Plan Review Details - Permit 06090243
Plan Review Stops For Permit 06090243
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-10-24 Cont ID  
Sent By jwitmer Date 2008-10-24 Time 11:26 Rev Time 1.55
Received By jwitmer Date 2008-10-24 Time 11:26 Sent To  
Notes
2008-10-24 11:27:04BUILDING PROVISO: SHEET 3.1
 1) 1009.11 HANDRAILS WILL REQUIRED ON BOTH SIDES OF THE
 STAIRS.
 2) 1012.1 GUARDRAIL REQUIRED ON THE OPEN SIDE OF THE
 STAIRS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-07-24 Cont ID  
Sent By jwitmer Date 2008-07-24 Time 16:46 Rev Time 2.20
Received By jwitmer Date 2008-07-24 Time 16:46 Sent To  
Notes
2008-07-24 16:56:43BUILDING PROVISO: SHEET 3.1
 1) 1009.11 HANDRAILS WILL REQUIRED ON BOTH SIDES OF THE
 STAIRS.
 2) 1012.1 GUARDRAIL REQUIRED ON THE OPEN SIDE OF THE
 STAIRS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-02-14 Cont ID  
Sent By jwitmer Date 2008-02-14 Time 13:53 Rev Time 2.22
Received By jwitmer Date 2008-02-14 Time 13:53 Sent To  
Notes
2008-02-14 13:53:42BUILDING PLAN REVIEW
 PERMIT: 06090243
 ADD: 5312 BROADWAY
 CONT: 3-D HOMES
 TEL: (561)662-9327
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2005 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 4TH ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B) INFORMATIONAL ONLY. PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL ONLY.106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER NOV. 21ST,2005 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2005 REVISIONS.
  
 2-4) COMPLIED.
  
 5) COMPLIED.
  
 6-8) COMPLIED.
  
 9) COMPLIED.
  
 9B) SEMI-COMPLIED. THE NEWDOOR SWINGS INTO THE CLEAR
 FLOOR SPACE REQUIRED BY THE COMMON USE SINKS.
  
 12-16) COMPLIED.
  
 17A) SEMI-COMPLIED. PLANS STILL INDICATE WALLS THAT
 MAKE UP THE VERTICAL STAIR SHAFT THAT ARE NOT RATED.
 SEE SHAFTS 707.4. ALSO PROVIDE RATED DOORS FOR THE
 VERICAL EXIT ENCLOSURE.
 SEE 715.3.
  
 18-21) COMPLIED.
  
 22)COMPLIED.
 NEW COMMENTS
 23)CORRIDOR WALLS AROUND THE FIRST AND SECOND FLOOR
 ASSEMBLY OCCUPANCIES THE PLANS DO NOT INDICATE AS RATED
 WALLS PLEASE SEE TABLE 1016.1.
  
 24)PLANS WILL NEED TO CORRECT THEIR OCCUPANT COUNTS
 OFFICES ARE 100 SQ FT PER PERSON, AND FIRST FLOOR
 ASSEMBLY REWRITE 7 SQ FT PER PERSON.
  
 25) THE SECOND FLOOR ONE EXIT IS OUT ONTO THE ROOF, AND
 DOWN AN EXIT STAIRWAY. THE PLANS SHOW A LINE THAT WOULD
 INDICATE A CHANGE IN ELEVATION ON THE ROOF. PLEASE
 PROVIDE
 WHAT CHANGE IN ELEVATION THIS IS? AND IF STAIRS WOULD
 BE REQUIRED.
  
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECODS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-10-30 Cont ID  
Sent By jwitmer Date 2007-10-30 Time 11:23 Rev Time 2.22
Received By jwitmer Date 2007-10-30 Time 11:23 Sent To  
Notes
2007-10-30 11:25:19BUILDING PLAN REVIEW
 PERMIT: 06090243
 ADD: 5312 BROADWAY
 CONT: 3-D HOMES
 TEL: (561)662-9327
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2005 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 4TH ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B) INFORMATIONAL ONLY. PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL ONLY.106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER NOV. 21ST,2005 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2005 REVISIONS.
  
 2-4) COMPLIED.
  
 5) COMPLIED.
  
 6-8) COMPLIED.
  
 9) COMPLIED.
  
 9B) SEMI-COMPLIED. THE NEWDOOR SWINGS INTO THE CLEAR
 FLOOR SPACE REQUIRED BY THE COMMON USE SINKS.
  
 12-16) COMPLIED.
  
 17A) SEMI-COMPLIED. PLANS STILL INDICATE WALLS THAT
 MAKE UP THE VERTICAL STAIR SHAFT THAT ARE NOT RATED.
 SEE SHAFTS 707.4. ALSO PROVIDE RATED DOORS FOR THE
 VERICAL EXIT ENCLOSURE.
 SEE 715.3.
  
 18-21) COMPLIED.
  
 22)COMPLIED.
 NEW COMMENTS
 23)CORRIDOR WALLS AROUND THE FIRST AND SECOND FLOOR
 ASSEMBLY OCCUPANCIES THE PLANS DO NOT INDICATE AS RATED
 WALLS PLEASE SEE TABLE 1016.1.
  
 24)PLANS WILL NEED TO CORRECT THEIR OCCUPANT COUNTS
 OFFICES ARE 100 SQ FT PER PERSON, AND FIRST FLOOR
 ASSEMBLY REWRITE 7 SQ FT PER PERSON.
  
 25) THE SECOND FLOOR ONE EXIT IS OUT ONTO THE ROOF, AND
 DOWN AN EXIT STAIRWAY. THE PLANS SHOW A LINE THAT WOULD
 INDICATE A CHANGE IN ELEVATION ON THE ROOF. PLEASE
 PROVIDE
 WHAT CHANGE IN ELEVATION THIS IS? AND IF STAIRS WOULD
 BE REQUIRED.
  
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECODS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-04-05 Cont ID  
Sent By jwitmer Date 2007-04-05 Time 10:16 Rev Time 3.22
Received By jwitmer Date 2007-04-05 Time 09:19 Sent To  
Notes
2007-04-05 10:22:51BUILDING PLAN REVIEW
 PERMIT: 06090243
 ADD: 5312 BROADWAY
 CONT: 3-D HOMES, INC
 TEL: (561)662-9327
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
 EX FL BLD CODE= 2004 EXISTING BUILDING
 CODE
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2-8 COMPLIED.
  
 9)SEE PLUMBING REQUIREMENTS FOR NEW RESROOM.
  
 10-15) COMPLIED,
  
 16) STAGE AND PLATFORMS, YOU CAN'T JUST QUOTE THE CODE
 SECTION, OF WHAT MATERIALS WILL THIS STAGE BE BUILT,
 WHAT IS THE SAFE BEARING LOAD OF THE STAGE?
  
 17A) JANITORS CLOSET AT THE BASE OF STAIRS, 1019.1.5 TO
 BE 1 HR FIRE RATED PROVIDE WHAT ASSEMBLY TYPE WILL BE
 USED?
  
 18) COMPLIED.
  
 19) 2ND REQUEST, THE FIRST FLOOR INDICATEDA NEW
 PAIR OF EXTERIOR DOORS.
 1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 1714.5.3 EXTERIOR DOOR ASSEMBLIES.
 EXTERIOR DOOR ASSEMBLIES NOT COVERED BY
 SECTION 1715.4.2 OR SECTION 1714.5.3.1
 SHALL BE TESTED FOR STRUCTURAL INTEGRITY
 IN ACCORDANCE WITH ASTM E 330 PROCEDURE
 A, AT A LOAD OF 1.5 TIMES THE REQUIRED
 DESIGN PRESSURE LOAD. THE LOAD SHALL BE
 SUSTAINED FOR 10 SECONDS WITH NO
 PERMANENT DEFORMATION OF ANY MAIN FRAME
 OR PANEL MEMBER IN EXCESS OF 0.4 PERCENT
 OF ITS SPAN AFTER THE LOAD IS REMOVED. HIGH-VELOCITY
 HURRICANE ZONES SHALL
 COMPLY WITH TAS 202. AFTER EACH
 SPECIFIED LOADING, THERE SHALL BE NO
 GLASS BREAKAGE, PERMANENT DAMAGE TO
 FASTENERS, HARDWARE PARTS, OR ANY OTHER
 DAMAGE WHICH CAUSES THE DOOR TO BE
 INOPERABLE.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 20)FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXTERIOR SWING DOORS PROVIDE THE CORRECT REPORT THAT
 TIES TO THE FL REPORT# 4553/ THE REPORT SHOULD BE UL
 4553 SEE PDF FILE!
  
 21) 2ND REQUEST, WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 22) THE NEW WING WALL ON THE BACK EXTERIOR OF BUILDING
 THAT SEPERATES THE 2ND FLOOR STAIR FROM THE NEW EXIT
 REAR OF CHURCH PROVIDES LESS THAN 44" CREATES BOTTLE
 NECKING EFFECT, CAN'T REDUCE THE EXIT FLOW.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-05 Cont ID  
Sent By jwitmer Date 2006-10-05 Time 07:37 Rev Time 5.50
Received By jwitmer Date 2006-10-05 Time 07:36 Sent To  
Notes
2006-10-05 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06090243
 ADD: 5312 BROADWAY
 CONT: 3-D HOMES, INC
 TEL: (561)662-9327
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
 EX FL BLD CODE= 2004 EXISTING BUILDING
 CODE
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) HOLDS ON PROPERTY:
 SEE ATTACHMENTHOLDS ON PROPERTY, WORKING
  
 WIWTHOUT PERMIT & CHANGE IN OCCUPANCY!!!
  
 4) PLEASE CHANGE THE SCOPE OF WORK ON
 THE PERMIT APPLICATION UNDER DESCRIPTION
 OF WORK FOR THIS PROJECT TO REFLECT THE
 WORK COMPLETED WITHOUT BENEFIT OF A
 PERMIT AND FOR CHANGE OF OCCUPANCY ALSO
 REQUIRING A PERMIT.105.1*/306 EX FL BLD
 CODE.
 3401.1 SCOPE.
 ALTERATION, REPAIR, ADDITION, RELOCATION
 AND CHANGE OF OCCUPANCY OF EXISTING
 STRUCTURES AND BUILDINGS SHALL COMPLY
 WITH THE PROVISIONS OF THE 2004 FLORIDA
 EXISTING BUILDING CODE .
 1001.4 ALTERATIONS.
 A BUILDING SHALL NOT HEREAFTER BE
 ALTERED TO REDUCE THE CAPACITY OF THE
 MEANS OF EGRESS TO LESS THAN REQUIRED BY
 THIS CHAPTER NOR SHALL ANY CHANGE OF
 OCCUPANCY BE MADE IN ANY BUILDING UNLESS
 SUCH BUILDING CONFORMS WITH THE
 REQUIREMENTS OF THIS CHAPTER
 13-101.3.2 BUILDINGS HAVING A CHANGE OF
 OCCUPANCY THAT WERE PERMITTED AFTER
 MARCH 15, 1979, SHALL COMPLY WITH THE
 REQUIREMENTS OF SUBCHAPTER 13-4 FOR
 COMMERCIAL APPLICATIONS AND
 MULTIPLE-FAMILY RESIDENTIAL BUILDINGS
 GREATER THAN THREE STORIES.
 THIS REVIEW WILL TAKE PLACE USING THE
 2004 EXISTING BUILDING CODE & THE 2004
 FL BUILDING CODE. THE LEVEL OF
 ALTERATIONS WILL BE CONSIDERED A LEVEL
 II ALTERATION.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6) NEW INFORMATION FROM THE
 ARCHITECTURAL BOARD ABOUT DRAFTING FIRMS
  
 WORKING UNDER THE LICENSE OF A DESIGN PROFESSIONAL.
 PLEASE SEE FL S S 481.229
 AND THE ELECTRICAL COMMENT# 2.
  
 7) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G) NUMBER OF FLOORS
 H) NUMBER OF ROOMS
 I) SQ. FT. LIV SPACE/ FL
 J) SQ. FT. FOOTPRINT
 K) SQ. FT. UNDER ROOF (TOTAL)
  
 8) AT THIS TIME NOT KNOWING IF THIS
 BUILDING HAS AUTOMATIC FIRE SPRINKLERS
 THE SECOND FLOOR WILL REQUIRE AREAS OF
 RESCUE ASSISTANCE. 105.1*, CHANGE OF
 OCCUPANCY INVOKES 11-4.1.6 ACCESSIBLE
 BUILDINGS: ALTERATIONS,
 (1)(B) IF EXISTING ELEMENTS, SPACES, OR
 COMMON AREAS ARE ALTERED, THEN EACH SUCH
 ALTERED ELEMENT, SPACE, FEATURE, OR AREA
 SHALL COMPLY WITH THE APPLICABLE
 PROVISIONS OF 11-4.1.1 T0 11-4.1.1
 MINIMUM REQUIREMENTS FOR NEW
 CONSTRUCTION.
 11-4.1.3(9)IN BUILDINGS OR
 FACILITIES, OR PORTIONS OF BUILDINGS OR FACILITIES,
 REQUIRED TO BE ACCESSIBLE,
 ACCESSIBLE MEANS OF EGRESS SHALL BE
 PROVIDED IN THE SAME NUMBER AS REQUIRED
 FOR EXITS BY LOCAL BUILDING/LIFE SAFETY REGULATIONS.
 WHERE A REQUIRED EXIT FROM
 AN OCCUPIABLE LEVEL ABOVE OR BELOW A
 LEVEL OF ACCESSIBLE EXIT DISCHARGE IS
 NOT ACCESSIBLE, AN AREA OF RESCUE
 ASSISTANCE SHALL BE PROVIDED ON EACH
 SUCH LEVEL (IN A NUMBER EQUAL TO THAT OF INACCESSIBLE
 REQUIRED EXITS). AREAS OF
 RESCUE ASSISTANCE SHALL COMPLY WITH
 SECTION 11-4.3.11 . A HORIZONTAL EXIT,
 MEETING THE REQUIREMENTS OF LOCAL
 BUILDING/LIFE SAFETY REGULATIONS, SHALL
 SATISFY THE REQUIREMENT FOR AN AREA OF
 RESCUE ASSISTANCE.
 11-4.3.11.1 AREA OF RECUE ASSISTANCE
 LOCATION AND CONSTRUCTION SHALL MEET ALL
 THE REQUIREMENTS OF THIS SECTION,
 11-4.3.11 (1)-(5).
  
 9) THE NEW MENS RESTROOM LOCATED ON
 SHEET ONE DOESN,T MEET THE REQUIREMENTS
 OF 11-4.17.3.
  
 10) PROVIDE A LIFE SAFETY PLAN FOR THE
 FIRST AND SECOND FLOORS. PROVIDE AN
 OCCUPANT LOAD FIRST AND SECOND FLOORS
 AND CAPACITY FOR EACH OF THE DOORWAYS
 STAIRS AND EXITS. ALSO INDICATE EXIT
 SIGNS AND DIRECTIONALS ON PLANS. 1023.1
  
 11) THE SHEET# 1 INDICATES FIRST FLOOR
 A CLOSET AT THE REAR OF THE CHURCH WITH
 A PAIR OF 3'-0" DOORS THE CORIDOR WITH
 IS 4'-6" OR 54" WIDE. THE DOORS TO THIS
 CLOSET BEING 36" LEAVING A CLEAR WITH OF
 18". THE MINIMUM CLEAR WITH WIDTH
 REQUIRED IS 22" WITH AN OCCUPANT LOAD .
 50.
 1008.1.8.8
 DURING ITS SWING, ANY DOOR IN A MEANS OF
 EGRESS SHALL LEAVE UNOBSTRUCTED AT LEAST
 ONE HALF OF THE REQUIRED WIDTH OF AN
 AISLE, CORRIDOR, PASSAGEWAY, OR LANDING,
 NOR PROJECT MORE THAN 7 INCHES (178 MM)
 INTO THE REQUIRED WIDTH OF AN AISLE,
 CORRIDOR, PASSAGEWAY OR LANDING, WHEN
 FULLY OPEN.
  
 12) SHEET# 1 LOWER LEFT CORNER OF PLAN,
 THE HALLWAYS LEAD TO A PAIR OF 2 2'-6
 DOORS, IT APPEARS THE CORRIDOR IS LESS
 THAN 44" WIDE.1016.2.
  
 13) SHEET# 1 LOWER LEFT CORNER OF THE
 PLAN DOUBLE DOORS :
 11-4.13.4 DOUBLE-LEAF DOORWAYS.
 IF DOORWAYS HAVE TWO INDEPENDENTLY
 OPERATED DOOR LEAVES, THEN AT LEAST ONE
 LEAF SHALL MEET THE SPECIFICATIONS IN
 SECTION 11-4.13.5 AND SECTION 11-4.13.6
 . THAT LEAF SHALL BE AN ACTIVE LEAF.
 11-4.13.5 CLEAR WIDTH.
 DOORWAYS SHALL HAVE A MINIMUM CLEAR
 OPENING OF 32 INCHES (813 MM) WITH THE
 DOOR OPEN 90 DEGREES, MEASURED BETWEEN
 THE FACE OF THE DOOR AND THE OPPOSITE
 STOP [SEE FIGURE 11-24 (A), FIGURE 11-24
 (B), FIGURE 11-24 (C), AND FIGURE 11-24
 (D)].
  
 14) SHEET# 1 LOWER LEFT CORNER THE PAIR
 OF DOORS LABELED # 4 TO THE EXTERIOR
 BLOCK THE 2ND STORY EXIT STAIRS AS
 INDICATED.THE PLANS INDICATE NEW DOORS,
 WHAT IS THE CHANGE IN FLOOR ELEVATION TO
 THE EXTERIOR?
  
 15) SHEET# 1 FRONT ENTRY DOOR SWINGS THE
 WRONG WAY, 1008.1.2DOORS SHALL SWING
 IN THE DIRECTION OF EGRESS TRAVEL WHERE
 SERVING AN OCCUPANT LOAD OF 50.
  
 16) STAGES AND PLATFORMS
 410.3.1 STAGE CONSTRUCTION.
 STAGES SHALL BE CONSTRUCTED OF MATERIALS
 AS REQUIRED FOR FLOORS FOR THE TYPE OF CONSTRUCTION OF
 THE BUILDING IN WHICH
 SUCH STAGES ARE LOCATED.
 EXCEPTIONS:
 1.STAGES OF TYPE IIB OR IV
 CONSTRUCTION WITH A NOMINAL 2-INCH (51
 MM) WOOD DECK, PROVIDED THAT THE STAGE
 IS SEPARATED FROM OTHER AREAS IN
 ACCORDANCE WITH SECTION 410.3.4 .
 2.IN BUILDINGS OF TYPE IIA, IIIA
 AND VA CONSTRUCTION, A
 FIRE-RESISTANCE-RATED FLOOR IS NOT
 REQUIRED, PROVIDED THE SPACE BELOW THE
 STAGE IS EQUIPPED WITH AN AUTOMATIC FIRE-EXTINGUISHING
 SYSTEM IN ACCORDANCE
 WITH SECTION 903 OR 904.
 3.IN ALL TYPES OF CONSTRUCTION, THE
 FINISHED FLOOR SHALL BE CONSTRUCTED OF
 WOOD OR APPROVED NONCOMBUSTIBLE
 MATERIALS. OPENINGS THROUGH STAGE FLOORS
 SHALL BE EQUIPPED WITH TIGHT-FITTING,
 SOLID WOOD TRAP DOORS WITH APPROVED
 SAFETY LOCKS.
 PROVIDE CLARITY AND COMPLIANCE WITH
 THESE SECTIONS OF THE CODE.
  
 17A) SHEET# 1 EAST SIDE OF THE BUILDING
 PLEASE PROVIDE CLAARITY ON THE JANITORS
 CLOSET LOCATED BENEATH THE STAIRWAY WITH
 A RETURN DUCT ?
 1019.1.5 ENCLOSURES UNDER STAIRWAYS.
 THE WALLS AND SOFFITS WITHIN ENCLOSED
 USABLE SPACES UNDER ENCLOSED AND
 UNENCLOSED STAIRWAYS SHALL BE PROTECTED
 BY 1-HOUR FIRE-RESISTANCE-RATED
 CONSTRUCTION, OR THE FIRE-RESISTANCE
 RATING OF THE STAIRWAY ENCLOSURE,
 WHICHEVER IS GREATER. ACCESS TO THE
 ENCLOSED USABLE SPACE SHALL NOT BE
 DIRECTLY FROM WITHIN THE STAIR
 ENCLOSURE.
  
 17B) IS THERE RATINGS BETWEEN THE
 JANITORS CLOSET AND STAIR FRAMING?
  
 18A) SHEET# 2 EXISTING MEETING ROOM HAS
 607 SQ FT AND A OCCUPANT LOAD OF 96. TWO
 MEANS OF EGRESS ARE REQUIRED FOR THIS
 AREA.TABLE 1014.1.
  
 18B)1014.2.1 TWO EXITS OR EXIT ACCESS
 DOORWAYS.
 WHERE TWO EXITS OR EXIT ACCESS DOORWAYS
 ARE REQUIRED FROM ANY PORTION OF THE
 EXIT ACCESS, THE EXIT DOORS OR EXIT
 ACCESS DOORWAYS SHALL BE PLACED A
 DISTANCE APART EQUAL TO NOT LESS THAN
 ONE-HALF OF THE LENGTH OF THE MAXIMUM
 OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA TO BE SERVED MEASURED
 IN A STRAIGHT LINE BETWEEN EXIT DOORS OR
 EXIT ACCESS DOORWAYS. INTERLOCKING OR
 SCISSOR STAIRS SHALL BE COUNTED AS ONE
 EXIT STAIRWAY.
 EXCEPTIONS:
 1.WHERE EXIT ENCLOSURES ARE
 PROVIDED AS A PORTION OF THE REQUIRED
 EXIT AND ARE INTERCONNECTED BY A 1-HOUR
 FIRE-RESISTANCE-RATED CORRIDOR
 CONFORMING TO THE REQUIREMENTS OF
 SECTION 1016 , THE REQUIRED EXIT
 SEPARATION SHALL BE MEASURED ALONG THE
 SHORTEST DIRECT LINE OF TRAVEL WITHIN
 THE CORRIDOR.
 2.WHERE A BUILDING IS EQUIPPED
 THROUGHOUT WITH AN AUTOMATIC SPRINKLER
 SYSTEM IN ACCORDANCE WITH SECTION
 903.3.1.1 OR 903.3.1.2 , THE SEPARATION
 DISTANCE OF THE EXIT DOORS OR EXIT
 ACCESS DOORWAYS SHALL NOT BE LESS THAN
 ONE-THIRD OF THE LENGTH OF THE MAXIMUM
 OVERALL DIAGONAL DIMENSION OF THE AREA
 SERVED.
  
 18C) DEPENDING ON THE LOCATION WHERE THE
 SECOND MEANS OF EGRESS IS CUT IN ON THE
 EXISTING MEETING ROOM WITH AN OCCUPANT
 LOAD OF 96 THE DOOR LEADING TO THE
 PRAYER ROOM WILL ALSO NEED TO HAVE THE
 SWING REVERSED, 1008.1.2: DOORS SHALL
 SWING IN THE DIRECTION OF EGRESS TRAVEL
 WHERE SERVING AN OCCUPANT LOAD OF 50 OR
 GREATER.
  
 19) THE FIRST FLOOR INDICATEDA NEW
 PAIR OF EXTERIOR DOORS.
 1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 1714.5.3 EXTERIOR DOOR ASSEMBLIES.
 EXTERIOR DOOR ASSEMBLIES NOT COVERED BY
 SECTION 1715.4.2 OR SECTION 1714.5.3.1
 SHALL BE TESTED FOR STRUCTURAL INTEGRITY
 IN ACCORDANCE WITH ASTM E 330 PROCEDURE
 A, AT A LOAD OF 1.5 TIMES THE REQUIRED
 DESIGN PRESSURE LOAD. THE LOAD SHALL BE
 SUSTAINED FOR 10 SECONDS WITH NO
 PERMANENT DEFORMATION OF ANY MAIN FRAME
 OR PANEL MEMBER IN EXCESS OF 0.4 PERCENT
 OF ITS SPAN AFTER THE LOAD IS REMOVED. HIGH-VELOCITY
 HURRICANE ZONES SHALL
 COMPLY WITH TAS 202. AFTER EACH
 SPECIFIED LOADING, THERE SHALL BE NO
 GLASS BREAKAGE, PERMANENT DAMAGE TO
 FASTENERS, HARDWARE PARTS, OR ANY OTHER
 DAMAGE WHICH CAUSES THE DOOR TO BE
 INOPERABLE.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 20)FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXTERIOR SWING DOORS
  
 21) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 22) PROVIDE AN INTERIOR WALL & CEILING
 SCHEDULE BASED ON OCCUPANCY TABLE 803.5.
  
  
 NOTE THE NEXT REVIEW MAY HAVE ADDITIONAL
 COMMENTS DUE TO THE DESIGN TEAMS
 RESPONCE TO THE FIRST REVIEW.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-07-28 Cont ID  
Sent By dpalmer Date 2008-07-28 Time 09:23 Rev Time 0.00
Received By dpalmer Date 2008-07-28 Time 09:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-01-12 Cont ID  
Sent By dpalmer Date 2008-01-12 Time 17:17 Rev Time 0.00
Received By dpalmer Date 2008-01-12 Time 17:17 Sent To  
Notes
2008-01-12 17:18:31*** TEMPORARY FAILED STATUS ****
  
 *** TEMPORARY FAILED STATUS ***
  
 1) NOTE: ELECTRICAL PLANS ARE OK, HOWEVER THE FORM 400C
 SUBMITTED IS REQUIRED TO BE SIGNED, DATED AND SEALED BY
 THE DESIGNER AND ENGINEER OF RECORD.
 PLEASE ALSO VERY LIGHTING DENSITIES SHOWN ON 400C WITH
 THAT OF THE LIGHTING SHOWN ON PLANS.
  
 FBC 13-103.1.1.1, FS 471.025 AND FAC 61G15-23.002,
 61G15-33.004
  
 PLEASE KNOW THE ABOVE MAY BE SUBMITTED AT ANYTIME
 BEFORE OTHER REVIEWS ARE COMMENCED. PLEASE CONTACT THIS
 REVIEWER AS THESE NEED TO BE SUBMITTED AS SOON AS
 POSSIBLE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-10-16 Cont ID  
Sent By dpalmer Date 2007-10-16 Time 15:21 Rev Time 0.00
Received By dpalmer Date 2007-10-16 Time 14:37 Sent To  
Notes
2007-10-16 15:21:39 
 *** DENIED 3RD REVIEW *****
  
 ** PLEASE SEE COMMENTS FROM PREVIOUS REVIEWS STILL NEED
 TO BE ADDRESSED.
 THERE ARECOMMENTS BELOW WHICH STILL NEED TO BE
 ADDRESSED. ONCE ALL REVIEWS ARE DONE AND IF ALL REVIEWS
 ARE IN A *PASSED* STATUS, PLEASE CONTACT THIS
 REVIEWER.
 IF PLANS COME BACK WITH COMMENTS FROM ANY OTHER TRADES,
 THESE MUST BE ADDRESSED AT THIS TIME.
  
 1) NOTE: PLEASE SEE AS STATED AND REQUESTED ON THE
 PREVIOUS REVIEWS. PLEASE SUBMIT LIGHTING PHOTO-METRIC
 LEVELS FOR STAIRS UNDER NORMAL AND EMERGENCY
 CONDITIONS. PLEASE SEE NFPA-101 (LIFE SAFETY CODE)
 7.8.1.3, 7.9.2.2 WHICH WAS GIVEN ON PREVIOUS
 REVIEW(S).
 PLEASE SEE MINIMUM LEVELS ARE REQUIRED ALSO PER FLORIDA
 ADMINISTRATIVE CODE 61G15-33.004
  
 2) NOTE: PLEASE SEE THIS SAME LIFE SAFETY CODE AND FBC
 CHAPTER 10 AS OCCUPANCY SENSOR DEVICES MAY BE USED FOR
 CONTROL OF LIGHTING HOWEVER A MINIMUM OF TWO DEVICES IN
 STAIR AREA WOULD BE REQUIRED FOR CONTROL OF LIGHTING
 FIXTURES. THE FAILURE OF ANY ONE DEVICE FOR CONTROL OF
 EGRESS LIGHTING CAN NOT LEAVE NAY ONE AREA IN DARKNESS
 UNDER NORMAL OR EMERGENCY CONDITIONS.
  
 3) NOTE: PLEASE SEE RISER AND PANEL MDP WHICH INDICATES
 150AMP OVER CURRENT PROTECTION FEEDING A 100AMP
 DISCONNECT AND CONTROL PANEL FOR ELEVATOR.
  
 ** FOR INFORMATION ONLY, THE RECORDED NOC SUBMITTED HAS
 EXPIRED PER FS 713.13(2).
 WILL NEED ONLY TO BE RE-RECORDED ONCE PICKING UP
 PERMIT.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-03-18 Cont ID  
Sent By dpalmer Date 2007-03-18 Time 14:00 Rev Time 0.00
Received By dpalmer Date 2007-03-18 Time 12:13 Sent To  
Notes
2007-03-18 14:09:15** UNSAT **
  
 ** PLEASE KNOW THAT THIS IS A CHANGE IN OCCUPANCY AND
 ALL ELECTRICAL WILL BE REQUIRED TO MEET THE CURRENT
 CODES ADOPTED WHEN PERMIT WAS APPLIED.
 THE PERMIT DESCRIPTION ON COMPUTER NOW INDICATES BUILD
 OUT FOR NEW CHURCH.
  
 ***********************************
 ** PLEASE SEE PLANS ARE STAMPED FROM PALM BEACH COUNTY
 FOR IMPACT FEES WHICH INDICATE *EXISTING* USEAND
 PLANS SUBMITTED TO PALM BEACH COUNTY ALSO INDICATE
 EXISTING USE AS A CHURCH. PLEASE KNOW THIS WILL BE
 FORWARD TO PALM BEACH COUNTY FOR THIS USE AS NEW AS IT
 IS NOT EXISTING.
 ***************************************
  
 1) NOTE: PLEASE SEE THAT ALL OF THE CODES WHICH PLANS
 ARE UNDER DESIGN AND RECORD SHALL BE STATED ON PLANS AS
 FOLLOWS.
 2004 FBC
 2002 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
 ** THESE ARE REQUIRED FOR THE REVIEWER AT A MINIMUM AND
 OTHER CODES WILL BE REQUIRED FOR OTHER TRADES.
  
 2) NOTE: PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER ON TITLE BLOCKS FOR THE COMPANY
 LISTED AS MCR PROFESSIONAL ENGINEERING INC. PLEASE SEE
 SHEET IS ATTACHED FROM THE DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION WITH THE LICENSE INFORMATION AS
 NEED. PLEASE SEE THE FLORIDA ADMINISTRATIVE CODE
 61G15-23.002 AND FLORIDA STATUTES 471.023.
  
 3) NOTE: PLEASE SEE FBC CHAPTER 13.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. PLEASE SEE
 SOME AREAS WHICH DO NOT INDICATE ANY LIGHTING CONTROLS.
 PLEASE SEE AREAS OF STAIRS WHICH WILL ALSO BE NOTED IN
 ANOTHER NOTE FOR LIFE SAFETY AND EGRESS WHICH WILL BE
 REQUIRED TO CONTAIN A AUTOMATED DEVICE FOR OCCUPANTS
 WHERE SWITCHED.
 PLEASE VERIFY THE COVERAGE ON THE DEVICES AS NOTED AS
 THE COVERAGE IN LARGER BATHROOMS WHICH CONTAIN MULTIPLE
 STALLS AND ALSO HALLWAY AREAS WHICH INDICATE WALL
 MOUNTED DEVICES. PLEASE VERIFY IF THESE DEVICES AS
 SHOWN WILL PROVIDE THE COVERAGE AS NEEDED.
 PLEASE SEE 13-415.1.ABC.3 FOR TANDEM WIRING.
 PLEASE SEE 13-415.1.AB.1, PLEASE SEE MISSING ENERGY
 CALCULATIONS FOR BUILD OUT OF NEW CHURCH.
 PLEASE SEE 13-415.2 AS LIGHTING POWER DENSITIES ARE NOT
 INDICATED FOR ALL AREAS. PLEASE BE SURE TO CORRELATE
 THIS WITH THE ENERGY CALCULATIONS WHICH ARE TO BE
 SUBMITTED.
 * PLEASE SEE ALL OF CHAPTER 13.
 13-103.1.1.1
  
 4) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK NEEDS TO BE DECLARED. UNABLE TO VERIFY AT THIS
 TIME. BASED ON THE SCOPE OF ELECTRICAL WORK AND OTHER
 TRADES THE APPLIED VALUE IS LOW. PLEASE SEE FBC 108.3
 ADMIN SECTION.
  
 5) NOTE: PLEASE CORRELATE ELECTRICAL PLANS AND RISER
 FOR THE ELECTRICAL SERVICE AS SHOWN AND NOTED. PLEASE
 KNOW THERE ARE MANY NOTES ON PLANS TO VERIFY SERVICE,
 CONDUCTORS, AND FEEDERS ETC. PLEASE KNOW THAT ALL THE
 VERIFICATION IS REQUIRED BEFORE PERMIT ISSUANCE AND
 SHALL BE STATED ON PLANS AS REQUIRED FOR NEW BUILD
 OUT.
 PLEASE SEE RISER MENTIONS NEW PANELS, YET MDP MENTIONS
 PANELS AS EXISTING?
 THESE ARE PANELS WHICH WERE INSTALLED WITHOUT PERMITS,
 THEY SHALL BE INCLUDED AS *NEW* ON THESE RECORD SETS OF
 PLANS.
 PLEASE SEE MDP AND PLANS DO NOT MATCH AND PROVIDE
 ENOUGH INFORMATION FOR THE PANELS SHOWN FOR AIR
 HANDLING UNITS 1,2 AND 3.
 (PLEASE ALSO SEE THE NEXT COMMENT #6.)
 PLEASE CLARIFY SEVERAL PANELS ON PLANS WHICH MENTIONS
 *EXIST PANEL, NOT USED*? PLEASE SEE NO INFORMATION IS
 PROVIDED FOR THESE AND WHETHER OR NOT THESE PANELS ARE
 BEING REMOVED? PLEASE INDICATE IF THEY. PLEASE INDICATE
 IF THEY ARE BEING REMOVED, IF NOT THEN PLEASE INCLUDE
 ON PANEL SCHEDULES, PLANS, RISER ETC.
  
 6) NOTE: PLEASE CORRELATE ALL LOADS FOR AIR
 CONDITIONING EQUIPMENT. PLEASE SEE THE LOAD
 CALCULATIONS INDICATE A TOTAL OF 27KVA, YET THE PANEL
 SCHEDULE FOR PANEL *B* ALONE SHOWS 30KVA FOR A/C
 EQUIPMENT. PLEASE SEE THE LOAD ON CIRCUIT 1 ON THE MDP
 INDICATES 18KVA WHICH EXCEEDS THE RATING OF THE OVER
 CURRENT PROTECTION DEVICE AS SHOWN FEEDING AHU 1, 2 AND
 3?
 PLEASE SEE NOTE ABOVE AS INFORMATION FOR THE FEEDERS
 ETC TO THE AHU PANELS NEEDS TO BE SUBMITTED FOR REVIEW.
 NOT ENOUGH INFORMATION IS SUBMITTED FOR FULL REVIEW OF
 CODE COMPLIANCE.
 NEC 220, 424.3, 215.5, ETC.
 FBC 106.3.5.1.2, 106.1.2
 ** PLEASE ALSO VERIFY THE CONDENSING UNITS WHICH ARE
 SHOWN AS 3-PHASE AND AIR HANDLING UNITS AS SINGLE PHASE
 AND CONDENSING UNITS BEING SHOWN AS 3-PHASE WITH AIR
 HANDLING UNITS TO A SINGLE PHASE PANEL??
  
 7) NOTE: PLEASE PROVIDE ALL CIRCUITING ON PANEL
 SCHEDULES FOR ALL ROOMS AND AREAS WHICH THE CIRCUIT
 FEEDS. PLEASE SEE 408.4 AND COMMENTARY WHICH IS TAKEN
 FROM THE CODE.
 * CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 8) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR ALL
 EGRESS PATHS MEETING NFPA-101 7.8 AND 7.9.
 PLEASE SEE 7.8.1.3 AND 7.9.2.2 FOR STAIR AREAS.
 PLEASE SHOW LIGHTING LEVELS UNDER NORMAL AND EMERGENCY
 CONDITIONS.
 PLEASE ALSO SEE NOTE ABOVE WITH RESPECT TO CONTROLS FOR
 LIGHTING WHICH SHALL NOT LEAVE ANY ONE AREA IN TOTAL
 DARKNESS BASED ON THE SWITCHING OF A DEVICE, TRIPPING
 OF A BREAKER ETC.
 PLEASE SEE BUILDING COMMENTS FOR POSSIBLE 2ND MEANS OF
 EGRESS WHICH MAY BE REQUIRED. PLEASE KNOW ANY OTHER
 EGRESS PATH FROM SECOND FLOOR WHICH MAY APPEARS TO
 PLACE OCCUPANTS OVER A ROOF AREA AND THEN TO STAIRS ON
 THE OUTSIDE OF A BUILDING LEADING TO THE PUBLIC RIGHT
 OF WAY BELOW.
 PLEASE PROVIDE LIGHTING AS REQUIRED FOR THESE AREAS.
 PLEASE INDICATE NORMAL AND EMERGENCY FOR STAGE AREA AND
 STAIRS FROM THIS AREA.
  
 9) NOTE: PLEASE SEE 620.23, 620.24 WHICH REQUIRES
 DEDICATED CIRCUITS FOR ELEVATOR LIGHTS/RECEPTACLES AND
 ELEVATOR EQUIPMENT ROOMS. PLEASE SEE THAT SOME OF THIS
 IS DONE; HOWEVER PLEASE SEE THAT THESE CIRCUITS MAY NOT
 FEED ANY OTHER AREAS.
 PLEASE ALSO INDICATE AN EMERGENCY LIGHT FIXTURE OF SOME
 KIND IN ELEVATOR EQUIPMENT ROOM. 700.12E, 700.16, LS
 7.8, 7.9 AND STATE ELEVATOR CODE.
  
 10) NOTE: PLEASE INDICATE HOW LIGHTING AND RECEPTACLE
 LOADS ARE DERIVED. PLEASE SEE 220.3, 220.10, 220.11,
 220.13 ETC.
  
 11) NOTE: PLEASE PLACE INFORMATION ON SYMBOL LEGEND FOR
 HORN AND STROBE DEVICES FOR FBC 2004 ADA LEVELS.
 11-4.28.1, .2 AND .3(4).
 PLEASE SEE THERE ARE SEVERAL DIFFERENCES IN THE POWER
 PLANS COMPARED TO THE LIGHTING PLANS FOR DEVICE
 LOCATIONS.
 PLEASE ALSO SEE 11-4.28.1 AS THERE IS MANY LOCATIONS
 /ROOMS/AREAS WHICH DO NOT INDICATE ANY DEVICES.
  
 12) NOTE: PLEASE CORRELATE ALL ARCHITECTURAL SHEETS
 WITH THE ELECTRICAL PLANS AS THERE ARE PANELS NOTED ON
 OTHER SHEETS WHICH DO NOT CORRELATE WITH ELECTRICAL FOR
 SIZES ETC.
 FBC 106.1.2, 106.3.5.1.2.
  
 13) NOTE: PLEASE SEE TITLE BLOCKS WHICH CONTAINS
 *WHITE-OUT* OVER THE DRAFTING FIRM, PLEASE DO NOT USE
 WHITE OUT ON PLANS AND REMOVE THE TITLE BLOCKS WHEN
 REVISING PLANS.
 FS 471/481
  
 ** PLEASE COMPLETE, CORRELATE AND SUBMIT PLANS FOR
 REVIEW.
 ** PLEASE KNOW AT THIS TIME, BASED ON MANY ITEMS WHICH
 CAN NOT BE REVIEWED FOR CODE COMPLIANCE, THERE MAY VERY
 WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH ARE
 NOT ON THIS REVIEW AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-17 Cont ID  
Sent By dpalmer Date 2006-09-17 Time 15:59 Rev Time 0.00
Received By dpalmer Date 2006-09-17 Time 15:50 Sent To  
Notes
2006-09-17 00:00:00********UNSAT ************
  
 1) NOTE: PLEASE SUBMIT COMPLETE
 ELECTRICAL PLANS FOR THIS BUILDING AS
 THIS WAS A CHANGE IN OCCUPANCY WHICH WAS
 NEVER PERMITTED. PLEASE SEE PERMIT
 APPLICATIONS WHICH WERE PLACED ON "HOLD"
 AND/VOIDED IN 2005.
 PLEASE SEE PLANS MENTIONS PANELS SHOWN
 AS EXISTING, HOWEVER THESE WERE NEVER
 PERMITTED.
  
 ** PLEASE SEE 2004 FBC , 2002 NFPA-70,
 NFPA-72 2002, NFPA-101 2003.
  
 2) NOTE: PLEASE KNOW AS VALUE FOR SCOPE
 OF WORK WILL EXCEED $25K, THE SCOPE OF
 MUST BE DONE BY AN ARCHITECT OR ENGINEER
 AND A "DRAFTING FIRM" MAY NOT DO
 COMMERICAL PLANS OVER $25K.
 PLEASE CONTACT THE FLORIDA BOARD OF
 ARCHITECTS AND/OR LEGAL COUNSEL TO THE
 BOARD.
 FS 481.229.
  
 3) NOTE: PLEASE SEE PERMIT APPLICATION
 SHOWN MENTIONS ONLY REPLACING AN
 EXTERIOR DOORS, HOWEVER PLANS INDICATES
 BATH RMS ETC . PLEASE SEE NOTE ABOVE
 WHICH WILL ALSO REQUIRE COMPLETE PLANS
 FOR CHANGE.
 PLEASE SEE FBC AND NFPA-70, 101 ETC FOR
 ASSEMBLY OCCUPANCIES.
  
 ONE SET OF PLANS IS BEING RETAINED BY
 THIS OFFICE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2008-11-07 Cont ID  
Sent By mgonzale Date 2008-11-07 Time 10:23 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2008-11-07 10:22:51APPROVED WITH PROVISO.
 PROVIDE SILT FENCE AROUND SITE CONSTRUCTIONS AREA. MUST
 COMPLY WITH NPDES.
 MANNY GONZALEZ, PROJEC COORDINATOR, ENGINEERING
 SERVICES (561) 494-1085

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2008-07-18 Cont ID  
Sent By rchokshi Date 2008-07-18 Time 11:03 Rev Time 0.00
Received By rchokshi Date 2008-07-18 Time 10:55 Sent To B
Notes
2008-07-18 10:56:55FAILED FOR FOLLOWING REASONS:
  
  
 1. PLEASE SHOW ON DRAWING THE DUMPSTER LOCATION WITH
 THE MINIMUM DIMENSIONS OF THE DUMPSTER PAD APPROVED BY
 THE CITY.
 OUR RESPONSE :O.K
  
 2. DUMPSTER DIMENSIONS MUST MEET MINIMUM LENGTH, WIDTH,
 & HEIGHT PER CITY STANDARDS.
  
 ADUMPSTER SKETCH WITH MINIMUM DIMENSION CAN BE
 FOUND AT THE CITY'S WEB PAGE AT
 HTTP://EXCITINGCITY.COM/ENGINEERING/ENG_STANDARDS.HTM
 IF YOU CAN NOT MEET MINIMUM DIMENSIONS, NEED A LETTER
 FROM SANITATION DEPT APPROVING ALTERNATE ARRANGEMENT.
  
 OUR RESPONSE: O.K.
  
 3.DUMPSTER LOCATIONMUST BE ACCESSIBLE TO CITY
 COLLECTION TRUCK FOR LOADING/UNLOADING DUMPSTER.
  
 OUR RESPONSE: O.K.
  
 YOU STILL NEED TO PROVIDE THE RESPONSE FOR THE
 FOLLOWING ITEMS 4 &5 ASKED BY JONATHAN BRAMLEY,
 DIRECTOR
  
 4. SHT 1 PROVIDES ADDITIONAL INFORMATION ON THE
 PROPOSED PARKING LAYOUT.AS REFERENCED ABOVE IT IS NOT
 CLEAR THAT THE CORRECT DUMPSTER ENCLOSURE CAN BE
 PROVIDED IN THE LOCATION THAT IS SUGGESTED.
  
 5. PLEASE PROVIDE EXISTING GRADES AND CURRENT FLOW
 LINES ON THE EXISTING SITE DETAIL.ON THE PROPOSED
 LAYOUT PLEASE SHOW EXISTING GRADES OR FINAL GRADES,IF
 THEY WILL CHANGE, TO DEMONSTRATE THAT ALL FLOWS WILL
 REMAIN ON SITE AND FLOW IS INTO THE IMPOUND AREAS TO
 SUPPORT THE PROPOSED DRAINAGE STATEMENT.
  
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION
 NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
  
 PLEASE RE SPOND ABOVE COMMENTSIN DETAIL TO EXPEDITE
 YOUR PERMIT
  
 JONATHAN BRAMLEY - FOR RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2008-02-05 Cont ID  
Sent By jbramley Date 2008-02-05 Time 15:22 Rev Time 0.00
Received By jbramley Date 2008-02-05 Time 14:55 Sent To  
Notes
2008-02-05 15:22:30FAILED FOR FOLLOWING REASONS:
  
  
 1. PLEASE SHOW ON DRAWING THE DUMPSTER LOCATION WITH
 THE MINIMUM DIMENSIONS OF THE DUMPSTER PAD APPROVED BY
 THE CITY.
 2. DUMPSTER DIMENSIONS MUST MEET MINIMUM LENGTH, WIDTH,
 & HEIGHT PER CITY STANDARDS.
 ADUMPSTER SKETCH WITH MINIMUM DIMENSION CAN BE
 FOUND AT THE CITY'S WEB PAGE AT
 HTTP://EXCITINGCITY.COM/ENGINEERING/ENG_STANDARDS.HTM
 IF YOU CAN NOT MEET MINIMUM DIMENSIONS, NEED A LETTER
 FROM SANITATION DEPT APPROVING ALTERNATE ARRANGEMENT.
 3.DUMPSTER LOCATIONMUST BE ACCESSIBLE TO CITY
 COLLECTION TRUCK FOR LOADING/UNLOADING DUMPSTER. 4. SHT
 1 PROVIDES ADDITIONAL INFORMATION ON THE PROPOSED
 PARKING LAYOUT.AS REFERENCED ABOVE IT IS NOT CLEAR
 THAT THE CORRECT DUMPSTER ENCLOSURE CAN BE PROVIDED IN
 THE LOCATION THAT IS SUGGESTED.
 5. PLEASE PROVIDE EXISTING GRADES AND CURRENT FLOW
 LINES ON THE EXISTING SITE DETAIL.ON THE PROPOSED
 LAYOUT PLEASE SHOW EXISTING GRADES OR FINAL GRADES,IF
 THEY WILL CHANGE, TO DEMONSTRATE THAT ALL FLOWS WILL
 REMAIN ON SITE AND FLOW IS INTO THE IMPOUND AREAS TO
 SUPPORT THE PROPOSED DRAINAGE STATEMENT.
  
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION
 NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
  
 PLEASE RE SPOND ABOVE COMMENTSIN DETAIL TO EXPEDITE
 YOUR PERMIT
  
 JONATHAN BRAMLEY - FOR RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2008-08-05 Cont ID  
Sent By mawillia Date 2008-08-05 Time 15:08 Rev Time 0.00
Received By mawillia Date 2008-08-05 Time 14:31 Sent To  
Notes
2008-08-05 14:49:20*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;PLAN SHEETS 1.2, 5.1, AND 6.1 WHICH
 PEVIOUSLY STAMPED ON 2/13/08 WERE RESTAMPED, INITIALED,
 AND DATED.E-2, E-3, E-4, AND E-5 (PREVIOUSLY STAMPED)
 NEEDED NO RE-STAMP.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-02-13 Cont ID  
Sent By mawillia Date 2008-02-13 Time 16:45 Rev Time 0.00
Received By mawillia Date 2008-02-13 Time 16:08 Sent To  
Notes
2008-02-13 16:44:40*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;PLAN SHEETS 1.2, 5.1, 6.1, E-2, E-3,
 E-4, AND E-5 WERE STAMPED, INITIALED, AND DATED.
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-10-31 Cont ID  
Sent By mawillia Date 2007-10-31 Time 17:54 Rev Time 0.00
Received By mawillia Date 2007-10-31 Time 16:22 Sent To  
Notes
2007-10-31 17:54:47*****UNSAT*****
  
 PLEASE ACKNOWLEDGE THE FOLLOWING COMMENTS TAKEN FROM
 PREVIOUS FIRE PLAN REVIEW:
  
  
 01.)FLORIDA FIRE PREVENTION CODE, 2004 EDITION SHALL
 BE REFERENCED. ADD TO CODE SUMMARY NOTES, SHEET 1.1
  
 03.)AN ADDRESS IS REQUIRED ON THE BUILDING OF NO LESS
 THAN 6" IN HEIGHT AND 1" IN WIDTH.ON SHEET 1.2, THE
 MINIMUM WIDTH (STROKE) OF THE NUMBER IS INCORRECTLY
 DETAILED
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-04-03 Cont ID  
Sent By mawillia Date 2007-04-03 Time 16:46 Rev Time 0.00
Received By mawillia Date 2007-04-03 Time 16:06 Sent To  
Notes
2007-04-03 16:38:51*****DENIED*****
  
 PLEASE ACKNOWLEDGE THE FOLLOWING COMMENTS TAKEN FROM
 10/24/2006 FIRE PLAN REVIEW:
  
  
 01.)NFPA 101, 2003 EDITION AND FLORIDA FIRE
 PREVENTION CODE, 2004 EDITION SHALL BE REFERENCED. ADD
 TO CODE SUMMARY NOTES, SHEET 1/5
  
 02.)STRUCTURES UNDERGOING CONSTRUTION, ALTERATION,
 AND DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
 ADD TO SHEET 1
  
 03.)AN ADDRESS IS REQUIRED ON THE BUILDING OF NO LESS
 THAN 6" IN HEIGHT AND 1" IN WIDTH.PLEASE INDICATE
 LOCATION OF THE ADDRESS ON THE APPROPIATE ELEVATION
 FRONTING BROADWAY AVENUE.PLEASE DISPLAY ON THE
 APPROPIATE EXTERIOR ELEVETION
  
  
 08.)PANIC HARDWARE IS REQUIRED ON EXIT DOORS SERVING
 AN OCCUPANT LOAD GREATER THAN ONE HUNDRED.PLEASE
 ACKNOWLEDGE
  
 09.)PLEASE INDICATE THE MINIMUM INTERIOR FINISH
 CLASSIFICATIONFOR WALLS AND CEILING IN TERMS OF CLASS
 A, B, OR C IN ACCORDANCE WITH NFPA 101, 10.2.PLEASE
 ACKNOWLEDGE
  
 10.)CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES).
 ADD TO SHEET 1
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM EAS ADDRESSED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-24 Cont ID  
Sent By mawillia Date 2006-10-24 Time 10:11 Rev Time 0.00
Received By mawillia Date 2006-10-24 Time 10:11 Sent To  
Notes
2006-10-24 11:03:23*****DENIED*****
  
  
  
  
 01.)NFPA 101, 2003 EDITION AND FLORIDA FIRE
 PREVENTION CODE, 2004 EDITION SHALL BE REFERENCED.
  
 02.)STRUCTURES UNDERGOING CONSTRUTION, ALTERATION,
 AND DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.)AN ADDRESS IS REQUIRED ON THE BUILDING OF NO LESS
 THAN 6" IN HEIGHT AND 1" IN WIDTH.PLEASE INDICATE
 LOCATION OF THE ADDRESS ON THE APPROPIATE ELEVATION
 FRONTING BROADWAY AVENUE.
  
 04.)WHAT IS THE OCCUPANCY CLASSIFICATION (I.E.
 ASEMBLY, BUSINESS, EDUCATIONAL) FOR THIS BUILDING?
  
 05.)IS THE BUILDING PROTECTED BY FIRE PROTECTION
 SYSTEMS SUCH AS A FIRE SPRINKLER AND/OR FIRE ALARM
 SYSTEM?
  
 06.)IN REFERENCE TO #5, IF THE SCOPE OF THE INTERIOR
 BUILDOUT REQUIRES MODIFICATION OF THE FIRE FIRE
 PROTECTION SYSTEM, SEPARATE PERMIT AND PLANS ARE TO BE
 SUBMITTED FOR REVIEW.
  
 07.)IN ADDITION TO THE FIRE EXTINGUISHERS SHOWN ON
 THE LIFE SAFETY SHEETS, PLEASE INDICATE THE LOCATION OF
 EXIT LIGHTS, EMERGENCY LIGHTS, AND COMMON PATH TRAVEL
 DISTANCES TO THE EXITS.
  
 08.)PANIC HARDWARE IS REQUIRED ON EXIT DOORS SERVING
 AN OCCUPANT LOAD GREATER THAN ONE HUNDRED.
  
 09.)PLEASE INDICATE THE MINIMUM INTERIOR FINISH
 CLASSIFICATIONFOR WALLS AND CEILING IN TERMS OF CLASS
 A, B, OR C IN ACCORDANCE WITH NFPA 101, 10.2.
  
 10.)CONSTRUTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES).
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-10-15 Cont ID  
Sent By adarroug Date 2008-10-15 Time 11:55 Rev Time 0.00
Received By adarroug Date 2008-10-15 Time 11:55 Sent To  
Notes
2008-10-16 16:18:50TO "COMM" BD#49
2008-10-15 11:55:33WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-07-11 Cont ID  
Sent By adarroug Date 2008-07-11 Time 09:46 Rev Time 0.00
Received By adarroug Date 2008-07-11 Time 09:46 Sent To  
Notes
2008-07-11 09:46:59TO "COMM" BD#29

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-01-10 Cont ID  
Sent By mmiller Date 2008-01-10 Time 17:06 Rev Time 0.00
Received By mmiller Date 2008-01-10 Time 17:06 Sent To  
Notes
2008-01-10 17:06:33SENT TO COMMERICAL BOARD # 62

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-20 Cont ID  
Sent By adarroug Date 2007-09-20 Time 08:09 Rev Time 0.00
Received By adarroug Date 2007-09-20 Time 08:09 Sent To  
Notes
2007-10-12 16:16:54TO "COMM" BD#54
2007-09-20 08:10:05WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-06 Cont ID  
Sent By adarroug Date 2007-03-06 Time 11:56 Rev Time 0.00
Received By adarroug Date 2007-03-06 Time 11:56 Sent To  
Notes
2007-03-08 11:55:44TO "COMM" BD#27
2007-03-06 11:56:47WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-24 Cont ID  
Sent By mawillia Date 2006-10-24 Time 11:11 Rev Time 0.00
Received By mawillia Date 2006-09-09 Time 19:22 Sent To  
Notes
2006-09-15 00:00:00TO "COMM" BD#26
2006-09-09 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2008-11-02 Cont ID  
Sent By rregueir Date 2008-11-02 Time 14:23 Rev Time 0.00
Received By rregueir Date 2008-11-02 Time 14:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2008-07-30 Cont ID  
Sent By rregueir Date 2008-07-30 Time 13:16 Rev Time 0.00
Received By rregueir Date 2008-07-30 Time 09:02 Sent To  
Notes
2008-07-30 13:16:48REVIEW #: 5TH
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. OK
  
 2. PAGE M.1 OUTDOOR AIR CALCULATIONS TABLE STATES THAT
 THESE CALCULATIONS ARE BASED ON ?TABLE 2 OF ASHRAE
 62-04.? THERE IS NO SUCH TABLE TO BE FOUND IN ASHRAE
 62.1-2004 EDITION. OUTSIDE AIR CALCULATIONS ARE TO BE
 BASED ON FBCM TABLE 403.3 OR ASHRAE 62.1-04 IN
 ACCORDANCE WITH FBCM 403.4. IF ASHRAE 62.1-04 IS TO BE
 USED FOR VENTILATION, THE VENTILATION RATE PROCEDURE
 SHALL BE DETERMINED IN ACCORDANCE WITH SECTIONS 6.2
 THROUGH 6.2.9. THE CALCULATIONS FOR THE REQUIRED
 VENTILATION RATES SHALL BE DETERMINED BASED ON THE
 VALUES LISTED IN TABLE 6-1, INCLUDING ANTICIPATED
 OCCUPANT LOADS. OCCUPANT LOADS SHALL NOT BE BASED ON
 ARCHITECTURAL PLANS. THEY SHALL BE BASED ON THE
 OCCUPANCY CATEGORY AND OCCUPANT DENSITY SHOWN ON TABLE
 6-1.
  
 THE RATES SHOWN ON THE TABLE ON PAGE M.1 DO NOT
 CORRESPOND WITH TABLE 6-1 OF ASHRAE 62.1-04. EXAMPLE:
 AHU #1 SERVES 1 ? CONFERENCE ROOMS AND A MEETING HALL.
 SEE ?CONFERENCE/MEETING? UNDER THE GENERAL CATEGORY ON
 TABLE 6-1.
  
 NOTE: THE COOLING LOADS OF THE PROPOSED A/C SYSTEMS IS
 INCREASING SIGNIFICANTLY BASED ON REDESIGNED OUTSIDE
 AIR BEING FED THROUGH THESE SYSTEMS. PLEASE PROVIDE
 COOLING LOAD CALCULATIONS FOR EACH SYSTEM IN ACCORDANCE
 WITH FBCB 13-407.1.ABC.1.
  
 3. OK
  
 4. OK
  
 5. OK
  
 6.
 A) AN ENGINEERING SHEET FOR THE ROOFTOP CONDENSER
 STANDS HAS BEEN PROVIDED. HOWEVER, THERE IS NO
 INFORMATION ON THIS SHEET REGARDING ATTACHMENT OF THE
 STAND TO THE STRUCTURE. PAGE M.1 SHOWS A ROOF STAND
 WITH THE STATEMENT ?PRE-ENGINEERED EQUIPMENT RACK.? IF
 THIS IS PRE ENGINEERED, THEN A PRODUCT APPROVAL MUST BE
 PROVIDED AND THIS PRODUCT APPROVAL SHALL BE APPROVED IN
 WRITING BY THE DESIGNER OF RECORD IN ACCORDANCE WITH
 FBCB 106.3.3. FOR MORE INFORMATION ON THE FLORIDA
 PRODUCT APPROVAL SYSTEM PLEASE VISIT
 WWW.FLORIDABUILDING.ORG.
 B) OK
  
 7. RTU FLOAT SWITCH IS OK. HOWEVER, MEANS AND LOCATION
 OF CONDENSATE DISPOSAL IS STILL NOT SHOWN ON PLANS AS
 PREVIOUSLY REQUESTED IN ACCORDANCE WITH FBCM 307.2.
  
 8. OK EXCEPT, SEE COMMENT #2 ABOVE FOR COOLING LOAD
 CALCULATIONS WHICH SHALL BE APPENDED TO THE ENERGY
 CALCULATIONS IN ACCORDANCE WITH FBCB 13-407.1.ABC.1.
  
 9. OK
  
 NOTE:F.S. 553.80(2)(B) WITH RESPECT TO EVALUATION OF
 DESIGN PROFESSIONALS' DOCUMENTS, IF A LOCAL GOVERNMENT
 FINDS IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH
 THE FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW.
  
 THIS SERVES ONLY AS A WARNING AT THIS TIME. SHOULD ANY
 SUBSEQUENT REVIEW FAIL FOR ANY OF THE PREVIOUSLY STATED
 CODE SECTION, A FINE OF FOUR TIMES THE PLAN REVIEW FEE
 SHALL BE IMPOSED. ONE SET OF PLANS IS BEING RETAINED AS
 A RECORD OF PREVIOUS CODE VIOLATIONS SHOULD IT BECOME
 NECESSARY TO IMPOSE THE FINE UNDER FS 553.80(2)(B)
  
 PLEASE RESPOND TO EACH COMMENT IN WRITING WITH A
 DESCRIPTION OF HOW EACH COMMENT HAS BEEN ADDRESSED AS
 WELL AS WHERE THE INFORMATION CAN BE FOUND.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-02-08 Cont ID  
Sent By rregueir Date 2008-02-08 Time 15:49 Rev Time 0.00
Received By rregueir Date 2008-02-07 Time 16:50 Sent To  
Notes
2008-02-08 15:49:34REVIEW #: 4TH
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 NOTE: RESPONSE LETTER FROM GORDON BUCK INDICATES THE
 MECHANICAL PROJECT HAS BEEN COMPLETELY REDESIGNED.
 THEREFORE, A COMPLETE REVIEW OF THE MECHANICAL SYSTEM
 IS NECESSARY AND ADDITIONAL NEW COMMENTS ARE POSSIBLE.
  
 1. BATHROOMS HAVE BEEN RECONFIGURED FROM WHAT WAS SHOWN
 ON PREVIOUS PLANS. THE WOMEN?S RESTROOM DOES NOT HAVE
 ADEQUATE EXHAUST. THE FLOOR PLAN ON PG M.2 NOW SHOWS
 THE WOMEN?S RESTROOM WITH 4 WATER CLOSETS. FLOOR PLAN
 ALSO SHOWS AN EXHAUST FAN PROVIDING 150 CFM OF EXHAUST.
 A MINIMUM OF 50 CFM PER WATER CLOSET IS REQUIRED IN
 ACCORDANCE WITH FBC, M TABLE 403.3. AS SUCH THE WOMEN?S
 RESTROOM REQUIRES A MINIMUM OF 200 CFM OF EXHAUST.
 ALSO, BOTH THE MEN?S AND WOMEN?S RESTROOMS SHOW SUPPLY
 AIR IN EXCESS OF THE EXHAUST AIR. ALL AIR SUPPLIED TO
 THE RESTROOMS SHALL BE EXHAUSTED IN ACCORDANCE WITH
 FBC, M 403.2.1.
  
 2. OUTSIDE AIR CALCULATIONS ARE NOT IN CONFORMANCE WITH
 THE REQUIREMENTS OF TABLE 403.3. THE FOLLOWING ARE
 EXAMPLES ONLY. THE CALCULATIONS FOR THE ENTIRE BUILDING
 SHOULD BE CHECKED FOR ACCURACY PRIOR TO RESUBMITTAL.
 -AHU #1: THIS UNIT SERVES TWO CONFERENCE ROOMS AND A
 MEETING HALL. FBC, M TABLE 403.3 PUTS THE OCCUPANT LOAD
 IN THESE AREAS AT 50 PEOPLE PER 1000 SQUARE FEET. WITH
 ONE OF THE CONFERENCE ROOMS DIVIDED IN HALF (BECAUSE IT
 IS SERVED BY AHU 1 AND AHU 3, THE TOTAL SQUARE FEET OF
 THESE THREE AREAS IS 402 SF. AT 50/1000 THESE AREAS
 HAVE AN OCCUPANT LOAD OF 20 PEOPLE WITH AN OUTSIDE AIR
 RATE OF 20 CFM PER PERSON FOR A TOTAL REQUIRED OUTSIDE
 AIR VOLUME OF 400 CFM.
 -AHU #2 AND AHU #4: THE OCCUPANT LOAD OF THE ASSEMBLY
 AREAS ARE TO BE CALCULATED AT 150 PEOPLE PER 1000
 SQUARE FEET. WHERE SPACES HAVING DIFFERENT VENTILATION
 RATE REQUIREMENTS ARE SERVED BY A COMMON VENTILATION
 SYSTEM, THE RATIO OF OUTDOOR AIR TO TOTAL SUPPLY AIR
 FOR THE SYSTEM SHALL BE DETERMINED BASED ON THE SPACE
 HAVING THE LARGEST OUTDOOR AIR REQUIREMENT IN
 ACCORDANCE WITH FBC, M 403.3.2. THEREFORE, THE ENTIRE
 SPACE SERVED BY AHU #2 AND AHU #4 SHALL BE CALCULATED
 AT THE RATE STATED ABOVE. ACCORDING TO THE TABLE ON PG
 M.1, THESE UNITS SERVE A COMBINED SPACE OF 4665 SQUARE
 FEET FOR A TOTAL OCCUPANT LOAD OF 700 PEOPLE. AT A RATE
 OF 15 CFM PER PERSON THE TOTAL REQUIRED VOLUME OF
 10,500 CFM. AHU #2 AND AHU #4 ARE NOT CAPABLE OF
 SUPPLYING THESE QUANTITIES EVEN AT 100% OUTSIDE AIR.
 NOTE: THERE ARE DIFFERENT DESIGN PARAMETERS AND SYSTEM
 CONFIGURATIONS WHICH COULD SIGNIFICANTLY REDUCE THE
 AMOUNT OF OUTSIDE AIR REQUIRED FOR THESE SPACES. THESE
 NUMBERS ARE BASED SOLELY ON THE INFORMATION AND SYSTEMS
 SHOWN ON THE PLANS. PLEASE CALL IF THE DESIGNERS WOULD
 LIKE TO DISCUSS ALTERNATIVES OR OPTIONS.
  
 3. AHU #2, AHU #4 AND PU #6 AT 5 TONS ARE CAPABLE OF
 PRODUCING CFM IN EXCESS OF 2,000 AND THEREFORE A FAN
 SHUT-DOWN BY SMOKE DETECTOR IS STILL REQUIRED ON THESE
 SYSTEMS IN ACCORDANCE WITH FBC, M 606.2.1.
  
 4. OK. FLOOR PLAN NOW SHOWS DUCTED RETURNS, THUS
 ELIMINATING PLENUM CLOSETS.
  
 5. PG M.3: PRIVATE BATH IS STILL MISSING EXHAUST AS
 REQUIRED IN ACCORDANCE WITH FBC, M TABLE 403.3.
  
 6. A) CONDENSING UNITS SHOWN ON ROOF INSTALLED ON
 EXISTING A/C STANDS. AS STATED IN PREVIOUS REVIEW, WORK
 DONE WITHOUT A PERMIT WILL NOT BE CONSIDERED EXISTING.
 THEREFORE, PRE-ENGINEERED A/C STANDS ARE REQUIRED TO
 HAVE PRODUCT APPROVAL IN ACCORDANCE WITH FAC RULE
 9B-72. PROVIDE PRODUCT APPROVAL DOCUMENTATION, REVIEWED
 AND APPROVED IN WRITING BY THE PROJECT DESIGN
 PROFESSIONAL IN ACCORDANCE WITH FBC 106.3.3. ALSO, PU
 #6 IS INSTALLED ON A ROOF CURB. PROVIDE DETAIL WITH
 WIND LOAD CALCULATIONS FOR BUILDING PLAN REVIEW TO SHOW
 HOW CURB IS TO BE ATTACHED TO STRUCTURE AND HOW UNIT IS
 TO BE ATTACHED TO CURB. MECHANICAL EQUIPMENT,
 APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES
 ON THE EQUIPMENT AND THE SUPPORTS AS DETERMINED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING PER
 FBC, M 301.13.
 NOTE: THIS REQUIREMENT INCLUDES THE ROOFTOP PACKAGE
 UNIT ITSELF, WHICH MUST ALSO BE DESIGNED AND TESTED TO
 WITHSTAND WIND PRESSURES AS REQUIRED BY THIS SECTION.
 B) CU #4, CU #5 AND PU #6 ARE LOCATED ON SECOND STORY
 ROOF. HOW IS THIS EQUIPMENT TO BE ACCESSED FOR SERVICE?
 WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE
 INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT
 EXCEEDING 16 FEET, SUCH ACCESS SHALL BE PROVIDED BY A
 PERMANENT APPROVED MEANS OF ACCESS, THE EXTENT OF WHICH
 SHALL BE FROM GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND
 APPLIANCES? LEVEL SERVICE SPACE IN ACCORDANCE WITH FBC,
 M 306.5. PLEASE SEE THIS CODE SECTION FOR ADDITIONAL
 SPECIFIC REQUIREMENTS. PROVIDE DETAIL ON PLANS SHOWING
 COMPLIANCE WITH THIS SECTION.
  
 7. THIS COMMENT WAS NOT ADDRESSED. ALSO, ROOFTOP
 PACKAGE UNIT REQUIRES AUXILIARY DRAIN PROTECTION IN
 ACCORDANCE WITH FBC, M 307.2.3. A FLOAT SWITCH INSIDE
 THE UNIT ON THE PRIMARY DRAIN PAN WILL MEET THIS
 REQUIREMENT.
  
 8. COMPLETION OF PROCEDURES DEMONSTRATING COMPLIANCE
 WITH THIS CODE FOR COMMERCIAL BUILDINGS SHALL BE SIGNED
 AND SEALED BY AN ARCHITECT OR ENGINEER LICENSED TO
 PRACTICE IN THE STATE OF FLORIDA IN ACCORDANCE WITH FBC
 13-103.1.1.1.
  
 NEW COMMENT: GENERAL NOTE #2 ON PG M.1 STATES THAT
 OUTSIDE AIR IS PROVIDED BY OARTU 1 & 2. THIS NOTE IS
 NOT APPLICABLE TO THIS JOB AT THIS TIME AND SHOULD BE
 REMOVED FROM PLANS. FBC 106.1.1.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-11-06 Cont ID  
Sent By rregueir Date 2007-11-06 Time 13:33 Rev Time 0.00
Received By rregueir Date 2007-11-05 Time 16:29 Sent To  
Notes
2007-11-06 13:33:12REVIEW #: 3RD
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 *PLEASE NOTE* A FINE OF FOUR TIMES THE PERMIT FEE WAS
 ISSUED FOR MECHANICAL, ELECTRICAL AND PLUMBING FOR WORK
 DONE WITHOUT A PERMIT. PLEASE PROVIDE DETAILED
 INFORMATION REGARDING WORK DONE WITHOUT PERMITS AS WELL
 AS ALL WORK TO BE DONE UNDER THIS PERMIT. THERE HAS
 BEEN A CHANGE OF OCCUPANCY UNDERTAKEN WITHOUT PERMITS.
 THEREFORE THE NOTES ON THE PLANS REGARDING THE EXISTING
 CHURCH ARE NOT ACCURATE. THERE IS NO ASSEMBLY OCCUPANCY
 AT THIS LOCATION EXISTING OR OTHERWISE PRIOR TO THE
 ISSUANCE OF A CERTIFICATE OF OCCUPANCY BY THE BUILDING
 OFFICIAL. THE ISSUANCE OF PERMITS AND THE SUCCESSFUL
 COMPLETION OF ALL REQUIRED INSPECTIONS ARE REQUIRED
 BEFORE A CERTIFICATE OF OCCUPANCY CAN BE ISSUED.
  
 NOTE: ALL A/C SYSTEMS IN THIS PROPOSED BUILDING WERE
 INSTALLED WITHOUT A PERMIT. UNTIL THEY HAVE BEEN
 PERMITTED, INSPECTED AND PASSED, THEY ARE NOT TO BE
 CONSIDERED EXISTING. REMOVE NOTATIONS FROM PLANS
 CLAIMING THE MECHANICAL SYSTEMS ARE EXISTING. PLEASE
 PROVIDE THE REQUIRED DETAILS AND DOCUMENTATION FOR
 NEWLY INSTALLED A/C SYSTEMS. INCLUDE EQUIPMENT
 SCHEDULES, DUCT SIZES, CFMS AT ALL DIFFUSERS AND
 REGISTERS. SEE FBC,M 106.3.5.1.4.
  
 NOTE: ALL A/C SYSTEMS WILL BE REVIEWED AS NEW. HOWEVER,
 THE REVIEW WILL BE LIMITED BASED ON THE SMALL AMOUNT OF
 INFORMATION PROVIDED. ADDITIONAL COMMENTS ARE LIKELY
 ONCE ALL REQUIRED INFORMATION IS PROVIDED.
  
 1. PG M.1: BATHROOM EXHAUST, HVAC NOTE # 6 INDICATES
 THAT BATH EXHAUST FANS ARE 100 CFM. THE WOMEN?S
 BATHROOM HAS 3 WATER CLOSETS AND THE MEN?S BATHROOM HAS
 2 WATER CLOSETS AND 2 URINALS. THESE SPACES ARE
 REQUIRED TO HAVE EXHAUST RATES OF 50 CFM PER WATER
 CLOSET OR URINAL IN ACCORDANCE WITH FBC,M TABLE 403.3.
 THE WOMEN?S RESTROOM REQUIRES MIN. 150 CFM AND THE
 MEN?S RESTROOM REQUIRES MIN. 200 CFM. SHOW HOW THESE
 FANS ARE TO BE CONTROLLED, THE SIZE AND LOCATION OF
 EXHAUST DUCTS AND THE DISCHARGE LOCATION. SHOW
 COMPLIANCE WITH FBC,M 401.3, 401.5, 401.6, 403.2.1(3).
  
 2. PG M.1: OUTDOOR AIR CALCULATIONS SCHEDULE SHOWN ON
 PLANS DOES NOT ACTUALLY CONTAIN ANY CALCULATIONS. IT IS
 MERELY A LISTING OF THE REQUIREMENTS OF FBC,M TABLE
 403.3. IT PROVIDES NO INFORMATION REGARDING THE AMOUNT
 OF OUTSIDE AIR REQUIRED FOR EACH LOCATION OR THE AMOUNT
 OF OUTSIDE AIR BEING PROVIDED FOR EACH AREA. SHOW THE
 CALCULATIONS BASED ON THE ACTUAL OCCUPANT LOAD OF THESE
 SPACES AND THE AMOUNT OF OUTSIDE AIR PROVIDED. ALSO,
 PROVIDE AN AIR BALANCE SCHEDULE SHOWING WHETHER OR NOT
 THE BUILDING IS PRESSURIZED WITH RESPECT TO THE
 OUTDOORS IN ACCORDANCE WITH FBC 13-409.1.ABC.2.
  
 3. PG M.1: AHU?S IN CLOSET #2 ARE BOTH SHOWN SHARING A
 RETURN PLENUM CLOSET. WHERE MULTIPLE AIR-HANDLING
 SYSTEMS SHARE COMMON RETURN AIR PLENUMS WITH A COMBINED
 DESIGN CAPACITY GREATER THAN 2,000 CFM, THE RETURN AIR
 AND SUPPLY AIR SYSTEM SHALL BE PROVIDED WITH SMOKE
 DETECTORS IN ACCORDANCE WITH FBC,M 606.2.1. SEE FBC,M
 606.2.2.
 ANY OF THE OTHER SMOKE DETECTORS SHALL BE INSTALLED IN
 ANY OF THE OTHER SUPPLY AIR SYSTEMS IN THE BUILDING
 WITH A DESIGN CAPACITY GREATER THAN 2,000 CFM IN THE
 SUPPLY AIR DUCT. FBC,M 606.2.1.
 4. WHAT TYPE OF DOORS ARE TO BE USED ON THE A/C CLOSETS
 WHICH ARE BEING USED AS PLENUMS? MATERIALS EXPOSED
 WITHIN PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED
 IN ACCORDANCE WITH ASTM E 84. FBC,M 602.2.1. SHOW A
 DOOR SCHEDULE OR PROVIDE SOME INDICATION ON PLANS THAT
 DOORS USED AS PART OF PLENUM ENCLOSURES ARE IN
 COMPLIANCE WITH THIS SECTION.
  
 5. PG M.2: FLOOR PLAN SHOWS TWO SEPARATE TOILET ROOMS.
 PROVIDE VENTILATION IN THESE AREAS IN ACCORDANCE WITH
 FBC,M TABLE 403.3. SEE COMMENT #1 FOR ADDITIONAL
 REQUIREMENTS.
  
 6. LOCATIONS AND METHODS OF INSTALLATION FOR OUTDOOR
 MECHANICAL EQUIPMENT ARE NOT SHOWN ON PLANS. SHOW THE
 LOCATION OF ALL OUTDOOR EQUIPMENT ALONG WITH MEANS OF
 INSTALLATION WHICH IS IN COMPLIANCE WITH FBC,M 301.13
 AND FBC SEC.1609.
  
 7. SHOW MEANS AND LOCATION OF CONDENSATE DISPOSAL IN
 COMPLIANCE WITH FBC,M 307.2, INCLUDING MEANS OF
 AUXILIARY OR SECONDARY DRAIN PROTECTION IN ACCORDANCE
 WITH FBC,M 307.2.3. NOTE: ALL CONDENSATE DRAIN
 MATERIALS USED IN THE PLENUM CLOSETS SHALL BE
 NON-COMBUSTIBLE IN COMPLIANCE WITH FBC,M 602.2.1.
  
 8. CHANGE OF OCUPANCY: BUILDINGS HAVING A CHANGE OF
 OCCUPANCY THAT WERE PERMITTED AFTER MARCH 15, 1979,
 SHALL COMPLY WITH THE REQUIREMENTS OF SUBCHAPTER 13-4
 FOR COMMERCIAL APPLICATIONS. WHERE THE EFFICIENCY OF A
 BUILDING COMPONENT IS UNKNOWN, IT SHALL BE DETERMINED
 IN ACCORDANCE WITH THE CRITERIA SPECIFIED IN SECTION
 101.4.2.1. SEE FBC 13-101.3. PROVIDE AN ENERGY CODE
 COMPLIANCE FORM IN ACCORDANCE WITH FBC 13-400.0.ABC.
 SEE ALSO FBC 13-400.3.ABC.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-03-27 Cont ID  
Sent By rregueir Date 2007-03-27 Time 10:47 Rev Time 0.00
Received By rregueir Date 2007-03-27 Time 10:39 Sent To  
Notes
2007-03-27 10:46:54PLEASE SEE PREVIOUS MECHANICAL REVIEW COMMENTS. NO
 INFORMATION HAS BEEN PROVIDED REGARDING THE SCOPE OF
 MECHANICAL WORK. NO ENERGY CALCULATIONS HAVE BEEN
 PROVIDED.
  
 *PLEASE NOTE* A FINE OF FOUR TIMES THE PERMIT FEE WAS
 ISSUED FOR MECHANICAL, ELECTRICAL AND PLUMBING FOR WORK
 DONE WITHOUT A PERMIT. PLEASE PROVIDE DETAILED
 INFORMATION REGARDING WORK DONE WITHOUT PERMITS AS WELL
 AS ALL WORK TO BE DONE UNDER THIS PERMIT. THERE HAS
 BEEN A CHANGE OF OCCUPANCY UNDERTAKEN WITHOUT PERMITS.
 THEREFORE THE NOTES ON THE PLANS REGARDING THE EXISTING
 CHURCH ARE NOT ACCURATE. THERE IS NO ASSEMBLY OCCUPANCY
 AT THIS LOCATION EXISTING OR OTHERWISE PRIOR TO THE
 ISSUANCE OF A CERETIFICATE OF OCCUPANCY BY THE BUILDING
 OFFICIAL. THE ISSUANCE OF PERMITS AND THE SUCCESSFUL
 COMPLETION OF ALL REQUIRED INSPECTIONS ARE REQUIRED
 BEFORE A CERTIFICATE OF OCCUPANCY CAN BE ISSUED.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-17 Cont ID  
Sent By pkrauss Date 2006-10-17 Time 15:07 Rev Time 0.00
Received By pkrauss Date 2006-10-17 Time 14:33 Sent To  
Notes
2006-10-17 16:06:27DENIED:
 NO MECHANICAL WORK OR CONTRACTOR INDICATED HOWEVER, 4X
 FEE WAS ISSUED FOR MEP'S STARTING WORK WITHOUT PERMIT,
 THIS INDICATES MECHANICAL WORK HAS ALREADY BEEN DONE.
 PLEASE PROVIDE ENERGY CALCULATIONS PER 2004 FBC CHAPTER
 13 SUB-CHAPTER 4.
  
 PLEASE PROVIDE PLANS WITH MECHANICAL PERMIT
 APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561) 805-6719 OR E-MAIL [email protected].

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-07-29 Cont ID  
Sent By kstevens Date 2008-07-29 Time 06:21 Rev Time 0.00
Received By kstevens Date 2008-07-29 Time 06:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2008-02-05 Cont ID  
Sent By kstevens Date 2008-02-05 Time 15:28 Rev Time 0.00
Received By kstevens Date 2008-02-05 Time 15:28 Sent To  
Notes
2008-02-05 15:35:06DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FBC-2004 EXISTING BLDG CODE
  
 ****FROM PREVIOUS REVIEW:
 COMMENT NUMBERS TO STAY THE SAME.
  
 ******FROM PREVIOUS REVIEWS: 3RD REVIEW***
  
 ********FROM PREVIOUS REVIEWS: 4TH REVIEW***
  
 1. OK
 2. OK
 3. OK
  
 4. SUBMIT CALCULATIONS FOR MINIMUM PLUMBING FACILITIES
 PER TABLES 1004.2 AND 403.1.
 ****NOT ADDRESSED. IT SEEMS THAT THERE IS MORE THAN A-3
 OCCUPANCY. PLEASE SEE SECTION 403.1.1 POTTY PARITY FOR
 THE A-3 OCCUPANCY. INDICATE ALL OCUPANCIES AND INDICATE
 THE SQUARE FOOTAGE OF ALL OCCUPANCIES AS WELL AS THE
 TOTAL OCCUPANCY LOAD OF EACH OCCUPANCY. ******RESPONSE
 NOTED, BUT THE CALCULATIONS WERE NOT SUBMITTED. IS THE
 TOTAL AREA OF THE BUILDING TO BE A-3 OCCUPANCY
 INCLUDING ALL THE OFFICES ON THE SECOND FLOOR? THE
 TOTAL SQUARE FOOTAGE IS 10411SF @ 7NET THE TOTAL
 OCCUPANCY IS 1488. THIS NUMBER DIVIDED BY 2, (MEN &
 WOMEN), COMES TO 744 EACH. 744 DIVIDED BY 150 EQUALS 5
 WATER CLOSETS FOR MEN AND 744 DIVIDED BY 75 EQUALS 10
 WATER CLOSETS FOR WOMEN TO ACHIEVE POTTY PARITY
 REQUIRED BY SECTION 403.1.1. THAT SAID, IF THERE IS
 OTHER OCCUPANCIES BESIDES ASSEMBLY PLEASE INDICATE BY
 SUBMITTING CALCULATIONS FOR MINIMUM PLUMBING
 FACILITIES.
 ********RESPONSE NOTED, BUT THE CALCULATIONS ONLY
 ACCOUNT FOR 3233SF, BUT THE TOTAL AREA IS INDICATED AS
 10,411SF. INDICATE WHERE THE OTHER 7178SF REQUIRED IN
 THE CALCULATION IS INDICATED.
  
 5. OK
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
 14. OK
  
 **********NEW COMMENTS**********
  
 1B. OK
 2B. OK
  
 **********NEW COMMENT**********
  
 1C. IN RELATIONSHIP TO THE CHANGE OF OCCUPANCY, SECTION
 806.1 OF THE FLORIDA BUILDING CODE EXISTING BUILDING
 INDICATES "ACCESSIBILITY IN PORTIONS OF BUILDINGS
 UNDERGOING A CHANGE OF OCCUPANCY CLASSIFICATION SHALL
 COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE,
 BUILDING. IS THE SECOND FLOOR CONSIDERED ASSEMBLY
 OCCUPANCY, AND WHAT WAS THE OCCUPANCY PREVIOUSLY.
 PLEASE CLARIFY.
 ********RESPONSE NOTED, BUT THE TOILET ROOMS ON THE
 SECOND FLOOR SHALL BE ACCESSIBLE PER SECTION 806.1 OF
 THE EXISTING BUILDING CODE
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-11-24 Cont ID  
Sent By kstevens Date 2007-11-24 Time 17:14 Rev Time 0.00
Received By kstevens Date 2007-11-24 Time 17:14 Sent To  
Notes
2007-11-24 17:23:29DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
 COMMENT NUMBERS TO STAY THE SAME.
  
 ******FROM PREVIOUS REVIEWS: 3RD REVIEW***
  
 1. OK
 2. OK
 3. OK
  
 4. SUBMIT CALCULATIONS FOR MINIMUM PLUMBING FACILITIES
 PER TABLES 1004.2 AND 403.1.
 ****NOT ADDRESSED. IT SEEMS THAT THERE IS MORE THAN A-3
 OCCUPANCY. PLEASE SEE SECTION 403.1.1 POTTY PARITY FOR
 THE A-3 OCCUPANCY. INDICATE ALL OCUPANCIES AND INDICATE
 THE SQUARE FOOTAGE OF ALL OCCUPANCIES AS WELL AS THE
 TOTAL OCCUPANCY LOAD OF EACH OCCUPANCY. ******RESPONSE
 NOTED, BUT THE CALCULATIONS WERE NOT SUBMITTED. IS THE
 TOTAL AREA OF THE BUILDING TO BE A-3 OCCUPANCY
 INCLUDING ALL THE OFFICES ON THE SECOND FLOOR? THE
 TOTAL SQUARE FOOTAGE IS 10411SF @ 7NET THE TOTAL
 OCCUPANCY IS 1488. THIS NUMBER DIVIDED BY 2, (MEN &
 WOMEN), COMES TO 744 EACH. 744 DIVIDED BY 150 EQUALS 5
 WATER CLOSETS FOR MEN AND 744 DIVIDED BY 75 EQUALS 10
 WATER CLOSETS FOR WOMEN TO ACHIEVE POTTY PARITY
 REQUIRED BY SECTION 403.1.1. THAT SAID, IF THERE IS
 OTHER OCCUPANCIES BESIDES ASSEMBLY PLEASE INDICATE BY
 SUBMITTING CALCULATIONS FOR MINIMUM PLUMBING
 FACILITIES.
  
 5. OK
  
 6. POTTY PARITY IS REQUIRED PER SECTION 403.1.1. THIS
 IS NOT INDICATED ON PLANS.
 ****NOT ADDRESSED
 ******RESPONSE NOTED, BUT SECTION 403.1.1 IS NOT
 COMPLIED WITH. THE CODE SECTION STATES "IN ASSEMBLY
 OCCUPANCIES, RESTROOMS WHICH ARE OPEN TO THE PUBLIC
 MUST HAVE A RATIO OF 3:2 WATER CLOSETS PROVIDED FOR
 WOMEN AS THE TOTAL OF WATER CLOSETS AND URINALS
 PROVIDED FOR MEN". POTTY PARITY CALCULATIONS SUBMITTED
 HAVE 4 WATER CLOSETS FOR MEN TO 3 WATER CLOSETS FOR
 WOMEN.
  
 7. OK
 8. OK
  
 9. SHT 3/5 NEW MEN'S TOILET ROOM STALL DOES NOT COMPLY
 WITH FIGURE 30E AS REQUIRED IN SECTION 11-4.17.3
 EXCEPTION. ALSO A TURNING AREA IS REQUIRED IN THE
 TOILET ROOMS. PLEASE INDICATE ON PLANS. SECTION
 11-4.22.3.
 ****RESPONSE NOTED, BUT THE TURNING AREA IS NOT SHOWN
 IN THE TOILET ROOMS AS REQUIRED. (NOT REQUIRED IN THE
 ACCESSIBLE STALL).
 ******RESPONSE NOTED, BUT THE STALL STILL DOES NOT
 COMPLY WITH FIGURE 30E. THE LAV IS NOT ALLOWED IN THE
 CLEAR FLOOR SPACE OF THE WATER CLOSET. FIVE FEET OF
 CLEAR FLOOR SPACE FROM THE WALL ADJACENT TO THE WATER
 CLOSET TO THE SIDE OF THE LAV. THE LAV CAN NOT BE IN
 THE CLEAR FLOOR SPACE OF THE WATER CLOSET.
  
 10. OK
  
 11. SUBMIT A DETAIL FOR THE URINAL SHOWING COMPLIANCE
 WITH 11-4.18 AND ALL SUBSECTIONS.
 ****RESPONSE NOTED, BUT THE FOLLOWING SECTIONS WERE NOT
 ADDRESSED:
 A. OK
 B. 11-4.18.4 FLUSH CONTROLS
 ******RESPONSE NOTED, BUT THE CONTROL HEIGHT IS
 REQUIRED.
  
 12. OK
 13. OK
 14. OK
  
 **********NEW COMMENTS**********
  
 1B. OK
  
 2B. SHT 3/5 MEN'S TOILET ROOM ACCESSIBLE STALL. THE
 ACCESSIBLE W/C SHALL BE LOCATED IN THE CORNER, DIAGONAL
 TO THE DOOR. SECTION 11-4.17.3 EXCEPTION (2).
 ******RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
  
 **********NEW COMMENT**********
  
 1C. IN RELATIONSHIP TO THE CHANGE OF OCCUPANCY, SECTION
 806.1 OF THE FLORIDA BUILDING CODE EXISTING BUILDING
 INDICATES "ACCESSIBILITY IN PORTIONS OF BUILDINGS
 UNDERGOING A CHANGE OF OCCUPANCY CLASSIFICATION SHALL
 COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE,
 BUILDING. IS THE SECOND FLOOR CONSIDERED ASSEMBLY
 OCCUPANCY, AND WHAT WAS THE OCCUPANCY PREVIOUSLY.
 PLEASE CLARIFY.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-03-19 Cont ID  
Sent By kstevens Date 2007-03-19 Time 17:14 Rev Time 0.00
Received By kstevens Date 2007-03-19 Time 17:14 Sent To  
Notes
2007-03-19 17:42:32DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
 COMMENT NUMBERS TO STAY THE SAME.
  
 1. OK
 2. OK
 3. OK
  
 4. SUBMIT CALCULATIONS FOR MINIMUM PLUMBING FACILITIES
 PER TABLES 1004.2 AND 403.1.
 ****NOT ADDRESSED. IT SEEMS THAT THERE IS MORE THAN A-3
 OCCUPANCY. PLEASE SEE SECTION 403.1.1 POTTY PARITY FOR
 THE A-3 OCCUPANCY. INDICATE ALL OCUPANCIES AND INDICATE
 THE SQUARE FOOTAGE OF ALL OCCUPANCIES AS WELL AS THE
 TOTAL OCCUPANCY LOAD OF EACH OCCUPANCY.
  
 5. OK
  
 6. POTTY PARITY IS REQUIRED PER SECTION 403.1.1. THIS
 IS NOT INDICATED ON PLANS.
 ****NOT ADDRESSED
  
 7. OK
 8. OK
  
 9. SHT 3/5 NEW MEN'S TOILET ROOM STALL DOES NOT COMPLY
 WITH FIGURE 30E AS REQUIRED IN SECTION 11-4.17.3
 EXCEPTION. ALSO A TURNING AREA IS REQUIRED IN THE
 TOILET ROOMS. PLEASE INDICATE ON PLANS. SECTION
 11-4.22.3.
 ****RESPONSE NOTED, BUT THE TURNING AREA IS NOT SHOWN
 IN THE TOILET ROOMS AS REQUIRED. (NOT REQUIRED IN THE
 ACCESSIBLE STALL).
  
 10. SHT 3/5 ELEVATIONS FOR WATER CLOSETS AND LAVS. SHOW
 THE FOLLOWING INFORMATION:
 FOR W/C'S
 A. OK
 B. 11-4.16.3 HEIGHT (SHOWN AS 20") (NOT ADDRESSED)
 (17" TO 19")
 C. OK
 D. 11-4.16.5 FLUSH CONTROLS (NOT ADDRESSED)
 FOR LAV'S
 A. 11-4.19.3 CLEAR FLOOR SPACE (NOT ADDRESSED)B.
 11-4.19.5 FAUCETS (NOT ADDRESSED)
  
 11. SUBMIT A DETAIL FOR THE URINAL SHOWING COMPLIANCE
 WITH 11-4.18 AND ALL SUBSECTIONS.
 ****RESPONSE NOTED, BUT THE FOLLOWING SECTIONS WERE NOT
 ADDRESSED:
 A. 11-4.18.3 CLEAR FLOOR SPACE
 B. 11-4.18.4 FLUSH CONTROLS
  
 12. SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING
 FOUNTAIN PER 11-4.15 AND ALL SUBSECTIONS, AS WELL AS
 11-4.1.3(10)(B) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING IF THE DRINKING FOUNTAIN
 IS NOT A HIGH/LOW UNIT.
 ****RESPONSE NOTED, BUT A DETAIL FOR THE ACCESSIBLE
 DRINKING FOUNTAIN HAS NOT BEEN SUBMITTED.
  
 13. SHT 3/5 PLUMBING SANITARY RISER DIAGRAM. URINALS
 ARE NOT VENTED. SECTION 901.2.1.
 ****RESPONSE NOTED, BUT THE RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE
 REQUIREMENTS.--THE FLOOR PLAN SHOWS TWO URINALS,
 BUT THE RISER DIAGRAM SHOW THREE URINALS.--THE
 DRINKING FOUNTAIN IS NOT SHOWN ON THE RISER DIAGRAM. --
 THE LAV IN THEACCESSIBLE STALL IS NOT VENTED.-- THE
 URINALS STILL ARE NOT VENTED.SECTION 106.1.1. (SEE
 RED LINE MARKINGS ON THE COPY OF THE RISER DIAGRAM.
  
 14. SUBMIT A WATER RISER DIAGRAM ISOMETRIC. SHOW ALL
 PIPE SIZES, VALVES, AND WATER HAMMER ARRESTORS AS
 REQUIRED BY SECTION 604.9. IF WATER HAMMER ARRESTORS
 ARE INSTALLED, THEY SHALL BE LOCATED NEAR THE FIXTURE
 IN AN "EFFECTIVE RANGE" NOT IN THE CEILING. PDI-WH 201
 AND MANUF. INSTALLATION INSTRUCTIONS.
 ****NO RESPONSE. NOT ADDRESSED.
  
 **********NEW COMMENTS**********
  
 1B. ALL SHEETS. THE ADDRESS FOR THE ENGINEER DOES NOT
 REFLECT THE ADDRESS ON THE FLORIDA DBPR WEBSITE. PLEASE
 UPDATE THE WEBSITE OR CHANGE THE TITLE BLOCK. FAC
 61G15-23.002(2)&FS 471.025. (SEE ATTACHED DBPR
 WEBSITE SHEET).
  
 2B. SHT 3/5 MEN'S TOILET ROOM ACCESSIBLE STALL. THE
 ACCESSIBLE W/C SHALL BE LOCATED IN THE CORNER, DIAGONAL
 TO THE DOOR. SECTION 11-4.17.3 EXCEPTION (2).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-10-11 Cont ID  
Sent By kstevens Date 2006-10-11 Time 07:32 Rev Time 0.00
Received By kstevens Date 2006-10-11 Time 07:32 Sent To  
Notes
2006-10-11 08:02:08DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. AN ARCHITECT OR ENGINEER IS REQUIRED TO DESIGN THE
 PLANS PER FS 481.229
  
 2. HOLD DATED 2-9-05 INDICATES THAT COMPLETE PLANS ARE
 REQUIRED. THIS IS A CHANGE OF OCCUPANCY, AND WORK WAS
 DONE WITH PERMITS. PLEASE SUBMIT FLOOR PLANS FOR BOTH
 FLOORS SHOWING FLOOR PLANS PRIOR TO CHANGES MADE WITH
 OUT PERMITS. SECTION 106.1.1.
  
 3. PER FBC-2004 EXISTING BUILDING CODE, INDICATE LEVEL
 OF ALTERATION. CHAPTER 3.
  
 4. SUBMIT CALCULATIONS FOR MINIMUM PLUMBING FACILITIES
 PER TABLES 1004.2 AND 403.1.
  
 5. SEPARATE FACILITIES ARE REQUIRED FOR MEN AND WOMEN.
 NO WOMEN'S TOILET ROOM INDICATED. SECTION 403.2.
  
 6. POTTY PARITY IS REQUIRED PER SECTION 403.1.1. THIS
 IS NOT INDICATED ON PLANS.
  
 7. PER TABLE 403.1 AT LEAST ONE DRINKING FOUNTAIN IS
 REQUIRED.
  
 8. SHT 3/5 HAS A NOTE THAT STATES, "PLUMBING PERMIT ON
 RECORD". SEE ATTACHED SHEET. NO PLUMBING PERMIT IS
 INDICATED ON RECORD.
  
 9. SHT 3/5 MEW MEN'S TOILET ROOM STALL DOES NOT COMPLY
 WITH FIGURE 30E AS REQUIRED IN SECTION 11-4.17.3
 EXCEPTION. ALSO A TURNING AREA IS REQUIRED IN THE
 TOILET ROOMS. PLEASE INDICATE ON PLANS. SECTION
 11-4.22.3.
  
 10. SHT 3/5 ELEVATIONS FOR WATER CLOSETS AND LAVS. SHOW
 THE FOLLOWING INFORMATION:
 FOR W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT (SHOWN AS 20")
 C. 11-4.16.4 GRAB BARS (SHOW LENGTHS)
 D. 11-4.16.5 FLUSH CONTROLS
 FOR LAV'S
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19.5 FAUCETS
  
 11. SUBMIT A DETAIL FOR THE URINAL SHOWING COMPLIANCE
 WITH 11-4.18 AND ALL SUBSECTIONS.
  
 12. SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING
 FOUNTAIN PER 11-4.15 AND ALL SUBSECTIONS, AS WELL AS
 11-4.1.3(10)(B) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING IF THE DRINKING FOUNTAIN
 IS NOT A HIGH/LOW UNIT.
  
 13. SHT 3/5 PLUMBING SANITARY RISER DIAGRAM. URINALS
 ARE NOT VENTED. SECTION 901.2.1.
  
 14. SUBMIT A WATER RISER DIAGRAM ISOMETRIC. SHOW ALL
 PIPE SIZES, VALVES, AND WATER HAMMER ARRESTORS AS
 REQUIRED BY SECTION 604.9. IF WATER HAMMER ARRESTORS
 ARE INSTALLED, THEY SHALL BE LOCATED NEAR THE FIXTURE
 IN AN "EFFECTIVE RANGE" NOT IN THE CEILING. PDI-WH 201
 AND MANUF. INSTALLATION INSTRUCTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 6 Status P Date 2008-10-21 Cont ID  
Sent By eschneid Date 2008-10-21 Time 09:30 Rev Time 0.00
Received By eschneid Date 2008-10-21 Time 09:30 Sent To  
Notes
2008-10-21 09:34:44PASSED W/PROVISO
  
 PROVISO: THE A/C LOUVERED SCREENS ARE TO BE PAINTED TO
 MATCH THE COLOR OF THE BUILDING.
  
 NOTES:
  
 1) AN IRRIGATION PERMIT IS REQUIRED. REMEMBER THAT THE
 GRASS STRIP ON THE NORTH SIDE OF THE PROPERTY (IN THE
 RIGHT-OF-WAY) IS REQUIRED TO BE IRRIGATED.
  
 2) THE SIDEWALK EASEMENT WILL NEED TO BE IN PLACE PRIOR
 TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
  
 CONTACT ERIC SCHNEIDER @ (5610 822-1435.

Review Stop Z ZONING
Rev No 5 Status F Date 2008-07-17 Cont ID  
Sent By eschneid Date 2008-07-17 Time 16:13 Rev Time 0.00
Received By eschneid Date 2008-07-17 Time 16:12 Sent To  
Notes
2008-07-17 16:25:50FAILED
  
 1) REPEAT COMMENT - THE 4'10" HIGH AC EQUIPMENT ON THE
 ROOF SHALL BE SCREENED. PLANS/ELEVATIONS/PICTURES TO
 DEMONSTRATE THIS HAVE NOT BEEN PROVIDED. ELEVATIONS DO
 NOT SHOW AC EQUIPMENT OR PARAPET HEIGHTS.
  
 2) REPEAT COMMENT - THE TERMINAL LANDSCAPE ISLAND AT
 THE SOUTHWEST CORNER OF THE PROPERTY DOES NOT HAVE 5
 FEET OF PLANTING AREA.THERE IS ROOM TO SHIFT THE ROW
 TO THE NORTH.
  
 3) ONE ADDITIONAL PERIMETER TREE IS REQUIRED ALONG THE
 PROPERTY LINE AT THE SOUTH END OF THE REAR PARKING
 (WHERE THE DUMPSTER WAS FORMERLY SHOWN).
  
 4) ALL LANDSCAPE IS TO BE PROTECTED FROM VEHICULAR
 ENCROACHMENT.THE PLANS DO NOT INDICATE THE CURB TYPE
 ALONG THE WEST PROPERTY BOUNDARIES.A TYPE "D" CURB IS
 REQUIRED.PLEASE REMEMBER THAT THE LANDSCAPE AREAS
 SHALL REMAIN AT LEAST 5 FEET WIDE OF PLANTING AREA.
  
 5) AN IRRIGATION PERMIT IS REQUIRED.NOTE THAT THE
 GRASS STRIP ON THE NORTH SIDE OF THE PROPERTY (IN THE
 RIGHT-OF-WAY) IS REQUIRED TO BE IRRIGATED.
  
 6) IT IS RECOMMENDED THAT THE SABAL PALMS BE
 UNDERPLANTED WITH SHRUBS OR GROUND COVER, NOT SOD AS
 SHOWN.
  
 7) PLEASE NOTE THAT THE SIDEWALK EASEMENT WILL NEED TO
 BE IN PLACE PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF
 OCCUPANCY.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 4 Status F Date 2008-01-23 Cont ID  
Sent By eschneid Date 2008-01-23 Time 09:00 Rev Time 0.00
Received By eschneid Date 2008-01-23 Time 09:00 Sent To  
Notes
2008-01-23 09:48:44FAILED
  
 1) THE SITE AND LANDSCAPE PLANS INCORRECTLY SHOW THE
 PROPERTY LINE INCORRECTLY IN RELATIONSHIP TO THE
 ADJACENT SIDEWALKS AND CURBLINES AS THEY ARE SHOWN ON
 THE SURVEY.THIS HAS CAUSED AN ISSUE WITH THE REQUIRED
 8 FOOT SIDEWALK THAT IS REQUIRED ALONG BROADWAY AVENUE.
 THE SOUTH PARKING LOT WILL NEED TO BE ADJUSTED.
  
 2) REPEAT COMMENT - BASED ON THE INFORMATION PROVIDED
 ON THE SURVEY, 3 FEET OF THE REQUIRED SIDEWALK WILL
 NEED TO BE ON THE SITE.THIS 3 FOOT STRIP WILL REQUIRE
 THE OWNER TO SIGN A PUBLIC ACCESS EASEMENT.PLEASE
 CONTACT VINCE NOEL, CITY SURVEYOR, AT 494-1040.
  
 3) REPEAT COMMENT - THE DUMPSTER ENCLOSURE SHOWN ON THE
 PLANS DOES NOT MEET MINIMUM CITY STANDARDS.IT IS MY
 UNDERSTANDING FROM PREVIOUS MEETINGS THAT THIS IS AN
 EXISTING DUMPSTER AND LOCATION YOU ARE TRYING TO
 "VEST."THE ENGINEERING SERVICES DEPARTMENT,
 SPECIFICALLY, EMERY FABIAN @ 494-1040, SHALL APPROVE
 THE SIZE AND LOCATION PRIOR TO THE APPROVAL OF THIS
 BUILDING PERMIT.IF THE ENGINEERING SERVICES
 DEPARTMENT DOES NOT APPROVE THE DUMPSTER SIZE OR
 LOCATION, THEN THE SITE AND LANDSCAPE PLANS WILL NEED
 TO BE REDESIGNED.
  
 4) THE AC EQUIPMENT ON THE ROOF SHALL BE SCREENED.
 PLANS/ELEVATIONS/PICTURES TO DEMONSTRATE THIS HAVE NOT
 BEEN PROVIDED.
  
 5) REPEAT COMMENT - THE LANDSCAPE TERMINAL ISLANDS ARE
 REQUIRED TO HAVE 5 FEET OF PLANTING AREA.THE PLANS
 SHOW CURBING INCLUDED IN THE 5 FEET.
  
 6) A SHADE OR FLOWERING TREE IS REQUIRED IN THE
 TERMINAL ISLAND ADJACENT TO THE HANDICAP PARKING
 SPACE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 3 Status F Date 2007-10-22 Cont ID  
Sent By eschneid Date 2007-10-22 Time 20:06 Rev Time 0.00
Received By eschneid Date 2007-10-22 Time 20:06 Sent To  
Notes
2007-10-22 20:13:49FAILED
  
 1) A SURVEY LESS THAN ONE YEAR OLD IS REQUIRED.THE
 SURVEY SHALL SHOW ALL EASEMENTS. (REPEAT COMMENT)
  
 2) THE LANDSCAPE BUFFERS ARE REQUIRED TO BE PROVIDED ON
 THE PARCEL.IT APPEARS THAT SOME OF THE BUFFERS ALONG
 THE WEST AND SOUTH PROPERTY LINES MAY NOT BE ON THE
 SITE.THIS WILL BE CONFIRMED ONCE A SURVEY WILL BE
 PROVIDED.
  
 3) PURSUANT TO SECTION 94-443(C)(3)(A), EACH ROW OF
 PARKING SPACES SHALL BE TERMINATED BY LANDSCAPE ISLANDS
 OF NOT LESS THAN FIVE (5) FEET IN WIDTH AND NOT LESS
 THAN THE LENGTH OF THE ADJACENT PARKING STALL.THE
 LANDSCAPE ISLAND SHALL HAVE A MINIMUM RADIUS OF 2 FEET
 AT ITS END SO AS TO ALLOW CAR MANEUVERING.THE
 LANDSCAPE ISLAND SHALL CONTAIN AT LEAST ONE SHADE OR
 FLOWERING TREE.NOTE THAT THE ISLANDS NEED TO BE ON
 THE PROPERTY LINE.ADDITIONALLY, THE MIDDLE ROW IN THE
 SOUTH PARKING LOT DOES NOT HAVE LANDSCAPE.(REPEAT
 COMMENT)
  
 4) A PUBLIC ACCESS EASEMENT WILL BE REQUIRED FOR THE
 PORTION OF THE SIDEWALK ON THE SUBJECT PARCEL.
  
 5) THE DUMPSTER, DUMPSTER ENCLOSURE AND LOCATION OF THE
 DUMPSTER SHALL BE APPROVED BY THE ENGINEERING SERVICES
 DEPARTMENT. (REPEAT COMMENT)
 A. PLEASE PROVIDE A COPY OF A SITE PLAN SIGNED APPROVED
 FROM THE ENGINEERING SERVICES DEPARTMENT.
  
 6) THE IRRIGATION WILL REQUIRE A PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-03-15 Cont ID  
Sent By eschneid Date 2007-03-13 Time 09:59 Rev Time 0.00
Received By eschneid Date 2007-03-13 Time 09:48 Sent To  
Notes
2007-03-13 15:09:36FAILED
  
 1) A SURVEY LESS THAN ONE YEAR OLD IS REQUIRED.THE
 SURVEY SHALL SHOW ALL EASEMENTS.
  
 2) A LANDSCAPE PLAN, PREPARED BY A LANDSCAPE ARCHITECT,
 IS REQUIRED.
  
 3) AN ELEVATION OF THE BUILDING ALONG BROADWAY AVENUE
 SHALL BE PROVIDED.
 A. PLEASE STATE WHETHER ANY EXTERIOR IMPROVEMENTS WILL
 BE DONE TO THE BUILDING FA?ADE(S).
  
 4) PURSUANT TO SECTION 94-219(D)(9)(B), ALL EXISTING
 SURFACE PARKING LOTS SHALL BE LANDSCAPED WITH A 36-INCH
 HIGH PERIMETER HEDGE AND SHADE TRESS AT EVERY THIRD
 PARKING SPACE.SHRUBS SHALL BE PLANTED AT TWO-FOOT
 INTERVALS.
 A. A LANDSCAPE BUFFER SHALL BE PROVIDED ALONG THE WEST
 AND SOUTH SIDES OF THE PARKING LOT TO THE SOUTH OF THE
 SITE.
  
 5) PURSUANT TO SECTION 94-443(C)(3)(A), EACH ROW OF
 PARKING SPACES SHALL BE TERMINATED BY LANDSCAPE ISLANDS
 OF NOT LESS THAN FIVE (5) FEET IN WIDTH AND NOT LESS
 THAN THE LENGTH OF THE ADJACENT PARKING STALL.THE
 LANDSCAPE ISLAND SHALL HAVE A MINIMUM RADIUS OF 2? FEET
 AT ITS END SO AS TO ALLOW CAR MANEUVERING.THE
 LANDSCAPE ISLAND SHALL CONTAIN AT LEAST ONE SHADE OR
 FLOWERING TREE.
  
 6) PURSUANT TO SECTION 94-443(C)(5)(A), LANDSCAPE AREAS
 SHALL BE SEPARATED FROM VEHICULAR USE AREAS BY
 NONMOUNTABLE, CONCRETE CURBING OF THE TYPE
 CHARACTERIZED AS ?TYPE D?.A ?TYPE D? CURB SHALL BE
 PROVIDED ALONG ALL VEHICULAR USE AREAS.
  
 7) PURSUANT TO SECTION 94-221(B)(6), SIDEWALKS ALONG
 BROADWAY AVENUE SHALL BE A MINIMUM OF EIGHT FEET IN
 CLEAR WIDTH.
  
 8) PROPOSED CBS WALL SHALL BE SIX (6) FEET HIGH FOR ITS
 ENTIRE LENGTH.
  
 9) IN ORDER TO INCREASE A PEDESTRIAN ORIENTED MIXED USE
 DISTRICT ALONG BROADWAY AVENUE, THE BROADWAY MIXED USE
 DISTRICT REGULATIONS REQUIRES ALL BUILDINGS TO HAVE
 PRINCIPAL PEDESTRIAN ENTRANCES FACING THE BROADWAY
 FRONTAGE LINE.IF THERE IS AN OPPORTUNITY, PLEASE
 PROVIDE A DOORWAY TO BROADWAY AVENUE.
  
 10) DUMPSTER, DUMPSTER ENCLOSURE AND LOCATION OF THE
 DUMPSTER SHALL BE APPROVED BY THE ENGINEERING SERVICES
 DEPARTMENT.
 A. PLEASE PROVIDE A COPY OF A SITE PLAN SIGNED APPROVED
 FROM THE ENGINEERING SERVICES DEPARTMENT.
 B. PURSUANT TO SECTION 94-221(D)(10), DUMPSTERS SHALL
 BE ENCLOSED IN A STRUCTURE CONSISTENT WITH THE
 ARCHITECTURE OF THE BUILDING.THE MATERIAL OF THE
 PROPOSED DUMPSTER ENCLOSURE (A WOOD FENCE) IS NOT
 CONSISTENT WITH THE ARCHITECTURE OF THE BUILDING.
 C. PURSUANT TO SECTION 94-444(B), DUMPSTER ENCLOSURE
 SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES PLANTED AT
 TWO-FOOT INTERVALS.
  
 11) THE PLANNING AND ZONING DEPARTMENT RECOGNIZES THAT
 THE EXISTING PARKING LOT IS NOT STRIPED AND THUS THE
 TOTAL NUMBER OF EXISTING PARKING SPACES IS NOT DEFINED.
 THEREFORE; THERE SHALL BE AS MANY PARKING SPACES
 MEETING CODE REQUIREMENT AS CAN BE PROVIDED IN THE
 RECONFIGURATION OF THE EXISTING PARKING LOT.
  
 12) PARKING SPACES ON THE SOUTH SIDE OF THE SITE ARE
 ALONG THE CURB CUT ON 52ND ST AND THUS PRESENT AN
 UNSAFE SITUATION.THE CURB CUT SHALL BE RECONFIGURED
 WHERE CONFLICTS EXIST OR THE PARKING SPACES SHALL BE
 ELIMINATED.
  
 13) PURSUANT TO SECTION 94-485(G), CURBS, WHEELSTOPS,
 OR BOLLARDS SHALL BE INSTALLED TO PROTECT LANDSCAPED
 AREAS, PEDESTRIAN AREA, BUILDINGS, AND PROPERTY LINES.
 PROVIDE A CURB AROUND THE BUILDING.
  
 14) DELINEATE THE WALKWAY OR ACCESS AISLE FROM THE
 HANDICAP PARKING SPACES TO THE MAIN ENTRANCE OF THE
 BUILDING.
  
 15) HANDICAP PARKING STALL DETAIL MEETING CODE
 REQUIREMENTS SHALL BE PROVIDED.
 A. HANDICAP SYMBOL SHALL BE TWO (2) FEET FROM THE OPEN
 END OF THE PARKING SPACE.
 B. HANDICAP SYMBOL SHALL FACE RIGHT.
  
 16. WHEEL STOPS SHALL BE SIX (6) INCHES IN HEIGHT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-10-03 Cont ID  
Sent By eschneid Date 2006-10-03 Time 14:53 Rev Time 0.00
Received By eschneid Date 2006-10-03 Time 14:53 Sent To  
Notes
2006-10-03 00:00:00PARKING AND LANDSCAPE REVISIONS REQUIRED
 PER DISCUSSION WITH THE ZONING STAFF.
  
 CONTACT ERIC SCHNEIDER @ 561) 822-1435.
2006-09-17 00:00:00CHANGE IN OCCUPANCY.