Plan Review Details - Permit 06090691
Plan Review Stops For Permit 06090691
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-11-17 Cont ID  
Sent By lursu Date 2006-11-17 Time 13:05 Rev Time 0.00
Received By lursu Date 2006-11-17 Time 13:05 Sent To  
Notes
2006-11-17 13:05:33TEMPORARY PCN WAS CREATED FOR THIS STRUCTURE .PERMIT
 WAS ASSIGNED TO IT.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 E-MAIL:[email protected]
2006-10-22 19:49:37NEEDS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-04-20 Cont ID  
Sent By shill Date 2007-04-20 Time 08:42 Rev Time 0.00
Received By shill Date 2007-04-20 Time 08:42 Sent To  
Notes
2007-04-20 10:09:14***PROVISOS***
 SAMANTHA M. HILL, BUILDING PLANS EXAMINER 561-805-6724
 [email protected]
  
 1.)A CO HOLD HAS BEEN PLACED ON THIS PERMIT.THE
 ATTORNEYS FOR VP BUILDINGS AND THE ENGINEER DISPUTE THE
 REQUIREMENT BY FBPE (JOHN RYANS) THAT A CERTIFICATE OF
 AUTHORIZATION PER FS471.023 IS REQUIRED FOR VP
 BUILDINGS (LETTER IN THE FILE).THE ENGINEER HAS
 SIGNED, SEALED, AND DATED THE STRUCTURAL PLAN FOR THE
 VP BUILDING AS AN INDIVIDUAL, REMOVING THE COMPANY FROM
 THE PLAN.PRIOR TO CO, ONE OF THE FOLLOWING MUST
 OCCUR:
  
 A.DOCUMENTATION FROM FBPE CONFIRMING THAT
 CERTIFICATE OF AUTHORIZATION IS NOT REQUIRED FOR VP
 BUILDINGS, AKA VARCO PRUDEN BUILDINGS, OR
  
 B.CERTIFICATE OF AUTHORIZATION OBTAINED FOR VP
 BUILDINGS FROM FBPE, AND STRUCTURAL PLAN ON FILE WITH
 THE CITY REVISED TO INCLUDE THAT NUMBER.
  
 2.)SUBMIT LIGHTING POLE CALCS WITH CORRECT ASCE 7-02
 REFERENCE, FBC35.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-04-04 Cont ID  
Sent By shill Date 2007-04-04 Time 07:05 Rev Time 0.00
Received By shill Date 2007-04-04 Time 05:11 Sent To  
Notes
2007-04-04 07:10:33****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)N/A.
  
 2.)VP BUILDINGS SHEETS, SEE FIRST CORRECTION LIST IN
 REGARDS TO ALL INFORMATION REQUIRED BY FAC61G15-23.002.
 I BELIEVE THAT THE ENGINEER HAS ADDRESSED THE ISSUE OF
 CERTIFICATE OF AUTHORIZATION FOR PRACTICING ENGINEERING
 THROUGH A COMPANY VERBALLY.PLEASE HAVE HIM ADDRESS
 THIS ISSUE WITH A LETTER FOR THE FILE.
  
 3.)S2.1, PROVIDE CALCULATIONS FOR ROOF COMPONENTS &
 CLADDING, CORNER ZONE, <10SF, -69PSF.SEE FBC TABLE
 1609.6.2.1(2), ROOF 0 TO 27 DEGREES.
  
 4.)PROVIDE THE INSTALLATION INSTRUCTIONS, ERECTION
 GUIDE, EVALUATION REPORT FOR THE VP BUILDINGS ROOF.
 CONFIRM THAT THIS PRODUCT MEETS OR EXCEEDS DESIGN
 PRESSURES REQUIRED BY EITHER SHEET S2.1 (WITH
 CALCULATIONS) OR REVISED SHEET S2.1.
  
 5.)N/A

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-01-09 Cont ID  
Sent By shill Date 2007-01-09 Time 12:04 Rev Time 0.00
Received By shill Date 2007-01-08 Time 13:44 Sent To  
Notes
2007-01-09 12:05:41****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL
 561-233-5025 FOR MORE INFORMATION.
  
 THE PLANS MUST BE STAMPED.ONLY A RECEIPT WAS
 PROVIDED.PLEASE NOTE THAT THE STAMPED PLAN WHICH YOU
 PROVIDED IS WITH THE DENIED FOUNDATION PERMIT
 APPLICATION PACKAGE.WE MUST HAVE A COPY ON FILE PRIOR
 TO PERMIT ISSUANCE.
  
 3.-4.)ADDRESSED.
  
 5.)PLEASE REVISE THE PERMIT APPLICATION TO REFLECT
 THE CORRECT TEMPORARY PARCEL ID.
  
 6.-8.)ADDRESSED.
  
 9.)PROVIDE COMPONENTS & CLADDING PRESSURES,
 FBC1603.1.4.
  
 NOT ADDRESSED.THE RESPONSE LETTER STATES THAT IT IS
 PROVIDED BY VP.VP PLAN STATES THAT ALL COMPONENTS &
 CLADDING HAVE BEEN DESIGNED BY A FLORIDA DESIGN
 PROFESSIONAL AND ARE NOT ON THE PLAN PER FBC
 1606.1.7(5).THIS IS NOT A VALID CODE SECTION, AND IS
 REQUIRED ON THE PLAN, WIND DESIGN CRITERIA,
 FBC1063.1.4.
  
 DESIGNER IS TO SPECIFY COMPONENT & CLADDING PRESSURES,
 PER OPENING AND FOR THE ROOF SYSTEMS.PRODUCT
 APPROVALS ARE THEN VERIFIED FOR COMPLIANCE.
  
 10.)ADDRESSED.
  
 11.)THE RESPONSE REGARDING S2 OCCUPANCY IS
 ACKNOWLEDGED.THIS IS ACCEPTABLE WITH THE EXCEPTION OF
 UNLIMITED TRAVEL DISTANCE FOR ACCESSIBLE EXITS.NOTE
 THAT THE TRAVEL DISTANCE FOR THE TWO ACCESSIBLE EXITS
 ARE APPROXIMATELY 350 AND 450 FEET, BUT OTHER EXITS
 HAVE LESS TRAVEL DISTANCE.PLEASE CONTACT ME TO
 DISCUSS PRIOR TO RESUBMITTAL.
  
 12.)IF NECESSARY, REVISE TRAVEL DISTANCE, OCCUPANT
 LOAD, ANY OTHER ITEMS AFFECTED BY ITEM 11.
  
 13.)ADDRESSED.PLEASE SEE ITEM 11 ABOVE.
  
 14.)3-A9.2, PROVIDE A GUARD DETAIL IN COMPLIANCE WITH
 FBC1012 AND FBC1607.7.
  
 PLEASE INCLUDE REQUIREMENT OF 1607.7.1.1.
  
 15.)2-A9.2, THE HANDRAIL EXTENSIONS ARE TO COMPLY
 WITH FBC1009.11.5.ANY ACCESSIBLE STAIRS ARE TO ALSO
 COMPLY WITH FBC11-4.9.4.
  
 IT IS NOT CLEAR WHY THE STAIRS AT THE LOADING DOCK ARE
 NOT ACCESSIBLE.THE EXCEPTIONS TO ACCESSIBILITY DO NOT
 APPLY.PLEASE REVISE HANDRAIL DETAILS.ALSO SEE
 FBC1009.3.2, STAIR TREADS TO BE SOLID.
  
 16.)ADDRESSED.
  
 17-18.) SEE ITEM 11.
  
 19-21.)ADDRESSED.
  
 22.)SUBMIT THREE ORIGINAL ENERGY CALCS (ONLY ONE
 PROVIDED).
  
 23-24.) ADDRESSED.
  
 25.)FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED
 IN ADDITION TO THE NOA SUBMITTED, FAC9B72.
 WWW.FLORIDABUILDING.ORG FOR MORE INFORMATION.
  
 ANY PRODUCT APPROVALS NOT SUBMITTED AND REVIEWED PRIOR
 TO PERMIT ISSUANCE WILL REQUIRE SEPARATE PERMITS.
  
 REGARDING THE PRODUCT APPROVALS SUBMITTED, NOTE THE
 FOLLOWING:
  
 A. ONLY ONE SET SUBMITTED; THREE REQUIRED.
  
 B. TWO PRODUCT APPROVALS WERE REVIEWED BY DOR, TWO WERE
 NOT.ALL ARE REQUIRED TO BE REVIEWED AND APPROVED BY
 DESIGNER OF RECORD, FBC*106.3.3.
  
 C. THE VP FLORIDA STATE PRODUCT APPROVAL IS DENIED.
 PROVIDE PRODUCT APPROVALS FOR THE ROOF SYSTEMS.IF A
 MIAMIDADE NOA IS AVAILABLE, A LOCAL.PRODUCT APPROVAL
 CAN BE ISSUED USING THE NOA.IF IT IS NOT AVAILABLE,
 SEE FAC9B72 IN REGARDS TO REQUIREMENTS FOR A LOCAL
 PRODUCT APPROVAL APPLICATION.IF MORE THAN ONE
 FASTENING OPTION IS AVAILABLE, INDICATE WHICH SYSTEM OR
 FASTENING WILL BE USED SO THAT CODE COMPLIANCE CAN BE
 DETERMINED.
  
 D. PRODUCT APPROVAL REQUIRED FOR THE WALL LOUVERS.
  
 26.)ENGINEERING FOR VP BUILDINGS, DECLARE GOVERNING
 CODE.
  
 GOVERNING CODE IS FBC2004.PLANS STATE ASCE7-02 AND
 CITES CODE REFERENCES FROM FBC2001.PLEASE REVISE;
 DESIGN IS TO BE IN COMPLIANCE WITH FBC2004.
  
 27-31.) ADDRESSED.
  
 NEW COMMENTS:
  
 32.)FIRE SPRINKLER PLANS, FP1 AND FP2, ARE LISTED ON
 THE COVER SHEET BUT ARE NO LONGER IN THE PLANS.THIS
 IS A STATUTORY REQUIREMENT, PLEASE PROVIDE.
  
 33.)SEE ATTACHED FS553.80(2)(B).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-24 Cont ID  
Sent By shill Date 2006-10-24 Time 11:11 Rev Time 0.00
Received By shill Date 2006-10-23 Time 17:48 Sent To  
Notes
2006-10-19 15:23:29****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL
 561-233-5025 FOR MORE INFORMATION.
  
 3.)THE COPY OF THE PLAT PROVIDED IS NOT RECORDED.
 PLEASE ADVISE AS TO STATUS.IF THIS IS RECORDED,
 PROVIDE PLAT FILING INFORMATION (BOOK/PAGE).
  
 4.)THE PLAT PROVIDED AND THE PROPOSED PLAT LINES ON
 THE OVERALL SITE PLAN PREPARED BY BOWYER SINGLETON DO
 NOT MATCH.FOR INSTANCE, THE CIRCULAR SECTION AT THE
 END OF THE ROAD (PARCEL G) DOES NOT APPEAR ON THE
 OVERALL SITE PLAN.THE PLAT LINES ARE INCOMPLETE ON
 THE OVERALL SITE PLAN.
  
 5.)THE APPLICATION REFERS TO TWO DIFFERENT PARCEL ID
 NUMBERS.YOU CANNOT CROSS PROPERTY LINES.PROVIDE
 INFORMATION IN REGARDS TO THE LOCATION OF THE TWO
 PARCELS, ENDING IN 3010 AND 3040.OUR GIS RECORDS
 SHOWS 3010 AS A VERY SMALL PARCEL (POSSIBLY A ROAD)
 GOING THROUGH THE MIDDLE OF THE LARGER PARCEL, 3040.
 PLEASE CONTACT ME TO DISCUSS IF YOU ARE UNSURE AS TO
 HOW TO GET THIS MATTERS RESOLVED.
  
 6.) FBC* 109.3.7RESIDENT INSPECTOR. SUBMIT INSPECTOR
 RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA,
 DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.A RESIDENT
 INSPECTOR PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO
 ONE OR MORE OF THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS
 OF CONSTRUCTION
  
 ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION
 SERVICES MANAGER - TEL:
 561 805 6711), A MEETING INVOLVING THE OWNER, RESIDENT
 INSPECTOR, JOB INSPECTOR, CONTRACTOR AND ENGINEER. THIS
 MUST BE DONE PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL
 SETS OF ALL DOCUMENTS ARE REQUIRED FOR PERMITTING.
  
 7.)VALUATION ADJUSTMENT DONE USING BUILDING VALUATION
 DATA FROM THE ICC WEBSITE, SEE ATTACHED BILL.
  
 8.)RADON FEES DUE, FS553.721.SEE ATTACHED BILL.
  
 9.)PROVIDE COMPONENTS & CLADDING PRESSURES,
 FBC1603.1.4.
  
 10.)THE ACCESSIBLE ROUTE FROM THE PUBLIC WAY IS SHOWN
 ON THE OVERALL SITE PLAN, SHOW SLOPE AND WIDTH
 FBC11-4.1.2(1).
  
 11.)S2 DECLARED, SEE FBC311.3, DEFINITION IS FOR
 NON-COMBUSTIBLE STORAGE.PROVIDE INFORMATION IN
 REGARDS TO WHAT WILL BE STORED AND WHAT ACTIVITY WILL
 TAKE PLACE IN THIS BUILDING.HOW WILL YOU CONTROL THE
 SHIPPING OF COMBUSTIBLES SUCH AS PAPER AND BOOKS?NOTE
 THAT PACKAGING MUST BE ADDRESSED AS WELL AS THE ITEMS
 STORED.
  
 12.)IF NECESSARY, REVISE TRAVEL DISTANCE, OCCUPANT
 LOAD, ANY OTHER ITEMS AFFECTED BY ITEM 11.
  
 13.)PROVIDE A LIFE SAFETY PLAN, FBC*106.3.5.1.1(6)
 AND (7).INCLUDE THE FOLLOWING:
 EGRESS CAPACITIES, FBC1005.
 INDICATE ACCESSIBLE EXITS FBC11-4.1.3(9)
 ANY OTHER INFORMATION REQUIRED TO DETERMINE CODE
 COMPLIANCE
  
 14.)3-A9.2, PROVIDE A GUARD DETAIL IN COMPLIANCE WITH
 FBC1012 AND FBC1607.7.
 15.)2-A9.2, THE HANDRAIL EXTENSIONS ARE TO COMPLY
 WITH FBC1009.11.5.ANY ACCESSIBLE STAIRS ARE TO ALSO
 COMPLY WITH FBC11-4.9.4.
  
 16.)SEE FBC11-4.1.3(8)(III), WHERE FEASIBLE,
 ACCESSIBLE ENTRANCES SHALL BE THE ENTRANCES USED BY THE
 MAJORITY OF PEOPLE VISITING OR WORKING IN THE BUILDING.
 IT IS NOT CLEAR IF THE WAREHOUSE ENTRY IS ACCESSIBLE.
  
 17.)FBC11-4.1.3(9), ACCESSIBLE MEANS OF EGRESS SHALL
 BE PROVIDED IN THE SAME NUMBER AS REQUIRED FOR EXITS BY
 LOCAL BUILDING/LIFE SAFETY REGULATIONS; MORE THAN ONE
 EXIT REQUIRED FROM THE STORAGE AREA DUE TO OCCUPANT
 LOAD, FBC10181.2. A RAMP IS SHOWN AT THE BUILDING
 ENTRANCE, NO OTHER ACCESSIBLE EXITS SHOWN.IT IS NOT
 CLEAR IF THE STOOPS SHOWN AT THE DOORS AT GRADE LEVEL
 ARE AT THE SAME ELEVATION AS THE ASPHALT OR IF THEY ARE
 HIGHER.PLEASE CLARIFY ON THE PLAN.
  
 18.)FBC11-4.1.3(8)(A)(II), ACCESSIBLE ENTRANCES
 REQUIRED AT LEAST EQUIVALENT TO THE NUMBER OF
 ACCESSIBLE EXITS.
  
 19.)72 INCHES OF STRAIGHT AND LEVEL CLEARANCE
 REQUIRED AT THE BOTTOM OF THE RAMP, FBC11-4.8.4(2).
  
 20.)A3.1 DOES NOT SHOW AN ELEVATION CHANGE INSIDE OF
 THE BUILDING, BUT THE ELEVATIONS ON A2.1 SHOW A RAMP TO
 THE EAST DOOR, SOUTH ELEVATION, BUT THE OTHER DOOR IS
 SET AT GRADE.PLEASE CLARIFY.
  
 21.)SPECIFY INTERIOR FINISH CLASSIFICATION, FBC TABLE
 803.5.
  
 22.)ENERGY CALCS REQUIRED.WHEN SUBMITTING, SIGN THE
 OWNER/AGENT LINE OF THE ENERGY CALC, VERIFY THAT SF
 AREA ON THE ENERGY CALC MATCHES THE SF ON THE PLAN, AND
 INCLUDE CORRECT JURISDICTION CITY OF WEST PALM BEACH,
 604700.
  
 23.)IMPACT PROTECTION REQUIRED.NONIMPACT STOREFRONT
 PRODUCT APPROVALS WERE SUBMITTED.SEE ATTACHED POLICY,
 ITEM 13, IN REGARDS TO IMPACT PROTECTION ON COMMERCIAL
 BUILDINGS.USE IF REMOVABLE SHUTTERS ON COMMERCIAL
 BUILDINGS MUST BE APPROVED BY THE BUILDING OFFICIAL.
  
  
 24.)IF YOU ARE USING HURRICANE SHUTTERS, SEE ATTACHED
 SCHEDULE FOR INSTALLATION.PROVIDE PRODUCT APPROVALS
 AND ALL REQUIRED INFORMATION TO DETERMINE CODE
 COMPLIANCE.
  
 25.)FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED
 IN ADDITION TO THE NOA SUBMITTED, FAC9B72.
 WWW.FLORIDABUILDING.ORG FOR MORE INFORMATION.
  
 26.)ENGINEERING FOR VP BUILDINGS, DECLARE GOVERNING
 CODE.
  
 27.)MECHANICAL EQUIPMENT LOADS NOT ADDRESSED ON THE
 VP BUILDING STRUCTURALS.
  
 28.)THE ENGINEER'S SIGNATURE IS A PHOTOCOPY (VP). SEE
 FAC61G15-23.002.
  
 29.)ENGINEER'S TITLE BLOCK IS TO COMPLY WITH
 FAC61G15-23.002.
  
 30.)THE ARCHITECT SPECIFIES IMPACT GLASS, NONIMPACT
 PRODUCT APPROVALS SUBMITTED.
  
 31.)ROOF DRAINAGE IS TO COMPLY WITH FBC1503.4.
 PROVIDE CALCULATIONS AND DETAILS FOR SCUPPERS AND
 OVERFLOW SCUPPERS.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-10-07 Cont ID  
Sent By dpalmer Date 2007-10-07 Time 09:31 Rev Time 0.00
Received By dpalmer Date 2007-10-07 Time 09:20 Sent To PC
Notes
2007-10-07 09:32:17REV'S FOR 4.1 AND 5.1, FOR REV #6 ONLY.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-04-19 Cont ID  
Sent By dpalmer Date 2007-04-19 Time 10:57 Rev Time 0.00
Received By dpalmer Date 2007-04-19 Time 09:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-03-18 Cont ID  
Sent By dpalmer Date 2007-03-18 Time 10:27 Rev Time 0.00
Received By dpalmer Date 2007-03-18 Time 10:26 Sent To  
Notes
2007-03-18 10:28:49** UNSAT 3RD REVIEW**
  
  
 1) NOTE: PLEASE SEE THE METHOD/WHOLE BUILDING SUBMITTED
 DOES NOT CONTAIN ANY *INTERIOR* LIGHTING INPUT DATA?
 PLEASE CLARIFY?
 DOES NOT SHOW ANY ENTERED OR DOES NOT SHOW ANY IN THE
 INPUT DATA REPORT?
 FBC 13-415.1.AB.1.1.
 PLEASE ALSO SEE SHEET 3 OF SUBMITTED CALCULATIONS WHICH
 REQUIRES THE ENGINEER TO SIGN, DATE AND SEAL SHEET.
 THIS IS THE SHEET WHICH CONTAINS THE *CERTIFICATIONS*.
 FBC 13-103.1.1.1
  
 2) NOTE: PLEASE CLARIFY HOW THE PLANS WHICH WERE
 REVISED AFTER THE MEETING WHICH WAS HELD ON 2/26/07 ARE
 DATED BY THE ENGINEER ON 2/2/07?
 FS 471.025 AND FAC 61G15-23.002 REQUIRES THE ENGINEER
 TO SIGN, AND DATE PLANS WHEN THEY ARE SEALED. THE
 REVISION DATE EVEN INDICATES A DATE OF 2/2/07 WHICH IS
 NOT POSSIBLE AS THESE WERE NEW SHEETS ENTERED INTO THE
 SETS ON 3/15/07.
  
 3) NOTE: PLEASE SEE BATHROOM AREAS IN FRONT ARE MISSING
 LIGHTING CONTROLS PER 13-415.1.ABC.1.2.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-03-18 09:39:442007-03-18 09:39:44
 NEW SHEETS AND PLANS SUBMITTED ON 3/15/07.
2007-03-08 16:11:272007-03-08 16:11:27
 PLANS ON HOLD FOR REVIEW. 3/8/07
 NEW CORRECTIONS WHICH WERE REQUIRED TO BE SUBMITTED BY
 MARCH 1ST HAVE NOT BEEN BROUGHT IN. AT THE REQUEST FROM
 MARK PARKHIL BY E-MAIL, PLANS ARE NOT TO BE REVIEWED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-01-12 Cont ID  
Sent By dpalmer Date 2007-01-12 Time 17:10 Rev Time 0.00
Received By dpalmer Date 2007-01-12 Time 12:03 Sent To  
Notes
2007-01-12 17:10:50*****UNSAT 2ND REVIEW ******
  
 FED-EX GROUND.
  
 ** PLEASE ADDRESSING ON PLANS SHALL BE REQUIRED TO
 CORRELATE. PLEASE SEE PERMIT APPLICATION, THE ASSIGNED
 ADDRESS AND PLANS DO NOT MATCH. PLEASE SEE THE ADDRESS
 SHALL APPEAR ON ALL SHEETS TITLE BLOCKS. FAC 61G1,
 61G15
  
 ** PLEASE SEE SOME COMMENTS FROM THE PREVIOUS REVIEWS
 WHICH ARE STILL IN NEED OF ADDRESSING.
 COMMENTS WILL BE IDENTIFIED AS FOLLOWS IN THE SAME
 NUMERICAL ORDER FROM THE PREVIOUS REVIEW. ANY NEW NOTES
 WILL BE ADDED TO THE END OF THE REVIEW.
  
 A) NO, MEANS THE COMMENT IS STILL IN NEED OF FURTHER OR
 CORRECTED INFORMATION. IT WILL BE FOLLOWED BY FURTHER
 EXPLANATION FOR MORE INFORMATION OR TO TRY AND BETTER
 EXPLAIN THE COMMENT.
 B) OK, IS COMMENT IS ADDRESSED AND THE PREVIOUS NOTE
 WILL BE REMOVED.
 C) NO/OK IS THAT PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED BUT NOT ALL. A FURTHER EXPLANATION WILL BE
 TYPED TO PROVIDE MORE INFORMATION FOR WHAT IS NEED.
  
  
 1) NOTE:NO, PLEASE SEE THERE ARE NUMEROUS SHEETS IN
 ONE SET WHICH ARE NOT SIGNED, DATED OR SEALED AT ALL.
 PLEASE SEE YET ANOTHER SET ONLY CONTAINS ONE ELECTRICAL
 SHEET WHICH IS SIGNED, DATED AND SEALED.PLEASE SEE
 THE THIRD SETS ALSO.
 PLEASE SEE THE SAME SETS CONTAINS MANY MECHANICAL AND
 PLUMBING SHEETS WHICH ARE NOT SIGNED, DATED OR SEALED
 EITHER?
 PLEASE SEE OTHER SETS WHICH SOME SHEETS ARE SIGNED,
 DATED AND SEALED AND MANY OTHER SHEETS ARE NOT?
 PLEASE SEE OTHER DOCUMENTS WHICH ARE IN FACT
 PHOTO-COPIES OF SIGNED AND SEALED DOCUMENTS.
 AS PREVIOUSLY MENTIONED, ALL THREE SETS, ALL DOCUMENTS
 PREPARED BY THE DESIGNERS OF RECORD ARE REQUIRED TO
 CONTAIN AN ORIGINAL SIGNATURE, DATED AND A RAISED
 EMBOSSED SEALED AS REQUIRED IN THE SECTIONS OF THE
 FLORIDA ADMINISTRATIVE CODE AND FLORIDA STATUTES GIVEN
 ON PREVIOUS REVIEW.
 ** PLEASE KNOW, SETS OF PLANS MAY BE RETAINED BY THIS
 OFFICE.
 ** PLEASE ALSO KNOW THAT THIS COMMENT IS REQUIRED FOR
 ALL TRADES AND FOR ALL SHEETS WHETHER OR NOT COMMENT IS
 MADE BY ANY OTHER REVIEWER(S).
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE ALL MEP SHEETS SHALL CONTAIN THE RAISED
 EMBOSSED SEAL FOR THE ENGINEER OF RECORD. PLEASE SEE
 FAC 61G15-23.001,FS 471.025
 PLEASE ALSO SEE THE SEAL WHICH IS BEING INDICATED ON
 SAID MEP'S IS NO LONGER VALID WITH THE STATE OF
 FLORIDA. PLEASE SEE FAC 61G15-23.001, WHICH PASSED A
 RULING IN FEB 04" WHICH REQUIRED THE SEAL WORDING TO
 CHANGE FROM "CERTIFICATE" TO "LICENSE". PLEASE KNOW AN
 EXTENSION WAS GIVEN TO 12/31/05.
  
 2) NOTE: OK.
  
 3) NOTE: NO, THIS IS STILL REQUIRED AND IT HAS COME TO
 OUR ATTENTION THAT THE FIRM DOES NOT CONTAIN THE
 LICENSE NUMBER AS NEEDED AND AS REQUIRED PER SECTIONS
 GIVEN BELOW IN THE PREVIOUS REVIEW. PLEASE SEE RESPONSE
 MENTIONS THE ENGINEER WAS ADDED TO THE TITLE BLOCKS,
 HOWEVER THIS IS NOT THE ONLY REQUIRED INFORMATION.
 PLEASE ALSO KNOW THAT EVEN THOUGH THE ENGINEERING FIRM
 AS SHOWN IS LOCATED OUT OF STATE, THIS HAS NO BEARING
 ON THE REQUIREMENT.
 ** THE TITLE BLOCKS WERE REVISED FOR THE FOUNDATION
 PERMIT. IF THIS IS DONE, ADDRESS AND COMPLETED
 INFORMATION FOR THE INDIVIDUAL ENGINEER OF EACH TRADE
 IS REQUIRED TO BE COMPLETED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING REQUIRED INFORMATION ON TITLE
 BLOCKS. PLEASE SEE MISSING THE PRINTED LICENSE # OF
 ARCHITECT ON A SHEETS. PLEASE SEE THE MISSING
 INFORMATION AS REQUIRED ON ENGINEERING FIRM. PLEASE SEE
 MISSING CERTIFICATE OF AUTHORIZATION NUMBER. PLEASE SEE
 ALL TITLE BLOCKS FOR ALL SHEETS ARE REQUIRED TO MEET
 FAC 61G1-16.004, 61G15-23.002 AND FS 481.219, 471.023.
 ** REQUIRED FOR ALL WHETHER OR NOT COMMENT IS MADE BY
 OTHER REVIEWER(S).
  
 4) NOTE: OK.
  
 5) NOTE: NO, PLEASE SEE THE ENERGY CALCULATIONS
 SUBMITTED DO NOT COMPLY OR SUPPLY THE INFORMATION AS
 NEEDED UNDER 13-415.1AB.1 OR 13-415.2. PLEASE SEE THE
 SHEETS SUBMITTED, SOME ARE SIGNED AND SEALED AND SOME
 ARE NOT.
 PLEASE SEE LIGHTING PERFORMANCE ON PLANS INDICATES THE
 2003 ICC WHICH IS NOT ADOPTED INTO THE STATE OF
 FLORIDA.
 PLEASE ALSO SEE THE ENTIRE BUILDING IS BEING DESIGNATED
 AS ONE USE?
 PLEASE SEE THE PREVIOUS NOTE AS THE COMPLIANCE
 BREAKDOWN REQUIRED FOR METHOD A SHOULD BE SUBMITTED
 SHOWING ALL INFORMATION AS NEEDED.
 THIS MAY NOT BE CONSIDERED INDUSTRIAL WORK. A CALL TO
 GO OVER USAGE MAY HELP.
  
 **PREVIOUS REVIEW NOTE**
 PLEASE SEE FBC 2004 FOR REQUIRED ENERGY CALCULATIONS.
 PLEASE SEE 1993 ASHAE/ ETC IS BEING REFLECTED ON SAID
 DOCUMENTS. PLEASE SEE FBC 2004 CHAPTER 13.
 13-415.1.AB.1
 PLEASE KNOW THESE WILL ALSO BE REQUIRED TO BE SIGNED,
 DATED AND SEALED AS REQUIRED ON NOTES ABOVE. PLEASE SEE
 THESE ARE ALSO STAMPED WITH A "RUBBER STAMP" FOR SAID
 SEAL AND CONTAINS "CERTIFICATE" IN SEAL.
  
 6) NOTE:OK/NO. PLEASE SEE RESPONSE LETTER MENTIONS
 THAT THE ENTIRE BUILDING WILL BE OPERATING 24/7. THIS
 EXCEPTION SHALL BE NOTED AND STATED ON THE PLANS.
 PLEASE SEE NO INFORMATION FOR THE WORST CASE VOLTAGE
 DROP CALCULATIONS OR SCENARIOS COULD BE LOCATED ON
 PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE CHAPTER 13 13-415.1.ABC.1.1, .1.2 AND .1.3
 FOR MINIMUM LIGHTING CONTROLS REQUIRED. PLEASE PROVIDE
 PERFORMANCE CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.
 PLEASE SEE TABLES AND SPACE BY SPACE METHODS.
 PLEASE PROVIDE SCHEDULING.
 PLEASE SEE ALL OF CHAPTER 13, BASED ON THE 2004 FBC.
 PLEASE PROVIDE ALL WORST CASE SCENARIO'S FOR VOLTAGE
 DROP CALCULATIONS PER13-413.1ABC.1 FOR BOTH BRANCH
 CIRCUIT AND FEEDERS.
  
 7) NOTE:NO, THE ATTACHED DOCUMENTS DO NOT PROVIDE THE
 WIND LOAD INFORMATION, DO NOT SUPPLE THE MAXIMUM EPA,
 AND IF SUBMITTING SHOP/PRODUCTS, FOR COMPLIANCE AND
 SHOWING AND STATING THE INFORMATION ON PLANS, THEN ALL
 OF THESE DOCUMENTS FOR POLES, WIND LOAD INFORMATION AND
 EPA'S SHALL BE REVIEWED AND STAMPED/SIGNED BY THE
 ENGINEER OF RECORD.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE WIND LOAD CALCULATIONS FOR SITE LIGHTING
 POLES. PLEASE KNOW, THE BUILDING/STRUCTURAL REVIEWER
 WILL REVIEW SAID DOCUMENTS FOR ACTUAL WIND LOADS WHICH
 WILL BE REQUIRED TO SHOW EPA FOR PROPOSED FIXTURES.
 FBC 2004 140MPH. ETC.
  
 8) NOTE:NO, PLEASE SEE RESPONSE MENTIONS DESIGN WILL
 MEET THIS; HOWEVER NO REVIEW FOR COMPLIANCE CAN BE DONE
 UNTIL PHOTO-METRICS ARE SHOWN FOR COMPLIANCE. THE
 LEVELS ARE BEING SUBMITTED FOR WAREHOUSE UNDER NORMAL,
 HOWEVER NO INFORMATION FOR CONDITIONS UNDER EMERGENCY
 OR OFFICE EGRESS AREAS IS SHOWN.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE PROVIDE MINIMUM PHOTO-METRICS FOR EGRESS
 LIGHTING PER NFPA-101 7.8, 7.9
 PLEASE SEE NORMAL IS SHOWN, HOWEVER NEED TO SEE MIN
 UNDER EMERGENCY CONDITIONS.
  
 9) NOTE: OK, AS NOTED HOWEVER SEE OTHER NEW COMMENTS AS
 THE PLANS WERE REVIEWED AS THIS MAIN DIST PANEL
 CONTAINING A SINGLE MCB RATED AT THE 1600AMPS.
 SEE NEW NOTES.
  
 10) NOTE: OK.
  
 11) NOTE: PLEASE SEE 110.9, 240.13 AND PROVIDE ALL
 MINIMUM REQUIRED AIC RATINGS AND SELECTIVE COORDINATION
 FOR EQUIPMENT AS SHOWN. PLEASE SHOW DETAIL FOR
 EQUIPMENT.
  
 12) NOTE: NO, PLEASE SEE RESPONSE SAYS THE EGC IS
 AFTER; HOWEVER PLEASE SEE RISER NOTE WHICH SHOWS ALL
 PHASE CONDUCTORS AND AN EGC FROM THE FPL(LOCAL POWER
 COMPANY ) TRANSFORMER.
 PLEASE SEE RISER.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 250.6, 250.24B AS AN "EQUIPMENT GROUNDING
 CONDUCTOR" IS BEING SHOWN BEFORE THE FIRST MEANS OF
 DISCONNECT ON THE LINE SIDE OF THE MAIN. PLEASE KNOW
 THE EGC IS ONLY INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 13) NOTE: OK.
  
 14) NOTE: NO, RESPONSE MENTIONS WHAT TO DO, HOWEVER
 WHERE IS THIS DETAIL ON PLANS AS PREVIOUSLY REQUESTED?
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE A STRUCTURAL SUPPORT DETAIL FOR BOTH
 TRANSFORMERS.
 PLEASE KNOW THIS STRUCTURAL DETAIL WILL BE REVIEWED BY
 BUILDING REVIEWER.
 FBC 106.1.2
  
 15) NOTE: OK.
  
 16) NOTE:NO. PLEASE SEE RESPONSE MENTIONS THE MINIMUM
 LEVELS WHICH ARE REQUIRED PER ADA UNDER THE FBC AS
 EXCESSIVE. THESE ARE MINIMUM LEVELS. PLEASE SEE THE FBC
 DICTATES THE LEVELS WHICH ARE MORE RESTRICTIVE THAN
 THAT OF THE LEVELS IN NFPA-72. PLEASE SEE THAT THERE
 ARE MAXIMUM LEVELS WHICH ARE 1000 CD.
 THE LEVELS FOR THESE AREAS WHICH ARE TAKEN DIRECTLY
 FROM THE SECTIONS GIVEN MUST MEET THESE LEVELS AT A
 MINIMUM.
 AS REVIEWING THE RESPONSE IT HAS BEEN NOTED, HOWEVER
 THESE ARE STATED IN THE CODE THERE IS NO MENTION FOR
 EXCEPTIONS DUE TO MEDICAL CONDITIONS AS MENTIONED.
 PLEASE PROVIDE MORE INFORMATION FOR THESE LEVELS FROM
 THE FBC IF SECTIONS WRE INF THE CODE WHICH WILL SUPPORT
 THESE LESSER LEVELS.
  
 ** PREVIOUS REVIEW NOTES**
 PLEASE SEE FBC 11-4.28, 11-4.28.2 AND .3(4) WHICH
 REQUIRE A MIN OF 75 CANDELAS AT ALL AREAS AS STATED FOR
 ADA. PLEASE SEE MIN LEVELS STATED FOR ADA ON PLANS
 MENTIONS 15CD?
 PLEASE KNOW ALL OF THESE AREAS WILL BE TESTED FOR
 MINIMUM LEVELS, PLEASE BE SURE THE DEVICES AS SHOWN AND
 INSTALLED WILL MEET TESTED LEVELS. PLEASE ADJUST NOTES
 ON PLANS AT THIS TIME.
  
 17) NOTE: OK.
  
 18) NOTE: OK/NO, PLEASE SEE RESPONSE MENTIONS THAT ALL
 CONVEYOR SYSTEMS AND ELECTRICAL WORK WILL BE UNDER A
 SEPARATE PERMIT PLANS AND FEES. PLEASE SEE THE MDP
 SHOWS CONDUCTORS AND CONDUITS BEING INSTALLED AT THIS
 TIME YET THE RISER DOES NOT SHOW THESE CONDUITS BEING
 DONE AT THIS TIME. PLEASE ALSO SEE NEW NOTE WITH
 RESPECT TO THE AMOUNT OF MAINS.
 PLEASE ADJUST MDP IF THIS WORK IS NOT BEING DONE AT
 THIS TIME AS SHOWN ON RISER AS FUTURE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE INFORMATION FOR CONVEYOR SYSTEM, PLEASE
 PROVIDE INFORMATION ON ALL LISTINGS FOR EQUIPMENT BRING
 INSTALLED.
 PLEASE PROVIDE SPECS ON THE MCC.
 110.3, 90.7.
 FBC 106.1.2
  
 19) NOTE: OK.
  
 20) NOTE:OK, THIS WAS ONLY NOTED A
  
 21) NOTE: NO, PLEASE SEE RESPONSE MENTIONS THAT THE
 LOCK ON/OFF DEVICE WILL PART OF THE BREAKER, HOWEVER
 THIS IS ONLY BEING NOTED IN RESPONSE LETTER, PLEASE
 PLACE THIS NOTE ON PLANS RELEVANT TO THE PANEL
 SCHEDULES AND BREAKERS BEING INSTALLED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PANEL NOTES MENTIONS "LOCK-OFF" BREAKERS,
 PLEASE KNOW THESE TYPE OF LOCK OFF DEVICES SHALL BE AN
 INTEGRAL PART OF THE BREAKER AND SHALL NOT BE REMOVABLE
 WITHOUT THE REMOVAL OF SAID BREAKER. 90.7, 110.3, 90.4
  
 22) NOTE: OK, FUELING STATION WILL NOT BE PART OF THIS
 PERMIT.
  
 ** NEW NOTES THIS REVIEW **
  
 23) NOTE: PLEASE SEE AS THE MDP CONTAINS MORE THAN SIX
 SPACES AND THEY ARE NOT BEING COMPLETED AND SPACES ARE
 NOT FILLED AT THIS TIME, A MCB WILL BE REQUIRED. OTHER
 OPTIONS WOULD BE TO INSTALL THE 3-POLE BREAKERS AS
 SPARES AT THIS TIME AND WILL BE REQUIRED TO BE SHOWN,
 OR THE PLANS SHALL BE NOTED THAT THE DEAD-FRONT FROM
 THE MANUFACTURE SHALL CONTAIN A PERMANENT FACTORY
 INSTALLED FILLER FOR THIS SECTION FOR 2D.
 230.70, 230.71 90.4.
 PLEASE KNOW, THE OTHER OPTION WOULD BE TO INSTALL A
 1600AMP MCB WITH GF PROTECTION.
  
 24) NOTE: PLEASE SEE MDP WHICH SHOWS 1/0'S FOR THE
 FEEDERS TO THE TRANSFORMER FOR PP1, HOWEVER RISER SHOWS
 #1'S. PLEASE CORRELATE.
 PLEASE KEEP IN MIND THE VOLTAGE DROP AS PREVIOUSLY
 NOTED.
  
 25) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) IS
 BEING GIVEN AS A NOTICE AT THIS TIME WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE; HOWEVER ONE SET OF PLANS MAY BE RETAINED.
  
 ** PLEASE KNOW AS THERE IS INFORMATION WHICH HAS NOT
 YET BEEN SUBMITTED FOR REVIEW, THERE MAY BE COMMENTS ON
 NEXT REVIEW WHICH ARE NOT STATED IN THESE REVIEW
 NOTES.
  
  
 *** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected] ND IF IT IS AN ISSUE THEN RELOCATION
 WILL BE REQUIRED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-23 Cont ID  
Sent By dpalmer Date 2006-10-23 Time 14:05 Rev Time 0.00
Received By dpalmer Date 2006-10-22 Time 19:45 Sent To  
Notes
2006-10-23 14:05:24*****UNSAT ******
  
 FED-EX GROUND.
  
 ** PLEASE ADDRESSING ON PLANS SHALL BE REQUIRED TO
 CORRELATE. PLEASE SEE PERMIT APPLICATION AND PLANS DO
 NOT MATCH WITH THE ADDRESS IN OUR SYSTEM AS SHOWN.
  
  
 1) NOTE: PLEASE SEE ALL MEP SHEETS SHALL CONTAIN THE
 RAISED EMBOSSED SEAL FOR THE ENGINEER OF RECORD. PLEASE
 SEE FAC 61G15-23.001,FS 471.025
 PLEASE ALSO SEE THE SEAL WHICH IS BEING INDICATED ON
 SAID MEP'S IS NO LONGER VALID WITH THE STATE OF
 FLORIDA. PLEASE SEE FAC 61G15-23.001, WHICH PASSED A
 RULING IN FEB 04" WHICH REQUIRED THE SEAL WORDING TO
 CHANGE FROM "CERTIFICATE" TO "LICENSE". PLEASE KNOW AN
 EXTENSION WAS GIVEN TO 12/31/05.
  
 2) NOTE: PLEASE SEE FS 471.025, PLEASE SEE ALL PLANS
 DOCUMENTS ETC ARE REQUIRED TO CONTAIN THE ORIGINAL
 LEGAL SIGNATURE DATE AND SEAL.
 PLEASE SEE "VP" BUILDING SHEETS AS THESE CONTAIN A
 RAISED SEAL OVER "PHOTO-COPIED" SIGNATURE OF THE DESIGN
 PROFESSIONAL.
 PLEASE SEE BUILDING REVIEW COMMENTS AS THESE ARE ALSO
 MISSING THE REQUIRED TITLE BLOCK FOR THESE SHEETS/
 PLEASE SEE THE ELECTRICAL PLANS APPEAR TO BE SIGNED
 WITH INITIALS?
 IF INDEED THIS IS THE LEGAL SIGNATURE OF THE DESIGN
 PROFESSIONAL PLEASE PROVIDE A SIGNED, DATED, SEALED AND
 NOTARIZED LETTER FOR LEGAL SIGNATURE.
 THIS WILL BE PLACED IN OUR SIGNATURE FILE FOR ANY
 FUTURE REFERENCE AS NEEDED.
 FS 471.025, FAC 61G15-23.002
  
 3) NOTE: PLEASE SEE MISSING REQUIRED INFORMATION ON
 TITLE BLOCKS. PLEASE SEE MISSING THE PRINTED LICENSE #
 OF ARCHITECT ON A SHEETS. PLEASE SEE THE MISSING
 INFORMATION AS REQUIRED ON ENGINEERING FIRM. PLEASE SEE
 MISSING CERTIFICATE OF AUTHORIZATION NUMBER. PLEASE SEE
 ALL TITLE BLOCKS FOR ALL SHEETS ARE REQUIRED TO MEET
 FAC 61G1-16.004, 61G15-23.002 AND FS 481.219, 471.023.
 ** REQUIRED FOR ALL WHETHER OR NOT COMMENT IS MADE BY
 OTHER REVIEWER(S).
  
 4) NOTE: PLEASE SEE ALL OF THE FOLLOWING MINIMUM CODES
 ARE REQUIRED TO BE REFLECTED ON PLANS. 2004 FBC, , 2002
 NFPA-70, 2002 NFPA-72, 2003 NFPA-101 .
  
 5) NOTE: PLEASE SEE FBC 2004 FOR REQUIRED ENERGY
 CALCULATIONS. PLEASE SEE 1993 ASHAE/ ETC IS BEING
 REFLECTED ON SAID DOCUMENTS. PLEASE SEE FBC 2004
 CHAPTER 13.
 13-415.1.AB.1
 PLEASE KNOW THESE WILL ALSO BE REQUIRED TO BE SIGNED,
 DATED AND SEALED AS REQUIRED ON NOTES ABOVE. PLEASE SEE
 THESE ARE ALSO STAMPED WITH A "RUBBER STAMP" FOR SAID
 SEAL AND CONTAINS "CERTIFICATE" IN SEAL.
  
 6) NOTE: PLEASE SEE CHAPTER 13 13-415.1.ABC.1.1, .1.2
 AND .1.3 FOR MINIMUM LIGHTING CONTROLS REQUIRED. PLEASE
 PROVIDE PERFORMANCE CALCULATIONS PER 13-415.2,
 13-415.2.ABC.1. PLEASE SEE TABLES AND SPACE BY SPACE
 METHODS.
 PLEASE PROVIDE SCHEDULING.
 PLEASE SEE ALL OF CHAPTER 13, BASED ON THE 2004 FBC.
 PLEASE PROVIDE ALL WORST CASE SCENARIO'S FOR VOLTAGE
 DROP CALCULATIONS PER13-413.1ABC.1 FOR BOTH BRANCH
 CIRCUIT AND FEEDERS.
  
 7) NOTE: PLEASE PROVIDE WIND LOAD CALCULATIONS FOR SITE
 LIGHTING POLES. PLEASE KNOW, THE BUILDING/STRUCTURAL
 REVIEWER WILL REVIEW SAID DOCUMENTS FOR ACTUAL WIND
 LOADS WHICH WILL BE REQUIRED TO SHOW EPA FOR PROPOSED
 FIXTURES.
 FBC 2004 140MPH. ETC.
  
 8) NOTE: PLEASE PROVIDE MINIMUM PHOTO-METRICS FOR
 EGRESS LIGHTING PER NFPA-101 7.8, 7.9
 PLEASE SEE NORMAL IS SHOWN, HOWEVER NEED TO SEE MIN
 UNDER EMERGENCY CONDITIONS.
  
 9) NOTE: PLEASE INDICATE THE REQUIRED MAIN AND GFP FOR
 THE 1600A MAIN.
 PLEASE SEE 230.70, 240.13 AND 230.95.
  
 10) PLEASE ALSO SEE POSSIBLE MISPRINT FOR 2B BREAKER
 WHICH IS BEING SHOWN AS 2225A'S.?
 FBC ADMINISTRATIVE SECTION 106.3.5.1.2.
  
 11) NOTE: PLEASE SEE 110.9, 240.13 AND PROVIDE ALL
 MINIMUM REQUIRED AIC RATINGS AND SELECTIVE COORDINATION
 FOR EQUIPMENT AS SHOWN. PLEASE SHOW DETAIL FOR
 EQUIPMENT.
  
 12) NOTE: PLEASE SEE 250.6, 250.24B AS AN "EQUIPMENT
 GROUNDING CONDUCTOR" IS BEING SHOWN BEFORE THE FIRST
 MEANS OF DISCONNECT ON THE LINE SIDE OF THE MAIN.
 PLEASE KNOW THE EGC IS ONLY INSTALLED AFTER THE FIRST
 MEANS OF DISCONNECT.
  
 13) NOTE: PLEASE INDICATE THE FEED-THRU LUGS ON EACH
 LP1 AND PP1, OR ARE THE SECONDARY SECTIONS FED BY OCP
 DEVICES FROM SECTIONS (1). ?
 240.4,310.16 ETC?
 106.1.2 FBC ADMIN SECT.
  
 14) NOTE: PLEASE PROVIDE A STRUCTURAL SUPPORT DETAIL
 FOR BOTH TRANSFORMERS.
 PLEASE KNOW THIS STRUCTURAL DETAIL WILL BE REVIEWED BY
 BUILDING REVIEWER.
 FBC 106.1.2
  
 15) NOTE: PLEASE SEE THERE ARE SHEETS WHICH INDICATE
 NOTES, HOWEVER THOSE NOTES ARE ACTUALLY CROSSED OUT ON
 SHEETS FOR NOTES.??
 PLEASE CLARIFY AND CORRELATE THIS.
 FBC 106.1.2
  
 16) NOTE: PLEASE SEE FBC 11-4.28, 11-4.28.2 AND .3(4)
 WHICH REQUIRE A MIN OF 75 CANDELAS AT ALL AREAS AS
 STATED FOR ADA. PLEASE SEE MIN LEVELS STATED FOR ADA ON
 PLANS MENTIONS 15CD?
 PLEASE KNOW ALL OF THESE AREAS WILL BE TESTED FOR
 MINIMUM LEVELS, PLEASE BE SURE THE DEVICES AS SHOWN AND
 INSTALLED WILL MEET TESTED LEVELS. PLEASE ADJUST NOTES
 ON PLANS AT THIS TIME.
  
 17) NOTE: PLEASE ALSO SEE WITH RESPECT TO THE NOTE #16
 ABOVE , PLEASE SEE PLANS REFERENCE 2002 BOCA, FOR CODE.
 PLEASE ADJUST.
 2004 FBC.
  
 18) NOTE: PLEASE PROVIDE INFORMATION FOR CONVEYOR
 SYSTEM, PLEASE PROVIDE INFORMATION ON ALL LISTINGS FOR
 EQUIPMENT BRING INSTALLED.
 PLEASE PROVIDE SPECS ON THE MCC.
 110.3, 90.7.
 FBC 106.1.2
  
 19) NOTE: PLEASE PROVIDE LOAD CALCULATIONS FOR THE
 MCC1. COULD NOT LOCATE ANY ON PLANS?
 220.31, LARGEST MOTOR LOADS ETC.
 215.3, 230.42
 FBC 106.3.5.1.2
  
 20) NOTE: PLEASE SEE POSSIBLE BUILDING FIRE REVIEW
 NOTES AS TRANSFORMER/ AND ELECTRICAL EQUIPMENT APPEAR
 TO BE LOCATED IN AN EGRESS CORRIDOR. PLEASE SEE THIS
 MAY OR MAY NOT BE PERMITTED AS SHOWN? IF THIS IS A
 RATED CORRIDOR, PLEASE KNOW, THIS EQUIPMENT WILL MOST
 LIKELY BE REQUIRED TO BE RELOCATED.
  
 21) NOTE: PLEASE SEE PANEL NOTES MENTIONS "LOCK-OFF"
 BREAKERS, PLEASE KNOW THESE TYPE OF LOCK OFF DEVICES
 SHALL BE AN INTEGRAL PART OF THE BREAKER AND SHALL NOT
 BE REMOVABLE WITHOUT THE REMOVAL OF SAID BREAKER. 90.7,
 110.3, 90.4
  
 22) NOTE: PLEASE SEE SOME OTHER AREAS INDICATED AS
 "FUTURE" AT THIS TIME MAY AFFECT THE INSTALLATIONS OF
 SOME ELECTRICLA EQUIPMENT AND OTHER EQUIPMENT ON PLANS
 AS SHOWN. PLEASE SEE NEC 500, AND OTHER NFPA'S RELEVANT
 TO ANY OTHER POSSIBLE SCOPE OF WORK WHICH WILL BE
 DECLARED AS HAZARDOUS AT THIS TIME OR AT A LATER TIME.
  
 ** PLEASE KNOW AS THERE IS INFORMATION WHICH HAS NOT
 YET BEEN SUBMITTED FOR REVIEW, THERE MAY BE COMMENTS ON
 NEXT REVIEW WHICH ARE NOT STATED IN THESE REVIEW
 NOTES.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
2006-10-23 06:46:18REVIEW IN PROGRESS
2006-10-22 19:46:04ONE SET IN ELEC FOR REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2007-03-22 Cont ID  
Sent By rchokshi Date 2007-03-22 Time 13:07 Rev Time 0.00
Received By rchokshi Date 2007-03-22 Time 13:02 Sent To  
Notes
2007-03-22 13:07:29ACCORDING TO E-MAIL FROM STEVE PAWLYKDATED 2/21/07,
 NO CHANGES WERE MADE AFTER LAST ENG REVIEW.THIS
 E-MAIL IS IN COMPUTER SYSTEM FOR OUR FUTURE
 RECORDS.THEREFORE, ENG REVIEW PASS.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-01-26 Cont ID  
Sent By rchokshi Date 2007-01-26 Time 11:01 Rev Time 0.00
Received By rchokshi Date 2007-01-26 Time 10:41 Sent To  
Notes
2007-01-26 11:01:28PLEASE EXPLAIN IN A LETTER EACH OF THE ITEMS BELOW AND
 IN DRAWING REVISION BLOCK,WHAT CHANGES YOU MADE AFTER
 11/13/06 OUR APPROVAL.
  
 1. ANY CHANGES IN STANDARDS NOTES OF CITY OF WPB ON
 DRAWINGSFOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY,
 PARKING, HANDICAP PARKING, PAINT ?
 2.ANY CHANGES IN DUMPSTER & ITS ENCLOSURE DETAILS ?
 LOCATION ON DWG, LOCATION MUST BE ACCESSIBLE FOR PICKUP
 TRUCK?.
 3. ANY CHANGES INFIRST FLOOR ELEVATION, CENTER LINE
 OF ROAD , SIDEWALK ELEVATION?MUST MEET FL BLDG CODE,
 PLEASE SHOW ON THE DRAWINGS.
 4. ANY CHANGES INSFWMD PERMIT? ANY CHANGES IN GEO
 TECH REPORT?
 5. ANY CHAGES IN STORM WATER CALCULATIONS, ? ANY
 CHANGES IN PERVIOUS AREA, LIKE GREEN, LAKES, ETC,
 IMPERVIOUS AREA CAL.?,
 6.ANY CHANGES IN THE SITE AREA, YOU ARE DEVELOPING FOR
 THIS PROJECT ? SO, WE CAN CHECK PERVIOUS, IMPERVIOUS
 CAL.
 7. ANY CHAGES IN CONNECTTING THE STORM WATER PIPES IN
 YOUR SITE? ITS DETAILS.
 8. ANY CHANGES IN STORM WATER PIPES AROUND YOUR SITE?
 SO, WE CANSEE THE BEST PIPE TO CONNECT WITH THE STORM
 WATERFROM ALL OTHER STORM WATER PIPES. PLEASE SHOW
 DETAIL OF THE CONTROL STRUCTURES WITH ELEVATIONS,
 NOTCHES, BLEEDING ELEVATION, ETC DID YOU CHANGE
 EXFILTRATION TRENCH ?
 9.ANY CHAGES INPOLLUTION PREVENTION DETAILS,CLOTHES
 USED FOR SILT ETC.?,PLAN MUSTPLANS SHOWSILT FENCE
 AROUND THE SITE
 10.ANY CHANGES INWATER & SEWER PLANS? MUST BE
 APPROVED FROM 45TH STREET (MANNY G.), UTILITY DEPT
 BEFORE WE APPROVED
 11.ANY CHANGES IN CATCH BASINS NEAREST YOUR SITE, AND
 AROUND YOUR SITE FOR STORM WATER DRAIN?
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2006-11-13 Cont ID  
Sent By rchokshi Date 2006-11-13 Time 13:33 Rev Time 0.00
Received By rchokshi Date 2006-11-13 Time 13:29 Sent To  
Notes
2006-11-13 13:32:51ACCORDING TO LETTER (E-MAIL) FROM STEVEN M. PAWLYK OF
 BOWER-SINGLETON DATED NOV 13, 06, THIS PERMIT IS
 COVERED UNDER PERMIT#06071716.SO, THIS IS PASSED
  
 RASIK CHOKSHI, 805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-04-19 Cont ID  
Sent By mawillia Date 2007-04-19 Time 18:45 Rev Time 0.00
Received By mawillia Date 2007-04-19 Time 16:46 Sent To  
Notes
2007-04-19 18:45:23*****APPROVED*****
  
  
 ALL COMMENTS FROM FROM PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;PLAN SHEETS A1.3, A2.1, E3.1, E6.2,
 FP-01, AND FP-02 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-04-03 Cont ID  
Sent By mawillia Date 2007-04-03 Time 13:48 Rev Time 0.00
Received By mawillia Date 2007-04-03 Time 12:36 Sent To  
Notes
2007-04-03 13:46:54****PROVISO*****
  
  
  
  
  
  
  
  
 20.FIRE ALARM SYSTEM IS TO BE CLASS A OR FULLY
 ADDRESSABLE.PLEASE CORRECT TYPOGRAPHICAL ERROR IN
 FIRE ALARM PLAN NOTE #3 (SEE SHEET E6.1 & E6.2);
 WORDING SHOULD BE ADDRESSABLE NOT ACCESSIBLE.....
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-01-30 Cont ID  
Sent By mawillia Date 2007-01-30 Time 10:26 Rev Time 0.00
Received By mawillia Date 2007-01-30 Time 10:25 Sent To  
Notes
2007-01-30 10:34:27*****DENIED*****
  
  
 COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW ARE STILL
 IN NEED OF ACKNOWLEDGING IN/ON THE SUBMITTED PLANS.
 PLEASE BE ADVISED THAT A COPY OF 11/06/2006'S COMMENTS
 ARE ATTACHED.
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-11-06 Cont ID  
Sent By mawillia Date 2006-11-06 Time 14:03 Rev Time 0.00
Received By mawillia Date 2006-11-06 Time 14:02 Sent To  
Notes
2006-11-06 14:36:09*****DENIED*****
  
  
  
 01.NFPA 101 - 2003 EDITION AND FLORIDA FIRE
 PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED.
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION SHALL COMPLY WITH NFPA241.
  
 03.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF.
  
 04.ALL PAVEMENT ROAD SYSTEMS SHALL BE CAPABLE OF
 SUPPORTING 32 TONS FOR FIRE EQUIPMENT.
  
 05.LANDSCAPING SHALL NOT OBSTRUCT OR INTERFERE WITH
 FIRE PROTECTION EQUIPMENT.PROPER CLEARANCES SHALL BE
 MAINTAINED AT ALL TIMES.
  
 06.SHOW/DISPLAY THE NUMERICAL ADDRESS OF THE BUILDING
 ON THE PROPER ELEVATION.AS PER WEST PALM BEACH CODE,
 THOSE NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND 1"
 IN WIDTH.IF A MONUMENT SIGN OR MARKEE IS REQUIRED, A
 NUMERICAL ADDRESS WILL ALSO BE POSTED.IF THERE ARE
 GOING TO BE SEVERAL ADDRESSED BUILDINGS WITHIN THE FED
 EX COMPLEX, A RANGE OF ADDRESSES FROM THE LOWEST TO THE
 HIGHEST WILL BE REQUIRED ON THE MONUMENT SIGN OR
 MARKEE.
  
 07.FIRE DEPARTMENT CONNECTIONS (FDC'S) SHALL BE
 POSITIONED SO THAT THEY CANNOT BE BLOCKED BY STORAGE,
 VESSELS, EQUIPMENT, ETC.
  
 08.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE
 DEPARTMENT CONNECTIONS.
  
 09.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK
 IS REQUIRED FOR DOUBLECHECK DETECTOR ASSEMBLY.
  
 10.KNOX BOX FOR THE BUILDING WILL BE REQUIRED. PLEASE
 CONTACT THE FIRE PREVENTION BUREAU AT (561) 804-4724
 FOR APPLICATIONS.
  
 11.WILL THERE BE SECURITY GATES TO THE PREMISES AND
 IF SO, HOW WILL THE MEANS OF EGRESS BE IMPACTED?
  
 12.PLEASE PROVIDE PRESCIPTIVE STRENGHT FOR ALL
 HANDRAILS / GUARDRAILS.
  
 13.ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA
 80.
  
 14.INTERIOR FINISH FOR WALLS AND CEILING IN EXITS AND
 EXIT ACCESS CORRIDORS SHALL BE CLASS "A" OR CLASS "B".
  
 15.LIFE SAFETY PLAN SHALL INCLUDE ALL COMMON PATHS OF
 TRAVEL TO EXITS.
  
 16.FIRE EXTINGUISHERS ARE TO BE RATED 2A-10BC.
  
 17.SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED
 FOR FIRE SPRINKLER AND FIRE ALARM SYSTEMS.
  
 18.FIRE SPRINKLER SYSTEM IS TO BE MONITORED.
  
 19.THE FIRE ALARM SHALL BE UL CERTIFIED FOR CENTRAL
 STATION SERVICE.
  
 20.FIRE ALARM SYSTEM IS TO BE CLASS A OR FULLY
 ADDRESSABLE.
  
 21.DELAYED-EGRESS LOCKS AND/ORACCESS-CONTROLLED
 EGRESS DOORS SHALL COMPLY WITH NFPA 101, CH. 7.2.1.6,
 SPECIAL LOCKING ARRANGEMENTS.
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-12-12 Cont ID  
Sent By adarroug Date 2007-12-12 Time 11:12 Rev Time 0.00
Received By adarroug Date 2007-12-12 Time 11:12 Sent To Z
Notes
2007-12-12 11:13:02TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-10-17 Cont ID  
Sent By adarroug Date 2007-10-17 Time 12:38 Rev Time 0.00
Received By adarroug Date 2007-10-17 Time 12:38 Sent To P
Notes
2007-10-17 12:39:20TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-10-05 Cont ID  
Sent By adarroug Date 2007-10-05 Time 14:51 Rev Time 0.00
Received By adarroug Date 2007-10-05 Time 14:51 Sent To E
Notes
2007-10-05 14:52:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-10-03 Cont ID  
Sent By adarroug Date 2007-10-03 Time 17:48 Rev Time 0.00
Received By adarroug Date 2007-10-03 Time 17:48 Sent To M
Notes
2007-10-03 17:48:22TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-06-19 Cont ID  
Sent By adarroug Date 2007-06-19 Time 10:25 Rev Time 0.00
Received By adarroug Date 2007-06-19 Time 10:25 Sent To P
Notes
2007-06-19 10:25:50TO "KSTEVENS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-10 Cont ID  
Sent By adarroug Date 2007-04-10 Time 14:52 Rev Time 0.00
Received By adarroug Date 2007-04-10 Time 14:52 Sent To  
Notes
2007-04-11 15:49:42TO "COMM" BD#12--PLANS ON RACK-6 ROLLS AND BINDERS
2007-04-10 14:52:34WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-28 Cont ID  
Sent By adarroug Date 2007-02-28 Time 16:04 Rev Time 0.00
Received By adarroug Date 2007-02-28 Time 16:04 Sent To  
Notes
2007-03-02 09:45:16TO "COMM" BD#13/PLANS ON RACK--5 ROLLS/BOOKS
2007-02-28 16:04:36WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-01 Cont ID  
Sent By adarroug Date 2006-11-01 Time 11:23 Rev Time 0.00
Received By kstevens Date 2006-11-01 Time 10:52 Sent To  
Notes
2007-01-04 08:22:171/4/06-TO "COMM" BD#5/ROLLED PLANS BY "BTROBAUG" DESK
2006-12-15 11:23:4512/8/06--WAITING FOR "COMM' BD
2006-10-17 08:42:18TO "COMM' BD#40
2006-09-19 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-10-20 Cont ID  
Sent By rregueir Date 2007-10-20 Time 18:34 Rev Time 0.00
Received By rregueir Date 2007-10-20 Time 18:34 Sent To PC
Notes
2007-10-20 18:34:20PIPE PENETRATIONS, SUBMITTAL

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-10-04 Cont ID  
Sent By hmoser Date 2007-10-04 Time 07:42 Rev Time 0.00
Received By hmoser Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-03-27 Cont ID  
Sent By rregueir Date 2007-03-27 Time 07:44 Rev Time 0.00
Received By rregueir Date 2007-03-26 Time 15:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-01-19 Cont ID  
Sent By pkrauss Date 2007-01-18 Time 15:07 Rev Time 0.00
Received By pkrauss Date 2007-01-18 Time 15:07 Sent To  
Notes
2007-01-18 15:27:02DENIED:
 RESPONSE TO COMMENTS FROM REVIEW DATED 10/20/06:
  
 COMMENT 1:OK
 COMMENT 2:OK
 COMMENT 3:RESPONSE INDICATES CO SENSORS ACTIVATION
 WILL BE AT 25 PPM.RESPONSE DOES NOT INDICATE
 MANUFACTURER SUBMITTAL DATA WITH REGARDS TO THE
 SENSORS.PLEASE NOTE, PLANS INDICATE FUME SENSORS
 MOUNTED AT 5 FT ABOVE FINISHED FLOOR WHEREAS THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS MAY DIFFER
 FROM THIS HEIGHT.PLEASE PROVIDE SUBMITTAL DATA ON THE
 SENORS.
  
 COMMENT 4 THROUGH 17:OK
  
 COMMENT 18: ALL ELECTRICAL & PLUMBING PLANS IN SOME OF
 THE PLAN SETS ARE MISSING SEAL, SIGNATURE AND DATE FROM
 THE ENGINEER OF RECORD AS REQUIRED BY FS 471.025 & FAC
 61G15-23.002.
  
 NEW COMMENTS - PROVISO:
 19.PLAN SHEET M3.1 KEYED NOTE 6 INIDCATES FANS WILL BE
 MOUNTED 36" ABOVE FINISHED FLOOR.PER 2004 FMC 303.4,
 EQUIPMENT SHALL NOT BE INSTALLED IN A LOCATION WHERE
 SUBJECT TO MECHANICAL DAMAGE UNLESS PROTECTED BY
 APPROVED BARRIERS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-20 Cont ID  
Sent By pkrauss Date 2006-10-20 Time 13:39 Rev Time 0.00
Received By pkrauss Date 2006-10-20 Time 11:32 Sent To  
Notes
2006-10-20 15:28:51DENIED:
 1.PLAN SHEET M1.1 INDICATES THE DESIGN IS TO THE
 INTERNATIONAL MECHANICAL CODE.THIS SHOULD READ 2004
 FLORIDA BUILDING CODE/MECHANICAL.
  
 2.PLAN SHEET M3.1 "KEYED NOTES" NUMBER 6 INDICATES
 THE INTAKE LOUVER FOR MAKE-UP AIR IS LOCATED 36" A.F.F.
 THIS APPEARS TO BE LOCATED IN A LOADING OR PARKING
 AREA.PER 2004 401.5.1 INTAKE OPENINGS SHALL BE
 LOCATED A MINIMUM OF 10 FT FROM ANY NOXIOUS CONTAMINANT
 SUCH AS PARKING LOTS, STREETS, ALLEYS, AND LOADING
 DOCKS.PLEASE CLARIFY.
  
 3.PLAN SHEET M3.1 NOTE 3 INDICATES FUME SENSOR
 MOUNTED 5 FT A.F.F., MATCH TO EXISTING & CONNECT TO
 EXISTING SYSTEM.THE PERMIT APPLICATION INDICATES THIS
 IS A NEW BUILDING, WHAT WILL BE "EXISTING"? PROVIDE
 MANUFACTURE SUBMITTAL DATA FOR THE SENSOR.AT WHAT
 PARTS PER MILLION WILL THE SENSOR BE SET AT (25 PPM -
 PER 2004 FMC 404.1).
  
 4.PLEASE INDICATE HOW THE REQUIREMENT FOR
 VENTILATION RATE OF .05 CFM PER SQUARE FT WHEN THE FANS
 WILL NOT RUN CONTINUOUSLY.
  
 5.PLAN SHEET A2.1 DETAIL 1 (WEST ELEVATION), WHAT
 WILL BE USING THE DRIVE-IN DOOR, VEHICLES, FORK-LIFTS,
 ETC.
  
 6.PLAN SHEET M3.1, PLEASE CLARIFY WHAT THE "SPECIAL
 HANDLING CAGE" WILL BE UTILIZED FOR.EF-10IS NOT
 INDICATED ON THE FAN SCHEDULE ON PLAN SHEET.PLAN
 SHEET M5.2 INDICATES AN EXHAUST FAN TO THE HOOD, IS
 THIS EF-10?
  
 7.PLEASE INDICATE WHAT THE FUME HOOD WILL BE USED
 FOR.
  
 8.PLAN SHEET M3.2 INDICATES DUCT SMOKE DETECTORS IN
 THE RETURN AIR DUCT.PER 2004 FMC 606.2.1, SMOKE
 DETECTORS ARE REQUIRED IN THE SUPPLY AIR DUCT.
  
 9.PLEASE PROVIDE A DETAIL OF THE RTU ATTACHMENT TO
 THE ROOF.NO SUPPORT IS INDICATED ON THE STRUCTURAL,
 ARCHITECTURAL OR MECHANICAL PLANS.SHOW COMPLIANCE
 WITH 2004 FBC 1509.7.
  
 10.PROVIDE LOCATION OF THE CONDENSING UNIT (GROUND OR
 ROOF).
  
 11.PLEASE INDICATE ACCESS TO THE EQUIPMENT LOCATED ON
 THE ROOF.PER 2001 FMC 306.5, EQUIPMENT ON LOCATED ON
 ROOF OR ELEVATED STRUCTURE AT A HEIGHT GREATER THAN 16
 FT SHALL HAVE A PERMANENT MEANS OF ACCESS.PLEASE
 NOTE,ACCESS SHALL NOT REQUIRE CLIMBING OVER
 OBSTRUCTIONS GREATER THAN 30 INCHES OR WALKING ON ROOFS
 HAVING A SLOPE GREATER THAN 4/12 PITCH.
  
 12.PER 2004 FMC 306.6 ROOFS HAVING GREATER THAN 25%
 SLOPE AND HAVING AN EDGE MORETHAN 30 INCHES ABOVE GRADE
 AT SUCH EDGE, A LEVEL PLATFORM SHALL BE PROVIDED ON
 EACH SIDE OF THE APPLIANCETO WHICH ACDESS IS REQUIRED
 BY THE MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR
 SERVICE, REPAIR OR MAINTENANCE.THE PLATFORM SHALL NOT
 BE LESS THAN 30 INCHES IN ANY DIMENSION AND BE PROVIDED
 WITH GUARDS IN ACCORDANCE WTIH SECTION 304.10.
  
 13.PLEASE PROVIDE MOUNTING DETAIL FOR SF1 THROUGH
 7.13.
  
 14.PLANS DO NOT INDICATE OVERFLOW PROTECTION AS
 REQUIRED IN 2004 FMC 307.2.3.
  
 15.PLAN SHEET A0,2 INDICATES "FUTURE FUEL ISLAND &
 MAITENANCE GARAGE"WILL THIS BE UNDER A SEPARATE
 PERMIT?
  
 16.PLEASE PROVIDE OUTSIDE AIR CALCULATIONS IN
 ACCORDANCE WITH 2004 FMC TABLE 403.3.
  
 17.PLEASE PROVIDE ENERGY CALCULATIONS IN ACCORDANCE
 WITH 2004 FBC CHAPTER 13 SUB-CHAPTER 4.
  
 18.PER FAC 61G15-23.001(1), SEALS ARE TO BE EMBOSSED
 (RAISED) TYPE,STAMPS ARE NOT ACCEPTABLE.ENGINEERS
 SHALL LEGIBLY INDICATE NAME, ADDRESS, AND NUMBER ON
 EACH SHEET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].
  
  
  

Review Stop P PLUMBING
Rev No 6 Status F Date 2007-11-13 Cont ID  
Sent By kstevens Date 2007-11-13 Time 12:59 Rev Time 0.00
Received By kstevens Date 2007-11-13 Time 12:59 Sent To  
Notes
2007-11-13 12:59:37REVISION DENIED. SDR-35 NOT FOR INSIDE THE BUILDING.

Review Stop P PLUMBING
Rev No 5 Status P Date 2007-06-20 Cont ID  
Sent By kstevens Date 2007-06-20 Time 17:54 Rev Time 0.00
Received By kstevens Date 2007-06-20 Time 17:54 Sent To  
Notes
2007-06-20 17:56:24REVISIONS OK - REVISIONS TO SHEETS P1.1, P3.1, P7.1 &
 P8.1. SEE PSK-1, PSK-2, PSK-3 & PSK,4.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-03-21 Cont ID  
Sent By kstevens Date 2007-03-21 Time 10:55 Rev Time 0.00
Received By kstevens Date 2007-03-21 Time 10:55 Sent To  
Notes
2007-03-21 10:57:40 
  
 PASSED/PROVISO
  
 ONLY 50% OF THE DRINKING FOUNTAINS TO BE ACCESSIBLE.
 50% SHALL BE AT NORMAL HEIGHT FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
  
  
  
  
 ..

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-03-19 Cont ID  
Sent By kstevens Date 2007-03-19 Time 10:45 Rev Time 0.00
Received By kstevens Date 2007-03-19 Time 10:45 Sent To  
Notes
2007-03-19 10:51:03DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 MUNICIPAL CODE
  
 ***FROM PREVIOUS REVIEWS****
  
 1. ALL ARCHITECTURAL SHEETS. THE BUSINESS LICENSE
 NUMBER IS REQUIRED IN THE TITLE BLOCK PER FAC
 61G1-16.004(2) & FS 481.2055.
 ****RESPONSE NOTED, BUT COMMENT WAS NOT ADDRESSED.
 ******NO RESPONSE, NOT ADDRESSED
  
 2. OK
  
 3. ALL M,E,P SHEETS. A CERTIFICATE OF AUTHORIZATION IS
 REQUIRED FOR THE ENGINEERING COMPANY PER FAC
 61G15-23.002(2) & FS 471.025. - THE SIGNATURE OF THE
 ENGINEER IS REQUIRED ON THE SEAL. IT APPEARS TO BE AN
 INITIAL AND NOT A SIGNATURE. PLEASE PROVIDE A SIGNED,
 SEALED, DATED, NOTORIZED LETTER INDICATING THE LEGAL
 SIGNATURE OF THE ENGINEER FOR OUR FILES. FAC
 61G15-23.002(1) & FS 471.025.
 ****RESPONSE NOTED, BUT NOT COMPLETLY ADDRESSED. THE
 CERTIFICATE OF AUTHORIZATION NUMBER (EB) IS NOT SHOWN
 ON THE TITLE BLOCK OF THE ENGINEER. ALSO THE SIGNED,
 SEALED, NOTORIZED LETTER REQUESTED INDICATING THE LEGAL
 SIGNATURE FOR OUR FILES HAS NOT BEEN SUBMITTED.
 ******RESPONSE NOTED, BUT THE SIGNED, SEALED, DATED,
 NOTORIZED LETTER REQUESTED SHOWING THE LEGAL SIGNATURE
 HAS NOT BEEN SUBMITTED.
  
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
  
 *************NEW COMMENTS*************
  
 1B. PER SECTION 11-4.1.3(10)(B) 50% OF ALL DRINKING
 FOUNTAINS PROVIDED SHALL COMPLY WITH 11-4.15. PLANS
 SHOW 7 DRINKING FOUNTAINS, BUT ONLY 1, (P8) COMPLIES. A
 MINIMUM OF 4 DRINKING FOUNTAINS SHALL COMPLY WITH
 SECTION 11-4.15 & ALL SUBSECTIONS.
 ******RESPONSE NOTED, BUT WITH ALL DRINKING FOUNTAINS
 BEING AT ACCESSIBLE HEIGHT, SECTION 11-4.1.3(10)(A),
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING NOW NEEDS TO BE ADDRESSED.
  
 2B. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6713
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-01-24 Cont ID  
Sent By kstevens Date 2007-01-24 Time 18:48 Rev Time 0.00
Received By kstevens Date 2007-01-24 Time 18:48 Sent To  
Notes
2007-01-24 19:00:39DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 MUNICIPAL CODE
  
 1. ALL ARCHITECTURAL SHEETS. THE BUSINESS LICENSE
 NUMBER IS REQUIRED IN THE TITLE BLOCK PER FAC
 61G1-16.004(2) & FS 481.2055.
 ****RESPONSE NOTED, BUT COMMENT WAS NOT ADDRESSED.
  
 2. ALL M,E,P SHEETS. SEAL REQUIRED TO BE AN EMBOSSING
 TYPE SEAL, AND THE SEAL SHALL CONTAIN THE WORD
 "LICENSE" EFFECTIVE FEBRUARY 5, 2004, BUT A GRACE
 PERIOD TO JANUARY 1, 2006 WAS GIVEN. PLEASE CHANGE SEAL
 AND MAKE SURE IT IS A RAISED, IMPRESSION TYPE SEAL.
 (SEE ATTACHED SHEET)FAC 61G15-23.001 & FS 471.025.
 ****RESPONSE NOTED, BUT NOT ALL SHEETS FROM ALL THREE
 SETS HAVE BEEN SIGNED, SEALED, DATED. RECHECK SOME
 SHEETS THAT HAVE THE NEW SEAL AFFIXED AS NOT ALL THE
 INFORMATION FROM THE SEAL IS LEGIBLE.
  
 3. ALL M,E,P SHEETS. A CERTIFICATE OF AUTHORIZATION IS
 REQUIRED FOR THE ENGINEERING COMPANY PER FAC
 61G15-23.002(2) & FS 471.025. - THE SIGNATURE OF THE
 ENGINEER IS REQUIRED ON THE SEAL. IT APPEARS TO BE AN
 INITIAL AND NOT A SIGNATURE. PLEASE PROVIDE A SIGNED,
 SEALED, DATED, NOTORIZED LETTER INDICATING THE LEGAL
 SIGNATURE OF THE ENGINEER FOR OUR FILES. FAC
 61G15-23.002(1) & FS 471.025.
 ****RESPONSE NOTED, BUT NOT COMPLETLY ADDRESSED. THE
 CERTIFICATE OF AUTHORIZATION NUMBER (EB) IS NOT SHOWN
 ON THE TITLE BLOCK OF THE ENGINEER. ALSO THE SIGNED,
 SEALED, NOTORIZED LETTER REQUESTED INDICATING THE LEGAL
 SIGNATURE FOR OUR FILES HAS NOT BEEN SUBMITTED.
  
 4. SHT A3.4 SHOW COMPLIANCE WITH THE FOLLOWING:
 11-4.16.5 FLUSH CONTROLS, 11-4.18.4 FLUSH CONTROLS,
 11-4.19.2 CLEARANCES, 11-4.19.4 EXPOSED PIPES &
 SURFACES, 11-4.19.5 FAUCETS.
 ****RESPONSE NOTED, BUT COMMENTS ARE NOT ADDRESSED.
 (SEE DETAIL 13 FLUSH CONTROLS FOR 11-4.16.5- ALL
 OTHER INFORMATION NOT INDICATED).
  
 5. OK
  
 6. SHT P3.1 THE SAND/OIL INTERCEPTOR SHALL BE SIZED AND
 APPROVED BY THE UTILITY DEPT. CONTACT LYNN MASSON,
 ENVIRONMENTAL COMPLIANCE AT (561) 822-2271, OR FAX
 (561) 822-2279, OR E-MAIL [email protected]. WASTE ORD.
 3434.
 ****RESPONSE NOTED. PLEASE SEE ATTACHED SHEET FROM MR.
 RODNEY COMPO INDICATING THE APPROVED MINIMUM
 RECOMMENDED SIZE OF INTERCEPTOR. THIS SHALL BE
 INDICATED ON THE PLANS. ALSO A ZURN MODEL Z1188 IS
 INDICATED. PLEASE INDICATE IF THIS IS THE MAKE & MODEL
 INTERCEPTOR BEING INSTALLED. IF NOT PLEASE INDICATE
 MAKE & MODEL OF INTERCEPTOR TO BE INSTALLED AND SUBMIT
 MANUF. SPECIFICATION SHEETS.
  
 7. OK
  
 8. SHT P8.2 WATER RISER DIAGRAM. SUBMIT A WATER RISER
 DIAGRAM IN AN ISOMETRIC FORM THAT REFLECTS THE FLOOR
 PLAN. SHOW ALL PIPE SIZES, VALVES, AND WATER HAMMER
 ARRESTORS REQUIRED BY SECTION 604.9 LOCATED IN AN
 "EFFECTIVE RANGE" (NOT IN THE CEILING). SECTION
 106.1.3. - FULL OPEN VALVES ARE REQUIRED ON ALL WATER
 DOWN-FEED LINES. SECTION 606.1(2).
 ****RESPONSE NOTED, BUT SOME FULL OPEN VALVES ARE NOT
 INDICATED ON THE WATER DOWN-FEED LINES TO THE HOSE
 BIBBS.
  
 *************NEW COMMENTS*************
  
 1B. PER SECTION 11-4.1.3(10)(B) 50% OF ALL DRINKING
 FOUNTAINS PROVIDED SHALL COMPLY WITH 11-4.15. PLANS
 SHOW 7 DRINKING FOUNTAINS, BUT ONLY 1, (P8) COMPLIES. A
 MINIMUM OF 4 DRINKING FOUNTAINS SHALL COMPLY WITH
 SECTION 11-4.15 & ALL SUBSECTIONS.
  
 2B. SHT P4.1 PREVIOUSLY, THE RPZV BACKFLOW WAS LOCATED
 AT THE METER FOR THIS BUILDING. IS THE BACKFLOW AT THE
 METER TO BE DELETED? IS THERE A MASTER METER AND RPZV
 BACKFLOW FOR THE PROJECT? IF NOT, THE BACKFLOW WILL
 HAVE TO BE LOCATED AS NEAR THE METER AS POSSIBLE, ON
 PRIVATE PROPERTY.PLEASE CLARIFY.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6713
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-10-28 Cont ID  
Sent By kstevens Date 2006-10-28 Time 10:19 Rev Time 0.00
Received By kstevens Date 2006-10-28 Time 10:19 Sent To  
Notes
2006-10-28 11:23:11DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 MUNICIPAL CODE
  
 1. ALL ARCHITECTURAL SHEETS. THE BUSINESS LICENSE
 NUMBER IS REQUIRED IN THE TITLE BLOCK PER FAC
 61G1-16.004(2) & FS 481.2055.
  
 2. ALL M,E,P SHEETS. SEAL REQUIRED TO BE AN EMBOSSING
 TYPE SEAL, AND THE SEAL SHALL CONTAIN THE WORD
 "LICENSE" EFFECTIVE FEBRUARY 5, 2004, BUT A GRACE
 PERIOD TO JANUARY 1, 2006 WAS GIVEN. PLEASE CHANGE SEAL
 AND MAKE SURE IT IS A RAISED, IMPRESSION TYPE SEAL.
 (SEE ATTACHED SHEET)FAC 61G15-23.001 & FS 471.025.
  
 3. ALL M,E,P SHEETS. A CERTIFICATE OF AUTHORIZATION IS
 REQUIRED FOR THE ENGINEERING COMPANY PER FAC
 61G15-23.002(2) & FS 471.025. - THE SIGNATURE OF THE
 ENGINEER IS REQUIRED ON THE SEAL. IT APPEARS TO BE AN
 INITIAL AND NOT A SIGNATURE. PLEASE PROVIDE A SIGNED,
 SEALED, DATED, NOTORIZED LETTER INDICATING THE LEGAL
 SIGNATURE OF THE ENGINEER FOR OUR FILES. FAC
 61G15-23.002(1) & FS 471.025.
  
 4. SHT A3.4 SHOW COMPLIANCE WITH THE FOLLOWING:
 11-4.16.5 FLUSH CONTROLS, 11-4.18.4 FLUSH CONTROLS,
 11-4.19.2 CLEARANCES, 11-4.19.4 EXPOSED PIPES &
 SURFACES, 11-4.19.5 FAUCETS.
  
 5. SHT P1.1 FIXTURE CONNECTION SCHEDULE. FLOOR DRAINS
 ARE NOT APPROVED INDIRECT WASTE RECEPTORS. EITHER A
 FLOOR SINK OR A HUB DRAIN IS REQUIRED FOR THE INDIRECT
 WASTE FROM THE ICE MAKER, P-11. PLEASE CORRECT
 REFERENCE, AND IF SHOWN ON THE FLOOR PLAN AND THE SANT.
 RISER DIAGRAM, CHANGE THOSE ALSO. SECTIONS 802.3 &
 802.3.2.
  
 6. SHT P3.1 THE SAND/OIL INTERCEPTOR SHALL BE SIZED AND
 APPROVED BY THE UTILITY DEPT. CONTACT LYNN MASSON,
 ENVIRONMENTAL COMPLIANCE AT (561) 822-2271, OR FAX
 (561) 822-2279, OR E-MAIL [email protected]. WASTE ORD.
 3434.
  
 7. SHT P8.1 SANITARY RISER DIAGRAM. SUBMIT A SANITARY
 RISER DIAGRAM IN AN ISOMETRIC FORM THAT REFLECT THE
 FLOOR PLAN. SHOW ALL PIPE SIZES, VENTS, TRAPS AND
 INDICATE THE DRAINAGE FIXTURE UNITS AS THEY ACCUMULATE
 IN THE SYSTEM. SECTION 106.1.3.
  
 MAIN ENTRY: ISO?MET?RIC
 PRONUNCIATION: "I-S&-'ME-TRIK
 FUNCTION: ADJECTIVE
 1 : OF, RELATING TO, OR CHARACTERIZED BY EQUALITY OF
 MEASURE; ESPECIALLY : RELATING TO OR BEING A
 CRYSTALLOGRAPHIC SYSTEM CHARACTERIZED BY THREE EQUAL
 AXES AT RIGHT ANGLES.
  
 8. SHT P8.2 WATER RISER DIAGRAM. SUBMIT A WATER RISER
 DIAGRAM IN AN ISOMETRIC FORM THAT REFLECTS THE FLOOR
 PLAN. SHOW ALL PIPE SIZES, VALVES, AND WATER HAMMER
 ARRESTORS REQUIRED BY SECTION 604.9 LOCATED IN AN
 "EFFECTIVE RANGE" (NOT IN THE CEILING). SECTION
 106.1.3. - FULL OPEN VALVES ARE REQUIRED ON ALL WATER
 DOWN-FEED LINES. SECTION 606.1(2).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6713
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2007-12-13 Cont ID  
Sent By eschneid Date 2007-12-13 Time 11:57 Rev Time 0.00
Received By eschneid Date 2007-12-13 Time 11:57 Sent To  
Notes
2007-12-13 12:00:59NOTE THAT THE LANDSCAPE PLAN SHALL BE THE GOVERNING
 DOCUMENT FOR THIS REVISION TO THE FOUNDATION LANDSCAPE.

Review Stop Z ZONING
Rev No 3 Status P Date 2007-03-27 Cont ID  
Sent By btrobaug Date 2007-03-27 Time 18:06 Rev Time 0.00
Received By btrobaug Date 2007-03-27 Time 18:06 Sent To  
Notes
2007-03-27 18:07:17OK PER ERIC SCHNEIDER./WRT.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-01-22 Cont ID  
Sent By eschneid Date 2007-01-22 Time 16:06 Rev Time 0.00
Received By eschneid Date 2007-01-22 Time 16:06 Sent To  
Notes
2007-01-22 16:06:51FAILED
  
 1) ALL APPLICABLE CONDITIONS OF ORDINANCE NO. 3987-06
 SHALL BE SATISFIED, SPECIFICALLY:
  
 A) A TRAFFIC STATEMENT, PREPARED BY A LICENSED TRAFFIC
 ENGINEER, SHALL BE SUBMITTED TO THE PLANNING & ZONING
 AND CONSTRUCTION SERVICES DEPTS. OUTLINING THE NUMBER
 OF DAILY TRIPS, AM TRIPS AND PM TRIPS GENERATED BY THE
 FEDEX GROUND FACILITY.
  
 2) PROVIDE A RECORDED COPY OF THE PLAT.
  
 3) THE BOWYER SINGLETON PLANS AND THE LANDSCAPE PLANS
 SHALL BE REVISED TO REFLECT THE ADA SIDEWALK/ROUTE FROM
 THE EASTERNMOST DISABLED PARKING SPACE SHOWN ON THE
 ARCHITECT'S SITE PLAN FOR THE FEDEX FREIGHT FACILITY.
  
 4) THE CORTLAN MORAN AND LANDSCAPE PLANS SHALL BE
 REVISED TO SHOW ALL OF THE "ISLAND FLUMES" AS DEPICTED
 ON THE BOWYER SINGLETON PLANS.
  
 5) PARKING DETAIL ON BOWYER SINGLETON SHEET 13 OF 29
 SHALL SHOW 2 FEET FROM THE CURB TO THE BACK OF THE
 WHEEL STOP, NOT 2 FEET TO THE MIDDLE OF THE WHEEL
 STOP.
  
 6) A PARKING TABLE IS REQUIRED.THE 1ST REVISION
 RESPONSE STATED THERE IS A PARKING TABLE BUT FAILED TO
 IDENTIFY WHICH PLAN CONTAINED IT.
  
 7) THE PROPERTY LINE SHOWN ON THE CORTLAN MORAN SHEET
 A0.2 AND ON BOWYER SINGLETON SHEET 4 OF 29 IS SHOWN
 INCORRECTLY AT THE CUL-DE-SAC.
  
 8) THE SQUARE FOOTAGE LISTED FOR THE PHASE I BUILDING
 DIFFERS ON CORTLAN MORAN PLANS (97,298) AND BOWYER
 SINGLETON PLANS (97,297).
  
 9) PLEASE RESPOND IN WRITING TO THE COMMENTS ABOVE.
  
 ERIC SCHNEIDER (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-11-01 Cont ID  
Sent By eschneid Date 2006-11-01 Time 13:36 Rev Time 0.00
Received By eschneid Date 2006-11-01 Time 13:36 Sent To  
Notes
2006-11-01 14:15:50FAILED
  
 1) ALL APPLICABLE CONDITIONS OF ORDINANCE NO. 3987-06
 SHALL BE SATISFIED.
  
 A) A MINOR AMENDMENT IS REQUIRED TO:
  
 I) SHOW ALL IMPROVEMENTS OUTSIDE OF THE 12 FOOT WIDE
 UTILITY EASEMENT.
  
 II) CORRECT THE FEDERAL EXPRESS FREIGHT ADA PARKING (OR
 A LETTER FROM THE CONSTRUCTION SERVICES DEPT. STATING
 THAT THE PARKING AS SHOWN MEETS ADA REQ.)
  
 III) SHOW THE REQUIRED NOISE BARRIER ALONG THE EASTERN
 PROPERTY LINE OF PREMIER PARK OF COMMERCE.
  
 B) A TRAFFIC STATEMENT, PREPARED BY A LICENSED TRAFFIC
 ENGINEER, SHALL BE SUBMITTED TO THE PLANNING & ZONING
 AND CONSTRUCTION SERVICES DEPTS. OUTLINING THE NUMBER
 OF DAILY TRIPS, AM TRIPS AND PM TRIPS GENERATED BY THE
 FEDEX GROUND FACILITY.
  
 2) THE PLAT IS REQUIRED TO BE RECORDED.
  
 3) BOWYER SINGLETON SITE PLANS (SPECIFICALLY SHEET
 3-29) ARE NOT THE LATEST VERSIONS APPROVED BY ORD. NO.
 3987-06.
  
 4) NO LANDSCAPE PLAN SUBMITTED - PLEASE VERIFY THAT
 WHEN SUBMITTED IT REFLECTS THE MINOR AMENDMENT CHANGES
 LISTED IN 1)A)III) ABOVE.
  
 5) PARKING TABLE IS REQUIRED.
  
 6) THE PARKING DETAIL ON CORTLAN MORAN SHEET A0.2 IS
 INCORRETCT.PLEASE USE OR REFERENCE THE DETAIL
 PROVIDED BY BOWYER SINGLETON ON SHEET 13 OF 29.
  
 ERIC SCHNEIDER (561) 822-1435.