Plan Review Details - Permit 06090369
Plan Review Stops For Permit 06090369
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-10-18 Cont ID  
Sent By alange Date 2006-10-18 Time 09:46 Rev Time 0.00
Received By alange Date 2006-10-18 Time 09:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-06-04 Cont ID  
Sent By btrobaug Date 2007-05-02 Time 16:19 Rev Time 0.33
Received By btrobaug Date 2007-05-02 Time 16:19 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-11-27 Cont ID  
Sent By btrobaug Date 2006-11-27 Time 16:40 Rev Time 0.33
Received By btrobaug Date 2006-11-17 Time 12:20 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-21 Cont ID  
Sent By btrobaug Date 2006-09-21 Time 16:02 Rev Time 0.33
Received By btrobaug Date 2006-09-21 Time 15:41 Sent To P
Notes
2006-09-21 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE MANUFACTURERS SPECIFICATIONS
 ALSO RECOMMENDATION REGARDING
 CLEARANCES, FOR THE GENERATOR.
  
 2} PROVIDE SPECIFICATIONS FOR THE
 TRANSFER SWITCH.
  
 3} AN ELEVATION CERTIFICATE IS REQUIRED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-11-27 Cont ID  
Sent By mperson Date 2006-11-27 Time 15:58 Rev Time 0.45
Received By mperson Date 2006-11-27 Time 15:58 Sent To M
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-09-27 Cont ID  
Sent By mperson Date 2006-09-27 Time 09:48 Rev Time 0.33
Received By mperson Date 2006-09-27 Time 09:48 Sent To B
Notes
2006-09-27 00:00:00******DENIED******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED ON
 THE ISOMETRIC DRAWING FOR GAS PLAN
 REVIEW:
  
 1. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: THIS INCLUDES THE EXISTING GAS
 SYSTEM PLEASE SEE THE ATTACHED PERMIT
 INFORMATION INDICATING GAS AT SAID
 ADDRESS.
  
 2. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: REFERENCE NOTE ON COMMENT 1
  
 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT AND INSTALLATION INSTRUCTIONS
 TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND THE FBC-2004 FUEL GAS
 CODE SEC 402.2
 NOTE: NEED SHEETS ON REGULATORS AND
 GENERATOR.
  
 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-04-23 Cont ID  
Sent By adarroug Date 2007-04-23 Time 15:01 Rev Time 0.00
Received By adarroug Date 2007-04-23 Time 15:01 Sent To E
Notes
2007-04-23 15:01:53TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-27 Cont ID  
Sent By spalmer Date 2007-03-27 Time 17:44 Rev Time 0.00
Received By spalmer Date 2007-03-27 Time 17:44 Sent To M
Notes
2007-03-27 17:44:21TO TOM GORDON

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-03-25 Cont ID  
Sent By adarroug Date 2007-03-25 Time 12:29 Rev Time 0.00
Received By adarroug Date 2007-03-25 Time 12:29 Sent To Z
Notes
2007-03-25 12:30:03TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-16 Cont ID  
Sent By adarroug Date 2006-11-16 Time 15:06 Rev Time 0.00
Received By adarroug Date 2006-11-16 Time 15:06 Sent To E
Notes
2006-11-16 15:06:41TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-20 Cont ID  
Sent By adarroug Date 2006-09-20 Time 14:56 Rev Time 0.00
Received By adarroug Date 2006-09-20 Time 14:56 Sent To E
Notes
2006-09-20 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-18 Cont ID  
Sent By alange Date 2006-10-18 Time 09:46 Rev Time 0.00
Received By alange Date 2006-09-13 Time 14:01 Sent To  
Notes
2006-09-13 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-03-28 Cont ID  
Sent By tgordon Date 2007-03-28 Time 08:53 Rev Time 0.25
Received By tgordon Date 2007-03-28 Time 08:53 Sent To  
Notes
2007-03-28 08:56:04*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION
 ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE RESISTANCE
 RATING OF 1 HOUR OR (2) THE WEATHERPROOF ENCLOSURE IS
 CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 FOLLOW MANUFACTURER'S RECOMMENDED
 CLEARANCES AROUND EQUIPMENT FOR
 SERVICING,AND PROVIDE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-11-28 Cont ID  
Sent By tgordon Date 2006-11-28 Time 08:42 Rev Time 0.30
Received By tgordon Date 2006-11-28 Time 08:42 Sent To  
Notes
2006-11-28 08:44:06*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION
 ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE RESISTANCE
 RATING OF 1 HOUR OR (2) THE WEATHERPROOF ENCLOSURE IS
 CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 FOLLOW MANUFACTURER'S RECOMMENDED
 CLEARANCES AROUND EQUIPMENT FOR
 SERVICING,AND PROVIDE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 2 Status P Date 2007-03-27 Cont ID  
Sent By jroach Date 2007-03-27 Time 09:22 Rev Time 0.00
Received By jroach Date 2007-03-27 Time 09:22 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-09-18 Cont ID  
Sent By mmclean Date 2006-09-18 Time 17:56 Rev Time 0.00
Received By mmclean Date 2006-09-18 Time 17:56 Sent To I
Notes
2006-09-18 00:00:00NOTE: THE PROPOSED GENERATOR SHALL NOT
 BE CLOSER THAN 6FT FROM SIDE PROPERTY
 LINE.