Plan Review Details - Permit 06090474
Plan Review Stops For Permit 06090474
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-09-21 Cont ID  
Sent By lursu Date 2006-09-21 Time 14:47 Rev Time 0.00
Received By lursu Date 2006-09-14 Time 14:56 Sent To  
Notes
2006-09-21 00:00:00ATTACH PERMIT TO : TEMP7442430208101
2006-09-14 00:00:00NEED TO ADD AN EXTENSION TO THIS ADDRESS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-11-29 Cont ID  
Sent By rmcdouga Date 2006-11-29 Time 14:35 Rev Time 0.00
Received By rmcdouga Date 2006-11-29 Time 14:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-19 Cont ID  
Sent By rmcdouga Date 2006-09-19 Time 07:52 Rev Time 0.00
Received By rmcdouga Date 2006-09-19 Time 07:15 Sent To  
Notes
2006-09-19 00:00:00DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) 505.2 AREA LIMITATION.
 THE AGGREGATE AREA OF A MEZZANINE OR
 MEZZANINES WITHIN A ROOM SHALL NOT
 EXCEED ONE-THIRD OF THE AREA OF THAT
 ROOM OR SPACE IN WHICH THEY ARE LOCATED.
 THE ENCLOSED PORTIONS OF ROOMS SHALL NOT
 BE INCLUDED IN A DETERMINATION OF THE
 SIZE OF THE ROOM IN WHICH THE MEZZANINE
 IS LOCATED. IN DETERMINING THE ALLOWABLE
 MEZZANINE AREA, THE AREA OF THE
 MEZZANINE SHALL NOT BE INCLUDED IN THE
 AREA OF THE ROOM. SUBMIT CALCULATIONS
 INDICATING THAT THE AREA OF THE
 MEZZANINE DOES NOT EXCEED ONE-THIRD OF
 THE FLOOR AREA OF THE ROOM IN WHICH IT
 IS LOCATED, NOT INCLUDING THE ENCLOSED
 AREAS OF THE FIRST FLOOR (INCLUDING NEW
 ENCLOSURE AT OVERHEAD DOOR).
  
 3) THE EXTERIOR OVERHEAD DOOR IS
 REQUIRED TO REMAIN.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-11-16 Cont ID  
Sent By dpalmer Date 2006-11-16 Time 14:07 Rev Time 0.00
Received By dpalmer Date 2006-11-16 Time 13:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-20 Cont ID  
Sent By dpalmer Date 2006-09-20 Time 12:24 Rev Time 0.00
Received By dpalmer Date 2006-09-20 Time 07:51 Sent To  
Notes
2006-09-20 00:00:00**********UNSAT *************
  
 1) NOTE: PLEASE INDICATE ALL CIRCUITING
 ON PLANS AND CORRELATE WITH A PANEL
 SCHEDULE TO BE PROVIDED.
 408.4, 310.16,240.4
 FBC 106.1.2
  
 2) NOTE: PLEASE CLARIFY THE NEW OR
 EXISTING LIGHTING LEVELS FOR THE STAIRS
 WAYS FOR A MIN OF 10FT CANDLES UDNER
 NORMAL AND 1FT MIN UNDER EMERGENCY.
 7.8.1.3, 7.9.2.2
 PLEASE ALSO INDICATE SOME SORT OF EM
 BATTERY BACK UP FIXTURE REQUIRED FOR MIN
 LTS.
  
 3) NOTE: PLEASE SEE BUILDING REVIEW
 COMMENTS AS TO ANY COMMENTS WHIHC MAY
 AFFECT THE ELECTRICAL DESIGN.
  
 4) NOTE: PLEASE SEE ITEMS ON NOTES WHICH
 ARE NOT ON PLANS. SD'S ETC.
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE THAT ALL PLANS ARE
 REQUIRED TO CONTAIN THE PRINTED NAME,
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 PLANS AND DESIGN.
 FBC 106.1.2 ADMIN SECT.
  
 6) NOTE: PLEASE COMPLETE PANEL SCHEDULE
 WITH ALL OCP AND CONDUCTOR SIZES. PLEASE
 SEE THAT SOME ITEMS ARE SHOWN , BUT NOT
 CLEAR WHAT THEY ARE FEEDING. (50A
 CIRCUIT, ETC
 ALL AREAS /ROOMS ARE TO BE SPECIFIC .
 240.4,310.16,408.4
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-11-22 Cont ID  
Sent By mwennerg Date 2006-11-22 Time 15:07 Rev Time 0.00
Received By mwennerg Date 2006-11-22 Time 15:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-09-21 Cont ID  
Sent By mwennerg Date 2006-09-21 Time 11:20 Rev Time 0.00
Received By mwennerg Date 2006-09-21 Time 11:20 Sent To  
Notes
2006-09-21 00:00:00***DENIED***
  
 1) PLANS SHOW EXISTING STROBE LIGHTS.
 WHAT ARE THEY CONNECTED TO? IF PART OF A
 FIRE ALARM SYSTEM OR EXISTING STAND
 ALONE AC UNIT DUCTS, PLEASE INDICATE AND
 ALSO SHOW IF THEY INCLUDE AUDIBILITY.
  
 2) IS THERE AN EXISTING FIRE SPRINKLER
 SYSTEM, AND IF SO WILL THIS WORK HAVE AN
 IMPACT ON SUCH SYSTEM?
  
 3) CONSTRUCTION, ALTERATION AND
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-06 Cont ID  
Sent By adarroug Date 2007-03-06 Time 16:27 Rev Time 0.00
Received By adarroug Date 2007-03-06 Time 16:27 Sent To M
Notes
2007-03-06 16:27:27TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-07 Cont ID  
Sent By adarroug Date 2006-11-07 Time 16:52 Rev Time 0.00
Received By adarroug Date 2006-11-07 Time 16:52 Sent To  
Notes
2006-11-16 11:44:07TO "BOB"#13
2006-11-07 16:52:58WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-21 Cont ID  
Sent By mwennerg Date 2006-09-21 Time 11:33 Rev Time 0.00
Received By mwennerg Date 2006-09-14 Time 16:55 Sent To  
Notes
2006-09-14 00:00:00TO "BOB"#12

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-03-08 Cont ID  
Sent By tgordon Date 2007-03-08 Time 13:41 Rev Time 0.15
Received By tgordon Date 2007-03-08 Time 13:41 Sent To  
Notes
2007-03-08 13:42:32MECHANICAL REVISION TO PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-03-07 Cont ID  
Sent By tgordon Date 2007-03-07 Time 12:02 Rev Time 0.25
Received By tgordon Date 2007-03-07 Time 12:02 Sent To  
Notes
2007-03-07 12:12:34MECHANICAL REVISION
 *** DENIED ***
 1) PLEASE SHOW CFM'S AT SUPPLY AIR GRILLS.
 NOTE. 12" RETURN AIR DUCT MAY BE TO SMALL BUT CAN NOT
 DETERMINE UNTIL CFM'S ARE SHOWN.
  
 2)ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-11-22 Cont ID  
Sent By tgordon Date 2006-11-22 Time 11:20 Rev Time 0.20
Received By tgordon Date 2006-11-22 Time 11:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-09-15 Cont ID  
Sent By tgordon Date 2006-09-15 Time 13:36 Rev Time 0.30
Received By tgordon Date 2006-09-15 Time 13:36 Sent To  
Notes
2006-09-15 00:00:00*** DENIED ***
 1) PLANS NEED THE DESIGNER'S INFORMATION
 ON THEM. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 2) 10" RETURN AIR DUCT (FLEX) TO TRUNK
 LINE IS TO SMALL, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  