Plan Review Stops For Permit 06090668 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
P |
Date |
2008-09-04 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-09-04 |
Time |
12:28 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-09-04 |
Time |
12:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2008-08-20 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-08-20 |
Time |
14:24 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-08-20 |
Time |
14:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2008-06-13 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-06-13 |
Time |
08:34 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-06-13 |
Time |
08:34 |
Sent To |
|
|
Notes |
2008-06-13 08:34:42 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | 1.)SEE PREVIOUS LIST.THE OWNER ON THE APPLICATION | | DOES NOT MATCH OUR RECORDS. | | | | REVISE APPLICATION OR PROVIDE PROOF OF OWNERSHIP. | | | | 2.)SEE ELECTRIC COMMENTS.VOIDED SHEETS ARE TO BE | | REMOVED FROM THE COLLATED BOUND PERMIT SETS.THE | | VOIDED SHEETS SHOULD BE SUBMITTED SEPARATELY FOR | | REFERENCE. | | | | SHEETS F1, E7 STAMPED - OK. | | | | | | HE |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2008-04-29 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-04-29 |
Time |
10:06 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-04-29 |
Time |
10:06 |
Sent To |
|
|
Notes |
2008-04-29 10:07:08 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | 1.)SEE PREVIOUS LIST.THE OWNER ON THE APPLICATION | | DOES NOT MATCH OUR RECORDS. | | | | REVISE APPLICATION OR PROVIDE PROOF OF OWNERSHIP. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2007-09-04 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-09-04 |
Time |
16:46 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-09-04 |
Time |
16:46 |
Sent To |
|
|
Notes |
2007-09-04 16:48:22 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | 1.)SEE PREVIOUS LIST.THE OWNER ON THE APPLICATOIN | | DOES NOT MATCH OUR RECORDS. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-10-11 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2006-10-11 |
Time |
16:15 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2006-10-11 |
Time |
16:15 |
Sent To |
|
|
Notes |
2006-10-11 16:20:35 | 1.)PROVIDE ANCHORING INFORMATION TO | | COMPLY WITH FBC1606.1.3; STRUCTURAL | | MEMBERS AND SYSTEMS, AND COMPONENTS AND CLADDING IN A | | BUILDING OR STRUCTURE SHALL BE ANCHORED TO RESIST | | WIND-INDUCED OVERTURNING, UPLIFT AND SLIDING AND TO | | PROVIDE CONTINUOUS LOAD PATHS FOR THESE FORCES TO THE | | FOUNDATION.WHERE A PORTION OF THE RESISTANCE TO THESE | | FORCES IS PROVIDED BY DEAD LOAD, THE MINIMUM DEAD LOAD | | LIKELY TO BE IN PLACE DURING A DESIGN WIND EVENT SHALL | | BE USED. | | | | 2.)THE VALUE IS TOO LOW.PROVIDE A REASONABLE VALUE | | OR AN ESTIMATED VALUE WILL BE DONE FOR YOU USING | | MARSHALL & SWIFT. | | | | 3.)A NOTICE OF COMMENCEMENT MUST BE FILED WITH THE | | CLERK OF COURTS BEFORE A PERMIT CAN BE ISSUED. | | | | 4.)THE OWNER AND ADDRESS ON THE APPLICATION AND SITE | | PLAN PREPARED BY THE ENGINEER DO NOT MATCH THE PARCEL | | ID PROVIDED.PROVIDE A COMPLETE SURVEY OR SITE PLAN OF | | THE PARCEL, SHOWING ALL PROPERTY LINES.IMPROVEMENT | | CANNOT CROSS THE PROPERTY LINE. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
7 |
Status |
P |
Date |
2008-08-26 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-08-26 |
Time |
14:47 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-08-26 |
Time |
14:47 |
Sent To |
FIRE |
|
Notes |
2008-08-26 14:49:47 | ** EQUIPMENT GROUNDING CONDUCTOR IS REQUIRED FROM NEW | | MAINS TO EXISTING SWB. THERE IS NO WAY TO GUARANTEE NO | | METALLIC PATHS BETWEEN BUILDIGN AND EQUIPMENT SUCH AS | | PHONE, CABLE, PIPING ETC. | | NEUTRALS SHALL BE SEPARATED AT THE EXISITNG SERVICE | | LOCATION. | | 250.32. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
6 |
Status |
F |
Date |
2008-08-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-08-13 |
Time |
13:48 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-08-13 |
Time |
13:48 |
Sent To |
|
|
Notes |
2008-08-13 13:49:59 | ** DENIEDREVIEW ** | | | | ** ONCE AGAIN THE SAME NOTE AS PREVIOUS REVIEW | | APPLIES. | | | | ** SEE SHEETS. FOR EXAMPLE: SHEET E-3 IS FOLD OVER, | | STATES TO *SEE REVISED* YET THERE IS NOT REVISED E-3. | | THIS IS ONE EXAMPLE!!! | | | | | | 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW WHICH | | STATED TO REMOVE ANY OLD/VOIDED SHEETS FROM SETS AND | | INSERT NEW REVISED SHEETS INTO TWO COMPLETE SETS FOR | | REVIEW AND POSSIBLE STAMPING. | | THIS WAS NOT DONE. | | PLEASE ALSO SEE COMMENTS FROM OTHER TRADES WHICH ARE | | REQUIRED TO BE ADDRESSED WHICH MAY AFFECT PROJECT FOR | | PERMIT ISSUANCE. | | | | | | ** IMPORTANT** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF | | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT | | HESITATE IN CONTACTING THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
F |
Date |
2008-06-18 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-06-18 |
Time |
14:03 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-06-18 |
Time |
14:03 |
Sent To |
|
|
Notes |
2008-06-18 14:03:15 | ** DENIEDREVIEW ** | | | | | | 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW WHICH | | STATED TO REMOVE ANY OLD/VOIDED SHEETS FROM SETS AND | | INSERT NEW REVISED SHEETS INTO TWO COMPLETE SETS FOR | | REVIEW AND POSSIBLE STAMPING. | | THIS WAS NOT DONE. | | PLEASE ALSO SEE COMMENTS FROM OTHER TRADES WHICH ARE | | REQUIRED TO BE ADDRESSED WHICH MAY AFFECT PROJECT FOR | | PERMIT ISSUANCE. | | | | | | ** IMPORTANT** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF | | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT | | HESITATE IN CONTACTING THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2008-04-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-04-07 |
Time |
12:44 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-04-07 |
Time |
12:44 |
Sent To |
|
|
Notes |
2008-04-07 12:44:38 | ** DENIED ** | | | | 1) NOTE: PLEASE SEE COMMENTS FROM MECHANICAL REVIEW | | WITH RESPECT TO LOCATION AND SET BACKS. AS THIS WILL | | AFFECT ALL OTHER SHEETS ELECTRICAL PLANS MAY NOT BE | | STAMPED AT THIS TIME. | | | | ** PLEASE REMOVE ANY OLD/VOIDED SHEETS FROM SETS. | | PLEASE DO NOT LEAVE THESE IN SETS AS THEY ARE NOT | | NEEDED. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2007-09-05 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-09-05 |
Time |
09:01 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-09-05 |
Time |
07:39 |
Sent To |
|
|
Notes |
2007-09-05 09:01:17 | ** DENIED 2ND ** | | | | 1) NOTE: PLEASE SEE NOTES DATED 6/19/07 SPECIFICALLY | | NOTE #1. THE NOTE #2 WAS ADJUSTED AND FEES WERE PAID. | | THE NOTE #3 WILL STILL BE REQUIRED. | | THIS REVIEWER HAS ATTACHED A COPY OF THE PREVIOUS NOTES | | DATED 6/19/07. | | | | ** AS STATED ON PREVIOUS REVIEW: | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2007-06-19 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-06-19 |
Time |
08:15 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-06-19 |
Time |
07:27 |
Sent To |
|
|
Notes |
2007-06-19 08:16:28 | *** UNSAT 2ND REVIEW *** | | | | 1) NOTE: PLEASE SEE PLANS WERE SUBMITTED BACK WITHOUT | | ANY CORRECTIONS OR CHANGES MADE TO PLANS. THE REQUIRED | | INFORMATION IS NOT ACCEPTABLE ON LETTERS FROM | | CONTRACTOR. ALL CHANGES TO PLANS AND INFORMATION NEEDED | | ARE TO BE ON PLANS AND DONE BY THE ENGINEER OF RECORD. | | OTHER SUPPORTING DOCUMENTATION SUCH AND MANUFACTURE | | SPEC/CUT SHEETS OF ALL EQUIPMENT AS PREVIOUSLY | | REQUESTED IS TO BE ATTACHED. THE SHEETS ATTACHED ARE | | NOT ALL AS REQUESTED. | | | | 2) NOTE: PLEASE SEE THE VALUE FOR THE TOTAL SCOPE OF | | WORK IS COMING BACK AT $148K WHICH IS ABOUT THE SAME | | VALUE OF THE PREVIOUS PROJECT AT STORE #50 HOWEVER THE | | SCOPE VALUE IS HIGHER THAN THAT APPLIED. THIS VALUE IS | | TO BE FOR ALL, INCLUDING GAS HOOK-UP, EQUIPMENT, AND | | LABOR ETC. THIS IS TO INCLUDE ALL MATERIALS, EQUIPMENT, | | DESIGN COST ETC EVEN IF ANY OF THESE ARE OWNER | | SUPPLIED. | | PLEASE PROVIDE A COMPLETE LIST AND BREAKDOWN OF ALL | | ABOVE AND THESE VALUES WILL BE COMPARED TO ADOPTED | | GUIDES UNDER THE FBC. A VALUE MAY BE ASSESSED BY THIS | | OFFICE IF AN ACCURATE VALUE IS NOT PROVIDED FOR ALL. | | FEES ARE DUE AT THIS TIME. PROJECT IS BEING PLACED INTO | | A HOLD STATUS AND NO OTHER REVIEWS WILL BE DONE UNTIL | | THESE FEES ARE PAID. IF FEES ARE NOT PAID BY 6/27/07 | | THE PLANS WILL BE REMOVED FROM THE REVIEW PROCESS | | COMPLETELY. THESE SHOULD BE PAID UPON REVIEW OF THESE | | COMMENTS BASED ON THE FIRST INCREASE IN THE AMOUNT OF | | $1,975.80. PLANS WILL BE RETAINED BY THIS OFFICE AND | | NOT RELEASED UNTIL FEES ARE PAID.PLEASE KNOW THIS | | COMMENT HAS BEEN MADE ON SEVERAL PROJECTS FOR THE SAME | | SCOPE OF WORK AND THE SAME RESPONSE IS MADE WITHOUT ANY | | CORRECTIONS TO APPLIED WORK. ALL PERMIT APPLICATIONS, | | PLANS MAY BE RETAINED BY THIS OFFICE FOR REVIEW FROM | | THE CONTRACTORS LICENSING BOARD. | | FBC 108.3 | | | | 3) NOTE: PLEASE SEE THE PLUMBING REVIEW COMMENTS AS THE | | GAS INFORMATIONWILL BE REQUIRED IN THE SUBMITTED | | PACKAGE. | | | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2006-10-06 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-10-06 |
Time |
14:04 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-10-06 |
Time |
12:10 |
Sent To |
|
|
Notes |
2006-10-06 00:00:00 | ***********UNSAT ************* | | | | PUBLIX GENERATOR | | HAVERHILL, #821 | | | | 1) NOTE:PLEASE ADJUST VALUE FOR | | COMPLETE SCOPE OF WORK BEING APPLIED | | FOR. THE VALUE OF $10K ON PERMIT | | APPLICATION AUBMITTED IS EXTREMELY LOW | | PLEASE KNOW, THAT VALUE SHALL BE | | ALL LABOR AND MATERIALS EVEN IF | | MATERIALS ARE OWNER SUPPLIED. PLEASE SEE | | VALUE FOR LABOR AND INSTALLATION IS WAY | | LOW FOR SCOPE PF WORK. PLEASE SEE FBC | | 2004, ADMINISTRATIVE CODE SECTION 108.3 | | AS ADOPTED BY THE CITY OF WEST PALM | | BEACH. | | PLEASE KNOW, A VALUE WILL BE ASSESSED | | USING THE MARSHALL'S& SWIFT GUIDE. | | PLEASE KNOW, UNDER CONTRACTING LAWS AND | | RULES SET UP AND ADOPTED INTO FLORIDA | | STATUES, 489, FBC ADMINISTRATIVE SECTION | | 105.5.1 ANY INFORMATION PROVIDED ON | | OFFICAL PERMIT APPLICATION IF KNOWINGLY | | BEING FALSIFIED CAN VOID/REVOKE SUCH | | PERMIT/ APPLICATION. | | | | 2) NOTE: PLEASE KNOW, ANY SYSTEMS | | LOCATED IN A FLOOD ZONE "A" WILL BE | | REQUIRED TO BE MOUNTED AT A MIN OF 6" | | ABOVE BFE. PLEASE SEE BUILDING REVIEW | | COMMENTS. | | | | 3) NOTE: PLEASE SUBMIT SPECS/MANUFACTURE | | CUT SHEETS.APS/ ATS DO NOT INDICATE | | THE REQUIRED MEANS OF DISCONNECT AS | | REQUIRED BY 230.76,230.79,225.31-39. | | PLEASE SEE A MANUAL MEANS OF DISCONNECT | | COULD NOT BE LOCATED RATED FOR THE LOAD | | SERVED ON THE OUTSIDE OF EQUIPMENT | | SUBMITTED. | | THIS WAS NEVER VERIFIED FROM PREVIOUS | | PERMIT PULLED FOR PREVIOUS PROJECT. | | NO PERMITS WILL BE RELEASED UNLESS THIS | | IS VERIFIED ON ALL SUBMITTED SPECS AND | | PLANS SUBMITTED BEFORE PERMIT IS ISSUED. | | PLEASE SEE ALL EQUIPMENT SHALL BE LISTED | | FOR USE.90.7, 110.3 | | | | 4) NOTE: PLEASE INDICATE THE OCP AT THE | | GEN. PLEASE SEE 445.13 AS IT HAS COME TO | | OUR ATTENTION ON A PREVIOUS PROJECT THAT | | THE GEN MAY NOT CONTAIN OCP AND CAN NOT | | BE VERIFIED AT THIS TIME. | | | | 5) NOTE: PLEASE SEE NO LOAD CALCULATIONS | | WERE SUBMITTED FOR REVIEW. PLEASE | | SUBMIT. | | PLEASE SUBMIT AND INDICATE ANY LOAD | | SHEDDING DETAILS IF APPLICABLE. | | 702.5, 220 | | | | 6) NOTE: PLEASE PROVIDE INFORMATION IF | | THE GEN WILL BE FEEDING ANY "LEGALLY | | REQUIRED STAND-BY SYSTEMS. | | | | | | 7) NOTE:PLEASE SEE PLANS SHALL | | INDICATE THE CURRENT CODES IN EFFECT FOR | | INSTALLATION AS FOLLOWS. | | PLEASE SEE FBC 2004 CHAPTER 27FOR | | ADOPTED CODES RELEVANT TO POWER | | GENERATORS. | | 2002 NFPA-70, 2002 NFPA-110. | | | | 8) NOTE: PLEASE EXPLAIN, NOTE WHICH | | MENTIONS TO SET THE OCP ABOVE THE | | EXISTING MAIN ON E-1.??? | | | | 9) NOTE: PLEASE SEE THE APS/ATS IS | | BECOMING THE NEW FIRST MEANS OF | | DISCONNECT HOWEVER THE NEW GROUNDING | | ELECTRODE SYSTEMS DOES NOT SEEM TO BE | | COMPLETE AS PER 250.50. | | PLEASE SEE GROUNDING DETAIL MENTIONS NEW | | SLAB STEEL WHICH IS OK, HOWEVER PLEASE | | INDICATE ATTACHMENT. | | THESE NEW SLAB/STEEL ATTACHMENTS DO NOT | | MEET THE MIN REQUIREMENTS. PER | | 250.50,250.52, 250.104 | | IF SLAB STEEL IS ONLY BEING BONDED , | | THEN PLEASE INDICATE. | | PLEASE COMPLETE GROUNDING ELECTRODE | | SYSTEM(S) AND BONDING FOR ALL AS ABOVE. | | | | 10) NOTE: PLEASE INDICATE THE ACTUAL | | SEPARATION OF ALL NEUTRAL AND | | "GROUNDING" CONDUCTORS FROM THE FIRST | | MEANS OF DISCONNECT. 250.6, 250.24B | | DETAIL SHOWS THESE TO REMAIN TOGETHER | | WHICH WOULD PARALLEL THE NEUTRAL WHICH | | IS NOT PERMITTED. | | | | 11) NOTE: PLEASE SEE SETS OF CONDUITS | | AND FEEDERS DO NOT SEEM TO INDICATE | | THEW NEW REQUIRED "EQUIPMENT GROUNDING | | CONDUCTOR" TO THE EXISITING MAINS. THESE | | ARE NO LONGER THE FIRST MEANS OF | | DISCONNECT. | | PER 250.110,250.122,250.24B | | 215.5 | | | | 12) NOTE: | | | | 13) NOTE:PLEASE KNOW, BASED ON A | | PREVIOUS PROJECT, IS THIS UNIT GOING TO | | BE BE "BI-FUEL"?? | | IF SO, SUBMIT ALL INFORMATION AND SPECS | | ON UNIT(S). | | 90.7, 110.3 | | | | | | ** PLEASE KNOW, AS MUCH INFORMATION WAS | | NOT SUBMITTED, A COMPLETE REVIEW COULD | | NOT BE DONE. | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
6 |
Status |
P |
Date |
2008-09-02 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-09-02 |
Time |
11:56 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-09-02 |
Time |
11:51 |
Sent To |
B1 |
|
Notes |
2008-09-02 11:53:13 | *****APPROVED***** | | | | | | PLAN SHEETS E1.1 AND E3 WERE STAMPED, INITIALED, AND | | DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
5 |
Status |
F |
Date |
2008-08-14 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-08-14 |
Time |
11:13 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-08-14 |
Time |
10:51 |
Sent To |
|
|
Notes |
2008-08-14 11:05:00 | *****PROVISO***** | | | | THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN | | ALL OTHER REVIEWERS HAVE BEEN SATISFIED. | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2008-06-20 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-06-20 |
Time |
12:12 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-06-20 |
Time |
12:01 |
Sent To |
|
|
Notes |
2008-06-20 12:08:14 | *****PROVISO***** | | | | THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN | | ALL OTHER REVIEWERS HAVE BEEN SATISFIED. | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
F |
Date |
2008-04-24 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-04-24 |
Time |
12:05 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-04-24 |
Time |
12:01 |
Sent To |
|
|
Notes |
2008-04-24 12:04:48 | *****PROVISO***** | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE | | BEEN ADDRESSED;HOWEVER THE APPROPIATE PLAN SHEET(S) | | TO BE FIRE-STAMPED WHEN ALL OTHER REVIEWERS HAVE BEEN | | SATISFIED. | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2007-09-24 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-09-24 |
Time |
13:56 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-09-24 |
Time |
13:39 |
Sent To |
|
|
Notes |
2007-09-24 13:51:28 | *****PROVISO***** | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE | | BEEN ADDRESSED;HOWEVER THE APPROPIATE PLAN SHEET(S) | | TO BE FIRE-STAMPED WHEN ALL OTHER REVIEWERS HAVE BEEN | | SATISFIED. | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2006-12-05 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-12-05 |
Time |
12:04 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-12-05 |
Time |
11:59 |
Sent To |
|
|
Notes |
2006-12-05 12:36:42 | *****DENIED***** | | | | | | | | 1.PLEASE SHOW/DISPLAY THE LOCATION OF THE PROPOSED | | GENERATOR IN RELATIONSHIP TO THE BUILDING(S), | | STREETS/ROADWAYS, ETC IN THE IMMEDIATE VICINITY. | | | | 2.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR | | HINDER EMERGENCY RESPONDERS ACCESS TO THE SAID PROPERTY | | OR VICINITY THEROF. | | | | 3.WILL THE PROPOSED GENERATOR BE TIED INTO THE FIRE | | ALARM SYSTEM CURRENTLY BEING USED AT PUBLIX? | | | | 4.HOW WILL THE PROPOSED STRUCTURE BE PROTECTED FROM | | VEHICULAR DAMAGE? | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FUEL |
DIESEL GENERATOR |
Rev No |
2 |
Status |
P |
Date |
2008-05-27 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-05-27 |
Time |
11:03 |
Rev Time |
0.15 |
Received By |
tgordon |
Date |
2008-05-27 |
Time |
11:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FUEL |
DIESEL GENERATOR |
Rev No |
1 |
Status |
F |
Date |
2008-04-04 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-04-04 |
Time |
14:40 |
Rev Time |
0.20 |
Received By |
tgordon |
Date |
2008-04-04 |
Time |
14:36 |
Sent To |
|
|
Notes |
2008-04-04 14:39:19 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA | | ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS). | | | | *** DENIED *** | | 1) THE GENERATOR HAS A 1,000 GALLON DIESEL FUEL STORAGE | | TANK BELOW IT AND NEEDS TO COMPLY WITH NFPA 30 TABLE | | 4.3.2.1.1(B) WHICH REQUIRES THE TANK TO BE 15 FEET FROM | | A PROPERTY LINE THAT IS OR CAN BE BUILT UPON. PLANS | | SHOW THE TANK IS 10'-11" FROM THE WEST PROPERTY LINE, | | PLEASE CORRECT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
N |
Date |
2008-04-12 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-04-12 |
Time |
16:47 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-04-12 |
Time |
16:47 |
Sent To |
|
|
Notes |
2008-04-12 16:50:25 | POWER SECURE HAS INDICATED THAT THIS WILL BE A DIESEL | | GENERATOR AND THE BI-FUEL KIT WILL BE DONE BY SEPARATE | | PERMIT. |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2007-09-20 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-09-20 |
Time |
16:39 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-09-20 |
Time |
16:39 |
Sent To |
|
|
Notes |
2007-09-20 16:41:06 | DENIED | | REFERENCE: FBC-2004 FUEL GAS | | FBC-2004 CHAPTER 1 | | | | A. A SOURCE HAS INDICATED THAT THE GENERATOR MAY BE | | BI-FUEL, (DIESEL AND NATURAL GAS OR LP GAS). IF THIS IS | | CORRECT, THE FOLLOWING INFORMATION WILL BE REQUIRED FOR | | THE REQUIRED GAS PERMIT: | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE BEING USED. | | | | 3. TYPE OF GAS, (LP OR NATURAL). | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | 402.4(33). | | | | 5. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION | | AIR (IF APPLICABLE) PER FBC-2004 FUEL | | GAS CODE SECTION 304. | | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | 8. SUBMIT A DETAIL SHOWING THE TYPE, | | LOCATION, SIZE AND TERMINATION OF THE | | GAS VENTS PER FBC-2004 FUEL GAS CODE | | SECS. 502 THRU 505. | | | | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | 10. CLEARLY SHOW THE LOCATION AND CAP- | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | OR ASME), THE DISTANCE OF THE TANK FROM | | THE BUILDING AND ADJACENT PROPERTY LINES | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | INGS, AND THE LOCATION OF ANY BUILDING | | OPENINGS BELOW THE RELIEF VALVE OF THE | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | 11. CLEARLY INDICATE ON THE PLAN IF THE | | LP TANK IS ABOVE OR BELOW GROUND, AND | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | PER NFPA 58. IF THE TANK | | IS BELOW GROUND THE CONTAINER SHALL BE | | SECURILY ANCHORED PER NFPA 58 SECTION | | 3-2.2.7(H). | | | | B. MANUF. SPECIFICATION SHEETS SHALL BE OF SUFFICIENT | | CLARITY AND BELEGIBLE. SHEETS SUBMITTED DO NOT MEET | | THIS REQUIREMENT.--ALSO SUBMIT MANUF. INSTALLATION | | INSTRUCTIONS SHOWING ALL REQUIRED CLEARANCES FROM | | BUILDINGS OR STRUCTURES. SECTION 106.1.1. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2008-07-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-07-24 |
Time |
13:50 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-07-24 |
Time |
13:50 |
Sent To |
|
|
Notes |
2008-07-24 13:53:29 | TO "COMM" BD#19 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2008-05-19 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-05-19 |
Time |
12:50 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-05-19 |
Time |
12:50 |
Sent To |
|
|
Notes |
2008-05-19 12:53:55 | TO "COMM" BD#56 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2008-04-01 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-04-01 |
Time |
13:21 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-04-01 |
Time |
13:21 |
Sent To |
|
|
Notes |
2008-04-01 13:24:09 | TO "COMM" BD#49 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-08-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-06 |
Time |
14:16 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-06 |
Time |
14:16 |
Sent To |
|
|
Notes |
2007-08-30 14:20:30 | TO "COMM" BD#41 | 2007-08-06 14:17:03 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-05-23 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-05-23 |
Time |
08:20 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-05-23 |
Time |
08:20 |
Sent To |
|
|
Notes |
2007-06-12 13:35:39 | TO "COMM" BD#27 | 2007-05-23 08:20:59 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-12-05 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-12-05 |
Time |
13:50 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-09-21 |
Time |
09:24 |
Sent To |
|
|
Notes |
2006-10-06 00:00:00 | TO "COMM" BD#30 | 2006-09-21 00:00:00 | WAITING FOR "COMM" BD |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2008-05-27 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-05-27 |
Time |
11:03 |
Rev Time |
0.15 |
Received By |
tgordon |
Date |
2008-05-27 |
Time |
11:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2008-04-04 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-04-04 |
Time |
14:27 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2008-04-04 |
Time |
14:27 |
Sent To |
|
|
Notes |
2008-04-04 14:34:58 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA | | ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS). | | | | *** DENIED *** | | 1) AS NOTED IN LAST REVIEW 9/6/08 NOTE #1. THE | | GENERATOR HAS A 1,000 GALLON DIESEL FUEL STORAGE TANK | | BELOW IT AND NEEDS TO COMPLY WITH NFPA 30 TABLE | | 4.3.2.1.1(B) WHICH REQUIRES THE TANK TO BE 15 FEET FROM | | A PROPERTY LINE THAT IS OR CAN BE BUILT UPON. PLAN SHOW | | THE TANK IS 10'-11" FROM THE WEST PROPERTY LINE, PLEASE | | CORRECT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2007-09-06 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-09-06 |
Time |
14:25 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-09-06 |
Time |
14:25 |
Sent To |
|
|
Notes |
2007-09-06 14:40:25 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA | | ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS). | | | | *** DENIED *** | | 1) AT TIME OF LAST REVIEW I HAD MISSED THAT THIS | | GENERATOR HAD A 1,000 GALLON DIESEL FUEL STORAGE TANK | | BELOW IT AND NEEDS TO COMPLY WITH NFPA 30 TABLE | | 4.3.2.1.1(B) WHICH REQUIRES THE TANK TO BE 15 FEET FROM | | PROPERTY LINE THAT IS OR CAN BE BUILT UPON. PLAN PAGE | | E3 SHOWS THE TANK 10'-11" FROM THE PROPERTY LINE, | | PLEASE CORRECT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2006-10-24 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-10-24 |
Time |
09:43 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2006-10-24 |
Time |
09:43 |
Sent To |
|
|
Notes |
2006-10-24 09:47:34 | *** DENIED *** | | 1) SEE REVIEW NOTES BY OTHER DEPARTMENTS, PLEASE MAKE | | CORRECTIONS. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
N |
Date |
2007-09-20 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-09-20 |
Time |
16:24 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2006-10-20 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2006-10-20 |
Time |
12:55 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2006-10-20 |
Time |
12:55 |
Sent To |
|
|
Notes |
2006-10-20 12:56:06 | INFORMATION SUBMITTED INDICATES THE FUEL SOURCE IS | | DIESEL. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2008-04-03 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2008-04-03 |
Time |
16:24 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2008-04-03 |
Time |
16:24 |
Sent To |
|
|
Notes |
2008-04-03 16:25:42 | ***PROVISO*** | | | | 1) PRIOR TO FINAL INSPECTION, THE PROPOSED FENCE SHALL | | BE INSTALLED.SHRUBS/HEDGES SHALL BE INSTALLED ALONG | | THE PERIMETER OF THE FENCE AT A MINIMUM OF TWO (2) FOOT | | INTERVALS. | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER, | | AT (561) 822-1435. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2007-09-13 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2007-09-13 |
Time |
08:17 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2007-09-13 |
Time |
08:17 |
Sent To |
|
|
Notes |
2007-09-13 08:20:10 | ***FAILED*** | | | | 1) MINOR AMENDMENT TO THE PARADISE PLAZA COMMERCIAL | | PLANNED DEVELOPMENT (CPD) SHALL BE SUBMITTED AND | | APPROVED TO THE CITY'S PLANNING DEPARTMENT PRIOR TO THE | | ISSUANCE OF A BUILDING PERMIT. | | | | 2) AS REQUIRED BY SECTION 94-444(B) OF THE CITY'S | | ZONING AND LAND DEVELOPMENT REGULATIONS, GENERATOR | | SHALL BE SCREENED WITH A WALL OF ADEQUATE HEIGHT AND | | LANDSCAPED WITH SHRUBS/HEDGES PLANTED AT 2-FOOT | | INTERVALS. | | | | QUESTIONS/COMMENTS, PLEASE CONTACT JOHN ROACH, SENIOR | | PLANNER, AT (561) 822-1435. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2006-11-14 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2006-11-14 |
Time |
11:05 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2006-11-14 |
Time |
11:05 |
Sent To |
I |
|
Notes |
2006-11-14 11:08:31 | ***FAILED*** | | | | 1) MINOR AMENDMENT TO THE PARADISE PLAZA COMMERCIAL | | PLANNED DEVELOPMENT (CPD) SHALL BE SUBMITTED AND | | APPROVED TO THE CITY'S PLANNING DEPARTMENT PRIOR TO THE | | ISSUANCE OF A BUILDING PERMIT. | | | | 2) AS REQUIRED BY SECTION 94-444(B) OF THE CITY'S | | ZONING AND LAND DEVELOPMENT REGULATIONS, GENERATOR | | SHALL BE SCREENED WITH A WALL OF ADEQUATE HEIGHT AND | | LANDSCAPED WITH SHRUBS/HEDGES PLANTED AT 2-FOOT | | INTERVALS. | | | | QUESTIONS/COMMENTS, PLEASE CONTACT JOHN ROACH, SENIOR | | PLANNER, AT (561) 822-1435. |
|
|