Plan Review Details - Permit 06090582
Plan Review Stops For Permit 06090582
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-23 Cont ID  
Sent By adarroug Date 2006-09-23 Time 17:33 Rev Time 0.00
Received By adarroug Date 2006-09-23 Time 17:33 Sent To M
Notes
2006-09-23 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-18 Cont ID  
Sent By tgordon Date 2006-09-18 Time 16:27 Rev Time 0.00
Received By tgordon Date 2006-09-18 Time 13:40 Sent To  
Notes
2006-09-18 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-10-02 Cont ID  
Sent By tgordon Date 2006-10-02 Time 11:52 Rev Time 0.25
Received By tgordon Date 2006-10-02 Time 11:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-09-18 Cont ID  
Sent By tgordon Date 2006-09-18 Time 16:08 Rev Time 0.30
Received By tgordon Date 2006-09-18 Time 16:08 Sent To  
Notes
2006-09-18 00:00:00*** DENIED ***
 1) MANUAL J CAL'S ARE CALLING FOR 23,867
 SENSIBLE BTU'S, THE PLANS ARE CALLING
 FOR 35,000 SENSIBLE BTU'S, THE PLANS CAN
 ONLY CALL FOR 20% MORE THAN THE MANUAL J
 CAL'S, PER 2005 FBC CH. 13
 607.1.ABC.1.1, PLEASE CORRECT.
  
 2) PLEASE SUBMIT A SIGNED PROPOSAL OR
 AJUST THE VALUE ON THE PERMIT
 APPLICATION, AS THE VALUE ON THE PERMIT
 APPLICATION APPEARS LOW FOR THE WORK TO
 BE DONE, OR THE CITY WPB WILL AJUST THE
 VALUE USING MARSHALL & SWIFT ESTIMATOR,
 PER 2004 CITY WPB AMEND. 108.3 .
  
 3) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 4) PLEASE ARRANGE FOR PERMIT # 06071027
 TO BE VOIDED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.