INSTRUCTIONS.HAVE THE | | PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD PRIOR | | TO SUBMITTAL, FBC*106.3.3. | | | | 2.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED | | FOR THE ROOF HATCH FAC9B72. | | | | SHOP DRAWINGS WERE SUBMITTED.PROVIDE FLORIDA STATE | | PRODUCT APPROVAL OR APPLY FOR LOCAL PRODUCT APPROVAL AS | | REQUIRED BY FAC9B72. | | | | 3.)THE ROOFING PRODUCT APPROVALS WERE ALREADY | | SUBMITTED.HOWEVER, SEE GENERAL LIMITATION #7. | | ENHANCED FASTENING CALCULATIONS PREPARED BY AN | | ARCHITECT, ENGINEER, OR REGISTERED ROOF CONSULTANT | | REQUIRED.(OK -SUBMITTED W/ROOF PERMIT 07070582) | | | | (NOA06-0626.05, ASSEMBLY PAGE 27) |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2007-05-01 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-05-01 |
Time |
08:03 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-05-01 |
Time |
08:03 |
Sent To |
|
|
Notes |
2007-05-01 08:08:56 | *** PROVISO *** | | | | 1.)SUBMIT PRODUCT APPROVALS COMPLIANT WITH THE DESIGN | | PRESSURE REQUIREMENT OF +-33 (S2.1) FOR THE GARAGE | | DOORS OR REVISE S2.1.THE PRODUCT APPROVAL SUBMITTED | | HAS DP LIMITATION OF +28/-32. | | | | 2.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED | | FOR THE ROOF HATCH FAC9B72. | | | | INFORMATIONAL NOTE - NOA06-0626.05, ASSEMBLY PAGE 27 | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2007-04-09 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-04-09 |
Time |
08:50 |
Rev Time |
16.00 |
Received By |
shill |
Date |
2007-04-04 |
Time |
07:44 |
Sent To |
|
|
Notes |
2007-04-04 07:45:09 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | ***NOTE - PLAN REVIEW COMMENTS WERE CHANGED 4/12/07 TO | | DOCUMENT ITEMS DISCUSSED/NEGOTIATED WITH ARCHITECT AND | | CONTRACTOR IN A MEETING 4/11/07** | | ***NOTE THAT A LIFE SAFETY PLAN WAS ACCEPTED DURING THE | | PLAN REVIEW PROCESS DURING REVIEW #3.THIS IS THE 4TH | | COURTESY REVIEW REFERRED TO IN THE PLAN REVIEW | | NOTES.*** | | | | 1-8.) ADDRESSED. | | | | 9.)A SEPARATE PERMIT WILL BE REQUIRED FOR THE SIGN | | SHOWN ON A-0.1.SEPARATE PLANS AND PERMIT APPLICATION | | WILL BE REQUIRED.INFORMATIONAL ONLY; THIS IS NOT | | REQUIRED TO BE ADDRESSED AT THIS TIME. | | | | 10-12.)ADDRESSED. | | | | 13.)EXTRA FP1 SHEETS WERE SUBMITTED.PLEASE PROVIDE | | THREE ORIGINALS, ONE PUT INTO EACH ROLLED PERMIT SET. | | | | THREE SETS SUBMITTED.PLEASE KEEP THE THREE SETS IN | | THE PACKAGE.THEY ARE NOT CURRENTLY A PART OF THE | | BOUND SET.THIS IS ACCEPTABLE; HOWEVER, PLEASE ENSURE | | THAT THEY ARE NOT INADVERTENTLY REMOVED FROM THE | | PACKAGE AS THIS IS A STATUTORY REQUIREMENT AND THE | | PERMIT CANNOT BE ISSUED WITHOUT SPRINKLER PLANS. | | | | 14-15.) ADDRESSED. | | | | 16.)A NEW LIFE SAFETY PLAN WAS ACCEPTED DURING THE | | PLAN REVIEW PROCESS.NOTE THAT THE ORIGINAL LS PLAN | | SUBMITTED DID NOT PROPERLY ADDRESS THE COMMENTS AND A | | NEW LS PLAN WAS SUBMITTED AFTER DISCUSSION WITH THE | | ARCHITECT. | | | | 3RD REVIEW:ONLY ONE ACCESSIBLE EXIT SHOWN FOR EACH | | AREA.BASED ON OCCUPANT LOAD, TWO EXITS ARE REQUIRED | | FOR THE DISTRIBUTION AREA, TWO EXITS ARE REQUIRED FOR | | THE OFFICE AREA.PROVIDE ALL INFORMATION FOR EXITING | | ON THE LIFE SAFETY PLAN FOR THE ACCESSIBLE EXITS. | | REVIEW WAS STOPPED AND I AGREED TO ACCEPT A NEW LIFE | | SAFETY PLAN IN ATTEMPT TO ISSUE THE PERMIT IF ALL OTHER | | ITEMS WERE ADDRESSED FROM ALL PLAN REVIEWERS, INCLUDING | | MY LIST.HOWEVER, THE LIFE SAFETY PLAN SUBMITTED WAS | | NOT COMPLIANT. | | | | FOURTH (COURTESY) REVIEW.THE NEW LIFE SAFETY PLAN | | SHOULD BE REVISED TO SHOW THE FOLLOWING FOR THE SECOND | | ACCESSIBLE MEANS OF EGRESS FROM THE DISTRIBUTION AREA: | | | | EXIT LIGHTS, FBC1006.3 | | EXIT CAPACITY, FBC1004.1.3 | | DOOR SWING, FBC1008.1.2 | | TRAVEL DISTANCE, FBC1015 | | EGRESS CAPACITY, FBC1005 | | | | NOTE THAT TRAVEL DISTANCE IS SHOWN THROUGH THE MIDDLE | | OF SOME ROOMS; THIS IS USUALLY DONE AROUND THE | | PERIMETER OF THE ROOM, FBC1015.1. | | | | ALL OF THE ABOVE INFORMATION WAS PROVIDED ON THE LIFE | | SAFETY PLAN BUT DID NOT ADDRESS ACCESSIBLE MEANS OF | | EGRESS.SEE COMMENT 17, ACCESSIBLE MEANS OF EGRESS | | SHALL BE PROVIDED IN THE SAME NUMBER AS REQUIRED FOR | | EXITS BY LOCAL BUILDING/LIFE SAFETY REGULATIONS, | | FBC11-4.1.3(9).A LIFT WAS ADDED, EXITING THROUGH THE | | OFFICE AREA WAS DISCUSSED BUT NOTHING IS SHOWN ON THE | | PLAN; OTHER INFORMATION ABOVE NOT PROVIDED. | | | | 17.)FBC11-4.1.3(9), ACCESSIBLE MEANS OF EGRESS SHALL | | BE PROVIDED IN THE SAME NUMBER AS REQUIRED FOR EXITS BY | | LOCAL BUILDING/LIFE SAFETY REGULATIONS. A RAMP IS SHOWN | | AT THE BUILDING ENTRANCE, NO OTHER ACCESSIBLE EXITS | | SHOWN. | | | | 2ND REVIEW, THE RESPONSE LETTER STATES THAT ALL EXITS | | ARE ACCESSIBLE.SEE FBC11-3, DEFINITION OF EGRESS, | | MEANS OF; DOES NOT INCLUDE STAIRS, STEPS, OR | | ESCALATORS. | | | | (REVISED 4/12) 3RD COURTESY REVIEW, TWO EXITS ARE | | REQUIRED FROM THE DISTRIBUTION AREA AND TWO EXITS | | REQUIRED FROM THE OFFICE AREA.ONLY ONE ACCESSIBLE | | EXIT FOR EACH AREA IS SHOWN. | | | | (REVISED 4/12) 4TH REVIEW, REVISED LIFE SAFETY PLAN | | SUBMITTED DURING REVIEW; THERE IS STILL ONLY ONE | | ACCESSIBLE EXIT FROM THE DISTRIBUTION AREA, TWO | | REQUIRED BASED ON OCCUPANT LOAD. | | | | 18.)1ST/2ND REVIEW: THIS BUILDING REQUIRES MORE THAN | | ONE EXIT, SEE FBC1018.2.THIS WAS NOT ADDRESSED FOR | | ACCESSIBLE EXITS; ONLY ONE SHOWN. | | | | (REVISED 4/12) 3RD REVIEW:SEE COMMENT 17. | | | | (REVISED 4/12) 4TH COURTESY REVIEW:THERE IS NOW ONE | | ACCESSIBLE EXIT SHOWN FOR THE DISTRIBUTION AREA | | (REQUIRES TWO BASED ON OCCUPANT LOAD) AND ONE FOR THE | | OFFICE AREA.OFFICE AREA IS COMPLIANT AS IT REQUIRES | | ONE EXIT BASED ON OCCUPANT LOAD, BUT TWO ACCESSIBLE | | EXITS ARE REQUIRED FOR THE DISTRIBUTION AREA. | | | | 19-22.)ADDRESSED. | | | | 23.)1ST/2ND REVIEWS: EXIT OR EXIT ACCESS DOORWAY | | ARRANGEMENT SHALL COMPLY WITH FBC1014.2 OR | | FBC1014.2.2., SHOW DISTANCE APART, SEE EXCEPTION 2. | | THERE ARE TO BE TWO ACCESSIBLE EXITS WHICH ARE REMOTELY | | LOCATED.ONLY ONE SHOWN ON THE PLAN (ALL OTHERS HAVE | | STAIRS). | | | | 3RD REVIEW (REVISED 4/12):THE TWO DOORS SHOWN SERVE | | TWO DIFFERENT AREAS.SHOW THE TWO ACCESSIBLE EXITS, | | REMOTELY LOCATED, AS REQUESTED. | | | | 4TH (COURTESY) REVIEW: THE DISTANCE IS SHOWN BETWEEN | | THE TWO ACCESSIBLE EXITS BUT THE EXIT WITH THE RAMP | | DOES NOT SERVE THE DISTRIBUTION AREA (NO EXIT SIGNS | | FROM DISTRIBUTION AREA THROUGH OFFICE, NOTHING ON THE | | PLAN TO SHOW THAT THIS IS TO BE AN EXIT TO SERVE THE | | DISTRIBUTION AREA).IT IS CLEAR THAT NON ACCESSIBLE | | EXITS ARE COMPLIANT.SHOW COMPLIANCE FOR ACCESSIBLE | | EXITS AS REQUESTED ON PREVIOUS REVIEWS. | | | | 24.) ADDRESSED. | | | | 25.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC. | | | | 26.)THE COMMENT REGARDING REMOVABLE SHUTTERS WAS, I | | BELIEVE, ADDRESSED WITH SUBMITTAL OF IMPACT DOOR | | PRODUCT APPROVALS.IT APPEARS THAT IMPACT RATED | | PRODUCTS WILL BE USED.PLEASE NOTE THAT IF NON IMPACT | | PRODUCT APPROVALS ARE SUBMITTED ON THIRD REVIEW, A | | SHUTTER INSTALLATION PLAN WILL BE REQUIRED PRIOR TO | | PERMIT ISSUANCE.PLEASE CONTACT ME IF YOU WOULD LIKE | | TO PROPOSE THE USE OF REMOVABLE SHUTTERS TO DISCUSS | | THAT APPROVAL PROCESS.IF ALL PRODUCTS WILL BE IMPACT | | RATED, DISREGARD THE COMMENT. | | | | THIRD REVIEW - PLEASE SUBMIT ALL REQUIRED PRODUCT | | APPROVALS AT THIS TIME. | | | | 27.)PLEASE NOTE THAT PRODUCT APPROVALS FOR IMPACT | | DOORS WERE SUBMITTED.PRODUCT APPROVALS ARE TO BE | | REVIEWED BY DESIGNER OF RECORD, FBC*106.3.3.NO OTHER | | PRODUCT APPROVALS WERE SUBMITTED.FLORIDA STATE OR | | LOCAL PRODUCT APPROVAL REQUIRED IN ADDITION TO THE | | EVALUATION REPORT (MIAMIDADE NOA IN THIS CASE) | | PROVIDED, FAC9B72; WWW.FLORIDABUILDING.ORG.IF FLORIDA | | STATE PRODUCT APPROVAL IS NOT AVAILABLE, PLEASE CONTACT | | ME TO DISCUSS. | | | | NO ROOFING PR-DUCT APPROVALS WERE SUBMITTED. CONTRACTOR | | OR DOR IS TO SELECT THE APPROVED ASSEMBLY. | | | | FOR ALL OTHER PRODUCTS, INCLUDING THE STANDING SEAM | | ROOF PANELS, IF THERE ARE DIFFERENT OPTIONS FOR | | INSTALLATION AND NOT ALL OF THEM ARE COMPLIANT FOR | | DESIGN PRESSURES FOR THIS BUILDING, CIRCLE THE | | INSTALLATION OR PARTICULAR OPTION YOU ARE USING SO THAT | | CODE COMPLIANCE CAN BE DETERMINED. | | | | THIRD REVIEW ? THE PRODUCT APPROVALS WHICH ARE IN THE | | PACKAGE STILL HAVE NO EVIDENCE THAT THEY HAVE BEEN | | REVIEWED BY DESIGNER OF RECORD.THIS MAY BE DONE WITH | | A SHOP DRAWING REVIEW STAMP, A LETTER, OR INCORPORATED | | INTO THE PLAN BY REFERENCE. | | | | ALL PRODUCT APPROVALS REQUIRED BY FAC9B72 ARE REQUIRED | | AT THIS TIME DUE TO A POLICY CHANGE.STATEMENTS IN THE | | PREVIOUS COMMENTS THAT THEY COULD BE SUBMITTED IN THE | | FUTURE UNDER SEPARATE PERMIT HAVE BEEN REMOVED FROM | | THIS REVIEW TO AVOID CONFUSION. | | | | AS THE DOR DID NOT PROVIDE A SCHEDULE, ALL WALL | | PRODUCTS ARE TO COMPLY WITH WORST CASE WALL PRESSURE OF | | -48PSF.PRODUCT APPROVALS REQUIRED INCLUDE STOREFRONT, | | SKYLIGHT, OVERHEAD DOOR, FULL LOUVER METAL DOOR, | | LOUVERS, ROOF HATCH, 24 GA GALVALUME STANDING SEAM | | METAL ROOF, 4 PLY BUR OVER INSULATED LW CONCRETE.THIS | | MAY NOT BE A COMPLETE LIST; CONTRACTOR OR DOR IS | | RESPONSIBLE FOR THE COMPLETENESS OF THE SUBMITTED | | PACKAGE. | | | | **4/12/07** DURING THE MEETING WITH THE ARCHITECT I | | BECAME AWARE THAT THE THREE BOUND SETS OF DOCUMENTS | | SUBMITTED WERE NOT IDENTICAL SETS.THERE WERE SOME | | PRODUCT APPROVALS REVIEWED BY DOR IN THE OTHER PACKAGE. | | THE ROOF PRODUCT APPROVAL WAS REVIEWED BY ANOTHER | | ARCHITECT FROM A DIFFERENT PRODUCT. | | | | WHEN RESUBMITTING, PLEASE PROVIDE THREE IDENTICAL BOUND | | SETS FOR PERMIT ISSUANCE.FAILURE TO DO SO WILL RESULT | | IN PERMIT DELAYS. | | | | ALL OTHER COMMENTS IN REGARDS TO PRODUCT APPROVALS | | STILL APPLY.FLORIDA STATE OR LOCAL PRODUCT APPROVAL | | REQUIRED FOR ALL PRODUCTS, FAC9B72, | | WWW.FLORIDABUILDING.ORG.FLORIDA STATE PRODUCT | | APPROVAL IS TO BE FOR THE 2004 CODE (NOT 2001 AS IS THE | | CASE WITH THE OVERHEAD DOOR PRODUCT APPROVAL).ONLY | | ONE SHEET OF THE NOA FOR THE INGERSOLL RAND DOOR WAS | | SUBMITTED; ALL SHEETS REQUIRED.IF A FLORIDA STATE | | PRODUCT APPROVAL IS NOT AVAILABLE FOR ANY OF THE | | PRODUCTS YOU HAVE SELECTED, PLEASE CONTACT ME IN | | REGARDS TO THE PROCEDURE FOR APPLICATION FOR LOCAL | | PRODUCT APPROVAL. | | | | 28.)SQUARE FOOT AREAS ON THE ENERGY CALCS DO NOT | | MATCH THE PLAN. | | | | THIRD REVIEW - THE ARCHITECT RESPONSE LETTER STATES | | THAT INSIDE DIMENSIONS WERE USED FOR THE ENERGY CALCS. | | SEE FBC 13, CHAPTER 2, DEFINITION OF FLOOR AREA, GROSS. | | AS NEW ENERGY CALCS ARE REQUIRED, ELECTRIC REVIEW WILL | | ALSO BE REQUIRED ON RESUBMITTAL.NOTE THAT ENERGY | | CALCS ARE A STATUTORY REQUIREMENT AND STATUTORY | | REQUIREMENTS CAN NEVER BE WAIVED OR PROVISO?D (PER | | BUILDING OFFICIAL). | | | | 29.)FROM FIRST REVIEW - THE ENGINEER'S TITLE BLOCK IS | | TO COMPLY WITH FAC61G15-23.002, VP BUILDINGS. | | | | 4/12/07MR. JOHN RYAN, ATTORNEY FOR FLORIDA BOARD OF | | PROFESSIONAL ENGINEERS, CONFIRMED THE CERTIFICATE OF | | AUTHORIZATION REQUIREMENT, FS471.023.THE ENGINEER'S | | LETTER STATING THAT ENGINEERING IS NOT THE PRODUCT | | OFFERED TO THE PUBLIC IS ACKNOWLEDGED.HOWEVER, WHEN | | PRACTICING ENGINEERING THROUGH A COMPANY, A CERTIFICATE | | OF AUTHORIZATION IS REQUIRED REGARDLESS OF PRODUCT | | OFFERED.PLEASE CONTACT FBPE IF YOU NEED FURTHER | | CLARIFICATION, 850-521-0500.AS THIS IS A STATUTORY | | REQUIREMENT, THIS CANNOT BE WAIVED OR PROVISO'D; PLANS | | MUST BE IN COMPLIANCE FOR PERMITTING. | | | | 30.)ADDRESSED. | | | | 31.)THE ENGINEER'S SIGNATURE IS A PHOTOCOPY, ORIGINAL | | WET SIGNATURE REQUIRED.SEE PANEL SHEETS AND VP | | SHEETS. | | | | THIRD REVIEW - PANEL ENGINEERING STILL HAS A PHOTOCOPY | | SIGNATURE.ALSO ALL INFORMATION REQUIRED BY | | FAC61G15-23.002 IS REQUIRED TO BE ON EACH SHEET | | (CERTIFICATE OF AUTHORIZATION). | | | | THE FOOTERS, SITEWORK, AND STRUCTURE (PANELS, STEEL | | STRUCTURE) WERE ISSUED UNDER SEPARATE PERMITS.HAVE | | THE CHANGES SHOWN ON THE CIVIL DRAWINGS BEEN MADE TO | | THE ISSUED SITEWORK PERMIT?PLEASE PROVIDE A PERMIT | | NUMBER FOR THE SITEWORK. | | | | THE PANEL PLANS AND STEEL STRUCTURAL PLANS ARE NOT | | REQUIRED FOR THIS PERMIT AS THEY ARE INCLUDED IN THE | | SCOPE OF WORK OF ANOTHER PERMIT.IF EITHER PLAN IS | | CHANGED AS A RESULT OF THESE COMMENTS, THE CHANGES | | SHOULD BE SUBMITTED AS REVISIONS TO THE ISSUED PERMIT. | | ALSO HAVING A SET INCLUDED FOR REFERENCE (AS LONG AS IT | | MATCHES THE PERMIT SET) WILL ASSIST IN PLAN REVIEW. | | | | 32-36.) ADDRESSED. | | | | 37.)SEE ATTACHED FS553.80(2)(B).NOTE THAT THIS IS A | | MANDATORY FINE AND CANNOT BE WAIVED.NOTE THAT SOME | | COMMENTS HAVE ALREADY BEEN MADE THREE TIMES (ENERGY | | CALCS, LIFE SAFETY).A 4X PLAN REVIEW FEE HAS BEEN | | CHARGED. | | | | NEW COMMENTS: | | | | 38.)SEE CIVIL SHEET 17 OF 29 PREPARED BY BOYER | | SINGLETON.THIS SHEET HAS A DATE OF FEBRUARY 12, 2007, | | NO CHANGES CLOUDED.THE SECOND BUILDING REVIEW WAS | | JANUARY 30, 2007.THIS IS EITHER A NEW SHEET OR | | CHANGES WERE MADE TO THE SHEET AND NOT INDICATED.ALL | | CHANGES TO THE PLAN ARE TO BE CLEARLY INDICATED WITH | | CLOUDS AND REVISION NUMBERS.WHEN CHANGES ARE | | SUBMITTED A COMPLETE NEW PLAN REVIEW IS REQUIRED AS I | | CANNOT DETERMINE SPECIFICALLY WHAT HAS CHANGED.NOTE | | THAT THE ARCHITECT (CORRECTLY) CLOUDED THE PAGE NUMBER | | TO SHOW NEW SHEETS. | | | | THE "TURNSTILE & HANDICAPPED SECURITY GATE" DETAIL ON | | SHEET 17 IS ILLEGIBLE.AS THIS DETAIL IS REQUIRED TO | | SHOW CODE COMPLIANCE (ACCESSIBILITY, EGRESS) PLEASE | | PROVIDE LEGIBLE DETAILS. | | | | 4/12/07 ** IN THE MEETING WITH ARCHITECT ON 4/11/7, IT | | WAS DISCUSSED THAT THIS DETAIL IS ALSO IN THE ELECTRIC | | DRAWINGS.TO AVOID FURTHER PERMITTING DELAYS, DO NOT | | ADDRESS THIS COMMENT AT THIS TIME.FOR THE FUTURE, | | PLEASE NOTE THAT ALL DETAILS ARE REQUIRED TO BE | | LEGIBLE!!!WHEN ISSUING THE PERMIT I WILL MAKE A NOTE | | ON THE PLAN REFERRING TO THE APPROPRIATE ELECTRIC | | SHEET. | | | | 39.)SHEET 18 OF 24 OF THE CIVIL DRAWINGS CONTAINS | | INFORMATION IN REGARDS TO THE FUEL TANK.THIS IS | | CURRENTLY IN THE PLAN REVIEW PROCESS UNDER SEPARATE | | PERMIT.AS THIS SHEET HAS NOT BEEN REVIEWED BY ALL | | TRADES FOR CODE COMPLIANCE, AND TO AVOID HAVING | | INFORMATION IN THIS PERMIT WHICH CONFLICTS WITH OTHER | | PERMITS, PLEASE REMOVE THIS SHEET. | | | | 40.)A3.0, THERE IS A NEW NOTE STATING THAT A | | SATELLITE DISH IS TO BE INSTALLED AND A SLEEVE PROVIDED | | IN THE TILT WALL PANEL.PROVIDE A DETAIL FOR THE | | SATELLITE DISH AND A SPECIFICATION FOR THE SLEEVE.THE | | WALL PANEL ENGINEER IS TO INCLUDE THIS INFORMATION IN | | HIS STRUCTURAL DRAWINGS.SEE SHEET PN10; THERE IS A | | NOTE ADDRESSING CORE DRILLING AFTER ERECTION.IT IS | | NOT CLEAR IF THIS SLEEVE IS TO BE PROVIDED IN THE PANEL | | WHEN IT IS CONSTRUCTED OR IF IT IS DRILLED AFTER | | ERECTION.IN EITHER CASE, IT REQUIRES THE APPROVAL OF | | THE WALL PANEL ENGINEER AND SHOULD ALSO BE ADDRESSED ON | | HIS DRAWINGS SO THAT THE STRUCTURAL DRAWINGS ARE | | CONSISTENT WITH THE ARCHITECTURAL DRAWINGS. | | | | **4/12/07** IN THE MEETING WITH THE ARCHITECT, IT WAS | | AGREED THAT THE STRUCTURE/WALL PANEL PERMIT IS TO BE | | REVISED AND THAT THIS PLAN WILL BE REVISED TO SHOW | | METHOD OF ATTACHMENT AND ALSO WILL STATE THAT SHOP | | DRAWINGS WILL BE REQUIRED PRIOR TO ISSUANCE. | | | | 41.)A4.0, ELEVATION AND ENTRY DETAIL, SEE | | FBC11-4.13.7.WHEN SCALED, IT APPEARS TO MEET THE | | MINIMUM REQUIREMENT EXACTLY BUT PLEASE NOTE THAT | | REQUIREMENT ON THE PLAN. | | | | 42.)SEE THE STRUCTURAL PAGES PREPARED AND SIGNED BY | | BRADLEY B. JOHNSON, PE.FS471, FAC61G15-23, THE SEAL | | IS NOT LEGIBLE. | | | | **4/12/07**IN THE MEETING WITH THE ARCHITECT AND | | CONTRACTOR, IT WAS AGREED THAT THE BEST COURSE OF | | ACTION WOULD BE TO SUBMIT AS SOON AS POSSIBLE.THE | | ENGINEER HAS ORDERED A NEW SEAL.IF NEWLY SEALED | | SHEETS ARE NOT AVAILABLE AT THE TIME OF RESUBMITTAL, I | | WILL ALLOW THE CONTRACTOR OR ARCHITECT TO BRING IN THE | | NEW SHEETS (NEW SEAL ONLY, NO CHANGE TO DRAWING) AFTER | | RESUBMITTAL PROVIDED THAT ALL OTHER COMMENTS FROM ALL | | PLANS EXAMINERS HAVE BEEN SATISFIED. | | | | 43.)***NEW COMMENT 4/12/07***THE ARCHITECT'S | | OBJECTION TO SHOWING COMPLIANCE WITH ALL EXITING | | REQUIREMENTS FOR ACCESSIBLE EXITS IS NOTED.AS | | DISCUSSED, THE NEW LIFE SAFETY PLAN WILL SHOW | | COMPLIANCE AS REQUESTED ALTHOUGH THE ARCHITECT DOES NOT | | AGREE WITH THE REQUIREMENT. | | | | HOWEVER, WE ARE IN AGREEMENT REGARDING ITEMS #17 AND | | 18.MY UNDERSTANDING IS THAT THE ARCHITECT AGREES THAT | | TWO ARE REQUIRED AND ONLY ACCESSIBLE EXIT SERVING THE | | DISTRIBUTION AREAIS SHOWN ON THE PLAN, FOUR REVIEWS. | | | | | | TO EXPEDITE PLAN REVIEW, INCLUDE A RESPONSE LETTER | | INDICATING HOW EACH ITEM WAS ADDRESSED WHEN | | RESUBMITTING. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2007-01-30 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-01-30 |
Time |
11:14 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-01-23 |
Time |
08:35 |
Sent To |
|
|
Notes |
2007-01-30 11:14:52 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | 1-8.) ADDRESSED. | | | | 9.)A SEPARATE PERMIT WILL BE REQUIRED FOR THE SIGN | | SHOWN ON A-0.1.SEPARATE PLANS AND PERMIT APPLICATION | | WILL BE REQUIRED.INFORMATIONAL ONLY; THIS IS NOT | | REQUIRED TO BE ADDRESSED AT THIS TIME. | | | | 10.)ADDRESSED. | | | | 11.)ADDRESSED. | | | | 12.)S1 WAS DECLARED, BUT THE LIFE SAFETY PLAN SHOWS | | S2.PLEASE ADDRESS. | | | | 13.)EXTRA FP1 SHEETS WERE SUBMITTED.PLEASE PROVIDE | | THREE ORIGINALS, ONE PUT INTO EACH ROLLED PERMIT SET. | | | | | | 14-15.) ADDRESSED. | | | | 16.)A LIFE SAFETY PLAN WAS PROVIDED IN RESPONSE TO | | THE PREVIOUS COMMENT.PLEASE ADDRESS THE FOLLOWING | | ITEMS: | | | | A. THE PURPOSE OF THE OVERLAPPING CIRCLES ON THE PLAN | | IS NOT CLEAR, AND NO PATH OF EGRESS TRAVEL WAS SHOWN. | | TYPICALLY THE WORST CASE TRAVEL DISTANCE IS SHOWN FROM | | EACH AREA TO THE REQUIRED EXITS.PLEASE REMOVE THE | | CIRCLES AS THEY MAKE THE PLAN DIFFICULT TO READ, OR | | CLARIFY THE PURPOSE. | | | | B. THE LIFE SAFETY PLAN STATES THAT TRAVEL DISTANCE IS | | UNLIMITED FOR S2 OCCUPANCY, BUT YOU HAVE DECLARED S1 ON | | SHEET A0.0.SEE FBC TABLE 1015.1, S1 HAS A MAXIMUM | | TRAVEL DISTANCE OF 250FEET, FULLY SPRINKLED BUILDING. | | ALSO SEE OTHER NOTES REGARDING ACCESSIBLE EXITS. | | | | C. OCCUPANT LOAD OF 63 HAS BEEN DECLARED FOR THE | | WAREHOUSE AREA.A0.0 DECLARES 32,720 SF.SEE FBC | | TABLE 1004.1.2, FBC 1004.1 STATES THAT OCCUPANT LOAD | | CANNOT BE LESS THAN THE TABLE, SO SHOULD BE A MINIMUM | | OF 65 BASED ON SF AREA. | | | | D. FBC1005.1, THE LOSS OF ANY ONE MEANS OF EGRESS SHALL | | NOT REDUCE THE AVAILABLE CAPACITY TO LESS THAN 50 | | PERCENT OF THE REQUIRED CAPACITY.BASED ON DESIGN | | OCCUPANT LOAD FOR THE BUSINESS AREA, THE EXITING DOES | | NOT COMPLY.PLEASE ADDRESS. | | | | E. THE SCALE APPEARS TO BE 1/16.NOTE THE SCALE ON THE | | PLAN.PROVIDE OVERALL DIMENSIONS. | | 17.)FBC11-4.1.3(9), ACCESSIBLE MEANS OF EGRESS SHALL | | BE PROVIDED IN THE SAME NUMBER AS REQUIRED FOR EXITS BY | | LOCAL BUILDING/LIFE SAFETY REGULATIONS. A RAMP IS SHOWN | | AT THE BUILDING ENTRANCE, NO OTHER ACCESSIBLE EXITS | | SHOWN. | | | | THE RESPONSE LETTER STATES THAT ALL EXITS ARE | | ACCESSIBLE.SEE FBC11-3, DEFINITION OF EGRESS, MEANS | | OF; DOES NOT INCLUDE STAIRS, STEPS, OR ESCALATORS. | | | | 18.)THIS BUILDING REQUIRES MORE THAN ONE EXIT, SEE | | FBC1018.2.THIS WAS NOT ADDRESSED FOR ACCESSIBLE | | EXITS; ONLY ONE SHOWN. | | | | 19.)A1.0 SHOWS A CHECK WRITING STAND, PLEASE NOTE ON | | THE PLAN THAT THIS AREA IS NOT OPEN TO THE PUBLIC. | | | | 20-21.) ADDRESSED. | | | | 22.)FBC11-4.1.3(8)(A)(II), ACCESSIBLE ENTRANCES | | REQUIRED AT LEAST EQUIVALENT TO THE NUMBER OF | | ACCESSIBLE EXITS.SEE OTHER COMMENTS.ENTRANCES WITH | | STAIRS DO NOT MEET THE REQUIREMENTS OF VERTICAL | | ACCESSIBILITY. | | | | 23.)EXIT OR EXIT ACCESS DOORWAY ARRANGEMENT SHALL | | COMPLY WITH FBC1014.2 OR FBC1014.2.2., SHOW DISTANCE | | APART, SEE EXCEPTION 2.THERE ARE TO BE TWO ACCESSIBLE | | EXITS WHICH ARE REMOTELY LOCATED.ONLY ONE SHOWN ON | | THE PLAN (ALL OTHERS HAVE STAIRS). | | | | 24.)ADDRESSED. | | | | 25.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC. | | | | 26.)THE COMMENT REGARDING REMOVABLE SHUTTERS WAS, I | | BELIEVE, ADDRESSED WITH SUBMITTAL OF IMPACT DOOR | | PRODUCT APPROVALS.IT APPEARS THAT IMPACT RATED | | PRODUCTS WILL BE USED.PLEASE NOTE THAT IF NONIMPACT | | PRODUCT APPROVALS ARE SUBMITTED ON THIRD REVIEW, A | | SHUTTER INSTALLATION PLAN WILL BE REQUIRED PRIOR TO | | PERMIT ISSUANCE.PLEASE CONTACT ME IF YOU WOULD LIKE | | TO PROPOSE THE USE OF REMOVABLE SHUTTERS TO DISCUSS | | THAT APPROVAL PROCESS.IF ALL PRODUCTS WILL BE IMPACT | | RATED, DISREGARD THE COMMENT. | | | | 27.)PLEASE NOTE THAT PRODUCT APPROVALS FOR IMPACT | | DOORS WERE SUBMITTED.PRODUCT APPROVALS ARE TO BE | | REVIEWED BY DESIGNER OF RECORD, FBC*106.3.3.NO OTHER | | PRODUCT APPROVALS WERE SUBMITTED.NOTE THAT ANY | | PRODUCT APPROVALS NOT SUBMITTED AND REVIEWED PRIOR TO | | PERMIT ISSUANCE WILL REQUIRE SEPARATE PERMITS WITH | | SEPARATE FEES.FLORIDA STATE OR LOCAL PRODUCT | | APPROVAL REQUIRED IN ADDITION TO THE EVALUATION REPORT | | (MIAMIDADE NOA IN THIS CASE) PROVIDED, FAC9B72. | | WWW.FLORIDABUILDING.ORGIF FLORIDA STATE PRODUCT | | APPROVAL IS NOT AVAILABLE, PLEASE CONTACT ME TO | | DISCUSS. | | | | NO ROOFING PRODUCT APPROVALS WERE SUBMITTED.THIS MAY | | BE DONE WHEN THE ROOF PERMIT IS APPLIED FOR (WITH | | SEPARATE FEES BASED ON VALUE), OR MAY BE DONE NOW. | | CONTRACTOR OR DOR IS TO SELECT THE APPROVED ASSEMBLY. | | | | | | FOR ALL OTHER PRODUCTS, INCLUDING THE STANDING SEAM | | ROOF PANELS, IF THERE ARE DIFFERENT OPTIONS FOR | | INSTALLATION AND NOT ALL OF THEM ARE COMPLIANT FOR | | DESIGN PRESSURES FOR THIS BUILDING, CIRCLE THE | | INSTALLATION OR PARTICULAR OPTION YOU ARE USING SO THAT | | CODE COMPLIANCE CAN BE DETERMINED. | | | | 28.)SQUARE FOOT AREAS ON THE ENERGY CALCS DO NOT | | MATCH THE PLAN. | | | | 29.)ADDRESSED. | | | | 30.)INCLUDE THE CORRECT JURISDICTION ON THE ENERGY | | CALCS, 604700 FBC13. | | | | 31.)THE ENGINEER'S SIGNATURE IS A PHOTOCOPY, ORIGINAL | | WET SIGNATURE REQUIRED.SEE PANEL SHEETS AND VP | | SHEETS. | | | | NEW COMMENTS: | | | | 32.)A1.2, SPECIFY DESIGN CRITERIA FOR STAIR AND GUARD | | RAIL RATHER THAN QUOTING A CODE SECTION.PROVIDE A | | DETAIL FOR THE STAIR HANDRAIL, GUARD RAILS, AND RAMP | | HANDRAIL.SEE FBC11-4.8.5, FBC11-4.9.4.WHEN SCALED, | | STAIR HANDRAIL EXTENSIONS ARE NOT LONG ENOUGH. | | | | CLARIFY 5-A4.0 HANDRAIL.IT APPEARS ON THE BOTTOM HALF | | OF THE RAMP BUT NOT THE TOP HALF. | | | | 33.)5-A4.0, SHOW THE MINIMUM DIMENSION WHERE THE RAMP | | CHANGES DIRECTION.WHEN SCALED IT IS COMPLIANT AT | | 60IN, FBC11-4.8.4(3). | | | | 34.)SOILS REPORTS NOT NECESSARY AS THEY WERE PROVIDED | | WITH THE FOUNDATION PERMIT. | | | | 35.)THE PANEL CALCS STATES THAT THE PROJECT NAME IS | | SEA HUNTER BOATS ON SOME PAGES. | | | | 36.)S2.1, ENGINEER HAS SPECIFIED 69PSF FOR THE FLAT | | DECK ROOF, ZONES 2 AND 3.PROVIDE CALCULATIONS. | | | | 37.)SEE ATTACHED FS553.80(2)(B). | | | | | | TO EXPEDITE PLAN REVIEW, INCLUDE A RESPONSE LETTER | | INDICATING HOW EACH ITEM WAS ADDRESSED WHEN | | RESUBMITTING. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-10-23 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2006-10-23 |
Time |
10:51 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2006-10-20 |
Time |
09:10 |
Sent To |
|
|
Notes |
2006-10-23 10:52:13 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 | | EXISTING BUILDING CODE | | FBC*CITY OF WEST PALM BEACH | | AMENDMENTS TO THE FBC2004 | | | | 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO | | PERMIT PICKUP, FS713.13. | | | | 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY | | PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL | | 561-233-5025 FOR MORE INFORMATION. | | | | 3.)THE COPY OF THE PLAT PROVIDED IS NOT RECORDED. | | PLEASE ADVISE AS TO STATUS.IF THIS IS RECORDED, | | PROVIDE PLAT FILING INFORMATION (BOOK/PAGE). | | | | 4.)THE PLAT PROVIDED AND THE PROPOSED PLAT LINES ON | | THE OVERALL SITE PLAN PREPARED BY BOWYER SINGLETON DO | | NOT MATCH.FOR INSTANCE, THE CIRCULAR SECTION AT THE | | END OF THE ROAD (PARCEL G) DOES NOT APPEAR ON THE | | OVERALL SITE PLAN.THE PLAT LINES ARE INCOMPLETE ON | | THE OVERALL SITE PLAN. | | | | 5.)THE APPLICATION REFERS TO TWO DIFFERENT PARCEL ID | | NUMBERS.YOU CANNOT CROSS PROPERTY LINES.PROVIDE | | INFORMATION IN REGARDS TO THE LOCATION OF THE TWO | | PARCELS, ENDING IN 3010 AND 3040.OUR GIS RECORDS | | SHOWS 3010 AS A VERY SMALL PARCEL (POSSIBLY A ROAD) | | GOING THROUGH THE MIDDLE OF THE LARGER PARCEL, 3040. | | PLEASE CONTACT ME TO DISCUSS IF YOU ARE UNSURE AS TO | | HOW TO GET THIS MATTERS RESOLVED. | | | | 6.) FBC* 109.3.7RESIDENT INSPECTOR. SUBMIT INSPECTOR | | RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA, | | DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.A RESIDENT | | INSPECTOR PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO | | ONE OR MORE OF THE FOLLOWING: | | - BUILDINGS/ADDITIONS OF TYPE I OR II | | CONSTRUCTION | | - ANY MAJOR STRUCTURAL ALTERATIONS | | - STRUCTURES IN WHICH THE CONCRETE | | DESIGN IS BASED ON COMPRESSIVE | | STRENGTH (F'C) IN EXCESS OF 3000 PSI | | - PILE DRIVING | | - BUILDINGS OVER 20,000 SQFT IN AREA | | - BUILDINGS OVER 2 STORIES IN HEIGHT | | - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS | | OF CONSTRUCTION | | | | ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION | | SERVICES MANAGER - TEL: | | 561 805 6711), A MEETING INVOLVING THE OWNER, RESIDENT | | INSPECTOR, JOB INSPECTOR, CONTRACTOR AND ENGINEER. THIS | | MUST BE DONE PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL | | SETS OF ALL DOCUMENTS ARE REQUIRED FOR PERMITTING. | | | | 7.)THERE ARE TWO FULL SETS OF CIVILS WITH DIFFERENT | | DATES.MANY SHEETS APPEAR UNNECESSARY AS THEY ARE FOR | | OTHER BUILDINGS.THERE IS ALREADY A SITEWORK PERMIT | | PENDING.PLEASE COORDINATE WITH ENGINEERING; ANY CIVIL | | SHEETS REQUIRED IN THIS PACKAGE TO SHOW CODE COMPLIANCE | | IS TO MATCH OTHER APPROVED DRAWINGS.ALSO NOTE THAT | | THERE ARE DETAILS FROM THE CITY OF RIVIERA BEACH. | | | | 8.)RADON FEES DUE, FS553.721.SEE ATTACHED. | | | | 9.)A SEPARATE PERMIT WILL BE REQUIRED FOR THE SIGN | | SHOWN ON A-0.1.SEPARATE PLANS AND PERMIT APPLICATION | | WILL BE REQUIRED.NOTE THAT WIND DESIGN CRITERIA | | FBC1603.1.4 WILL BE REQUIRED.DESIGN CRITERIA SHOWN | | DOES NOT PROVIDE ALL REQUIRED INFORMATION. | | | | 10.)THE ACCESSIBLE ROUTE FROM THE PUBLIC WAY IS SHOWN | | ON A-0.1, SHOW SLOPE AND WIDTH FBC11-4.1.2(1). | | | | 11.)S2 DECLARED, SEE FBC302; IT APPEARS THAT THIS IS | | A MIXED USE DUE TO THE 5000 SF OF BUSINESS AREA, | | FBC302.3. | | | | 12.)S2 DECLARED, SEE FBC311.3, DEFINITION IS FOR | | NON-COMBUSTIBLE STORAGE.PROVIDE INFORMATION IN | | REGARDS TO WHAT WILL BE STORED AND WHAT ACTIVITY WILL | | TAKE PLACE IN THIS BUILDING.NOTE THAT PACKAGING MUST | | BE ADDRESSED AS WELL AS THE ITEMS STORED. | | | | 13.)THE FEDEX FREIGHT SITE PLAN (CIVIL) SHOWS A 10FT | | CANOPY.SEE FBC502, DEFINITION OF AREA, BUILDING. | | PLEASE CLARIFY WHAT THIS IS, AND SHOULD THIS BE | | INCLUDED IN BUILDING AREA? | | | | 14.)EXTRA FP1 SHEETS WERE SUBMITTED; NOT CLEAR AS TO | | WHY.PLEASE PROVIDE ONLY THREE COMPLETE ORIGINAL SETS | | FOR PERMITTING, COLLATED. | | | | 15.)ELECTRIC SHEETS SHOW EXIT LIGHTS LEADING TO THE | | WAREHOUSE AREA, NONE AT DOORS TO THE OUTSIDE.SEE | | FBC1006.3. | | | | 16.)PROVIDE A LIFE SAFETY PLAN, FBC*106.3.5.1.1(6) | | AND (7).INCLUDE THE FOLLOWING: | | OCCUPANT LOAD FOR EACH AREA, FBC302. | | EGRESS CAPACITIES, FBC1005. | | EXIT LIGHTS, FBC1006.3. | | EXITING INFORMATION, FBC10. | | ANY OTHER INFORMATION REQUIRED TO DETERMINE CODE | | COMPLIANCE | | | | 17.)FBC11-4.1.3(9), ACCESSIBLE MEANS OF EGRESS SHALL | | BE PROVIDED IN THE SAME NUMBER AS REQUIRED FOR EXITS BY | | LOCAL BUILDING/LIFE SAFETY REGULATIONS. A RAMP IS SHOWN | | AT THE BUILDING ENTRANCE, NO OTHER ACCESSIBLE EXITS | | SHOWN. | | | | 18.)THIS BUILDING REQUIRES MORE THAN ONE EXIT, SEE | | FBC1018.2. | | | | 19.)A1.0 SHOWS A CHECK WRITING STAND, REFERS TO DTL | | 4/A2.01.I COULD NOT LOCATE THAT SHEET.PROVIDE A | | DETAIL, OR CHANGE REFERENCE, AND SHOW ACCESSIBILITY | | FBC11-7.2. | | | | 20.)BREAK ROOM IS SHOWN AS POD AREA, WHAT DOES THIS | | MEAN? | | | | 21.)A1.0 SHOWS AN AREA OF RESCUE.DO YOU MEAN AREA | | OF RESCUE ASSISTANCE?IT IS ACCEPTABLE TO EXCEED CODE, | | BUT NOTE THAT THIS IS NOT REQUIRED FBC11-4.1.3(9) | | EXCEPTION.ALSO THIS IS FOR EXITS FROM OCCUPIABLE | | LEVELS ABOVE OR BELOW THE LEVEL OF THE MEANS OF | | ACCESSIBLE EXIT DISCHARGE.THIS IS THE LEVEL OF | | ACCESSIBLE EXIT DISCHARGE, SO AN ACCESSIBLE EXIT IS | | REQUIRED. | | | | 22.)FBC11-4.1.3(8)(A)(II), ACCESSIBLE ENTRANCES | | REQUIRED AT LEAST EQUIVALENT TO THE NUMBER OF | | ACCESSIBLE EXITS. | | | | 23.)EXIT OR EXIT ACCESS DOORWAY ARRANGEMENT SHALL | | COMPLY WITH FBC1014.2 OR FBC1014.2.2., SHOW DISTANCE | | APART, SEE EXCEPTION 2. | | | | 24.)S2.1, CONCRETE NOTE 1, REFERS TO ACI318-95, | | PLEASE USE CURRENT STANDARD.CHECK ALL REFERENCES. | | | | 25.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC. | | | | 26.)IMPACT PROTECTION REQUIRED.NONIMPACT STOREFRONT | | PRODUCT APPROVALS WERE SUBMITTED.SEE ATTACHED POLICY, | | ITEM 13, IN REGARDS TO IMPACT PROTECTION ON COMMERCIAL | | BUILDINGS.USE IF REMOVABLE SHUTTERS ON COMMERCIAL | | BUILDINGS MUST BE APPROVED BY THE BUILDING OFFICIAL. | | | | | | 27.)IF YOU ARE USING HURRICANE SHUTTERS, SEE ATTACHED | | SCHEDULE FOR INSTALLATION.PROVIDE PRODUCT APPROVALS | | AND ALL REQUIRED INFORMATION TO DETERMINE CODE | | COMPLIANCE. | | | | 28.)SQUARE FOOT AREAS ON THE ENERGY CALCS DO NOT | | MATCH THE PLAN. | | | | 29.)THE ENGINEER'S TITLE BLOCK IS TO COMPLY WITH | | FAC61G15-23.002, VP BUILDINGS. | | | | 30.)INCLUDE THE CORRECT JURISDICTION ON THE ENERGY | | CALCS, 604700 FBC13. | | | | 31.)THE ENGINEER'S SIGNATURE IS A TITLE BLOCK, | | ORIGINAL WET SIGNATURE REQUIRED. | | | | 32.)PROVIDE ROOF DRAINAGE CALCULATIONS FBC1503.4. | | PROVIDE DETAILS, SHOW OVERFLOW. | | | | | | TO EXPEDITE PLAN REVIEW, INCLUDE A RESPONSE LETTER | | INDICATING HOW EACH ITEM WAS ADDRESSED WHEN | | RESUBMITTING. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
8 |
Status |
P |
Date |
2007-11-01 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-11-01 |
Time |
08:15 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-11-01 |
Time |
08:15 |
Sent To |
PC |
|
Notes |
2007-11-01 08:17:09 | *** PROVISO **** | | | | | | 1) NOTE: PLEASE SUBMIT REVISED ENERGY CALCULATIONS | | BEFORE FINAL AS LIGHTING FIXTURES HAVE CHANGED. FBC | | CHAPTER 13 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
7 |
Status |
P |
Date |
2007-09-15 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-09-15 |
Time |
09:38 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-09-15 |
Time |
09:28 |
Sent To |
PC |
|
Notes |
2007-09-15 09:39:34 | REV 4A ND 5 FOR 2.1, 2.2 2.3 ONLY. | | NOTES FROM PREVIOUS REVIEW STILL APPLY |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
6 |
Status |
F |
Date |
2007-09-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-09-13 |
Time |
13:40 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-09-13 |
Time |
13:15 |
Sent To |
|
|
Notes |
2007-09-13 13:41:09 | | | ** DENIED ** | | | | 1) NOTE: PLEASE SEE THE NEW SEPARATE ELECTRICAL SERVICE | | AND METER LOCATION WOULD BE UNDER A SEPARATE PERMIT FOR | | THE SERVICE. THIS IS NOT ACTUALLY COMING FROM THE | | BUILDING ELECTRICAL SERVICE OR ANY PART OF THE | | BUILDING. | | PLEASE SEE THIS LOCATION WILL ALSO REQUIRE AN ADDRESS | | EXTENSION TO PCN FOR NEW METER/SERVICE LOCATION. PLEASE | | BE SURE TO GET WITH THE FPL REPRESENTATIVE AND THE CITY | | ADDRESSING REVIEWER LILI LACRAMIOARA @ 561-822-1239. | | | | 2) NOTE: PLEASE CLARIFY RISER AS THIS SHOWS A *GROUND* | | ON THE LINE SIDE OF THE FIRST MEANS OF DISCONNECT. IS | | THIS THE NEUTRAL/GROUNDED CONDUCTOR? | | NO *EQUIPMENT GROUNDING CONDUCTORS* ARE ALLOWED ON THE | | LINE SIDE OF SERVICE MAINS. | | 250.6, 250.24 | | | | 3) NOTE: TWO GROUND RODS MINIMUM WILL BE REQUIRED PER | | 250.50 AND 250.56 | | | | 4) NOTE: PLEASE PROVIDE INFORMATION FOR PUMP SIZE AND | | OVER CURRENT PROTECTION INFORMATION. | | REVIEW OF SOME ITEMS FOR CONDUCTOR SIZES, SERVICE ETC | | CAN NOT BE REVIEWED AT THIS TIME. | | | | ** PLEASE KNOW THE ABOVE ELECTRICAL WILL NEED TO BE | | SUBMITTED UNDER AN ELECTRICAL PERMIT FOR THE NEW | | SEPARATE SERVICE. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. | | | | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2007-05-01 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-05-01 |
Time |
08:44 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-05-01 |
Time |
08:44 |
Sent To |
|
|
Notes |
2007-05-01 08:45:11 | REVISED SHEET E2.1 TO MEET BLDG CODE REQUIRED EXIT. | | THE REDLINED NOTES ON PLANS AS OF 3/20/07 REVIEW IS | | STILL NOTED. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2007-03-20 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-03-20 |
Time |
15:50 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-03-20 |
Time |
15:44 |
Sent To |
|
|
Notes |
2007-03-20 15:52:17 | ***REDLINED 8.1 AND 8.2 FOR FUEL WHICH IS UNDER A | | SEPARATE PERMIT |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2007-03-18 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-03-18 |
Time |
16:21 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-03-18 |
Time |
14:55 |
Sent To |
|
|
Notes |
2007-03-18 16:24:30 | ** UNSAT ** | | | | 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS | | SUBMITTED DOES NOT CONTAIN ANY INTERIOR LIGHTING ON THE | | COMPLIANCE SUMMARY SHEET #2. THIS LIGHTING IS IN THE | | INPUT DATA REPORT WHICH IS ATTACHED TO ENERGY | | CALCULATIONS. | | PLEASE BE SURE TO HAVE THE PRINTED NAME AND LICENSE | | NUMBER OF THE DESIGNER OF RECORD ON SHEET 3. | | PLEASE SEE SHEET 7 WHICH IS NOT FILLED OUT. | | REVIEW FOR CODE COMPLIANCE AND COORDIANTION WITH PLANS | | TO BE DONE UPON FINAL DOCUMENTS. | | ** THIS WILL NOT BE THE ONLY OUTSTANDING COMMENT FROM | | TRADES. | | PLEASE KNOW *IF* WAS TO REMAIN THE ONLY COMMENT FOR | | ISSUANCE, THEN CALL TO GO OVER. | | | | 2) PLEASE SEE BUILDING REVIEW COMMENTS. ** ONLY NOTED, | | SEE THE *PN* SHEETS SUBMITTED CONTAIN A RAISED SEAL OF | | OVER A PHOTO-COPIED SIGNATURE FROM THE ENGINEER OF | | RECORD WHICH IS REQUIRED TO BE ORIGINAL ALONG WITH THE | | DATE WHEN SIGNED. FAC 61G15-23.002, FS 471.025 | | | | ** REDLINED SHEET 8.1 AND 8.2, FUEL SYSTEM IS UNDER A | | SEPARATE PERMIT. PLANS ARE FOR MAIN POWER AND REFERENCE | | ONLY. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2007-01-09 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-01-09 |
Time |
13:20 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-01-07 |
Time |
19:53 |
Sent To |
|
|
Notes |
2007-01-09 13:22:47 | ** UNSAT ** | | | | 2ND REVIEW | | FED EX FREIGHT | | | | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL | | ARE IN NEED OF PROVIDING MORE INFORMATION AND/OR | | ADDRESSING. | | | | ** PLEASE SEE SOME NEW COMMENTS BASED ON SUBMITTALS AND | | PLANS SUBMITTED. | | | | 1) NOTE: ** THIS IS NOT A COMMENT FOR KAMM CONSULTING, | | HOWEVER IS BEING NOTED BY THIS REVIEWER. | | PLEASE SEE THE VP SHEETS AND THE PN SHEETS CONTAIN | | RAISED SEALS OVER PHOTO-COPIED SIGNATURES FOR THE | | ENGINEERS ON EACH OF THESE WHICH IS NOT PERMITTED UNDER | | FLORIDA STATUTES 471.025 AND FLORIDA ADMINISTRATIVE | | CODE 61G15-23.002 | | PLEASE SEE BUILDING REVIEW COMMENTS FOR THIS ALSO. | | **THIS WAS COMMENT #2 FROM THE PREVIOUS REVIEW. | | PLEASE KNOW ONE SET OF PLANS MAY BE RETAINED BY THIS | | OFFICE. | | | | 2) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 | | WHICH SPEAKS OF MAXIMUM TIMES PERMITTED ON THE TYPE OF | | DEVICES INSTALLED. | | PLEASE SEE NOTES ON E0.1 AND 2.1 IN SEVERAL PLACES | | INDICATE OCCUPANCY TYPE DEVICES WITH 3HRS AND 4HRS FOR | | MAXIMUM TIMES. PLEASE SEE THE SECTIONS AS NOTED ABOVE | | AS THE MAXIMUM PERMITTED TIMES ON THESE TYPES OF | | DEVICES IS 30MINS FROM THE LAST SENSING OF THE | | OCCUPANT. | | PLEASE ADJUST NOTES AND ALSO PLEASE BE SURE TO ADJUST | | ALL DEVICES TO CONTAIN NOTES FOR THIS. | | **PREVIOUS REVIEW NOTE #3 | | | | 3) NOTE: PLEASE SEE THE PERFORMANCE/ENERGY CALCULATIONS | | SUBMITTED WHICH DO NOT PROVIDE THE INFORMATION NEEDED | | FOR REVIEW. | | PLEASE SEE RESPONSE LETTER SPEAKS OF EXTERIOR LIGHTING | | CONTACTOR AND PHOTO-METRICS PLANS BY OTHERS? | | PLEASE SEE ENERGY CALCULATIONS SUBMITTED INDICATE ALL | | CONTROLS AS MANUAL ON/OFF WHEN PLANS INDICATE | | OTHERWISE? | | PLEASE PROVIDE INFORMATION FOR THE PERFORMANCE OF | | LIGHTING DENSITIES. | | **PREVIOUS REVIEW NOTE #4 | | | | 4) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR | | FEEDER(S) AND BRANCH CIRCUIT(S) PER 13-413.1.ABC.1.1. | | RESPONSE LETTER MENTIONS TO SEE 4.1 AND 5.1, HOWEVER | | 4.1 IS AIC CALCULATIONS, AND 5.1 WAS THE RISER DIAGRAM | | SHEETS WHICH THIS REVIEWER COULD NOT LOCATED ANY | | VOLTAGE DROP CALCULATIONS/ OR WORST CASE INFORMATION. | | **PREVIOUS REVIEW #6 | | | | 5) NOTE: PLEASE SEE INFORMATION ON ACCESS CONTROL | | SYSTEM DOES NOT YET PROVIDE ENOUGH INFORMATION. PLEASE | | SEE NFPA-101 2003 | | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. | | 7.2.1.5.1 DOORS SHALL BE ARRANGED TO BE OPENED READILY | | FROM THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. | | | | 7.2.1.5.2 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE | | OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR | | OPERATION FROM THE EGRESS SIDE. | | 7.2.1.6 SPECIAL LOCKING ARRANGEMENTS. | | PLEASE SEE FIRE REVIEW COMMENTS AS WELL AS THE RESPONSE | | AND NOTE ON PLANS MENTIONS IN THE EVENT OF POWER | | FAILURE UNDER EMERGENCY OR NORMAL POWER THE FIRE ALARM | | AND SECURITY WILL NOT BE AFFECTED. | | PLEASE SEE THIS IS BEING CONSIDERED AN EGRESS CONCERN | | AND NOT THAT OF THE NOTE AS STATED. | | ** PREVIOUS NOTE #9 | | | | 6) NOTE: PLEASE SUBMIT ALL MANUFACTURES SPEC/CUT SHEETS | | FOR THE GENERATOR, ATS, WP ENCLOSURE AND FUEL TANKS. | | PLEASE CORRELATE THESE WITH THE SUBMITTED PLANS. | | SOME OF THESE WERE SUBMITTED, HOWEVER NOT FOR BOTH | | TANKS AND PLEASE SEE SOME OF THESE DO NOT MATCH WITH | | THE SUBMITTED PLANS. | | PLEASE SEE THE RESPONSE LETTER DOES NOT CONTAIN A | | RESPONSE FOR NOTE #11 FROM PREVIOUS REVIEW. | | 90.7, 110.3 NEC | | FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION. | | ** PREVIOUS NOTE #11 | | | | 7) NOTE: PLEASE SEE 225.31-225.39, 702, 110.27 FOR | | DISCONNECTING MEANS REQUIRED FOR FEEDERS FROM THE | | GENERATOR. THE RESPONSE LETTER MENTIONS TO BE BY | | OTHERS; HOWEVER THIS INFORMATION IS REQUIRED AT THIS | | TIME. PLEASE KNOW THIS IS A DISCONNECTING MEANS AND IS | | NOT REQUIRED TO CONTAIN OVER CURRENT PROTECTION. THERE | | ARE SEVERAL WAYS OF DOING THIS, HOWEVER THE USE OF THE | | BREAKER INSIDE THE GEN UNIT WHICH MAY NOT MEET 110.27 | | OR 702. | | PLEASE PROVIDE MORE INFORMATION ON DISCONNECT, THIS MAY | | BE LOCATED OUTSIDE MAIN ELECTRICAL ROOM ON BUILDING OR | | IN MAIN ELECTRICAL ROOM. SIGNAGE WILL BE REQUIRED. | | 702.8, 230.2E | | ** PREVIOUS REVIEW NOTE #19 | | | | 8) NOTE: PLEASE SEE NOTE #20 FROM THE PREVIOUS REVIEW | | WITH RESPECT TO SLAB DETAIL, HEIGHT MOUNTING ETC FOR | | THE GENERATOR PER NFPA-110 CHAPTER 7. | | PLEASE SEE THE RESPONSE LETTER DOES NOT CONTAIN A | | RESPONSE FOR NOTE #20. | | | | 9) NOTE: PLEASE SHOW MORE INFORMATION FOR NEC 514. | | PLEASE SEE 514.11(A) AND (C). PLEASE SEE COMMENTARY | | WHICH SPEAKS OF THE LOCATION AND SIGNAGE REQUIREMENTS. | | PLANS DO CONTAIN SOME NOTES FOR THESE HOWEVER PLEASE | | PROVIDE MORE DETAILS. PLEASE SEE THAT THE PUSHBUTTON EM | | CUT-OFF DEVICE SHOULD BE LOCATED AWAY FROM ANY HAZARD | | BUT NOT MORE THAN 100FT.PLEASE SEE THE DISTANCE AND | | THE LOCATION AS THIS IS BEING SHOWN BEHIND THE ADJACENT | | BUILDING WHICH IS PER SCALE PERHAPS LESS THAN 20FT FROM | | THE TANK GIVES CONCERN. PLEASE SEE FIRE MARSHAL'S | | COMMENTS ALSO. | | ** PREVIOUS REVIEW NOTE #22 | | | | 10) NOTE: PLEASE SEE PROVIDE MORE INFORMATION ON THE | | CLASS AND DIVISION LOCATIONS SURROUNDING THE FUEL | | DISPENSING. PLEASE SEE THE RESPONSE MENTIONED TO SEE | | THE TWO SHEETS, HOWEVER THOSE SHEET 1.1 AND 1.4 ONLY | | INDICATE THE DOTTED LINES FOR THE AREA. | | PLEASE SEE NEC 500, 514 | | FBC ADMIN SECTION 106.1.2 | | ** PREVIOUS REVIEW NOTE #23. | | | | 11) NOTE: PLEASE CLARIFY THE LIGHTING FOR LIGHTS TO THE | | PUBLIC RIGHT OF WAY. PLEASE SEE THE STAIRS LOCATED | | OUTSIDE OF THE EGRESS DOORS WHICH WILL REQUIRE | | EMERGENCY LIGHTING OF SOME SORT. | | PLEASE ALSO SEE RESPONSE MENTIONS FOR SITE | | PHOTO-METRICS TO BE PROVIDED BY OTHERS, HOWEVER PLEASE | | SEE THE SITE LIGHTING IS BEING PERMITTED UNDER THIS | | BASE BUILDING. | | LS 101 7.8, 7.9 | | ** PREVIOUS REVIEW NOTE #26. | | | | 12) NOTE: PLEASE SEE THE MISSING STRUCTURAL BUILDING | | STEEL AND FIRE SPRINKLER LINE ATTACHMENT AS PART OF THE | | GROUNDING ELECTRODE SYSTEM. | | 250.50, 250.104. | | | | ** ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | 2007-01-07 19:53:19 | 2007-01-07 19:53:19 | | IN ELEC FOR REVIEW. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2006-10-24 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-10-24 |
Time |
10:31 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-10-22 |
Time |
19:47 |
Sent To |
|
|
Notes |
2006-10-24 10:36:28 | *** PLEASE SEE NOW THAT AN ADDRESS HAS BEEN CREATED, | | PLEASE PLACE ON TITLE BLOCKS FOR PLANS. | 2006-10-24 10:31:25 | ********* UNSAT ********** | | | | | | 1) NOTE: PLEASE LIST ALL OF THE FOLLOWING CODES | | RELEVANT TO PLANS AND DESIGNS ON THEOR RESPECTIVE | | SHEETS. | | PLEASE SEE THE FOLLOWING ARE REQUIRED AT A MINIMUM: | | 2002NFPA-70, 2002 NFPA-72, 2003 NFPA-101, 2003 NFPA-20, | | 2002 NFPA-110, 2000 NPPA-30A,2004 FBC . | | PLEASE BE AWARE OF ANY OTHER APPLICABLE CODES FROM | | OTHER REVIEWERS WHICH MAY BE REQUIRED. | | | | 2) NOTE: PLEASE SEE "VP" BUILDING SHEETS AND SETS WHICH | | CONTAINEDRAISED SEALS OVER "PHOTO-COPIED" SIGNATURES. | | PLEASE SEE THIS COMMENT IS MADE WETHER OR NOT COMMENT | | IS MADE BY ANY OTHER REVIEWER. | | PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002, | | FLORIDA STATUTES 471.025, PLEASE ALSO SEE MISSING | | REQUIRED TITLE BLOCK INFORMATION. | | | | 3) NOTE: PLEASE SEE FBC 2004 CHAPTER 13. | | 13-415.1.ABC.1.1, .1.2 AND .1.3. PLEASE SEE NO MORE | | THAN 4HRS IS PERMITTED ON OVER-RIDE DEVICES. (SOME | | SHOWN AS 12HRS). PLEASE SEE OTHER AREAS WHERE A TIMED | | OR OCCUPANT TYPE DEVICE IS NOT INDICATED. PLEASE | | CLARIFY THE USE OF THE MOMNETARY CONTACTS, FOR AREAS OF | | INGRESS/EGRESS.THE OCCUPANT MUST BE ABLE TO OVER RIDE | | ANY TIME OF DAY SCHEDULEING DEVICE AND SEE THE LIGHTING | | BEING CONTROLLED. (TIMES OR SENSOR TYPE). PLEASE SEE | | SYSMBOL LEGEND NEEDS TO INDICATE THE MAX AMOUNT OF | | TIMES ON DEVICE WHICH ARE SHOWN ON THIS LEGEND, HOWEVER | | NOT ON PLANS. | | (30MINS MAX OS, 4HRS MAX TIMER TYPE) | | | | 4) NOTE: PLEASE PROVIDE ALL LIGHTING PERFORMANCE | | CALCULATIONS PER 13-415.2, 13-415.2.ABC.1, TBALES | | 415.2.C.1, 415.2.B1, AS SPACE BY SPACE WILL BE REQUIRED | | FOR SOME AREAS. | | PLEASE SEE METHOD "A" AS SUBMITTED DOES NOT SHOW | | THESE. | | | | 5) NOTE: PLEASE SEE NO PLANS, DOCUMENTS ETC MAY CONTAIN | | "WHITE-OUT" OF ANY KIND ON SAID DOCUMENTS WITH | | HANDWRITTEN ITEMS OVER SUCH SHEETS. PLEASE SEE ENERGY | | CALCULATIONS. | | FS471 | | | | 6) NOTE: PLEASE PROVIDE VOLTAGE DROP CALCULATIONS FOR | | WORST CASE FOR EACH FOR FEEDERS AND BRANCH CIRCUITS. | | PLEASE SEE FBC 13-413.1.ABC.1.1 &.1.2. | | | | 7) NOTE: PLEASE SEE SYMBOLSHOWN IN STORAGE/SPRINKLER | | ROOM ON 3.1, AND 2.1 APPEARS TO BE THAT OF A | | TRANSFORMER, YET THIS IS UNCLEAR AT THIS TIME.?? | | FBC ADMIN SECT 106.1.2 | | | | 8) NOTE: PLEASE SEE IT WILL NOT BE PERMITTED THAT THE | | ONLY ACCESS TO THE MAIN ELECTRICAL ROOM IS THROUGH A | | STORAGE ROOM AND AREA. THESE TYPES OF ROOMS DO NOT | | TYPICALLY PROVIDE THE READY ACCESS TO THE ELECTRICAL | | EQUIPMENT IN THE QUICK TIME WHICH MAY BE NEED IN THE | | CASE OF AN EMERGENCY FOR FIRE DEPARTMENT OR ANY OTHER | | PERSONNEL TRYING TO SHUT OFF THE POWER. PLEASE SEE THAT | | RELOCATION OR ACCESS SEPARATELY FOR ROOM WILL BE | | REQUIRED AT THIS TIME. | | 230.70,110.26, 408.7,90.4 | | | | 9) NOTE: PLEASE SEE POSSIBLE FIRE REVIEW COMMENTS WIHT | | RESPECT TO ACCESS CONTROL SYSTEM WHICH WILL REQUIRE | | ADDITIONAL INFORMATION. PLEASE INDICATE THAT IN THE | | EVENT OF AN EMERGENCY OR FAILURE OF NORMAL POWER EGRESS | | FROM THE BUILDING WILL NOT BE AFFECTED. PLEASE SEE LS | | 101. SEE FIRE REVIEW COMMENTS. | | | | 10) NOTE: PLEASE SEE FBC 11-4.28, 11-4.28.3. PLEASE | | INDICATE THE MIN LEVELS FOR DB RATINGS OF HORNS/ OR | | COMBO DEVICES.PLEASE SEE SCHEDULE INDICATES A | | POSSIBLE OF 15CD MIN, HOWEVER AS INDICATE ON PLANS AND | | ADA REQUIREMENTS, A MIN OF 75 CD IS REQUIRED. PLEASE | | PROVIDE AND COMPLETE THE LAYOUT OF THE FA DEVICES ON | | PLANS. THE 2ND AND THIRD SECTIONS DO NOT APPEAR ON FA | | SHEETS. | | 11-4.28.3(4). | | | | 11) NOTE: PLEASE SUBMIT COMPLETE MANUFACTURE SPECS/CUT | | SHEETS FOR ALL OF THE FOLLOWING. GENERATOR, FUEL | | TANK(REVIEW BY OTHERS), ATS, FIRE PUMP AND FIRE PUMP | | CONTROLLER. PLEASE SEE AS NONE OF THESE ARE SUBMITTED | | AT THIS TIME NOT REVIEW FOR SOME CODE REQUIRED ITMES | | CAN EB DONE. | | 110.3, 90.7. | | | | 12) NOTE: PLEASE INDICATE ALL OCP DEVICE SIZES AT THE | | GEN. PLEASE SEE SHEET7.3 INDICATES A BREAKER FOR FIRE | | PUMP AT GEN AS G-1 , YET THE RISER DOES NOT INDICATE | | THIS BREAKER AT ALL ON GEN. | | PLEASE SEE 445.13 AS THE SIZING OF THE FEEDERS CAN NOT | | BE VERIFIED AT THIS TIME. | | | | 13) NOTE: PLEASE SEE THE GEN SEEMS IT WILL FEED A FIRE | | PUMP, THE STAND-BY FOR THIS BUILDING AND THE POSSIBLE | | STAND-BY FOR AN ADDITIONAL LOCATION, HOWEVER A COMPLETE | | LOAD SUMMARY AND LOAD SHEDDDING DETAILS HAVE NOT BEEN | | PROVIDED AT THIS TIME. PLEASE SEE THE LOAD ON THE MD IS | | THE ONLY LOAD SHOWN AT THIS TIME. PLEASE PROVIDE A LOAD | | SUMMARY FOR THE GEN AS THIS IS A LEGALLY REQUIRED | | STAND-BY UNIT. | | 701.6,6.3 OF NFPA-110, NFPA-20 9.6.1.1 ETC.,THESE | | ITEMS CAN NOT BE REVIEWED AT THIS TIME. | | | | 14) NOTE: PLEASE PROVIDE ALL MINIMUM FUEL CONSUMPTION | | FOR THEGENERATOR AS THIS FEED THE FIRE PUMP AND | | SYSTEM AS SHOWN NEEDS TO MEET THE MINIMUM OF HRS FOR | | 100% LOAD INCLUDING ALL OTHER LOADS 9.6.2.2. | | CAN NOT REVIEW AT THIS TIME. | | | | 15) NOTE: PLEASE SUBMIT ALL THE INFORMATION FOR FIRE | | PUMP SERVICE, LOCATION, LOCKED ROTOR OCP SIZE ETC. | | PLEASE SEE PLANS AND RISER DO NOT SEEM TO INDICATE ANY | | INFORMATION FOR THE FIRE PUMP. PLEASE SEE FP SHEETS | | ALSO DO NOT INDICATE ANY FP?PLEASE SEE 2003 NFPA-20 | | CHAPTER 9 FOR DISCONNECTING MEANS, ISOLATION SWITCH | | REQUIREDETC ETC. | | | | 16) NOTE: PLEASE PROVIDE ALL AIC RATINGS FOR ALL | | SERVICE EQUIPMENT. PLEASE PROVIDE A DETAIL FOR | | SELECTIVE COORDINATION. 110.9/240.12. | | PLEASE SEE NEC 701.6, 700.5 AND NFPA-110, 6.5.2 ETC FOR | | ATS AND ALL OTHER EQUIPMENT ASSOCIATED WITH ELECTRICAL | | SYSTEM. | | | | 17) NOTE: PLEASE VERFIY WITH MANUFACTURE THE GENERATOR | | GROUNDING SCENARIO, AS IT IS KNOWN TO THIS OFFICE SOME | | OF THESE DEPENDING ON THE MANUFACTURE ARE SHIPPED AND | | WIRED FOR SEPARATELY DERIVED SYSTEM, PLEASE MAKE ANY | | ADJUSTMENTS AS NEED. | | 90.7., 250.20, 250.50, ETC | | | | 18) NOTE: PLEASE CORRELATE CIRCUITING FOR PANEL FD, | | PANEL "LB" DOES NOT SHOW FEEDING OF THIS PANEL . | | PLEASE SEE CIRCUITS FOR OTHER ITEMS SHOWN ON SCHEDULE. | | 240.4,310.16,408.4, | | FBC 106.3.5.1.2. ADMIN SECT. | | | | 19) NOTE: PLEASE SEE MISSIGN A DISONNECTING MEANS FOR | | FEEDERS FROM GENERATOR INTO BLDG LOCATED IN CLOSE | | PROXIMITY OF OTHER MAINS OR MEETINGEXCEPTIONS UNDER | | CODE, HOWEVER SYSTEM IS NOT KNOWN AT THIS TIME | | CLASSIFICATION OF BACK UP POWER IS NOT CLEAR. PLEASE | | ALSO KNOW AS INFORMATION FOR THE GEN AND W/P ENCLOSURE | | AND ACCESS IS ALSO NOT KNOW AT THIS TIME. | | 225.31-225.39 | | 700, 701, 702 ? | | | | 20) NOTE: PLEASE SEE NOT INFORMATION FOR LOCATION, | | ELEVATION, MOUNTING , SLAB DETAIL ETC COULD BE LOCATED | | ON PLANS. PLEASE SEE NFPA-110 2002 CHAPTER 7, AS MANY | | OF THESE SCETIONS APPLY, HOWEVER AS NOTHING COULD BE | | LOCATED FOR THIS, A REVIEW FOR COMPLIANCE COULD NOT BE | | DONE AT THIS TIME. | | | | 21) NOTE: PLEASE SEE MD AS THIS SHOWS A NEUTRAL | | CONDUCTOR BEING SHOWN FEEDING THE TRANSFORMER WHICH IS | | A SD SYSTEM. PLEASE SEE 250.30, 250.20 ETC | | | | 22) NOTE: PLEASE SEE ANY COMMENTS WITH RESPECT THE EM | | SHUT OFF OF POWER FOR THEFD PANEL. PLEASE SEE 514 | | | | 23) NOTE: PLEASE PROVIDE A LAYOUT AND SHOW ALL | | HAZARDOUS LOCATIONSON PLANS. | | 500. CLASS AND DIVISIONS. | | | | 24) NOTE: PLEASE SEE MECH REVIEW NOTES FOR SEPARATE | | FUEL PERMIT REQUIRED. | | | | 25: ) NOTE: PLEASE SEE THE GEN SPECIFICATIONS ON 7.3 DO | | NOT LIST THE OTHER OCP/ BREAKERS ON GEN AS SHOWN ON | | RISER. | | | | 26) ) NOTE: PLEASE PROVIDE EM BATTERY BACK UP | | FIXTURE(S) OF SOME TYPE LEADING TO THE PUBLIC RIGHT OF | | WAY. PLEASE PROVIDE PHOTO-METRICS FOR EGRESS PATHS | | UNDER NORMAL AND UNDER EMERGENCY POWER. PLEASSE SEE | | NFPA-101 7.8.1.3, 7.9.2.2, PLEASE SEE STAIR AREAS | | LEADING TO THE OUTSIDE. | | | | 27) NOTE: PLEASE SEE SOME SHEETS IN SETS ARE PLACED IN | | SETS BACKWARDS. PLEASE SEE THE FOLLOWING NOTE. | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE KNOW AS THERE IS INFORMATION NOT YET | | SUBMITTED FOR REVIEW , PLEASE KNOW THERE MAY BE FURTHER | | COMMENTS UPON NEXT REVIEW. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | | | | | 2006-10-22 19:47:55 | ONE SET IN ELEC FOR REVIEW |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
N |
Date |
2007-10-16 |
|
|
Cont ID |
|
Sent By |
rchokshi |
Date |
2007-10-16 |
Time |
11:46 |
Rev Time |
0.00 |
Received By |
rchokshi |
Date |
2007-10-16 |
Time |
11:46 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
P |
Date |
2006-11-13 |
|
|
Cont ID |
|
Sent By |
rchokshi |
Date |
2006-11-13 |
Time |
13:23 |
Rev Time |
0.00 |
Received By |
rchokshi |
Date |
2006-11-13 |
Time |
13:17 |
Sent To |
|
|
Notes |
2006-11-13 13:22:54 | ACCORDING TO A LETTER (E-MAIL) FROM STEVEN M. PAWLYK OF | | BOWYER-SINGLETON DATED NOV 13, 06,THIS PRMIT IS | | COVERED UNDER PERMIT#06071716.PERMIT # 06071716 IS | | REVIEWED AND PASSED SOMETIME AGO.THEREFORE, THIS IS | | PASSED. | | | | RASIK CHOKSHI805-6723 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2007-05-01 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-05-01 |
Time |
15:46 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-05-01 |
Time |
14:25 |
Sent To |
|
|
Notes |
2007-05-01 15:46:36 | *****APPROVED***** | | | | | | PLAN SHEETS A1.2, A4.0, E2.1, E2.2, E2.3, FA0.1, FA2.1, | | FA2.2, FA2.3, FP-1, FP-2, AND FP-3 WERE STAMPED, | | INITIALED, AND DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2007-04-19 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-04-19 |
Time |
14:35 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-05-01 |
Time |
14:25 |
Sent To |
|
|
Notes |
2007-04-19 13:57:47 | *****PROVISO***** | | | | | | THE COMMENTS FROM PREVIOUS FIRE PLAN REVIEWS HAVE BEEN | | ADDRESSED, HOWEVER, THE PLANS WILL BE FIRE STAMPED WHEN | | OTHER PLAN REVIEW COMMENTS HAVE BEEN SATISFIED.ONLY | | ONE SET OF FIRE PROTECTION SHEETS WERE REVIEWED DUE TO | | FP SHEETS NOT BEING ATTACHED TO THE REST OF THE | | SUBMITTED PLAN SHEETS.PLEASE | | VERIFY/COORDINATE/ARRANGE THAT ALL PLAN SHEETS BE | | SUBMITTED AS A SET. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2007-01-29 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-02-01 |
Time |
14:15 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-01-29 |
Time |
14:15 |
Sent To |
|
|
Notes |
2007-01-29 14:19:10 | *****DENIED***** | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, | | INCLUDE A RESPONSE SHEET INDICATING HOW/WHERE EACH ITEM | | FROM 10/31/2006 WAS ADDRESSED (ON/IN THE PLANS). | | | | | | | | 05.LANDSCAPING SHALL NOT OBSTRUCT OR INTERFERE WITH | | FIRE PROTECTION EQUIPMENT.PROPER CLEARANCES SHALL BE | | MAINTAINED AT ALL TIMES.PLEASE NOTE IN LANDSCAPING | | PLANS | | | | 07.FIRE DEPARTMENT CONNECTIONS (FDC'S) SHALL BE | | POSITIONED SO THAT THEY CANNOT BE BLOCKED BY STORAGE, | | VESSELS, EQUIPMENT, ETC.PLEASE NOTE ON FIRE SPRINKLER | | DRAWINGS | | | | 08.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE | | DEPARTMENT CONNECTIONS.NOTE ON FIRE SPRINKLER | | DRAWINGS | | | | 09.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK | | IS REQUIRED FOR DOUBLECHECK DETECTOR ASSEMBLY.NOTE | | ON FIRE SPRINKLER DRAWINGS | | | | 19.LIFE SAFETY PLAN SHALL INCLUDE ALL COMMON PATHS OF | | TRAVEL TO EXITS.INCLUDE TRAVEL DISTANCE TO EXITS AS | | PER 2003 NFPA 101: 7.6.1 | | | | 22.FIRE SPRINKLER SYSTEM IS TO BE MONITORED.NOTE ON | | FIRE SPRINKLER DRAWINGS | | | | 23.FIRE ALARM SHALL BE UL CERTIFIED FOR CENTRAL | | STATION SERVICE.NOTE IN FIRE ALARM DRAWING | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2006-10-31 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-10-31 |
Time |
10:55 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-10-31 |
Time |
10:55 |
Sent To |
|
|
Notes |
2006-10-31 12:10:40 | *****DENIED***** | | | | | | | | 01.NFPA 101 - 2003 EDITION AND FLORIDA FIRE | | PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED. | | | | 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION SHALL COMPLY WITH NFPA241. | | | | 03.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL | | NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID | | PROPERTY OR VICINITY THEREOF. | | | | 04.ALL PAVEMENT ROAD SYSTEMS SHALL BE CAPABLE OF | | SUPPORTING 32 TONS FOR FIRE EQUIPMENT. | | | | 05.LANDSCAPING SHALL NOT OBSTRUCT OR INTERFERE WITH | | FIRE PROTECTION EQUIPMENT.PROPER CLEARANCES SHALL BE | | MAINTAINED AT ALL TIMES. | | | | 06.SHOW/DISPLAY THE NUMERICAL ADDRESS OF THE BUILDING | | ON THE PROPER ELEVATION.AS PER WEST PALM BEACH CODE, | | THOSE NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND 1" | | IN WIDTH.IF A MONUMENT SIGN OR MARKEE IS REQUIRED, A | | NUMERICAL ADDRESS WILL ALSO BE POSTED.IF THERE ARE | | GOING TO BE SEVERAL ADDRESSED BUILDINGS WITHIN THE FED | | EX COMPLEX, A RANGE OF ADDRESSES FROM THE LOWEST TO THE | | HIGHEST WILL BE REQUIRED ON THE MONUMENT SIGN OR | | MARKEE. | | | | 07.FIRE DEPARTMENT CONNECTIONS (FDC'S) SHALL BE | | POSITIONED SO THAT THEY CANNOT BE BLOCKED BY STORAGE, | | VESSELS, EQUIPMENT, ETC. | | | | 08.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE | | DEPARTMENT CONNECTIONS. | | | | 09.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK | | IS REQUIRED FOR DOUBLECHECK DETECTOR ASSEMBLY. | | | | 10.KNOX BOX FOR THE BUILDING WILL BE REQUIRED. PLEASE | | CONTACT THE FIRE PREVENTION BUREAU AT (561) 804-4724 | | FOR APPLICATIONS. | | | | 11.WILL THERE BE SECURITY GATES TO THE PREMISES AND | | IF SO, HOW WILL THE MEANS OF EGRESS BE IMPACTED? | | | | 12.PROVIDE MORECANOPY DETAILS IN REGARDS TO SMOKE | | FLAME RETARDANT CAPABILITIES. | | | | 13.PROVIDE MORE DETAILS FOR GENERATOR INCLUDING | | MANUFACTURER SPEC SHEETS. | | | | 14.PLEASE INDICATE WHERE AND IN WHAT QUANTITY WILL | | FUEL OR ANY OTHER COMBUSTIBLE/FLAMMABLE LIQUIDS BE | | STORED AT THE NEW FACILITY. | | | | 15.PLEASE PROVIDE PRESCIPTIVE STRENGHT FOR ALL | | HANDRAILS / GUARDRAILS. | | | | 16.ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA | | 80. | | | | 17.PLEASE ILLUSTRATE ALL EXIT DISCHARGE LOCATIONS | | FROM THE BUILDING.EXIT DISCHARGE LOCATIONS SHALL | | COMPLY WITH APPLICABLE FIRE CODE REQUIREMENTS. | | | | 18.INTERIOR FINISH FOR WALLS AND CEILING IN EXITS AND | | EXIT ACCESS CORRIDORS SHALL BE CLASS "A" OR CLASS "B". | | | | 19.LIFE SAFETY PLAN SHALL INCLUDE ALL COMMON PATHS OF | | TRAVEL TO EXITS. | | | | 20.INDICATE LOCATION OF 2A-10BC RATED FIRE | | EXTINGUISHERS AT DISTANCES TO SATISFY THE 75' TRAVEL | | DISTANCE REQUIREMENT. | | | | 21.SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED | | FOR FIRE SPRINKLER AND FIRE ALARM SYSTEMS. | | | | 22.FIRE SPRINKLER SYSTEM IS TO BE MONITORED. | | | | 23.WILL THE STRUCTURE HAVE A FIRE ALARM SYSTEM?IF | | SO, FIRE ALARM SHALL BE UL CERTIFIED FOR CENTRAL | | STATION SERVICE. | | | | 24.FIRE ALARM SYSTEM IS TO BE CLASS A OR FULLY | | ADDRESSABLE. | | | | 25.DELAYED-EGRESS LOCKS AND/ORACCESS-CONTROLLED | | EGRESS DOORS SHALL COMPLY WITH NFPA 101, CH. 7.2.1.6, | | SPECIAL LOCKING ARRANGEMENTS. | | | | 26.PLEASE PROVIDE SPEC SHEETS FOR FIRE PUMP AND | | ASSOCIATED EQUIPMENT. | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
13 |
Status |
N |
Date |
2007-12-10 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-12-10 |
Time |
14:22 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-12-10 |
Time |
14:21 |
Sent To |
B |
|
Notes |
2007-12-10 14:22:51 | TO "SHILL" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
12 |
Status |
N |
Date |
2007-12-03 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-12-03 |
Time |
15:46 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-12-03 |
Time |
15:46 |
Sent To |
P |
|
Notes |
2007-12-03 15:46:47 | TO "P" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
11 |
Status |
N |
Date |
2007-10-29 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-10-29 |
Time |
16:49 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-10-29 |
Time |
16:49 |
Sent To |
E |
|
Notes |
2007-10-29 16:49:34 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
10 |
Status |
N |
Date |
2007-10-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-10-24 |
Time |
14:16 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-10-24 |
Time |
14:16 |
Sent To |
P |
|
Notes |
2007-10-24 14:16:19 | TO "P" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
9 |
Status |
N |
Date |
2007-09-28 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-09-28 |
Time |
11:12 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-09-28 |
Time |
11:12 |
Sent To |
B |
|
Notes |
2007-09-28 11:12:52 | TO "SHILL" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
8 |
Status |
N |
Date |
2007-09-20 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-09-20 |
Time |
16:59 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-09-20 |
Time |
16:59 |
Sent To |
B |
|
Notes |
2007-10-12 16:43:17 | 10/12/07--TO "Z" BOX/REV | 2007-09-20 17:00:17 | TO "SHILL" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
7 |
Status |
N |
Date |
2007-09-20 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-09-20 |
Time |
15:46 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-09-20 |
Time |
15:46 |
Sent To |
|
|
Notes |
2007-10-10 12:06:32 | TO "COMM" BD#12 | 2007-09-20 15:46:34 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2007-09-18 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-09-18 |
Time |
11:48 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-09-18 |
Time |
11:48 |
Sent To |
|
|
Notes |
2007-09-18 11:48:32 | WAITING FOR "COMM" BD-REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2007-09-13 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-09-13 |
Time |
15:58 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-09-13 |
Time |
15:58 |
Sent To |
|
|
Notes |
2007-09-13 15:59:08 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2007-08-21 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-21 |
Time |
11:32 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-21 |
Time |
11:32 |
Sent To |
|
|
Notes |
2007-09-13 11:33:13 | TO "COMM" BD#59 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-03-09 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-03-09 |
Time |
09:57 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-03-09 |
Time |
15:20 |
Sent To |
|
|
Notes |
2007-03-09 15:22:32 | TO "COMM" BD#44/PLANS ON RACK-4 ROLLS/PAPERWORK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-01-09 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-12-05 |
Time |
13:23 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-12-05 |
Time |
15:10 |
Sent To |
|
|
Notes |
2007-01-05 10:54:33 | TO "COMM" BD#15/PLANS ON RACK | 2006-12-05 15:10:44 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-11-15 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-11-13 |
Time |
09:02 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-09-20 |
Time |
13:49 |
Sent To |
|
|
Notes |
2006-10-17 13:25:22 | TO "COMM" BD#38 | 2006-10-13 13:50:57 | WAITING FOR "COMM" BD |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2007-03-30 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-03-30 |
Time |
10:59 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-03-30 |
Time |
10:43 |
Sent To |
|
|
Notes |
2007-03-30 10:59:48 | NEW SHEETS WERE ADDED, REVIEWED. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2007-02-06 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-02-06 |
Time |
09:32 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-02-05 |
Time |
15:24 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2006-10-24 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2006-10-24 |
Time |
19:40 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2006-10-24 |
Time |
16:44 |
Sent To |
|
|
Notes |
2006-10-24 19:55:53 | ----------------DENIED---------------- | | 1. M0.1 OUTSIDE AIR CALCULATIONS SCHEDULE: NOTE STATES | | "ALL RTU'S ARE EXISTING..." HOW ARE UNITS EXISTING ON | | NEW BUILDING? PLEASE CORRECT OR CLARIFY. | | | | 2. M0.1 MECHANICAL NOTES: NOTE 7B STATES "ALL AIR | | CONDITIONING DUCTWORK SHALL BE OF 1 1/2"... | | FIBERGLASS..."THIS IS IN CONFLICT WITH NOTE 7C. | | PLEASE CLARIFY. | | | | 3. M2.1 ROOMS 117 AND 119 SHOW TRANSFER JUMPERS FOR | | RETURN AIR. PROVIDE SIZES FOR FLEX DUCTS TO SHOW | | COMPLIANCE WITH FBC,M 601.4 EXCEPTION 1. DUCT SIZES ON | | FLEX SCHEDULE DO NOT MEET THE EXCEPTION REQUIREMENTS. | | | | 4. M2.1 ROOM 120 THE DESIGN CFM OF THE DUCTED RETURN | | (500CFM) IS LESS THAN THAT OF THE SUPPLY (600CFM) PLUS | | THE TRANSFER RETURN AIR FROM ROOM 119 (80CFM) FOR A | | TOTAL OF 680CFM TO BE RETURNED. PLEASE SHOW BALANCED | | RETURN I THIS AREA PER FBC,M 601.4 | | | | 5. M0.1 NOTE #20: NO DETAIL FOR ROOF-TO-CURB OR | | CURB-TO-EQUIPMENT ATTACHMENTS WAS PROVIDED BY | | STRUCTURAL ENGINEER. SHOW COMPLIANCE WITH WIND LOAD | | REQUIREMENTS OF FBC 1509, 1522 AND CHAPTER 16. | | | | 6. PLEASE SHOW LOCATIONS FOR CONDENSATE DISPOSAL IN | | COMPLIANCE WITH FBC,M 307.2 AND FBC 1503.6. SECONDARY | | DRAIN PROTECTION IS ALSO REQUIRED PER FBC,M 307.2.3. IS | | THIS WHAT IS MEANT ON EQUIPMENT SCHEDULE NOTE #13? | | | | 7. GUARDS SHALL BE PROVIDED WHERE EQUIPMENT REQUIRING | | SERVICE IS LOCATED WITHIN 10 FEET OF ROOF EDGE PER | | FBC,M 304.10 | | | | 8. M7.1 GRAVITY RELIEF HOOD DETAIL: THIS HOOD APPEARS | | TO BE FOR INKATE PURPOSES BUT IT IS SHOWN ATTACHED TO | | AN EXHAUST DUCT. THE BACKDRAFT DAMPER AS SHOWN WILL NOT | | ALLOW AIR TO ENTER THE BUILDING THROUGH THE HOOD. | | PLEASE CLARIFY. | | | | RONALD J REGUEIRO | | 561.805.6734 | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
6 |
Status |
N |
Date |
2007-12-14 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-12-14 |
Time |
10:09 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-12-14 |
Time |
10:09 |
Sent To |
|
|
Notes |
2007-12-14 10:10:25 | REVISIONS NOT APPROVED, SHEETS WITH THESE REVISIONS | | HAVE BEEN APPROVED PREVIOUSLY. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
5 |
Status |
P |
Date |
2007-12-14 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-12-14 |
Time |
10:08 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-12-14 |
Time |
10:08 |
Sent To |
|
|
Notes |
2007-12-14 10:09:40 | REVISIONS OK--SHTS P0.1, P3.1 & P5.1 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
F |
Date |
2007-10-17 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-10-17 |
Time |
10:16 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-10-16 |
Time |
10:42 |
Sent To |
|
|
Notes |
2007-10-17 10:21:23 | REVISIONSDENIED | | REFERENCE: FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1. SHEETS PO.1, P3.1 & P5.1. A PROFESSIONAL ENGINEER | | SHALL SIGN HIS NAME TO ALL PLANS. INITIALS ARE NOT | | ACCEPTABLE. PLEASE SIGN ALL SHEETS AS THEY ARE SEALED | | AND DATED FOR REVIEW. FAC 61G15-23.002(1)(2) & FS | | 471.025. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2007-04-03 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-04-03 |
Time |
08:09 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-03-23 |
Time |
09:53 |
Sent To |
|
|
Notes |
2007-04-03 08:09:38 | NEW SHEETS - PO.1, P2.2, P3.1, P3.2 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2007-01-24 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-01-24 |
Time |
16:01 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-01-23 |
Time |
18:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2006-10-27 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2006-10-27 |
Time |
12:55 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2006-10-27 |
Time |
12:55 |
Sent To |
|
|
Notes |
2006-10-27 13:15:10 | DENIED | | REFERENCE: FBC-2004 PLUMB | | FBC-2004 BUILDING | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | | | 1. SHTS A-1.0 & A-1.1 INDICATE THE CLEAR FLOOR SPACE | | FOR THE BREAK ROOM SINKS PER SECTION 11-4.24.5. - | | INDICATE THE CLEAR FLOOR SPACE FOR THE URINALS PER | | SECTION 11-4.18.3. | | | | 2. SHT A-3.0 DETAIL #5 SHOW THE HEIGHT FOR THE OVERFLOW | | SCUPPER. SEE SECTION 1503.4.3. | | | | | | 3. SHT A-7.1 DETAILS #2 & 6 SHOW COMPLIANCE WITH | | SECTION 11-4.19.5 FAUCETS. | | | | 4. SHT A-7.1 DETAILS #4 & 5 SHOW COMPLIANCE WITH | | SECTIONS 11-4.24.2 HEIGHT, (DETAIL 5), 11-4.24.3 KNEE | | CLEARANCE, 11-4.24.5 CLEAR FLOOR SPACE, (FORWARD | | APPROACH REQUIRED). GARBAGE DISPOSALS ARE NOT APPROVED | | IN THE CLEAR FLOOR SPACE/KNEE CLEARANCE AREA. PLEASE | | DELETE REFERENCE TO GARBAGE DISPOSALS. | | | | 5. SHT A-7.1 DETAILS #1 & 6 SHOW COMPLIANCE WITH | | SECTION 11-4.18.3 CLEAR FLOOR SPACE & SECTION 11-4.18.4 | | FLUSH CONTROLS. | | | | 6. SHT A-7.1 DETAILS #6 & 7 INDICATE COMPLIANCE WITH | | SECTIONS 11-4.16, 11-4.18, 11-4.19, & 11-4.22 AND ALL | | SUBSECTIONS. SUBMIT THE ELEVATIONS FOR ACCESSIBLE | | STALLS. INDICATE 1'6" OFF THE WALL TO THE CENTERLINE OF | | THE W/C FIXTURE, AND 1'3" MIN. TO THE CENTERLINE OF THE | | LAV OFF THE WALL. SEE FIGS. 28, & 32. | | | | 7. SHT A-8.0 ROOM FINISH SECEDULE. ROOM MARKS F-10. | | INDICATE HOW PAINT ON G.B. AND/OR BLOCK MEETS THE | | REQUIREMENT FOR A "SMOOTH, HARD, NONABSORBENT SURFACE", | | REQUIRED IN SECTION 1210.2. | | | | 8. SHT P5.1 DOMESTIC WATER ISOMETRIC. WATER HAMMER | | ARRESTOR SHALL BE LOCATED NEAR THE FIXTURE IN AN | | "EFFECTIVE RANGE", NOT IN THE CEILING AS SHOWN. PDI-WH | | 201 AND MANUF. INSTALLATION INSTRUCTIONS. - A FULL OPEN | | VALVE IS REQUIRED AT THE ENTRANCE INTO THE STRUCTURE | | PER SECTION 606.1(2). PLEASE INDICATE ON WATER RISER | | ISOMETRIC DIAGRAM. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
5 |
Status |
P |
Date |
2007-10-18 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-10-18 |
Time |
16:13 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-10-18 |
Time |
16:12 |
Sent To |
I |
|
Notes |
2007-10-18 16:13:49 | ADDITION OF LIFT ONLY.PER ERIC SCHNEIDER. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
P |
Date |
2007-10-12 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2007-10-12 |
Time |
14:51 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2007-10-12 |
Time |
14:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2007-03-14 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2007-03-14 |
Time |
17:26 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2007-03-14 |
Time |
17:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2007-01-22 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2007-01-22 |
Time |
13:01 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2007-01-22 |
Time |
13:01 |
Sent To |
|
|
Notes |
2007-01-22 13:14:58 | FAILED | | | | 1) ALL APPLICABLE CONDITIONS OF ORDINANCE NO. 3987-06 | | SHALL BE SATISFIED. | | | | A) A TRAFFIC STATEMENT, PREPARED BY A LICENSED TRAFFIC | | ENGINEER, SHALL BE SUBMITTED TO THE PLANNING & ZONING | | AND CONSTRUCTION SERVICES DEPTS. OUTLINING THE NUMBER | | OF DAILY TRIPS, AM TRIPS AND PM TRIPS GENERATED FOR | | EACH USE AND ITS SQUARE FOOTAGE FOR EACH BUILDING. | | | | 2) PROVIDE A RECORDED COPY OF THE PLAT. | | | | 3) THE BOWYER SINGLETON PLANS (SHEETS 3, 5, 8, 20 AND | | 20 OF 29) AND THE LANDSCAPE PLANS SHALL BE UPDATED TO | | REFLECT THE ADA SIDEWALK/ROUTE FROM THE EASTERNMOST | | DISABLED PARKING SPACE SHOWN ON THE ARCHITECT'S SITE | | PLAN. | | | | 4) PARKING DETAIL ON BOWYER SINGLETON SHEET 13 OF 29 | | SHALL SHOW 2 FEET FROM THE CURB TO THE BACK OF THE | | WHEEL STOP, NOT 2 FEET TO THE MIDDLE OF THE WHEEL | | STOP. | | | | 5) 119 PARKING SPACES ARE REQUIRED FOR FULL PROJECT. | | THE STORAGE AREA REQUIRED 1 PARKING SPACE WAS LEFT OUT | | ON THE PARKING TABLE. | | | | 6) THE SITE AREA LISTED ON SHEET A-0.0 DIFFERS FROM THE | | SQUARE FOOTAGE LISTED ON THE PLAT FOR PARCEL D.\ | | | | 7) THE SQUARE FOOTAGE LISTED FOR THE PHASE I BUILDING | | DIFFERS ON ARCHITECTURAL PLANS SHEET A-0.0 (37,904) AND | | SHEET A-0.1 (37,808) AND THE BOWYER SINGLETON PLANS. | | | | 8) WHY DO THE ARCHITECTURAL PLANS LIST "BUILDING AREA" | | AS HAVING MORE SQUARE FOOTAGE THEN THE ACTUAL BUILDING | | SQUARE FOOTAGE? | | | | 9) PLEASE RESPOND IN WRITING TO THE COMMENTS ABOVE. | | | | ERIC SCHNEIDER (561) 822-1435. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2006-10-31 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2006-10-31 |
Time |
17:15 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2006-10-31 |
Time |
17:15 |
Sent To |
|
|
Notes |
2006-10-31 17:48:18 | FAILED | | | | 1) ALL APPLICABLE CONDITIONS OF ORDINANCE NO. 3987-06 | | SHALL BE SATISFIED. | | | | A) A MINOR AMENDMENT IS REQUIRED TO: | | | | I) SHOW ALL IMPROVEMENTS OUTSIDE OF THE 12 FOOT WIDE | | UTILITY EASEMENT. | | | | II) CORRECT THE FEDERAL EXPRESS FREIGHT ADA PARKING (OR | | A LETTER FROM THE CONSTRUCTION SERVICES DEPT. STATING | | THAT THE PARKING AS SHOWN MEETS ADA REQ.) | | | | III) SHOW THE REQUIRED NOISE BARRIER. | | | | B) A TRAFFIC STATEMENT, PREPARED BY A LICENSED TRAFFIC | | ENGINEER, SHALL BE SUBMITTED TO THE PLANNING & ZONING | | AND CONSTRUCTION SERVICES DEPTS. OUTLINING THE NUMBER | | OF DAILY TRIPS, AM TRIPS AND PM TRIPS GENERATED FOR | | EACH USE AND ITS SQUARE FOOTAGE FOR EACH BUILDING. | | | | 2) THE PLAT IS REQUIRED TO BE RECORDED. | | | | 3) BOWYER SINGLETON SITE PLANS AND LANDSCAPE PLANS ARE | | NOT THE LATEST VERSIONS APPROVED BY ORD. NO. 3987-06. | | | | 4) PLAN LINE IS SHOWN INCORRECTLY ON BOWYER SINGLETON | | SHEET 5 OF 29. | | | | 5) 119 PARKING SPACES ARE REQUIRED FOR FULL PROJECT. | | THE STORAGE AREA REQUIRED 1 PARKING SPACE WAS LEFT OUT | | ON THE PARKING TABLE. | | | | ERIC SCHNEIDER (561) 822-1435. | | |
|
|
|