Plan Review Details - Permit 06090301
Plan Review Stops For Permit 06090301
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-10-23 Cont ID  
Sent By alange Date 2006-10-23 Time 08:41 Rev Time 0.00
Received By alange Date 2006-10-23 Time 08:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-11-09 Cont ID  
Sent By btrobaug Date 2006-11-09 Time 12:11 Rev Time 0.50
Received By btrobaug Date 2006-11-09 Time 11:56 Sent To PC
Notes
2006-11-09 12:02:22 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT. FOR REVIEW.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-18 Cont ID  
Sent By btrobaug Date 2006-10-18 Time 07:22 Rev Time 0.50
Received By btrobaug Date 2006-10-18 Time 07:04 Sent To G
Notes
2006-10-18 07:22:04 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE
 PLAN/DRAWINGS, SHALL PRINT AND SIGN THEIR NAME ON THE
 SHEETS THEY DRAW. PLEASE DO THIS PRIOR TO
 RESUBMITTING.
  
 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, GENERATOR, TRANSFER SWITCH,
 DISCONNECTS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED. DO THIS ON A SITE
 PLAN, NOT ON THE SURVEY, 106.1.3FBC.
  
 3} PROVIDE SPECIFICATIONS FOR THE TRANSFER SWITCH.
 THERE IS A DOUBLE THROW DISCONNECT SUBMITTED, BUT THE
 RISER INDICATES A ATS. IF THIS IS TO BE A MANUAL
 TRANSFER PLEASE MODIFY DRAWINGS TO INDICATE SAME.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2006-10-19 Cont ID  
Sent By btrobaug Date 2006-10-19 Time 07:23 Rev Time 0.45
Received By mperson Date 2006-10-19 Time 14:36 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-30 Cont ID  
Sent By adarroug Date 2006-10-30 Time 10:26 Rev Time 0.00
Received By adarroug Date 2006-10-30 Time 10:26 Sent To E
Notes
2006-10-30 10:27:35TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-19 Cont ID  
Sent By adarroug Date 2006-09-19 Time 08:14 Rev Time 0.00
Received By adarroug Date 2006-09-19 Time 08:14 Sent To E
Notes
2006-09-19 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-23 Cont ID  
Sent By alange Date 2006-10-23 Time 08:42 Rev Time 0.00
Received By alange Date 2006-09-12 Time 08:28 Sent To  
Notes
2006-09-12 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-09-20 Cont ID  
Sent By tgordon Date 2006-09-20 Time 16:18 Rev Time 0.15
Received By tgordon Date 2006-09-20 Time 16:18 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-09-16 Cont ID  
Sent By mmclean Date 2006-09-16 Time 08:14 Rev Time 0.00
Received By mmclean Date 2006-09-16 Time 08:14 Sent To I
Notes
2006-09-16 00:00:00NOTE: THE PROPOSED GENERATOR SHALL NOT
 PROJECT INTO THE 10FT DRAINAGE EASEMENT.