Plan Review Details - Permit 06090668
Plan Review Stops For Permit 06090668
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-09-04 Cont ID  
Sent By shill Date 2008-09-04 Time 12:28 Rev Time 0.00
Received By shill Date 2008-09-04 Time 12:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-08-20 Cont ID  
Sent By shill Date 2008-08-20 Time 14:24 Rev Time 0.00
Received By shill Date 2008-08-20 Time 14:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-06-13 Cont ID  
Sent By shill Date 2008-06-13 Time 08:34 Rev Time 0.00
Received By shill Date 2008-06-13 Time 08:34 Sent To  
Notes
2008-06-13 08:34:42****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)SEE PREVIOUS LIST.THE OWNER ON THE APPLICATION
 DOES NOT MATCH OUR RECORDS.
  
 REVISE APPLICATION OR PROVIDE PROOF OF OWNERSHIP.
  
 2.)SEE ELECTRIC COMMENTS.VOIDED SHEETS ARE TO BE
 REMOVED FROM THE COLLATED BOUND PERMIT SETS.THE
 VOIDED SHEETS SHOULD BE SUBMITTED SEPARATELY FOR
 REFERENCE.
  
 SHEETS F1, E7 STAMPED - OK.
  
  
 HE

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-04-29 Cont ID  
Sent By shill Date 2008-04-29 Time 10:06 Rev Time 0.00
Received By shill Date 2008-04-29 Time 10:06 Sent To  
Notes
2008-04-29 10:07:08****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)SEE PREVIOUS LIST.THE OWNER ON THE APPLICATION
 DOES NOT MATCH OUR RECORDS.
  
 REVISE APPLICATION OR PROVIDE PROOF OF OWNERSHIP.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-04 Cont ID  
Sent By shill Date 2007-09-04 Time 16:46 Rev Time 0.00
Received By shill Date 2007-09-04 Time 16:46 Sent To  
Notes
2007-09-04 16:48:22****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)SEE PREVIOUS LIST.THE OWNER ON THE APPLICATOIN
 DOES NOT MATCH OUR RECORDS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-11 Cont ID  
Sent By shill Date 2006-10-11 Time 16:15 Rev Time 0.00
Received By shill Date 2006-10-11 Time 16:15 Sent To  
Notes
2006-10-11 16:20:351.)PROVIDE ANCHORING INFORMATION TO
 COMPLY WITH FBC1606.1.3; STRUCTURAL
 MEMBERS AND SYSTEMS, AND COMPONENTS AND CLADDING IN A
 BUILDING OR STRUCTURE SHALL BE ANCHORED TO RESIST
 WIND-INDUCED OVERTURNING, UPLIFT AND SLIDING AND TO
 PROVIDE CONTINUOUS LOAD PATHS FOR THESE FORCES TO THE
 FOUNDATION.WHERE A PORTION OF THE RESISTANCE TO THESE
 FORCES IS PROVIDED BY DEAD LOAD, THE MINIMUM DEAD LOAD
 LIKELY TO BE IN PLACE DURING A DESIGN WIND EVENT SHALL
 BE USED.
  
 2.)THE VALUE IS TOO LOW.PROVIDE A REASONABLE VALUE
 OR AN ESTIMATED VALUE WILL BE DONE FOR YOU USING
 MARSHALL & SWIFT.
  
 3.)A NOTICE OF COMMENCEMENT MUST BE FILED WITH THE
 CLERK OF COURTS BEFORE A PERMIT CAN BE ISSUED.
  
 4.)THE OWNER AND ADDRESS ON THE APPLICATION AND SITE
 PLAN PREPARED BY THE ENGINEER DO NOT MATCH THE PARCEL
 ID PROVIDED.PROVIDE A COMPLETE SURVEY OR SITE PLAN OF
 THE PARCEL, SHOWING ALL PROPERTY LINES.IMPROVEMENT
 CANNOT CROSS THE PROPERTY LINE.
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2008-08-26 Cont ID  
Sent By dpalmer Date 2008-08-26 Time 14:47 Rev Time 0.00
Received By dpalmer Date 2008-08-26 Time 14:47 Sent To FIRE
Notes
2008-08-26 14:49:47** EQUIPMENT GROUNDING CONDUCTOR IS REQUIRED FROM NEW
 MAINS TO EXISTING SWB. THERE IS NO WAY TO GUARANTEE NO
 METALLIC PATHS BETWEEN BUILDIGN AND EQUIPMENT SUCH AS
 PHONE, CABLE, PIPING ETC.
 NEUTRALS SHALL BE SEPARATED AT THE EXISITNG SERVICE
 LOCATION.
 250.32.
  

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2008-08-13 Cont ID  
Sent By dpalmer Date 2008-08-13 Time 13:48 Rev Time 0.00
Received By dpalmer Date 2008-08-13 Time 13:48 Sent To  
Notes
2008-08-13 13:49:59** DENIEDREVIEW **
  
 ** ONCE AGAIN THE SAME NOTE AS PREVIOUS REVIEW
 APPLIES.
  
 ** SEE SHEETS. FOR EXAMPLE: SHEET E-3 IS FOLD OVER,
 STATES TO *SEE REVISED* YET THERE IS NOT REVISED E-3.
 THIS IS ONE EXAMPLE!!!
  
  
 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW WHICH
 STATED TO REMOVE ANY OLD/VOIDED SHEETS FROM SETS AND
 INSERT NEW REVISED SHEETS INTO TWO COMPLETE SETS FOR
 REVIEW AND POSSIBLE STAMPING.
 THIS WAS NOT DONE.
 PLEASE ALSO SEE COMMENTS FROM OTHER TRADES WHICH ARE
 REQUIRED TO BE ADDRESSED WHICH MAY AFFECT PROJECT FOR
 PERMIT ISSUANCE.
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-06-18 Cont ID  
Sent By dpalmer Date 2008-06-18 Time 14:03 Rev Time 0.00
Received By dpalmer Date 2008-06-18 Time 14:03 Sent To  
Notes
2008-06-18 14:03:15** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW WHICH
 STATED TO REMOVE ANY OLD/VOIDED SHEETS FROM SETS AND
 INSERT NEW REVISED SHEETS INTO TWO COMPLETE SETS FOR
 REVIEW AND POSSIBLE STAMPING.
 THIS WAS NOT DONE.
 PLEASE ALSO SEE COMMENTS FROM OTHER TRADES WHICH ARE
 REQUIRED TO BE ADDRESSED WHICH MAY AFFECT PROJECT FOR
 PERMIT ISSUANCE.
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-04-07 Cont ID  
Sent By dpalmer Date 2008-04-07 Time 12:44 Rev Time 0.00
Received By dpalmer Date 2008-04-07 Time 12:44 Sent To  
Notes
2008-04-07 12:44:38** DENIED **
  
 1) NOTE: PLEASE SEE COMMENTS FROM MECHANICAL REVIEW
 WITH RESPECT TO LOCATION AND SET BACKS. AS THIS WILL
 AFFECT ALL OTHER SHEETS ELECTRICAL PLANS MAY NOT BE
 STAMPED AT THIS TIME.
  
 ** PLEASE REMOVE ANY OLD/VOIDED SHEETS FROM SETS.
 PLEASE DO NOT LEAVE THESE IN SETS AS THEY ARE NOT
 NEEDED.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-09-05 Cont ID  
Sent By dpalmer Date 2007-09-05 Time 09:01 Rev Time 0.00
Received By dpalmer Date 2007-09-05 Time 07:39 Sent To  
Notes
2007-09-05 09:01:17** DENIED 2ND **
  
 1) NOTE: PLEASE SEE NOTES DATED 6/19/07 SPECIFICALLY
 NOTE #1. THE NOTE #2 WAS ADJUSTED AND FEES WERE PAID.
 THE NOTE #3 WILL STILL BE REQUIRED.
 THIS REVIEWER HAS ATTACHED A COPY OF THE PREVIOUS NOTES
 DATED 6/19/07.
  
 ** AS STATED ON PREVIOUS REVIEW:
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-19 Cont ID  
Sent By dpalmer Date 2007-06-19 Time 08:15 Rev Time 0.00
Received By dpalmer Date 2007-06-19 Time 07:27 Sent To  
Notes
2007-06-19 08:16:28*** UNSAT 2ND REVIEW ***
  
 1) NOTE: PLEASE SEE PLANS WERE SUBMITTED BACK WITHOUT
 ANY CORRECTIONS OR CHANGES MADE TO PLANS. THE REQUIRED
 INFORMATION IS NOT ACCEPTABLE ON LETTERS FROM
 CONTRACTOR. ALL CHANGES TO PLANS AND INFORMATION NEEDED
 ARE TO BE ON PLANS AND DONE BY THE ENGINEER OF RECORD.
 OTHER SUPPORTING DOCUMENTATION SUCH AND MANUFACTURE
 SPEC/CUT SHEETS OF ALL EQUIPMENT AS PREVIOUSLY
 REQUESTED IS TO BE ATTACHED. THE SHEETS ATTACHED ARE
 NOT ALL AS REQUESTED.
  
 2) NOTE: PLEASE SEE THE VALUE FOR THE TOTAL SCOPE OF
 WORK IS COMING BACK AT $148K WHICH IS ABOUT THE SAME
 VALUE OF THE PREVIOUS PROJECT AT STORE #50 HOWEVER THE
 SCOPE VALUE IS HIGHER THAN THAT APPLIED. THIS VALUE IS
 TO BE FOR ALL, INCLUDING GAS HOOK-UP, EQUIPMENT, AND
 LABOR ETC. THIS IS TO INCLUDE ALL MATERIALS, EQUIPMENT,
 DESIGN COST ETC EVEN IF ANY OF THESE ARE OWNER
 SUPPLIED.
 PLEASE PROVIDE A COMPLETE LIST AND BREAKDOWN OF ALL
 ABOVE AND THESE VALUES WILL BE COMPARED TO ADOPTED
 GUIDES UNDER THE FBC. A VALUE MAY BE ASSESSED BY THIS
 OFFICE IF AN ACCURATE VALUE IS NOT PROVIDED FOR ALL.
 FEES ARE DUE AT THIS TIME. PROJECT IS BEING PLACED INTO
 A HOLD STATUS AND NO OTHER REVIEWS WILL BE DONE UNTIL
 THESE FEES ARE PAID. IF FEES ARE NOT PAID BY 6/27/07
 THE PLANS WILL BE REMOVED FROM THE REVIEW PROCESS
 COMPLETELY. THESE SHOULD BE PAID UPON REVIEW OF THESE
 COMMENTS BASED ON THE FIRST INCREASE IN THE AMOUNT OF
 $1,975.80. PLANS WILL BE RETAINED BY THIS OFFICE AND
 NOT RELEASED UNTIL FEES ARE PAID.PLEASE KNOW THIS
 COMMENT HAS BEEN MADE ON SEVERAL PROJECTS FOR THE SAME
 SCOPE OF WORK AND THE SAME RESPONSE IS MADE WITHOUT ANY
 CORRECTIONS TO APPLIED WORK. ALL PERMIT APPLICATIONS,
 PLANS MAY BE RETAINED BY THIS OFFICE FOR REVIEW FROM
 THE CONTRACTORS LICENSING BOARD.
 FBC 108.3
  
 3) NOTE: PLEASE SEE THE PLUMBING REVIEW COMMENTS AS THE
 GAS INFORMATIONWILL BE REQUIRED IN THE SUBMITTED
 PACKAGE.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-06 Cont ID  
Sent By dpalmer Date 2006-10-06 Time 14:04 Rev Time 0.00
Received By dpalmer Date 2006-10-06 Time 12:10 Sent To  
Notes
2006-10-06 00:00:00***********UNSAT *************
  
 PUBLIX GENERATOR
 HAVERHILL, #821
  
 1) NOTE:PLEASE ADJUST VALUE FOR
 COMPLETE SCOPE OF WORK BEING APPLIED
 FOR. THE VALUE OF $10K ON PERMIT
 APPLICATION AUBMITTED IS EXTREMELY LOW
 PLEASE KNOW, THAT VALUE SHALL BE
 ALL LABOR AND MATERIALS EVEN IF
 MATERIALS ARE OWNER SUPPLIED. PLEASE SEE
 VALUE FOR LABOR AND INSTALLATION IS WAY
 LOW FOR SCOPE PF WORK. PLEASE SEE FBC
 2004, ADMINISTRATIVE CODE SECTION 108.3
 AS ADOPTED BY THE CITY OF WEST PALM
 BEACH.
 PLEASE KNOW, A VALUE WILL BE ASSESSED
 USING THE MARSHALL'S& SWIFT GUIDE.
 PLEASE KNOW, UNDER CONTRACTING LAWS AND
 RULES SET UP AND ADOPTED INTO FLORIDA
 STATUES, 489, FBC ADMINISTRATIVE SECTION
 105.5.1 ANY INFORMATION PROVIDED ON
 OFFICAL PERMIT APPLICATION IF KNOWINGLY
 BEING FALSIFIED CAN VOID/REVOKE SUCH
 PERMIT/ APPLICATION.
  
 2) NOTE: PLEASE KNOW, ANY SYSTEMS
 LOCATED IN A FLOOD ZONE "A" WILL BE
 REQUIRED TO BE MOUNTED AT A MIN OF 6"
 ABOVE BFE. PLEASE SEE BUILDING REVIEW
 COMMENTS.
  
 3) NOTE: PLEASE SUBMIT SPECS/MANUFACTURE
 CUT SHEETS.APS/ ATS DO NOT INDICATE
 THE REQUIRED MEANS OF DISCONNECT AS
 REQUIRED BY 230.76,230.79,225.31-39.
 PLEASE SEE A MANUAL MEANS OF DISCONNECT
 COULD NOT BE LOCATED RATED FOR THE LOAD
 SERVED ON THE OUTSIDE OF EQUIPMENT
 SUBMITTED.
 THIS WAS NEVER VERIFIED FROM PREVIOUS
 PERMIT PULLED FOR PREVIOUS PROJECT.
 NO PERMITS WILL BE RELEASED UNLESS THIS
 IS VERIFIED ON ALL SUBMITTED SPECS AND
 PLANS SUBMITTED BEFORE PERMIT IS ISSUED.
 PLEASE SEE ALL EQUIPMENT SHALL BE LISTED
 FOR USE.90.7, 110.3
  
 4) NOTE: PLEASE INDICATE THE OCP AT THE
 GEN. PLEASE SEE 445.13 AS IT HAS COME TO
 OUR ATTENTION ON A PREVIOUS PROJECT THAT
 THE GEN MAY NOT CONTAIN OCP AND CAN NOT
 BE VERIFIED AT THIS TIME.
  
 5) NOTE: PLEASE SEE NO LOAD CALCULATIONS
 WERE SUBMITTED FOR REVIEW. PLEASE
 SUBMIT.
 PLEASE SUBMIT AND INDICATE ANY LOAD
 SHEDDING DETAILS IF APPLICABLE.
 702.5, 220
  
 6) NOTE: PLEASE PROVIDE INFORMATION IF
 THE GEN WILL BE FEEDING ANY "LEGALLY
 REQUIRED STAND-BY SYSTEMS.
  
  
 7) NOTE:PLEASE SEE PLANS SHALL
 INDICATE THE CURRENT CODES IN EFFECT FOR
 INSTALLATION AS FOLLOWS.
 PLEASE SEE FBC 2004 CHAPTER 27FOR
 ADOPTED CODES RELEVANT TO POWER
 GENERATORS.
 2002 NFPA-70, 2002 NFPA-110.
  
 8) NOTE: PLEASE EXPLAIN, NOTE WHICH
 MENTIONS TO SET THE OCP ABOVE THE
 EXISTING MAIN ON E-1.???
  
 9) NOTE: PLEASE SEE THE APS/ATS IS
 BECOMING THE NEW FIRST MEANS OF
 DISCONNECT HOWEVER THE NEW GROUNDING
 ELECTRODE SYSTEMS DOES NOT SEEM TO BE
 COMPLETE AS PER 250.50.
 PLEASE SEE GROUNDING DETAIL MENTIONS NEW
 SLAB STEEL WHICH IS OK, HOWEVER PLEASE
 INDICATE ATTACHMENT.
 THESE NEW SLAB/STEEL ATTACHMENTS DO NOT
 MEET THE MIN REQUIREMENTS. PER
 250.50,250.52, 250.104
 IF SLAB STEEL IS ONLY BEING BONDED ,
 THEN PLEASE INDICATE.
 PLEASE COMPLETE GROUNDING ELECTRODE
 SYSTEM(S) AND BONDING FOR ALL AS ABOVE.
  
 10) NOTE: PLEASE INDICATE THE ACTUAL
 SEPARATION OF ALL NEUTRAL AND
 "GROUNDING" CONDUCTORS FROM THE FIRST
 MEANS OF DISCONNECT. 250.6, 250.24B
 DETAIL SHOWS THESE TO REMAIN TOGETHER
 WHICH WOULD PARALLEL THE NEUTRAL WHICH
 IS NOT PERMITTED.
  
 11) NOTE: PLEASE SEE SETS OF CONDUITS
 AND FEEDERS DO NOT SEEM TO INDICATE
 THEW NEW REQUIRED "EQUIPMENT GROUNDING
 CONDUCTOR" TO THE EXISITING MAINS. THESE
 ARE NO LONGER THE FIRST MEANS OF
 DISCONNECT.
 PER 250.110,250.122,250.24B
 215.5
  
 12) NOTE:
  
 13) NOTE:PLEASE KNOW, BASED ON A
 PREVIOUS PROJECT, IS THIS UNIT GOING TO
 BE BE "BI-FUEL"??
 IF SO, SUBMIT ALL INFORMATION AND SPECS
 ON UNIT(S).
 90.7, 110.3
  
  
 ** PLEASE KNOW, AS MUCH INFORMATION WAS
 NOT SUBMITTED, A COMPLETE REVIEW COULD
 NOT BE DONE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2008-09-02 Cont ID  
Sent By mawillia Date 2008-09-02 Time 11:56 Rev Time 0.00
Received By mawillia Date 2008-09-02 Time 11:51 Sent To B1
Notes
2008-09-02 11:53:13*****APPROVED*****
  
  
 PLAN SHEETS E1.1 AND E3 WERE STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status F Date 2008-08-14 Cont ID  
Sent By mawillia Date 2008-08-14 Time 11:13 Rev Time 0.00
Received By mawillia Date 2008-08-14 Time 10:51 Sent To  
Notes
2008-08-14 11:05:00*****PROVISO*****
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 ALL OTHER REVIEWERS HAVE BEEN SATISFIED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-06-20 Cont ID  
Sent By mawillia Date 2008-06-20 Time 12:12 Rev Time 0.00
Received By mawillia Date 2008-06-20 Time 12:01 Sent To  
Notes
2008-06-20 12:08:14*****PROVISO*****
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 ALL OTHER REVIEWERS HAVE BEEN SATISFIED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-04-24 Cont ID  
Sent By mawillia Date 2008-04-24 Time 12:05 Rev Time 0.00
Received By mawillia Date 2008-04-24 Time 12:01 Sent To  
Notes
2008-04-24 12:04:48*****PROVISO*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;HOWEVER THE APPROPIATE PLAN SHEET(S)
 TO BE FIRE-STAMPED WHEN ALL OTHER REVIEWERS HAVE BEEN
 SATISFIED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-09-24 Cont ID  
Sent By mawillia Date 2007-09-24 Time 13:56 Rev Time 0.00
Received By mawillia Date 2007-09-24 Time 13:39 Sent To  
Notes
2007-09-24 13:51:28*****PROVISO*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;HOWEVER THE APPROPIATE PLAN SHEET(S)
 TO BE FIRE-STAMPED WHEN ALL OTHER REVIEWERS HAVE BEEN
 SATISFIED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-12-05 Cont ID  
Sent By mawillia Date 2006-12-05 Time 12:04 Rev Time 0.00
Received By mawillia Date 2006-12-05 Time 11:59 Sent To  
Notes
2006-12-05 12:36:42*****DENIED*****
  
  
  
 1.PLEASE SHOW/DISPLAY THE LOCATION OF THE PROPOSED
 GENERATOR IN RELATIONSHIP TO THE BUILDING(S),
 STREETS/ROADWAYS, ETC IN THE IMMEDIATE VICINITY.
  
 2.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR
 HINDER EMERGENCY RESPONDERS ACCESS TO THE SAID PROPERTY
 OR VICINITY THEROF.
  
 3.WILL THE PROPOSED GENERATOR BE TIED INTO THE FIRE
 ALARM SYSTEM CURRENTLY BEING USED AT PUBLIX?
  
 4.HOW WILL THE PROPOSED STRUCTURE BE PROTECTED FROM
 VEHICULAR DAMAGE?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FUEL DIESEL GENERATOR
Rev No 2 Status P Date 2008-05-27 Cont ID  
Sent By tgordon Date 2008-05-27 Time 11:03 Rev Time 0.15
Received By tgordon Date 2008-05-27 Time 11:03 Sent To  
Notes
***NONE***

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status F Date 2008-04-04 Cont ID  
Sent By tgordon Date 2008-04-04 Time 14:40 Rev Time 0.20
Received By tgordon Date 2008-04-04 Time 14:36 Sent To  
Notes
2008-04-04 14:39:19PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) THE GENERATOR HAS A 1,000 GALLON DIESEL FUEL STORAGE
 TANK BELOW IT AND NEEDS TO COMPLY WITH NFPA 30 TABLE
 4.3.2.1.1(B) WHICH REQUIRES THE TANK TO BE 15 FEET FROM
 A PROPERTY LINE THAT IS OR CAN BE BUILT UPON. PLANS
 SHOW THE TANK IS 10'-11" FROM THE WEST PROPERTY LINE,
 PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2008-04-12 Cont ID  
Sent By kstevens Date 2008-04-12 Time 16:47 Rev Time 0.00
Received By kstevens Date 2008-04-12 Time 16:47 Sent To  
Notes
2008-04-12 16:50:25POWER SECURE HAS INDICATED THAT THIS WILL BE A DIESEL
 GENERATOR AND THE BI-FUEL KIT WILL BE DONE BY SEPARATE
 PERMIT.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-09-20 Cont ID  
Sent By kstevens Date 2007-09-20 Time 16:39 Rev Time 0.00
Received By kstevens Date 2007-09-20 Time 16:39 Sent To  
Notes
2007-09-20 16:41:06DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 A. A SOURCE HAS INDICATED THAT THE GENERATOR MAY BE
 BI-FUEL, (DIESEL AND NATURAL GAS OR LP GAS). IF THIS IS
 CORRECT, THE FOLLOWING INFORMATION WILL BE REQUIRED FOR
 THE REQUIRED GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 B. MANUF. SPECIFICATION SHEETS SHALL BE OF SUFFICIENT
 CLARITY AND BELEGIBLE. SHEETS SUBMITTED DO NOT MEET
 THIS REQUIREMENT.--ALSO SUBMIT MANUF. INSTALLATION
 INSTRUCTIONS SHOWING ALL REQUIRED CLEARANCES FROM
 BUILDINGS OR STRUCTURES. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-07-24 Cont ID  
Sent By adarroug Date 2008-07-24 Time 13:50 Rev Time 0.00
Received By adarroug Date 2008-07-24 Time 13:50 Sent To  
Notes
2008-07-24 13:53:29TO "COMM" BD#19

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-05-19 Cont ID  
Sent By adarroug Date 2008-05-19 Time 12:50 Rev Time 0.00
Received By adarroug Date 2008-05-19 Time 12:50 Sent To  
Notes
2008-05-19 12:53:55TO "COMM" BD#56

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-04-01 Cont ID  
Sent By adarroug Date 2008-04-01 Time 13:21 Rev Time 0.00
Received By adarroug Date 2008-04-01 Time 13:21 Sent To  
Notes
2008-04-01 13:24:09TO "COMM" BD#49

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-06 Cont ID  
Sent By adarroug Date 2007-08-06 Time 14:16 Rev Time 0.00
Received By adarroug Date 2007-08-06 Time 14:16 Sent To  
Notes
2007-08-30 14:20:30TO "COMM" BD#41
2007-08-06 14:17:03WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-23 Cont ID  
Sent By adarroug Date 2007-05-23 Time 08:20 Rev Time 0.00
Received By adarroug Date 2007-05-23 Time 08:20 Sent To  
Notes
2007-06-12 13:35:39TO "COMM" BD#27
2007-05-23 08:20:59WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-05 Cont ID  
Sent By adarroug Date 2006-12-05 Time 13:50 Rev Time 0.00
Received By adarroug Date 2006-09-21 Time 09:24 Sent To  
Notes
2006-10-06 00:00:00TO "COMM" BD#30
2006-09-21 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-05-27 Cont ID  
Sent By tgordon Date 2008-05-27 Time 11:03 Rev Time 0.15
Received By tgordon Date 2008-05-27 Time 11:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-04-04 Cont ID  
Sent By tgordon Date 2008-04-04 Time 14:27 Rev Time 0.30
Received By tgordon Date 2008-04-04 Time 14:27 Sent To  
Notes
2008-04-04 14:34:58PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 9/6/08 NOTE #1. THE
 GENERATOR HAS A 1,000 GALLON DIESEL FUEL STORAGE TANK
 BELOW IT AND NEEDS TO COMPLY WITH NFPA 30 TABLE
 4.3.2.1.1(B) WHICH REQUIRES THE TANK TO BE 15 FEET FROM
 A PROPERTY LINE THAT IS OR CAN BE BUILT UPON. PLAN SHOW
 THE TANK IS 10'-11" FROM THE WEST PROPERTY LINE, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-09-06 Cont ID  
Sent By tgordon Date 2007-09-06 Time 14:25 Rev Time 0.30
Received By tgordon Date 2007-09-06 Time 14:25 Sent To  
Notes
2007-09-06 14:40:25PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) AT TIME OF LAST REVIEW I HAD MISSED THAT THIS
 GENERATOR HAD A 1,000 GALLON DIESEL FUEL STORAGE TANK
 BELOW IT AND NEEDS TO COMPLY WITH NFPA 30 TABLE
 4.3.2.1.1(B) WHICH REQUIRES THE TANK TO BE 15 FEET FROM
 PROPERTY LINE THAT IS OR CAN BE BUILT UPON. PLAN PAGE
 E3 SHOWS THE TANK 10'-11" FROM THE PROPERTY LINE,
 PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-24 Cont ID  
Sent By tgordon Date 2006-10-24 Time 09:43 Rev Time 0.30
Received By tgordon Date 2006-10-24 Time 09:43 Sent To  
Notes
2006-10-24 09:47:34*** DENIED ***
 1) SEE REVIEW NOTES BY OTHER DEPARTMENTS, PLEASE MAKE
 CORRECTIONS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status N Date 2007-09-20 Cont ID  
Sent By kstevens Date 2007-09-20 Time 16:24 Rev Time 0.00
Received By kstevens Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-10-20 Cont ID  
Sent By kstevens Date 2006-10-20 Time 12:55 Rev Time 0.00
Received By kstevens Date 2006-10-20 Time 12:55 Sent To  
Notes
2006-10-20 12:56:06INFORMATION SUBMITTED INDICATES THE FUEL SOURCE IS
 DIESEL.

Review Stop Z ZONING
Rev No 3 Status P Date 2008-04-03 Cont ID  
Sent By jroach Date 2008-04-03 Time 16:24 Rev Time 0.00
Received By jroach Date 2008-04-03 Time 16:24 Sent To  
Notes
2008-04-03 16:25:42***PROVISO***
  
 1) PRIOR TO FINAL INSPECTION, THE PROPOSED FENCE SHALL
 BE INSTALLED.SHRUBS/HEDGES SHALL BE INSTALLED ALONG
 THE PERIMETER OF THE FENCE AT A MINIMUM OF TWO (2) FOOT
 INTERVALS.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-09-13 Cont ID  
Sent By jroach Date 2007-09-13 Time 08:17 Rev Time 0.00
Received By jroach Date 2007-09-13 Time 08:17 Sent To  
Notes
2007-09-13 08:20:10***FAILED***
  
 1) MINOR AMENDMENT TO THE PARADISE PLAZA COMMERCIAL
 PLANNED DEVELOPMENT (CPD) SHALL BE SUBMITTED AND
 APPROVED TO THE CITY'S PLANNING DEPARTMENT PRIOR TO THE
 ISSUANCE OF A BUILDING PERMIT.
  
 2) AS REQUIRED BY SECTION 94-444(B) OF THE CITY'S
 ZONING AND LAND DEVELOPMENT REGULATIONS, GENERATOR
 SHALL BE SCREENED WITH A WALL OF ADEQUATE HEIGHT AND
 LANDSCAPED WITH SHRUBS/HEDGES PLANTED AT 2-FOOT
 INTERVALS.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT JOHN ROACH, SENIOR
 PLANNER, AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-11-14 Cont ID  
Sent By jroach Date 2006-11-14 Time 11:05 Rev Time 0.00
Received By jroach Date 2006-11-14 Time 11:05 Sent To I
Notes
2006-11-14 11:08:31***FAILED***
  
 1) MINOR AMENDMENT TO THE PARADISE PLAZA COMMERCIAL
 PLANNED DEVELOPMENT (CPD) SHALL BE SUBMITTED AND
 APPROVED TO THE CITY'S PLANNING DEPARTMENT PRIOR TO THE
 ISSUANCE OF A BUILDING PERMIT.
  
 2) AS REQUIRED BY SECTION 94-444(B) OF THE CITY'S
 ZONING AND LAND DEVELOPMENT REGULATIONS, GENERATOR
 SHALL BE SCREENED WITH A WALL OF ADEQUATE HEIGHT AND
 LANDSCAPED WITH SHRUBS/HEDGES PLANTED AT 2-FOOT
 INTERVALS.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT JOHN ROACH, SENIOR
 PLANNER, AT (561) 822-1435.