Plan Review Details - Permit 06090338
Plan Review Stops For Permit 06090338
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-09-12 Cont ID  
Sent By lursu Date 2006-09-12 Time 16:11 Rev Time 0.00
Received By lursu Date 2006-09-12 Time 16:11 Sent To  
Notes
2006-09-12 00:00:00EXT #0006 WAS ADDED FOR UNIT 100

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-12-07 Cont ID  
Sent By jwitmer Date 2006-12-07 Time 08:14 Rev Time 0.00
Received By jwitmer Date 2006-12-12 Time 08:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-05 Cont ID  
Sent By jwitmer Date 2006-10-05 Time 16:45 Rev Time 0.77
Received By jwitmer Date 2006-10-05 Time 16:29 Sent To  
Notes
2006-10-05 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06090338
 ADD: 560 VILLAGE SUITE# 100
 CONT: FISHER
 TEL: (561)691-4916
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) DOOR 102 AND 121A ARE MISSING THE
 REQUIRED 18" ON THE LATCH SIDE.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
  
 2) EXIT STAIRWAY( NOT IN UNIT) BETWEEN
 OFFICE 116 AND 117 INTERIOR DOOR SWINGS
 THE WRONG WAY. 1008.1.2 DOORS SHALL
 SWING IN THE DIRECTION OF EGRESS TRAVEL
 WHERE SERVING AN OCCUPANT LOAD OF 50 OR
 MORE PERSONS.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-03-08 Cont ID  
Sent By dpalmer Date 2007-03-08 Time 16:38 Rev Time 0.00
Received By dpalmer Date 2007-03-08 Time 16:15 Sent To PC
Notes
2007-03-08 16:39:01REDLINED 408.4 AS PANEL SCHEDULE SHALL HAVE A PANEL
 DIRECTORY WHICH IS SPECIFIC TO ALL ITEMS BEING SERVED.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-02-14 Cont ID  
Sent By dpalmer Date 2007-02-14 Time 15:47 Rev Time 0.00
Received By dpalmer Date 2007-02-14 Time 15:32 Sent To  
Notes
2007-02-14 15:47:35 
 **** UNSAT ****
  
 1) NOTE:PLEASE SEE THAT THE PANEL SCHEDULE NEEDS TO
 BE REVISED TO CORRELATE TO ALL AREAS AND ROOMS WHICH
 CIRCUITS FEED.
 PLEASE SEE THE FOLLOWING TEXT WHICH IS EXTRACTED FROM
 408.4 COMMENTARY OF THE NEC.
  
 *CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.*
  
 PLEASE KNOW AS THE DRYWALL IS ALREADY INSTALLED, THESE
 PLANS WILL BE FOR FINAL AND THE ABOVE IS REQUIRED TO
 SPECIFIC AT THIS TIME. THIS IS FOR BOTH PANELS P AND
 P2.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-01-04 Cont ID  
Sent By dpalmer Date 2007-01-04 Time 19:30 Rev Time 0.00
Received By dpalmer Date 2007-01-04 Time 19:21 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-12-24 Cont ID  
Sent By dpalmer Date 2006-12-24 Time 14:04 Rev Time 0.00
Received By dpalmer Date 2006-12-24 Time 13:29 Sent To PC
Notes
2006-12-24 14:05:03**UNSAT 3RD REVIEW **
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH IS
 STILL IN NEED OF ADDRESSING.
 PLEASE SEE NOTE # 1 FROM PREVIOUS REVIEW.
  
 1) NOTE: PLEASE BE SURE TO REMOVE ANY OLD
 NON-APPLICABLE SHEETS FROM ENERGY CALCULATIONS WHICH DO
 NOT APPLY. PLEASE SEE OLD SHEETS WERE LEFT IN ALONG
 WITH NEW.
 PLEASE CORRELATE ENERGY CALCULATIONS WITH THE FIXTURES
 AND WATTAGE OF EACH FIXTURE ON PLAN. PLEASE SEE THE
 WATTAGE DOES NOT CORRELATE.
 THE EXCEPTION AS PERMITTED AS NOTED IS OK, HOWEVER
 PLEASE SEE NOT ALL AREAS ARE BEING INCLUDED IN ENERGY
 CALCULATIONS.
 PLEASE ALSO SEE THERE ARE ROOMS WHICH ARE NOT BEING
 INCLUDED FOR CONTROLS. DUE TO THE REMODEL/BUILD OUT
 TAKING PLACE, THESE AREAS SHALL ALSO BE INCLUDED AS
 STATED IN THE PREVIOUS REVIEW FOR ALL SEPARATE SPACES
 CONTAINING FLOOR TO CEILING HEIGHT PARTITIONS.
 PLEASE SEE ROOMS, 107,108,109,117, 118, 119 AND ROOM
 WHICH IS NOTED AS CONFERENCE ROOM IN CENTER OF PLANS.
 AT LAST CONVERSATION, IT WAS UNDERSTOOD THAT ALL AREAS
 WOULD BE INCLUDED.
  
 13-415.1.ABC.1.1, .1.2, AND .1.3, 13-415.1AB.1,
 13-415.2.ABC.1
  
 ** PLEASE KNOW THIS IS NOT SOMETHING THAT CANNOT BE
 REDLINED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-11-28 Cont ID  
Sent By dpalmer Date 2006-11-28 Time 19:57 Rev Time 0.00
Received By dpalmer Date 2006-11-28 Time 19:21 Sent To  
Notes
2006-11-28 19:57:37**** UNSAT ***
  
 1) NOTE: PLEASE SEE ENERGY CALCULATIONS SUBMITTED WHICH
 INDICATE MANUAL ON/OFF CONTROL CHOSEN FOR THE METHOD OF
 CONTROLLING LIGHTING. PLEASE CHOOSE AUTO OPTION.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. PLEASE SEE
 MISSING OVER RIDE DEVICES LOCATED IN ALL SPACES
 CONTAINING FLOOR TO CEILING HEIGHT PARTITIONS.
 PLEASE SEE MISSING THE MAX TIMES PERMITTED FOR TYPE OF
 OVER RIDES WHICH ARE NOT SHOWN AT THIS TIME. (30 MINS
 MAX FOR OCCUPANT SENSOR TYPE DEVICES, 4HRS MAX FOR
 TIMER TYPE.)
 PLEASE SEE MISSING OVER RIDE CONTROLS AS THEY ARE
 REQUIRED AT THE LOCATIONS OF INGRESS/EGRESS SO THE
 OCCUPANT MAY BE ABLE TO CONTROL THE LIGHTS WHICH ARE IN
 SIGHT.
 PLEASE INDICATE DEVICES AND CORRELATE WITH THE SYMBOL
 LEGEND.
 PLEASE EXPLAIN NOTE NUMBER #6 ON DRAWING KEY NOTES AS
 IT MENTIONS RELAY FOR NOT BEING ABLE TO OPERATE SOME
 RECESSED LIGHTING AT THE SAME TIME WITH OTHERS??
  
 2) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4).
 PLEASE KNOW, ANY NEW FA DEVICES INSTALLED MUST MEET
 THESE MINIMUM LEVELS. THIS WAS NOT IN PREVIOUS REVIEW
 AS THIS WAS NOT IN THE SCOPE OF WORK OF ELECTRICAL
 REVIEW, HOWEVER IT NOW IS.THE PRIMARY ISSUE IS ITEM
 11-4.28.3(4) WHICH REQUIRES A MIN OF 75 CANDELAS FOR
 ANY NEW STROBE DEVICES.
 PLEASE INDICATE ON LEGEND.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, COMMENTS OR IF ANY PART OF
 NOTES ABOVE ARE NOT UNDERSTOOD OR TYPED IN A MANNER
 WHICH IS NOT CLEAR, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE OR REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-29 Cont ID  
Sent By dpalmer Date 2006-09-29 Time 07:13 Rev Time 0.00
Received By dpalmer Date 2006-09-29 Time 07:03 Sent To  
Notes
2006-09-29 00:00:00** UNSAT **
  
 1) NOTE: PLEASE STATE THE FOLLOWING
 RELEVANT CODES (WHICH ARE ON PLANS)
 HOWEVER PLEASE GIVE YEAR EDITIONS
 CURRENTLY INEFFECT FOR THE DESIGN.
 2002 NFPA-70, 2002 NFPA-72, 2003
 NFPA-101.
  
  
 2) NOTE: PLEASE EXPLAIN SERVICE
 SCENARIO, IT IS UNCLEAR AT THIS TIME. IT
 SEEMS LIGHTING ETC IS BEING NOTED AND
 SHOWNFROM A SERVICE WHICH ALSO
 FEEDS THE REST OF THE FLOOR??
 IS THIS NOT A SEPARATE TENANT? PLANS
 INDICATE ADJACENT TENANT SPACES, HOWEVER
 MAY NOT HAVE A SERVICE WHICH FEEDS ONE
 TEANT FEED ANOTHER. PLEASE VERIFY AND
 SHOW THE LOCATION OF THE OTHER
 ELECTRICAL EQUIPMENT/SERVICE. NOT ABLE
 TO DETERMINE SOME ITEMS AT THIS TIME.
 110.26,240.24,210.25 ETC.
  
 3) NOTE: PLEASE SEE FBC CHAPTER 13 FOR
 NEW BUILD OUTS OF TENANT SPACES AND
 LIGHTING CONTROLS REQUIRED.
 13-415.1.ABC.1.1,.1.2,.1.3.
 PLEASE SEE CALCULAITONS FOR 13-415.2, 13-415.2.ABC.1,
 TABLES 415.2.C.1, AND
 415.2.B.1.
 DEPENDING ON WHAT WORK IS BEING DONE, IT
 SEEMS THESE REQUIREMENTS FOR LIGHTING
 CONTROLS ARE REQUIRED AND LPD'S ARE
 REQUIRED ALSO.
  
 4) NOTE: PLEASE SEE A COUPLE OF OUTSIDE
 OFFICES IN TENANT SPACE WHICH DO NOT
 INDICATE ANY LIGHTING??
  
 5) NOTE: PLEASE SEE BLDG AND POSSIBLE
 FIRE REVIEW COMMENTS AS THE SEEMS TO
 SHOW AN EGRESS DOOR ON THE EXIT STAIR
 TOWERS WHICH OPENS IN. ?? IT IS KNOWN
 THAT THIS MAY NOT BE A PART OF THIS BLD
 OUT HOWEVER IF THIS IS SHOWN ON
 ARCHITECURAL AND MEP PLANS, DOOR SWING
 SHOULD BE VERIFIED. THIS WAS
 HIGH-LIGHTED ON PLANS.
  
  
 ** PLEASE SEE ANY COMMENTS WHICH MAY
 AFFECT THE ELECTRICAL PLANS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-12-05 Cont ID  
Sent By mawillia Date 2006-12-05 Time 14:13 Rev Time 0.00
Received By mawillia Date 2006-12-05 Time 14:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-10-20 Cont ID  
Sent By mawillia Date 2006-10-20 Time 14:46 Rev Time 0.00
Received By mawillia Date 2006-10-20 Time 14:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-03-07 Cont ID  
Sent By adarroug Date 2007-03-07 Time 15:25 Rev Time 0.00
Received By adarroug Date 2007-03-07 Time 15:25 Sent To E
Notes
2007-03-07 15:25:43TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-02-13 Cont ID  
Sent By adarroug Date 2007-02-13 Time 09:39 Rev Time 0.00
Received By adarroug Date 2007-02-13 Time 09:39 Sent To  
Notes
2007-02-13 09:39:44TO "BOB"#15

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-01-04 Cont ID  
Sent By adarroug Date 2007-01-04 Time 16:41 Rev Time 0.00
Received By adarroug Date 2007-01-04 Time 16:41 Sent To E
Notes
2007-01-04 16:42:01TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-19 Cont ID  
Sent By adarroug Date 2006-12-19 Time 16:19 Rev Time 0.00
Received By adarroug Date 2006-12-19 Time 16:19 Sent To E
Notes
2006-12-19 16:23:09TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-15 Cont ID  
Sent By adarroug Date 2006-11-15 Time 14:40 Rev Time 0.00
Received By adarroug Date 2006-11-15 Time 14:40 Sent To  
Notes
2006-11-27 16:43:40TO "COMM" BD#23
2006-11-15 14:40:32WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-20 Cont ID  
Sent By mawillia Date 2006-10-20 Time 14:46 Rev Time 0.00
Received By mawillia Date 2006-09-12 Time 11:49 Sent To  
Notes
2006-09-25 00:00:00TO "COMM" BD#18
2006-09-12 00:00:00WAITING FOR "COMM" BD-THIS JOB IS OVER
 5000 SQ. FT

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-02-28 Cont ID  
Sent By hmoser Date 2007-02-28 Time 18:51 Rev Time 0.00
Received By hmoser Date 2007-02-28 Time 18:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-02-21 Cont ID  
Sent By tgordon Date 2007-02-21 Time 11:03 Rev Time 0.30
Received By tgordon Date 2007-02-21 Time 11:03 Sent To  
Notes
2007-02-21 11:04:13REVISION TO MECH. PLANS PAGE M-1.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-12-11 Cont ID  
Sent By hmoser Date 2006-12-11 Time 18:20 Rev Time 0.00
Received By hmoser Date 2006-12-11 Time 17:47 Sent To  
Notes
2006-12-11 18:24:55PLEASE REFER TO SECTION 601.4 BALANCED RETURN AIR 2004
 FBC (M)
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-10-17 Cont ID  
Sent By hmoser Date 2006-10-17 Time 15:55 Rev Time 0.00
Received By hmoser Date 2006-10-17 Time 15:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-10-14 Cont ID  
Sent By kstevens Date 2006-10-14 Time 10:03 Rev Time 0.00
Received By kstevens Date 2006-10-14 Time 10:03 Sent To  
Notes
2006-10-14 10:04:32DEMO OF SINK ONLY - NO DEAD ENDS PER 704.5 - PLUMBING
 PERMIT REQUIRED.