Plan Review Details - Permit 06090672
Plan Review Stops For Permit 06090672
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-10-10 Cont ID  
Sent By rmcdouga Date 2006-10-10 Time 15:10 Rev Time 0.00
Received By rmcdouga Date 2006-10-10 Time 15:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-11-28 Cont ID  
Sent By dpalmer Date 2006-11-28 Time 09:54 Rev Time 0.00
Received By dpalmer Date 2006-11-28 Time 08:30 Sent To  
Notes
2006-11-28 09:58:50***********UNSAT *************
  
 PUBLIX GENERATOR
 831 VILLAGE, #319
  
 ** PLEASE SEE THE SAME PLANS AS PREVIOUSLY SUBMITTED
 ARE SUBMITTED BACK WITH OUT ANY CHANGES.
  
 1) NOTE:PLEASE SEE THE VALUE HAS BEEN ADJUSTED.
 PLEASE SEE AN AMOUNT OF FEES DUE ARE $1975.80.
 THIS IS DUE BEFORE PLANS CAN BE PICKED UP.
  
 2) NOTE:PLEASE SEE NOTE FROM PERVIOUS REVIEW WITH
 RESPECT TO THE EQUIPMENT SPECS. PLEASE SEE NONE WERE
 SUBMITTED IN PERMIT APPLICATION PACKAGE. PLEASE SEE
 NOTE BELOW WAS FROM PREVIOUS REVIEW.
 THE EQUIPMENT ON THE PREVIOUS PROJECT HAS NOT BEEN
 FINALIZED AND THERE IS STILL QUESTION ON THE
 EQUIPMENT.
  
 ** PREVIOUS NOTE **
 PLEASE SUBMIT SPECS/MANUFACTURE CUT SHEETS.APS/ ATS
 DO NOT INDICATE THE REQUIRED MEANS OF DISCONNECT AS
 REQUIRED BY 230.76, 230.79, 225.31-39.
 PLEASE SEE A MANUAL MEANS OF DISCONNECT COULD NOT BE
 LOCATED RATED FOR THE LOAD SERVED ON THE OUTSIDE OF
 EQUIPMENT SUBMITTED.
 THIS WAS NEVER VERIFIED FROM PREVIOUS PERMIT PULLED FOR
 PREVIOUS PROJECT.
 NO PERMITS WILL BE RELEASED UNLESS THIS IS VERIFIED ON
 ALL SUBMITTED SPECS AND PLANS SUBMITTED BEFORE PERMIT
 IS ISSUED.
 PLEASE SEE ALL EQUIPMENT SHALL BE LISTED FOR USE.90.7,
 110.3
  
 3) NOTE: PLEASE SEE THE RELAY DEVICE AS BEING NOTED IN
 THE RESPONSE LETTER IS NOT AN ACCEPTABLE MEANS OF OCP
 AS NOTED IN THE RESPONSE LETTER.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE INDICATE THE OCP AT THE
 GEN. PLEASE SEE 445.13 AS IT HAS COME TO OUR ATTENTION
 ON A PREVIOUS PROJECT THAT THE GEN MAY NOT CONTAIN OCP
 AND CAN NOT BE VERIFIED AT THIS TIME.
  
 4) NOTE:PLEASE SUBMIT AND INDICATE ALL LOAD
 CALCULATIONS OR HIGHEST DEMAND LOADS ON PLANS. MAY NOT
 BE IN RESPONSE LETTER AS THE ENGINEER OF RECORD SHALL
 SIGN, DATE AND SEAL INFORMATION PROVIDED. PLEASE ADJUST
 PLANS AND INCLUDE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NO LOAD CALCULATIONS WERE SUBMITTED FOR
 REVIEW. PLEASE SUBMIT.
 PLEASE SUBMIT AND INDICATE ANY LOAD SHEDDING DETAILS IF
 APPLICABLE.
 702.5, 220
  
 5) NOTE: PLEASE SEE FBC CHAPTER 27, AS THIS HAS NOT
 BEEN REVISED TO INCLUDE AN EXCEPTION FOR EXCLUSION OF
 OPTIONAL STAND-BY SYSTEMS. PLEASE SEE2002 NFPA-70, 2002
 NFPA-110.
 PLEASE SEE PLANS SHALL INDICATE ALL RELEVANT CODES. **
 PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS SHALL INDICATE THE CURRENT CODES IN
 EFFECT FOR INSTALLATION AS FOLLOWS.
 PLEASE SEE FBC 2004 CHAPTER 27 FOR ADOPTED CODES
 RELEVANT TO POWER GENERATORS.
  
  
 6) NOTE: PLEASE CLARIFY THE COMPLETE GROUNDING
 ELECTRODE SYSTEM, PLEASE CLARIFY AND SHOW THE COLD
 WATER PIPE, SPRINKLER ETC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE APS/ATS IS BECOMING THE NEW FIRST MEANS
 OF DISCONNECT HOWEVER THE NEW GROUNDING ELECTRODE
 SYSTEMS DOES NOT SEEM TO BE COMPLETE AS PER 250.50.
 PLEASE SEE GROUNDING DETAIL MENTIONS NEW SLAB STEEL
 WHICH IS OK, HOWEVER PLEASE INDICATE ATTACHMENT. THESE
 NEW SLAB/STEEL ATTACHMENTS DO NOT MEET THE MIN
 REQUIREMENTS.
 PER 250.50,250.52, 250.104
 IF SLAB STEEL IS ONLY BEING BONDED THEN PLEASE
 INDICATE.
 PLEASE COMPLETE GROUNDING ELECTRODE SYSTEM(S) AND
 BONDING FOR ALL AS ABOVE.
  
 7) NOTE: PLEASE SEE RESPONSE NOW MENTIONS THIS UNIT
 BEING A BI-FUEL UNIT, HOWEVER THE MANUFACTURE SPECS/CUT
 SHEETS SUBMITTED WERE NOT CHANGED, INFORMATION FOR THIS
 SYSTEM WAS NOT SUBMITTED AND GAS RISER INFORMATION WAS
 NOT SUBMITTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW, BASED ON A PREVIOUS PROJECT, IS THIS
 UNIT GOING TO BE "BI-FUEL"??
 IF SO, SUBMIT ALL INFORMATION AND SPECS ON UNIT(S).
 90.7, 110.3
  
  
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-06 Cont ID  
Sent By dpalmer Date 2006-10-06 Time 14:59 Rev Time 0.00
Received By dpalmer Date 2006-10-06 Time 14:59 Sent To  
Notes
2006-10-06 00:00:00***********UNSAT *************
  
 PUBLIX GENERATOR
 831 VILLAGE, #319
  
 1) NOTE:PLEASE ADJUST VALUE FOR
 COMPLETE SCOPE OF WORK BEING APPLIED
 FOR. THE VALUE OF $10K ON PERMIT
 APPLICATION AUBMITTED IS EXTREMELY LOW
 PLEASE KNOW, THAT VALUE SHALL BE
 ALL LABOR AND MATERIALS EVEN IF
 MATERIALS ARE OWNER SUPPLIED. PLEASE SEE
 VALUE FOR LABOR AND INSTALLATION IS WAY
 LOW FOR SCOPE PF WORK. PLEASE SEE FBC
 2004, ADMINISTRATIVE CODE SECTION 108.3
 AS ADOPTED BY THE CITY OF WEST PALM
 BEACH.
 PLEASE KNOW, A VALUE WILL BE ASSESSED
 USING THE MARSHALL'S& SWIFT GUIDE.
 PLEASE KNOW, UNDER CONTRACTING LAWS AND
 RULES SET UP AND ADOPTED INTO FLORIDA
 STATUES, 489, FBC ADMINISTRATIVE SECTION
 105.5.1 ANY INFORMATION PROVIDED ON
 OFFICAL PERMIT APPLICATION IF KNOWINGLY
 BEING FALSIFIED CAN VOID/REVOKE SUCH
 PERMIT/ APPLICATION.
  
 2) NOTE: PLEASE KNOW, ANY SYSTEMS
 LOCATED IN A FLOOD ZONE "A" WILL BE
 REQUIRED TO BE MOUNTED AT A MIN OF 6"
 ABOVE BFE. PLEASE SEE BUILDING REVIEW
 COMMENTS.
  
 3) NOTE: PLEASE SUBMIT SPECS/MANUFACTURE
 CUT SHEETS.APS/ ATS DO NOT INDICATE
 THE REQUIRED MEANS OF DISCONNECT AS
 REQUIRED BY 230.76,230.79,225.31-39.
 PLEASE SEE A MANUAL MEANS OF DISCONNECT
 COULD NOT BE LOCATED RATED FOR THE LOAD
 SERVED ON THE OUTSIDE OF EQUIPMENT
 SUBMITTED.
 THIS WAS NEVER VERIFIED FROM PREVIOUS
 PERMIT PULLED FOR PREVIOUS PROJECT.
 NO PERMITS WILL BE RELEASED UNLESS THIS
 IS VERIFIED ON ALL SUBMITTED SPECS AND
 PLANS SUBMITTED BEFORE PERMIT IS ISSUED.
 PLEASE SEE ALL EQUIPMENT SHALL BE LISTED
 FOR USE.90.7, 110.3
  
 4) NOTE: PLEASE INDICATE THE OCP AT THE
 GEN. PLEASE SEE 445.13 AS IT HAS COME TO
 OUR ATTENTION ON A PREVIOUS PROJECT THAT
 THE GEN MAY NOT CONTAIN OCP AND CAN NOT
 BE VERIFIED AT THIS TIME.
  
 5) NOTE: PLEASE SEE NO LOAD CALCULATIONS
 WERE SUBMITTED FOR REVIEW. PLEASE
 SUBMIT.
 PLEASE SUBMIT AND INDICATE ANY LOAD
 SHEDDING DETAILS IF APPLICABLE.
 702.5, 220
  
 6) NOTE: PLEASE PROVIDE INFORMATION IF
 THE GEN WILL BE FEEDING ANY "LEGALLY
 REQUIRED STAND-BY SYSTEMS.
  
  
 7) NOTE:PLEASE SEE PLANS SHALL
 INDICATE THE CURRENT CODES IN EFFECT FOR INSTALLATION
 AS FOLLOWS.
 PLEASE SEE FBC 2004 CHAPTER 27FOR
 ADOPTED CODES RELEVANT TO POWER
 GENERATORS.
 2002 NFPA-70, 2002 NFPA-110.
  
 8) NOTE: PLEASE EXPLAIN, NOTE WHICH
 MENTIONS TO SET THE OCP ABOVE THE
 EXISTING MAIN ON E-1.???
  
 9) NOTE: PLEASE SEE THE APS/ATS IS
 BECOMING THE NEW FIRST MEANS OF
 DISCONNECT HOWEVER THE NEW GROUNDING
 ELECTRODE SYSTEMS DOES NOT SEEM TO BE
 COMPLETE AS PER 250.50.
 PLEASE SEE GROUNDING DETAIL MENTIONS NEW
 SLAB STEEL WHICH IS OK, HOWEVER PLEASE
 INDICATE ATTACHMENT.
 THESE NEW SLAB/STEEL ATTACHMENTS DO NOT
 MEET THE MIN REQUIREMENTS. PER
 250.50,250.52, 250.104
 IF SLAB STEEL IS ONLY BEING BONDED ,
 THEN PLEASE INDICATE.
 PLEASE COMPLETE GROUNDING ELECTRODE
 SYSTEM(S) AND BONDING FOR ALL AS ABOVE.
  
 10) NOTE:
  
 11) NOTE: PLEASE SEE SETS OF CONDUITS
 AND FEEDERS DO NOT SEEM TO INDICATE
 THEW NEW REQUIRED "EQUIPMENT GROUNDING
 CONDUCTOR" TO THE EXISITING MAINS. THESE
 ARE NO LONGER THE FIRST MEANS OF
 DISCONNECT.
 PER 250.110,250.122,250.24B
 215.5
  
  
 12) NOTE:PLEASE KNOW, BASED ON A
 PREVIOUS PROJECT, IS THIS UNIT GOING TO
 BE BE "BI-FUEL"??
 IF SO, SUBMIT ALL INFORMATION AND SPECS
 ON UNIT(S).
 90.7, 110.3
  
  
 ** PLEASE KNOW, AS MUCH INFORMATION WAS
 NOT SUBMITTED, A COMPLETE REVIEW COULD
 NOT BE DONE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-01-03 Cont ID  
Sent By mawillia Date 2007-01-03 Time 13:55 Rev Time 0.00
Received By mawillia Date 2007-01-03 Time 13:55 Sent To  
Notes
2007-01-03 13:56:17*****APPROVED*****
  
  
  
 TO BE STAMPED AND SIGNED WHEN ALL PLAN REVIEWS HAVE
 BEEN SATISFIED

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-25 Cont ID  
Sent By mcarsill Date 2006-10-25 Time 16:03 Rev Time 0.00
Received By mcarsill Date 2006-10-25 Time 15:55 Sent To  
Notes
2006-10-25 16:03:061. WHAT EQUIPMENT WILL THE GENERATOR SUPPLY WITHIN THE
 STORE.
 2. PLEASE DESCRIBE ANY AND ALL LIFE SAFETY EQUIPMENT
 PLANNED TO BE SUPPLIED BY THE GENERATOR.
 3. PLEASE PROVIDE MORE DETAILS ON GENERATOR ENCLOSURE.
 4. IS THE DOOR LOCATED NEAR THE GENERATOR ENCLOSURE AN
 EXIT DOOR.
 5. DIESEL FUEL STORAGE TANK TO COMPLY WITH NFPA 30.

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status F Date 2006-12-13 Cont ID  
Sent By pkrauss Date 2006-12-13 Time 08:46 Rev Time 0.00
Received By pkrauss Date 2006-12-13 Time 08:46 Sent To  
Notes
2006-12-13 08:50:54DENIED:
 SEE MECHANICAL COMMENTS;
  
 PLAN SHEET SD1 THE "SPECIAL INSTRUCTIONS" INDICATE
 MOUNT UNIT AND INSTALL FUEL LINES.WILL THIS BE DONE
 AT THE JOB LOCATION OR AT THE FACTORY?PLEASE INDICATE
 IF ANY FUEL PIPING IS TO BE INSTALLED REMOTE TO THE
 GENERATOR.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-01-08 Cont ID  
Sent By kstevens Date 2007-01-08 Time 17:17 Rev Time 0.00
Received By kstevens Date 2007-01-08 Time 17:17 Sent To  
Notes
2007-01-08 17:24:51DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 A. RESPONSE TO COMMENT NUMBER 12 OF THE ELECTRICAL
 REVIEW INDICATES THE GENERATOR SHALL HAVE NATURAL GAS
 CONNECTED TO THE GENERATOR. THE FOLLOWING INFORMATION
 IS REQUIRED FOR THE SEPARATE GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. IF 2LB SYSTEM,
 INDICATE THE LOCATION OF THE REGULATOR. SHUT OFF VALVE
 TO BE UPSTREAM OF REGULATOR. SUBMIT MANUF.
 SPECIFICATION SHEET FOR REGULATOR, AND INDICATE MODEL
 NUMBER.
  
 7. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-16 Cont ID  
Sent By adarroug Date 2006-11-16 Time 09:45 Rev Time 0.00
Received By adarroug Date 2006-11-16 Time 09:45 Sent To  
Notes
2006-11-27 16:48:28TO "COMM" BD#29
2006-11-16 09:57:01WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date 2006-10-25 Cont ID  
Sent By adarroug Date 2006-10-25 Time 09:47 Rev Time 0.00
Received By adarroug Date 2006-09-21 Time 09:02 Sent To  
Notes
2006-10-06 00:00:00TO "COMM" BD#22
2006-09-21 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-12-13 Cont ID  
Sent By pkrauss Date 2006-12-13 Time 07:27 Rev Time 0.00
Received By pkrauss Date 2006-12-12 Time 14:07 Sent To  
Notes
2006-12-13 07:38:39COMMENTS BY RON REGUEIRO DATED 10-23-06 WERE
 ADDRESSED.
  
 PLANS MUST BE SUBMITTED TO PALM BEACH COUNTY
 ENVIRONMENTAL DEPARTMENT DIVISION OF STORAGE TANK
 COMPLIANCE AT THE FOLLOWING ADDRESS:
  
 2300 N JOG ROAD
 (4TH FLOOR)
 WEST PALM BEACH, FL 33411
  
 PLEASE SUBMIT PLANS FOR INSTALLATION APPROVAL TO CHIP
 GREEN.YOU MAY CONTACT CHIP GREEN AT (561)233-2400.
  
 PLEASE NOTE, THE EXHAUST FROM THE GENERATOR SHALL BE A
 MINIMUM OF 10 FEET FROM ANY FRESH AIR INTAKES, WINDOWS,
 DOORS, ETC.
  
  
 DENIED:NEW COMMENT
  
 PLAN SHEET SD1 THE "SPECIAL INSTRUCTIONS" INDICATE
 MOUNT UNIT AND INSTALL FUEL LINES.WILL THIS BE DONE
 AT THE JOB LOCATION OR AT THE FACTORY?PLEASE INDICATE
 IF ANY FUEL PIPING IS TO BE INSTALLED REMOTE TO THE
 GENERATOR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-23 Cont ID  
Sent By rregueir Date 2006-10-23 Time 17:17 Rev Time 0.00
Received By rregueir Date 2006-10-23 Time 17:17 Sent To  
Notes
2006-10-23 17:25:511. PLEASE PROVIDE GENERATOR DOCUMENTATION, SPECS FOR
 GENERATOR.
  
 2. APPLICATION INDICATES USE OF EXISTING SLAB, YET
 PLANS SHOW NEW SLAB WITH SUB-BASE FUEL TANK
 (UNDERGROUND?). PLEASE CLARIFY.
  
 3. DOES UNDERGROUND TANK REQUIRE ANY KIND OF FOOTERS OR
 TIE-DOWNS? PLEASE CLARIFY.
  
 RONALD J REGUEIRO
 561.805.6734
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-10-20 Cont ID  
Sent By kstevens Date 2006-10-20 Time 12:41 Rev Time 0.00
Received By kstevens Date 2006-10-20 Time 12:41 Sent To  
Notes
2006-10-20 12:42:20INFORMATION SUBMITTED INDICATES FUEL SOURCE IS DIESEL.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-12-05 Cont ID  
Sent By kdfreema Date 2006-12-05 Time 15:25 Rev Time 0.00
Received By kdfreema Date 2006-12-05 Time 15:25 Sent To  
Notes
2006-12-05 17:07:45** FAILED**
  
 RESPONSE NOTED, HOWEVER THE UNIT IS REQUIRED TO BE
 SCREENED BY MEANS OF A WALL AND LANDSCAPING INDEPENDENT
 OF THE SOUND/WEATHER PROOFING ENCLOSURE. PLEASE REFER
 TO SEC. 94-444(B) FOR THE REQUIREMENTS. AS PART OF YOUR
 RESUBMITTAL, PLEASE INCLUDE LANDSCAPE PLANS AND
 ELEVATIONS FOR THE ENCLOSURE.
  
 REGARDING THE SURVEY YOUR RESPONSE IS NOTED, HOWEVER,
 WHAT WAS INCLUDED IS NOT A SURVEY. PLEASE INCLUDE A
 SURVEY SHOWING THE LOCATION OF THE GENERATOR AND ALL
 EASEMENTS ON THE PROPERTY.
  
 ADDITIONALLY, THE ADDITION OF THE GENERATOR WILL
 REQUIRE A MINOR PLANNED DEVELOPMENT AMENDMENT. PLEASE
 VISIT WWW.WPB.ORG/PLAN AND DOWNLOAD THE 2006-2007
 DEVELOPMENT APPLICATION. THE REQUIREMENTS FOR THE
 AMENDMENT ARE CONTAINED WITHIN THE APPLICATION.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT (561)
 822-1435 OR [email protected] WITH ANY QUESTIONS YOU
 MAY HAVE.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-10-26 Cont ID  
Sent By kdfreema Date 2006-10-25 Time 17:02 Rev Time 0.00
Received By kdfreema Date 2006-10-25 Time 17:01 Sent To  
Notes
2006-10-26 08:48:50**FAILED**
  
 NO SCREENING IS SHOWN ON THE PLANS. GENERATORS MUST BE
 SCREENED IN ACCORDANCE WITH SEC. 94-444(B) OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS. SCREENING
 SHALL BE CONSTRUCTED OF BRICK, DECORATIVE CONCRETE,
 OTHER DECORATIVE MASONRY, OR COMPARABLY DURABLE WOOD
 AND STEEL. WALLS SHALL BE LANDSCAPED WITH SHRUBS AND
 HEDGES PLANTED AT TWO-FOOT INTERVALS. AS PART OF THE
 RESUBMITTAL PLEASE INCLUDE LANDSCAPE PLANS AND
 ELEVATIONS FOR THE ENCLOSURE.
  
 A SURVEY OF THE PROPERTY, INCLUDING THE GENERATOR
 LOCATION AND CORRESPONDING DISTANCES TO PROPERTY LINES
 SHALL BE PRORVIDED.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT (561)
 822-1435 OR [email protected] WITH ANY QUESTIONS YOU
 MAY HAVE.