Plan Review Details - Permit 06090648
Plan Review Stops For Permit 06090648
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-09-25 Cont ID  
Sent By shill Date 2006-09-25 Time 08:41 Rev Time 0.00
Received By shill Date 2006-09-25 Time 07:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-20 Cont ID  
Sent By shill Date 2006-09-20 Time 10:24 Rev Time 0.00
Received By shill Date 2006-09-20 Time 10:24 Sent To  
Notes
2006-09-20 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
 ____1.)A NOTICE OF COMMENCEMENT
 MUST BE FILED WITH THE CLERK OF COURTS
 BEFORE A PERMIT CAN BE ISSUED.
  
 _XX_2.)CONTRACTOR IS TO PROVIDE THE
 FOLLOWING INFORMATION ON THE
 APPLICATION, SEE ATTACHED POLICY:
  
  ROOF DECK TYPE
  AREA OF EACH ROOF TYPE
  
 _XX_3.)THE EVALUATION REPORT
 SUBMITTED IS ILLEGIBLE.IT DOES NOT
 MATCH THE REPORT ON THE WEBSITE.THE
 PRODUCT APPROVAL 1654 IS FOR LWIC DECK.
 PLEASE ADDRESS.
  
 ____4.)FOR THE FLAT DECK, SELECT THE
 APPROVED ASSEMBLY YOU ARE USING.
  
 ____ 5.)ON THE TILE PRODUCT APPROVAL,
 INDICATE WHICH METHOD OF ATTACHMENT YOU
 ARE USING.
  
 ____ 6.)SEE PRODUCT LIMITATION #7.
 CALCULATIONS PREPARED BY AN ARCHITECT,
 ENGINEER, OR REGISTERED ROOF CONSULTANT
 REQUIRED FOR ENHANCED FASTENING.
  
  
  
  