Plan Review Details - Permit 06090410
Plan Review Stops For Permit 06090410
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2007-04-13 Cont ID  
Sent By lursu Date 2007-04-13 Time 10:37 Rev Time 0.00
Received By lursu Date 2007-04-13 Time 10:34 Sent To  
Notes
2007-04-13 10:37:25THE SITE ADDRESS FOR THIS STRUCTURE WAS CHANGED FORM
 3031 OKEECHOBEE BLVD ( WHICH WAS INCORRECT) TO 3023
 OKEECHOBEE BLVD.THIS ADDRESS WAS ASSIGNED BASED ON THE
 OWNER' S REPRESENTATIVES REQUEST .ON THE REVISED SITE
 PLANS PLEASE MAKE THE NECESSARY CORRRECTIONS TO REFLECT
 THE NEW SITE ADDRESS.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 2 Status P Date 2006-10-16 Cont ID  
Sent By lursu Date 2006-10-16 Time 13:10 Rev Time 0.00
Received By lursu Date 2006-10-16 Time 13:10 Sent To PC
Notes
2006-10-16 13:11:54ASSIGN PERMIT TO EXT #0002 FOR 3021 OKEECHOBEE BLVD

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2006-09-22 Cont ID  
Sent By lursu Date 2006-09-22 Time 11:03 Rev Time 0.00
Received By lursu Date 2006-09-22 Time 11:03 Sent To  
Notes
2006-09-22 00:00:00PROJECT UNDER REVIEW

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2008-09-09 Cont ID  
Sent By shill Date 2008-09-09 Time 14:12 Rev Time 0.00
Received By shill Date 2008-09-09 Time 14:12 Sent To  
Notes
2008-09-09 14:13:54****CORRECTIONS****
 ****NO RESUB FEE **IF** NEXT REVIEW IS FOR IMPACT FEES
 ONLY****
 ****IMPACT FEES****
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
  
 1.) A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.) ADDRESSED.
  
 3.) IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY PRIOR
 TO PERMIT ISSUANCE, 2300 N JOG RD. PLEASE CALL
 561-233-5025 FOR MORE INFORMATION.
  
 7.) FBC* 109.3.7 RESIDENT INSPECTOR. SUBMIT INSPECTOR
 RESUME' AND LICENSE DOCUMENTS TO KEN CONRAD,
 561-805-6666. A RESIDENT INSPECTOR PROGRAM IS REQUIRED,
 ON THIS PROJECT, DUE TO ONE OR MORE OF THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS OF
 CONSTRUCTION
  
 ALSO, PLEASE ARRANGE WITH KEN CONRAD (INSPECTION
 SERVICES MANAGER - TEL:
 561 805 6666), A MEETING INVOLVING THE OWNER, RESIDENT
 INSPECTOR, JOB INSPECTOR, CONTRACTOR AND ENGINEER. THIS
 MUST BE DONE PRIOR TO PERMIT ISSUANCE. THREE ORIGINAL
 SETS OF ALL DOCUMENTS ARE REQUIRED FOR PERMITTING.
  
  
 56.) COMMENTS REGARDING PRODUCT APPROVALS:
  
 A. ADDRESSED.
  
 B. SUBMIT FLORIDA STATE PRODUCT APPROVAL AND ASSOCIATED
 DOCUMENTS (EVALUATION REPORT, INSTALLATION
 INSTRUCTIONS) FOR THE FLEMING DOOR (FL3341).
 WWW.FLORIDABUILDING.ORG FAC9B72.
  
 NEW COMMENT:
  
 57. AS DISCUSSED, THE REVIEW OF NEW PRODUCT APPROVALS
 WILL BE DONE AT THE SAME TIME THAT IMPACT FEES ARE
 REVIEWED (CONFIRMATION OF BUILDING SIZE, PAYMENT). A
 REVIEW INVOLVING CODE ISSUES WILL REQUIRE A RESUB FEE.
 AS DISCUSSED, THE ISSUE OF ONE PRODUCT APPROVAL WILL
 NOT DELAY PERMIT ISSUANCE. THE PERMIT WOULD BE ISSUED
 WITH PROVISO THAT THE REQUIRED PRODUCT APPROVALS BE
 SUBMITTED AS A REVISION.
  
 IF CODE COMPLIANT PAPERWORK IS NOT SUBMITTED AT THE
 TIME OF IMPACT FEE REVIEW, THE PERMIT WILL BE ISSUED
 WITH THE PROVISO THAT THIS BE SUBMITTED AS A REVISION
 PRIOR TO INSTALLATION.
  
 58. IT DOES NOT APPEAR THAT THE 16 PAGE DOCUMENT FOR
 THE FLEMING DOOR (AVAILABLE AT WWW.
 FLORIDABUILDING.ORG) ENTITLED "RECOMMENDED ERECTION
 INSTRUCTIONS FOR STEEL FRAMES" OR THE LETTER REGARDING
 COMPLIANCE TO 2004 EDITION OF FLORIDA BUILDING CODE
 (ISSUED BY UL) WAS INCLUDED IN THE PACKAGE. SHOP
 DRAWINGS ARE NOT REQUIRED; IN FACT, SHOULD BE REMOVED
 FROM THE PACKAGE TO AVOID CONFLICTS BETWEEN THE SHOPS
 AND THE PRODUCT APPROVAL. ONLY THE FLORIDA STATE OR
 LOCAL PRODUCT APPROVAL WITH ASSOCIATED BACKUP
 DOCUMENTATION (INSTALLATION INSTRUCTIONS, EVALUATION
 REPORT) OR MIAMIDADE NOA ARE REQUIRED. THREE DOCUMENTS
 ARE SHOWN ON THE INTERNET FOR THIS DOOR; THEY ARE LINKS
 NEAR THE BOTTOM OF THE PAGE. PLEASE CONFIRM THAT THESE
 DOCUMENTS ARE INCLUDED WHEN RESUBMITTING AT THE SAME
 TIME AS IMPACT FEES (TO AVOID A RESUBMITTAL FEE).
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2007-12-28 Cont ID  
Sent By shill Date 2007-12-28 Time 16:46 Rev Time 0.00
Received By shill Date 2007-12-28 Time 16:46 Sent To  
Notes
2007-12-28 16:47:16****CORRECTIONS****
 ****NO RESUB FEE****
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB
 FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)ADDRESSED.
  
 3.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL
 561-233-5025 FOR MORE INFORMATION.
  
 4-55.)ADDRESSED.
  
 56.)COMMENTS REGARDING PRODUCT APPROVALS:
  
 A.ADDRESSED.
  
 B.SUBMIT FLORIDA STATE PRODUCT APPROVAL AND
 ASSOCIATED DOCUMENTS (EVALUATION REPORT, INSTALLATION
 INSTRUCTIONS) FOR THE FLEMING DOOR (FL3341).
 WWW.FLORIDABUILDING.ORGFAC9B72.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2007-11-16 Cont ID  
Sent By shill Date 2007-11-16 Time 17:52 Rev Time 0.00
Received By shill Date 2007-11-16 Time 17:52 Sent To  
Notes
2007-11-16 18:01:59****CORRECTIONS****
 3ND COURTESY REVIEW FOR 4TH SUBMITTAL
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
  
 FROM PREVIOUS LISTS:
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)ADDRESSED.
  
 3.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL
 561-233-5025 FOR MORE INFORMATION.
  
 4-55.)ADDRESSED.
  
 56.)COMMENTS REGARDING PRODUCT APPROVALS:
  
 A.SEE PREVIOUS LISTS IN REGARDS TO OVERHEAD DOOR
 PRODUCT APPROVALS.THE NOAS SUBMITTED DO NOT COMPLY
 WITH DESIGN PRESSURE REQUIREMENTS FOR D1A (SHEET S10,
 +56/-73).IT IS COMPLIANT FOR D1 ONLY (+56/-61).
  
 B.SUBMIT PRODUCT APPROVALS FOR THE FLEMING DOOR.THE
 PRODUCT APPEARS TO MEET DESIGN PRESSURE REQUIREMENT OF
 +56/-61, BUT PRODUCT APPROVALS WERE NOT SUBMITTED, ONLY
 SHOP DRAWINGS.THE COVER SHEET REFERS TO THREE
 DIFFERENT NOAS.ONLY ONE STEEL DOOR IS BEING
 INSTALLED.PROVIDE THE FLORIDA STATE PRODUCT APPROVAL
 (IF AVAILABLE) AND A CURRENT NOA FOR THIS PRODUCT.
 REFERRING TO THE NOA NUMBER IS NOT SUFFICE AS THE
 EVALUATION REPORT AND INSTALLATION INSTRUCTIONS ARE
 ALSO REQUIRED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-10-10 Cont ID  
Sent By shill Date 2007-10-10 Time 17:21 Rev Time 0.00
Received By shill Date 2007-10-10 Time 17:21 Sent To  
Notes
2007-10-10 17:23:51****CORRECTIONS****
 2ND REVIEW FOR 4TH SUBMITTAL
 ACCEPTED MSP1 AND PRODUCT APPROVALS MID REVIEW
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB
 FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LISTS:
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)ADDRESSED.
  
 3.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL
 561-233-5025 FOR MORE INFORMATION.
  
 4-6.) ADDRESSED.
  
 7.)SEE PREVIOUS LISTS REGARDING RESIDENT INSPECTOR
 REQUIREMENT AND A MEETING WITH HAROLD PISKURA,
 561-805-6711.THE PERMIT CANNOT BE PASSED, STAMPED,
 AND ISSUED UNTIL THIS IS COMPLETED.
  
 8-27.)ADDRESSED.
  
 28.)MSP 1 OK; ADDRESSED
  
 40-55.)ADDRESSED.
  
 56.)NEW PRODUCT APPROVALS SUBMITTED MID REVIEW WILL
 BE REVIEWED AFTER IMPACT FEES HAVE BEEN PAID AND
 PROVISO'D IF NECESSARY.
  
 NEW COMMENT:
  
 57.)I AGREED TO ACCEPT MSP1 MID REVIEW TO AVOID
 ADDITIONAL REVIEWS ON RESUBMITTAL.HOWEVER, A102 WAS
 ALSO CHANGED.THIS IS NOT THE SHEET WITH THE PLUMBING
 FIXTURE CALCS (WHICH ARCHITECT ADVISED WOULD BE SWAPPED
 OUT IN ADDITION TO MSP1).WHAT CHANGED ON THIS SHEET?
 THE ONLY CLOUDED REVISION DOES NOT RELATE TO ANY OF MY
 COMMENTS AND IT WAS NOT AGREED THAT THIS SHEET COULD BE
 CHANGED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-07-26 Cont ID  
Sent By shill Date 2007-07-26 Time 07:19 Rev Time 0.00
Received By shill Date 2007-07-26 Time 07:19 Sent To  
Notes
2007-07-26 07:22:28****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB
 FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LISTS:
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)ADDRESSED.
  
 3.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL
 561-233-5025 FOR MORE INFORMATION.
  
 4-6.) ADDRESSED.
  
 7.)SEE PREVIOUS LISTS REGARDING RESIDENT INSPECTOR
 REQUIREMENT AND A MEETING WITH HAROLD PISKURA,
 561-805-6711.THE PERMIT CANNOT BE PASSED, STAMPED,
 AND ISSUED UNTIL THIS IS COMPLETED.
  
 8-27.)ADDRESSED.
  
 28.)THE THIRD RESPONSE LETTER STATES THAT ALL LIFE
 SAFETY INFORMATION WAS INCLUDED IN MSP1; THIS FOURTH
 RESPONSE LETTER STATES THAT THE INFORMATION IS ON A101.
 I WAS UNABLE TO LOCATE OCCUPANT LOAD, SEE FBC 1004.1.2,
 TABLE 1004.1.2.THERE IS A PLUMBING FIXTURE OCCUPANT
 LOAD ON A102, BUT THIS ONLY INCLUDES ONE FLOOR OF THE
 GARAGE.THIS OCCUPANT LOAD DOES NOT INCLUDE THE
 SERVICE AREA OR ROOF PARKING.FOR EGRESS, YOU MUST
 DECLARE OCCUPANT LOAD PER AREA AND IT CANNOT BE LESS
 THAN FBC TABLE 1004.1.2 AS PER REQUIREMENTS OF FBC
 1004.1.2.THE PLUMBING FIXTURE OCCUPANT LOAD USES
 200SF PER OCCUPANT, BUT THIS IS FOR PARKING GARAGE
 ONLY, NOT FOR THE SERVICE AREA.OCCUPANT LOAD IS A
 LIFE SAFETY ISSUE (CONFIRM ADEQUATE MEANS OF EGRESS)
 AND CANNOT BE WAIVED, ALSO CANNOT USE THE PLUMBING
 FIXTURE OCCUPANT LOAD AS IT DOES NOT BREAK DOWN
 OCCUPANTS BY FLOOR AND OCCUPANCY AND THAT NUMBER IS
 LESS THAN HALF OF WHAT IS REQUIRED FOR EGRESS.AN
 OCCUPANT LOAD WAS PROVIDED FOR THE LOUNGE/TRAINING, BUT
 THIS NEEDS TO BE DONE FOR EVERY SPACE (OCCUPANT LOAD
 FOR SERVICE AREA, 2ND FLOOR PARKING, ROOFTOP PARKING,
 STORAGE AREAS).IT IS NOT CLEAR WHY THE PLUMBING
 FIXTURE OCCUPANT LOAD WOULD INCLUDE ONLY THE SECOND
 FLOOR PARKING GARAGE OF 17,365 AND NOT INCLUDE THE
 SERVICE GARAGE, ROOFTOP PARKING, AND OTHER AREAS.
  
 40-55.)ADDRESSED.
  
 56.)REGARDING THE PRODUCT APPROVALS SUBMITTED (FIRST
 REVIEW FOR THE PRODUCT APPROVALS):
  
 THE OVERHEAD DOOR PRODUCT APPROVAL IS LIMITED TO A 10'
 WIDE DOOR, +-65PSF.THERE ARE THREE OVERHEAD DOORS
 WHICH ARE WIDER THAN 10' AND ONE WHICH HAS A DESIGN
 PRESSURE WHICH EXCEEDS -65 (HAS A DP OF -73).PLEASE
 ADDRESS.
  
 THE FLEMING DOOR SPECS REFER TO THREE DIFFERENT NOA
 NUMBERS BUT NONE WERE PROVIDED.THE SHOP DRAWINGS
 PROVIDED ARE NOT REQUIRED, BUT THE EVALLUATION REPORT
 (NOA) IS REQUIRED.PLEASE PRINT THE NOA(S) FOR THE
 DOOR(S) YOU WISH TO USE.IT APPEARS THAT THE PRODUCTS
 ARE COMPLIANT WITH THE DP REQUIREMENT OF +56/-61.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-06-22 Cont ID  
Sent By shill Date 2007-06-22 Time 13:54 Rev Time 0.00
Received By shill Date 2007-06-15 Time 08:35 Sent To  
Notes
2007-06-22 13:55:13****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LIST:
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)ADDRESSED.
  
 3.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL
 561-233-5025 FOR MORE INFORMATION.
  
 4-5.) ADDRESSED.
  
 6.)THE INFORMATION REQUIRED FOR THE ENGINEER
 FAC61G15-23.002 IS TO BE ON EACH SHEET.THIS COMMENT
 IS FOR THE FIRE SPRINKLER ENGINEER.THIS APPLIES TO
 THE CALCS AND THE DRAWINGS.IF AN INDEX SHEET IS NOT
 PROVIDED FOR THE CALCS, EACH SHEET IS TO BE SIGNED,
 SEALED, AND DATED.
  
 7.) FBC* 109.3.7 RESIDENT INSPECTOR. SUBMIT INSPECTOR
 RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA,
 DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.A RESIDENT
 INSPECTOR PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO
 ONE OR MORE OF THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS
 OF CONSTRUCTION
  
 ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION
 SERVICES MANAGER - TEL:
 561 805 6711), A MEETING INVOLVING THE OWNER, RESIDENT
 INSPECTOR, JOB INSPECTOR, CONTRACTOR AND ENGINEER. THIS
 MUST BE DONE PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL
 SETS OF ALL DOCUMENTS ARE REQUIRED FOR PERMITTING.
  
 3RD REVIEW ? ONLY TWO SETS WERE SUBMITTED.NOTE THAT
 ALTHOUGH THIS PLAN HAS PASSED SOME REVIEWS, ANOTHER
 REVIEW WILL BE REQUIRED SO THAT THOSE REVIEWERS CAN
 STAMP THEIR SHEETS WHEN THE THIRD SET IS SUBMITTED.
  
 8.) PROVIDE ORIGINAL SIGNED, SEALED, DATED SOILS
 REPORTS, FBC1802.2.1, 1802.2.3.THREE SETS REQUIRED.
 AS STATED IN THE PREVIOUS REVIEWS, THE SIGNATURE CANNOT
 BE A PHOTOCOPY.
  
 9.) ADDRESSED.
  
 10.)ADDRESSED, BUT SEE OTHER COMMENTS REGARDING
 PRODUCT APPROVALS.
  
 11.)ADDRESSED.
  
 12.)IT IS NOT CLEAR IF THE EQUIPMENT SHEDS WERE
 INCLUDED IN THE BUILDING CODE SUMMARY.THIS IS THE
 THIRD REQUEST FOR THIS INFORMATION.IS THIS AREA
 INCLUDED IN ONE OF THE OTHER EXISTING BUILDINGS?THE
 PLAN SHOWS THE EXISTING EQUIPMENT SHED AGAINST THIS
 BUILDING.ARE YOU DESIGNING AS ONE BUILDING OR TWO
 SEPARATE BUILDINGS?
  
 13-17.) ADDRESSED.
  
 18.)REGARDING MAXIMUM AREA OF EXTERIOR WALL OPENINGS,
 OPENINGS AND PERCENTAGES WERE PROVIDED FOR THE EXISTING
 BUILDINGS.PROVIDE ALSO FOR THE PROPOSED BUILDING TO
 SHOW COMPLIANCE WITH FBC TABLE 704.8.NOTE THAT EAST
 ELEVATION HAS A LARGE AMOUNT OF OPENINGS ON A PORTION
 OF THE WALL.SEE THE ATTACHED COMMENTARY IN REGARDS TO
 UNIFORM DISTRIBUTION.
  
 THE % OF WALL OPENINGS, EXISTING VW SERVICE TO NEW
 SERVICE, SHOULD BE 15%-45%.
  
 EQUIPMENT SHEDS ARE SHOWN.ARE THEY ALSO TYPE II B
 CONSTRUCTION?ONE IS SHOWN CONNECTED TO THE NEW
 SERVICE BUILDING, BUT NOT DETAILS ARE PROVIDED.IS
 THIS AN EXISTING BUILDING?COMPLIANCE WITH FBC TABLE
 601, FBC TABLE 704.8 IS TO BE SHOWN ON THE PLAN.
  
 19.)ADDRESSED.
  
 20.)MSP1 STATES THAT EXISTING HUMMER BUILDING HAS A 2
 HOUR WALL.IS THIS THE EXISTING CONDITION, OR WILL THE
 FIRE RESISTANCE OF THE WALL BE INCREASED TO COMPLY WITH
 THE NEW 2 HOUR REQUIREMENT?PROVIDE A DETAIL, EITHER
 CALCULATED FIRE RESISTANCE OR UL ASSEMBLY FOR THE
 EXISTING WALL.SEE FBC TABLE 602.IT IS ACCEPTABLE TO
 EXCEED CODE COMPLIANCE, BUT B OCCUPANCY REQUIREMENT IS
 1 HOUR.THE NEW SERVICE HAS A 2 HOUR REQUIREMENT.
  
 MSP1 STATES THAT THE EXISTING SERVICE BUILDING HAS A 2
 HOUR WALL.IS THIS THE EXISTING CONDITION, OR WILL THE
 FIRE RESISTANCE OF THE WALL BE INCREASED TO COMPLY WITH
 THE NEW 2 HOUR REQUIREMENT?PROVIDE A DETAIL, EITHER
 CALCULATED FIRE RESISTANCE OR UL ASSEMBLY FOR THE
 EXISTING WALL.
  
 PLEASE NOTE REQUIREMENTS FOR NEW SERVICE BUILDING. NOTE
 ON MSP1 AND SHOW REQUIREMENTS ON THE PLAN.MSP1 SHOWS
 2 HOUR ON THE WALL ADJACENT TO THE HUMMER SHOWROOM, BUT
 DOES NOT SHOW THE 2 HOUR REQUIREMENT FOR THE STORAGE
 AND OIL STORAGE AREAS.
  
 21.)ADDRESSED.
  
 22.)WHAT IS BETWEEN THE PROPOSED SERVICE/PARKING AND
 EXISTING VW SERVICE/VW SHOWROOM?THIS WAS DISCUSSED IN
 A MEETING AS BEING A CANOPY. PLEASE LABEL THIS AREA.
  
 23.)A101 AND OTHER DETAILS, STAIR DOORS A132, A2-03,
 A303, SEE FBC11-4.13 AND FBC FIGURE 11-26, TWO HINGED
 DOORS IN A SERIES.
  
 THIS WAS ADDRESSED ON MOST PAGES.PLEASE ALSO REVISE
 THE ELECTRICAL SHEETS AND CHECK ALL SHEETS.
  
 24-27.) ADDRESSED.
  
 28.)RESPONSE LETTER STATES THAT ALL LIFE SAFETY
 INFORMATION WAS INCLUDED IN MSP1.I WAS UNABLE TO
 LOCATE OCCUPANT LOAD, SEE FBC 1004.1.2, TABLE
 1004.1.2.
  
 34.)ADDRESSED.
  
 33.)STATE WHETHER THIS HAS BEEN DESIGNED AS AN OPEN
 PARKING GARAGE OR ENCLOSED PARKING GARAGE, STATE IN THE
 CODE SUMMARY, FBC406, AND SEE ALL REQUIREMENTS, SHOW ON
 PLAN.
  
 PLEASE INCORPORATE INFORMATION INTO THE PLAN AS
 REQUESTED.THIRD REQUEST. THE RESPONSE LETTER STATES
 THAT THIS INFORMATION IS INCLUDED ON MSP1, BUT I WAS
 UNABLE TO FIND THE CLASSIFICATION OF OPEN OR ENCLOSED.
  
 34-36.) ADDRESSED.
  
 37.)A101, ROOF PLAN, 2ND FLOOR PLAN, STORAGE IS SHOWN
 WITH AN OPENING INTO THE STAIR.SEE 1019.1.1, OPENINGS
 TO BE LIMITED TO THOSE NECESSARY FOR EXIT ACCESS FROM
 NORMALLY OCCUPIED SPACES.
  
 YOUR OBJECTION TO THE COMMENT IS NOTED.PLEASE SEE
 ATTACHED COMMENTARY, INCLUDING THE SENTENCE WHICH
 SPECIFICALLY EXCLUDES STORAGE CLOSETS AS THEY DO NOT
 CONSIDER THIS A "NORMALLY OCCUPIED SPACE" REGARDLESS OF
 BUILDING OCCUPANCY CLASSIFICATION.ALSO NOTE THAT
 ALTHOUGH YOU ARE PROPOSING ENCLOSED SPACE ON THE ROOF,
 A FIRE SPRINKLER PLAN WAS NOT PROVIDED FOR THE ROOF.
  
 38.)FIRE EXIT, FIRST FLOOR, TO HAVE SEPARATION FROM
 THE OCCUPANCY ABOVE IF AN OCCUPANCY SEPARATION IS
 REQUIRED.GG-A108.
  
 YOUR RESPONSE STATES THAT VERTICAL OPENINGS ARE NOT
 REQUIRED TO BE PROTECTED.I WAS REFERRING TO THE FLOOR
 CEILING ASSEMBLY BETWEEN THE FIRE EXIT 1ST FLOOR, S1
 OCCUPANCY, AND THE RAMP/PARKING GARAGE, S2 ON THE
 SECOND FLOOR.A 2 HOUR IS SHOWN THROUGHOUT THE
 REMAINDER OF THE BUILDING ON SECTION G-G AND APPEARS TO
 ALSO BE SHOWN ON A-A-106.THIS ALSO APPLIES TO MENS
 ROOM F-F A108.
  
 39.)ADDRESSED.
  
 40.)PLEASE PROVIDE OCCUPANT LOAD AS PREVIOUSLY
 REQUESTED FOR THE LOUNGE/TRAINING AREA SO THAT EGRESS
 REQUIREMENTS AND COMPLIANCE CAN BE DETERMINED.
  
 41-51.) ADDRESSED.
  
 52.)PLEASE SUBMIT ALL PRODUCT APPROVALS REQUIRED AT
 THIS TIME.DOOR PRODUCT APPROVALS WERE NOT SUBMITTED.
 PROVIDE WIND DESIGN CRITERIA FBC1603.1.4 INCLUDING
 COMPONENTS AND CLADDING DESIGN PRESSURES.
  
 53.)THE SIGNATURE FOR AN ENGINEER CANNOT BE A STAMP
 (STRUCTURAL ENGINEER), SEE FAC61G15-23.002, FS471.025.
  
 54.)PLEASE CLOUD ALL CHANGES AND SUBMIT OLD SHEETS.
 PLEASE INCLUDE A RESPONSE LETTER INDICATING HOW EACH
 ITEM HAS BEEN ADDRESSED.
  
 NEW COMMENTS:
  
 55.)FLORIDA STATE PRODUCT APPROVAL COVER SHEET,
 FL5723, WAS SUBMITTED FOR SHUTTERS.USE OF REMOVABLE
 SHUTTERS ON COMMERCIAL BUILDINGS IS TO BE APPROVED BY
 THE BUILDING OFFICIAL, SEE ATTACHED POLICY, ITEM 13.
 SUBMIT AN INSTALLATION PLAN WITH ALL REQUIRED
 INFORMATION (SEE POLICY).THIS MAY BE DONE PRIOR TO
 RESUBMITTAL VIA EMAIL.ONCE A PRELIMINARY INSTALLATION
 PLAN IS APPROVED BY THE BUILDING OFFICIAL, ORIGINALS
 WILL BE REQUIRED.
  
 56.)IF YOU ARE USING SHUTTERS, AN INSTALLATION
 SCHEDULE IS REQUIRED ALONG WITH A KEY PLAN SHOWING
 INSTALLATION LOCATIONS; SEE ATTACHED.ALSO PRINT THE
 EVALUATION REPORT AND INSTALLATION INSTRUCTIONS.IT IS
 NOT CLEAR WHY SHUTTERS WERE INCLUDED IN THE PACKAGE
 (NOT CLEAR WHERE THEY WILL BE INSTALLED).
  
 57.)OLD SHEETS WERE LEFT IN THE PACKAGE.PLEASE MARK
 THESE SHEETS VOID, REMOVE FROM THE SETS, AND SUBMIT
 SEPARATELY FOR REFERENCE.
  
 58.)S2 SHOWS EXISTING FOOTERS AND FOOTERS WHICH
 APPEAR TO ENCROACH THE ASSUMED PROPERTY LINE AND THE
 EXISTING HUMMER BUILDING, 1'6" AWAY.PLEASE CLARIFY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-14 Cont ID  
Sent By shill Date 2007-03-14 Time 16:26 Rev Time 0.00
Received By shill Date 2007-03-06 Time 08:46 Sent To  
Notes
2007-03-14 16:26:58****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB
 FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LIST:
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)PROVIDE A SURVEY FOR THIS PROPERTY, FBC*106.3.4,
 SHOWING PROPERTY LINE AND ALL EXISTING IMPROVEMENTS.
 THE RESPONSE LETTER STATES THAT A SURVEY HAS BEEN
 INCLUDED BUT IT WAS NOT IN THE PACKAGE.
  
 3.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL
 561-233-5025 FOR MORE INFORMATION.
  
 4.)RADON FEES DUE, FS*553.721.SEE ATTACHED.THIS
 FEE MUST BE PAID WHEN THE PLANS ARE PICKED UP.
  
 5.)DUE TO VALUATION ADJUSTMENT, FEES HAVE BEEN
 INCREASED.SEE ATTACHED.PLEASE PAY AT THE TIME THAT
 THE PLANS ARE PICKED UP.
  
 6.)FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE
 REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5),
 FS553.79 (2), ATTACHED LETTER FROM DCA.
  
 THE FIRE SPRINKLER PLANS WERE IN THE PACKAGE, BUT THE
 INFORMATION REQUIRED FOR THE ENGINEER FAC61G15-23.002
 IS NOT ON EACH SHEET, AND THE SEAL IS ILLEGIBLE.
  
 7.) FBC* 109.3.7RESIDENT INSPECTOR. SUBMIT INSPECTOR
 RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA,
 DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.A RESIDENT
 INSPECTOR PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO
 ONE OR MORE OF THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS
 OF CONSTRUCTION
  
 ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION
 SERVICES MANAGER - TEL:
 561 805 6711), A MEETING INVOLVING THE OWNER, RESIDENT
 INSPECTOR, JOB INSPECTOR, CONTRACTOR AND ENGINEER. THIS
 MUST BE DONE PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL
 SETS OF ALL DOCUMENTS ARE REQUIRED FOR PERMITTING.
  
 8.)PROVIDE A SOILS INVESTIGATION REPORT, FBC1802.2.1,
 1802.2.3.THREE SETS REQUIRED.
  
 THE SIGNATURE FOR AN ENGINEER CANNOT BE A PHOTOCOPY,
 SEE FAC61G15-23.002, FS471.025.
  
 9.)THE SEAL IS ILLEGIBLE (ARCHITECT).PLEASE
 ADDRESS, FS481.221.
  
 RESPONSE LETTER STATES THAT THIS HAS BEEN ADDRESSED,
 BUT I STILL CANNOT READ THE SEAL.
  
 10.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER
 OF RECORD, FBC*106.3.3.
  
 THE RESPONSE LETTER STATES THAT THE PRODUCT APPROVALS
 HAVE BEEN REVIEWED BY DESIGNER OF RECORD.ONLY ONE
 FLORIDA STATE PRODUCT APPROVAL WAS SUBMITTED AND AN NOA
 FOR LOUVERS, WITHOUT THE REQUIRED DOCUMENTATION
 (EVALUATION REPORT, INSTALLATION INSTRUCTIONS) TO SHOW
 CODE COMPLIANCE AND FOR INSPECTIONS.THE PRODUCT
 APPROVALS DID NOT HAVE A SHOP DRAWING REVIEW STAMP.
 APPROVAL IS TO BE IN THE FORM OF A REVIEW STAMP OR A
 COVER LETTER SPECIFICALLY REFERRING TO EACH PRODUCT
 APPROVAL IN THE PACKAGE.STATING ?PRODUCT APPROVALS
 HAVE BEEN REVIEWED BY DESIGNER OF RECORD? (A STATEMENT
 IN A TYPED RESPONSE LETTER WHICH IS NOT SIGNED AND
 GIVES NO INDICATION WHATSOEVER AS TO WHO PREPARED THE
 DOCUMENT; NO LETTERHEAD, NAME, SIGNATURE) DOES NOT SHOW
 CODE COMPLIANCE; IT DOESN?T STATE WHICH DESIGN
 PROFESSIONAL REVIEWED THE PRODUCT APPROVALS NOR WHICH
 PRODUCT APPROVALS WERE REVIEWED, AND NOTHING SIGNED BY
 THE DESIGNER WHO REVIEWED THE PRODUCT APPROVALS.
  
 11.)INCLUDE FBC EB IN GOVERNING CODE.THIS PROPOSED
 IMPROVEMENT IS TO COMPLY WITH FBC EB CHAPTER 9; SEE
 ALSO FBC EB 901.2.SOME COMMENTS AND REQUEST FOR
 ADDITIONAL INFORMATION RELATE TO THIS CODE SECTION.
  
 12.)INCLUDE A CODE SUMMARY. DECLARE BUILDING TYPE
 FBC6 (INCLUDE A OR B), BUILDING HEIGHT AND AREA FBC5,
 OCCUPANCY CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY,
 FIRE SPRINKLER INFORMATION.NOTE THAT CANOPIES AND
 EQUIPMENT SHEDS ARE TO BE INCLUDED, SEE FBC 502,
 DEFINITION OF AREA, BUILDING.BUILDING TYPE WILL BE
 BASED ON WORST CASE UNLESS A FIRE WALL SEPARATES THE
 BUILDING AREAS.DETAILS OF EXISTING CONDITIONS SHOWING
 FIRE RESISTANCE MAY BE REQUIRED.PLEASE CONTACT ME IF
 YOU ARE UNSURE OF WHICH DETAILS TO INCLUDE.
  
 THIS INFORMATION IS TO BE ON THE PLAN, NOT IN THE
 RESPONSE LETTER.NOTE THAT THE RESPONSE LETTER IS NOT
 ON LETTERHEAD, AND DOES NOT INDICATE WHO PREPARED IT,
 AND IS UNSIGNED.PLANS ARE TO SHOW CODE COMPLIANCE,
 BUT IF LETTERS ARE ACCEPTED AS A SUPPLEMENT TO THE PLAN
 AT OTHER TIMES, THEY ARE TO MEET THE SAME REQUIREMENTS
 AS ANY DOCUMENT PREPARED BY AN ARCHITECT OR ENGINEER
 AND SUBMITTED FOR PUBLIC RECORD.
  
  
 A 2 HOUR WALL WAS ADDED ON THE PROPOSED SERVICE
 BUILDING ADJACENT TO THE HUMMER SHOWROOM.IT IS NOT
 CLEAR WHAT DESIGN INTENT IS AS THIS DOES NOT COMPLY
 WITH FBC 705, OPENINGS IN COMPLIANCE WITH FBC705.8.IF
 YOU ARE USING AN ASSUMED PROPERTY LINE BETWEEN
 BUILDINGS, INFORMATION REGARDING THE HUMMER SHOWROOM
 AND THE VW CANOPY BUILDING IS REQUIRED TO DETERMINE
 COMPLIANCE WITH FBC TABLE 503, FBC TABLE 601, FBC TABLE
 620, NO OPENINGS ALLOWED. THE SITE PLAN STILL SHOWS
 THIS AS ONE BUILDING.SHEET A102 SHOWS THE EQUIPMENT
 ADJACENT TO THE PROPOSED SERVICE BUILDING (ATTACHED),
  
 THIS LIST MAY NOT BE COMPLETE AS DESIGN INTENT IS NOT
 CLEAR.IT APPEARS THAT THIS IS TO BE SEPARATE
 BUILDINGS, BUT OPENINGS ARE SHOWN WITH NO INFORMATION
 REGARDING THE EXISTING BUILDINGS WAS PROVIDED.IF THE
 PROPOSED BUILDING IS TO BE SEPARATED FROM THE EXISTING
 BUILDINGS WITH A FIRE WALL, SEE FBC705 AND SHOW
 COMPLIANCE WITH ALL REQUIREMENTS.
  
 13.)REGARDING OCCUPANCY CLASSIFICATIONS, PLEASE SEE
 FBC304, FBC311.2, FBC311.3.OTHER CODE SECTIONS MAY
 APPLY.
  
 SEE ITEM 12 ABOVE.ALL REQUIRED INFORMATION IS TO BE
 ON THE PLAN.THE LETTER STATES THAT THIS IS S1 AND S2,
 BUT IT SHOWS A VEHICLE SHOWROOM, FBC304.INFORMATION
 IN REGARDS TO THE ADJACENT BUILDINGS MUST BE PROVIDED
 TO DETERMINE CODE COMPLIANCE.
  
 14.)WHAT HAZARDOUS MATERIALS WILL BE STORED AND IN
 WHAT QUANTITIES?SEE FBC TABLE 307.7(1), FBC 406.6.
  
 ADDRESS THIS IN THE PLAN.PROVIDE MSDS FOR THE
 HAZARDOUS MATERIALS.
  
 15.)DECLARE AN OCCUPANCY CLASSIFICATION FOR THE OIL
 STORAGE, SEE FBC TABLE 307.7(1), FBC406.6.NOTE
 QUANTITIES.
  
 THIS IS TO BE DONE ON THE PLAN; DECLARE OCCUPANCY
 CLASSIFICATION AND QUANTITIES.THE RESPONSE LETTER
 STATES THAT THIS IS S1, PLEASE STATE QUANTITY OF
 MAXIMUM HAZARDOUS MATERIALS STORED ON THE PLAN.
  
 16.)SHOW HOW COMPLIANCE WITH FBC TABLE 503 HAS BEEN
 ACCOMPLISHED; SEE ALSO FBC 302.IF HEIGHT OR AREA
 MODIFICATIONS HAVE BEEN USED AS PER FBC 503 THROUGH
 508, PUT ALL INFORMATION AND CALCULATIONS ON THE PLAN.
 INFORMATION PROVIDED SHOULD BE CLEAR IN REGARDS TO
 BUILDING TYPE, BUILDING AREA, AND OCCUPANCY
 CLASSIFICATION IN REGARDS TO THE EXISTING BUILDINGS
 (INCLUDING AREAS REFERRED TO AS "CANOPY" AND
 "EQUIP.SHED", ETC.) AS WELL AS THE NEW IMPROVEMENT.
  
 THIS IS TO BE DONE ON THE PLAN.SEE OTHER COMMENTS;
 CODE COMPLIANCE CANNOT BE DETERMINED.
  
 17.)IT IS NOT CLEAR WHETHER THE EXISTING SERVICE
 SHOWN ON THE WEST SIDE MSP-1 WILL BE A PART OF THE NEW
 BUILDING (APPEARS TO BE ATTACHED AT THE NORTHWEST
 PORTION, THE REST OF THE EXISTING SERVICE IS ALONG THE
 RAMP) OR IF IT A SEPARATE BUILDING, TO BE SEPARATED
 WITH AN ASSUMED PROPERTY LINE.IF THIS IS A SEPARATE
 BUILDING, SHOW COMPLIANCE WITH FBC TABLE 602 BY SHOWING
 THE BUILDING TYPE AND OCCUPANCY, ASSUMED PROPERTY LINE,
 DISTANCE OF EACH BUILDING FROM THE ASSUMED PROPERTY
 LINE.COMPLIANCE FOR EACH BUILDING MUST BE SHOWN,
 INCLUDING FIRE RESISTANCE RATING FOR THE EXISTING
 BUILDING.
  
 IF THIS IS NOT A SEPARATE BUILDING, INCLUDE THIS
 BUILDING IN THE CODE SUMMARY, SEE ITEM 3.
  
 NOT ADDRESSED.THE RESPONSE LETTER STATES THAT THIS IS
 A SEPARATE BUILDING, BUT NO INFORMATION WAS PROVIDED AS
 REQUESTED.
  
 18.)SEPARATIONS ARE TO COMPLY WITH FBC TABLE 302.3.2.
 AS NO FIRE SPRINKLER INFORMATION OR FBC TABLE 503
 COMPLIANCE WAS PROVIDED, IT IS NOT CLEAR IF THE 2 HOUR
 SHOWN BETWEEN B AND S1 IS CORRECT.
  
 INCLUDE SPRINKLER INFORMATION IN A CODE SUMMARY.THE
 RESPONSE LETTER AND PLAN SHOWS THAT THE PROPOSED GARAGE
 WILL BE SPRINKLERED.ARE THE OTHER BUILDINGS FULLY
 SPRINKLERED, INCLUDING THE CANOPY AREA, EQUIPMENT SHED,
 ETC.?IF THIS IS TWO BUILDING SEPARATED AS PER FBC
 TABLE 602, BOTH BUILDINGS MUST COMPLY AND NO OPENINGS
 ALLOWED FBC TABLE 704.8.
  
 19.)NO HORIZONTAL SEPARATIONS WERE SHOWN.
  
 PLEASE SHOW ALL REQUIRED SEPARATIONS; BETWEEN S1 AND
 THE PARKING GARAGE FBC406.2.7.PROVIDE DETAILS.
  
 20.)PROVIDE DISTANCE OF ADJACENT BUILDINGS TO THE
 PROPOSED RENOVATED BUILDING.FOR INSTANCE, DISTANCE
 FROM USED CARS TO HUMMER SHOWROOM, USED CARS TO
 EXISTING SERVICE.CONNECTING MULTIPLE BUILDINGS MAY
 AFFECT BUILDING TYPE FBC5, WHICH MAY AFFECT CODE
 COMPLIANCE WITH FBC TABLE 602.PROVIDE INFORMATION IN
 REGARDS TO OCCUPANCY CLASSIFICATION AND BUILDING TYPE
 FOR OTHER STRUCTURES.
  
 SEE OTHER COMMENTS.DESIGN INTENT IS NOT CLEAR. THE
 RESPONSE LETTER STATES THAT THE PROPOSED BUILDING IS A
 SEPARATE STRUCTURE, BUT IT SHOWS OPENINGS WHICH ARE NOT
 ALLOWED FBC TABLE 704.8 AND NO INFORMATION PROVIDED IN
 REGARDS TO THE OTHER BUILDINGS.
  
 21.)MSP-1, BUILDING/LOT COVERAGE ZONING INFORMATION
 REFERS TO AN EXISTING LEVITZ BUILDING BUT THAT BUILDING
 IS NOT REFERENCED ON THE SITE PLAN.
  
 THE RESPONSE LETTER REQUESTS THAT I SPEAK WITH
 PLANNING.THE PLANS ARE TO SHOW CODE COMPLIANCE.
 PLEASE PROVIDE INFORMATION REGARDING THE BUILDINGS ON
 THE SITE AS REQUESTED IN OTHER COMMENTS.THE CODE
 SUMMARY PROVIDED IS TO CORRELATE WITH THE BUILDING
 NAMES ON THE SITE PLAN.FOR INSTANCE, THE SITE PLAN
 STATES THAT EXISTING LEVITZ BUILDING IS 62,399 SQUARE
 FEET, BUT THERE IS NOTHING LABELED LEVITZ BUILDING ON
 THE PLAN.
  
 22.)WHAT IS BETWEEN THE PROPOSED SERVICE/PARKING AND
 EXISTING VW SERVICE/VW SHOWROOM?
  
 THE RESPONSE LETTER STATES THAT THERE ARE EXISTING
 CANOPIES.THIS AREA IS CONSIDERED TO BE BUILDING AREA.
 SEE OTHER COMMENTS REGARDING BUILDING SEPARATION AND
 OPENINGS.SEE OTHER COMMENTS REGARDING WHETHER OR NOT
 THIS IS CONSIDERED ONE BUILDING OR SEPARATE BUILDINGS
 AS THE PLANS ARE NOT CLEAR.
  
 23.)A101 AND OTHER DETAILS, STAIR DOORS A132, A2-03,
 A303, SEE FBC11-4.13 AND FBC FIGURE 11-26, TWO HINGED
 DOORS IN A SERIES.
  
 THIS WAS ADDRESSED ON MOST PAGES.PLEASE ALSO REVISE
 THE MECHANICAL SHEETS.
  
 24.)A111E, DOOR TO MENS LOCKER, SHOW MANEUVERING
 SPACE, PULL SIDE, FBC11 FIGURE 25.
  
 THIS SHEET IS NO LONGER IN THE PLAN.WAS THIS A
 DETAILED FLOOR PLAN?PROVIDE OLD SHEETS WHEN
 RESUBMITTING.
  
 25.)MSP-1 SHOWS A PROPOSED PHASE 2 OF PARKING
 STRUCTURE.NOTE THAT ONLY THE CURRENT IMPROVEMENT IS
 UNDER REVIEW FOR CODE COMPLIANCE.
  
 26.)ADDRESSED.
  
 27.)MSP-1, ACCESSIBLE ROUTE FROM THE PUBLIC WAY IS
 SHOWN FBC11-4.1.2(1), SHOW MAXIMUM SLOPE ON THE PLAN.
  
 THE RESPONSE LETTER STATES THAT THIS HAS BEEN REVIEWED
 UNDER PRIOR PERMIT APPLICATIONS.THIS PLAN IS TO SHOW
 CODE COMPLIANCE.PLEASE ADDRESS THE COMMENT AS
 REQUESTED.
  
 28.)PROVIDE A LIFE SAFETY PLAN FOR THE PROPOSED
 SERVICE/PARKING GARAGE BUILDING, ALL FLOORS SHOWING
 TRAVEL DISTANCE AND EXITS, EGRESS COMPONENT WIDTHS,
 OCCUPANCY CLASSIFICATION, OCCUPANT LOAD, DISTANCE APART
 OF REQUIRED EXITS, ANY OTHER PERTINENT INFORMATION TO
 DETERMINE CODE COMPLIANCE.THE EXIT DISCHARGE IS TO
 BE TO THE OUTSIDE OF THE BUILDING, INCLUDING OUTSIDE OF
 THE CANOPY COVERED AREAS, AND TRAVEL DISTANCE IS TO
 INCLUDE TRAVEL THROUGH THESE AREAS IF THIS.
  
 PLEASE PROVIDE ALL REQUESTED INFORMATION.THE LIFE
 SAFETY PLAN PROVIDED DOES NOT INCLUDE ALL OF THE ABOVE
 INFORMATION.NO OCCUPANT LOAD WAS PROVIDED, AND THE
 TRAVEL DISTANCE IS SHOWN TO THE CANOPY AREA.TRAVEL
 DISTANCE IS TO BE TO THE OUTSIDE, NOT TO THE BUILDING
 AREA OF AN ADJACENT BUILDING.AS NO OPENINGS WOULD BE
 ALLOWED WITH A 0? TO 3? BUILDING SEPARATION (SEE FBC,
 THE OPEN AREA LEADING TO THE CANOPY WOULD ALSO NOT BE
 ALLOWED.A COMPLETE REVIEW CANNOT BE PERFORMED UNTIL
 DESIGN INTENT IS CLEAR.
  
 29.)ADDRESSED.
  
 30.)THERE APPEARS TO BE AN EXISTING SERVICE BUILDING
 ON THE WEST SIDE.INCLUDE A LIFE SAFETY PLAN SHOWING
 HOW EGRESS WILL BE AFFECTED.
  
 THE RESPONSE LETTER PARTIALLY ADDRESSES THIS COMMENT.
 PLEASE INCORPORATE THE INFORMATION INTO THE PLAN.
 PLEASE SHOW MEANS OF EGRESS FROM THE EXISTING SERVICE
 BUILDING; SHOW THAT IT IS NOT THROUGH THE SIDE ADJACENT
 TO THE PROPOSED SERVICE BUILDING AND PARKING
 STRUCTURE.
  
 31.)PROVIDE A LIFE SAFETY PLAN FOR THE EXISTING
 HUMMER BUILDING, FIRST FLOOR AND SECOND FLOOR (2 HOUR
 WALL SHOWN ON 2ND FLOOR) IF APPLICABLE.
  
 THE RESPONSE LETTER PARTIALLY ADDRESSES THIS COMMENT.
 PLEASE INCORPORATE THE INFORMATION INTO THE PLAN.
 PLEASE SHOW MEANS OF EGRESS FROM THE EXISTING HUMMER
 BUILDING; SHOW THAT IT IS NOT THROUGH THE CANOPY AREA.
 IF IT IS, AS YOU ARE CLOSING OFF THE CANOPY AREA, THAT
 DISTANCE MUST BE ADDED TO THE TRAVEL DISTANCE.
  
 32.)A FOLDING PARTITION IS SHOWN ON THE PLAN IN THE
 MEZZANINE/TRAINING AREA.DOES THIS PARTITION CLOSE? IT
 DOES NOT COMPLY WITH EGRESS DOOR REQUIREMENTS,
 FBC1008.1.2, PLEASE ADDRESS.IF IT DOES NOT CLOSE, PUT
 THAT REQUIREMENT ON THE PLAN.
  
 THE PARTITION WAS REMOVED FROM MOST SHEETS BUT STILL
 APPEARS ON THE MECHANICAL PAGES.PLEASE CHECK ALL
 SHEETS.
  
 33.)STATE WHETHER THIS HAS BEEN DESIGNED AS AN OPEN
 PARKING GARAGE OR ENCLOSED PARKING GARAGE, STATE IN THE
 CODE SUMMARY, FBC406, AND SEE ALL REQUIREMENTS, SHOW ON
 PLAN.
  
 PLEASE INCORPORATE INFORMATION INTO THE PLAN AS
 REQUESTED.THE RESPONSE LETTER STATES TO SEE ITEM 12
 FOR THE CODE SUMMARY, BUT REQUESTED INFORMATION WAS NOT
 PROVIDED.PLEASE INCLUDE IN THE PLAN.
  
 34.)PROVIDE DESIGN SPECIFICATIONS FOR THE GUARD,
 FBC1607.7, FBC1012.
  
 THE RESPONSE LETTER STATES THAT THIS WILL BE DONE
 THROUGH SHOP DRAWINGS.DESIGNER OF RECORD IS TO
 PROVIDE DETAILS AND DESIGN CRITERIA AS REQUESTED
 FBC*106.1.1.
  
 35.)ADDRESSED.
  
 36.)WHAT IS THE 3FT4IN DIMENSION SHOWN AT THE STAIR,
 #303 AND 203?IT APPEARS TO BE AN OPENING, NOT ALLOWED
 IN A VERTICAL EXIT.PLEASE CLARIFY.
  
 THIS WAS REMOVED FROM MOST SHEETS BUT STILL APPEARS ON
 THE MECHANICAL SHEETS.PLEASE ADDRESS AND MAKE ALL
 SHEETS CONSISTENT.
  
 37.)A101, ROOF PLAN, 2ND FLOOR PLAN, STORAGE IS SHOWN
 WITH AN OPENING INTO THE STAIR.SEE 1019.1.1, OPENINGS
 TO BE LIMITED TO THOSE NECESSARY FOR EXIT ACCESS FROM
 NORMALLY OCCUPIED SPACES.
  
 THE RESPONSE LETTER STATES, ?THIS SPACE IS A FREQUENTLY
 VISITED STORAGE AREA.OPENINGS TO EXIT STAIR SHOULD BE
 ALLOWED.?PLEASE SHOW IN THE CODE WHERE THIS IS
 ALLOWED.
  
 38.)FIRE EXIT, FIRST FLOOR, TO HAVE SEPARATION FROM
 THE OCCUPANCY ABOVE IF AN OCCUPANCY SEPARATION IS
 REQUIRED.GG-A108.
  
 AN OCCUPANCY SEPARATION IS REQUIRED FOR GARAGES,
 FBC406.2.7.FBC302.3.1 STATES THAT FIRE SEPARATIONS
 ARE NOT REQUIRED BETWEEN USES, EXCEPT AS REQUIRED BY
 OTHER PROVISIONS.YOUR RESPONSE LETTER STATES THAT YOU
 HAVE COMPLIED WITH THE MOST STRINGENT REQUIREMENT, BUT
 COMPLIANCE HAS NOT BEEN SHOWN.PLEASE SEE OTHER
 COMMENTS.
  
 39.)DECLARE INTERIOR FINISH CLASSIFICATION, FBC TABLE
 803.5.
  
 PLEASE ADDRESS ON THE PLAN.
  
 40.)THE LOUNGE/TRAINING AREA SHOWS A 2 HOUR
 SEPARATION, NO HORIZONTAL SEPARATION.IF THE OCCUPANCY
 SEPARATION IS REQUIRED, HORIZONTAL SEPARATION ALSO
 REQUIRED, PROVIDE CALCULATED FIRE RESISTANCE FBC7 OR
 TESTED ASSEMBLY, FLOOR AND CEILING.
  
 WHAT IS THE OCCUPANCY CLASSIFICATION OF THE
 LOUNGE/TRAINING AREA?PLEASE SEE FBC302.ALSO PROVIDE
 OCCUPANT LOAD FOR THIS AREA.SEE OTHER COMMENTS.
  
 41.)ADDRESSED.
  
 42.)ADDRESSED.PLEASE INCLUDE OCCUPANCY
 CLASSIFICATION SO THAT COMPLIANCE WITH FBC1607.1 CAN BE
 DETERMINED.
  
 43.)NO EXIT LIGHTS SHOWN ON FIRST FLOOR OR ROOF,
 FBC1006.3.
  
 44.)ADDRESSED.
  
 45.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC,
 FBC13.
  
 THIS HAS BEEN DONE, BUT IF THE ENERGY CALCS CHANGE
 THROUGH THE PLAN REVIEW PROCESS, PLEASE SIGN NEW ENERGY
 CALCS.
  
 46-49.)THESE COMMENTS RELATE TO PRODUCT APPROVALS
 WHICH WERE NOT SUBMITTED.
  
 50.)ADDRESSED.
  
 51.)ADDRESSED ON A201, SHEET A200 NO LONGER IN THE
 PACKAGE.
  
 NEW COMMENTS:
  
 52.)PRODUCT APPROVALS NOT REVIEWED PRIOR TO PERMIT
 ISSUANCE WILL REQUIRE SEPARATE PERMITS.NO PRODUCT
 APPROVALS SUBMITTED WITH THIS PERMIT APPLICATION
 PACKAGE.
  
 53.)THE SIGNATURE FOR AN ENGINEER CANNOT BE A STAMP
 (STRUCTURAL ENGINEER), SEE FAC61G15-23.002, FS471.025.
  
 54.)PLEASE CLOUD ALL CHANGES AND SUBMIT OLD SHEETS.
 PLEASE INCLUDE A RESPONSE LETTER INDICATING HOW EACH
 ITEM HAS BEEN ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-13 Cont ID  
Sent By shill Date 2006-10-13 Time 12:55 Rev Time 0.00
Received By shill Date 2006-10-10 Time 08:26 Sent To  
Notes
2006-10-13 13:06:43****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)PROVIDE A SURVEY FOR THIS PROPERTY, FBC*106.3.4,
 SHOWING PROPERTY LINE AND ALL EXISTING IMPROVEMENTS.
  
 3.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL
 561-233-5025 FOR MORE INFORMATION.
  
 4.)RADON FEES DUE, FS*553.721.SEE ATTACHED.
  
 5.)DUE TO VALUATION ADJUSTMENT, FEES HAVE BEEN
 INCREASED.SEE ATTACHED.
  
 6.)FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE
 REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5),
 FS553.79 (2), ATTACHED LETTER FROM DCA.
  
 7.) FBC* 109.3.7RESIDENT INSPECTOR. SUBMIT INSPECTOR
 RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA,
 DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.A RESIDENT
 INSPECTOR PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO
 ONE OR MORE OF THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS
 OF CONSTRUCTION
  
 ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION
 SERVICES MANAGER - TEL:
 561 805 6711), A MEETING INVOLVING THE OWNER, RESIDENT
 INSPECTOR, JOB INSPECTOR, CONTRACTOR AND ENGINEER. THIS
 MUST BE DONE PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL
 SETS OF ALL DOCUMENTS ARE REQUIRED FOR PERMITTING.
  
 8.)PROVIDE A SOILS INVESTIGATION REPORT, FBC1802.2.1,
 1802.2.3.THREE SETS REQUIRED.
  
 9.)THE SEAL IS ILLEGIBLE (ARCHITECT).PLEASE
 ADDRESS, FS481.221.
  
 10.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER
 OF RECORD, FBC*106.3.3.
  
 11.)INCLUDE FBC EB IN GOVERNING CODE.THIS PROPOSED
 IMPROVEMENT IS TO COMPLY WITH FBC EB CHAPTER 9; SEE
 ALSO FBC EB 901.2.SOME COMMENTS AND REQUEST FOR
 ADDITIONAL INFORMATION RELATE TO THIS CODE SECTION.
  
 12.)INCLUDE A CODE SUMMARY. DECLARE BUILDING TYPE
 FBC6 (INCLUDE A OR B), BUILDING HEIGHT AND AREA FBC5,
 OCCUPANCY CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY,
 FIRE SPRINKLER INFORMATION.NOTE THAT CANOPIES AND
 EQUIPMENT SHEDS ARE TO BE INCLUDED, SEE FBC 502,
 DEFINITION OF AREA, BUILDING.BUILDING TYPE WILL BE
 BASED ON WORST CASE UNLESS A FIRE WALL SEPARATES THE
 BUILDING AREAS.DETAILS OF EXISTING CONDITIONS SHOWING
 FIRE RESISTANCE MAY BE REQUIRED.PLEASE CONTACT ME IF
 YOU ARE UNSURE OF WHICH DETAILS TO INCLUDE.
  
 13.)REGARDING OCCUPANCY CLASSIFICATIONS, PLEASE SEE
 FBC304, FBC311.2, FBC311.3.OTHER CODE SECTIONS MAY
 APPLY.
  
 14.)WHAT HAZARDOUS MATERIALS WILL BE STORED AND IN
 WHAT QUANTITIES?SEE FBC TABLE 307.7(1), FBC 406.6.
  
 15.)DECLARE AN OCCUPANCY CLASSIFICATION FOR THE OIL
 STORAGE, SEE FBC TABLE 307.7(1), FBC406.6.NOTE
 QUANTITIES.
  
 16.)SHOW HOW COMPLIANCE WITH FBC TABLE 503 HAS BEEN
 ACCOMPLISHED; SEE ALSO FBC 302.IF HEIGHT OR AREA
 MODIFICATIONS HAVE BEEN USED AS PER FBC 503 THROUGH
 508, PUT ALL INFORMATION AND CALCULATIONS ON THE PLAN.
 INFORMATION PROVIDED SHOULD BE CLEAR IN REGARDS TO
 BUILDING TYPE, BUILDING AREA, AND OCCUPANCY
 CLASSIFICATION IN REGARDS TO THE EXISTING BUILDINGS
 (INCLUDING AREAS REFERRED TO AS ?CANOPY? AND
 ?EQUIP.SHED?, ETC.) AS WELL AS THE NEW IMPROVEMENT.
  
 17.)IT IS NOT CLEAR WHETHER THE EXISTING SERVICE
 SHOWN ON THE WEST SIDE MSP-1 WILL BE A PART OF THE NEW
 BUILDING (APPEARS TO BE ATTACHED AT THE NORTHWEST
 PORTION, THE REST OF THE EXISTING SERVICE IS ALONG THE
 RAMP) OR IF IT A SEPARATE BUILDING, TO BE SEPARATED
 WITH AN ASSUMED PROPERTY LINE.IF THIS IS A SEPARATE
 BUILDING, SHOW COMPLIANCE WITH FBC TABLE 602 BY SHOWING
 THE BUILDING TYPE AND OCCUPANCY, ASSUMED PROPERTY LINE,
 DISTANCE OF EACH BUILDING FROM THE ASSUMED PROPERTY
 LINE.COMPLIANCE FOR EACH BUILDING MUST BE SHOWN,
 INCLUDING FIRE RESISTANCE RATING FOR THE EXISTING
 BUILDING.
  
 IF THIS IS NOT A SEPARATE BUILDING, INCLUDE THIS
 BUILDING IN THE CODE SUMMARY, SEE ITEM 3.
  
 18.)SEPARATIONS IF REQUIRED ARE TO COMPLY WITH FBC
 TABLE 302.3.2.AS NO FIRE SPRINKLER INFORMATION OR FBC
 TABLE 503 COMPLIANCE WAS PROVIDED, IT IS NOT CLEAR IF
 THE 2 HOUR SHOWN BETWEEN B AND S1 IS CORRECT.
  
 19.)NO HORIZONTAL SEPARATIONS WERE SHOWN.SEE
 PREVIOUS COMMENT, NOT CLEAR AT THIS TIME IF IT IS
 REQUIRED.
  
 20.)PROVIDE DISTANCE OF ADJACENT BUILDINGS TO THE
 PROPOSED RENOVATED BUILDING.FOR INSTANCE, DISTANCE
 FROM USED CARS TO HUMMER SHOWROOM, USED CARS TO
 EXISTING SERVICE.CONNECTING MULTIPLE BUILDINGS MAY
 AFFECT BUILDING TYPE FBC5, WHICH MAY AFFECT CODE
 COMPLIANCE WITH FBC TABLE 602.PROVIDE INFORMATION IN
 REGARDS TO OCCUPANCY CLASSIFICATION AND BUILDING TYPE
 FOR OTHER STRUCTURES.
  
 21.)MSP-1, BUILDING/LOT COVERAGE ZONING INFORMATION
 REFERS TO AN EXISTING LEVITZ BUILDING BUT THAT BUILDING
 IS NOT REFERENCED ON THE SITE PLAN.
  
 22.)WHAT IS BETWEEN THE PROPOSED SERVICE/PARKING AND
 EXISTING VW SERVICE/VW SHOWROOM?
  
 23.)A101 AND OTHER DETAILS, STAIR DOORS A132, A203,
 A303,SEE FBC11-4.13 AND FBC FIGURE 11-26, TWO HINGED
 DOORS IN A SERIES.
  
 24.)A111E, DOOR TO MENS LOCKER, SHOW MANEUVERING
 SPACE, PULL SIDE, FBC11 FIGURE 25.
  
 25.)MSP-1 SHOWS A PROPOSED PHASE 2 OF PARKING
 STRUCTURE.NOTE THAT ONLY THE CURRENT IMPROVEMENT IS
 UNDER REVIEW FOR CODE COMPLIANCE.
  
 26.)S4, THERE IS A NOTE FOR 6IN CONCRETE SLAB AT THE
 ELEVATOR AREA.IS THIS SUPPOSED TO BE FOR THE
 MEZZANINE?6IN CONCRETE SLAB SHOWN FOR VESTIBULE.
  
 27.)MSP-1, ACCESSIBLE ROUTE FROM THE PUBLIC WAY IS
 SHOWN FBC11-4.1.2(1), SHOW MAXIMUM SLOPE ON THE PLAN.
  
 28.)PROVIDE A LIFE SAFETY PLAN FOR THE PROPOSED
 SERVICE/PARKING GARAGE BUILDING, ALL FLOORS SHOWING
 TRAVEL DISTANCE AND EXITS, EGRESS COMPONENT WIDTHS,
 OCCUPANCY CLASSIFICATION, OCCUPANT LOAD, DISTANCE APART
 OF REQUIRED EXITS, ANY OTHER PERTINENT INFORMATION TO
 DETERMINE CODE COMPLIANCE.THE EXIT DISCHARGE IS TO
 BE TO THE OUTSIDE OF THE BUILDING, INCLUDING OUTSIDE OF
 THE CANOPY COVERED AREAS, AND TRAVEL DISTANCE IS TO
 INCLUDE TRAVEL THROUGH THESE AREAS IF THIS.
  
 29.)IT APPEARS THAT THE BUILDING AREA BETWEEN THE
 IMPROVEMENT AND VW AREAS IS AN OPEN CANOPY, SO EGRESS
 ON THAT SIDE FOR THE OTHER BUILDING IS NOT AFFECTED. IS
 THIS CORRECT?IF NOT, PROVIDE A LIFE SAFETY PLAN FOR
 THAT AREA.
  
 30.)THERE APPEARS TO BE AN EXISTING SERVICE BUILDING
 ON THE WEST SIDE.INCLUDE A LIFE SAFETY PLAN SHOWING
 HOW EGRESS WILL BE AFFECTED.
  
 31.)PROVIDE A LIFE SAFETY PLAN FOR THE EXISTING
 HUMMER BUILDING, FIRST FLOOR AND SECOND FLOOR (2 HOUR
 WALL SHOWN ON 2ND FLOOR) IF APPLICABLE.
  
 32.)A FOLDING PARTITION IS SHOWN ON THE PLAN IN THE
 MEZZANINE/TRAINING AREA.DOES THIS PARTITION CLOSE? IT
 DOES NOT COMPLY WITH EGRESS DOOR REQUIREMENTS,
 FBC1008.1.2, PLEASE ADDRESS.IF IT DOES NOT CLOSE, PUT
 THAT REQUIREMENT ON THE PLAN.
  
 33.)STATE WHETHER THIS HAS BEEN DESIGNED AS AN OPEN
 PARKING GARAGE OR ENCLOSED PARKING GARAGE, STATE IN THE
 CODE SUMMARY, FBC406, AND SEE ALL REQUIREMENTS, SHOW ON
 PLAN.
  
 34.)PROVIDE DESIGN SPECIFICATIONS FOR THE GUARD,
 FBC1607.7, FBC1012.
  
 35.)A101, MEZZANINE PLAN SHOWS A PLYWOOD DECK,
 CEILING OVER JANITOR?S CLOSET.AS NO BUILDING TYPE WAS
 DECLARED, IT IS NOT CLEAR IF THIS IS PERMITTED
 (COMBUSTIBLE).PLEASE CONFIRM PRIOR TO RESUBMITTAL.
  
 36.)WHAT IS THE 3FT4IN DIMENSION SHOWN AT THE STAIR,
 #303 AND 203?IT APPEARS TO BE AN OPENING, NOT ALLOWED
 IN A VERTICAL EXIT.PLEASE CLARIFY.
  
 37.)A101, ROOF PLAN, 2ND FLOOR PLAN, STORAGE IS SHOWN
 WITH AN OPENING INTO THE STAIR.SEE 1019.1.1, OPENINGS
 TO BE LIMITED TO THOSE NECESSARY FOR EXIT ACCESS FROM
 NORMALLY OCCUPIED SPACES.
  
 38.)FIRE EXIT, FIRST FLOOR, TO HAVE SEPARATION FROM
 THE OCCUPANCY ABOVE IF AN OCCUPANCY SEPARATION IS
 REQUIRED.GG-A108.
  
 39.)DECLARE INTERIOR FINISH CLASSIFICATION, FBC TABLE
 803.5.
  
 40.)THE LOUNGE/TRAINING AREA SHOWS A 2 HOUR
 SEPARATION, NO HORIZONTAL SEPARATION.IF THE OCCUPANCY
 SEPARATION IS REQUIRED, HORIZONTAL SEPARATION ALSO
 REQUIRED, PROVIDE CALCULATED FIRE RESISTANCE FBC7 OR
 TESTED ASSEMBLY, FLOOR AND CEILING.
  
 41.)THE NOTE A106 STATES THAT THE FUSIBLE LINK IS TO
 BE MANUALLY OPERATED.CLARIFY.
  
 42.)PROVIDE DESIGN CRITERIA, LIVE LOADS, FOR
 MEZZANINE AS PER FBC TABLE 1607.1.NOT INCLUDED ON
 S1.
  
 43.)NO EXIT LIGHTS SHOWN ON FIRST FLOOR OR ROOF,
 FBC1006.3.
  
 44.)MEZZANINE IS TO BE OPEN TO THE ROOM IT IS LOCATED
 IN, SEE FBC505.4.
  
 45.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC,
 FBC13.
  
 46.)PRODUCT APPROVAL FOR OVERHEAD DOOR HAS A PRODUCT
 LIMITATION OF -53, S10 SPECIFIES EITHER -61 FOR D1 OR
 -73 FOR D1A.
  
 47.)PROVIDE FLORIDA STATE PRODUCT APPROVAL FOR ALL
 PRODUCTS, INCLUDING ONES WITH A NOA.IF IT IS NOT
 AVAILABLE, A LOCAL PRODUCT APPROVAL WILL BE ISSUED.
  
 48.)SPEC SHEETS PROVIDED FOR THE FLEMING DOOR.
 PRODUCT APPROVALS REQUIRED.THE DOOR DOES NOT MEET
 DESIGN PRESSURE FOR D1A.
  
 49.)UNITED ENERTECH LOUVERS APPEAR CODE COMPLIANT.
 SEE ITEM 47 AND 10.
  
 50.)A200, NOTES FOR HC BAR BACKING REFER TO PT WOOD.
 NOTE THAT THAT IS A COMBUSTIBLE.BUILDING TYPE HAS NOT
 BEEN DECLARED, SO CODE COMPLIANCE CANNOT BE
 DETERMINED.
  
 51.)A200, ACCESSIBLE SINK IS TO BE A MAX OF 6 1/2 IN
 DEEP, FBC11-4.24.
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-12-28 Cont ID  
Sent By dpalmer Date 2007-12-28 Time 16:09 Rev Time 0.00
Received By dpalmer Date 2007-12-28 Time 16:09 Sent To B
Notes
2007-12-28 16:11:29**PLANS REDLINED**
  
 1) AS LOADS FOR LIGHTING HAVE DECREASED DUE TO LESS
 WATTAGE ON FIXTURES, PLEASE REVISE PANELS/LOADS BEFORE
 FINAL. IF OTHER REVISIONS ARE DONE BEFORE ROUGH THIS
 MAY BE REVISED AT THAT TIME FOR INSPECTION.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-10-18 Cont ID  
Sent By dpalmer Date 2007-10-18 Time 16:33 Rev Time 0.00
Received By dpalmer Date 2007-10-18 Time 16:33 Sent To  
Notes
2007-10-18 16:33:37 
 *** DENIED 5TH REVIEW *****
  
 1) NOTE: PLEASE KNOW THIS IS THE FIRST TIME THE INPUT
 DATA REPORT IS BEING REVIEWED.
 PLEASE SEE THE INPUT DATA REPORT SUBMITTED WITH
 ARCHITECTURAL PLANS AND BLACK BINDER WHICH WAS NOT
 SUBMITTED AS A RESUB AND ALSO THE NEW INPUT DATA REPORT
 SHEETS LEFT AFTER MEETING HELD ON 10/11/07 DO NOT
 CORRELATE WITH THE ENERGY CALCULATIONS SUMMARY SHEETS
 NOR DO EITHER ONE COORDINATE WITH THE PLANS.
 PLEASE KNOW AS THIS IS THE FIRST TIME THE SHEETS WERE
 SUBMITTED THIS IS THE FIRST ACTUAL REVIEW OF
 DOCUMENTS.
 PLEASE SEE FOR EXAMPLE: THE IDR WHICH WAS RUN ON
 4/25/07 UNDER THE 3.0 VERSION CONTAINS EXTERIOR
 LIGHTING FIXTURES HOWEVER THE SUMMARY SHEETS STATES
 *NONE ENTERED*.
 PLEASE SEE FOR EXAMPLE: THE TYPE *M* FIXTURES FOR
 PARKING GARAGE WHICH ARE SHOWN AS 1000WATTS ON THE
 PLANS AND FIXTURE LEGEND ARE ONLY 455WATTS ON THE IDR.
 PLEASE SEE FOR EXAMPLE: THE INPUT DATA REPORT DATED
 9/11/07 DOES NOT CONTAIN ANY EXTERIOR LIGHTING FIXTURES
 WHICH ARE NOT POSSIBLE WHEN THE PLANS CONTAIN NUMEROUS
 INCLUDING THE TYPE *M* AS NOTED ABOVE ALONG WITH
 MISSING TYPE *K*.
 PLEASE SEE FOR EXAMPLE THE INTERIOR LIGHTING FIXTURES
 *J* AND *JQ* WHICH ARE IN SERVICE BAY AREAS IN WHICH
 THE NUMBER OF FIXTURES ON PLANS ARE DIFFERENT THAN THE
 IDR.
 PLEASE SEE FOR EXAMPLE: THE STAIRS (BOTH), HALLWAY
 AREA, VESTIBULE ETC WHICH THESE TOTAL NUMBER OF
 FIXTURES ON PLANS EXCEED THAT AS ON THE IDR.
  
 THESE ARE SOME EXAMPLES. PLEASE GO THROUGH THE ENERGY
 CALCULATIONS, PLEASE RUN COMPLETE ENERGY CALCULATIONS
 UNDER 2.11 (2004 FBC W/2005 REVISION).
 THIS OFFICE WILL REQUIRE BOTH THE SUMMARY SHEETS AND
 THE INPUT DATA SHEETS TO COORDINATE WITH THE DATES THEY
 HAVE BEEN RUN.\
 13-415.1.B, 13-415.2, 13-415.2.ABC.1.3,13-103.1.1.1
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. THIS
 WILL BE A RE-SUBMITTAL AND THE RE-SUBMITTAL FEE OF 10%
 OF THE BASE PERMIT FEE WILL BE DUE.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-07-27 Cont ID  
Sent By dpalmer Date 2007-07-27 Time 16:32 Rev Time 0.00
Received By dpalmer Date 2007-07-27 Time 15:30 Sent To  
Notes
2007-07-27 16:32:54 
 *** UNSAT 4TH REVIEW ***
  
 1) NOTE: PLEASE SEE THE PREVIOUS REVIEWS WHICH
 REQUESTED THE INPUT DATA REPORT TO BE SUBMITTED AS
 REQUIRED FOR REVIEW. THE RESPONSE LETTER FROM DESIGN
 TEAM MENTIONS THIS WILL BE SUBMITTED HOWEVER COULD NOT
 LOCATE THIS WITH THE ENERGY CALCULATIONS OR OTHER
 DOCUMENTS SUBMITTED.
 PLEASE SUBMIT SO THAT A REVIEW OF SAID ENTERED
 INFORMATION CAN BE REVIEW WITH PLANS.
 13-415.1.B/13-415.2
  
 2) NOTE: PLEASE SEE PREVIOUS NOTES MENTIONED THAT THE
 MECHANICAL EQUIPMENT WAS STILL BEING SHOWN ON THE
 ADJACENT *BUILDING* ON ELECTRICAL AND OTHER TRADE
 SHEETS.. PLEASE SEE THE RESPONSE WAS THAT THIS
 EQUIPMENT WOULD BE MOVED TO ROOF. THIS WAS DONE ON
 ELECTRICAL PLANS HOWEVER THE MECHANICAL PLANS STILL
 INDICATE THIS EQUIPMENT ON THE ADJACENT BUILDING.
 PLEASE ADJUST M-PLANS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-04-22 Cont ID  
Sent By dpalmer Date 2007-04-22 Time 11:16 Rev Time 0.00
Received By dpalmer Date 2007-04-22 Time 09:09 Sent To  
Notes
2007-04-22 11:16:36 
 ******* UNSAT 3RD REVIEW ******
  
 ** PLEASE SEE THAT THERE ARE STILL SOME ITEMS FROM
 PREVIOUS REVIEWS WHICH HAVE NOT YET BEEN CLEARED UP AND
 NEED TO BE ADDRESSED.
  
 1) NOTE: PLEASE SEE RESPONSE FROM DESIGNERS MENTIONS
 THE ADDRESS WHICH HAS BEEN GIVEN BY THE ADDRESSING
 REVIEWER IS THAT OF 3023 AND IS NOW ON ALL TITLE BLOCKS
 ACCORDINGLY, HOWEVER THE TITLE BLOCKS ON ALL SHEETS
 STILL INDICATE 3021?
 PLEASE KNOW IF THIS IS THE ONLY COMMENT ON SOME SHEETS,
 THIS MAY BE HAND PRINTED ON SHEETS BY CONTRACTOR OR
 OTHER DESIGN STAFF.
 PLEASE REVISE ON SHEETS WHICH NEED TO BE CHANGED OUT.
  
 2) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO
 CONTROL OF EGRESS LIGHTING IN STAIRS. RESPONSE MENTIONS
 THAT ONCE ON DEVICE IS ACTIVATED THAT 15MINS IS MORE
 THAN ENOUGH TIME TO EGRESS TO THE NEXT LEVEL, HOWEVER
 THE COMMENT IS FOR THE FAILURE OF ANY ONE SINGLE DEVICE
 (OCCUPANCY SENSORS) CAN NOT LEAVE ANY ONE AREA OF
 EGRESS IN TOTAL DARKNESS.
 PLEASE SEE 7.8.1.2.2 AUTOMATIC, MOTION SENSOR?TYPE
 LIGHTING SWITCHES SHALL BE PERMITTED WITHIN THE MEANS
 OF EGRESS, PROVIDED THAT THE SWITCH CONTROLLERS ARE
 EQUIPPED FOR FAIL-SAFE OPERATION, THE ILLUMINATION
 TIMERS ARE SET FOR A MINIMUM 15-MINUTE DURATION, AND
 THE MOTION SENSOR IS ACTIVATED BY ANY OCCUPANT MOVEMENT
 IN THE AREA SERVED BY THE LIGHTING UNITS.
 PLEASE ALSO SEE CHAPTER 10 OF THE FBC 1006.1.2 WHICH
 STATES THE SAME.
 IT IS LS 101 7.9.2.2 WHICH MENTIONS THE FAILURE OF A
 SINGLE DEVICE, SWITCHING, TRIPPING OF A BREAKER ETC.
 THIS WOULD REQUIRE A MINIMUM OF TWO OCCUPANCY SENSORS
 OR DEVICES OF SOME TYPE TO DETECT THE OCCUPANT AND TURN
 ON THE LIGHTING. IF AN OCCUPANT WAS TO LEAVE AN UPPER
 FLOOR, AND THE DEVICE WAS NOT IN WORKING ORDER, THEN A
 SECOND DEVICE IS REQUIRED IN THE VICINITY TO DO THE
 SAME AS THE PRIMARY DEVICE.
  
 3) NOTE: PLEASE SEE THAT AS THIS IS BEING CONSIDERED
 AND CONSTRUCTED AS A SEPARATE BUILDING, AS NOTED ON
 PREVIOUS REVIEW, THE MECHANICAL AND ELECTRICAL
 EQUIPMENT IS STILL BE SHOWN ON THE EXISTING ROOF OF THE
 EXISTING BUILDING WHICH IS NOT CONSIDER PART OF THE NEW
 *BUILDING*
 PLEASE RELOCATE.
 PLEASE SEE SOME SHEETS STILL INDICATE THE PREVIOUS WALL
 AND FLOOR LAYOUTS WHICH DO NOT COORDINATE WITH THE REST
 OF THE PLANS. (*SITE PLANS*)
 FBC 106.1.2
 225.30, 230.3.
  
 4) NOTE: PLEASE SEE NOW THERE ARE HAND DRAWN CHANGES TO
 SHEET E-101 WHICH ONE OF THE ITEMS IN THAT OF AN EXIT
 SIGN WHICH IS PLACED SO THAT THE OCCUPANTS IN SOUTHEAST
 STAIR TOWER ARE TO EGRESS INTO THE ADJACENT HUMMER
 BUILDING??
 NO HAND DRAWN CHANGES ARE PERMITTED TO PLANS FS
 471.025
 PLEASE SEE FIRE AND BUILDING REVIEWS.
 PLEASE SEE THE ELEVATION ON A105 SHOWS WHAT APPEARS TO
 BE AN EXIT DOORWAY FROM VESTIBULE TO OUTSIDE, SHOULD
 NOT THIS EXIT LIGHT BE LOCATED ABOVE THE EAST DOOR IN
 THIS STAIR TOWER?
 PLEASE SEE OTHER HAND DRAWN CIRCULAR SYMBOL WHICH IS
 ALSO ADJACENT TO THIS SAME AREA?
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE RESPONSE LETTERS MENTIONS THE OVER
 RIDE TIMES AND TIMES HOWEVER COULD NOT LOCATE THE TIMES
 FOR THE OCCUPANCY DEVICES. PLANS DO NOTE THE TIME FOR
 THE OVER RIDE OF THE SERVICE BAY. 13-415.1.ABC.1.1
  
 6) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO THE
 MINIMUM LEVELS FOR HORN AND STROBE DEVISE WHICH ARE
 REQUIRED TO BE STATED ON THE BASE SET OF BUILDING PLANS
 FOR FBC ADA COMPLIANCE. IT IS KNOWN THAT ANY FA WORK
 WILL BE UNDER SEPARATE PERMIT HOWEVER BASE BUILDINGS
 MUST INDICATE MINIMUM COMPLIANCE.
 FBC 11-4.28.1,.2 AND .3(4).
 FBC 106.3.5.1.2
  
 7) NOTE: PLEASE SEE PREVIOUS REVIEW AND RESPONSE
 MENTIONS THAT THE MINIMUM LEVELS FOR WIND LOADS FOR
 ROOF TOP LIGHT POLES WILL BE STATED ON PLANS AND TO SEE
 FIXTURE LEGEND HOWEVER THE FIXTURE LEGEND DOES NOT
 INDICATE THE *140MPH MINIMUM* DESIGNATION.
 THE CALCULATIONS CAN BE SET UP AS A *PROVISO* WHICH
 WILL ALLOW ISSUANCE AND CALCULATIONS TO BE SUBMITTED
 BEFORE INSTALLATION, HOWEVER PLEASE STATE THE 140. FBC
 106.1.2
  
 8) NOTE: PLEASE SEE THE THIRD PARKING
 LEVEL/OUTSIDE/EXTERIOR LIGHTING WHICH STILL INDICATE
 LIGHTING TO A LIGHTING CONTACTOR #3, BUT NO DETAIL WAS
 SUBMITTED.
 PLEASE SHOW.
 FBC 106.1.2, 106.3.5.1.2
  
 9) NOTE: PLEASE SEE PREVIOUS NOTES WHICH MENTIONED TO
 CORRELATE AND COMPLETE THE ENERGY CALCULATIONS AND TO
 VERIFY THE METHOD AS SUBMITTED.
 PLEASE SEE THE FRONT COVER SHEET MENTIONS THAT THE
 INPUT DATA REPORT MUST BE SUBMITTED ALONG WITH
 COMPLIANCE REPORT, HOWEVER THIS HAS NOT BEEN DONE.
 PLEASE SEE 13-415.1.AB.1.1
  
 10) NOTE: ** NOT A COMMENT FOR TEELE ENGINEERING.
 PLEASE SEE THE PREVIOUS REVIEW WHICH INDICATED THAT THE
 *S* SHEETS CONTAINED A *RUBBER-STAMP* FOR REQUIRED
 ORIGINAL SIGNATURE, AND RESPONSE WAS THAT ALL SHEETS
 WILL NOW BE SIGNED, HOWEVER ONLY ONE OF THE *S* SHEETS
 WERE CORRECTED. PLEASE SEE BUILDING REVIEW NOTES AS
 THIS IS ONLY BEING NOTED BY THIS REVIEWER AT THIS TIME
 AND DOES NOT AFFECT THE ELECTRICAL PLANS.
 FS 471.025
  
 11) NOTE: PLEASE SEE NOTE BELOW ON PREVIOUS REVIEW
 WHICH REQUESTED ALL OLD/VOIDED SHEETS TO BE REMOVED
 FROM THE TWO COMPLETED SETS. ONE SET OF EACH OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED WITH THE TWO SETS
 SEPARATELY AND NOT INCLUDED IN SETS.
 THIS WILL HELP ALLEVIATE ANY CONFUSION FOR NEW AND OLD
 SHEETS , AND WILL HELP TO NOT CAUSE ANY FURTHER DELAYS
 IN THE PROJECT.
  
  
 ** PLEASE BE AWARE OF COMMENTS FROM OTHER TRADES WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-02-01 Cont ID  
Sent By dpalmer Date 2007-02-01 Time 18:31 Rev Time 0.00
Received By dpalmer Date 2007-01-31 Time 18:30 Sent To  
Notes
2007-02-01 18:30:502007-02-01 18:30:50
  
 ******* UNSAT 2ND REVIEW ******
  
 *** PLEASE SEE THERE ARE ITEMS FROM THE PREVIOUS REVIEW
 WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW
 COMMENTS BASED ON CHANGES IN PLANS AND NEW INFORMATION
 AND/OR CHANGES MADE TO PLANS.
  
 **** IMPORTANT****
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 THE PREVIOUS REVIEW WITH A *NO*, *OK* OR *NO/OK*.
  
 A) A, NO WILL CONTAIN A FURTHER EXPLANATION AS TO WHY
 THE COMMENT MAY NOT HAVE BEEN FULLY ADDRESSED WITH THE
 PREVIOUS REVIEW NOTE BELOW WITH **PREVIOUS REVIEW NOTE
 #1**
  
 B) A, OK, WILL HAVE NO COMMENTS EXCEPT PERHAPS A
 REFERENCE TO SEE ** NEW NOTES*. THE PREVIOUS REVIEW
 NOTE WILL BE REMOVED.
  
 C) A, NO/OK, WILL HAVE FURTHER EXPLANATION AS PART OF
 THE COMMENT MAY HAVE BEEN ADDRESSED, HOWEVER NOT ALL.
 THE PREVIOUS REVIEW NOTE WILL BE NOTED **PREVIOUS
 REVIEW NOTE #1**
  
 D) NEW NOTES WILL BE ADDED TO THE END AND LABELED **
 NEW NOTES **
  
  
  
  
 1) A) NOTE: NO, PLEASE SEE THE ADDRESS HAS NOT YET BEEN
 CHANGED AND PLEASE SEE THIS IS NOT A SEPARATE BUILDING
 BY DEFINITIONS OF THE FBC AND MAY OR MAY NOT CONTAIN A
 NEW ADDRESS. THIS HAS BEEN SENT TO THE ADDRESSING
 REVIEWER AS IT IS A CODE RELATED COMMENT. PLEASE SEE
 POSSIBLE COMMENTS FROM BUILDING, AND FIRE REVIEWER(S).
 THIS ADDRESS MAY OR MAY NOT BE OK, IT IS UNCERTIAN AT
 THIS TIME.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE PERMIT APPLICATION AND PLANS MENTIONS AND
 SHOWS "3021", HOWEVER THIS PROJECT IS LOCATED ON A
 LEGAL ADDRESS IN OUR SYSTEM OF "3001".
 PLEASE KNOW TITLE BLOCKS SHALL BE REVISED UPON
 CORRECTING OF ADDRESS.
  
 1) NOTE: OK.
  
 2) NOTE: OK FOR MEP PLANS, SEE NEW COMMENTS FOR OTHER
 SHEETS WHICH DO NOT APPLY TO TEELE & ASSC.
  
 3) NOTE: NO/OK, NOTES ADDED FOR ITEMS BELOW 18INCHES,
 HOWEVER PLEASE SEE ROOMS CONTAINING FUEL/LIQUIDS ETC
 WHICH WILL BE A CLASS AND DIVISION LOCATION NEED TO BE
 DESIGNATED.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE NEC 511, AND PLEASE INDICATE ALL RELEVANT AREAS
 AND LAYOUT ON PLANS.
  
 4) NOTE:NO, PLEASE SEE SOME AREAS FOR STAIRS WERE
 ADDED; HOWEVER PLEASE SEE THIS COMMENT IS BASED ON ALL
 EGRESS PATHS WHICH MAY CONTAIN OCCUPANTS WHICH NEED TO
 EGRESS FROM THE BUILDING.
 PLEASE SEE THE EXIT CORRIDOR; PLEASE SEE AREAS OF
 PARKING GARAGE WHICH DO NOT SEEM TO CONTAIN ANY
 EMERGENCY LIGHTING. PLEASE SEE THE LIGHTING IS BEING
 SHOWN ON THESE SAME UPPER LEVELS WITH OUT THE USE OF
 ANY NIGHT LIGHTS OR PHOTO-CELL OVER RIDES EVEN FOR DAY
 TIME OPERATIONS FOR MINIMUM LIGHTING.PLEASE SEE
 COMMENTS WITH RESPECT TO CONTACTORS AND CONTROLS.
 PLEASE EXPLAIN HOW THE STAIRS ARE SHOWING ONE LEVEL OF
 LIGHTING UNDER NORMAL AND ONE LEVEL OF LIGHTING UNDER
 EMERGENCY WHEN THE FIXTURES ARE THE SAME TYPES AND ARE
 BATTERY BACK UP. DO THESE CONTAIN A REDUCTION OF THE
 LIGHTING LEVELS BUILT IN?
 PLEASE ALSO SEE THAT THE STAIR LIGHTING IS BEING SHOWN
 ON OCCUPANCY SENSOR TYPE DEVICES WHICH ARE OK, HOWEVER
 PLEASE SEE DUE TO THE LAYOUT, THE FAILURE OF ONE DEVICE
 WOULD LEAVE ANY ONE AREA IN THE MEANS OF EGRESS PATH IN
 TOTAL WHICH WOULD NOT MEET THE MINIMUM LIGHTING FOR
 LIFE SAFETY. PLEASE ADJUST DEVICES OR CALL TO GO OVER
 OTHER POSSIBLE OPTIONS.
 ** PLEASE SEE THE FOLLOWING SCENARIO:AN OCCUPANT IS
 LOCATED IN THE PARKING GARAGE ON THE SECOND LEVEL (OR
 OTHER LOCATIONS IN BUILDING) WHICH DO NOT CONTAIN OF
 OVER RIDE(S) FOR LIGHTING WHEN THE LIGHTING SHUTS OFF
 DUE TO THE TIME SET. PLEASE SEE THE AREA FOR MEANS OF
 EGRESS WOULD BE A HAZARD AND SHOULD CONTAIN EITHER
 SENOR DEVICES WHICH PROVIDE COVERAGE FOR OVER RIDE OR
 OTHER MEANS OF LIGHT FOR THE OCCUPANT TO FIN THEIR WAY
 TO THE MANUAL OVER RIDE DEVICE.
 PLEASE PROVIDE TIMES OF SCHEDULING.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE NFPA-101 7.8.1.3,
 7.9.2.2. PLEASE SUBMIT AND SUPPLY ALL MIN PHOTO-METRICS
 REQUIRED FOR STAIR TOWERS UNDER NORMAL AND EMERGENCY
 POWER.
 PLEASE ALSO INDICATE LIGHTING LEVELS (MIN) REQUIRED FOR
 ALL OTHER AREAS OF EGRESS. PLEASE SEE THERE ARE AREAS
 ON PLANS WHICH DO NOT SEEM TO MEET THIS.
 10FT CANDLES UNDER NORMAL AND 1FT CANDLE UNDER EM IN
 STAIRS.
 ALL OTHER AREAS 1FT MIN.
  
 5) NOTE: OK.
  
 6) NOTE: OK.
  
 7) NOTE: OK.
  
 8) NOTE: OK.
  
 9) NOTE: OK.
  
 10) NOTE: OK.
  
 11) NOTE: OK.
  
 12) NOTE: NO, NOTED ABOVE IN COMMENT #4.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #1**
 PLEASE SEE FIRE REVIEW COMMENTS FOR GARAGE AREAS LTS,
 REQ'D EM BACK UP.
 AS PREVIOUSLY NOTED ABOVE FOR ELECTRICAL REVIEW ALSO.
 LS101 7.9
  
 13) NOTE: NO/OK, PLEASE SEE SOME AREAS WHERE INGRESS
 INTO SPACE ARE SHOWN INDICATE A *S* AS FOR A STANDARD
 SWITCH. PLEASE SEE ANY OVER RIDE TYPE SHOWN THIS WAY
 SHOULD BE CLARIFIED ON SYMBOL LEGEND.
 PLEASE SEE SEPARATE AREAS (ELEVATOR PIT) WHICH WILL
 REQUIRE AUTOMATIC MEANS OF SHUT OFF (TIMER). PLEASE SEE
 THERE ARE OVER RIDES SHOWN ON CONTACTOR #1 WHICH DOES
 NOT INDICATE TYPE AND AMOUNT OF TIME ON THE OVER RIDE.
 PLEASE SEE OTHER AREAS WHICH A DEVICE WILL BE REQUIRED
 AND MAXIMUM TIMES FOR ALL DEVICES SHOULD BE INDICATED.
 PLEASE SEE 30MINS FOR OCCUPANCY SENSOR TYPE DEVICES AND
 4HRS MAX FOR TIMER TYPE.
 PLEASE SEE INPUT DATA IS MISSING FROM THE ENERGY
 CALCULATIONS.
 PLEASE SEE METHOD USED WILL AFFECT THE INFORMATION.
 THESE CALCULATIONS SUBMITTED ARE METHOD *B*.
 ** PLEASE SEE NEW NOTES WITH RESPECT TO CONTACTORS,
 CONTROLS AND CIRCUITING ON PLANS AND CONTACTORS.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #1**
 PLEASE SEE 2004 FBC CHAPTER 13 FOR CONTROLS FOR ALL
 LIGHTING.
 PLEASE INDICATE AND SHOW THE SYSTEM BEING PROPOSED.
 PLEASE PROVIDE SCHEDULING OF SYSTEMS.
 PLEASE PROVIDE OVER RIDES, LOCATIONS, AND AREAS FOR
 SEPARATE CONTROLS REQUIRED. PLEASE SEE FBC
 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE SHOW AND INDICATE THE TYPE OF OVER RIDE
 DEVICES, AND MAX ALLOWED TIMES. (NOTE: TIMER TYPE (4HRS
 MAX), OCCUPANT SENSOR TYPE 30MINS MAX).
 ALL AREAS WITH FLR TO CEILING HEIGHT PARTITIONS REQUIRE
 SEPARATE CONTROLS.
 PLEASE PROVIDE PERFORMANCE CALCULATIONS AND PLEASE SEE
 THE MAXIMUM PERMITTED
 "LIGHTING POWER DENSITIES" (LPD) ALLOWED FOR AREAS.
 PLEASE SEE SPACES AND USE PERMITTED IN TABLES.
 13-415.2, 13-415.2.ABC.1, TABLES? 13-415.2.B.
 ALL LPD'S ARE TO BE SHOWN.
  
 14) NOTE: NO, PLEASE SEE PLANS THE ARCHITECTURAL PLANS
 DO NOT CORRELATE WITH THE MECHANICAL AND PLUMBING
 SHEETS WITH RESPECT TO THE WALL(S) FROM THE SHOWROOM OF
 THE EXISTING BUILDING AND THE ADDITION.
 PLEASE SEE THAT A PARTIAL 2HR RATED WALL DOES NOT
 CONSTITUTE A SEPARATE BUILDING BY DEFINITION IN THE
 FBC. THIS WOULD BE REQUIRED TO BE A 4 HOUR RATED FIRE
 WALL. PLEASE SEE THE DEFINITIONS OF A FIRE WALL IN THE
 FBC. THE PLANS AS SUBMITTED DO NOT COMPLY WITH THIS.
 PLEASE KNOW BASED ON THIS AND COORDINATION OF SHEETS A
 SEPARATE SERVICE FOR THIS ADDITION TO AN EXISTING
 BUILDING IS NOT GRANTED AS PREVIOUSLY STATED. PLEASE
 ALSO SEE THE PLANS STILL INDICATE MECHANICAL EQUIPMENT
 FOR THE NEW BUILDING BEING SHOWN INSTALLED ON THE
 EXISTING SHOW ROOM PORTION OF THE BUILDING.
 ** PLEASE BE SURE TO SEE NEW NOTES FOR COORDINATION
 FROM ELECTRICAL PLANS TO ARCHITECTURAL PLANS.
  
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE THIS IS NOT BEING CONSIDERED A SEPARATE
 "BUILDING" AND IS PART OF THE CURRENT STRUCTURE AS THIS
 NEW STRUCTURE CONTAINS OPENINGS ETC FOR EGRESS ETC.
 PLEASE SEE FBC DEFINITIONS.
 PLEASE SEE NEC 230.2, AS THE NEW PROPOSED SEPARATE
 SERVICE NOT BEING FED FROM THE EXISTING SERVICE
 LOCATION GROUPED ETC IS NOT PERMITTED AS SHOWN. 230.2,
 230.72 ETC.
 IN ORDER TO GRANT THE NEW SERVICE FOR A NEW "BUILDING",
 THIS WOULD REQUIRE AND
 "FIREWALL", 4 HR RATED, COLLAPSIBLE ON BOTH SIDES WITH
 OUT AFFECTS ON THE STRUCTURAL INTEGRITY OF EITHER
 STRUCTURE. BY THE PLANS SUBMITTED, THIS IS NOT ACHIEVED
 AT THIS TIME.
  
 15) NOTE: OK.
  
 16) NOTE: OK..
  
 17) NOTE: OK.
  
 18) NOTE: NO? RESPONSE LETTER MENTIONS TO SEE REVISED
 ELECTRICAL PLANS FOR THIS HOWEVER THIS INFORMATION
 COULD NOT BE LOCATED.
 PLEASE KNOW PLANS ARE REQUIRED TO STATE THE MINIMUM, A
 *PROVISO* MAY BE SET UP TO OBTAIN THE STRUCTURAL
 CALCULATIONS LATER BEFORE ANY INSTALLATION OF BOLTS,
 BASE, ETC FOR POLES.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SUBMIT ALL WIND LOAD CALCULATIONS FOR ROOF TOP
 LT POLES WITH
 EPA FIGURED FOR ALL LT FIXTURES PROPOSED.
 THE CALCULATIONS AND SPEC FOR POLES WILL BE REVIEWED
 FOR STRUCTURAL CONNECTIONS, WIND LOADS ETC BY THE
 STRUCTURAL REVIEWER.
 THEY MUST MEET FBC 2004 140MPH MIN, 3 SEC GUST.
  
 19) NOTE: NO? RESPONSE MENTIONS TO SEE REVISED PLANS,
 HOWEVER NO INFORMATION COULD BE FOUND FOR PREVIOUS
 REQUEST.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SUBMIT THE MANUFACTURE SPECS /CUT SHEETS FOR
 THE TANK LESS WATER HEATER. PLEASE BE SURE THEY
 INDICATE THE
 NRTL LISTING.
 110.3, 90.7.
  
 20) NOTE:NO, SAME COMMENT. THIS IS NOTED AS THIS IS
 BEING PROPOSED AS A SEPARATE BUILDING, YET THIS IS NOT
 BEING MET AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE AS PLUMBING PLANS ALSO INDICATE BEING TIED
 INTO THE EXISTING BUILDING, IT SEEMS THE PERMIT
 APPLICATION WOULD BETTER DESCRIBE PROJECT AS AN
 ADDITION.
 THIS WILL BE DECIDED BY DESIGN FOR NOTES FROM ALL
 REVIEWER(S).
  
  
 ************ NEW NOTES *********
  
 21) NOTE: PLEASE SEE THE *S* SHEETS SUBMITTED CONTAIN A
 *RUBBER STAMP* FOR THE REQUIRED ORIGINAL SIGNATURE FROM
 THE ENGINEER. PLEASE SEE THE FLORIDA ADMINISTRATIVE
 CODE 61G15-23.002 AND FLORIDA STATUTES 471.025. THIS
 COMMENT IS MADE AND REQUIRED WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
 PLEASE KNOW ONE SET OF PLANS WILL BE RETAINED AS THIS
 COMMENT HAS BEEN MADE TO THIS SAME ENGINEER ON OTHER
 PROJECTS PREVIOUSLY.
  
 22) NOTE: PLEASE SEE FIRE SPRINKLER PLANS DO NOT
 CONTAIN ANY TITLE BLOCK FOR THE ENGINEER WHICH IS
 SIGNING AND SEALING DOCUMENTS.
 PLEASE ALSO SEE THAT THE SEAL IS NOT CLEAR AND VISIBLE
 WITH INFORMATION ON SAID SEAL.
 PLEASE SEE THAT EVEN SHADOWING DOES NOT PROVIDE
 INFORMATION.
 FAC 61G15-23.002 AND 61G15-23.001.,
 THIS COMMENT IS ALSO REQUIRED WHETHER OR NOT COMMENT IS
 MADE BY ANY OTHER TRADE(S).
 ONE SET IS BEING RETAINED.
 ** PLEASE KNOW THAT THE FIRE SPRINKLERS EVEN THOUGH
 REQUIRED TO BE SHOWN WITH THE BASE BUILDING PERMITTED
 PLANS WILL STILL BE REQUIRED TO BE UNDER A SEPARATE
 PERMIT, PLANS AND FEES AT A LATE DATE.
  
 23) NOTE: PLEASE SUBMIT COMPLETE DETAILS FOR FIRE ALARM
 SYSTEM BEING PROPOSED AND HOW THIS SYSTEM WILL BE TIED
 IN THE EXISTING SYSTEM. PLEASE KNOW THE BASE LOCATIONS
 AND DEVICES ARE REQUIRED AT THIS TIME FOR BASE
 BUILDING.
 PLEASE SEE THAT ALL OF THE MINIMUM LEVELS TO MEET FBC
 11-4.28.1, .2 AND .3(4) IS REQUIRED TO BE STATED ON
 PLANS.
 THIS COMMENT WAS NOT MADE ON THE PREVIOUS PLAN REVIEW
 BY THIS REVIEWER HOWEVER THIS IS NOW REQUIRED AS PART
 OF THE ELECTRICAL REVIEW.
 FBC 106.1.2 AND 106.3.5.1.2
  
 ** PLEASE KNOW THAT THE FIRE ALARM SCOPE OF WORK WILL
 STILL BE UNDER A SEPARATE PERMIT PLANS AND FEES ART A
 LATER DATE.
  
 24) NOTE: PLEASE SEE THERE ARE SEVERAL DIFFERENCES ON
 THE ARCH SHEETS, FROM THE ELECTRICAL, MECHANICAL AND
 PLUMBING SHEETS.
 WALLS DO NOT CORRELATE. (DOORS ETC)
 FBC 106.1, 106.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION ANDFBC CHAPTER 11.
  
  
 PLEASE SEE THE STAIRS AS THE ELECTRICAL PLANS SHOW
 DOORS WHICH ARE OPPOSING WHICH DO NOT MEET THE MINIMUM
 REQUIREMENTS FOR ADA. PLEASE SEE STAIRS/VESTIBULE
 AREAS. THE A SHEETS DO NOT SHOW THIS SAME DOOR SWINGS.
 PLEASE SEE CHAPTER 11 AND BUILDING REVIEW COMMENTS FOR
 THIS. THIS IS FOR INFORMATION AT THIS TIME AS
 COORDINATION BETWEEN THE SHEETS IS IMPERATIVE.
  
 25) NOTE: PLEASE SEE THAT THE CIRCUITS AS SHOWN ON THE
 PLANS WHICH ARE NOTED TO THE LIGHTING CONTACTORS ARE
 NOT COMPLETE ON THE LIGHTING CONTACTORS.
 PLEASE SEE THE IDENTIFICATION OF THE CIRCUITS ON THE
 SECOND FLOOR INDICATES TO LIGHTING CONTACTOR #2,
 HOWEVER PLEASE SEE THE CONTACTOR DETAIL ON THAT SHEET
 IS LABELED *CONTACTOR #1*.
 PLEASE SEE LEVELS ANDFIXTURES WHICH MENTIONS LIGHTING
 CONTACTOR #3, YET NO DETAIL FOR A LC #3 WAS SHOWN.
 PLEASE COORDINATE.
 PLEASE SEE NOTES ABOVE WITH RESPECT TO THE CONTACTORS
 AND THE OVER RIDE DEVICES REQUIRES AND THE MAXIMUM
 AMOUNT OF TIMES ON THESE OVER RIDES.
  
 27) NOTE: PLEASE SEE 109.3.6.4.4
 PLANS WHICH ARE SIGNED, DATED AND SEALED BY AN
 ARCHITECT OR ENGINEER SHALL CONTAIN A STATEMENT THAT: *
 TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODES AND THE APPLICABLE FIRE-SAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND CHAPTER (FLORIDA
 STATUTES) 633.
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES FOR ALL TRADES/TITLE SHEETS FOR EACH TRADE
 AND/OR TITLE BLOCKS.
  
 28) NOTE: PLEASE PROVIDE A DETAIL/NOTE FOR ALL
 EMERGENCY AND EXIT LIGHTS WHICH ARE REQUIRED TO BE
 WIRED AHEAD OF ANY SWITCHING DEVICES.
 PLEASE KNOW THIS IS NOT A NEW CODE, HOWEVER SINCE THE
 IMPLEMENTATION OF CHAPTER 13 OF THE FBC. THIS
 JURISDICTION HAS HAD NUMEROUS INSTANCES WHERE THE
 EMERGENCY FIXTURES ARE BEING WIRED ON THE LOAD OF THE
 NEW OCCUPANCY SENSORS, OVER RIDES, TIMERS ETC. THIS
 SHOULD NOT HAVE TO BE MADE ON PLANS, HOWEVER PLEASE
 PROVIDE A DETAIL CLOUDED OFF OF THE CONTACTOR OR ON A
 SEPARATE DETAIL OF SOME KIND.
 FBC 106.1.2, NEC 700.12E.
  
 29) NOTE: PLEASE SEE COLOR CODING FOR CONDUCTORS FOR
 277/480V SHOULD BE BROWN, PURPLE , YELLOW. AS NO
 277/480V IS BEING SHOWN AS PART OF THIS BUILDING, THIS
 COULD BE REDLINED ON PLANS.
  
 30) NOTE: PLEASE SEE COPY OF FS 553.80(2)(B) WITH
 RESPECT TO REPEAT CODE COMPLIANT COMMENTS. THIS IS ONLY
 A NOTICE BEING GIVEN AT THIS TIME.
 ** PLEASE KNOW BASED ON THE NOTES FOR ALL TRADES, ONE
 COMPLETE SET OF PLANS IS BEING RETAINED BY THIS
 OFFICE.
  
  
  
  
 ** PLEASE BE AWARE OF COMMENTS FROM OTHER TRADES WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-02 Cont ID  
Sent By dpalmer Date 2006-10-02 Time 20:32 Rev Time 0.00
Received By dpalmer Date 2006-09-30 Time 19:47 Sent To  
Notes
2006-10-02 00:00:00*******UNSAT ******
  
  
 1)A) NOTE: PLEASE SEE PERMIT APPLICATION
 AND PLANS MENTIONS AND SHOWS "3021",
 HOWEVER THIS PROJETC IS LOCATED ON A
 LEGAL ADDRESS IN OUR SYSTEM OF "3001".
 PLEASE KNOW TITLE BLOCKS SHALL BE
 REVISED UPON CORRECTING OF ADDRESS.
  
 1) NOTE: PLEASE BE SURE ALL OF THE
 FOLLOWING CODES ARE STATED ON PLANS AT A
 MINIMUM.
 2002 NFPA-70, 2002 NFPA-72, 2003
 NFPA-101, NFPA-30A AND 2004 FBC.
 PLEASE KNOW, THERE MAY BE OTHER CODES
 REQUESTED BY OTHER TRADES TO BE STATED
 ON PLANS RELEVANT TO DESIGN.
  
 2) NOTE: PLEASE SEE MISSING LICENSING
 INFORMATION ON TITLE BLOCKS FOR ALL MEP
 PLANS AS REQUIRED PER FAC 61G15-23.002,
 FS 471.023
  
 3) NOTE: PLEASE NEC 511, AND PLEASE
 INDICATE ALLRELEVANT AREAS AND LAYOUT
 ON PLANS.
  
 4) NOTE: PLEASE SEE NFPA-101 7.8.1.3,
 7.9.2.2. PLEASE SUBMIT AND SUPPLY ALL
 MIN PHOTO-METRICS REQUIRED FOR STAIR
 TOWERS UNDER NORMAL AND EMERGENCY POWER.
 PLEASE ALSO INDICATE LIGHTING LEVELS
 (MIN) REQUIRED FOR ALL OTHER AREAS OF
 EGRESS. PLEASE SEE THERE ARE AREAS ON
 PLANS WHICH DO NOT SEEM TO MEET THIS.
 10FT CANDLES UNDER NORMAL AND 1FT CANDLE
 UNDER EM IN STAIRS.
 ALL OTHER AREAS 1FT MIN.
  
 5) NOTE: PLEASE SEE THERE ARE AREAS OF
 EGRESS WHICH IS NOT INDICATING ANY
 EGRESS OR BATTERY BACK UP LTS. PLEASE
 SEE ALL AREAS OF COMMON USAGE
 INCLUDING MAIN ELECTRICAL ROOM, ELEVATOR
 EQUIPMENT RM AND OTHER AREAS ON PLANS
 WHICH WILL REQUIRE BATTERY BACK UP
 FIXTURES OF SOME SORT. PLEASE SEE
 700.12E, 700.16, LS 101 7.8, 7.9, STATE
 ELEVATOR CODE.
 ** PLEASE KNOW, EM ILLUMINATION IS
 REQUIRED OUT OF THE BUILDING TO THE
 PUBLIC RIGHT OF WAY.
 PLEASE ALSO BE SURE TO ADJUST FIXTURE
 SCHEDULE FOR ALL.
  
 6) NOTE: PLEASE LIST AND IDENTIFY ALL
 LIGHTING FIXTURES ON PLANS AND CORRELATE
 WITH THE SUBMITTED SCHEDULE.
 FBC 106.1.2, 106.3.5.1.2 ADMINISTRATIVE
 SECTIONS AS ADOPTED BY THE CITY OF WEST
 PALM BEACH.
  
 7) NOTE: PLEASE PROVIDE ROOM AND AREA
 DESIGNATIONS ON PLANS FOR ALL SPACES.
 PLEASE KNOW, MANY ITEMS FOR REVIEW OF
 CODE COMPLIANCE MAY NOT BE DONE AT THIS
 TIME.
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECT.
  
 8) NOTE: PLEASE COMPLETE ALL CIRCUITING
 ON PLANS AND CORRELATE WITH THE PANEL
 SCHEDULES SUBMITTED.
 408.4, 310.16, 240.4
 FBC 106.1.2, 106.3.5.1.2
  
 9) NOTE: PLEASE SEE 620.23 AND 620.24.
 PLEASE SEE LTS/RECEPTS FOR THE ELEVATOR
 ROOM(S) SHALL CONTAIN DEDICATED CIRCUITS
 AND MAY NOT FEED ANY OTHER AREAS.
  
 10) NOTE: PLEASE SEE SOME LOCATION ON
 PLANS WHERE AN "S" IS SHOWN WHICH IS THE
 SYMBOL FOR "SWITCH" ON LEGEND, HOWEVER
 THEY ARE NOT SHOWN AS CONTROLLING
 ANYTHING?
 PLEASE COMPLETE, OR ADJUST.
 FBC 106.1.2
  
 11) NOTE: PLEASE SEE A BATH RM WITH NOT
 LT FIXTURE BEING SHOWN.
 PLEASE ALSO SEE BATH RMS WITH MULTIPLE
 STALLS SHALL ALSO CONTAIN EM BATTERY
 BACK UP FIXTURES.
 LS 101 7.8,7.9
  
 12) NOTE: PLEASE SEE FIRE REVIEW
 COMMENTS FOR GARAGE AREAS LTS, REQ'D EM
 BACK UP.
 AS PREVIOUSLY NOTED ABOVE FOR ELECTRICAL
 REVIEW ALSO.
 LS101 7.9
  
 13) NOTE: PLEASE SEE 2004 FBC CHAPTER 13
 FOR CONTROLS FOR ALL LIGHTING.
 PLEASE INDICATE AND SHOW THE SYSTEM
 BEING PROPOSED. PLEASE PROVIDE
 SCHEDULING OF SYSTEMS.
 PLEASE PROVIDE OVER RIDES, LOCATIONS,
 AND AREAS FOR SEPARATE CONTROLS
 REQUIRED. PLEASE SEE FBC
 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE SHOW AND INDICATE THE TYPE OF
 OVER RIDE DEVICES,A ND MAX ALLOWED
 TIMES. (NOTE: TIMER TYPE (4HRS MAX),
 OCCUPANT SENSOR TYPE 30MINS MAX).
 ALL AREAS WITH FLR TO CEILING HEIGHT
 PARTITIONS REQUIRE SEPARATE CONTROLS.
 PLEASE PROVIDE PERFORMANCE CALCULATIONS
 AND PLEASE SEE THE MAXIMUM PERMITTED
 "LIGHTING POWER DENSITIES" (LPD) ALLOWED
 FOR AREAS.
 PLEASE SEE SPACES AND USE PERMITTED IN
 TABLES.
 13-415.2, 13-415.2.ABC.1, TABLES
 13-415.2.B.
 ALL LPD'S ARE TO BE SHOWN.
  
 14) NOTE: PLEASE SEE THIS IS NOT BEING
 CONSIDERED A SEPARATE "BUILDING" AND IS
 PART OF THE CURRENT STRUCTURE AS THIS
 NEW STRUCTURE CONTAINS OPENINGS ECT FOR
 EGRESS ETC.
 PLEASE SEE FBC DEFINITIONS.
 PLEASE SEE NEC 230.2, AS THE NEW
 PROPOSED SEPARATE SERVICE NOT BEING FED
 FROM THE EXISTING SERVICE LOCATION
 GROUPED ETC IS NOT PERMITTED AS SHOWN. 230.2,230.72
 ETC.
 IN ORDER TO GRANT THE NEW SERVICE FOR A
 NEW "BUILDING", THIS WOULD REQUIRE AND
 "FIREWALL", 4 HR RATED, COLLAPSIBLE ON
 BOTH SIDES WITH OUT AFFECT THE
 STRUCTURAL INTEGRITY OF EITHER
 STRUCTURE. BY THE PLANS SUBMITTED,THIS
 IS NOT ACHIEVED AT THIS TIME.
  
 15) NOTE: PLEASE SEE MISSING EXT/EM LT
 AS VEST, FOR EGRESS.
 LS 101 7.8, 7.9
 PLEASE SEE PLANS ARE REDLINED FOR MANY
 AREAS IN WHICH SOME COMMENTS ARE
 RELEVANT, HOWEVER ARE IN NO WAY ALL.
  
 16) NOTE: PLEASE SEE 250.50, AS THE NEW
 FOOTER STEEL SHALL BE PART OF THE
 EXISTING GROUNDING ELECTRODE SYSTEM.
 250.50
  
 17) NOTE: PLEASE SEE AREA ON "MEZZ"
 LEVEL WHICH SEEMS TO INDICATE A/C
 EQUIPMENT. PLEASE SEE 210.63 FOR MISSING GFI.210.8B
  
 18) NOTE: PLEASE SUBMIT ALL WIND LOAD
 CALCULATIONS FOR ROOF TOP LT POLES WITH
 EPA FIGURED FOR ALL LT FIXTURES
 PROPOSED.
 THE CALCULATIONS AND SPEC FOR POLES WILL
 BE REVIEWED FOR STRUCTURAL CONNECTIONS,
 WIND LOADS ETC BY THE STRUCTURAL
 REVIEWER.
 THEY MUST MEET FBC 2004 140MPH MIN, 3
 SEC GUST.
  
 19) NOTE: PLEASE SUBMIT THE MANUFACTURE
 SPECS /CUT SHEETS FOR THE TANKLESS WATER
 HEATER. PLEASE BE SURE THEY INDICATE THE
 NRTL LISTING.
 110.3, 90.7.
  
 20) NOTE: PLEASE SEE AS PLUMBING PLANS
 ALSO INDICATE BEING TIED INTO THE
 EXISTING BUILDING, IT SEEMS THE PERMIT
 APPLICATION WOULD BETTER DESCRIBE
 PROJECT AS AN ADDITION.
 THIS WILL BE DECIDED BY DESIGN FOR NOTES
 FROM ALL REVIEWER(S).
  
 ** PLEASE KNOW, AS THERE ARE ITEMS NOT
 IN DESIGN AT THIS TIME REQUIRED FOR
 REVIEW, THERE MAY BE COMMENTS ON FURTHER
 REVIEWS.
  
 ** PLEASE BE AWARE OF COMMENTS FROM
 OTHER TRADES WHICH WILL AFFECT
 ELECTRICAL PLANS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
2006-10-01 00:00:00*** REVIEW IN PROGRESS, PLANS TO GO
 INTO "F" STATUS, NOTES OT FOLLOW.
2006-09-29 00:00:00IN ELEC FOR REVIEW,

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2007-05-18 Cont ID  
Sent By rchokshi Date 2007-05-18 Time 11:12 Rev Time 0.00
Received By rchokshi Date 2007-05-18 Time 11:10 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-02-02 Cont ID  
Sent By rchokshi Date 2007-02-02 Time 11:25 Rev Time 0.00
Received By rchokshi Date 2007-02-02 Time 11:07 Sent To  
Notes
2007-02-02 11:25:34ACCORDING TO YOUR PERMIT DESCRIPTION YOU PROVIDED US,
 YOU ARE BUILDING A NEW BUILDING FOR PARTS,OFFICES,ETC
 ON 1ST FLOOR AND CAR PARKING GARAGE ON 2ND FLOOR.
 THEREFORE, PLEASEPROVIDE THE FOLLOWING INFO.
  
 2. PLEASE SHOW STANDARDS NOTES OF CITY OF WPB ON
 DRAWINGSFOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY,
 PARKING, HANDICAP PARKING, PAINTPER CITY CODES ETC.,,
 MUST MEET PER ADA,,ETC.,
 3. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 4. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FL BLDG CODE, PLEASE SHOW
 ON THE DRAWINGS.
 5. PLEASE PROVIDE A COPY OF SFWMD PERMIT,AND GEO TECH
 REPORT.
 6.PLEASE SHOW STORM WATER CALCULATIONS, WHAT CRITERIA
 YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER ENTIRE SITE
 OR2.5"CRITERIA, ?PERVIOUS AREA, LIKE GREEN,
 LAKES, ETC,IMPERVIOUS AREA CAL.,
 7. WHAT IS THE SITE AREA, YOU ARE DEVELOPING FOR THIS
 PROJECT ONLY ? SO, WE CAN CHECK PERVIOUS, IMPERVIOUS
 CAL. PLEASE SHOW PRE & POST CHANGE IN
 PERVIOUS/IMPERVIOUS AREA.
 8. HOW YOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE BEST PIPE TO
 CONNECT WITH THE STORM WATERFROM ALL OTHER STORM
 WATER PIPES. PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC DID YOU USE EXFILTRATION TRENCH ?
 9. POLLUTION PREVENTION DETAILS,CLOTHES USED FOR SILT
 ETC., PLANS SHOWING SILT FENCE AROUND THE SITE
 10. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED
 11. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2006-10-23 Cont ID  
Sent By rchokshi Date 2006-10-23 Time 13:48 Rev Time 0.00
Received By rchokshi Date 2006-10-23 Time 13:37 Sent To  
Notes
2006-10-23 13:48:30FAILED FOR FOR FOLLOWING REASONS:
  
 NEED CIVIL DRAWINGS, WHAT WE NEED IN CIVIL DWGS ARE AS
 FOLLOWS
  
 1. POLLUTION PREVENTION PLANS, & DETAILS
 2. STORM WATER CAL.,PERVIOUS,IMPERVIOUS AREA
 CAL.,RUNOFF CAL.,GEOTECHNICAL REPORTS,SFWMD PERMIT
 3.UTILITY REVIEW FROM 45TH STREET (MANNY G.)
 4. SIDEWALK,DRIVEWAY ,APPROACH, PARKING, ADA
 REQUIREMENTS, DUMPSTER ENCLOSURE, ETC., PER CITY OF WPB
 STANDARDS
 5.SITE ELE.,CENTER LINE ROAD ELE, SIDEWALK ELE, FIRST
 FLOOR ELE, ETC., FOR FLOOD CONTROL
 6. PLEASE SHOW STORM WATER INLET,OUT FALLS ETC.,
  
 PLEASE RESPOND EACH ITEM TO EXPEDITE THE PERMIT
 PROCESS
  
 RASIK CHOKSHI 805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-09-13 Cont ID  
Sent By mawillia Date 2007-09-13 Time 17:59 Rev Time 0.00
Received By mawillia Date 2007-09-13 Time 16:51 Sent To  
Notes
2007-09-13 17:04:33**APPROVED*****
  
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN SATISFIED;PLAN SHEETS A-105, E- 100, 101, 102,
 103, AND 200 WERE STAMPED, INITIALED, AND DATED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-05-17 Cont ID  
Sent By mawillia Date 2007-05-17 Time 15:39 Rev Time 0.00
Received By mawillia Date 2007-05-17 Time 14:22 Sent To  
Notes
2007-05-17 15:37:57*****UNSAT*****
  
  
 PREVIOUS COMMENTS WHICH STILL NEED TO BE ADDRESSED:
  
 03.ON PAGE E-103 ONLY TWO ILLUMINATED EXIT SIGNS
 EXIST.EXIT SIGNAGE IS USED TO DIRECT PERSONS TO EXITS
 EVEN WHEN THEY ARE NOT CLEARY OBVIOUS.DISPLAY NEW
 EXIT SIGN PLACEMENT SUCH THAT NO POINT IN AN EXIT
 ACCESS CORRIDOR IS IN EXCESS OF THE RATED VIEWING
 DISTANCE OR 100 FEET, WHICHEVER IS LESS, FROM THE
 NEAREST SIGN.
  
 04.NO EMERGENCY SIGN LIGHTING DECLARED ON PAGE E-103.
 PLEASE INDICATE LOCATION OF THESE DEVICES
  
 09.BUILDING ADDRESS WITH A MININIMUM OF 6" IN HEIGHT
 AND 1" IN WIDTH REQUIRED.IN ADDITION TO THE HEIGHT
 REQUIREMENT AS SHOWN ON SHEET A-5, THE WIDTH
 REQUIREMENT SHALL BE ADHERED ALSO.
  
 15.CONSTRUCTION, DEMOLITION, AND RENOVATION
 OPERATIONS SHALL COMPLY WITH NFPA 241.INDICATE ON
 APPROPIATE PLAN SHEET
  
 16.DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
 INDICATE ON THE APPROPIATE PLAN SHEET
  
 17.A KNOX-BOX WILL BE REQUIRED FOR THE BUILDING.
 INDICATE ON THE APPROPIATE PLAN SHEET THAT THE KNOX BOX
 WILL BE INSTALLED IN AN ACCESSIBLE LOCATION AND/OR
 WHERE DIRECTED BY THE FIRE MARSHAL.
  
 NEW COMMENT
  
 AA.IT IS NOTED AS PER LILU URSA THAT THE NUMERICAL
 ADDRESS IS 3023;HOWEVER3021 IS LISTED IN THE TITLE
 BLOCK OF SOME OF THE SUBMITTED PLAN SHEETS.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH COMMENT
 WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-02-23 Cont ID  
Sent By mawillia Date 2007-02-23 Time 10:02 Rev Time 0.00
Received By mawillia Date 2007-02-23 Time 10:02 Sent To B
Notes
2007-02-23 10:18:31*****UNSAT*****
  
  
 THE FOLLOWING COMMENTS TAKEN FROM PREVIOUS FIRE PLAN
 REVIEW OF 10/25/2006 STILL NEED TO BE ADDRESSED:
  
  
 01.INDICATE THE TYPES OF AUTOMOTIVE REPAIRS THAT ARE
 PLANNED FOR THE BUILDING.PLEASE BE SPECIFIC
  
 02.SPRINKLER PLANS WERE SUBMITTED, HOWEVER, SEE
 ELECTRICAL PLAN REVIEW NOTE #22 IN REFERENCE TO THE
 SIGNING AND SEALING OF DOCUMENTS.
  
 03.ON PAGE E-103 ONLY TWO ILLUMINATED EXIT SIGNS
 EXIST.EXIT SIGNAGE IS USED TO DIRECT PERSONS TO EXITS
 EVEN WHEN THEY ARE NOT CLEARY OBVIOUS. ADD EXTRA EXIT
 SIGN LIGHTIN PARKING AREA DIRECTING PERSONS TO THE
 NEAREST EXIT.
  
 04.NO EMERGENCY SIGN LIGHTING DECLARED ON PAGE E-103.
 PLEASE INDICATE LOCATION OF THESE DEVICES
  
 06.PLEASE PROVIDE PRODUCT APPROVALS FOR THE CO
 DETECTORS PLANNED FOR USE.
  
 09.BUILDING ADDRESS WITH A MININIMUM OF 6" IN HEIGHT
 AND 1" IN WIDTH REQUIRED.PLEASE DISPLAY/SHOW ON THE
 APPROPIATE EXTERIOR ELEVATION
  
 12.NO PORTABLE FIRE EXTINGUISHERS PROVIDED.SHOW THE
 LOCATION OF THE FIRE EXTINGUISHERS WHICH SATISFY THE
 75' TRAVEL DISTANCE
  
 13.PLEASE PROVIDE PRESCRIPTIVE STRENGHT REQUIREMENTS
 FOR ALL HANDRAILS, GUARDRAILS, AND CABLE RAIL SYSTEMS.
 INDICATE THE LOCATION OF THIS INFORMATION ON THE
 SPECIFIC STRUCTURAL SHEET(S)
  
 15.CONSTRUCTION, DEMOLITION, AND RENOVATION
 OPERATIONS SHALL COMPLY WITH NFPA 241.INDICATE ON
 APPROPIATE PLAN SHEET
  
 16.DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
 INDICATE ON THE APPROPIATE PLAN SHEET
  
 17.A KNOX-BOX WILL BE REQUIRED FOR THE BUILDING.
 INDICATE ITS LOCATION ON THE APPROPIATE EXTERIOR
 ELEVATION
  
 19.PLEASE DECLARE DISTANCE FROM EXHAUST TERMINATION
 POINTS TO ANY BUILDING OPENINGS.SHOW THE DISTANCE OF
 EXHAUST FUMES BEING EMITTED TO THE NEAREST WINDOWS,
 DOORS, AIR INTAKES, OR SIMILAR OPENINGS
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH COMMENT
 WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-25 Cont ID  
Sent By mcarsill Date 2006-10-25 Time 14:49 Rev Time 0.00
Received By mcarsill Date 2006-10-25 Time 14:22 Sent To  
Notes
2006-10-25 14:48:511. PLEASE INDICATE THE TYPES OF AUTOMOTIVE REPAIRS THAT
 ARE PLANNED FOR THE BUILDING.
 2. PLANS SEEM TO INDICATE THAT THE BUILDING WILL BE
 FIRE SPRINKLER PROTECTED HOWEVER NO FIRE SPRINKLER
 PLANS WERE NOTED.
 3. ON PAGE E-103 ONLY TWO ILLUMINATED EXIT SIGNS EXIST.
 EXIT SIGNAGE IS USED TO DIRECT PERSONS TO EXITS EVEN
 WHEN THEY ARE NOT CLEARLY OBVIOUS.
 4. NO EMERGENCY LIGHTING DECLARED ON PAGE E-103. 5. NO
 EXIT SIGN MARKINGS SHOWN ON PAGE E-200.
 6. PLEASE PROVIDE PRODUCT APPROVALS FOR THE CO
 DETECTORS PLANNED FOR USE. DO THEY COME FACTORY SET OR
 WILL CALIBRATION GAS BE NEEDED TO SET THESE POINTS. 7.
 NO EMERGENCY LIGHTS DISPLAYED FOR MEZZANINE ON PAGE
 E-102.
 8. PLEASE PROVIDE A LIST OF CHEMICALS AND THEIR AMOUNTS
 PLANNED FOR THE BUILDING.
 9. BUILDIND ADDRESS REQUIRED . A MINIMUM OF AT LEAST 6"
 IN HEIGHT AND 1" IN WIDTH.
 10. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS IN NON AUTOMOTIVE WORK AREAS. 11.
 SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE SPRINKLER
 AND FIRE ALARM SYSTEM.
 12. NO PORTABLE FIRE EXTINGUISHERS PROVIDED.
 13. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR ALL HANDRAILS, GUARDRAILS, AND CABLE RAIL SYSTEMS.
 14. PLEASE DECLARE OCCUPANCY TYPE AND OCCUPANT LOADS
 FOR THE BUILDING.
 15. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
 16. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. 17. A
 KNOX-BOX WILL BE REQUIRED FOR THE BUILDING. 18. IS THE
 BUILDING CONSIDERED OPEN OR CLOSED FOR DESIGN
 PURPOSES.
 19. PLEASE DECLARE DISTANCE FROM EXHAUST TERMINATION
 POINTS TO ANY BUILDING OPENINGS.
 20. PLEASE INDICATE HOW FLAMMABLE OR COMBUSTIBE LIQUIDS
 WILL BE STORED, HANDLED, AND DISPOSED OF WITHIN THE
 BUILDING.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION OFFICER 804-4709
  
 MICHAEL A. WILLIAMS, FIRE PREVENTION CAPTAIN 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-09-08 Cont ID  
Sent By adarroug Date 2008-09-08 Time 14:57 Rev Time 0.00
Received By adarroug Date 2008-09-08 Time 14:57 Sent To B
Notes
2008-09-08 14:58:28TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-01-10 Cont ID  
Sent By spalmer Date 2008-01-10 Time 08:45 Rev Time 0.00
Received By spalmer Date 2008-01-10 Time 08:45 Sent To B
Notes
2008-01-10 08:45:28TO SAMANTHA HILLS DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-12-28 Cont ID  
Sent By spalmer Date 2007-12-28 Time 15:16 Rev Time 0.00
Received By spalmer Date 2007-12-28 Time 15:16 Sent To E
Notes
2007-12-28 15:16:43TO DEWEY PALMERS DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-07-16 Cont ID  
Sent By adarroug Date 2007-07-16 Time 11:43 Rev Time 0.00
Received By adarroug Date 2007-07-16 Time 11:43 Sent To  
Notes
2007-07-27 11:39:22TO "COMM" BD#53
2007-07-16 11:43:35WAITING FOR " COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-17 Cont ID  
Sent By adarroug Date 2007-04-17 Time 15:25 Rev Time 0.00
Received By adarroug Date 2007-04-17 Time 15:25 Sent To  
Notes
2007-04-17 15:28:47TO "COMM" BD#48

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-12 Cont ID  
Sent By adarroug Date 2007-01-12 Time 09:28 Rev Time 0.00
Received By adarroug Date 2007-01-12 Time 09:28 Sent To  
Notes
2007-01-29 08:53:44TO "COMM" BD#48
2007-01-12 09:28:31WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-25 Cont ID  
Sent By mcarsill Date 2006-10-25 Time 14:58 Rev Time 0.00
Received By mcarsill Date 2006-09-14 Time 15:55 Sent To  
Notes
2006-09-25 00:00:00TO "COMM" BD#45
2006-09-14 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-09-02 Cont ID  
Sent By rregueir Date 2007-09-02 Time 09:59 Rev Time 0.00
Received By rregueir Date 2007-09-02 Time 09:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-05-09 Cont ID  
Sent By rregueir Date 2007-05-09 Time 10:54 Rev Time 0.00
Received By rregueir Date 2007-05-09 Time 09:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-02-14 Cont ID  
Sent By rregueir Date 2007-02-14 Time 15:37 Rev Time 0.00
Received By rregueir Date 2007-02-14 Time 15:37 Sent To  
Notes
2007-02-14 15:42:53COMMENTS LIST BELOW IN RELATION TO PREVIOUS PLAN REVIEW
 COMMENTS AS WELL AS RESPONSES.
  
 1. OK
  
 2. AIR FROM SERVICE GARAGE MAY NOT BE USED FOR
 VENTILLATION OF MEN'S LOCKER ROOM PER FBC,M 403.2.1(3).
 VENTILLATION SHOULD COME DIRECTLY FROM THE OUTDOORS.
  
 3. FBC,M 804.3.5 APPLIES TO CHIMNEYS AND VENTS FOR
 SOLID FUEL BURNING APPLIANCES AND DOS NOT APPLY IN THIS
 CIRCUMSTANCE. A MINIMUM OF 10' BETWEEN GARAGE EXHAUST
 FANS AND INTAKE OPENINGS IS REQUIRED PER FBC,M
 401.5.1.
  
 4. OK
  
 5. OK
  
 6. OK
  
 7. SEE COMMENT #3
  
  
 PLAN REVIEW BY:
 RONALD J REGUEIRO
 561-805-6734
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-18 Cont ID  
Sent By pkrauss Date 2006-10-18 Time 07:53 Rev Time 0.00
Received By pkrauss Date 2006-10-18 Time 06:47 Sent To  
Notes
2006-10-18 08:32:40DENIED:
 1.PLEASE NOTE PERMIT APPLICATION INDICATES 2 STORY
 PARKING GARAGE WHEREAS THE THE PLANS APPEAR TO HAVE THE
 REPAIR OR SERVICE GARAGE ON THE FIRST FLOOR WITH
 PARKING ABOVE.
  
 2.PLAN SHEET M-100,THE DOOR INTO THE MEN'S LOCKER
 ROOM (A111) IS INDICATED AS "LOUVERED BOTH SIDES".
 PLEASE CLARIFY IS THIS AIR MAKE-UP?PLEASE SHOW
 COMPLIANCE WITH THE FOLLOWING:
  
 3. PER 2004 FMC 401.5.1 OUTSIDE AIR INTAKE OPENINGS
 SHALL BE LOCATED A MINIMUM OF 10FT FROM ANY HAZARDOUS
 EXHAUST.AIR FROM THE GARAGE SHALL NOT BE
 RECIRCULATED.
  
 4. 2004 FMC 404.3 CONNECTING WAITING ROOMS, OFFICES AND
 SIMILAR USES THAT ARE ACCESSORY TO THE PUBLIC GARAGE
 SHALL BE MAINTAINED AT A POSITIVE PRESSURE.
  
 5. 2004 FMC 502.14,THE EXHAUST FROMA REPAIR GARAGE
 SHALL RUN CONTINUOUSLY.
  
 6.PLEASE PROVIDE FRESH AIR CALCULATIONS FOR ALL AREAS
 IN ACCORDANCE WITH 2004 FMC TABLE 403.3.
  
 7.PLAN SHEET A-109 THE EXHAUST APPEARS TO TO BE
 WITHIN 10 FT OF THE FRESH AIR INTAKE LOUVERS, AIR
 REMOVED BY BY THE EXHAUST SHALL BE DISCHARGED OUTDOORS
 AT A POINT WHERE IT CAN NOT BE READILY DRAWN BACK INTO
 THE BUILDING.
  
 8.PLEASE PROVIDE CLEARANCES FROM OTHER BUILDINGS ON
 THE SAME LOT, FRESH AIR INTAKES, DOORS, WINDOWS, ETC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-08-28 Cont ID  
Sent By kstevens Date 2007-08-28 Time 10:07 Rev Time 0.00
Received By kstevens Date 2007-08-28 Time 10:07 Sent To  
Notes
2007-08-28 10:17:41STAMPED 3RD SET OF PLANS COPIED FROM ONE SET AND
 RESEALED & RESIGNED BY THE ENGINEER.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-06-01 Cont ID  
Sent By kstevens Date 2007-06-01 Time 10:38 Rev Time 0.00
Received By kstevens Date 2007-06-01 Time 10:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-02-12 Cont ID  
Sent By kstevens Date 2007-02-12 Time 17:56 Rev Time 0.00
Received By kstevens Date 2007-02-12 Time 17:56 Sent To  
Notes
2007-02-12 14:39:15DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS. THE IMPRESSION SEAL SHALL
 IMPRESS INFORMATION REQUIRED BY FAC 61G1-16.002(1) & FS
 481.2055 ON EACH SHEET.
 *****RESPONSE NOTED, BUT ALL REQUIRED INFORMATION SHALL
 BE IMPRESSED ON EACH SHEET, AND THE INFORMATION SHALL
 BE LEGLBLE. NOT ALL INFORMATION IS LEGIBLE.
  
 2. OK
  
 3. SHT A-104 INDICATE THE SQUARE FOOTAGE AND OCCUPANCY
 OF THE SERVICE AREA, OIL STORAGE ARE, AND BUSINESS
 AREAS. SUBMIT CALCULATIONS FOR MINIMUM FACILITIES FOR
 EACH OCCUPANCY PER TABLES 1004.1.2 & 403.1. SEPARATE
 FACILITIES ARE REQUIRED FOR EACH SEX PER SECTION 403.2.
 ONLY MEN'S FACILITIES ARE SHOWN.
 ****RESPONSE NOTED, BUT THE INFORMATION IS NOT LOCATED
 ON SHT A-104. ALSO RESPONSE "ALSO PLEASE SEE RESPONSES
 TO BUILDING PLAN REVIEW" IS NOT TOO CLEAR AS BUILDING
 HAS 51 COMMENTS. PLEASE INDICATE WHICH COMMENT WILL
 RESPOND TO MY COMMENT. THIS WILL HELP EXPEDITE THE PLAN
 REVIEW PROCESS. IT APPEARS THAT THERE ARE SOME AREAS
 THAT ARE NOT STORAGE. THE PARTS WARRANTY AREA, AND THE
 LOUNGE/TRAINING AREA.--SECTION 403.3 STATES THAT
 THE REQUIRED WATER CLOSETS, LAVS, SHALL BE DISTRIBUTED
 EQUALLY BETWEEN THE SEXES.THE OCCUPANT LOAD SHALL BE
 COMPOSED OF 50 PERCENT OF EACH SEX, UNLESS STATISTICAL
 DATA APPROVED BY THE CODE OFFICIAL INDICATE A DIFFERENT
 DISTRIBUTION OF THE SEXES.
  
 4. SHT A-200 SHOW COMPLIANCE FOR THE FOLLOWING:FOR
 W/C'S
 A. OK
 B. 11-4.16.5 FLUSH CONTROLS
 ****RESPONSE NOTED, BUT DETAILS 18 & 31 SHOW THE FLUSH
 CONTROL ON THE WALL SIDE.
 FOR TOILET STALL
 A. OK
 FOR THE URINAL
 A. OK
 FOR LAVS
 A. 11-4.19.2 CLEARANCES
 ****NOT ADDRESSED
 B. 11-4.19.5 FAUCETS
 ****NOT ADDRESSED
  
 5. SHT A-201 SHOW COMPLIANCE FOR THE FOLLOWING:FOR
 KIT. SINK
 A. 11-4.24.5 CLEAR FLOOR SINK (FORWARD APPROACH
 REQUIRED)
 ****NOT ADDRESSED
 B. OK
  
 5. OK
  
 6. SHT P-100 BECAUSE OF THE AUTOMOBILE SERVICE WORK AN
 OIL/GREASE INTERCEPTOR MAY BE REQUIRED. PLEASE CONTACT
 LYNN MASSON, ENVIRONMENTAL COMPLIANCE MANAGER FOR A
 DETERMINATION. CONTACT HER AT (561) 822-2271, OR BY FAX
 (561) 822-2279, OR BY E-MAIL [email protected]. WASTE
 ORD. 3434.
 ****WAITING FOR WORD FROM ENVIRONMENTAL COMPLIANCE AS
 THEY WILL HAVE TO ISSUE THE RESULTS OF THE REQUIREMENT.
 THERE ARE STILL SERVICE SINKS AND IT WILL BE THEIR
 DETERMINATION.
  
 7. SHT P-101 SUBMIT MANUF. SPECIFICATION SHEETS FOR THE
 INSTANT-FLOW WATER HEATER FOR THE KITCHEN SINK. SPECS.
 SHALL SHOW A LISTING FOR THE W/H. SECTIONS 106.1.2 &
 303.4.
 ****RESPONSE NOTED, BUT MANUF. SPECIFICATION SHEETS
 WERE NOT LOCATED.
  
 8. SHT P-200 SHOW THE CLEANOUTS AS REQUIRED IN SECTION
 1101.8 FOR THE STORM RISERS.
 ****RESPONSE NOTED, BUT THE CLEANOUTS FOR SECTIONS
 708.3.1, 708.3.2, 708.3.3, & 708.3.4 WERE NOT SHOWN ON
 THE FLOOR PLAN, NOR ON THE RISER DIAGRAMS.
  
 9.OK
 10. OK
  
 11. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SUPPLY TO
 THE BUILDING. SECTION 608.13.2.
 ****RESPONSE NOTED, BUT AN RPZV BACKFLOW IS REQUIRED ON
 EACH BUILDING. PLEASE INDICATE A BACKFLOW PRIOR TO THE
 WATER SERVICE ENTERING THE BUILDING TO SHOW
 COMPLIANCE.
  
 12. SHT P-200 WATER RISER DIAGRAM. FULL OPEN VALVES
 REQUIRED ON EACH WATER DOWN-FEED PIPE. SECTION
 606.1(4).
 ****RESPONSE NOTED, BUT THE VALVES ARE NOT SHOWN AT
 FIXTURES P1, P2, P3, P4, P4, P6 & P9.
  
 13. OK
 14. OK
 15. OK
 16. OK
  
 ************NEW COMMENT*************
  
 1B. SHTS A-200 & A-201 ARE OUT OF SEQUENCE IN ONE SET
 OF PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-10-14 Cont ID  
Sent By kstevens Date 2006-10-14 Time 15:51 Rev Time 0.00
Received By kstevens Date 2006-10-14 Time 15:51 Sent To  
Notes
2006-10-14 16:51:48DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS. THE IMPRESSION SEAL SHALL
 IMPRESS INFORMATION REQUIRED BY FAC 61G1-16.002(1) & FS
 481.2055 ON EACH SHEET.
  
 2. ALL PME SHEETS SHALL SHOW THE CERTIFICATE OF
 AUTHORIZATION NUMBER ON EACH SHEET. SOME SHEETS HAVE
 OTHERS DO NOT. FAC 61G15-23.002(2) & FS 471.025.
  
 3. SHT A-104 INDICATE THE SQUARE FOOTAGE AND OCCUPANCY
 OF THE SERVICE AREA, OIL STORAGE ARE, AND BUSINESS
 AREAS. SUBMIT CALCULATIONS FOR MINIMUM FACILITIES FOR
 EACH OCCUPANCY PER TABLES 1004.1.2 & 403.1. SEPARATE
 FACILITIES ARE REQUIRED FOR EACH SEX PER SECTION 403.2.
 ONLY MEN'S FACILITIES ARE SHOWN.
  
 4. SHT A-200 SHOW COMPLIANCE FOR THE FOLLOWING:FOR
 W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.5 FLUSH CONTROLS
 FOR TOILET STALL
 A. 11-4.17.3 EXCEPTION(1) - 60" REQUIRED FROM WALL
 NEXT TO THE W/C TO THE SIDE OF THE LAV. SEE FIG.
 11-30(E)
 FOR URINAL
 A. 11-4.18.4 FLUSH CONTROLS
 FOR LAVS
 A. 11-4.19.2 CLEARANCES
 B. 11-4.19.5 FAUCETS
  
 5. SHT A-201 SHOW COMPLIANCE FOR THE FOLLOWING:FOR
 KIT. SINK
 A. 11-4.24.5 CLEAR FLOOR SINK (FORWARD APPROACH
 REQUIRED)
 B. 11-4.24.7 FAUCETS (VIEW 1 SHOWS A DIFFERENT FAUCET
 TYPE FROM THE COUNTER DETAIL PLEASE CORRELATE TO
 REQUIRED TYPE FAUCET).
  
 5. SHT P-100 INDICATES EXISTING SANITARY BLDG DRAIN.
 THIS WAS PROBABLY INSTALLED AS A SEWER FROM THE HUMMER
 BLDG. ORIGINALLY. PLEASE INDICATE THE MATERIAL THAT WAS
 INSTALLED, AS THE MATERIAL WILL BE REQUIRED TO COMPLY
 WITH TABLES 702.1 & 702.2. INDICATE THE DRAINAGE
 FIXTURE UNITS FROM THE HUMMER BUILDING. A COPY OF THE
 HUMMER BUILDING PLUMBING RISER DIAGRAM SHALL BE
 SUBMITTED TO VERIFY DFU'S IN ORDER TO PROPERLY SIZE THE
 BUILDING DRAIN FOR THE SERVICE/PARKING BUILDING.
 INDICATE IF THE CLEANOUT REQUIRED BY SECTION 708.3.5
 NEAR THE JUNCTION OF THE BLDG DRAIN AND THE BLDG SEWER
 OF THE HUMMER BLDG HAS BEEN DELETED. SECTION 106.1.1 &
 TABLE 710.1(1).
  
 6. SHT P-100 BECAUSE OF THE AUTOMOBILE SERVICE WORK AN
 OIL/GREASE INTERCEPTOR MAY BE REQUIRED. PLEASE CONTACT
 LYNN MASSON, ENVIRONMENTAL COMPLIANCE MANAGER FOR A
 DETERMINATION. CONTACT HER AT (561) 822-2271, OR BY FAX
 (561) 822-2279, OR BY E-MAIL [email protected]. WASTE
 ORD. 3434.
  
 7. SHT P-101 SUBMIT MANUF. SPECIFICATION SHEETS FOR THE
 INSTANT-FLOW WATER HEATER FOR THE KITCHEN SINK. SPECS.
 SHALL SHOW A LISTING FOR THE W/H. SECTIONS 106.1.2 &
 303.4
  
 8. SHT P-200 SHOW THE CLEANOUTS AS REQUIRED IN SECTION
 1101.8 FOR THE STORM RISERS.
  
 9. SHT P-200 THE SQUARE FOOTAGE SHOWN ON RISERS RD1,
 RD3, & RD4 DOES NOT REFLECT THE SQUARE FOOTAGE SHOWN ON
 THE ROOF PLUMBING PLAN. PLEASE CORRELATE RISERS AND
 ROOF PLAN. SECTION 106.1.1 & TABLE 1106.3.
  
 10. SHT P-200 EWH PIPING SCHEMATIC. SHOW COMPLIANCE
 WITH SECTION 607.3.2 THERMAL EXPANSION CONTROL.
  
 11. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SUPPLY TO
 THE BUILDING. SECTION 608.13.2.
  
 12. SHT P-200 WATER RISER DIAGRAM. FULL OPEN VALVES
 REQUIRED ON EACH WATER DOWN-FEED PIPE. SECTION
 606.1(4).
  
 13. SHT P-200 SANT. RISER DIAGRAM INDICATE IF CLEANOUT
 REQUIRED BY SECTION 708.3.5 FROM HUMMER BLDG HAS BEEN
 DELETED. SHOW THE CLEANOUT REQUIRED BY SECTION 708.3.5
 NEAR THE JUNCTION OF THE BLDG DRAIN AND THE BUILDING
 SEWER FOR THE SERVICE/PARKING BUILDING. SHOW THE DFU'S
 AS THEY ACCUMULATE THE THE SYSTEM, INCLUDING THE DFU'S
 FROM THE HUMMER BUILDING. TABLE 710.1(1) & SECTION
 106.1.1.
  
 14. SHT P-200 PLUMBING SPECIFICATIONS #5(A) INDICATES
 CPVC AS AN ACCEPTABLE SUBSTATUTE FOR THE SANITARY
 WASTE. THIS IS NOT APPROVED PER TABLES 702.1 & 702.2.
  
 15. SHT P-200 PLUMBING SPECIFICATIONS #5(F) AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM REFERENCE.
 SECTION 604.9.
  
 16. SHT P-200 SANT., STORM, AND WATER RISER DIAGRAM
 REFER TO THE CIVIL PLANS. THE CIVIL PLANS WERE NOT
 SUBMITTED. PLEASE SUBMIT A COPY OF THE CIVIL PLANS.
 SECTION 106.1.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 4 Status P Date 2007-08-08 Cont ID  
Sent By kdfreema Date 2007-08-08 Time 16:58 Rev Time 0.00
Received By kdfreema Date 2007-08-08 Time 16:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2007-05-08 Cont ID  
Sent By kdfreema Date 2007-05-08 Time 09:49 Rev Time 0.00
Received By kdfreema Date 2007-05-08 Time 09:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2007-02-05 Cont ID  
Sent By kdfreema Date 2007-02-05 Time 16:17 Rev Time 0.00
Received By kdfreema Date 2007-02-05 Time 16:17 Sent To I
Notes
2007-02-05 16:18:121) RESPONSE NOTED, HOWEVER, THE ORIGINAL COMMENT
 STANDS. THE LANDSCAPE PLAN IS REQUIRED TO BE SUBMITTED
 AT THE TIME OF BUILDING PERMIT.
  
 2) RESPONSE NOTED, HOWEVER, SITE PLAN APPROVAL IS
 CONTINGENT UPON ZONING COMPLIANCE REVIEW AT THE TIME OF
 PERMITTING.
  
 3) PLEASE CLARIFY THE 9 SPACES SOUTH OF THE VW
 SHOWROOM. THEY?RE DESIGNATED AS CUSTOMER PARKING;
 HOWEVER, THEY ALSO APPEAR TO BE COUNTED AS DISPLAY
 SPACE.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER AT 561-822-1435
 WITH ANY QUESTIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-10-04 Cont ID  
Sent By kdfreema Date 2006-10-04 Time 16:57 Rev Time 0.00
Received By kdfreema Date 2006-10-04 Time 16:57 Sent To  
Notes
2006-10-04 00:00:00** FAILED **
  
 THE LANDSCAPE PLAN IS REQUIRED TO BE
 SUBMITTED AT THE TIME OF BUILDING
 PERMIT.
  
 AS SHOWN, PHASE I PARKING TABLE DOES NOT
 MATCH THE PARKING SHOWN ON THE SITE
 PLAN. THE TABLE STATES
 THAT 75 PARKING SPACES ARE PROVIDED
 WHILE ONLY 63 PARKING SPACES HAVE BEEN
 DESIGNATED TO COUNT TOWARD THE REQUIRED
 PARKING. THE TOTAL PARKING REQUIREMENT
 IS 69 SPACES, LEAVING THE SITE 6
 PARKING SPACES SHORT OVERALL.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER,
 AT (561) 822-1435 OR [email protected]
 WITH ANY QUESTIONS YOU MAY HAVE.


Account Summary | Usage Policy | Privacy Policy