Plan Review Details - Permit 06090449
Plan Review Stops For Permit 06090449
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-09-14 Cont ID  
Sent By lursu Date 2006-09-14 Time 15:14 Rev Time 0.00
Received By lursu Date 2006-09-14 Time 11:29 Sent To  
Notes
2006-09-14 00:00:00NEED AN EXTENSION FOR THIS ADDRESS
 ATTACH PERMIT TO EXT #009 UNIT 104

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-08-29 Cont ID  
Sent By jwitmer Date 2007-08-29 Time 16:09 Rev Time 2.00
Received By jwitmer Date 2007-08-29 Time 14:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-03-29 Cont ID  
Sent By jwitmer Date 2007-03-29 Time 15:02 Rev Time 0.66
Received By jwitmer Date 2007-03-29 Time 15:01 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-12-07 Cont ID  
Sent By jwitmer Date 2006-12-07 Time 14:02 Rev Time 1.77
Received By jwitmer Date 2006-12-07 Time 14:02 Sent To  
Notes
2006-12-07 14:03:51PERMIT: 06090449
 ADD: 2247 PALM BEACH LAKES BLVD., SUITE 104
 CONT: TROPIC BUILDERS
 TEL: (561)271-8723
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATETHE REVISION &
 REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2) IF THE WORK
 DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT ACTUALLY
 COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID.
  
 3) COMPLIED.
  
 4) COMPLIED.
  
 5) COMPLIED.
  
 6) 2ND REQUEST,PLANS INDICATE DOOR# 101 ARE MISSING
 THE REQUIRED 18" ON THE PULL SIDE OF DOOR. 11-4.13.6
 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS THAT
 ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN
 IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH IN THE REQUIRED
 CLEARANCES SHALL BE CLEAR & LEVEL.
 1003.3.3 HORIZONTAL PROJECTIONS .
 ELEMENTS CANNOT PROJECT OVER A WALKING SURFACE MORE
 THAN 4 INCHES (102 MM) WHEN THEY ARE LOCATED BETWEEN 27
 AND 80 INCHES (686 AND 2032 MM) ABOVE THE FLOOR.
 HANDRAILS CAN PROJECT UP TO 4" INCHES (114 MM) FROM THE
 WALL.
  
 7) THE ARCHITECTS NAME LESLAW A. CZACZYK INTHE
 TITLEBLOCK
 IS STAMPED SIGNATURE NOT AN ORIGINAL AS REQUIRED BY:
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-10 Cont ID  
Sent By jwitmer Date 2006-10-10 Time 07:33 Rev Time 1.11
Received By jwitmer Date 2006-10-10 Time 07:33 Sent To  
Notes
2006-10-10 07:46:55BUILDING PLAN REVIEW
 PERMIT: 06090449
 ADD: 2247 PALM BEACH LAKES BLVD., SUITE 104
 CONT: TROPIC BUILDERS
 TEL: (561)271-8723
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATETHE REVISION &
 REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2) IF THE WORK
 DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT ACTUALLY
 COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID.
  
 3) THE ARCHITECT OF RECORD IS MISSING THEIR PRINTED
 NAME IN THE TITLEBLOCK. FSS 481.221.
  
 4) T.1 CODE NOTE # 8 TO INDICATE THE CURRENT FLORIDA
 ACCESSIBILITY CODE 2004 FLORIDA BUILDING CODE,
 BUILDING- CHAPTER 11.
  
 5)T.1 IS MISSING IN THE PROJECT DATA :
 5A) 2004 FLORIDA EXISTING BUILDING CODE
 5B) LEVEL OF ALTERATION
 5C) TOTAL SQ. FOOTAGE /FLOOR
 5D) HEIGHT OF BLDG. & STORIES.
  
 6) PLANS INDICATE THE FRONT ENTRY DOOR & DOOR# 101 ARE
 MISSING THE REQUIRED 18" ON THE PULL SIDE OF DOOR.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS THAT
 ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN
 IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH IN THE REQUIRED
 CLEARANCES SHALL BE CLEAR & LEVEL. BUILDING PLAN
 REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-08-01 Cont ID  
Sent By dpalmer Date 2007-08-01 Time 17:47 Rev Time 0.00
Received By dpalmer Date 2007-08-01 Time 17:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-04-08 Cont ID  
Sent By dpalmer Date 2007-04-08 Time 09:30 Rev Time 0.00
Received By dpalmer Date 2007-04-08 Time 09:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-03-02 Cont ID  
Sent By dpalmer Date 2007-03-02 Time 09:15 Rev Time 0.00
Received By dpalmer Date 2007-03-01 Time 17:53 Sent To  
Notes
2007-03-02 09:16:36*** UNSAT ***
  
 1) NOTE: PLEASE SEE THE LIGHTING POWER DENSITIES AND
 THE LIGHTING FIXTURES ON PLANS AND FIXTURE LEGEND DO
 NOT CORRELATE.
 PLEASE SEE THERE ARE SEVERAL AREAS/ROOMS WHICH THE
 LIGHTING WATTAGE EXCEEDS THAT OF THE TABLES AND
 ALLOWANCES PERMITTED BY THE TABLES AND THE FBC ENERGY
 CODE.
 13-415.2.
 PLEASE SEE 13-415.1AB.1.1 AND SEE ENERGY CALCULATIONS
 FOR USE.
 PLEASE SEE THE TABLES FOR MAX LIGHTING ALLOWANCES.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-03-01 17:53:14IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-12-03 Cont ID  
Sent By dpalmer Date 2006-12-03 Time 20:10 Rev Time 0.00
Received By dpalmer Date 2006-12-03 Time 19:30 Sent To  
Notes
2006-12-03 20:12:58*** UNSAT 2ND REVIEW****
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW AND NEW
 NOTES DUE TO THE PLANS SUBMITTED.
 THE NOTES BELOW ARE TAKEN DIRECTLY FROM PREVIOUS REVIEW
 AND INDICATE A "NO OR OK". IF A "NO" IS SHOWN FURTHER
 EXPLANATION/NOTES MAY BE PRESENT.
 ** PLEASE SEE ANY NEW NOTES ARE BEING ADDED TO THE
 BOTTOM OF FIRST REVIEW NOTES.
  
 ** PLEASE KNOW A RESPONSE LETTER FROM THE DESIGN
 PROFESSIONAL EXPLAINS HOW EACH COMMENT WAS ADDRESSED OR
 A RESPONSE ON THE COMMENT ITSELF IS MOST HELPFUL IN THE
 REVIEW PROCESS.
  
 1) NOTE: OK, HOWEVER SEE NEW NOTES.
  
 2) NOTE: OK.
  
 3) NOTE:NO, IT IS UNCLEAR WHERE THIS DETAIL IS ON
 PLANS. DETAIL FOR THE REDUNDANT GROUNDING IS REQUIRED.
 WHICH METHOD WILL BE USED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT NEC 517, 517.13 DETAILS IS SHOWN ON
 PLANS.
 PLEASE SEE NOTE BELOW RISER DENOTING GROUND BOND PER
 NEC MAY NOT USED IN LIEU OF DETAIL REQUIRED.
 FBC 106.1.2 ADMIN SECT AS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
 4) NOTE:NO, PLEASE SEE PLANS NOW INDICATE "OC SENSOR"
 TYPE DEVICES AT ALL LOCATIONS. PLEASE SEE THAT THE
 EMERGENCY LIGHTS AND EXIT LIGHTS SHALL BE SHOWN AHEAD
 OF ANY LIGHTING CONTROL DEVICE. PLEASE SEE SOME EXT LTS
 DO NOT INDICATE CIRCUITING. PLEASE SEE 700.12E.
 PLEASE SEE LIGHTING POWER DENSITIES COULD NOT BE
 LOCATED ON PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1, .1.2 AND
 .1.3.
 PLEASE PROVIDE LIGHTING CONTROL(S), STATED DEVICES, AND
 LOCATIONS OF OVER RIDES AND DEVICES. PLEASE INDICATE
 THE MAX TIMES ON OVER RIDES. (FYI, TIMER TYPE
 4HRS MAX, OCCUPANT TYPE 30MINS MAX).
 PLEASE INDICATE THE MAX LPD(LIGHTING POWER DENSITIES).
 PER 13-415.2.ABC.1, TABLES 415.
  
 5) NOTE: NO, SAME NOTE.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE INDICATE ALL ROOM/AREAS DESIGNATIONS ON PLANS
 AND CORRELATE PANEL SCHEDULE WHICH IS TO BE SPECIFIC TO
 AREAS BEING FED.
 408.4,
  
 6) NOTE: OK. MEETS EXCEPTION.
  
 7) NOTE: OK? PLEASE SEE RISER SEEMS TO BE OK, HOWEVER A
 QUESTION ON THE DESIGNATION OF MULTIPLE BREAKERS IN THE
 MDP WHICH MENTIONS DESIGNATIONS TO OTHER PANEL "A'S??
 PLEASE CLARIFY IN RESPONSE/PLANS THE OTHER BREAKERS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE RISER SHOW THE MAIN PANEL IN SPACE AS 400
 MCB. PLEASE SEE THIS APPEARS TO BE A MISPRINT AS THE
 SCHEDULE AND SERVICE PROVIDED MENTIONS 300A.
 (POSSIBLE, 400MLO/300MCB.
 FBC 106.1.2 ADMIN SECT.
  
 8) NOTE: OK.
  
 9) NOTE: NO, PLEASE SHOW, HOW WATTS PER SQ FT, HOW MANY
 RECEPTS AND VA PER RECEPT AND HOW THE CONNECTED LOADS
 SHOWN ARE BEING DERIVED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE WHERE THE CONNECTED LOADS ARE BEING
 DERIVED.
 PLEASE INDICATE A LOAD SUMMARY FOR SPACE. PLEASE ALSO
 INDICATE ALL CONTINUOUS LOADS AT 125% (3OR MORE HRS).
 220.3,220.10,220.11,220.13,215.3, 230.42
 ETC.
  
 10) NOTE: NO, PLEASE SEE MISSING EQUIPMENT GROUNDING
 STILL NOT SHOWN FROM PANEL "A" TO "A-1".
 PREVIOUS NOTE REQUESTED TO SHOW ALL.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE "EQUIPMENT GROUNDING" METHOD FROM MAIN
 MDP TO ALL EQUIPMENT.
 250.110, 250.122.
 ** PLEASE KNOW, IF USING CONDUIT, THERE MUST BE THE NEW
 CONNECTORS WHICH MUST BE LISTED FOR THIS PURPOSE,
 OTHERWISE PLEASE INDICATE THE "EQUIPMENT GROUNDING
 CONDUCTOR" PER 250.122.
  
 11) NOTE: OK, HOWEVER VERIFY A 400A MLO PANEL ONLY
 BEING 30POLES? THIS DOES NOT NEED TO BE CHANGED ON
 PLANS. THIS WILL BE VERIFIED IN FIELD. IF PANEL
 INSTALLED, IS INDEED A 42CIRCUIT PANEL, THEN PLANS WILL
 BE REQUIRED TO BE REVISED.
  
 ** PREVIOUS REVIEW NOTE **PLEASE SEE PANEL "A-1"
 INDICATES 30POLES, YET SHOWS 42 CIRCUITS/POLES ARE
 SHOWN ON PANEL..
 PLEASE CORRELATE AND ADJUST.
 106.1.2 FBC.
  
 12) NOTE: OK. SHOWS 65K FOR BRANCH CIRCUIT BREAKER.
  
  
  
 *** NEW NOTES FOR SECOND REVIEW***
  
 1) NOTE: PLEASE SEE BOTH SETS OF NEW REVISED PLANS
 BEING SUBMITTED CONTAIN A "RUBBER-STAMP" FOR THE
 REQUIRED ORIGINAL SIGNATURE. PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G1-16.003, 004 AND FLORIDA
 STATUTES WHICH REQUIRES AN ORIGINAL SIGNATURE.
 (EVIDENCE OF AUTHENTICITY).
 PLEASE KNOW, AT THIS TIME ONE SET OF EACH OF THE PLANS
 WILL BE RETAINED BY THIS OFFICE, INCLUDING ONE SET OF
 ORIGINAL SUBMITTED PLANS WHICH WERE SIGNED WITH AN
 ORIGINAL SIGNATURE.
 PLEASE KNOW, IF THERE IS ANY VERIFICATION NEEDED FOR
 SIGNATURE REQUIRED PLEASE CONTACT THE FLORIDA BOARD OF
 ARCHITECT?S LEGAL COUNSEL. MR. LES SMITH INVESTIGATOR
 TO THE BOARD OR MR. DAVID MINACCI PROSECUTING
 ATTORNEY.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-30 Cont ID  
Sent By dpalmer Date 2006-09-30 Time 15:10 Rev Time 0.00
Received By dpalmer Date 2006-09-30 Time 14:19 Sent To  
Notes
2006-09-30 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE FAC 61G1-16.004,
 WHICH REQUIRES THE PRINTED NAME OF THE
 ARCHITECT ON TITLE BLOCKS.
 PLEASE ALSO SEE THAT THE RAISED SEALS
 MUST BE CLEAR AND VISABLE WITH ALL
 INFORMATION AS REQUIRED ON SAID SEAL.
 PLEASE SEE SEALS ARE NOT EASILY
 READABLE.
 FS 481.221, FAC 61G1-16.003
 ** THIS IS REQUIRED FOR ALL SHEETS AND
 FOR ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2) NOTE: PLEASE SEE THE FOLLOWING MIN
 CODES SHALL BE STATED ON PLANS. IMPLY
 STATING THE "LATEST EDITION" CAN NOT BE
 USED AS THE LATEST EDITIONS OF SOME
 CODES ARE OUT AND AVAILABLE YET NOT YET
 ADOPTED BY THE STATE.
 PLEASE STATE THE FOLLOWING.
 2002 NFPA-70 (NEC), 2002 NFPA-72, 2003
 NFPA-101, 2004 FBC.
 PLEASE KNOW, OTHER CODES RELEVANT MAY BE
 REQUESTED BY OTHER REVIEWER(S).
  
 3) NOTE: PLEASE SEE THAT NEC 517, 517.13
 DETAIL IS SHOWN ON PLANS.
 PLEASE SEE NOTE BELOW RISER DENOTING
 GROUND BOND PER NEC MAY NOT USED IN LEIU
 OF DETAIL REQUIRED.
 FBC 106.1.2 ADMIN SECT AS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
 4) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1,
 .1.2 AND .1.3.
 PLEASE PROVIDE LIGHTING CONTROL(S),
 STATED DEVICES, LOCATIONS OF OVER RIDES
 AND EVICES. PLEASE INDICATE THE MAX
 TIMES ON OVER RIDES. (FYI, TIMER TYPE
 4HRS MAX, OCCUPANT TYPE 30MINS MAX).
 PLEASE INDICATE THE MAX LPD(LIGHTING
 POWER DENSITIES). PER 13-415.2.ABC.1,
 TABLES 415.
  
 5) NOTE: PLEASE INDICATE ALL ROOM/AREAS DESIGNATIONS ON
 PLANS AND CORRELATE
 PANEL SCHEDULE WHICH IS TO BE SPECIFIC
 TO AREAS BEING FED.
 408.4,
  
 6) NOTE: PLEASE PROVIDE EITHER NEW OR
 EXISTING SIGN CIRCUIT LOCATION PER
 600.5. IT IS UNCLEAR AT THIS TIME.
  
 7) NOTE: PLEASE SEE RISER SHOW THE MAIN
 PANEL IN SPACE AS 400 MCB. PLEASE SEE
 THIS APPEARS TO BE A MISPRINT AS THE
 SCHEDULE AND SERVICE PROVIDED MENTIONS
 300A.
 POSSIBLE, 400MLO/300MCB.
 FBC 106.1.2 ADMIN SECT.
  
 8) NOTE: PLEASE INDICATE IF PANEL "A"
 CONTAINS "FEED-THRU" LUGS OR IS THERE
 OCP WHICH FEEDS PANEL"A-1'.??
  
 9) NOTE: PLEASE INDICATE WHERE THE
 CONNECTED LOADS ARE BEIGN DERIVED.
 PLEASE INDICATE A LOAD SUMMARY FOR
 SPACE. PLEASE ALSO INDICATE ALL
 CONTINUOUS LOADS AT 125% (3OR MORE HRS).
 220.3,220.10,220.11,220.13,215.3, 230.42
 ETC.
  
 10) NOTE: PLEASE INDICATE "EQUIPMENT
 GROUNDING" METHOD FROM MAIN MDP TO ALL
 EQUIPMENT.
 250.110, 250.122.
 ** PLEASE KNOW, IF USINGCONDUIT, THERE
 MUST BE THE NEW CONNECTORS WHICH MUST BE
 LSTED FOR THIS PURPOSE, OTHERWISE PLEASE
 INDICATE THE "EQUIPMENT GROUNDING
 CONDUCTOR" PER 250.122.
  
 11) NOTE; PLEASE SEE PANEL "A-1"
 INDICATES 30POLES, YET SHOWS 42
 CIRCUITS/POLES ARE SHOWN ON PANEL..
 PLEASE CORRELATE AND ADJUST.
 106.1.2 FBC.
  
 12) NOTE; PLEASE PROVIDE THE AIC RATING
 FOR THE NEW MB FROM MDP TO NEW TENANT
 SPACE.
 PLEASE ALSO SEE THE AIC RATING FOR EACH
 OF THE TENANT PANELS IS BEING SHOWN AT
 22K, WHICH SEEMS HIGH FOR BRANCH BRKRS??
 ** THIS IS OK, HOWEVER PLEASE KNOW, IF
 SHOWN, THEN 22K RATED BRNACH BRKRS WILL
 BE REQUIRED.
 110.9,
 FBC 106.1.2 ADMIN SECT.
 106.3.5.1.2
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT THE ELECTRICAL PLANS/DEISGN.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-08-30 Cont ID  
Sent By mawillia Date 2007-08-30 Time 15:53 Rev Time 0.00
Received By mawillia Date 2007-08-30 Time 15:43 Sent To  
Notes
2007-08-30 15:53:05*****APPROVED*****
  
  
  
 REVISED PLAN SHEETS A.1AND E.2 WERE STAMPED, INITIALED,
 AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-04-12 Cont ID  
Sent By mawillia Date 2007-04-12 Time 14:56 Rev Time 0.00
Received By mawillia Date 2007-04-12 Time 14:37 Sent To  
Notes
2007-04-12 14:55:50*****APPROVED*****
  
  
  
 PLAN SHEETS A.1, A.2, AND E.2 WERE STAMPED, INITIALED,
 AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-03-22 Cont ID  
Sent By mawillia Date 2007-03-22 Time 10:07 Rev Time 0.00
Received By mawillia Date 2007-03-22 Time 09:24 Sent To  
Notes
2007-03-22 10:07:52****PROVISO*****
  
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;APPROPIATE PLAN SHEET(S) WILL BE
 STAMPED ONCE OTHER PLAN REVIEWS HAVE BEEN SATISFIED.
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-12-22 Cont ID  
Sent By mawillia Date 2006-12-22 Time 11:58 Rev Time 0.00
Received By mawillia Date 2006-12-22 Time 11:58 Sent To  
Notes
2006-12-22 12:04:45*****DENIED*****
  
 THE FOLLOWING COMMENTS WERE TAKEN FROM THE PREVIOUS
 FIRE PLAN REVIEW:
  
  
  
 1.)IN ADDTION TO NFPA 101 (2003 EDITION), THE FLORIDA
 FIRE PREVENTION CODE (2004 EDITION) SHALL BE
 REFERENCED.
  
 2.)STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.)CONSTRUCTION, AND/OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY AND THE VICINITY THEREOF (INCLUDING FIRE
 LANES).
  
 4.) ALL EXITS AND EXIT CORRIDORS ARE TO REMAIN CLEAR
 AND UNOBSTRUCTED DURING CONSTRUCTION OPERATIONS.
  
 5.)ON SHEET A.1 IT SHOWS THAT ACCESS TO THE FIRE
 EXTINGUISHER(S) WILL BE OBSTRUCTED WHEN THE DOOR IS/ARE
 OPENED.OK!!
  
 6.)PLANS OR INFORMATION DOES NOT INDICATE IF THE
 EXISTING BUILDING HAS A FIRE ALARM SYSTEM.IF SO,
 PLEASE SHOW A LAYOUT OF THE DEVICES IN THE EXISTING/NEW
 TENANT SPACE.
  
 7.)IF THE SCOPE OF THE INTERIOR BUILDOUT REQUIRES
 MODIFICATION OF THE FIRE ALARM OR FIRE SPRINKLER
 SYSTEM, SEPARATE PERMIT AND DRAWINGS ARE TO SUBMITTED
 FOR REVIEW.
  
 8.)THE FIRE DEPARTMENT WILL BE NOTIFIED WHEN A FIRE
 PROTECTION SYSTEM IS SHUT DOWN AND WHEN IT IS RETURNED
 TO SERVICE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-25 Cont ID  
Sent By mawillia Date 2006-10-25 Time 10:27 Rev Time 0.00
Received By mawillia Date 2006-10-25 Time 10:25 Sent To  
Notes
2006-10-25 13:53:03*****DENIED*****
  
  
  
 1.)NFPA 101 (2003 EDITION) AND FLORIDA FIRE
 PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED.
  
 2.)STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.)CONSTRUCTION, AND/OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY AND THE VICINITY THEREOF (INCLUDING FIRE
 LANES).
  
 4.) ALL EXITS AND EXIT CORRIDORS ARE TO REMAIN CLEAR
 AND UNOBSTRUCTED DURING CONSTRUCTION OPERATIONS.
  
 5.)ON SHEET A.1 IT SHOWS THAT ACCESS TO THE FIRE
 EXTINGUISHER(S) WILL BE OBSTRUCTED WHEN THE DOOR IS/ARE
 OPENED.
  
 6.)PLANS OR INFORMATION DOES NOT INDICATE IF THE
 EXISTING BUILDING HAS A FIRE ALARM SYSTEM.IF SO,
 PLEASE SHOW A LAYOUT OF THE DEVICES IN THE EXISTING/NEW
 TENANT SPACE.
  
 7.)IF THE SCOPE OF THE INTERIOR BUILDOUT REQUIRES
 MODIFICATION OF THE FIRE ALARM OR FIRE SPRINKLER
 SYSTEM, SEPARATE PERMIT AND DRAWINGS ARE TO SUBMITTED
 FOR REVIEW.
  
 8.)THE FIRE DEPARTMENT WILL BE NOTIFIED WHEN A FIRE
 PROTECTION SYSTEM IS SHUT DOWN AND WHEN IT IS RETURNED
 TO SERVICE.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-12-12 Cont ID  
Sent By adarroug Date 2007-12-12 Time 10:34 Rev Time 0.00
Received By adarroug Date 2007-12-12 Time 10:34 Sent To FIRE
Notes
2007-12-12 10:35:27TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-10-09 Cont ID  
Sent By adarroug Date 2007-10-09 Time 13:53 Rev Time 0.00
Received By adarroug Date 2007-10-09 Time 13:53 Sent To M
Notes
2007-10-09 13:54:11TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-07-19 Cont ID  
Sent By adarroug Date 2007-07-19 Time 13:29 Rev Time 0.00
Received By adarroug Date 2007-07-19 Time 13:28 Sent To  
Notes
2007-07-30 09:00:27TO "COMM" BD#30
2007-07-19 13:29:22WAITING FOR "COMM" BD--REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-30 Cont ID  
Sent By spalmer Date 2007-03-30 Time 17:38 Rev Time 0.00
Received By spalmer Date 2007-03-30 Time 17:38 Sent To  
Notes
2007-03-30 17:38:33WAITING FOR COMM BOARD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-02-14 Cont ID  
Sent By adarroug Date 2007-02-14 Time 16:26 Rev Time 0.00
Received By adarroug Date 2007-02-14 Time 16:26 Sent To  
Notes
2007-02-26 11:32:45TO "COMM" BD#19
2007-02-14 16:26:43WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-29 Cont ID  
Sent By dpalmer Date 2006-11-29 Time 14:22 Rev Time 0.00
Received By dpalmer Date 2006-11-29 Time 14:22 Sent To  
Notes
2006-11-29 14:22:25TO COMM BOARD #47

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-16 Cont ID  
Sent By adarroug Date 2006-11-16 Time 13:19 Rev Time 0.00
Received By adarroug Date 2006-11-16 Time 13:19 Sent To B
Notes
2007-04-02 17:26:11TO COMM BOARD # 17
2006-11-16 13:20:10WAITING FOR "COMM"BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-25 Cont ID  
Sent By mawillia Date 2006-10-25 Time 10:25 Rev Time 0.00
Received By mawillia Date 2006-09-15 Time 11:13 Sent To  
Notes
2006-09-30 00:00:00TO COMM BOARD #6
2006-09-15 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-10-20 Cont ID  
Sent By rregueir Date 2007-10-20 Time 19:16 Rev Time 0.00
Received By rregueir Date 2007-10-20 Time 18:41 Sent To PC
Notes
2007-10-20 19:16:52REV PG M-1

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2007-10-20 Cont ID  
Sent By rregueir Date 2007-08-06 Time 18:41 Rev Time 0.00
Received By rregueir Date 2007-08-06 Time 11:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-03-17 Cont ID  
Sent By rregueir Date 2007-03-17 Time 14:11 Rev Time 0.00
Received By rregueir Date 2007-03-17 Time 14:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-12-07 Cont ID  
Sent By pkrauss Date 2006-12-07 Time 10:07 Rev Time 0.00
Received By pkrauss Date 2006-12-07 Time 10:07 Sent To  
Notes
2006-12-07 10:14:04DENIED:
 1.THE RESUBMITTAL DOES NOT CONTAIN ANY MECHANICAL
 SHEETS.WAS THIS AN OVERSIGHT OR IS THE MECHANICAL
 CONTRACTOR TO PROVIDE PLANS WITH THE MECHANICAL PERMIT
 APPLICATION.PLEASE CLARIFY.
  
 2.PLEASE NOTE, SIGNATURE ON THE RESUBMITTED PLANS IS
 NOT AN ORIGINAL SIGNATURE IT IS A STAMP AS REQUIRED BY
 THE FLORIDA ADMINSTRATIVE CODE 61G1-16.003 & 004.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-17 Cont ID  
Sent By pkrauss Date 2006-10-17 Time 16:27 Rev Time 0.00
Received By pkrauss Date 2006-10-17 Time 16:11 Sent To  
Notes
2006-10-17 16:32:49DENIED:
 ARCHITECTS SEAL IS NOT LEGIBLE, PLEASE ALSO PROVIDE
 PRINTED NAME OF SAID ARCHITECT IN ACCORDANCE WITH FS
 481.221, FAC 61G1-16.003, 61G1-16.004.
  
 PLANS ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719.

Review Stop MEDGAS MEDICAL GAS
Rev No 3 Status P Date 2007-03-09 Cont ID  
Sent By kstevens Date 2007-03-09 Time 07:56 Rev Time 0.00
Received By kstevens Date 2007-03-07 Time 18:58 Sent To  
Notes
2007-05-15 10:47:27PICTURE CERTIFICATIONS REQUIRED AT THE TIME OF
 APPLICATION

Review Stop MEDGAS MEDICAL GAS
Rev No 2 Status F Date 2007-01-10 Cont ID  
Sent By kstevens Date 2007-01-10 Time 07:12 Rev Time 0.00
Received By kstevens Date 2007-01-09 Time 18:56 Sent To  
Notes
2007-01-10 07:34:36DENIED
 REFERENCE: NFPA 99C
  
 FROM PREVIOUS REVIEW:
  
 15. A SEPARATE MED-GAS PERMIT IS REQUIRED FOR THE
 VACUUM AND COMPRESSED AIR SYSTEMS. CERTIFICATION FOR
 THE CONTRACTOR, INSTALLER AND/OR BRAZER WITH PICTURE
 IDENTIFICATION IS REQUIRED AT THE TIME OF APPLICATION.
 (INFORMATIONAL ONLY).
  
 *************NEW COMMENT*************
  
 1B. THE PERSONAL SIGNATURE OF THE ARCHITECT SHALL
 APPEAR ON ALL ARCHITECTURAL DOCUMENTS. 61G1-16.003 & FS
 481.2055. THE SEAL IS STAMPED WITH A SIGNATURE STAMP.
 THIS IS NOT APPROVED. PLEASE SIGN EACH SHEET.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status F Date 2006-10-16 Cont ID  
Sent By kstevens Date 2006-10-16 Time 18:50 Rev Time 0.00
Received By kstevens Date 2006-10-14 Time 19:01 Sent To  
Notes
2006-10-16 18:52:53DENIED
 REFERENCE:NFPA 99C 2002
  
 1. A SEPARATE MED-GAS PERMIT IS REQUIRED FOR THE VACUUM
 AND COMPRESSED AIR SYSTEMS. CERTIFICATION FOR THE
 CONTRACTOR, INSTALLER AND/OR BRAZER WITH PICTURE
 IDENTIFICATION IS REQUIRED AT THE TIME OF APPLICATION.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2007-08-30 Cont ID  
Sent By kstevens Date 2007-08-30 Time 12:42 Rev Time 0.00
Received By kstevens Date 2007-08-30 Time 12:42 Sent To  
Notes
2007-08-30 12:43:13 
  
 REVISION OK - SHTS P-1, P-2 & P-3

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-04-10 Cont ID  
Sent By kstevens Date 2007-04-10 Time 10:46 Rev Time 0.00
Received By kstevens Date 2007-04-10 Time 10:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-03-09 Cont ID  
Sent By kstevens Date 2007-03-09 Time 07:55 Rev Time 0.00
Received By kstevens Date 2007-03-07 Time 18:58 Sent To  
Notes
2007-03-09 08:01:37DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE FLORIDA
 STATUTES
 NFPA 99C 2002
  
 FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
  
 9. SHT P.2 PLUMBING LEGEND #2 AND DETAIL #3 WATER
 FILTER SYSTEM. FILTER SHALL COMPLY WITH NSF 42. SUBMIT
 MANUF. SPECIFICATION. SECTION 611.1.
 ****NO RESPONSE - NOT ADDRESSED.
 ******RESPONSE NOTED, AND INDICATES THE FILTERED WATER
 SYSTEM HAS BEEN DELETED, BUT THE PLANS STILL SHOW
 "FILTERED C.W. TYP. BRANCH"ON THE VAC. AIR & FILTERED
 WATER DIAGRAM. PLEASE CLARIFY. SECTION 106.1.1.
  
 10. SUBMIT RISER ISOMETRICS FOR THE FOLLOWING. THE
 WATER SYSTEM, SHOWING ALL PIPE SIZES, VALVES, AND WATER
 HAMMER ARRESTORS REQUIRE BY SECTION 604.9. THE VACUUM
 SYSTEM SHOWING ALL PIPE SIZES, VALVES, ETC. THE
 COMPRESSED AIR SYSTEM, SHOWING ALL PIPE SIZES, VALVES
 ETC. SECTION 106.3.5.1.3, AND FIGURES 4.5.2.1.3(A) OR
 4.5.2.1.3(B) FOR THE VACUUM SYSTEM.
 ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN,
 AND THE FULL OPEN VALVES ON ALL WATER DOWN-FEED LINES
 REQUIRED BY SECTION 606.1(4) ARE NOT SHOWN ON THE WATER
 RISER ISOMETRIC.
 ******RESPONSE NOTED, BUT THE WATER HAMMER ARRESTORS
 SHALL BE LOCATED IN AN "EFFECTIVE RANGE" NEAR THE
 FIXTURES, NOT IN THE CEILING. PDI-WH 201 & MANUF.
 INSTALLATION INSTRUCTIONS.
  
 11. OK
 12. OK
 13. OK
 14. OK
 15. OK
  
 *************NEW COMMENT*************
  
 1B. OK
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-01-10 Cont ID  
Sent By kstevens Date 2007-01-10 Time 07:12 Rev Time 0.00
Received By kstevens Date 2007-01-09 Time 18:56 Sent To  
Notes
2007-01-10 07:23:35DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE FLORIDA
 STATUTES
 NFPA 99C 2002
  
 FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
  
 4. SHT A.1 TOILET ROOM 115 ADAPTABLE RESTROOM. SHOW THE
 W/C TO BE 1'6" OFF THE WALL TO THE CENTERLINE OF THE
 FIXTURE. FIGURE 28.SHOW A 5' TURNING AREA PER SECTION
 11-4.22.3.
 ****RESPONSE NOTED, BUT THE DOOR SWING SHALL SWING OUT
 OF THE TOILET ROOM FOR THE ROOM TO BE ADAPTABLE.
  
 5. SHT A.1 FINISH SCHEDULE. INDICATE HOW PAINTED GWB
 MEETS THE REQUIREMENTS OF A "SMOOTH, HARD, NONABSORBENT
 SURFACE" AS REQUIRED IN SECTION 1210.2. TOILET ROOMS
 104 & 111.
 ****RESPONSE NOTED, BUT EPOXY PAINT DOES NOT COMPLY
 WITH THE REQUIREMENT FOR A HARD SURFACE.
  
 6. SHT A.4 DETAIL 9/A.4 SECTION REQUIRES A KNEE
 CLEARANCE THAT IS 27" HIGH, 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH THE SINKS. UNDERLAVATORY
 ENCLOSURE IS NOT APPROVED. DELETE FROM THE DETAIL. SHOW
 COMPLIANCE WITH THE FOLLOWING:
 A. OK
 B. OK
 C. 11-4.24.6 EXPOSED PIPES & SURFACES - NOT
 ADDRESSED.
 D. OK
  
 7. OK
 8. OK
  
 9. SHT P.2 PLUMBING LEGEND #2 AND DETAIL #3 WATER
 FILTER SYSTEM. FILTER SHALL COMPLY WITH NSF 42. SUBMIT
 MANUF. SPECIFICATION. SECTION 611.1.
 ****NO RESPONSE - NOT ADDRESSED.
  
 10. SUBMIT RISER ISOMETRICS FOR THE FOLLOWING. THE
 WATER SYSTEM, SHOWING ALL PIPE SIZES, VALVES, AND WATER
 HAMMER ARRESTORS REQUIRE BY SECTION 604.9. THE VACUUM
 SYSTEM SHOWING ALL PIPE SIZES, VALVES, ETC. THE
 COMPRESSED AIR SYSTEM, SHOWING ALL PIPE SIZES, VALVES
 ETC. SECTION 106.3.5.1.3, AND FIGURES 4.5.2.1.3(A) OR
 4.5.2.1.3(B) FOR THE VACUUM SYSTEM.
 ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN,
 AND THE FULL OPEN VALVES ON ALL WATER DOWN-FEED LINES
 REQUIRED BY SECTION 606.1(4) ARE NOT SHOWN ON THE WATER
 RISER ISOMETRIC.
  
 11. OK
 12. OK
 13. OK
 14. OK
 15. A SEPARATE MED-GAS PERMIT IS REQUIRED FOR THE
 VACUUM AND COMPRESSED AIR SYSTEMS. CERTIFICATION FOR
 THE CONTRACTOR, INSTALLER AND/OR BRAZER WITH PICTURE
 IDENTIFICATION IS REQUIRED AT THE TIME OF APPLICATION.
 (INFORMATIONAL ONLY).
  
 *************NEW COMMENT*************
  
 1B. THE PERSONAL SIGNATURE OF THE ARCHITECT SHALL
 APPEAR ON ALL ARCHITECTURAL DOCUMENTS. 61G1-16.003 & FS
 481.2055. THE SEAL IS STAMPED WITH A SIGNATURE STAMP.
 THIS IS NOT APPROVED. PLEASE SIGN EACH SHEET.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-10-16 Cont ID  
Sent By kstevens Date 2006-10-16 Time 17:51 Rev Time 0.00
Received By kstevens Date 2006-10-14 Time 19:01 Sent To  
Notes
2006-12-03 20:15:03ATTACHED SHEET WITH REFERENCE TO FS 553.80(2)B), ONLY A
 NOTICE FOR INFORMATIONAL PURPOSE AT THIS TIME.
2006-10-16 18:48:33DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 NFPA 99C 2002
  
 1. SHT T.1 CODE NOTES #8 ACCESSIBILITY TO BE PER
 FBC-2004 CHAPTER 11. CORRECT REFERENCE.
  
 2. ALL SHEETS. SEAL SHALL IMPRESS INFORMATION REQUIRED
 BY FAC 61G1-16.002(1) & FS 481.221. PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT REQUIRED IN THE TITLE
 BLOCK. FAC 61G1-16.004(6) & FS 481.2055.
  
 3. SHT A.0 SHOW COMPLIANCE WITH THE FOLLOWING:FOR
 W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.5 FLUSH CONTROLS
  
 4. SHT A.1 TOILET ROOM 115 ADAPTABLE RESTROOM. SHOW THE
 W/C TO BE 1'6" OFF THE WALL TO THE CENTERLINE OF THE
 FIXTURE. FIGURE 28.SHOW A 5' TURNING AREA PER SECTION
 11-4.22.3.
  
 5. SHT A.1 FINISH SCHEDULE. INDICATE HOW PAINTED GWB
 MEETS THE REQUIREMENTS OF A "SMOOTH, HARD, NONABSORBENT
 SURFACE" AS REQUIRED IN SECTION 1210.2. TOILET ROOMS
 104 & 111.
  
 6. SHT A.4 DETAIL 9/A.4 SECTION REQUIRES A KNEE
 CLEARANCE THAT IS 27" HIGH, 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH THE SINKS. UNDERLAVATORY
 ENCLOSURE IS NOT APPROVED. DELETE FROM THE DETAIL. SHOW
 COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE (CABINET DOORS ARE NOT
 APPROVED IN THE CLEAR FLOOR SPACE. DELETE FROM
 DETAIL).
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
 D. 11-4.24.7 FAUCETS
  
 7. SHT P.1 PLUMBING FIXTURE LEGEND SK-2 SINK MODEL NOT
 APPROVED. (SEE ATTACHED MANUF. SHEET). MAXIMUM DEPTH
 FOR AN ACCESSIBLE SINK IS 6-1/2" PER SECTION 11-4.24.4.
 8" IS INDICATED ON MANUF. SPECIFICATION SHEET.
  
 8. SHT P.1 EWH & REC. PUMP DIAG. SHOWS PVC PIPE FOR P/T
 DISCHARGE LINE & EMERGENCY PAN DRAIN LINE. THIS IS NOT
 APPROVED. SECTION 504.6.2 AND TABLE 605.4. - PAN DRAIN
 LINE AND P/T DISCHARGE LINE ARE SHOWN AS AIR BREAKS TO
 THE FLOOR SINK. AIR GAPS ARE REQUIRED. SECTION 802.2
 AND DEFINITIONS.- A NOTE INDICATES "TO JAN. SINK BELOW"
 BUT DETAIL SHOW PIPING TO FLOOR SINK. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 9. SHT P.2 PLUMBING LEGEND #2 AND DETAIL #3 WATER
 FILTER SYSTEM. FILTER SHALL COMPLY WITH NSF 42. SUBMIT
 MANUF. SPECIFICATION. SECTION 611.1.
  
 10. SUBMIT RISER ISOMETRICS FOR THE FOLLOWING. THE
 WATER SYSTEM, SHOWING ALL PIPE SIZES, VALVES, AND WATER
 HAMMER ARRESTORS REQUIRE BY SECTION 604.9. THE VACUUM
 SYSTEM SHOWING ALL PIPE SIZES, VALVES, ETC. THE
 COMPRESSED AIR SYSTEM, SHOWING ALL PIPE SIZES, VALVES
 ETC. SECTION 106.3.5.1.3, AND FIGURES 4.5.2.1.3(A) OR
 4.5.2.1.3(B) FOR THE VACUUM SYSTEM.
  
 11. SHT P.2 THE COMPRESSOR AIR INTAKE SHALL COMPLY WITH
 NFPA 99C SECTION 5.1.3.5.13.2. THE MATERIALS FOR THE
 COMPRESSOR INTAKE PIPING SHALL COMPLY WITH NFPA 99C
 SECTIONS 5.1.3.5.13.4 & 5.1.10.2.1.
  
 12. SHTS P.1 & P.2 MORE INFORMATION IS REQUIRED FOR
 ROOM 117. SUBMIT AN ELEVATION FOR THE SOUTH AND EAST
 WALLS. IT APPEARS THAT THE WATER HEATER AND THE AIR
 COMPRESSOR ARE LOCATED IN THE SAME SPACE. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 13. SHT P.2 DETAIL #6 VACUUM TUBES SHALL BE HARD-DRAWN
 SEAMLESS COPPER PER NFPA 99C SECTION 5.1.10.2.1. DELETE
 FROM REFERENCE THE OTHER MATERIALS.
  
 14. SHT P.2 DETAIL #1 MORE INFORMATION IS REQUIRED.
 SUBMIT INFORMATION ON THE DETAIL FOR THE AIR COMPRESSOR
 INDICATING IF THE AIR INTAKE WILL BE CONNECTED TO THE
 COMPRESSOR. IF NOT THE FLOOR SINK WILL NOT BE APPROVED
 IN ROOM 117. SECTION 106.1.1.
  
 15. A SEPARATE MED-GAS PERMIT IS REQUIRED FOR THE
 VACUUM AND COMPRESSED AIR SYSTEMS. CERTIFICATION FOR
 THE CONTRACTOR, INSTALLER AND/OR BRAZER WITH PICTURE
 IDENTIFICATION IS REQUIRED AT THE TIME OF APPLICATION.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved