Plan Review Details - Permit 06090670
Plan Review Stops For Permit 06090670
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-10-10 Cont ID  
Sent By rmcdouga Date 2006-10-10 Time 14:12 Rev Time 0.00
Received By rmcdouga Date 2006-10-10 Time 14:12 Sent To  
Notes
2006-10-10 14:20:21 
 BUILDING PROVISO
  
 1)EQUIPMENT IS LOCATED IN AN "AO" FLOOD ZONE AND IS
 REQUIRED BY CITY CODE TO BE LOCATED 6" ABOVE THE BASE
 FLOOD ELEVATION. AN ELEVATION CERTIFICATE WILL BE
 REQUIRED BEFORE FINAL INSPECTION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-06 Cont ID  
Sent By dpalmer Date 2006-10-06 Time 15:07 Rev Time 0.00
Received By dpalmer Date 2006-10-06 Time 15:07 Sent To  
Notes
2006-10-06 00:00:00***********UNSAT *************
  
 PUBLIX GENERATOR
 8989 OKEECHOBEE, #653
  
 1) NOTE:PLEASE ADJUST VALUE FOR
 COMPLETE SCOPE OF WORK BEING APPLIED
 FOR. THE VALUE OF $10K ON PERMIT
 APPLICATION AUBMITTED IS EXTREMELY LOW
 PLEASE KNOW, THAT VALUE SHALL BE
 ALL LABOR AND MATERIALS EVEN IF
 MATERIALS ARE OWNER SUPPLIED. PLEASE SEE
 VALUE FOR LABOR AND INSTALLATION IS WAY
 LOW FOR SCOPE PF WORK. PLEASE SEE FBC
 2004, ADMINISTRATIVE CODE SECTION 108.3
 AS ADOPTED BY THE CITY OF WEST PALM
 BEACH.
 PLEASE KNOW, A VALUE WILL BE ASSESSED
 USING THE MARSHALL'S& SWIFT GUIDE.
 PLEASE KNOW, UNDER CONTRACTING LAWS AND
 RULES SET UP AND ADOPTED INTO FLORIDA
 STATUES, 489, FBC ADMINISTRATIVE SECTION
 105.5.1 ANY INFORMATION PROVIDED ON
 OFFICAL PERMIT APPLICATION IF KNOWINGLY
 BEING FALSIFIED CAN VOID/REVOKE SUCH
 PERMIT/ APPLICATION.
  
 2) NOTE: PLEASE KNOW, ANY SYSTEMS
 LOCATED IN A FLOOD ZONE "A" WILL BE
 REQUIRED TO BE MOUNTED AT A MIN OF 6"
 ABOVE BFE. PLEASE SEE BUILDING REVIEW
 COMMENTS.
  
 3) NOTE: PLEASE SUBMIT SPECS/MANUFACTURE
 CUT SHEETS.APS/ ATS DO NOT INDICATE
 THE REQUIRED MEANS OF DISCONNECT AS
 REQUIRED BY 230.76,230.79,225.31-39.
 PLEASE SEE A MANUAL MEANS OF DISCONNECT
 COULD NOT BE LOCATED RATED FOR THE LOAD
 SERVED ON THE OUTSIDE OF EQUIPMENT
 SUBMITTED.
 THIS WAS NEVER VERIFIED FROM PREVIOUS
 PERMIT PULLED FOR PREVIOUS PROJECT.
 NO PERMITS WILL BE RELEASED UNLESS THIS
 IS VERIFIED ON ALL SUBMITTED SPECS AND
 PLANS SUBMITTED BEFORE PERMIT IS ISSUED.
 PLEASE SEE ALL EQUIPMENT SHALL BE LISTED
 FOR USE.90.7, 110.3
  
 4) NOTE: PLEASE INDICATE THE OCP AT THE
 GEN. PLEASE SEE 445.13 AS IT HAS COME TO
 OUR ATTENTION ON A PREVIOUS PROJECT THAT
 THE GEN MAY NOT CONTAIN OCP AND CAN NOT
 BE VERIFIED AT THIS TIME.
  
 5) NOTE: PLEASE SEE NO LOAD CALCULATIONS
 WERE SUBMITTED FOR REVIEW. PLEASE
 SUBMIT.
 PLEASE SUBMIT AND INDICATE ANY LOAD
 SHEDDING DETAILS IF APPLICABLE.
 702.5, 220
  
 6) NOTE: PLEASE PROVIDE INFORMATION IF
 THE GEN WILL BE FEEDING ANY "LEGALLY
 REQUIRED STAND-BY SYSTEMS.
  
  
 7) NOTE:PLEASE SEE PLANS SHALL
 INDICATE THE CURRENT CODES IN EFFECT FOR
 INSTALLATION AS FOLLOWS.
 PLEASE SEE FBC 2004 CHAPTER 27FOR
 ADOPTED CODES RELEVANT TO POWER
 GENERATORS.
 2002 NFPA-70, 2002 NFPA-110.
  
 8) NOTE: PLEASE EXPLAIN, NOTE WHICH
 MENTIONS TO SET THE OCP ABOVE THE
 EXISTING MAIN ON E-1.???
  
 9) NOTE: PLEASE SEE THE APS/ATS IS
 BECOMING THE NEW FIRST MEANS OF
 DISCONNECT HOWEVER THE NEW GROUNDING
 ELECTRODE SYSTEMS DOES NOT SEEM TO BE
 COMPLETE AS PER 250.50.
 PLEASE SEE GROUNDING DETAIL MENTIONS NEW
 SLAB STEEL WHICH IS OK, HOWEVER PLEASE
 INDICATE ATTACHMENT.
 THESE NEW SLAB/STEEL ATTACHMENTS DO NOT
 MEET THE MIN REQUIREMENTS. PER
 250.50,250.52, 250.104
 IF SLAB STEEL IS ONLY BEING BONDED ,
 THEN PLEASE INDICATE.
 PLEASE COMPLETE GROUNDING ELECTRODE
 SYSTEM(S) AND BONDING FOR ALL AS ABOVE.
  
 10) NOTE: PLEASE INDICATE THE ACTUAL
 SEPARATION OF ALL NEUTRAL AND
 "GROUNDING" CONDUCTORS FROM THE FIRST
 MEANS OF DISCONNECT. 250.6, 250.24B
 DETAIL SHOWS THESE TO REMAIN TOGETHER
 WHICH WOULD PARALLEL THE NEUTRAL WHICH
 IS NOT PERMITTED.
  
 11) NOTE: PLEASE SEE SETS OF CONDUITS
 AND FEEDERS DO NOT SEEM TO INDICATE
 THEW NEW REQUIRED "EQUIPMENT GROUNDING
 CONDUCTOR" TO THE EXISITING MAINS. THESE
 ARE NO LONGER THE FIRST MEANS OF
 DISCONNECT.
 PER 250.110,250.122,250.24B
 215.5
  
 12) NOTE: PLEASE SEE SITE AND LAYOUT S
 FROM E-4 TO E-4.1 DO NOT CORRELATE.
  
 13) NOTE:PLEASE KNOW, BASED ON A
 PREVIOUS PROJECT, IS THIS UNIT GOING TO
 BE BE "BI-FUEL"??
 IF SO, SUBMIT ALL INFORMATION AND SPECS
 ON UNIT(S).
 90.7, 110.3
  
 14) NOTE: PLEASE CLARIFY VOLTAGES AS
 PLANS INDICATE 12/208V AND 277/480VA
 TRANSFORMERS???
  
  
 ** PLEASE KNOW, AS MUCH INFORMATION WAS
 NOT SUBMITTED, A COMPLETE REVIEW COULD
 NOT BE DONE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-12-19 Cont ID  
Sent By mawillia Date 2006-12-19 Time 16:23 Rev Time 0.00
Received By mawillia Date 2006-12-19 Time 16:23 Sent To  
Notes
2006-12-19 16:40:36*****PROVISO*****
  
  
  
 1.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR
 HINDER EMERGENCY RESPONDER ACCESS TO THE SAID PROPERTY
 OR VICINITY THEREOF (INCLUDING FIRE LANES).
  
 2.STATIONARY GENERATORS FOR EMERGENCY USE OR STANDBY
 POWER SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 110.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS,INDICATE
 HOW/WHERE EACH PROVISO ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status F Date 2006-12-13 Cont ID  
Sent By pkrauss Date 2006-12-13 Time 13:56 Rev Time 0.00
Received By pkrauss Date 2006-12-13 Time 13:56 Sent To  
Notes
2006-12-13 13:57:12DENIED:
  
 PLAN SHEET SD1 THE "SPECIAL INSTRUCTIONS" INDICATE
 MOUNT UNIT AND INSTALL FUEL LINES.WILL THIS BE DONE
 AT THE JOB LOCATION OR AT THE FACTORY?PLEASE INDICATE
 IF ANY FUEL PIPING IS TO BE INSTALLED REMOTE TO THE
 GENERATOR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-19 Cont ID  
Sent By mawillia Date 2006-12-19 Time 16:42 Rev Time 0.00
Received By mawillia Date 2006-09-21 Time 09:06 Sent To  
Notes
2006-10-03 00:00:00TO "COMM" BD#16
2006-09-21 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-12-13 Cont ID  
Sent By pkrauss Date 2006-12-13 Time 11:07 Rev Time 0.00
Received By pkrauss Date 2006-12-13 Time 11:07 Sent To  
Notes
2006-12-13 11:41:49DENIED:
 1.PLANS NEED APPROVAL BY PALM BEACH COUNTY
 ENVIRONMENTAL DEPARTMENT FOR STORAGE TANK COMPLIANCE.
 THIS AGENCY IS LOCATED AT:
  
 2300 N JOG ROAD
 (4TH FLOOR)
 WEST PALM BEACH, FL33411
 PLEASE RE-SUBMIT TO THE CITY OF WEST BEACH CONSTRUCTION
 SERVICES DEPARTMENT AFTER APPROVAL BY DERM.
  
 3.PLAN SHEET E4 INDICATES THE GENERATOR AS BEING 4'
 6" FROM A DOOR, PER 2004 FMC 401.5.1 EXHAUST SHALL
 TERMINATE A MINIMUM OF 10 FT FROM FRESH AIR INTAKES,
 DOORS, WINDOWS, ETC.PLEASE INDICATE LOCATION OF THE
 EXHAUST FROM THE GENERATOR.
  
 4.PLAN SHEET SD1 THE "SPECIAL INSTRUCTIONS" INDICATE
 MOUNT UNIT AND INSTALL FUEL LINES.WILL THIS BE DONE
 AT THE JOB LOCATION OR AT THE FACTORY?PLEASE INDICATE
 IF ANY FUEL PIPING IS TO BE INSTALLED REMOTE TO THE
 GENERATOR.
  
 5.PLEASE NOTE, THE PADS THAT ALL EQUIPMENT WILL BE
 INSTALLED ON SHALL MEET THE CITY'S REQUIREMENT OF 6"
 ABOVE THE BASE FLOOD ELEVATION.CITY CODE SEC. 94-546
 (3) (B) (2).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-10-20 Cont ID  
Sent By kstevens Date 2006-10-20 Time 11:25 Rev Time 0.00
Received By kstevens Date 2006-10-20 Time 11:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-10-04 Cont ID  
Sent By kdfreema Date 2006-10-04 Time 11:02 Rev Time 0.00
Received By kdfreema Date 2006-10-04 Time 11:02 Sent To  
Notes
2006-10-04 00:00:00**FAILED**
  
 THE GENERATOR IS SUBJECT TO THE
 SCREENING REQUIREMENTS FOUND IN SEC.
 94-444(B) WHICH READS AS FOLLOWS:
  
 "B)OUTDOOR STORAGE FOR NONRESIDENTIAL
 AND MULTIFAMILY USES; STORAGE AND
 DISPOSAL FACILITIES.OUTDOOR
 INCINERATORS, GARBAGE OR TRASH
 RECEPTACLES, FUEL OIL OR PROPANE TANKS,
 AND STORAGE RACKS SHALL NOT BE PERMITTED
 UNLESS APPROPRIATE SCREENING IS
 PROVIDED. SCREENING SHALL BE CONSTRUCTED
 OF BRICK, DECORATIVE CONCRETE, OTHER
 DECORATIVE MASONRY, OR COMPARABLY
 DURABLE WOOD AND STEEL. WALLS SHALL BE
 LANDSCAPED WITH SHRUBS AND HEDGES
 PLANTED AT TWO-FOOT INTERVALS. A
 FOUR-SIDED ENCLOSURE WITH AN OBSCURING
 GATE MAY BE REQUIRED AS A CONDITION FOR
 SITE PLAN APPROVAL. PLANS FOR THE LAYOUT
 OF TRASH RECEPTACLESSHALL BE IN
 ACCORDANCE WITH THE MINIMUM REQUIREMENTS
 SET FORTH IN FIGURE XIV-3. THE
 PROVISIONS OF THIS SECTION SHALL NOT
 APPLY TO LITTER CONTAINERS PROVIDED FOR
 THE CONVENIENCE OF PEDESTRIANS. ALL
 AREAS FOR THE STORAGE AND DISPOSAL OF
 TRASH AND GARBAGE SHALL BE PAVED WITH
 CONCRETE SURFACE AS REQUIRED BY THE CITY
 DEPARTMENT OF ENGINEERING AND PUBLIC
 WORKS."
  
 IN THIS APPLICATION, AN ENCLOSURE
 COMPOSED OF CONCRETE BLOCK IS PREFERED
 TO MORE EFFECTIVELY BUFFER THE NOISE
 PRODUCED BY THE GENERATOR FROM THE
 RESIDENCES NORTH OF THE STORE.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER,
 AT (561) 822-1435 OR [email protected]
 WITH ANY QUESTIONS YOU MAY HAVE.